2,400 V to 14,400 V BIL 75 kV to 110 kV                                                Application
Outdoor Voltage                                                            Designed for outdoor service; suitable for operating
                                                                                               meters, instruments, relays, and control devices.
                       JVW-4/JVW-5                                                             Thermal Rating (Volt-Amperes)
                                            60 Hz                                              55°C Rise above 30°C Ambient ............................. 1500
                                 When choosing your GE Instrument Trans-                       ANSI Meter Accuracy Classification, 60 Hz
                                 former, don't forget to explore the benefits of
                                 using GE's 0.15 accuracy class AccuBute line.
                                                                                               Operated at rated voltage
        AVAILABLE                See page 2.10.                                                  W, X, M, Y, Z; all models ........................................ 0.3
                                                                                                 ZZ; all models ......................................................... 1.2
                                                                                               Operated at 58% of rated voltage ➁
                                                                                                 W, X, M, Y; all models ............................................ 0.3
                                                                                                 Z; all models ........................................................... 1.2
                                                                                               Burden impedance as at rated voltage, but operated at
                                                                                               58% of rated voltage ➂
                                                                                                 W', X' M', Y', Z'; all models .................................... 0.3
                                                                                               Weight - Shipping/Net
                                                                                               (approximate, in pounds)
                                                                                               Transformer ...................................................... 120/105
                                                                                               Reference Drawings
                                                                                               JVW-4
                                                                                               Accuracy Curve at
                                                                                               120 Secondary Volts, 60 Hz ....................... 9689241659
                                                                                               Excitation Curves:
                                                                                                 60:1 & 70:1 ............................................... 9689241591
                                                                                                 100:1 & 120:1 ........................................... 9689241629
                                                                                               Outline Drawing; Two-Bushing
                                                                                               Transformer ...................................................... 9932529
                                                                                               Wiring Diagram .................... refer to page 42, figure 5
                             JVW-4 -5, two-bushing model
      JVW-4/JVW-5 DATA TABLE
                     Line-To-Line                                                                                             Catalog Number
                    Circuit Voltage                                     Transformer                  JVW-4                                    JVW-5
                  For Permissible                                         Rating ➀                  BIL 75 kV                               BIL 110 kV
                 Primary Connection                                  Primary                       Two-Bushing                 Single-Bushing        Two-Bushing
          ∆         Y        Y Only                 GY Only ➃        Voltage     Ratio                Model                        Model                Model
        2,400     2,400       4,160                     ---           2,400       20:1             764X030011                         ---                 ---
        4,200     4,200       7,280                     ---           4,200       35:1             764X030012                         ---                 ---
        4,800     4,800       8,320                     ---           4,800       40:1             764X030013                         ---                 ---
        7,200     7,200          ---                    ---           7,200       60:1             764X030014                         ---                 ---
          ---       ---          ---                 7200 ➄           7,200       60:1                  ---                     765X030051            765X030042
          ---       ---          ---                 8400 ➅           8,400       70:1                  ---                     765X030052            765X030044
        12,000   12,000      12,000                     ---          12,000      100:1                  ---                           ---             765X030045
        14,400   14,400      14,400                     ---          14,400      120:1                  ---                           ---             765X030046
      Notes:
      ➀ For continuous operation, the transformer-rated primary voltage should not be              determining the accuracy classification under such conditions, the Volt-Ampere
        exceeded by more than 10%. Under emergency conditions, over-voltage must be                rating of the burden is maintained constant, regardless of the transformer
        limited to 1.25 times the transformer primary-voltage rating for two-bushing models,       secondary voltage.
        and 1.40 times the rating for single-bushing models.                                   ➂   The prime symbol (‘) is used to signify that these burdens do not correspond to
      ➁ Applies to transformers connected Y-Y on a circuit in which the line-to-line voltage       standard ANSI definitions.
        is the same as the transformer-rated primary voltage. In each case, the transformer    ➃   Single-bushing design with removable grounding strap.
        is operated with reduced voltage and reduced excitation (58% of normal). In            ➄   12,470 in Y configuration.
                                                                                               ➅   14,560 in Y configuration.
                                                                                                                                                 Data subject to change without notice.
2-8            GE Meter 130 Main St., Somersworth, NH 03878 USA & Canada: (800) 626-2004 Fax: (518) 869-2828; GE Worldwide: (518) 869-5555
                                                                                                       Outdoor – Voltage – JVW-4/JVW-5
JVW-5                                                                            Ground Terminal
Accuracy Curve at                                                                Please refer to General Product Information, item 4.23.
120 Secondary Volts, 60 Hz ....................... 9689241659
Excitation Curves:                                                               Conduit Box
  60:1 & 70:1 ............................................... 9689241591         Please refer to General Product Information, item 12.1.
  100:1 & 120:1 ........................................... 9689241629
OutlineDrawings:                                                                 Polarity
  Two-Bushing Model ...................................... 9932529               Please refer to General Product Information, item 7.2.
  Single-Bushing Model ................................... 9932530
Wiring Diagram .................... refer to page 42, figure 5                   Baseplate and Mounting
                                                                                 Please refer to General Product Information, items 5.3,
Accessories ........................... Catalog Number                           5.15, and the Applications Information Section of this
Mounting Hardware                                                                volume.
  “L” Mounting Brackets ........................... 8944634002
  Channel Bracket ..................................... 5466227001               Nameplate
  Suspension Hooks ................................... 8944630001                Please refer to General Product Information, item 6.4.
Secondary Conduit Box ............................. 9689897001
                                                                                 Rating Identification
Construction and Insulation                                                      Please refer to General Product Information, item 13.1.
Please refer to General Product Information, item 1.4.
                                                                                 Maintenance
Core and Coils                                                                   Please refer to General Product Information, item 10.1
Please refer to General Product Information, item 3.8.                           and pages 24-27.
                                                                                 Note:
Primary                                                                          1. Voltage transformers of this type are available for use in 50 Hz appli-
Terminals                                                                          cations in many ratings. However, Industry Standard IEEE 57.13 to which
Please refer to General Product Information, item 4.6.                             we test transformers does not apply at 50 Hz. Customers who order
                                                                                   voltage transformers for 50 Hz application should provide an accuracy
Secondary                                                                          specification including Burden VA and Power Factor. If an accuracy
Terminals                                                                          specification is not made available, the transformer(s) will be tested at
Please refer to General Product Information, item 4.18.                            60 Hz with test burdens as defined in IEEE 57.13 for 60 Hz application.
                                                                                        14.25
                                              Inches                                   (36.20)
                                                                                                       13.13
                                               (CM)                                                   (33.35)
                                                                                         12.25
                                                                                        (31.12)
                                                                9.94      8.63
                                                              (25.25) (21.92)
                                                                     9.50
                                                                   (24.13)
                                                                  0.44 (1.12) Dia.
                                                                  (8 holes)
                                                                                                     10.00
                                                    13.19                                           (25.40)
                                                   (33.50)                                   11.00
                                                                                            (27.94)
                                                                                  H1
                                                                         16.88                   12000
                                                                        (42.88)
                                                                                             X1
                                                                                                   GRD
                                                     JVW-4/JVW-5 mechanical dimensions
                                                                                                                           Data subject to change without notice.
        GE Meter 130 Main St., Somersworth, NH 03878 USA & Canada: (800) 626-2004 Fax: (518) 869-2828; GE Worldwide: (518) 869-5555                                 2-9