NMR 601 Submittal (27312)

The document provides equipment schedules and descriptions for various air conditioning equipment for a project including packaged air conditioning units, precision air conditioning units, and cassette type split units. It includes model numbers, cooling capacities, supply air flow rates, electrical details, and optional accessories for the different equipment.

Uploaded by

prabhugandi6101
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3K views286 pages

NMR 601 Submittal (27312)

The document provides equipment schedules and descriptions for various air conditioning equipment for a project including packaged air conditioning units, precision air conditioning units, and cassette type split units. It includes model numbers, cooling capacities, supply air flow rates, electrical details, and optional accessories for the different equipment.

Uploaded by

prabhugandi6101
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 286

NMR 601

Submittal
(FORM 7930)

FOR

UPGRADE SECURITY FACILITIES EAST/ WEST


PIPELINE PUMP-STATION-4

CUSTOMER: L&T.
END USER: M/s ARAMCO

Page 1 of 286
HVAC Euipment

Page 2 of 286
NMR 601.1
Equipment Schedule

Page 3 of 286
UNIT SCHEDULE

Total Sensible Total


Supply Ambient EAT LAT
Cooling Cooling ESP Power
Sr. No. Tag# Model Air temperature (DB/WB) (DB/WB) Qty
Capacity Capacity (PA) Input
(LPS) (°C) (°C) (°C)
(kW) (kW) (KW)

PACU-1,2 (SEC
1 PTX022-FA3 66.88 47.89 2,550.00 650 38.2 55.6 31.20/21.67 15.43/14.60 4
SUPPORT TYPE 1)

PACU-1,2 (SEC
2 PTX036-FA2 93.64 65.89 3,020.00 650 52.9 55.6 31.60/21.67 13.53/12.94 2
SUPPORT TYPE 2)

3 PACU1A&2A (PIC BLDG) PY075 16.04 16.18 850.00 500 9.5 55.6 29.70/18.10 13.64/12.22 6

4 PACU-01 (GENERATOR) PV048 11.11 10.85 660.70 62 6.1 54.0 24.90/16.00 11.26/10.54 3

5 CRAC-USS1-00 DPM024-ZRC024(Wall) 5.97 5.75 566.00 - 3.2 52.0 23.89/16.98 16.15/13.98 6

6 CRAC-FS-001 DPM048-ZRC048(Wall) 12.22 11.88 1,038.00 - 6.2 52.0 23.89/16.98 15.05/13.58 6

Design Data:

2. Cool only (No heater).

3. Power supply: 380V-3Ph-60Hz.

Page 4 of 286
CRAC UNIT SCHEDULE

Total
Cooling Supply Air ESP Electric Heater Humidifier Qty /
Sr. No. Ref/Tag Model
Capacity LPS (PA) Cap (KW/Stg (KG/HR) Set
(KW)

PS1- Existing SSB (Indoor) DPM BTD EDA 26.1 1604 50 9.0/2 5 2

1 22.3
PS1- Existing SSB
ZRX043 7380.78 - - - 2
(Outdoor)

Design Data:
1. Ambient Air Temp. : 46.00˚C.
2. Power supply: 380V-3Ph-60Hz.

Page 5 of 286
CASSETTE-TYPE SPLIT UNITS SCHEDULE

Supply Nominal
Heat
Air Flow Cooling
SI TAG UNIT Pump QTY
H/L/M Capacity
Cap. (KW)
(CFM) (TR)
SIZ48CHAXCD/C
1 FCU-01 2000/1800/1600 3.35 1.6 6
KZ48CDGHIKD

SIZ48CHAXCD/C
2 FCU-02 2000/1800/1600 3.35 1.6 6
KZ48CDGHIKD

1.POWER SUPPLY-230V-1PH-60Htz

Page 6 of 286
NMR 601.2
Equipment Description

Page 7 of 286
PROJECT NAME : UPGRADE SECURITY FACILITIES EAST/ WEST PIPELINE PUMP-STATION-4
EQUIPMENT : PTX-Series
TYPE : MODULAR PACKAGED AIR CONDITIONING UNIT
MANUFACTURER: ZAMIL AIR CONDITIONERS

EQUIPMENT DESCRIPTION

PTX-series:
Modular Packaged Air Conditioners. outdoor application assembled in a weatherproof enclosure mounted
on a heavy gauge galvanized steel sheet press formed base.

Unit consists of:


- Scroll compressors (R-410a).
- Condenser coils with Resistic coating made of Cu tubes/Al fins with 12 FPI.
- Evaporator coils with Resistic coating made of Cu tubes/Al fins.
- Propeller condenser fans driven by TEAO type motors.
- 2.0-inch-thick Al washable pre-filter and bag filter.
- Backward curved blade evaporator blower driven by TEFC type motor with belt guard.
- Electronic Thermostat
- Microprocessor based electronic control board and other standard controls.

Power supply: 380V/3Ph/60Hz

Unit shall be with the following accessories/options:

- Stainless Steel Name plate


- 316 Stainless Steel drain pan
- Pump down solenoid valve
- Replaceable filter drier and shut off valve
- Pressure gauge
- VFC
- Compressor Circuit Breaker
- Earth lugs
- HV terminal
- 10% spare terminal
- Door stopper on ACCU control panel
- Resistec coated hinges.
- Double skin
- Fan cycling switch
- Hot Gas bypass valve
- Anti ice thermostat
Page 8 of 286
PROJECT NAME : UPGRADE SECURITY FACILITIES EAST/ WEST PIPELINE PUMP-STATION-4
EQUIPMENT : PY-Series
TYPE : PACKAGED AIR CONDITIONING UNIT
MANUFACTURER: ZAMIL AIR CONDITIONERS

EQUIPMENT DESCRIPTION
PY-series: Packaged Air Condition Units, High Efficiency,
consisting of:
- Hermetic scroll compressor.
- Refrigerant R-410a.
- Inner skin.
- Condenser propeller fan driven by TEFC type motor.
- 2-inch Al washable pre-filter.
- Condenser coils with Resistic coating made of Cu tubes/Al fins with 12 FPI.
- Evaporator coils with Resistic coating made of Cu tubes/Al fins.
- Backward curved blade blower driven by ODP type motor.
- Electronic thermostat.

Power Supply: 380V/3Ph/60Hz

Unit shall be with the following accessories/options:


- UL listed
- AHRI Certified
- Fan cycling switch.
- Volt free contact.
- Compressor circuit breaker.
- Pump down solenoid valve.
- Replaceable core filter dryer with shut off valves and sight glass.
- Metallic coil guard.
- Earth lugs.
- External overload relay for each condenser fan.
- SS name plate.
- SS 316 drain pan.
- 10% spare terminal, and HV terminal safety cover.
- Coil bend resisTec coating - evaporator.

Page 9 of 286
PROJECT NAME : UPGRADE SECURITY FACILITIES EAST/ WEST PIPELINE PUMP-STATION-4
EQUIPMENT : PTX-Series
TYPE : MODULAR PACKAGED AIR CONDITIONING UNIT
MANUFACTURER: ZAMIL AIR CONDITIONERS

EQUIPMENT DESCRIPTION
PV-series: Vertical Packaged Air Condition Units

consisting of:
- Hermetic scroll compressor.
- Refrigerant R-410a.
- Evaporator and condenser coils made of Cu tubes/AL fins with ResisTec coating.
- Forward curved blade blower driven by ODP type motor.
- Condenser propeller fan with side air discharge driven by TEAO type motors.
- 2-inch-thick Aluminum filter and other control features
- Power supply: 380V-3Ph-60Hz.
- Cooling only.

Accessories and options included are:


- AHRI UL listed.
- Differential pressure switch (DPS)
- FA manual damper.
- Under voltage monitor (UVM)
- Shelter application communication
- Volt free contact
- SS name plate
- Grille for the supply air discharge return air intake

Page 10 of 286
EQUIPMENT DESCRIPTION

Precision A/C units, consisting of Air Handling Unit with matching Air-Cooled Condensing Unit.
The indoor AHU, DPM-series, wall mounted type consists of:

- DX cooling coils made of Cu tubes/Al fins


- Electronic commutated backward fan (EC)
- 1 inch Aluminum washable filter
- Electric heater
- Humidifier

Options and accessories:

- Volt free contact (VFC)


- Smoke detector sensor
- Fire detector sensor
- Water detector sensor
- Condensate pump (Field installed)
- BACNET compatibility
- SS name plate

The outdoor ACCU, ZRC-series, consist of:


- Single hermetic scroll compressor
- Compressor circuit breaker
- Condenser coil Cu tubes/Al fins
- Condenser propeller fan(s) direct driven by TEAO type motor(s) and other controls

Options and accessories:

- Compressor suction and discharge service valve


- Unit full guard
- External overload for condenser fan
- External overload for Compressor
- Pressure gauges
- SS name plate

Page 11 of 286
NMR 601.3
Technical Data

Page 12 of 286
PacZAC

Packaged Unit 1.1.136.0

Customer: Done By: / Engineering


General Info

Project: Upgrade Security Facilities East/ West pipelin Location:

Ref/Tag: PACU01,02 2550 Quantity: 1

Revision: Rev 0 Date: Wednesday, March 1, 2023

Required Capacity Required Entering Required Outside Required Air


Temperatures Conditions Conditions
External
Total Sensible Dry Bulb Wet Bulb Ambient Altitude Air Flow Static Pressure

kW kW °C °C °C ft LPS Pa
Input Conditions

66.81 48.30 31.20 21.67 55.60 0.00 2,550.00 650.00

Required Power Supply Auxiliary Required Options

Voltage Phases Frequency Pre Filter Final Filter Blower Type Heater

Volts Phase Hertz 2'' 15'' kW


380V (4 Wire) 3 60Hz Aluminum Bag Filter Backward Fan Not Required

Selected Unit Model


PTX022-FA3

Performance @ 55.6 °C Ambient Physical Data


Total Cooling Capacity 66.88 kW Fan Data Condenser Evaporator Units
Total Sensible Capacity 47.89 kW
Total Power Input 38.2 kW Size 800 400
Quantity 2 1
Air Flow 10,546.1 2,550.0 LPS
Psychrometric Data Fan Speed 900|1100 2,180 RPM
Entering (On Coil) Leaving (Off Coil) Coil Data Condenser Evaporator Units

Coil Face Area 48.9 13.3 sqft


Dry Bulb 31.20 °C Dry Bulb 15.43 °C
Output Performance

Coil Tube Diameter 3/8 3/8 in


Wet Bulb 21.67 °C Wet Bulb 14.60 °C
Number of Rows 3 6
Fins Per Inch 12 12 FPI
Compressor Data Fins Material Al Al

Type Hermetic Scroll


Quantity 2 Electric Heater Filter Data
Capacity No Heater 24X20 Inch
Electrical Data FLA Amps 4 Each
Condenser Evaporator Units

380/400-3-60Hz 380/400-3-60Hz
Refrigerant
Power Supply (4 wire) (4 wire)
Refrigerant R410A
Compressor RLA (Each) 26.4/26.4 Amps
Charge Per System 479 Oz
Compressor LRA (Each) 145/145 Amps
Fan Motor (Each) 2.3 5.5 kW*
Fan Motor Speed 900|1100 3,450 RPM General Data
Fan Motor FLA* (Each) 4.1 11.4 Amps
Unit MCA 79.0 Amps Drain Connection Refer DWG
Unit MOCP 100.0 Amps External Static Pressure 650.00 Pa
FLA tolerance ± 5%
Products Certifications

1 of 1
Page 13 of 286
PacZAC

Packaged Unit 1.1.136.0

Customer: Done By: / Engineering


General Info

Project: Upgrade Security Facilities East/ West pipeli Location:

Ref/Tag: PACU1,2 3020 Quantity: 1

Revision: Rev 0 Date: Wednesday, March 1, 2023

Required Capacity Required Entering Required Outside Required Air


Temperatures Conditions Conditions
External
Total Sensible Dry Bulb Wet Bulb Ambient Altitude Air Flow Static Pressure

kW kW °C °C °C ft LPS Pa
Input Conditions

93.45 65.29 31.60 21.67 55.60 0.00 3,020.00 650.00

Required Power Supply Auxiliary Required Options

Voltage Phases Frequency Pre Filter Final Filter Blower Type Heater

Volts Phase Hertz 2'' 15'' kW


380V (4 Wire) 3 60Hz Synthetic Bag Filter Backward Fan Not Required

Selected Unit Model


PTX036-FA2

Performance @ 55.6 °C Ambient Physical Data


Total Cooling Capacity 93.64 kW Fan Data Condenser Evaporator Units
Total Sensible Capacity 65.89 kW
Total Power Input 52.9 kW Size 800|760 400
Quantity 4 1
Air Flow 15,876.3 3,020.0 LPS
Psychrometric Data Fan Speed 820|1100 2,360 RPM
Entering (On Coil) Leaving (Off Coil) Coil Data Condenser Evaporator Units

Coil Face Area 97.8 16.7 sqft


Dry Bulb 31.60 °C Dry Bulb 13.53 °C
Output Performance

Coil Tube Diameter 3/8 3/8 in


Wet Bulb 21.67 °C Wet Bulb 12.94 °C
Number of Rows 3 6
Fins Per Inch 12 12 FPI
Compressor Data Fins Material Al Al

Type Hermetic Scroll


Quantity 4 Electric Heater Filter Data
Capacity No Heater 24x20 / 20x20 Inch
Electrical Data FLA Amps 2/4 Each
Condenser Evaporator Units

380/400-3-60Hz 380/400-3-60Hz
Refrigerant
Power Supply (4 wire) (4 wire)
Refrigerant R410A
Compressor RLA (Each) 17.2/17.2 Amps
Charge Per System 482 Oz
Compressor LRA (Each) 123/123 Amps
Fan Motor (Each) 1.15 7.5 kW*
Fan Motor Speed 820|1100 3,450 RPM General Data
Fan Motor FLA* (Each) 3.0 14.7 Amps
Unit MCA 99.8 Amps Drain Connection Refer DWG
Unit MOCP 110.0 Amps External Static Pressure 650.00 Pa
FLA tolerance ± 5%
Products Certifications

1 of 1
Page 14 of 286
PacZAC

Packaged Unit 1.1.120.0

Customer: Done By: KHALID


General Info

Project: Upgrade Security Facilities East/ West pipeline


Location:
pump-station-4

Ref/Tag: PACU 1 Quantity: 1

Revision: Rev 0 Date: 20 ‫ر و أ‬,

Required Capacity Required Entering Required Outside Required Air


Temperatures Conditions Conditions
External
Total Sensible Dry Bulb Wet Bulb Ambient Altitude Air Flow Static Pressure

kW kW °C °C °C ft LPS Pa
Input Conditions

16.06 16.06 29.70 18.10 55.60 0.00 850.00 500.00

Required Power Supply Auxiliary Required Options

Voltage Phases Frequency Pre Filter Final Filter Blower Type Heater

Volts Phase Hertz 2'' 15'' kW


380V (4 Wire) 3 60Hz Aluminum Bag Filter Backward Fan Not Required

Selected Unit Model


PY075

Performance @ 55.6 °C Ambient Physical Data


Total Cooling Capacity 16.04 kW Fan Data Condenser Evaporator Units
Total Sensible Capacity 16.18 kW
Total Power Input 9.5 kW Size 26'' 315
Quantity 1 1
Air Flow 2,967.8 850.0 LPS
Psychrometric Data Fan Speed 1130 2,418 RPM
Entering (On Coil) Leaving (Off Coil) Coil Data Condenser Evaporator Units

Coil Face Area 16.3 9.0 sqft


Dry Bulb 29.70 °C Dry Bulb 13.64 °C
Output Performance

Coil Tube Diameter 3/8 3/8 in


Wet Bulb 18.10 °C Wet Bulb 12.22 °C
Number of Rows 3 4
Fins Per Inch 12 14 FPI
Compressor Data Fins Material Al Al

Type Hermetic Scroll


Quantity 1 Electric Heater Filter Data
Capacity No Heater 16.5x18-3/8 Inch
Electrical Data FLA Amps 4 Each
Condenser Evaporator Units

380/400-3-60Hz 380/400-3-60Hz
Refrigerant
Power Supply (4 wire) (4 wire)
Refrigerant R410A
Compressor RLA (Each) 11.4 Amps
Charge Per System Oz
Compressor LRA (Each) 83 Amps
Fan Motor (Each) 3/4HP 2 HP*
Fan Motor Speed 1130 3,450 RPM General Data
Fan Motor FLA* (Each) 1.6 3.1 Amps
Unit MCA 19.0 Amps Drain Connection 3/4''
Unit MOCP 30.0 Amps External Static Pressure 500 Pa
FLA tolerance ± 5%
Products Certifications

1 of 1
Page 15 of 286
PacZAC

Packaged Unit 1.1.120.0

Customer: Done By: KHALID


General Info

Project: Upgrade Security Facilities East/ West pipeline


Location:
pump-station-4

Ref/Tag: PACU 3 Quantity: 1

Revision: Rev 0 Date: 20 ‫ر و أ‬,

Required Capacity Required Entering Required Outside Required Air


Temperatures Conditions Conditions
External
Total Sensible Dry Bulb Wet Bulb Ambient Altitude Air Flow Static Pressure

kW kW °C °C °C ft LPS Pa
Input Conditions

10.81 10.81 24.90 14.40 55.60 0.00 661.00 62.00

Required Power Supply Auxiliary Required Options

Blower
Voltage Phases Frequency Pre Filter Motor Speed Heater

Volts Phase Hertz 2'' kW


380V (4 Wire) 3 60Hz Aluminum HIGH Not Required

Selected Unit Model


PV048

Performance @ 54 °C Ambient Physical Data


Total Cooling Capacity 11.11 kW Fan Data Condenser Evaporator Units
Total Sensible Capacity 10.85 kW
Total Power Input 6.1 kW Size 24'' 9x9
Quantity 1 1
Air Flow 1,172.5 660.7 LPS
Psychrometric Data Fan Speed 1100 1,200 RPM
Entering (On Coil) Leaving (Off Coil) Coil Data Condenser Evaporator Units

Coil Face Area 8.0 5.0 sqft


Dry Bulb 24.90 °C Dry Bulb 11.26 °C
Output Performance

Coil Tube Diameter 3/8 3/8 in


Wet Bulb 16.00 °C Wet Bulb 10.54 °C
Number of Rows 4 4
Fins Per Inch 14 14 FPI
Compressor Data Fins Material Al Al

Type Hermetic Scroll


Quantity 1 Electric Heater Filter Data
Capacity No Heater 36x22x2 Inch
Electrical Data FLA Amps 1 Each
Condenser Evaporator Units

380/400-3-60Hz 380/400-3-60Hz
Refrigerant
Power Supply (4 wire) (4 wire)
Refrigerant R410A
Compressor RLA (Each) 9.9 Amps
Charge Per System 195 Oz
Compressor LRA (Each) 64 Amps
Fan Motor (Each) 1/3HP 0.5 HP
Fan Motor Speed 1100 1,200 RPM General Data
Fan Motor FLA* (Each) 2.5 3.5 Amps
Unit MCA 18.4 Amps Drain Connection 3/4''
Unit MOCP 25.0 Amps External Static Pressure 62.00 Pa
FLA tolerance ± 5%
Products Certifications

1 of 1
Page 16 of 286
Prochill Zamil
Print Date: 04/03/2023

DPM BTD EDA 26.1

Configured unit accessories


UNDE - Downward air ejection
HH - Cooling , heating and humidification/dehumidification
VEC - EC fans
AF - Dirty filter alarm
FEU5 - High efficiency filters with filter grade ISO ePM10 50% (M5/F5)
TB50 - Base frame with height-adjustable feet (500 mm)
GRLD - "Datalink" local network management
PBA - BACnet protocol over TCP-IP
A46N - 400/3N/60 power supply
SAL - Under-floor flooding sensor
REFF - 24V relay for remote smoke/fire sensor
RMMT - Maximum and minimum voltage relay
GABB - Packaging in wooden crate
ITB - Wooden packaging for base frame
General description
Air conditioners designed specifically to create "an ideal atmosphere" for electronic systems, by removing excess
heat and keeping humidity within the tolerance limits with the highest levels of reliability and safety.
SPECIFICATIONS
Refrigerant fluid
R410A
Structure

Zamil Air Conditioners, P.O. Box 41015, 2nd Industrial City, Dammam 31521, KSA
Page 3 of 9
Tel: +966 13 8125400, Fax: +966 13 8121977
www.zamilac.com

Page 17 of 286
Prochill Zamil
Print Date: 04/03/2023

The cabinet is made with galvanized steel sandwich panels that are epoxy powder coated. The panels are
internally insulated with glass wool, to obtain fire insulation class A1 (in accordance with EN13501). This type of
panel allows good thermal and acoustic insulation. Air tightness is achieved with adhesive sealing strips placed all
around the edges of the panels. The uprights and infills are made of galvanized sheet-iron.
The front panel closing the electrical control panel can be opened by handle for easy inspection of the inside.
Access to all the refrigerant and electrical components of the unit is from the front of the machine only; this
solution makes it unnecessary to carry out any work from the side and eliminates the obligation to consider
“technical spaces” around the air conditioning units. All the front panels are fixed to the structure by ¼ turn
fasteners and can therefore be easily removed. All the materials forming the structure are recyclable and CFC-
free.
Finish
Orange peel.
RAL
7016
FILTERS
The filters are of filtration class ISO Coarse 75% (G4) and designed to minimize head losses and to have a high
degree of filtration. The thickness of the filters can be 50 or 100 mm depending on the sizes or the set-ups. The
filters are removed from the front of the unit. High efficiency filters can be supplied on request.
Coils
Finned pack, copper tubes and aluminium fins, with corrugated profile and hydrophilic surface treatment. The
sensible heat ratio is close to 1. The fin profile was specially designed to prevent carry-over of condensation even
at high through speeds. A stainless steel condensation collection basin is installed at the base of the coil,
complete with fitting for drain and siphon.
Fans
Radial with reverse blades, with directly coupled 4-pole motor (AC), having thermal overload protection.
The flow of air into the fan is continuously controlled by a differential pressure switch that activates an alarm when
there is no air flow.
Remote condenser
Remote condensers can be combined with axial fans; power supply 230/1/50. This accessory is in the catalogue
in the standard or low noise versions. The protective devices and speed controllers are included in the internal
unit. The speed controller allows correct condensation with ambient temperatures down to -15°C. For beyond that
limit, and down to -35°C, a low temperature kit is available with flooding condensation control.
Electric post-heating
Banks of electric heaters, with heating elements with low surface temperature, made of stainless material. In the
event of overheating, a safety thermostat intervenes by stopping the power supply to the heaters and activating
an alarm.
Humidification
Immersed electrode humidifier supplied with mains water, controlled through microprocessor, for steam
production with continuous modulation.
Refrigerant circuit
The circuit includes:
- charging valve
- liquid sight glass
- dehydrator filter
- pipe taps on suction and delivery side

Zamil Air Conditioners, P.O. Box 41015, 2nd Industrial City, Dammam 31521, KSA
Page 4 of 9
Tel: +966 13 8125400, Fax: +966 13 8121977
www.zamilac.com

Page 18 of 286
Prochill Zamil
Print Date: 04/03/2023

- thermostatic expansion valve having external pressure equalization


- high and low pressure switches
- solenoid valve
- liquid receiver
- safety valves
- shut-off valve in the liquid line
- gas shut-off valves
- delivery valve in the compressor
- copper refrigerant pipes with anti-condensation insulation on the suction line
Electrical control panel
The circuit includes:
- Main disconnect switch
- Fuses to protect the power circuits
- Fuses to protect the auxiliary circuits
- Automatic circuit breaker to protect the auxiliary and power circuits
- Compressor contactors
- Fan contactors (AC)
- Contactors for heaters
- Contactors for humidifier
Microprocessor
To control the following functions:
- Ambient temperature
- Humidity
- Speed of the condensation fans
- Compressor timings
- Automatic rotation of compressor starting sequence
- Alarm signal on two levels
- Controlled automatic reset of high and low pressure alarms
- Alarm log recording with "black box" function
- a Modbus RS485 serial port for reading and writing purposes
- a RJ45 port for IP communication, including a reading and writing Modbus TCP/IP, available as standard
- Management of several units in local network with automatic rotation and non-interference logic
- Display of the following on the display:
--> Ambient temperature
--> Humidity
--> Air flow
--> Saturated suction and delivery pressure and temperature

Zamil Air Conditioners, P.O. Box 41015, 2nd Industrial City, Dammam 31521, KSA
Page 5 of 9
Tel: +966 13 8125400, Fax: +966 13 8121977
www.zamilac.com

Page 19 of 286
Prochill Zamil
Print Date: 04/03/2023

--> Description of alarms


--> Compressor operation hour meter
--> Status of controlled devices
Standard power supply [V/ph/Hz]
400/3~/60
400/3N~/60 if remote condenser present
CONTROLS AND SAFETY DEVICES
All the units are fitted with the following control and safety components:
- High pressure switch with manual reset for each compressor;
- Low pressure switch with automatic reset and limited interventions managed by the control;
- High pressure safety valve;
- Protection against overtemperature for compressors;
- Protection against overtemperature for fans;
Testing
Operating tests carried out at the factory
Refrigerant circuit charged with nitrogen; oil charge in the compressor
Refrigerant circuit charged with nitrogen; oil charge in the compressor
CONFIGURED UNIT ACCESSORIES DESCRIPTION
VEC - EC fans
The units can be combined with the innovative direct current EC axial fans (Electronically Commutated) with
electronically commutated brushless motor. These motors with permanent magnet rotor guarantee very high
efficiency levels for every operating condition and
allow a 15% saving per fan to be obtained. Also, through a 0-10V analogue signal sent to each fan, the
microprocessor allows condensation control by continuous control of air flow as the external air temperature
changes and a consequent reduction in noise emission.
AF - Dirty filter alarm
The flow of air into the fan is continuously controlled by a differential pressure switch that triggers an alarm when
there is no air flow.
FEU5 - High efficiency filters
Filter grade ISO ePM10 50% (M5/F5)
PBA - BACnet protocol over IP (Ethernet)
The control is set for using the BACnet protocol (instead of Modbus) on the Ethernet port.
By default, the programming gives read-only access to the control of the unit. Enabling of read/write access
should be requested when ordering.
SAL - Under-floor flooding sensor
For detection of water leaks, complete with sensor to be placed in the area to control. Further sensors can be
connected on request to allow control of several areas.
RMMT - Maximum and minimum voltage relay
This device carries out continuous control of the supply voltage of the unit and checks that it is always within an
allowable range. If the voltage value stabilizes above or below this range, the device will stop the unit to prevent
damage to the electric motors. This device will carry out phase sequence control.
GABB - Packaging in wooden crate

Zamil Air Conditioners, P.O. Box 41015, 2nd Industrial City, Dammam 31521, KSA
Page 6 of 9
Tel: +966 13 8125400, Fax: +966 13 8121977
www.zamilac.com

Page 20 of 286
Prochill Zamil
Print Date: 04/03/2023

The unit is protected by a made-to-measure wooden crate. The accessory is mandatory if shipping by container is
required

Zamil Air Conditioners, P.O. Box 41015, 2nd Industrial City, Dammam 31521, KSA
Page 7 of 9
Tel: +966 13 8125400, Fax: +966 13 8121977
www.zamilac.com

Page 21 of 286
Prochill Zamil
Print Date: 04/03/2023

CONFIGURED UNIT TECHNICAL DATA


Unit DPM BTD EDA
Model 26.1
Refrigerant fluid R410A
Conditions
Inlet air temperature °C 24.0
Inlet air relative humidity % 50.0
Height asl m 0
Condensing temperature °C 60.0
Performances
Total capacity kW 22.3
Sensible capacity kW 20.5
Net sensible cooling capacity kW 19.88
Sensible / Total ratio 0.92
Compressors absorbed power kW 8.6
Total Heat Rejected kW 30.86
EER 2.44
NSEER 2.17
Outlet air temperature °C 13.2
Outlet air relative humidity % 95.1
Air flow rate m3/h 5775
Available pressure Pa 50
Fans absorbed power kW 0.57
Sound levels
Sound pressure (S4) dB(A) 52
(S4) at 2 meters in free filed, at nominal conditions

Compressors
Type scroll
Number 1
Fans
Type Radial
Number 1
Evaporator
Type Finned pack
Number 1
Rows 4
Frontal section m² 0.84
Connections
Gas supply: diameter mm 1 x 18
Liquid return: diameter mm 1 x 16
Dimensions
Length mm 1102

Zamil Air Conditioners, P.O. Box 41015, 2nd Industrial City, Dammam 31521, KSA
Page 8 of 9
Tel: +966 13 8125400, Fax: +966 13 8121977
www.zamilac.com

Page 22 of 286
Prochill Zamil
Print Date: 04/03/2023

Width mm 850
Height mm 2490
Weight
Net weight kg 423
Electrical heating
Thermal capacity kW 9.0
Capacity steps 2
Humidification
Capacity kg/h 5.0
ELECTRICAL DATA (Theoretical calculations)
Power supply V/ph/Hz 400/3N~/60 ±10%
Control power supply V/ph/Hz 24V/1~/50-60 Hz
Electrical performances
Maximum absorbed power (E1) kW 27.15
Maximum starting current - LRA A 138.0
Full load current - FLA A 40.0

Zamil Air Conditioners, P.O. Box 41015, 2nd Industrial City, Dammam 31521, KSA
Page 9 of 9
Tel: +966 13 8125400, Fax: +966 13 8121977
www.zamilac.com

Page 23 of 286
Remote Condenser Unit
CuZAC

1.1.136.0

Customer: Done By: 150724


General Info

Project: Location:

Ref/Tag: Quantity: 2

Revision: Date: Monday, April 3, 2023

Required Power Supply Required Heat Required Outside Required


Rejection Conditions Condensing Temp
Input Conditions

Voltage Phases Frequency Heat Rejection Comp Qty Ambient Altitude Condensing Temp

Volts Phase Hertz kW 1 °C m °C


(380-480) 3 60/50 30.68 52.78 0.00 60.00

Selected Unit Model


ZRX043

Performance Fan Data


Required Total Heat Rejection / Comp 30.68 kW Size 630 mm
Selected Total Heat Rejection / Comp 32.90 kW Quantity 3
Output Performance

Difference 7.24 % Air Flow 15639 CFM


Total Unit Power Input 2.82 KW Fan Speed 1250 RPM

Electrical Data Coil Data


Power Supply (380-480)-3-60/50 Coil Face Area 28.5 ft²
Fan Motor Power (EA) 1 KW Coil Tube Dia 3/8 Inch
Fan Motor Speed 1250 RPM Rows 2
Fan Motor FLA 1.8 Amp Fins Per Inch 14
Unit MCA 6.75 Amp Coil Material AL/CU
Unit MOCP 12.15 Amp

Weight
Weight 215 kg

1 of 1

Page 24 of 286
Computer Room Unit
PacZAC

1.1.82.0

Customer:
Customer: ARAMCO ENGINEERING CO., LTD.
SAMSUNG Done
Done:By: Eng'r Jamal
M.ABBADI
General Info

Project:
Project: ****
HUGRS PROJECT Location:
Location: JUBAIL
HAWIYAH

Ref/Tag:
Ref/Tag: CRAC-PIB1-001
CRAC-CCB-001
CRAC-PIB2-001
CRAC-USS1-001
CRAC-USS2-001
**** Quantity:
Quantity: 1 1

Revision:
Revision: Rev .A
00 Date:
Date: April 1,27
Sunday, September 2020
2021

Required Capacity Required Entering RequiredOutside


Required Outside Required Air
Temperatures Conditions Conditions
External
Total Sensible
Sensible Dry Bulb Wet Bulb Ambient Altitude Air Flow Static Pressure

kW kW °C °C °C m LPS Pa
Input Conditions

5.80
*.9 - 23.89 16.98 52.0 0.00 426.5
566.0 0.00

Required Power Supply Auxiliary Required Options

Voltage Phases Frequency Air Filter Humidifier Heater

Volts Phase Hertz 1'' kW


230V 1 60Hz Aluminum 3.0 KG/H 5.0

Selected Unit Model


DPM024-ZRC024(Wall)

Performance @52.0°C Ambient Physical Dat


Total Cooling Capacity 5.97 KW
Fan Data Condenser Evaporator Units
Total Sensible Capacity 5.75 KW
Total Power Input 3.15 KW Size 500 225
NSenCOP @ AHRI 2.60 KW/KW
Quantity 1 2
Air Flow 1,268.0 566.0 LPS
Psychometric Data Fan Speed 970 2810 RPM
Entering (Return Temp) Leaving (Supply Temp) Coil Data Condenser Evaporator Units

Coil Face Area 7.9 3.3 sqft


Dry Bulb 23.89 °C Dry Bulb 16.15 °C
Output Performance

Coil Tube Diameter 3/8 3/8 in


Wet Bulb 16.98 °C Wet Bulb 13.98 °C
Number of Rows*** 2 3
Fins Per Inch 14 14 FPI
Compressor Data Fins Material Al Al

Type Hermetic Scroll


Quantity 1 Electric Heater Humidifier
Capacity 5 kW 1 Stage Capacity 3 KG/H
Electrical Data FLA 21.7 Amps FLA 9.8 Amps

Filter Data (W X H )
Condenser Evaporator Units

230-1-60Hz 230-1-60Hz
Power Supply
Compressor RLA (Each) 15.0 Amps 32 X 12 inch ( QTY = 1 )
Compressor LRA (Each) 58.3 Amps
Fan Motor (Each) 0.42 (0.17 each) KW
Fan Motor Speed 970 2810 RPM General Data
Fan Motor FLA* (Each) 1.85 1.44 Amps
Unit MCA 20.6 43.0 Amps Drain Pan Connection 3/4'' NPT
Unit MOCP 30.0 50.0 Amps Humidifier Supply Connection G 3/4" M
FLA tolerance ± 5% Humidifier Drain Connection 32 mm

Notes :
1. Gross Cooling Capacity is indicated. For net Cooling Capacity , subtract indoor motor heat.
2. Total Power Input includes Compressor(s), Indoor Motor(s) & Condenser(s) .
3. NSenCOP is calculated in accordance to AHRI 1360 standard.
4. Indoor & Outdoor Units are shipped with Nitrogen holding Charge ,R410A is Field Charging.

Page 25 of 286
Computer Room Unit
PacZAC

1.1.82.0

Customer:
Customer: SAMSUNG ENGINEERING CO., LTD. Done
Done:By: Eng'r Jamal ALfaifi
M.ABBADI
General Info

Project:
Project: ****
HUGRS PHASE 1-2 Location:
Location: JUBAIL
HAWIYAH

Ref/Tag:
Ref/Tag: CRAC-FS-001
**** Quantity:
Quantity: 21
1 1

Revision:
Revision: A
Rev 00 Date:
Date: April 1, 2021
Wednesday, 18 November 2020

Required Capacity Required Entering Required Outside Required Air


Temperatures Conditions Conditions
External
Total Sensible Dry Bulb Wet Bulb Ambient Altitude Air Flow Static Pressure

kW kW °C °C °C m LPS Pa
Input Conditions

12.00 - 23.89 16.98 52.0 0.00 1038 0.00

Required Power Supply Auxiliary Required Options

Voltage Phases Frequency Air Filter Humidifier Heater

Volts Phase Hertz 1'' kW


230V 1 60Hz Aluminum 5.0 KG/H 10.0

Selected Unit Model


DPM048-ZRC048 (Wall)

Performance @ 52.0°C Ambient Physical Data


Total Cooling Capacity 12.22 KW
Fan Data Condenser Evaporator Units
Total Sensible Capacity 11.88 KW
Total Power Input 6.17 KW Size 560 225
NSenCOP @ AHRI 2.60 KW/KW
Quantity 1 4
Air Flow 2,025.0 1038 LPS
Psychometric Data Fan Speed 1040 2786 RPM
Entering (Return Temp) Leaving (Supply Temp) Coil Data Condenser Evaporator Units

Coil Face Area 14.4 5.0 sqft


Dry Bulb 23.89 °C Dry Bulb 15.05 °C
Output Performance

Coil Tube Diameter 3/8 3/8 in


Wet Bulb 16.98 °C Wet Bulb 13.58 °C
Number of Rows 3 4
Fins Per Inch 14 14 FPI
Compressor Data Fins Material Al Al

Type Hermetic Scroll


Quantity 1 Electric Heater Humidifier
Capacity 10 kW 1 Stage Capacity 5 KG/H
Electrical Data FLA 43.4 Amps FLA 16.3 Amps

Filter Data (W X H )
Condenser Evaporator Units

230-1-60Hz 230-1-60Hz
Power Supply
Compressor RLA (Each) 24.3 Amps 28 X 12 inch ( QTY = 2 )
Compressor LRA (Each) 117 Amps
Fan Motor (Each) 0.7 (0.17 each) KW
Fan Motor Speed 1040 2786 RPM General Data
Fan Motor FLA* (Each) 3.1 1.44 Amps
Unit MCA 33.5 83.7 Amps Drain Pan Connection 3/4'' NPT
Unit MOCP 50.0 90.0 Amps Humidifier Supply Connection G 3/4" M
FLA tolerance ± 5% Humidifier Drain Connection 32 mm

Notes :
1. Gross Cooling Capacity is indicated. For net Cooling Capacity , subtract indoor motor heat.
2. Total Power Input includes Compressor(s), Indoor Motor(s) & Condenser(s) .
3. NSenCOP is calculated in accordance to AHRI 1360 standard.
4. Indoor & Outdoor Units are shipped with Nitrogen holding Charge ,R410A is Field Charging.

Page 26 of 286
SPECIFICATIONS
INDOOR UNIT SIZ24CHAXCD SIZ48CHAXCD
MODEL NUMBER
OUTDOOR UNIT CKZ24CDAHIKD CKZ48CDGHIKD
MODE OF OPERATION Cool onl y / Hea l pump HEA T P UM P HEA T P UM P
POWER SUPPLY Vol ts -Ph-Hz 230-1-60 230-1-60
ENERGY CLASS ( SEER ) B C
COOLING CAPACITY ( T1 & T3 ) Btuh 22000 / 20000 40200 / 34400
COOLING CAPACITY ( T1 & T3 ) wa tts 6448 / 5861 11781 / 10082
HEATING CAPAICTY wa tts 7,000 16,000
POWER INPUT ( T1 & T3 ) wa tts 1864 / 2353 3407 / 4047
POWER INPUT ( Hea ti ng ) wa tts 1,850 4,764
EER ( T1 & T3 ) Btuh/W 11.8 / 8.5 11.8 / 8.5
COP ( Hea ti ng ) W/W 3.85 3.35
SEER Btuh/W 15.66 13.99
ANNUAL ENERGY CONSUMPTION kWh 5,075 9,770
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 1300/1100/850 2000/1800/1600
SOUND PRESSURE LEVEL (1M) dBA 51-44 52-46
COMPRESSOR TYPE Twi n DC Inverter Rota ry Twi n DC Inverter Rota ry
REFRIGERANT TYPE R410a R410a
LIQUID - SUCTION PIPE DIA i nch 3/8" , 5/8" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH (Total/vertical) meter 20 / 10 50 / 20
INDOOR UNIT ( Body ) Kg 24 / 29 34 / 36
NET WEIGHT, KG INDOOR UNIT ( Panel ) Kg 6.5 / 9.5 6.5 / 9.5
OUTDOOR UNIT Kg 67 / 72 96 / 105
INDOOR UNIT ( Body ) mm 840×230×840 840×230×840
DIMENSIONS (LxWxH), MM INDOOR UNIT ( Panel ) mm 950×40×950 950×40×950
OUTDOOR UNIT mm 946x410x810 972×400x1330
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.

Page 27 of 286
NMR 601.4
Equipment Drawing

Page 28 of 286
PTX 022 FA3

3135

1100 1400 635


R1 R5 RA

1 Filter access 2

500
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet

BAG FILTER SECTION


4 Elecrical control box (Hinged door)
5 Lifting points

2124
2200

1200
6 Blower and motor access
7 Evaporator coil access
8 Horizontal supply

500
R2 R6 RB

250 2000 250 318 318

TOP VIEW

Air Discharge Air Discharge

816 568 816

81
Supply Air 8

568
4
2281

3 1
6 7
Return Air

1053
2200 162
226 635
5
END VIEW SIDE VIEW FRONT VIEW

R1 R2 R3 R4 UNIT WEIGHT (KG) CHRIS


417 406 308 299 1430 AL / CU *.*.*
RA RB SECTION WEIGHT (KG) PTX022 *.*.*
70 70 140 CAD.DIMS. ABBADI
Page 29 of 286PACKAGE_UNITS 31/01/22
COMMON\PACKAGE\PAX-REV01\PTX-DWG-LAYOUT
PTX 036 FA2

4235

2200 1400 635


R1 R3 R5 RA
1 Filter access

305
2
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet

BAG FILTER SECTION


4 Elecrical control box (Hinged door)
5 Lifting points
6 Blower and motor access Fresh Air

2200

2124

1590
7 Evaporator access
8 Horizontal supply

305
R2 R4 R6 RB

250 1550 1550 250 318 318

TOP VIEW

Air Discharge Air Discharge

816 568 816

81
8
Supply Air

568
4
2281

3 1
6 7
Fresh Air

1053
137
2200 226 635
5 SIDE VIEW
END VIEW FRONT VIEW

R1 R2 R3 R4 R5 R6 UNIT WEIGHT (KG)


282 233 363 295 182 160 1515 AL / CU CHRIS
*-*-*
RA RB
PTX036 ABBADI
SECTION WEIGHT (KG)
87.5 87.5 175 CAD.DIMS. ABBADI
Page 30 of 286PACKAGE_UNITS 06/12/20
COMMON\PACKAGE\PAX-REV01\PTX-DWG-LAYOUT
UNIT DIMENSIONS
PY075

COMPRESSOR / CONTROLS ACCESS PANEL


ACCESS PANEL FOR BLOWER & MOTOR M

CONTROL COMPARTMENT

CONDENSATE DRAIN OUTLET


3/4" NPT

AIR IN

AIR IN SUPPLY AIR RETURN AIR

TOP VIEW DUCT COLLAR


AIR OUT
K J H N

FILTER
SUPPLY AIR RETURN AIR
COND. COIL ACCESS

G
F

COND. COIL OPENING OPENING


PANEL
C

POWER SUPPLY CONN


DRAIN OUTLET
E

[5.21]
O

132
D
L P Ø 12.7 ( 0.5) MOUNTING HOLES
B (2 EACH SIDE)
A

SIDE VIEW FRONT VIEW SIDE VIEW

MODEL A B C D E F G H J K L M N O P
PY 075 2080 (81.89) 1162 (45.75) 1034 (40.71) 1114 (43.86) 308 (12.15) 550 (21.64) 810 (31.92) 300 (11.81) 251 (9.87) 396 (15.59) 152 (5.98) 175 (6.88) 24 (0.94) 171 (6.73) 1775 (69.88)

NOTE : ALL DIMS ARE IN mm (DIMS IN BRACKETS ARE INCHES)

44
Page 31 of 286
ACCESS DETAILS
PV036 - PV060

9
Page 32 of 286
DPM 26.1
AIRFLOW INLET

Ep
Ep

Af

Rp
1990

1990
Eh

H
H

11 1080 11 10 830 10
1102 850 800

AIRFLOW OUTLET

40 1000 40
155 47
35

Hin
270
417,5

AIRFLOW OUTLET
578

Hd

Cd
112,5

85
Gout*
300

228
55 138

122

Gin*
70
24
32

102,5
335 130 615
Es
Rd
Rl CONNESSIONI FRIGO CONN.
REFRIGERANT CONNECTIONS DC
CONNECTIONS Rd Rl Gin/Gout
17.1 16 12 1"
22.1 16 12 1"
26.1 18 16 1"
SOLO VERSIONE DC 32.1 18 16 1"1/4
* ONLY FOR DC VERSION 36.1 18 16 /

Rev. Date Draftman Checked by Revision description

C 24-06-2020 Sushant O. Peron N. MODIFIED LOGO


B 20/07/2017 Barbetta M. Turri G. Correct connections table

Machining tolerances: ISO 2768 - m


Denomination - Dimensional Drawing Code Drawing Rev.
DIMENSIONAL DRAWING
DATATECH UEDA/UEDA DC FRAME "S" / A49344 C
Scale Date Draftsman Checked by
Sheet N. 1 di 2
1:20 24-06-2020 F.Bellamio Cappellato of
Replace draw. Replaced by Page
draw. 33 of 286 Weight [kg]
/ / /
1080
150 780 150

18
794

830
18
IMPRONTA A TERRA/FOOTPRINT

WEIGHT UNDER S VERSION HH (Kg)

MODEL UEDA UEDA DC


17.1 388.5 425.0
22.1 388.7 425.2
26.1 432.1 468.6
32.1 432.4 478.7
36.1 440.8 487.1

VERSION CO, SUBTRACT Kg: 17.9


VERSION CH, SUBTRACT Kg: 9.9
VERSION EC FAN, SUBTRACT Kg: 27.6

Rev. Date Draftman Checked by Revision description

C 24-06-2020 Sushant O. Peron N. MODIFIED LOGO


B 20/07/2017 Barbetta M. Turri G. Correct connections table

Machining tolerances: ISO 2768 - m


Denomination - Dimensional Drawing Code Drawing Rev.
DIMENSIONAL DRAWING
DATATECH UEDA/UEDA DC FRAME "S" / A49344 C
Scale Date Draftsman Checked by
Sheet N. 2 di 2
1:20 24-06-2020 F.Bellamio Cappellato of
Replace draw. Replaced by Page
draw. 34 of 286 Weight [kg]
/ / /
NMR 601.5
Power Requirement

Page 35 of 286
POWER REQUIREMENTS

PROJECT: UPGRADE SECURITY FACILITIES EAST/ WEST PIPELINE PUMP-STATION-4

Condenser Condenser fan Blower Blower motor Electric Heater


Compressor RLA Compressor LRA Unit
Sr.No TAG Model fan motor motor FLA motor FLA KW (STAGES) Unit MCA Power supply
(Amps) (Amps) MOCP
(Kw) (Amps) (Kw) (Amps)

PACU-1,2 (SEC
1 PTX022-FA3 26.4 X 2 145 X 2 2.3 X 2 4.1 X 2 5.50 11.4 NIL 79.0 100 380V-3PH-60Hz
SUPPORT TYPE 1)

PACU-1,2 (SEC
2 PTX036-FA2 17.2 X 4 123 X 4 1.15 X 4 3X4 7.50 14.7 NIL 99.8 110 380V-3PH-60Hz
SUPPORT TYPE 2)

3 PACU1A&2A (PIC BLDG) PY075 11.4 83 0.5 1.6 1.49 3.1 NIL 19.0 30 380V-3PH-60Hz

4 PACU-01 (GENERATOR) PV048 9.9 64 0.5 2.5 0.37 3.5 NIL 18.4 25 380V-3PH-60Hz

DPM BTD EDA


5 PS1- Existing SSB - 138 1 2 27.15 40.0 9.0/2 6.75 12.15 230V-1PH-60Hz
26.1/ZRX043

6 CRAC-USS1-001 DPM024-ZRC024(Wall) 15 58.3 0.42 1.85 0.17 X 2 1.44 X 2 5/1 20.6/43.0 30/50.0 230V-1PH-60Hz

7 CRAC-FS-001 DPM048-ZRC048(Wall) 24.3 117 0.7 3.1 0.17 X 4 1.44 X 4 10 / 1 20.6/43.0 30/50.0 230V-1PH-60Hz

Page 36 of 286
NMR 601.6
Brochure/catalogue

Page 37 of 286
Page 38 of 286
Company Business
Zamil Air Conditioners (ZAC), a sector business of Zamil Industrial, is the largest supplier of air conditioners in the Middle East. It manufactures and markets
a whole range of air conditioners from room air conditioners to packaged units to large capacity chillers for residential, commercial and industrial applica-
tions. Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabia and today is a leading
international manufacturer of air conditioning systems & service solutions and is Number One in the Middle East. ZAC’s operations are structured into four
companies supporting seven in-house brands and twelve products and service units as well as a number of international brands under the OEM Sales. The
seven in-house brands are Zamil Air Conditioners, Classic, Zamil, Cooline, CoolCare, Climatech and Geoclima.

The four companies are:


1. Zamil Air Conditioners & Home Appliances Co. (L.L.C.), supporting Zamil, Classic, Cooline, GE and OEM brands for consumers.
2. Zamil Central Air Conditioners Co. (L.L.C.), supporting Zamil Air Conditioners, Cooline and Climatech for commercial and industrial customers.
3. Zamil Air Conditioning and Refrigeration Services Co. (L.L.C.), providing electromechanical engineering, construction and project management services,
HVAC Operation & Maintenance, Retrofit Services, Spare Parts, Fire Protection, Controls, Electrical Services, Coils, Ducting and Coating.
4. Geoclima srl is an independent business supporting other three companies for their requirements of Chillers and Double Skin AHU’s.

The first three Companies- direct their business operations from the First and Second Industrial Cities in Dammam, Saudi Arabia and have a product design
center in Austria.
GEOCLIMA has its engineering and production departments located at Monfalcone, Italy. All the four companies, while operating independently, supple-
ment each other’s activities in a way that makes synergy work at its best and achieves ZAC’s goals of maximizing customer value and satisfaction.

OEM Sales - Private Labeling


Zamil Air Conditioners produces branded air conditioners under OEM agreements for several leading international brands. Such relationships are testimony
to the excellence of ZAC’s engineering and production processes. Most of the units produced under the private labeling agreements are for window and
mini-split systems. However, ZAC is expanding its OEM offerings to include residential and light commercial units. Some of the OEM brands manufactured
at Zamil Air Conditioners are: Supra, Sanyo and Blue Star.

Joint Venture
Middle East Air Conditioners - Joint Venture with General Electric.
Zamil Air Conditioners partners with GE Appliances - Europe since 1997, in a joint venture called Middle East Air Conditioners (MEAC), for manufacturing
and marketing of GE branded air conditioners. MEAC was awarded the license to manufacture Window, Mini Splits and Ducted Split types under the brand
names GE, Hotpoint and RCA. Today, MEAC enjoys extensive coverage in Saudi Arabia, GCC and the African market. In an ever-changing market, MEAC
continually strives to acquire new technologies and stylish integrated design with optimum performance and reliability that bring greater value to customers.

Factories and Production


Zamil Air Conditioners has two prime manufacturing plants in Dammam, Saudi Arabia and a production facility in Italy operated by GEOCLIMA and a prod-
uct design center in Austria. ZAC can produce up to 900,000 room air conditioners, 300,000 mini-split systems and 65,000 central airconditioning systems
per annum and supplies air conditioning products to over 55 countries across the world - the major markets being GCC, Middle East, North Africa, Europe
and Asia.

Quality & Product Certificates


The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.
ZAC’s products are certified with:
1. CE (Council of European Community).
2. UL (Underwriters Laboratory).
3. Eurovent (Certified Performance).
4. ISO 9001-2008 (International Organization for Standardization).
5. AHRI (Air-Conditioning, Heating and Refrigeration Institute).
Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed bin Fahd Al Saud
Award for Factory Safety.

Our Products & Service Units


In addition to consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners manufactures a host of residential,
commercial and industrial air conditioners. This broad product range extends from the concealed units up to 5 TR, the ducted splits up to 30 TR, the pack-
aged units up to 100 TR, the single and double skin air handling units up to 138,316 CFM, the water chillers up to 590 TR and the centrifugal chillers up to
5,000 TR cooling capacity.

Our products and services include, in addition to Maintenance, Retrofit & Operations (MRO), complete integrate suite of solutions like:
• Zamil Projects: Providing EPC for electromechanical works for Industrial, Utility and Oil & Gas customers.
• Zamil Controls: Design, assembly, integration and commissioning of low current & low voltage systems.
• Zamil Fire Protection: Design, integration and commissioning of active fire protection systems.
• Zamil Electrical: Design, integration and commissioning of lv/mv (low voltage/middle voltage) systems.
• Coil & Coating: Coil replacement, anti-corrosion coating, water proofing & reflective coating and passive fire protection solutions.
• Zamil Ducting: Facilities designs and manufactures high quality duct systems and other HVAC industry related products, utilizing state of the
art automated duct lines, Plasma Cutting, CNC Turret punch press and other specific machinery through two duct factories located in Saudi
Arabia western province (Yanbu) and Eastern province (Dammam).

Page 39 of 286
INDEX
Contents Page

Model decoding .......................................................................................................................................................... 2

Configurations..............................................................................................................................................................3

Introduction ..............................................................................................................................................................4-7

Standard Specifications ..........................................................................................................................................8-14

Optional Items ......................................................................................................................................................15-18

Standard feature/options/accessories .......................................................................................................................19

Physical data ........................................................................................................................................................20-22

Selection Procedure...................................................................................................................................................23

Cooling Capacities ................................................................................................................................................24-31

Electrical data .......................................................................................................................................................32-43

Fan performance data ..........................................................................................................................................44-64

Static pressure drop .............................................................................................................................................65-66

Filter dimensions ........................................................................................................................................................67

Unit dimensions ....................................................................................................................................................68-89

Optional sections, dimensions ..............................................................................................................................90-99

Roof Curb and Rain hood assembly...................................................................................................................100-101

Typical shchematic wiring diagram...... .............................................................................................................103-104

Economizer board & control connection ..................................................................................................................105

Rigging instructions .................................................................................................................................................106

Installation clearance ........................................................................................................................................107-108

Load distribution & mounting location........................................................................................................................109

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

1
Page 40 of 286
MODEL DECODING
1, 2 & 3 4, 5 & 6 7 8 9 10 11 12 13 14
BASIC NOMINAL COMPRESSOR TYPE ELECTRICAL REFRIGERATION CONDENSER COIL EVAPORATOR SUPPLY AIR BLOWER (3) BLOWER
COOLING SUPPLY CIRCUIT TYPE (1) COIL ARRANGEMENT (2) MOTOR
CAPACITY (V-Ph-Hz) (KW)
(TONS)
PTX 006 S : SASO H : 230-3-60 S : SINGLE SCROLL A : ALUMINUM FIN A : ALUMINUM FIN A : 1" SINGLE SKIN - TOP SUPPLY F : FORWARD CURVED C : 1.1
MODULAR 007 COMPLAINT, HIGH COMPRESSOR (CONFIG- A) BLOWER
PACKAGED EFFICIENCY AND M : 380/400-3-60 (PTX006-PTX007) B : PRE-COATED B : PRE COATED D : 1.5
008 SCROLL (4 WIRE) ALUMINUM FIN ALUMINUM FIN B : 1" SINGLE SKIN - FRONT SUPPLY B : BACKWARD CURVED
UNITS
(R-410A) 010 COMPRESSORS D : DUAL SCROLL (CONFIG- B) BLOWER E : 2.2
012 F : 460-3-60 COMPRESSORS C : COPPER FIN C : COPPER FIN C : 1" SINGLE SKIN - SIDE SUPPLY
016 (PTX008-PTX035) (CONFIG-C ) C : F + SPRING ISOLATOR F :3
D : ALUMINUM FIN D : ALUMINUM FIN
018 T : TRIO SCROLL WITH RESISTEC WITH RESISTEC D : 1" SINGLE SKIN - DOWN SUPPLY D : B + SPRING ISOLATOR G:4
020 COMPRESSORS COATING COATING (CONFIG- D )
022 (PTX027 & 031) H : F + BELT GUARD H : 5.5
025 E : COPPER FIN E : COPPER FIN E : 2" DOUBLE SKIN - TOP SUPPLY
027 Q : QUADRUPLE W/- RESISTEC W/- RESISTEC (CONFIG-A) I : B + BELT GUARD I : 7.5
SCROLL COATING COATING
028 COMPRESSORS F : 2" DOUBLE SKIN - FRONT SUPPLY M : F + C + H COMBO J : 11
030 (PTX036-PTX105) (CONFIG- B)
031 N : B + D + I COMBO K : 15
G : 2" DOUBLE SKIN SIDE SUPPLY
035 (CONFIG- C )
L : 18.5
036
H : 2" DOUBLE SKIN - DOWN SUPPLY
040 (CONFIG- D ) M : 22
045
050 N : 30
060 O : 37
070
080 P : 45
090
105

15 16 17 18 19 20 21 22 23 & 24
HEATER KITS ELECTRICAL KITS MECHANICAL KITS FILTER EXTRA SECTIONS UNITS DRAIN PAN & DAMPERS SPECIAL OPTIONS

2
OPTIONS (4) OPTIONS OPTIONS OPTIONS OPTIONS (9) ENCLOSURE DRIP ELIMINATOR
(KW)
N : NO HEATER A : STD OPTIONS(5) A : STD. OPTIONS(7) A : STD. FILTER- A : STANDARD (WITHOUT A : STANDARD A : STD. DRAIN PAN A : STD. AA : STD.
RACK WITH 2" SECTION)

Page 41 of 286
A : 7.5 K : FAN CYCLING M : REPLACEABLE AB : UV LAMP
SWITCHES. DISPOSABLE B : 4" MINI PLEATED FINAL F : UNIT FULL D : STAINLESS B : MANUAL FRESH
CORE FILTER DRIER FILTERS(8) GUARD DRAIN PAN (304) AIR DAMPER AC : ELECTRONIC
B : 10 V : VOLT FREE CONTACT(6) & SHUT-OFF VALVE FILTER THERMOSTAT
C : 12.5 C : COMP CIRCUIT F : STD. FILTER- C : BAG FILTER SECTION E : STD. DRAIN PAN C : MANUAL FRESH AD : ANTI - ICE THERMOSTAT
P : PRESSURE GAUGES
BREAKER (SUCTION & DIS- RACK WITH 2" D : MIXING BOX SECTION WITH DRIP AIR DAMPER & AE : DIFFERENTIAL
D : 15 THICKPLEATED - TOP RETURN ELIMINATOR RETURN
D : NON FUSED CHARGE) PRESSURE SWITCH FOR
E : 20 DISCONNECT SWITCH FILTERS E : MIXING BOX SECTION AIR DAMPER PRE FILTER
H : HOT GAS BYPASS -FRONT RETURN F : STAINLESS
F : 22.5 P : PUMP DOWN M : STD. FILTER- STEEL DRAIN F : ECONOMIZER AF : DIFFERENTIAL
SOLENOID VALVE R : CONDENSER PRES- RACK WITH F : MIXING BOX SECTION PAN WITH DRIP CONTROL WITH PRESSURE SWITCH FOR
G : 25 B : K + V COMBO SURE RELIEF VALVE 2" THICK -SIDE RETURN ELMINATOR OUTSIDE AIR PRE FILTER &
ALUMINUM G : MIXING BOX SECTION (304) THERMOSTAT FINAL FILTER
H : 30 E : K + C COMBO J : M + P COMBO
FILTERS -DOWN RETURN TYPE AH : HINGED DOOR FOR
I : 37.5 G : K + P COMBO N : M + H COMBO BLOWER FAN & MOTOR
H : B + D COMBO
H : K+D COMBO K : M + R COMBO G : ECONOMIZER SECTION
K : 40 I : B + E COMBO CONTROL WITH
T : K + V + C COMBO O : P + H COMBO AI : AC+AD
L : 45 J : B + F COMBO ENTHALPY
M : K + V + P COMBO SENSOR TYPE AJ : AC+AD+AE COMBO
F : H + R COMBO K : B + G COMBO
M : 50 N : V + C + P COMBO AK : AC+AD+AF COMBO
Q : M + H +R COMBO L : C + D COMBO H : ECONOMIZER
O : 60 Q : V+C+D COMBO AL : AC+AD+AE+AH COMBO
T : M + P +H COMBO M : C + E COMBO CONTROL WITH
U : V+D+P COMBO ENTHALPY AM : AC+AD+AF+AH COMBO
P : 80 L : P + H +R COMBO N : C + F COMBO
L : K+V+C+P COMBO SENSOR TYPE &
Q : 100 O : C + G COMBO CO2 MONITOR
O : K+V+C+P+D COMBO U : M + P + R COMBO
W : M+P+H+R COMBO

NOTES: (1) Please refer to PTX capacity control Chart (Page #8).
(2) 1" thick Fiber glass insulation is standard for all models.
(3) All units are supplied with forward curved blower as standard, while backward curved blower is option.
(4) Please refer to PTX electric heater Chart (Page #16).
(5) Standard electrical options contain Under Voltage Mointor(UVM) & fixed low/ high pressure switches.
(6) A combination of volt free contact option: 1. Unit on/off indication; 2. Compressor run & Unit trip indication; 3.Blower run & trip indication; 4. Unit trip.
(7) Standard options contain sealed type filter drier and sight glass.
(8) 2 " disposable filter is standard for all models.
(9) The insulation thickness of the mixing box or bag filter section is based on decoding #12.
CONFIGURATIONS

CONFIGURATION - A CONFIGURATION - C
TOP SUPPLY COMBINATION OPTIONS SIDE SUPPLY COMBINATION OPTIONS

RA RA

RA RA

FA FA RA FA FA RA

FRONT RETURN TOP RETURN SIDE RETURN


SA - Supply Air RA - Return Air FA - Fresh Air SA - Supply Air RA - Return Air FA - Fresh Air FRONT RETURN TOP RETURN SIDE RETURN
FA - Opposite side
FA - Opposite side

3
CONFIGURATION - B CONFIGURATION - D

Page 42 of 286
FRONT SUPPLY COMBINATION OPTIONS BOTTOM SUPPLY COMBINATION OPTIONS

RA RA

FA FA RA FA FA RA

RA SA RA
SA - Supply Air RA - Return Air FA - Fresh Air FRONT RETURN BOTTOM RETURN SIDE RETURN BOTTOM RETURN
SA - Supply Air RA - Return Air FA - Fresh Air FRONT RETURN SIDE RETURN
FA - Opposite side FA - Opposite side
FEATURES AND BENEFITS
* R-410A environmentally friendly refrigerant (HFC refrigerant).
* Gross Cooling capacity from 6.1 TR up to 107.2 TR for 60Hz.
* EER meets ASHRAE90.1 and SASO- 2874 standards.
* PTX006-PTX060 are AHRI certified accordance to 340/360 standards.
* Independent refrigeration circuits with scroll compressors for efficient cooling process.
* Unit’s cooling operating up to (52oC) 125oF ambient temperature.
* Thermal expansion valve, filter drier kit and moisture indicator.
* Copper tubes and aluminum fins coils.
* Compact unit design with smaller unit footprint at lower installation cost.
* Single wall evaporator section with 1" fiberglass insulation.
* Access panels with easy opened 'C' clamp and no screw features in all access panels.
* 2" (50 mm) thick disposable pre-filter applicable to all models.
* Available in Top, front, side and down supply duct configuration.
* Belt driven blower fan motor with adjustable motor pulley applicable for all models.
* Rigging holes in base rail for easy lifting & Installation.
* High pressure switch and low pressure switch protection.
* Single power point connection to reduce filed wiring cost.
* Easy access to all components for excellent serviceability.
* Condenser coil is provided with Integral sub-cooling circuits to increase overall unit efficiency.
* High efficient permanently lubricated condenser fan motors (TEAO) with class 'F' insulation.
* Smart microprocessor controller with 220V control voltage protected with control fuse.
* Quality assurance according to ISO 9001:2008, Which guarantees high and constant product quality.

COOLING RATING TABLE


COOLING TOTAL POWER INPUT AIR FLOW
MODEL No. NET CAPACITY (MBH) EER
STAGES (KW) (CFM)
PTX006 1 71 5.96 2500 11.9
PTX007 1 83 7.16 2800 11.55
PTX008 2 102 8.54 3500 11.9
PTX010 2 123 10.72 4000 11.45
PTX012 2 146 12.87 4500 11.3
PTX016 2 190 16.86 5600 11.25
PTX018 2 208 18.32 6400 11.35
PTX020 2 242 22.74 8000 10.6
PTX022 2 274 26.13 8500 10.45
PTX025 2 302 29.37 9400 10.25
PTX027 3 304 28.55 10600 10.6
PTX028 2 322 31.11 10600 10.35
PTX030 2 348 33.85 11400 10.25
PTX031 3 346 33.48 11400 10.3
PTX035 2 405 39.52 12500 10.2
PTX036 4 400 39.03 12500 10.2
PTX040 4 455 43.08 14500 10.55
PTX045 4 540 52.15 15000 10.35
PTX050 4 590 57.74 16500 10.2
PTX060 4 680 64.92 19500 10.4
PTX070 4 770 76.92 18700 10.0
PTX080 4 890 90.12 23000 9.85
PTX090 4 1000 101.14 25000 9.85
PTX105 4 1190 119.48 26400 9.95
NOTES:
1. Rated in accordance with AHRI 340/360 & SASO Standards
2. Ratings are based on:95oF DB Outdoor (Ambient) Temperature.
3. EER : Energy Efficiency Ratio.

4
Page 43 of 286
WHY ZAMIL PACKAGED ROOFTOP SYSTEMS?
The PTX Series air-cooled modular packaged rooftop units from Zamil Air Conditioners are produced in an ISO 9001:2008
certified facility. They are designed to provide engineering excellence on comfort air conditioning and industrial cooling
with a superior combination of high-energy efficiency & energy saving, high performance, application flexibility, ease of
service & maintenance and the ability to withstand extreme ambient temperatures found in the climate of the Gulf region.

The PTX series are modular packaged units with a design that consists of scroll compressor(s), cooling coil, condenser
coil, fans, control wiring and inter connecting piping. These units are shipped in single packaged, fully charged with
R-410A refrigerant, and are suitable for mounting on the roof or ground with easy installation and excellent serviceability.
The unit features an integral weather resistant control panel, ready for field connection to utilities and ducts.

PTX006

The PTX series units are designed to use ozone friendly HFC R-410A refrigerant. HFC R-410A is highly efficient thermo-
dynamic proprieties, created to serve as one of the key substitutes for HCFC based refrigerants. R-410A is environmen-
tally safer for long term use, no chlorine and does not contribute to Ozone depletion. There is no phasing out and no
replacement costs for the life of the equipment.

5
Page 44 of 286
R-410A CHARACTERISTICS

* Ozone friendly- HFC compound, No Chlorine & have zero ODP.

* R-410A has a significantly higher liquid heat transfer coefficient than R-22.

* R-410A has lower density than R-22.

* Higher Pressure Range, 50% to 70% higher than R-22.

* It’s a Blended Refrigerant (50% R-32 and 50% R-125).

* This blend is a Near-Azeotrope thus; it acts very much like a single compound refrigerant.

* No Fractionation problems.
* Temperature glide less than 0.2°F over it’s operating range.

* Critical temperature is 161°F.

* Critical pressure is 700 Psig.

* R-410A utilizes Polyol Ester (POE) based oils.

* R-410A cylinders are rose colored.

* Environmentally safer for long term usage.

* No phase out & no replacement cost.

* Low toxicity & non-flammable.

* Compatible with steel, copper, aluminum and brass.

6
Page 45 of 286
SCROLL COMPRESSORS
The scroll compressors are consists of two involutes or Archimedean spirals. One spiral is positioned inside the
other to form a series of crescent-shaped pockets. During compression the upper spiral remains stationary and the
lower one, being eccentrically mounted on the drive shaft, describes an orbital rather than a simple rotary motion.

Compressor working principle Scroll compressor

1. Compression in the scroll is created by the interaction of an orbiting spiral and a stationary spiral. A refrigerant
enters the outer openings as one of the spirals orbits.

2. The open passages are sealed off as gas is drawn into the spiral.

3. As the spiral continues to orbit, the gas is compressed into two increasingly smaller pockets.

4. By the time the gas arrives at the center port, discharge pressure has been reached.

5. During operation, all six gas passages are in various stages of compression at all times, resulting in nearly
continuous suction and discharge.

Refrigerant enters the compressor at the suction connection and flows around the motor’s housing and enters at the
bottom side through the openings and oil droplets separate from the refrigerant and fall into the oil sump. All suction
refrigerant passes through the electrical motor, ensuring full motor cooling, after that the refrigerant enters the scroll
elements.

Scroll compressor involutes Pockets arrangement

7
Page 46 of 286
STANDARD SPECIFICATIONS
A. UNIT CONSTRUCTION
BASE: The base rail is constructed of heavy gauge galvanized steel with lifting holes for ease in rigging and lifting. It
also includes mounting holes suitable to affix with neoprene pads or spring isolators.
CABINET: The unit cabinet is a modular construction design with a base frame and panels made of heavy gauge
galvanized steel. All panels, top and bottom base pan, vertical posts, cross channels and supporting brackets are joined
together and bolted. The steel sheet panels are zinc-coated and galvanized by the hot dip process of lock-forming quality
conforming to ASTM A 653 commercial weight G-90, followed by a baked on electrostatic polyester dry powder coat,
capable of withstanding 1500 hours of salt spray test in accordance with ASTM B-117.

Cooling Capacity Stage Table


B. COMPRESSOR
NO .OF
All compressors used in the PTX series are MODEL COOLING CAPACITY STAGE
COMPRESSORS
hermetically scroll design type with a high energy PTX006 0-100 % 1
efficiency ratio, low noise and quite operation. All PTX007 0-100 % 1
PTX008 0-50-100% 2
compressors conform to AHRI 540 standard and PTX010 0-50-100% 2
are equipped with internal motor protection, factory PTX012 0-50-100% 2
PTX016 0-50-100% 2
installed crankcase heaters and rubber vibration PTX018 0-50-100% 2
isolators for quiet and efficient operation. Standard PTX020 0-50-100% 2
equipment includes a single compressor for (PTX006 PTX022 0-50-100% 2
PTX025 0-50-100% 2
& PTX007), dual compressors for (PTX008 - PTX035), PTX027 0-33-66-100 % 3
Triple Compressors for (PTX027 & PTX031) & PTX028 0-50-100% 2
PTX030 0-50-100% 2
quadruple compressors for (PTX036 - PTX105). Each PTX031 0-33-66-100 % 3
compressor has lockout devices to protect it from PTX035 0-50-100% 2
short cycling when tripped by safety controls. Each PTX036 0-25-50-100% 4
PTX040 0-25-50-100% 4
compressor has a separate condenser coil with its PTX045 0-25-50-100% 4
own safety controls. Sight glass, filter drier and under PTX050 0-25-50-100% 4
PTX060 0-25-50-100% 4
voltage monitor are standard on all models. PTX070 0-25-50-100% 4
PTX080 0-25-50-100% 4
PTX090 0-25-50-100% 4
PTX105 0-25-50-100% 4

C. AIR HANDLING SECTION


OVERVIEW: The air handling section is made to meet the compact
design requirements as seen in the Figure. This section contains the
evaporator coil, drip eliminator (optional), blower fan and motor, elec-
tric heater (optional) and 2" (50mm) filter rack.

AIR HANDLING COMPARTMENT: The air handling section is


provided with 1" (25mm) thick 3 Ibs/ft3 (48 Kg/m3) density
fiberglass insulation with single wall as standard & 2" (50mm) thick
3 Ibs/ft3 (48 Kg/m3) density fiberglass insulation with double painted
wall construction as an option. This will prevent condensation
from forming on the casing. Insulation meets the requirements of
NFPA 90A regulations for smoke and flame spread ratings and is
protected against deterioration and erosion from air currents. All
access panels, fixed panels, top and bottom panels are made
of galvanized steel, fastened and sealed with a rubber gasket to
prevent air and water leakage.
All access panels are fixed with 'C' clamp and free of screws, creates
flexibility and simple method of removing and re-installation the access
panels during maintenance.
Air Handling Section

8
Page 47 of 286
PRE FILTER RACK: Filters can be easily accessed through the filter access rack. 2" (50mm) disposable filters are
standard for all models.
As an option, Zamil Air Conditioners can offer the following:

* 2" aluminum filters.


* 2" pleated filter.

Disposable Filter Aluminum Filter Pleated Filter

EVAPORATOR COIL: The evaporator coil is fin and tube type,


constructed of seamless copper tube mechanically bonded to
enhanced aluminum fins for maximum heat transfer efficiency. The
fins have full self spacing collars, which completely cover each tube
while the staggered tube design improves the thermal efficiency.
Each coil equipped with a properly sized thermostatic (TXV)
expansion valve and distributor to ensure that equal refrigerant
is fed to all circuits as well as seamless copper headers. The
number of circuits is chosen to provide optimum heat transfer and
reasonable refrigerant velocity and pressure drop. End plates and
tube support sheets are made of 18 gauge galvanized steel, formed
to provide structural strength. Each evaporator coil is pressure
tested in the factory at 450 psig air pressure respectively which
conforms to AHRI 410. As options, Zamil Air Conditioners can offer:

1. Copper Fins
2. Pre-coated Aluminum Fins
3. ResisTec Coating for Aluminum or Copper fins

Evaporator Coil

DRAIN PAN: One of the primary functions of an air conditioning system is to remove water from the air it circulates,
therefore in order to remove the condensed water formed during de-humidification, a drain pan should be provided
under the evaporator (cooling) coil. The drain pan is mounted under evaporator coil on a positive sloped with single side
coupling connection to eliminate standing water and minimize bacteria growth. It’s fabricated from G-90 galvanized steel,
powder coated and the outer surface is insulated with 1/8'' closed cell insulation to prevent condensation. For additional
corrosion protection. As an option, a stainless steel drain pan or Pan Resistec coating can be provided.

9
Page 48 of 286
SUPPLY AIR FAN (BLOWER) Air Handling Section
• Double inlet, double width (DWDI) centrifugal fan.
• Forward fan with high quality and optimum selection.
• Backward fan is applicable to all models.
• All fan assemblies are statically and dynamically balanced
and every unit is vibration tested before shipment from factory.
• Fan drive by adjustable pitch pulleys and V-belt drive are standard.
• All fan and motor assemblies are isolated from the main unit on 1"
deflection rubber isolator mounts while 1" deflection spring isolators
is optional feature.
• Blower motor is mounted on an adjustable base and secured by a
locking device. Alignment and tensioning can be done in the field
without moving the motor from the base frame. Blower Section
BLOWER MOTOR:
Fan motors are of the Totally Enclosed Fan Cooled (TEFC) type, 2 poles or 4 poles with class "B" temperature rise for
class "F" insulation at 50oC ambient temperature and continuous duty. The motor’s index of protection is IP55, which
protects from dust and water. It is mounted on an adjustable base for proper alignment and belt tension adjustment.
Motors are suitable for use with a variable frequency drive. For motor sizing, all mechanical losses are considered in
relation to the safety factor.

Blower Motor

D. AIR COOLED CONDENSING SECTION


• Open design permits unrestricted condenser airflow, access to
compressors, refrigeration components and piping.
• High efficiency scroll compressors are standard.
• Each compressor has a separate condenser coil.
• Each refrigerant circuit is furnished with an accessible sight glass, filter
drier, high-pressure switch, low-pressure switch and expansion valve.
• Each compressor has a crankcase heater as standard.
• The compressor motor is provided with built-in thermal protection
during winding and an external overload relay for over-load protection.
• Vertical air discharge minimizes condenser fan noise. Three phase
condenser fan motors eliminate reverse rotation failures.

Condenser Section

10
Page 49 of 286
CONDENSER FAN
Condenser fans are constructed of die cast aluminum blades
/ hubs with direct driven motors. All fans are statically and
dynamically balanced to operate at minimum noise and
vibration. Fan blades are designed with appropriate pitch
angle which result in maximum airflow through the condenser
coil. Condenser fan, the impeller and motor are constructed
to form one integral unit. All fan motors are equipped with
IP54 ingress protection, three phase with class "F" winding
insulation and ball bearings for high ambient application.
These fan motors are of the totally enclosed air over type
(TEAO) with inherent thermal protection of the automatic reset
type. As options, Zamil Air Conditioners can offer: Condenser Fan

1. IP55 ingress protection


2. UL recognized condenser fan
3. Fan with protective coating

CONDENSER COIL: Condenser coil is of the fin and tube type, constructed of seamless (3/8" OD) inner grooved copper
tube, mechanically bonded to enhanced aluminum fins for maximum heat transfer efficiency. The fins have full self
spacing collars, which completely cover each tube while the staggered tube design improves the thermal efficiency. The
number of circuits is chosen to provide optimum heat transfer and reasonable refrigerant velocity and pressure drop.
End plates and tube support sheets are made of 18 gauge galvanized steel, formed to provide structural strength. Each
condenser coil is pressure tested in the factory at 650 psig air pressure respectively. As an option, Zamil Air Conditioners
can offer:

1. Copper Fins
2. Pre-coated Aluminum Fins
3. ResisTec Coating for Aluminum & Copper fins

CRANKCASE HEATERS: Compressors are equipped with crankcase heater. The compressor crankcase heater is
always on when the compressor is de-energized. This protects the system against refrigerant migration, oil dilution
and potential compressor failure.

FILTER DRIER: Refrigerant circuits are kept free of harmful moisture, sludge, acids and oil contaminating particles by
the filter drier. Sealed type is standard on all models while replaceable core filter drier is optional.

SIGHT GLASS: The moisture indicating sight glass is installed in the liquid line and its color indicator shows moisture
contents and provides a means for checking the system’s refrigerant charge.

11
Page 50 of 286
E. CONTROL PANEL
The standard control panel design is equivalent to
NEMA-4 (IP65) standard with hinged door for easy
access. It’s designed to be weather proof and to
prevent accumulation of dust. Internal power and
control wiring is neatly routed, properly anchored
and all wires are identified with cable markers as
per NEC standard applicable to HVAC units. Major
control devices fixed in the control panel are UL
approved and reliable in operation at high ambient
conditions for a long period of time.

1. Controller board
2. Control transformer
3. Auxiliary terminal block
4. Condenser fan motor contactors
5. External overload relay for condenser fan motor
(optional)
6. Condenser fan motor circuit breaker
7. Control fuse
8. High voltage terminal block
9. Earth terminal block
10. Compressor circuit breaker (optional)
11. Compressor contactor
12. Compressor overload relay
13. Blower motor circuit breaker
14. Blower motor contactor
15. Control relays
Control Panel
16. Voltage monitor relay (UVM)

F. ELECTRICAL SPECIFICATIONS 2. UNIT OPTIONAL FEATURES:


1. UNIT STANDARD FEATURES: • Volt free contacts
• Under voltage monitor (phase failure Relay) • Fan cycling switches
• Ferrules for wires • Compressor circuit breaker
• Labels for wires and components • Unit disconnect switch
• Warning labels • Circuit breaker for each condenser fan
• PVC cable channels • External overload for each condenser fan
• Low and high terminal blocks • Discharge temperature sensor
• Copper ground bus • Pump down solenoid valve
• Crankcase heater for compressors • Hot gas bypass valve
• 220 V- 1 Ph- 50/60 Hz control voltage • Anti-freeze protection
• Internal protection for compressors and condenser fans • 2 or 4 stage thermostat
• Control fuses • Current transformers
• Service lamp
• Dirty filter indications
• Economizer (free cooling system)
• Electric heaters

12
Page 51 of 286
G. MICROPROCESSOR CONTROLLER

These Packaged units are provided with a microprocessor control board incorporating the following features:

A. BALANCE LOADING OF COMPRESSORS: The unit’s electronic control automatically operates lead/lag sequence
of compressors. This is to load the compressors evenly over long periods of operation. If required however, compressor
#1 can also be set to always lead. In this case, compressor #1 always starts first and stops last. (Selectable through dip
switch setting on control board).

B. PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoid’s opening and compressor starting to equalize the pressure in the system necessary for compressor to start-up.
(Selectable through dip switch setting on control board).

C. COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for
compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermostat
due to load demand.

D. COMPRESSOR LOCK-OUT FUNCTION: If any of the unit’s safety control trips due to abnormal conditions, the
electronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a
qualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system conditions.

E. FAULT DIAGNOSTICS: In case of system fault, LED’s on the board emits a flashing signal indicating where the fault
is. This is to guide the service technician in identifying the fault.

F. DIGITAL I/O’s: The unit’s control board is compatible to operate with a DDC controller or any standard 24V a.c. thermo-
stat commercially available.

Inputs from DDC or thermostat to the controller for 2 stage models:


* G - Indoor fan operates
* Y1 - 1st stage cooling
* Y2 - 2nd stage cooling
* W1- 1st stage heating
* W2- 2nd stage heating

Outputs from controller to the unit’s controlled devices for 2 stage models:
6. Evaporator fan
7. Compressor 1
8. Compressor 2
9. Heater 1
10. Heater 2
11. Condenser fan 1
12. Condenser fan 2
13. Pump down solenoid 1 (P1)
14. Pump down solenoid 2 (P2)
15. Compressor 1 trip (X1)
16. Compressor 2 trip (X2)

13
Page 52 of 286
G. SEQUENTIAL CONTROL: With input signals from the thermostat or DDC, the motors in the equipment is started in
sequential order: supply fan – condenser fan – compressor; at a pre-determined timings.
Cooling starting sequence without Pump down Solenoid:

Cooling starting sequence without Pump down Solenoid:

Cooling starting sequence with Pump down Solenoid:

Heating starting sequence:

H. VOLTAGE MONITOR RELAY (UVM)


This device protects the motors in the unit from faults such as, under or over voltage, unbalance, phase loss and phase
reversal of the power supply. When the device senses any of these faults, it will cut-off the supply in the control circuit
thereby cutting off power to the motors. The voltage monitor will re-set automatically when power is brought back to
normal conditions.

TRIP & RE-SET VOLTAGE (% OF SET POINT)


LINE VOLTAGE
UNDER VOLTAGE OVER VOLTAGE PHASE IMBALANCE
RANGE
TRIP RE-SET TRIP RE-SET TRIP RE-SET
190 - 480 VAC 90% 93% 110% 107% 6% 4.5%

I. MOTOR OVERLOAD PROTECTION


Motors are provided with overload relays or a built-in thermal winding device or both for its overload protection.

14
Page 53 of 286
OPTIONAL ITEMS
A. MIXING BOX SECTION
When fresh air and return air mixing is required, mixing box is selected. The mixing box section is constructed of single
wall of heavy gauge galvanized steel with 1" thick (25mm) 3 Ibs/ft3 (48 Kg/m3) density fiberglass insulation. A double
skin (inner wall) made of galvanized steel with 2" (50mm) thick fiberglass insulation can be provided as an option.

B. BAG FILTER SECTION


The bag filter section is constructed of single wall heavy gauge galvanized
steel with 1" thick (25mm) 3 Ibs/ft3 (48 Kg/m3) density fiberglass
insulation. As an option, double skin (inner wall) made of galvanized
steel with 2" (50mm) thick fiberglass insulation can be provided. Per
filter media is an aluminum filter or pleated while the bag filter media is
synthetic micro-fiber with high efficiency air cleaning capability. As an
option the filter pressure gauge (Magnehelic manometer) can be ordered
with each filter section to help promote regular servicing and prevent
clogging.

Bag Filter

C. 4" MINI PLEATED FILTER:


As alterative solution to Bag Fitter , Zamil can offer high efficiency filter with compact design which is equivalent to bag
filter efficiency 4" mini pleated filter is designed to perform in difficult operating conditions .The filter media is made of
ultra-fine wet laid fibers.

Mini Pleated Filter

D. HOT GAS BYPASS CONTROL


Hot gas bypass control can be provided on the lead circuit to permit operation of the system down to 80% of its unloaded
capacity. Under low ambient conditions, it controls temperature by eliminating the need to cycle the compressor on and
off, ensuring narrow temperature swing and lengthening the life span of the compressor.

E. DRIP ELIMINATOR
The drip (moisture) eliminator is required when the velocity across the cooling coil is above 500 FPM. Eliminators are
made of plastic material encased within a galvanized steel frame which is placed between the coil and blower. This
arrangement eliminates water carry over with low pressure drop.

F. PUMP DOWN SOLENOID VALVE (PDS)


A pump down solenoid valve is installed in the liquid line. When the room thermostat is satisfied, the valve closes and the
compressor continues to run until a substantial portion of the refrigerant has been pumped out from the evaporator coil.
The low pressure switch will cycle off the compressor at a predetermined evaporator pressure.

15
Page 54 of 286
G. PRESSURE GAUGES
This option is used for monitoring and inspecting the suction and discharge pressure, it is installed on the condensing
section which allows inspection of refrigerant system performance.

H. UNIT GUARD
The guard is mounted on the condensing section only, which protects the condenser coil from physical damage.

I. BULK HEAD LIGHT


The bulk head lights can be equipped inside the fan section to provide light for servicing purpose.

J. MANUAL & MOTORIZED DAMPERS


The best way to control the return airflow with fresh air is by adding dampers on the mixing box section. These dampers
are heavy duty, multi-blade, low leakage and of opposed blade design. The dampers are prepared for either manual or
motorized operation (motor can be provided as an option).

Zamil dampers are entirely made of aluminum profiles with reinforced


polyamide accessories, the blades of the damper has airfoil shape
and perfectly controlled by gears that are spaced out by special
spacers located in the damper frame.

Zamil damper has an excellent anti-corrosion features as it is made


of aluminum and polyamide which make it light in weight and yet
extremely strong because of its well-engineered design. The
damper’s air tightness is enhanced by special gasket inserted in
both, the blades and the frame itself.

The outdoor air damper is equipped with a rain hood (factory


installed) as standard on the side of the unit as seen in Figure below.
The rain hood is constructed from galvanized steel, finished with the
same durable paint finish as the main unit and includes cleanable
aluminum filter to drain water away from the entering air stream.
Manual Dampers

K. ELECTRIC HEATERS Electric Heating Capacity Table


Electric heaters are of the resistance open-coil type and MODEL ELECTRIC HEATING NO .OF
CAPACITY (KW) HEATING STAGE
conform to the requirements of UL 573 or equivalent. Electrical PTX006 7.5,10,12.5,15 1
characteristics, kW capacities and number of stages are as PTX007 7.5,10,12.5,15 1
indicated. Thermal cutouts, fusible links and airflow switches are PTX008 10,15,20,20,25 2
PTX010 10,15,20,20,25 2
provided to shut-off power to heaters in case of airflow failure. PTX012 10,15,20,25,30 2
PTX016 10,15,20,25,30 2
PTX018 10,15,20,25,30 2
PTX020 10,15,20,30,40 2
PTX022 10,15,20,30,40 2
PTX025 10,15,20,30,40 2
PTX027 22.5,30,37.5,45 3
PTX028 20,30,40,50 2
PTX030 20,30,40,50 2
PTX031 22.5,30,37.5,45 3
PTX035 20,30,40,50 2
PTX036 20,30,40,50 4
PTX040 30,40,50,60 4
PTX045 30,40,50,60 4
PTX050 30,40,50,60 4
PTX060 30,40,50,60 4
PTX070 30,40,50,60 4
PTX080 40,50,60,80,100 4
Electric Heater PTX090 40,50,60,80,100 4
PTX105 40,50,60,80,100 4

16
Page 55 of 286
L. FAN CYCLE SWITCH HEAD PRESSURE CONTROL (FCS)
The capacity of air-cooled condensers varies with the difference between condensing temperature and condenser
entering air temperature (ambient temperature). It increases as this difference increases. For a given capacity, a drop in
the ambient temperature will lower the condensing temperatures and if the ambient temperature drops below a given limit,
head pressure control is required. Control shall be set for a minimum of 95°F (35°C) saturated refrigerant condensing
temperature, or to suit the specified application.

M. COMPRESSOR CIRCUIT BREAKER


This feature protects against compressor branch circuit fault. When tripped (manually or automatically), the breaker cut-
off the power supply to the compressor and disable its control through the breaker's auxiliary contacts.

N. ECONOMIZER/CO2 MONITORING
The economizer permits low cost operation by utilizing cool outdoor air for free cooling. A damper on the economizer
controls the amount of outdoor air and on closed position it provides a leak proof seal. It can easily be adjusted for 100%
outdoor air, 100% return air or any proportions of mixed air.

The economizer is operated either by a dry bulb outdoor air thermostat (OAT) or a solid state enthalpy controller (EC)
used to sense the outdoor air temperature. The unit is equipped with an electronic control board and the economizer uses
controller with a sensitive feedback system that carefully modulates the damper to allow correct percentage of fresh air
and return air. The economizer controller is designed to match with the Zamil electronic thermostat.

1. OUTDOOR AIR THERMOSTAT (OAT) ECONOMIZER CONTROL


Economizer operation is governed by outdoor temperature and unit OAT setting, as follows:

a. Outdoor Temperature > Outdoor Air Thermostat (OAT) setting:


If the thermostat calls for cooling, the economizer damper moves to minimum position, simultaneously blower motor,
compressor-1 & fan motors would start. If further cooling is required, compressor-2 also starts with a time delay. After the
thermostat is satisfied the compressors are staged out. The economizer controller moves the damper automatically to
closed position simultaneously the blower is also shutdown.

b. Outdoor Temperature < Outdoor Air Thermostat (OAT) setting:


As the cooling load would be low, the economizer controller will operate as stage-1 of cooling system first switching
ON the blower motor simultaneously modulating the damper in steps to required position, allowing the cool outside
air into indoor side. If further cooling is required compressor-1 & fan motors will switch ON as stage-2 of the system,
whereas compressor-2 is pulled out of service. As the room temperature is attained, economizer controls will cut-off the
compressor, fan motors simultaneously closing damper to fully closed position.

2. ENTHALPY SENSOR FOR ECONOMIZER CONTROL


The solid state enthalpy sensor is capable of accurately sensing outdoor air enthalpy content (temperature & humidity)
and controlling the economizer damper for the minimum heat content introduce to the evaporator coil. Thereby, providing
an efficient & economical system operation.

3. CO2 MONITOR
Indoor air quality (IAQ) is becoming more and more important, CO2 monitoring give an indication of the amount of CO2
inside a facility. Once it is exceeding a certain level it sends a signal to the control system demanding for fresh air to
replace the inside poor quality air. The control is responding in opening the damper and at the same time there is input in
the control for an exhaust relief fan externally connected to the unit as it purge the poor quality air.

17
Page 56 of 286
O. ULTRA VIOLET LIGHT FOR IMPROVED INDOOR AIR QUALITY
1. IMPROVED OVERALL INDOOR AIR QUALITY
When used for general IAQ control, UV FLOWTM products can successfully:
• Control fungi in HVAC systems to reduce or eliminate mold-related allergies.
• Prevent the development of different types of bacteria.
• Reduce the spread of cold and flu viruses and other airborne transmitted diseases.
• Eliminate odors and maintain a fresh air smell indoors.

UV FLOWTM Emitters pose no risk to components, equipment or inhabitants. Their


non-chemical energy kills organisms without producing secondary contamination
and costs little to operate.

2. SAVE ENERGY AND CUT COSTS UV Light


UV FLOWTM can reduce maintenance cost as UVC lights successfully eliminate the bio-film (dirt) that fouls surface of
heat exchangers - completely cleaning and continuously maintaining coils and drain pans to 'as new' conditions. This in
turn improves heat-transfer efficiency, coil pressure drop, and fan performance.

P. UNIT DISCONNECT SWITCH


A single non-fused disconnect switch is provided for disconnecting electrical power
at the unit. The disconnect switch is mounted internally on the control panel and
operated by an externally mounted handle.
Disconnect Switch
Q. ELECTRONIC THERMOSTAT
Electronic thermostat can control up to four cooling stages and four heating stages
depending on the number of compressors and electric heaters.

The thermostat normally displays room temperature and mode of operation. The
temperature can be set by up/down buttons for both cooling and heating cycles. The
thermostat also allows you to select continuous fan operation or have the fan on
intermittent operation with the equipment. The thermostat is best located about 1500
mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and should not
be exposed to direct light from lamps, sun etc. It should be in return air stream, away
from supply air registers/diffusers.

Electronic Thermostat
R. ANTI-CORROSIVE COATING
: A single component of aluminum impregnated coating applied on the fins of heat exchanging coils. The product
has been designed for Middle East climate conditions. A high chemical, abrasion and UV resistance has been proven in
both laboratories and on field environment. The coating can be applied at the factory as well as in the field for maintenance
or rejuvenation purposes.

Multi : A two component coating system that withstands the extreme climate conditions. The coating can be applied
to all metal parts of HVAC equipment; the piping, the compressors and grids might require a different pre- treatment and
layer build up. Please check ResisTec product information sheets, the heat exchangers can not be coated using this type.
The coating can be applied at the factory as well as in the field for maintenance or rejuvenation purposes.

Pan : A two pack self levelling coating, to be poured in drain pans and into other HVAC bottoms. The coating seals
all seams and bolt and creates a non-corrosive and hygienic surface that will last for the life time of the equipment. The
coating can be applied at the factory as well as in the field for maintenance or rejuvenation purposes.

18
Page 57 of 286
STANDARD FEATURES / OPTIONS
DESCRIPTION STANDARD FEATURES OPTIONS (FACTORY INSTALLED)
Scroll compressors
Compressor circuit breakers
Compressor overload protection
Compressor with Serivce Valves
Condenser fan - direct drive, propeller type & Fan Guard
Condenser motor circuit breakers
Condenser motor external overload
Forward curved blower
Backward curved blower
Blower motor -TEFC & IP55
Blower motor circuit breaker
Aluminum fin evaporator coils & condenser Coils
Pre-coated aluminum fin evaporator & condenser coils
Copper fin evaporator & condenser coils
ResisTec coating on Evpaorator coils or Condenser Coils
Top supply air direction -Configuration A
Front supply air direction -Configuration B
Side supply air direction -Configuration C
Bottom supply air direction -Configuration D
1'' single skin construction for Air Side Section
2'' double skin construction for Air Side Section
2" thick disposable filters
2" thick aluminum filters
2" thick pleated filters
Bag filter section (15" depth) (F9 )
Mini pleated filter section ( 4" depth) ( F9 )
Mixing box section ( Front /Top /Bottom /Side) Return air
Unit full guard
Drip eliminator
Stainless steel drain pan ( SS-304 )
Manual volume dampers
Supply volume damper
Back draft damper
Economizer control with outside air temperature sensor
Economizer control with enthalpy sensor
Economizer control with outside air temperature sensor & CO2 monitor
Economizer control with enthalpy sensor & CO2 monitor
UV light
Anti-ice sensor
Sight glass (moisture indicator)
Sealed type filter drier
Replaceable core filter drier
Hot gas bypass for Lead Refrgeation circuit
Condenser pressure relief valve
Pressure gauges
Pump down solenoid valve
Discharge gas muffler
Discharge gas sensor
Differential pressure switch for Filters
Magnehelic gauge for Filters
Belt guard
Extended regrease line
High/low pressure switch (Fixed type)
Fan cycling switch ( Fixed type)
UVM (Under Voltage Monitor)
Volt free contact
Bulkhead light
Non-fused disconnect switch
Electric heater
Multiple Stage Thermostat

19
Page 58 of 286
PHYSICAL DATA
MODEL NUMBER PTX006 PTX007 PTX008 PTX010 PTX012 PTX016 PTX018 PTX020

GROSS CAPACITY, TONS* 6.1 7.1 8.8 10.6 12.5 16.3 17.9 20.9

NUMBER OF REFRIGERATION CIRCUIT 1 1 2 2 2 2 2 2

TYPE HERMETIC SCROLL

OIL TYPE POE OIL

COMPRESSOR OIL PER SYSTEM (Liters) 1.24 1.77 1.24 1.24 1.24 1.77 1.77 3.25

REFRIGERANT R-410A

CHARGE PER SYSTEM (oz. ) 318 453 314 321 288 471 595 479

TYPE PROPELLER WITH DIRECT DRIVEN MOTOR

QTY. 2 2 2 2 2 2 2 2
CONDENSER FAN
MOTOR TYPE TOTALLY ENCLOSED AIR OVER TYPE (TEAO) , CLASS F INSULATION

MOTOR SIZE (KW) 0.29 0.29 0.45 0.45 1.15 1.15 1.15 2.1

TYPE INNER GROOVED TUBES & ENHANCED FINS

CONDENSER COIL FINS SPACING (FPI) 14 14 14 14 14 14 14 14

TOTAL FACE AREA (SQ. FT.) 24.6 24.6 33.2 33.2 40.4 48.9 48.9 48.9

TYPE INNER GROOVED TUBES & ENHANCED FINS

EVAPORATOR COIL FINS SPACING (FPI) 14 14 14 14 14 14 14 14

TOTAL FACE AREA (SQ. FT.) 8 8 12 12 16.7 16.7 16.7 25

TYPE DIDW CENTRIFUGAL FAN WITH V-BELT DRIVE

QTY. SINGLE FAN


EVAPORATOR
BLOWER MOTOR TYPE TOTALLY ENCLOSED FAN COOLED TYPE (TEFC) , CLASS F INSULATION & IP55
(FORWARD CURVED)
MOTOR KW - STD./ALT. 1.1/1.5/2.2 1.5/2.2/3.0 1.5/2.2/3.0 2.2/3.0/4.0 2.2/3.0/4.0 3.0/4.0/5.5 4.0/5.5 4.0/5.5/7.5

NOMINAL AIR FLOW, CFM 2500 2800 3500 4000 4500 5600 6400 8000

TYPE DIDW CENTRIFUGAL FAN WITH V-BELT DRIVE

QTY. SINGLE FAN


EVAPORATOR
BLOWER MOTOR TYPE TOTALLY ENCLOSED FAN COOLED TYPE (TEFC) , CLASS F INSULATION & IP55
(BACKWARD CURVED)
MOTOR KW - STD./ALT. 2.2/3.0 2.2/3.0/4.0 3.0/4.0 3.0/4.0/5.5 4.0/5.5 4.0/5.5/7.5 5.5/7.5 7.5/11.0

NOMINAL AIR FLOW, CFM 2500 2800 3500 4000 4500 5600 6400 8000

OPEN (PSIG) 650±15 650±15 650±15 650±15 650±15 650±15 650±15 650±15
HIGH PRESSURE
SWITCH
CLOSE (PSIG) 500±22 500±22 500±22 500±22 500±22 500±22 500±22 500±22

OPEN (PSIG) 50±7 50±7 50±7 50±7 50±7 50±7 50±7 50±7
LOW PRESSURE
SWITCH
CLOSE (PSIG) 90±7 90±7 90±7 90±7 90±7 90±7 90±7 90±7

SOUND PRESSURE LEVEL, dBA (1m /3m / 5m), ** 59.7 \ 53.7 \ 50.2 62.4 \ 56.3 \ 52.8 65.8 \ 59.8 \ 56.3 65.8 \ 59.8 \ 56.3 70.6 \ 64.6 \ 61 71.1 \ 65.1 \ 61.6 72.7 \ 66.7 \ 63.2 72.3 \ 66.2 \ 62.7

BASIC WEIGHT, KG - CONFIGURATION A,C &D*** 480 510 625 645 780 865 910 1025

BASIC WEIGHT, KG - CONFIGURATION B*** 480 480 625 645 850 935 980 1095

* COOLING CAPACITY @ 95° F DB OUTDOOR (AMBIENT) TEMPERATURE.


** BASED ON FREE FIELD AREA AT AHRI CONDITION . TOLERANCE: ± 2dBA.
*** BASIC WEiGHT INCLUDES SINGLE SKIN AHU SECTION , STANDARD MOTOR , STANDARD BLOWER FAN AND AL/CU COILS , FOR OTHER WEIGHT ANALYSIS , PLEASE REFER TO IOM.

20
Page 59 of 286
PHYSICAL DATA
MODEL NUMBER PTX022 PTX025 PTX027 PTX028 PTX030 PTX031 PTX035 PTX036

GROSS CAPACITY, TONS* 23.6 26.3 26.6 28.1 30.5 30.3 35.6 35.5

NUMBER OF REFRIGERATION CIRCUIT 2 2 3 2 2 3 2 4

TYPE HERMETIC SCROLL

OIL TYPE POE OIL

COMPRESSOR OIL PER SYSTEM (Liters) 3.25 3.25 1.77 3.25 3.25 3.25 3.25 1.77

REFRIGERANT R-410A

CHARGE PER SYSTEM (oz. ) 479 599 479 706/618 708 481 906 482

TYPE PROPELLER WITH DIRECT DRIVEN MOTOR

QTY. 2 2 3 4 4 3 4 4
CONDENSER FAN
MOTOR TYPE TOTALLY ENCLOSED AIR OVER TYPE (TEAO) , CLASS F INSULATION

MOTOR SIZE (KW) 2.1 2.1 1.15 1.15 1.15 1.15 1.15 1.15

TYPE INNER GROOVED TUBES & ENHANCED FINS

CONDENSER COIL FINS SPACING (FPI) 14 14 14 14 14 14 14 14

TOTAL FACE AREA (SQ. FT.) 48.9 48.9 73.3 69 72.3 73.3 97.8 97.8

TYPE INNER GROOVED TUBES & ENHANCED FINS

EVAPORATOR COIL FINS SPACING (FPI) 14 14 14 14 14 14 14 14

TOTAL FACE AREA (SQ. FT.) 25 25 25 25 25 25 25 25

TYPE DIDW CENTRIFUGAL FAN WITH V-BELT DRIVE

QTY. SINGLE FAN


EVAPORATOR
BLOWER MOTOR TYPE TOTALLY ENCLOSED FAN COOLED TYPE (TEFC) , CLASS F INSULATION & IP55
(FORWARD CURVED)
MOTOR KW - STD./ALT. 5.5/7.5 5.5/7.5/11.0 5.5/7.5/11.0 5.5/7.5/11.0 7.5/11.0 7.5/11.0 7.5/11.0/15.0 7.5/11.0/15.0

NOMINAL AIR FLOW, CFM 8500 9400 10600 10600 11400 11400 12500 12500

TYPE DIDW CENTRIFUGAL FAN WITH V-BELT DRIVE

QTY. SINGLE FAN


EVAPORATOR
BLOWER MOTOR TYPE TOTALLY ENCLOSED FAN COOLED TYPE (TEFC) , CLASS F INSULATION & IP55
(BACKWARD CURVED)
MOTOR KW - STD./ALT. 7.5/11.0 7.5/11.0/15.0 11.0/15.0 11.0/15.0 11.0/15.0 11.0/15.0 11.0/15.0/18.5 11.0/15.0/18.5

NOMINAL AIR FLOW, CFM 8500 9400 10600 10600 11400 11400 12500 12500

OPEN (PSIG) 650±15 650±15 650±15 650±15 650±15 650±15 650±15 650±15
HIGH PRESSURE
SWITCH
CLOSE (PSIG) 500±22 500±22 500±22 500±22 500±22 500±22 500±22 500±22

OPEN (PSIG) 50±7 50±7 50±7 50±7 50±7 50±7 50±7 50±7
LOW PRESSURE
SWITCH
CLOSE (PSIG) 90±7 90±7 90±7 90±7 90±7 90±7 90±7 90±7

SOUND PRESSURE LEVEL, dBA (1m /3m / 5m), ** 73.9 \ 67.9 \ 64.3 74.7 \ 68.7 \ 65.2 74.5 \ 68.5 \ 64.9 76.7 \ 70.7 \ 67.2 76.7 \ 70.7 \ 67.2 75.5 \ 69.5 \ 65.9 77.9 \ 71.9 \ 68.4 75.7 \ 69.7 \ 66.2

BASIC WEIGHT, KG - CONFIGURATION A,C &D*** 1050 1100 1310 1335 1360 1380 1450 1460

BASIC WEIGHT, KG - CONFIGURATION B*** 1125 1170 1380 1405 1430 1450 1520 1530

* COOLING CAPACITY @ 95° F DB OUTDOOR (AMBIENT) TEMPERATURE.


** BASED ON FREE FIELD AREA AT AHRI CONDITION . TOLERANCE: ± 2dBA
*** BASIC WEIGHT INCLUDES SINGLE SKIN AHU SECTION , STANDARD MOTOR , STANDARD BLOWER FAN AND AL/CU COILS , FOR OTHER WEIGHT ANALSIS , PLEASE REFER TO IOM

21
Page 60 of 286
PHYSICAL DATA
MODEL NUMBER PTX040 PTX045 PTX050 PTX060 PTX070 PTX080 PTX090 PTX105

GROSS CAPACITY, TONS* 39.9 46.9 51.5 59.3 69.6 80.2 89.9 107.2

NUMBER OF REFRIGERATION CIRCUIT 4 4 4 4 4 4 4 4

TYPE HERMETIC SCROLL

OIL TYPE POE OIL

COMPRESSOR OIL PER SYSTEM (Liters) 3.25 3.25 3.25 3.25 3.25 4.5/3.25 4.5 4.5

REFRIGERANT R-410A

CHARGE PER SYSTEM (oz. ) 609 619 625 831 843 974/723 986 1450

TYPE PROPELLER WITH DIRECT DRIVEN MOTOR

QTY. 4 4 6 6 6 8 8 8
CONDENSER FAN
MOTOR TYPE TOTALLY ENCLOSED AIR OVER TYPE (TEAO) , CLASS F INSULATION

MOTOR SIZE (KW) 1.15 2.1 1.15 1.15 2.1 2.1 2.1 2.1

TYPE INNER GROOVED TUBES & ENHANCED FINS

CONDENSER COIL FINS SPACING (FPI) 14 14 14 14 14 14 14 14

TOTAL FACE AREA (SQ. FT.) 97.8 97.8 131.6 131.6 131.6 170.3 195.5 238

TYPE INNER GROOVED TUBES & ENHANCED FINS

EVAPORATOR COIL FINS SPACING (FPI) 14 14 14 14 14 14 14 14

TOTAL FACE AREA (SQ. FT.) 37.5 37.5 37.5 58.6 58.6 67.2 67.2 67.2

TYPE DIDW CENTRIFUGAL FAN WITH V-BELT DRIVE

QTY. SINGLE FAN


EVAPORATOR
BLOWER MOTOR TYPE TOTALLY ENCLOSED FAN COOLED TYPE (TEFC) , CLASS F INSULATION & IP55
(FORWARD CURVED)
MOTOR KW - STD./ALT. 11.0/15.0 11.0/15.0 11.0/15.0/18.5 15.0/18.5 15.0/18.5/22.0 15.0/18.5/22.0/30.0 18.5/22.0/30.0 18.5/22.0/30.0

NOMINAL AIR FLOW, CFM 14500 15000 16500 19500 22000 27000 29000 31000

TYPE DIDW CENTRIFUGAL FAN WITH V-BELT DRIVE

QTY. SINGLE FAN


EVAPORATOR
BLOWER MOTOR TYPE TOTALLY ENCLOSED FAN COOLED TYPE (TEFC) , CLASS F INSULATION & IP55
(BACKWARD CURVED)
MOTOR KW - STD./ALT. 15.0/18.5 15.0/18.5/22.0 15.0/18.5/22.0 15.0/18.5/22.0/30.0 18.5/22.0/30.0 22.0/30.0/37.0 22.0/30.0/37.0 30.0/37.0/45.0

NOMINAL AIR FLOW, CFM 14500 15000 16500 19500 22000 27000 29000 31000

OPEN (PSIG) 650±15 650±15 650±15 650±15 650±15 650±15 650±15 650±15
HIGH PRESSURE
SWITCH
CLOSE (PSIG) 500±22 500±22 500±22 500±22 500±22 500±22 500±22 500±22

OPEN (PSIG) 50±7 50±7 50±7 50±7 50±7 50±7 50±7 50±7
LOW PRESSURE
SWITCH
CLOSE (PSIG) 90±7 90±7 90±7 90±7 90±7 90±7 90±7 90±7

SOUND PRESSURE LEVEL, dBA (1m /3m / 5m), ** 76.7 \ 70.7 \ 67.2 76.9 \ 70.9 \ 67.4 79.2 \ 73.2 \ 69.7 79.2 \ 73.2 \ 69.7 79.7 \ 73.7 \ 70.2 82.7 \ 76.7 \ 73.2 84.4 \ 78.4 \ 74.9 87.3 \ 81.3 \ 77.8

BASIC WEIGHT, KG - CONFIGURATION A,C &D*** 1910 1940 2085 2840 2890 3765 4165 4515

BASIC WEIGHT, KG - CONFIGURATION B*** 2015 2045 2190 3020 3070 4045 4445 4800

* COOLING CAPACITY @ 95° F DB OUTDOOR (AMBIENT) TEMPERATURE.


** BASED ON FREE FIELD AREA AT AHRI CONDITION . TOLERANCE: ± 2dBA
*** BASIC WEIGHT INCLUDES SINGLE SKIN AHU SECTION , STANDARD MOTOR , STANDARD BLOWER FAN AND AL/CU COILS , FOR OTHER WEIGHT ANALYSIS , PLEASE REFER TO IOM

22
Page 61 of 286
SELECTION PROCEDURE
Below example explains the procedure of using this catalogue for selecting the optimum PTX model in order to meet the
design requirements.

1. Determine cooling capacity requirements at design conditions


Data:

Design Ambient temperature : 115°F


Evaporator entering air temperature : 80°F DB / 67°F WB
Evaporator airflow : 19,500 CFM
Required cooling capacity : 630,000 BTUH
Sensible heat capacity : 470,000 BTUH
Altitude : 0 FT
External static pressure : 1.0 INCH WG.
Additional Accessories : 2" Aluminum Pre-Filter & 4" Mini Pleated final Filter
Power supply (V-Ph-Hz) : 380/400-3-60

2. Unit selection based on required cooling capacity


Enter cooling capacity performance data at condenser entering air temp. at 115°F and evaporator entering air temp.80°F
DB, 67°F WB, 19,500 CFM airflow. The PTX060 unit will give 634,000 BTUH cooling capacity (gross) and 481,900 BTUH
sensible heat capacity (gross).

3. Determine fan speed and power requirements at design conditions


Before entering the fan performance tables, calculate the summation of external static pressure for the required compo-
nents as follows, refer to air pressure drop sheet (page 66 )
External static pressure : 1.0 INCH WG.
2" Aluminum Filter (Medium Condition) : 0.36 INCH WG
4" Mini Pleated Filter (Medium Condition) : 1.01 INCH WG
2.37 INCH WG.

Enter fan performance table for PTX060 model. For 19,500 CFM and external static pressure of 2.37 INCH WG, it require
669 RPM and 14.1 motor power consumption (kW) wherein 15.0 KW motor will meet job requirements

4.To calculate leaving air conditions (see footnote for capacity tables)
DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM)
WBL = DBL – [DR (DBE – WBE)]
When sensible capacity approaches 1.0, especially at entering
DB higher than 80°F, find DBL in the same manner above, but
WBL is to be found from intersection of DBL Line on a psychometric
chart with the horizontal line of humidity ratio (W) where
(at SHR = 1), WL = WE.

5. Altitude correction factors for cooling capacity

ALTITUDE, FT. 2000 4000 6000 8000 10000


Total Capacity 0.98 0.96 0.93 0.90 0.88
FACTOR
Sensible Capacity 0.93 0.86 0.80 0.75 0.70

23
Page 62 of 286
COOLING CAPACITIES
Model No.: PTX006
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
2100/0.028 2500/0.037 2800/0.043
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 68.4 74.3 80.0 70.5 76.7 82.8 71.7 78.3 84.6
85 SC 65.0 53.1 44.5 69.1 58.1 48.0 70.3 61.7 50.7
kW 4.82 4.82 4.79 4.83 4.81 4.77 4.83 4.8 4.75
TC 65.5 71.1 76.5 67.4 73.3 78.9 68.6 74.7 80.4
95 SC 63.7 51.9 43.2 66.1 56.7 46.7 67.2 60.3 49.2
kW 5.29 5.29 5.31 5.29 5.3 5.33 5.29 5.3 5.33
TC 62.1 67.5 72.4 63.8 69.4 74.4 64.9 70.7 75.7
105 SC 60.9 50.4 41.7 62.6 55.2 45.1 63.6 58.8 47.5
kW 5.84 5.87 5.93 5.84 5.89 5.97 5.85 5.91 6
TC 58.2 63.4 67.9 59.8 65.0 69.7 60.8 66.0 -
115 SC 57.0 48.9 40.1 58.6 53.6 43.5 59.5 57.0 -
kW 6.49 6.55 6.63 6.5 6.57 6.67 6.51 6.59 -
TC 53.8 58.7 63.2 55.2 60.3 - 56.1 61.3 -
125 SC 52.7 47.0 38.4 54.1 51.8 - 55.0 55.4 -
kW 7.24 7.29 7.34 7.25 7.31 - 7.26 7.32 -

Model No.: PTX007


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
2400/0.021 2800/0.029 3100/0.033
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 81.3 87.8 93.8 83.3 90.1 96.3 84.7 91.7 97.8
85 SC 77.1 62.9 52.4 81.7 68.0 56.0 83.0 71.8 58.6
kW 5.54 5.67 5.8 5.57 5.72 5.87 5.59 5.75 5.91
TC 77.6 84.0 89.8 79.6 86.2 92.2 80.9 87.5 93.7
95 SC 75.4 61.3 50.9 78.0 66.5 54.6 79.3 70.2 57.2
kW 6.15 6.27 6.37 6.18 6.31 6.41 6.2 6.33 6.44
TC 73.7 79.8 85.5 75.5 81.8 87.8 76.7 83.2 89.1
105 SC 73.7 59.7 49.3 74.0 64.8 53.0 75.2 68.6 55.6
kW 6.84 6.96 7.03 6.88 6.98 7.05 6.89 7 7.06
TC 69.5 75.3 80.7 71.3 77.2 82.7 72.3 78.4 -
115 SC 68.2 57.9 47.6 69.8 63.0 51.2 70.8 66.7 -
kW 7.62 7.73 7.77 7.65 7.75 7.78 7.67 7.76 -
TC 65.1 70.5 75.4 66.5 72.1 - 67.4 73.1 -
125 SC 63.7 56.1 45.7 65.2 61.1 - 66.1 64.8 -
kW 8.49 8.59 8.62 8.52 8.6 - 8.53 8.61 -

Model No.: PTX008


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
3100/0.028 3500/0.034 4000/0.04
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 99.7 108.1 116.0 101.7 110.3 118.5 103.9 112.9 121.2
85 SC 95.5 77.9 65.0 99.7 82.7 68.4 101.8 88.8 72.7
kW 6.77 6.82 6.85 6.78 6.83 6.85 6.8 6.84 6.86
TC 95.5 103.5 110.9 97.5 105.6 113.2 99.4 107.9 115.5
95 SC 93.6 76.0 63.1 95.5 80.9 66.5 97.4 86.9 70.7
kW 7.57 7.64 7.69 7.59 7.65 7.7 7.6 7.67 7.72
TC 90.8 98.4 105.4 92.4 100.3 107.4 93.9 102.3 109.5
105 SC 89.0 74.0 61.1 90.6 78.9 64.5 92.1 84.8 68.6
kW 8.51 8.59 8.65 8.52 8.6 8.67 8.54 8.62 8.69
TC 85.4 92.7 99.4 86.9 94.5 101.2 88.7 96.2 103.3
115 SC 83.7 71.8 59.0 85.2 76.7 62.3 86.9 82.5 66.5
kW 9.57 9.66 9.73 9.59 9.67 9.75 9.61 9.69 9.77
TC 79.6 86.7 93.4 81.0 88.3 95.0 82.4 90.0 -
125 SC 78.0 69.5 56.9 79.4 74.4 60.2 80.8 80.2 -
kW 10.76 10.84 10.91 10.78 10.86 10.93 10.79 10.88 -
TC – Total Capacity (1000 Btuh) Gross kW – Compressor & Condenser Motor Power Input DBE – Dry Bulb Temp. (°F) of Air Entering Coil DBL – Dry Bulb Temp. (°F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (°F) of Air Entering Coil WBL – Wet Bulb Temp. (°F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800°F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

24
Page 63 of 286
COOLING CAPACITIES
Model No.: PTX010
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
3500/0.022 4000/0.028 4500/0.034
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 120.8 130.5 139.9 123.6 133.7 143.3 125.9 136.4 146.3
85 SC 113.6 92.8 77.6 122.5 99.3 82.2 123.4 105.6 86.8
kW 8.31 8.45 8.59 8.34 8.5 8.65 8.37 8.54 8.7
TC 115.0 124.6 133.4 117.7 127.5 136.6 119.8 129.9 139.3
95 SC 110.9 90.4 75.2 115.3 96.8 79.8 117.4 103.2 84.3
kW 9.3 9.47 9.63 9.34 9.51 9.69 9.37 9.56 9.74
TC 108.9 117.9 126.5 111.2 120.5 129.3 113.1 122.7 131.7
105 SC 108.2 87.7 72.7 109.0 94.1 77.2 110.9 100.4 81.6
kW 10.48 10.65 10.83 10.52 10.7 10.89 10.55 10.75 10.94
TC 102.0 110.8 118.9 104.2 113.2 121.4 105.9 115.1 -
115 SC 100.0 84.9 69.9 102.1 91.4 74.4 103.8 97.5 -
kW 11.83 12.01 12.17 11.87 12.05 12.23 11.9 12.09 -
TC 94.6 103.0 110.7 96.6 105.1 - 98.0 106.9 -
125 SC 92.7 81.9 67.0 94.6 88.2 - 96.1 94.5 -
kW 13.36 13.52 13.66 13.39 13.56 - 13.41 13.59 -

Model No.: PTX012


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
4000/0.018 4500/0.024 5000/0.029
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 141.5 154.0 166.3 144.5 157.6 170.4 147.1 160.8 174.0
85 SC 132.3 108.7 91.6 141.6 115.5 96.5 144.1 122.2 101.3
kW 10.72 10.68 10.58 10.72 10.66 10.54 10.71 10.64 10.49
TC 135.4 147.4 158.5 138.2 150.4 162.0 140.5 153.3 165.1
95 SC 129.5 106.0 88.7 135.5 112.6 93.4 137.7 119.2 98.1
kW 11.63 11.64 11.68 11.63 11.65 11.7 11.63 11.66 11.71
TC 128.3 139.6 149.9 130.8 142.4 152.7 133.1 144.8 155.2
105 SC 126.3 102.8 85.5 128.2 109.5 90.0 130.5 116.0 94.6
kW 12.73 12.81 12.95 12.74 12.84 13.01 12.75 12.87 13.07
TC 120.3 130.9 140.4 122.6 133.4 - 124.4 135.5 -
115 SC 117.9 99.4 82.0 120.1 106.0 - 121.9 112.4 -
kW 14.02 14.15 14.34 14.04 14.19 - 14.06 14.23 -
TC 111.2 121.6 - 113.1 123.7 - 115.0 125.5 -
125 SC 109.0 95.8 - 110.9 102.2 - 112.7 108.6 -
kW 15.51 15.62 - 15.53 15.64 - 15.55 15.66 -

Model No.: PTX016


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
4800/0.012 5600/0.019 6400/0.026
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 185.52 199.35 211.96 190.57 204.9 217.55 194.65 209.2 222.11
85 SC 166.6 136.8 114.9 181.4 147.5 122.3 190.8 157.8 129.5
kW 13.52 13.78 14.01 13.6 13.88 14.11 13.67 13.96 14.19
TC 177.15 191.03 204.09 182.03 196.4 209.82 186 200.88 214.38
95 SC 162.6 133.3 111.9 177.5 144.1 119.5 182.3 154.6 126.7
kW 14.8 15.07 15.31 14.88 15.16 15.42 14.95 15.24 15.51
TC 168.58 182.29 195.18 173 187.42 200.87 176.52 191.45 205.54
105 SC 158.7 129.7 108.5 169.5 140.5 116.2 173 150.9 123.6
kW 16.31 16.58 16.84 16.38 16.67 16.96 16.44 16.76 17.06
TC 158.75 172.72 185.44 163.24 177.47 190.48 166.76 181.18 -
115 SC 154.2 125.9 104.9 160 136.6 112.4 163.4 146.9 -
kW 18.02 18.31 18.59 18.1 18.4 18.72 18.16 18.49 -
TC 149.33 162.1 173.84 152.99 166.06 - 156.17 169.53 -
125 SC 146.3 121.6 100.6 149.9 132.1 - 153 142.5 -
kW 19.98 20.26 20.56 20.04 20.35 - 20.1 20.44 -
TC – Total Capacity (1000 Btuh) Gross kW – Compressor & Condenser Motor Power Input DBE – Dry Bulb Temp. (°F) of Air Entering Coil DBL – Dry Bulb Temp. (°F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (°F) of Air Entering Coil WBL – Wet Bulb Temp. (°F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800°F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

25
Page 64 of 286
COOLING CAPACITIES
Model No.: PTX018
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
5600/0.016 6400/0.024 7200/0.03
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 203.8 220.7 236.2 208.9 226.4 242.3 213.3 231.0 247.7
85 SC 187.3 154.0 129.3 202.1 164.7 136.9 209.1 174.9 144.4
kW 14.39 14.63 14.83 14.45 14.7 14.91 14.51 14.76 14.98
TC 195.0 210.7 225.5 199.4 215.9 231.2 203.6 220.4 235.9
95 SC 183.4 149.9 125.3 197.9 160.4 132.9 199.5 170.8 140.1
kW 15.79 16.05 16.27 15.85 16.12 16.35 15.91 16.19 16.42
TC 185.2 200.3 214.4 189.4 205.0 219.4 192.9 208.8 223.8
105 SC 179.0 145.7 121.2 185.6 156.2 128.5 189.1 166.3 135.8
kW 17.4 17.68 17.92 17.47 17.76 18 17.53 17.83 18.07
TC 174.5 189.1 202.8 178.5 193.4 207.2 181.0 197.0 -
115 SC 174.1 141.1 116.9 174.9 151.6 124.2 177.4 161.8 -
kW 19.23 19.52 19.76 19.3 19.6 19.84 19.35 19.66 -
TC 163.2 177.7 190.7 166.8 181.5 - 169.7 184.8 -
125 SC 160.0 136.7 112.5 163.4 147.0 - 166.3 157.2 -
kW 21.27 21.57 21.82 21.34 21.65 - 21.4 21.71 -

Model No.: PTX020


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
6800/0.019 8000/0.028 9200/0.033
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 236.7 255.6 271.8 243.3 262.2 278.7 248.5 267.6 283.9
85 SC 222.1 181.6 151.1 238.4 196.8 161.9 243.6 211.8 172.2
kW 18.16 18.43 18.62 18.25 18.51 18.67 18.32 18.57 18.71
TC 226.1 244.4 260.9 232.2 250.8 267.6 236.9 256.1 273.2
95 SC 217.3 177.0 147.1 227.5 192.4 157.9 232.2 207.4 168.4
kW 19.85 20.16 20.41 19.94 20.26 20.51 20.01 20.34 20.59
TC 214.5 232.3 248.9 220.0 238.6 255.5 224.5 243.7 -
105 SC 212.1 172.1 142.7 215.6 187.7 153.6 220.0 202.8 -
kW 21.85 22.18 22.45 21.94 22.28 22.56 22.01 22.36 -
TC 202.1 219.6 235.7 207.4 225.1 - 211.3 229.7 -
115 SC 198.0 167.1 137.9 203.3 182.5 - 207.0 197.5 -
kW 24.16 24.47 24.69 24.24 24.55 - 24.31 24.61 -
TC 189.0 205.5 220.4 193.5 210.5 - 197.2 214.6 -
125 SC 185.3 161.6 132.4 189.6 177.0 - 193.3 192.0 -
kW 26.76 26.98 27.01 26.83 27.01 - 26.88 27.02 -

Model No.: PTX022


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
7200/0.018 8500/0.027 9600/.032
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 267.3 288.1 308.3 275.2 297.0 318.1 280.7 303.4 324.9
85 SC 242.4 199.0 167.6 265.7 215.9 179.7 275.1 229.9 189.5
kW 20.84 21.2 21.49 20.96 21.33 21.62 21.04 21.42 21.71
TC 254.8 275.3 294.6 262.2 283.7 303.8 267.3 289.7 310.0
95 SC 236.6 193.7 162.3 260.0 210.7 174.4 261.9 224.6 184.1
kW 22.86 23.24 23.58 22.98 23.38 23.74 23.07 23.48 23.85
TC 240.9 261.0 279.4 247.8 268.3 287.3 252.7 273.9 293.0
105 SC 230.3 187.9 156.7 242.8 204.6 168.4 247.6 218.6 178.1
kW 25.26 25.67 26.06 25.38 25.82 26.24 25.47 25.93 26.37
TC 225.3 244.4 261.7 231.5 251.0 268.9 235.5 256.0 -
115 SC 223.2 181.3 150.1 226.9 197.8 161.9 230.8 211.8 -
kW 28.02 28.46 28.91 28.14 28.62 29.11 28.22 28.74 -
TC 208.0 225.7 241.8 213.3 231.4 - 216.7 235.6 -
125 SC 203.8 173.9 142.9 209.1 190.4 - 212.3 204.1 -
kW 31.14 31.62 32.14 31.25 31.79 - 31.34 31.92 -
TC – Total Capacity (1000 Btuh) Gross kW – Compressor & Condenser Motor Power Input DBE – Dry Bulb Temp. (°F) of Air Entering Coil DBL – Dry Bulb Temp. (°F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (°F) of Air Entering Coil WBL – Wet Bulb Temp. (°F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800°F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

26
Page 65 of 286
COOLING CAPACITIES
Model No.: PTX025
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
8000/0.015 9400/0.024 10800/0.03
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 299.1 322.2 342.9 307.6 331.3 352.6 314.8 339.0 360.4
85 SC 271.9 223.2 187.1 297.5 241.5 200.0 308.5 259.5 212.6
kW 23.02 23.57 24.06 23.2 23.78 24.3 23.35 23.96 24.49
TC 284.4 306.6 327.4 292.0 315.4 336.8 298.8 322.6 344.5
95 SC 265.1 216.8 181.2 290.5 235.3 194.2 292.8 253.2 206.8
kW 25.22 25.68 25.97 25.38 25.81 26.06 25.5 25.91 26.11
TC 268.8 290.3 311.5 275.7 298.7 321.0 281.9 305.7 -
105 SC 258.0 210.0 175.2 270.1 228.6 188.5 276.2 246.7 -
kW 27.67 28.03 28.19 27.79 28.11 28.22 27.88 28.16 -
TC 252.0 274.0 295.6 258.9 282.0 305.1 264.5 288.9 -
115 SC 250.4 203.5 169.3 253.7 222.1 182.9 259.2 240.3 -
kW 30.34 30.66 30.86 30.44 30.74 30.92 30.51 30.8 -
TC 235.0 257.7 279.4 241.7 265.3 - 246.6 272.0 -
125 SC 230.2 197.1 163.4 236.8 215.7 - 241.7 234.1 -
kW 33.25 33.67 34.12 33.35 33.82 - 33.43 33.95 -

Model No.: PTX027


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
9000/0.023 10600/0.032 11600/0.037
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 300.8 325.4 348.1 309.5 335.0 358.3 314.4 340.0 364.0
85 SC 284.8 232.6 194.0 303.3 252.7 208.1 308.1 264.7 216.9
kW 21.86 22.24 22.58 21.98 22.38 22.73 22.04 22.46 22.81
TC 287.5 310.6 332.2 295.6 319.4 341.8 299.7 324.4 347.0
95 SC 278.8 226.5 188.1 289.7 246.5 202.3 293.7 258.9 211.0
kW 24 24.42 24.78 24.13 24.57 24.94 24.2 24.64 25.02
TC 272.9 295.0 315.5 280.4 303.3 324.4 284.1 307.3 329.0
105 SC 272.4 220.3 182.0 274.8 240.4 196.2 278.4 252.3 204.7
kW 26.46 26.92 27.29 26.6 27.06 27.45 26.67 27.14 27.53
TC 257.3 278.6 298.4 263.7 285.8 306.1 267.4 289.7 -
115 SC 252.1 213.9 175.8 258.5 233.7 189.7 262.0 245.7 -
kW 29.25 29.72 30.11 29.38 29.87 30.26 29.45 29.94 -
TC 240.4 261.4 280.5 246.6 268.4 - 249.7 271.6 -
125 SC 235.6 207.3 169.5 241.7 227.3 - 244.7 239.0 -
kW 32.35 32.84 33.24 32.48 32.98 - 32.54 33.05 -

Model No.: PTX028


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
9000/0.022 10600/0.029 11600/0.034
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 317.7 343.4 366.4 327.5 353.4 377.5 332.6 359.1 383.6
85 SC 292.4 239.9 200.8 320.5 259.8 215.1 325.9 272.1 223.9
kW 24.19 24.74 25.25 24.38 24.96 25.5 24.47 25.08 25.63
TC 303.5 327.4 350.0 312.2 337.3 360.6 316.9 342.5 366.0
95 SC 286.1 233.3 194.7 306.0 253.6 209.0 310.6 265.8 217.6
kW 26.45 26.97 27.33 26.63 27.13 27.47 26.72 27.21 27.53
TC 287.5 311.0 332.9 295.6 319.8 342.7 299.7 324.4 348.0
105 SC 278.7 226.8 188.4 289.7 246.7 202.6 293.7 258.7 211.3
kW 29.01 29.46 29.71 29.16 29.57 29.77 29.23 29.63 29.79
TC 270.6 293.4 315.1 278.1 301.5 324.4 282.0 306.3 329.0
115 SC 265.2 219.8 181.9 272.5 239.6 196.2 276.4 252.0 204.6
kW 31.84 32.23 32.45 31.96 32.33 32.51 32.02 32.37 32.53
TC 252.6 275.1 296.4 259.1 282.6 304.7 262.8 286.7 -
125 SC 247.5 212.6 175.2 253.9 232.5 189.2 257.6 244.5 -
kW 34.93 35.35 35.7 35.05 35.47 35.84 35.1 35.54 -
TC – Total Capacity (1000 Btuh) Gross kW – Compressor & Condenser Motor Power Input DBE – Dry Bulb Temp. (°F) of Air Entering Coil DBL – Dry Bulb Temp. (°F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (°F) of Air Entering Coil WBL – Wet Bulb Temp. (°F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800°F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

27
Page 66 of 286
COOLING CAPACITIES
Model No.: PTX030
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
9700/0.019 11400/0.028 13000/0.034
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 344.9 372.6 398.2 355.2 384.0 410.9 363.1 392.8 420.3
85 SC 319.1 261.5 219.0 349.6 283.5 234.9 355.8 303.5 249.0
kW 25.89 26.53 27.09 26.1 26.78 27.35 26.27 26.97 27.55
TC 329.3 355.8 380.2 338.8 366.2 391.7 346.1 374.2 400.1
95 SC 312.1 254.6 212.2 332.0 276.6 228.0 339.2 296.4 241.9
kW 28.27 28.86 29.27 28.47 29.05 29.42 28.62 29.18 29.51
TC 311.9 337.3 360.9 320.4 346.9 371.0 327.4 354.5 -
105 SC 304.1 247.1 205.1 314.0 269.0 220.5 320.9 289.0 -
kW 30.97 31.49 31.79 31.14 31.63 31.86 31.27 31.72 -
TC 293.8 317.9 340.0 301.5 326.2 349.4 307.0 333.1 -
115 SC 287.9 239.5 197.4 295.5 261.0 212.9 300.9 281.0 -
kW 33.97 34.45 34.72 34.13 34.57 34.78 34.24 34.65 -
TC 273.9 296.9 318.2 280.7 304.4 - 286.1 310.5 -
125 SC 268.4 231.2 189.7 275.0 252.8 - 280.3 272.5 -
kW 37.29 37.81 38.2 37.44 37.95 - 37.54 38.06 -

Model No.: PTX031


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
9700/0.019 11400/0.027 13000/0.035
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 343.2 370.1 394.0 353.2 381.0 404.5 361.4 388.9 413.0
85 SC 318.3 260.4 217.4 348.6 282.5 232.5 354.2 302.0 246.5
kW 25.23 25.74 26.11 25.4 25.91 26.27 25.53 26.03 26.37
TC 327.1 353.7 377.3 336.8 363.8 387.8 343.8 371.4 396.2
95 SC 310.9 253.8 211.2 330.0 275.6 226.5 337.0 295.4 240.5
kW 27.92 28.48 28.95 28.1 28.68 29.16 28.24 28.83 29.31
TC 310.2 335.6 359.3 318.9 345.0 369.6 325.1 352.2 -
105 SC 303.4 246.4 204.5 312.5 268.2 220.0 318.6 288.0 -
kW 31.08 31.67 32.16 31.26 31.87 32.36 31.4 32.02 -
TC 292.1 316.2 339.2 299.5 325.2 348.4 305.9 332.0 -
115 SC 286.2 238.7 197.2 293.5 260.7 212.5 299.8 280.6 -
kW 34.7 35.26 35.65 34.86 35.42 35.78 34.99 35.53 -
TC 272.2 295.2 316.1 279.2 303.0 - 284.4 308.8 -
125 SC 266.7 230.5 188.9 273.6 252.3 - 278.7 272.0 -
kW 38.76 39.17 39.25 38.89 39.23 - 38.99 39.25 -

Model No.: PTX035


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
10600/0.012 12500/0.021 14400/0.028
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 401.8 432.4 461.2 414.5 446.5 475.9 424.8 457.6 488.6
85 SC 364.1 298.9 251.2 400.0 325.1 269.5 416.3 350.1 287.7
kW 29.42 30.25 31.17 29.7 30.66 31.72 29.94 31.03 32.22
TC 383.8 414.0 443.8 395.4 427.6 458.6 405.3 438.9 471.8
95 SC 355.8 291.2 244.5 391.5 317.3 263.1 397.2 342.8 281.7
kW 32.1 32.91 33.67 32.37 33.25 34.08 32.6 33.54 34.42
TC 364.4 394.3 423.7 375.3 407.5 438.7 384.6 418.3 450.7
105 SC 346.9 283.2 236.9 367.8 309.5 256.0 376.9 335.1 274.1
kW 35.17 35.92 36.54 35.42 36.19 36.83 35.62 36.41 37.06
TC 343.6 372.7 400.4 353.5 384.2 413.9 362.0 393.9 -
115 SC 337.5 274.4 228.2 346.4 300.3 247.0 354.8 325.7 -
kW 38.61 39.28 39.78 38.82 39.5 39.98 39 39.66 -
TC 321.0 347.9 372.0 330.1 357.1 - 336.9 365.2 -
125 SC 314.6 264.6 217.9 323.5 289.8 - 330.2 315.0 -
kW 42.39 42.99 43.4 42.58 43.16 - 42.72 43.29 -
TC – Total Capacity (1000 Btuh) Gross kW – Compressor & Condenser Motor Power Input DBE – Dry Bulb Temp. (°F) of Air Entering Coil DBL – Dry Bulb Temp. (°F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (°F) of Air Entering Coil WBL – Wet Bulb Temp. (°F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800°F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

28
Page 67 of 286
COOLING CAPACITIES
Model No.: PTX036
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
10600/0.013 12500/0.022 14400/0.029
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 399.5 432.0 462.1 412.9 446.5 478.1 423.5 458.8 491.1
85 SC 362.9 298.7 251.5 399.3 325.0 270.3 415.1 350.8 288.5
kW 29.12 29.63 30.08 29.31 29.84 30.31 29.46 30.02 30.5
TC 382.0 412.7 441.5 393.8 425.9 455.9 404.1 437.0 467.4
95 SC 354.8 290.7 243.7 390.6 316.7 262.2 396.0 342.2 280.0
kW 31.98 32.54 33.02 32.17 32.76 33.25 32.33 32.93 33.44
TC 362.6 392.0 419.6 373.6 404.3 432.7 382.8 413.9 443.2
105 SC 345.9 282.2 235.4 366.2 308.2 253.8 375.1 333.2 271.5
kW 35.27 35.87 36.37 35.46 36.08 36.6 35.63 36.26 36.78
TC 341.8 370.4 396.7 351.9 381.5 408.5 360.2 390.2 -
115 SC 336.6 273.5 226.9 344.8 299.3 245.0 353.0 324.2 -
kW 38.98 39.61 40.12 39.18 39.82 40.35 39.33 39.99 -
TC 319.6 347.4 372.9 329.0 357.7 - 336.3 365.8 -
125 SC 313.2 264.3 218.1 322.4 290.1 - 329.6 315.1 -
kW 43.11 43.76 44.29 43.3 43.97 - 43.46 44.14 -

Model No.: PTX040


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
12400/0.018 14500/0.027 16600/0.033
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 451.2 487.0 519.2 464.4 501.0 533.3 475.2 512.4 544.6
85 SC 410.8 337.4 282.9 448.1 364.2 301.5 465.7 389.9 319.5
kW 32.87 33.5 33.97 33.08 33.71 34.15 33.25 33.87 34.28
TC 431.2 465.5 497.3 442.9 479.0 511.4 452.8 489.4 522.4
95 SC 401.6 328.5 274.6 438.4 355.4 293.6 443.7 380.9 311.6
kW 36.37 37.04 37.6 36.58 37.27 37.84 36.75 37.46 38.03
TC 409.0 442.4 473.7 420.2 455.1 487.0 429.7 464.9 498.0
105 SC 391.4 319.0 265.8 411.7 346.0 284.7 421.1 371.6 303.0
kW 40.48 41.19 41.78 40.69 41.42 42.02 40.86 41.61 42.22
TC 385.8 418.2 448.0 395.5 429.3 460.7 404.3 438.3 470.8
115 SC 381.2 309.5 256.4 387.6 336.0 275.5 396.2 361.5 293.7
kW 45.22 45.91 46.42 45.42 46.11 46.59 45.58 46.26 46.72
TC 360.4 391.4 419.1 369.6 401.1 430.0 376.9 409.5 -
125 SC 353.2 298.9 245.9 362.2 325.1 264.6 369.3 350.9 -
kW 50.57 51.13 51.34 50.74 51.23 51.33 50.87 51.29 -

Model No.: PTX045


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
12800/0.011 15000/0.02 17300/0.027
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 528.7 569.9 608.9 545.1 588.5 629.4 560.1 605.3 647.4
85 SC 457.9 379.6 322.4 498.1 409.0 343.5 539.7 439.1 365.0
kW 40.64 41.28 41.79 40.88 41.52 42.03 41.08 41.73 42.24
TC 504.8 545.5 584.0 520.9 563.2 603.5 534.5 579.0 619.8
95 SC 446.4 369.1 312.6 487.3 398.5 333.8 528.2 428.7 354.9
kW 44.54 45.19 45.76 44.76 45.45 46.04 44.96 45.67 46.29
TC 478.0 518.3 555.3 492.8 534.5 573.0 505.8 549.0 587.7
105 SC 433.7 357.7 301.5 474.3 386.9 322.4 495.7 416.9 343.2
kW 49.18 49.87 50.51 49.4 50.14 50.83 49.6 50.38 51.12
TC 448.4 487.2 522.1 462.1 502.0 538.1 473.4 513.0 551.9
115 SC 420.0 344.7 288.8 460.6 374.0 309.6 463.9 402.9 330.6
kW 54.57 55.3 56.02 54.79 55.58 56.39 54.98 55.8 56.72
TC 416.1 451.7 484.6 427.5 465.0 498.6 437.2 475.5 -
125 SC 405.6 330.2 274.7 418.9 359.4 295.3 428.5 388.3 -
kW 60.69 61.47 62.31 60.9 61.77 62.71 61.08 62.05 -
TC – Total Capacity (1000 Btuh) Gross kW – Compressor & Condenser Motor Power Input DBE – Dry Bulb Temp. (°F) of Air Entering Coil DBL – Dry Bulb Temp. (°F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (°F) of Air Entering Coil WBL – Wet Bulb Temp. (°F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800°F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

29
Page 68 of 286
COOLING CAPACITIES
Model No.: PTX050
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
14000/0.008 16500/0.016 18800/0.022
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 583.2 628.8 669.6 603.2 649.5 691.6 617.7 665.9 708.5
85 SC 507.4 420.6 356.1 555.9 455.0 380.5 598.9 486.5 402.7
kW 43.82 44.81 45.74 44.19 45.27 46.26 44.48 45.62 46.67
TC 555.7 598.4 638.8 573.7 618.8 660.2 587.4 633.3 676.8
95 SC 494.1 407.4 343.9 542.3 442.5 368.7 585.6 473.4 391.0
kW 48.19 49.12 49.75 48.55 49.44 50.01 48.81 49.67 50.16
TC 525.8 567.5 607.9 542.1 586.6 628.9 554.6 600.7 645.2
105 SC 480.1 394.3 332.0 527.9 429.5 357.1 543.5 460.6 379.6
kW 53.09 53.87 54.28 53.39 54.09 54.39 53.6 54.22 54.43
TC 493.5 535.9 576.5 509.0 553.7 596.9 520.2 567.3 612.7
115 SC 465.0 381.4 320.0 498.8 416.3 345.3 509.8 447.6 367.9
kW 58.46 59.11 59.52 58.7 59.31 59.66 58.86 59.44 59.75
TC 460.6 503.2 544.5 474.5 520.0 564.8 485.8 533.8 -
125 SC 450.2 367.9 307.9 465.0 402.9 333.8 476.1 434.9 -
kW 64.29 64.99 65.74 64.49 65.28 66.13 64.65 65.52 -

Model No.: PTX060


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
16600/0.009 19500/0.018 22400/0.025
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 671.23 723.97 773.87 691.63 747.31 798.8 708.6 766.2 818.97
85 SC 590.3 488.1 413.5 644.5 527.7 441.6 697.5 566 468.7
kW 50.01 51.34 52.46 50.47 51.85 52.99 50.85 52.26 53.41
TC 640.13 691.59 738.76 659.35 711.81 760.92 674.44 729.29 779.33
95 SC 575.4 474.4 399.8 629.9 513 427.3 661 551.3 454.1
kW 54.88 56.15 57.03 55.32 56.56 57.36 55.67 56.86 57.59
TC 606.86 655.6 700.78 623.66 674.61 721.36 638.33 690.45 737.75
105 SC 559.9 459.3 385.2 613.5 498.2 412.7 625.6 536.2 439.2
kW 60.4 61.55 62.24 60.79 61.87 62.44 61.1 62.1 62.55
TC 570.69 617.46 659.94 586.27 634.03 678.43 599.29 648.69 -
115 SC 543.2 443.6 369.7 574.5 481.9 397 587.3 520.2 -
kW 66.52 67.59 68.23 66.87 67.87 68.42 67.13 68.07 -
TC 531.63 576.44 616.95 545.49 591.76 - 556.34 604.02 -
125 SC 525.5 427.1 353.7 534.6 465.7 - 545.2 503.1 -
kW 73.26 74.38 75.28 73.58 74.72 - 73.83 74.98 -

Model No.: PTX070


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
18700/0.007 22000/0.013 25300/0.021
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 785.5 844.7 900.8 811.0 872.7 930.7 831.2 895.0 955.6
85 SC 682.9 565.2 479.3 747.4 611.7 512.2 809.9 656.8 544.6
kW 62.33 63.89 65.58 62.87 64.66 66.61 63.35 65.36 67.55
TC 749.6 808.3 865.3 773.6 835.5 895.5 792.6 857.7 920.6
95 SC 665.6 549.5 465.2 730.1 596.4 498.9 776.8 642.0 531.7
kW 67.75 69.31 70.79 68.29 69.98 71.58 68.75 70.56 72.26
TC 712.2 770.2 825.8 733.3 795.4 854.7 751.8 816.0 879.1
105 SC 648.1 533.5 449.7 711.5 580.1 483.5 736.8 625.4 516.6
kW 73.95 75.44 76.69 74.46 76 77.28 74.87 76.46 77.76
TC 671.4 727.2 780.6 691.2 750.6 806.2 707.7 768.9 827.8
115 SC 629.1 515.4 432.4 677.3 562.1 465.6 693.6 606.9 498.1
kW 80.89 82.27 83.31 81.35 82.73 83.74 81.71 83.08 84.07
TC 628.2 679.4 726.5 645.1 698.2 746.4 659.2 714.0 762.3
125 SC 609.5 495.8 412.2 632.2 541.1 444.0 646.0 586.1 475.0
kW 88.55 89.79 90.65 88.94 90.15 90.96 89.25 90.43 91.18
TC – Total Capacity (1000 Btuh) Gross kW – Compressor & Condenser Motor Power Input DBE – Dry Bulb Temp. (°F) of Air Entering Coil DBL – Dry Bulb Temp. (°F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (°F) of Air Entering Coil WBL – Wet Bulb Temp. (°F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800°F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

30
Page 69 of 286
COOLING CAPACITIES
Model No.: PTX080
EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
23000/0.011 27000/0.02 31000/0.028
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 905.0 975.2 1041.5 932.9 1006.7 1074.6 956.3 1032.1 1101.3
85 SC 801.0 660.9 558.6 874.4 714.5 596.3 946.0 766.0 632.5
kW 74.09 75.61 77.02 74.61 76.24 77.75 75.06 76.78 78.38
TC 865.9 935.3 998.8 891.8 963.3 1030.3 913.1 987.8 1057.1
95 SC 782.6 644.3 541.9 855.7 696.7 579.7 894.9 748.4 616.7
kW 80.4 81.93 83.25 80.92 82.51 83.89 81.34 82.99 84.42
TC 823.8 890.4 952.1 847.1 917.7 981.3 867.2 939.4 1004.9
105 SC 763.2 625.5 524.1 835.5 678.7 561.8 849.8 729.7 597.9
kW 87.66 89.17 90.43 88.15 89.71 90.99 88.55 90.14 91.44
TC 777.7 840.6 899.5 798.8 865.0 924.2 817.2 884.3 944.7
115 SC 742.2 605.0 504.4 782.8 657.8 541.0 800.9 708.4 576.6
kW 95.85 97.36 98.57 96.32 97.85 99.06 96.7 98.25 99.45
TC 727.6 785.7 836.9 745.9 805.3 857.8 761.8 822.5 -
125 SC 719.8 583.1 481.2 731.0 634.4 517.4 746.6 685.2 -
kW 104.97 106.49 107.69 105.42 106.95 108.14 105.77 107.32 -

Model No.: PTX090


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
25000/0.008 29000/0.016 33000/0.022
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 1013.1 1093.6 1167.6 1043.8 1126.5 1204.2 1069.8 1156.0 1233.6
85 SC 892.4 738.4 624.8 969.7 793.8 665.0 1045.8 849.5 703.4
kW 82.4 83.94 85.11 82.94 84.48 85.61 83.38 84.91 85.99
TC 970.6 1048.1 1119.1 999.5 1078.7 1151.7 1022.4 1104.5 1178.0
95 SC 872.3 718.9 605.8 949.7 774.2 645.1 1001.9 828.5 683.0
kW 89.74 91.28 92.51 90.25 91.82 93.03 90.68 92.25 93.45
TC 923.8 998.2 1064.0 950.2 1025.9 1092.8 972.0 1048.7 1116.8
105 SC 850.3 698.1 584.6 927.4 753.0 623.2 952.6 806.7 661.1
kW 98.17 99.78 101.11 98.68 100.33 101.67 99.1 100.78 102.13
TC 872.6 941.8 1002.5 895.9 965.6 1027.7 914.5 985.7 1047.0
115 SC 826.9 674.8 561.3 878.0 728.7 599.5 896.2 782.1 636.1
kW 107.72 109.46 110.92 108.24 110.03 111.52 108.66 110.5 112.01
TC 814.8 879.0 933.5 835.3 898.9 955.1 851.2 917.0 -
125 SC 800.5 649.3 535.5 818.5 702.5 573.4 834.2 756.2 -
kW 118.43 120.33 121.95 118.95 120.92 122.57 119.39 121.4 -

Model No.: PTX105


EVAPORATOR AIRFLOW, CFM/DR
CONDENSER
26400/0.008 31000/0.01 35600/0.017
ENTERING AIR
EVAPORATOR ENTERING AIR, WBE (°F)
TEMP (°F)
62 67 71 62 67 71 62 67 71
TC 1200.9 1294.4 1382.3 1245.4 1342.6 1434.5 1282.8 1382.8 1476.8
85 SC 1005.1 840.0 719.4 1095.5 905.5 766.7 1184.1 969.3 811.9
kW 97.6 99.64 101.44 98.43 100.61 102.46 99.16 101.42 103.29
TC 1152.6 1242.9 1327.6 1192.7 1287.5 1375.6 122 7.0 1325.7 1415.3
95 SC 981.5 817.2 697.1 1070.3 882.1 743.7 1158.1 946.1 788.8
kW 106.66 108.72 110.6 107.48 109.69 111.7 108.16 110.51 112.64
TC 1097.4 1184.6 1266.1 1134.6 1227.0 1311.4 1166.5 1260.9 1347.7
105 SC 954.4 791.6 672.3 1043.2 857.0 719.0 1130.9 919.7 763.7
kW 117.46 119.59 121.6 118.25 120.57 122.77 118.93 121.42 123.78
TC 1036.4 1120.5 1198.8 1071.2 1158.5 1240.5 1099.8 1189.9 1273.9
115 SC 925.2 764.0 645.8 1014.3 828.5 692.2 1077.8 891.3 736.7
kW 129.99 132.26 134.42 130.79 133.26 135.6 131.47 134.12 136.61
TC 969.7 1050.7 1125.9 1000.9 1084.6 1162.8 1025.3 1112.8 1192.5
125 SC 894.1 734.8 617.7 982.8 798.6 663.4 1004.8 861.0 707.2
kW 144.32 146.75 148.94 145.13 147.72 150.01 145.81 148.52 150.91
TC – Total Capacity (1000 Btuh) Gross kW – Compressor & Condenser Motor Power Input DBE – Dry Bulb Temp. (°F) of Air Entering Coil DBL – Dry Bulb Temp. (°F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (°F) of Air Entering Coil WBL – Wet Bulb Temp. (°F) of Air Leaving Coil
NOTES: 1. Direct interpolation is permissible – Do not extrapolate.
2. Capacities above are based on DBE = 800°F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

31
Page 70 of 286
ELECTRICAL DATA
MODELS: PTX006 - PTX007

MODEL NUMBER
DESCRIPTION
PTX006 PTX007

VOLTAGE COMPRES-
FM COMPRES- ELECTRIC ELECTRIC
RANGE BM SOR BM
POWER SUPPLY (2 each) SOR HEATER HEATER
(see note) MCA MOCP MCA MOCP
(V-Ph-Hz)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA

0 0 34.1 50 0 0 40.5 60
7.5 18.8 34.1 50 7.5 18.8 40.5 60
1.1 11.5 10 25.1 36.8 50 1.5 5.7 10 25.1 40.5 60
12.5 31.4 44.6 50 12.5 31.4 46.3 60
15 37.7 52.4 60 15 37.7 54.2 60

0 0 35.5 50 0 0 43.2 60
7.5 18.8 35.5 50 7.5 18.8 43.2 60
1.5 4.3 10 25.1 38.5 50 2.2 8.4 10 25.1 43.2 60
12.5 31.4 46.3 50 12.5 31.4 49.7 60
15 37.7 54.2 60 15 37.7 57.6 60
230-3-60 207 253 1.2 21.9 136 25.9 164
0 0 38.2 60 0 0 46.3 70
7.5 18.8 38.2 60 7.5 18.8 46.3 70
2.2 5.7 10 25.1 41.9 60 3 11.5 10 25.1 46.3 70
12.5 31.4 49.7 60 12.5 31.4 53.6 70
15 37.7 57.6 60 15 37.7 61.4 70

0 0 41.3 60 0 0 49.5 70
7.5 18.8 41.3 60 7.5 18.8 49.5 70
3 8.4 10 25.1 45.8 60 4 14.7 10 25.1 49.8 70
12.5 31.4 53.6 60 12.5 31.4 57.6 70
15 37.7 61.4 70 15 37.7 65.4 70

0 0.0 18.3 25 0 0.0 21.7 35


7.5 11.4 18.3 25 7.5 11.4 21.7 35
1.1 2.6 10 15.2 22.2 25 1.5 3.3 10 15.2 23.1 35
12.5 19.0 27.0 30 12.5 19.0 27.9 35
15 22.8 31.7 35 15 22.8 32.6 35

0 0.0 19.0 30 0 0.0 23.3 35


7.5 11.4 19.0 30 7.5 11.4 23.3 35
1.5 3.3 10 15.2 23.1 30 2.2 4.9 10 15.2 25.1 35
12.5 19.0 27.9 30 12.5 19.0 29.9 35
15 22.8 32.6 35 15 22.8 34.6 35
380/400-3-60
342 418 0.7 11.4 83 13.6 73
(4 WIRE)
0 0.0 20.6 30 0 0.0 25.0 35
7.5 11.4 20.6 30 7.5 11.4 25.0 35
2.2 4.9 10 15.2 25.1 30 3 6.6 10 15.2 27.2 35
12.5 19.0 29.9 30 12.5 19.0 32.0 35
15 22.8 34.6 35 15 22.8 36.7 40

0 0.0 22.3 30 0 0.0 26.9 40


7.5 11.4 22.5 30 7.5 11.4 26.9 40
3 6.6 10 15.2 27.2 30 4 8.5 10 15.2 29.6 40
12.5 19.0 32.0 35 12.5 19.0 34.4 40
15 22.8 36.7 40 15 22.8 39.1 40

0 0.0 14.8 20 0 0.0 19.8 30


7.5 9.4 14.8 20 7.5 9.4 19.8 30
1.1 2.2 10 12.6 18.4 20 1.5 3 10 12.6 19.8 30
12.5 15.7 22.4 25 12.5 15.7 23.4 30
15 18.8 26.3 30 15 18.8 27.3 30

0 0.0 15.6 20 0 0.0 21.5 30


7.5 9.4 15.6 20 7.5 9.4 21.5 30
1.5 3 10 12.6 19.4 20 2.2 4.7 10 12.6 21.6 30
12.5 15.7 23.4 25 12.5 15.7 25.5 30
15 18.8 27.3 30 15 18.8 29.4 30
460-3-60 414 506 0.6 9.1 66.1 12.5 75
0 0.0 17.3 25 0 0.0 23.0 35
7.5 9.4 17.6 25 7.5 9.4 23.0 35
2.2 4.7 10 12.6 21.6 25 3 6.2 10 12.6 23.4 35
12.5 15.7 25.5 30 12.5 15.7 27.4 35
15 18.8 29.4 30 15 18.8 31.3 35

0 0.0 18.8 25 0 0.0 24.6 35


7.5 9.4 19.5 25 7.5 9.4 24.6 35
3 6.2 10 12.6 23.4 25 4 7.8 10 12.6 25.4 35
12.5 15.7 27.4 30 12.5 15.7 29.4 35
15 18.8 31.3 35 15 18.8 33.3 35

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection
NOTE: The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still operate beyond
this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken to improve voltages to within ±5% of
nominal voltage supply rating.

32
Page 71 of 286
ELECTRICAL DATA
MODELS: PTX008 - PTX010

MODEL NUMBER
DESCRIPTION
PTX008 PTX010
COMPRES-
VOLTAGE COMPRES-
FM ELECTRIC SOR ELECTRIC
RANGE SOR BM BM
POWER SUPPLY (2 each) HEATER (2 each) HEATER
(see note) (2 each) MCA MOCP MCA MOCP
(V-Ph-Hz)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA
0 0 45.4 60 0 0 51.1 60
10 25.1 45.4 60 10 25.1 51.1 60
1.5 5.7 15 37.7 54.2 60 2.2 8.4 15 37.7 57.6 60
20 50.2 69.9 70 20 50.2 73.3 80
25 62.8 85.6 90 25 62.8 88.9 90
0 0 48.1 60 0 0 54.2 70
10 25.1 48.1 60 10 25.1 54.2 70
2.2 8.4 15 37.7 57.6 60 3 11.5 15 37.7 61.4 70
20 50.2 73.3 80 20 50.2 77.1 80
25 62.8 88.9 90 25 62.8 92.8 100
230-3-60 207 253 1.75 16.1 136 17.4 110
0 0 51.2 60 0 0 57.4 70
10 25.1 51.2 60 10 25.1 57.4 70
3 11.5 15 37.7 61.4 70 4 14.7 15 37.7 65.4 70
20 50.2 77.1 80 20 50.2 81.1 90
25 62.8 92.8 100 25 62.8 96.8 100
0 0 54.4 70 0 0 63.1 80
10 25.1 54.4 70 10 25.1 63.1 80
4 14.7 15 37.7 65.4 70 5.5 19.8 15 37.7 71.8 80
20 50.2 81.1 90 20 50.2 87.5 90
25 62.8 96.8 100 25 62.8 103.2 110
0 0.0 27.6 35 0 0.0 32.3 40
10 15.2 27.6 35 10 15.2 32.3 40
1.5 3.3 15 22.8 32.6 35 2.2 4.9 15 22.8 34.6 40
20 30.4 42.1 45 20 30.4 44.1 45
25 38.0 51.6 60 25 38.0 53.6 60
0 0.0 29.2 35 0 0.0 34.0 45
10 15.2 29.2 35 10 15.2 34.0 45
2.2 4.9 15 22.8 34.6 35 3 6.6 15 22.8 36.7 45
20 30.4 44.1 45 20 30.4 46.2 50
380/400-3-60 25 38.0 53.6 60 25 38.0 55.7 60
342 418 1.01 9.9 64 11.3 65.6
(4 WIRE) 0 0.0 30.9 40 0.0 0.0 35.9 45
10 15.2 30.9 40 15.2 15.2 35.9 45
3 6.6 15 22.8 36.7 40 4 8.5 22.8 22.8 39.1 45
20 30.4 46.2 50 30.4 30.4 48.6 50
25 38.0 55.7 60 38.0 38.0 58.1 60
0 0.0 32.8 40 0.0 0.0 38.9 50
10 15.2 32.8 40 15.2 15.2 38.9 50
4 8.5 15 22.8 39.1 40 5.5 11.4 22.8 22.8 42.7 50
20 30.4 48.6 50 30.4 30.4 52.2 60
25 38.0 58.1 60 38.0 38.0 61.7 70
0 0.0 20.7 25 0 0.0 22.4 25
10 12.6 20.7 25 10 12.6 22.4 25
1.5 3 15 18.8 27.3 30 2.2 4.7 15 18.8 29.4 30
20 25.1 35.1 40 20 25.1 37.3 40
25 31.4 43.0 45 25 31.4 45.1 50
0 0.0 22.4 25 0 0.0 23.9 30
10 12.6 22.4 25 10 12.6 23.9 30
2.2 4.7 15 18.8 29.4 30 3 6.2 15 18.8 31.3 35
20 25.1 37.3 40 20 25.1 39.1 40
25 31.4 45.1 50 25 31.4 47.0 50
460-3-60 414 506 0.88 7.1 55 7.1 52
0 0.0 23.9 30 0 0.0 25.7 30
10 12.6 23.9 30 10 12.6 25.7 30
3 6.2 15 18.8 31.3 35 4 7.8 15 18.8 33.3 35
20 25.1 39.1 40 20 25.1 41.1 45
25 31.4 47.0 50 25 31.4 49.0 50
0 0.0 25.7 30 0 0.0 28.3 35
10 12.6 25.7 30 10 12.6 28.3 35
4 7.8 15 18.8 33.3 35 5.5 9.9 15 18.8 35.9 40
20 25.1 41.1 45 20 25.1 43.8 45
25 31.4 49.0 50 25 31.4 51.6 60

NOTE: Please refer to page 32 for note & legend.

33
Page 72 of 286
ELECTRICAL DATA
MODELS: PTX012 - PTX016

MODEL NUMBER
DESCRIPTION
PTX012 PTX016

VOLTAGE COMPRES- COMPRES-


FM ELECTRIC ELECTRIC
RANGE SOR BM SOR BM
POWER SUPPLY (2 each) HEATER HEATER
(see note) (2 each) MCA MOCP (2 each) MCA MOCP
(V-Ph-Hz)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA

0 0 67.9 80 0 0 84.5 110


10 25.1 67.9 80 10 25.1 84.5 110
15 37.7 67.9 80 15 37.7 84.5 110
2.2 8.4 3 11.5
20 50.2 73.3 80 20 50.2 84.5 110
25 62.8 88.9 90 25 62.8 92.8 110
30 75.3 104.6 110 30 75.3 108.5 110

0 0 71.0 90 0 0 87.7 110


10 25.1 71.0 90 10 25.1 87.7 110
15 37.7 71.0 90 15 37.7 87.7 110
3 11.5 4 14.7
20 50.2 77.1 90 20 50.2 87.7 110
25 62.8 92.8 100 25 62.8 96.8 110
30 75.3 108.5 110 30 75.3 112.5 125
230-3-60 207 253 5.1 21.9 136 27.9 164
0 0 74.2 90 0 0 92.8 110
10 25.1 74.2 90 10 25.1 92.8 110
15 37.7 74.2 90 15 37.7 92.8 110
4 14.7 5.5 19.8
20 50.2 81.1 90 20 50.2 92.8 110
25 62.8 96.8 100 25 62.8 103.2 110
30 75.3 112.5 125 30 75.3 118.9 125

0 0 79.3 100 0 0 98.5 125


10 25.1 79.3 100 10 25.1 98.5 125
15 37.7 79.3 100 15 37.7 98.5 125
5.5 19.8 7.5 25.5
20 50.2 87.5 100 20 50.2 98.5 125
25 62.8 103.2 110 25 62.8 110.3 125
30 75.3 118.9 125 30 75.3 126.0 150

0 0.0 36.6 45 0 0.0 47.5 60


10 15.2 36.6 45 10 15.2 47.5 60
15 22.8 36.6 45 15 22.8 47.5 60
2.2 4.9 3 6.6
20 30.4 44.1 45 20 30.4 47.5 60
25 38.0 53.6 60 25 38.0 55.7 60
30 45.6 63.1 70 30 45.6 65.2 70

0 0.0 38.3 45 0 0.0 49.4 60


10 15.2 38.3 45 10 15.2 49.4 60
15 22.8 38.3 45 15 22.8 49.4 60
3 6.6 4 8.5
20 30.4 46.2 50 20 30.4 49.4 60
25 38.0 55.7 60 25 38.0 58.1 60
380/400-3-60 30 45.6 65.2 70 30 45.6 67.6 70
342 418 3 11.4 83 15.5 94.3
(4 WIRE) 0 0.0 40.2 50 0 0.0 52.3 60
10 15.2 40.2 50 10 15.2 52.3 60
15 22.8 40.2 50 15 22.8 52.3 60
4 8.5 5.5 11.4
20 30.4 48.6 50 20 30.4 52.3 60
25 38.0 58.1 60 25 38.0 61.7 70
30 45.6 67.6 70 30 45.6 71.2 80

0 0.0 43.1 50 0 0.0 55.6 70


10 15.2 43.1 50 10 15.2 55.6 70
15 22.8 43.1 50 15 22.8 55.6 70
5.5 11.4 7.5 14.7
20 30.4 52.2 60 20 30.4 56.4 70
25 38.0 61.7 70 25 38.0 65.9 70
30 45.6 71.2 80 30 45.6 75.4 80

0.0 30.4 35 0 0.0 42.0 50


0 12.6 30.4 35 10 12.6 42.0 50
7.5 18.8 30.4 35 15 18.8 42.0 50
2.2 4.7 10 3 6.2
25.1 37.3 40 20 25.1 42.0 50
12.5 31.4 45.1 50 25 31.4 47.0 50
15 37.7 52.9 60 30 37.7 54.8 60

0 0.0 31.9 40 0 0.0 43.6 50


10 12.6 31.9 40 10 12.6 43.6 50
15 18.8 31.9 40 15 18.8 43.6 50
3 6.2 4 6.8
20 25.1 39.1 40 20 25.1 43.6 50
25 31.4 47.0 50 25 31.4 49.0 50
30 37.7 54.8 60 30 37.7 56.8 60
460-3-60 414 506 2.6 9.1 66.1 13.6 100
0 0.0 33.5 40 0 0.0 45.7 50
10 12.6 33.5 40 10 12.6 45.7 50
15 18.8 33.5 40 15 18.8 45.7 50
4 7.8 5.5 9.9
20 25.1 41.1 45 20 25.1 45.7 50
25 31.4 49.0 50 25 31.4 51.6 60
30 37.7 56.8 60 30 37.7 59.4 60

0 0.0 35.8 45 0 0.0 49.3 60


10 12.6 35.8 45 10 12.6 49.3 60
15 18.8 35.9 45 15 18.8 49.3 60
5.5 9.9 7.5 13.5
20 25.1 43.8 45 20 25.1 49.3 60
25 31.4 51.6 60 25 31.4 56.1 60
30 37.7 59.4 60 30 37.7 63.9 70

NOTE: Please refer to page 32 for note & legend.

34
Page 73 of 286
ELECTRICAL DATA
MODELS: PTX018 - PTX020

MODEL NUMBER
DESCRIPTION
PTX018 PTX020
COMPRES-
VOLTAGE COMPRES-
FM ELECTRIC SOR ELECTRIC
RANGE SOR BM BM
POWER SUPPLY (2 each) HEATER (2 each) HEATER
(see note) (2 each) MCA MOCP MCA MOCP
(V-Ph-Hz)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA

0 0 103.3 125
0 0 94.0 110 10 25.1 103.3 125
10 25.1 94.0 110 15 37.7 103.3 125
4 14.7 20 50.2 103.3 125
15 37.7 94.0 110 30 75.3 112.5 125
4 14.7
20 50.2 94.0 110 40 100.4 143.9 150
25 62.8 96.8 110
0 0 108.4 125
30 75.3 112.5 125 10 25.1 108.4 125
15 37.7 108.4 125
5.5 19.8 20 50.2 108.4 125
0 0 99.1 125 30 75.3 118.9 125
10 25.1 99.1 125 40 100.4 150.3 175
230-3-60 207 253 5.1 30.7 191 15 37.7 99.1 125 33.6 225
5.5 19.8 0 0 114.1 125
20 50.2 99.1 125 10 25.1 114.1 125
25 62.8 103.2 125 15 37.7 114.1 125
7.5 25.5
30 75.3 118.9 125 20 50.2 114.1 125
30 75.3 126.0 150
0 0 104.8 125 40 100.4 157.4 175
10 25.1 104.8 125 0 0 125.8 150
15 37.7 104.8 125 10 25.1 125.8 150
7.5 25.5 15 37.7 125.8 150
20 50.2 104.8 125 11 36.5 20 50.2 125.8 150
25 62.8 110.3 125 30 75.3 139.8 150
30 75.3 126.0 150 40 100.4 171.1 175

0 0.0 53.2 70 0 0.0 64.2 80


10 15.2 64.2 80
10 15.2 53.2 70 15 22.8 64.2 80
4 8.5
15 22.8 53.2 70 20 30.4 64.2 80
4 8.5 30 45.6 67.6 80
20 30.4 53.2 70
40 60.8 86.6 90
25 38.0 58.1 70
30 45.6 67.6 70 0 0.0 67.1 80
10 15.2 67.1 80
0 0.0 56.1 70 15 22.8 67.1 80
5.5 11.4 20 30.4 67.1 80
10 15.2 56.1 70 30 45.6 71.2 80
380/400-3-60 15 22.8 56.1 70 40 60.8 90.2 100
342 418 3 17.2 123 5.5 11.4 21.4 140
(4 WIRE) 20 30.4 56.1 70
0 0.0 70.4 90
25 38.0 61.7 70 10 15.2 70.4 90
30 45.6 71.2 80 15 22.8 70.4 90
7.5 14.7 20 30.4 70.4 90
30 45.6 75.4 90
0 0.0 59.4 70 40 60.8 94.3 100
10 15.2 59.4 70
15 22.8 59.4 70 0 0.0 76.8 90
7.5 14.7 10 15.2 76.8 90
20 30.4 59.4 70 15 22.8 76.8 90
11 21.1
25 38.0 65.9 70 20 30.4 76.8 90
30 45.6 75.4 80 30 45.6 83.4 90
40 60.8 102.3 110

0 0.0 45.2 50 0 0.0 57.2 70


10 12.6 45.2 50 10 12.6 57.2 70
15 18.8 57.2 70
15 18.8 45.2 50 4 7.8
4 7.8 20 25.1 57.2 70
20 25.1 45.2 50 30 37.7 57.2 70
25 31.4 49.0 50 40 50.2 72.5 80
30 37.7 56.8 60 0 0.0 59.3 70
10 12.6 59.3 70
0 0.0 47.3 60 15 18.8 59.3 70
5.5 9.9 20 25.1 59.3 70
10 12.6 47.3 60 30 37.7 59.4 70
15 18.8 47.3 60 40 50.2 75.1 80
5.5 9.9
460-3-60 414 506 2.6 14.3 100 20 25.1 47.3 60 18.6 114
25 31.4 51.6 60 0 0.0 62.9 80
10 12.6 62.9 80
30 37.7 59.4 60 15 18.8 62.9 80
7.5 13.5 20 25.1 62.9 80
30 37.7 63.9 80
0 0.0 50.9 60 40 50.2 79.6 80
10 12.6 50.9 60
0 0.0 68.4 80
15 18.8 50.9 60 10 12.6 68.4 80
7.5 13.5
20 25.1 50.9 60 15 18.8 68.4 80
11 18.9
25 31.4 56.1 60 20 25.1 68.4 80
30 37.7 70.7 80
30 37.7 63.9 70 40 50.2 86.4 90

NOTE: Please refer to page 32 for note & legend.

35
Page 74 of 286
ELECTRICAL DATA
MODELS: PTX022 - PTX025

MODEL NUMBER
DESCRIPTION
PTX022 PTX025
COMPRES-
VOLTAGE COMPRES-
FM ELECTRIC SOR ELECTRIC
RANGE SOR BM BM
POWER SUPPLY (2 each) HEATER (2 each) HEATER
(see note) (2 each) MCA MOCP MCA MOCP
(V-Ph-Hz)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA

0 0 116.3 150 0 0 153.4 200


10 25.1 116.3 150 10 25.1 153.4 200
15 37.7 153.4 200
15 37.7 116.3 150 5.5 19.8
5.5 19.8 20 50.2 153.4 200
20 50.2 116.3 150 30 75.3 153.4 200
30 75.3 118.9 150 40 100.4 153.4 200
40 100.4 150.3 175 0 0 159.1 200
0 0 122.0 150 10 25.1 159.1 200
15 37.7 159.1 200
10 25.1 122.0 150 7.5 25.5
20 50.2 159.1 200
15 37.7 122.0 150 30 75.3 159.1 200
11 25.5
20 50.2 122.0 150 40 100.4 159.1 200
230-3-60 207 253 6.5 37.1 239 53.6 245
30 75.3 126.0 150 0 0 170.1 200
40 100.4 157.4 175 10 25.1 170.1 200
15 37.7 170.1 200
11 36.5
20 50.2 170.1 200
0 0 133.0 150 30 75.3 170.1 200
10 25.1 133.0 150 40 100.4 171.1 200
15 37.7 133.0 150 0 0 183.2 225
7.5 36.5 10 25.1 183.2 225
20 50.2 133.0 150
30 75.3 139.8 150 15 37.7 183.2 225
15 49.6
20 50.2 183.2 225
40 100.4 171.1 175 30 75.3 183.2 225
40 100.4 187.5 225
0.0 0.0 78.4 100 0 0.0 78.4 100
15.2 15.2 78.4 100 10 15.2 78.4 100
15 22.8 78.4 100
22.8 22.8 78.4 100 5.5 11.4
5.5 11.4 20 30.4 78.4 100
30.4 30.4 78.4 100 30 45.6 78.4 100
45.6 45.6 78.4 100 40 60.8 90.2 100
60.8 60.8 90.2 100 0 0.0 81.7 100
0.0 0.0 81.7 100 10 15.2 81.7 100
15 22.8 81.7 100
15.2 15.2 81.7 100 7.5 14.7
20 30.4 81.7 100
22.8 22.8 81.7 100 30 45.6 81.7 100
7.5 14.7
380/400-3-60 30.4 30.4 81.7 100 40 60.8 94.3 100
342 418 3.78 26.4 145 26.4 145
(4 WIRE) 45.6 45.6 81.7 100 0 0.0 88.1 110
60.8 60.8 94.3 100 10 15.2 88.1 110
15 22.8 88.1 110
11 21.1
20 30.4 88.1 110
0.0 0.0 88.1 110 30 45.6 88.1 110
15.2 15.2 88.1 110 40 60.8 102.3 110
22.8 22.8 88.1 110 0 0.0 96.1 110
11 21.1 10 15.2 96.1 110
30.4 30.4 88.1 110
45.6 45.6 88.1 110 15 22.8 96.1 110
15 28.6
20 30.4 96.1 110
60.8 60.8 102.3 110 30 45.6 96.1 110
40 60.8 111.7 125
0 0.0 62.5 80 0 0.0 64.1 80
10 12.6 62.5 80 10 12.6 64.1 80
15 18.8 64.1 80
15 18.8 62.5 80 5.5 9.9
5.5 9.9 20 25.1 64.1 80
20 25.1 62.5 80 30 37.7 64.1 80
30 37.7 62.5 80 40 50.2 75.1 80
40 50.2 75.1 80 0 0.0 67.7 80
0 0.0 66.1 80 10 12.6 67.7 80
15 18.8 67.7 80
10 12.6 66.1 80 7.5 13.5
20 25.1 67.7 80
15 18.8 66.1 80 30 37.7 67.7 80
7.5 13.5
20 25.1 66.1 80 40 50.2 79.6 80
460-3-60 414 506 3.79 20 125 20.7 125
30 37.7 66.1 80 0 0.0 73.1 90
40 50.2 79.6 80 10 12.6 73.1 90
15 18.8 73.1 90
11 18.9
20 25.1 73.1 90
0 0.0 71.5 90 30 37.7 73.1 90
10 12.6 71.5 90 40 50.2 86.4 90
15 18.8 71.5 90 0 0.0 80.5 100
11 18.9 10 12.6 80.5 100
20 25.1 71.5 90
30 37.7 71.5 90 15 18.8 80.5 100
15 25.2
20 25.1 80.5 100
40 50.2 86.4 90 30 37.7 80.5 100
40 50.2 94.3 100

NOTE: Please refer to page 32 for note & legend.

36
Page 75 of 286
ELECTRICAL DATA
MODELS: PTX027 - PTX028

MODEL NUMBER
DESCRIPTION
PTX027 PTX028
FM COMPRES-
VOLTAGE (3 each for COMPRES-
ELECTRIC SOR ELECTRIC
RANGE PTX027 SOR BM BM
POWER SUPPLY HEATER (2 each) HEATER
(see note) & 4 for (3 each) MCA MOCP MCA MOCP
(V-Ph-Hz) PTX028)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA
0 0 134.9 150 0 0 165.2 200
22.5 56.5 134.9 150 20 50.2 165.2 200
5.5 19.8 30 75.3 134.9 150 5.5 19.8 30 75.3 165.2 200
37.5 94.1 142.4 150 40 100.4 165.2 200
45 113.0 165.9 175 50 125.5 181.6 200
0 0 140.6 150 0 0 170.9 225
22.5 56.5 140.6 150 20 50.2 170.9 225
7.5 25.5 30 75.3 140.6 150 7.5 25.5 30 75.3 170.9 225
37.5 94.1 149.5 150 40 100.4 170.9 225
45 113.0 173.1 175 57.1 300 50 125.5 188.8 225
230-3-60 207 253 5.1 30.7 191 & &
0 0 153.0 175 53.6 245 0 0 181.9 225
22.5 56.5 153.0 175 20 50.2 181.9 225
11 36.5 30 75.3 153.0 175 11 36.5 30 75.3 181.9 225
37.5 94.1 163.3 175 40 100.4 181.9 225
45 113.0 186.8 200 50 125.5 202.5 225
0 0 169.4 200 0 0 195.0 250
22.5 56.5 169.4 200 20 50.2 195.0 250
15 49.6 30 75.3 169.4 200 15 49.6 30 75.3 195.0 250
37.5 94.1 179.7 200 40 100.4 195.0 250
45 113.0 203.2 225 50 125.5 218.9 250
0 0.0 76.3 96.4 0 0.0 87.3 110
22.5 34.2 76.3 96.4 20 30.4 87.3 110
5.5 11.4 30 45.6 76.3 96.4 5.5 11.4 30 45.6 87.3 110
37.5 57.0 85.5 107.0 40 60.8 90.2 110
45 68.4 99.7 121.2 50 76.0 109.2 110
0 0.0 79.6 90 0 0.0 90.6 110
22.5 15.2 79.6 90 20 30.4 90.6 110
7.5 14.7 30 22.8 79.6 90 7.5 14.7 30 45.6 90.6 110
37.5 30.4 89.6 90 40 60.8 94.3 110
45 38.0 103.8 110 30 139 50 76.0 113.3 125
380/400-3-60
342 418 3 17.2 123 & &
(4 WIRE) 0 0.0 87.0 100 0 0.0 97.0 125
26.4 145
22.5 34.2 87.0 100 20 30.4 97.0 125
11 21.1 30 45.6 87.0 100 11 21.1 30 45.6 97.0 125
37.5 57.0 97.6 100 40 60.8 102.3 125
45 68.4 111.8 125 50 76.0 121.3 125
0 0.0 96.4 110 0 0.0 104.5 125
22.5 34.2 96.4 110 20 30.4 104.5 125
15 28.6 30 45.6 96.4 110 15 28.6 30 45.6 104.5 125
37.5 57.0 107.0 110 40 60.8 111.7 125
45 68.4 121.2 125 50 76.0 130.7 150
0 0.0 64.2 70 0 0.0 73.1 90
22.5 28.2 64.2 70 20 25.1 73.1 90
5.5 9.9 30 37.7 64.2 70 5.5 9.9 30 37.7 73.1 90
37.5 47.1 71.2 80 40 50.2 75.1 90
45 56.5 83.0 90 50 62.8 90.8 100
0 0.0 67.8 80 0 0.0 76.7 100
22.5 28.2 67.8 80 20 25.1 76.7 100
7.5 13.5 30 37.7 67.8 80 7.5 13.5 30 37.7 76.7 100
37.5 47.1 75.7 80 40 50.2 79.6 100
45 56.5 87.5 90 25.7 150 50 62.8 95.3 100
460-3-60 414 506 2.6 14.3 100 & &
0 0.0 67.8 90 20.7 125 0 0.0 82.1 100
22.5 28.2 67.8 90 20 25.1 82.1 100
11 18.9 30 37.7 67.8 90 11 18.9 30 37.7 82.1 100
37.5 47.1 75.7 90 40 50.2 86.4 100
45 56.5 87.5 100 50 62.8 102.1 110
0 0.0 82.2 30 0 0.0 88.4 110
22.5 28.2 82.2 30 20 25.1 88.4 110
15 25.2 30 37.7 82.2 35 15 25.2 30 37.7 88.4 110
37.5 47.1 90.3 45 40 50.2 94.3 110
45 56.5 102.1 50 50 62.8 109.9 110

NOTE: Please refer to page 32 for note & legend.

37
Page 76 of 286
ELECTRICAL DATA
MODELS: PTX030 - PTX031

MODEL NUMBER
DESCRIPTION
PTX030 PTX031
FM
VOLTAGE (4 each for COMPRES- COMPRES-
ELECTRIC ELECTRIC
RANGE PTX030 SOR BM SOR BM
POWER SUPPLY HEATER HEATER
(see note) & 3 for (2 each) MCA MOCP (3 each) MCA MOCP
(V-Ph-Hz) PTX031)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA

0 0 174.4 225 0 0 150.0 175


20 50.2 174.4 225 22.5 50.2 150.0 175
7.5 25.5 30 75.3 174.4 225 7.5 25.5 30 75.3 150.0 175
40 100.4 174.4 225 37.5 100.4 150.0 175
50 125.5 188.8 225 45 100.4 173.1 175

0 0 185.4 225 0 0 161.7 175


20 50.2 185.4 225 22.5 50.2 161.7 175
230-3-60 207 253 5.1 57.1 300 11 36.5 30 75.3 185.4 225 33.6 225 11 36.5 30 75.3 161.7 175
40 100.4 185.4 225 37.5 100.4 163.3 175
50 125.5 202.5 225 45 100.4 186.8 200

0 0 198.5 250 0 0 178.1 225


20 50.2 198.5 250 22.5 50.2 178.1 225
15 49.6 30 75.3 198.5 250 15 49.6 30 75.3 178.1 225
40 100.4 198.5 250 37.5 100.4 179.7 225
50 125.5 218.9 250 45 100.4 203.2 225

0 0.0 94.2 110 0 0.0 93.3 110


20 30.4 94.2 110 22.5 30.4 93.3 110
7.5 14.7 30 45.6 94.2 110 7.5 14.7 30 45.6 93.3 110
40 60.8 94.3 110 37.5 60.8 93.3 110
50 76.0 113.3 125 45 60.8 103.8 110

0 0.0 100.6 125 0 0.0 99.7 110


20 30.4 100.6 125 22.5 30.4 99.7 110
380/400-3-60
342 418 3 30 139 11 21.1 30 45.6 100.6 125 21.4 140 11 21.1 30 45.6 99.7 110
(4 WIRE)
40 60.8 102.3 125 37.5 60.8 99.7 110
50 76.0 121.3 125 45 60.8 111.8 110

0 0.0 108.1 125 0 0.0 109.0 125


20 30.4 108.1 125 22.5 30.4 109.0 125
15 28.6 30 45.6 108.1 125 15 28.6 30 45.6 109.0 125
40 60.8 111.7 125 37.5 60.8 109.0 125
50 76.0 130.7 150 45 60.8 121.2 125

0 0.0 81.7 100 0 0.0 87.2 100


20 25.1 81.7 100 22.5 25.1 87.2 100
7.5 13.5 30 37.7 81.7 100 7.5 13.5 30 37.7 87.2 100
40 50.2 81.7 100 37.5 50.2 87.2 100
50 62.8 95.3 100 45 50.2 87.2 100
0 0.0 43.6 50
0 0.0 87.1 110
10 12.6 43.6 50
20 25.1 87.1 110
15 18.8 43.6 50
460-3-60 414 506 2.6 25.7 150 11 18.9 30 37.7 87.1 110 18.6 114 11 18.9
20 25.1 43.6 50
40 50.2 87.1 110
25 31.4 49.0 50
50 62.8 102.1 110
30 37.7 56.8 60
0 0.0 93.4 110 0 0.0 95.1 110
20 25.1 93.4 110 22.5 25.1 95.1 110
15 25.2 30 37.7 93.4 110 15 25.2 30 37.7 95.1 110
40 50.2 94.3 110 37.5 50.2 95.1 110
50 62.8 109.9 110 45 50.2 102.0 110

NOTE: Please refer to page 32 for note & legend.

38
Page 77 of 286
ELECTRICAL DATA
MODELS: PTX035 - PTX036

MODEL NUMBER
DESCRIPTION
PTX035 PTX036
COMPRES-
VOLTAGE COMPRES-
FM ELECTRIC SOR ELECTRIC
RANGE SOR BM BM
POWER SUPPLY (4 each) HEATER (4 each) HEATER
(see note) (2 each) MCA MOCP MCA MOCP
(V-Ph-Hz)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA
0 0 185.6 225 0 0 176.4 200
20 50.2 185.6 225 20 50.2 176.4 200
7.5 25.5 30 75.3 185.6 225 7.5 25.5 30 75.3 176.4 200
40 100.4 185.6 225 40 100.4 176.4 200
50 125.5 188.8 225 50 125.5 188.8 200
0 0 196.6 250 0 0 188.8 225
20 50.2 196.6 250 20 50.2 188.8 225
11 36.5 30 75.3 196.6 250 11 36.5 30 75.3 188.8 225
40 100.4 196.6 250 40 100.4 188.8 225
50 125.5 202.5 250 50 125.5 202.5 225
230-3-60 207 253 5.1 62.1 340 30.7 191
0 0 209.7 250 0 0 205.2 250
20 50.2 209.7 250 20 50.2 205.2 250
15 49.6 30 75.3 209.7 250 15 49.6 30 75.3 205.2 250
40 100.4 209.7 250 40 100.4 205.2 250
50 125.5 218.9 250 50 125.5 218.9 250
0 0 223.2 250 0 0 221.8 250
20 50.2 223.2 250 20 50.2 221.8 250
18.5 62.9 30 75.3 223.2 250 18.5 62.9 30 75.3 221.8 250
40 100.4 223.2 250 40 100.4 221.8 250
50 125.5 235.5 250 50 125.5 235.5 250
0 0.0 112.0 125 0 0.0 99.8 110
20 30.4 112.0 125 20 30.4 99.8 110
7.5 14.7 30 45.6 112.0 125 7.5 14.7 30 45.6 99.8 110
40 60.8 112.0 125 40 60.8 99.8 110
50 76.0 113.3 125 50 76.0 113.3 125
0 0.0 118.4 150 0 0.0 107.2 110
20 30.4 118.4 150 20 30.4 107.2 110
11 21.1 30 45.6 118.4 150 11 21.1 30 45.6 107.2 110
40 60.8 118.4 150 40 60.8 107.2 110
380/400-3-60 50 76.0 121.3 150 50 76.0 121.3 125
342 418 3 37.9 196 17.2 123
(4 WIRE) 0 0.0 125.9 150 0 0.0 116.6 125
20 30.4 125.9 150 20 30.4 116.6 125
15 28.6 30 45.6 125.9 150 15 28.6 30 45.6 116.6 125
40 60.8 125.9 150 40 60.8 116.6 125
50 76.0 130.7 150 50 76.0 130.7 150
0 0.0 133.6 150 0 0.0 126.2 150
20 30.4 133.6 150 20 30.4 126.2 150
18.5 36.3 30 45.6 133.6 150 18.5 36.3 30 45.6 126.2 150
40 60.8 133.6 150 40 60.8 126.2 150
50 76.0 140.3 150 50 76.0 140.3 150
0 0.0 91.4 110 0 0.0 84.7 90
20 25.1 91.4 110 20 25.1 84.7 90
7.5 13.5 30 37.7 91.4 110 7.5 13.5 30 37.7 84.7 90
40 50.2 91.4 110 40 50.2 84.7 90
50 62.8 95.3 110 50 62.8 95.3 100
0 0.0 96.8 125 0 0.0 91.2 110
20 25.1 96.8 125 20 25.1 91.2 110
11 18.9 30 37.7 96.8 125 11 18.9 30 37.7 91.2 110
40 50.2 96.8 125 40 50.2 91.2 110
50 62.8 102.1 125 50 62.8 102.1 110
460-3-60 414 506 2.6 30 179 14.3 100
0 0.0 103.1 125 0 0.0 99.1 110
20 25.1 103.1 125 20 25.1 99.1 110
15 25.2 30 37.7 103.1 125 15 25.2 30 37.7 99.1 110
40 50.2 103.1 125 40 50.2 99.1 110
50 62.8 109.9 125 50 62.8 109.9 110
0 0.0 106.4 125 0 0.0 103.2 125
20 25.1 106.4 125 20 25.1 103.2 125
18.5 28.5 30 37.7 106.4 125 18.5 28.5 30 37.7 103.2 125
40 50.2 106.4 125 40 50.2 103.2 125
50 62.8 114.1 125 50 62.8 114.1 125

NOTE: Please refer to page 32 for note & legend.

39
Page 78 of 286
ELECTRICAL DATA
MODELS: PTX040 - PTX045

MODEL NUMBER
DESCRIPTION
PTX040 PTX045
COMPRES-
VOLTAGE COMPRES-
FM ELECTRIC SOR ELECTRIC
RANGE SOR BM BM
POWER SUPPLY (4 each) HEATER (4 each) HEATER
(see note) (4 each) MCA MOCP MCA MOCP
(V-Ph-Hz)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA

0 0 200.4 225 0 0 220.2 250


30 75.3 220.2 250
30 75.3 200.4 225 11 36.5 40 100.4 220.2 250
11 36.5 40 100.4 200.4 225 50 125.5 220.2 250
50 125.5 202.5 225 60 150.6 233.9 250

60 150.6 233.9 250 0 0 236.4 250


30 75.3 236.4 250
0 0 216.8 250 15 49.6 40 100.4 236.4 250
5.1 50 125.5 236.4 250
30 75.3 216.8 250 60 150.6 250.3 300
(6.5
230-3-60 207 253 33.6 225 37.1 239
FOR 15 49.6 40 100.4 216.8 250 0 0 253.0 300
PTX045) 30 75.3 253.0 300
50 125.5 218.9 250 18.5 62.9 40 100.4 253.0 300
60 150.6 250.3 300 50 125.5 253.0 300
60 150.6 266.9 300
0 0 233.4 250 0 0 266.7 300
30 75.3 233.4 250 30 75.3 266.7 300
18.5 62.9 40 100.4 233.4 250 22 73.8 40 100.4 266.7 300
50 125.5 235.5 250 50 125.5 266.7 300
60 150.6 266.9 300 60 150.6 280.5 300
0 0.0 124.1 125 0 0.0 148.4 150
30 45.6 148.4 150
30 45.6 124.1 125 11 21.1 40 60.8 148.4 150
11 21.1 40 60.8 124.1 125 50 76.0 148.4 150
60 91.2 148.4 150
50 76.0 124.1 125
0 0.0 156.5 175
60 91.2 140.3 150
30 45.6 156.5 175
0 0.0 133.4 150 15 28.6 40 60.8 156.5 175
3 50 76.0 156.5 175
30 45.6 133.4 150 60 91.2 156.5 175
380/400-3-60 (3.78
342 418 21.4 140 15 28.6 40 60.8 133.4 150 26.4 145
(4 WIRE) FOR 0 0.0 166.1 200
PTX045) 50 76.0 133.4 150 30 45.6 166.1 200
60 91.2 149.7 150 18.5 36.3 40 60.8 166.1 200
50 76.0 166.1 200
0 0.0 143.0 175 60 91.2 166.1 200
30 45.6 143.0 175 0 0.0 174.0 200
18.5 36.3 40 60.8 143.0 175 30 45.6 174.0 200
22 42.6 40 60.8 174.0 200
50 76.0 143.0 175
50 76.0 174.0 200
60 91.2 159.3 175 60 91.2 174.0 200
0 0.0 104.4 125 0 0.0 119.1 125
30 37.7 119.1 125
30 37.7 108.4 125
11 18.9 40 50.2 119.1 125
11 18.9 40 50.2 108.4 125 50 62.8 119.1 125
50 62.8 108.4 125 60 75.3 119.1 125
60 75.3 117.8 125 0 0.0 126.7 150
30 37.7 126.7 150
0 0.0 116.3 125
15 25.2 40 50.2 126.7 150
2.6 30 37.7 116.3 125 50 62.8 126.7 150
(3.79 60 75.3 126.7 150
460-3-60 342 418 18.6 114 15 25.2 40 50.2 116.3 125 20 125
FOR 0 0.0 130.8 150
PTX045) 50 62.8 116.3 125 30 37.7 130.8 150
18.5 28.5 40 50.2 130.8 150
60 75.3 125.6 150
50 62.8 130.8 150
0 0.0 120.4 125 60 75.3 130.8 150
30 37.7 120.4 125 0 0.0 137.4 150
18.5 28.5 40 50.2 120.4 125 30 37.7 137.4 150
22 33.8 40 50.2 137.4 150
50 62.8 120.4 125
50 62.8 137.4 150
60 75.3 129.8 150 60 75.3 137.4 150

NOTE: Please refer to page 32 for note & legend.

40
Page 79 of 286
ELECTRICAL DATA
MODELS: PTX050 - PTX060

MODEL NUMBER
DESCRIPTION
PTX050 PTX060
COMPRES-
VOLTAGE COMPRES-
FM ELECTRIC SOR ELECTRIC
RANGE SOR BM BM
POWER SUPPLY (6 each) HEATER (4 each) HEATER
(see note) (4 each) MCA MOCP MCA MOCP
(V-Ph-Hz)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA
0 0 294.9 300 0 0 322.9 350
30 75.3 294.9 300 30 75.3 322.9 350
11 36.5 40 100.4 294.9 300 15 49.6 40 100.4 322.9 350
50 125.5 294.9 300 50 125.5 322.9 350
60 150.6 294.9 300 60 150.6 322.9 350
0 0 308.0 350 0 0 337.6 400
30 75.3 308.0 350 30 75.3 337.6 400
15 49.6 40 100.4 308.0 350 18.5 62.9 40 100.4 337.6 400
50 125.5 308.0 350 50 125.5 337.6 400
60 150.6 308.0 350 60 150.6 337.6 400
230-3-60 207 253 5.1 53.6 245 57.1 300
0 0 323.6 250 0 0 351.3 400
30 75.3 323.6 250 30 75.3 351.3 400
18.5 62.9 40 100.4 323.6 250 22 73.8 40 100.4 351.3 400
50 125.5 323.6 250 50 125.5 351.3 400
60 150.6 323.6 250 60 150.6 351.3 400
0 0 337.3 400 0 0 375.8 450
30 75.3 337.3 400 30 75.3 375.8 450
22 73.8 40 100.4 337.3 400 30 93.4 40 100.4 375.8 450
50 125.5 337.3 400 50 125.5 375.8 450
60 150.6 337.3 400 60 150.6 375.8 450
0 0.0 151.3 175 0 0.0 174.1 200
30 45.6 151.3 175 30 45.6 174.1 200
11 21.1 40 60.8 151.3 175 15 28.6 40 60.8 174.1 200
50 76.0 151.3 175 50 76.0 174.1 200
60 91.2 151.3 175 60 91.2 174.1 200
0 0.0 159.4 175 0 0.0 183.4 200
30 45.6 159.4 175 30 45.6 183.4 200
15 28.6 40 60.8 159.4 175 18.5 36.3 40 60.8 183.4 200
50 76.0 159.4 175 50 76.0 183.4 200
380/400-3-60 60 91.2 159.4 175 60 91.2 183.4 200
342 418 3 26.4 145 30 139
(4 WIRE) 0 0.0 169.0 200 0 0.0 191.3 225
30 45.6 169.0 200 30 45.6 191.3 225
18.5 36.3 40 60.8 169.0 200 22 42.6 40 60.8 191.3 225
50 76.0 169.0 200 50 76.0 191.3 225
60 91.2 169.0 200 60 91.2 191.3 225
0 0.0 176.9 200 0 0.0 205.4 250
30 45.6 176.9 200 30 45.6 205.4 250
22 42.6 40 60.8 176.9 200 30 53.9 40 60.8 205.4 250
50 76.0 176.9 200 50 76.0 205.4 250
60 91.2 176.9 200 60 91.2 205.4 250
0 0.0 122.5 125 0 0.0 150.0 175
30 37.7 122.5 125 30 37.7 150.0 175
11 18.9 40 50.2 122.5 125 15 25.2 40 50.2 150.0 175
50 62.8 122.5 125 50 62.8 150.0 175
60 75.3 122.5 125 60 75.3 150.0 175
0 0.0 129.9 150 0 0.0 154.0 175
30 37.7 129.9 150 30 37.7 154.0 175
15 25.2 40 50.2 129.9 150 18.5 28.5 40 50.2 154.0 175
50 62.8 129.9 150 50 62.8 154.0 175
60 75.3 129.9 150 60 75.3 154.0 175
460-3-60 414 506 2.6 20.7 125 25.7 150
0 0.0 134.0 150 0 0.0 160.7 175
30 37.7 134.0 150 30 37.7 160.7 175
18.5 28.5 40 50.2 134.0 150 22 33.8 40 50.2 160.7 175
50 62.8 134.0 150 50 62.8 160.7 175
60 75.3 134.0 150 60 75.3 160.7 175
0 0.0 140.7 150 0 0.0 174.4 200
30 37.7 140.7 150 30 37.7 174.4 200
22 33.8 40 50.2 140.7 150 30 44.8 40 50.2 174.4 200
50 62.8 140.7 150 50 62.8 174.4 200
60 75.3 140.7 150 60 75.3 174.4 200
NOTE: Please refer to page 32 for note & legend.

41
Page 80 of 286
ELECTRICAL DATA
MODELS: PTX070 - PTX080

MODEL NUMBER
DESCRIPTION
PTX070 PTX080
FM COMPRES-
VOLTAGE (6 each for COMPRES-
ELECTRIC SOR ELECTRIC
RANGE PTX070 SOR BM BM
POWER SUPPLY HEATER (4 each) HEATER
(see note) & 8 for (4 each) MCA MOCP MCA MOCP
(V-Ph-Hz) PTX080)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA

0 0 352.5 400 0 0 407.4 450


40 100.4 407.4 450
30 75.3 352.5 400 50 125.5 407.4 450
15 49.6 60 150.6 407.4 450
15 49.6 40 100.4 352.5 400
80 200.8 407.4 450
50 125.5 352.5 400 100 251.0 407.4 450
60 150.6 352.5 400 0 0 420.7 500
40 100.4 420.7 500
0 0 366.0 400 50 125.5 420.7 500
18.5 62.9 60 150.6 420.7 500
50 125.5 366.0 400
80 200.8 420.7 500
18.5 62.9 60 150.6 366.0 400 100 251.0 420.7 500
80 200.8 366.0 400 0 0 431.6 500
100 251.0 392.4 400 80.7 538 40 100.4 431.6 500
230-3-60 207 253 6.5 62.1 340 & & 22 73.8 50 125.5 431.6 500
0 0 379.7 450 60 150.6 431.6 500
62.1 340 80 200.8 431.6 500
50 125.5 379.7 450 100 251.0 431.6 500
22 73.8 60 150.6 379.7 450 0 0 454.4 500
80 200.8 379.7 450 40 100.4 454.4 500
30 93.4 50 125.5 454.4 500
100 251.0 406.0 450 60 150.6 454.4 500
80 200.8 454.4 500
0 0 404.2 450 100 251.0 454.4 500
50 125.5 404.2 450 0 0 482.6 500
40 100.4 482.6 500
30 93.4 60 150.6 404.2 450 50 125.5 482.6 500
80 200.8 404.2 450 37 116 60 150.6 482.6 500
100 251.0 430.5 450 80 200.8 482.6 500
100 251.0 482.6 500
0 0.0 212.4 250 0 0.0 223.1 250
40 60.8 259.7 300
30 45.6 212.4 250 50 76.0 259.7 300
15 28.6 60 91.2 259.7 300
15 28.6 40 60.8 212.4 250
80 121.6 259.7 300
50 76.0 212.4 250 100 151.9 259.7 300
60 91.2 212.4 250 0 0.0 269.3 300
40 60.8 269.3 300
0 0.0 220.1 250 50 76.0 269.3 300
18.5 36.3 60 91.2 269.3 300
50 76.0 220.1 250
80 121.6 269.3 300
18.5 36.3 60 91.2 220.1 250 100 151.9 269.3 300
80 121.6 220.1 250 0 0.0 277.2 300
100 151.9 235.3 250 39.3 290 40 60.8 277.2 300
380/400-3-60 50 76.0 277.2 300
342 418 3.78 37.9 196 0 0.0 227.5 250 & & 22 42.6 60 91.2 277.2 300
(4 WIRE)
37.9 196 80 121.6 277.2 300
50 76.0 227.5 250
100 151.9 277.2 300
22 42.6 60 91.2 227.5 250 0 0.0 291.3 300
80 121.6 227.5 250 40 60.8 291.3 300
100 151.9 243.2 250 30 53.9 50 76.0 291.3 300
60 91.2 291.3 300
80 121.6 291.3 300
0 0.0 241.7 250 100 151.9 291.3 300
50 76.0 241.7 250 0 0.0 307.6 350
30 53.9 60 91.2 241.7 250 40 60.8 307.6 350
37 66.9 50 76.0 307.6 350
80 121.6 241.7 250 60 91.2 307.6 350
100 151.9 257.3 300 80 121.6 307.6 350
100 151.9 307.6 350
0 0.0 175.4 200 0 0.0 192.7 225
40 50.2 192.7 225
30 37.7 175.4 200 50 62.8 192.7 225
15 25.2 60 75.3 192.7 225
15 25.2 40 50.2 175.4 200
80 100.4 192.7 225
50 62.8 175.4 200 100 125.5 192.7 225
60 75.3 175.4 200 0 0.0 196.0 225
40 50.2 196.0 225
0 0.0 178.7 200 50 62.8 196.0 225
18.5 28.5 60 75.3 196.0 225
50 62.8 178.7 200
80 100.4 196.0 225
18.5 28.5 60 75.3 178.7 200 100 125.5 196.0 225
80 100.4 178.7 200 0 0.0 201.3 225
100 125.5 192.5 200 34.3 229 40 50.2 201.3 225
460-3-60 414 506 3.79 30 179 & & 22 33.8 50 62.8 201.3 225
0 0.0 185.0 200 60 75.3 201.3 225
30 179 80 100.4 201.3 225
50 62.8 185.0 200 100 125.5 201.3 225
22 33.8 60 75.3 185.0 200 0 0.0 214.9 250
80 100.4 185.0 200 40 50.2 214.9 250
30 44.8 50 62.8 214.9 250
100 125.5 199.1 200 60 75.3 214.9 250
80 100.4 214.9 250
0 0.0 198.7 225 100 125.5 214.9 250
50 62.8 198.7 225 0 0.0 228.0 250
40 50.2 228.0 250
30 44.8 60 75.3 198.7 225 50 62.8 228.0 250
37 55.3 60 75.3 228.0 250
80 100.4 198.7 225
100 125.5 212.9 225 80 100.4 228.0 250
100 125.5 228.0 250

NOTE: Please refer to page 32 for note & legend.

42
Page 81 of 286
ELECTRICAL DATA
MODELS: PTX090 - PTX105

MODEL NUMBER
DESCRIPTION
PTX090 PTX105
COMPRES-
VOLTAGE COMPRES-
FM ELECTRIC SOR ELECTRIC
RANGE SOR BM BM
POWER SUPPLY (8 each) HEATER (4 each) HEATER
(see note) (4 each) MCA MOCP MCA MOCP
(V-Ph-Hz)

Min. Max. FLA RLA LRA kW FLA Nom. kW FLA RLA LRA kW FLA Nom. kW FLA

0 0 457.9 500 0 0 518.7 600


40 100.4 518.7 600
40 100.4 457.9 500 50 125.5 518.7 600
50 125.5 457.9 500 18.5 62.9 60 150.6 518.7 600
18.5 62.9
60 150.6 457.9 500 80 200.8 518.7 600
80 200.8 457.9 500 100 251.0 518.7 600
100 251.0 457.9 500 0 0 529.6 529.6
40 100.4 529.6 529.6
0 0 468.8 500 50 125.5 529.6 529.6
40 100.4 468.8 500 22 73.8 60 150.6 529.6 529.6
50 125.5 468.8 500 80 200.8 529.6 529.6
22 73.8 100 251.0 529.6 529.6
60 150.6 468.8 500
80 200.8 468.8 500 0 0 549.2 600
100 251.0 468.8 500 40 100.4 549.2 600
230-3-60 207 253 6.5 80.7 538 95 605 30 93.4 50 125.5 549.2 600
0 0 491.6 500 60 150.6 549.2 600
40 100.4 491.6 500 80 200.8 549.2 600
50 125.5 491.6 500 100 251.0 549.2 600
30 93.4 0 0 577.0 600
60 150.6 491.6 500
80 200.8 491.6 500 40 100.4 577.0 600
37 116 50 125.5 577.0 600
100 251.0 491.6 500 60 150.6 577.0 600
80 200.8 577.0 600
0 0 519.8 600 100 251.0 577.0 600
40 100.4 519.8 600 0 0 605.8 700
50 125.5 519.8 600 40 100.4 605.8 700
37 116 50 125.5 605.8 700
60 150.6 519.8 600 45 139
80 200.8 519.8 600 60 150.6 605.8 700
100 251.0 519.8 600 80 200.8 605.8 700
100 251.0 605.8 700
0 0.0 233.6 250 0 0.0 312.6 350
40 60.8 233.6 250 40 60.8 312.6 350
18.5 36.3 50 76.0 312.6 350
50 76.0 233.6 250 60 91.2 312.6 350
18.5 36.3
60 91.2 233.6 250 80 121.6 312.6 350
80 121.6 233.6 250 100 151.9 312.6 350
100 151.9 235.3 250 0 0.0 318.9 350
40 60.8 318.9 350
240.7 250 50 76.0 318.9 350
0 0.0 22 42.6
240.7 250 60 91.2 318.9 350
50 76.0
240.7 250 80 121.6 318.9 350
22 42.6 60 91.2 100 151.9 318.9 350
240.7 250
80 121.6 0 0.0 330.2 350
240.7 250
100 151.9 40 60.8 330.2 350
243.2 250
380/400-3-60 50 76.0 330.2 350
342 418 3.78 39.3 290 0 0.0 254.8 300 57.9 380 30 53.9 60 91.2 330.2 350
(4 WIRE)
40 60.8 254.8 300 80 121.6 330.2 350
50 76.0 254.8 300 100 151.9 330.2 350
30 53.9 0 0.0 345.5 400
60 91.2 254.8 300
80 121.6 254.8 300 40 60.8 345.5 400
100 151.9 257.3 300 37 66.9 50 76.0 345.5 400
60 91.2 345.5 400
80 121.6 345.5 400
0 0.0 271.1 300 100 151.9 345.5 400
40 60.8 271.1 300 0 0.0 362.0 400
50 76.0 271.1 300 40 60.8 362.0 400
37 66.9
60 91.2 271.1 300 50 76.0 362.0 400
45 80.1 60 91.2 362.0 400
80 121.6 271.1 300
100 151.9 273.5 300 80 121.6 362.0 400
100 151.9 362.0 400
0 0.0 203.9 225 0 0.0 237.7 250
40 50.2 203.9 225 40 50.2 237.7 250
18.5 28.5 50 62.8 237.7 250
50 62.8 203.9 225 60 75.3 237.7 250
18.5 28.5
60 75.3 203.9 225 80 100.4 237.7 250
80 100.4 203.9 225 100 125.5 237.7 250
100 125.5 203.9 225 0 0.0 243.0 250
40 50.2 243.0 250
0.0 209.2 225 50 62.8 243.0 250
0 22 33.8
50.2 209.2 225 60 75.3 243.0 250
50 80 100.4 243.0 250
62.8 209.2 225
22 33.8 60 100 125.5 243.0 250
75.3 209.2 225
80 0 0.0 254.7 300
100.4 209.2 225
100 40 50.2 254.7 300
125.5 209.2 225
460-3-60 414 506 3.79 34.3 229 42.1 320 30 44.8 50 62.8 254.7 300
0 0.0 222.8 250 60 75.3 254.7 300
40 50.2 222.8 250 80 100.4 254.7 300
100 125.5 254.7 300
50 62.8 222.8 250
30 44.8 0 0.0 267.8 300
60 75.3 222.8 250 40 50.2 267.8 300
80 100.4 222.8 250 50 62.8 267.8 300
100 125.5 222.8 250 37 55.3 60 75.3 267.8 300
80 100.4 267.8 300
0 0.0 235.9 250 100 125.5 267.8 300
40 50.2 235.9 250 0 0.0 282.7 300
50 62.8 235.9 250 40 50.2 282.7 300
37 55.3 50 62.8 282.7 300
60 75.3 235.9 250 45 67.2
80 100.4 235.9 250 60 75.3 282.7 300
100 125.5 235.9 250 80 100.4 282.7 300
100 125.5 282.7 300

NOTE: Please refer to page 32 for note & legend.

43
Page 82 of 286
FAN PERFORMANCE DATA
Model No.: PTX006 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

I 867 II ***
2100 772 0.46 857 0.55 935 0.66 1007 0.76 1075 0.87 *** *** *** *** *** *** *** *** *** ***
1146 1.04
III***
2200 784 0.50 0.60 943 0.70 1015 0.81 1082 0.92 *** *** *** *** *** *** ***
2300 795 0.54 876 0.64 952 0.75 1023 0.86 1089 0.98 1152 1.10 1212 1.22 *** *** *** *** ***
2400 807 0.58 887 0.69 961 0.80 1031 0.91 1097 1.03 1159 1.16 1218 1.28 1275 1.41 *** *** *** ***
2500 819 0.63 897 0.74 970 0.85 1039 0.97 1104 1.09 1166 1.22 1225 1.35 1281 1.48 1335 1.56 *** ***
2600 831 0.68 907 0.79 979 0.91 1047 1.03 1112 1.15 1173 1.28 1232 1.41 1288 1.50 1341 1.63 1393 1.76
2700 844 0.73 918 0.84 989 0.96 1056 1.09 1120 1.22 1180 1.35 1238 1.48 1294 1.57 1347 1.70 1399 1.84
2800 856 0.78 929 0.90 999 1.02 1065 1.15 1128 1.28 1188 1.42 1245 1.50 1300 1.64 1353 1.78 1405 1.92
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is bas ed on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 1.1 KW motor to be used for unshaded portion.
3. Alt. 1.5 KW & 2.2 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX006 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2100
2200
2172
2201
I 1.32
1.25 2232
2259
1.34
1.41
2291
2317
1.43
1.50
2349
2374
1.52
1.59
2406
2429
1.61
1.69
2463
2485
1.71
1.79
2519
2539
1.80
1.88
2574
2593
1.90
1.98
2629
2646
2.00
2.04
II2699
2683 2.06
2.14
2300 2231 1.39 2288 1.48 2344 1.58 2400 1.67 2455 1.77 2508 1.87 2562 1.97 2614 2.02 2666 2.12 2717 2.22
2400 2262 1.47 2318 1.56 2374 1.66 2428 1.75 2481 1.85 2534 1.95 2586 2.05 2637 2.11 2688 2.21 2738 2.31
2500 2295 1.55 2350 1.64 2404 1.74 2457 1.84 2509 1.94 2561 2.04 2612 2.10 2662 2.20 2712 2.30 2761 2.41
2600 2328 1.63 2382 1.73 2435 1.83 2488 1.93 2539 2.03 2589 2.09 2639 2.19 2689 2.29 2737 2.40 2785 2.51
2700 2363 1.72 2416 1.82 2468 1.92 2519 2.02 2569 2.08 2619 2.18 2668 2.29 2716 2.40 2764 2.50 2811 2.61
2800 2398 1.81 2450 1.91 2501 2.02 2552 2.08 2601 2.18 2650 2.28 2698 2.39 2745 2.50 2792 2.61 2839 2.72
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 2.2 KW motor to be used for unshaded portion.
3. Alt. 3.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

44
Page 83 of 286
FAN PERFORMANCE DATA
Model No.: PTX007 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
2400
2500
831
843
0.61
0.66
I 920
909 0.72
0.77
982
992
0.83
0.89
1050
1059
0.95
1.01
1115
1123
1.07
1.13
1177
1184
1.19
1.26
1235
1242
1.32
1.39
1291
1298
1.45
1.47
***
***
***
***
II ***
*** ***
***
2600 856 0.71 931 0.83 1001 0.94 1068 1.07 1132 1.19 1192 1.32 1250 1.46 1305 1.54 1358 1.67 *** ***
2700 869 0.77 942 0.88 1012 1.00 1077 1.13 1140 1.26 1200 1.39 1257 1.48 1312 1.61 1365 1.75 1416 1.89
2800 882 0.82 954 0.94 1022 1.07 1087 1.20 1149 1.33 1208 1.46 1265 1.55 1319 1.69 1371 1.83 1422 1.97
2900 896 0.88 966 1.01 1033 1.13 1096 1.26 1158 1.40 1216 1.49 1272 1.62 1326 1.76 1378 1.91 1429 2.05

III2.23
3000 909 0.95 978 1.07 1043 1.20 1106 1.34 1167 1.43 1224 1.56 1280 1.70 1334 1.85 1385 1.99 1435 2.14
3100 923 1.02 990 1.14 1054 1.28 1116 1.41 1176 1.50 1233 1.64 1288 1.78 1341 1.93 1392 2.08 1442
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 1.5 KW motor to be used for unshaded portion.
3. Alt. 2.2 KW & 3.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX007 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
2400
2500
2279
2312
1.50
1.58
I2367
2335 1.59
1.67
2390
2420
1.69
1.77
2443
2473
1.78
1.87
2497
2525
1.88
1.97
2549
2577
1.98
2.03
2601
2627
2.04
2.13
2652
2677
2.14
2.23
2703
2727
2.24
2.33
2753
2776
II2.442.34

2600 2346 1.66 2400 1.76 2452 1.86 2504 1.96 2555 2.02 2605 2.12 2655 2.22 2704 2.33 2753 2.43 2801 2.54
2700 2381 1.75 2433 1.85 2485 1.96 2536 2.06 2586 2.12 2636 2.22 2684 2.32 2732 2.43 2780 2.54 2827 2.65
2800 2416 1.85 2468 1.95 2519 2.05 2569 2.11 2618 2.22 2667 2.32 2715 2.43 2762 2.54 2808 2.65 2855 2.76
2900 2453 1.94 2504 2.05 2554 2.11 2603 2.21 2651 2.32 2699 2.43 2746 2.54 2792 2.65 2838 2.76 2883 2.87

III3.12
3000 2490 2.04 2540 2.10 2589 2.21 2637 2.32 2685 2.43 2732 2.54 2778 2.65 2824 2.76 2869 2.88 2913 2.99
3100 2527 2.10 2576 2.21 2625 2.32 2672 2.43 2719 2.54 2765 2.66 2811 2.77 2856 2.88 2900 3.00 2944
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 2.2 KW motor to be used for unshaded portion.
3. Alt. 3.0 KW & 4.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

45
Page 84 of 286
FAN PERFORMANCE DATA
Model No.: PTX008 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
3100
3200
681
688
I 0.72
0.68 754
760
0.81
0.86
822
827
0.95
1.00
886
891
1.09
1.14
946
950
1.24
1.29
1003
1006
1.39
1.45
1056
1060
1.50
1.55
1107
1111
1.65
1.71
1156
1159
1.81
1.88
***
***
II ******
3300 695 0.77 766 0.90 833 1.05 895 1.19 954 1.35 1010 1.46 1063 1.61 1114 1.77 1162 1.94 1209 2.11
3400
3500
702
710
0.81
0.86
772
779
0.95
1.00
838
844
1.10
1.15
900
905
1.25
1.30
959
963
1.40
1.46
1014
1018
1.51
1.57
1067
1071
1.67
1.73
1118
1121
1.84
1.90
1166
1169
2.00
2.07
1212
1215
III2.17
2.24
3600 717 0.91 785 1.05 849 1.20 910 1.36 967 1.47 1022 1.63 1075 1.80 1125 1.97 1172 2.14 1219 2.32
3700 725 0.96 792 1.11 855 1.26 915 1.42 972 1.53 1026 1.70 1078 1.86 1128 2.04 1176 2.21 1222 2.39
3800 733 1.01 798 1.17 861 1.32 920 1.43 977 1.59 1031 1.76 1082 1.93 1132 2.11 1179 2.28 1225 2.47
3900 741 1.07 805 1.22 867 1.38 925 1.49 981 1.66 1035 1.83 1086 2.00 1136 2.18 1183 2.36 1229 2.54
4000 749 1.13 812 1.29 873 1.45 931 1.56 986 1.73 1039 1.90 1090 2.07 1139 2.25 1187 2.44 1232 2.62
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 1.5 KW motor to be used for unshaded portion.
3. Alt. 2.2 KW & 3.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX008 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
3100
3200
1979
2001 I 1.87
1.80 2029
2050
1.92
2.00
2078
2098
2.04
2.12
2126
2146
2.17
2.25
2174
2193
2.29
2.38
2221
2239
2.42
2.51
2267
2284
2.55
2.64
2312
2329
2.68
2.77
2357
2373
2.82
2.91
2401
2416
II3.04
2.95

3300 2023 1.95 2071 2.07 2119 2.20 2166 2.33 2212 2.46 2257 2.59 2302 2.73 2346 2.86 2390 3.00 2433 3.14
3400 2045 2.03 2093 2.15 2140 2.28 2186 2.41 2232 2.54 2277 2.68 2321 2.82 2364 2.95 2407 3.09 2449 3.23
3500 2068 2.11 2116 2.23 2162 2.37 2207 2.50 2252 2.63 2296 2.77 2340 2.91 2383 3.05 2425 3.19 2467 3.33
3600 2092 2.19 2138 2.32 2184 2.45 2229 2.59 2273 2.73 2317 2.86 2360 3.00 2402 3.15 2444 3.29 2485 3.43
3700 2116 2.27 2162 2.41 2207 2.54 2251 2.68 2295 2.82 2338 2.96 2380 3.10 2422 3.25 2463 3.39 2504 3.54
3800 2140 2.36 2185 2.50 2230 2.64 2274 2.78 2317 2.92 2359 3.06 2401 3.20 2442 3.35 2483 3.50 2523 3.65
3900 2165 2.45 2209 2.59 2253 2.73 2297 2.87 2339 3.02 2381 3.16 2422 3.31 2463 3.46 2503 3.61 2543 3.76
4000 2190 2.55 2234 2.69 2277 2.83 2320 2.98 2362 3.12 2403 3.27 2444 3.42 2484 3.57 2524 3.72 2564 3.87
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 3.0 KW motor to be used for unshaded portion.
3. Alt. 4.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II

46
Page 85 of 286
FAN PERFORMANCE DATA
Model No.: PTX010 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
3500
3600
730
737
0.87
0.92
I 804
797 1.01
1.06
861
867
1.15
1.21
922
927
1.30
1.36
979
984
1.46
1.52
1033
1038
1.62
1.68
1085
1089
1.78
1.85
1135
1139
1.95
2.02
1182
1186
2.12
2.19
1228
II2.29
1232 2.37
3700 745 0.97 811 1.11 873 1.27 932 1.42 989 1.58 1042 1.75 1094 1.91 1143 2.09 1190 2.26 1235 2.44
3800 753 1.03 818 1.17 879 1.32 938 1.48 994 1.65 1047 1.81 1098 1.98 1147 2.16 1194 2.34 1239 2.52
3900 762 1.08 825 1.23 886 1.39 943 1.55 999 1.71 1052 1.88 1102 2.06 1151 2.24 1198 2.42 1243 2.60
4000 770 1.14 832 1.29 892 1.45 949 1.61 1004 1.78 1056 1.95 1107 2.13 1155 2.31 1202 2.50 1247 2.69
4100 778 1.20 840 1.36 899 1.52 955 1.68 1009 1.85 1061 2.03 1111 2.21 1159 2.39 1206 2.58 1250 2.77
4200 787 1.26 847 1.42 905 1.59 961 1.75 1015 1.93 1066 2.11 1116 2.29 1163 2.47 1210 2.66 1254 2.86
4300 795 1.33 855 1.49 912 1.66 967 1.83 1020 2.00 1071 2.18 1120 2.37 1168 2.56 1214 2.75 1258 2.95
4400 804 1.40 862 1.56 919 1.73 973 1.90 1026 2.08 1076 2.27 1125 2.45 1172 2.64 1218 2.84 1262 3.04
4500 813 1.47 870 1.64 926 1.81 980 1.98 1031 2.16 1081 2.35 1130 2.54 1177 2.73 1222 2.93 III3.13
1266
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 2.2 KW motor to be used for unshaded portion.
3. Alt. 3.0 KW & 4.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX010 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.2 t 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
3500
3600
2082
2106
2.14
2.23
I 2152
2129 2.27
2.36
2175
2197
2.40
2.49
2220
2242
2.54
2.63
2265
2286
2.67
2.77
2309
2329
2.81
2.90
2352
2372
2.95
3.05
2395
2414
3.09
3.19
2437
2456
3.23
3.33
II3.48
2479
2497
3.37

3700 2130 2.31 2175 2.45 2220 2.58 2264 2.72 2308 2.86 2351 3.00 2393 3.15 2434 3.29 2476 3.44 2516 3.58
3800 2154 2.41 2199 2.54 2244 2.68 2287 2.82 2330 2.96 2372 3.11 2414 3.25 2455 3.40 2496 3.54 2536 3.69
3900 2179 2.50 2224 2.64 2267 2.78 2310 2.92 2353 3.06 2394 3.21 2435 3.36 2476 3.51 2516 3.66 2556 3.81
4000 2204 2.60 2248 2.74 2291 2.88 2334 3.02 2376 3.17 2417 3.32 2458 3.47 2498 3.62 2537 3.77 2576 3.88
4100 2230 2.70 2273 2.84 2316 2.98 2358 3.13 2399 3.28 2440 3.43 2480 3.58 2520 3.73 2559 3.89 2597 4.00
4200 2256 2.80 2299 2.94 2341 3.09 2382 3.24 2423 3.39 2463 3.54 2503 3.70 2542 3.85 2581 3.96 2619 4.12
4300 2282 2.90 2324 3.05 2366 3.20 2407 3.35 2447 3.51 2487 3.66 2526 3.82 2565 3.93 2603 4.09 2641 4.25
4400 2511 3.78
III4.51
2309 3.01 2350 3.16 2391 3.32 2432 3.47 2471 3.63 2550 3.90 2588 4.05 2626 4.21 2663 4.37
4500 2335 3.13 2377 3.28 2417 3.43 2457 3.59 2496 3.75 2535 3.91 2573 4.02 2611 4.18 2649 4.34 2686
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 3.0 KW motor to be used for unshaded portion.
3. Alt. 4.0 KW & 5.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

47
Page 86 of 286
FAN PERFORMANCE DATA
Model No.: PTX012 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
4000
4200
599
608
I 0.94
0.86 662
670
1.01
1.10
722
729
1.18
1.27
778
784
1.35
1.45
831
836
1.52
1.63
880
885
1.71
1.82
927
932
1.89
2.01
972
976
2.09
2.21
1014
1019
2.28
2.41
1055
1060
II2.62
2.49

4400 618 1.04 679 1.20 736 1.37 790 1.55 842 1.74 890 1.93 937 2.13 981 2.33 1023 2.54 1064 2.75
4600 629 1.13 688 1.30 744 1.48 797 1.67 847 1.86 896 2.05 942 2.25 985 2.46 1028 2.67 1068 2.89
4800 639 1.24 697 1.41 751 1.60 804 1.78 853 1.98 901 2.18 947 2.39 990 2.60 1032 2.82 1072 3.04
5000 650 1.35 706 1.53 759 1.72 811 1.91 860 2.11 907 2.32 952 2.53 995 2.75 1037 2.97 III3.19
1077

NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 2.2 KW motor to be used for unshaded portion.
3. Alt. 3.0 KW & 4.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX012 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
4000
4200
1774
1805
I 2.41
2.26 1817
1848
2.41
2.56
1860
1890
2.56
2.71
1903
1931
2.71
2.87
1944
1972
2.86
3.03
1985
2012
3.02
3.19
2025
2051
3.17
3.35
2064
2090
3.33
3.51
2103
2128
3.49
3.67
2141
2165
3.65
3.84
4400 1837 2.56 1879 2.72 1920 2.88 1961 3.04 2000 3.20 2040 3.37 2078 3.53 2116 3.70 2153 3.87 2190 3.94
4600
4800
1870
1904
2.73
2.90
1911
1944
2.89
3.07
1952
1984
3.05
3.24
1991
2023
3.22
3.41
2030
2061
3.39
3.58
2069
2099
3.55
3.75
2107
2136
3.72
3.83
2144
2172
3.80
4.00
2180
2209
3.97
4.18
II4.14
2217
2244 4.35
5000 1939 3.08 1978 3.25 2017 3.43 2055 3.60 2093 3.78 2130 3.86 2166 4.04 2202 4.21 2238 4.39 2273 4.57
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 4.0 KW motor to be used for unshaded portion.
3. Alt. 5.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

48
Page 87 of 286
FAN PERFORMANCE DATA
Model No.: PTX016 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
4800
5000
577
586
1.15
1.24
I 638
630 1.35
1.44
679
686
1.55
1.66
724
731
1.77
1.87
768
774
1.98
2.10
809
814
2.20
2.33
847
853
2.43
2.56
885
890
2.66
2.80
920
926
2.89
3.03
***
960
II3.28
***

5200 595 1.33 646 1.55 693 1.76 738 1.99 780 2.22 820 2.45 859 2.69 896 2.93 931 3.18 965 3.43
5400 604 1.43 654 1.65 701 1.88 745 2.11 787 2.34 826 2.58 865 2.83 901 3.08 936 3.33 970 3.59
5600 613 1.54 662 1.76 708 1.99 752 2.23 793 2.47 833 2.72 871 2.97 907 3.23 942 3.49 975 3.75
5800 622 1.65 670 1.88 716 2.12 759 2.36 800 2.61 839 2.86 876 3.12 912 3.38 947 3.65 981 3.92
6000 631 1.77 678 2.01 723 2.25 766 2.50 806 2.75 845 3.01 882 3.27 918 3.54 952 3.81 986 3.99
6200 640 1.89 687 2.14 731 2.38 773 2.64 813 2.90 851 3.16 888 3.43 924 3.71 958 3.89 991 III4.16
6400 650 2.03 695 2.27 739 2.53 780 2.79 820 3.05 858 3.32 894 3.60 930 3.88 964 4.06 996 4.34
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 3.0 KW motor to be used for unshaded portion.
3. Alt. 4.0 KW & 5.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.
5. * Is not applicable

Model No.: PTX016 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
4800
5000
1585
1606
2.84
2.99
I 1645
1626 3.03
3.18
1666
1685
3.22
3.38
1705
1723
3.41
3.57
1744
1761
3.60
3.77
1782
1798
3.80
3.88
1819
1835
3.90
4.07
1856
1872
4.10
4.28
1892
1907
4.30
4.48
1928
1943 II4.69
4.50

5200 1627 3.15 1666 3.35 1704 3.54 1742 3.74 1780 3.85 1816 4.05 1852 4.25 1888 4.46 1923 4.67 1958 4.88
5400 1649 3.32 1687 3.52 1725 3.72 1762 3.83 1799 4.03 1835 4.23 1870 4.44 1905 4.65 1940 4.86 1974 5.07
5600 1672 3.49 1709 3.69 1746 3.80 1783 4.01 1819 4.21 1854 4.42 1889 4.63 1923 4.84 1957 5.06 1991 5.28
5800 1695 3.67 1732 3.79 1768 3.99 1804 4.20 1839 4.41 1874 4.62 1908 4.83 1942 5.05 1976 5.27 2009 5.49
6000 1719 3.86 1755 3.97 1791 4.18 1826 4.39 1860 4.61 1895 4.82 1928 5.04 1962 5.26 1995 5.49 2027 5.71
6200
6400
1744
1769
3.96
4.16
1779
1803
4.17
4.38
1814
1838
4.38
4.59
1848
1871
4.60
4.81
1882
1905
4.82
5.03
1916
1938
5.04
5.26
1949
1970
5.26
5.48
1982
2003
5.48
5.71
2014
2034
5.71
5.94
2046
2066
III5.94
6.18
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 4.0 KW motor to be used for unshaded portion.
3. Alt. 5.5 KW & 7.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

49
Page 88 of 286
FAN PERFORMANCE DATA
Model No.: PTX018 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 670
5600 613 1.54 662 1.76 708 1.99 752 2.23 793 2.47 833 2.72 871 2.97 907 3.23 942 3.49 975 3.75
5800 622 1.65 1.88 716 2.12 759 2.36 800 2.61 839 2.86 876 3.12 912 3.38 947 3.65 981 3.82
6000 631 1.77 678 2.01 723 2.25 766 2.50 806 2.75 845 3.01 882 3.27 918 3.54 952 3.81 986 3.99
6200 640 1.89 687 2.14 731 2.38 773 2.64 813 2.90 851 3.16 888 3.43 924 3.71 958 3.89 991 4.16
6400
6600
650
659
2.03
2.16
695
704
2.27
2.41
739
747
2.53
2.67
780
787
2.79
2.94
820
827
3.05
3.21
858
864
3.32
3.49
894
901
3.60
3.77
930
935
3.78
3.96
964
969
4.06
4.24
996
1002
II4.34
4.53
6800 668 2.30 712 2.56 755 2.83 795 3.10 834 3.37 871 3.66 907 3.85 941 4.14 975 4.43 1007 4.72
7000 678 2.45 721 2.72 763 2.99 802 3.26 841 3.55 878 3.84 913 4.03 947 4.32 981 4.62 1013 4.91
7200 687 2.61 730 2.88 771 3.15 810 3.44 848 3.73 884 3.92 919 4.22 953 4.51 986 4.81 1018 5.12
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 4.0 KW motor to be used for unshaded portion.
3. Alt. 5.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

Model No.: PTX018 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 1732
5600 1672 3.49 1709 3.69 1746 3.90 1783 4.11 1819 4.32 1854 4.53 1889 4.75 1923 4.96 1957 5.18 1991 5.28
5800 1695 3.67 3.88 1768 4.09 1804 4.30 1839 4.51 1874 4.73 1908 4.95 1942 5.17 1976 5.40 2009 5.49
6000 1719 3.86 1755 4.07 1791 4.29 1826 4.50 1860 4.72 1895 4.94 1928 5.16 1962 5.39 1995 5.49 2027 5.71
6200 1744 4.06 1779 4.27 1814 4.49 1848 4.71 1882 4.93 1916 5.16 1949 5.39 1982 5.48 2014 5.71 2046 5.94
6400 1769 4.27 1803 4.48 1838 4.71 1871 4.93 1905 5.16 1938 5.39 1970 5.48 2003 5.71 2034 5.94 2066 6.18
6600 1794 4.48 1828 4.70 1862 4.93 1895 5.16 1928 5.39 1960 5.49 1992 5.72 2024 5.95 2055 6.19 2086 II6.42
6800 1820 4.70 1853 4.93 1886 5.16 1919 5.39 1951 5.49 1983 5.73 2015 5.96 2046 6.20 2077 6.44 2107 6.68
7000 1846 4.94 1879 5.17 1912 5.40 1944 5.50 1975 5.74 2007 5.97 2038 6.21 2068 6.45 2099 6.70 2129 6.94
7200 1873 5.18 1905 5.29 1937 5.52 1969 5.75 2000 5.99 2031 6.23 2061 6.48 2091 6.72 2121 6.97 2151 7.22
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 5.5 KW motor to be used for unshaded portion.
3. Alt. 7.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

50
Page 89 of 286
FAN PERFORMANCE DATA
Model No.: PTX020 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 632 II ***
6800 557 1.84 604 2.11 647 2.40 688 2.70 727 3.00 764 3.32 799 3.64 833 3.87 866 4.20 *** *** *** ***
7000 588 2.09 2.38 674 2.67 713 2.98 751 3.30 787 3.62 821 3.86 854 4.19 886 4.52 *** *** ***
7200 593 2.20 637 2.49 678 2.79 717 3.11 754 3.43 790 3.76 824 3.99 857 4.33 889 4.67 919 5.02 *** ***
7400 598 2.32 641 2.61 682 2.92 721 3.24 758 3.56 794 3.80 828 4.13 861 4.48 892 4.82 922 5.17 952 5.53
7600
7800
604
610
2.44
2.56
646
651
2.74
2.87
687
691
3.05
3.18
725
730
3.37
3.51
762
766
3.70
3.75
797
801
3.94
4.09
831
835
4.28
4.43
864
867
4.63
4.78
895
899
4.98
5.14
926
929
5.34
5.50
955
958
III5.70
5.87
8000 615 2.69 656 3.00 696 3.32 734 3.65 770 3.90 805 4.24 838 4.59 871 4.94 902 5.31 932 5.67 961 6.05
8200 621 2.82 662 3.14 701 3.46 738 3.80 774 4.05 809 4.39 842 4.75 874 5.11 905 5.47 935 5.85 964 6.23
8400 627 2.96 667 3.28 705 3.61 742 3.86 778 4.20 812 4.55 845 4.91 877 5.28 908 5.65 938 6.03 967 6.41
8600 632 3.10 672 3.43 710 3.77 747 4.01 782 4.36 816 4.72 849 5.08 881 5.45 912 5.83 941 6.21 970 6.60
8800 638 3.25 677 3.58 715 3.83 751 4.17 786 4.52 820 4.89 853 5.25 884 5.63 915 6.01 945 6.40 973 6.80
9000 644 3.41 683 3.74 720 3.99 756 4.34 791 4.69 824 5.06 857 5.43 888 5.81 918 6.20 948 6.59 976 6.99
9200 650 3.57 688 3.81 725 4.16 761 4.51 795 4.87 828 5.24 860 5.62 891 6.00 922 6.39 951 6.79 980 7.20
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 4.0 KW motor to be used for unshaded portion.
3. Alt. 5.5 KW & 7.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX020 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 1588
6800 1522 4.21 1556 4.45 1589 4.69 1622 4.94 1655 5.19 1687 5.44 1719 5.69 1750 5.95 1781 6.21 1811 6.47 1842 6.74
7000 1555 4.51 4.75 1621 5.00 1653 5.25 1685 5.50 1716 5.76 1747 6.02 1778 6.28 1808 6.55 1838 6.82 1868 7.09
7200 1570 4.68 1603 4.93 1635 5.18 1667 5.44 1698 5.69 1729 5.95 1760 6.22 1790 6.48 1820 6.75 1850 7.03 1879 7.25
7400 1586 4.86 1618 5.12 1650 5.37 1681 5.63 1712 5.89 1742 6.15 1773 6.42 1802 6.69 1832 6.96 1861 7.19 1890 7.46
7600 1602 5.05 1633 5.31 1664 5.56 1695 5.83 1726 6.09 1756 6.36 1786 6.63 1815 6.90 1844 7.18 1873 7.40 1902 7.68
7800 1618 5.24 1649 5.50 1680 5.76 1710 6.03 1740 6.30 1770 6.57 1799 6.85 1828 7.12 1857 7.35 1886 7.63 1914 7.91
8000 1634 5.44 1665 5.70 1695 5.97 1725 6.24 1755 6.51 1784 6.79 1813 7.07 1842 7.29 1870 7.58 1899 7.86 1926 8.15
8200
8400
1651
1668
5.65
5.86
1682
1698
5.91
6.13
1711
1728
6.18
6.40
1741
1757
6.46
6.68
1770
1786
6.73
6.96
1799
1814
7.01
7.19
1828 7.24
1842 7.47
1856 7.52
1870 7.76
1884
1898
7.81
8.05
II1925
1912 8.10
8.34
1939
1953
8.39
8.64
8600 1686 6.08 1715 6.35 1744 6.63 1773 6.91 1802 7.20 1830 7.43 1857 7.71 1885 8.01 1912 8.30 1939 8.60 1966 8.89
8800 1704 6.30 1733 6.58 1761 6.87 1790 7.15 1818 7.38 1845 7.67 1873 7.96 1900 8.26 1927 8.55 1954 8.85 1980 9.16
9000 1722 6.54 1750 6.82 1778 7.11 1806 7.34 1834 7.63 1861 7.92 1889 8.22 1915 8.52 1942 8.82 1968 9.12 1995 9.43
9200 1740 6.78 1768 7.06 1796 7.30 1823 7.59 1851 7.88 1878 8.18 1905 8.48 1931 8.78 1957 9.09 1983 9.39 2009 9.70
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 7.5 KW motor to be used for unshaded portion.
3. Alt. 11.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

51
Page 90 of 286
FAN PERFORMANCE DATA
Model No.: PTX022 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 616
7200 567 1.99 612 2.27 654 2.56 695 2.85 733 3.16 770 3.48 805 3.80 838 4.13 871 4.47 902 4.82 *** ***
7400 572 2.09 2.38 658 2.67 698 2.97 736 3.29 773 3.61 808 3.94 841 4.27 873 4.61 904 4.96 934 5.32
7600 577 2.20 620 2.49 662 2.79 702 3.09 740 3.41 776 3.74 811 4.07 844 4.41 876 4.76 907 5.12 937 5.48
7800 582 2.31 625 2.60 666 2.91 705 3.22 743 3.54 779 3.87 813 4.21 847 4.56 879 4.91 910 5.27 939 5.64
8000 587 2.43 629 2.73 670 3.03 709 3.35 746 3.68 782 4.01 816 4.36 849 4.71 881 5.07 912 5.43 942 5.80
8200 592 2.55 634 2.85 674 3.16 713 3.48 750 3.82 785 4.16 819 4.50 852 4.86 884 5.22 915 5.59 944 5.97
8400 597 2.68 639 2.98 678 3.30 717 3.62 753 3.96 788 4.30 822 4.66 855 5.02 887 5.39 917 5.76 947 6.14
8600 603 2.80 643 3.12 683 3.44 720 3.77 757 4.11 792 4.46 825 4.81 858 5.18 889 5.55 920 5.93 949 6.32
8800 608 2.94 648 3.25 687 3.58 724 3.92 760 4.26 795 4.62 829 4.98 861 5.35 892 5.72 923 6.11II 952 6.50
9000 613 3.08 653 3.40 692 3.73 728 4.07 764 4.42 798 4.78 832 5.14 864 5.52 895 5.90 925 6.29 955 6.69
9200 619 3.22 658 3.55 696 3.88 733 4.23 768 4.58 802 4.95 835 5.32 867 5.70 898 6.08 928 6.48 957 6.88
9400 625 3.37 663 3.70 701 4.04 737 4.39 772 4.75 805 5.12 838 5.49 870 5.88 901 6.27 931 6.67 960 7.07
9600 630 3.53 668 3.86 705 4.21 741 4.56 776 4.92 809 5.30 842 5.68 873 6.06 904 6.46 933 6.86 962 7.27
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 5.5 KW motor to be used for unshaded portion.
3. Alt. 7.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

Model No.: PTX022 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I1599
7200 1551 4.54 1584 4.79 1616 5.04 1648 5.29 1680 5.55 1711 5.80 1742 6.07 1773 6.33 1803 6.60 1833 6.87 1862 7.14
7400 1566 4.72 4.97 1631 5.22 1662 5.47 1693 5.73 1724 6.00 1755 6.26 1785 6.53 1814 6.80 1844 7.08 1873 7.30
7600 1582 4.89 1614 5.15 1645 5.40 1676 5.66 1707 5.93 1737 6.19 1767 6.46 1797 6.73 1826 7.01 1855 7.23 1884 7.51
7800 1598 5.08 1629 5.34 1660 5.60 1691 5.86 1721 6.13 1751 6.40 1781 6.67 1810 6.95 1839 7.22 1868 7.45 1896 7.73
8000 1614 5.27 1645 5.53 1675 5.80 1706 6.06 1736 6.33 1765 6.61 1794 6.88 1823 7.16 1852 7.39 1880 7.67 1908 7.96
8200 1630 5.47 1661 5.73 1691 6.00 1721 6.27 1750 6.55 1779 6.82 1808 7.10 1837 7.33 1865 7.61II 1893 7.90 1921 8.19
8400 1647 5.67 1677 5.94 1707 6.21 1736 6.49 1765 6.76 1794 7.05 1823 7.27 1851 7.56 1879 7.85 1906 8.14 1934 8.43
8600 1664 5.88 1694 6.15 1723 6.43 1752 6.71 1781 6.99 1809 7.22 1837 7.51 1865 7.79 1893 8.09 1920 8.38 1947 8.68
8800 1682 6.10 1711 6.37 1740 6.65 1768 6.94 1797 7.22 1825 7.45 1852 7.74 1880 8.04 1907 8.33 1934 8.63 1960 8.93
9000 1700 6.32 1728 6.60 1757 6.89 1785 7.17 1813 7.41 1840 7.70 1868 7.99 1895 8.29 1922 8.58 1948 8.89 1974 9.19
9200 1718 6.55 1746 6.84 1774 7.12 1802 7.36 1829 7.65 1856 7.94 1883 8.24 1910 8.54 1937 8.84 1963 9.15 1989 9.46
9400 1736 6.79 1764 7.08 1791 7.31 1819 7.61 1846 7.90 1873 8.20 1899 8.50 1926 8.80 1952 9.11 1978 9.42 2003 9.73
9600 1754 7.03 1782 7.27 1809 7.56 1836 7.86 1863 8.16 1889 8.46 1916 8.77 1942 9.08 1967 9.39 1993 9.70 2018 10.01
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 7.5 KW motor to be used for unshaded portion.
3. Alt. 11.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

52
Page 91 of 286
FAN PERFORMANCE DATA
Model No.: PTX025 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 646
8000 599 2.51 641 2.81 681 3.12 720 3.44 757 3.77 792 4.11 826 4.45 859 4.81 890 5.17 921 5.53 950 5.91
8200
8400
605
610
2.64
2.77 651
2.94
3.07
686
690
3.26
3.39
724
728
3.58
3.72
760
764
3.91
4.06
795
799
4.26
4.41
829
832
4.61
4.77
862
865
4.97
5.13
893
896
5.33
5.50
923
926
5.70
5.87
II953
956
6.08
6.26
8600 615 2.90 656 3.21 695 3.54 732 3.87 768 4.22 802 4.57 836 4.93 868 5.30 899 5.67 929 6.05 958 6.44
8800 621 3.04 661 3.36 699 3.69 736 4.03 771 4.37 806 4.73 839 5.09 871 5.47 902 5.85 932 6.23 961 6.63
9000 627 3.18 666 3.51 704 3.84 740 4.18 775 4.54 809 4.90 842 5.27 874 5.64 905 6.03 935 6.42 964 6.82
9200 632 3.33 671 3.66 708 4.00 745 4.35 779 4.70 813 5.07 846 5.44 877 5.82 908 6.21 938 6.61 967 7.01
9400 638 3.49 676 3.82 713 4.16 749 4.51 783 4.88 817 5.25 849 5.62 881 6.01 911 6.41 941 6.81 970 7.21
9600 644 3.65 682 3.98 718 4.33 753 4.69 788 5.05 821 5.43 853 5.81 884 6.20 914 6.60 944 7.01 972 7.36
9800 650 3.81 687 4.15 723 4.50 758 4.87 792 5.24 825 5.62 857 6.01 887 6.40 918 6.80 947 7.21 975 7.57
10000 656 3.98 692 4.33 728 4.68 762 5.05 796 5.43 829 5.81 860 6.20 891 6.60 921 7.01 950 7.37 978 7.79
10200 662 4.16 698 4.51 733 4.87 767 5.24 800 5.62 832 6.01 864 6.41 894 6.81 924 7.22 953 7.58 981 8.01
10400 668 4.34 703 4.69 738 5.06 772 5.44 805 5.82 837 6.21 868 6.61 898 7.02 928 7.39 956 7.81III984 8.23
10600 674 4.52 709 4.89 743 5.26 777 5.64 809 6.03 841 6.42 872 6.83 902 7.24 931 7.61 960 8.03 987 8.46
10800 680 4.72 715 5.08 748 5.46 781 5.84 814 6.24 845 6.64 876 7.05 905 7.41 934 7.83 963 8.26 991 8.70
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 5.5 KW motor to be used for unshaded portion.
3. Alt. 7.5 KW & 11.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX025 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 1670
8000 1623 5.34 1654 5.61 1684 5.87 1714 6.14 1744 6.41 1773 6.68 1803 6.96 1831 7.19 1860 7.47 1888 7.75 1916 8.04
8200 1639 5.54 5.81 1700 6.08 1730 6.35 1759 6.63 1788 6.90 1817 7.19 1845 7.41 1873 7.70 1901 II7.99 1929 8.28
8400 1656 5.75 1686 6.02 1716 6.29 1745 6.57 1774 6.85 1803 7.13 1831 7.36 1859 7.65 1887 7.93 1914 8.23 1942 8.52
8600 1674 5.97 1703 6.24 1732 6.52 1761 6.80 1790 7.08 1818 7.31 1846 7.59 1874 7.88 1901 8.18 1928 8.47 1955 8.77
8800 1691 6.19 1720 6.46 1749 6.74 1778 7.03 1806 7.26 1834 7.55 1861 7.84 1888 8.13 1916 8.43 1942 8.73 1969 9.03
9000 1709 6.41 1738 6.69 1766 6.98 1794 7.21 1822 7.50 1849 7.79 1877 8.09 1904 8.38 1930 8.68 1957 8.99 1983 9.29
9200 1727 6.65 1755 6.93 1783 7.22 1811 7.46 1838 7.75 1865 8.04 1892 8.34 1919 8.64 1945 8.95 1972 9.25 1997 9.56
9400 1745 6.89 1773 7.18 1801 7.41 1828 7.71 1855 8.00 1882 8.30 1908 8.61 1935 8.91 1961 9.22 1987 9.53 2012 9.84
9600 1764 7.14 1791 7.37 1819 7.67 1845 7.97 1872 8.27 1899 8.57 1925 8.88 1951 9.18 1976 9.50 2002 9.81 2027 10.13
9800 1783 7.34 1810 7.63 1837 7.93 1863 8.23 1889 8.54 1916 8.84 1941 9.15 1967 9.47 1992 9.78 2018 10.10 2043 10.35
10000 1802 7.60 1828 7.90 1855 8.20 1881 8.51 1907 8.82 1933 9.13 1958 9.44 1984 9.76 2009 10.08 2034 10.33 2058 10.65
10200 1821 7.87 1847 8.17 1873 8.48 1899 8.79 1925 9.10 1950 9.42 1975 9.73 2000 10.05 2025 10.31 2050 10.63 2074 10.96
10400 1840 8.14 1866 8.45 1892 8.76 1917 9.08 1943 9.39 1968 9.71 1993 10.03 2017 10.29 2042 10.62 2066 10.94 2090 11.27 III
10600 1860 8.43 1885 8.74 1911 9.06 1936 9.37 1961 9.69 1986 10.02 2010 10.28 2035 10.60 2059 10.93 2083 11.26 2107 11.60
10800 1879 8.72 1905 9.04 1930 9.36 1955 9.68 1979 10.00 2004 10.26 2028 10.59 2052 10.92 2076 11.26 2100 11.59 2123 11.93
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 7.5 KW motor to be used for unshaded portion.
3. Alt. 11 KW & 15 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

53
Page 92 of 286
FAN PERFORMANCE DATA
Model No.: PTX027/028 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
9000
9200
534
538
2.79
2.91
I 574
571 3.12
3.24
606
609
3.45
3.59
640
643
3.80
3.94
672
675
4.16
4.30
703
706
4.52
4.67
733
736
4.89
5.05
762
764
5.27
5.43
790
792
5.66
5.82
817
819
6.05
6.22
843
845
6.45
II6.63
9400 542 3.04 578 3.38 613 3.72 646 4.08 678 4.45 709 4.82 738 5.20 767 5.59 794 5.99 821 6.39 847 6.80
9600 546 3.17 582 3.51 616 3.86 649 4.23 681 4.60 711 4.97 741 5.36 769 5.76 797 6.16 823 6.57 849 6.98
9800 551 3.30 586 3.65 620 4.01 653 4.38 684 4.75 714 5.14 744 5.53 772 5.93 799 6.33 826 6.75 851 7.16
10000 555 3.44 590 3.80 624 4.16 656 4.53 687 4.91 717 5.30 746 5.69 774 6.10 802 6.51 828 6.93 854 7.30
10200 560 3.59 594 3.95 628 4.31 660 4.69 690 5.07 720 5.47 749 5.87 777 6.28 804 6.69 830 7.12 856 7.49
10400 564 3.74 598 4.10 631 4.47 663 4.85 694 5.24 723 5.64 752 6.04 780 6.46 807 6.88 833 7.25 858 7.68
10600 569 3.89 603 4.26 635 4.63 667 5.02 697 5.41 726 5.82 755 6.23 782 6.65 809 7.07 835 7.45 860 7.88
10800 574 4.04 607 4.42 639 4.80 670 5.19 700 5.59 729 6.00 758 6.41 785 6.84 812 7.21 838 7.65 863III8.09
11000 578 4.21 611 4.59 643 4.97 674 5.37 704 5.77 732 6.19 761 6.61 788 7.03 814 7.41 840 7.85 865 8.29
11200 583 4.37 615 4.76 647 5.15 677 5.55 707 5.96 736 6.38 764 6.80 791 7.18 817 7.61 843 8.06 868 8.51
11400 588 4.54 620 4.93 651 5.33 681 5.74 710 6.15 739 6.57 767 7.00 793 7.38 820 7.82 845 8.27 870 8.73
11600 592 4.72 624 5.11 655 5.52 685 5.93 714 6.35 742 6.77 770 7.21 796 7.59 822 8.04 848 8.49 873 8.95
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 5.5 KW motor to be used for unshaded portion.
3. Alt. 7.5 KW & 11.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX027/028 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
9000
9200
1402
1414
5.91
6.09
I 1442
1431 6.22
6.40
1459
1470
6.54
6.72
1487
1497
6.85
7.05
1514
1524
7.18
7.37
1541
1551
7.51
7.70
1567
1577
7.84
8.04
1594
1603
8.17
8.38
1620
1629
8.51
8.72
1645
1654
8.86
9.07
1671
1679
9.20
9.42
9400 1426 6.27 1453 6.59 1481 6.91 1508 7.24 1535 7.57 1561 7.91 1587 8.25 1613 8.59 1638 8.94 1663 9.29 1688 9.64
9600 1437 6.46 1465 6.78 1492 7.11 1519 7.44 1545 7.78 1571 8.12 1597 8.46 1623 8.81 1648 9.16 1673 9.51 1697 9.87
9800 1450 6.65 1477 6.98 1503 7.31 1530 7.65 1556 7.99 1582 8.33 1607 8.68 1633 9.03 1658 9.38 1682 9.74 1707 10.10
10000 1462 6.85 1489 7.18 1515 7.52 1541 7.86 1567 8.20 1593 8.55 1618 8.90 1643 9.25 1668 9.61 1692 9.97 1716 10.27
10200 1474 7.06 1501 7.39 1527 7.73 1553 8.07 1578 8.42 1604 8.77 1629 9.13 1653 9.48 1678 9.85 1702 10.21 1726 10.51
10400 1487 7.27 1513 7.61 1539 7.95 1564 8.30 1590 8.65 1615 9.00 1639 9.36 1664 9.72 1688 10.09 1712 10.39 1736 10.76
10600 1499 7.48 1525 7.83 1551 8.17 1576 8.52 1601 8.88 1626 9.24 1651 9.60 1675 9.96 1699 10.26 1722 10.63 1746 11.01
10800 1512 7.70 1538 8.05 1563 8.40 1588 8.76 1613 9.11 1638 9.48 1662 9.84 1686 10.21 1709 10.51 1733 10.89 1756 11.27
11000 1525 7.93 1551 8.28 1576 8.63 1600 8.99 1625 9.36 1649 9.72 1673 10.09 1697 10.40 1720 10.77 1744 11.15 1767 11.53 II
11200 1538 8.16 1563 8.52 1588 8.87 1613 9.24 1637 9.60 1661 9.97 1685 10.28 1708 10.65 1732 11.03 1755 11.41 1777 11.80
11400 1551 8.40 1576 8.76 1601 9.12 1625 9.49 1649 9.86 1673 10.23 1696 10.54 1720 10.92 1743 11.30 1766 11.68 1788 12.07
11600 1565 8.64 1589 9.00 1614 9.37 1638 9.74 1661 10.12 1685 10.42 1708 10.80 1731 11.19 1754 11.57 1777 11.96 1799 12.35
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 11.0 KW motor to be used for unshaded portion.
3. Alt. 15.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

54
Page 93 of 286
FAN PERFORMANCE DATA
Model No.: PTX030/031 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 601
9700 562 3.36 597 3.71 630 4.07 662 4.43 693 4.81 724 5.19 752 5.58 780 5.98 808 6.39 834 6.80 859 7.22
9900 566 3.50 3.85 634 4.22 666 4.59 697 4.97 727 5.36 755 5.76 783 6.16 810 6.57 836 6.99 862 7.36
10100 571 3.65 605 4.01 638 4.38 670 4.75 700 5.14 730 5.53 758 5.93 786 6.34 813 6.76 839 7.18 864 7.55
10300 575 3.80 609 4.16 642 4.54 673 4.92 704 5.31 733 5.71 761 6.11 789 6.53 815 6.95 841 7.32 867 7.75
10500 580 3.95 614 4.32 646 4.70 677 5.09 707 5.48 736 5.89 764 6.30 792 6.72 818 7.14 844 7.52 869 7.95
10700 585 4.11 618 4.49 650 4.87 681 5.26 710 5.66 739 6.07 767 6.49 795 6.91 821 7.29 847 7.72 872 8.16
10900 590 4.28 622 4.66 654 5.05 684 5.44 714 5.85 743 6.26 770 6.68 797 7.11 824 7.49 849 7.93II874 8.37
11100 594 4.45 627 4.83 658 5.23 688 5.63 718 6.04 746 6.46 774 6.88 800 7.26 827 7.70 852 8.14 877 8.59
11300 599 4.62 631 5.01 662 5.41 692 5.82 721 6.23 749 6.66 777 7.09 803 7.47 829 7.91 855 8.36 879 8.81
11600 607 4.89 638 5.29 668 5.70 698 6.11 727 6.54 754 6.96 781 7.35 808 7.79 834 8.24 859 8.69 883 9.15
11800 612 5.08 642 5.48 673 5.90 702 6.31 730 6.74 758 7.18 785 7.56 811 8.01 837 8.46 862 8.92 886 9.39
12000 616 5.27 647 5.68 677 6.10 706 6.52 734 6.95 761 7.34 788 7.78 814 8.23 840 8.69 864 9.16 889 9.63
12200 621 5.46 652 5.88 681 6.30 710 6.73 738 7.17 765 7.56 792 8.01 817 8.46 843 8.93 867 9.40 891 9.87
12400 626 5.67 656 6.09 685 6.52 714 6.95 741 7.34 769 7.78 795 8.24 821 8.70 846 9.17 870 9.64 894 10.12
12600 631 5.87 661 6.30 690 6.73 718 7.17 745 7.56 772 8.02 798 8.47 824 8.94 849 9.41 873 9.89 897 10.38
12800 636 6.08 666 6.52 694 6.96 722 7.35 749 7.79 776 8.25 802 8.71 827 9.19 852 9.66 876 10.14 900 10.64
13000 641 6.30 670 6.74 699 7.18 726 7.58 753 8.03 780 8.49 805 8.96 830 9.44 855 9.92 879 10.41 903 10.90
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 7.5 KW motor to be used for unshaded portion.
3. Alt. 11.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.
Model No.: PTX030/031 (BACKWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
9700
I 1492
1453 6.67 1480 7.00 1507 7.33 1534 7.66 1560 8.00 1586 8.34 1611 8.69 1637 9.04 1661 9.39 1686 9.75 1711 10.11
9900 1466 6.87 7.20 1519 7.54 1545 7.88 1571 8.22 1597 8.57 1622 8.92 1647 9.27 1672 9.63 1696 9.99 1720 10.28
10100 1478 7.08 1505 7.41 1531 7.75 1557 8.09 1582 8.44 1608 8.79 1633 9.14 1657 9.50 1682 9.86 1706 10.23 1730 10.53
10300 1491 7.29 1517 7.63 1543 7.97 1568 8.32 1594 8.67 1619 9.02 1643 9.38 1668 9.74 1692 10.11 1716 10.41 1740 10.78
10500 1503 7.51 1529 7.85 1555 8.20 1580 8.55 1605 8.90 1630 9.26 1655 9.62 1679 9.98 1703 10.29 1727 10.66 1750 11.03
10700 1516 7.73 1542 8.08 1567 8.43 1592 8.78 1617 9.14 1642 9.50 1666 9.87 1690 10.23 1714 10.54 1737 10.91 1760 11.29
10900 1529 7.96 1555 8.31 1580 8.66 1604 9.02 1629 9.38 1653 9.75 1677 10.12 1701 10.42 1725 10.80 1748 11.17 1771 11.55
11100 1542 8.19 1567 8.55 1592 8.90 1617 9.27 1641 9.63 1665 10.00 1689 10.31 1712 10.68 1736 11.06 1759 11.44 1782 11.82
11300 1556 8.43 1580 8.79 1605 9.15 1629 9.52 1653 9.89 1677 10.19 1701 10.57 1724 10.95 1747 11.33 1770 11.71 1792 12.10
II
11600 1576 8.80 1600 9.17 1624 9.53 1648 9.91 1672 10.22 1695 10.59 1719 10.97 1742 11.36 1764 11.74 1787 12.13 1809 12.53
11800 1589 9.06 1613 9.42 1637 9.80 1661 10.17 1685 10.48 1708 10.86 1731 11.25 1753 11.64 1776 12.03 1798 12.42 1820 12.82
12000 1603 9.31 1627 9.69 1651 10.06 1674 10.38 1697 10.76 1720 11.14 1743 11.53 1765 11.92 1788 12.32 1810 12.72 1832 13.12
12200 1617 9.58 1640 9.96 1664 10.27 1687 10.65 1710 11.04 1733 11.43 1755 11.82 1778 12.22 1800 12.61 1822 13.02 1843 13.42
12400 1631 9.85 1654 10.23 1677 10.55 1700 10.94 1723 11.33 1746 11.72 1768 12.11 1790 12.51 1812 12.92 1834 13.32 1855 13.73
12600 1645 10.13 1668 10.45 1691 10.84 1714 11.23 1736 11.62 1758 12.02 1781 12.42 1802 12.82 1824 13.23 1846 13.64 1867 14.05
12800 1659 10.35 1682 10.74 1704 11.13 1727 11.52 1749 11.92 1771 12.32 1793 12.72 1815 13.13 1837 13.54 1858 13.95 1879 14.37
13000 1673 10.64 1696 11.03 1718 11.42 1741 11.82 1763 12.22 1785 12.63 1806 13.04 1828 13.45 1849 13.86 1870 14.28 1891 14.70
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 11 KW motor to be used for unshaded portion.
3. Alt. 15.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

55
Page 94 of 286
FAN PERFORMANCE DATA
Model No.: PTX035/036 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
10600
10900
595
602
4.17
4.43
I 635
628 4.55
4.81
660
666
4.93
5.20
690
696
5.33
5.60
720
725
5.73
6.01
748
754
6.14
6.43
776
781
6.55
6.85
803
808
6.98
7.23
829
834
7.35
7.66
855
859
7.78
8.10
880
884
8.22
8.55
11200 610 4.69 642 5.08 672 5.48 702 5.89 731 6.30 759 6.73 786 7.16 812 7.54 838 7.98 863 8.43 II8.88
888
11500 617 4.96 648 5.36 679 5.77 708 6.19 736 6.61 764 7.04 791 7.42 817 7.86 843 8.31 868 8.77 892 9.23
11800 625 5.25 655 5.66 685 6.07 714 6.50 742 6.93 769 7.31 796 7.75 822 8.20 847 8.66 872 9.12 896 9.59
12100 632 5.55 662 5.96 692 6.39 720 6.82 748 7.20 775 7.64 801 8.09 827 8.55 852 9.01 877 9.48 900 9.96
12400 640 5.86 670 6.28 698 6.71 726 7.15 754 7.54 780 7.99 807 8.44 832 8.91 857 9.38 881 9.86 905 10.27
12700 648 6.18 677 6.61 705 7.05 733 7.44 760 7.89 786 8.34 812 8.81 837 9.28 862 9.76 886 10.24 909 10.66
13000 655 6.51 684 6.95 712 7.34 739 7.79 766 8.25 792 8.71 817 9.19 842 9.66 867 10.15 890 10.57 914 11.07
13300 663 6.85 691 7.25 719 7.70 746 8.16 772 8.62 798 9.10 823 9.58 847 10.06 872 10.48 895 10.98 III11.48
918
13600 671 7.21 699 7.61 726 8.07 752 8.54 778 9.01 804 9.49 828 9.98 853 10.40 877 10.90 900 11.40 923 11.91
13900 679 7.52 706 7.98 733 8.45 759 8.93 784 9.41 810 9.90 834 10.32 858 10.82 882 11.33 905 11.84 928 12.35
14200 686 7.90 713 8.37 740 8.85 765 9.33 791 9.82 815 10.25 840 10.75 864 11.26 887 11.77 910 12.28 932 12.81
14400 692 8.16 718 8.64 744 9.12 770 9.61 795 10.11 820 10.54 844 11.04 867 11.55 891 12.07 913 12.59 936 13.12
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 7.5 KW motor to be used for unshaded portion.
3. Alt. 11.0 KW & 15.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX035/036 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 1564
10600 1519 7.75 1545 8.09 1571 8.44 1596 8.80 1621 9.15 1645 9.52 1669 9.88 1693 10.18 1717 10.55 1741 10.92 1764 11.30
10900 1539 8.09 8.45 1589 8.80 1614 9.16 1638 9.52 1663 9.89 1687 10.20 1710 10.57 1734 10.94 1757 11.32 1780 11.70 II
11200 1559 8.45 1584 8.81 1608 9.17 1633 9.54 1657 9.91 1681 10.21 1704 10.59 1727 10.97 1751 11.35 1773 11.73 1796 12.12
11500 1579 8.83 1604 9.19 1628 9.56 1652 9.93 1675 10.24 1699 10.61 1722 10.99 1745 11.38 1768 11.76 1790 12.15 1813 12.55
11800 1600 9.21 1624 9.58 1648 9.96 1671 10.27 1694 10.65 1718 11.03 1740 11.41 1763 11.80 1785 12.19 1808 12.59 1830 12.99
12100 1620 9.61 1644 9.99 1667 10.30 1691 10.68 1714 11.07 1736 11.45 1759 11.85 1781 12.24 1803 12.64 1825 13.04 1847 13.45
12400 1641 10.02 1665 10.34 1688 10.72 1711 11.11 1733 11.50 1756 11.90 1778 12.29 1800 12.69 1822 13.10 1843 13.51 1865 13.92
12700 1662 10.38 1685 10.77 1708 11.16 1731 11.55 1753 11.95 1775 12.35 1797 12.76 1819 13.16 1840 13.57 1862 13.99 1883 14.40
13000 1684 10.82 1706 11.22 1729 11.61 1751 12.01 1773 12.42 1795 12.82 1816 13.23 1838 13.64 1859 14.06 1880 14.48 1901 14.81
13300 1705 11.28 1728 11.68 1750 12.08 1772 12.48 1793 12.89 1815 13.31 1836 13.72 1857 14.14 1878 14.56 1899 14.89 1920 15.32
13600 1727 11.74 1749 12.15 1771 12.56 1792 12.97 1814 13.39 1835 13.81 1856 14.23 1877 14.65 1898 14.99 1918 15.41 1938 15.85

III
13900 1749 12.23 1771 12.64 1792 13.06 1813 13.47 1835 13.90 1855 14.32 1876 14.66 1897 15.08 1917 15.52 1937 15.95 1957 16.39
14200 1771 12.73 1792 13.15 1814 13.57 1835 13.99 1855 14.42 1876 14.76 1897 15.19 1917 15.62 1937 16.06 1957 16.50 1977 16.95
14400 1786 13.07 1807 13.49 1828 13.92 1849 14.35 1870 14.69 1890 15.12 1910 15.55 1930 15.99 1950 16.43 1970 16.88 1990 17.33
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 11.0 KW motor to be used for unshaded portion.
3. Alt. 15.0 KW & 18.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

56
Page 95 of 286
FAN PERFORMANCE DATA
Model No.: PTX040 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
12400
12700
468
472
3.76
3.94
I 505
501 4.21
4.40
532
536
4.67
4.87
562
565
5.15
5.35
591
594
5.65
5.86
619
622
6.16
6.37
645
648
6.68
6.90
671
673
7.21
7.44
696
698
7.75
7.99
720
722
8.31
8.55
743
745
8.87
9.12
13000 477 4.13 508 4.59 539 5.07 568 5.56 597 6.07 624 6.59 650 7.13 676 7.67 700 8.23 724 8.80 747 9.38
13300 481 4.33 512 4.80 543 5.28 572 5.78 600 6.29 627 6.82 653 7.36 678 7.91 703 8.48 726 9.06 749 9.64
13600 485 4.54 516 5.01 546 5.50 575 6.00 603 6.52 630 7.06 656 7.60 681 8.16 705 8.74 729 9.32 751 9.91
13900 490 4.75 520 5.23 550 5.72 578 6.23 606 6.76 632 7.30 658 7.85 683 8.42 707 9.00 731 9.59 754 10.19
14200 494 4.97 524 5.45 553 5.95 582 6.47 609 7.00 635 7.55 661 8.1 1 686 8.68 710 9.27 733 9.86 756 10.40
14500 499 5.19 528 5.68 557 6.19 585 6.72 612 7.26 638 7.81 664 8.37 688 8.96 712 9.55 735 10.15 758 10.69
14800 503 5.43 533 5.92 561 6.44 589 6.97 615 7.51 641 8.07 666 8.65 691 9.23 715 9.83 738 10.37 760 10.99
15100 508 5.67 537 6.17 565 6.69 592 7.23 619 7.78 644 8.35 669 8.93 693 9.52 717 10.12 740 10.67 762 11.29
15400 513 5.92 541 6.43 569 6.96 596 7.50 622 8.06 648 8.63 672 9.22 696 9.81 720 10.36 742 10.97 765 11.60
15700 517 6.18 545 6.69 573 7.23 599 7.78 625 8.34 651 8.92 675 9.51 699 10.12 722 10.66 745 11.29 767 11.92
16000 522 6.44 550 6.97 577 7.50 603 8.06 629 8.63 654 9.21 678 9.81 702 10.36 725 10.98 747 11.61II769 12.25
16300 527 6.72 554 7.25 581 7.79 607 8.35 632 8.93 657 9.52 681 10.13 705 10.67 728 11.30 750 11.93 772 12.59
16600 531 7.00 559 7.54 585 8.09 611 8.66 636 9.24 660 9.84 684 10.38 708 11.00 730 11.63 753 12.27 774 12.92
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 11.0 KW motor to be used for unshaded portion.
3. Alt. 15.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

Model No.: PTX040 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I1300
12400 1263 8.05 1289 8.47 1314 8.90 1339 9.33 1364 9.77 1388 10.21 1413 10.67 1437 11.12 1461 11.59 1484 12.06 1508 12.53
12700 1274 8.32 8.75 1325 9.18 1349 9.61 1374 10.06 1398 10.51 1422 10.96 1446 11.43 1469 11.89 1493 12.37 1516 12.85
13000 1286 8.60 1311 9.03 1336 9.46 1360 9.91 1384 10.36 1408 10.81 1432 11.27 1455 11.74 1478 12.21 1501 12.69 1524 13.17
13300 1298 8.89 1323 9.32 1347 9.76 1371 10.21 1395 10.66 1418 11.12 1441 11.59 1465 12.06 1487 12.53 1510 13.02 1533 13.51
13600 1310 9.18 1334 9.62 1358 10.07 1382 10.52 1405 10.98 1429 11.44 1452 11.91 1474 12.39 1497 12.87 1519 13.36 1542 13.85
13900 1323 9.49 1346 9.93 1370 10.38 1393 10.84 1416 11.30 1439 11.77 1462 12.25 1484 12.73 1507 13.21 1529 13.71 1551 14.20
14200 1335 9.80 1359 10.25 1382 10.71 1405 11.17 1428 11.64 1450 12.11 1473 12.59 1495 13.08 1517 13.57 1539 14.06 1560 14.47
14500 1348 10.13 1371 10.58 1394 11.04 1417 11.51 1439 11.98 1461 12.46 1483 12.94 1505 13.43 1527 13.93 1549 14.34 1570 14.84
14800 1361 10.46 1384 10.92 1406 11.39 1429 11.86 1451 12.34 1473 12.82 1495 13.31 1516 13.80 1538 14.30 1559 14.71 1580 15.22
15100 1374 10.81 1397 11.27 1419 11.74 1441 12.22 1463 12.70 1484 13.19 1506 13.68 1527 14.18 1548 14.59 1570 15.10 1590 15.61
15400 1388 11.16 1410 11.63 1432 12.10 1453 12.59 1475 13.07 1496 13.57 1518 14.07 1539 14.48 1560 14.98 1580 15.50 1601 16.01
15700 1401 11.52 1423 12.00 1445 12.48 1466 12.97 1487 13.46 1508 13.96 1529 14.37 1550 14.87 1571 15.39 1591 15.90 1612 16.43 II
16000 1415 11.90 1436 12.38 1458 12.86 1479 13.36 1500 13.85 1521 14.27 1541 14.77 1562 15.28 1582 15.80 1602 16.32 1623 16.85
16300 1429 12.28 1450 12.77 1471 13.26 1492 13.76 1512 14.17 1533 14.67 1553 15.18 1574 15.70 1594 16.22 1614 16.75 1634 17.28
16600 1443 12.67 1464 13.17 1484 13.66 1505 14.17 1525 14.58 1546 15.09 1566 15.61 1586 16.13 1606 16.66 1625 17.19 1645 17.72

NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 15 KW motor to be used for unshaded portion.
3. Alt. 18.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

57
Page 96 of 286
FAN PERFORMANCE DATA
Model No.: PTX045 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 520
12800 484 4.15 516 4.61 546 5.08 575 5.58 604 6.09 631 6.61 657 7.14 682 7.69 706 8.24 730 8.80 753 9.38
13100 488 4.34 4.81 550 5.29 579 5.79 607 6.31 633 6.84 659 7.38 684 7.93 709 8.49 732 9.06 755 9.65
13400 493 4.55 524 5.02 553 5.51 582 6.02 610 6.54 636 7.07 662 7.62 687 8.18 711 8.75 735 9.33 757 9.92
13700 497 4.76 528 5.24 557 5.74 586 6.25 613 6.78 639 7.32 665 7.87 690 8.44 714 9.02 737 9.61 760 10.20
14000 502 4.98 532 5.47 561 5.97 589 6.49 616 7.02 642 7.57 668 8.13 692 8.70 716 9.29 739 9.88 762 10.42
14300 506 5.21 536 5.70 565 6.21 592 6.74 619 7.28 645 7.83 671 8.40 695 8.98 719 9.57 742 10.17 764 10.71
14600 511 5.45 540 5.94 569 6.46 596 6.99 623 7.54 649 8.10 673 8.67 698 9.26 721 9.86 744 10.40 767 11.01
14900 516 5.69 544 6.19 572 6.72 600 7.26 626 7.81 652 8.38 677 8.96 701 9.55 724 10.15 747 10.70 769 11.32
15200 520 5.94 549 6.45 577 6.98 603 7.52 630 8.09 655 8.66 679 9.24 703 9.84 727 10.39 749 11.00 771 11.63
15500 525 6.20 553 6.72 581 7.25 607 7.81 633 8.37 658 8.95 683 9.54 706 10.15 729 10.69 752 11.32 774 11.95
15800 530 6.47 558 6.99 585 7.54 611 8.09 637 8.66 661 9.25 686 9.85 709 10.39 732 11.01 755 11.64 776 12.28
16100 535 6.75 562 7.27 589 7.82 615 8.39 640 8.97 665 9.56 689 10.16 712 10.71 735 11.34 II
757 11.97 779 12.62
16400 540 7.03 567 7.57 593 8.12 619 8.69 644 9.28 668 9.87 692 10.42 715 11.04 738 11.67 760 12.32 782 12.97
16700 545 7.32 571 7.87 597 8.43 623 9.00 647 9.60 672 10.20 695 10.75 718 11.37 741 12.01 763 12.66 784 13.32
17000 549 7.62 576 8.18 602 8.74 627 9.33 651 9.92 675 10.47 698 11.08 721 11.72 744 12.36 766 13.02 787 13.69
17300 555 7.94 580 8.50 606 9.07 631 9.66 655 10.20 679 10.81 702 11.43 725 12.07 747 12.72 768 13.38 790 14.06

NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 11.0 KW motor to be used for unshaded portion.
3. Alt. 15.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.

Model No.: PTX045 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
CFM 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 1323
12800 1286 8.54 1311 8.97 1336 9.41 1360 9.85 1385 10.29 1409 10.75 1432 11.21 1456 11.67 1479 12.14 1503 12.62 1525 13.10
13100 1298 8.83 9.26 1347 9.70 1371 10.15 1395 10.60 1419 11.06 1442 11.52 1465 11.99 1489 12.47 1511 12.95 1534 13.44
13400 1310 9.13 1334 9.56 1358 10.01 1382 10.46 1406 10.91 1429 11.38 1452 11.85 1475 12.32 1498 12.80 1520 13.29 1543 13.78
13700 1322 9.43 1346 9.87 1370 10.32 1393 10.78 1417 11.24 1440 11.71 1463 12.18 1485 12.66 1508 13.14 1530 13.64 1552 14.13
14000 1335 9.74 1358 10.19 1382 10.65 1405 11.11 1428 11.57 1451 12.05 1473 12.52 1495 13.01 1518 13.50 1540 13.99 1561 14.40
14300 1348 10.07 1371 10.52 1394 10.98 1417 11.45 1439 11.92 1462 12.39 1484 12.88 1506 13.37 1528 13.86 1550 14.27 1571 14.77
14600 1361 10.40 1384 10.86 1406 11.32 1429 11.79 1451 12.27 1473 12.75 1495 13.24 1517 13.73 1538 14.23 1560 14.64 1581 15.15 II
14900 1374 10.74 1396 11.21 1419 11.68 1441 12.15 1463 12.63 1485 13.12 1506 13.61 1528 14.11 1549 14.52 1570 15.03 1591 15.54
15200 1387 11.10 1409 11.57 1431 12.04 1453 12.52 1475 13.01 1496 13.50 1518 14.00 1539 14.41 1560 14.91 1581 15.42 1602 15.94
15500 1401 11.46 1422 11.93 1444 12.41 t1466 12.90 1487 13.39 1508 13.89 1530 14.30 1550 14.80 1571 15.31 1592 15.83 1612 16.35
15800 1414 11.83 1436 12.31 1457 12.80 1479 13.29 1500 13.79 1521 14.20 1541 14.70 1562 15.21 1583 15.73 1603 16.25 1623 16.77
16100 1428 12.22 1449 12.70 1471 13.19 1492 13.69 1512 14.19 1533 14.60 1554 15.11 1574 15.63 1594 16.15 1614 16.67 1634 17.21
16400 1442 12.61 1463 13.10 1484 13.60 1505 14.10 1525 14.51 1546 15.02 1566 15.54 1586 16.06 1606 16.58 1626 17.11 1646 17.65
16700 1456 13.02 1477 13.51 1497 14.01 1518 14.43 1538 14.94 1558 15.45 1578 15.97 1598 16.50 1618 17.03 1638 17.56 1657 18.10
17000 1470 13.43 1491 13.93 1511 14.35 1531 14.86 1551 15.37 1571 15.89 1591 16.42 1611 16.95 1630 17.48 1650 18.02 1669 18.57 III
17300 1485 13.86 1505 14.27 1525 14.78 1545 15.30 1565 15.82 1584 16.34 1604 16.87 1623 17.41 1643 17.95 1662 18.49 1681 19.04

NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 15.0 KW motor to be used for unshaded portion.
3. Alt. 18.5 KW & 22.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

58
Page 97 of 286
FAN PERFORMANCE DATA
Model No.: PTX050 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I 546
14000 512 5.14 541 5.63 570 6.14 598 6.66 625 7.20 651 7.76 676 8.32 700 8.89 724 9.48 747 10.08 769 10.62
14300 516 5.37 5.87 574 6.38 602 6.92 628 7.46 654 8.02 679 8.59 703 9.17 727 9.77 749 10.31 II
772 10.92
14600 521 5.61 550 6.12 578 6.64 605 7.18 632 7.73 657 8.29 682 8.87 706 9.46 729 10.06 752 10.61 774 11.22
14900 526 5.86 554 6.38 582 6.90 609 7.45 635 8.00 660 8.58 685 9.16 709 9.76 732 10.30 755 10.91 777 11.54
15200 531 6.12 559 6.64 586 7.17 613 7.73 639 8.29 664 8.87 688 9.46 712 10.06 735 10.61 757 11.23 779 11.86
15500 536 6.39 563 6.91 590 7.45 617 8.01 642 8.58 667 9.16 691 9.76 715 10.30 738 10.92 760 11.55 782 12.19
15800 540 6.66 568 7.19 595 7.74 621 8.31 646 8.88 671 9.47 695 10.08 718 10.62 741 11.25 763 11.88 784 12.53
16100 545 6.95 572 7.48 599 8.04 625 8.61 650 9.19 674 9.79 698 10.33 721 10.95 744 11.58 766 12.22 787 12.87
16400 550 7.24 577 7.78 603 8.34 629 8.92 653 9.51 677 10.11 701 10.66 724 11.28 747 11.92 768 12.57 790 13.23
16700 555 7.54 582 8.09 608 8.66 633 9.24 657 9.83 681 10.38 704 11.00 727 11.63 750 12.27 771 12.92 793 13.59
17000 560 7.85 586 8.41 612 8.98 637 9.57 661 10.17 685 10.71 708 11.34 731 11.98 753 12.63 774 13.29 795 13.96
17300 565 8.17 591 8.73 616 9.31 641 9.90 665 10.45 688 11.07 711 11.70 734 12.34 756 13.00 777 13.66 798 14.25
17600 570 8.49 596 9.06 621 9.65 645 10.19 669 10.80 692 11.42 715 12.06 737 12.71 759 13.37 780 14.04 801 14.64
17900 576 8.83 601 9.41 625 10.00 649 10.54 673 11.16 696 11.79 718 12.43 741 13.09 762 13.76 783 14.35 804 15.03

*** III***
18200 581 9.18 605 9.76 630 10.30 654 10.91 677 11.53 700 12.17 722 12.82 744 13.48 765 14.06 786 14.74 *** ***
18500 586 9.53 610 10.13 634 10.66 658 11.28 681 11.91 703 12.55 726 13.21 747 13.88 769 14.46 789 15.15
18800 591 9.90 615 10.43 639 11.04 662 11.66 685 12.30 707 12.95 729 13.61 751 14.20 772 14.88 *** *** *** ***

NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 11.0 KW motor to be used for unshaded portion.
3. Alt. 15.0 KW & 18.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.
Model No.: PTX050 (BACKWARD FAN)
External Static Pressure (inch wg.)
Airflow,
CFM 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I
14000 1343 9.89 1366 10.34 1389 10.80 1412 11.26 1435 11.73 1458 12.20 1480 12.68 1503 13.17 1525 13.66 1547 13.67 1568 14.16
14300 1355 10.22 1379 10.67 1402 11.14 1424 11.60 1447 12.08 1469 12.56 1491 13.04 1513 13.53 1535 14.03 1557 14.03 1578 14.52
14600 1368 10.56 1391 11.02 1414 11.48 1436 11.96 1459 12.44 1481 12.92 1503 13.41 1524 13.90 1546 13.91 1567 14.40 1588 14.90
14900 1382 10.91 1404 11.37 1426 11.84 1449 12.32 1471 12.80 1492 13.29 1514 13.79 1535 13.80 1557 14.29 1578 14.78 1599 15.28 II
15200 1395 11.26 1417 11.74 1439 12.21 1461 12.70 1483 13.18 1504 13.68 1525 13.69 1547 14.18 1568 14.67 1588 15.17 1609 15.68
15500 1409 11.63 1430 12.11 1452 12.59 1474 13.08 1495 13.57 1516 14.07 1537 14.08 1558 14.57 1579 15.07 1599 15.57 1620 16.08
15800 1422 12.01 1444 12.49 1465 12.98 1487 13.47 1508 13.97 1528 13.98 1549 14.47 1570 14.97 1590 15.47 1611 15.98 1631 16.50
16100 1436 12.40 1457 12.89 1479 13.38 1500 13.88 1520 13.89 1541 14.38 1561 14.88 1582 15.38 1602 15.89 1622 16.40 1642 16.92
16400 1450 12.80 1471 13.29 1492 13.79 1513 13.81 1533 14.30 1554 14.80 1574 15.30 1594 15.81 1614 16.32 1634 16.84 1653 17.36
16700 1464 13.21 1485 13.71 1506 13.73 1526 14.22 1546 14.72 1566 15.22 1586 15.73 1606 16.24 1626 16.76 1645 17.28 1665 17.81
17000 1479 13.64 1499 14.14 1519 14.15 1540 14.64 1559 15.15 1579 15.65 1599 16.16 1619 16.68 1638 17.20 1657 17.73 1677 18.26

III
17300 1493 14.07 1513 14.08 1533 14.58 1553 15.08 1573 15.59 1592 16.10 1612 16.61 1631 17.14 1651 17.66 1670 18.20 1689 18.73
17600 1508 14.02 1528 14.51 1547 15.02 1567 15.52 1586 16.04 1606 16.55 1625 17.08 1644 17.60 1663 18.14 1682 18.67 1701 19.21
17900 1522 14.46 1542 14.96 1561 15.47 1581 15.98 1600 16.50 1619 17.02 1638 17.55 1657 18.08 1676 18.62 1695 19.16 1713 19.71
18200 1537 14.91 1556 15.42 1576 15.93 1595 16.45 1614 16.97 1633 17.50 1652 18.03 1670 18.57 1689 19.11 1707 19.66 1726 20.21
18500 1552 15.37 1571 15.88 1590 16.40 1609 16.93 1628 17.46 1646 17.99 1665 18.53 1683 19.07 1702 19.62 1720 20.17 1738 20.73
18800 1567 15.84 1586 16.36 1605 16.89 1623 17.42 1642 17.95 1660 18.49 1679 19.03 1697 19.58 1715 20.13 1733 20.69 1751 21.25
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 15 KW motor to be used for unshaded portion.
3. Alt. 18.5 KW & 22.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

59
Page 98 of 286
FAN PERFORMANCE DATA
Model No.: PTX060 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
16600
16900 I
421 5.12 448 5.70 475 6.28 501 6.89 525 7.51 549 8.14 572 8.79 594 9.44 615 10.12 636 10.80 656 11.49
424 5.32 451 5.90 478 6.49 503 7.10 528 7.73 551 8.36 574 9.02 596 9.68 617 10.36 638 11.05 658 11.75
17200 427 5.51 454 6.10 480 6.70 505 7.32 530 7.95 553 8.60 576 9.26 598 9.93 619 10.62 639 11.31 659 12.02
17500 430 5.72 457 6.31 483 6.92 508 7.55 532 8.18 555 8.84 578 9.51 600 10.19 621 10.88 641 11.58 661 12.30
17800 433 5.93 460 6.52 486 7.14 511 7.78 534 8.42 557 9.08 580 9.76 601 10.45 622 11.14 643 11.85 663 12.57
18100 437 6.14 463 6.75 489 7.37 513 8.01 537 8.66 560 9.33 582 10.01 603 10.71 624 11.42 645 12.13 664 12.86
18400 440 6.36 466 6.97 491 7.61 516 8.25 539 8.91 562 9.59 584 10.27 605 10.98 626 11.69 646 12.42 666 13.15
18700 443 6.58 469 7.21 494 7.85 518 8.50 542 9.17 564 9.85 586 10.55 607 11.26 628 11.97 648 12.71 668 13.45
19000 447 6.82 472 7.45 497 8.09 521 8.75 544 9.43 566 10.12 588 10.82 609 11.53 630 12.26 650 13.00 669 13.75
19300 450 7.05 475 7.69 500 8.35 523 9.01 546 9.69 569 10.39 590 11.10 612 11.82 632 12.56 652 13.30 671 14.06
19600 453 7.29 478 7.94 503 8.60 526 9.28 549 9.97 571 10.67 593 11.39 614 12.12 634 12.86 654 13.61 673 14.28
19900 457 7.54 482 8.20 506 8.87 529 9.55 552 10.25 574 10.96 595 11.68 616 12.41 636 13.16 656 13.92 675 14.60
20200
20500
460 7.80 485 8.46 509 9.14 532 9.83 554 10.53 576 11.25 597 11.98 618 12.72 638 13.48 658 14.15 677 14.92
463 8.06 488 8.73 511 9.41 534 10.11 557 10.82 578 11.54 599 12.28 620 13.03 640 13.79 660 14.48 679 15.26
II
20800 467 8.33 491 9.01 515 9.70 537 10.40 559 11.12 581 11.85 602 12.59 622 13.35 642 14.12 662 14.80 681 15.59
21100 470 8.60 494 9.29 518 9.99 540 10.70 562 11.42 583 12.16 604 12.91 625 13.68 644 14.36 664 15.14 682 15.94
21400 474 8.89 498 9.58 521 10.28 543 11.00 565 11.73 586 12.48 607 13.24 627 14.01 646 14.70 666 15.49 684 16.28
21700 477 9.17 501 9.87 524 10.58 546 11.31 567 12.05 588 12.80 609 13.57 629 14.26 649 15.04 668 15.84 686 16.64
22000 481 9.47 504 10.17 527 10.89 549 11.63 570 12.37 591 13.14 611 13.91 631 14.60 651 15.39 670 16.19 688 17.00
22300 485 9.76 507 10.48 530 11.21 552 11.95 573 12.71 594 13.47 614 14.16 634 14.95 653 15.74 672 16.56 690 17.38
22400 486 9.87 509 10.58 531 11.32 553 12.06 574 12.82 594 13.58 615 14.27 635 15.07 654 15.86 673 16.68 691 17.50
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 15.0 KW motor to be used for unshaded portion.
3. Alt. 18.5 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I & II.
Model No.: PTX060 (BACKWARD FAN)
External Static Pressure (inch wg.)
Airflow,
2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
16600
16900
1136 10.85
1145 11.14 I 1157 11.37
1166 11.67
1178 11.91
1187 12.21
1199 12.45
1207 12.76
1220 13.00 1240 13.55 1260 14.11 1280 14.59 1300 15.16
1228 13.31 1248 13.87 1268 14.35 1288 14.91 1307 15.49 II
1320 15.74
1327 16.07
1339 16.32
1346 16.66
17200 1154 11.44 1175 11.98 1195 12.52 1215 13.08 1236 13.63 1256 14.11 1275 14.68 1295 15.25 1314 15.83 1334 16.42 1353 17.01
17500 1163 11.75 1183 12.29 1204 12.84 1224 13.40 1244 13.96 1263 14.44 1283 15.01 1302 15.59 1322 16.18 1341 16.77 1359 17.37
17800 1172 12.07 1192 12.62 1212 13.17 1232 13.73 1252 14.30 1271 14.78 1291 15.36 1310 15.94 1329 16.53 1348 17.13 1366 17.73
18100 1181 12.39 1201 12.95 1221 13.50 1241 14.07 1260 14.55 1280 15.13 1299 15.71 1318 16.30 1336 16.89 1355 17.50 1374 18.10
18400 1190 12.72 1210 13.28 1230 13.85 1249 14.42 1269 14.90 1288 15.48 1307 16.07 1326 16.66 1344 17.26 1363 17.87 1381 18.48
18700 1200 13.06 1219 13.63 1239 14.11 1258 14.68 1277 15.26 1296 15.85 1315 16.44 1333 17.04 1352 17.64 1370 18.25 1388 18.87
19000 1209 13.41 1229 13.98 1248 14.46 1267 15.04 1286 15.63 1305 16.22 1323 16.81 1342 17.42 1360 18.03 1378 18.65 1396 19.27
19300 1219 13.76 1238 14.34 1257 14.82 1276 15.41 1295 16.00 1313 16.60 1
1332 7.20 1350 17.81 1368 18.42 1386 19.05 1404 19.67
19600
19900
1228 14.13
1238 14.41
1247
1257
14.61
14.99
1266
1276
15.20
15.58
1285
1294
15.79
16.17
1303
1312
16.38
16.77
1322
1331
16.98
17.38
III
1340 17.59 1358 18.21
1349 17.99 1367 18.61
1376
1384
18.83
19.24
1394
1402
19.45
19.87
1411
1419
20.09
20.51
20200 1248 14.78 1267 15.37 1285 15.96 1303 16.56 1321 17.17 1339 17.78 1357 18.40 1375 19.03 1393 19.66 1410 20.29 1427 20.94
20500 1258 15.17 1276 15.76 1295 16.36 1313 16.97 1331 17.58 1348 18.20 1366 18.82 1384 19.45 1401 20.09 1418 20.731436 21.26
20800 1268 15.56 1286 16.16 1304 16.76 1322 17.38 1340 17.99 1358 18.62 1375 19.25 1392 19.88 1410 20.52 1427 21.17 1444 21.71
21100 1278 15.96 1296 16.57 1314 17.18 1332 17.79 1349 18.42 1367 19.05 1384 19.68 1401 20.32 1418 20.97 1435 21.51IV1452 22.16
21400 1288 16.37 1306 16.98
1324 17.60 1341 18.22 1359 18.85 1376 19.48 1393 20.12 1410 20.77 1427 21.31 1444 21.96 1461 22.62
21700 1298 16.79 1316 17.41
1333 18.03 1351 18.66 1368 19.29 1385 19.93 1402 20.58 1419 21.23 1436 21.77 1453 22.43 1469 23.09
22000 1308 17.22 1326 17.84 1343 18.47 1361 19.10 1378 19.74 1395 20.39 1412 21.04 1428 21.58 1445 22.24 1461 22.90 1478 23.57
22300 1319 17.66 1336 18.28 1353 18.92 1370 19.56 1387 20.20 1404 20.85 1421 21.40 1437 22.05 1454 22.72 1470 23.39 1487 24.06
22400 1322 17.80 1340 18.43 1357 19.07 1374 19.71 1391 20.36 1407 21.01 1424 21.55 1441 22.21 1457 22.88 1473 23.55 1489 24.23
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 15.0 KW motor to be used for unshaded portion.
3. Alt. 18.5 KW, 22.0 & 30 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II, III & IV.

60
Page 99 of 286
FAN PERFORMANCE DATA
Model No.: PTX070 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
18700
19100
450
455
6.75
7.07 I 476 7.38
480 7.71
501 8.02
505 8.36
525 8.68
528 9.03
548 9.35
551 9.71
570 10.04
573 10.40
592 10.74
595 11.11
613 11.45
616 11.83
634 12.17
636 12.57
654 12.91
656 13.31
673
675
13.65
14.07
19500 459 7.40 484 8.05 508 8.71 532 9.38 555 10.07 577 10.78 598 11.50 619 12.23 639 12.97 659 13.72 678 14.40
19900 464 7.74 489 8.39 513 9.07 536 9.75 558 10.45 580 11.17 601 11.90 622 12.63 642 13.39 661 14.15 680 14.83
20300 469 8.08 493 8.75 517 9.44 539 10.13 562 10.84 583 11.57 604 12.30 625 13.05 645 13.81 664 14.49 683 15.27
20700 473 8.45 497 9.13 521 9.82 543 10.52 565 11.24 587 11.97 607 12.72 628 13.48 647 14.16 667 14.94 686 II 15.72
21100 478 8.82 502 9.51 525 10.21 547 10.92 569 11.66 590 12.40 611 13.15 631 13.92 650 14.61 670 15.39 688 16.19
21500 483 9.20 506 9.90 529 10.61 551 11.34 572 12.08 593 12.83 614 13.59 634 14.28 653 15.06 672 15.86 691 16.66
21900 488 9.60 511 10.31 533 11.03 555 11.76 576 12.51 597 13.27 617 14.05 637 14.74 656 15.53 675 16.34 694 17.15
22300 492 10.00 515 10.72 537 11.46 559 12.20 580 12.96 601 13.73 621 14.42 640 15.21 659 16.01 678 16.83 697 17.65
22700 497 10.42 520 11.15 541 11.90 563 12.65 584 13.42 604 14.20 624 14.90 643 15.70 662 16.51 681 17.33 699 18.17
23100 502 10.85 524 11.59 546 12.35 567 13.11 587 13.89 608 14.59 627 15.39 647 16.20 666 17.02 684 17.85 702 18.69
23500 507 11.30 529 12.05 550 12.82 571 13.59 591 14.28 611 15.08 631 15.89 650 16.71 669 17.53 687 18.38 705 19.23
23900 512 11.76 533 12.52 554 13.29 575 14.08 595 14.78 615 15.59 634 16.40 653 17.23 672 18.07 690 18.92 708 19.78
24300 517 12.22 538 13.00 559 13.78 579 14.49 599 15.29 619 16.10 638 16.93 657 17.77 675 18.61 693 19.47 711 20.34
24700 521 12.71 543 13.49 563 14.20 583 14.99 603 15.81 623 16.63 642 17.47 660 18.31 679 19.17 697 20.04 714 20.93
25100
25300
526
529
13.20
13.46
547 14.00
550 14.16
568
570
14.71
14.97
588
590
15.52
15.79
607
609
16.34
16.62
627
629
17.18
17.45
645
647
18.02
18.30
664
666
18.88
19.16
682
684
19.75
20.04
700
701
20.62
20.92
***
***
III******
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 15.0 KW motor to be used for unshaded portion.
3. Alt. 18.5 KW & 22 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX070 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
RPM KW RPM KW RPM KW RPM KW
18700
19100
1205
1218
13.13
13.60 I1225
1237
13.69
14.17
1244
1256
14.26
14.74
1263
1275
14.84
15.33
1282 15.42 1301 16.01 1320 16.60 1339 17.20 1357 17.81 1375 18.42 1393 19.04
1294 15.91 1313 16.51 1331 17.11 1349 17.72 1368 18.33 1386 18.95 1403 19.58
II
19500 1231 14.08 1250 14.66 1269 15.24 1287 15.83 1306 16.42 1324 17.03 1342 17.64 1360 18.25 1378 18.87 1396 19.50 1414 20.13
19900 1244 14.58 1262 15.16 1281 15.75 1299 16.35 1318 16.95 1336 17.56 1354 18.17 1372 18.80 1389 19.42 1407 20.06 1424 20.70
20300 1257 15.09 1275 15.68 1294 16.28 1312 16.88 1330 17.49 1348 18.11 1366 18.73 1383 19.36 1401 19.99 1418 20.63 1435 21.28
20700 1270 15.61 1288 16.21 1306 16.82 1324 17.43 1342 18.04 1360 18.67 1377 19.30 1395 19.93 1412 20.57 1429 21.22 1446 21.76
21100 1284 16.15 1302 16.76 1319 17.37 1337 17.99 1355 18.61 1372 19.24 1389 19.88 1407 20.52 1424 21.17 1441 21.71 1457 22.37
21500 1297 16.71 1315 17.32 1333 17.94 1350 18.57 1367 19.20 1385 19.84 1402 20.48 1419 21.13 1435 21.67 1452 22.33 1469 22.99
21900 1311 17.28
1328 17.90 1346 18.53 1363 19.16 1380 19.80 1397 20.45
1414 21.10 1431 21.64 1447 22.30 1464 22.96 1480 23.63
22300 1325 17.87 1342 18.50 1359 19.13 1376 19.77 1393 20.42 1410 21.07 1426 21.61 1443 22.28 1459 22.94 1476 23.61 1492 24.29
22700 1338 18.47 1356 19.11 1373 19.75 1389 20.40 1406 21.05 1423 21.60 1439 22.26 1455 22.93 1472 23.60 1488 24.28 1504 24.96
23100 1352 19.09 1369 19.73 1386 20.39
1403 21.04 1419 21.59 1436 22.25 1452 22.92 1468 23.60 1484 24.28 1500 24.96 1516 25.65
23500 1367 19.73 1383 20.38 1400 21.04 1416 21.59 1433 22.25 1449 22.92 1465 23.60 1481 24.28 1497 24.97 1512 25.66 1528 26.36
23900 1381 20.38 1397 21.04 1414 21.59 1430 22.26 1446 22.93 1462 23.61 1478 24.30 1494 24.99 1509 25.68 1525 26.38 1540 27.09
24300 1395 21.05 1411 21.60 1428 22.27 1444 22.95 1459 23.63 1475 24.32 1491 25.01 1506 25.71 1522 26.41 1537 27.12 1553 27.83
24700 1410 21.62 1426 22.29 1442 22.97 1457 23.66 1473 24.35 1489 25.04 1504 25.74 1520 26.44 1535 27.15 1550 27.87 1565 28.59
25100
25300
1424 22.32 1440 23.00 1456 23.69 1471 24.38 1487 25.08 1502 25.78 1518 26.49
1431 22.68 1447 23.36 1463 24.06 1478 24.75 1494 25.45 1509 26.16 1524 26.87
1533 27.20 1548 27.92
1539 27.59 1554 28.31
1563 29 1578
1569 29 1584
III 29.37
29.76
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 18.5 KW motor to be used for unshaded portion.
3. Alt. 22.0 KW & 30.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

61
Page 100 of 286
FAN PERFORMANCE DATA
Model No.: PTX080 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
23000
23400 I
345 6.99 367 7.81 389 8.66 410 9.53 429 10.44 448 11.36 466 12.30 484 13.27 501 14.16 517 15.15 533 16.16
347 7.23 370 8.06 391 8.92 411 9.80 431 10.71 450 11.64 468 12.59 485 13.57 502 14.47 518 15.47 534 16.49 II
23800 350 7.48 372 8.31 393 9.18 413 10.08 433 10.99 451 11.93 469 12.89 487 13.88 504 14.79 520 15.80 536 16.82
24200 352 7.73 374 8.58 395 9.45 415 10.35 435 11.28 453 12.23 471 13.20 488 14.10 505 15.10 521 16.13 537 17.17
24600 354 7.99 376 8.85 397 9.73 417 10.64 436 11.57 455 12.53 473 13.51 490 14.42 507 15.43 523 16.46 538 17.51
25000 357 8.25 378 9.12 399 10.01 419 10.93 438 11.87 457 12.84 474 13.83 491 14.74 508 15.76 524 16.81 540 17.86
25400 359 8.53 381 9.40 401 10.30 421 11.23 440 12.18 458 13.15 476 14.15 493 15.08 510 16.11 526 17.16 541 18.23
25900 362 8.87 383 9.76 404 10.67 423 11.61 442 12.57 460 13.56 478 14.47 495 15.50 511 16.54 527 17.61 543 18.68
26300
26700
365 9.17 386 10.06 406 10.98 425 11.92 444 12.90 462 13.89 480 14.81 497 15.85 513 16.90 529 17.97 544 19.05
367 9.46 388 10.36 408 11.29 427 12.24 446 13.22 464 14.14 481 15.16 498 16.20 514 17.26 530 18.34 546 19.44
III
27100 369 9.76 390 10.67 410 11.61 429 12.57 448 13.56 466 14.48 483 15.51 500 16.56 516 17.63 532 18.71 547 19.82
27500 372 10.07 392 10.98 412 11.93 431 12.91 450 13.90 467 14.83 485 15.87 501 16.92 518 18.00 533 19.10 549 20.22
27900 374 10.38 395 11.31 414 12.26 433 13.25 451 14.16 469 15.18 486 16.23 503 17.30 519 18.38 535 19.49 550 20.62
28300 377 10.70 397 11.64 416 12.61 435 13.60 453 14.52 471 15.55 488 16.60 505 17.68 521 18.78 536 19.89 552 21.02
28700 379 11.03 399 11.98 419 12.95 437 13.95 455 14.88 473 15.92 490 16.99 506 18.06 522 19.17 538 20.30 553 21.32
29100 382 11.37 402 12.33 421 13.30 439 14.22 457 15.25 475 16.30 492 17.37 508 18.46 524 19.58 539 20.71 555 21.74
29500 385 11.71 404 12.68 423 13.67 441 14.59 459 15.62 476 16.69 493 17.76 510 18.87 525 19.99 541 21.12 556 22.17
29900 387 12.07 406 13.04 425 14.04 443 14.97 461 16.01 478 17.08 495 18.17 511 19.27 527 20.40 543 21.44 558 22.60
30300 390 12.42 409 13.41 427 14.33 445 15.35 463 16.40 480 17.48 497 18.58 513 19.70 529 20.83 544 21.87 559 23.05
30700
IV
392 12.79 411 13.78 430 14.70 448 15.74 465 16.80 482 17.88 499 18.99 515 20.12 530 21.27 546 22.31 561 23.49
31000 394 13.07 413 14.07 431 15.00 449 16.04 467 17.11 483 18.19 500 19.31 516 20.44 532 21.48 547 22.65 562 23.83
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 15.0 KW motor to be used for unshaded portion.
3. Alt. 18.5 KW, 22.00 KW & 30.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II, III & IV.
5. * Is not applicable
Model No.: PTX080 (BACKWARD FAN)
External Static Pressure (inch wg.)
Airflow,
2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
23000
23400 I
879 14.85 897 15.62
885 15.21 903 15.99
915 16.40 932 17.19 950 17.99 967 18.79 983 19.61
920 16.78 937 17.57 955 18.38 971 19.19 988 20.01
1000 20.43 1016 21.15 1032 21.99
1004 20.84 1021 21.57 1037 22.41 II
1048 22.83
1052 23.26
23800 890 15.58 908 16.36 925 17.16 943 17.96 960 18.77 976 19.60 993 20.43 1009 21.15 1025 21.99 1041 22.84 1057 23.70
24200 896 15.95 913 16.74 931 17.55 948 18.36 965 19.18 981 20.01 998 20.85 1014 21.58 1030 22.43 1045 23.29 1061 24.15
24600 902 16.33 919 17.13 936 17.94 953 18.76 970 19.59 986 20.43 1002 21.16 1018 22.01 1034 22.87 1050 23.74 1065 24.61
25000 907 16.72 925 17.53 942 18.35 958 19.18 975 20.01 991 20.86 1007 21.60 1023 22.45 1039 23.32 1055 24.19 1070 25.07
25400 913 17.12 930 17.94 947 18.76 964 19.60 980 20.44 996 21.18 1012 22.04 1028 22.90 1044 23.78 1059 24.66 1075 25.55
25900 921 17.63 937 18.45 954 19.29 971 20.13 987 20.99 1003 21.74 1019 22.60 1034 23.48 1050 24.36 1065 25.25 1080 26.15
26300 927 18.04 943 18.88 960 19.72 976 20.57 992 21.32 1008 22.19 1024 23.06 1039 23.94 1055 24.83 1070 25.73 1085 26.64
26700 933 18.46 949 19.31 966 20.16 982 21.02 998 21.77 1014 22.65 1029 23.53 1045 24.42 1060 25.32 1075 26.23 1090 27.14
27100 939 18.90 955 19.75 971 20.61 987 21.36 1003 22.24 1019 23.12 1034 24.01 1050 24.91 1065 25.81 1080 26.73 1095 27.65
27500 945 19.34 961 20.20 977 21.06 993 21.82 1009 22.71 1024 23.59 1040 24.49 1055 25.40 1070 26.31 1085 27.23 1100 28.04
27900 951 19.79 967 20.65 983 21.41 999 22.29 1015 23.18 1030 24.08 1045 24.99 1060 25.90 1075 26.82 1090 27.75 1105 28.57
28300 957 20.24 973 21.12 989 21.89 1005 22.77 1020 23.67 1036 24.58 1051 25.49 1066 26.41 1081 27.34 1095 28.16 1110 29.10
28700 963 20.71 979 21.48 995 22.37 1011 23.26 1026 24.17 1041 25.08 1056 26.00 1071 26.93 1086 27.75 1101 28.69 1115 29.64
29100 970 21.18 986 21.96 1001 22.85 1017 23.76 1032 24.67 1047 25.59 1062 26.52 1077 27.46 1091 28.28 1106 29.23 1120 30.19
29500 976 21.55 992 22.45 1007 23.35 1023 24.26 1038 25.18 1053 26.11 1068 27.05 1082 27.88 1097 28.83 1111 29.78 1125 30.75
29900 983 22.04 998 22.95 1014 23.86 1029 24.78 1044 25.71 1059 26.64 1073 27.59 1088 28.42 1102 29.38 1117 30.34 1131 31.31
30300
30700
989 22.54 1004 23.45
996 23.05 1011 23.97
1020 24.37 1035 25.30 1050 26.24 1064 27.18 1079 28.02
1026 24.90 1041 25.83 1056 26.78 1070 27.61 1085 28.57
1094 28.97 1108 29.94 1122 30.91
1099 29.54 1113 30.51 1128 31.49
III1136 31.89
1141 32.48
31000 1000 23.44 1016 24.36 1031 25.30 1046 26.24 1060 27.19 1075 28.03 1089 28.99 1104 29.96 1118 30.94 1132 31.93 1146 32.92
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 22.0 KW motor to be used for unshaded portion.
3. Alt. 30.0 KW & 37 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.
5. * Is not applicable

62
Page 101 of 286
FAN PERFORMANCE DATA
Model No.: PTX090 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KWRPM KW RPM KW
25000
25500 I
364 8.48 385 9.35 406 10.24 425 11.16 444 12.11 462 13.08 480 14.06 497 15.08 513
367 8.83 388 9.71 408 10.61 428 11.54 447 12.50 465 13.48 482 14.48 499 15.50 515 16.55 531 17.60 547 18.68
16.10 529 17.15 545 18.21
II
26000 370 9.19 391 10.08 411 10.99 430 11.94 449 12.90 467 13.89 484 14.91 501 15.94 517 16.99 533 18.06 548 19.14
26500 373 9.56 394 10.46 414 11.38 433 12.34 451 13.32 469 14.32 486 15.35 503 16.39 519 17.45 535 18.53 550 19.63
27000 376 9.94 397 10.85 416 11.79 435 12.76 454 13.74 471 14.75 488 15.79 505 16.85 521 17.92 537 19.01 552 20.12
27500 379 10.33 400 11.25 419 12.20 438 13.18 456 14.18 474 15.20 491 16.25 507 17.31 523 18.40 539 19.50 554 20.63
28000 383 10.73 403 11.67 422 12.63 440 13.62 458 14.63 476 15.66 493 16.72 509 17.79 525 18.89 541 20.00 556 21.14
28500 386 11.15 406 12.09 425 13.07 443 14.06 461 15.08 478 16.13 495 17.20 512 18.28 527 19.39 543 20.51 558 21.55
29000 389 11.57 408 12.53 427 13.51 446 14.52 464 15.56 481 16.61 497 17.69 514 18.79 529 19.90 545 21.04 560 22.08
29500 392 12.01 412 12.98 430 13.97 448 14.99 466 16.04 483 17.11 500 18.20 516 19.30 532 20.43 547 21.46 562 22.63
30000 396 12.46 415 13.44 433 14.45 451 15.48 468 16.53 486 17.61 502 18.71 518 19.83 534 20.97 549 22.01 564 23.18
30500 399 12.92 418 13.91 436 14.93 454 15.97 471 17.04 488 18.12 504 19.24 520 20.37 536 21.40 551 22.56 566 23.75 III
31000 402 13.40 421 14.40 439 15.43 456 16.48 474 17.56 490 18.65 507 19.77 523 20.92 538 21.96 553 23.13 568 24.33
31500 405 13.88 424 14.90 442 15.94 459 17.00 476 18.09 493 19.20 509 20.33 525 21.37 540 22.53 555 23.72 570 24.92
32000 409 14.39 427 15.41 445 16.46 462 17.53 479 18.63 495 19.75 511 20.90 527 21.94 542 23.12 557 24.32 572 25.52
32500 412 14.90 430 15.93 448 16.99 465 18.08 482 19.19 498 20.32 514 21.35 529 22.53 544 23.71 559 24.92 574 26.14
33000 415 15.42 433 16.47 451 17.54 468 18.64 484 19.76 500 20.90 516 21.95 532 23.12 547 24.32 561 25.53 576 26.77
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 18.5 KW motor to be used for unshaded portion.
3. Alt. 22.0 KW & 30.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

Model No.: PTX090 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I
25000 913 16.98 930 17.80 947 18.62 964 19.45 980 20.29 997 21.13 1013 21.87 1028 22.73 1044 23.60 1060 24.48 1075 25.36
25500
26000
920 17.49
928 18.01
937 18.31
945 18.84
954 19.14
961 19.68
971 19.98
978 20.53
987 20.83 1003
994 21.28 1010
21.58
22.14
1019
1025
22.44
23.01
1035
1041
23.31
23.89
1050
1056
24.19
24.78
1066
1072
25.07
25.68
II
1081
1087
25.96
26.58
26500 935 18.54 952 19.39 968 20.24 985
21.10 1001 21.85 1016 22.72 1032 23.60 1047 24.49 1063 25.39 1078 26.29 1093 27.21
27000 943 19.09 959 19.94 976 20.80 992
21.56 1008 22.43 1023 23.31 1039 24.20 1054 25.10 1069 26.01 1084 26.93 1099 27.85
27500 951 19.65 967 20.51
983 21.27 999
22.14 1015 23.03 1030 23.92 1045 24.82 1061 25.73 1076 26.65 1090 27.57 1105 28.38
28000 959 20.22
975 21.09 991 21.86 1006
22.74 1022 23.64 1037 24.54 1052 25.45 1067 26.37 1082
1111 29.05 27.29 1097 28.11
28500 966 20.81
982 21.57 998 22.46 1014
23.36 1029 24.26 1044 25.17 1059 26.09 1074 27.02 1089
1118 29.73 27.96 1103 28.78
29000 974 21.29 990 22.18 1006 23.08 1021
23.98 1036 24.90 1051 25.82 1066 26.75 1081 27.69 1096
1110 29.46 1124 30.42 28.51
29500 982 21.90 998 22.80 1013 23.71 1029
24.62 1044 25.55 1059 26.48 1073 27.42 1088 28.25
1102 29.20 1117 30.16 1131 31.13 III
30000 990 22.53 1006 23.44 1021 24.35 1036
25.28 1051 26.21 1066 27.16 1081 27.99 1095 28.94
1109 29.90 1124 30.87 1138 31.85
30500 999 23.17 1014 24.09 1029 25.01 1044
25.95 1059 26.89 1073 27.85 1088 28.68
1102 29.65 1116 30.62 1130 31.60 1144 32.59
31000 1007 23.82 1022 24.75 1037 25.69 1052
26.63 1066 27.59 1081 28.43
1095 29.40 1109 30.37 1124 31.35 1137 32.34 1151 33.34
31500 1015 24.49 1030 25.43 1045 26.38 1060
27.33 1074 28.18 1088 29.15 1103 30.12 1117 31.11 1131 32.10 1145 33.10 1158 34.10
32000 1023 25.17 1038 26.12 1053 27.08 27.93 1082 28.90 1096 29.88 1110 30.86 1124 31.86 1138 32.86 1152 33.87 1165 34.88
1067
32500 1032 25.87 1047 26.83 1061 27.80 1075
28.66 1090 29.64 1104 30.62 1118 31.62 1132 32.62 1145 33.64 1159 34.66 1172 35.68
33000 1040 26.59 1055 27.56 1069 28.41 1084 29.40 1098 30.39 1112 31.39 1125 32.39 1139 33.41 1153 34.43 1166 35.46 1180 36.49
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 22.0 KW motor to be used for unshaded portion.
3. Alt. 30.0 KW & 37.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.

63
Page 102 of 286
FAN PERFORMANCE DATA
Model No.: PTX105 (FORWARD FAN)
External Static Pressure (inch wg.)
Airflow,
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
26400
26900 I
373 9.48 393 10.38 413 11.31 432 12.26 451 13.23 469 14.23 486 15.26 503 16.30 519 17.36 535 18.43 550 19.53
376 9.86 396 10.77 416 11.71 435 12.67 453 13.66 471 14.67 488 15.70 505 16.75 521 17.82 537 18.92 552 20.02
II
27400 379 10.25 399 11.17 419 12.12 437 13.10 456 14.09 473 15.11 490 16.16 507 17.22 523 18.30 539 19.41 554 20.52
27900 382 10.65 402 11.58 421 12.55 440 13.53 458 14.54 476 15.57 492 16.62 509 17.70 525 18.79 541 19.91 556 21.04
28400 385 11.06 405 12.01 424 12.98 443 13.97 460 14.99 478 16.04 495 17.10 511 18.19 527 19.29 542 20.41 558 21.44
28900 388 11.49 408 12.44 427 13.42 445 14.43 463 15.46 480 16.51 497 17.59 513 18.69 529 19.80 545 20.94 560 21.98
29400 392 11.92 411 12.89 430 13.88 448 14.90 466 15.94 483 17.01 499 18.09 515 19.20 531 20.33 547 21.36 561 22.52
29900 395 12.37 414 13.35 433 14.35 451 15.38 468 16.43 485 17.51 502 18.60 518 19.72 533 20.86 549 21.90 563 23.07
30400 398 12.83 417 13.82 435 14.83 453 15.87 471 16.94 487 18.02 504 19.13 520 20.26 535 21.29 551 22.46 565 23.64
30900 401 13.30 420 14.30 438 15.33 456 16.38 473 17.45 490 18.55 506 19.67 522 20.80 538 21.85 553 23.02 567 24.21
31400 405 13.78 423 14.80 441 15.83 459 16.89 476 17.98 492 19.08 509 20.22 524 21.25 540 22.41 555 23.60 569 24.80
31900
32400
408 14.28 426 15.30 444 16.35 461 17.43 478 18.52 495 19.64 511 20.78 527 21.82 542 23.00 557 24.19 571 25.40
411 14.79 429 15.82 447 16.88 464 17.97 481 19.08 497 20.20 513 21.36 529 22.41 544 23.59 559 24.80 573 26.02
III
32900 415 15.32 433 16.36 450 17.43 467 18.52 484 19.64 500 20.78 516 21.83 531 23.00 546 24.19 561 25.41 576 26.65
33400 418 15.85 436 16.91 453 17.99 470 19.09 486 20.22 502 21.26 518 22.42 534 23.61 549 24.82 563 26.04 578 27.29
33900 421 16.40 439 17.47 456 18.56 473 19.67 489 20.82 505 21.86 521 23.03 536 24.23 551 25.45 565 26.68 580 27.94
34400 425 16.96 442 18.04 459 19.14 476 20.27 492 21.31 508 22.47 523 23.66 538 24.87 553 26.10 568 27.34 *** ***
34900 428 17.53 445 18.63 462 19.74 478 20.88 495 21.93 510 23.11 526 24.30 541 25.52 555 26.76 570 28.00 *** ***
35400 431 18.12 449 19.24 465 20.36 481 21.39 497 22.56 513 23.75 528 24.95 543 26.18 558 27.43 *** *** *** ***
35600 433 18.37 450 19.48 466 20.61 483 21.64 498 22.82 514 24.01 529 25.22 544 26.46 559 27.71 *** *** *** ***
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module... etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 18.5 KW motor to be used for unshaded portion.
3. Alt. 22.0 KW & 30.0 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II & III.
5. * Not applicable

Model No.: PTX105 (BACKWARD FAN)


External Static Pressure (inch wg.)
Airflow,
2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6
CFM
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW

I
26400 934 18.34 951 19.17 967 20.02 983 20.87 999 21.73 1015 22.60 1031 23.48 1046 24.37 1061 25.27 1077 26.17 1091 27.08
26900 941 18.88 958 19.72 974 20.58 990 21.44 1006 22.31 1022 23.19 1037 24.08 1053 24.98 1068 25.89 1083 26.80 1098 27.72
27400 949 19.43 965 20.29 982 21.15 997 22.02 1013 22.91 1029 23.80 1044 24.70 1059 25.60 1074 26.52 1089 27.44 1104 28.25
27900 957 20.00 973 20.86 989 21.74 1005 22.62 1020 23.51 1036 24.41 1051 25.32 1066 26.24 1081 27.16 1096 27.98 1110 28.91
28400 965 20.58 981 21.45 997 22.34 1012 23.23 1028 24.13 1043 25.04 1058 25.96 1073 26.89 1087 27.82 1102 28.64 1117 29.59
28900 973 21.17 989 22.06 1004 22.95 1020 23.86 1035 24.77 1050 25.69 1065 26.62 1080 27.55 1094 28.38 1109 29.32 1123 30.28
29400
29900
981 21.78
989 22.40
996 22.68
1004 23.31
1012 23.58
1020 24.22
1027 24.49
1035 25.15
1042 25.42 1057 26.35 1072 27.28
1050 26.08 1064 27.02 1079 27.85
1087 28.11
1094 28.80
1101
1108
29.06
29.76
1115
1122
II
30.02
30.73
1130
1136
30.98
31.70
30400 997 23.04 1012 23.95 1027 24.88 1042 25.81 1057 26.76 1072 27.71 1086 28.54 1101
29.51 1115 30.47 1129 31.45 1143 32.44
30900 1005 23.69 1020 24.62 1035 25.55 1050 26.50 1065 27.45 1079 28.29 1094 29.25 1108
30.22 1122 31.20 1136 32.19 1150 33.19
31400 1013 24.35 1028 25.29 1043 26.24 1058 27.19 1073 28.03 1087 29.00 1101 29.98 1115
30.96 1129 31.95 1143 32.94 1157 33.95
31900 1022 25.03 1037 25.98 1051 26.94 1066 27.90 1080 28.75 1095 29.73 1109 30.71 1123
31.71 1137 32.71 1150 33.71 1164 34.73
32400 1030 25.73 1045 26.69 1059 27.66 1074 28.51 1088 29.49 1102 30.47 1116 31.47 1130
32.47 1144 33.48 1157 34.50 1171 35.52
32900 1039 26.44 1053 27.41 1068 28.27 1082 29.25 1096 30.24 1110 31.23 1124 32.24 1138
33.25 1151 34.27 1165 35.30 1178 36.33
33400
33900
1047 27.17
1056 27.91
1062 28.03
1070 28.78
1076
1084
29.01
29.77
1090
1098
30.00
30.77
1104 31.00 1118
1112 31.78 1126
32.01
32.80
1132 33.02
1139 33.82
1145
34.04
1153
34.86
1159
1166
35.07 1172 36.11
35.90 1180 36.75
III1185
1193
36.96
37.80
34400 1064 28.55 1078 29.54 1092 30.55 1106 31.56 1120 32.58 1134 33.61 1147 34.64 1161
35.68 1174 36.73 1187 37.59 1200 38.65
34900 1073 29.32 1087 30.33 1101 31.34 1115 32.36 1128 33.39 1142 34.43 1155 35.47 1168 36.53 1182 37.39 1195 38.45 1208 39.52
35400 1082 30.11 1096 31.12 1109 32.15 1123 33.18 1136 34.22 1150 35.27 1163 36.32 1176 37.19 1189 38.25 1202 39.32 1215 40.40
35600 1085 30.43 1099 31.45 1113 32.48 1126 33.51 1140 34.56 1153 35.61 1166 36.67 1179 37.54 1192 38.60 1205 39.68 1218 40.76
NOTES: 1. Fan performance includes blower speed (RPM) and motor power input (KW) is based on 2" thick disposable filters , unit casing, wet coils and drive losses.
If any accessories used such as bag filters, economizer, heater module ….etc. Add accessories pressure drop to external static pressure before using fan
performance tables.
2. Standard 30.0 KW motor to be used for unshaded portion.
3. Alt. 37.0 KW & 45 KW motor to be used for shaded portion.
4. Bordered region indicate alternative drives I, II, & III.

64
Page 103 of 286
COMPONENT STATIC PRESURE DROP (INCH OF WATER)
2" ALUMINUM FILTER 2" PLEATED FILTER 4" MINI PLEATED FILTER 15" BAG FILTER SUPPLY SUPPLY
AIRFLOW ELECTRIC RETURN DRIP
MODEL No. DAMPER DAMPER
(CFM) HEATER DAMPER ELIMINATOR
INITIAL FINAL INITIAL FINAL INITIAL FINAL INITIAL FINAL (H) (V)

2100 0.11 0.50 0.191 0.7 0.374 1.5 0.267 1.00 0.032 0.129 0.359 0.359 0.005
2275 0.14 0.50 0.188 0.7 0.415 1.5 0.292 1.00 0.035 0.152 0.409 0.409 0.011
PTX006 2450 0.17 0.50 0.188 0.7 0.456 1.5 0.317 1.00 0.037 0.175 0.461 0.461 0.018
2625 0.20 0.50 0.192 0.7 0.498 1.5 0.343 1.00 0.040 0.199 0.515 0.515 0.024
2800 0.23 0.50 0.200 0.7 0.540 1.5 0.368 1.00 0.042 0.223 0.571 0.571 0.031
2400 0.16 0.50 0.188 0.7 0.444 1.5 0.310 1.00 0.036 0.168 0.446 0.446 0.016
2575 0.19 0.50 0.191 0.7 0.486 1.5 0.336 1.00 0.039 0.192 0.500 0.500 0.022
PTX007 2750 0.22 0.50 0.198 0.7 0.528 1.5 0.361 1.00 0.041 0.216 0.555 0.555 0.029
2925 0.25 0.50 0.208 0.7 0.571 1.5 0.387 1.00 0.044 0.241 0.612 0.612 0.036
3100 0.28 0.50 0.222 0.7 0.615 1.5 0.412 1.00 0.046 0.267 0.671 0.671 0.043
3100 0.10 0.50 0.194 0.7 0.353 1.5 0.253 1.00 0.046 0.267 0.671 0.671 0.004
3325 0.12 0.50 0.189 0.7 0.386 1.5 0.274 1.00 0.049 0.301 0.750 0.750 0.009
PTX008 3550 0.15 0.50 0.187 0.7 0.420 1.5 0.295 1.00 0.052 0.336 0.832 0.832 0.015
3775 0.17 0.50 0.188 0.7 0.454 1.5 0.317 1.00 0.055 0.372 0.917 0.917 0.020
4000 0.19 0.50 0.191 0.7 0.489 1.5 0.338 1.00 0.059 0.408 1.006 1.006 0.026
3500 0.14 0.50 0.188 0.7 0.412 1.5 0.291 1.00 0.052 0.328 0.814 0.814 0.013
3750 0.17 0.50 0.188 0.7 0.450 1.5 0.314 1.00 0.055 0.368 0.908 0.908 0.020
PTX010 4000 0.19 0.50 0.191 0.7 0.489 1.5 0.338 1.00 0.059 0.408 1.006 1.006 0.026
4250 0.22 0.50 0.198 0.7 0 .528 1.5 0.361 1.00 0.062 0.451 1.107 1.107 0.032
4500 0.25 0.50 0.207 0.7 0.568 1.5 0.385 1.00 0.065 0.494 1.213 1.213 0.039
4000 0.09 0.50 0.196 0.7 0.340 1.5 0.244 1.00 0.053 0.173 0.838 0.838 0.000
4250 0.11 0.50 0.192 0.7 0.367 1.5 0.262 1.00 0.056 0.194 0.922 0.922 0.003
PTX012 4500 0.13 0.50 0.189 0.7 0.395 1.5 0.280 1.00 0.059 0.216 1.010 1.010 0.007
4750 0.15 0.50 0.187 0.7 0.423 1.5 0.297 1.00 0.062 0.237 1.101 1.101 0.012
5000 0.17 0.50 0.188 0.7 0.452 1.5 0.315 1.00 0.065 0.260 1.194 1.194 0.016
4800 0.15 0.50 0.187 0.7 0.429 1.5 0.301 1.00 0.062 0.242 1.119 1.119 0.012
5200 0.18 0.50 0.190 0.7 0.475 1.5 0.329 1.00 0.067 0.278 1.271 1.271 0.019
PTX016 5600 0.22 0.50 0.196 0.7 0.522 1.5 0.358 1.00 0.072 0.315 1.432 1.432 0.027
6000 0.25 0.50 0.208 0.7 0.570 1.5 0.386 1.00 0.077 0.353 1.600 1.600 0.034
6400 0.29 0.50 0.224 0.7 0.619 1.5 0.414 1.00 0.082 0.392 1.775 1.775 0.042
5600 0.22 0.50 0.196 0.7 0.522 1.5 0.358 1.00 0.072 0.315 1.432 1.432 0.027
6000 0.25 0.50 0.208 0.7 0.570 1.5 0.386 1.00 0.077 0.353 1.600 1.600 0.034
PTX018 6400 0.29 0.50 0.224 0.7 0.619 1.5 0.414 1.00 0.082 0.392 1.775 1.775 0.042
6800 0.32 0.50 0.244 0.7 0.668 1.5 0.443 1.00 0.087 0.433 1.959 1.959 0.049
7200 0.36 0.50 0.269 0.7 0.719 1.5 0.471 1.00 0.092 0.475 2.151 2.151 0.057
6800 0.13 0.50 0.188 0.7 0.397 1.5 0.281 1.00 0.045 0.148 0.651 0.651 0.008
7400 0.16 0.50 0.188 0.7 0.443 1.5 0.309 1.00 0.049 0.174 0.745 0.745 0.015
PTX020 8000 0.19 0.50 0.191 0.7 0.489 1.5 0.338 1.00 0.053 0.202 0.843 0.843 0.022
8600 0.23 0.50 0.199 0.7 0.536 1.5 0.366 1.00 0.056 0.230 0.945 0.945 0.029
9200 0.26 0.50 0.212 0.7 0.584 1.5 0.394 1.00 0.060 0.258 1.052 1.052 0.037
7200 0.15 0.50 0.187 0.7 0.428 1.5 0.300 1.00 0.048 0.165 0.713 0.713 0.012
7800 0.18 0.50 0.189 0.7 0.473 1.5 0.328 1.00 0.051 0.192 0.810 0.810 0.019
PTX022 8400 0.22 0.50 0.196 0.7 0.520 1.5 0.357 1.00 0.055 0.220 0.910 0.910 0.027
9000 0.25 0.50 0.207 0.7 0.568 1.5 0.385 1.00 0.059 0.249 1.016 1.016 0.034
9600 0.28 0.50 0.223 0.7 0.616 1.5 0.413 1.00 0.063 0.278 1.126 1.126 0.042
8000 0.19 0.50 0.191 0.7 0.489 1.5 0.338 1.00 0.053 0.202 0.843 0.843 0.022
8700 0.23 0.50 0.201 0.7 0.544 1.5 0.371 1.00 0.057 0.234 0.963 0.963 0.030
PTX025 9400 0.27 0.50 0.217 0.7 0.600 1.5 0.404 1.00 0.061 0.268 1.088 1.088 0.039
10100 0.31 0.50 0.239 0.7 0.658 1.5 0.437 1.00 0.066 0.303 1.220 1.220 0.048
10800 0.36 0.50 0.268 0.7 0.716 1.5 0.470 1.00 0.070 0.339 1.358 1.358 0.057

NOTES: 1. Add component static pressure drop to duct static pressure drop to determine the total external static pressure.
2. Initial pressure drop of filter is based on clean condition.
3. Final pressure drop of filter is based on dirty condition.
4. Supply damper pressure drop is based on H (horizontal air direction) or V(vertical air direction).

65
Page 104 of 286
COMPONENT STATIC PRESURE DROP (INCH OF WATER)
2" ALUMINUM FILTER 2" PLEATED FILTER 4" MINI PLEATED FILTER 15" BAG FILTER SUPPLY SUPPLY
AIRFLOW ELECTRIC RETURN DRIP
MODEL No. DAMPER DAMPER
(CFM) HEATER DAMPER ELIMINATOR
INITIAL FINAL INITIAL FINAL INITIAL FINAL INITIAL FINAL (H) (V)

9000 0.25 0.50 0.207 0.7 0.568 1.5 0.385 1.00 0.059 0.249 1.016 1.016 0.034
9650 0.29 0.50 0.224 0.7 0.621 1.5 0.416 1.00 0.063 0.280 1.135 1.135 0.042
PTX027/028 10300 0.33 0.50 0.247 0.7 0.674 1.5 0.446 1.00 0.067 0.313 1.259 1.259 0.051
10950 0.37 0.50 0.275 0.7 0.729 1.5 0.477 1.00 0.071 0.347 1.389 1.389 0.060
11600 0.41 0.50 0.308 0.7 0.785 1.5 0.507 1.00 0.075 0.381 1.523 1.523 0.069
9700 0.29 0.50 0.226 0.7 0.625 1.5 0.418 1.00 0.063 0.283 1.144 1.144 0.043
10525 0.34 0.50 0.256 0.7 0.693 1.5 0.457 1.00 0.068 0.325 1.303 1.303 0.054
PTX030/031 11350 0.39 0.50 0.294 0.7 0.763 1.5 0.496 1.00 0.073 0.368 1.471 1.471 0.065
12175 0.44 0.50 0.341 0.7 0.835 1.5 0.535 1.00 0.078 0.412 1.647 1.647 0.077
13000 0.50 0.50 0.397 0.7 0.909 1.5 0.573 1.00 0.084 0.459 1.831 1.831 0.089
10600 0.34 0.50 0.259 0.7 0.699 1.5 0.460 1.00 0.069 0.328 1.318 1.318 0.055
11550 0.40 0.50 0.305 0.7 0.781 1.5 0.505 1.00 0.075 0.378 1.513 1.513 0.068
PTX035/036 12500 0.46 0.50 0.362 0.7 0.864 1.5 0.550 1.00 0.080 0.430 1.719 1.719 0.081
13450 0.53 0.50 0.430 0.7 0.949 1.5 0.595 1.00 0.086 0.484 1.936 1.936 0.095
14400 0.59 0.50 0.510 0.7 1.037 1.5 0.639 1.00 0.092 0.540 2.164 2.164 0.110
12400 0.21 0.50 0.194 0.7 0.510 1.5 0.350 1.00 0.064 0.216 0.420 1.182 0.025
13450 0.25 0.50 0.207 0.7 0.565 1.5 0.383 1.00 0.070 0.249 0.479 1.346 0.034
PTX040 14500 0.29 0.50 0.225 0.7 0.622 1.5 0.416 1.00 0.075 0.283 0.540 1.518 0.042
15550 0.33 0.50 0.249 0.7 0.680 1.5 0.449 1.00 0.080 0.319 0.603 1.699 0.052
16600 0.37 0.50 0.280 0.7 0.739 1.5 0.482 1.00 0.085 0.355 0.669 1.889 0.061
12800 0.22 0.50 0.198 0.7 0.531 1.5 0.363 1.00 0.066 0.228 0.442 1.243 0.028
13925 0.27 0.50 0.214 0.7 0.591 1.5 0.398 1.00 0.072 0.264 0.506 1.423 0.038
PTX045 15050 0.31 0.50 0.237 0.7 0.652 1.5 0.434 1.00 0.077 0.302 0.573 1.612 0.047
16175 0.36 0.50 0.267 0.7 0.715 1.5 0.469 1.00 0.083 0.341 0.642 1.811 0.057
17300 0.40 0.50 0.304 0.7 0.779 1.5 0.504 1.00 0.089 0.380 0.715 2.021 0.068
14000 0.27 0.50 0.215 0.7 0.595 1.5 0.401 1.00 0.072 0.267 0.510 1.435 0.038
15200 0.32 0.50 0.241 0.7 0.660 1.5 0.438 1.00 0.078 0.307 0.582 1.638 0.049
PTX050 16400 0.36 0.50 0.274 0.7 0.728 1.5 0.476 1.00 0.084 0.348 0.657 1.852 0.059
17600 0.41 0.50 0.315 0.7 0.796 1.5 0.514 1.00 0.090 0.391 0.734 2.078 0.070
18800 0.47 0.50 0.364 0.7 0.867 1.5 0.551 1.00 0.096 0.436 0.815 2.315 0.082
16600 0.15 0.50 0.187 0.7 0.427 1.5 0.369 1.00 0.068 0.294 0.669 1.302 0.027
18050 0.18 0.50 0.190 0.7 0.475 1.5 0.405 1.00 0.074 0.339 0.764 1.489 0.036
PTX060 19500 0.22 0.50 0.197 0.7 0.524 1.5 0.441 1.00 0.080 0.385 0.864 1.687 0.046
20950 0.25 0.50 0.209 0.7 0.574 1.5 0.476 1.00 0.085 0.432 0.968 1.895 0.056
22400 0.29 0.50 0.226 0.7 0.625 1.5 0.512 1.00 0.091 0.481 1.076 2.113 0.066
18700 0.20 0.50 0.192 0.7 0.497 1.5 0.421 1.00 0.076 0.359 0.808 1.576 0.041
20350 0.24 0.50 0.203 0.7 0.553 1.5 0.462 1.00 0.083 0.412 0.924 1.807 0.052
PTX070 22000 0.28 0.50 0.221 0.7 0.611 1.5 0.502 1.00 0.089 0.468 1.046 2.052 0.063
23650 0.32 0.50 0.245 0.7 0.670 1.5 0.543 1.00 0.096 0.525 1.173 2.310 0.075
25300 0.37 0.50 0.275 0.7 0.730 1.5 0.583 1.00 0.102 0.585 1.307 2.581 0.087
23000 0.19 0.50 0.191 0.7 0.490 1.5 0.430 1.00 0.060 0.364 0.581 1.052 0.043
25000 0.23 0.50 0.201 0.7 0.544 1.5 0.471 1.00 0.065 0.417 0.663 1.201 0.054
PTX080 27000 0.27 0.50 0.217 0.7 0.600 1.5 0.512 1.00 0.070 0.472 0.749 1.358 0.066
29000 0.31 0.50 0.239 0.7 0.657 1.5 0.553 1.00 0.075 0.529 0.839 1.523 0.078
31000 0.36 0.50 0.267 0.7 0.716 1.5 0.594 1.00 0.080 0.589 0.932 1.696 0.090
25000 0.23 0.50 0.201 0.7 0.544 1.5 0.471 1.00 0.065 0.417 0.663 1.201 0.054
27000 0.27 0.50 0.217 0.7 0.600 1.5 0.512 1.00 0.070 0.472 0.749 1.358 0.066
PTX090 29000 0.31 0.50 0.239 0.7 0.657 1.5 0.553 1.00 0.075 0.529 0.839 1.523 0.078
31000 0.36 0.50 0.267 0.7 0.716 1.5 0.594 1.00 0.080 0.589 0.932 1.696 0.090
33000 0.40 0.50 0.302 0.7 0.775 1.5 0.635 1.00 0.085 0.650 1.029 1.877 0.103
26400 0.26 0.50 0.212 0.7 0.583 1.5 0.500 1.00 0.068 0.455 0.723 1.310 0.062
28700 0.31 0.50 0.236 0.7 0.649 1.5 0.547 1.00 0.074 0.520 0.825 1.498 0.076
PTX105 31000 0.36 0.50 0.267 0.7 0.716 1.5 0.594 1.00 0.080 0.589 0.932 1.696 0.090
33300 0.41 0.50 0.307 0.7 0.784 1.5 0.641 1.00 0.085 0.659 1.044 1.905 0.105
35600 0.46 0.50 0.355 0.7 0.854 1.5 0.688 1.00 0.091 0.733 1.161 2.124 0.120

NOTES: 1. Add component static pressure drop to duct static pressure drop to determine the total external static pressure.
2. Initial pressure drop of filter is based on clean condition.
3. Final pressure drop of filter is based on dirty condition.
4. Supply damper pressure drop is based on H (horizontal air direction) or V(vertical air direction).

66
Page 105 of 286
FILTER DIMENSIONS
2" PRE-FILTER 15" BAG FILTER 4" MINI PLEATED
MODEL
DIMENSION QTY. DIMENSION QTY. DIMENSION QTY.
12x24 1 12x24 1 12x24 1
PTX006 20x24 2 20x24 2 20x24 2
12x24 1 12x24 1 12x24 1
PTX007 20x24 2 20x24 2 20x24 2
PTX008 24x20 4 24x20 4 24x20 4

PTX010 24x20 4 24x20 4 24x20 4


24x20 2 24x20 2 24x20 2
PTX012 20x20 4 20x20 4 20x20 4
24x20 2 24x20 2 24x20 2
PTX016 20x20 4 20x20 4 20x20 4
24x20 2 24x20 2 24x20 2
PTX018 20x20 4 20x20 4 20x20 4
PTX020 20x24 8 20x24 8 20x24 8

PTX022 20x24 8 20x24 8 20x24 8

PTX025 20x24 8 20x24 8 20x24 8

PTX027 20x24 8 20x24 8 20x24 8

PTX028 20x24 8 20x24 8 20x24 8

PTX030 20x24 8 20x24 8 20x24 8

PTX031 20x24 8 20x24 8 20x24 8

PTX035 20x24 8 20x24 8 20x24 8

PTX036 20x24 8 20x24 8 20x24 8

PTX040 20x24 12 20x24 12 20x24 12

PTX045 20x24 12 20x24 12 20x24 12

PTX050 20x24 12 20x24 12 20x24 12


24x20 4 20x20 4 24x20 4
PTX060 24x24 12 20x24 12 24x24 12
24x20 4 20x20 4 24x20 4
PTX070 24x24 12 20x24 12 24x24 12
20x20 6 20x24 4 20x20 6
PTX080 20x24 18 24x24 12 20x24 18
20x20 6 20x24 4 20x20 6
PTX090 20x24 18 24x24 12 20x24 18
PTX105 20x20 6 20x24 4 20x20 6
20x24 18 24x24 12 20x24 18

Filter Efficiency Table


Dust spot Efficiency.
Filter Type Thickness (Inch) Rating
(ASHRAE52.1)
Disposable (Synthetic) Filter 2 Less than 20% G2 /EU2
Aluminum 2 Less than 20% G2/EU2
Pleated Filter 2 20-30% G4/EU4
Bag Filter 15 + 95 % F9/EU9
Mini Pleated 4 + 95 % F9/EU9

67
Page 106 of 286
DIMENSIONS
PTX006 & PTX007 (VERTICAL SUPPLY)

1 Filter access
2 3/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

Supply Air

END VIEW FRONT VIEW END VIEW

PTX006 & PTX007 (HORIZONTAL SUPPLY)

1 Filter access
2 3/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

68
Page 107 of 286
DIMENSIONS
PTX006 & PTX007 (SIDE SUPPLY)

1 Filter access
2 3/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

TOP VIEW

454

END VIEW FRONT VIEW END VIEW

PTX006 & PTX007 (DOWN SUPPLY)

1 Filter access
2 3/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

69
Page 108 of 286
DIMENSIONS
PTX008 & PTX010 (VERTICAL SUPPLY)

1 Filter access
2 3/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


PTX008 & PTX010 (HORIZONTAL SUPPLY)

1 Filter access
2 3/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

70
Page 109 of 286
DIMENSIONS
PTX008 & PTX010 (SIDE SUPPLY)

1 Filter access
2 3/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX008 & PTX010 (DOWN SUPPLY)

1 Filter access
2 3/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

71
Page 110 of 286
DIMENSIONS
PTX012, PTX016 & PTX018 (VERTICAL SUPPLY)

1 Filter access
2 1" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

Supply Air

END VIEW FRONT VIEW END VIEW

PTX012, PTX016 & PTX018 (HORIZONTAL SUPPLY)

1 Filter access
2 1" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

72
Page 111 of 286
DIMENSIONS
PTX012, PTX016 & PTX018 (SIDE SUPPLY)

1 Filter access
2 1" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX012, PTX016 & PTX018 (DOWN SUPPLY)

1 Filter access
2 1" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

Supply Air

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

73
Page 112 of 286
DIMENSIONS
PTX020, PTX022 & PTX025 (VERTICAL SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX020, PTX022 & PTX025 (HORIZONTAL SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

74
Page 113 of 286
DIMENSIONS
PTX020, PTX022 & PTX025 (SIDE SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX020, PTX022 & PTX025 (DOWN SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

75
Page 114 of 286
DIMENSIONS
PTX027 & PTX031 (VERTICAL SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX027 & PTX031 (HORIZONTAL SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

76
Page 115 of 286
DIMENSIONS
PTX027 & PTX031 (SIDE SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX027 & PTX031 (DOWN SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

77
Page 116 of 286
DIMENSIONS
PTX028, PTX030 & PTX035 (VERTICAL SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX028, PTX030 & PTX035 (HORIZONTAL SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

78
Page 117 of 286
DIMENSIONS
PTX028, PTX030 & PTX035 (SIDE SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

Air Discharge Air Discharge TOP VIEW


2281

715

2200

END VIEW FRONT VIEW END VIEW

PTX028, PTX030 & PTX035 (DOWN SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

79
Page 118 of 286
DIMENSIONS
PTX036 (VERTICAL SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX036 (HORIZONTAL SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

80
Page 119 of 286
DIMENSIONS
PTX036 (SIDE SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

Air Discharge Air Discharge TOP VIEW


2281

715

2200

END VIEW FRONT VIEW END VIEW

PTX036 (DOWN SUPPLY)

1 Filter access
2 1-1/4" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

81
Page 120 of 286
DIMENSIONS
PTX040 & PTX045 (VERTICAL SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX040 & PTX045 (HORIZONTAL SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

82
Page 121 of 286
DIMENSIONS
PTX040 & PTX045 (SIDE SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

Supply Air
TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX040 & PTX045 (DOWN SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

83
Page 122 of 286
DIMENSIONS
PTX050 (VERTICAL SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX050 (HORIZONTAL SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

84
Page 123 of 286
DIMENSIONS
PTX050 (SIDE SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX050 (DOWN SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (one side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

85
Page 124 of 286
DIMENSIONS
PTX060 & PTX070 (VERTICAL SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (two side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX060 & PTX070 (HORIZONTAL SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (two side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

86
Page 125 of 286
DIMENSIONS
PTX060 & PTX070 (SIDE SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (two side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

TOP VIEW

Supply Air

END VIEW FRONT VIEW END VIEW

PTX060 & PTX070 (DOWN SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (two side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

87
Page 126 of 286
DIMENSIONS
PTX080, PTX090 & PTX105 (VERTICAL SUPPLY)

4686
1 Filter access
2 1-1/2" FPT drain coupling (two side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Vertical Supply

735
TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX080, PTX090 & PTX105 (HORIZONTAL SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (two side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Horizontal Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

88
Page 127 of 286
DIMENSIONS
PTX080, PTX090 & PTX105 (SIDE SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (two side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Side Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW

PTX080, PTX090 & PTX105 (DOWN SUPPLY)

1 Filter access
2 1-1/2" FPT drain coupling (two side)
3 Electric power inlet
4 Electrical control box (Hinged door)
5 Lifting points
6 Blower and motor access
7 Evaporator coil access
8 Down Supply

TOP VIEW

END VIEW FRONT VIEW END VIEW


NOTE: All dimensions are in mm. Tolerance: ±2 mm.

89
Page 128 of 286
OPTIONAL SECTIONS, BAG FILTER

SA

RA B

MODEL No. ‘L’ ‘A’ ‘B’ SECTION WEIGHT (KG)


PTX006 635 1290 645 75
PTX007 635 1290 645 75
PTX008 635 1290 1053 90
PTX010 635 1290 1053 90
PTX012 635 1590 1053 140
PTX016 635 1590 1053 140
PTX018 635 1590 1053 140
PTX020 635 1984 1053 175
PTX022 635 1984 1206 175
PTX025 635 1984 1206 175
PTX027 635 1984 1206 175
PTX028 635 1984 1206 175
PTX030 635 1984 1206 175
PTX031 635 1984 1206 175
PTX035 635 1984 1206 175
PTX036 635 1984 1206 175
PTX040 635 1984 1866 220
PTX045 635 1984 1866 220
PTX050 635 1984 1866 220
PTX060 635 1984 2300 300
PTX070 635 1984 2300 300
PTX080 635 2390 2300 325
PTX090 635 2390 2300 325
PTX105 635 2390 2300 325

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

90
Page 129 of 286
OPTIONAL SECTIONS, MIXING BOX (STD) FRONT RETURN

SA

FA
B RA B
D

A
C

MODEL No. ‘L’ ‘A’ ‘B’ ‘C’ ‘D’ SECTION WEIGHT (KG)
PTX006 650 305 614 1200 412 85
PTX007 650 305 614 1200 412 85
PTX008 650 305 614 1200 412 100
PTX010 650 305 614 1200 412 100
PTX012 685 305 614 1590 412 160
PTX016 685 305 614 1590 412 160
PTX018 685 305 614 1590 412 160
PTX020 712 305 1220 1740 715 265
PTX022 712 305 1220 1740 715 265
PTX025 712 305 1220 1740 715 265
PTX027 712 305 1220 1740 715 265
PTX028 712 305 1220 1740 715 265
PTX030 712 305 1220 1740 715 265
PTX031 712 305 1220 1740 715 265
PTX035 712 305 1220 1740 715 265
PTX036 712 305 1220 1740 715 265
PTX040 712 305 1826 1740 1018 320
PTX045 712 305 1826 1740 1018 320
PTX050 712 305 1826 1740 1018 320
PTX060 914 660 1220 1740 1119 450
PTX070 914 660 1220 1740 1119 450
PTX080 914 660 1220 2140 1119 510
PTX090 914 660 1220 2140 1119 510
PTX105 914 660 1220 2140 1119 510

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

91
Page 130 of 286
OPTIONAL SECTIONS, BAG FILTER & MIXING BOX (STD)
FRONT RETURN

SA

FA
B RA D
B

A
C

MODEL No. ‘L’ ‘A’ ‘B’ ‘C’ ‘D’ SECTION WEIGHT (KG)
PTX006 1042 305 614 1200 412 115
PTX007 1042 305 614 1200 412 115
PTX008 1042 305 614 1200 412 125
PTX010 1042 305 614 1200 412 125
PTX012 1042 305 614 1590 412 235
PTX016 1042 305 614 1590 412 235
PTX018 1042 305 614 1590 412 235
PTX020 1143 305 1220 1740 715 290
PTX022 1143 305 1220 1740 715 290
PTX025 1143 305 1220 1740 715 290
PTX027 1143 305 1220 1740 715 290
PTX028 1143 305 1220 1740 715 290
PTX030 1143 305 1220 1740 715 290
PTX031 1143 305 1220 1740 715 290
PTX035 1143 305 1220 1740 715 290
PTX036 1143 305 1220 1740 715 290
PTX040 1143 305 1826 1740 1018 340
PTX045 1143 305 1826 1740 1018 340
PTX050 1143 305 1826 1740 1018 340
PTX060 1465 660 1220 1740 1119 535
PTX070 1465 660 1220 1740 1119 535
PTX080 1465 660 1220 2140 1119 640
PTX090 1465 660 1220 2140 1119 640
PTX105 1465 660 1220 2140 1119 640

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

92
Page 131 of 286
OPTIONAL SECTIONS, BAG FILTER & MIXING BOX
TOP RETURN / BOTTOM RETURN

RA
SA
D
A

MODEL No. ‘L’ ‘A’ ‘B’ ‘C’ ‘D’ SECTION WEIGHT (KG)
PTX006 1285 305 614 1200 412 130
PTX007 1285 305 614 1200 412 130
PTX008 1285 305 614 1200 412 145
PTX010 1285 305 614 1200 412 145
PTX012 1300 305 614 1590 412 280
PTX016 1300 305 614 1590 412 280
PTX018 1300 305 614 1590 412 280
PTX020 1588 305 1220 1740 715 410
PTX022 1588 305 1220 1740 715 410
PTX025 1588 305 1220 1740 715 430
PTX027 1790 305 1220 1740 715 430
PTX028 1790 305 1220 1740 715 430
PTX030 1790 305 1220 1740 715 430
PTX031 1790 305 1220 1740 715 430
PTX035 1790 305 1220 1740 715 430
PTX036 1790 305 1220 1740 715 430
PTX040 1790 305 1826 1740 1018 515
PTX045 1790 305 1826 1740 1018 515
PTX050 1790 305 1826 1740 1018 515
PTX060 1955 660 1220 1740 1119 695
PTX070 1955 660 1220 1740 1119 695
PTX080 1955 660 1220 2140 1119 810
PTX090 1955 660 1220 2140 1119 810
PTX105 1955 660 1220 2140 1119 810

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

93
Page 132 of 286
OPTIONAL SECTIONS, MIXING BOX - TOP RETURN / BOTTOM RETURN

RA
SA

D
A

MODEL No. ‘L’ ‘A’ ‘B’ ‘C’ ‘D’ SECTION WEIGHT (KG)
PTX006 840 305 614 1200 412 95
PTX007 840 305 614 1200 412 95
PTX008 840 305 614 1200 412 110
PTX010 840 305 614 1200 412 110
PTX012 890 305 614 1590 412 190
PTX016 890 305 614 1590 412 190
PTX018 890 305 614 1590 412 190
PTX020 1054 305 1220 1740 715 275
PTX022 1054 305 1220 1740 715 275
PTX025 1054 305 1220 1740 715 275
PTX027 1257 305 1220 1740 715 315
PTX028 1257 305 1220 1740 715 315
PTX030 1257 305 1220 1740 715 315
PTX031 1257 305 1220 1740 715 315
PTX035 1257 305 1220 1740 715 315
PTX036 1257 305 1220 1740 715 315
PTX040 1257 305 1826 1740 1018 380
PTX045 1257 305 1826 1740 1018 380
PTX050 1257 305 1826 1740 1018 380
PTX060 1280 660 1220 1740 1119 520
PTX070 1280 660 1220 1740 1119 520
PTX080 1404 660 1220 2140 1119 625
PTX090 1404 660 1220 2140 1119 625
PTX105 1404 660 1220 2140 1119 625

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

94
Page 133 of 286
OPTIONAL SECTIONS, MIXING BOX - SIDE RETURN

SA

RA
FA B

MODEL No. ‘L’ ‘A’ ‘B’ ‘C’ ‘D’ SECTION WEIGHT (KG)
PTX006 840 305 614 548 614 95
PTX007 840 305 614 548 614 95
PTX008 840 305 614 548 614 110
PTX010 840 305 614 548 1018 110
PTX012 890 305 614 548 1018 190
PTX016 890 305 614 548 1018 190
PTX018 890 305 614 548 1018 190
PTX020 1054 305 1220 729 1220 275
PTX022 1054 305 1220 729 1220 275
PTX025 1054 305 1220 729 1220 275
PTX027 1257 305 1220 932 1220 315
PTX028 1257 305 1220 932 1220 315
PTX030 1257 305 1220 932 1220 315
PTX031 1257 305 1220 932 1220 315
PTX035 1257 305 1220 932 1220 315
PTX036 1257 305 1220 932 1220 315
PTX040 1257 305 1826 932 1826 380
PTX045 1257 305 1826 932 1826 380
PTX050 1257 305 1826 932 1826 380
PTX060 1280 660 1220 985 2028 520
PTX070 1280 660 1220 985 2028 520
PTX080 1404 660 1220 1150 2028 625
PTX090 1404 660 1220 1150 2028 625
PTX105 1404 660 1220 1150 2028 625

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

95
Page 134 of 286
OPTIONAL SECTIONS, BAG FILTER & MIXING BOX - SIDE RETURN

SA

RA
FA B

MODEL No. ‘L’ ‘A’ ‘B’ ‘C’ ‘D’ SECTION WEIGHT (KG)
PTX006 1285 305 614 548 614 130
PTX007 1285 305 614 548 614 130
PTX008 1285 305 614 548 614 145
PTX010 1285 305 614 548 1018 145
PTX012 1300 305 614 548 1018 280
PTX016 1300 305 614 548 1018 280
PTX018 1300 305 614 548 1018 280
PTX020 1588 305 1220 729 1220 410
PTX022 1588 305 1220 729 1220 410
PTX025 1588 305 1220 729 1220 430
PTX027 1790 305 1220 932 1220 430
PTX028 1790 305 1220 932 1220 430
PTX030 1790 305 1220 932 1220 430
PTX031 1790 305 1220 932 1220 430
PTX035 1790 305 1220 932 1220 430
PTX036 1790 305 1220 932 1220 430
PTX040 1790 305 1826 932 1826 515
PTX045 1790 305 1826 932 1826 515
PTX050 1790 305 1826 932 1826 515
PTX060 1955 660 1220 985 2028 695
PTX070 1955 660 1220 985 2028 695
PTX080 1955 660 1220 1150 2028 810
PTX090 1955 660 1220 1150 2028 810
PTX105 1955 660 1220 1150 2028 810

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

96
Page 135 of 286
OPTIONAL SECTIONS, 4" MINI PLEATED & MIXING BOX (STD)
FRONT RETURN

SA

FA
B RA D
B

C
A

MODEL No. ‘L’ ‘A’ ‘B’ ‘C’ ‘D’ SECTION WEIGHT (KG)
PTX006 760 305 614 1200 412 90
PTX007 760 305 614 1200 412 90
PTX008 760 305 614 1200 412 105
PTX010 760 305 614 1200 412 105
PTX012 795 305 614 1590 412 170
PTX016 795 305 614 1590 412 170
PTX018 795 305 614 1590 412 170
PTX020 822 305 1220 1740 715 275
PTX022 822 305 1220 1740 715 275
PTX025 822 305 1220 1740 715 275
PTX027 822 305 1220 1740 715 275
PTX028 822 305 1220 1740 715 275
PTX030 822 305 1220 1740 715 275
PTX031 822 305 1220 1740 715 275
PTX035 822 305 1220 1740 715 275
PTX036 822 305 1220 1740 715 275
PTX040 822 305 1826 1740 1018 330
PTX045 822 305 1826 1740 1018 330
PTX050 822 305 1826 1740 1018 330
PTX060 914 660 1220 1740 1119 450
PTX070 914 660 1220 1740 1119 450
PTX080 914 660 1220 2140 1119 510
PTX090 914 660 1220 2140 1119 510
PTX105 914 660 1220 2140 1119 510

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

97
Page 136 of 286
OPTIONAL SECTIONS, 4" MINI PLEATED & MIXING BOX
TOP RETURN / BOTTOM RETURN

RA
SA
D
A

MODEL No. ‘L’ ‘A’ ‘B’ ‘C’ ‘D’ SECTION WEIGHT (KG)
PTX006 950 305 614 1200 412 100
PTX007 950 305 614 1200 412 100
PTX008 950 305 614 1200 412 115
PTX010 950 305 614 1200 412 115
PTX012 1000 305 614 1590 412 200
PTX016 1000 305 614 1590 412 200
PTX018 1000 305 614 1590 412 200
PTX020 1164 305 1220 1740 715 295
PTX022 1164 305 1220 1740 715 295
PTX025 1164 305 1220 1740 715 295
PTX027 1367 305 1220 1740 715 335
PTX028 1367 305 1220 1740 715 335
PTX030 1367 305 1220 1740 715 335
PTX031 1367 305 1220 1740 715 335
PTX035 1367 305 1220 1740 715 335
PTX036 1367 305 1220 1740 715 335
PTX040 1367 305 1826 1740 1018 400
PTX045 1367 305 1826 1740 1018 400
PTX050 1367 305 1826 1740 1018 400
PTX060 1280 660 1220 1740 1119 540
PTX070 1280 660 1220 1740 1119 540
PTX080 1280 660 1220 2140 1119 645
PTX090 1404 660 1220 2140 1119 645
PTX105 1404 660 1220 2140 1119 645

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

98
Page 137 of 286
OPTIONAL SECTIONS, 4" MINI PLEATED & MIXING BOX - SIDE RETURN

SA

RA
FA B

MODEL No. ‘L’ ‘A’ ‘B’ ‘C’ ‘D’ SECTION WEIGHT (KG)
PTX006 950 305 614 548 614 100
PTX007 950 305 614 548 614 100
PTX008 950 305 614 548 614 115
PTX010 950 305 614 548 1018 115
PTX012 1000 305 614 548 1018 200
PTX016 1000 305 614 548 1018 200
PTX018 1000 305 614 548 1018 200
PTX020 1164 305 1220 729 1220 295
PTX022 1164 305 1220 729 1220 295
PTX025 1164 305 1220 729 1220 295
PTX027 1367 305 1220 932 1220 335
PTX028 1367 305 1220 932 1220 335
PTX030 1367 305 1220 932 1220 335
PTX031 1367 305 1220 932 1220 335
PTX035 1367 305 1220 932 1220 335
PTX036 1367 305 1220 932 1220 335
PTX040 1367 305 1826 932 1826 400
PTX045 1367 305 1826 932 1826 400
PTX050 1367 305 1826 932 1826 400
PTX060 1280 660 1220 985 2028 540
PTX070 1280 660 1220 985 2028 540
PTX080 1280 660 1220 1150 2028 645
PTX090 1404 660 1220 1150 2028 645
PTX105 1404 660 1220 1150 2028 645

Note:
1. All dimensions are in mm.
2. Filter access is applicable on both sides

99
Page 138 of 286
RAINHOOD ASSEMBLY FOR FRESH AIR & ECONOMIZER
DAMPER
2" ALU. FILTER
RAIN HOOD

FRESH AIR DAMPER WITH RAINHOOD (2" ALU FILTER)


MODEL DIMENSION QTY MODEL DIMENSION QTY
HOOD ACCESSORIES
1. STEEL BAR PTX006 12" X 24" 1 PTX030 12" X 24" 2
2. LIFTING CABLE OR CHAIN PTX007 12" X 24" 1 PTX031 12" X 24" 2
3. CHAIN SLING
4. BOLT & NUT PTX008 12" X 24" 1 PTX035 12" X 24" 2
5. SPREADER BAR PTX010 12" X 24" 1 PTX036 12" X 24" 2
PTX012 12" X 24" 1 PTX040 12" X 24" 3
PTX016 12" X 24" 1 PTX045 12" X 24" 3
PTX018 12" X 24" 1 PTX050 12” X 24” 3
PTX020 12" X 24" 2 PTX060 24” X 24” 2
PTX022 12" X 24" 2 PTX070 24” X 24” 2
PTX025 12" X 24" 2 PTX080 24” X 24” 2
PTX027 12" X 24" 2 PTX090 24” X 24” 2
PTX028 12" X 24" 2 PTX100 24” X 24” 2

FRESH AIR DAMPER WITH RAINHOOD (2" ALU FILTER)


MODEL DIMENSION QTY MODEL DIMENSION QTY
PTX006 20" X 24" 1 PTX030 24"X24"/12"X24" 2/2
PTX007 20" X 24" 1 PTX031 24"X24"/12"X24" 2/2
PTX008 20" X 20" 2 PTX035 24"X24"/12"X24" 2/2
PTX010 20" X 20" 2 PTX036 24"X24"/12"X24" 2/2
PTX012 20" X 20" 2 PTX040 24"X24"/12"X24" 3/3
PTX016 20" X 20" 2 PTX045 24"X24"/12"X24" 3/3
PTX018 20" X 20" 2 PTX050 24"X24"/12"X24" 3/3
PTX020 16"X24"/12"X24" 2/2 PTX060 24"X24"/12"X24" 4/4
PTX022 16"X24"/12"X24" 2/2 PTX070 24"X24"/12"X24" 4/4
PTX025 16"X24"/12"X24" 2/2 PTX080 24"X24"/12"X24" 4/4
PTX027 24"X24"/12"X24" 2/2 PTX090 24"X24"/12"X24" 4/4
PTX028 24"X24"/12"X24" 2/2 PTX100 24"X24"/12"X24" 4/4

100
Page 139 of 286
ROOF CURB WEIGHT (kg)

SUPPLY
AIR
OPENING

RETURN
AIR
OPENING
SUPPLY
AIR
OPENING

ROOF CURB FOR UNIT WITH FRONT ROOF CURB FOR UNIT WITH DOWN
& SIDE RETURN /DOWN SUPPLY RETURN / DOWN SUPPLY

STD UNIT PRE-


MIXING BOX &
FILTER / BAG FILTER MIXING BOX MIXING BOX & BAG
MODELS 4" MINI PLEATED
4" MINI SECTION SECTION FILTER SECTION
SECTION
PLEATED
PTX006 63 120 129 148 134
PTX007 63 120 129 148 134
PTX008 63 120 129 148 134
PTX010 63 120 129 148 134
PTX012 83 137 148 166 153 UNIT BASE RAIL

PTX016 83 137 148 166 153


UNIT INSERT GUIDE
PTX018 83 137 148 166 153
PTX020 93 148 166 190 171 WOODEN BATTEN
(FIELD SUPPLIED)
PTX022 93 148 166 190 171 GASKET
(SUPPLIED WITH CURB)
PTX025 93 148 166 190 171
COUNTER FLASHING
PTX027 143 196 223 246 228 (FIELD SUPPLIED)
PTX028 143 196 223 246 228
ROOFING FELT
PTX030 143 196 223 246 228 (FIELD SUPPLIED) DUCT
(FIELD SUPPLIED)
PTX031 143 196 223 246 228 CANT STRIP
(FIELD SUPPLIED)
PTX035 143 196 223 246 228 FLEXIBLE CONNECTION
ROOFING MATERIAL
PTX036 143 196 223 246 228 (FIELD SUPPLIED)

PTX040 153 208 235 259 240 RIGID INSULATION


(FIELD SUPPLIED)
PTX045 153 208 235 259 240
PTX050 193 248 275 259 280
PTX060 270 307 335 364 335 ROOF-CURVE ARRANGEMENT DETAIL
PTX070 270 307 335 364 335
PTX080 380 417 451 475 451
PTX090 380 417 451 475 451
PTX100 380 417 451 475 451

101
Page 140 of 286
TYPICAL SCHEMATIC WIRING DIAGRAM
QUADRUPLE COMPRESSOR

HVTB
L1
POWER
REFERSUPPLY
TO UNIT TO FUSED
NAMEPLATE FOR DISCONNECT L2
POWER SUPPLY SWITCH OR CB
380/415V-3PH-60HZ & NEUTRAL L3
(SEE NOTE-4) PLEASE REFER NEXT PAGE
FOR CONDENSER FAN MOTOR
LUG POWER CONNECTIONS.

CB

NTB

L1E
L2E
L3E
NEUTRAL
(SEE NOTE-9)
CC1 CC2 CC3 CC4 BMC

OLR1 OLR2 OLR3 OLR4 OLR

T1C
T2C
T3C

T1D
T2D
T3D
T1A
T2A
T3A

T1B
T2B
T3B

68
69
70
COMP COMP COMP COMP
BM
1 2 3 4
UVM CONNECTION
L1 L2 L3

L1 L2 L3 UVM
1 UVM-1 8

TO ATB 1
(REMOVE JP1)
TO ATB 1A

TO HVTB TO NTB
SMOKE DETECTOR L1 N

ATB ATB
F1
1 JP1 1A JP2 1B
PLEASE REFER TO FAN MOTOR BMC
CONTROL CONNECTION, (SHEET 2 OF 2)
OPTIONAL OPTIONAL BMR
VFC CONNECTION PDS CONNECTION
(SHEET 2 OF 2) (SHEET 2 OF 2)
TO TO TO TO CC2
FR2 FR1 PDS1 PDS2
CC1

( NOTE 7)
SWITCHING CONTACTS
41B

41A

3B

3A
14

4A

4B

FROM T'STAT CONTROLLER OR DDC


( NOTE 6) (by others)
LVTB
OUTFAN2

OUTFAN1

HEATER2

HEATER1

TB1
COMP1
COMP2

15
INFAN

R
LIVE

TO ATB
X2

X1

R R
P1

P2

17 24Vac
C C
OLR-1
G1 19 CBA-1A G2 BM CONTROL G
G G
FUSE 31A Y1
ECB1
STG1 COOLING
NEUTRAL

Y1 Y1
LED 31B STG2 COOLING Y2
LED FAULT INDICATOR Y2 Y2
POWER INDICATOR YR3 Y3
SQMBO4 ( P 4 ) W1 Y3
STG3 COOLING
32C
LOCK2 LOCK1 STG4 COOLING Y4
W2 YR4 Y4
SYSTEM2 SYSTEM1 32D

ON/OFF
PRI

(ON/OFF)

TRANS1 P4_## HP1


230v (HP1)
12v-0-12v
HP2

ON DIP
(HP2)

22A LPS1
LP1
DIP SWITCH
SEC

(LP1) 23A P

22B LPS2
J_PROG LP2
LVTB LOCATION 23B P
(LP2)

PLEASE REFER TO FAN MOTOR


CONTROL CONNECTION, (SHEET 2 OF 2)
TO ATB OPTIONAL OPTIONAL TO ATB
VFC CONNECTION PDS CONNECTION
1 (SHEET 2 OF 2) (SHEET 2 OF 2)
2
TO TO TO TO
TO ATB TO ATB FR4 FR3 PDS3 PDS4 CC4
2
CC3
41D

41C

4D

3D

3C
4C
OUTFAN2

OUTFAN1

HEATER2

HEATER1

TB1 BMR-1
COMP1
COMP2

15B 15C
INFAN
LIVE

X2

X1

P2

R
P1

C
G JP
FUSE 31C
YR3-1

ECB2
NEUTRAL

Y1
LED 31D YR4-1
LED FAULT INDICATOR Y2
POWER INDICATOR
SQMBO4 ( P 4 ) W1
LOCK2 LOCK1
W2
SYSTEM2 SYSTEM1
ON/OFF
PRI

(ON/OFF)
OLR3-1 HPS3
TRANS2 HP1 21C JP7 JP9
P4_## 24C 25C 26C
P
230v (HP1) 27C
OLR4-1 HPS4
12v-0-12v 21D
HP2 24D JP8 25D JP10 26D
P
(HP2) 27D
ON DIP

22C LPS3
LP1
DIP SWITCH
SEC

(LP1) 23C P

22D LPS4
J_PROG LP2
LVTB LOCATION 23D P
(LP2)

Note: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for the exact wiring diagram.

102
Page 141 of 286
TYPICAL SCHEMATIC WIRING DIAGRAM
QUADRUPLE COMPRESSOR

COMP. WITH CB CONNECTION (OPTIONAL) OPTIONAL CONNECTIONS


TO HVTB TO HVTB TO HVTB TO HVTB
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3

PUMP DOWN SOLENOID CONNECTION UNIT STATUS (VFC) INDICATION CONNECTION


PDS2 ATB UNIT ON/OFF
CB1 CB2 CB3 CB4
2 1 AR1 2
PDS1

L1C
L2C
L3C

L1D
L2D
L3D
L1A
L2A
L3A

L1B
L2B
L3B

4B

4A
45 AR1-1A 46
CC1 CC2 CC3 CC4

P2

P1
ECB1 UNIT ON
OLR1 OLR2 OLR3 OLR4 PDS4 ATB
2 UNIT TRIP
T1C
T2C
T3C

T1D
T2D
T3D
T1A
T2A
T3A

T1B
T2B
T3B

PDS3 43 FR1-1A 44A FR2-1A 44B FR3-1A 44C FR4-1A 44

4D

4C
COMP COMP COMP COMP
UNIT TRIP

P2

P1
1 2 3 4 ECB2 INDIVIDUAL COMP. RUN/TRIP
FR1 2
COMP CB AUXILIARY CONTACT CONNECTION HOT GAS BY PASS CONNECTION COMP 1 TO ECB1 41A
X1
ECB ECB LVTB
17 FR1-2A
C
HP1 21A HP3 21C AR8
CB1A-1A 27A CB3A-1A 27C 31A CC1A-2A
(HP1) 8A (HP3) 8C Y1
HPS1 HPS3
AR9
HP2 21B HP4 21D 31B
CB2A-1A 27B CB4A-1A 27D Y2 55 56 58
(HP2) 8B HPS2 (HP4) 8D HPS4
1 LPS NO COMP1 ON
C
7E AR8-1 7F AR9-1 7G
HGS 2
COMP1 TRIP
NC
P
NOTE FR2 2
COMP 2 TO ECB1 41B
FOR UNITS WITH HGS CONNECTION, COMP 1 SHALL BE LEAD COMPRESSOR. X2
DIP SWITCH S2 IN ECB SHOULD ALWAYS BE IN "ON" POSITION.
FR2-2A
COMP. SSPS CONNECTION (AS APPLICABLE) CC2A-2A
COMP. 1: (SEE NOTE 5)
SSPS1
24A 25A
M1/11 M2/14
PRESSURE SWITCH SETTINGS (R410a) 1 2 60 61 63
OIL PRESSURE SWITCH CONNECTION L1/MP/L L2/R/N
(SEMI-HERMETIC COMPRESSORS ONLY) NAME OPEN (PSIG) CLOSE (PSIG)
COMP2 ON
COMP 1 LPS1 & 2 (REMOVE JP3)
AR3 2 COMP. 2: COMP2 TRIP
TO CC1 95 SSPS2
LPS(HGS) 108 24B 25B
3A M1/11 M2/14
OPS1 FR3 2
1 AR3-1A 28A 2 HPS1 & 2 1 2 COMP 3 TO ECB2 41C
2 240 L1/MP/L L2/R/N X1
FCS1 & 2
FR3-2A
25A 26A (REMOVE JP4)
OPS1-1
COMP. 3: SSPS3 CC3A-2A
24C 25C
(REMOVE JP5) M1/11 M2/14
COMP 2 AR4 ECB DIP SWITCH SETTINGS & LED INDICATORS 1
L1/MP/L
2
2 L2/R/N
TO CC2 S1 OFF=TEST MODE DISABLE ON= TEST MODE ENABLE
3B 65 66 68
OPS2 LOAD BALANCE (REMOVE JP7)
S2 OFF= (Comp1&2 Auto Lead Lag) ON= COMPRESSOR 1 LEAD
AR4-1A 28B 2 COMP. 4:
2 240 SSPS4 COMP3 ON
S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION 24D 25D
ON= DUAL COMPRESSOR M1/11 M2/14 COMP3 TRIP
S4 OFF= SINGLE COMPRESSOR
25B 26B FACTORY SETTINGS OF DIP SWITCHES LED INDICATORS 1 2
OPS2-1 L1/MP/L L2/R/N FR4 2
Green power on/off indicator COMP 4 TO ECB2 41D
DIP SWITCH # S1 S2 S3 S4 X2
(REMOVE JP6) Red system lock-out due to system fault (REMOVE JP8)
ON system 1 fault diagnostic FR4-2A
COMP 3 AR5 OFF
2 Yellow blinking slow - LPS1 ckt fault
TO CC3 CC4A-2A
3C notes: blinking fast - HPS1 ckt fault
* Set dip switch #3 according to unit's option
1 OPS3 (pump down or no pump down) system 2 fault diagnostic
AR5-1A 28C 2
2 240 * Ensure dip switch #1 is in OFF position Orange blinking slow - LPS2 ckt fault COMP. CRANKCASE 230V HTR CONNECTION
before operating the unit. blinking fast - HPS2 ckt fault 70 71 73
1B CC1A-1B C.HTR1 2
25C OPS3-1 26C COMP. 1: 100A
COMP4 ON
NON-FUSED DISCONNECT SWITCH CONNECTION C.HTR2
1B CC2A-1B 2
(REMOVE JP9) COMP. 2: 100B COMP4 TRIP
SW
COMP 4 HVTB
AR6 2 L1 L1
1B CC3A-1B C.HTR1 2
COMP. 3: 100C BM RUN/TRIP
TO CC4
3D TO EQUIPMENT L2 L2
OPS4 CKT BREAKER 1B CC4A-1B C.HTR2 2 ATB ATB
AR6-1A 28D 2 L3 L3 COMP. 4: 100D
1 CBA-1B AR2 2
2 240
(SEE NOTE-4)
20

COMP. CRANKCASE 380V HTR CONNECTION TB1(ECB1) OLR-1 AR2-1B LVTB


25D 26D G1 19 G2
OPS4-1 G G
L1 CC1A-1B C.HTR1 L2
COMP. 1: 100A NOTE
(REMOVE JP10) FOLLOW ABOVE CONNECTION FOR UNITS WITH VFC CONNECTION .
L2 CC2A-1B C.HTR2 L3
COMP. 2: 100B 48 BMCA-1A 49
L1 CC3A-1B C.HTR1 L2
100C
ANTI ICE CONNECTION (OPTIONAL) HOT GAS BY PASS CONNECTION COMP. 3:
BM RUN
LVTB L2 C.HTR2 L3
ECB1 17 COMP. 4:
CC4A-1B
100D 51 OLR-2 52
C
22A LPS1 AR8 AR2-2A
LP1 31A
AI-1 23A Y1
29A P
AR9
(LP1) 31B BM TRIP
LPS2 Y2
22B
LP2
29B AI-2 23B P
(LP2) LPS
1 NO
C
7E AR8-1 7F AR9-1 7G
HGS 2
ECB2
NC
22C LPS3 NOTE
P
LP3 FOR UNITS WITH HGS CONNECTION, COMP 1 SHALL BE LEAD COMPRESSOR.
29C AI-3 23C P DIP SWITCH S2 IN ECB SHOULD ALWAYS BE IN "ON" POSITION.
(LP3)
22D LPS4
LP4
29D AI-4 23D P
(LP4)

Note: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for the exact wiring diagram.

103
Page 142 of 286
TYPICAL SCHEMATIC WIRING DIAGRAM
LEGEND
CONDENSER FAN MOTOR POWER & CONTROL CONNECTIONS : WITH FAN CYCLING OPTION (8FANS)
AFS AIR FLOW SWITCH

STANDARD CONNECTION (NO FAN CYCLING SWITCH) AR AUXILIARY RELAY


ECB1 FM1 ECB2 FM2
ATB AUXILIARY TERMINAL BLOCK
T.O.P FMC1 ATB T.O.P FMC2 ATB
12A 12A 13A 12B 12B 13B
OUTFAN 1 2 OUTFAN 1 2 BM BLOWER MOTOR
FM3 FM4
T.O.P FMC3 T.O.P FMC4
12C 13C 12D 13D BMC BLOWER MOTOR CONTRACTOR
FM5 FM6 BMCA BMC AUXILIARY CONTACT
T.O.P FMC5 T.O.P FMC6
12E 12E 13E 12F 12F 13F
OUTFAN 2 OUTFAN 2
FM7 FM8 CB CIRCUIT BREAKER
T.O.P FMC7 T.O.P FMC8
12G 13G 12H 13H
CC COMPRESSOR CONTACTOR
CCA CC AUXILIARY CONTACT
L1 L2 L3 L1 L2 L3 C.HTR CRANKCASE HEATER
L1 L2 L3 L1 L2 L3

COMP/C COMPRESSOR
CB6 CB7 CB8 CB9
ECB ELECTRONIC CONTROL BOARD
F FUSE
FL HEATER FUSE LINK
FCS FAN CYCLING SWITCH
100
101
102

103
104
105

106
107
108

109
110
111
FMC1 FMC3 FMC2 FMC4 FMCA FMC AUXILIARY CONTACT
FMC5 FMC7 FMC6 FMC8
FM FAN MOTOR (CONDENSER)
35C
36C
37C

35D
36D
37D
35A
36A
37A

35B
36B
37B

35G
36G
37G

35H
36H
37H
35E
36E
37E

35F
36F
37F
FMC FAN MOTOR CONTACTOR
FM1 FM3 FM2 FM4 FM5 FM7 FM6 FM8 FR FAULT RELAY
HC HEATER CONTACTOR

8-FAN MOTOR LAYOUT HGS HOT GAS BY-PASS SOLENOID


HPS HIGH PRESSURE SWITCH
CONTROL
PANEL

HVTB HIGH VOLTAGE TERMINAL BLOCK


OPTIONAL CONNECTION (WITH FAN CYCLING SWITCH)
JP JUMPER
TO ECB1 FM1 TO ECB2 FM2 LPS LOW PRESSURE WITCH
OUTFAN 1 T.O.P FMC1 OUTFAN 1 T.O.P FMC2
12A 13A 12B 13B
2 2 LUG LUG GROUND
FM3 FM4
FCS1 T.O.P FMC3 FCS2 T.O.P FMC4 MOHT HEATER OVERHEAT THERMOSTAT (MANUAL RESET)
10A 11A 12C 13C 10B 11B 12D 13D
2 2
P P
OLR OVERLOAD RELAY
TO ECB1 FM5 TO ECB2 FM6
OUTFAN 2 OUTFAN 2
12E
T.O.P FMC5 12F
T.O.P FMC6 OHT HEATER OVERHEAT THERMOSTAT (AUTO RESET)
13E 13F
2 2
P PRESSURE
FM7 FM8
FCS3 T.O.P FMC7 FCS4 T.O.P FMC8
10C 11C 12G 13G 10D 11D 12H 13H PDS PUMP DOWN SOLENOID
2 2
P P
S DIP SWITCH (IN ECB)
SSPS SOLID STATE PROTECTION SYSTEM
T.O.P. FM THERMAL OVERLOAD PROTECTION
HEATER CONNECTIONS DETAILS (OPTIONAL)
TRANS TRANSFORMER
HEATER DATA TABLE
TTL KW
7.5 7.5KW
STAGE1 STAGE2 STAGE3 STAGE4
UVM VOLTAGE MONITOR RELAY
POWER CONNECTION CONTROL CONNECTION 10 10KW
12.5 12.5KW __ __
FIELD WIRING
15 15KW
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
10 5KW 5KW
15 7.5KW 7.5KW SPLICE-CLOSED END
20 5/10KW 5/10KW 5KW 5KW

ECB HC1
22.5
30
7.5KW
7.5/15KW
7.5KW
7.5/15KW
7.5KW
7.5KW 7.5KW
TERMINAL BLOCK OR TERMINATION POINT
29 28 40 10KW/20KW 10KW/20KW 10KW 10KW
CB12 CB14 CB16 CB18 HEATER 1 50
60
12.5KW/25KW
15KW/30KW
12.5KW/25KW
15KW/30KW
12.5KW
15KW
12.5KW
15KW
NOTES
71G
72G
73G
71E
72E
73E

2x10KW+10KW 2x10KW+10KW 10KW+10KW 10KW+10KW


71C
72C
73C

80
HC2 1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
71A
72A
73A

30 100 12.5KW x4/2 12.5KW x4/2 12.5KW x2 12.5KW x2


HEATER 2
HC1 HC3 HC5 HC7 2. ANY WIRE REPLACEMENT, SHOULD BE OF THE 90°C TYPE
HEATER BOX CONNECTION SCHEMES OR ITS EQUIVALENT. USE COPPER CONDUCTORS ONLY.
(380V AND 460V HEATERS)
ATB
1 HC1A-1A 28A HC3 L1 L2 L3 L1 L2 L3 3. POWER MUST BE SUPPLIED TO CRANKCASE HEATER
T1G
T2G
T3G

FOR A MINIMUM OF 12 HOURS, PRIOR TO SYSTEM START


T1H
T2H
T3H
T1F
T2F
T3F

T1I
T2I
T3I

HC5
HEATER1 HEATER3 HEATER5 HEATER7
OHT OHT
UP. IF POWER SUPPLY HAS BEEN INTERRUPTED FOR
HC7 FL FL OHT OHT A PROLONGED PERIOD, OIL SUMP HEATERS MUST BE
(Stage 1 Heaters)
MOHT MOHT
ENERGIZED FOR 12 HRS MINIMUM, BEFORE STARTING
HC2A-1A 28B HC4 COMPRESSOR.
( 5 TO 12.5KW ) ( 15KW )
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
HC6
4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
HEATER BOX CONNECTION SCHEMES
(230V HEATERS)
TO BE PROVIDED BY CONSUMER WITH RATING AS
HC8 OHT FL RECOMMENDED BY ZAMIL
L1
CB13 CB15 CB17 CB19 5. COMPRESSOR 1 & 2 ARE EITHER PROVIDED WITH
AFS SSPS OR INTERNAL LINE BREAK THERMAL OVERLOAD
71H
72H
73H
71D
72D
73D

71F
72F
73F
71B
72B
73B

ATB
2
NC
C PROTECTION.
NO
HC2 HC4 HC6 HC8
L2
OHT FL
6. IN 460-V-3PH-60HZ MODELS, A STEP DOWN CONTROL
L3
( 5 TO 7.5KW )
TRANSFORMER IS PROVIDED FOR THE 230V CONTROL
L1
VOLTAGE.
T1G
T2G
T3G

T1H
T2H
T3H
T1F
T2F
T3F

T1I
T2I
T3I

OHT FL 7. USE SHIELDED TYPE CABLE, #18AWG (min), FOR LVTB


HEATER2 HEATER4 HEATER5 HEATER6 FIELD WIRING. GROUND CONNECT AT BOTH ENDS.
FL OHT
(Stage 2 Heaters) 8. COOLING OUTPUT SIGNAL FROM CONTROLLER SHOULD
NOTE: L2

FOLLOW APPLICABLE POWER AND CONTROL CONNECTION AS PER


OHT FL FOLLOW THE SEQUENCE:
L3
REQUIRED HEATER KW OF UNIT. REFER HEATER TABLE FOR
CORRESPONDING NOS. OF HEATERS AND CONTACTORS.
( 10 TO 15KW ) ON SEQUENCE - Y1 FIRST, THEN Y2
OFF SEQUENCE - Y2 FIRST, THEN Y1
9. NEUTRAL LINE IS REQUIRED ON 380/400V-3PH-60HZ
POWER SUPPLY ONLY.

104
Page 143 of 286
ECONOMIZER BOARD AND CONTROL CONNECTION
(APPLICABLE ON DUAL COMPRESSOR MODELS)
TO ATB
1 2

TRANS2
SWITCHING CONTACTS
FROM T'STAT CONTROLLER OR DDC 230V
(by others)
24V
( NOTE 8) ( NOTE 7)
LVTB F5 ATB
R R 15C
R 17
C C
C
G BM CONTROL G 18A BMR 18B OLR-1
19 CBA-1A
G
Y1 STG1 COOLING Y1 31A YR1
Y1
Y2 STG2 COOLING Y2 31B YR2
Y2
W1 STG1 HEATING W1 HR1
W1
W2 STG2 HEATING W2 HR2
W2
R
C

R
C

R C G Y1 Y2 W1 W2 R C B C1 C2 H1 H2 RETURN AIR
DAMPER ACTUATOR
B1 (S3)
SUPPLY AIR TEMP. SENSOR P3 P3 FEEDBACK
(SAT) 165 ECONOMIZER CONTROL BOARD B2 (S2) POTENTIOMETER
P2 P2
166 ET 858
STS

B3 (S1)
P1 P1
1-
RAD

B3 (black) 1

2+ B4 (red) MOTOR
2
3+ B5 (white)
COM 3
INDOOR AIR
24V
QUALITY SENSOR
AQS

(OPTIONAL) 0~10V DC

(OAT)
ET858
L
167
C
ODS

168
H OUTDOOR AIR
DAMPER ACTUATOR
P3 A1 (S3)
P3 FEEDBACK
(EC) A2 (S2) POTENTIOMETER
TO ECB2 P2 P2
167 A3 (S1)
ENTHALPHY CONTROLLER 2 ODS P1 P1
1
168
OPTIONAL - IN PLACE OF OAT 1-
OAD

3
(USE NO CONTACT) TR TR1 A3 (black) 1
POTENTIOMETERS REF A4 (red)
2+ 2 MOTOR
POT 1 POT 2 POT 3 POT 4
C NO NC
3+ A5 (white)
24V ac 3

RELAY OUTPUT
FOR RELIEF FAN
(OPTIONAL)

ECONOMIZER BOARD SETTINGS


POTENTIOMETER # SETTING FUNCTION
POT 1 (OPTIONAL) AIR QUALITY SENSOR SETTING

POT 2 75% OAD POSITION TO ENERGIZE RELIEF FAN RELAY

POT 3 25% MINIMUM OAD POSITION

POT 4 52 F SUPPLY AIR TEMPERATURE SETTING- TO ACTIVATE ECON CYCLE

INPUT SIGNAL CONNECTION TO ECB (P3) BOARD BLOWER MOTOR RUN & TRIP INDICATION (VFC)

ECB
ATB ATB
1 CBA-1B AR2 2
20

OLR-1 AR2-1B ATB


TB1 BMR 18B 19
(COIL) 17
15A
R NOTE
C FOLLOW ABOVE CONNECTION FOR UNITS WITH VFC CONNECTION .
18A BMR-1A
G
32A YR1-1A 48 BMCA-1A 49
Y1
32B YR2-1A
Y2
34A HR1-1A
W1 BM RUN
34B HR2-1A
W2
51 OLR-2 52

AR2-2A

BM TRIP

105
Page 144 of 286
LIFTING AND RIGGING INSTRUCTION
ATTENTION TO RIGGERS
Hook rigging sling thru the holes on the lifting plates, as shown below.
Lifting plates or holes on the base rail are centered on the unit’s center of gravity.
Center of gravity is not unit center line.
Ensure center of gravity aligns with the main lifting point before lifting.
Use spreader bar when rigging to prevent the slings from damaging the unit.

CAUTION
All panels should be in place when rigging.
Care must be taken to avoid damage to the coils during handling.
Insert packing material between coils & slings as necessary.

1. STEEL BAR LIFT


2. LIFTING CABLE OR CHAIN
3. CHAIN SLING
4. BOLT & NUT PROPER
5. SPREADER BAR 5 CLEARANCE
TO BE
PROVIDED

STEEL BAR MUST BE 2.00" (PTX006-010) & 2.50" (PTX012-105) NOMINAL PIPE
THROUGH UNIT FOR SLINGS TO AVOID BASE DAMAGE.

106
Page 145 of 286
INSTALLATION AND SERVICE CLEARANCE (SINGLE)

B
CLEARANCE
MODEL
A B C
PTX006 - PTX010 1900 1650 1650
PTX012 - PTX018 1900 2200 2200
PTX020 - PTX045 2000 2200 2200
PTX050 - PTX070 2000 2500 2500
PTX080 - PTX105 2000 2500 2500

Note:
1. If unit is installed in special pit, please observe same tolerance for walls. Pit height should not exceed unit height.
2. No obstruction above condenser fan

107
Page 146 of 286
INSTALLATION AND SERVICE CLEARANCE (MULTIPLE)

CLEARANCE
MODEL
A B C D
PTX006 - PTX010 1900 1650 1650 1650
PTX012 - PTX018 1900 2200 2200 2200
PTX020 - PTX045 2000 2200 2200 2200
PTX050 - PTX070 2000 2500 2500 2500
PTX080 - PTX105 2000 2500 2500 2500

Note:
1. If unit is installed in special pit, please observe same tolerance for walls. Pit height should not exceed unit height.
2. No obstruction above condenser fan

108
Page 147 of 286
LOAD DISTRIBUTION (kg) & MOUNTING POINTS (STANDARD UNIT)
MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 TOTAL WT. MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 TOTAL WT.
PTX006 140 110 130 100 480 PTX006 140 110 130 100 480
PTX007 151 120 135 104 510 PTX007 151 120 135 104 510
PTX008 187 155 158 125 625 PTX008 187 155 158 125 625
PTX010 190 158 167 130 645 PTX010 190 158 167 130 645
PTX012 235 190 199 156 780 PTX012 240 194 229 187 850
PTX016 266 220 214 165 865 PTX016 270 224 245 196 935
PTX018 286 239 218 167 910 PTX018 290 243 249 198 980
PTX020 262 233 168 119 133 110 1025 PTX020 263 235 185 137 149 126 1095
PTX022 265 235 179 122 138 111 1050 PTX022 266 236 198 141 156 128 1125
PTX025 282 252 183 126 142 115 1100 PTX025 283 254 200 143 159 131 1170
PTX027 255 207 303 245 174 126 1310 PTX027 256 208 319 261 192 144 1380
PTX028 252 208 318 255 175 127 1335 PTX028 254 209 335 271 192 144 1405
PTX030 256 211 323 258 180 132 1360 PTX030 258 212 339 274 198 149 1430
PTX031 275 219 318 255 181 132 1380 PTX031 277 221 334 271 198 149 1450
PTX035 276 231 344 278 185 136 1450 PTX035 278 232 360 294 202 154 1520
PTX036 280 232 347 279 185 137 1460 PTX036 282 233 363 295 203 154 1530
PTX040 347 286 500 368 231 178 1910 PTX040 350 288 525 394 255 203 2015
PTX045 351 290 505 372 237 185 1940 PTX045 354 292 530 397 262 210 2045
PTX050 240 213 257 255 338 338 222 222 2085 PTX050 240 213 258 255 364 364 248 248 2190
PTX060 358 321 409 406 391 391 282 282 2840 PTX060 358 320 418 414 432 432 323 323 3020
PTX070 364 326 417 413 394 394 291 291 2890 PTX070 363 326 425 422 435 435 332 332 3070
PTX080 309 309 285 285 279 279 431 431 313 313 265 266 3765 PTX080 309 309 285 285 279 279 477 477 360 360 313 312 4045
PTX090 353 353 362 362 324 324 447 447 324 324 273 272 4165 PTX090 353 353 362 362 324 324 494 493 371 371 319 319 4445
PTX105 404 404 418 418 376 376 463 462 324 324 273 273 4515 PTX105 404 404 418 418 376 376 510 510 372 372 320 320 4800

AL / CU CONDENSER COIL AL / CU CONDENSER COIL


CONFIGURATION A / C / D CONFIGURATION B

MODELS L W MODELS L W
PTX006 - PTX010 (A/B/C/D) 140 110 PTX012 - PTX018 (A/B/C/D) 2000 2124

PTX 006 - PTX 010 PTX 012 - PTX 018

MODELS L W MODELS L W
PTX020 - PTX025 (A/B/C/D) 1124 2124 PTX050 (A/B/C/D) 1513 2124
PTX027 - PTX036 (A/B/C/D) 1674 2124 PTX060 - PTX070 (A/B/D) 1958 2124
PTX040 - PTX045 (A/B/C/D) 1814 2124 PTX060 - PTX070 (C) 2492 2124

PTX 020 - PTX 045 PTX 050 - PTX 070

MODELS L W
PTX080 - PTX105 (A/B/D) 1680 2124
PTX080 - PTX105 (C) 2020 2124

PTX 080 - PTX 105

109
Page 148 of 286
Page 149 of 286
ADE IN
M

SAUDI ARABIA
M
A D E I N

Packaged Units
PY (R-410A) High Efficiency Series UP TO

PY036 - PY390 55OC


3 TR thru 33 TR
10 kW thru 116 kW

Page 150 of 286


Company Profile
Zamil Air Conditioners, a sector business of Zamil Industrial, is the largest manufacturer of air conditioners in the Middle East.
The company manufactures and markets the complete range of air conditioners, from room air conditioners to packaged units
to large chillers for residential, commercial and industrial applications.

Founded in 1974, Zamil Air Conditioners was one of the first air conditioning companies to be established in Saudi Arabia. Today,
the company produces about one million air conditioners per year. Aside from its head office and two manufacturing plants in
Dammam, Saudi Arabia, the company also has production facilities in India. The company supplies air conditioning products to
over 55 countries across the world, with its major markets located in the GCC, Middle East, North Africa, Europe and Asia.

Zamil Air Conditioners is the first Middle Eastern company to achieve the prestigious AHRI certification (Air-Conditioning, Heating
and Refrigeration Institute, USA). The company is also 9001:2015 Quality Management System, ISO14001:2015 (Environment
Management) and OHSAS 45001:2018 (Occupational Safety) certified with many of its products tested and approved by
Eurovent, AHRI, SASO, ESMA & UL.

Companies:
• Zamil Air Conditioners & Home Appliances Co. (L.L.C),
• Zamil Central Air Conditioners Co. (L.L.C),
• Zamil Air Conditioning and Refrigeration Services Co. (L.L.C)

Manufacturing Facilities:
The company has two factories in Saudi Arabia located in the 1st and 2nd Industrial Cities of Dammam. The company also has
production facilities in India.

Annual Production Capacity:


• Window Air Conditioners: 700,000
• Mini-Split Systems: 300,000
• Central Air Conditioners: 50,000

Core Values

VISION:
To be the partner-of-choice COMMUNITY &
for environmental control HONESTY &
PROSPERITY
INTEGRITY
solutions that are based We believe in mutual prosperity.
We believe goodwill and good
on lifetime value reputation are core to our business.
We aspire to thrive in business
while bringing progress and
We uphold honesty, integrity, prosperity to our own people and
professionalism and a high level of communities where we operate.
business ethics. We observe prudence Our culture, our ideas, our
and fairness in dealing with our practices, our environmental
MISSION: stakeholders. concern, and our teamwork lead
us to create superior values for
To make air-conditioning people and communities
Affordable, Reliable and around us.

Energy-Efficient
VALUES
LEADERSHIP &
CUSTOMER & PRUDENCE
EXCELLENCE We cultivate talent and leadership
to create sound business
We are diligent about understanding solutions, to best meet our
and fulfilling our customers’ needs. customer needs, and to develop
We strive to please our customers with markets, people and shareholder
excellence in quality and services. We value. We do so by optimizing use
listen to our customers and “go the of funds, resources, materials, and
extra mile” to satisfy them. INNOVATION & technologies. We build prudence
CHANGE and cost-effectiveness in our
leadership culture passing on
We are passionate about
benefits to our customers.
meaningful innovation. We are a
learning organization. We learn
from our experiences and global
best practices, and we innovate to
create leading local solutions
leveraging on world class
knowledge. We embrace positive
change brought forth by innovation
and aspirations to grow our
business.

Page 151 of 286


Research & Development
Zamil Air Conditioners boasts of its state-of-the-art testing facilities – “Ikhtebar” which is a third party air conditioner testing
facility built by Intertek Testing Services (ITS) and certified by Electrical Testing Laboratories (ETL). Equipped to perform a wide
range of tests under many recognized local and international standards including: AHRI 210/240; AHRI 410; AHRI 310/380; AHRI
430; AHRI 440; AHRI 340/360; ASHRAE 116; ASHRAE 37;ASHRAE 41.1; AHRI 365; ISO 5151; SASO 385; SASO 2682; UL 1995
and AHRI 550/590.

Features:
• Performance test of whole range of air conditioners – consumer as well as commercial, in capacities from ½ TR to 600 TR
• Support research and development initiatives through implementation of state of the art computational programs.
• Test products for conformance to local and international certifications and standards such as SASO, AHRI, UL, AHAM etc.

Facility:
• Calorimetric Test Rooms
• Psychrometric Test Rooms
• Chiller Test Facility
• Sound Lab
• Reliability Test Facility

Parent Company
Headquartered in Dammam, Saudi Arabia, Zamil Industrial Investment Company ('Zamil Industrial') is a premier business group
engaged in the design, engineering and manufacturing of innovative products and solutions for the global building and construc-
tion industry.

Zamil Industrial offers a wide range of products and services in four sectors viz. HVAC, Steel, Insulation and Concrete. Zamil
Industrial’s key products and services include: air conditioning systems, pre-engineered steel buildings, steel structures, telecom
and transmission towers, process equipment, precast concrete building products, insulation products, installation and mainte-
nance of HVAC Solutions, and solar power solutions.

The company employs more than 15,500 people and derives about 25% of its revenues from outside Saudi Arabia. Zamil Indus-
trial products are sold in more than 90 countries around the globe, and the company operates manufacturing facilities in Saudi
Arabia, United Arab Emirates, Egypt, India and Vietnam. Zamil Industrial shares are actively traded on the Saudi Stock Exchange
(Tadawul).

Page 152 of 286


INDEX

Contents Page

Model Options and Accessories .................................................................................................................................. 1

Blower Drive Options / Standard Specifications / Options / Accessories ................................................................. 2-5

Physical Data ............................................................................................................................................................. 6-8

AHRI Capacity Rating ................................................................................................................................................... 9

Selection procedure .................................................................................................................................................... 10

Cooling capacities ................................................................................................................................................. 11-17

Electrical data ........................................................................................................................................................ 18-28

Fan performance data ........................................................................................................................................... 29-35

Sound level data .................................................................................................................................................... 36-41

Static pressure drop / Blower motor efficiency ........................................................................................................... 42

Unit dimensions ..................................................................................................................................................... 43-48

Controls and sequence of operation ........................................................................................................................... 49

Typical schematic wiring diagram .......................................................................................................................... 50-51

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

Page 153 of 286


MODEL OPTIONS AND ACCESSORIES

A: STANDARD FEATURES

1. Evaporator coil with Aluminum Fins


2. Condenser coil with Aluminum Fins
3. 1" Aluminum Filter
4. Compressor crankcase heaters
5. Filter drier
6. Compressor internal thermal protection
7. Low pressure switch
8. High pressure switch
9. Under Voltage Monitor (UVM)
10. Anti-Ice
11. Evaporator motor external overload protection
12. Volt free contact (VFC)

B: FACTORY INSTALLED OPTIONS

1. Evaporator coil with Pre-coated Aluminum Fins


2. Condenser coil with Pre-coated Aluminum Fins
3. Unit equipped with Sight Glass
4. External Overload Relay for Condenser motor and Compressors
5. Inner Skin
6. Fresh air opening
7. 2" Aluminum Filter (Applicable for PY075-390 Only).
8. Evaporator coil with Aluminum & Resistec Coating.
9. Condenser coil with Aluminum & Resistec Coating.
10. Unit equipped with Pump Down Solenoid
11. Stainless Steel Drain Pan
12. Differential Pressure Switch, for dirty filter indication.
13. Evaporator coil with Copper Fins
14. Condenser coil with Copper Fins
15. Fan Cycling Switch or low ambient kit (Applicable for PY120-PY390 only)
16. Compressor Rotor-lock Service Valve
17. Pressure Relief Valve.
18. Backward fan option can be provided, for fan performance data please refer to closest sales office.
19. Compressor circuit breaker
20. Suction and discharge pressure gauges

C: Field Installed Accessories:

1. Electric Heater KIT (for kW rating, refer to page # 5)


2. UV Light KIT
3. Metallic Coil Guard
4. Bag filter (not applicable for PY036, PY048 and PY060), for bag filter option layout contact our
nearest sales office.
5. Cooling & Heating thermostat

1
Page 154 of 286
BLOWER DRIVE OPTIONS
MOTOR BLOWER APPROX. SPEED
MODEL PULLEY SPEED RANGE (RPM) PULLEY PITCH CHANGE PER
OPTION PULLEY TURN
NUMBER HP (kW) RPM PITCH DIA.
(INCH) MINIMUM MAXIMUM DIA. (INCH) (RPM)
ALT. I 1.5 (1.1) 1750 3.1 - 4.1 889 1176 6.1 48
PY075
ALT. II 2 (1.5) 1750 3.1 - 4.1 1064 1407 5.1 57
ALT. I 2 (1.5) 1750 3.1 - 4.1 764 1010 7.1 41
ALT. II 2 (1.5) 1750 3.1 - 4.1 1004 1328 5.4 54
ALT. II 3 (2.2) 1750 3.1 - 4.1 1004 1328 5.4 54
PY090
ALT. III 2 (1.5) 1750 3.1 - 4.1 1323 1750 4.1 71
ALT. III 3 (2.2) 1750 3.1 - 4.1 1323 1750 4.1 71
ALT. IV 5 (3.7) 1750 3.7- 4.7 1407 1788 4.6 64
ALT. I 2 (1.5) 1750 3.1 - 4.1 733 970 7.4 39
PY120 ALT. II 3 (2.2) 1750 3.1 - 4.1 889 1176 6.1 48
ALT. III 5 (3.7) 1750 3.7 - 4.7 1156 1469 5.6 52
ALT. I 3 (2.2) 1750 3.1 - 4.1 889 1176 6.1 48
PY150
ALT. II 5 (3.7) 1750 3.7 - 4.7 1061 1348 6.1 48
ALT. I 3 (2.2) 1750 3.1 - 4.1 610 806 8.9 33
PY180 ALT. II 5 (3.7) 1750 3.7 - 4.7 771 979 8.4 35
ALT. III 7.5 (5.6) 1750 4.3 - 5.5 896 1146 8.4 42
ALT. I 5 (3.7) 1750 3.7 - 4.7 689 875 9.4 31
PY210 ALT. II 7.5 (5.6) 1750 4.3 - 5.5 846 1081 8.9 39
ALT. III 10 (7.5) 1750 4.8 - 6.0 933 1167 9.0 39
ALT. I 5 (3.7) 1750 3.7 - 4.7 654 830 9.9 32
ALT. I 7.5 (5.6) 1750 3.7 - 4.7 654 830 9.9 32
ALT. II 5 (3.7) 1750 4.3 - 5.5 800 1023 9.4 39
PY240
ALT. II 7.5 (5.6) 1750 4.3 - 5.5 800 1023 9.4 39
ALT. III 7.5 (5.6) 1750 4.8 - 6.0 976 1220 8.6 39
ALT. III 10 (7.5) 1750 4.8 - 6.0 976 1220 8.6 39
ALT. I 5 (3.7) 1750 3.7 - 4.7 654 830 9.9 32
ALT. I 10 (7.5) 1750 3.7 - 4.7 654 830 9.9 32
ALT. II 5 (3.7) 1750 4.8 - 6.0 764 954 11 32
PY300
ALT. II 10 (7.5) 1750 4.8 - 6.0 764 954 11 32
ALT. III 10 (7.5) 1750 4.8 - 6.0 933 1167 9 39
ALT. III 15 (11) 1750 4.8 - 6.0 933 1167 9 39
ALT. I 7.5 (5.6) 1750 4.3 - 5.5 561 718 13.4 26
ALT. II 7.5 (5.6) 1750 4.3 - 5.5 690 883 10.9 32
ALT. II 10 (7.5) 1750 4.3 - 5.5 690 883 10.9 32
PY360
ALT. III 7.5 (5.6) 1750 4.8 - 6.0 893 1117 9.4 37
ALT. III 10 (7.5) 1750 4.8 - 6.0 893 1117 9.4 37
ALT. IV 15 (11) 1750 4.8 - 6.0 893 1117 9.4 37
ALT. I 7.5 (5.6) 1750 4.3 - 5.5 606 776 12.4 28
ALT. I 10 (7.5) 1750 4.3 - 5.5 606 776 12.4 28
PY390 ALT. II 7.5 (5.6) 1750 4.8 - 6.0 763 954 11.0 51
ALT. II 10 (7.5) 1750 4.8 - 6.0 763 954 11.0 51
ALT. III 15 (11) 1750 4.8 - 6.0 893 1117 9.4 55

STANDARD SPECIFICATIONS
A. General
Packaged cooling or combination heating and cooling units suitable for mounting on the roof or ground. The packaged unit consists of
scroll compressors, cooling coil, condenser coil, control wiring and interconnecting piping - all factory assembled and mounted on
heavy gauge G-90 galvanized steel sheet press formed base, ready for field connection to utilities and ducts. The packaged unit is of
rigid construction with holes provided in the base rails for overhead rigging. The unit is provided with an integral weather resistant
control panel.

These units are rated, tested and manufactured in accordance with:


1. ASHRAE 90.1 4. SASO 2874
2. AHRI 210/240 standard 5. UL1995
3. AHRI 340/360 standard

Note: UL1995 certificate can be provided as an option

B. Unit Enclosure
Panels are of heavy gauge, G-90 galvanized steel sheet with removable access panels, completely weatherized for outdoor installation
and properly reinforced and brazed. Panels and access doors are provided for inspection and access for all internal parts. Enclosures
are provided with adequately reinforced points of support for setting the unit. Steel sheet panels are zinc-coated and galvanized by the
hot dip process of lock forming quality conforming to ASTM A 653 commercial weight G-90, followed by baked on electrostatic polyes-
ter dry powder coat paint, on all external panels.

2
Page 155 of 286
C. Compressor
Compressors are hermetic scroll for all models. They are provided with all the standard controls and accessories necessary for safe
operation. These are equipped with internal motor protector, factory installed crank case heater and rubber vibration isolator for quiet
and efficient operation.

D. Air Cooled Condensing Section


1. The air-cooled condensing section is enclosed within the unit housing and consists of condenser coil, fan(s), electric motor(s) and
inherently protected compressor(s). Inner grooved copper tubes , mechanically bonded to enhanced aluminum fins are standard
for all condenser coils. As an option, Anti-corrosion coils with either enhanced pre-coated, spray-coated or corrugated copper fins
can be provided. tube support sheets are galvanized steel, formed to provide structural strength.
2. Fans are propeller type, direct driven, upward discharge and provided with fan grille mounted on the casing.
3. Motors are totally enclosed air-over type with class ‘F’ insulation & IP55 ratings. Inherent thermal protection is automatic reset
type.

E. Evaporator Coil Section


1. All cooling coils are of enhanced louvered fins and inner grooved copper , mechanically bonded to aluminum fins. As an option,
Anti-corrosion coils with either enhanced pre-coated, spray-coated or corrugated copper fins can be provided. Tube support
sheets are galvanized steel, formed to provide structural strength.
2. Drain Pan: An insulated drain Pan made of G-90 galvanized steel is provided.
3. Insulation: Insulation is supplied in adequate density and thickness for all units to prevent condensation from forming on the unit
casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and erosion from air currents.
F. Evaporator Blower
PY036 - PY060: Evaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure using direct
drive motors, ECM for PY048 and PY060 only. These fans are statically / dynamically balanced.
PY075 - PY390: Evaporator fan is of centrifugal forward-curved blade design capable of handling total required CFM and static
pressure in the low and the medium ranges. Casings are made of galvanized steel. Blower motors are conform to NEMA MG
standards. Fan drive is through adjustable pitch pulleys and belt driven. Blower motor is mounted on adjustable base and secured by
locking device. Fan wheels shafts and bearing are selected to operate at 25% below first critical speed. Pillow block bearings are
used Shaft is turned, ground and polished from solid steel. Fans and pulleys are keyed to shaft and designed for continuous
operation at maximum motor horse power and fan speed. All rotating components and assemblies are statically and dynamically
balanced and every unit is vibration tested before shipment from the factory.
G. Microprocessor Controller
These Packaged units are provided with a microprocessor control board incorporating the following features:
• BALANCE LOADING OF COMPRESSORS: The unit’s electronic control automatically operates lead/lag sequence of compres-
sors. This is to load the compressors evenly over long periods of operation. If required however, compressor-1 can also be set to
always lead. In this case, compressor-1 always starts first and stops last. (Selectable through dip switch setting on control board).

• PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between solenoid’s
opening and compressor starting to equalize the pressure in the system necessary for compressor to startup. (Selectable through
dip switch setting on control board).

• COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for compressor.
This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermostat due to load demand.

• COMPRESSOR LOCK-OUT FUNCTION: If any of the unit’s safety control trips due to abnormal conditions, the electronic
controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a qualified service
technician. The unit can be re-started through thermostat re-set after ensuring safe system conditions.

• FAULT DIAGNOSTICS: In case of system fault, LED’s on the board emits a flashing signal indicating where the fault is.This is to
guide the service technician in identifying the fault.

• DIGITAL I/O’s: The unit’s control board is compatible to operate with a DDC controller or any standard 24V a.c. thermostat
commercially available.

• SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequential order:
supply fan – condenser fan – compressor; at a pre-determined timings.

H. Under Voltage Monitor (UVM)


All package units are provided with under voltage monitor (UVM). UVM Combines voltage monitoring phase loss, reversal and imbal-
ance. When the voltage drops below safe limit, the control relays turn off the equipment. When the device sense such faults, it will
cut-off the supply in the control circuit there by cutting off to the motors. The voltage monitor will re-set automatically when power is
brought back to its normal condition.

3
Page 156 of 286
I. Anti Ice Thermostat
All package units are provided with Anti Ice thermostat. This thermostat is located on the evaporator coil. It detects frost build-up and
turns off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be re-energized.

J. Volt Free Contacts (VFC)


All package units are provided with Volt Free Contacts (VFC) for unit Run/Trip, Evaporator motor Run/Trip and Compressor Run/Trip
indication.

OPTIONS AND ACCESSORIES FIELD INSTALLED ACCESSORIES

A. Electronic Thermostat
General information: Electronic thermostat shall control one or two stage heating and cooling applications. The thermostat normally
displays room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also allows you to select continu-
ous fan operation, or have the fan on intermittent operation with the equipment. The thermostat is best located about 1500 mm (5 Ft.)
above floor level, on a partition wall (not an outside wall), and should not be exposed to direct light from lamps, sun etc. It should be in
return air stream, away from supply air registers/diffusers.

• Single/Dual stage - Cooling & Heating.


• Low voltage control - 24 VAC (nominal).
• Room temperature display - in °C.
• Mode of operation - FAN/COOL/HEAT/AUTO.
• Fan mode - ON: Continuous fan operation; AUTO: Fan operates ON/OFF with compressor.
• Heating & cooling setpoint is permissible.
• Temperature set button - Up for increasing & down for decreasing temperature.
• Remote sensing function as an option.

TYPICAL THERMOSTAT
Heating Cooling Selector Switch Positions
EPN DESCRIPTION
Stages Stages Mode Switch Fan Switch
(SINGLE)
1&2 1 OFF-HEAT/COOL ON - AUTO 7900007604
PY036-090

(DUAL)
1&2 2 OFF-HEAT/COOL ON - AUTO 7900007605
PY120-390

B. Electric Heaters
Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electrical characteristics,
kW capacities and number of stages are as indicated in page #5. Airflow switches, fusible links and overheat limit thermostats are
provided to shut-off power in case of airflow failure/overheat. Electric heater kit is installed as an externally mounted kit at the supply
opening.

C. UV FlowTM Light Emitters:


The damp & dark environment inside the unit could contribute for the growth and development of hazardous bacteria and fungi. The
UV flowTM concept uses emitter of Ultra Violet to simulate the effect of healthy sun radiation. This will inhibit the growth of these micro-
organism reducing in this manner mold related allergies and diseases. Breath safely with UV flowTM.

D. Bag Filter Section


The bag filter section is constructed of single wall heavy gauge galvanized steel with 1" thick (25mm) 3 Ibs/ft3 (48 kg/m3) density
fiberglass insulation. Pre filter media is an aluminum filter, while the bag filter media is synthetic micro-fiber with high efficiency air
cleaning capability. As an option Differential Pressure Switch (DPS) can be ordered with each filter section to help promote regular
servicing and prevent clogging.

E. Metallic Coil Guard


The guard is mounted on the condensing section only, which protects the condenser coil from physical damage.

4
Page 157 of 286
FIELD INSTALLED ACCESSORIES

UV Ligh, Bag filter & Metallic Coil Guard EPN


UV Light Kit Bag Filter Kit Metallic Coil Guard Kit
MODEL
EPN Description EPN Description EPN Description
PY036-PY060 7900007610 UV LIGHT *** *** 7900007670 METALIC COIL GUARD
KIT-PY036-060 KIT-PY036-060
PY075 7900007613 UV LIGHT 7900007633 BAG FILTER 7900007673 METALIC COIL GUARD
KIT-PY075 KIT-PY075 KIT-PY075
PY090 7900007612 UV LIGHT 7900007632 BAG FILTER 7900007672 METALIC COIL GUARD
KIT-PY090 KIT-PY090 KIT-PY090
PY120 7900007615 UV LIGHT 7900007635 BAG FILTER 7900007675 METALIC COIL GUARD
KIT-PY120 KIT-PY120 KIT-PY120
PY150 7900007616 UV LIGHT 7900007636 BAG FILTER 7900007676 METALIC COIL GUARD
KIT-PY150 KIT-PY150 KIT-PY150
PY18 0-PY300 7900007617 UV LIGHT 7900007637 BAG FILTER 7900007677 METALIC COIL GUARD
KIT-PY180-300 KIT-PY180-300 KIT-PY180-300
PY360-PY390 7900007622 UV LIGHT 7900007642 BAG FILTER 7900007682 METALIC COIL GUARD
KIT-PY360-390 KIT-PY360-390 KIT-PY360-390

Electric Heater EPN


Voltage Heater Capacity C: 230V/1Ph/60Hz H: 230V/3Ph/60Hz M:380V/400V-3Ph-60Hz
Model kW / No. of Stages EPN EPN EPN
PY036 5 / 1 Stage 7900007500 *** ***
5 / 1 Stage 7900007500 7900007504 7900007539
PY048 -PY060
7.5 / 1 Stage *** 7900007505 7900007540
10 / 2 Stage 7900007501 7900007506 7900007541

Voltage Heater Capacity H: 230V/3Ph/60Hz M: 380V/400V-3Ph-60Hz F: 460V/3Ph/60Hz


Model kW / No. of Stages EPN EPN EPN
5 / 1 Stage 7900007507 7900007542 7900007574
7.5 / 1 Stage 7900007508 7900007543 7900007575
PY075
10 / 2 Stage 7900007509 7900007544 7900007576
15 / 2 Stage 7900007510 7900007545 7900007577
7.5 / 1 Stage 7900007511 7900007546 7900007578
10 / 2 Stage 7900007512 7900007547 7900007579
15 / 2 Stage 7900007513 7900007548 7900007580
PY090-PY120
20 / 2 Stage 7900007514 7900007549 7900007581
7.5 / 1 Stage 7900007519 7900007554 7900007586
10 / 2 Stage 7900007520 7900007555 7900007587
PY150
15 / 2 Stage 7900007521 7900007556 7900007588
20 / 2 Stage 7900007522 7900007557 7900007589
20 / 2 Stage 7900007523 7900007558 7900007590
PY18 0-PY210
30 / 2 Stage 7900007524 7900007559 7900007591
20 / 2 Stage 7900007523 7900007558 7900007590
PY240-300 30 / 2 Stage 7900007524 7900007559 7900007591
40 / 2 Stage 7900007525 7900007560 7900007592
20 / 2 Stage 7900007536 7900007571 7900007597
PY360-PY390 30 / 2 Stage 7900007537 7900007572 7900007598
40 / 2 Stage 7900007538 7900007573 7900007599

5
Page 158 of 286
PHYSICAL DATA
(DIRECT DRIVE MOTOR)

MODEL NUMBER PY036 PY048 PY060

NOMINAL CAPACITY, TONS (kW)* 3 (10.5) 4 (14.1) 5 (17.6)


COOLING CAPACITY (Btuh) 35200 53800 58000

POWER INPUT (kW) 3 4.1 4.6


GROSS EER 11.7 13.1 12.6
Quantity 1 1 1
COMPRESSOR Oil (oz) 25 42 42
Refrigerant R-410A
Type/Drive Propeller/Direct

CONDENSER FAN Qty. - Diameter (inch) 1-24 1-24 1-24


Nominal CFM (L/S) 4000 (1888) 4000 (1888) 4000 (1888)
Motor HP - RPM 1/3-1075 1/3-1075 1/3-1075
Type Inner Grooved Copper Tubes and Enhanced AL Fins
CONDENSER COIL
Total face area, Sq. ft. (Sq. m.) 13.1 (1.2) 13.1 (1.2) 13.1 (1.2)
Type Centrifugal
Size (inch) 10 x 8 10 x 8 10 x 8
EVAPORATOR
BLOWER Drive type Direct Drive
Nominal CFM (L/S) 1000 (566) 1600 (755) 1600 (755)

Motor HP - (Standard) 1/2 3/4 3/4


EVAPORATOR Type Inner Grooved Copper Tubes and Enhanced AL Fins
COIL
Total face area, Sq. ft. (Sq. m.) 6.2 (0.6) 6.6 (0.61) 6.6 (0.61)
HIGH PRESSURE Open 650 ± 10 PSIG
SWITCH
Close 500 ± 22 PSIG

LOW PRESSURE Open 50 ± 7 PSIG


SWITCH Close 90 ± 7 PSIG

RETURN AIR Quantity 2 2 2


FILTERS Size (inch) 16 x 29 16 x 29 16 x 29
SHIPPING WEIGHT kg 232 238 240

*Cooling capacity @ 80°F DB/67°F WB indoor and 95°F DB ambient temperature.


AHRI standard condition as per AHRI 210/240 standard.
NOTE: Direct drive motors have single speed connection only. Factory set at medium speed.

6
Page 159 of 286
PHYSICAL DATA

MODEL NUMBER PY075 PY090 PY120 PY150 PY180

NOMINAL CAPACITY, TONS (kW)* 6(21.1) 8(28.3) 10(35.2) 12.5(44) 15(52.8)


COOLING CAPACITY (Btuh) 73600 96500 116500 146100 167000
POWER INPUT (kW) 6.3 8 10 12.7 14.5
GROSS EER 11.7 12.0 11.7 11.5 11.5
Quantity 1 1 2 2 2
COMPRESSOR Oil (oz) 60 60 43 x 2 60 x 2 60 x 2
Refrigerant R-410A
Type/Drive Propeller/Direct

CONDENSER FAN Qty. - Diameter (inch) 1 - 26 1 - 28 2 - 24 2 - 26 2 - 30


Nominal CFM (L/S) 6200(2926) 8700(4106) 6800(3210) 12000(5663) 15960(7532)
Motor HP - RPM 3/4 - 1140 2 - 1140 1/3 - 1075 3/4 - 1140 1.5 - 1140
Type/Drive Inner Grooved Copper Tubes and Enhanced AL Fins
CONDENSER COIL
Total face area, Sq. ft. (Sq. m.) 16.3 (1.5) 28 (2.1) 22.4 (2.1) 28.4 (2.6) 37.1 (3.4)
Type Centrifugal
Size (mm) 315 315 355 355 450
EVAPORATOR Drive type Belt Driven
BLOWER
Nominal CFM (L/S) 2200(1038) 2800(1322) 3600(1699) 4200(1982) 5000(2360)
Motor HP - Std. / Alt 1.5/2 2/3/5 2/3/5 3/5 3/5/7.5
Factory setting full turns open 3 3 3 3 3

EVAPORATOR Type Inner Grooved Copper Tubes and Enhanced AL Fins


COIL
Total face area, Sq. ft. (Sq. m.) 9 (0.84) 9.5 (0.88) 14.5 (1.35) 19.6 (1.82) 22 (2.04)

HIGH PRESSURE Open 650 ± 10 PSIG


SWITCH Close 500 ± 22 PSIG

LOW PRESSURE Open 50 ± 7 PSIG


SWITCH Close 90 ± 7 PSIG

RETURN AIR Quantity 4 4 4 6 8


FILTERS Size (inch) 16-1/2 x 18-3/8 18 x 24 24 x 21 18 x 18 (1), 18 x 24 (3), 12 x 24 (2),
24 x 24 (2) 24 x 24 (6)

SHIPPING WEIGHT kg 352 453 490 837 967

*Cooling capacity @ 80°F DB/67°F WB indoor and 95°F DB ambient temperature.


AHRI standard condition as per AHRI 340/360 standard.

7
Page 160 of 286
PHYSICAL DATA

MODEL NUMBER PY210 PY240 PY300 PY360 PY390

CAPACITY, TONS (kW)* 17.5(61.5) 20(70.3) 25(88) 29.4(103.5) 33.1(116.3)


COOLING CAPACITY (Btuh) 203700 229600 291750 348500 396700

POWER INPUT (kW) 17.8 19.1 25.8 31.8 36.7


GROSS EER 11.4 12.0 11.3 11 10.8
Quantity 2 2 2 2 2
COMPRESSOR Oil (oz) 60 x 2 60 + 110 110 x 2 114 x 2 114 x 2
Refrigerant R-410A
Type/Drive Propeller/Direct

CONDENSER FAN Qty. - Diameter (inch) 2 - 30 2 - 30 2 - 30 2 - 32 2 - 32


Nominal CFM (L/S) 15960(7532) 18800(8873) 18800(8873) 24720(11666) 24720(11666)
Motor HP - RPM 1.5 - 1140 1.5 - 1140 1.5 - 1140 2.7 - 1100 2.7 - 1100
Type/Drive Inner Grooved Copper Tubes and Enhanced AL Fins
CONDENSER COIL
Total face area, Sq. ft. (Sq. m.) 37.1 (3.4) 37.1 (3.4) 37.1 (3.4) 48.2 (4.5) 54.9 (5.1)
Type Centrifugal
Size (mm) 450 450 450 500 500
EVAPORATOR Drive type Belt Driven
BLOWER
Nominal CFM (L/S) 6500(3067) 6500(3067) 8100(3823) 9900(4672) 10400(4908)

Motor HP - Std. / Alt 5/7.5/10 5/7.5/10 5/10/15 7.5/10/15 7.5/10/15


Factory setting full turns open 3 3 3 3 3

EVAPORATOR Type Inner Grooved Copper Tubes and Enhanced AL Fins


COIL
Total face area, Sq. ft. (Sq. m.) 27.3 (2.53) 27.3 (2.53) 27.3 (2.53) 27 (2.51) 27 (2.51)

HIGH PRESSURE Open 650 ± 10 PSIG


SWITCH Close 500 ± 22 PSIG

LOW PRESSURE Open 50 ± 7 PSIG


SWITCH Close 90 ± 7 PSIG

RETURN AIR Quantity 8 8


FILTERS Size (inch) 12 x 24 (2), 24 x 24 (6) 24 x 24 (6), 20 x 24 (2)
SHIPPING WEIGHT kg 970 978 984 1362 1365

*Cooling capacity @ 80°F DB/67°F WB indoor and 95°F DB ambient temperature.


AHRI standard condition as per AHRI 340/360 standard.

8
Page 161 of 286
AHRI CAPACITY RATING

Standard Airflow rate Net Cooling Capacity


Model EER
(CFM) (BTU/Hr)

PY036 1200 34000 11.50


PY048 1600 52000 12.4
PY060 1600 57000 12.05
PY075 2200 72000 11.35
PY090 2800 93000 11.6
PY120 3600 113000 11.30
PY150 4200 142000 11.15
PY180 5000 164000 11.20
PY210 6500 198000 11.05
PY240 6500 222000 11.65
PY300 8100 280000 10.90
PY360 9900 334000 10.70
PY390 10400 380000 10.50

9
Page 162 of 286
SELECTION PROCEDURE

1. Determine cooling and heating capacity requirements at design conditions


Data:
Condenser entering air temperature : 950F
Evaporator entering air temperature : 800F DB / 670F WB
Evaporator airflow : 6000 CFM
Required cooling capacity : 158,000 BTUH
Sensible heat capacity : 118,000 BTUH
Required heating capacity : 20 kW - 2 modules
External static pressure : 1.26 INCH WG.
Power supply (V-Ph-Hz) : 380/400-3-60
Altitude : 0 (Sea level)

2. Unit selection based on required cooling capacity


Enter cooling capacity performance data at condenser entering air temp. at 950F and evaporator entering air temp. 800F DB, 670F
WB, 6000 CFM airflow. The PY180 unit will give 172,170 BTUH cooling capacity (gross) and 134,000 BTUH sensible heat capacity
(gross).

3. Electric heater selection


Heating capacity required =20 kW.
Enter electric heating table for PY180 at 380/400-3-60 power supply.
20 kW heater at 380/400 volts satisfies the required heating.

4. Determine fan speed and power requirements at design conditions


Before entering the fan performance tables, calculate the summation of external static pressure for the required components as
follows.
External static pressure (duct) : 1.26 INCH WG.
Electric heater : 0.14 INCH WG.

External static pressure 1.4 INCH WG.

Enter the fan performance table for PY180 model. For 6000 CFM and external static pressure of 1.4 INCH WG, it requires 866 RPM
and 3.7 brake horse power (BHP) wherein the standard motor will meet job requirements.

5. Determine input power to motor


Use fan motor efficiency table.

BHP x 746 watts 3.7 x 746


Blower motor watts = = = 3408 watts.
Motor efficiency 0.81
866 RPM and 3.7 brake horse power (BHP) wherein the standard motor will meet job requirements.

6. Determine net capacities


Above capacities are gross and do not include blower motor heat gain.
Determine net capacities as follows:
Net cooling capacity = Gross cooling capacity – blower motor heat
= 172,170 – (3408 WATTS x 3.413 BTUH/WATTS) = 160,539 BTUH
Net sensible capacity = 134,000 – (3408 WATTS x 3.413 BTUH/WATTS) = 122,369 BTUH
7. Altitude correction factors for cooling capacity

ALTITUDE, FT. 2000 4000 6000 8000 10000

Correction Total capacity 0.98 0.96 0.93 0.90 0.88


Factor
Sensible capacity 0.93 0.86 0.80 0.75 0.70

10
Page 163 of 286
COOLING CAPACITIES

Model No.: PY036


EVAPORATOR AIRFLOW, CFM
CONDENSER
750 875 1000
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 31.66 34.69 37.78 32.79 35.86 38.99 33.67 36.79 39.88
85 SC 27.47 23.34 19.18 29.87 25.02 20.18 32.13 26.55 21.00
kW 2.06 2.08 2.10 2.07 2.09 2.11 2.08 2.09 2.12
TC 30.33 33.22 36.21 31.36 34.33 37.28 32.18 35.18 38.12
95 SC 26.81 22.67 18.51 29.18 24.31 19.45 31.39 25.80 20.25
kW 2.34 2.36 2.38 2.35 2.37 2.38 2.35 2.37 2.39
TC 28.95 31.72 34.48 29.91 32.74 35.45 30.65 33.53 36.21
105 SC 26.13 21.97 17.77 28.46 23.58 18.65 30.65 25.06 19.42
kW 2.65 2.66 2.69 2.65 2.67 2.70 2.66 2.68 2.70
TC 27.44 30.05 32.70 28.28 30.98 33.62 29.24 31.70 34.29
115 SC 25.39 21.20 17.01 27.67 22.76 17.88 29.24 24.20 18.58
kW 3.00 3.02 3.04 3.01 3.02 3.04 3.01 3.03 3.05
TC 25.81 28.33 30.81 26.67 29.18 31.60 27.73 29.79 32.18
125 SC 24.61 20.41 16.20 26.67 21.94 16.99 27.73 23.31 17.64
kW 3.41 3.42 3.43 3.41 3.42 3.44 3.42 3.43 3.44

Model No.: PY048


EVAPORATOR AIRFLOW, CFM
CONDENSER
1400 1600 1800
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 49.25 53.86 58.48 50.52 55.21 59.89 51.53 56.36 60.85
85 SC 45.89 38.26 30.75 49.09 40.41 31.96 51.53 42.40 32.94
kW 2.94 2.97 3.00 2.95 2.98 3.00 2.95 2.98 3.01
TC 46.65 51.05 55.44 47.82 52.33 56.63 48.95 53.35 57.53
95 SC 44.81 37.14 29.65 47.82 39.25 30.76 48.95 41.20 31.71
kW 3.38 3.38 3.41 3.36 3.39 3.42 3.37 3.40 3.43
TC 43.97 48.23 52.30 45.07 49.33 53.28 46.47 50.26 54.09
105 SC 43.24 35.67 28.21 45.07 37.66 29.19 46.47 39.53 30.09
kW 3.81 3.83 3.86 3.81 3.84 3.88 3.82 3.85 3.89
TC 41.18 45.17 48.97 42.50 46.19 49.91 43.81 47.08 50.63
115 SC 41.18 34.05 26.64 42.50 36.00 27.62 43.81 37.80 28.42
kW 4.32 4.35 4.38 4.34 4.36 4.39 4.35 4.37 4.39
TC 38.45 42.08 45.53 39.89 42.99 46.39 41.13 43.66 46.96
125 SC 38.45 32.42 25.04 39.89 34.29 25.94 41.13 35.95 26.64
kW 4.90 4.93 4.96 4.91 4.94 4.96 4.92 4.94 4.97

TC – Total Capacity (1000 Btuh) Gross WBE – Wet Bulb Temp. (0F) of Air Entering Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross kW – Compressor power input
DBE – Dry Bulb Temp. (0F) of Air Entering Coil

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.


2. Capacities above are based on DBE = 800F.
For different conditions and full selection, contact your nearest Zamil sales office.

11
Page 164 of 286
COOLING CAPACITIES

Model No.: PY060


EVAPORATOR AIRFLOW, CFM
CONDENSER
1500 1700 1900
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 55.27 60.22 65.18 56.56 61.59 66.59 57.66 62.75 67.64
85 SC 50.27 42.05 34.00 53.41 44.18 35.22 56.40 46.18 36.23
kW 3.47 3.50 3.52 3.48 3.50 3.52 3.48 3.51 3.54
TC 52.67 57.37 62.07 53.83 58.66 63.30 54.83 59.69 64.33
95 SC 49.22 40.97 32.91 52.28 43.08 34.03 54.83 45.00 35.05
kW 3.96 3.96 3.98 3.95 3.97 3.99 3.95 3.98 3.99
TC 49.88 54.34 58.73 50.94 55.44 59.88 51.89 56.42 60.80
105 SC 47.56 39.38 31.38 50.56 41.36 32.46 51.89 43.24 33.41
kW 4.45 4.48 4.50 4.45 4.49 4.51 4.46 4.49 4.51
TC 46.72 51.04 55.17 47.72 52.12 56.25 49.03 52.94 57.12
115 SC 45.70 37.66 29.73 47.72 39.61 30.75 49.03 41.38 31.64
kW 5.01 5.04 5.06 5.02 5.05 5.06 5.03 5.05 5.07
TC 43.29 47.27 51.25 44.50 48.27 52.20 45.76 49.02 52.89
125 SC 43.29 35.69 27.92 44.50 37.60 28.86 45.76 39.28 29.66
kW 5.62 5.66 5.68 5.63 5.66 5.68 5.64 5.67 5.69

Model No.: PY075


EVAPORATOR AIRFLOW, CFM
CONDENSER
1600 2200 2400
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 65.86 72.17 78.64 70.39 76.96 83.56 71.45 78.08 84.67
85 SC 57.11 48.49 39.90 67.58 55.81 44.16 70.75 57.94 45.32
kW 4.43 4.44 4.45 4.44 4.44 4.45 4.44 4.45 4.45
TC 62.98 69.10 75.40 67.21 73.59 79.83 68.56 74.63 80.93
95 SC 55.67 47.08 38.52 66.04 54.27 42.60 68.56 56.33 43.75
kW 4.92 4.92 4.92 4.92 4.92 4.93 4.92 4.92 4.93
TC 59.92 65.84 71.81 64.00 69.94 75.91 65.61 70.94 76.86
105 SC 54.17 45.59 36.99 64.00 52.57 40.90 65.61 54.63 41.98
kW 5.44 5.45 5.45 5.45 5.45 5.45 5.45 5.45 5.45
TC 56.66 62.23 67.85 60.90 65.95 71.62 62.42 66.82 72.48
115 SC 52.57 43.93 35.31 60.90 50.71 39.08 62.42 52.74 40.06
kW 6.04 6.05 6.05 6.05 6.05 6.05 6.05 6.05 6.05
TC 53.00 58.41 63.74 57.59 61.70 67.02 58.95 62.52 67.69
125 SC 50.80 42.19 33.58 57.59 48.76 37.07 58.95 50.73 37.94
kW 6.70 6.70 6.71 6.70 6.71 6.71 6.71 6.71 6.71

TC – Total Capacity (1000 Btuh) Gross WBE – Wet Bulb Temp. (0F) of Air Entering Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross kW – Compressor power input
DBE – Dry Bulb Temp. (0F) of Air Entering Coil

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.


2. Capacities above are based on DBE = 800F.
For different conditions and full selection, contact your nearest Zamil sales office.

12
Page 165 of 286
COOLING CAPACITIES

Model No.: PY090


EVAPORATOR AIRFLOW, CFM
CONDENSER
2200 2800 3600
ENTERING AIR
TEMP. EVAPORATOR ENTERING AIR, DBE/WBE
80/62 80/67 80/72 80/62 80/67 80/72 80/62 80/67 80/72
TC 87.61 95.51 103.62 91.85 100.05 108.24 95.82 104.16 112.23
85 SC 74.92 63.62 52.39 84.21 70.09 56.14 95.05 77.36 60.10
kW 5.49 5.60 5.72 5.55 5.67 5.79 5.61 5.73 5.85
TC 84.49 92.22 100.01 88.53 96.50 104.39 92.46 100.32 107.96
95 SC 72.74 61.48 50.34 81.85 67.76 53.96 91.72 74.86 57.66
kW 6.22 6.22 6.32 6.16 6.27 6.40 6.22 6.33 6.46
TC 79.94 87.28 94.68 83.68 91.16 98.63 87.92 94.66 102.01
105 SC 71.18 59.85 48.67 80.18 66.02 52.15 87.75 72.92 55.73
kW 6.81 6.92 7.04 6.87 6.98 7.09 6.93 7.04 7.14
TC 75.30 82.25 89.19 78.58 85.81 92.71 83.20 88.96 95.72
115 SC 69.51 58.10 46.87 78.35 64.16 50.18 83.20 70.90 53.55
kW 7.60 7.72 7.84 7.67 7.78 7.89 7.74 7.83 7.94
TC 70.19 76.82 83.36 73.32 80.01 86.40 78.05 82.82 88.94
125 SC 67.34 55.98 44.75 73.23 61.80 47.88 77.95 68.38 50.94
kW 8.51 8.61 8.71 8.56 8.66 8.79 8.63 8.70 8.83

Model No.: PY120


EVAPORATOR AIRFLOW, CFM
CONDENSER
2800 3600 4600
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 106.06 115.89 125.88 111.29 121.42 131.53 118.09 126.04 135.87
85 SC 95.12 79.89 64.77 108.61 89.23 70.03 118.09 99.22 75.13
kW 7.28 7.36 7.42 7.32 7.40 7.46 7.37 7.43 7.48
TC 101.92 111.47 120.91 106.87 116.54 126.05 113.85 120.70 130.15
95 SC 93.03 77.89 62.68 106.49 86.94 67.69 113.85 96.69 72.62
kW 8.16 8.23 8.32 8.20 8.29 8.35 8.27 8.32 8.37
TC 97.34 106.43 115.59 102.47 111.15 120.20 109.22 115.06 123.83
105 SC 90.77 75.55 60.44 102.47 84.47 65.19 109.22 94.06 69.86
kW 9.13 9.21 9.28 9.18 9.25 9.31 9.23 9.27 9.33
TC 92.02 100.71 109.34 97.61 104.93 113.49 103.83 108.56 116.69
115 SC 88.20 72.95 57.76 97.61 81.61 62.31 103.83 90.99 66.56
kW 10.18 10.26 10.33 10.24 10.30 10.36 10.29 10.33 10.38
TC 85.81 94.13 102.31 91.99 97.96 106.08 97.64 101.14 109.04
125 SC 85.17 69.90 54.75 91.99 78.34 59.05 97.64 87.45 62.92
kW 11.28 11.38 11.45 11.36 11.41 11.48 11.41 11.44 11.50

TC – Total Capacity (1000 Btuh) Gross WBE – Wet Bulb Temp. (0F) of Air Entering Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross kW – Compressor power input
DBE – Dry Bulb Temp. (0F) of Air Entering Coil

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.


2. Capacities above are based on DBE = 800F.
For different conditions and full selection, contact your nearest Zamil sales office.

13
Page 166 of 286
COOLING CAPACITIES

Model No.: PY150


EVAPORATOR AIRFLOW, CFM
CONDENSER
3000 4200 5000
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 129.97 142.51 155.32 139.78 152.94 165.98 144.62 157.59 170.63
85 SC 110.77 94.67 78.33 132.58 109.92 87.34 144.62 118.70 92.15
kW 8.97 8.99 9.01 8.98 9.01 9.03 8.99 9.01 9.04
TC 124.40 136.47 148.84 133.46 146.11 158.88 139.14 150.41 162.81
95 SC 108.01 91.87 75.58 129.48 106.77 84.31 139.14 115.37 88.78
kW 9.93 9.96 9.97 9.96 9.97 9.98 9.96 9.97 9.99
TC 118.19 129.95 141.90 126.74 138.88 150.98 133.10 142.86 154.73
105 SC 105.00 88.84 72.62 126.21 103.45 80.95 133.10 111.81 85.23
kW 11.02 11.02 11.02 11.02 11.02 11.03 11.02 11.02 11.03
TC 111.59 122.77 134.16 120.29 130.94 142.36 126.40 134.54 145.69
115 SC 101.75 85.56 69.37 120.29 99.74 77.25 126.40 107.98 81.27
kW 12.22 12.24 12.23 12.23 12.24 12.23 12.24 12.23 12.23
TC 104.48 115.15 125.83 113.76 122.51 133.15 119.28 125.71 136.06
125 SC 98.29 82.04 65.82 113.76 95.85 73.26 119.28 103.85 76.94
kW 13.54 13.56 13.57 13.55 13.57 13.58 13.56 13.57 13.58

Model No.: PY180


EVAPORATOR AIRFLOW, CFM
CONDENSER
4000 5000 6000
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 153.03 167.43 182.29 159.92 174.88 189.64 166.52 180.08 194.83
85 SC 136.89 115.20 93.64 154.10 127.07 100.39 166.52 137.60 105.95
kW 9.20 9.40 9.60 9.29 9.50 9.70 9.39 9.57 9.77
TC 146.32 160.31 174.69 152.80 167.17 181.57 160.13 172.17 186.64
95 SC 133.59 111.91 90.43 150.67 123.56 96.92 160.13 134.00 102.29
kW 10.25 10.44 10.63 10.34 10.53 10.72 10.44 10.59 10.79
TC 139.21 152.66 166.20 145.76 158.89 172.61 153.26 163.51 177.09
105 SC 130.12 108.40 86.82 145.76 119.75 93.06 153.26 129.89 98.10
kW 11.43 11.62 11.82 11.52 11.72 11.90 11.63 11.78 11.96
TC 131.65 144.61 157.49 139.00 150.51 163.51 146.00 154.45 167.10
115 SC 126.40 104.69 83.10 139.00 115.94 89.12 146.00 125.63 93.54
kW 12.78 12.96 13.15 12.88 13.04 13.24 12.98 13.10 13.29
TC 123.74 136.20 148.37 131.89 141.42 153.59 138.35 145.45 156.81
125 SC 122.57 100.86 79.22 131.89 111.62 84.72 138.35 121.34 88.85
kW 14.28 14.45 14.63 14.39 14.52 14.71 14.48 14.58 14.75

TC – Total Capacity (1000 Btuh) Gross WBE – Wet Bulb Temp. (0F) of Air Entering Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross kW – Compressor power input
DBE – Dry Bulb Temp. (0F) of Air Entering Coil

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.


2. Capacities above are based on DBE = 800F.
For different conditions and full selection, contact your nearest Zamil sales office.

14
Page 167 of 286
COOLING CAPACITIES

Model No.: PY210


EVAPORATOR AIRFLOW, CFM
CONDENSER
5000 6500 8000
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 186.42 203.09 219.71 195.39 212.43 229.01 205.78 218.78 235.58
85 SC 168.54 141.07 113.59 193.77 158.15 122.96 205.78 172.92 130.45
kW 11.73 11.98 12.25 11.86 12.13 12.40 12.02 12.23 12.50
TC 178.89 194.77 210.72 187.95 203.66 219.54 198.24 209.42 225.08
95 SC 164.86 137.27 109.78 187.95 154.05 118.82 198.24 168.55 125.68
kW 12.98 13.22 13.51 13.12 13.36 13.65 13.27 13.48 13.74
TC 170.49 185.88 201.42 180.36 194.12 209.62 189.93 199.55 214.40
105 SC 160.83 133.16 105.82 180.36 149.67 114.42 189.93 163.80 120.91
kW 14.44 14.66 14.90 14.58 14.79 15.04 14.73 14.88 15.12
TC 161.70 176.58 191.31 172.22 184.03 198.72 181.09 189.18 202.89
115 SC 156.55 128.89 101.52 172.22 144.98 109.73 181.09 158.92 115.47
kW 16.08 16.30 16.52 16.24 16.41 16.64 16.37 16.49 16.70
TC 152.68 166.78 180.64 163.88 173.58 187.24 171.89 178.41 191.06
125 SC 152.11 124.37 96.94 163.88 140.05 104.50 171.89 153.67 109.79
kW 17.88 18.12 18.34 18.07 18.23 18.43 18.20 18.30 18.48

Model No.: PY240


EVAPORATOR AIRFLOW, CFM
CONDENSER
5000 7000 8500
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 211.01 229.44 248.22 225.26 244.51 263.02 233.45 251.74 269.87
85 SC 182.94 154.98 127.32 215.60 177.20 139.71 231.24 190.89 146.49
kW 12.53 12.79 13.07 12.73 13.01 13.30 12.85 13.12 13.41
TC 201.00 218.60 236.49 214.28 232.44 249.86 222.24 239.11 256.05
95 SC 178.83 150.81 123.22 208.61 172.44 134.90 222.24 185.85 141.34
kW 14.30 14.30 14.58 14.24 14.52 14.79 14.37 14.62 14.89
TC 190.65 207.36 224.11 203.15 220.05 236.26 210.92 226.05 241.88
105 SC 172.76 144.95 117.51 199.98 165.76 128.52 210.92 178.72 134.50
kW 15.77 16.01 16.28 15.95 16.19 16.47 16.06 16.31 16.56
TC 179.72 195.73 211.42 191.72 207.18 222.34 199.74 212.56 227.06
115 SC 166.43 138.85 111.62 191.24 158.96 121.89 199.74 171.20 127.27
kW 17.74 17.97 18.20 17.91 18.13 18.36 18.03 18.22 18.44
TC 168.48 183.57 198.25 180.04 193.86 207.81 188.13 198.80 212.04
125 SC 159.96 132.56 105.56 180.04 151.74 114.95 188.13 163.58 119.91
kW 19.94 20.16 20.37 20.11 20.30 20.51 20.22 20.37 20.57

TC – Total Capacity (1000 Btuh) Gross WBE – Wet Bulb Temp. (0F) of Air Entering Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross kW – Compressor power input
DBE – Dry Bulb Temp. (0F) of Air Entering Coil

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.


2. Capacities above are based on DBE = 800F.
For different conditions and full selection, contact your nearest Zamil sales office.

15
Page 168 of 286
COOLING CAPACITIES

Model No.: PY300


EVAPORATOR AIRFLOW, CFM
CONDENSER
6000 8000 10000
ENTERING AIR
TEMP. (0F) EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
TC 266.71 289.89 312.57 282.72 306.10 329.10 293.72 317.22 340.15
85 SC 224.45 191.70 158.80 256.92 213.80 171.74 285.24 232.51 181.62
kW 16.30 16.67 17.08 16.56 16.98 17.36 16.73 17.16 17.54
TC 253.41 275.64 298.02 268.50 291.21 313.31 278.30 301.18 323.08
95 SC 218.85 186.13 153.65 250.92 207.96 166.10 278.30 226.08 175.51
kW 18.64 18.64 19.04 18.52 18.92 19.32 18.69 19.11 19.50
TC 239.37 260.74 281.80 253.22 274.88 295.91 262.28 284.69 304.79
105 SC 210.65 178.32 146.16 241.95 199.45 157.97 262.28 217.12 166.80
kW 20.54 20.92 21.32 20.78 21.19 21.60 20.95 21.37 21.78
TC 225.1 245.37 265.03 237.71 258.33 277.81 247.53 266.7 285.34
115 SC 202.51 170.39 138.46 232.90 190.74 149.57 247.53 207.56 157.58
kW 23.06 23.42 23.87 23.28 23.66 24.12 23.46 23.90 24.29
TC 209.94 229.22 248.15 221.20 240.99 259.42 232.29 248.86 265.91
125 SC 193.79 162.06 130.75 221.20 181.55 141.10 232.29 197.80 148.36
kW 25.93 26.23 26.57 26.11 26.45 26.79 26.29 26.58 27.01

Model No.: PY360


EVAPORATOR AIRFLOW, CFM
CONDENSER
8000 9200 11000
ENTERING AIR
TEMP. EVAPORATOR ENTERING AIR, DBE/WBE
80/62 80/67 80/72 80/62 80/67 80/72 80/62 80/67 80/72
TC 334.53 363.34 392.35 344.18 373.48 402.49 355.29 384.90 413.44
85 SC 288.18 243.22 198.65 309.00 257.51 206.89 337.53 276.56 216.94
kW 19.59 20.06 20.54 19.74 20.22 20.72 19.92 20.42 20.91
TC 312.80 339.58 366.39 321.14 348.47 375.02 331.14 358.67 384.95
95 SC 275.48 231.34 187.54 295.42 244.85 194.99 323.00 263.12 204.67
kW 22.43 22.43 22.91 22.10 22.58 23.07 22.28 22.77 23.26
TC 290.69 315.59 340.33 298.37 323.60 347.99 307.82 332.90 356.68
105 SC 262.59 219.24 176.46 281.95 232.14 183.42 303.99 249.62 192.22
kW 24.63 25.10 25.58 24.77 25.25 25.73 24.95 25.43 25.90
TC 268.74 291.91 314.49 275.52 298.93 321.23 285.08 307.21 328.54
115 SC 249.85 207.28 165.19 266.40 219.57 171.62 279.81 236.16 179.63
kW 27.63 28.09 28.55 27.76 28.23 28.69 27.95 28.40 28.85
TC 250.08 272.01 293.08 256.59 278.32 298.85 267.13 285.66 305.24
125 SC 240.75 199.06 157.20 251.61 210.96 163.07 261.94 226.94 170.47
kW 30.98 31.41 31.85 31.11 31.54 31.97 31.31 31.69 32.11

TC – Total Capacity (1000 Btuh) Gross WBE – Wet Bulb Temp. (0F) of Air Entering Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross kW – Compressor power input
DBE – Dry Bulb Temp. (0F) of Air Entering Coil

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.


2. Capacities above are based on DBE = 800F.
For different conditions and full selection, contact your nearest Zamil sales office.

16
Page 169 of 286
COOLING CAPACITIES

Model No.: PY390


EVAPORATOR AIRFLOW, CFM
CONDENSER
8600 10000 12000
ENTERING AIR
TEMP. EVAPORATOR ENTERING AIR, DBE/WBE
80/62 80/67 80/72 80/62 80/67 80/72 80/62 80/67 80/72
TC 367.84 399.91 431.66 379.80 412.00 443.88 392.90 425.44 456.98
85 SC 300.52 255.07 209.41 324.28 271.49 218.93 355.56 292.45 230.44
kW 23.22 23.87 24.57 23.45 24.14 24.85 23.73 24.43 25.15
TC 352.30 382.51 412.87 363.22 393.94 424.29 375.23 406.11 436.34
95 SC 294.74 248.71 202.95 318.19 264.93 212.18 349.20 285.54 223.22
kW 26.42 26.42 27.11 26.00 26.68 27.38 26.26 26.96 27.67
TC 335.75 364.55 393.07 345.74 374.79 403.23 357.09 386.00 414.47
105 SC 288.33 242.06 195.96 311.55 257.80 204.76 340.55 277.90 215.40
kW 28.64 29.29 29.96 28.86 29.53 30.22 29.12 29.80 30.49
TC 317.94 345.41 371.96 327.13 354.60 381.54 338.72 364.66 390.90
115 SC 281.31 234.75 188.32 304.26 250.01 196.88 329.52 269.81 206.65
kW 31.83 32.47 33.13 32.04 32.69 33.36 32.31 32.94 33.61
TC 299.30 324.98 350.30 307.36 333.33 358.54 319.72 342.51 367.38
125 SC 273.80 226.73 180.33 295.47 241.64 188.24 315.41 261.02 197.63
kW 35.34 35.95 36.58 35.53 36.16 36.79 35.82 36.39 37.02

TC – Total Capacity (1000 Btuh) Gross WBE – Wet Bulb Temp. (0F) of Air Entering Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross kW – Compressor power input
DBE – Dry Bulb Temp. (0F) of Air Entering Coil

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.


2. Capacities above are based on DBE = 800F.
For different conditions and full selection, contact your nearest Zamil sales office.

17
Page 170 of 286
ELECTRICAL DATA

MODEL No.: PY036


Power supply Voltage range FM Compressor BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 20.2 30
230-1-60 207 253 2.5 12.7 77 0.5 1.8 5 21.7 29.4 30
10* 43.5 56.6 60

MODEL No.: PY048


Power supply Voltage range FM Compressor BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 37.6 50
5 21.7 37.6 50
230-1-60 207 253 2.5 23.9 135 0.75 5.2
7.5 32.6 47.3 50
10* 43.5 60.9 70
- - 27.8 40
5 12.6 27.8 40
230-3-60 207 253 2.5 16.1 98 0.75 5.2
7.5 18.8 30 40
10* 25.1 37.9 40
- - 20.1 25

380/400-3-60 5 7.6 20.1 25


342 418 2.5 9.9 64 0.75 5.2
(4 WIRE)
7.5 11.4 20.7 25
10* 15.2 25.5 30

MODEL No.: PY060


Power supply Voltage range FM Compressor BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 42.6 60
5 21.7 42.6 60
230-1-60 207 253 2.5 27.9 134 0.75 5.2
7.5 32.6 47.3 60
10* 43.5 60.9 70
- - 29.8 45
5 12.6 29.8 45
230-3-60 207 253 2.5 17.7 110 0.75 5.2
7.5 18.8 30.0 45
10* 25.1 37.9 45
- - 18.8 25

380/400-3-60 5 7.6 18.8 25


342 418 2.5 8.9 66 0.75 5.2
(4 WIRE)
7.5 11.4 20.7 25
10* 15.2 25.5 30

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.
18
Page 171 of 286
ELECTRICAL DATA

MODEL No.: PY075


Power supply Voltage range FM Compressor BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 33.0 50.0
5 12.6 33.0 50.0
1.5 3.9 7.5 18.8 33.0 50.0
(STD)
10* 25.1 36.3 50.0
15* 37.7 51.9 60.0
230-3-60 207 253 2.6 21.2 123
- - 34.4 50.0
5 12.6 34.4 50.0
2 5.3 7.5 18.8 34.4 50.0
(ALT)
10* 25.1 38.0 50.0
15* 37.7 53.7 60.0
- - 18.7 30
5 7.6 18.7 30
1.5 2.2 7.5 11.4 18.7 30
(STD)
10* 15.2 21.8 30
15* 22.8 31.3 35
380/400-3-60 342 418 1.6 11.9 78
(4 WIRE) - - 19.5 30
5 7.6 19.5 30
2 3.1 7.5 11.4 19.5 30
(ALT)
10* 15.2 22.8 30
15* 22.8 32.3 35
- - 15.4 20
5 6.3 15.4 20
1.5 2.1 7.5 9.4 15.4 20
(STD)
10* 12.6 18.4 20
15* 18.8 26.2 30
460-3-60 414 506 1.9 9.1 66.1
- - 16.1 25
5 6.3 16.1 25
2 2.8 7.5 9.4 16.1 25
(ALT)
10* 12.6 19.2 25
15* 18.8 27.1 30

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

19
Page 172 of 286
ELECTRICAL DATA
MODEL No.: PY090
Power supply Voltage range FM Compressor BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 44.5 70
7.5 18.8 44.5 70
2 5.3 10* 25.1 44.5 70
(STD) 15* 37.7 53.7 70
20* 50.2 69.4 70
- - 47.1 70
7.5 18.8 47.1 70
230-3-60 207 253 4.3 27.9 164 3 7.9 10* 25.1 47.1 70
(ALT) 15* 37.7 56.9 70
20* 50.2 72.6 80
- - 53 80
7.5 18.8 53 80
5 13.8 10* 25.1 53 80
(ALT) 15* 37.7 64.3 80
20* 50.2 80 90
- - 25 40
7.5 11.4 25 40
2 3.1 10* 15.2 25 40
(STD) 15* 22.8 32.4 40
20* 30.4 41.9 45
- - 26.5 40
7.5 11.4 26.5 40
380-3-60 342 418 2.5 15.5 94.3 3 4.6 10* 15.2 26.5 40
(4 WIRE) (ALT) 15* 22.8 34.2 40
20* 30.4 43.7 45
- - 30.3 45
7.5 11.4 30.3 45
5 8.4 10* 15.2 30.3 45
(ALT) 15* 22.8 39.0 45
20* 30.4 48.5 50
- - 22.0 35
7.5 9.4 22.0 35
2 2.8 10* 12.6 22.0 35
(STD) 15* 18.8 27.0 35
20* 25.1 34.9 40
- - 23.6 35
7.5 9.4 23.6 35
460-3-60 414 506 2.2 13.6 100.0 3 4.4 10* 12.6 23.6 35
(ALT) 15* 18.8 29.0 35
20* 25.1 36.9 40
- - 26.1 35
7.5 9.4 26.1 35
5 6.9 10* 12.6 26.1 35
(ALT) 15* 18.8 32.2 35
20* 25.1 40 45

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

20
Page 173 of 286
ELECTRICAL DATA
MODEL No.: PY120
Power supply Voltage range FM (each) Comp (each) BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 50.1 60
7.5 18.8 50.1 60
2 5.3 10* 25.1 50.1 60
(STD) 15* 37.7 53.7 60
20* 50.2 69.4 70
- - 52.7 70
7.5 18.8 52.7 70
230-3-60 207 253 2.5 17.7 110 3 7.9 10* 25.1 52.7 70
(ALT) 15* 37.7 56.9 70
20* 50.2 72.6 80
- - 58.6 70
7.5 18.8 58.6 70
5 13.8 10* 25.1 58.6 70
(ALT) 15* 37.7 64.3 70
20* 50.2 80.0 90
- - 28.1 35
7.5 11.4 28.1 35
2 3.1 10* 15.2 28.1 35
(STD) 15* 22.8 32.3 35
20* 30.4 41.8 45
- - 29.6 35
7.5 11.4 29.6 35
380/400-3-60 342 418 2.5 8.9 66 3 4.6 10* 15.2 29.6 35
(4 WIRE) (ALT) 15* 22.8 34.2 35
20* 30.4 43.7 45
- - 33.4 40
7.5 11.4 33.4 40
5 8.4 10* 15.2 33.4 40
(ALT) 15* 22.8 39.0 40
20* 30.4 48.5 50
- - 22.9 30
7.5 9.4 22.9 30
2 2.8 10* 12.6 22.9 30
(STD) 15* 18.8 27.1 30
20* 25.1 34.9 40
- - 24.4 30
7.5 9.4 24.4 30
460-3-60 414 506 1.15 7.9 55 3 4.4 10* 12.6 24.4 30
(ALT) 15* 18.8 29.0 30
20* 25.1 36.8 40
- - 27.0 30
7.5 9.4 27.0 30
5 6.9 10* 12.6 27.0 30
(ALT) 15* 18.8 32.2 35
20* 25.1 40.0 45

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

21
Page 174 of 286
ELECTRICAL DATA

MODEL No.: PY150


Power supply Voltage range FM (each) Comp (each) BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 60.9 80
7.5 18.8 60.9 80
3 7.9 10* 25.1 60.9 80
(STD)
15* 37.7 60.9 80
20* 50.2 72.6 80
230-3-60 207 253 2.6 21.2 123
- - 66.7 80
7.5 18.8 66.7 80
5 13.8 10* 25.1 66.7 80
(ALT)
15* 37.7 66.7 80
20* 50.2 80.0 90
- - 34.6 45
7.5 11.4 34.6 45
3 4.6 10* 15.2 34.6 45
(STD)
15* 22.8 34.6 45
20* 30.4 43.7 45
380/400-3-60 342 418 1.6 11.9 78
(4 WIRE) - - 38.4 50
7.5 11.4 38.4 50
5 8.4 10* 15.2 38.4 50
(ALT)
15* 22.8 39.0 50
20* 30.4 48.5 50
- - 28.6 35
7.5 9.4 28.6 35
3 4.4 10* 12.6 28.6 35
(STD)
15* 18.8 29.0 35
20* 25.1 36.8 40
460-3-60 414 506 1.9 9.1 66
- - 31.2 40
7.5 9.4 31.2 40
5 6.9 10* 12.6 31.2 40
(ALT)
15* 18.8 32.2 40
20* 25.1 40.0 45

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

22
Page 175 of 286
ELECTRICAL DATA

MODEL No.: PY180


Power supply Voltage range FM (each) Comp (each) BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 74.6 90
3 7.9 20* 50.2 74.6 90
(STD)
30* 75.3 104.0 110
- - 80.5 100
230-3-60 207 253 5.2 25.0 149 5 13.8 20* 50.2 80.5 100
(ALT)
30* 75.3 111.4 125
- - 85.3 110
7.5 18.6 20* 50.2 85.3 110
(ALT)
30* 75.3 117.4 125
- - 38.1 50
3 4.6 20* 30.4 43.7 50
(STD)
30* 45.6 62.7 70
- - 41.9 50
380/400-3-60 342 418 3.0 12.2 88 5 8.4 20* 30.4 48.5 50
(4 WIRE) (ALT)
30* 45.6 67.5 70
- - 45.4 50
7.5 11.9 20* 30.4 52.9 60
(ALT)
30* 45.6 71.9 80
- - 36.8 45
3 4.4 20* 25.1 36.9 45
(STD)
30* 37.7 52.6 60
- - 39.3 50
460-3-60 414 506 2.9 11.8 75 5 6.9 20* 25.1 40.0 50
(ALT)
30* 37.7 55.7 60
- - 41.7 50
7.5 9.3 20* 25.1 43.0 50
(ALT)
30* 37.7 58.7 60

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

23
Page 176 of 286
ELECTRICAL DATA

MODEL No.: PY210


Power supply Voltage range FM (each) Comp (each) BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 87.0 110
5 13.8 20* 50.2 87.0 110
(STD)
30* 75.3 111.4 125
- - 91.8 110
230-3-60 207 253 5.2 27.9 164 7.5 18.6 20* 50.2 91.8 110
(ALT)
30* 75.3 117.4 125
- - 99.4 125
10 26.2 20* 50.2 99.4 125
(ALT)
30* 75.3 126.9 150
- - 49.3 60
5 8.4 20* 30.4 49.3 60
(STD)
30* 45.6 67.5 70
- - 52.8 60
380/400-3-60 342 418 3.0 15.5 94 7.5 11.9 20* 30.4 52.9 60
(4 WIRE) (ALT)
30* 45.6 71.9 80
- - 56.5 70
10 15.6 20* 30.4 57.5 70
(ALT)
30* 45.6 76.5 80
- - 43.3 50
5 6.9 20* 25.1 43.3 50
(STD)
30* 37.7 55.7 60
- - 45.7 50
460-3-60 414 506 2.9 13.6 100 7.5 9.3 20* 25.1 45.7 50
(ALT)
30* 37.7 58.7 60
- - 49.5 60
10 13.1 20* 25.1 49.5 60
(ALT)
30* 37.7 63.4 70

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

24
Page 177 of 286
ELECTRICAL DATA

MODEL No.: PY240


Power supply Voltage range FM (each) Comp (each) BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 94.1 125
5 20* 50.2 94.1 125
(STD) 13.8 30* 75.3 111.4 125
40* 100.4 142.8 150
- - 98.9 125
27.9 164 20* 50.2 98.9 125
7.5
230-3-60 207 253 5.2 & & 18.6
(ALT) 30* 75.3 117.4 125
33.6 225
40* 100.4 148.8 150
- - 106.5 125
10 20* 50.2 106.5 125
26.2
(ALT) 30* 75.3 126.9 150
40* 100.4 158.3 175
- - 56.7 70
5 20* 30.4 56.7 70
8.4
(STD) 30* 45.6 67.5 70
40* 60.8 86.5 90
- - 60.2 80
15.5 94.3
7.5 20* 30.4 60.2 80
380/400-3-60 342 418 3.0 & & 11.9
(ALT) 30* 45.6 71.9 80
(4 WIRE) 21.4 140
40* 60.8 90.8 100
- - 63.9 80
10
(ALT) 15.6 20* 30.4 63.9 80
30* 45.6 76.5 80
40* 60.8 95.5 100
- - 49.6 60
5 20* 25.1 49.6 60
6.9
(STD) 30* 37.7 55.7 60
40* 50.2 71.4 80
- - 52.0 70
13.6 100 7.5 20* 25.1 52.0 70
460-3-60 414 506 2.9 & & 9.3
(ALT) 30* 37.7 58.7 70
18.6 114
40* 50.2 74.4 80
- - 55.8 70
10 20* 25.1 55.8 70
13.1
(ALT) 30* 37.7 63.4 70
40* 50.2 79.1 80

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

25
Page 178 of 286
ELECTRICAL DATA

MODEL No.: PY300


Power supply Voltage range FM (each) Comp (each) BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 107.7 125
5 20* 50.2 107.7 125
(STD) 13.8 30* 75.3 111.4 125
40* 100.4 142.8 150
- - 120.1 150
10 20* 50.2 120.1 150
230-3-60 207 253 5.2 37.1 239 26.2
(ALT) 30* 75.3 126.9 150
40* 100.4 158.3 175
- - 132 150
15 20* 50.2 132 150
38.0
(ALT) 30* 75.3 142 150
40* 100.4 173 175
- - 73.8 100
5 20* 30.4 73.8 100
8.4
(STD) 30* 45.6 73.8 100
40* 60.8 86.5 100
- - 81.0 100
10 20* 30.4 81.0 100
380/400-3-60 342 418 3.0 26.4 145 15.6
(ALT) 30* 45.6 81.0 100
(4 WIRE)
40* 60.8 95.5 100
- - 88.4 110
15
(ALT) 23.0 20* 30.4 88.4 110
30* 45.6 88.4 110
40* 60.8 104.7 110
- - 57.7 70
5 20* 25.1 57.7 70
6.9
(STD) 30* 37.7 57.7 70
40* 50.2 71.4 80
- - 63.9 80
10 20* 25.1 63.9 80
460-3-60 414 506 2.9 20.0 125 13.1
(ALT) 30* 37.7 63.9 80
40* 50.2 79.1 80
- - 69.8 80
15 20* 25.1 69.8 80
19.0
(ALT) 30* 37.7 70.8 80
40* 50.2 86.5 90

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

26
Page 179 of 286
ELECTRICAL DATA

MODEL No.: PY360


Power supply Voltage range FM (each) Comp (each) BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 159.2 200
7.5 20* 50.2 159.2 200
(STD) 20.6 30* 75.3 159.2 200
40* 100.4 159.2 200
- - 163.0 200
53.6 245 20* 50.2 163.0 200
10
230-3-60 207 253 6.8 & & 24.4
(ALT) 30* 75.3 163.0 200
57.1 300
40* 100.4 163.0 200
- - 176.6 225
15 20* 50.2 176.6 225
38.0
(ALT) 30* 75.3 176.6 225
40* 100.4 176.6 225
- - 83.3 110
7.5 20* 30.4 83.3 110
11.4
(STD) 30* 45.6 83.3 110
40* 60.8 90.3 110
- - 87.0 110
26.4 145
10 20* 30.4 87.0 110
380-3-60 342 418 4.0 & & 15.1
(ALT) 30* 45.6 87.0 110
(4 WIRE) 30 139
40* 60.8 94.9 110
- - 92.9 110
15
(ALT) 21.0 20* 30.4 92.9 110
30* 45.6 92.9 110
40* 60.8 102.2 110
- - 70.7 90
7.5 20* 25.1 70.7 90
10.3
(STD) 30* 37.7 70.7 90
40* 50.2 75.6 90
- - 72.6 90
20.7 125
10 20* 25.1 72.6 90
460-3-60 414 506 3.8 & & 12.2
25.7 150 (ALT) 30* 37.7 72.6 90
40* 50.2 78.0 90
- - 79.5 100
15 20* 25.1 79.5 100
19.1
(ALT) 30* 37.7 79.5 100
40* 50.2 86.6 100

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

27
Page 180 of 286
ELECTRICAL DATA

MODEL No.: PY390


Power supply Voltage range FM (each) Comp (each) BM Electric Heater
MCA MOCP
(V-PH-HZ) Min Max. FLA RLA LRA HP FLA Nom. kW FLA
- - 168.9 225
7.5 20* 50.2 168.9 225
(STD) 20.6
30* 75.3 168.9 225
40* 100.4 168.9 225
- - 172.7 225
57.1 300 10 20* 50.2 172.7 225
230-3-60 207 253 6.8 & & (ALT) 24.4
30* 75.3 172.7 225
62.1 340
40* 100.4 172.7 225
- - 186.3 225
15 20* 50.2 186.3 225
(ALT) 38.0
30* 75.3 186.3 225
40* 100.4 186.3 225
- - 96.8 125
7.5 20* 30.4 96.8 125
(STD) 11.4
30* 45.6 96.8 125
40* 60.8 96.8 125
- - 100.5 125
30 139 10 20* 30.4 100.5 125
380-3-60 342 418 4.0 & & (ALT) 15.1
(4 WIRE) 30* 45.6 100.5 125
37.9 196
40* 60.8 100.5 125
- - 106.4 125
15 20* 30.4 106.4 125
(ALT) 21.0
30* 45.6 106.4 125
40* 60.8 106.4 125
- - 81.1 110
7.5 20* 25.1 81.1 110
(STD) 10.3
30* 37.7 81.1 110
40* 50.2 81.1 110
- - 83.0 110
25.7 150 10 20* 25.1 83.0 110
460-3-60 414 506 3.8 & & (ALT) 12.2
30 173 30* 37.7 83.0 110
40* 50.2 83.0 110
- - 89.9 110
15 20* 25.1 89.9 110
(ALT) 19.1 30* 37.7 89.9 110
40* 50.2 89.9 110

LEGEND:
BM - Blower Motor FM - Fan Motor HP - Horse Power
FLA - Full Load Amps RLA - Rated Load Amps LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps MOCP - Maximum Over Current Protection

*Two stage heater

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while
further voltage tolerances can be supported with special orders.

28
Page 181 of 286
FAN PERFORMANCE DATA
(DIRECT DRIVE MOTOR)

MODEL No.: PY036

BLOWER EXTERNAL STATIC PRESSURE (inch wg.)


MOTOR
SPEED 0.1 0.2 0.3 0.4 0.5 0.6

HIGH CFM 1200 1125 1050 950 875 770

MEDIUM CFM 1050 950 875 840 810 720

LOW CFM 900 850 800 750 710 650

MODEL No.: PY048


BLOWER CFM @ EXTEERNAL STATIC PRESSURE (INCHES OF WATER)
MOTOR
SPEED 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6

HIGH 2125 2100 2070 2050 2040 2010 1981 1955 1930 1910 1900 1828

MEDIUM 1700 1675 1655 1655 1600 1575 1555 1530 1500 1480 1450 1410

LOW 1410 1380 1350 1310 1260 1240 1225 1170 1140 1100 * *

MODEL No.: PY060


BLOWER CFM @ EXTEERNAL STATIC PRESSURE (INCHES OF WATER)
MOTOR
SPEED 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6

HIGH 2125 2100 2070 2050 2040 2010 1981 1955 1930 1910 1900 1828

MEDIUM 1700 1675 1655 1625 1600 1575 1555 1530 1500 1480 1450 1410

LOW 1410 1380 1350 1310 1260 1240 1225 * * * * *

NOTE: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Direct drive motors have single speed connection only. Factory set at medium speed. Thermostats are also single speed
type only. Refer to the unit wiring diagram for connecting to other motor speeds.

29
Page 182 of 286
FAN PERFORMANCE DATA

Model No.: PY075


External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1600 886 0.51 1001 0.66 1114 0.84 1226 1.05 II
1800 868 0.54 973 0.68 1076 0.84 1178 1.03 1278 1.25 1378 1.49
2000 860 0.59 957 0.72 1052 0.88 1145 1.06 1237 1.25 1328 1.46 1418 1.70
2200 858 0.64 948 0.78 1036 0.92 1123 1.10 1208 1.29 1293 1.49 1376 1.70
2400 860 0.71 945 0.84 1028 0.99 1109 1.17 1189 1.34 1268 1.53 1346 1.74
Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 1.5 HP motor to be used for the unshaded portion.
3. Alt. 2 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

Model No.: PY090


External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2200 687* 0.43* 784 0.54 876 I 0.67 966 0.80 1054 0.97 1140 1.14 1225 1.33 1309 1.53 1393 1.74 1475 1.98 1557 2.25 1639 2.53 IV
2400 730* 0.54* 820 0.64 906 0.78 989 0.92 1071 1.09 1152
II1.25 1231 1.43 1309 1.64 1387 1.85
III1463 2.08 1539 2.33 1615 2.60 1690 2.88
2600 774 0.64 858 0.78 938 0.91 1016 1.06 1093 1.22 1168 1.39 1242 1.58 1316 1.77 1388 1.98 1460 2.21 1531 2.45 1602 2.71 1672 2.98
2800 819 0.78 897 0.91 973 1.06 1046 1.21 1118 1.38 1189 1.55 1259 1.74 1328 1.93 1396 2.14 1464 2.37 1531 2.60 1597 2.86 1663 3.11
3000 864 0.94 938 1.07 1009 1.22 1079 1.38 1147 1.55 1214 1.73 1280 1.92 1345 2.12 1409 2.33 1473 2.55 1536 2.79 1599 3.03 1661 3.28
3200 910 1.11 979 1.26 1047 1.41 1113 1.58 1177 1.76 1241 1.93 1303 2.13 1365 2.33 1426 2.53 1487 2.76 1547 2.99 1606 3.24 1665 3.49
3400 956 1.30 1022 1.46 1086 1.62 1148 1.80 1210 1.97 1270 2.16 1330 2.36 1389 2.56 1447 2.77 1504 3.00 1562 3.23 1618 3.47 1674 3.73
3600 1002 1.51 1065 1.68 1126 1.85 1186 2.02 1244 2.21 1302 2.41 1359 2.61 1415 2.82 1470 3.04 1525 3.26 1580 3.50 1634 3.74 1687 3.99

Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 2 HP motor to be used for the unshaded portion.
3. 3 HP and 5 HP motor to be used for shaded portion.
4. Bordered regions indicate alternative drives I, II, III & IV.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

30
Page 183 of 286
FAN PERFORMANCE DATA

Model No.: PY120


External Static Pressure (inch wg.)
Airflow,
0.4 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.6
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2800 767 0.84 905 1.17 968 1.34 1029 1.53 1087 1.72 1143 1.92 1197* 2.12* 1248 2.32 1299 2.55 1395 2.99
3000 769 0.91 904 1.25 966
I 1.42 1026 1.61 1083 1.80
II
1138 2.00 1191* 2.21* 1243
III
2.43 1292 2.64 1387 3.10
3200 772 0.98 904 1.33 965 1.50 1024 1.70 1080 1.89 1134 2.10 1187* 2.31* 1238 2.53 1287 2.75 1381 3.22
3400 777 1.06 905 1.41 965 1.60 1023 1.80 1078 2.00 1132 2.21 1183 2.43 1233 2.64 1282 2.87 1375 3.34
3600 782 1.15 908 1.50 966 1.70 1023 1.90 1077 2.10 1130 2.32 1181 2.53 1230 2.76 1278 2.99 1370 3.47
3800 788 1.25 911 1.61 968 1.81 1024 2.01 1077 2.23 1129 2.44 1179 2.65 1228 2.90 1275 3.12 1366 3.61
4000 795 1.34 915 1.72 971 1.92 1025 2.13 1078 2.35 1129 2.56 1178 2.79 1226 3.03 1273 3.27 1363 3.75
4200 803 1.45 920 1.84 975 2.05 1028 2.25 1080 2.48 1130 2.71 1178 2.94 1226 3.16 1272 3.42 1360 3.91
4400 812 1.57 925 1.97 979 2.17 1032 2.40 1082 2.61 1131 2.84 1179 3.08 1226 3.32 1271 3.57 1359 4.08
4600 821 1.69 932 2.10 985 2.32 1036 2.53 1085 2.76 1134 3.00 1181 3.24 1227 3.49 1271 3.74 1358 4.25

Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 2 HP motor to be used for the unshaded portion.
3. 3 HP and 5 HP motor to be used for shaded portion.
4. Bordered regions indicate alternative drives I, II & III .
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

Model No.: PY150


External Static Pressure (inch wg.)
Airflow,
0.4 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.6
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3000 738* 0.84* 876 1.17 940 1.34 1001 1.53 1059 1.72 1115 I1.92 1169 2.12 1221 2.33 1271 II2.55 1367 3.00
3200 741* 0.91* 876 1.25 938 1.42 998 1.61 1055 1.81 1110 2.01 1164 2.21 1215 2.43 1265 2.65 1360 3.11
3400 745* 0.98* 877 1.33 938 1.51 996 1.70 1053 1.90 1107 2.10 1160 2.32 1210 2.53 1260 2.76 1354 3.23
3600 750* 1.06* 878 1.42 938 1.61 996 1.80 1051 2.01 1105 2.21 1156 2.43 1207 2.65 1255 2.88 1348 3.35
3800 756* 1.15* 881 1.51 940 1.70 996 1.90 1051 2.12 1103 2.33 1154 2.55 1204 2.77 1252 3.00 1344 3.49
4000 762* 1.25* 884 1.62 942 1.82 997 2.02 1051 2.23 1103 2.45 1153 2.67 1201 2.91 1249 3.14 1340 3.63
4200 770* 1.35* 889 1.73 945 1.93 999 2.14 1052 2.36 1103 2.57 1152 2.80 1200 3.04 1247 3.28 1337 3.78
4400 778* 1.46* 894 1.85 949 2.06 1002 2.27 1054 2.49 1104 2.72 1152 2.95 1200 3.19 1246 3.43 1334 3.94
4600 787* 1.58* 900 1.98 954 2.18 1006 2.41 1057 2.63 1106 2.87 1153 3.10 1200 3.34 1245 3.59 1333 4.10
4800 797* 1.70* 907 2.12 959 2.33 1010 2.56 1060 2.79 1108 3.02 1155 3.26 1201 3.50 1246 3.75 1332 4.28
5000 807* 1.84* 914 2.27 966 2.48 1016 2.71 1064 2.95 1112 3.18 1158 3.43 1203 3.67 1247 3.93

Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 3 HP motor to be used for the unshaded portion.
3. 5 HP motor to be used for shaded portion.
4. Bordered regions indicate alternative drives I & II.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

31
Page 184 of 286
FAN PERFORMANCE DATA

Model No.: PY180


External Static Pressure (inch wg.)
Airflow,
0.4 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.6
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4000 624 1.29 752 1.92 813 I 2.27 871 2.65 928 3.07 II 983 3.51 III
4200 620 1.34 746 1.96 805 2.31 863 2.68 918 3.10 972 3.53 1024 3.98
4400 618 1.39 741 2.01 799 2.36 855 2.73 909 3.12 962 3.55 1014 4.01 1064 4.49 1113 4.99
4600 616 1.45 736 2.06 793 2.41 848 2.77 901 3.18 953 3.59 1004 4.05 1053 4.52 1101 5.01
4800 615 1.51 732 2.12 788 2.47 842 2.83 894 3.23 945 3.65 995 4.09 1043 4.54 1091 5.04 1183* 6.09*
5000 615 1.58 729 2.20 783 2.53 836 2.90 888 3.28 938 3.70 987 4.14 1034 4.60 1081 5.08 1171* 6.11*
5200 615 1.66 726 2.27 780 2.60 831 2.98 882 3.35 931 3.77 979 4.20 1026 4.65 1072 5.13 1161* 6.15*
5400 616 1.73 724 2.35 777 2.68 827 3.04 877 3.43 925 3.83 972 4.26 1019 4.72 1064 5.19 1152* 6.19*
5600 617 1.82 723 2.43 774 2.77 824 3.14 873 3.51 920 3.91 966 4.34 1012 4.79 1056 5.25 1143 6.26
5800 618 1.90 722 2.52 772 2.87 821 3.23 869 3.61 915 4.01 961 4.44 1006 4.88 1049 5.34 1135 6.33
6000 621 2.00 722 2.63 771 2.96 819 3.32 866 3.70 911 4.10 956 4.53 1000 4.96 1043 5.43 1127 6.41

Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 3 HP motor to be used for the unshaded portion.
3. Alt. II (5 HP) & Alt. III (7.5 HP) motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I, II & III.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

Model No.: PY210


External Static Pressure (inch wg.)
Airflow,
0.4 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.6
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5000 585* 1.45* 701 2.04 756 2.36 810 2.71 I 862 3.10 913* 3.50* 962 II3.91 1011 4.37 1058 4.84 1149* 5.84*
5200 586* 1.51* 699 2.10 753 2.43 805 2.79 857 3.16 906* 3.55* 955 3.98 1003 4.42 1049 4.88 1139* 5.88*
5400 587* 1.60* 697 2.18 750 2.51 801 2.86 852 3.23 900* 3.63* 948 4.05 995 4.48 1041 4.95 1129* 5.92*
5600 588* 1.68* 696 2.27 748 2.59 798 2.94 847 3.31 895* 3.70* 942 4.12 988 4.56 1033 5.01 1121* 5.99*
5800 590* 1.76* 695 2.36 746 2.68 795 3.03 844 3.40 891* 3.79* 937 4.21 982 4.64 1026 5.09 1112 6.06
6000 592* 1.85* 695 2.45 745 2.77 793 3.12 841 3.50 887* 3.89* 932 4.29 976 4.72 1020 5.17 1105 6.14
6200 595* 1.94* 696 2.55 744 2.88 792 3.23 838 3.59 883* 3.98* 928 4.40 972 4.83 1014 5.27 1098 6.22
6400 598* 2.05* 696 2.65 744 2.99 790 3.34 836 3.70 881 4.09 924 4.50 967 4.93 1009 5.38 1092 6.31
6600 601* 2.14* 698 2.76 744 3.10 790 3.45 835 3.82 878 4.21 921 4.61 963 5.04 1005 5.48 1086 6.42
6800 605* 2.27* 699 2.88 745 3.22 790 3.57 833 3.94 877 4.33 919 4.73 960 5.16 1001 5.60 1081 6.54
7000 609* 2.37* 701 3.00 746 3.34 790 3.70 833 4.08 875 4.46 917 4.87 957 5.29 998 5.74 1076 6.66
7200 613* 2.51* 704 3.14 747 3.47 790 3.83 833 4.21 874 4.60 915 5.00 955 5.43 995 5.87 1072 6.80
7400 617* 2.63* 706 3.27 749 3.62 791 3.97 833 4.34 874 4.75 914 5.15 953 5.58 992 6.01 1068 6.94
7600 622* 2.76* 709 3.42 751 3.75 793 4.12 834 4.49 874 4.89 913 5.29 952 5.72 990
III6.17 1065 7.09
7800 627* 2.91* 712 3.57 754 3.91 795 4.28 835 4.65 874 5.05 913 5.46 951 5.88 989 6.33 1062 7.25
8000 632* 3.04* 716 3.71 756 4.06 796 4.44 836 4.81 875 5.21 913 5.63 950 6.05 987 6.49 1060 7.43

Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 5 HP motor to be used for the unshaded portion.
3. 7.5 HP and 10 HP motor to be used for shaded portion.
4. Bordered regions indicate alternative drives I, II & III.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

32
Page 185 of 286
FAN PERFORMANCE DATA

Model No.: PY240


External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5000
5500
458*
490*
0.95*
1.21*
522*
549*
1.18*
1.45*
583
605
1.43
1.72
642
660
1.72
2.01
699
714
2.02
2.33
754
765
I 2.35
2.67
808
816
2.69
3.02
860
865
3.07
3.39
911
913
3.47
3.79
II III
6000 523* 1.5* 578* 1.77* 630 2.05 681 2.36 731 2.68 780 3.03 828 3.39 874 3.78 920 4.18 964 4.61
6500 557* 1.86* 607* 2.14* 657 2.44 705 2.76 752 3.1 797 3.45 842 3.82 886 4.21 930 4.62 972 5.05 1014 5.5 1055 5.97 1095 6.45
7000 591* 2.27* 638* 2.57* 685 2.88 730 3.22 774 3.57 817 3.93 860 4.32 902 4.72 943 5.13 983 5.56 1023 6.02 1062 6.49 1100 6.97
7500 626* 2.73* 670 3.06 714 3.39 756 3.74 798 4.1 839 4.48 879 4.87 919 5.28 958 5.71 996 6.15 1034 6.61 1072 7.09 1109 7.57
8000 661 3.27 703 3.61 744 3.95 784 4.32 823 4.69 862 5.08 901 5.5 938 5.91 976 6.35 1012 6.81 1049 7.27 1084 7.75 1120 8.24
8500 696 3.87 736 4.22 775 4.58 813 4.96 850 5.36 887 5.76 924 6.18 960 6.62 995 7.06 1030 7.53 1065 8 1099 8.5 1133 9.01

Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 5 HP motor to be used for the unshaded portion.
3. 7.5 HP and 10 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I, II & III.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

Model No.: PY300


External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6000 522* 1.5* 576* 1.77* 629* 2.05* 680 2.35 730 2.68 779 I 3.02 826 3.38 873II3.77 918 4.17 963 III1007
4.6 5.04 1050 5.5 1092 5.98
6500 555* 1.85* 606* 2.13* 655 2.44 703 2.75 750 3.08 796 3.43 841 3.81 885 4.2 928 4.61 971 5.04 1012 5.48 1053 5.95 1094 6.43
7000 589* 2.27* 637* 2.56* 683 2.87 728 3.2 772 3.55 816 3.91 858 4.3 900 4.71 941 5.12 981 5.55 1021 6.01 1060 6.47 1099 6.96
7500 624* 2.72* 668 3.04 712 3.38 754 3.71 796 4.08 837 4.46 877 4.85 917 5.27 956 5.68 995 6.13 1033 6.58 1070 7.06 1107 7.55
8000 659 3.26 701 3.59 742 3.94 782 4.3 821 4.68 860 5.07 899 5.47 937 5.9 974 6.33 1011 6.78 1047 7.25 1083 7.72 1118 8.23
8500 694 3.85 733 4.2 772 4.57 810 4.95 848 5.34 885 5.74 922 6.15 958 6.6 993 7.04 1028 7.51 1063 7.98 1097 8.47 1131 8.97
9000 729 4.52 767 4.88 804 5.27 840 5.66 876 6.07 911 6.49 946 6.92 980 7.37 1014 7.83 1048 8.3 1081 8.78 1114 9.29 1146 9.8
9500 765 5.25 800 5.64 836 6.05 870 6.45 904 6.88 938 7.31 971 7.76 1004 8.22 1037 8.69 1069 9.18 1101 9.68 1132 10.19 1164 10.71
10000 801 6.07 835 6.47 868 6.89 901 7.32 934 7.76 966 8.22 998 8.67 1029 9.16 1060 9.64 1091 10.13 1122 10.64 1152 11.17 1182* 11.7*

Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 5 HP motor to be used for the unshaded portion.
3. 10 HP and 15 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I, II & III.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

33
Page 186 of 286
FAN PERFORMANCE DATA

Model No.: PY360


External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8000 508* 2.29* 554* 2.63* 598 2.99 641 3.36 684 3.78 726 4.21 768 4.68 810 5.17 851 5.71 893 6.27 935 6.89 977 7.53 1019 8.23
8200 518* 2.44* 563 2.79 606 3.15 648 3.54 690 3.95 731 4.40 772 4.85 813 5.35 854 5.88 894 6.45 935 7.05 976 7.69 1017 8.38
III976
II 5.24
8400 528* 2.60* 572 2.96 614 3.32 655 3.73 696 4.14 736 4.58 777 5.04 816 5.55 856 6.07 896 6.64 936 7.24 7.87 1015 8.54
8600 538* 2.77* 581 3.14 622 3.51
I663 3.91 703 4.33 742 4.77 781 820 5.74 859 6.27 898 6.84 937 7.43 976 8.06 1015 8.71
8800 548* 2.95* 590 3.32 630 3.70 670 4.10 709 4.53 748 4.97 786 5.46 825 5.95 863 6.47 901 7.04 939 7.63 977 8.24 1015 8.91
9000 558* 3.14* 599 3.51 639 3.90 678 4.30 716 4.73 754 5.19 792 5.67 829 6.17 866 6.69 904 7.25 941 7.84 978 8.46 1015 9.12
9200 568 3.32 608 3.71 647 4.10 685 4.52 723 4.95 760 5.40 797 5.88 834 6.39 871 6.92 907 7.48 943 8.07 980 8.69 1016 9.33
9400 578 3.53 618 3.91 656 4.32 693 4.73 730 5.17 767 5.63 803 6.11 839 6.62 875 7.16 911 7.71 946 8.30 982 8.91 1017 9.56
9600 588 3.74 627 4.13 664 4.53 701 4.96 738 5.40 774 5.87 809 6.35 844 6.86 879 7.40 914 7.96 949 8.54 984 9.16 1019 9.80
9800 599 3.95 636 4.36 673 4.77 709 5.20 745 5.64 780 6.11 815 6.61 850 7.12 880 7.65 919 8.22 953 8.81 987 9.41
IV1021 10.05
10000 609 4.17 646 4.58 682 5.00 718 5.44 753 5.90 787 6.37 822 6.86 856 7.39 883 7.92 923 8.49 957 9.06 990 9.68 1023 10.32
10200 619 4.41 655 4.83 691 5.25 726 5.70 760 6.15 794 6.64 828 7.13 861 7.65 895 8.19 928 8.75 961 9.34 993 9.96 1026 10.59
10400 629 4.65 665 5.07 700 5.51 734 5.95 768 6.42 802 6.90 835 7.41 868 7.94 900 8.47 933 9.05 965 9.64 997 10.24 1029 10.88
10600 639 4.89 674 5.32 709 5.76 743 6.23 776 6.70 809 7.18 841 7.69 874 8.23 906 8.77 938 9.34 970 9.93 1001 10.54 1033 11.18
10800 650 5.16 684 5.59 718 6.05 751 6.50 784 6.98 816 7.48 848 7.99 880 8.53 912 9.08 943 9.65 974 10.24 1005 10.84 1036 11.49
11000 660 5.43 694 5.87 727 6.33 760 6.80 792 7.28 824 7.79 855 8.30 883 8.83 918 9.38 949 9.96 979 10.56 1010 11.17 1040 11.81

Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 7.5 HP motor to be used for the unshaded portion.
3. 10 HP and 15 HP motor to be used for shaded portion.
4. Bordered regions indicate alternative drives I, II, III & IV.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

34
Page 187 of 286
FAN PERFORMANCE DATA

Model No.: PY390


External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8600 589* 3.20* 630 3.59 671 3.99 711 4.42 750 4.87 789 5.35 828 5.84 867 6.38 906 6.94 945 7.55 984* 8.19* 1023* 8.86* 1062 9.57
8800 593* 3.34* 633 3.73 673 4.13 712 4.56 751 5.01 789 5.48 827 5.99 865 6.51 903 7.08 941 7.67 979* 8.30* 1017 8.95 1055 9.65
9000 596* 3.49* 636 3.87 675 4.28 714 4.71 752 5.16 789 5.63 827 6.13 864 6.66 901 7.21 938 7.80 975* 8.42* 1012 9.08 1050 9.76
9200 600* 3.63* 639 4.02 678 4.44 715 4.87 753 5.31 790 5.79 826 6.29 863 6.81 899 7.36 936 7.94 972* 8.55* 1008 9.20 1045 9.87
9400 604* 3.78* 642 4.17 680 4.58 717 5.03
I 754 5.47 790 5.95
II
827 6.45 862 6.97 898 7.52 934
III
8.10 969* 8.70* 1005 9.33 1040 10.00
9600 608 3.93 646 4.33 683 4.75 720 5.19 756 5.64 791 6.11 827 6.61 862 7.13 897 7.68 932 8.24 967* 8.85* 1002 9.48 1036 10.13
9800 612 4.09 649 4.49 686 4.92 722 5.36 758 5.82 793 6.29 828 6.78 862 7.31 896 7.86 931 8.42 965 9.01 999 9.64 1033 10.28
10000 616 4.25 653 4.66 689 5.09 725 5.54 760 5.99 794 6.47 828 6.97 862 7.49 896 8.03 930 8.59 963 9.18 997 9.80 1030 10.44
10200 621 4.42 657 4.84 692 5.27 727 5.71 762 6.18 796 6.66 830 7.16 863 7.68 896 8.22 929 8.78 962 9.37 995 9.99 1028 10.62
10400 625 4.60 661 5.03 696 5.46 730 5.91 764 6.37 798 6.85 831 7.36 864 7.87 896 8.42 929 8.98 961 9.56 994 10.17 1026 10.80
10600 629 4.79 665 5.20 699 5.64 733 6.10 767 6.57 800 7.05 832 7.56 865 8.08 897 8.62 929 9.18 961 9.76 992 10.38 1024 11.01
10800 634 4.97 669 5.40 703 5.84 736 6.30 769 6.77 802 7.27 834 7.76 866 8.28 898 8.83 929 9.40 961 9.97 992 10.58 1023 11.21
11000 639 5.16 673 5.60 707 6.05 740 6.50 772 6.98 804 7.48 836 7.98 868 8.51 899 9.05 930 9.61 961 10.19 991 10.79 1022 11.42
11200 643 5.36 677 5.80 711 6.26 743 6.72 775 7.20 807 7.69 838 8.20 869 8.73 900 9.28 930 9.84 961 10.42 991 11.02 1021 11.64
11400 648 5.56 682 6.01 714 6.47 747 6.94 778 7.43 810 7.92 840 8.43 871* 8.97* 901 9.50 931 10.07 961 10.66 991 11.25 1021 11.88
11600 653 5.76 686 6.22 719 6.69 750 7.16 782 7.65 812 8.15 843 8.67 873* 9.20* 903 9.75 933 10.31 962 10.90 991 11.50 1021 12.12
11800 658 5.99 691 6.45 723 6.92 754 7.40 785 7.88 815 8.39 845* 8.91* 875* 9.45* 905 10.00 934 10.56 963 11.14 992 11.74 1021 12.36
12000 663 6.21 695 6.68 727 7.14 758 7.63 788 8.14 818 8.65 848* 9.17* 878* 9.71* 907 10.25 936 10.82 964 11.41 993 12.01 1021 12.63

Notes: 1. Values include losses for clean 1" filters, wet coils and unit casing.
2. Standard 7.5 HP motor to be used for the unshaded portion.
3. 10 HP and 15 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I, II & III.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

35
Page 188 of 286
SOUND LEVEL DATA

To obtain Sound Pressure Level measured 5 ft. (~1.5 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP (see step 4 & table below).
2. Read dBA level from respective graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from sound power factor table and add dBA level to each values in the row to obtain
Sound Power Level (dB re 10-12 watts).
4. Calculate TSP (Total Static Pressure) as follows:
TSP = ISP + ESP
ESP (External Static Pressure) from Job Specification.
ISP (Internal Static Pressure) Calculate from table below.

FACE VELOCITY INTERNAL STATIC PRESSURE (inch wg.)


(FPM)
2 ROW 3 ROW 4 ROW

200 0.42 0.44 0.47

300 0.67 0.73 0.78

400 0.88 0.95 1.05

450 1.02 1.13 1.23

500 1.16 1.29 1.49

NOTE:
Internal static pressure drop (ISP) include clean 1" filter, wet coil and unit casing.

36
Page 189 of 286
SOUND LEVEL DATA
MODEL: PY036-PY060
STATIC EFFECIENCY %

SOUND POWER FACTOR TABLE


VALUES GIVE THE SOUND POWER

Octave Band
Center Frequency – Hz 63 125 250 500 1000 2000 4000 8000

493-887 RPM –7.5 +0.5 +7.5 +10.5 +5.5 +2 –1 –6.5

887-1750 RPM –8 +0.5 +7 +7 +8 +1.5 –1.5 –6.5

1750-2500 RPM –8 +0.5 +7 +7 +5 +4.5 –1.5 –6.5

To obtain Sound Pressure Level at distance of 5 ft. (1.6 m) directly opposite to the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12watts).

37
Page 190 of 286
SOUND LEVEL DATA
MODEL: PY075-PY090
STATIC EFFECIENCY %

SOUND POWER FACTOR TABLE


VALUES GIVE THE SOUND POWER

Octave Band
Center Frequency – Hz 63 125 250 500 1000 2000 4000 8000
251-495 RPM –6 +2 +11.5 +8 +5.5 +2 –1 –6.5
495-990 RPM –6.5 +1.5 +8 +10.5 +5 +1.5 –1.5 –7
990-1953 RPM –7 +1.5 +8 +7 +8 +1.5 –2 –7.5
1953-2050 RPM –7 +1.5 +8 +7 +5 +4.5 –2 –7.5

To obtain Sound Pressure Level at distance of 5 ft. (1.6 m) directly opposite to the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12watts).

38
Page 191 of 286
SOUND LEVEL DATA
MODELS: PY120-PY150
STATIC EFFECIENCY %

SOUND POWER FACTOR TABLE


VALUES GIVE THE SOUND POWER

Octave Band
Center Frequency – Hz 63 125 250 500 1000 2000 4000 8000

211-417 RPM –4.5 +3 +12 +8 +5 +2 –1.5 –7

417-835 RPM –5.5 +2.5 +8.5 +10.5 +4.5 +1.5 –2 –7.5

835-1647 RPM –5.5 +2.5 +8 +7 +7 +1 –2.5 –7.5

To obtain Sound Pressure Level at distance of 5 ft. (1.6 m) directly opposite to the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12watts).

39
Page 192 of 286
SOUND LEVEL DATA
MODELS: PY180 - PY300
STATIC EFFECIENCY %

SOUND POWER FACTOR TABLE


VALUES GIVE THE SOUND POWER

Octave Band
Center Frequency – Hz 63 125 250 500 1000 2000 4000 8000

255-443 RPM –3.5 +4 +12.5 +8 +4.5 +1.5 –2 –7.5

443-887 RPM –4 +3.5 +9 +10 +4 +1 –2.5 –8

887-1750 RPM –4 +3.5 +8.5 +7 +7 +0.5 –3 –8

To obtain Sound Pressure Level at distance of 5 ft. (1.6 m) directly opposite to the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12watts).

40
Page 193 of 286
SOUND LEVEL DATA
MODELS: PY360-PY390
STATIC EFFECIENCY %

SOUND POWER FACTOR TABLE


VALUES GIVE THE SOUND POWER

Octave Band
Center Frequency – Hz 63 125 250 500 1000 2000 4000 8000

267-507 RPM –3 +4.5 +12.5 +7.5 +4.5 +1.5 –2 –7.5

507-1014 RPM –3.5 +3.5 +9 +10 +4 +0.5 –2.5 –8

1014-2000 RPM –4 +3.5 +8.5 +7 +6.5 +0.5 –3 –8

To obtain Sound Pressure Level at distance of 5 ft. (1.6 m) directly opposite to the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12watts).

41
Page 194 of 286
STATIC PRESSURE DROP (inch wg.)

MODELS: PY036-PY060
CFM
COMPONENT
900 1200 1400 1600 1800 2200
1 HEATER MODULE 0.12 0.12 0.12 0.13 0.14 0.15
2 HEATER MODULE 0.19 0.19 0.19 0.20 0.21 0.21

MODELS: PY075-PY090
CFM
COMPONENT
1600 1800 2000 2200 2400 2600 3000 3000 3400 3600 3800
1 HEATER MODULE 0.11 0.12 0.13 0.13 0.14 0.15 0.16 0.16 0.17 0.18 0.18
2 HEATER MODULE 0.18 0.19 0.19 0.19 0.20 0.20 0.21 0.21 0.22 0.23 0.23

MODELS: PY120-PY150
CFM
COMPONENT
2600 2800 3000 3400 3800 4000 4200 4800 5200 5800
1 HEATER MODULE 0.04 0.04 0.05 0.08 0.10 0.11 0.12 0.14 0.16 0.18
2 HEATER MODULE 0.06 0.06 0.07 0.10 0.12 0.14 0.15 0.18 0.20 0.22

MODELS: PY180-P210
CFM
COMPONENT
4800 5200 5300 6000 6200 6800 7000 7400 7600 7800 8200
1 HEATER MODULE 0.08 0.08 0.08 0.08 0.08 0.09 0.10 0.10 0.10 0.11 0.11
2 HEATER MODULE 0.14 0.14 0.14 0.14 0.14 0.16 0.16 0.16 0.16 0.17 0.17

MODELS: PY240-390
CFM
COMPONENT
6000 6600 7200 7800 8400 9000 9600 10200 10800 11400 12000
1 HEATER MODULE 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15
2 HEATER MODULE 0.14 0.14 0.16 0.17 0.18 0.19 0.20 0.21 0.12 0.23 0.24

BLOWER MOTOR EFFICIENCY

MOTOR HP 0.5 .75 1 1.5 2 3 5 7.5 10 15

EFFECIENCY (%) 0.87 0.87 0.87 0.87 0.87 0.89 0.88 0.91 0.90 0.91

42
Page 195 of 286
UNIT DIMENSIONS
PY036-060

COMPRESSOR / CONTROLS ACCESS PANEL


ACCESS PANEL 175
FOR BLOWER & MOTOR
[6.88]

CONTROL COMPARTMENT
CONDENSER COIL

CONDENSATE DRAIN OUTLET


3/4" NPT

AIR IN

AIR IN SUPPLY AIR RETURN AIR


TOP VIEW DUCT COLLAR
248
AIR OUT [9.76]
375 125 24
[14.76] [4.92] [0.94]

RETURN AIR FILTER


SUPPLY AIR
ACCESS PANEL
[24.8]

[27.95]
COND. COIL COND. COIL
946 [37.26]

630

OPENING OPENING

710
POWER SUPPLY CONN
DIA 2.0" HOLE
DRAIN OUTLET
[5.98]
152

[6.73]

[5.21]
171

132
872 250 1188
[34.33] [9.84] [46.77]
925 1688
[36.42] [66.45]
12.7 ( 0.5) MOUNTING HOLES
4 NOS.
SIDE VIEW FRONT VIEW SIDE VIEW
NOTE : ALL DIMS ARE IN mm (DIMS IN BRACKETS ARE INCHES)

43
Page 196 of 286
UNIT DIMENSIONS
PY075

COMPRESSOR / CONTROLS ACCESS PANEL


ACCESS PANEL FOR BLOWER & MOTOR M

CONTROL COMPARTMENT

CONDENSATE DRAIN OUTLET


3/4" NPT

AIR IN

AIR IN SUPPLY AIR RETURN AIR

TOP VIEW DUCT COLLAR


AIR OUT
K J H N

FILTER
SUPPLY AIR RETURN AIR
COND. COIL ACCESS

G
F

COND. COIL OPENING OPENING


PANEL
C

POWER SUPPLY CONN


DRAIN OUTLET
E

[5.21]
O

132
D
L P Ø 12.7 ( 0.5) MOUNTING HOLES
B (2 EACH SIDE)
A

SIDE VIEW FRONT VIEW SIDE VIEW

MODEL A B C D E F G H J K L M N O P
PY 075 2080 (81.89) 1162 (45.75) 1034 (40.71) 1114 (43.86) 308 (12.15) 550 (21.64) 810 (31.92) 300 (11.81) 251 (9.87) 396 (15.59) 152 (5.98) 175 (6.88) 24 (0.94) 171 (6.73) 1775 (69.88)

NOTE : ALL DIMS ARE IN mm (DIMS IN BRACKETS ARE INCHES)

44
Page 197 of 286
UNIT DIMENSIONS
PY090

MODEL A B C D E F G H J K L M N O P Q ØR
PY 090 2080 (81.890) 1158 (45.59) 1124 (44.25) 1120 (44.1) 254 (10.0) 656 (25.83) 848 (33.4) 273 (10.74) 210 (8.27) 501 (19.72) 152 (6.00) 178 (7.00) 49 (1.90) 108 (4.26) 888 (34.95) 965 (38.00) 51 (2.00)

NOTE : ALL DIMS ARE IN mm (DIMS IN BRACKETS ARE INCHES)

45
Page 198 of 286
UNIT DIMENSIONS
PY120

ACCESS PANEL FOR


COMPRESSOR ACCESS PANEL CONTROLS , BLOWER & MOTOR
M

CONTROL
COMPARTMENT

CONDENSATE DRAIN OUTLET


3/4" NPT

AIR IN

AIR IN
SUPPLY AIR RETURN AIR

DUCT COLLAR
TOP VIEW
AIR OUT AIR OUT

K J H N

FILTER
SUPPLY AIR RETURN AIR
ACCESS
G

COND. COIL COND. COIL OPENING


F

OPENING
PANEL
C

C
POWER SUPPLY CONN
DIA 2.0" HOLE DRAIN OUTLET
E

[5.21]
O

132
D
L P
B
A

SIDE VIEW FRONT VIEW Ø 12.7 ( 0.5) MOUNTING HOLES


(2 EACH SIDE) SIDE VIEW

MODEL A B C D E F G H J K L M N O P

PY 120 2259 (88.94) 1458 (57.42) 1250 (49.2) 1422 (55.98) 255 (10.03) 707 (27.84) 930 (36.61) 367 (14.46) 190 (7.48) 476 (18.74) 176 (6.93) 145 (5.709) 48 (1.89) 200 (7.87) 1907 (75.08)

NOTE : ALL DIMS ARE IN mm (DIMS IN BRACKETS ARE INCHES)

46
Page 199 of 286
UNIT DIMENSIONS
PY150-300

S
M

K U H N

P
R

136 [5.37]
F

D
D G L L G ØX
B
B A

MODEL A B C D G L N H K P R S M U E F ØX
PY150 2794 (110.00) 1727 (68.00) 1266 (49.83) 1660 (65.35) 197 (7.75) 1200 (47.25) 83 (3.27) 817 (32.17) 720 (28.35) 912 (35.9) 912 (35.9) 665 (26.18) 194 (7.64) 171 (6.73) 215 (8.46) 221 (8.70) 44 (1.75)

PY180-300 3048 (120.00) 2145 (84.44) 1446 (56.94) 2077 (81.75) 324 (12.76) 1200 (47.25) 125 (4.92) 780 (30.71) 614 (24.17) 1105 (43.51) 1053 (41.47) 665 (26.18) 288 (11.34) 226 (8.91) 221 (8.69) 247 (9.73) 44 (1.75)

NOTE : ALL DIMS ARE IN mm (DIMS IN BRACKETS ARE INCHES)

47
Page 200 of 286
UNIT DIMENSIONS
PY360-390

MODEL A B C D E F G H J K L M N O P Q ØR
PY 360 - 390 3683 (145.00) 2184 (86.00) 1451 (57.12) 2113 (83.20) 41 (1.63) 1125 (44.29) 220 (8.68) 1118 (44.00) 252 (9.92) 1055 (41.53) 126 (4.97) 868 (34.16) 319 (12.55) 676 (26.61) 258 (10.17) 680 (26.77) 51 (2.00)

NOTE : ALL DIMS ARE IN mm (DIMS IN BRACKETS ARE INCHES)

48
Page 201 of 286
CONTROLS & SEQUENCE OF OPERATION

Scroll compressors are designed to operate in single direction only. Hence, care has to be taken to ensure correct rotation when the
system is operated. Verification of correct rotation is by observing that the suction pressure drops and discharge pressure rises when
compressor run. Reverse rotation results in abnormal sound, as well as, substantially low current draw and by interchanging power
supply wire L1 & L3 will correct this problem.
The operation of the air conditioning unit is controlled by a 24VAC electronic control board.

GENERAL
The thermostat normally displays room temperature and mode of operation. The five buttons on the front of the unit allow
complete control of the thermostat. The thermostat also allows to select continuous fan operation (useful when using an
air cleaner) or have the fan come on with the compressor.

SWITCH FUNCTION
- On/Off Key : Switch the system On or Off.
- Up Key : To increases the set temperature.
- Down Key : To decreases the set temperature.
- Mode Key : Changes the mode to Fan, Cool, Heat or Auto.
- Fan Key : Changes the Fan Operation to Auto or Continuous.

USER CONTROLS
Mode:
Select the desired mode of operation by pressing of the mode button:

Fan: In this mode of operation, the compressor will be in inactive state. Display shows room temperature. Fan will be running.

Cool: In this mode of operation, the compressor will be ON after a delay depending on the differential of room temperature & Set
temperature.

Heat: In this mode of operation, Fan is ON.

Auto: In auto mode, thermostat provide automatic changeover from heating to cooling mode & vice versa. Thermostat automati-
cally switches to maintain the desired temperature.

HOOK-UP WIRING DIAGRAM


(THERMOSTAT CONTROLLER TO PACKAGED UNIT)
THERMOSTAT

NOTE: OPTIONAL CONNECTION:


Y2
IF REMOTE TEMPERATURE SENSING W1
FUNCTION IS REQUIRED.
Y1
SENSOR
PACU CONTROL PANEL REMOTE G
SENSOR -
24V(R)
24V(C)
W2

LVTB
R
24V ac
C
SUPPLY FAN CONTROL
G
STG1 COOLING
Y1
STG2 COOLING
Y2
W1
STG1 HEATER
W2 STG2 HEATER

LEGEND:
ATB AUXILIARY TERMINAL BLOCK
LVTB LOW VOLTAGE TERMINAL BLOCK

49
Page 202 of 286
TYPICAL SCHEMATIC WIRING DIAGRAM

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

50
Page 203 of 286
TYPICAL SCHEMATIC WIRING DIAGRAM

51
Page 204 of 286
Zamil Central Air Conditioners
P.O. Box 41015, Dammam 31521, Kingdom of Saudi Arabia
Tel.: +966 13 812 5400 Fax: +966 13 812 1977
Customer Service: 800 3041 000

@zamilac zamilac.com

Page 205 of 286


PL-AP-PY-60Hz-20-2M-E 21Z1
Vertical Package Units
PV (R-410A) Series
PV036 thru PV 060
3 TR thru 5 TR
10kW thru 17kW

Page 206 of 286


Certificate No.: IND.14.7268 U/Q
Company Business
Zamil Air Conditioners (ZAC), a sector business of Zamil Industrial, is the largest supplier of air conditioners in the Middle East. It manufactures and markets
a whole range of air conditioners from room air conditioners to packaged units to large capacity chillers for residential, commercial and industrial applica-
tions. Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabia and today is a leading
international manufacturer of air conditioning systems & service solutions and is Number One in the Middle East. ZAC’s operations are structured into four
companies supporting seven in-house brands and twelve products and service units as well as a number of international brands under the OEM Sales. The
seven in-house brands are Zamil Air Conditioners, Classic, Zamil, Cooline, CoolCare, Climatech and Geoclima.

The four companies are:


1. Zamil Air Conditioners & Home Appliances Co. (L.L.C.), supporting Zamil, Classic, Cooline, GE and OEM brands for consumers.
2. Zamil Central Air Conditioners Co. (L.L.C.), supporting Zamil Air Conditioners, Cooline and Climatech for commercial and industrial customers.
3. Zamil Air Conditioning and Refrigeration Services Co. (L.L.C.), providing electromechanical engineering, construction and project management services,
HVAC Operation & Maintenance, Retrofit Services, Spare Parts, Fire Protection, Controls, Electrical Services, Coils, Ducting and Coating.
4. Geoclima srl is an independent business supporting other three companies for their requirements of Chillers and Double Skin AHU’s.

The first three Companies- direct their business operations from the First and Second Industrial Cities in Dammam, Saudi Arabia and have a product design
center in Austria.
GEOCLIMA has its engineering and production departments located at Monfalcone, Italy. All the four companies, while operating independently, supple-
ment each other’s activities in a way that makes synergy work at its best and achieves ZAC’s goals of maximizing customer value and satisfaction.

OEM Sales - Private Labeling


Zamil Air Conditioners produces branded air conditioners under OEM agreements for several leading international brands. Such relationships are testimony
to the excellence of ZAC’s engineering and production processes. Most of the units produced under the private labeling agreements are for window and
mini-split systems. However, ZAC is expanding its OEM offerings to include residential and light commercial units. Some of the OEM brands manufactured
at Zamil Air Conditioners are: Supra, Sanyo and Blue Star.

Joint Venture
Middle East Air Conditioners - Joint Venture with General Electric.
Zamil Air Conditioners partners with GE Appliances - Europe since 1997, in a joint venture called Middle East Air Conditioners (MEAC), for manufacturing
and marketing of GE branded air conditioners. MEAC was awarded the license to manufacture Window, Mini Splits and Ducted Split types under the brand
names GE, Hotpoint and RCA. Today, MEAC enjoys extensive coverage in Saudi Arabia, GCC and the African market. In an ever-changing market, MEAC
continually strives to acquire new technologies and stylish integrated design with optimum performance and reliability that bring greater value to customers.

Factories and Production


Zamil Air Conditioners has two prime manufacturing plants in Dammam, Saudi Arabia and a production facility in Italy operated by GEOCLIMA and a prod-
uct design center in Austria. ZAC can produce up to 900,000 room air conditioners, 300,000 mini-split systems and 65,000 central airconditioning systems
per annum and supplies air conditioning products to over 55 countries across the world - the major markets being GCC, Middle East, North Africa, Europe
and Asia.

Quality & Product Certificates


The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.
ZAC’s products are certified with:
1. CE (Council of European Community).
2. UL (Underwriters Laboratory).
3. Eurovent (Certified Performance).
4. ISO 9001-2008 (International Organization for Standardization).
5. AHRI (Air-Conditioning, Heating and Refrigeration Institute).
Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed bin Fahd Al Saud
Award for Factory Safety.

Our Products & Service Units


In addition to consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners manufactures a host of residential,
commercial and industrial air conditioners. This broad product range extends from the concealed units up to 5 TR, the ducted splits up to 30 TR, the pack-
aged units up to 100 TR, the single and double skin air handling units up to 138,316 CFM, the water chillers up to 590 TR and the centrifugal chillers up to
5,000 TR cooling capacity.

Our products and services include, in addition to Maintenance, Retrofit & Operations (MRO), complete integrate suite of solutions like:
• Zamil Projects: Providing EPC for electromechanical works for Industrial, Utility and Oil & Gas customers.
• Zamil Controls: Design, assembly, integration and commissioning of low current & low voltage systems.
• Zamil Fire Protection: Design, integration and commissioning of active fire protection systems.
• Zamil Electrical: Design, integration and commissioning of lv/mv (low voltage/middle voltage) systems.
• Coil & Coating: Coil replacement, anti-corrosion coating, water proofing & reflective coating and passive fire protection solutions.
• Zamil Ducting: Facilities designs and manufactures high quality duct systems and other HVAC industry related products, utilizing state of the
art automated duct lines, Plasma Cutting, CNC Turret punch press and other specific machinery through two duct factories located in Saudi
Arabia western province (Yanbu) and Eastern province (Dammam).

Page 207 of 286


INDEX
Contents Page

Model decoding .......................................................................................................................................................... 2

Unit Features ............................................................................................................................................................3-5

Physical Data ...............................................................................................................................................................6

Cooling Capacities / Electrical Data .............................................................................................................................7

Dimensions ..................................................................................................................................................................8

Access Details .............................................................................................................................................................9

Typical schematic wiring diagram..........................................................................................................................10-11

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

1
Page 208 of 286
MODEL DECODING
1&2 3, 4 & 5 6 7 8 9 10 11 12
BASIC NOMINAL COOLING ELECTRICAL SUPPLY BLOWER MOTOR DRIVE OPTIONS HEATER EVAPORATOR COIL CONDENSER COIL PDS/SG OPTION
CAPACITY (MBH) (V-Ph-Hz) (kW-STAGE)
PV 036 C : 208/230-1-60 U : 0.5 HP ECM N : DIRECT DRIVE N : NO HEATER J : ALUMINUM FIN J : ALUMINUM FIN N : NO PDS/SG

VERTICAL 048 H : 208/230-3-60 A : 5/1 K : COATED ALUMINUM FIN K : COATED ALUMINUM FIN P : PDS
060
PACKAGED M : 380-3-60 (4 WIRE) C : 7.5 L : COPPER FIN L : COPPER FIN S : SIGHT GLASS
UNIT M : ALUMINUM FINS WITH RTC
D : 10/2* M : ALUMINUM FINS WITH RTC G:P&S
N : COPPER FINS WITH RTC
N : COPPER FINS WITH RTC

13 15 16 17 18 19
ELECTRICAL OPTIONS ACCESSORIES FILTER OPTIONS APPLICATIONS ACCESS REFRIGERANT

N : STANDARD UNIT N : STANDARD UNIT N : NO FILTER N : STANDART APPLICATION R : RH B : R-410A

B : CONDENSER MOTOR O.L.R. C : FRESH AIR HOOD & MANUAL DAMPER A : 2" ALUMINUM FILTER C : COMMUNICATION L : LH
SHELTER APPLICATION
C : COMPRESSOR MOTOR O.L.R. S : SS DRAIN PAN (SS316L) B : 2" PLEATED FILTER

D : COMPRESSOR C.B. E :C&S

H :B&C

I :B&D

J :C&D

2
O:B&C&D

Page 209 of 286


UNIT FEATURES
A. GENERAL
The wall mounted vertical packaged units from “Zamil Air Conditioners” are designed for optimum cooling, convenience
and dependability, which make them suitable for most demanding applications such as telecom industry, beside general
airconditioning applications. These self contained units have the sheet metal panels designed to provide service access
for compressors and electrical controls even when two units are mounted side by side with minimal space in between.
Filters and controls are accessible from the back of the unit.

B. UNIT ENCLOSURE
Panels are of heavy gauge, G-90 galvanized steel sheet with removable access panels, completely weatherized for
outdoor installation and properly reinforced & brazed. Panels and access doors will provide easy inspection and access
to all internal parts. Enclosures are provided with adequately reinforced points of support for wall mounting application.
Steel sheet panels are zinc-coated and galvanized by the hot dip process of lockforming quality conforming to ASTM A
653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat and capable of withstanding
1500 hours in salt spray test.

C. COMPRESSOR
Hermetic scroll compressors are used as standard for all models. They are provided with all the standard controls
necessary for proper and safe operation. These compressors are with improved internal pressure relief valve which
provides high pressure protection to the refrigerant system and rubber grommet for quiet and efficient operation.

D. AIR COOLED CONDENSING SECTION


1. The air-cooled condensing section is enclosed within the unit housing and consists of condenser coil, fan, electric
motor and inherently protected compressor. All condenser coils are of the corrugated fin-and-tube type constructed of
seamless copper tubes and mechanically bonded to aluminum fins. As an option, corrugated copper fins or coated
aluminum fins may be provided. Tube support sheets avre galvanized steel, formed to provide structural strength.
2. Fans are propeller type, direct drive, with side air discharge through the condenser coil.
3. Motors are totally enclosed air-over type. Inherent thermal protection is automatic reset type.

E. EVAPORATOR COIL SECTION


1. All cooling coils are of the corrugated fin-and-tube type constructed of seamless copper tubes and mechanically
bonded to aluminum fins. As an option, corrugated copper fins or coated aluminum fins may be provided.
Tube support sheets are galvanized steel, formed to provide structural strength. The refrigerant metering device is a
thermostatic expansion valve. A coated galvanized steel condensate drain pan is provided.
2. Insulation: Insulation is supplied in adequate thickness (1/2") and density to prevent condensation from forming on
the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and erosion
from air panels.

F. EVAPORATOR BLOWER ASSEMBLY


The direct drive evaporator blowers are of the centrifugal forward curved design. The twin blower wheels are constructed
of steel, and they are statically and dynamically balanced for quiet and smooth performance.

G. MOTORS
Motors are ECM type with an ultra high efficiency programmable brush-less DC Motors.

H. FILTERS
Two inch Pleated high efficiency filters are provided as standard.

3
Page 210 of 286
I. ELECTRICAL CONTROLS
1. FOR NORMAL AIR CONDITIONING APPLICATIONS
These Packaged units are provided with a microprocessor control board incorporating the following features:
• PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoid’s opening and compressor starting to equalize the pressure in the system necessary for compressor to
startup. (Selectable through dip switch setting on control board).
• COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for
compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermostat
due to load demand.
• COMPRESSOR LOCK-OUT FUNCTION: If any of the unit’s safety control trips due to abnormal conditions, the
electronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a
qualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system conditions.
• FAULT DIAGNOSTICS: In case of system fault, LED’s on the board emits a flashing signal indicating where the fault
is. This is to guide the service technician in identifying the fault.
• DIGITAL I/O’s: The unit’s control board is compatible to operate with a DDC controller or any standard 24V a.c.
thermostat commercially available.
• SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequential
order: supply fan – condenser fan – compressor; at a pre-determined timings.

2. FOR COMMUNICATION SHELTER APPLICATIONS (OPTIONAL CONTROL PANEL, To be ordered separately)


• This controller is designed to operate two air conditioning units paired together (Duty & Standby). The duration for this
is one week (default).
• This AC unit should start & stop based on two parameters:
a) Scheduled time.
b) Room temperature.
• In case of AC fault unit, the controller will do the following:
a) Detect the fault by the L/H pressure switches provided by the AC unit itself.
b) Automatically switch to the standby unit.
c) Send a signal to the alarm box BATB.
d) Alarms as indicating lamp on the front door of the HVAC panel.
• The HVAC panel is provided by lamp test & Selector switch (mode selection AUTO - OFF - MANUAL) and by manual
selection it is possible to make maintenance without loosing the cooling inside the shelter.
• All alarms (AC1 trip, AC2 trip, high temperature and common alarm):
The AC1 and AC2 trip is indicated by the panel lamps and the high temperature alarm and common alarm can be
connected to remote indication.
• In case of high temperature, the controller will turn on the standby until the temperature reaches the normal set point.
• HVAC door provide the following signals as lamp indication:
a) Power availability
b) AC1 - Run
c) AC2 - Run
d) AC1 - Trip
e) AC2 - Trip

Note: The controller is available in microcontroller as standard (PLC as optional)

4
Page 211 of 286
J. ELECTRONIC THREMOSTAT (Optional, for normal air conditioning applications)
General information: Electronic thermostat shall control one or two stage heating and cooling applications. The thermostat
normally displays room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also allows you to
select continuous fan operation, or have the fan on intermittent operation with the equipment.
The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall),
and should not be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply
air registers/diffusers.
• Single/dual stage - Cooling & heating.
• Low voltage control - 24 VAC (nominal).
• Room temperature display - in 0C or 0F.
• Mode of operation - FAN/COOL/HEAT/AUTO.
• Fan mode - ON: Continuous fan operation; AUTO: Fan operates ON/OFF with compressor.
• Heating & cooling setpoint is permissible.
• Temperature set button - Up for increasing & down for decreasing temperature.
• Built-in compressor fault & clogged filter indication led lights.
• Remote sensing function as an option. Duct sensor is provided with the thermostat.

TYPICAL THERMOSTAT
Heating Cooling Selector Switch Positions
Stages Stages Mode Switch Fan Switch
1&2 1 OFF-HEAT/COOL ON-AUTO

5
Page 212 of 286
PHYSICAL DATA
MODEL NUMBER PV036 PV048 PV060

NOMINAL CAPACITY (TONS) 3 4 5

COOLING CAPACITIES (@ 80.6°F Total capacity (BTUH) 35070 49810 58960


DB/66.2°F WB indoor, 95°F Outdoor) Sensible capacity (BTUH) 29510 37910 46250
COOLING CAPACITIES (@ 84.2°F Total capacity (BTUH) 31870 45470 53540
DB/66.2°F WB indoor, 114.8°F
Outdoor) Sensible capacity (BTUH) 31870 40790 50050

Type Scroll

Quantity 1 1 1

COMPRESSOR Oil (oz) 42 46 46

Refrigerant R-410a

Operating Charge (oz) 195 195 340

Type Propeller

Quantity - Diameter (inch) 1 - 24' 1 - 24 1 - 26'


CONDENSER FAN
Nominal CFM 2500 3000 5000

Motor HP - RPM 1/3 - 1075 1/3 - 1075 3/4 - 1075

Type Corrugated Fin and Tube

CONDENSER COIL Tube dia. - Rows - Fins per inch 3/8-4-14 3/8-4-14 3/8-4-14

Total face area (Sq. ft.) 8.0 8 12.8

Type Centrifugal

Size (inch) 8 x 8.5 (2 Nos.) 8 x 8.5 (2 Nos.) 8 x 8.5 (2 Nos.)

EVAPORATOR BLOWER Drive type Direct drive

Nominal airflow, CFM 1200 1400 1800

Motor HP 1/2 1/2 1/2

Type Corrugated Fin and Tube

EVAPORATOR COIL Tube dia. - Rows - Fins per inch 3/8-4-14 3/8-4-14 3/8-4-14

Total face area (Sq. ft.) 5.0 5.0 6.5

Quantity 1 1 1
RETURN AIR FILTERS
Size (inch) 36 x 22 x 2 36 x 22 x 2 46 x 22 x 2

WEIGHT Kgs. 255 265 290

6
Page 213 of 286
COOLING CAPACITIES
MODEL No. PV036, PV048 & PV060
PV036 PV048 PV060
CONDENSER 1200 1400 1800
ENTERING AIR
TEMP. (°F) EVAPORATOR ENTERING AIR, DBE/WBE
80/62 80/67 80/72 80/62 80/67 80/72 80/62 80/67 80/72
TC 34.15 36.97 39.87 48.20 52.46 56.66 56.84 62.03 67.20
85 SC 34.15 28.08 21.57 44.29 36.85 29.45 54.25 44.69 35.28
kW 2.16 2.19 2.22 3.25 3.31 3.38 3.46 3.48 3.48
TC 32.85 35.35 38.10 46.30 50.41 54.46 54.53 59.63 64.53
95 SC 32.85 27.32 20.79 43.37 35.89 28.51 53.10 43.56 34.12
kW 2.44 2.47 2.50 3.62 3.68 3.75 3.90 3.91 3.91
TC 31.51 33.63 36.17 44.26 48.20 52.10 52.12 56.89 61.61
105 SC 31.51 26.52 19.93 42.37 34.87 27.49 51.90 42.26 32.84
kW 2.75 2.77 2.80 4.03 4.10 4.16 4.39 4.40 4.40
TC 30.01 31.81 34.17 42.08 45.85 49.53 49.68 53.93 58.24
115 SC 30.01 25.68 19.02 41.30 33.79 26.39 49.68 40.89 31.34
kW 3.11 3.12 3.15 4.49 4.56 4.62 4.92 4.93 4.93
TC 28.44 29.84 32.07 39.93 43.43 46.96 46.81 50.37 54.44
125 SC 28.44 24.72 18.04 39.93 32.66 25.29 46.81 39.18 29.66
kW 3.51 3.52 3.54 4.99 5.05 5.10 5.49 5.51 5.52
TC - Total Capacity (1000 Btuh) Gross kW – Compressor Power input DBE – Dry Bulb Temp. (°F) of Air Entering Coil DBL – Dry Bulb Temp. (°F) of Air Leaving Coil
SC – Sensible Heat Capacity (1000 Btuh) Gross DR – Wet Bulb depression ratio WBE – Wet Bulb Temp. (°F) of Air Entering Coil WBL – Wet Bulb Temp. (°F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible – Do not extrapolate.


2. Capacities above are based on DBE = 80°F. For higher or lower DBE, add following correction factor to sensible capacity = 1.08 x CFM (1 – DR) (DBE – 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

ELECTRICAL DATA
MODEL No. PV036
VOLTAGE COMPRES- * * LEGEND:
POWER
RANGE SOR FAN BLOWER
SUPPLY MCA MOCP FLA - Full Load Amps
MOTOR MOTOR
(V-Ph-Hz)
MIN MAX RLA LRA FLA FLA
RLA - Rated Load Amps
230-1-60 208 230 15.7 77 2.2 3.5 25.3 40
LRA - Locked Rotor Amps

MOCP - Maximum Over Current Protection


MODEL No. PV048
MCA - Minimum Circuit Amps
VOLTAGE COMPRES- * *
POWER * Single phase motors
RANGE SOR FAN BLOWER
SUPPLY MCA MOCP
MOTOR MOTOR
(V-Ph-Hz)
MIN MAX RLA LRA FLA FLA NOTE: The equipment is guaranteed to operate within the voltage
range mentioned in the electrical data, while further voltage tolerances
230-3-60 187 253 16.1 98 2.2 3.5 25.8 40 can be supported with special orders

380/400-3-60
342 418 9.9 64 2.2 3.5 18.1 25
(4 WIRE)

MODEL No. PV060


VOLTAGE COMPRES- * *
POWER
RANGE SOR FAN BLOWER
SUPPLY MCA MOCP
MOTOR MOTOR
(V-Ph-Hz)
MIN MAX RLA LRA FLA FLA

230-3-60 180 253 17.7 110 2.6 3.5 28.2 45

380/400-3-60
342 418 8.9 66 1.6 3.5 16.2 25
(4 WIRE)

7
Page 214 of 286
DIMENSIONS
PV036 - PV060

DIMENSIONS
MODEL
NUMBER
A B C D E F G H I

PV036 2134 (84.0) 1143 (45.0) 1067 (42.0) 662 (26.1) 762 (30.0) 767 (30.2) 251 (9.9) 759 (29.9) 403 (15.9)

PV048 2134 (84.0) 1143 (45.0) 1067 (42.0) 662 (26.1) 762 (30.0) 767 (30.2) 251 (9.9) 759 (29.9) 403 (15.9)

PV060 2337 (92.0) 1397 (55.0) 1321 (52.0) 864 (34.0) 762 (30.0) 1021 (40.2) 251 (9.9) 1021 (40.2) 403 (15.9)

NOTES:
1. All dimensions are in millimeters, (dimensions in brackets are in inches).

8
Page 215 of 286
ACCESS DETAILS
PV036 - PV060

9
Page 216 of 286
TYPICAL SCHEMATIC WIRING DIAGRAM
For normal air conditioning application
LEGEND
BM BLOWER MOTOR
CAP CAPACITOR
CC COMPRESSOR CONTACTOR
CB CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP/C COMPRESSOR
FM FAN MOTOR (CONDENSER)
FCS FAN CYCLING SWITCH
HPS HIGH PRESSURE SWITCH
HVTB HIGH VOLTAGE TERMINAL BLOCK
L1 LINE 1
L2 LINE 2
L3 LINE 3
LPS LOW PRESSURE SWITCH
LUG LUG GROUND
LVTB LOW VOLTAGE TERMINAL BLOCK
NTB NEUTRAL TERMINAL BLOCK
ECB ELECTRONIC CIRCUIT BOARD
TRANS TRANSFORMER
__ __ __
FIELD INSTALLED
DISCONNECT - TAB
SPLICE - CLOSED END
TERMINAL BLOCK OR TERMINATION POINT
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
2. ANY WIRE REPLACEMENT SHOULD BE OF THE 90°C OR
ITS EQUIVALENT.
TO NTB TO HVTB
N L1 USE COPPER CONDUCTOR WIRES ONLY.
3. IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE
DIP SWITCH

ATB 230VAC (SD) (UVM) ATB


READ BROKEN LINES AS CONTINUOUS LINES.
1B JP2 1A JP1 1
4. POWER MUST BE SUPPLIED TO CRANKCASE HEATER
24A FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START
UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
HEATER MUST BE ON FOR 12 HOURS BEFORE OPERAT-
HPS 23A ING THE SYSTEM.
LPS 22A FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE-
SULT IN COMPRESSOR DAMAGE.

5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER


TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY ZAMIL.
6. COMPRESSOR IS PROVIDED WITH INTERNAL OVERLOAD.
7. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,
TURN OFF POWER FIRST & SET REQUIRED SETTING.
8. ALWAYS REFER MOTOR NAMEPLATE FOR THE
CONNECTIONS & WIRE COLOR.
9. THESE WIRES TO BE CONNECTED TO NEUTRAL LINE ON
380/400V-3Ph-60Hz POWER SUPPLY ONLY.
FUSE
10. NEUTRAL LINE REQUIRED ON 380/400V-3Ph-60Hz POWER
SUPPLY ONLY.

10
Page 217 of 286
TYPICAL SCHEMATIC WIRING DIAGRAM
Standard units (Quadruple Compressor)
LEGEND
BM BLOWER MOTOR
CAP CAPACITOR
CC COMPRESSOR CONTACTOR
CB CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP/C COMPRESSOR
FM FAN MOTOR (CONDENSER)
FCS FAN CYCLING SWITCH
HPS HIGH PRESSURE SWITCH
HVTB HIGH VOLTAGE TERMINAL BLOCK
L1 LINE 1
L2 LINE 2
L3 LINE 3
LPS LOW PRESSURE SWITCH
LUG LUG GROUND
LVTB LOW VOLTAGE TERMINAL BLOCK
NTB NEUTRAL TERMINAL BLOCK
ECB ELECTRONIC CIRCUIT BOARD
TRANS TRANSFORMER
__ __ __
FIELD INSTALLED
CONTROLLER DISCONNECT - TAB
TERMINALS ATB LHS UNIT SPLICE - CLOSED END
TERMINAL BLOCK OR TERMINATION POINT
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
2. ANY WIRE REPLACEMENT SHOULD BE OF THE 90°C OR
ITS EQUIVALENT.
USE COPPER CONDUCTOR WIRES ONLY.
3. IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.
4. POWER MUST BE SUPPLIED TO CRANKCASE HEATER
FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START
UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
HEATER MUST BE ON FOR 12 HOURS BEFORE OPERAT-
ING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE-
SULT IN COMPRESSOR DAMAGE.
CONTROLLER 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
TERMINALS ATB RHS UNIT TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY ZAMIL.
6. COMPRESSOR IS PROVIDED WITH INTERNAL OVERLOAD.
7. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,
TURN OFF POWER FIRST & SET REQUIRED SETTING.
8. ALWAYS REFER MOTOR NAMEPLATE FOR THE
CONNECTIONS & WIRE COLOR.
9. THESE WIRES TO BE CONNECTED TO NEUTRAL LINE ON
380/400V-3Ph-60Hz POWER SUPPLY ONLY.
10. NEUTRAL LINE REQUIRED ON 380/400V-3Ph-60Hz POWER
SUPPLY ONLY.

11
Page 218 of 286
Page 219 of 286
Page 220 of 286
Page 221 of 286
Page 222 of 286
Air Cooled Remote Condenser
ZRX series, 60HZ
ZRX010 thru ZRX074
10kW to 74kW

Page 223 of 286


Company Profile
Zamil Air Conditioners, a sector business of Zamil Industrial, is the largest manufacturer of air conditioners in the Middle East.
The company manufactures and markets the complete range of air conditioners, from room air conditioners to packaged units
to large chillers for residential, commercial and industrial applications.

Founded in 1974, Zamil Air Conditioners was one of the first air conditioning companies to be established in Saudi Arabia. Today,
the company produces about one million air conditioners per year. Aside from its head office and two manufacturing plants in
Dammam, Saudi Arabia, the company also has production facilities in India. The company supplies air conditioning products to
over 55 countries across the world, with its major markets located in the GCC, Middle East, North Africa, Europe and Asia.

Zamil Air Conditioners is the first Middle Eastern company to achieve the prestigious AHRI certification (Air-Conditioning, Heating
and Refrigeration Institute, USA). The company is also 9001:2015 Quality Management System, ISO14001:2015 (Environment
Management) and OHSAS 18001:2007 (Occupational Safety) certified with many of its products tested and approved by
Eurovent, AHRI, SASO, ESMA & UL.

Companies:
• Zamil Air Conditioners & Home Appliances Co. (L.L.C),
• Zamil Central Air Conditioners Co. (L.L.C),
• Zamil Air Conditioning and Refrigeration Services Co. (L.L.C)

Manufacturing Facilities:
The company has two factories in Saudi Arabia located in the 1st and 2nd Industrial Cities of Dammam. The company also has
production facilities in India.

Annual Production Capacity:


• Window Air Conditioners: 700,000
• Mini-Split Systems: 300,000
• Central Air Conditioners: 50,000

Core Values

VISION:
To be the partner-of-choice COMMUNITY &
for environmental control HONESTY &
PROSPERITY
INTEGRITY
solutions that are based We believe in mutual prosperity.
We believe goodwill and good
on lifetime value reputation are core to our business.
We aspire to thrive in business
while bringing progress and
We uphold honesty, integrity, prosperity to our own people and
professionalism and a high level of communities where we operate.
business ethics. We observe prudence Our culture, our ideas, our
and fairness in dealing with our practices, our environmental
MISSION: stakeholders. concern, and our teamwork lead
us to create superior values for
To make air-conditioning people and communities
Affordable, Reliable and around us.

Energy-Efficient
VALUES
LEADERSHIP &
CUSTOMER & PRUDENCE
EXCELLENCE We cultivate talent and leadership
to create sound business
We are diligent about understanding solutions, to best meet our
and fulfilling our customers’ needs. customer needs, and to develop
We strive to please our customers with markets, people and shareholder
excellence in quality and services. We value. We do so by optimizing use
listen to our customers and “go the of funds, resources, materials, and
extra mile” to satisfy them. INNOVATION & technologies. We build prudence
CHANGE and cost-effectiveness in our
leadership culture passing on
We are passionate about
benefits to our customers.
meaningful innovation. We are a
learning organization. We learn
from our experiences and global
best practices, and we innovate to
create leading local solutions
leveraging on world class
knowledge. We embrace positive
change brought forth by innovation
and aspirations to grow our
business.

Page 224 of 286


Research & Development
Zamil Air Conditioners boasts of its state-of-the-art testing facilities – “Ikhtebar” which is a third party air conditioner testing
facility built by Intertek Testing Services (ITS) and certified by Electrical Testing Laboratories (ETL). Equipped to perform a wide
range of tests under many recognized local and international standards including: AHRI 210/240; AHRI 410; AHRI 310/380; AHRI
430; AHRI 440; AHRI 340/360; ASHRAE 116; ASHRAE 37;ASHRAE 41.1; AHRI 365; ISO 5151; SASO 385; SASO 2682; UL 1995
and AHRI 550/590.

Features:
• Performance test of whole range of air conditioners – consumer as well as commercial, in capacities from ½ TR to 600 TR
• Support research and development initiatives through implementation of state of the art computational programs.
• Test products for conformance to local and international certifications and standards such as SASO, AHRI, UL, AHAM etc.

Facility:
• Calorimetric Test Rooms
• Psychrometric Test Rooms
• Chiller Test Facility
• Sound Lab
• Reliability Test Facility

Parent Company
Headquartered in Dammam, Saudi Arabia, Zamil Industrial Investment Company ('Zamil Industrial') is a premier business group
engaged in the design, engineering and manufacturing of innovative products and solutions for the global building and construc-
tion industry.

Zamil Industrial offers a wide range of products and services in four sectors viz. HVAC, Steel, Insulation and Concrete. Zamil
Industrial’s key products and services include: air conditioning systems, pre-engineered steel buildings, steel structures, telecom
and transmission towers, process equipment, precast concrete building products, insulation products, installation and mainte-
nance of HVAC Solutions, and solar power solutions.

The company employs more than 15,500 people and derives about 25% of its revenues from outside Saudi Arabia. Zamil Indus-
trial products are sold in more than 90 countries around the globe, and the company operates manufacturing facilities in Saudi
Arabia, United Arab Emirates, Egypt, India and Vietnam. Zamil Industrial shares are actively traded on the Saudi Stock Exchange
(Tadawul).

Page 225 of 286


INDEX

Contents Page

Model Decoding .......................................................................................................................................................... 1

Introduction .................................................................................................................................................................. 2

Features and Benefits / Standard Specifications / Options and Accessories ............................................................ 3-4

Physical Data ................................................................................................................................................................ 5

Total Heat Rejection (SI Units) ...................................................................................................................................... 6

Total Heat Rejection (Imperial Units) ............................................................................................................................. 7

Electrical data ............................................................................................................................................................... 8

Unit dimensions ....................................................................................................................................................... 9-11

Installation Clearance ................................................................................................................................................. 12

Riging Instruction ........................................................................................................................................................ 13

Wiring Diagram ........................................................................................................................................................... 14

Load Distribution (kg) and Mounting Points ................................................................................................................ 15

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

Page 226 of 286


ZRX SERIES MODEL DECODING

1,2,3 4,5,6 7 8 9
COOLING REFRIGERANT ELECTRICAL CONDENSER
BASIC CAPACITY(1) TYPE SUPPLY COIL
KW (V-Ph-Hz)

ZRX A: R-410A C: 230-1-60 (2) A : ALUMINUM FIN


REMOTE 010
CONDENSER
H : 230 - 3 - 60 C : COPPER FIN (12 FPI)
013

015
M : 400 - 3 - 60 M: AL FIN WITH ANTI-CORROSIVE COATING
018 (4 WIRE)

Q: CU FIN WITH ANTI-CORROSIVE COATING


(12FPI)
028 F: 460 - 3 - 60
035

038

043

055

061

074

10 11 12 13
FAN UNIT CASING KITS GENERAL OPTIONS
ELECTRICAL
OPTIONS

A : AC Fan G: GALVANIZED STEEL A-STD OPTIONS(3) A-STD OPTIONS


WITH POWDER COATING B-Fan Speed Controller (4) B- VIBRATION
ISOLATOR(6)
E : EC Fan S: STAINLESS STEEL (SS-304)

C-Condenser breaker for each


fan

V-VOLT FREE CONTACT


(STATUS INDICATION)(5)

M - B + C COMBO

N - B + V COMBO

O - C + V COMBO
Q - B + C + V COMBO

NOTES:
1- Nominal heat rejection capacity.
2- Single phase power supply is applicable for ZRX010-ZRX013 only.
3- Standard option includes Fan cycling switch for each fan & Disconnect Switch.
4- Fan speed controller is applicable for 230 V & 400 V only , and not applicble with EC fans.
5- Status indication is provided as volt free contacts to indicate common fan run & common fault.
6- Vibration isolator is rubber type only.

1
Page 227 of 286
INTRODUCTION

The ZRX series remote air cooled condenser units from Zamil Central Air Conditioners are produced in an ISO
9001:2015 certified facility .They are factory assembled and designed to provide engineering excellence in precision
cooling with a superior combination of energy saving, performance, application flexibility, ease of service mainte-
nance.

ZRX series units are direct-drive propeller fan-type air-cooled unit suitable for Mounting outdoors. It provides for the
heat rejection of independents refrigeration circuits.

ZRX series remote air cooled condenser units utilize the ambient air to cool off the circulating refrigerant R-410A to
the required temperature based on the required heat rejection. Unit casing has lifting holes in a rigid construction for
overhead rigging and delivered with an integral weather resistant electrical panel, to be instantly connected to utilities.

ZRX series remote air cooled condenser units are shipped with nitrogen holding charge from Zamil factory.

ZRX028

2
Page 228 of 286
FEATURES AND BENEFIT

• Flexible design and components for various specifications.


• Easy installation & excellent serviceability.
• Quality assurance according to ISO 9001: 2015. All deliveries meet performance specifications.
• Compatible with R-410A refrigerant.
• Low noise condenser fans, direct drive with rolled form venture design to eliminate airflow recycling.
• Condenser fan motors are totally enclosed air over type (TEAO) with class 'F' winding insulation.

STANDARD SPECIFICATIONS

A. UNIT ENCLOSURE
The unit cabinet is made of heavy gauge galvanized steel. The steel sheet panels are zinccoated and galvanized by the hot dip
process of lock-forming quality conforming to ASTM A 653 commercial weight G-90, followed by a baked on electrostatic
polyester dry powder coat color, capable of withstanding 1500 hours of salt spray test in accordance with ASTM B-117.

B. FINNED COIL SLAB


Coils are of the fin and tube type, constructed of seamless copper tube (3/8”- inner grooved) mechanically bonded to louvered
aluminum fins for maximum heat transfer efficiency while the coil slab is connected to Type “L” headers. The fins have full
self-spacing collars, which completely cover each tube while the staggered tube design improves the thermal efficiency. The
number of circuits is chosen to provide optimum heat transfer and reasonable refrigerant velocity and pressure drop .End plates
and tube support sheets are made of 18-gauge galvanized steel, formed to provide structural strength.

The hot gas header includes a factory-installed Schrader valves. Coils are leak-tested by charging H2N2 tracer gas in the factory
at 650 psig, filled and sealed with a nitrogen holding charge for shipment.

ZRX028

C. CONDENSER FANS & MOTORS


Condenser fans are constructed of die cast Aluminum blades/hubs with direct driven Motors. All fans are statically and dynami-
cally Balanced to operate at minimum noise and Vibration. Fan blades are designed with Appropriate pitch angle which result in
Maximum airflow through the condenser coil. Condenser fan, the impeller and motor are Constructed to form one integral unit.
All fan Motors are equipped with IP 54 ingress protection, three -phase with class ''F'' Winding insulation, and ball bearings for
high ambient application. These fan motors are of the totally enclosed air over type (TEAO) with inherent thermal protection of
the automatic reset type.

Condenser Fan

3
Page 229 of 286
D- FAN STAGING CONTROL (FAN CYCLING CONTROL)
The capacity of an air-cooled condenser varies with the difference between the Entering air dry bulb temperature and the
condensing temperature of the refrigerant, therefore in order to maintain the head pressure at low ambient, ZRX units are appli-
cable with Fan cycling switch as standard for each fan.

Fan cycling switch is an automatic winter control method and will maintain a Condensing pressure within reasonable limits by
cycling fan motors in response to outside air temperature entering the condensing.

E-DISCONNECT SWITCH
Disconnect switch provided to shut-off power to the equipment. The switch is non-fused and panel mounted type. Operating
handle of the switch is IP55 protection and mechanically interlocked with the door of control panel for safety purpose.

F- POWER AND CONTROL COMPONENTS


Magnetic contactors are provided on individual motors with pressure switches. Power distribution block or Disconnect switches
is provided in the panel for single point power supply for cable connection. Control power is 230Vac. Control wiring is designed
with removable jumper provisions connected on terminal blocks for the purpose of connecting volt-free contact signal to
start/stop individual fan or group of fans. These signals may come from customer’s control devices or may be requested to be
built-in the equipment. Circuit breakers are provided individually on each pair motors as optional

OPTIONS & ACCESSORIES

A. STATUS INDICATOR (VOLT FREE CONTACT)


Two volt-free contact signals are provided to indicate “common run” status and “Common fault” status. In multiple fan units, the
trip signal may not indicate that the entire unit has tripped. It indicates that at least one fan has tripped. Other fans will still be
operating continuously.

B. STAINLESS STEEL CONSTRUCTION


Zamil offers optional stainless steel construction for superior corrosion resistance especially for offshore application. This option
provides Type 304 or Type 316 stainless steel for the whole unit cabinet construction.

C. COIL OPTIONS
a. Aluminum fins pre-coated
b. Aluminum fins with ResisTec COATING
c. Copper fins (12 FPI)
d. Copper fins with ResisTec COATING (12 FPI)

D. Fan Speed Controller


Electronic speed controllers are designed to control the speed of fan motors depending on condensing pressure changes. It is
suitable for single phase and 3-phase motors (230V, 400V )only.

4
Page 230 of 286
PHYSICAL DATA - 60HZ

MODEL NUMBER ZRX010 ZRX013 ZRX015 ZRX018 ZRX028 ZRX035


Qty. 1 1 1 1 2 2
Diameter (mm) 560 560 630 630 630 630
CONDENSER FAN Nominal CFM 3804 3450 5213 4748 10426 9496
Motor kW 0.70 0.54 0.94 0.94 0.94 0.94
RPM 1040 900-980 940-1010 940-1010 940-1010 940-1010
Tube Dia–Rows–FPI 3/8–2–14 3/8–3–14 3/8–2–14 3/8–3–14 3/8–2–14 3/8–3–14
CONDENSER COIL
Total face area (Sq. ft.) 7.56 7.56 9.00 9.00 18.00 18.00
Discharge line size (OD), inch 7/8 7/8 7/8 7/8 1-1/8 1-1/8
REFRIGERANT LINES
Liquid line size (OD), inch 5/8 5/8 5/8 5/8 7/8 7/8
SOUND PRESSURE LEVEL, dBA ( 2 m )* 58 58 59 59 62 62

* BASED ON FREE FIELD AREA AT AHRI CONDITION . TOLERANCE: ± 2dBA

MODEL NUMBER ZRX038 ZRX043 ZRX055 ZRX061 ZRX074


Qty. 2 3 3 3 4
Diameter (mm) 630 630 630 630 630
CONDENSER FAN Nominal CFM 8752 15639 14244 13128 18992
Motor kW 0.94 0.94 0.94 0.94 0.94
RPM 940-1010 940-1010 940-1010 940-1010 940-1010
Tube Dia–Rows–FPI 3/8–4–14 3/8–2–14 3/8–3–14 3/8–4–14 3/8–3–14
CONDENSER COIL
Total face area (Sq. ft.) 18.00 28.50 28.50 28.50 38.00
Discharge line size (OD), inch 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8
REFRIGERANT LINES
Liquid line size (OD), inch 7/8 7/8 7/8 7/8 1-1/8
SOUND PRESSURE LEVEL, dBA ( 2 m )* 62 63 63 63 65

* BASED ON FREE FIELD AREA AT AHRI CONDITION . TOLERANCE: ± 2dBA

5
Page 231 of 286
SI UNITS

TOTAL HEAT REJECTION (KW)-60HZ

Unit TD TD TD
Model (8.0°C) (10.0°C) (12.0°C)

ZRX010 8.3 10.6 13.0

ZRX013 9.8 12.5 15.2

ZRX015 10.8 13.9 17.0

ZRX018 12.9 16.5 20.2

ZRX028 21.8 27.9 34.0

ZRX035 26.3 33.4 40.5

ZRX038 28.3 35.7 43.0

ZRX043 32.9 42.4 51.9

ZRX055 40.0 50.9 61.7

ZRX061 42.9 54.5 66.0

ZRX074 53.4 68.0 82.5

NOTES: Capacities are given according to following conditions:


1- TD = Temperature difference between the Entering Air ( Ambient ) Temperature and Condensing
Temperature ( Dew Point)
2- Inlet air ( Ambient ) Temperature = ( 35 °C )
3- Altitude= 0.0 meter

ALTITUDE CORRECTION FACTORS

ALTITUDE, METER 304.8 609.6 914.4 1219.2 1524 1828.8

FACTOR 0.987 0.969 0.955 0.94 0.919 0.903

6
Page 232 of 286
IMPERIAL UNITS

TOTAL HEAT REJECTION (1000BTUH)-60HZ

Unit TD TD TD
Model (14.4°F) (18.0°F) (21.6°F)

ZRX010 28.3 36.3 44.3

ZRX013 33.4 42.6 51.7

ZRX015 36.9 47.4 58.0

ZRX018 43.9 56.4 68.9

ZRX028 74.3 95.2 116.0

ZRX035 89.6 113.9 138.2

ZRX038 96.5 121.8 146.7

ZRX043 112.4 144.8 177.2

ZRX055 136.5 173.5 210.5

ZRX061 146.3 185.9 225.2

ZRX074 182.3 232.0 281.5

NOTES: Capacities are given according to following conditions :


1- TD = Temperature difference between the Entering Air ( Ambient ) Temperature and Condensing
Temperature ( Dew Point)
2- Inlet air ( Ambient ) Temperature = ( 95 °F )
3- Altitude= 0.0 FT

ALTITUDE CORRECTION FACTORS

ALTITUDE, FT. 1000 2000 3000 4000 5000 6000

FACTOR 0.987 0.969 0.955 0.94 0.919 0.903

7
Page 233 of 286
ELECTRICAL DATA - 60Hz

POWER SUPPLY (V-PH-Hz)

MODEL TFP FAN/UNIT 230-1-60 230-3-60 400-3-60 460-3-60


(60Hz)
FLA MCA MOCP FLA MCA MOCP FLA MCA MOCP FLA MCA MOCP

ZRX010 0.7 1 3.1 3.9 7.0 1.5 1.9 3.42 0.88 1.10 1.98 0.88 1.10 1.98

ZRX013 0.54 1 3.1 3.9 7.0 1.5 1.9 3.42 0.88 1.10 1.98 0.88 1.10 1.98

ZRX015 0.94 1 *** *** *** 2.8 3.5 6.3 1.6 2.0 3.6 1.6 2.0 3.6

ZRX018 0.94 1 *** *** *** 2.8 3.5 6.3 1.6 2.0 3.6 1.6 2.0 3.6

ZRX028 1.88 2 *** *** *** 2.8 6.3 9.1 1.6 3.6 5.2 1.6 3.6 5.2

ZRX035 1.88 2 *** *** *** 2.8 6.3 9.1 1.6 3.6 5.2 1.6 3.6 5.2

ZRX038 1.88 2 *** *** *** 2.8 6.3 9.1 1.6 3.6 5.2 1.6 3.6 5.2

ZRX043 2.82 3 *** *** *** 2.8 9.1 11.9 1.6 5.2 6.8 1.6 5.2 6.8

ZRX055 2.82 3 *** *** *** 2.8 9.1 11.9 1.6 5.2 6.8 1.6 5.2 6.8

ZRX061 2.82 3 *** *** *** 2.8 9.1 11.9 1.6 5.2 6.8 1.6 5.2 6.8

ZRX074 3.76 4 *** *** *** 2.8 11.9 14.7 1.6 6.8 8.4 1.6 6.8 8.4

LEGEND :
*** : Not Applicable
TFP : TOTAL FAN POWER CONSUMPTION -kW
FLA : Full Load Amps
MCA : Minimum Circuit Ampcity
MOCP : Maximum Over Current Protection

8
Page 234 of 286
DIMENSIONS - 60HZ

ZRX 010, 013

1. Discharge header (INLET) UNIT WT. R410A


2. Liquid header (OUTLET) (KG) AL/CU CU/CU

3. Electrical Panel ZRX010 92 110

4. Mounting Points ZRX013 96 115

5. Lifting Lugs

ZRX015, 018

1. Discharge header (INLET)


UNIT WT. R410A
2. Liquid header (OUTLET)
(KG) AL/CU CU/CU
3. Electrical Panel ZRX015 100 120
4. Mounting Points ZRX018 110 135
5. Lifting Lugs

9
Page 235 of 286
DIMENSIONS - 60HZ

ZRX 028, 035, 038

1. Discharge header (INLET) UNIT WT. R410a


2. Liquid header (OUTLET) (KG) AL/CU CU/CU

3. Electrical Panel ZRX028 170 205

4. Mounting Points ZRX035 180 230


ZRX038 190 250
5. Lifting Lugs

ZRX043, 055, 061

1. Discharge header (INLET) R410A


UNIT WT.
2. Liquid header (OUTLET) (KG) AL/CU CU/CU
3. Electrical Panel ZRX043 215 270
4. Mounting Points ZRX055 235 310

5. Lifting Lugs ZRX061 250 350

10
Page 236 of 286
DIMENSIONS - 60HZ

ZRX074

1. Discharge header (INLET)


UNIT WT. R410A
2. Liquid header (OUTLET)
(KG) AL/CU CU/CU
3. Electrical Panel
ZRX074 360 465
4. Mounting Points
5. Lifting Lugs

11
Page 237 of 286
INSTALLATION CLEARANCE

Note:
1. If unit is installed in special pit, please observesame tolerance for walls. Pit height should not exceed unit height.
2. No obstruction above condenser fan.

12
Page 238 of 286
RIGING INSTRUCTION

ATTENTION TO RIGGERS
Hook rigging sling thru the holes on the lifting lugs, as shown below.
Lifting lugs are centered around the unit’s center of gravity.
Ensure center of gravity aligns with the main lifting point before lifting.
Use spreader bar when rigging to prevent the slings from damaging the unit.

CAUTION
Care must be taken to avoid damage to the coils during handling.
Insert packing material between coils & slings as necessary.

13
Page 239 of 286
WIRING DIAGRAM

4-FAN MOTOR LAYOUT

1 2 3 4

HEADER
HVTB SIDE
TO FUSED L1
DISCONNECT
L2
POWER SUPPLY SWITCH OR CB
L3
(SEE NOTE-4)

NEUTRAL LINE APPLICALE 400V ONLY


NTB
POWER SUPPLY
NEUTRAL 230-1-60
100

101

102

103

104

105

106

107

108

109

110

111
LUG FMC1 FMC2 FMC3 FMC4

F1 FMC1
1 1 1 1
TO HVTB L1
35A

36A

37A

35B

36B

37B

35C

36C

37C

35D

36D

37D
11D
11A

11B

11C

37A
10A FCS1

10B FCS2

10D FCS4
10C FCS3

36A
FM1 FM2 FM3 FM4

35A
5C

5D
5A

5B

TK TK TK TK

18
16
14
12

(FM1) (FM2) (FM3) (FM4) FM1

FMC1A-1A FMC2A-1A FMC3A-1A FMC4A-1A


220 Vac

LEGEND
4C

4D
4A

4B

ATB AUXILIARY TERMINAL BLOCK


CB CIRCUIT BREAKER
FMC1 FMC2 FMC3 FMC4 SW DISS CONNECT SWITCH
ATB ATB ETB EARTHING TERMINAL BLOCK HIGH
12 13 ATB ATB ATB
19 HVTB VOLTAGE TERMINAL BLOCK FUSE
14 15 16 17 18
F FAN CYCLING SWITCH
21C

21D
21A

21B

FCS FAN MOTOR


FM FAN MOTOR CONTACTOR
ATB FMC NEUTRAL TERMINAL BLOCK
J1 J2 J3 J4
2 SWITCH
TO NTB N NTB
FM THERMAL OVERLOAD
NOTE: Remove corresponding jumpersJP, J2, J3, . . . as per specific fan/s or nos. S
TK PROTECTION
of fans required to be controlled.
TRANSFORMER

FAN1 FAN2 FAN3 FAN4 TRANS FIELD WIRING


RUN INDICATION RUN INDICATION RUN INDICATION RUN INDICATION GROUNDING / EARTHING
(OPTIONAL) (OPTIONAL) (OPTIONAL) (OPTIONAL)
(common)

S1 S2 S3 S4
NOTES
PRESSURE SWITCH SETTINGS NON-FUSED DISCONNECT SWITCH CONNECTION
1. ANY WIRE REPLACEMENT SHOULD BE OF
NAME OPEN (PSIG) CLOSE (PSIG) SW
HVTB 90 DEG C TYPE OR ITS EQUIVALENT.

FCS1 290 ± 5 348 ± 5 L1 L1 2. CONTROL TRANSFORMER IS REQUIRED ONLY


TO EQUIPMENT L2 L2 IN UNIT MODELS WITH :
FCS2 304 ± 5 362± 5 a) 460V-3PH-60HZ POWER SUPPLY
CKT BREAKER
FCS3 319 ± 5 377 ± 5 (SEE NOTE-4) L3 L3
FCS4 333 ± 5 391± 5

14
Page 240 of 286
15
Page 241 of 286
Zamil Central Air Conditioners
P.O. Box 41015, Dammam 31521, Kingdom of Saudi Arabia
Tel.: +966 13 812 5400 Fax: +966 13 812 1977
Customer Service: 92 0000 468 www.zamilac.com

Page 242 of 286


COMPUTER ROOM AIR CONDITIONERS (CRAC)
Models DPM/ZRC (018-060)
1.5 to 5 TR
60 HZ

Page 243 of 286


Company Profile
Zamil Air Conditioners, a sector business of Zamil Industrial, is the largest manufacturer of air conditioners in the Middle East.
The company manufactures and markets the complete range of air conditioners, from room air conditioners to packaged units
to large chillers for residential, commercial and industrial applications.

Founded in 1974, Zamil Air Conditioners was one of the first air conditioning companies to be established in Saudi Arabia. Today,
the company produces about one million air conditioners per year. Aside from its head office and two manufacturing plants in
Dammam, Saudi Arabia, the company also has production facilities in India. The company supplies air conditioning products to
over 55 countries across the world, with its major markets located in the GCC, Middle East, North Africa, Europe and Asia.

Zamil Air Conditioners is the first Middle Eastern company to achieve the prestigious AHRI certification (Air-Conditioning, Heating
and Refrigeration Institute, USA). The company is also 9001:2015 Quality Management System, ISO14001:2015 (Environment
Management) and OHSAS 18001:2007 (Occupational Safety) certified with many of its products tested and approved by
Eurovent, AHRI, SASO, ESMA & UL.

Companies:
• Zamil Air Conditioners & Home Appliances Co. (L.L.C),
• Zamil Central Air Conditioners Co. (L.L.C),
• Zamil Air Conditioning and Refrigeration Services Co. (L.L.C)

Manufacturing Facilities:
The company has two factories in Saudi Arabia located in the 1st and 2nd Industrial Cities of Dammam. The company also has
production facilities in India.

Annual Production Capacity:


• Window Air Conditioners: 700,000
• Mini-Split Systems: 300,000
• Central Air Conditioners: 50,000

Core Values

VISION:
To be the partner-of-choice COMMUNITY &
for environmental control HONESTY &
PROSPERITY
INTEGRITY
solutions that are based We believe in mutual prosperity.
We believe goodwill and good
on lifetime value reputation are core to our business.
We aspire to thrive in business
while bringing progress and
We uphold honesty, integrity, prosperity to our own people and
professionalism and a high level of communities where we operate.
business ethics. We observe prudence Our culture, our ideas, our
and fairness in dealing with our practices, our environmental
MISSION: stakeholders. concern, and our teamwork lead
us to create superior values for
To make air-conditioning people and communities
Affordable, Reliable and around us.

Energy-Efficient
VALUES
LEADERSHIP &
CUSTOMER & PRUDENCE
EXCELLENCE We cultivate talent and leadership
to create sound business
We are diligent about understanding solutions, to best meet our
and fulfilling our customers’ needs. customer needs, and to develop
We strive to please our customers with markets, people and shareholder
excellence in quality and services. We value. We do so by optimizing use
listen to our customers and “go the of funds, resources, materials, and
extra mile” to satisfy them. INNOVATION & technologies. We build prudence
CHANGE and cost-effectiveness in our
leadership culture passing on
We are passionate about
benefits to our customers.
meaningful innovation. We are a
learning organization. We learn
from our experiences and global
best practices, and we innovate to
create leading local solutions
leveraging on world class
knowledge. We embrace positive
change brought forth by innovation
and aspirations to grow our
business.

Page 244 of 286


Research & Development
Zamil Air Conditioners boasts of its state-of-the-art testing facilities – “Ikhtebar” which is a third party air conditioner testing
facility built by Intertek Testing Services (ITS) and certified by Electrical Testing Laboratories (ETL). Equipped to perform a wide
range of tests under many recognized local and international standards including: AHRI 210/240; AHRI 410; AHRI 310/380; AHRI
430; AHRI 440; AHRI 340/360; ASHRAE 116; ASHRAE 37;ASHRAE 41.1; AHRI 365; ISO 5151; SASO 385; SASO 2682; UL 1995
and AHRI 550/590.

Features:
• Performance test of whole range of air conditioners – consumer as well as commercial, in capacities from ½ TR to 600 TR
• Support research and development initiatives through implementation of state of the art computational programs.
• Test products for conformance to local and international certifications and standards such as SASO, AHRI, UL, AHAM etc.

Facility:
• Calorimetric Test Rooms
• Psychrometric Test Rooms
• Chiller Test Facility
• Sound Lab
• Reliability Test Facility

Parent Company
Headquartered in Dammam, Saudi Arabia, Zamil Industrial Investment Company ('Zamil Industrial') is a premier business group
engaged in the design, engineering and manufacturing of innovative products and solutions for the global building and construc-
tion industry.

Zamil Industrial offers a wide range of products and services in four sectors viz. HVAC, Steel, Insulation and Concrete. Zamil
Industrial’s key products and services include: air conditioning systems, pre-engineered steel buildings, steel structures, telecom
and transmission towers, process equipment, precast concrete building products, insulation products, installation and mainte-
nance of HVAC Solutions, and solar power solutions.

The company employs more than 15,500 people and derives about 25% of its revenues from outside Saudi Arabia. Zamil Indus-
trial products are sold in more than 90 countries around the globe, and the company operates manufacturing facilities in Saudi
Arabia, United Arab Emirates, Egypt, India and Vietnam. Zamil Industrial shares are actively traded on the Saudi Stock Exchange
(Tadawul).

Page 245 of 286


INDEX

Contents Page

Model Decoding ....................................................................................................................................................... 1-2

Standard & Optional features .................................................................................................................................... 3-5

Physical Data ............................................................................................................................................................. 6-7

Electrical data ............................................................................................................................................................... 8

Unit drawings .......................................................................................................................................................... 9-28

Schematic Diagram ............................................................................................................................................... 29-31

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

Page 246 of 286


DPM SERIES MODEL DECODING
1,2,3 4 5 6 6&7 8 9 10 11 12 13 14 15 16 17
NOMINAL ELECTRICAL SUPPLY AIR SUPPLY FAN & ELECTRIC KITS FILTER KITS ELECTRICAL KITS BMS
COOLING SUPPLY ARRANGEMENT MOTOR HEATER OPTIONS(3) OPTIONS MECHANICAL SYSTEM
BASIC SIZE SYSTEM DESIGN MOUNTING DESIGN EVAPORATOR COIL ( 1&2 ) HUMIDIFIER
CAPACITY (V-Ph-Hz) OPTIONS
(1000 BTUH)

DPM 18 A :ALUMINIUM FIN H : HORZINTAL SUPPLY D :DIRECT DRIVEN EC N : NO HUMIDIFIER N :NO HEATER A-STD A- STD A- STD BMS
A :WASHABLE
S: SPLIT DX , AIR AIRFLOW ( FRONT RTURN FAN WITH BACKWARD SYSTEM(5)
M: MINI SIZE C : CEILING MOUNTED C : 230-1-60 ALUMNIUM
DATA HANDLING UNIT WITH & BACK SUPPLY) CURVED AIR FILTER WITH 1'' V- VOLT FREE B- CONDENSATE
24 C :COPPER FIN
PROTECTION REMOTE CONDESING THIKNESS (MERV 4) CONTACT(4) PUMP B -BACNET
MACHINE UNIT (12 FPI)
(FIELD INTALLED) RS485
D : PRE-COATED S : SIDE SUPPLY AIRFLOW H: ELECTRODE E: ELECTRIC B :HIGH EFF. S- SOMKE
ALUMINIUM FIN (FRONT RTURN & CANISTER HEATER WASHABLE C -BACNET
36 DETECTOR
SIDE SUPPLY) HUMIDIFIER (SINGLE STAGE) AIR FILTER WITH 1'' TCP/IP
(R-410A) SENSOR
W: WALL MOUNTED THIKNESS (MERV 8)
F : A + HOT GAS
BYPASS PROVISION F-FIRE
48 DETECTOR
S: SCR ELECTRIC C :HIGH EFF.
G : C+ HOT GAS O : UPWARD SUPPLY HEATER SENSOR
WASHABLE

1
BYPASS PROVISION AIRFLOW ( FRONT RTURN (MODULATING) AIR FILTER WITH 2''
60 & TOP SUPPLY) THIKNESS (MERV 8) W.WATER
M :D+ HOT GAS DETECTOR
BYPASS PROVISION SENSOR

Page 247 of 286


D:S+F COMBO
E:S+F +W COMBO
Q:V+S+F +W COMBO

1- Horizntal & side supply airflow confguiraios are applicable for ceiling mounted units only , while Upward supply airflow is applicable for wall mounted units only.
2- 1" THK Fiber glass insulation with inner skin is standard for all models.
3- 1" MERV 8 Filter is standard for Ceiling Mounted units , while 1" MERV 4 is standard for Wall Mounted units.
4- A combination of volt free contact option : up to 5 dry contacts.
5- STD BMS system includes MODBUS RS485 & TCP/IP.
ZRC SERIES MODEL DECODING

1,2,3 4,5 6 7 8 9 10 11
NOMINAL COOLING ELECTRICAL KITS KITS
REFRIGERATION UNITS
BASIC CAPCITY SUPPLY CONDENSER COIL ELECTRICAL MECHNICAL
CIRCUIT TYPE ENCLOSURE
(1000 BTUH) (V-Ph-Hz) OPTIONS OPTIONS

ZRC 18 C: 230-1-60 S :Single scroll A : ALUMINUM FIN A- STD Options (1) A-STD options (1) A-STD options (1)
compressor
Zamil Air Cooled 24 C : COPPER FIN (12 FPI ) F- Unit Full Guard E- External Overload P : Pressure Gauge
Remote Condensing V :Single scroll For Condenser Fan
36 compressor M: AL FIN WITH R: Condenser Pressure
(R-410A) with service ANTI-CORROSIVE COATING Relief Valve
48 valve
Q: CU FIN WITH H: Hot Gas Bypass
60 ANTI-CORROSIV
COATING (12 FPI) J - P+R COMBO

O: P+ H COMBO

K: P + R COMBO

F: P +R +H COMBO

NOTE
1- Refer to Stadnard & Optional sheet , page No.

2
Page 248 of 286
STANDARD & OPTIONAL FEATURES
DESCRIPTION STANDARD FEATURES OPTIONAL FEATURES
INDOOR AIR HANDLING UNIT
Cooling only
Cooling & heating
Cooling , heating , humidification & dehumidification
Advanced controller with display
UVM (Under Voltage Monitor)
Backward curved fan ( EC FAN )
Motor circuit breaker
Motor with internal overload protection
Motor with External overload protection
Aluminum fin evaporator coils
Copper fin evaporator coils
Anti-corrosive coating on evaporator coils
1'' insulation with inner skin construction
Stainless steel drain pan ( SS-304 )
Washable Pleated filters,1" Thickness (MERV 8) for Ceiling Mounted
Washable Pleated filters,2" Thickness (MERV 8) for Ceiling Mounted
Washable Aluminum filters , 1" Thickness (MERV 2 ) for Wall Mounted
Differential pressure switch for Filter (Air Filter Alarm )
Electrode Humidifier
Electric Heater (Single Stage)
SCR Electric Heater (Modulating )
Disconnect switch
Condensate float switch
Condensate pump (Field Installed)
Volt free contact
Bulk head light
Anti-ice thermostat
OUTDOOR REMOTE CONDENSING UNIT
Scroll compressors
Compressor circuit breakers
Compressor with external overload protection
Compressor with serivce valves
Condenser fan - direct drive, propeller type & fan guard
Condenser motor circuit breakers
Condenser motor with external overload protection
Aluminum fin condenser coils
Copper fin condenser coils
Anti-corrosive coating on condenser Coils
Disconnect switch
Sight glass (moisture indicator)
Sealed type filter drier
Pump down solenoid valve
Hot gas bypass
Condenser pressure relief valve
Pressure gauges
Unit full guard
low pressure switch (Automatic rest)
High pressure switch ( Automatic rest)
Low Ambient Kit (Condenser fan speed controller )

3
Page 249 of 286
General
Indoor Air Handling Units
DPM computer room air conditioners specifically for data center applications; maximization of sensible capacity, efficiency,
reliability, availability and redundancy. The standard indoor AHU is cooling only type, while optional heating, humidification and
dehumidification type are available factory assembled, for complete standard and optional features please refer to page # 3.

Outdoor Condensing Units


ZRC series Zamil Air Cooled Remote Condensing units are made of commercial weight G-90 Galvanized steel sheets, paint:
electrostatic powder coat cool gray color, high efficiency tropical design powerful Scroll compressor, condenser coils made of
louvered fins & tube, external service valves, Condenser Fan direct drive, propeller type & fan guard top air discharge.

The standard outdoor condensing units comes with sealed type filter drier, sight glass, Pump Down Solenoid, High Pressure, Low
Pressure switches, Fan Speed Control. Aluminum fins are standard while Copper and anti-corrosive coating fins are optional, for
complete Standard and optional features kindly refer to page # 3.

STANDARD SPECIFICATIONS

A. General
The Zamil DPM Series Air Handling Units Horizontal & Side supply airflow configurations are applicable for ceiling mounted units
only, while upward supply airflow is applicable for wall mounted units only. They consists of DX cooling coil louvered fins & tube
type, electronic commutated backward fan (EC), thermal expansion valve (TXV), electric heaters & humidifier (wherever speci-
fied), Stainless steel Drain pan, Filters, Advance controller with display, Control Board and other controls in control panel. The
unit is ready to operate when piped to a suitable condensing unit, connected to power/controls and air ducts or for ceiling mount-
ed units.

B. Unit Enclosure
Casing Panels are of heavy gauge (G-90) galvanized steel sheets. Removable access panels are provided for inspection and
access to all internal parts. These panels are insulated with 1" thick fiberglass insulation to prevent condensation from forming
on the unit casing with inner skin construction. Insulation meets the requirements of NFPA 90A and is protected against deterio-
ration and erosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality
conforming to ASTM A-653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.

C. Coils
Coils are of the enhanced louvered fins with inner grooved copper tubes and mechanically bonded to aluminum fins. End plates
and tube support sheets are thick gauge galvanized steel, formed to provide structural strength. Aluminum fins are standard
while Copper and anticorrosive coating fins are optional

D. Drain Pans
Drain pans provided under cooling coil section are made of stainless steel with (304) for additional corrosion protection. Drain
outlets of 3/4" NPT is provided for field connection.

E. Evaporator Fan
Evaporator fan is electronic commutated backward fan (EC) design and sized to meet system airflow/pressure.

F. Filters
Filters are easily accessible through the filter access panel. 1" MERV 8 Filter is standard for Ceiling Mounted units, while 1 "
MERV 4 is standard for Wall Mounted units.

Aluminum Filters Pleated Filters


(MERV 4) (MERV 8)
4
Page 250 of 286
G. Microprocessor controller
The DPM Series Air handling units are provided with a microprocessor control board incorporating the following features:
A microprocessor-based, programmable electronic controller, featuring a multitasking operating system, which includes
programmable controllers, user terminals, gateways, communication devices and remote management devices. These devices
represent a powerful control system that can be easily interfaced with most Building Management Systems (BMS) available on
the market. The controller has been developed to provide solutions for several applications in air-conditioning, refrigeration, and
HVAC/R in general.
The Software is designed as a set of independent modules, one for each phase in HVAC/R software development, suite allows
teams of professionals with different skills to work in a group on the same project, increasing efficiency and adopting joint devel-
opment based on workflow.

The graphic display is an electronic device that allows complete management of graphics by the display of icons (defined at an
application software development level), as well as the management of international fonts, in two sizes: 5x7 and 11x15 pixels.

OPTIONS AND ACCESSORIES

A. Electric Heaters: Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equiva-
lent. Electrical characteristics, kW capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow
switches are provided to shut-off power to heaters in case of airflow failure.

B. Humidifier: The immersed electrode steam humidifier simply made up of a support system (with hoses, valves, etc.), a steam
cylinder, some auxiliary components and controlled by the dedicated controller and/or an external controller.

The range of immersed-electrode kits has been designed to be a universal, flexible and simple solution for such applications. The
kits are ideal for installation inside precision Units, thanks to their compactness and adaptability. . The full range features is capa-
ble of modulating the steam flow from 20% of the rated flow to 100%, according to the external demand.

5
Page 251 of 286
PHYSICAL DATA (MINI DPM-CEILING MOUNTED)

INDOOR MODEL NUMBER DPM018 DPM024 DPM036 DPM048 DPM060


OUTDOOR MODEL NUMBER ZRC018 ZRC024 ZRC036 ZRC048 ZRC060
NOMINAL CAPACITY TR 1.5 2.0 3.0 4.0 5.0
NUMBER OF REFRIGERATION CIRCUIT 1 1 1 1 1
INDOOR AIR HANDLING UNIT (DPM)
TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)
FINS SPACING ( FPI ) 14 14 14 14 14
EVAPORATOR COIL
NUMBER OF ROW 3 3 4 4 4
TOTAL FACE AREA (SQ. FT.) 2.67 3.33 4 5 5
TYPE ELECTRONIC COMMUTATED BACKWARD FAN (EC)
EVAPORATOR FAN QTY. SINGLE FAN
MOTOR TYPE EC, CLASS F INSULATION & IP54
AIR FLOW (CFM) 900 1200 1600 2200 2400
OUTDOOR REMOT CONDESING UNIT (ZRC)
TYPE HERMETIC SCROLL
OIL TYPE POE OIL
COMPRESSOR
OIL PER SYSTEM (OZ) 25 25 25 42 42
REFRIGERANT R-410A
TYPE PROPELLER WITH DIRECT DRIVEN MOTOR
QTY. 1 1 1 1 1
CONDENSER FAN AIR FLOW (CFM ) 2676 2676 4442 4272 4272
MOTOR TYPE TEAO , CLASS F INSULATION & IP54
MOTOR SIZE (KW) 0.42 0.42 0.70 0.70 0.70
TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)
FINS SPACING (FPI) 14 14 14 14 14
CONDENSER COIL
NUMBER OF ROW 2 2 2 2 3
TOTAL FACE AREA (SQ. FT.) 7.94 7.94 14.44 14.44 14.44
OPEN (PSIG) 650±15 650±15 650±15 650±15 650±15
HIGH PRESSURE SWITCH
CLOSE (PSIG) 500±22 500±22 500±22 500±22 500±22
OPEN (PSIG) 50±7 50±7 50±7 50±7 50±7
LOW PRESSURE SWITCH
CLOSE (PSIG) 90±7 90±7 90±7 90±7 90±7

6
Page 252 of 286
PHYSICAL DATA (MINI DPM-WALL MOUNTED)

INDOOR MODEL NUMBER DPM018 DPM024 DPM036 DPM048 DPM060


OUTDOOR MODEL NUMBER ZRC018 ZRC024 ZRC036 ZRC048 ZRC060
NUMBER OF REFRIGERATION CIRCUIT 1.5 2.0 3.0 4.0 5.0
NUMBER OF REFRIGERATION CIRCUIT 1 1 1 1 1
INDOOR AIR HANDLING UNIT (DPM)
TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)
FINS SPACING ( FPI ) 14 14 14 14 14
EVAPORATOR COIL
NUMBER OF ROW 3 3 4 4 4
TOTAL FACE AREA (SQ. FT.) 2.67 3.33 4 5 5
TYPE ELECTRONIC COMMUTATED BACKWARD FAN (EC)
EVAPORATOR FAN QTY. 2 2 3 4 4
MOTOR TYPE EC, CLASS F INSULATION & IP54
AIR FLOW (CFM) 900 1200 1600 2200 2400
OUTDOOR REMOT CONDESING UNIT (ZRC)
TYPE HERMETIC SCROLL
OIL TYPE POE OIL
COMPRESSOR
OIL PER SYSTEM (OZ) 25 25 25 42 42
REFRIGERANT R-410A
TYPE PROPELLER WITH DIRECT DRIVEN MOTOR
QTY. 1 1 1 1 1
CONDENSER FAN AIR FLOW (CFM ) 2676 2676 4442 4272 4272
MOTOR TYPE
MOTOR SIZE (KW) 0.42 0.42 0.70 0.70 0.70
TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)
FINS SPACING (FPI) 14 14 14 14 14
CONDENSER COIL
NUMBER OF ROW 2 2 2 2 3
TOTAL FACE AREA (SQ. FT.) 7.94 7.94 14.44 14.44 14.44
OPEN (PSIG) 650±15 650±15 650±15 650±15 650±15
HIGH PRESSURE SWITCH
CLOSE (PSIG) 500±22 500±22 500±22 500±22 500±22
OPEN (PSIG) 50±7 50±7 50±7 50±7 50±7
LOW PRESSURE SWITCH
CLOSE (PSIG) 90±7 90±7 90±7 90±7 90±7

7
Page 253 of 286
DPM SERIES ELECTRICAL DATA SHEET

Electrical Data Cooling Cooling & Heating Cooling , Heating &


Humdification

Mini DPM FREQUANCY Design Indoor Fan Indoor Fan Humdife Humdifer Electrcial Heater -
MODEL (HZ) Voltage Phase (Ceiling /Wall) QTY Motor Capcity FLA Heater-KW FLA MCA MOCP MCA MOCP MCA MOCP
-FLA (KG/H)

DPM18 60 230 1 Ceiling 1 2.1 3 9.8 5 21.73 2.6 15 29.8 35 42.0 50

DPM24 60 230 1 Ceiling 1 2.1 3 9.8 5 21.73 2.6 15 29.8 35 42.0 50

DPM36 60 230 1 Ceiling 1 5.65 3 9.8 5 21.73 7.1 15 34.2 40 46.4 50

DPM48 60 230 1 Ceiling 1 5.86 5 16.3 10 43.47 7.3 15 61.7 80 82.0 90

DPM60 60 230 1 Ceiling 1 5.86 5 16.3 10 43.47 7.3 15 61.7 80 82.0 90

DPM18 60 230 1 Wall 2 1.44 3 9.8 5 21.73 3.6 15 30.8 40 43 50

DPM24 60 230 1 Wall 2 1.44 3 9.8 5 21.73 3.6 15 30.8 40 43 50


DPM36 60 230 1 Wall 3 1.44 3 9.8 5 21.73 5.4 15 32.6 40 44 50

DPM48 60 230 1 Wall 4 1.44 5 16.3 10 43.47 7.2 15 61.5 80 83.7 90

DPM60 60 230 1 Wall 4 1.44 5 16.3 10 43.47 7.2 15 61.5 80 83.7 90

ZRC SERIES ELECTRICAL DATA SHEET


Remote FREQUANCY COMPRESSOR Compressor Compressor COND.FAN Condenser Fan- Condenser Fan-
Condesing Unit (HZ) Voltage Phase QTY. RLA LRA QTY FLA LRA MCA MOCP

ZRC18 60 230 1 1 10 48 1 1.85 3.4 14.4 20

ZRC24 60 230 1 1 15 58.3 1 1.85 3.4 20.6 30

ZRC36 60 230 1 1 18.6 79 1 3.1 5.1 26.4 40

ZRC48 60 230 1 1 24.3 117 1 3.1 5.1 33.5 50

ZRC60 60 230 1 1 27.9 134 1 3.1 5.1 38.0 60

LEGEND

FLA – Full Load Amps


KW – Kilo Watt
MCA – Minimum Circuit Amps
MOCP – Maximum Over Current Protection

NOTE: The equipment is guaranteed to operate within the voltage range mentioned in the electrical data, while further voltage tolerances can be supported
with special orders.

8
Page 254 of 286
DPM018 - CEILING MOUNTED
HORIZONTAL SUPPLY AIRFLOW

9
Page 255 of 286
DPM018 - CEILING MOUNTED
SIDE SUPPLY AIRFLOW

10
Page 256 of 286
DPM018 - WALL MOUNTED

11
Page 257 of 286
DPM024 - CEILING MOUNTED
HORIZONTAL SUPPLY AIRFLOW

12
Page 258 of 286
DPM024 - CEILING MOUNTED
SIDE SUPPLY AIRFLOW

13
Page 259 of 286
DPM024 - WALL MOUNTED

14
Page 260 of 286
DPM036 - CEILING MOUNTED
HORIZONTAL SUPPLY AIRFLOW

15
Page 261 of 286
DPM036 - CEILING MOUNTED
SIDE SUPPLY AIRFLOW

16
Page 262 of 286
DPM036 - WALL MOUNTED

17
Page 263 of 286
DPM048 - CEILING MOUNTED
HORIZONTAL SUPPLY AIRFLOW

18
Page 264 of 286
DPM048 - CEILING MOUNTED
SIDE SUPPLY AIRFLOW

19
Page 265 of 286
DPM048 - WALL MOUNTED

20
Page 266 of 286
DPM060 - CEILING MOUNTED
HORIZONTAL SUPPLY AIRFLOW

21
Page 267 of 286
DPM060 - CEILING MOUNTED
SIDE SUPPLY AIRFLOW

22
Page 268 of 286
DPM060 - WALL MOUNTED

23
Page 269 of 286
ZRC18

24
Page 270 of 286
ZRC24

25
Page 271 of 286
ZRC36

26
Page 272 of 286
ZRC48

27
Page 273 of 286
ZRC60

28
Page 274 of 286
SCHEMATIC DIAGRAM
COMPUTER ROOM UNIT-DPM

POWER SUPPLY L1
EC FAN CONNECTION
L2
( TO ECB1-Y1)

L1
L2

L1
L2
( ECB1-G0)

95A
G0
71A
72A

71B
72B
L1 N

12
11
14
24V
10V

DIGITAL INPUT(D1)

CO
NO
ANALOG INPUT(E1)

NC
GND
69
68

T1F
T2F
G0

H1F
EC H2F
95A

(Analog IN)

HUMIDIFIER (Stg. 1 Heating)


(optional) (optional)
Return Air Humidity
Antifreeze sensor

ECB1
External Temp
Room Temp

TRANS1
15 G
G
230Vac 24Vac G0

J1
G0
Vterm

Tx/RxGND
J24

J11 pLAN
GND

+
VREF
ATB ATB
1 2
U1
U2

c.PCO
J2
U3
G2 GND
+VDC

(manual reset)
G02
96A

96C

U4
GND
J3

5(NC)
Over Float sensor U5
(OFS) 6(COM) GND

20B
G
G0
OUT-T
G0
OUT-H

DIP SWITCH JUMPER

(auto-reset)
C1

SERIES
OHT1
4~20mA
NO1 (Compressor)
3A
J12
CONNECTTO-J26-FROM-ECB2-

(Cond fan)
NO2 43 (General Alarm)
4A
VG NO3
Tx/RxGNDTx/RxGND

C1
J25 BMS2

G0
95A EC FAN VG0
Y1
J4

Y2
Y3 99A
C4
J26 FBus2

99B W2 20A
JP2
NO4
99C (Pump down sol)
Smoke/Heat alarm
JP3 ID1 NO5 5A
Spot Flooding sensor ID2 NO6
J13

Comp 1 HP C4
P
ID3
Comp 1 LP COM 3
ID4
AFS
P
ID5 C7
P
1 NC
REMOTE-ON/OFF ID6 NO7
J5

J14

COM 3 DPS 2 NO ID7 C7


S

DPS (FILTER) ID8


IDC1
1 NC
HUM (Alarm) P NO8
RELAY C8
J15

NC8
(80065378D)

ATB
TO ECB1-J2 TO ECB1-J2
1 2 +VDC&GND +VDC&GND
G2 G02 G2 G02 Smoke/HeatT alarm

COM 24Vdc 24Vdc


1G 1H

CP
FP

NC
Ø
Smoke alarm 1 5 SA
Heat alarm 1 5 FA
2 3 2 3
NC

COM

NO

1C 1D 1E 1F
To ECB1 To ECB1

98A 98B

29
Page 275 of 286
SCHEMATIC DIAGRAM
COMPUTER ROOM UNIT-DPM

POWER SUPPLY L1
EC FAN CONNECTION
L2
( TO ECB1-Y1)

L1
L2

L1
L2
( ECB1-G0)

L1 N EC2

95A
EC3

G0
69C
68C

71A
72A
69B
68B

71B
72B

12
11
14
24V
10V

DIGITAL INPUT(D1)

CO
NO
ANALOG INPUT(E1)

NC
69A
68A

GND
H1F
H2F
EC1 (Analog IN)

HUMIDIFIER (Stg. 1 Heating)


(optional) (optional)
Return Air Humidity
Antifreeze sensor

ECB1
External Temp
Room Temp

TRANS1
15 G
G
230Vac 24Vac G0

J1
G0
Vterm

Tx/RxGND
J24

J11 pLAN
GND

+
VREF
ATB ATB
1 2
U1
U2

c.PCO
U3 J2
G2 GND
+VDC

(manual reset)
G02
96A

96C

U4
GND
J3

5(NC)
Over Float sensor U5
(OFS) 6(COM) GND

20B
G
G0
OUT-T
G0
OUT-H

DIP SWITCH JUMPER

(auto-reset)
C1

SERIES
OHT1
4~20mA
NO1 (Compressor)
3A
J12
CONNECTTO-J26-FROM-ECB2-

(Cond fan)
NO2 43 (General Alarm)
4A
VG NO3
Tx/RxGNDTx/RxGND

C1
J25 BMS2

G0
97A EC FAN VG0
SCR HEATER Y1
J4

W3 Y2
Y3 99A
C4
J26 FBus2

99B W2 20A
JP2
NO4
99C (Pump down sol)
Smoke/Heat alarm
JP3 ID1 NO5 5A
Spot Flooding sensor ID2 NO6
J13

Comp 1 HP C4
P
ID3
Comp 1 LP COM 3
ID4
AFS
P
ID5 C7
P
1 NC
REMOTE-ON/OFF ID6 NO7
J5

J14

COM 3 DPS 2 NO ID7 C7


S

DPS (FILTER) ID8


IDC1
1 NC
HUM (Alarm) P NO8
RELAY C8
J15

NC8
(80065378D)

ATB
TO ECB1-J2 TO ECB1-J2 Smoke/HeatT alarm
1 2 +VDC&GND +VDC&GND
G2 G02 G2 G02

COM 24Vdc 24Vdc


1G 1H

CP
FP

NC
Ø
Smoke alarm 1 5 SA
Heat alarm 1 5 FA
2 3 2 3
NC

COM

NO

1C 1D 1E 1F
To ECB1 To ECB1

98A 98B

30
Page 276 of 286
SCHEMATIC DIAGRAM
REMOTE CONDENSING UNIT (ZRC)

CRANKCASE HTR CONNECTION

ECB3

31
Page 277 of 286
Zamil Central Air Conditioners
P.O. Box 41015, Dammam 31521, Kingdom of Saudi Arabia
Tel.: +966 13 812 5400 Fax: +966 13 812 1977
Customer Service: 92 0000 468 www.zamilac.com

Page 278 of 286


PL-AP-DPM-60Hz-2M-E
SIZ24 / SIZ48
CASSETTE UNIT
AIR CONDITIONER
HEAT PUMP MODELS
AVAILABLE IN 2 & 4 TONS

Page 279 of 286 Made in China


INDOOR UNIT FEATURES

FRESH AIR
Fresh Air Intake

The fresh air option functions brings


you that fresh and comfortable air feeling.
Page 280 of 286
4 WAY AIR DEFLECTOR EASY INSTALLATION
Ultra-thin body design, the minimum
height is only 230mm and 285mm,
save installation space.

INDOOR DISPLAY
Sleep Mode ON & OFF Timer 24 Hours
In sleep mode the air condition- The timer ON / OFF
er automatically increase the set feature is used to turn OFF the
temperature (cool mode) or air conditioner or turn ON the air
decrease the set temperature conditioner automatically at set
(heat mode) in regular intervals time by user.
to keep comfort during sleep.

Page 281 of 286


OUTDOOR UNIT FEATURES

COMPRESSOR TESTED UP TO 60OC


Compressor are tested up to 60OC
ensure smooth operation at adverse
ambient conditions.

Page 282 of 286


ANTI RUST CASING
CKZ24-48 Powder coated anti rust casings are used for longer life.
Page 283 of 286
SPECIFICATIONS
INDOOR UNIT SIZ24CHAXCD SIZ48CHAXCD
MODEL NUMBER
OUTDOOR UNIT CKZ24CDAHIKD CKZ48CDGHIKD
MODE OF OPERATION Cool onl y / Hea l pump HEA T P UM P HEA T P UM P
POWER SUPPLY Vol ts -Ph-Hz 230-1-60 230-1-60
ENERGY CLASS ( SEER ) B C
COOLING CAPACITY ( T1 & T3 ) Btuh 22000 / 20000 40200 / 34400
COOLING CAPACITY ( T1 & T3 ) wa tts 6448 / 5861 11781 / 10082
HEATING CAPAICTY wa tts 7,000 16,000
POWER INPUT ( T1 & T3 ) wa tts 1864 / 2353 3407 / 4047
POWER INPUT ( Hea ti ng ) wa tts 1,850 4,764
EER ( T1 & T3 ) Btuh/W 11.8 / 8.5 11.8 / 8.5
COP ( Hea ti ng ) W/W 3.85 3.35
SEER Btuh/W 15.66 13.99
ANNUAL ENERGY CONSUMPTION kWh 5,075 9,770
EVAPORATOR AIRFLOW (HIGH /MEDIUM / LOW) CFM 1300/1100/850 2000/1800/1600
SOUND PRESSURE LEVEL (1M) dBA 51-44 52-46
COMPRESSOR TYPE Twi n DC Inverter Rota ry Twi n DC Inverter Rota ry
REFRIGERANT TYPE R410a R410a
LIQUID - SUCTION PIPE DIA i nch 3/8" , 5/8" 3/8" , 3/4"
MAX ALLOWED CONNECTION PIPE LENGTH (Total/vertical) meter 20 / 10 50 / 20
INDOOR UNIT ( Body ) Kg 24 / 29 34 / 36
NET WEIGHT, KG INDOOR UNIT ( Panel ) Kg 6.5 / 9.5 6.5 / 9.5
OUTDOOR UNIT Kg 67 / 72 96 / 105
INDOOR UNIT ( Body ) mm 840×230×840 840×230×840
DIMENSIONS (LxWxH), MM INDOOR UNIT ( Panel ) mm 950×40×950 950×40×950
OUTDOOR UNIT mm 946x410x810 972×400x1330
CONTINUOUS RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE:
1. (T1) Cooling capacity and power input data @ 27º C DB / 19°C WB Indoor temperature & 35ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
2. (T3) Cooling capacity and power input data @ 29º C DB / 19°C WB Indoor temperature & 46ºC DB outdoor temperature - ISO 5151 and SASO 2681 / 2663
3. Heating capacity & power input data @ Indoor 20º C DB / 15º WB Indoor temperature & 7ºC Outdoor temperature.
At outdoor temperature less than -2 deg C, other source of heating must be used.
4. Refrigerant charge for outdoor units suitable for 5 meters of interconnecting pipe, for exact charge refer outdoor unit Nameplate.
5. Sound Pressure level is measured at a distance of 1 mtr. In Hemi Anechoic room.

Page 284 of 286


Page 285 of 286
Zamil Air Conditioners
P.O. Box: 14440 Dammam: 31424, KSA
Phone: +966 13 847 3333 Fax: +966 13 847 1904
RIYADH - (011) 472 5555 JEDDAH - (012) 234 3630 YANBU - (014) 321 2151 CUSTOMER SERVICE
QASSIM - (016) 364 6198 MAKKAH - (012) 546 4167 TABUK - (014) 423 2840 800 304 1000
JUBAIL - (013) 341 6666 MADINAH - (014) 846 3771 GIZAN - (017) 321 3915 zamilac.com
Page 286 of 286