Ventilation
Ventilation
VENTILATION
၇.၁ (Indoor Air Quality [IAQ]) 7-1
၇.၁.၁ (Causes of Poor IAQ) 7-1
၇.၁.၂ (IAQ Control Methods) 7-2
၇.၁.၃ (IAQ Factors) 7-2
၇.၁.၄ (CO2 Levels) (IAQ) 7-2
၇.၂ (Natural Ventilation) 7-3
၇.၂.၁ Stack Effect 7-4
၇.၂.၂ (Design Information) 7-6
၇.၂.၃ Design outputs 7-6
၇.၂.၄ (Calculation Approach) 7-7
၇.၂.၅ Design Watch Points 7-7
၇.၃ Mechanical Ventilation 7-8
၇.၃.၁ 7-8
၇.၄ Hospital Operation Room Ventilation 7-8
၇.၄.၁ Ceiling Construction 7-12
၇.၅ (essential rooms) MV System 7-13
၇.၅.၁ ( (Exit Staircase Internal Passageway) 7-14
၇.၅.၂ ( ) Smoke stop lobby 7-17
၇.၅.၃ (ဂ) Fire Command Center (FCC Room) 7-18
၇.၅.၄ (ဃ) Smoke Stop Lobby Fire Fighting Lobby 7-20
၇.၅.၅ ( ) Fire Pump Room (Generator Room) 7-22
၇.၅.၆ ( ) Flammable and Explosive Substances Rooms 7-24
၇.၅.၇ ( ) (Kitchen) 7-24
၇.၆ Air handling systems mechanical ventilation 7-30
၇.၆.၁ Smoke Tripping of AHU 7-31
၇.၇ Engineered Smoke Control System - Design Consideration and Over View 7-33
၇.၇.၁ Designed Fire Size 7-35
၇.၇.၂ Smoke Extraction System 7-39
၇.၈ Basement Car Park Carbon Monoxide Monitoring and Ventilation Fan Control System 7-42
၇.၈.၁ Safe Level of (CO) 7-43
၇.၈.၂ Understanding of basement car park Mechanical Ventilation System Design 7-44
၇.၈.၃ Basement Car Park Carbon Monoxide Monitoring System's Design Consideration 7-46
၇.၈.၄ (CO) Sensor 7-47
၇.၈.၅ Control Strategies 7-48
၇.၈.၆ (Energy Saving) 7-49
၇.၉ Mechanical Smoke Purging System for Basement Car Park 7-50
၇.၁၀ (Outdoor Air Requirement) 7-51
၇.၁၀.၁ ASHRAE Standard 62.1 - 2004 (Minimum Ventilation Rates ) 7-52
၇.၁၁ Supply Air Rate 7-55
၇.၁၁.၁ (Outdoor Air Intake) 7-57
၇.၁၂ Contamination 7-58
၇.၁၂.၁ 7-58
၇.၁၂.၂ Return Air, Transfer Air Exhaust Air 7-58
၇.၁၃ Exhaust Air 7-61
၇.၁၃.၁ Toilet Ventilation Rates 7-61
၇.၁၃.၂ Minimum Exhaust Rates 7-61
၇.၁၃.၃ Exhaust Air Rates and Pressure Relationship 7-62
www.acmv.org 7-0
Air Conditioning and Mechanical Ventilation System(Vol. 1)
Chapter-7 Ventilation
ဂ
ဂ
(၁၀) ဂ
www.acmv.org 7-1
Chapter-7 Ventilation
၏
( ) (remove heat)
www.acmv.org 7-2
Air Conditioning and Mechanical Ventilation System(Vol. 1)
( ) ၲ (CO)
(CO₂) (contaminant)
(ဂ) (acceptable indoor air quality)
(outdoor air)
“ Vent ”
“M h ”
(naturally
ventilated)
(mechanical ventilated) air c
(mechanically
ventilated space) air con
(naturally ventilated space)
Air c
(smoking
room)
(code)
(naturally ventilated)
(occupied space)
h h
(As-built drawing) (maintenance)
(trouble shooting)
www.acmv.org 7-3
Chapter-7 Ventilation
၇-၄ Stack driven natural ventilation ၇-၅ Wind driven natural ventilation
၇.၂.၁ Stack Effect
(inside temperature)
(outside temperature) ( “S k E ”
natural ventilation Non-mechanical airflow ၌
( “Stack Effect”
(inside) (outside)
(air densities)
www.acmv.org 7-4
Air Conditioning and Mechanical Ventilation System(Vol. 1)
(air movement)
(temperatures difference ventilation
application stack effect
S k (air movement)
၌ (inlet point) (air outlet point)
(internal temperature)
၌
(airflow) (downwards direction)
ဤ (air flow
(machine enclosure)
“Stack Effect”
(tall enclosure)
k (airflow
(internal temperature)
(acceptable operating condition)
www.acmv.org 7-5
Chapter-7 Ventilation
“S kE ”
(၁) “Stack Effect” (air flow
(does not rely on wind)
(၂) (air flow) (stable air flow)
(၃) (greater control in
choosing areas of air intake)
(၄) (sustainable method)
“S kE ”
(၁) (lower magnitude)
(၂) (relies on temperature difference)
(၃)
(design restrictions)
(၄)
www.acmv.org 7-6
Air Conditioning and Mechanical Ventilation System(Vol. 1)
• control philosophy
(ဃ)
Stack effect
References for Natural Ventilation
www.acmv.org 7-7
Chapter-7 Ventilation
naturally ventilated
(louver) Exhaust air
(replacement air) (exhaust air)
၇.၃.၁
၇-၆ Supply air exhaust air ၇-၇ Supply air exhaust air
“ ressure” “
Pressure”
www.acmv.org 7-8
Air Conditioning and Mechanical Ventilation System(Vol. 1)
ဂ
(particles) ventilation system
High Efficiency Particulate Filter(HEPA) ႊ
(infiltration )
Airborne contaminant
(၁) micro-organism( )
(၂) Ventilation infiltration (particles)
(contamination)
Air distribution system (operation room)၌
(contamination) System
(airborne contaminant ) (isolate)
supply air (mixing)
(fresh air)
၇-၁၁ Laminar Flow - Full Ceiling Supply ၇-၁၂ Laminar Flow - Partial Ceiling Supply
www.acmv.org 7-10
Air Conditioning and Mechanical Ventilation System(Vol. 1)
၇-၁၃ An integrated system of laminar flow and linear slot diffusers that minimizes mixing of
room and supply air to create a controlled operating room work area.
(temperature gradient)
(air movement)
(temperature distribution) h
(high contaminated area) (air
velocity) (၀.၂) (0.2 m/s)
(patient room) (၀.၁) (0.1 m/s) (air
www.acmv.org 7-12
Air Conditioning and Mechanical Ventilation System(Vol. 1)
M M ဂ (fire
protection) h
ဂ ဂ
၂၁ M M ဂ
ဂ mechanical ventilation s
www.acmv.org 7-13
Chapter-7 Ventilation
(essential area/rooms)
mechanical ventilation system
( ) (exit staircase) internal passageway
)
( ) Smoke stop lobby (
)
(ဂ) Generator room ( )
(ဃ) Fire Command Center(FCC) (
)
( ) Fire pump room ( )
( ) Rooms involving use of flammable and explosive substances(
)
( ) Kitchen ( )
Mechanical ventilation s
) )
၇-၁၆ Smoke stop lobby ၇-၁၇ Smoke stop lobby (pressurized space)
stack eff
www.acmv.org 7-14
Air Conditioning and Mechanical Ventilation System(Vol. 1)
(emergency exit)
(pressure
(emergency exit)
(exit passage way) f duct
control p (independent system)
fan duct
(
(o
s (intake point)
(exhaust opening) ၅
www.acmv.org 7-15
Chapter-7 Ventilation
p (၂၄)
(natural ventilation)
(exit staircase) (pressurized)
၇-၂၀
(Pressurization Level)
Pressurized exit staircase (occupied
area) 50 p
(pressurized exit staircase) k -
smoke-stop
S k -
(occupied area)
www.acmv.org 7-16
Air Conditioning and Mechanical Ventilation System(Vol. 1)
(pressurized air)
www.acmv.org 7-17
Chapter-7 Ventilation
S k -
(exit staircase) smoke-s (s
s (intake point)
(exhaust opening) ၅
(indication light
www.acmv.org 7-18
Air Conditioning and Mechanical Ventilation System(Vol. 1)
(s s (intake
point ) (exhaust opening) ၅
Fire Command Center(FCC) f duct
control p (i ) supply
f
www.acmv.org 7-19
Chapter-7 Ventilation
- h
www.acmv.org 7-20
Air Conditioning and Mechanical Ventilation System(Vol. 1)
၇-၂၆ Mechanical ventilation of somke stop lobbies and fire fighting lobbise
www.acmv.org 7-21
Chapter-7 Ventilation
၇-၂၇ G
၇.၅.၅ ( ) Fire Pump Room (Generator Room)
( ) (fire pump)
f
www.acmv.org 7-22
Air Conditioning and Mechanical Ventilation System(Vol. 1)
(s s
(intake point) (exhaust
openings) ၅
၇-၂၉ Fire pump room Generator room and fire command center (FCC) room
www.acmv.org 7-23
Chapter-7 Ventilation
၇-၃၁ E
duct (fire pump room)
(generator room)
- h h
- h h ၂၀
duct
(fire rating) (fire rating)
(fire rated) (fire rating)
(fire rating)
h ၌
duct
၇.၅.၇ ( ) (Kitchen)
Mechanical kitchen
kitchen ၏ (volume) (၂၀ (20 air change)
kitchen hood (in
operation) kitchen hood (exhaust air)
www.acmv.org 7-24
Air Conditioning and Mechanical Ventilation System(Vol. 1)
Kitchen Exhaust
Kitchen exhaust hood cooking process
(grease-laden vapour)
(grease removal devices)
Fire suppression equipment (roof)
(building surface) Exhaust air (discharge)
V = Capture velocity which shall not be less than 0.30 m³/s for commercial type kitchens
L = Length of cooking surface, m
W = Width of cooking surface, m
H = Distance of hood to emitting surface, m
F = 1.0 For heavy duty high temperature kitchen
F = 0.7 for light duty, medium and low temperature cooking with equipment such as ovens,
steamer, ranges, griddles and fryers.
www.acmv.org 7-25
Chapter-7 Ventilation
Design Consideration
Kitchen hood kitchen exhaust duct
(unprotected combustible materials) 500 mm
Exhaust hoods
(cooking vapor emission)
kitchen hood exhaust air (velocity) 0.15 m³/s Kitchen exhaust
(hard-faced) mild steel stainless steel
aluminum
www.acmv.org 7-26
Air Conditioning and Mechanical Ventilation System(Vol. 1)
www.acmv.org 7-27
Chapter-7 Ventilation
www.acmv.org 7-28
Air Conditioning and Mechanical Ventilation System(Vol. 1)
Hood exhaust
(၂) Medium duty k h open deep fat fryers, donut fryers, kettle fryers,
and pressure fryers), electric and gas pasta cookers, electric and gas conveyor (pizza)
ovens
(၃) Heavy duty k h electric and gas underfired broilers, electric and
gas chain (conveyor) broilers, gas open burner ranges (with or without oven), electric and
gas wok ranges, electric and gas overfired (upright) broilers, and salamanders
K h kitchen h
(fire rated board K h h
fire damper
h
(
www.acmv.org 7-29
Chapter-7 Ventilation
Fume Hoods
fume hood system 7.5 m³/s feature
(၁) variable air volume hood exhaust Design exhaust air volume ၅၀%
www.acmv.org 7-30
Air Conditioning and Mechanical Ventilation System(Vol. 1)
(toilets)
(domestic kitchens) exhaust duct duct system
(connect) ( h h )
(connect) fan
(device) (industrial)
(commercial kitchens) exhaust duct duct
(separate system)
Exhaust duct (outdoors) discharge
exhaust air (pedestrians)
(outside floor level) 2.1
www.acmv.org 7-31
Chapter-7 Ventilation
၇-၄၂ k
၇.၆.၂ S k
Probe k
h h s
Return air s
smoke detec
a
t
၇-၄၃ Probe type smoke detector Smoke detector
S k
k s building fire alram s
Building Automation System(BAS)
www.acmv.org 7-32
Air Conditioning and Mechanical Ventilation System(Vol. 1)
၇.၇ Engineered Smoke Control System - Design Consideration and Over View
၇-၄၄
Engineered smoke control system
Engineered smoke control system M E
Air Conditioning and Mechanical Ventilation (ACMV) S
M ဂ
၇-၄၅
www.acmv.org 7-33
Chapter-7 Ventilation
A ventilation system
- k
(၁)
burning rate of 0.5 MW/m2 10 m2
h 2.6 M
(temperature) (277°C at 5MW. )
Effect of spreading and growing fires on smoke temperature
Constant burn rate at 0.5 MW/m2 Growing fire
Time from ignition Fire size Max. Fire size
Heat output 2
Heat output Max. smoke
(minutes) (m ) smoke (m2)
(MW) (MW) temp (C)
temp (°C)
- 0.3 0.6 80 0.1 0.4 43
8.0 1.2 2.4 144 0.4 1.5 66
16.0 5.0 10.0 277 1.5 6.0 118
18.5 8.5 17.0 356 2.6 10.0 152
20.0 10.0 20.0 384 3.0 12.0 159
22.0 _ - - 4.6 18.0 195
22.5 - - - 5.0 20.0 201
www.acmv.org 7-34
Air Conditioning and Mechanical Ventilation System(Vol. 1)
k (unsprinkled
2
fire M 20 m
engineered smoke control s
(designed fire s
engineered smoke control system
B
(၁၉၀၀) ( k ) engineered
smoke control system ၁၉၀၀
၅၀၀
a engineered smoke control system
www.acmv.org 7-35
Chapter-7 Ventilation
www.acmv.org 7-36
Air Conditioning and Mechanical Ventilation System(Vol. 1)
www.acmv.org 7-37
Chapter-7 Ventilation
www.acmv.org 7-38
Air Conditioning and Mechanical Ventilation System(Vol. 1)
၁၂၀၀ ၁၂၀၀ f
[Floor area = 1,200 m2 typical(1 fire zone)]
(၂၀ (၁၀)
(Atrium void= 20m long x 10m wide(200 m2))
smoke extraction s
(design f
(design f
၁၂
(၅၀၀၀ k
(3m x 3m sprinkler controlled, 12m perimeter, 5,000kW convective heat output)
)
၂.၂
(၁၇.၀၆)
(Inlet: 4 nos. twin leaf sliding doors, size 2.2m wide x 2m high, Total area = 17.60m2)
၃ “Design Clear
H h“
www.acmv.org 7-39
Chapter-7 Ventilation
= 11.85 x 2
= 23.70 kg/sec ( (၂၃.၇) ဂ )
(၄) ၌ (initial temperature)
initial temperature (I . k =θ )
www.acmv.org 7-40
Air Conditioning and Mechanical Ventilation System(Vol. 1)
= ½(209 + 68)
= 138.5°C > 18°C >> OK
(၇) (Absolute ambient temperature, To)
To = 300 °K (27 °C)
(၈) k temperature (Absolute temperature of smoke layer,Tcm)
= 300 + 138.5
= 438.5 °K
(၉) -(volume of smoke produce, Vp)
= 28.43m3
=add 20% safety factor
= 28.43m3 x 1.2
=34.12 m3/s
၃၄.၁၂
(၁၀) k
(Proposed smoke extraction rate, Ve)
၁၂ fan
= 34.12 / 5.0
= 6.82 m2
(၁၂)
www.acmv.org 7-41
Chapter-7 Ventilation
၇.၈ Basement Car Park Carbon Monoxide Monitoring and Ventilation Fan Control System
(basement car park)
h mechanical ventilation s
ဂ (internal combustion)
h basement car p k ၌
(exhaust gas)
ဂ ၌
www.acmv.org 7-42
Air Conditioning and Mechanical Ventilation System(Vol. 1)
၇-၆၇
(exhaust gas) ဂ
ဂ
(complete combustion) e h
( (CO)
(CO)
(CO) ဂ
(oxygen atom) (carbon atom)
(CO) ႊ (emissions)
( )
(CO) (level)
www.acmv.org 7-43
Chapter-7 Ventilation
Car park
(carbon monoxide)
(other combustion products)
ventilation
Natural ventilation ၍ car k
exhaust air mechanical ventilation
system system (car park)
(outdoor air)
(car park)
(low occupancy) 25
ppm (ventilation rate)
Residential parking area 25 ppm
averaged over an hour period Ventilation fan (switch off)
www.acmv.org 7-44
Air Conditioning and Mechanical Ventilation System(Vol. 1)
Car park ventilation supply air (part) exhaust air (part) ၍ ႏွစ္မ်ိဳး
ရွိသည္။ Exhaust air ၏ ၅၀% (high level) Exhaust air ၅၀%
(low level)
Low level (exhaust air grille)၏
(finished floor) 650 mm
Supply air intake ၏ (exhaust discharge opening)
(၅)
Car park Supply air outlet
(exhaust air)
www.acmv.org 7-45
Chapter-7 Ventilation
(design requirement)
( ) Fan (b k air flow capacity
(run) Car park
(break down)
( ) Duct section k
(ဂ) Duct section (operate) control
(in the event of failure)
section
(ဃ) Exhaust air supply air interlock Exhaust air
supply air (shutdown) Supply air (
) exhaust air (shutdown)
( ) Exhaust supply principle source electrical supply
(Emergy
g (power cable) )
basement car park
(intermixing )
၇.၈.၃ Basement Car Park Carbon Monoxide Monitoring System's Design Consideration
basement car p k (zone) supply fan exhaust fan
(zone) exhaust fan
C k s h
s exhaust air flow rate
B k h S S
SS
h )
www.acmv.org 7-46
Air Conditioning and Mechanical Ventilation System(Vol. 1)
k (CO)
(c Singapore Standards 553 - (Formerly CP 13)
(diameter)
(radius s
(positing)
car park z
sensor
www.acmv.org 7-47
Chapter-7 Ventilation
၇- ၆၀
(sensitiv . -
(detect)
s signal 4
s c
Singapore S 4 I (recommended)
( 9 PPM S M
(၈) M S h
k h h . car park
fan M sh
M
www.acmv.org 7-48
Air Conditioning and Mechanical Ventilation System(Vol. 1)
www.acmv.org 7-49
Chapter-7 Ventilation
www.acmv.org 7-50
Air Conditioning and Mechanical Ventilation System(Vol. 1)
Smoke purging
system
a
6
air change per h 9 air
ch h
Exhaust fan r
(exhaust fan rating : 250°C @ 2 hrs)
Smoke purging system
generator power supply emergency power su
S k supply air exhaust air fan
Supply air f basem k
Supply air f ဂ )
www.acmv.org 7-51
Chapter-7 Ventilation
(fresh a
(outdoor air requirement)
(occupants)
ဤ (per person )
(air quality)
(rate)
(contamination)
(rate)
( ) (per floor area) litres
2
per second per metre squared(l/s/m ဤ
(
)
(ဂ) (volume of the space) (air flow rate) Air Change rate
per Hour(ACH- Air change rate per hour
Ventilation infiltration
www.acmv.org 7-52
Air Conditioning and Mechanical Ventilation System(Vol. 1)
Educational Facilities
Daycare (through age 4) 10.0 0.18 25 17 0.43
Classrooms (ages 5 to 8) 10.0 0.12 25 15 0.37
Classrooms (ages 9 plus) 10.0 0.12 35 13 0.47
Lecture Classroom 8. 0.06 65 8 0.55
Lecture Hall (fixed seats) 8. 0.06 150 8 1.
Art Classroom 10.0 0.18 20 19 0.38
Science Laboratories 10.0 0.18 25 17 0.43
Wood/Metal Shop 10.0 0.18 20 19 0.38
Computer Lab 10.0 0.12 25 15 0.37
Media Center 10.0 0.12 25 15 0.37
Music/Theater/Dance 10.0 0.06 35 12 0.41
Multiuse Assembly 8. 0.06 100 8 0.8
Food and Beverage Service
Restaurant Dining Rooms 8. 0.18 70 10
Cafeteria/Fast Food 8. 0.18 100 9 0.93
Bars/Cocktail Lounges 8. 0.18 100 9 0.93
General
Conference/Meeting 5.0 0.06 50 6 0.31
Corridors - 0.06 - - 0.06
Storage Rooms - 0.12 - - 0.12
Outdoor Air Rate (1) Default Values (2)
Occupancy
People Area Occupant Density CFM per CFM
Category
CFM/Person CFM/SF People/1,000 SF Person per SF
Hotel, Motels, Resorts, Dormitories
Bedroom/Living Room 5.0 0.06 10 11 0.11
Barracks Sleeping Areas 5.0 0.06 20 8 0.16
Lobbies/Prefunction 8. 0.06 30 10 0.29
Multipurpose Assembly 5.0 0.06 120 6 0.66
Office Buildings
Office Space 5.0 0.06 5 17 0.09
Reception Areas 5.0 0.06 30 7 0.21
Telephone/Data Entry 5.0 0.06 60 6 0.36
Main Entry Lobbie 5.0 0.06 10 11 0.11
Miscellaneous Spaces
Bank Vault/Safe Deposit 5.0 0.06 5 17 0.09
Computer (not printing) 5.0 0.06 4 20 0.08
Pharmacy (prep area) 5.0 0.18 10 23 0.23
Photo Studios 5.0 0.12 10 17 0.17
Shipping/Receiving - 0.12 - - 0.12
Transportation Waiting 8. 0.06 100 8 0.81
Warehouses - 0.06 - - 0.06
www.acmv.org 7-53
Chapter-7 Ventilation
www.acmv.org 7-54
Air Conditioning and Mechanical Ventilation System(Vol. 1)
- Cooling load (air volume) 2.0 m3/s 2 air changes per hour
20 air changes per hour
Conventional ductwork system 20 air changes per hour (noise)
(Occupancy)
(outdoor air rate) a
(pattern)
(source of contamination)
(air quality requirements)
www.acmv.org 7-55
Chapter-7 Ventilation
Design approach
Outdoor air requirements
( ) (occupancy) outdoor air rate
Calculation procedure
Total outdoor air requirement
Fresh Air rate per person (l/s per person) CIBSE Guide B2 Table 3.3.
Design tip: (drawing) dimension Drawing length
outdoor air
allowance Variable Air Volume(VAV) system
www.acmv.org 7-56
Air Conditioning and Mechanical Ventilation System(Vol. 1)
Natural Ventilation
Habitable room
၂၀ ၁
(must not be less than 1/20 th of the floor area of the room
၁.၇
M h
H one air h h
Design Criteria
Ventilation system (basic requirement)
(ဂ) Ventilation
(outdoor air intake) (external wall) (roof
level)
(၅) Truck loading area or dock, bus parking idling area: 25 feet.
www.acmv.org 7-57
Chapter-7 Ventilation
(၈) Roof, landscaped grade or other surface directly below intake: 1 foot (or expected aver--
age snow depth, whichever is greater).
(၉) Garbage storage/pickup area, dumpsters: 15 feet.
၇.၁၂ Contamination
(outdoor air intake) ႊ
၇.၁၂.၁
(Air classification and recirculation)
Return Air = Air con space AHU
Transfer Air =
Exhaust Air = air classification
Return air transfer air exhaust air (air quality)
(contaminant concentration) ၍
Class 1
Contaminant concentration
(sensory – irritation intensity)
(air) class 1
(၁) Offices. (၁၂) Electrical/telephone closets.
(၂) Reception/waiting areas. (၁၃) Elevator machine rooms.
(၃) Telephone/data entry. (၁၄) Laundry rooms within dwelling units.
www.acmv.org 7-58
Air Conditioning and Mechanical Ventilation System(Vol. 1)
Class 1
Class 1 (transfer)
(recirculate)
Class 2
Moderate contaminant concentration, mild sensor-irritation mild offensive odor
c
(၁) Kitchens and kitchenettes. (၁၅) Copy printing rooms.
(၂) Toilet/bath rooms (၁၆) Wood/metal shop classrooms.
(၃) Locker rooms. (၁၇) Correctional facility booking/waiting areas.
(၄) Locker/dressing rooms. (၁၈) Bank vaults/safe deposit vaults.
(၅) Central laundry rooms. (၁၉) Pharmacy preparation areas.
(၆) Science laboratories. (၂၀) Warehouses.
(၇) University and college laboratories. (၂၁) Coin operated laundries.
(၈) Art classrooms. (၂၂) Gym/stadium (play areas).
(၉) Retail sales areas. (၂၃) Swimming pools and decks.
(၁၀) Barber shops. (၂၄) Health club/aerobics rooms.
(၁၁) Beauty and nail salons. (၂၅) Health club/weight rooms.
(၁၂) Prison cells with toilets. (၂၆) Food and beverage services: restaurant dining
(၁၃) Darkrooms. rooms, cafeterias, fast food establish ments,
(၁၄) Pet shops (animal areas). bars, cocktail lounges.
www.acmv.org 7-59
Chapter-7 Ventilation
Class 2
Class 2 (recirculate)
ၲရ ယ္ ႏွင့္ က်န္းမာေရးကို ထိခိုက္ေစသည့္ ေလမ်ား
မပါဝင္ေသာ္လည္း တျခားေသာေနရာ မ်ားတြင္ ျပန္လည္အသံုးျပဳရန္ (recirculate) Class 2
class 2 class 3
similar purpose same pollutant source Class 4
(transfer) recirculate class 1
transfer recirculate
Class 3
Contaminant concentration
(sensory irritation) (offensive odor)
class 3
(၁) Commercial kitchen hoods other than grease (၆) Janitor closets.
hoods.
(၂) Residential kitchen vented hoods. (၇) Trash/recycle rooms.
(၃) Refrigeration machinery rooms. (၈) General chemical/biological laboratories.
(၄) Boiler rooms. (၉) Daycare sick rooms.
(၅) Soiled laundry storage areas.
Class 3
Class 3 class 3
(recalculate )
Class 4
Fume gases ၲရယ္ ကိုျဖစ္ေစသည့္ အမႈန္မ်ား
အမႈိက္မ်ား(potentially dangerous particles) ၲရာယ္ရွိေသာေလမ်ား၊(Bio aerosols) ၏
class 4
Recirculation
(၁) Commercial kitchen grease hoods. (၅) Chemical storage rooms.
(၂) Laboratory hoods. (၆) Auto repair rooms.
(၃) Paint spray booths. (၇) Parking garages.
(၄) Diazo printing equipment discharges.
Class 4
Class 4
Ventilation (outdoor air) indoor air (recalculate
(filter)
၍
www.acmv.org 7-60
Air Conditioning and Mechanical Ventilation System(Vol. 1)
www.acmv.org 7-61
Chapter-7 Ventilation
www.acmv.org 7-62
Air Conditioning and Mechanical Ventilation System(Vol. 1)
-End-
www.acmv.org 7-63
Chapter-7 Ventilation
Contents
၇.၁ (Indoor Air Quality [IAQ]) ........................................................................1
၇.၃.၁ .......................................
၇.၇ Engineered Smoke Control System - Design Consideration and Over View .......................... 33
www.acmv.org 7-64
Air Conditioning and Mechanical Ventilation System(Vol. 1)
၇.၈ Basement Car Park Carbon Monoxide Monitoring and Ventilation Fan Control System .........42
၇.၈.၂ Understanding of basement car park Mechanical Ventilation System Design ..............................
၇.၈.၃ Basement Car Park Carbon Monoxide Monitoring System's Design Consideration .......................
၇.၉ Mechanical Smoke Purging System for Basement Car Park ................................................50
၇.၁၂.၁ ............................................
www.acmv.org 7-65