DI-9101E Intelligent Combination
Heat Photoelectric Smoke Detector
Features
Strong environmental adaptability due to drift
compensation.
Self-diagnostic.
0832-CPR-F0339
Reed switch testing. GST-0507-01
Removable innovative sensing chamber, easy for 14
maintenance.
Dirty chamber checking.
Fire LED allows 360°viewing
Remote indicator output available.
548q/04
Polling LED can be set to close.
2 levels smoke sensitivities programmable, level 1 Fig. 3 shows the installation of the detector.
complies with EN 54-7. Heat part complies with EN
54-5.
Electrical Box
Description
DI-9101E Intelligent Combination Heat Photoelectric Conduit
Smoke Detector integrates photoelectric detection and
fixed temperature and rate of rise detection technology
by combining smoke sensor and semi-conductor heat Base
sensor in mechanism and circuitry structure. Just 51.5mm
Detector
because of the combination of smoke detection and heat
detection, it not only overcomes the disadvantage that
detectors using common infrared scattering technology Fig. 3
are insensitive to black smoke with small particles, but
Application
also can pick up fire with obvious rise of temperature
such as alcohol flame, thus extending its application The detector can be addressed in field by using P-9910B
programmer. Please refer to P-9910B Hand Held
range. Programmer Installation and Operation Manual for
Connection and Cabling details.
In power-on state, input unlocking password and press
Fig. 1 shows the detector bottom and Fig. 2 DB-01 base. Clear to unlock. Press Function, then press “3”, the
A
screen shows “-” at the last digit.
C
Input corresponding sensitivity or parameter and press
B
Program, the screen will show a “P”, the corresponding
sensitivity or parameter is programmed. Press Clear to
clear the "P". Input locking password and press Clear to
return.
Rate of rise and level 1 is defaulted.
Parameters set using programmer
Input Parameter Smoke Heat Part Polling LED
of a Detector Sensitivity
1 1 Rate of Rise Normal
Fig. 1 Fig. 2 2 2 Normal
Rate of Rise
There are four terminals with numbers on the base. 129 1 Close
Rate of Rise
1&3: Loop connection (polarity-insensitive) 130 2 Close
2: Positive terminal of remote indicator Rate of Rise
4: Negative terminal of remote indicator Read Sensitivity Level: in power-on state, pressing Test,
Recommended Cabling the screen displays address of the detector. Pressing
1.0mm2 or above fire cable is recommended, laid “Up”, display sensitivity level, device type and initial
through metal or flame-retardant conduit, but subject to sensitivity in turns.
local codes. Different color cables for remote indicator Testing
are used to avoid wiring mistake. Before testing, please ensure that the detector has
Installation been installed correctly and powered up. After 10
seconds, testing begins.
A fixed installation direction is ensured by the location 1) The detector must be tested after installation and
elements on the detector and the base. Fix the base with periodical maintenance.
two tapping screws, and then align mark A on the 2) Testing method
detector with B on the base, rotate the detector to align a) Reed Switch Testing
mark A with mark C (Refer to Fig. 1 and 2 for the position Magnetic test zone is shown in Fig. 4. Put the
of the marks), the detector will be fitted to the base. magnet of commission tool close to that of the
detector and hold on for a few seconds until the
detector generates alarm.
30309533 Issue 1.04
Downloaded from www.Manualslib.com manuals search engine
Test Zone
The detector should be tested after re-installed to
ensure normal operation.
Fire simulation test should be done to the detector at
least every 6 months.
Specification
Operating Voltage loop 24V(16V~28V)
Standby Current ≤0.8mA
Alarm Current ≤1.8mA (without remote indicator)
Fig. 4
≤ 3.8mA (with remote indicator)
b) Smoke test
Fire LED Red. Flashes in polling, and
Taking a smoldering cotton rope close to the
illuminates in alarm
detector, blow the smoke into the detector until the
Polarized output. Directly connect
detector generates alarm.
to remote indicator (built in 10k
c) Temperature test Remote Indicator
Approach a heater (such as a hair drier) to the resistor in series, output current is
Output
thermistor of the detector until it alarms. 2mA); Flash in alarming and do
not illuminate in normal.
3) After testing, reset the detector. Notify the proper
authorities that the system is back to normal Programming Method Electronically programming
operation. Code Range one address within 1~242
If a detector fails in testing, clean it by the steps in
Wiring Non-polarized 2-core for loop.
Maintenance, and retest it. If it still fails, return it for
Polarized 2-core for remote
repair.
indicator.
Maintenance The sensitivity can be set by
Setting of sensitivity
The detector should be installed just before and range
programmer with two levels: Level
commissioning and kept well before installation, 1(default), level 2.
taken corresponding measures for dust-proof, Detector Class A2R
damp-proof and corrosion-proof. Action Temperature 62℃
The dust-proof cover should not be removed until Environment
the project is plunged into usage. Otherwise it may -10℃~50℃
Temperature
not report alarm properly. Relative Humidity ≤95%, non condensing
Clean the detectors regularly, at least once a year Material of Enclosure ABS
to ensure normal operation of the system.
Ingress Protection IP2X
If unwanted alarms are often found of the detector Rating
on site, the sensing chamber should be cleaned.
Dimensions Diameter: 100mm
Power must be removed from the detector before
Height: 54.5mm (with base)
cleaning.
Mounting Hole 45mm~75mm
Steps for chamber cleaning:
Distance
a) Open the top cover of detector, and draw out
the sensing chamber by slightly lifting its two Weight About 110g
sides using a straight screwdriver, as shown in Accessories and Tools
Fig. 5. Model Name Remark
P-9910B Hand held programmer Order separately
DB-01 Base Order separately
T-MT Commission Tool Order separately
WEEE Information
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper
Fig. 5 recycling, return this product to your local supplier
b) Clean the internal of the chamber by alcohol upon the purchase of equivalent new equipment, or
cotton swab with tweezers or using clean water dispose of it at designated collection points.
and brush. Make sure not to leave any fiber in Limited Warranty
the chamber.
GST warrants that the product will be free of charge for repairing
c) Put back the chamber and the top cover. or replacing from defects in design, materials and workmanship
Before cleaning, notify the proper authorities that during the warranty period. This warranty does not cover any
the system is under maintenance and will product that is found to have been improperly installed or used
temporarily be out of service. Disable the automatic in any way not in accordance with the instructions supplied with
controls relating to the zone or system under the product. Anybody, including the agents, distributors or
maintenance to avoid unwanted actions. employees, is not in the position to amend the contents of this
warranty. Please contact your local distributor for products not
covered by this warranty.
This document is subject to change without notice. Please contact GST for more information or questions.