Data sheet                                                                                                          6EP3337-8SB00-0AY0
SITOP PSU8200/1AC/24VDC/40A
                                                                        SITOP PSU8200 24 V/40 A stabilized power supply input: 120/230 V AC output: 24
                                                                        V DC/40 A *Ex approval no longer available*
Input
 type of the power supply network                                        1-phase and 2-phase AC
 supply voltage at AC
        ● initial value                                                  Automatic selection; startup starting from Ue ≥ 90/180 V
 supply voltage
        ● 1 at AC rated value                                            120 V
        ● 2 at AC rated value                                            230 V
 input voltage
        ● 1 at AC                                                        85 ... 132 V
        ● 2 at AC                                                        170 ... 264 V
 design of input wide range input                                        No
 operating condition of the mains buffering                              at Vin = 230 V
 buffering time for rated value of the output current in the event of    25 ms
 power failure minimum
 operating condition of the mains buffering                              at Vin = 230 V
 line frequency
        ● 1 rated value                                                  50 Hz
        ● 2 rated value                                                  60 Hz
 line frequency                                                          45 ... 65 Hz
 input current
        ● at rated input voltage 120 V                                   15 A
        ● at rated input voltage 230 V                                   9A
 current limitation of inrush current at 25 °C maximum                   50 A
 I2t value maximum                                                       8 A²·s
 fuse protection type                                                    Yes
        ● in the feeder                                                  Recommended miniature circuit breaker at 1-phase operation: 16 A
                                                                         characteristic C; required at 2-phase operation: circuit breaker 2-pole
                                                                         connected or circuit breaker 3RV2421-4BA10 (120 V) or 3RV2411-1JA10 (230
                                                                         V)
Output
 voltage curve at output                                                 Controlled, isolated DC voltage
 output voltage at DC rated value                                        24 V
 output voltage
        ● at output 1 at DC rated value                                  24 V
 relative overall tolerance of the voltage                               3%
 relative control precision of the output voltage
        ● on slow fluctuation of input voltage                           0.1 %
        ● on slow fluctuation of ohm loading                             0.1 %
 residual ripple
        ● maximum                                                        100 mV
        ● typical                                                        50 mV
6EP33378SB000AY0                                                                                                   Subject to change without notice
                                                                        9/22/2023
Page 1/4                                                                                                                      © Copyright Siemens
 voltage peak
     ● maximum                                                       240 mV
     ● typical                                                       220 mV
 adjustable output voltage                                           24 ... 28 V
 product function output voltage adjustable                          Yes
 type of output voltage setting                                      via potentiometer; max. 960 W
 display version for normal operation                                Green LED for 24 V OK; LED yellow for overload; LED red for short-circuit or
                                                                     latching shutdown
 type of signal at output                                            Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
 behavior of the output voltage when switching on                    Overshoot of Vout approx. 3 %
 response delay maximum                                              1.5 s
 voltage increase time of the output voltage
     ● typical                                                       30 ms
 output current
     ● rated value                                                   40 A
     ● rated range                                                   0 ... 40 A; +60 ... +70 °C: Derating 3%/K
 supplied active power typical                                       960 W
 short-term overload current
     ● on short-circuiting during the start-up typical               120 A
     ● at short-circuit during operation typical                     120 A
 duration of overloading capability for excess current
     ● on short-circuiting during the start-up                       25 ms
     ● at short-circuit during operation                             25 ms
 constant overload current
     ● on short-circuiting during the start-up typical               60 A
 product feature
     ● bridging of equipment                                         Yes; switchable characteristic
 number of parallel-switched equipment resources for increasing      2
 the power
Efficiency
 efficiency in percent                                               92 %
 power loss [W]
     ● at rated output voltage for rated value of the output         82 W
     current typical
     ● during no-load operation maximum                              6.8 W
Closed-loop control
 relative control precision of the output voltage with rapid         1%
 fluctuation of the input voltage by +/- 15% typical
 relative control precision of the output voltage load step of       1.9 %
 resistive load 50/100/50 % typical
 setting time
     ● load step 50 to 100% typical                                  2 ms
     ● load step 100 to 50% typical                                  2 ms
 relative control precision of the output voltage at load step of    3.8 %
 resistive load 10/90/10 % typical
 setting time
     ● load step 10 to 90% typical                                   1 ms
     ● load step 90 to 10% typical                                   1 ms
     ● maximum                                                       1 ms
Protection and monitoring
 design of the overvoltage protection                                < 32 V
     ● typical                                                       41 A
 property of the output short-circuit proof                          Yes
 design of short-circuit protection                                  Alternatively, constant current characteristic approx. 41 A or latching shutdown
 enduring short circuit current RMS value
     ● typical                                                       41 A
 overcurrent overload capability in normal operation                 250% Iout rated up to 25 ms, 150% Iout rated up to 5 s/min
 display version for overload and short circuit                      LED yellow for "overload", LED red for "latching shutdown" or "short-circuit"
Safety
 galvanic isolation between input and output                         Yes
 galvanic isolation                                                  Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
 operating resource protection class                                 Class I
6EP33378SB000AY0                                                                                                 Subject to change without notice
                                                                    9/22/2023
Page 2/4                                                                                                                    © Copyright Siemens
 leakage current
      ● maximum                                              0.1 mA
      ● typical                                              0.1 mA
 protection class IP                                         IP20
Approvals
 certificate of suitability
      ● CE marking                                           Yes
      ● UL approval                                          Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
                                                             (CSA C22.2 No. 60950-1, UL 60950-1)
      ● CSA approval                                         Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
                                                             (CSA C22.2 No. 60950-1, UL 60950-1)
      ● cCSAus, Class 1, Division 2                          No
      ● ATEX                                                 No
 certificate of suitability
      ● IECEx                                                No
      ● NEC Class 2                                          No
      ● ULhazloc approval                                    No
      ● FM registration                                      No
 type of certification CB-certificate                        Yes
 certificate of suitability
      ● EAC approval                                         Yes
      ● Regulatory Compliance Mark (RCM)                     Yes
 certificate of suitability shipbuilding approval            Yes
 shipbuilding approval                                       ABS, DNV GL
 Marine classification association
      ● American Bureau of Shipping Europe Ltd. (ABS)        Yes
      ● French marine classification society (BV)            No
      ● DNV GL                                               Yes
      ● Lloyds Register of Shipping (LRS)                    No
      ● Nippon Kaiji Kyokai (NK)                             No
EMC
 standard
      ● for emitted interference                             EN 55022 Class B
      ● for mains harmonics limitation                       -
      ● for interference immunity                            EN 61000-6-2
environmental conditions
 ambient temperature
      ● during operation                                     -25 ... +70 °C; with natural convection
      ● during transport                                     -40 ... +85 °C
      ● during storage                                       -40 ... +85 °C
 environmental category according to IEC 60721               Climate class 3K3, 5 … 95% no condensation
Mechanics
 type of electrical connection                               screw-type terminals
      ● at input                                             L, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded
      ● at output                                            +, -: 2 screw terminals each for 0.5 ... 10 mm²
      ● for auxiliary contacts                               13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²
 width of the enclosure                                      145 mm
 height of the enclosure                                     145 mm
 depth of the enclosure                                      150 mm
 required spacing
      ● top                                                  40 mm
      ● bottom                                               40 mm
      ● left                                                 0 mm
      ● right                                                0 mm
 net weight                                                  3.1 kg
 product feature of the enclosure housing can be lined up    Yes
 fastening method                                            Snaps onto DIN rail EN 60715 35x15
 electrical accessories                                      Buffer module, redundancy module
 mechanical accessories                                      Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
 MTBF at 40 °C                                               838 156 h
 other information                                           Specifications at rated input voltage and ambient temperature +25 °C (unless
6EP33378SB000AY0                                                                                        Subject to change without notice
                                                            9/22/2023
Page 3/4                                                                                                           © Copyright Siemens
                    otherwise specified)
6EP33378SB000AY0                           Subject to change without notice
                   9/22/2023
Page 4/4                                              © Copyright Siemens