Desiccant Dryer User Manual
Desiccant Dryer User Manual
Desiccant Dryers
Models TWP/TWB200 – TWP/TWB9000
User Manual
1
TWP/TWB200 – TWP/TWB9000
These instructions must be thoroughly read and understood before installing and operating
this product. Failure to operate this product in accordance with the instructions set forth in this
manual can lead to unsafe operating conditions and may void warranty. For additional infor-
mation, refer to this manual or contact the factory for recommendations. Please have the dryer
serial number and model ready when contacting the factory.
Phone 1-716-686-6400
2
TWP/TWB200 – TWP/TWB9000
Contents
Installation 5
General Operation 8
Flow Schematics 10
Wiring Diagrams 17
Start Up 22
Timing Configuration 23
Manual Stepping 24
Controller Display & Operation 24
Communications 44
Shutdown 52
Maintenance 52
Troubleshooting 72
Warranty XX
Technical Specifications 74
3
TWP/TWB200 – TWP/TWB9000
Use EXTREME CAUTION when working in the vicinity of the dryer. Adhere to all warning labels on dryer.
Relieve pressure before servicing dryer or associated equipment.
Always wear eye protection when in the vicinity of the dryer. Ear protection is recommended, especially if the dryer is
being operated without mufflers. Even when mufflers are used, a desiccant vessel blowing down to atmosphere will
raise particles, create more noise than during “normal” operation and may startle an individual not familiar with this
portion of the operation.
The dryer is uses heat to regenerate the desiccant. Any dryer surface may reach temperatures up to 350°F. Do not
touch hot surfaces. Partial insulation is provided to maximize dryer performance. The standard insulation does not
provide complete personnel protection or 100% thermal efficiency.
The emergency stop button will cut off 120V control voltage only. Supply voltage is not disconnected.
In the case of an overpressure situation there is a safety relief valve installed on each desiccant vessel designed to
protect the equipment. If the valves are pointed in a hazardous location to operators after dryer installation, they
should be piped to a safe location.
Dryers are designed for fail safe operation. In the event of a power failure, the inlet valves will fail in the open or last
position and the exhaust valves will fail closed. Compressed air will continue to flow through the dryer. When power
is restored, the cycle will continue on from where it left off at the time of the power loss.
Automatic or manual drain valves will eject water, oil, particulates, and air under partial pressure when operated.
Proper precautions must be taken.
Condensate drainage from compressed air systems may contain oil or other contaminants. Follow all applicable
regulations for safe handling and disposal.
Various component failures could cause large air loss and subsequent pressure drop. Preventative maintenance
should be performed to reduce this possibility. If this situation occurs, bypass the dryer immediately to restore
flow and pressure.
Oil in the desiccant bed combined with high regeneration temperature may create a potential for fire or
explosion. Proper cooling, pre-filtration, and condensate drainage must be maintained to reduce the possibility
of oil contamination.
Activated alumina dust is considered a nuisance dust. Proper precautions should be taken when handling desiccant.
For more information and for other types of desiccant, refer to the applicable Safety Data Sheet. For disposal of
used desiccant, refer to the local codes and regulations.
NOTE: desiccant contaminated with oil or other foreign substances may be covered under disposal regulations for
the contaminant.
Heated dryers are designed with a cooling cycle after heated regeneration to alleviate high temperatures from the
regenerated desiccant and vessel. It is normal for residual heat to remain in the regenerated vessel. Temperatures
of 200-350°F may be seen at switchover. The residual heat will dissipate quickly once the tower is online at full flow.
Downstream piping and components must be suitable for the elevated temperatures.
DOWNSTREAM AIR TEMPERATURE MAY EXCEED 200°F FOR A DURATION OF 15 MINUTES AFTER DRYING
VESSEL SWITCHOVER! TEMPERATURE CAN EXCEED 350°F AT LOWER FLOW!
4
TWP/TWB200 – TWP/TWB9000
INSTALLATION
Inspect the dryer upon receipt for any damage that may have occurred during shipment.
Each desiccant dryer is supplied with a User Manual, dryer general arrangement drawing, and ASME pressure
vessel U1A data reports (where applicable).
The initial charge of desiccant is included with the dryer. Ensure vessels are filled with desiccant prior to startup.
Models 2000 and larger include desiccant shipped separately in 25 lb bags to be installed by the user at the site.
Smaller dryers are shipped with desiccant installed.
Exhaust mufflers are supplied for each dryer. A quantity of two mufflers are shipped attached to the dryer, unin-
stalled, for models 200 and larger. Mufflers should not be installed until after startup to allow excess desiccant dust
to be cleared from the dryer and not prematurely clog the new mufflers.
The dewpoint sensor (optional) is shipped in a small container attached to the dryer. Take care not to misplace
before installing.
If placed in storage, place in a location protected from the environment. If stored outside, it is recommended that the
dryer be underneath a shelter and be shrink wrapped or crated to protect against rain. Desiccant dryers should not
be stored in a location exposed to freezing temperatures or direct sunlight. Dryers designed for outdoor use should
not be placed outside until ready for operation. All plugs and flange covers should remain in place until the dryer is
ready to be installed. Desiccant bags should remain in original closed packaging and be stored in a dry environment
until dryer is ready for operation. Dryers with desiccant installed should be stored in a dry environment.
The dryer should be moved using a pallet jack or fork truck. Desiccant dryers are tall and top heavy. Use caution
while moving the equipment to avoid tipping over. Many dryers have desiccant vessels equipped with lifting lugs.
DO NOT USE THE VESSEL LIFTING LUGS TO LIFT THE DRYER. They are only used to lift an empty vessel and are
not designed to hold the weight of the equipment.
Install in an area with an ambient temperature range of 40°F to 100°F. The area should be well lit and ventilated. It is
recommended to leave a minimum of four feet around all sides of the dryer for maintenance. Ensure that the dryer is
stable and properly secured on a vibration free floor before operation.
If installed outdoors, the desiccant dryer should be installed in an area protected from the effects of weather.
Locate under a roof if possible. Avoid direct sunlight so that the control display does not become damaged and can
be clearly read. If installed in an area with below freezing temperatures, proper heat trace and freeze protection must
be added to the equipment.
5
TWP/TWB200 – TWP/TWB9000
There are several connection points on the dryer. Make sure each connection is made prior to startup.
1. Air in connection – Will be marked on the dryer with a tag. Use piping suitable for the pressure and
temperature class.
2. Air out connection – Will be marked on the dryer with a tag. Use piping suitable for the pressure and
temperature class.
3. Prefilter drain connection – Located near the prefilter and labeled. Drain discharge is under pressure
equal to the system and must use piping suitable for the pressure and temperature class if piped to
another location. A coalescer type prefilter must be installed before the desiccant dryer if not supplied
with the dryer. It is critical to the performance of the dryer to protect the desiccant bed from oil bulk
moisture contamination.
4. Dewpoint sensor (Power Lock options only) - Located near the prefilter and labeled. Drain discharge
is under pressure equal to the system and must use piping suitable for the pressure and temperature
class if piped to another location. A coalescer type prefilter must be installed before the desiccant dryer
if not supplied with the dryer. It is critical to the performance of the dryer to protect the desiccant bed
from oil bulk moisture contamination.
ELECTRICAL CONNECTOR
DEWPOINT SENSOR
SAMPLE LINE
ISOLATION VALVE
SAMPLE LINE
BLEED TUBE
5. Power supply – Bring power to the high voltage panel. Verify voltage, phase, and frequency of power
supply matches dryer design by checking the serial label. Check that power supply is sufficient for amp
rating on serial label. Short circuit protection is the responsibility of the owner.
Mufflers are included with the dryer to reduce noise level only. They are not required for normal operation and
should not be installed for initial startup. The exhaust may be piped to another location to further reduce noise,
MATERIAL PROPERTY OF PARKER-HANNIFIN CORPORATION
PARKER HANNIFIN
DRAWN BY
THIS DOCUMENT CONTAINS INFORMATION THAT IS CONFIDENTIAL AND PROPRIETARY TO
FAF DIVISION
PARKER HANNIFIN, AND IS FURNISHED ON THE UNDERSTANDING THAT THE DOCUMENT
JZ
DATE
1/12/2016
but must not restrict purge air or dryer performance will suffer. The following considerations must be taken when
AND THE INFORMATION IT CONTAINS WILL NOT BE COPIED OR DISCLOSED TO OTHERS
LANCASTER, NY
OR USED FOR ANY PURPOSE OTHER THAN CONDUCTING BUSINESS WITH PARKER, AND
WILL BE RETURNED AND ALL FURTHER USE DISCONTINUED UPON REQUEST BY PARKER. SCALE
14086 USA UNITS
COPYRIGHT IS THE FIRST YEAR INDICATED ON THIS DOCUMENT. ALL RIGHTS RESERVED. 3:50 INCHES
TO 10 FEET, SAME PIPE DIAMETER SIZE AS DRYER EXHAUST VALVE. Ra SURFACE FINISH
TO 25 FEET, ONE PIPE DIAMETER SIZE LARGER THAN DRYER EXHAUST VALVE.
TO 50 FEET, TWO PIPE DIAMETER SIZES LARGER THAN DRYER EXHAUST VALVE.
TO 100 FEET, THREE PIPE DIAMETER SIZES LARGER THAN DRYER EXHAUST VALVE.
6
TWP/TWB200 – TWP/TWB9000
Each elbow installed in the exhaust piping is equivalent to 10 feet of pipe. If the exhaust piping is vertical, a drip line
must be installed to remove moisture. It is recommended to pipe the exhausts separately for ease of maintenance
and troubleshooting.
It is highly recommended to install bypass valves and piping around the dryer and filters to use during routine dryer
maintenance.
7
TWP/TWB200 – TWP/TWB9000
GENERAL OPERATION
The externally heated and blower purge desiccant dryers are designed to remove moisture in water vapor form, from
compressed air to yield dewpoints of -40°F or better. The twin tower design allows constant drying of compressed
air through one adsorption vessel while the other vessel desiccant bed regenerates by using heated dry purge air.
Compressed air is directed through the inlet valve and up through the drying desiccant vessel where moisture is
adsorbed by the desiccant. The low dewpoint dry air is then directed through the outlet check valve and down-
stream for use.
For externally heated dryers, regeneration of the saturated desiccant vessel bed is begun by blowing down the
saturated vessel bed. The quick change from line pressure to atmosphere causes moisture to detach itself from the
desiccant and be exhausted. The regeneration cycle is continued by directing 8% of the dry compressed air through
a purge valve and orifice. The purge air is expanded to atmosphere, passed across an electric resistance heater
where the air temperature is elevated to 400°F, then passed down through the saturated bed heating the desiccant.
Adsorbed moisture is released from the desiccant, and then exits the dryer through the exhaust valve and muffler.
Once heated regeneration is complete, the heater is powered off and cooling begins. Dry purge air continues to pass
through the regenerated bed, cooling it to reduce the air temperature spike downstream and allow the newly regen-
erated bed to readily adsorb moisture again after switchover.
For blower purge dryers, regeneration of the saturated desiccant vessel bed is begun by blowing down the sat-
urated vessel bed. The quick change from line pressure to atmosphere causes moisture to detach itself from the
desiccant and be exhausted. The regeneration cycle is continued by the blower pulling in ambient air and passing
this low pressure wet air across an electric resistance heater. The air temperature is elevated to 400°F, then passed
down through the saturated bed, heating the desiccant. Adsorbed moisture is released from the desiccant, and then
exits the dryer through the exhaust valve and muffler. Once heated regeneration is complete, the heater is powered
off and cooling begins. The blower continues to pass air through the regenerated bed, cooling it to reduce the air
temperature spike downstream and allow the newly regenerated bed to readily adsorb moisture again after switcho-
ver. A stream of dry purge air in the amount of 2% may also be used after blower cooling to reduce the dewpoint
spike at switchover caused by using wet ambient air with the blower.
Once regeneration is completed, the offline desiccant vessel is slowly pressurized to system pressure. The dryer is
ready for switchover, at which point compressed air will be directed though the newly regenerated desiccant bed for
drying and the opposite desiccant vessel begins regeneration. This cycle continues automatically.
The dryer inlet, exhaust, and repressurization valves are controlled by solenoid actuated control valves, which are
controlled by the dryer PLC. The PLC operates opens and closes the valves using a programmed timing sequence.
The PLC is equipped with various timing cycles to maximize the dryer efficiency. It is also possible to extend the
drying cycle time using the dewpoint demand function.
8
TWP/TWB200 – TWP/TWB9000
9
TWP/TWB200 – TWP/TWB9000
10
TWP/TWB200 – TWP/TWB9000
11
TWP/TWB200 – TWP/TWB9000
12
TWP/TWB200 – TWP/TWB9000
13
TWP/TWB200 – TWP/TWB9000
14
TWP/TWB200 – TWP/TWB9000
15
TWP/TWB200 – TWP/TWB9000
16
TWP/TWB200 – TWP/TWB9000
WIRING DIAGRAM STANDARD CONTROLLER
17
TWP/TWB200 – TWP/TWB9000
WIRING DIAGRAM STANDARD CONTROLLER
18
19
WIRING DIAGRAM STANDARD CONTROLLER
TWP/TWB200 – TWP/TWB9000
TWP/TWB200 – TWP/TWB9000
WIRING DIAGRAM STANDARD CONTROLLER
20
TWP/TWB200 – TWP/TWB9000
PANEL LAYOUT STANDARD CONTROLLER
21
TWP/TWB200 – TWP/TWB9000
START UP
Verify all piping and electrical connections are secure. Do not power the dryer at this time.
Start the compressor and pressurize the air system, bypassing the dryer.
Slowly pressurize the dryer by opening the inlet isolation valve. It is important to allow the dryer to slowly
pressurize to prevent fluidization of the desiccant bed. Rapid pressurization can also cause damage to the
vessel internal screens and filter elements.
The dryer must be started without the mufflers installed. This will expedite removal of excess desiccant dust and
prevent premature clogging of the mufflers.
CAUTION: USE EAR AND EYE PROTECTION WHEN OPERATING THE DRYER WITHOUT MUFFLERS. EXCESSIVE
NOISE WILL BE CREATED. DUST AND PARTICLES FROM THE SURROUNDING AREA MAY BECOME AIRBORNE.
OPERATION WITHOUT MUFFLERS EXCEEDS OSHA LIMITS.
Power up the dryer. Check rotation of blower by pushing in contactor manually. If opposite of the flow direction
arrow, switch the two leads.
Start in Heatless - Touch the START IN HEATLESS OPERATION button from the controller’s SERVICE screen to
start the dryer. The dryer will initially ensure that vessels are pressurized, then will begin by blowing down one
of the vessels while placing the opposite ‘drying’ vessel online. If you do not want the dryer to begin cycling
automatically, close the control air ball valve. This will prevent the inlet and exhaust valves from switching. In this
situation, a bad blowdown alarm will occur which must be reset from the control panel after re-opening the control
air ball valve.
The dryer can be run in the heatless mode for two or three cycles to quickly remove desiccant dust caused by
shipping or filling the unit. This also serves to verify that the vessels are switching normally, and to allow resolving
any issues with system pressure before applying heat the regeneration process.
Switch to Heated - When you are ready to switch the dryer to HEATED regeneration operation, simply touch the
START IN HEATED OPERATION button from the controller’s Service screen. The dryer will immediately repressurize,
then switch towers and start HEATED regeneration on the opposite vessel.
Check Purge Pressure - For TWP dryers, verify the purge pressure setting is correct for the operating conditions.
The purge pressure setting must be set to the factory advised setting while using the dewpoint demand feature.
The purge pressure must be set while in the Heated Regeneration State. Do not adjust the purge pressure when
operating in the heatless backup timing configuration.
Heating - Verify that the heater contactor(s) pull in and the purge air temperature value on the controller screen
begins to rise. If the dryer is blower type, then the blower will also be running at this time.
Over-Temp - There is a redundant over-temperature module inside the control cabinet that is preset at the factory to
650°F. This module monitors a thermocouple for purposes of independently sensing an over-temperature condition.
In addition, there is an over-temp setting, also preset the factory to 650°F, accessed from the ADVANCED SETTINGS
screen on the controller. This setting is associated with the purge temperature sensor.
22
TWP/TWB200 – TWP/TWB9000
It is not uncommon for the heater to shut down due to an over-temperature condition during initial startup of the
dryer. If this should happen, verify that the purge pressure setting agrees with the suggested setting and that there
is no backpressure in the regenerating tower (as would occur if a muffler was clogged or a check valve was not
functioning properly). If there is no sign of back pressure, then increase the overtemp adjustment on the over-temp
module, and the over-temp setting in the Advanced Setting screen by 50°F increments and reset the alarm. Repeat
until optimal overtemp settings are achieved. Consult factory if the dryer continues to shut down on over-temp at a
setting of 750°F or above.
Slowly open the dryer outlet isolation valve. Close the bypass valve. If applicable, tighten manway cover bolts. It is
common for the manway gasket to undergo additional compression on startup.
TIMING CONFIGURATION
The controller is designed for externally heated, blower purge and heatless backup cycle operation. The timing
configuration is pre-set at the factory for the specific dryer model. The default timing settings for each configuration
are listed below.
Heatless Backup Cycle: 14 min
Externally Heated Cycle: 8 hours Blower Purge Cycle: 8 hours
Drying: 7 min per tower.
Drying: 4 hours per tower. Drying: 4 hours per tower.
Purging: 6 min per tower.
Heating: 2 hours 30 min per tower. Heating: 2 hours 30 min per tower.
Repressurization: 1 min per.
Cooling/Purging: 1 hour 27 min per Cooling: 2 min per tower.
tower.
Purging: 85 min per tower.
Repressurization: 3 min per tower.
Repressurization: 3 min per tower.
The heating time is the maximum per tower per cycle. To save energy, the system is designed to end the heating
cycle and advance to cooling once the offline tower is fully regenerated. For blower purge models, the user may
disable the 2% cooling feature in order to prevent using dry purge air during regeneration. The cooling time will then
default to 25 min per tower per cycle.
Externally heated and blower purge dryers are both equipped with a heatless backup cycle as a standard feature.
This configuration may be selected by the user to use dry purge air for regeneration in place of heated air.
This operating cycle consumes 15-18% dry purge air and has a much shorter cycle time than the heated cycle.
Heatless backup can be used when there is an issue with the heated regeneration function of the dryer, but dry air is
still needed. The heatless backup cycle will allow the dryer to continue to produce dry air until a time when the dryer
can be shut down for service and maintenance. Heatless backup can also be used to more quickly purge a new
or oversaturated dryer. Once the dryer begins to achieve consistent dewpoint, the dryer can be switched back to
HEATED REGENERATION.
The dewpoint demand function is an energy savings feature that extends the drying cycle as long as the user
defined dewpoint requirements are met. The offline desiccant vessel completes its regeneration process as normal
and then waits in an idle state until the dewpoint degrade to the setpoint before switching over. By extending the
drying cycle, less purge air is consumed over a period of time. The Dewpoint Demand feature must be set to
ENABLED and the dewpoint sensor must be installed in the DEWPOINT SETTINGS screen.
23
TWP/TWB200 – TWP/TWB9000
MANUAL STEPPING
This feature is used to assist in maintenance and troubleshooting of the dryer. Touching the STEP button at the
main screen will advance thru the regeneration states. This allows the user to skip ahead to desired stages of the
regeneration process more quickly. Using this feature may yield worse than desired dewpoints until the dryer is
allowed to cycle uninterrupted. For safety, when attempting to switch out of repressurization or blowdown, the dryer
will wait until the pressures in the tanks are at a safe level before proceeding to the next state.
CAUTION: Never step through the cooling state. Doing so may result in extreme temperatures being released
downstream. Only switch out of cooling if you are certain there is no possibility of releasing dangerous heat
downstream.
The dryer’s controller is an Allen-Bradley® PLC coupled with a proprietary color, touch panel HMI. The controller
is factory programmed with the proper timing configurations for the dryer model. The controller features user
configurable drain settings, timing configuration, dewpoint demand cycles, system pressure and temperature
monitoring, system alarms with user configurable settings and alarm log, and a manual stepping feature for
maintenance. Additionally, there is reference information for troubleshooting dryer operation and alarms.
The standard controller display is accessible at the front of the dryer without opening the enclosure. If the enclosure
must be opened, always remember to close and secure the enclosure door when not using!
24
TWP/TWB200 – TWP/TWB9000
1. Menu Icon – Press to display the menu icons on the sides of the display.
4. Silence Button – Press to silence the alarm screen and turn off the alarm relay.
5. Alarm Reset Button – Press to reset all alarms and restart regeneration.
7. Step Button – Press to step to the next regeneration state – Use with caution.
8. Standby Button – Press to place the dryer in standby and to restart the dryer.
9. Log In / Log Out Buttons – Press to log in and log out as required
Supervisor default password is SUP (all caps).
These passwords may be changed, however, if the password is lost, the display must be completely reprogrammed
in order to reset, resulting in a potential service call!
ALL SYSTEMS OK
Default message – No alarms. Dryer is running in normal operation.
ALARM SHUTDOWN
Regeneration has shut down.
To restart, Press the Alarm Reset button.
GOING TO STANDBY
Standby button has been touched and the dryer is waiting to go to standby
If heating, the dryer will cool for 2 minutes before going to Standby.
25
TWP/TWB200 – TWP/TWB9000
SWITCHING TO HEATLESS
The Switch To Heatless button has been touched from the Service Screen.
The dryer will immediately switch to cooling and completely cool the tower before
switching to Heatless.
SWITCHING TO HEATED
The Switch To Heated button has been touched from the Service Screen.
The dryer will immediately switch to Heated once the towers have repressurized.
Refer to the Alarms Section for a complete list of alarm messages which are also
displayed on this line.
DRYER PARKED
The dryer has not yet been started. Once the dryer is started, it cannot be placed into
PARKED state without re-programming the PLC.
LEFT TOWER BLOWING DOWN / RIGHT TOWER BLOWING DOWN
Regenerating tower is waiting to depressurize before purging.
LEFT TOWER BLOWER COOLING / RIGHT TOWER BLOWER COOLING
(Blower Models Only).
Blower is cooling down the heater tube before switching to Cooling Regeneration.
BLOWER REGENERATION MODELS ONLY.
26
TWP/TWB200 – TWP/TWB9000
RIGHT DRYING - TIME REMAINING / LEFT DRYING - TIME REMAINING
Dryer still has time remaining on the drying tower and is waiting for the time to expire
before switching towers.
REGENERATING LEFT TOWER / REGENERATING RIGHT TOWER (Heatless Mode)
Dryer is in heatless backup mode and regenerating the tower.
b. Sensor Values
Inlet Pressure and Temperature
Outlet Pressure
Pre-Filter Pressure
After-Filter Pressure
Outlet Temperature
Left and Right Tank Pressures
Left and Right Exhaust Temperatures
Purge Temperature
Purge Pressure (Dry Purge models only)
Dewpoint (Optional)
Flow Meter (Optional)
c. Time
27
TWP/TWB200 – TWP/TWB9000
1. Heater Tube
Red when heater is active 7. 2% Purge Valve (Blower Purge ModelsOnly)
White – indicates valve(s) are open
2. Blower (Blower Purge Models Only) Yellow – indicates valves are closed
Green when blower is running,
Red during Blower related alarms 8. Repressurization Valve
White – indicates valve(s) are open
3. Blower Flow Switch (Blower Purge Models Only) Yellow – indicates valves are closed
Yellow – indicates lack of flow across flow switch
White – indicates lack of flow across flow switch 9. Outlet Check Valves (2)
Yellow – indicates flow across blower flow switch White – no air is flowing thru valve
Yellow – air is flowing thru valve
4. Exhaust Valves (2 or 4 depending on pre-exhaust)
White – indicates valve(s) are open 10. Purge Check Valves (2)
Yellow – indicates valves are closed White – no air is flowing thru valve
Yellow – air is flowing thru valve
5. Inlet Valves (2)
White – indicates valve(s) are open 11. Drain Valves (Optional)
Yellow – indicates valves are closed
28
TWP/TWB200 – TWP/TWB9000
3. Sensors Icon – Press to display real-time sensor values, including user sensors.
4. I/O Screens Icon – Press to display the states of the PLC Inputs and Outputs.
5. Service Icons – Press for access to user and service related functions.
9. Page Left and Page Right Icons – Press to step thru the setting screens.
10. Snapshot Icon – Press to save a snapshot of any screen to the flash drive.
29
TWP/TWB200 – TWP/TWB9000
Drain Settings
Optional - Only applicable for dryers which control the drains using the PLC.
30
TWP/TWB200 – TWP/TWB9000
There are two 4-20 mA inputs on the PLC for the user.
If Sensor #1 is selected as a Flow Meter input, its value is displayed on the Main Display
Sensors #1 and #2 real-time values are accessed from the Sensor Screen.
Alarm Settings
31
TWP/TWB200 – TWP/TWB9000
Advance Settings
Purge Temperature
Maintains purge temperature is this level during heating.
Over-temp Temperature
Shuts down dryer if purge temperature sensor rises above this setting.
This is independent of external over-temp alarm.
If this setting is disabled, the dryer will wait indefinitely until the tower pressure drops below 10psi before proceeding
to regeneration.
32
TWP/TWB200 – TWP/TWB9000
If this setting is disabled, the dryer will wait indefinitely for the tower pressure to rise to within 10 psi of inlet pressure
before proceeding to regeneration.
Use 2% Purge Cooling (Blower Models Only). Enable to use dry purge air during cooling on blower units, otherwise,
ambient air will be used, which will result in higher dewpoint spikes after switching.
Factory Settings
These settings are only available to the Dryer Manufacturer’s Factory or Service Personnel and are included here for
reference only.
These settings are only available to the Dryer Manufacturer’s Factory or Service Personnel and are included here for
reference only.
33
TWP/TWB200 – TWP/TWB9000
There are 5 trend windows, each focusing on different data groups.
When you first enter a trend display, you must hit ZOOM ALL to zoom out to a usable window.
The screen is historical data only and will not automatically update as new data is logged. To refresh the data, you
must hit one of the zoom buttons.
Use RIGHT and LEFT ARROW keys to move between trend screens.
Dewpoint Dewpoint
Purge Temperature
Inlet Temperature
Outlet Temperature
34
TWP/TWB200 – TWP/TWB9000
35
TWP/TWB200 – TWP/TWB9000
Export Data Sends data to the Flash Port in Excel readable format.
Step Cursor Left Moves cursor left one unit (resolution unit).
Step Cursor Right Moves cursor right one unit (resolution unit).
Search Opens a search window where a date and time can be entered.
Note: Changing the time to a value that is prior to the latest logged value will suspend trend user interaction until the
clock catches up to and surpasses the latest logged value. This will result in loss of data and possible confusion. To
prevent data loss, the data can be exported before the clock is changed, then cleared after the clock is changed. All
logged data will be lost, however.
36
TWP/TWB200 – TWP/TWB9000
Sensor Screen
Displays real time sensor values. This is the only place that the User Input 2 is displayed.
I / O Screens
Displays real time PLC inputs and Outputs for use in trouble shooting.
37
TWP/TWB200 – TWP/TWB9000
Service Screen
38
TWP/TWB200 – TWP/TWB9000
When switching modes, you must wait for the mode transition to complete before
you can switch back.
2. Test Drains
Press to open the drain valve for the amount of time determined by Drain Duration setting.
4. Reboot Display
Used to reboot the display panel should it be necessary.
An alternate method it to pull the orange plug on the back of the display panel.
5. Exit to System
Exits the application so that system level settings, such as communications
can be accessed.
6. Time/Date Set
Press to adjust the time and date.
See note in trending section for possible effects on data logging and trends.
7. Reference Guide
Press to access Reference Guide.
Use the onboard reference guide to learn about and troubleshoot dryer functions.
39
TWP/TWB200 – TWP/TWB9000
Service Screen
40
TWP/TWB200 – TWP/TWB9000
Alarm History
Displays a log of all alarm and event activity since the last time the history log was cleared.
User Buttons
41
TWP/TWB200 – TWP/TWB9000
Pressing Alarm Reset Button will reset all active alarms and automatically restart the dryer.
Alarm Relay
There is an alarm contact on the PLC for driving external alarm devices or for feeding into a PLC.
The alarm relay turns on whenever there is a new alarm and turns off when the alarm silence or alarm reset button is
pressed.
Alarm Reset
Clears all alarms and restarts regeneration.
42
Alarm Description Settings Notes
TOWER FAILED TO BLOWDOWN Alarms if regenerating tower Is not above 10 psi at the end of blowdown. Default is 60 seconds Shuts down regeneration (settable)
Adjustable from 15 to 300 seconds Manual reset
TOWER FAILED TO PRESSURIZE Alarms if regenerating tower Is not within 10 psi of the inlet pressure at the end of Default is 180 seconds, Always enabled Shuts down regeneration
repressurization. Adjustable from 30 to 600 seconds Manual reset
HIGH PURGE TEMPERATURE Alarms if the purge temperature rises above the high purge temperature set point. Default is 650ºF (343ºC), Always enabled The heater is inactive until the alarm is manually reset.
Adjustable from 200ºF to 800ºF (90ºC to 425ºC) This alarm does not shutdown regeneration.
ALARM CHART
HIGH OVER TEMPERATURE Alarms if the alarm contact from the external over-temp monitor are closed. Default is 650 ºF, Always enabled The heater is inactive until the alarm is manually reset.
Adjustable from module This alarm does not shutdown regeneration.
LOW PURGE TEMPERATURE Alarms if the purge temperature does not rise above 150 F within 15 minutes after Fixed at 150ºF (65ºC) The heater is inactive until the alarm is manually reset.
the heater turns on. Always enabled This alarm does not shutdown regeneration.
TWP/TWB200 – TWP/TWB9000
CLOGGED MUFFLER Alarms if the pressure in the regenerating tower is above 5 psi for 5 minutes Fixed at 5 psi (34 kPa) Automatically resets after pressure falls below setting
Always Enabled
LOW PURGE PRESSURE Alarms if the purge pressure is below the set point for 10 seconds during regeneration Default is 25 psi (170 kPa), Always enabled Automatically resets after pressure rises above setting
(models wihout blowers only) Adjustable from 0 to 100 psi ( 0 to 650 kPa)
HIGH INLET TEMPERATURE Alarm results when Inlet temperature is above 101 F Default is 101ºF (38ºC), Always enabled Automatically resets when the temperature falls below the set point
Adjustable from 0ºF to 200ºF (0ºC to 90ºC)
LOW INLET PRESSURE User settable alarm results when Inlet pressure is below 60 psi for 5 minutes Default is 60 psi (414 kPa), User Enabled Automatically resets when the pressure rises above the set point
Adjustable from 0 to 200 psi ( 0 to 1300 kPa)
HIGH DEW POINT Alarms if the dew-point is above the set point for 45 minutes Default is -20ºF (-28ºC), User Enabled Automatically resets when the dew point rises above the set point
Adjustable from -250ºF to 75ºF ( -150ºC to 20ºC)
CLOGGED PRE-FILTER Difference between inlet pressure and drying tower pressure is greater than 8 psi for Default is 8 psi (55 kPa), User Enabled Automatically resets when the pressure drops below the set point
5 minutes Adjustable from 0 to 25 psi ( 0 to 300 kPa)
CLOGGED AFTER-FILTER Difference between outlet pressure and drying tower pressure is greater than 8 psi Default is 8 psi (55 kPa), User Enabled Automatically resets when the pressure drops below the set point
for 5 minutes Adjustable from 0 to 25 psi ( 0 to 300 kPa)
BLOWER OVERLOAD ALARM Blower overload contact has opened while the blower is running. Blower FLA adjustment on device Manual reset to restart the dryer
(models with blowers only)
BLOWER FLOW ALARM Flow switch does not agree with blower output for 30 seconds. none Manual reset to restart the dryer
43
(models with blowers only
DRAIN FAULT Drain switch Input is closed for 5 seconds longer than Duration setting Use Drain Duration setting Automatically resets once the switch returns to normal
LOW AUX SENSOR Alarms when input falls below setpoint Default is 0, User Enabled Automatically reset when value rises above setpoint
Adjustable from -32767 to 32768
HIGH AUX SENSOR Alarms when input rises above setpoint Default is 0, User Enabled Automatically reset when value drops below setpoint
Adjustable from -32767 to 32768
LOSS OF CONTROL POWER Alarms if there is no voltage on the output of the control fuse. none Must be manually reset by the operator
LOSS OF SENSOR POWER Alarms if all pressures sensors register a fault. none Must be manually reset by the operator
INLET, or TANK PRESSURE SENSOR Sensor input is open or shorted to ground or V+ none Shuts down regeneration
FAULT Must be manually reset by the operator
OUTLET or PURGE PRESSURE SEN- Sensor input is open or shorted to ground or V+ none Must be manually reset by the operator
SOR FAULT
DEWPOINT SENSOR FAULT Sensor input is open or shorted to ground or V+ none Automatically reset once the fault condition clears
AUX SENSOR FAULT Sensor input is open or shorted to ground or V+ none Automatically reset once the fault condition clears
TEMPERATURE SENSOR FAULT Alarms if there is a break in the type J thermocouple sensor none Must be manually reset by the operator
TWP/TWB200 – TWP/TWB9000
COMMUNICATIONS
WARNING! - DO NOT ATTEMPT TO CHANGE SETTINGS OR OTHERWISE OPERATE THE DRYER REMOTELY
WITHOUT A FIRM UNDERSTANDING OF DRYER OPERATION. IMPROPER SETTINGS OR CONTROL MAY
RESULT IN DAMAGE TO DRYER COMPONENTS OR PHYSICAL INJURY.
The user’s panel includes an Ethernet and a Serial port which can be used for Modbus communications. The Ether-
net port can be used to access Modbus/TCP registers, as well as, the internal VNC servers across multiple dryers.
The Serial port can access Modbus RTU registers on a single dryer using either RS232 or RS422/485
hardware protocol.
VNC Server
The internal VNC server runs in the back ground by default. Any VNC Client may be used to access the dryer’s VNC
server via port 5900.
Excessive network traffic or network interference may cause the VNC server to intermittently shut down. Rebooting
the HMI via the Service menu or via Modbus register 40101 will restore the VNC Server after reboot.
Ethernet
The Ethernet port is pre-configured to acquire its network IP address and configuration from the network’s DHCP
server. Proper cabling and isolation techniques are required to prevent electrical noise from entering the system
through this port. Contact your local electrical parts distributer for assistance.
The serial port is located along the bottom edge of the HMI. This port supports full RS232, RS422, and RS485 hard-
ware protocols. This port is NOT isolated. Proper cabling and isolation techniques are required to prevent electrical
noise from entering the system through this port. Contact your local electrical parts distributer for assistance.
44
TWP/TWB200 – TWP/TWB9000
45
TWP/TWB200 – TWP/TWB9000
46
TWP/TWB200 – TWP/TWB9000
10069 R Input - Blower Flow Switch 1 = Blower Flow Switch Closed (Active) (Blower Models only)
10071 R Input - Drain Switch #1 1 = drain switch closed (Demand drains only)
10072 R Input - Drain Switch #2 1 = drain switch closed (Demand drains only)
10073 R Input - Over-temp Sense 1 = Over-temp module normal operation
0 = Over-temp module has tripped on high temperature.
Heaters are disabled
10074 R Input - Output Power Sense 1 = Output power is present,
0 = Blown fuse or missing power
10078 R Input - Run/Stop Switch 1 = External Run/Standby Switch set to Standby Position
10079 R Input - Remote Alarm Reset 1 = External contact closure resets Alarms and Restart Dryer
10081 R Alarm - Left Blowdown see separate alarm chart for details
10082 R Alarm - Right Blowdown see separate alarm chart for details
10083 R Alarm - Left Repressurization see separate alarm chart for details
10084 R Alarm - Right Repressurization see separate alarm chart for details
10085 R Alarm - High Purge Temperature see separate alarm chart for details
10086 R Alarm - Low Purge Temperature see separate alarm chart for details
10087 R Alarm - High Over Temperature see separate alarm chart for details
10089 R Alarm - Left Muffler see separate alarm chart for details
10090 R Alarm - Right Muffler see separate alarm chart for details
10091 R Alarm - Low Purge Pressure see separate alarm chart for details
10092 R Alarm - Inlet Temperature see separate alarm chart for details
10093 R Alarm - Inlet Pressure see separate alarm chart for details
10094 R Alarm - High Dewpoint see separate alarm chart for details
10095 R Alarm - Pre-filter see separate alarm chart for details
10096 R Alarm - After-filter see separate alarm chart for details
10097 R Alarm - Blower Motor Overload see separate alarm chart for details
10100 R Alarm - Blower Flow Switch see separate alarm chart for details
10101 R Alarm - Drain #1 Switch see separate alarm chart for details
10102 R Alarm - Drain #2 Switch see separate alarm chart for details
10103 R Alarm - Aux Sensor Input #1 Low see separate alarm chart for details
10104 R Alarm - Aux Sensor Input #1 High see separate alarm chart for details
47
TWP/TWB200 – TWP/TWB9000
48
TWP/TWB200 – TWP/TWB9000
49
TWP/TWB200 – TWP/TWB9000
50
TWP/TWB200 – TWP/TWB9000
40073 R/W Control Setting - Remote Shutdown Set to remotely shutdown the dryer
40074 R/W Control Setting - Remote Standby Set to remotely place the dryer in standby.
40075 R/W Control Setting - Heating Exhaust Limits Enable Default is 1, Heating Exhaust Limits are active
40076 R/W Control Setting - Cooling Exhaust Limits Enable Default is 0, Cooling Exhaust Limits are not active
40077 R/W Control Setting - Enable Inlet Filter Display inlet filter pressure and enable alarm
40078 R/W Control Setting - Store Factory Settings Store copy of settings in PLC
40079 R/W Control Setting - Recall Factory Settings Restore copy of settings in PLC
40080 R/W Control Setting - Dewpoint Sensor Enable Dewpoint sensor is installed
40081 R/W Control Setting - Test Drains Set to fire drains.
40084 R/W Control Setting - Enable Dual Acting Valve Factory Setting - Dryer uses dual acting inlet valves
40085 R/W Control Setting - Enable Pre-Exhaust Outputs Factory Setting - Dryer uses pre-exhaust valves
40086 R/W Alarm Setting - Acknowledge Alarms Set to silence the alarm display and turn off the alarm relay until
next alarm occurs
40087 R/W Alarm Setting - Clear all alarms Reset all alarms, Restarts dryer if it is shutdown.
40088 R/W Alarm Setting - Blowdown Alarm Enabled see separate alarm chart for details
40089 R/W Alarm Setting - Dewpoint Alarm Enabled see separate alarm chart for details
40090 R/W Alarm Setting - Low Inlet Pressure Alarm Enable see separate alarm chart for details
40091 R/W Alarm Setting - High Inlet Temp Alarm Enabled see separate alarm chart for details
40092 R/W Alarm Setting - After-Filter Alarm Enabled see separate alarm chart for details
40093 R/W Alarm Setting - Pre-Filter Alarm Enabled see separate alarm chart for details
40094 R/W Alarm Setting - Repressurization Alarm Enabled see separate alarm chart for details
40095 R/W Alarm Setting - Aux Sensor #1 Low Alarm Enabled see separate alarm chart for details
40096 R/W Alarm Setting - Aux Sensor #1 High Alarm Enabled see separate alarm chart for details
40097 R/W Alarm Setting - Aux Sensor #2 Low Alarm Enabled see separate alarm chart for details
40098 R/W Alarm Setting - Aux Sensor #2 High Alarm Enabled see separate alarm chart for details
40099 R/W User Sensor #1 Input Enable Enables user input # 1
40100 R/W User Sensor #2 Input Enable Enables user input # 1
40101 R/W Control - Reboot HMI Remotely Remotely reboot the HMI, Useful if VNC server shuts down
unexpectedly due to high network traffic
51
TWP/TWB200 – TWP/TWB9000
SHUT DOWN
The dryer should be sufficiently cooled down and allowed to repressurize before shutting down. Allow dryer to run
normally or use the manual stepping feature to proceed to the cooling stage and wait for cooling to end. After the
regenerating tower has sufficiently cooled down, place the dryer into STANDBY.
If the dryer is operating in the heatless backup mode of operation, place the dryer immediately into stand by.
Wait for the dryer to repressurize, then push the emergency stop button and open the main electrical disconnect.
Once the dryer is in STANDBY, the EMERGENCY STOP button can then be used to remove power from the valves,
the heater, and the blower. Open the main electrical disconnect to completely remove power from the dryer.
To put dryer into STANDBY, press the SWITCH TO STANDBY button on the display. The GOING TO STANDBY
message will appear on the screen. If pressed during the heating cycle, the dryer will proceed to cooling for two
minutes. Once the dryer repressurizes, the status message will change to read DRYER IN STANDBY. Both tanks
will be pressurized and the heater will remain off. To restart, press the DRYER IN STANDBY button on the display.
The regeneration cycle will immediately resume at the point in the regenerating process where the stand by button
was first pressed.
To depressurize the dryer, first follow the appropriate shutdown procedure. Open the dryer bypass valve.
Close the outlet isolation valve, and then the inlet isolation valve.
Open the manual drain valve on the afterfilter or control air filter to allow full depressurization of the dryer.
Verify all pressure is removed from equipment and power is disconnected before servicing.
If a dewpoint sensor is installed and the dryer will be out of service for an extended period of time, remove the
sensor and place in a safe, dry location. The sensor will be damaged if exposed to prolonged periods of saturated
conditions.
The dryer should be immediately bypassed to prevent loading the desiccant beds while the dryer is out of service.
MAINTENANCE
Use caution when near the dryer and wear eye protection. Hearing protection is recommended. Dryer maintenance
should only be performed by trained personnel. Always shutdown the dryer, relieve all pressure, and disconnect
power before servicing.
Daily
Check the dewpoint of the compressed air system to ensure it is in good operating condition.
Check purge pressure setting (TWP only), proper prefilter drain operation, and verify no back pressure on regenerat-
ing vessel to avoid more serious operating issues.
52
TWP/TWB200 – TWP/TWB9000
Weekly
Check air flow rate, air inlet pressure and temperature are within design specifications of dryer.
Check blower and blower inlet filter. (Blower purge models only).
Semi-annual
Check the condition of the prefilter and afterfilter elements. Verify the differential pressure across the filters.
Replace as needed.
Check desiccant quality. Desiccant from a freshly regenerated bed should be white, dry to the touch and of consis-
tent size and shape. Continuous adsorption and desorption causes the performance level of desiccant to decline
over time. Oil and contaminants causes reduction in the adsorption ability of the desiccant. It is recommended to
replace the desiccant every 3-5 years.
Check exhaust mufflers and verify there is no back pressure in regenerating vessel. If the muffler is clogged, it must
be cleaned or replaced.
Tighten wire connections to heater. Stud terminals should be tightened to a maximum torque of 20 in-lbs while the
bottom nut is supported. Stud terminals that do not have a bussbar or factory installed ring connector should only
be tightened to 9 in-lbs.
Check condition of blower inlet filter element and replace as needed. (Blower purge models only).
Inspect blower drive belt and idler pulley. Replace if needed. (Blower purge models 4000-9000 only).
Annual
Check condition of control air filter element. Replace as needed.
Check condition of all inlet and exhaust switching valves. It is recommended to clean and rebuild the valves to
maintain proper working condition.
Inspect blower head, tensioner, and pulleys for correct operation. (Blower purge models 4000-6000 only.)
53
TWP/TWB200 – TWP/TWB9000
54
TWP/TWB200 – TWP/TWB9000
55
TWP/TWB200 – TWP/TWB9000
PSV1
S7 S2b S8 CV1
PSV2
PI1 PT1 PT2 PI2
CV3
MV3
S5
S1 S3b S4
CV4
PSV1
DETAIL A
SCALE 0.25 : 1
RO1
RO2
S7 S2b S8 CV1
PSV2
PI1 PT1 PT2 PI2
CV3
MV3
PV1
S5
S1 S3b S4
CV4
A PV1
DETAIL A
SCALE 0.25 : 1 PV1
RO1
RO2
PV1
PV1
A
Ra SURFACE FINISH
PV1
PV1
PV1
PV1
56
TWP/TWB200 – TWP/TWB9000
TC6
HT1
D
AV2
DS4
BV3
PT5
CF1
PT3
MV4
PI3
CV5
BV2
PR1 CV6 TC2
AE1 ES2
TC1
TC3
DS2 ES1
S
TC6 OR USED FOR ANY PURPOSE OTHER THAN CONDUCTING BUSINESS WITH PARKER, AND
WILL BE RETURNED AND ALL FURTHER USE DISCONTINUED UPON REQUEST BY PARKER. SCALE
COPYRIGHT IS THE FIRST YEAR INDICATED ON THIS DOCUMENT. ALL RIGHTS RESERVED. 7:100
UNITS
INCHES
PART NUMBER
USE CORRESPONDING TOLERANCES UNLESS OTHERWISE SPECIFIED
TITLE
CONSTRUCTIO
WELDED PARTS AND SHEET METAL PARTS MACHINED PARTS ELECTRI
SALES DRAWINGS SHEET
2 PLACE (.00): ±.01 SIZE DRAWING NUMB
TWP600BY41NNN-MAN
C
FRACTIONS: ± 1/4 ALL TOLERANCES: ± 1/64 3 PLACE (.000): ±.005
2 OF 2
TWP60
ANGLES: ± 3º ANGLES: ± 2º ANGLES ± 1/2~
125
Ra SURFACE FINISH
DS3
AV2
BV3
PT5
DPI1
CV5
PT3
MV4
PI3 TC5
CV5
BV2
CV6 TC2
ES2 MV1
TC1
ES1
S10
DS1
TWP600BY41NNN-MAN REV-
57
125
Ra SURFACE FINISH
TWP/TWB200 – TWP/TWB9000
DESICCANT 25LB BAGS (QTY) AV1, AV2 PDA-1/8-25 (60) PDA-1/8-25 (70) PDA-1/8-25 (88)
FILTER ELEMENTS
COALESCER ELEMENT (QTY) PF1, PF2 JE-CC0800 (1) 6CU51-280 X 1 (1) 6CU51-280 X 1 (1)
PARTICULATE ELEMENT (QTY) AF1, AF2 JE-FC1330-HT (1) 10DS51-280 X 1 (1) 10DS51-280 X 1 (1)
CONTROL AIR FILTER ELEMENT (QTY) CF1 TP2201-PE (1) TP2201-PE (1) TP2201-PE (1)
REPAIR KITS
PRE EXHAUST VALVE REPAIR KIT PV7, PV8 TP7510-P1-RK TP7510-P1-RK TP7510-P1-RK
OUTLET CHK VALVE REPAIR KIT CV1, CV2 TP7431-SWRK TP7431-SWRK TP7431-SWRK
PURGE CHK VALVE REPAIR KIT CV3, CV4, CV5, CV6 TP7410-AB-RK TP7410-AB-RK TP7410-AB-RK
REPLACEMENT PARTS
PURGE CHECK VALVE CV3, CV4, CV5, CV6 TP7410-AB TP7410-AB TP7410-AB
CONTROL SOLENOID VALVE S2A, S2B, S3A, S3B TP8101-1D TP8101-1D TP8101-1D
CONTROL SOLENOID VALVE S1, S4, S7, S8, S9 TP8101-1D TP8101-1D TP8101-1D
58
TWP/TWB200 – TWP/TWB9000
S7 S2b S8
CV1
S1 S3b S4 C
S2a S3a
CV3
CV2
CV1 CV4
DETAIL A
SCALE 1 / 5 MV3
CF1
PR1
CV1 RO1
CV3 MV3 RO2
CV2 CF1
CV4 PR1
S5
PV7 RO1
PV1
CV3 RO2
CV2
CV5
CV4 TC1 PV2
S5
CV6
PV8
A PV2
TC5
CV5 TC3
PV7 PV3 TC2 T
PV1
CV6
TC1 PV2
PV7 TC3
PV1
PV8
PV2
TC5 MATERIAL PROPERTY OF PARKER-HANNIFIN CORPORATIO
THIS DOCUMENT CONTAINS INFORMATION THAT IS CONFIDENTIAL AND PROP
PARKER HANNIFIN, AND IS FURNISHED ON THE UNDERSTANDING THAT THE D
PV3 PV2
TC2 TC4 AND THE INFORMATION IT CONTAINS WILL NOT BE COPIED OR DISCLOSED TO
TC1
OR USED FOR ANY PURPOSE OTHER THAN CONDUCTING BUSINESS WITH PA
WILL BE RETURNED AND ALL FURTHER USE DISCONTINUED UPON REQUEST
COPYRIGHT IS THE FIRST YEAR INDICATED ON THIS DOCUMENT. ALL RIGHTS
PART NUMBER
USE CORRESPONDING TOLERANCES UNLESS OTHERWISE SPE
PV8
ANGLES: ± 3º ANGLES: ± 2º ANGLE
125
Ra SURFA
PV2
TC5
PV3 TC2 TC4
TC6
DS4
HT1
DS3 PT3
AV2 PI3
AF2
AV1 PSV2
PT1 PI2
PLC1
PSV1
PI1 MV2
PT5 MV3
PF1
DS2
ES2
ES1
DS4
AF2
AE1
PSV2
PI2
PLC1
MV2
PT5 MV3
DS2
DS1
PT4
ES2
ES1
MV1
S10
TWP1200FY41NNN-MAN REV-
60
COPYRIGHT IS THE FIRST YEAR INDICATED ON THIS DOCUMENT. ALL RIGHTS RESERVED. 1:20 INCHES
PART NUMBER TITLE
USE CORRESPONDING TOLERANCES UNLESS OTHERWISE SPECIFIED
EXT HEATED 1200 MANUAL DRAWING
WELDED PARTS AND SHEET METAL PARTS MACHINED PARTS
SALES DRAWINGS SHEET REVISION
2 PLACE (.00): ±.01 SIZE DRAWING NUMBER
TWP1200FY41NNN-MAN
C
FRACTIONS: ± 1/4 ALL TOLERANCES: ± 1/64 3 PLACE (.000): ±.005
ANGLES: ± 3º ANGLES: ± 2º ANGLES ± 1/2~ 2 OF 2 -
125
Ra SURFACE FINISH TWP1200FY41NNN-MAN
TWP/TWB200 – TWP/TWB9000
DESICCANT 25LB BAGS (QTY) AV1, AV2 PDA-1/8-25 (120) PDA-1/8-25 (160) PDA-1/8-25 (176)
FILTER ELEMENTS
COALESCER ELEMENT (QTY) PF1, PF2 6CU85-250 X 1 (1) 6CU85-360 X 1 (1) 6CU85-360 X 1 (1)
PARTICULATE ELEMENT (QTY) AF1, AF2 10DS51-280 X 1 (1) 10DS85-250 X 1 (1) 10DS85-250 X 1 (1)
CONTROL AIR FILTER ELEMENT (QTY) CF1 TP2201-PE (1) TP2201-PE (1) TP2201-PE (1)
REPAIR KITS
PRE EXHAUST VALVE REPAIR KIT PV7, PV8 TP7510-P1-RK TP7510-P1-RK TP7510-P1-RK
OUTLET CHK VALVE REPAIR KIT CV1, CV2 TP7441-SWRK TP7441-SWRK TP7441-SWRK
PURGE CHK VALVE REPAIR KIT CV3, CV4 TP7415-AB-RK TP7415-AB-RK TP7421-SWRK
REPLACEMENT PARTS
PURGE CHECK VALVE CV3, CV4, CV5, CV6 TP7415-AB TP7415-AB TP7421-SW
CONTROL SOLENOID VALVE S2A, S2B, S3A, S3B TP8101-1D TP8101-1D TP8101-1D
CONTROL SOLENOID VALVE S1, S4, S7, S8, S9 TP8101-1D TP8101-1D TP8101-1D
61
TWP/TWB200 – TWP/TWB9000
DESICCANT 25LB BAGS (QTY) AV1, AV2 PDA-1/8-25 (232) PDA-1/8-25 (288) PDA-1/8-25 (352) PDA-1/8-25 (456) PDA-1/8-25 (540)
FILTER ELEMENTS
COALESCER ELEMENT (QTY) PF1, PF2 6CU51-280 X 1 (3) 6CU51-280 X 1 (4) 6CU51-280 X 1 (4) 6CU51-280 X 1 (7) 6CU51-280 X 1 (7)
PARTICULATE ELEMENT (QTY) AF1, AF2 10DS85-360 X 1 (1) 10DS85-360 X 1 (1) 10DS51-280 X 1 (3) 10DS51-280 X 1 (4) 10DS51-280 X 1 (4)
CONTROL AIR FILTER ELEMENT (QTY) CF1 TP2201-PE (1) TP2201-PE (1) TP2201-PE (1) TP2201-PE (1) TP2201-PE (1)
REPAIR KITS
INLET VALVE REPAIR KIT PV2, PV3 TP7661-BD-HP-RK TP7661-BD-HP-RK TP7661-BD-HP-RK TP7681-BD-HP-RK TP7681-BD-HP-RK
INLET VALVE ACTUATOR PV2, PV3 TP7631-BD-HP-A TP7631-BD-HP-A TP7631-BD-HP-A TP7681-BD-HP-A TP7681-BD-HP-A
EXHAUST VALVE REPAIR KIT PV1, PV4 TP7631-BD-HP-RK TP7641-BD-HP-RK TP7641-BD-HP-RK TP7641-BD-HP-RK TP7641-BD-HP-RK
EXHAUST VALVE ACTUATOR PV1, PV4 TP7532-B-HP-A TP7542-B-HP-A TP7542-B-HP-A TP7542-B-HP-A TP7542-B-HP-A
PRE EXHAUST VALVE REPAIR KIT PV7, PV8 TP7515-P1-RK TP7520-P1-RK TP7520-P1-RK TP7520-P1-RK TP7520-P1-RK
OUTLET CHK VALVE REPAIR KIT CV1, CV2 TP7461-SWRK TP7461-SWRK TP7461-SWRK TP7481-SWRK TP7481-SWRK
PURGE CHK VALVE REPAIR KIT CV3, CV4 TP7431-SWRK TP7431-SWRK TP7431-SWRK TP7441-SWRK TP7441-SWRK
PURGE CHK VALVE REPAIR KIT CV5, CV6 TP7420-AB-RK TP7420-AB-RK TP7420-AB-RK TP7420-AB-RK TP7420-AB-RK
REPRESS VALVE REPAIR KIT PV5 TP7610-P1-RK TP7615-P1-RK TP7615-P1-RK TP7615-P1-RK TP7615-P1-RK
PURGE STOP VALVE REPAIR KIT S9 TP7615-P1-RK TP7620-P1-RK TP7620-P1-RK TP7620-P1-RK TP7620-P1-RK
REPLACEMENT PARTS
PRE EXHAUST VALVE PV7, PV8 TP7515-P1 TP7520-P1 TP7520-P1 TP7520-P1 TP7520-P1
OUTLET CHECK VALVE CV1, CV2 TP7461-SW TP7461-SW TP7461-SW TP7481-SW TP7481-SW
PURGE CHECK VALVE CV3, CV4 TP7431-SW TP7431-SW TP7431-SW TP7441-SW TP7441-SW
PURGE CHECK VALVE CV5, CV6 TP7420-AB TP7420-AB TP7420-AB TP7420-AB TP7420-AB
CONTROL SOLENOID VALVE S2A, S2B, S3A, S3B TP8101-1D TP8101-1D TP8101-1D TP8101-1D TP8101-1D
CONTROL SOLENOID VALVE S1, S4, S7, S8, S9 TP8101-1D TP8101-1D TP8101-1D TP8101-1D TP8101-1D
SAFETY RELIEF VALVE PSV1, PSV2, PSV3, PSV4 TP7120 TP7120 TP7120 TP7120 TP7130-150
VESSEL MANWAY GASKET AV1, AV2 FM21216-G FM21216-G FM21216-G FM21216-G FM21216-G
62
TWP/TWB200 – TWP/TWB9000
CV1
PV5 CV2
PR1
S7 S2b S8
RO2
CV5 MV3
S1 S3b S4
CF1
S2a S5 S3a
RO1
CV3
PV9
DETAIL A CV4
SCALE 0.2 : 1 S9
CV
PV1
PV2
PV3
CV1
A
PV4
PV5 CV2
PR1
RO2
CV5 MV3
CF1
PROPERTY OF PARKER-HANNIFIN CORPORATION DRAWN BY DATE
MATERIAL
TWP3000FY41NNN-MAN REV-
5/20/2016
THIS DOCUMENT CONTAINS INFORMATION THAT IS CONFIDENTIAL AND PROPRIETARY TO JZ PARKE
RO1 PARKER HANNIFIN, AND IS FURNISHED ON THE UNDERSTANDING THAT THE DOCUMENT
AND THE INFORMATION IT CONTAINS WILL NOT BE COPIED OR DISCLOSED TO OTHERS
GSF DI
LANCA
OR USED FOR ANY PURPOSE OTHER THAN CONDUCTING BUSINESS WITH PARKER, AND
CV3 WILL BE RETURNED AND ALL FURTHER USE DISCONTINUED UPON REQUEST BY PARKER. SCALE
COPYRIGHT IS THE FIRST YEAR INDICATED ON THIS DOCUMENT. ALL RIGHTS RESERVED. 1:25
UNITS
INCHES
14086 U
PART NUMBER TITLE
USE CORRESPONDING TOLERANCES UNLESS OTHERWISE SPECIFIED
PV9 WELDED PARTS AND SHEET METAL PARTS
EXT HEATED 3000 MANUAL DRA
CV4
MACHINED PARTS
SALES DRAWINGS SHEET
2 PLACE (.00): ±.01 SIZE DRAWING NUMBER
TWP3000FY41NNN-MAN
C
FRACTIONS: ± 1/4 ALL TOLERANCES: ± 1/64 3 PLACE (.000): ±.005
ANGLES: ± 3º ANGLES: ± 2º ANGLES ± 1/2~ 1 OF 2
S9 125
Ra SURFACE FINISH TWP3000FY41NNN-MA
CV6
PV1
PV2
PV3
63
PV4
PSV1
TWP/TWB200 – TWP/TWB9000 PT1
AV1
PF1
PI1
TC6
PT2 AV2
HT1 PI2
AE1 MV1
PLC1
ES1
PT3 TC3 PV7
PI3
TC4
PV8
ES2
TC2 PT4
TC5
S10
TC1
PSV1 OR USED FOR ANY PURPOSE OTHER THAN CONDUCTING BUSINESS WITH PARKER, AND
WILL BE RETURNED AND ALL FURTHER USE DISCONTINUED UPON REQUEST BY PARKER. SCALE
COPYRIGHT IS THE FIRST YEAR INDICATED ON THIS DOCUMENT. ALL RIGHTS RESERVED. 1:
PART NUMBER TITLE
USE CORRESPONDING TOLERANCES UNLESS OTHERWISE SPECIFIED
PT1 WELDED PARTS AND SHEET METAL PARTS MACHINED PARTS
SALES DRAWINGS
2 PLACE (.00): ±.01 SIZE
TWP3000FY41NNN-MAN
C
FRACTIONS: ± 1/4 ALL TOLERANCES: ± 1/64 3 PLACE (.000): ±.005
ANGLES: ± 3º ANGLES: ± 2º ANGLES ± 1/2~
125
Ra SURFACE FINISH
AV1
PF1
PI1
TC6 PSV2
PT2 AV2
HT1 PI2
MV1
PLC1
PF2
ES1
TC3 PV7
PV8
ES2
PT5
PT4
TWP3000FY41NNN-MAN REV-
S10
64
TWP/TWB200 – TWP/TWB9000
DESICCANT 25LB BAGS (QTY) AV1, AV2 PDA-1/8-25 (12) PDA-1/8-25 (20) PDA-1/8-25 (24) PDA-1/8-25 (30) PDA-1/8-25 (36) PDA-1/8-25 (48)
FILTER ELEMENTS
COALESCER ELEMENT (QTY) PF1, PF2 JF0320G-6CK (1) JF0320G-6CK (1) JF0430H-6CK (1) JF0650J-6CK (1) JF0650J-6CK (1) JF0900K-6CK (1)
PARTICULATE ELEMENT (QTY) AF1, AF2 JE-FC0350-HT (1) JE-FC0350-HT (1) JE-FC0450-HT (1) JE-FC0625-HT (1) JE-FC0625-HT (1) JE-FC0800-HT (1)
CONTROL AIR FILTER ELEMENT (QTY) CF1 TP2201-PE (1) TP2201-PE (1) TP2201-PE (1) TP2201-PE (1) TP2201-PE (1) TP2201-PE (1)
BLOWER INTAKE ELEMENT BF1 TP1415-E TP1415-E TP1415-E TP1420-E TP1420-E TP1420-E
REPAIR KITS
INLET VALVE REPAIR KIT PV2, PV3 TP7615-P1-RK TP7615-P1-RK TP7620-P1-RK TP7620-P1-RK TP7620-P1-RK TP7620-P1-RK
EXHAUST VALVE REPAIR KIT PV1, PV4 TP7510-P1-RK TP7510-P1-RK TP7515-P1-RK TP7520-P1-RK TP7520-P1-RK TP7520-P1-RK
OUTLET CHK VALVE REPAIR KIT CV1 TP7415-SDX-RK TP7415-SDX-RK TP7420-SDX-RK TP7420-SDX-RK TP7420-SDX-RK TP7420-SDX-RK
PURGE CHK VALVE REPAIR KIT CV3, CV4, CV5 TP7415-AB-RK TP7415-AB-RK TP7415-AB-RK TP7420-AB-RK TP7420-AB-RK TP7420-AB-RK
REPLACEMENT PARTS
INLET VALVE PV2, PV3 TP7615-P1 TP7615-P1 TP7620-P1 TP7620-P1 TP7620-P1 TP7620-P1
EXHAUST VALVE P1, PV4 TP7510-P1 TP7510-P1 TP7515-P1 TP7520-P1 TP7520-P1 TP7520-P1
OUTLET CHECK VALVE CV1 TP7415-SDX TP7415-SDX TP7420-SDX TP7420-SDX TP7420-SDX TP7420-SDX
PURGE CHECK VALVE CV3, CV4, CV5 TP7415-AB TP7415-AB TP7415-AB TP7420-AB TP7420-AB TP7420-AB
CONTROL SOLENOID VALVE S1, S2B, S3B, S4 TP8101-1D TP8101-1D TP8101-1D TP8101-1D TP8101-1D TP8101-1D
DRAIN VALVE S10, S11 TP8002 TP8002 TP8002 TP8002 TP8002 TP8002
MUFFLER, EXHAUST ES1, ES2 TP4215-1 TP4215-1 TP4215-1 TP4220-1 TP4220-1 TP4220-1
FILTER, CONTROL AIR CF1 TP2201-P TP2201-P TP2201-P TP2201-P TP2201-P TP2201-P
SAFETY RELIEF VALVE PSV1, PSV2 TP7105 TP7105 TP7105 TP7105 TP7105 TP7105
PRESSURE GAUGE PI1, PI2, PI3 LP1020 LP1020 LP1020 LP1020 LP1020 LP1020
BACKUP PURGE ORIFICE RO2 TP4118 TP4122 TP4125 TP4128 TP4131 TP4137
FILTER DP GAUGE DPI1, DPI2 2198HX 2198HX 2198HX 2198HX 2198HX 2198HX
PRESSURE TRANSDUCER PT1, PT2, PT3, PT4 TP2451 TP2451 TP2451 TP2451 TP2451 TP2451
TEMPERATURE GAUGE TG1, TG2 LT3250-.25 LT3250-.25 LT3250-.25 LT3250-.25 LT3250-.25 LT3250-.25
65
TWP/TWB200 – TWP/TWB9000
66
TWP/TWB200 – TWP/TWB9000
Blower Purge Spare Parts List (Flow schematic drawing# FS11687) (CONT’D)
REPLACEMENT PARTS (CONT’D)
THERMOCOUPLE TC1,TC2,TC3,TC4,TC5,TC6 TP2082-UNGRD TP2082-UNGRD TP2082-UNGRD
HEATER HT1 TP3618-4 TP3625-4 TP3630-1-60-4
BLOWER BL1 TP1752 TP1740-1 TP1775-1
PRESSURE TRANSDUCER PT1, PT2, PT3, PT4 TP2451 TP2451 TP2451
FLOW SWITCH FS1 DP6060-S-N4-SDB DP6060-S-N4-SDB DP6060-S-N4-SDB
HEATER CONTACTOR C1, C2 ES5050 ES5075 ES5075
BLOWER CONTACTOR MS1 ES5003-5AF ES5003-5AF ES5003-10AF
STARTER OVERLOAD OL ES5001-TF-10.0 ES5001-TF-7.6 ES5001-TF-13.0
HEATER FUSE EF3000 EF3040-F EF3050-F
BLOWER FUSE EF3015 EF3012 EF3020
PLC PLC1 TP2681-PLC-B1200 TP2681-PLC-B1200 TP2681-PLC-B9000
HMI DISPLAY HMI TP2681-HMI-B1200 TP2681-HMI-B1200 TP2681-HMI-B9000
FUSE, 1 AMP F1, F3 EF0100-2-TD EF0100-2-TD EF0100-2-TD
FUSE, 3 AMP F2 EF0300-2-TD EF0300-2-TD EF0300-2-TD
MEMORY CARD TP2681-MEM TP2681-MEM TP2681-MEM
DEWPOINT PROBE AE1 TP2190-1 TP2190-1 TP2190-1
MODELS WITH NEMA 4
NEMA 4 THERMOCOUPLE TC1,TC2,TC3,TC4,TC5,TC6 TP2083-N4 TP2083-N4 TP2083-N4
MODELS WITH OUTDOOR PACKAGE
BLOWER INTAKE ELEMENT BF1
MODELS WITH INSTRUMENTATION OPTION
PRESSURE GAUGE PI4, P5 LP1020 LP1020 LP1020
TEMPERATURE GAUGE TG1, TG2 LT3250-.25 LT3250-.25 LT3250-.25
67
TWP/TWB200 – TWP/TWB9000
68
TWP/TWB200 – TWP/TWB9000
Blower Purge Spare Parts List (Flow schematic drawing# FS11688) (CONT’D)
REPLACEMENT PARTS (CONT’D)
THERMOCOUPLE TC1,TC2,TC3,TC4,TC5,TC6 TP2082-UNGRD TP2082-UNGRD TP2082-UNGRD
VESSEL MANWAY GASKET AV1, AV2 FM21216-G FM21216-G FM21216-G
HEATER HT1 TP3638-4 TP3650-4 TP3660-4
BLOWER BL1 TP1776 TP1796 TP1796
PRESSURE TRANSDUCER PT1, PT2, PT3, PT4 TP2451 TP2451 TP2451
FLOW SWITCH FS1 DP6060-S-N4-SDB DP6060-S-N4-SDB DP6060-S-N4-SDB
HEATER CONTACTOR C1, C2, C3, C4 ES5075 ES5075 ES5075
BLOWER CONTACTOR MS1 ES5003-10AF ES5003-10AF ES5003-10AF
STARTER OVERLOAD OL ES5001-TF-13.0 ES5001-TF-16.0 ES5001-TF-16.0
HEATER FUSE EF3060-F EF3040-F EF3050-F
BLOWER FUSE EF3020 EF3025 EF3025
PLC PLC1 TP2681-PLC-B9000 TP2681-PLC-B9000 TP2681-PLC-B9000
HMI DISPLAY HMI TP2681-HMI-B9000 TP2681-HMI-B9000 TP2681-HMI-B9000
FUSE, 1 AMP F1, F3 EF0100-2-TD EF0100-2-TD EF0100-2-TD
FUSE, 3 AMP F2 EF0300-2-TD EF0300-2-TD EF0300-2-TD
MEMORY CARD TP2681-MEM TP2681-MEM TP2681-MEM
DEWPOINT PROBE AE1 TP2190-1 TP2190-1 TP2190-1
MODELS WITH NEMA 4
NEMA 4 THERMOCOUPLE TC1,TC2,TC3,TC4,TC5,TC6 TP2083-N4-12 TP2083-N4-12 TP2083-N4-12
MODELS WITH OUTDOOR PACKAGE
BLOWER INTAKE ELEMENT BF1
MODELS WITH INSTRUMENTATION OPTION
PRESSURE GAUGE PI4, P5 LP1020 LP1020 LP1020
TEMPERATURE GAUGE TG1, TG2 LT3250-.25 LT3250-.25 LT3250-.25
69
TWP/TWB200 – TWP/TWB9000
70
TWP/TWB200 – TWP/TWB9000
71
TWP/TWB200 – TWP/TWB9000
TROUBLESHOOTING
Power light on, other lights off, dryer does not operate
- Control air valve is closed: open control air valve; check condition of control air filter element.
- No air supply to dryer inlet: connect air supply.
- Dryer in Power Saving State: Disable Dewpoint Demand to go back to a standard timing cycle.
- Regenerating tower will not blow down: dryer not sequencing or in dewpoint demand mode: see above.
- Bad output, solenoid, or exhaust: replace part or correct issue.
- Dryer in heatless backup mode: switch to heated mode and press start button.
- Overtemp shutdown engaged: Check setting and press reset; if overtemp shuts down dryer again
consult factory.
- Thermocouple disconnected or defective: reconnect or replace.
- Purge flow set to low: adjust purge setting to spec (TWP dryers only).
Insufficient Heat
- Low purge flow: adjust purge setting to spec (TWP dryers only).
- Clogged muffler: clean, replace, or remove.
- Moisture load too high: adjust dryer inlet air flow conditions to within spec.
- Defective thermocouple or controller: replace.
72
TWP/TWB200 – TWP/TWB9000
- Air flow through blower is too high: choke off blower manual control valve.
Please note: When factory assistance is required, always provide serial number, model number, and full
description of problem.
73
TWP/TWB200 – TWP/TWB9000
TECHNICAL SPECIFICATIONS
Mod- Ca- Min PSI Air In/Out Air In/Out Power FLA Heater Blower Dryer LBS Operating
el pacity Size Connec- KW HP Avg Desiccant Weight
SCFM tion KW per Vessel LBS
200 200 80 1 1/2 IN NPT 240/1/60 11.4 6 0.75 2.7 150 1500
300 300 80 1 1/2IN NPT 460/3/60 12.5 6 1.5 4.3 235 1900
400 400 80 2 IN NPT 460/3/60 16.7 9 1.5 5.5 300 2180
500 500 80 2 IN NPT 460/3/60 21.5 12 3 7.4 375 2840
600 600 80 2 IN NPT 460/3/60 21.5 12 3 8.5 450 3420
800 800 80 2 IN NPT 460/3/60 29.1 15 5 11.9 600 4490
1000 1000 80 3 IN FLG 460/3/60 32.8 18 5 14.2 725 5700
1200 1200 80 3 IN FLG 460/3/60 39.0 25 4 16.1 850 6300
1500 1500 80 3 IN FLG 460/3/60 48.6 30 7.5 21.3 1100 7165
2000 2000 80 4 IN FLG 460/3/60 58.2 38 7.5 27.3 1500 9850
2600 2600 80 4 IN FLG 460/3/60 75.6 50 10 35.6 1900 12210
3000 3000 80 6 IN FLG 460/3/60 87.7 60 10 40.3 2200 12650
4000 4000 80 6 IN FLG 460/3/60 122.7 85 15 54.6 2900 18910
5000 5000 80 6 IN FLG 460/3/60 147.1 100 20 68.8 3600 21590
6000 6000 80 6 IN FLG 460/3/60 171.1 120 20 80.7 4400 24890
7500 7500 80 8 IN FLG 460/3/60 212.9 150 25 100.8 5700 29490
9000 9000 80 8 IN FLG 460/3/60 CF 180 40 125.7 6750 34080
Design Conditions of 100 psig at 100°F inlet air, 40° to 100°F ambient air.
To obtain dryer capacity at different operating conditions, multiply nominal capacity X temperature correction
factor X pressure correction factor.
74
TWP/TWB200 – TWP/TWB9000
Design Conditions of 100 psig at 100°F inlet air, 40° to 100°F ambient air
To obtain dryer capacity at different operating conditions, multiply nominal capacity X temperature correction factor X pressure correction factor
Maximum Inlet Temperature °F 90 95 100 105 110 115 120
Temperature Correction Factor 1.17 1.15 1.00 0.87 0.76 0.66 0.58
ENG-DFVS-SPECS-P
rev
75
Worldwide Filtration Manufacturing Locations
North America Europe Asia Pacific
Compressed Air Treatment Compressed Air Treatment Australia
Castle Hill, Australia
Gas Separation & Filtration Division domnick hunter Filtration & Separation +61 2 9634 7777
Airtek/Finite/domnick hunter/Zander Gateshead, England www.parker.com/australia
Lancaster, NY +44 (0) 191 402 9000
716 686 6400 www.parker.com/dhfns China
www.parker.com/faf Shanghai, China
Parker Gas Separations +86 21 5031 2525
Balston Etten-Leur, Netherlands www.parker.com/china
Haverhill, MA +31 76 508 5300
978 858 0505 www.parker.com/dhfns India
www.parker.com/balston Chennai, India
Hiross Zander +91 22 4391 0700
Essen, Germany www.parker.com/india
Engine Filtration +49 2054 9340
www.parker.com/hzfd Parker Fowler
Bangalore, India
Racor
+91 80 2783 6794
Modesto, CA Padova, Italy
www.johnfowlerindia.com
209 521 7860 +39 049 9712 111
www.parker.com/racor www.parker.com/hzfd Japan
Holly Springs, MS Tokyo, Japan
+81 45 870 1522
662 252 2656 Engine Filtration &
www.parker.com/japan
www.parker.com/racor Water Purification
Korea
Racor Hwaseon-City
Hydraulic Filtration Dewsbury, England +82 31 359 0852
+44 (0) 1924 487 000 www.parker.com/korea
Hydraulic & Fuel Filtration www.parker.com/rfde
Metamora, OH Singapore
419 644 4311 Racor Research & Development Jurong Town, Singapore
www.parker.com/hydraulicfilter Stuttgart, Germany +65 6887 6300
+49 (0)711 7071 290-10 www.parker.com/singapore
Laval, QC Canada
450 629 9594 Hydraulic Filtration Thailand
www.parkerfarr.com Bangkok, Thailand
Hydraulic Filter +66 2186 7000
Velcon
Arnhem, Holland www.parker.com/thailand
Colorado Springs, CO
+31 26 3760376
719 531 5855
www.parker.com/hfde
www.velcon.com
Urjala, Finland Latin America
+358 20 753 2500 Parker Comercio Ltda.
Process Filtration Filtration Division
Sao Paulo, Brazil
domnick hunter Process Filtration Condition Monitoring
Parker Kittiwake +55 12 4009 3500
SciLog www.parker.com/br
West Sussex, England
Oxnard, CA
+44 (0) 1903 731 470 Pan American Division
805 604 3400
www.kittiwake.com Miami, FL
www.parker.com/processfiltration
305 470 8800
Water Purification Process Filtration www.parker.com/panam
domnick hunter Process Filtration
Village Marine, Sea Recovery, Parker Twin Filter BV
Horizon Reverse Osmosis Birtley, England Africa
Carson, CA +44 (0) 191 410 5121 Aeroport Kempton Park, South Africa
310 637 3400 www.parker.com/processfiltration +27 11 9610700
www.parker.com/watermakers www.parker.com/africa
© 2016 Parker Hannifin Corporation. Product names are trademarks or registered trademarks of their respective companies. Publication: MAN-TWPB-AB
Rev 000 NA 07/2016