This document is an instruction manual for the Digital Fiber Sensor Amplifier FX-301(P). It has been modified since June 2004 to reflect changes made to the FX-301(P) sensor. The manual provides instructions on connecting the quick-connection cable to the amplifier, lists safety cautions, and specifies the amplifier's technical specifications and functions including cascading multiple amplifiers.

Uploaded by

Gaurav K
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
400 views4 pages

Panasonic FX-301(P) Manual

This document is an instruction manual for the Digital Fiber Sensor Amplifier FX-301(P). It has been modified since June 2004 to reflect changes made to the FX-301(P) sensor. The manual provides instructions on connecting the quick-connection cable to the amplifier, lists safety cautions, and specifies the amplifier's technical specifications and functions including cascading multiple amplifiers.

Uploaded by

Gaurav K
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Digital fiber sensor FX-301(P) has been modified since production in June. 2004.

Hence, this
instruction manual has been changed to reflect the modifications.
3 CONNECTION OF CONNECTOR TYPE FX-301(P)
Make sure that the power supply is off while connecting or disconnecting the quick-
connection cable.
INSTRUCTION MANUAL
Connection method Groove

Digital Fiber Sensor Amplifier FX-301(P) Ԙ Holding the connector of the quick-connection cable, align
its projection with the groove at the top portion of the
Projection
MJE-FX301 No.0034-48V amplifier connector.
Thank you very much for purchasing Panasonic products. Please read this Instruction ԙ Insert the connector till a click is felt.
Manual carefully and thoroughly for the correct and optimum use of this product.
Disconnection method Quick-connection cable
Kindly keep this manual in a convenient place for quick reference.
Ԙ Pressing the projection at the top of the quick-connection Projection
WARNING cable, pull out the connector.
٨ Never use this product as a sensing device for personnel protection. Note: Take care that if the connector is pulled out without pressing the
٨ In case of using sensing devices for personnel protection, use products which projection, the projection may break. Do not use a quick-
meet laws and standards, such as OSHA, ANSI or IEC etc., for personnel protec- connection cable whose projection has broken. Further, do not pull
by holding the cable, as this can cause a cable-break.
tion applicable in each region or country.
For further details on the fiber sensor amplifier, please refer to 'Panasonic Industrial 4 CAUTIONS
Devices SUNX website (http://panasonic.net/id/pidsx/global)' or contact our office. ٨ This product has been developed / produced for industrial use only.
٨ When the emission halt of the emitting power switching function is set from 'OFF' to 'ON', the
1 SPECIFICATIONS output may be unstable. Do not use the output control for 0.5 sec. after starting emission.
Type Connector type Cable type
٨ Make sure that the power supply is off while wiring.
Model NPN output
٨ Verify that the supply voltage variation is within the rating.
FX-301 FX-301-C1
No. PNP output ٨ Take care that if a voltage exceeding the rated range is applied, or if an AC power
Item FX-301P FX-301P-C1
supply is directly connected, the sensor may get burnt or damaged.
Supply voltage 12 to 24V DCr10% Ripple P-P 10% or less
٨ In case noise generating equipment (switching regulator, inverter motor, etc.) is used in the vicini-
Normal operation: 960mW or less
(current consumption 40mA or less at 24V supply voltage)
ty of this product, connect the frame ground (F.G.) terminal of the equipment to an actual ground.
Power consumption
ECO mode: 600mW or less ٨ If power is supplied from a commercial switching regulator, ensure that the frame
(current consumption 25mA or less at 24V supply voltage) ground (F.G.) terminal of the power supply is connected to an actual ground.
<NPN output type> <PNP output type> ٨ Do not use during the initial transient time (0.5 sec.) after the power supply is switched on.
NPN open-collector transistor PNP open-collector transistor ٨ Take care that short-circuit of the load or wrong wiring may burn or damage the sensor.
࡮Maximum sink current: 100mA (Note 1)࡮Maximum source current: 100mA (Note 1) ٨ Do not run the wires together with high-voltage lines or power lines or put them in
Output ࡮Applied voltage: 30V DC or less ࡮Applied voltage: 30V DC or less the same raceway. This can cause malfunction due to induction.
(between output and 0V) (between output and +V) ٨ For the cable to connect to the connector type sensor FX-301(P), be sure to use
࡮Residual voltage: 1.5V or less ࡮Residual voltage: 1.5V or less the optional quick-connection cable.
[at 100mA (Note 1) sink current] [at 100mA (Note 1) source current]
٨ Extension up to total 100m (if 5 to 8 units are connected in cascade: 50m, if 9 to 16
Output operation Light-ON or Dark-ON, selectable with jog switch units are connected in cascade: 20m) is possible with 0.3mm2, or more, cable.
Short-circuit protection Incorporated However, in order to reduce noise, make the wiring as short as possible.
Response time H-SP: 65Ǵs or less, FAST: 150Ǵs or less, S-D: 250Ǵs or less ٨ Take care that cable extension increases the residual voltage.
STD: 250Ǵs or less, LONG: 2ms or less selectable with jog switch ٨ This sensor is suitable for indoor use only.
Display 4 digit red LED display ٨ Avoid dust, dirt, and steam.
Sensitivity setting 2-level teaching / Limit teaching / Full-auto teaching / Manual adjustment ٨ Take care that the product does not come in contact with water, oil, grease, organ-
Fine sensitivity ic solvents, such as, thinner, etc., strong acid or alkaline.
Incorporated
adjustment function ٨ This sensor cannot be used in an environment containing inflammable or explosive gases.
Incorporated with variable ON-delay / OFF-delay / ONE-SHOT timer, ٨ Never disassemble or modify the sensor.
Timer function
switchable either effective or ineffective (Timer: approx. 0.5 to 9999ms)
Interference prevention
function
Incorporated [up to four fibers can be mounted adjacently (However,
H-SP mode is two fibers)]
5 CASCADING
-10 to +55͠ (If 4 to 7 units are connected in cascade: -10 to +50͠, ٨ Make sure that the power supply is off while adding or removing the amplifiers.
Ambient temperature if 8 to 16 units are connected in cascade: -10 to +45͠) ٨ Make sure to check the allowable ambient temperature, as it depends on the
(No dew condensation or icing allowed), Storage: -20 to +70͠ number of amplifiers connected in cascade.
Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH ٨ In case two, or more, amplifiers are connected in cascade, make sure to mount
Emitting element Red LED (modulated) them on a DIN rail.
Enclosure: Heat-resistant ABS, Transparent cover: Polycarbonate ٨ When the amplifiers move on the DIN rail depending on the attaching condition or
Material
Press switches: Acrylic, Jog switch: Heat-resistant ABS the amplifiers are mounted close to each other in cascade, fit them between the
Cable 㧙 0.3mm2 3-core cabtyre cable, 1m long optional end plates (MS-DIN-E) mounted at the two ends.
Weight 20g approx. 60g approx. ٨ Up to maximum 15 amplifiers can be added (total 16 amplifiers connected in cascade.)
Accessory FX-MB1 (Amplifier protection seal): 1 set ٨ When connecting more than two amplifiers in cascade, use the sub cable (CN-71-C‫)غ‬
as the quick-connection cable for the second amplifier onwards.
Notes: 1) 50mA, the connector type FX-301(P) five, or more, amplifiers are connected in cascade.
2) When the power supply is switched on, the light emission timing is automatically set for ٨ When connecting amplifiers not close to each other in parallel, be sure to mount the option-
interference prevention. al end plate (MS-DIN-E) at both sides of each amplifier or affix the communication window
3) The cable for amplifier connection is not supplied as an accessory. Make sure to use the seal of the accessory amplifier protection seal (FX-MB1) to the communication windows.
optional quick-connection cables given below. ٨ In case of using the connector type FX-301(P) with the cable type FX-301(P)-C1
Main cable (3-core): CN-73-C1 (cable length 1m), CN-73-C2 (cable length 2m) in cascade, mount the identical models together.
CN-73-C5 (cable length 5m) ٨ In case the modified version units are mounted with the conventional version units in
Sub cable (1-core): CN-71-C1 (cable length 1m), CN-71-C2 (cable length 2m)
cascade, place the modified version units to the right side (when viewed from the
CN-71-C5 (cable length 5m)
connector side) of the conventional version units. For a difference between the modi-
2 MOUNTING fied version unit and the conventional version unit, refer to ' 16 A DIFFERENCE BE-
TWEEN THE MODIFIED VERSION UNIT AND THE CONVENTIONAL VERSION UNIT'.
How to mount the amplifier ٨ The settings other than the interference prevention function cannot be transmitted be-
tween this product and other digital fiber amplifiers. Therefore, in case both models
Ԙ Fit the rear part of the mounting section of the amplifier of amplifiers are mounted in cascade, be sure to mount identical models together.
on a 35mm width DIN rail. ԙ
However, the interference prevention function is not incorporated into the FX-301㩿P㪀-HS
ԙ Press down the rear part of the mounting section of the and FX-303(P). Take care when the sensors are mounted in cascade.
unit on the 35mm width DIN rail and fit the front part of Ԙ ٨ Since the communication function of this product and that of the FX-301(P)-F is
the mounting section to the DIN rail. 35mm width DIN rail different, if these models are mounted in cascade, affix the accessory amplifier
How to remove the amplifier Ԙ protection seal (FX-MB1) to the communication windows of the amplifiers.
ԙ
Ԙ Push the amplifier forward. For mounting and removing the amplifier, refer to ' 2 MOUNTING'.
ԙ Lift up the front part of the amplifier to remove it.
Cascading method Sub cable (CN-71-C‫)غ‬
Note: Take care that if the front part is lifted without pushing the (optional)
amplifier forward, the hook on the rear portion of the mounting section is likely to break. Ԙ Mount the amplifiers, one by one,
How to connect the fiber cables on the 35mm width DIN rail.
ԙ Slide the amplifiers next to each
Be sure to fit the attachment to the fibers first before inserting the fibers to the other, and connect the quick-con- Main cable (CN-73-C‫)غ‬
amplifier. For details, refer to the instruction manual enclosed with the fibers. nection cables. (optional)
Ԛ Mount the optional end plates Slide
Ԙ Snap the fiber lock lever down. Ԛ
ԙ Insert the fiber cables slowly into the inlets until they stop. (Note 1) Ԙ (MS-DIN-E) at both the ends to hold
Ԛ Return the fiber lock lever to the original position, till it stops. the amplifiers between their flat sides. End plates (MS-DIN-E)
Fiber
ԛ Tighten the screws to fix the end (optional)
Notes: 1) In case the fiber cables are not inserted to a position where lock lever
plates.
they stop, the sensing range reduces. In case of a flexible fiber,
take care that it may bend inside the amplifier, during insertion.
2) With the coaxial reflective type fiber, such as, FD-G4 or FD-FM2, ԙ
insert the single-core fiber cable into the beam-emitting inlet and Dismantling
the multi-core fiber cable into the beam-receiving inlet. If they are Fiber End plates (MS-DIN-E)
inserted in reverse, the sensing accuracy will deteriorate.
Ԙ Loosen the screws of the end plates. (optional)
ԙ Remove the end plates.
Ԛ Slide the amplifiers and remove
them one by one. Slide
٨ PRO mode
6 I/O CIRCUIT DIAGRAMS
PRO1 Refer to ' 15 PRO
٨ NPN output type MODE PRO1
࡮Response time change function '' ࡮Stability function ''
Terminal No. of connector type Cable type / Color code of quick- mode setting'.
࡮Timer setting function '' ࡮Shift function ''
connection cable ࡮Hysteresis function '' ࡮Emitting power selection function ''
D1 (Brown) +V (Note 1) Terminal arrange-
1 ment diagram of Turn
Sensor circuit

Load the connector type


(Black) Output + 12 to 24V DC FX-301 PRO2 Refer to ' 15 PRO
3
- r10% MODE PRO2
100mA max. (Note 2) ࡮Digital display setting function ''
Tr1 ZD1
1 +V mode setting'.
࡮Digital display inversion function ''
(Blue) 0V (Note 1)
2 ࡮ECO mode setting function ''
3 Output

Internal circuit Users' circuit 2 0V Turn


٨ PNP output type PRO3 Refer to ' 15 PRO
Terminal No. of connector type MODE PRO3
Cable type / Color code of quick- ࡮Data bank load setting function ''
mode setting'.
connection cable ࡮Data bank save setting function ''
(Brown) +V (Note 1) Terminal arrange-
1 ment diagram of Turn
Sensor circuit

ZD2 100mA max. (Note 2) the connector type PRO4 Refer to ' 15 PRO
Tr2 + 12 to 24V DC FX-301P
3
r10% MODE PRO4
(Black) Output - ࡮Setting condition copy ࡮Remote data bank save
1 +V mode setting'.
Load function '' setting function ''
2 ࡮Remote data bank load ࡮Communication lock function ''
(Blue) 0V (Note 1) 3 Output setting function '' ࡮Back-up function ''
D2

Internal circuit Users' circuit 2 0V


Turn
Notes: 1) The quick-connection sub cable does not have +V (brown) and 0V (blue).
The power is supplied from the connector of the main cable. PRO5 Refer to ' 15 PRO
Turn MODE PRO5
2) 50mA max., if five, or more, the connector type FX-301(P) are connected in cascade. ࡮Code setting function '' ࡮Setting reset function ''
࡮Adjust lock setting function mode setting'.
Symbols...D1, D2: Reverse supply polarity protection diode
''
ZD1, ZD2: Surge absorption zener diode
Tr1: NPN output transistor The 0-ADJ setting function in this product was removed from production starting May, 2005.
Tr2: PNP output transistor
9 TEACHING MODE
7 PART DESCRIPTION In case of 2-level teaching
MODE indicator / L/D ON (Yellow)
Operation indicator (Orange) Stability indicator (Green) MODE indicator / TIMER (Yellow) ٨ This is the method of setting the threshold value by teaching two levels, corresponding to
the object present and object absent conditions. Normally, setting is done by this method.
Step Display Description

MODE indicator / RUN (Green) ࡮ Set the fiber within the sensing range.
MODE indicator / Press
MODE key Ԙ ࡮ Press MODE key to light up MODE indicator /
MODE indicator / TEACH (Yellow) PRO (Yellow)
TEACH (yellow).
MODE indicator / ADJ (Yellow) Digital display (Red) Jog switch
࡮ Press Jog switch in the object present condition.
8 OPERATION PROCEDURE ԙ ࡮ If the teaching is accepted, the read incident light intensity
blinks in the digital display. Press
٨ When the power supply is switched on, communication ࡮ The MODE indicator / TEACH (yellow) blinks.
self-check is carried out and normal condition is Ԛ
࡮ Press Jog switch in the object absent condition. Press
displayed [MODE indicator / RUN (green)] lights up and
࡮ If the teaching is accepted, the read incident light intensity blinks in the digi-
the digital display shows the incident light intensity. tal display and the threshold value is set at the mid-value between the inci-
MODE key Jog switch dent light intensities in the object present and the object absent conditions.
ԛ
After this, the judgment on the stability of sensing is displayed.
6WTP
Press Press In case stable sensing is possible: '䇭 䇭 䇭' 䇭 is displayed.
'+' side '-' side In case stable sensing is not possible: '䇭 䇭 䇭' 䇭 is displayed.
Ԝ ࡮ The threshold value is displayed.

ԝ ࡮ The incident light intensity appears in the digital display and the setting is complete.

In case of limit teaching


*1: When Jog switch is pressed, the setting is confirmed.
٨ This is the method of setting the threshold value by teaching only the object
*2: When MODE key is pressed for 2 sec., or more, the sensor returns to the 'RUN' mode.
absent condition (stable incident light condition). This is used for detection in the
*3: Cancellation is possible by pressing MODE key during setting.
presence of a background body or for detection of small objects.
*4: When Jog switch is turned in the 'RUN' mode, the current threshold value is displayed.
And then, the current incident light intensity display appears again automatically. Step Display Description

٨ NAVI mode ࡮ Set the fiber within the sensing range.


Press
Ԙ ࡮ Press MODE key to light up MODE indicator /
RUN Run TEACH (yellow).
This indicates normal sensing operation.
࡮ Press Jog switch in the object absent condition.
Press ԙ ࡮ If the teaching is accepted, the read incident light intensity
blinks in the display. Press
TEACH Teaching Refer to ' 9 TEACHING MODE'.
Sets the threshold value by '2-level teaching' or ࡮ The MODE indicator / TEACH (yellow) blinks.
'limit teaching', 'full-auto teaching'. Ԛ ࡮ Turn Jog switch to the '+' side or the '-' side. Turn
࡮ If Jog switch is turned to the '+' side, ' ' scrolls (twice) the
Press display from right to left, and the threshold level is shifted to a
ADJ Adjust Refer to ' 10 THRESHOLD VALUE FINE value approx. 15% higher (lower sensitivity) than that set at ԙ. Turn to '+' side
Allows fine adjustment of the threshold value. ADJUSTMENT MODE'. (Note) This is used in case of reflective type fibers.
࡮ If Jog switch is turned to the '-' side, ' ' scrolls (twice) the
Press display from left to right, and the threshold level is shifted to a
value approx. 15% lower (higher sensitivity) than that set at ԙ. Turn to '-' side
L/D ON L-ON / D-ON Refer to ' 11 OUTPUT OPERATION
(Note) This is used in case of thru-beam type fibers.
SETTING MODE'. ԛ
Sets output operation either Light-ON, or Dark-ON. High
OFF ON
Sensitivity level
Press Sensitivity 100% 15% Sensitivity level
TIMER Timer Refer to ' 12 TIMER OPERATION level 15% with object absent

Configures operation of the timer. SETTING MODE'. ON OFF Sensitivity level


Low 0
Turn to '+' side
Press Turn to '-' side
PRO Pro Refer to ' 15 PRO MODE'.
࡮ After this, the judgment on whether the set shift amount is possible or not
Allows various detailed settings to be configured, such as will be displayed.
optical communications, save / load and other settings.
٨ To PRO mode Ԝ
When the shift is possible: ' ' is displayed.
When the is not possible: ' ' is displayed.
Press Press
ԝ ࡮ The threshold value is displayed.

Ԟ ࡮ The incident light intensity appears in the digital display and the setting is complete.
Note: The approx. 15% amount of shift is the initial value. The amount of shift can be changed in the
PRO mode from approx. 0 to 80% (5% step). Refer to ' 15 PRO MODE / PRO1 mode setting'
for the setting method.
In case of full-auto teaching 15 PRO MODE
٨ Full-auto teaching is used when it is desired to set the threshold value without
For details of the settings and the setting procedure of the PRO mode, refer to 'Panasonic
stopping the assembly line, with the object in the moving condition.
Industrial Devices SUNX website (http://panasonic.net/id/pidsx/global)' or contact our office.
Step Display Description
٨ PRO settings can be done when MODE indicator / PRO
࡮ Set the fiber within the sensing range. (yellow) lights up.
Press
Ԙ ࡮ Press MODE key to light up MODE indicator /
TEACH (yellow). PRO1 mode setting
Turn
࡮ Press Jog switch continuously for 0.5 sec. or more with the
Ultra high speed Response time: 65Ǵs or less
ԙ object moving on the assembly line. (The incident light intensi-
ty is displayed during sampling.) Press
High speed Response time: 150Ǵs or less
࡮' ' is displayed on the digital display. Release the jog switch when the
Ԛ
object has passed. Reduced intensity (Note) Response time: 250Ǵs or less
Press
࡮ If the teaching is accepted, the read incident light intensity blinks in the digi-
tal display and the threshold value is set at the mid-value between the inci- Standard Response time: 250Ǵs or less
dent light intensities in the object present and the object absent conditions.
ԛ Long-range Response time: 2ms or less
After this, the judgment on the stability of sensing is displayed.
Press
In case stable sensing is possible: '䇭 䇭 䇭' 䇭 is displayed.
In case stable sensing is not possible: '䇭 䇭 䇭' 䇭 is displayed.
Ԝ ࡮ The threshold value is displayed. Note: The S-D mode is suitable for delicate sensing, such as when
Turn the received lights is saturated due to too short a sensing dis-
ԝ ࡮ The incident light intensity appears in the digital display and the setting is complete. tance or when detecting translucent objects, etc.

10 THRESHOLD VALUE FINE ADJUSTMENT MODE Press Turn


Without timer
٨ Fine adjustment of the threshold value can be done
when MODE indicator / ADJ (yellow) lights up. OFF-delay timer
࡮ When Jog switch is turned to the '+' side, the threshold
value increases (sensitivity decreases). ON-delay timer
When Jog switch is pressed, the threshold value is confirmed. ONE-SHOT timer

Press
Turn
Turn to the '+' side. Turn to the '+' side. Press Confirmed
The range of available timer delays is
Turn 0.5ms, 1 to 9999ms (1ms increments).
࡮ When Jog switch is turned to the '-' side, the threshold value decreases (sensitivity
increases). Turn
When Jog switch is pressed, the threshold value is confirmed. Hysteresis: Small
Press
Hysteresis: Standard
Turn
Turn to the '-' side. Turn to the '-' side. Press Confirmed Hysteresis: Large

Note: Set the threshold value at least a bit higher than the minimum threshold value. (The minimum
Turn
threshold value is where the value cannot be lowered any further even if the jog switch is
Turn
turned to '-' side.)
Margin width:r5%
Press
11 OUTPUT OPERATION SETTING MODE Margin width:r10%
٨ The output operation setting can be done when MODE
Margin width:r15%
indicator / L/D ON (yellow) lights up.
࡮ The output operation is changed when Jog switch is
Turn
turned to the '+' side or the '-' side.
When Jog switch is pressed, the threshold value is confirmed. Press
Amount of shift: 15% approx.

Turn Press Confirmed


Turn

The amount of shift can be changed approx. 0 to


Turn 80% (5% step).
12 TIMER OPERATION SETTING MODE
٨ The setting for whether the timer is used or not can be Press Turn
done when MODE indicator / TIMER (yellow) lights up. Emitting power Hi
٨ 10ms OFF-delay (initial value) timer is automatically set
when the timer is set to be used.
٨ Refer to ' 15 PRO MODE / PRO1 mode setting' for the setting method of the OFF-
delay timer, ON-delay timer and ONE-SHOT timer intervals.
Emitting power Lo
OFF-delay
(Without timer) timer Emission halt (Note 1)
Turn

Notes: 1) If the sensor is returned to RUN state in the emitting halt


Press: Confirmed condition, ' ' is displayed. The ' ' goes off when
Turn Turn
the emitting power is turned on.
2) Only in the response time࡮H-SP mode, ON condition, the
ONE-SHOT ON-delay emitting power is 3 level.
timer timer
Turn
Notes: 1) The timer interval set in the PRO mode is displayed.
2) The factory setting is without timer ' '.

13 KEY LOCK FUNCTION


٨ If the jog switch and MODE key are pressed for more than 2 sec. at the same time in 'RUN'
mode condition, the key operations are locked, and only the threshold value confirmation
function or the adjust function (valid only when the adjust lock function is canceled) is valid.
To cancel the lock function, press both the keys for more than 2 sec. once again.

14 ERROR INDICATION
٨ In case of errors, attempt the following measures.
Display Error description Measures
The load has short-circuited
Turn off the power, then check the load.
and excess current is flowing.
Communication error has
Check that the mounted amplifiers are in close
occurred at the time of
contact with each other.
connection in cascade.
PRO2 mode setting PRO5 mode setting
The 0-ADJ setting function in this product was removed from production starting May, 2005.
Press Press Turn
Incident light intensity display
Press Press Press Press
Percentage display
(Blinking)
Peak hold display
(Note 1)
Bottom hold display Press
Turn
: Select the
Turn : Confirmed desired code
Turn Press Turn (Note 2)
Press
Turn Turn OFF
Press
Turn ON Adjust lock ON

Turn Adjust lock OFF


Turn
Turn
Press Turn Turn
ECO OFF Press Press

ECO ON
Cancel
Press
Goes to 'RUN' mode
after blinking twice.
PRO3 mode setting
Notes: 1) When any code other than the codes given in the Code setting table below is used, ' ' is
displayed. The factory setting is ' '.
Press Turn 2) When the code setting function is used, refer to the 'Code setting table' given below.
Press
1CH Code setting table
Press Press
2CH
1st figure 2nd figure 3rd figure 4th figure
3CH
Direct Response H y s t e- Direct L-ON/ Direct Adjust Timer Direct
Cancel Display Timer
Press EQFG time resis EQFG D-ON EQFG lock operation EQFG
Turn
STD H-02 (standard) L-ON digit ON NON OFF
STD H-03 (large) L-ON Percent ON OFF-delay 1ms
Turn
Press STD H-01 (small) L-ON Peak hold ON ON-delay 3ms
1CH
Press Press LONG H-02 (standard) L-ON Bottom hold ON ONE-SHOT 5ms
2CH LONG H-03 (large) D-ON digit OFF NON 10ms
3CH LONG H-01 (small) D-ON Percent OFF OFF-delay 30ms
Cancel FAST H-02 (standard) D-ON Peak hold OFF ON-delay 50ms
Press
FAST H-03 (large) D-ON Bottom hold OFF ONE-SHOT 100ms
PRO4 mode setting FAST H-01 (small) 㧙 㧙 㧙 㧙 㧙 㧙 300ms
S-D H-02 (standard) 㧙 㧙 㧙 㧙 㧙 㧙 500ms
Press Press Press Press 㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 1s
㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 2s
Cancel 㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 3s
Press
㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 4s
Turn
㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 㧙 5s
Turn
Press 3) In order to change PRO mode setting to 'RUN' mode, press MODE key for 2 sec. or more.
1CH
Press Press
2CH
16 A DIFFERENCE BETWEEN THE MODIFIED VERSION
3CH Cancel
e.g.)
UNIT AND THE CONVENTIONAL VERSION UNIT
Press
When set ٨ The unit that 'NAVI' is printed only on a side is the modified version unit. The unit
Turn to ch.1 that 'NAVI' is printed on the both sides is the conventional version unit. Make sure
to check this when both version units are used together.

Turn
<Modified version unit>
Press 0#8+
'NAVI' is printed only on a side. 0GY#FXCPEGFUGPUQT
YKVJ8KUKDNG+PFKECVQT

1CH
Press Press
<Conventional version unit>
Turn 2CH 0#8+ 0#8+
'NAVI' is printed on the both sides. 0GY#FXCPEGFUGPUQT
YKVJ8KUKDNG+PFKECVQT
0GY#FXCPEGFUGPUQT
YKVJ8KUKDNG+PFKECVQT

3CH Cancel
e.g.)
When set
Turn
Press
to ch.1 17 INTENDED PRODUCTS FOR CE MARKING
٨ The models listed under “ 1 SPECIFICATIONS” come with CE Marking.
As for all other models, please contact our office.
Turn
Press
Communication lock function OFF ٨ Contact for CE
<Until June 30 ,2013>
Communication lock function ON Panasonic Electric Works Europe AG
Rudolf-Diesel-Ring 2, D-83607 Holzkirchen, Germany
<From July 1 ,2013>
Turn
Panasonic Marketing Europe GmbH Panasonic Testing Center
Turn Winsbergring 15, 22525 Hamburg,Germany
Press
Back-up ON

Back-up OFF

http://panasonic.net/id/pidsx/global
Overseas Sales Division (Head Office)
2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan
Phone: +81-568-33-7861 FAX: +81-568-33-8591
About our sale network, please visit our website.
PRINTED IN JAPAN © Panasonic Industrial Devices SUNX Co., Ltd. 2012

You might also like