LOAD LIST -JOB NO.
8081 -IOC TRICHI
DG SET SIZING
SL.NO EQUIP.NO. EQUP.NAME/SERVICE WORKING STAND RATED TOTAL KW
ING BY POWER WORKING
1 P101A/B MS TRANSFER PUMP 1 1 37 37
2 P102A/B SKO TRANSFER PUMP 1 1 55 55
3 P103A/B/C/ HSD TRANSFER PUMP 2 1 75 150
4 P104A/B FURFURAL DOSING PUMP 1 1 0.5 0.5
5 P105A/B/C BLUE DYE DOSING PUMP 3 NIL 0.5 1.5
6 TUBE WELL PUMP 2 NIL 15 30
7 P110A/B SUMP PUMP (FIRE WATER) 1 1 3.7 3.7
8 FIRE WATER JOCKEY PUMP 1 NIL 30 30
9 P106/107/1 PROVER VESSEL PUMP 3 3.7 11.1
11 MOV(TOTAL) 15 28 0.72 10.8
12 P109A/B DRINKING WATER PUMP 1 1 0.75 0.75
12 A.C. SETS 10 2 20
TOTAL KW WORKING LOADS 350.35
A KVA CONSIDERING 0.8PF,0.9 EFFI,0.85 LF 413.6076
OTHER KVA LOADS 0
1 UPS 1 20 20
4 CONTROL SUPPLY 1 2 2
5 SPACE HEATER(TOTAL) 1 2 2
6 POWER DBs 1 5 5
7 FIRE ALARM SYSTEM 1 2 2
8 FIRE PROTECTION 1 4 4
9 D G SET CONTROL SUPPLY 1 1 1
10 BATTERY CHARGER 1 2 2
11 PAGING SYSTEM 2 2 4
B TOTAL KVA 42
CONSIDERING LOAD FACTOR OF .7 TOTAL other KVA 29.4
C LOAD CONSIDERED FOR PIPE LINE DIV. (KVA) 62
D TOTAL KVA (A+B) (ONLY WORKING LOADS CONSIDERED) 443.0076389
CONSIDERING 10% LOAD VARIATION AND
DG SET AGEING FACTOR OF 0.9 , KVA REQUIRED 546.923011
E TOTAL KVA REQUIRED C+D 608.923011
MINIMUM REQUIRED RATING PER SET 608.9/2 304.4615055
STANDARD DG RATING AVAILABLE IN THIS RANGE 320KVA
HENCE SELECTED 640 KVA CAPACITY (TOTAL) WITH TWO DG SETS EACH
WITH 320 KVA RATING
C LIGHTING DG SET
KVA
1 LIGHTING LOADS (BUILDINGS 1 60 60
2 HIGHMAST LIGHT 9 7.2 64.8
TOTAL KVA 124.8
CONSIDERING A L.F OF .9 AND DG EFF. OF .9 SELECTED
D.G SET RATING 125 KVA