0% found this document useful (0 votes)
113 views21 pages

Battery Sizing UPS

Uploaded by

tony.kale
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
0% found this document useful (0 votes)
113 views21 pages

Battery Sizing UPS

Uploaded by

tony.kale
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 21
FC Fuji Electric Innovating Energy Technology Prior to selecting the UPS, it is necessary to determine the need. UPS may be needed for a variety of purposes such as lighting, startup power, transportation, mechanical utility systems, heating, refrigeration, production, fire protection, space conditioning, data processing, communica- tion, life support, or signal circuits. Some facilities need an UPS for more than one purpose. It is important to determine the accept- able delay between loss of primary power and availability of UPS power, the length of time that emergency or backup power is required, and the criticality of the load that the UPS must bear. All of these factors play into the sizing of the UPS and the selection of the type of the UPS SIZING CALCULATION SELECTION OF UPS 3 PHASE OR 1 PHASE Single phase power is used in most homes and small businesses and adequate for running lights, fans, 1 or 2 ACs, some computers and motors up to about 5 horsepower; a single phase motor draws significantly more current than the equivalent 3-phase motor, making S-phase power a more efficient choice for industrial applications Single-phase * vo 27 THE Figure-1 With the waveform of single-phase power, whon the wave passos through zero, the power supplied at that moment is zero. The wave cycles ‘50 times per second S-phase power is common in large businesses, data centers, as well as industry and manufacturing around the globe. While it is expensive to convert to three phase from an _ existing single. phase installation, 3-phase allows for smaller, safer and less expensive wiring. S-phase Vor Time Figure-2 S-phase powerhas 3 distinct wave cycles that overlap. Each ‘hase reaches its peak 120 degrees apart from the others so the level ‘of power supplied remains consistent (02) FC Fuji Electric Innovating Energy Technology Most consumers of electricity in India have a three phase mains connection if the tolal load is more than 5-7 KW. Only if expected load is below 5-7KW, then the consumer gets a single phase connection Even when the consumer has a three phase connection, the choice of three phase or single phase UPS depends on several factors like the loads to be connected to UPS and also electrical distribution within the facility from the building incomer, electrical switchgear and distribution units, to the room the loads to be protected are within This not only builds up a complete picture of the electrical circuits on-site, It also helps to determine whether to offer a three phase or single phase UPS system. UPS Systems - Input and Output Phases In UPS there are three potential phase configurations available, This is because a 3 phase mains or generator supply actually consists of three single phase supplies (and a neutral) with a 120 degree phase orientation between the them. ‘A 3 phase supply can deliver more electrical power than a single phase supply. ‘The laws of physics and Ohms Law also come into play, meaning that cable sizes also increase in diameter as amperages rise. A 10KVA output is generally the largest single phase UPS system available. This is due to the output amperage and cable requirements. 10KVA=10,000VA / 230Vac = 43.5Amps. In the world of UPS, it is common to refer to a single phase UPS only by its KVA/KW rating i.e. SKVA. However for a three phase UPS it is common te refer to the KVA/KW rating along with the number of phases i.e. 2OKVA 3/1 or 100KVA. 3/3. ‘© Copyrights Reserved SELECTION OF UPS 3 PHASE OR 71 PHASE 3 Phase UPS Systems (3/3 and 3/1) Most datacentres, commercial and industrial buildings will have a 3 phase electrical incomer that connects them via a local distribution transformer to the Mains, Three phase circuits may be required throughout the building to carry the large amounts of electrical power required for large KVA three phase This is a generalisation as many environments can include both single and three phase loads of course. From a UPS systems perspective, if we are to connect the UPS to a three phase supply we require a UPS with a 3/x configuration. If the loads are three phase as well, then we require a 3/8 configuration. If the loads are single phase we may need a 3/1 configuration. Using a three phase UPS system can simplify a power continuity plan and allows a site to adopt a centralised power protection plan, where one large UPS is used to protect a complete building or critical circuits and operations within it, This is in contrast to @ decentralised power continuity plan using a number of smaller UPS dispersed to protect clusters of loads like computers and lower power equipment (<10KVA) within a facility. Single Phase UPS Systems (1/1) The wall sockets that we typically plug into are single phase supplies rated at 230Vac 50Hz in India. Typical examples would include ATMs, small lab equipments, desktop computers, file servers, switches, routers, hubs and telecoms systems. Single phase UPS systems up to 2KVA can be supplied with a plug or with covered terminals for hardwired installation. At SKVA, the power required means that the UPS will be supplied as either a hardwired system or with a 16A plug. Above SKVA to the largest single phase UPS FC Fujiclectric Innovating Energy Technology system available (typically 10KVA) the UPS will require a hardwired installation and should also include an UPS maintenance bypass switch UPS System Load Sizing When sizing UPS itis important to know the phase configuration required by both the mains supply and the loads, in adsition to the overalll load size Electrical consultants and electrical contractors will often state both load size and phase configuration. An example would include '120KVA three phase’. This refers to a 120KVA load run from a three phase 415Vac, S0Hz supply. In terms of load sizing, this means that each phase (of the 3 phase electrical supply) will deliver upto 40KVA (or 174Amps at 280Vac). If the statement was 120KVA per phase then we would be looking at 3x120KVA per phase = 360KVA UPS load. The need for a 120KVA three phase UPS could be met. with three single phase output 40KVA UPS provided the connected loads are single phase loads. These would be 3/1 configured and installed one per phase. However, the overall capital, installation and energy efficiency costs just rose by a factor of 3 compared to a single 120KVA UPS system installation. 3/1 UPS upto G0KVA are also used in office environment where the loads are single phase and this removes the need to balance the load connections in each of the three phases. Larger 3/1 UPS even upto 200KVA are typically required for DCS and SCADA loads in heavy industries Ike Power Plant, Steel Plant ete. ores 1 Phase | 1 Phase lesor2sovac, SoH2 | 400vA-10KVA ‘aPnase|1 Phase] s/1___|415/230vac, S0H2 5 - 200KVA\ SPraso|SPhasol 3 __[4t6/a16Vac, Soh [1OKVA— 48M a) © Copyrights Reserved UPS SIZING STEADY STATE LOAD CONDITIONS Steady State Loading Conditions As like any other power source, UPS is a limited power supply and the capacity of the UPS is defined in KVA (apparent Power) and KW (real power). To arrive at the capacity of UPS and the configuration of UPS, the following steps needs to be followed + Step1> © Step 2> © Step3> Need of Load Configuration of UPS Check on the KVA & KW demand supplied by the UPS Step 1: Need of Load Tabulate the need of load as shown in the below table and arrive at the load demand of the loads expected to be connected to the UPS. (Note:The load power factor has tobe measured at the ste or can be assumed based on the past experience) KVA Demand Load Power Factor | KW Demand lLoag1 | Kvat al KVAx PFI lloag? | RwAa Pre KVAx Pre ltoags_[KVAS PFS KVAX PFS loadin _[KWAn PFo KVAxPFn [Total Load | KVA KWIKVA, KW Step 2: Configuration of UPS The criticality, of the loads will determine the necessary availability of the UPS. Based on the criticality the UPS capacity or configuration can be selected ‘Where N is the no of UPS, required to support the Load. For critical load with 66% redundancy N>2, where a minimum of 2 UPS is required to support the load and 1 UPS for redundancy. Fe FujiElectric Innovating Energy Technology INon-Criical Load o% N [critcat Loads 06% Net critical loads 00% NaN Critical Loads 100% 2N Fault Tolerant System Step 3: Selecting the required UPS capacity Based on the total demand and the configuration of UPS, the capacity of UPS is selected. The total load in KVA and KW derived in step 1 will have to divided by N as selected in step 2 to arrive the UPS capacity. ‘bialLoagin KW (From Sten") UPS Capaciy inv = => Tal US in kw Nien So 2) “etal Load in kVA (Fem St 1) UPS Gapaciy in vA = =Total UPS a KV, Nim Sep 2) ‘© Copyrights Reserved DYNAMIC LOADING CONDITIONS The sizing of UPS for loads which are dynamic in nature is a complicated subject, but with the recorded information as shown below, the optimised UPS capacity can be derived based on * Inrush Current-Nature & Duration * Peak Process Current-Nature & Duration * Number of Loads, sequence of their operation * Load Power Factor + KVA and KW Demand of the UPS Inrush Current Input surge current or switch-on surge isthe maximum, instantaneous input current drawn by an electrical device when first turned on, The inrush current can be omitted in the selection calculation if the load is switched on only once and run continuously till the next shutdown of the plant as we can switch the loads in manual bypass and once the loads reach the steady state current, the loads can be transferred to the UPS If the loads are switched on & off repetitively then the UPS selection should include the inrush current also. Peak Process Current It is the maximum current drawn momentarily by the loads during the process time. This current can be repetitive in nature. The peak current has to be part of the UPS Sizing calculation irrespective of the nature and duration. Fe Fuji Electric Innovating Energy Technology Number of Loads and Sequence of Operation The UPS selection depends on the no of loads, if there is only one load, then the selection of UPS is simple and is based on the maximum peak Current UPS Capacity in KVA = V3 XV X la sea, If there are multiple loads with a combination of static and dynamic loading characteristic, then the UPS capacity is selected based on the sequence of operation of the loads. Sequential Operation of Load When the loads are operated in sequence, the UPS capacity is selected based on the summation of rms currents of all the connected loads and the maximum rms peak current of the load as shown: in the below formula UPS Capacity in KVA =V3 XVX ((5,"I,)+ ) Non-Sequential Operation of Loads When the loads are not operated in a sequence, the UPS capacity is selected based on the summation of rms currents of all the connected loads and the rms peak current of all the connected load as shown in the below formula UPS capacity in KVA =V3 XV XE," | es pak) ‘© Copyrights Reserved BATTERY SIZING CALCULATION The purpose of the battery is to provide DC power to the inverter of the UPS when the mains fail and becomes an important component in the UPS system There are different technologies of battery available in the market like Lead acid battery which is further classified as Tubular battery, Sealed Maintenance free(SMF,VRLA)Battery, Nickel Cadmium and Lithium lon battery. Sealed Maintenance Free, Valve Regulated Lead Acid (SMF VRLA Battery) is mostly used with the UPS systems today. A VRLA battery utilizes a one-way, pressure-relief valve system to achieve a “tecombinant” technology. This means that the oxygen normally produced on the positive plate is absorbed by the negative plate. This suppresses the production of hydrogen at the negative plate. Water (H,O) is produced instead, retaining the moisture within the battery. It never needs watering, and should never be opened as this would expose the ballery to excess oxygen from the air. © The nominal cell voltage of a battery celllis 2V, 6 cells are connected in series inside the battery container to have a final voltage of 12V, + The capacity of the battery is defined as “Ampere Hour (AH)" ‘+ The batteries are connected in series to increase the voltage of the battery bank and are connected in parallel to increase the capacity of the battery bank FC Fuji Electric Innovating Energy Technology Figure 8 Schematic of Battery n Series and Parallel By design, the battery has to be operated in a controlled electrical and environmental conditions and the critical elements affecting battery life are: 1. Under charge > Charging of battery with a lower voltage and current 2. Cycling > Cyclic usage of battery 3. Overcharge > Charging of battery with a higher voltage or current which is above the recommended conditions of the manufacturer 4, Temperature > The ambient temperature References * IEEE 1184:2006 IEEE Guide for Batteries for Uninterruptible Power Supply Systems * IEEE 485:1997 IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications + Datasheet's of major battery manufacturer's © Copyrights Reserved LIFE EXPECTANCY O SMF VRLA BATTERY Design Life of Battery Design life is determined by the manufacturer and takes into account cell design and battery ageing under controlled conditions in the manufacturer's lab. However, the design life of battery can be only used for reference as the real service life of battery depends on the various factor like * Operating Temperature * Number of charge, discharge cycle * Charging conditions * Depth of discharge In simple terms, the battery will reach its end of life When its capacity falls below 80% of its rated capacity and warrants for immediate replacement. Impact of temperature on life of battery The battery is rated in watts/cell at an ambient temperature of 25-27deg C. When the operating temperature or battery is less the capacity of the battery will be reduced and when the temperature is higher than the design temperature, the capacity of the battery increases Elevated temperature operation will shorten battery life. A general rule of thumb for lead-acid batteries is that the prolonged use at elevated temperatures will reduce the battery life by approximately 50% for every 8 °C above 25°C FC Fuji Electric Innovating Energy Technology Expected Lite (Percent of Rated) 8s 8 8 38 8 7% 8 8 510105 110 Temperature (°F) Figure 4 Temperature vs Lite Curve Frequency and Depth of Discharge The life of a battery is related to the frequency and depth of discharges. A battery can provide more short duration, shallow cycles than long-duration, deep discharge cycles. Even momentary fluctuations in the AC power to the UPS may result in battery discharges for several seconds or more. Frequent cycling of the UPS battery, even for short durations, shortens battery life. \ are Uh 2100) 3 a 3%) 100% DD SOKO 30ND gal 2 24 No.of oles Figure 5 Cyclic Lite of Batory © Copyrights Reserved CONSIDERATIONS FOR BATTERY SIZING Load Profiling Sizing a battery is important to ensure that the loads being supplied or the power system being supported are adequately catered for by the battery for a period of time (ie, autonomy) for which it is designed Improper battery sizing can lead to poor autonomy limes, permanent damage to battery cells from over-discharge, and UPS shutdown due to low voltage. The load profiling has to be done based on * Nature of Loads to be supported by the battery * Continuous ‘+ Non-Continuous * Momentary * Baltery autonomy time * Design Margin * Ageing Factor * Effects of temperature Design Margin Design Margin is considered to provide a capacity margin to allow for unforeseen additions of load to the less-than optimum operating conditions of the battery due to improper maintenance, recent discharge, or ambient temperatures higher than anticipated, or a combination of these factors, A method of providing this design margin is by adding UPS system and load of 10-15% to the battery sizing calculations. 10-8 FG Fuji Electric Innovating Energy Technology ‘Ageing factor captures the decrease in battery performance due to age. The performance of a lead-acid battery is relatively stable but drops markedly at latter stages of life. The "knee point” of its life vs performance curve is approximately when the battery can deliver 80% of its rated capacity. After this point, the battery has reached the end of its useful life and should be replaced Therefore, to ensure that batlery can meet capacity throughout its useful life, an ageing factor of 1.25 should be applied (ie. 1 / 0.8) There are some exceptions, check with the manufacturer. be a Figur 6 Capacty vs Lite Curve Effects of Temperature Temperature correction factor is an allowance to capture the ambient installation temperature. The capacity for battery cells are typically quoted for a standard operating temperature of 25 deg C and where this differs with the installation temperature, a correction factor must be applied IEEE 485 gives guidance for vented lead-acid cells (see table), however for sealed lead-acid and Ni-Cd cells, please consult manufacturer for recommendations. Note that high temperatures, lower battery life irrespective of capacity and the correction factor is for capacity sizing only, i.e. you CANNOT increase battery life by increasing capacity. © Copyrights Reserved eV oasis = FO Ful cect CORRECTION tng Energy Technolgy CHO nan @)n| BATTERY SIZING Electrolyte Temperature Coll Size Electrolyte Temperature | Cell correction correction () (0) factor (ry (eo) factor 2 “39 1.820 78 25.6 0.994 30 4 1.430 79 26.41 0.987 35 17 1.850 80 267 0.980 40 44 1.300 81 272 0.976 45 72 1.250 82 278 972 50 100 1.190 83 28.3 0.968 55 128 1.180 84 28.9 0.964 60 186 1.110 85 29.4 0.960 65 183 1.080 86 30.0 0.956 66 189 1.072 a7 30.6 0.952 7 194 1.064 88 ai 0948 68 20.0 1.056 89 316 0.944 69 206 4.048 90 32.2 0.940 70 and 4.040 95 35.0 0.930 n a7 1.084 100 378 910 72 22.2 1.029 105 40.6 0.890 73 22.8 3.028 310 43.3 0.880 1 234 3.017 118 46.4 0.870 75 239 4.011 120 48.9 0.860 76 245 1.006 125 B17 0.850 77 25.0 1,000 Note -- This table is based on vented lead-acid nominal 1.215 specific gravity. However, it may be used for vented cells with upto @ 1.300 specific gravity. For cells of other designs, refer to the manufacturer. ‘© Copyrights Reserved BATTERY SIZING CALCULATION FOR UPS SYSTEMS Battery Sizing Calculation for UPS System The inverter of UPS provides a constant voltage to the loads connected to it. During a battery discharge the battery supplies constant power to the inverter of the UPS. The DC input voltage to the inverter decreases during the discharge. To maintain a constant power output, the battery discharge current increases accordingly Figure 7 Constant Power Discharge Characterstes There are different methods to connect the battery with the inverter of UPS. Battery can be connected directly to input of the inverter (refer Figure 8) In this case, the load on the battery is purely based on the output load connected to the inverter and the losses of the inverter bridge. aectfer ivener ne putt Hp one a wv Load 1 Battery Figure 8 Battry connected to the DC bus FC Fuji Electric Innovating Energy Technology Battery is connected to a DC-DC Converter and the output of the DC-DC converter is connected as an input to the UPS (refer figure 9) In this case, the load on the battery is based on the ‘output load connected to the inverter, the losses of the inverter bridge and also the losses of the DC-DC Converterwhich could increase the required battery capacity. Sy) Rector vert BT outperte 2 = Cetieal 2 = lose i+ aattery Bey Charger Figure 8 UPS with DC-DC Charger between the inverter and Battory UPS Efficiency And Power Factor UPS power ratings are quoted in volt-amperes (VA) and/or watts. The rating in watts is equal to the rating in volts-amperes multiplied by the power factor. UPS output power rating in watts = UPS output in volts-amperes x power factor The battery load for sizing purpose is the UPS ‘output rating in watts divided by the efficiency of the inverter. The efficiency should be based on rated UPS output. UPS output power into watts X1000 —svsttsr assy ‘Nominal battery load in W = Nominal battery load in W ‘Nominal battery loadin WiBatery = Nest Batteries — © Copyrights Reserved BATTERY SIZING FO Fuji Electric CALCULATION Innovating Energy Technology Adjusted Battery Load Calculation The nominal battery load should be adjusted for ageing and operating temperature conditions Battery Load in W/Battery = Nominal battery load in W/Battery x ageing factor x temperature correction factor x design margin This final battery load in battery has to be cross referred with the battery manufacturer's discharge characteristics for a specified battery autonomy time (sample table is shown in fig 10) with the required cutoff voltage to arrive at the capacity of the battery required. General Guidelines for Battery Selection * Calculate the load in Watts-hours as accurate as possible. * Include system losses due to efficiencies of power conditioning (inverter, battery charger - DC/DC converters), * Include the appropriate factors: Temperature autonomy, design margin, and depth of discharge (DOD), ageing factor * Consider shallow DOD (max 20% recommended) and occasional deeper DOD (max 80%) * Select highest battery capacities per unit to reduce the number of battery strings in parallel for better charge balance. The recommended maximum number of strings in parallel is 4. © Copyrights Reserved BATTERY SIZING FC Fuji Electric GC Al eu) LATION Innovating Energy Technology Constant power discharge rating watts per battery @ 27 °C* Eev DURATION Tomin [iSmn [20min | Gomm | 60mm | 2h | Shs | Shs [Shwe | iOhs [20h 160 | 3564 | 2801 | 2269 | tei7 | 1125 | @80 | 495 | 340 | 225 | 183 93 165 | S441 | 2764 | 2203 | 17ee | 1100 | @70 | 483 | a25 | 219 | 181 2 170 | S288 | era7_| 2i77 | 1755 | 107s | e589 | 470 | ste | 213 | 180 2 17 | 3135 | 2690 | 2ier | i724 | 1s0 | e493 | 6 | ai0 | 210 | 178 aT Tao | 2982 | 2570 | 207e | Teas | Toea | ese | aaz | aoa 207 | 177 30 Figure 10: Sample constant power discharge rating of battery Sample Calculation : 15 mins backup on a S00KVA UPS with an output power factor of 0.9 UPS Rating (KVA) 500KVA Specified by Customer of Gonsukant Actual Load on UPS (KVA) SO0KVA Specified by Customer or Consultant ‘Output Power Factor 08 Specified by Gustomer or Consukant Inverter Efficiency (n) 95% Based on UPS Manufacturer's data No of Batteries BONos Based on UPS Manufacturers data End Gell Vokage (ECV) Tv Specified by Gustomer o Gonsukant ‘Backup time required (in ins) Tomine Specified by Gustomer or Gansuant ‘Ageing Factor 125 Specified by Customer or Consultant Design Margin 1 Specified by Gustomer or Consultant “Temperature Correction Factor 1 Specified by Customer or Consukant Step 1: ‘Arrive UPS output power rating in watts = UPS output in volts-amperes x power factor 500 X 0.8 KW = 400KW Step Arrive the nominal battery load in W UPS output power in kW X1000 Answer of Step 1 Nominal battery loadin W = = Inverter efficiency Inverter efficiency 400 X 1000 = 421053 W 0.95 on) ‘© Copyrights Reserved Saunas FS Fuji Electric CALCULATION Innovating Energy Technology Step 3: Arrive the nominal battery load in W per Battery Answer of step 2 4721053 Nominal battery load in W/Battery = _______= _________ = 8421 W/Battery No of Batteries 50 Step 4: Arrive at the adjusted battery power required by taking into consideration design margin, ageing factor and TCF (Temperature correction factor) Adjusted nominal battery load in W/Battery = Answer of Step 3 X Design Margin X Ageing Factor X TCF = 8421.05 X 1X 1.25X 1 =10526 WiBattery As the maximum available AH is 200AH Battery in 12V SMF VLA battery, we need to parallel multiple strings of battery to achieve the desired backup time. Step 5 Watts/Per battery required (Answer of step 4) No of strings required = Watts the battery can deliver (from battery manufacturer datasheet) ‘A 160AH battery can deliver 3552 W at end cell voltage of 1.75V/Cell for 10 mins 10526 W = = 2.6 string 3552W Hence in this scenario, 8 strings of 160AH battery with 50 battery in each string will provide 10 mins backup at end cell voltage of 1.75V/Cell 3 strings ‘© Copyrights Reserved SELECTION OF CABLES Selection Of Cables The ctoss section of cables depends on * Permissible temperature rise * Permissible voltage drop For a given load, each of these parameters results ina minimum permissible cross section. The larger of the two must be used. When routing cables, care must be taken to maintain the required distances between control circuits and power circuits, to avoid any EMI disturbances caused by HF currents, Temperature Rise Permissible temperature rise in cables is limited by the withstanding capacity of cable insulation. ‘Temperature rise in cables depends on: © Type of core (Cu or Al) ¢ Installation method ‘* Number of touching cables type of cable, the maximum permissible current. Voltage Drops The maximum permissible voltage drops are * AC circuits (50 or 60 Hz) * If the voltage drop exceeds 3% (50-60 Hz), increase the cross section of conductors. * DC circuit * If the voltage drop exceeds 1%, increase the cross section of conductors. Special Case For Neutral Conductors In three-phase systems, the third-order harmonics {and their multiples) of single-phase loads add up in the neutral conductor (sum of the currents on the three phases). RG Fuji Electric Innovating Energy Technology For this reason, the following rule may be applied: neutral cross section = 2 x phase cross section in Sqmm Output Cables To artive at the cross section of the cable, the output current needs to be calculated using the below formula KVAX1000 Rated Current in A(l) ¥3 XV, using the cable manufacturer's datasheet and the conditions linked with routing and bunching of cables, the required cable can be selected ‘As thumb rule, we can consider 2A/sa mm to arrive the cross section of the required cables. Rated Current in A(!) Cross Section of Cables in sq mm. ‘© Copyrights Reserved INPUT, OUTPUT AND UPS TO BATTERY CABLES Input Cables The cross section of cables required for the input of the UPS can be derived using the same formula like output cables, but the input power in KVA needs to be derived based on the * Connected Load * Efficiency of the Inverter * Battery charging Power * Efficiency of Rectifier * Input power factor of rectifier * Minimum operating Voltage of Rectifier Step 1: Arrive at the input power of Inverter Capacity of UPS in KVA X Ourpur Power Factor x 1000, Inverter input Power Inverter Etielency Step 2: Calculate the battery charging power in W Batlery Charging Power = 2.2VX No of Cells X Charging Current ‘The charging current is iyoically 10% of AH Capacity Step 3: Calculate the Input power of Rectifier in W Inverter Input Power + Batery Charging Power Feciier Input Power Eticioncy of Rectiior Step 4: Calculate the input current drawn The rectifier input power calculated in step 3 needs to be converted to KVA by taking into consideration the input power factor FC Fuji Electric Innovating Energy Technology Rectifier Input Power in W Input Power in VA = Input Power Factor VA Rated Current in (A) = BX, where V,,., is the minimum operating Voltage of rectifier Rated Current in A(I) Cross Section of cables in sq mm UPS to Battery Cables The inverter of UPS provides a constant voltage to the loads connected to it, During a battery discharge the battery supplies constant power to the inverter of the UPS. The DC input voltage to the inverter decreases during the discharge. To maintain a constant power output, the battery discharge current increases accordingly. The selection of UPS to battery bank cables has to be based on the current at minimum discharge voltage, which can be derived based on the below formula UPS Capacity in KVA.X Power Factor X 1000, Current I, in A No of Coll X End Cell Vatage X Inverter ficiency Uninyvin cables are generally preferred for cables between UPS & battery due to high current carrying capacity and smaller cross sectional area. ‘© Copyrights Reserved CABLE DATASHEET FRO Fuji Electric Innovating Energy Technology Uninyvin | Size(area)| Conducter | Overall Diameter | Conductor Max Cable Diameter “Max” “Max” Resistance | Current Rating at 20°C *Max’ “Amps Core | “Sq.mm" ‘mm” “mm" “@/. 900m" BS-G-177 22 0.347 0.838 2 49.66 "1 20 0.566 1.04) 23 30.95) 14 18 0.966 1.32 25 17.82 18 16 147 1.55) 28 147 24 14 2.05 1.98) 34 8.41 34 12 3.22 2.43 38 5.35 43 10 5.33 3.15 5 3.23 61 8 8.76 4.24 63 1.97 87 6 133 5.54 75 13 15 4 218 62 93 0.802 160 2 33.3 8.76 "1 0.517 200 1 40.7 9.75 12.2 0.423 220 0 53 1 137, 0.325) 240 0 68.3 12.4 15.4 0.252 270 0 84.2 13.9) 169) 0.204 300 0 709 15.6 187 0.158 350 Ambient Tem.°C |40 | 45 | 50 |55 | 60 | 65 |70| 75 | 80] 85] 90] 95] 100 Derating Factors }1 |0.96 | 0.92] 0.88 | 0.83] 0.78 |0.75|0.73 |0.68|0.62 |0.53 |0.48 | 0.3 ‘© Copyrights Reserved CABLE DATASHEET FO Fuji Electric Innovating Energy Technology Maximum Continuous Rating Amperes in Free Air Uninyvin Cable | "Sq. mm. No ‘Single Cable | 3Bunched | 7Bunched| 2.Bunched Cables Cables Cables 22 0.347 14 7 5 4 20 0.566 14 9 7 5 18 0.966 18 13 10 6 16 17 24 15 "1 7 14 2.05) 31 24 7 12 12 3.22 43 30 22 15 10 5.38 61 47 36 25 8 876 87, 65. 49 36 6 13.3 115 87. 65. : 4 215 160 120 92 : 2 33.8 200 155 120 : 1 40.7 220 165, 130 : 0 53 240 185 168** : o 68.3, 270 210/240" 190" : 0 84.2 300 235/265" 210" : 0 109 350 2701305" 245"* - (‘Denotes two cables only, “* Denotes five cables only) © Copyrights Reserved SELECTION OF PROTECTIONS (CIRCUIT BREAKERS OR FUSES) Moulded Case Circuit Breakers are electro. mechanical devices, which protect a circuit from Overcurrent and Short Circuit Their primary functions are to provide a means either to manually open a circuit and automatically open a circuit under overload or short circuit conditions, The overcurrent, in an electrical circuit, may result from short circuit, overload or faulty design MCCB is an alternative to a fuse since it does not require replacement once an overload is detected. Unlike fuse, an MCCB can be easily reset after a fault and offers improved operational safety and convenience without incurring operating cost. Moulded case circuit breakers generally have a © Thermal element for overcurrent and * Magnetic element for short circuit release which has to MCCBs are now available with a variety of releases or operating mechanisms and these are given below * Thermal Magnetic Release * Electronic Release * Microprocessor Release Protections Against Short Circuit UPS is a limited power source, that is short circuit withstand capacity is also limited based on the selection of components, One of the features that must be carefully evaluated when choosing a UPS is its capability to properly withstand a short circuit current on its output for a certain amount of time, This capability depends on whether the output short circuit current is withstood solely by the inverter or by the source through the static bypass. © Copyrights Reserved FC Fuji Electric Innovating Energy Technology In the first case, the capability strictly depends on the UPS design and in the second case it the it characteristic of the SCR selected in the bypass path or fuse (if present in UPS) is based on When a short circuit happens on any one the distribution system on the output of the UPS, the current increases significantly. If the fault is not cleared within milliseconds, we might risk the uptime of other loads connected to the same UPS as the UPS or the upstream protection of the UPS will trip resulting in downtime of all the connected loads. In practice, for a given prospective short-circuit current value, the minimum it let-through of the upstream device must higher be than the maximum it let-though of the downstream device. For protection of short circuit on the downstream, the UPS will be based under two conditions Shortcirouit current with bypass source available Shortcircuit current without bypass source Shortcirouit current with downstream transformer in POU or global output of UPS SELECTION OF PROTECTIONS (CIRCUIT BREAKERS OR FUSES) I wcce: Fa Ha moone > é a i ey = I As pcos — L] — Short Circuit Curent with bypass MCB? Short Circuit Current without bypass Fault Figure 10 Shor circuit curent with bypass source avalable When a short circuit happens it will downstream the UPS, and the UPS will transfer the short circuit immediately to the static bypass as the static bypass will have a higher let-through energy("t). In this scenario, let through energy(i*t) of the MCB 7 has to be lower than that of the breakers present in the upstream in to have a proper discrimination of the short circuit. If the MCB 6 has a lower let through energy(it) when compared with MCB 7, then we risk to lose all the loads connected to MCB. The let through energy(i") of MCCB2 is very important. If the let through energy of MCCB 2 is higher than what the SCR can handle, then the SCR will fail. To protect the loads, SCR and to have the proper discrimination of short circuit, the following rule has to be respected FG Fuji Electric Innovating Energy Technology * i4S,,.> PMCC,, * PIMCC,,> MC*>iMC,, Short circuit current without bypass When the bypass is disabled or if the bypass source is not available and if short circuit happens downstream the UPS the inverter of UPS will support for a short duration before it trips because of electronic protections. In this scenario, the i MCCB3> it MCB6> it MCB7 For the magnetic setting of MCCB's & MCB's has to be coordinated with inverter S.C current. Short circuit current with Transformer in PDU or global output of UPS When a transformer is used either at the global output of the UPS or in a PDU,the transformer changes the short cirouit discrimination of the downstream circuit. Now the UPS short circuit current has no relevance to fault discrimination. The fault circuit current or the let though energy will purely depend on the impedance of the transformer. The short circuit current of the transformer is the ratio of full load current of the transformer and its impedance. If we have transformer with a rated current of 200A and with an impedance of 5%, the short circuit current of transformer will be 4KA. © Copyrights Reserved PROTECTING BATTERY FROM SHORT CIRCUITS Short Circuit Protection in Battery Path Battery is one of the vital components in an UPS system and its main purpose is to provide DC power to the inverter of the UPS when the mains fail and get charged through the rectifier when the mains return Like any other power source, battery will also contribute to the fault current when there is fault on the battery. The main parameters which contribute to magnitude of the current are battery's internal resistance (this depends on plate surface area, internal plate spacing and electrolyte type) and its external circuit resistance. The short circuit current will vary based on the condition and the age of the battery. Short Circuit Current of Battery Bank The short circuit current of the battery can be calculated based on the standard “IEC 61660-1, “short circuit currents in DC auxiliary installations in power plants and substations — part: Calculation of short circuit currents” Fe FujiElectric Innovating Energy Technology The following figure shows the curve of the short- circuit current delivered by a stationary lead-acid battery; as it can be seen in the figure, after the time, and this is the time necessary to reach the peak, and the short circuit value decreases to the quasi steady-state short circuit current. te t Figure 12 Curve of Short circuit curent in a battery The short circuit current of battery can be calculated by using the Ohms Law(V=IR). v The short circuit of the battery |, R Where V > Open Circuit Voltage of the battery R > _ Internal Resistance of the battery rrowecion | AY ot + Hf 4 ot HBot 4Rot ome (EES EERE Sas Figure 13 Poe Configuration of Battory bank basod on Operating Voltage © Copyrights Reserved CO ORDINATION OF SNM ian aan Aa Selection of Battery Breaker Capacity and its Trip Unit The selection the battery breaker depends on parameters like Operating Voltage of the Battery Bank: Generally most of the breakers are designed with an voltage of 250V/Pole and based on the operating voltage of the battery bank, the poles has to be connected in, series to achieve the desired voltage level as shown, in fig.13 Nominal Discharge Current of the Battery Bank: This is the current which passes through the breaker under normal conditions of battery discharge Short Circuit Current of the Cattery Bank: Most of the breakers have a thermal and a magnetic trip unit. While the thermal setting is used for overload protection, the magnetic setting is used for short circuit protection. When we discuss about battery protection, the magnetic setting of the breaker is used to disconnect the battery from the circuit when, there is a short circuit. It is important to select the breaker with the right trip unit so that the battery is isolated when there is an fault Note: When an AC breaker is used for a DC applications a derating is applicable on the trip settings of the breaker. Coordination of Battery Breaker with the Battery Fault Current Now that we have selected the right breaker for the battery protection, the most important task which lies ahead is to coordinate the battery breaker with the short circuit current of the battery FC Fuji Electric Innovating Energy Technology As we said earlier, the short circuit current depends ‘on the voltage and the internal resistance of the battery. The internal resistance increases with the ageing of battery under these conditions and the short circuit current decreases. If this short circuit current is less than the pickup value of the magnetic setting of the breaker the principle objective of using the breaker is defeated as the breaker will not trip. Figure 14 Schematic of a DC Gireut To overcome this issue, the magnetic pickup of the breaker trip unit is set at 70% of the nominal short circuit current so that even at low voltage or when the battery reaches the end of life, the battery breaker wil do its job of "protecting the battery * ‘The magnetic setting(!,.) of the breaker is < 70% of |,. of Battery (io: 7 © Copyrights Reserved

You might also like