10/12/23, 9:26 AM IEC 60502-1 Cables|Low Voltage Cables|600/1000V, PVC Insulated Cables according to IEC 60502-1 (armoured)|CE-mark
Home About Us Products Download Technical Lib Contact Enquiry Sitemap Links
https://www.caledonian-cables.net/Other_Standards/IEC_60502-1_Cable/PVC_Insulated_IEC_60502-1(armoured).htm 1/4
10/12/23, 9:26 AM IEC 60502-1 Cables|Low Voltage Cables|600/1000V, PVC Insulated Cables according to IEC 60502-1 (armoured)|CE-mark
IEC 60502-1 Cables
Alarm & Audio & Electronic 600/1000V, PVC Insulated 600/1000V, XLPE Insulated XLPE Insulated and Lead Sheathed more
Cables Cables Cables Cables
Automotive Cables IEC 60502-1 Cables
600/1000V, PVC Insulated Cables according to IEC 60502-1 (armoured)
Airport Cables
Application:
Aerial Bundled Cables
IEC 60502-1 cables are used for electricity supply in low voltage installation system, IEC 60502-1 cables are
Belden Equivalent Cables suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations,
Bus Cables local energy distributions, industrial plants, where there is no risk of mechanical damage.
Coaxial Cables Construction:
Cables for Oil Industry Conductors:
Control Cables Copper or Aluminium conductor, round standed or Shaped,
Class 2 to IEC 60228, BS EN 60228. For smaller sizes, a solid round conductor,
Composite Cables
Class 1 as per IEC 60228, BS EN 60228 can also be supplied upon request.
Data Cables
Insulation:
Elevator Cables PVC Insulation material and thickness shall be as per IEC 60502-1 and BS 6346.
Fiber Optic Cables PVC material shall be Type A as per IEC 60502-1 or TI1 as per BS EN 50363.
Flexible Cables PVC Insulation material as per SASO 1694 rated for 85°C continuous operation is also available upon special
Fire Resisting Cables(Fireflix) request.
Colour Code Colour Code (1) :
Fire Retardant Cables(FIRETOX)
1 Core : Red or Black
Flame Retardant Cables 2 Cores : Red, Black
(FIREGUARD) 3 Cores : Red, Yellow, Blue
4 Cores : Red, Yellow, Blue, Black
High Temperature Cables
5 Cores : Red, Yellow, Blue, Black, Green
Highway Cables Above 5 Cores: Black Cores with White numerals
Colour Code (2) :
Instrumentation Cables
1 Core : Brown or Blue
Industrial Cables 2 Cores : Brown or Blue
3 Cores : Brown, Black, Grey
Lan Cables
4 Cores : Blue, Brown, Black, Grey
Mining Cables 5 Cores : Green/Yellow, Blue, Brown, Black, Grey
Above 5 Cores: Black Cores with White numerals
Military Cables
Assembly/Inner Sheath :Two, Three or Four insulated conductors are laid-up together with non-hygroscopic
Medium/High Voltage Cables
fillers and the assembly is bedded with an extruded layer of PVC. In case of non armoured cables, this layer may
NEK606 Offshore & Marine be omitted .
Cables
Armour :Aluminum/Galvanized Steel Wires applied helically over the bedding as per IEC 60502 or as per BS
Marine, OIL,GAS & Petrochemical
5467, BS 6346. Single core cables shall be Aluminium wire armour. Aluminum/Steel Tapes applied helically over
Cables
the bedding of multi-core cables as per IEC 60502.
Power Cables
Outer Sheath:Outer sheath shall be of Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467.
Railway Cables Special type of PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC,
Robotics Sunlight resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such
Rolling Stock Cables as LLDPE, MDPE, HDPE, LSF, CPE are available on request.
Rubber & Crane Cables Fire Performance of Cable Sheaths :Cables can be supplied with special flame retardant PVC outer sheath to
Security Cables comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, can also
supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1, BS 7211, BS 6724 or
Special Cables
other equivalent standards.
Shipboard Cables(JIS)
Cable Parameters:
Spiral Cables
PVC insulation
Submarine Cables Single core( aluminum wire armoured)
Submersible Pump Cables for Oil
Industry
Telephone Cables
Thermocouple Cables
Telecommunication cables
VFD Cables
Windmill Cables
Diameter of Nominal Overall
Nominal Nominal Inner Nominal Alum Nominal Sheath
Other Cabless Conductor Insulation Diameter
Cross Section Covering thickness Wire dia. thickness
(Approx.) thickness (Approx.)
Customized Products mm² mm mm mm mm mm mm
Stock Cables 1x4 2.3 1 1 0.8 1.8 11.5
1x6 2.8 1 1 0.8 1.8 12
Accessories 1x10 3.6 1 1 0.8 1.8 12.8
https://www.caledonian-cables.net/Other_Standards/IEC_60502-1_Cable/PVC_Insulated_IEC_60502-1(armoured).htm 2/4
10/12/23, 9:26 AM IEC 60502-1 Cables|Low Voltage Cables|600/1000V, PVC Insulated Cables according to IEC 60502-1 (armoured)|CE-mark
1x16 4.5 1 1 0.8 1.8 13.7
1x25 5.6 1.2 1 0.8 1.8 15.2
BS 5308 Cables 1x35 6.7 1.2 1 1.25 1.8 17.2
1x50 8 1.4 1 1.25 1.8 18.9
PAS 5308 Cables
1x70 9.4 1.4 1 1.25 1.8 20.3
BS 5467 Cables 1x95 11 1.6 1 1.6 1.8 23
1x120 12.4 1.6 1 1.6 1.8 24.4
BS 6724 Cables
1x150 13.8 1.8 1 1.6 1.8 26.2
BS 6346 Cables 1x185 15.3 2 1 1.6 1.9 28.2
1x240 17.5 2.2 1 1.6 1.9 31
BS 7211 Cables
1x300 19.5 2.4 1 2 2.1 34.4
BS 8573 Cables 1x400 22.6 2.6 1.2 2 2.2 38.6
1x500 25.2 2.8 1.2 2 2.3 41.8
1x630 28.3 2.8 1.2 2.5 2.4 46.2
IEC 60502-1 Cables Two cores(Galvanized steel wire armoured)
En 50288-7 Cables
NF M 87-202
Diameter of Nominal Overall
Nominal Nominal Inner Nominal Steel Nominal Sheath
Conductor Insulation Diameter
Cross Section Covering thickness Wire dia. thickness
(Approx.) thickness (Approx.)
mm² mm mm mm mm mm mm
2x2.5 1.8 0.8 1 0.8 1.8 14
2x4 2.3 1 1 1.25 1.8 16.7
2x6 2.8 1 1 1.25 1.8 17.7
2x10 3.6 1 1 1.25 1.8 19.3
2x16 4.5 1 1 1.25 1.8 21.1
2x25 5.6 1.2 1 1.6 1.8 24.8
2x35 6.7 1.2 1 1.6 1.8 27
2x50 8 1.4 1 1.6 1.9 30.7
2x70 9.4 1.4 1 2 2.1 34.5
2x95 11 1.6 1.2 2 2.2 39.2
2x120 12.4 1.6 1.2 2 2.3 42.2
2x150 13.8 1.8 1.2 2.5 2.5 47.2
2x185 15.3 2 1.4 2.5 2.6 51.6
2x240 17.5 2.2 1.4 2.5 2.8 57.2
2x300 19.5 2.4 1.6 2.5 3 62.8
2x400 22.6 2.6 1.6 2.5 3.2 70.3
Three cores(Galvanized steel wire armoured)
Diameter of Nominal Overall
Nominal Nominal Inner Nominal Steel Nominal Sheath
Conductor Insulation Diameter
Cross Section Covering thickness Wire dia. thickness
(Approx.) thickness (Approx.)
mm² mm mm mm mm mm mm
3x2.5 1.8 0.8 1 0.8 1.8 14.5
3x4 2.3 1 1 1.25 1.8 17.4
3x6 2.8 1 1 1.25 1.8 18.4
3x10 3.6 1 1 1.25 1.8 20.2
3x16 4.5 1 1 1.6 1.8 22.8
3x25 5.6 1.2 1 1.6 1.8 26
3x35 6.7 1.2 1 1.6 1.9 28.5
3x50 8 1.4 1 2 2 33.3
3x70 9.4 1.4 1.2 2 2.1 37
3x95 11 1.6 1.2 2 2.3 41.6
3x120 12.4 1.6 1.2 2.5 2.4 45.9
3x150 13.8 1.8 1.4 2.5 2.6 50.4
3x185 15.3 2 1.4 2.5 2.7 54.8
3x240 17.5 2.2 1.5 2.5 2.9 61.2
3x300 19.5 2.4 1.6 2.5 3.1 66.8
3x400 22.6 2.8 1.6 3.15 3.4 76.7
3x500 25.2 2.8 1.8 3.15 3.7 83.6
Three cores+1(Galvanized steel wire armoured)
https://www.caledonian-cables.net/Other_Standards/IEC_60502-1_Cable/PVC_Insulated_IEC_60502-1(armoured).htm 3/4
10/12/23, 9:26 AM IEC 60502-1 Cables|Low Voltage Cables|600/1000V, PVC Insulated Cables according to IEC 60502-1 (armoured)|CE-mark
Diameter of Nominal Overall
Nominal Nominal Inner Nominal Steel Nominal Sheath
Conductor Insulation Diameter
Cross Section Covering thickness Wire dia. thickness
(Approx.) thickness (Approx.)
mm² mm mm mm mm mm mm mm mm
3x10 +6 3.6 2.8 1 1 1 1.25 1.8 21.9
3x16 +10 4.5 3.6 1 1 1 1.6 1.8 24.2
3x25 +16 5.6 4.5 1.2 1 1 1.6 1.8 27.9
3x35 +16 6.7 4.5 1.2 1 1 1.6 1.9 30.8
3x50 +25 8 5.6 1.4 1.2 1 2 2 36.4
3x70 +35 9.4 6.7 1.4 1.2 1.2 2 2.1 40.1
3x95 +50 11 8 1.6 1.4 1.2 2.5 2.3 46.3
3x120 +70 12.4 9.4 1.6 1.4 1.4 2.5 2.4 50.3
3x150 +70 13.8 9.4 1.8 1.4 1.4 2.5 2.6 55
3x185 +95 15.3 11 2 1.6 1.4 2.5 2.7 60.3
3x240 +120 17.5 12.4 2.2 1.6 1.6 2.5 2.9 67
3x300 +150 19.5 13.8 2.4 1.8 1.6 3.15 3.1 74.6
3x400 +185 22.6 15.3 2.6 2 1.8 3.15 3.4 84.1
3x500 +240 25.2 17.5 2.8 2.2 2 3.15 3.7 91.8
Four cores(Galvanized steel wire armoured)
Diameter of Nominal Overall
Nominal Nominal Inner Nominal Steel Nominal Sheath
Conductor Insulation Diameter
Cross Section Covering thickness Wire dia. thickness
(Approx.) thickness (Approx.)
mm² mm mm mm mm mm mm
4x4 2.3 1 1 1.25 1.8 18.5
4x6 2.8 1 1 1.25 1.8 19.7
4x10 3.6 1 1 1.25 1.8 22.3
4x16 4.5 1 1 1.6 1.8 24.5
4x25 5.6 1.2 1 1.6 1.9 28.2
4x35 6.7 1.2 1 1.6 2 31.1
4x50 8 1.4 1 2 2.1 36.7
4x70 9.4 1.4 1.2 2 2.3 40.4
4x95 11 1.6 1.2 2.5 2.5 46.6
4x120 12.4 1.6 1.4 2.5 2.6 50.6
4x150 13.8 1.8 1.4 2.5 2.7 55.3
4x185 15.3 2 1.4 2.5 2.9 60.6
4x240 17.5 2.2 1.6 2.5 3.1 67.3
4x300 19.5 2.4 1.6 3.15 3.4 74.9
4x400 22.6 2.6 1.8 3.15 3.7 84.4
4x500 25.2 2.8 2 3.15 3.9 92.1
Home | Caledonian company profile| Products | Enquiry | Download | Technical Lib | Sitemap | Links | Fireproof Cables |