0 ratings0% found this document useful (0 votes) 79 views15 pagesSGP Diploma
Switch gear and protection
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
also used for protection of transmission lines and feeders with slight;
The modifications are required to cope with the protection problems
greater length of lines. Further differential protection can ea used, Bit itb
expensive for longer lines due to greater length of pilot wires required.
The protection of bus-bars is very important since they form a vital part of the:
system.
Necessity : Bus bar protection is needed for the following reasons :
(a) In case of fault on a bus bar, the fault current and power may be very large ani
cause serious damage to the system.
(©) Faulton bus bars may affect continuity of power supply and cause d
of power to a large portion of the system
(c)
The stability of the system is affected by fault in bus zone.
In the case of large
Power systems protection
faulty sections are
of bus bar sections is necessary $0
solated before the fault Spreads over the whole system.
For the purpose of protectiion,
tof causes for bus-zone faults.
too (a) Failure of support insulator resulting in earth fault
less
{b) Flash over across support insulator duting over voltages
tl
he (c) Heavily polluted insulator causing flash over
(a) Failure of connected equipment
a} {e) Due to earth quake, mechanical damage ete.
ply §RUNETYPES OF SCHEMES FOR BUS-BAR PROTECTION a |
There are two main schemes of bus bar protection namely,
1. Differential Protection. 2. Frame Leakage Protection
and
1. Differential Protection : It is based on simple circulating current principle that during
normal load conditions or external fault conditions, the sum of currents entering a bus
jon
equals the sum of those leaving
LC) Generators
hat
ers
all
on
on
Lines
Differential Current Protection of Bus-zone
FIG 5.1:Frame Leakage Protecti:
develops are mostly earth faults, by providing earthed metal barrier s
conductor in the bus structure. With this arrangement every fault that might oe
involve a connection between a conductor and an earthed metal part.
| Outgoing Feeders» the switch g
h the primary of a CT Th
e leakage relay. In the eve
nt of earth ;
ork this rely will Operate. fault o
The aim of any particular arrangement of bus-bars is to achieve sufficient
‘operation, sufficient reliability and minium cost.
The following are the typical bus-bar arrangements.
1. Single bus bars
} 2. Duplicate bus bars.
i tations. The basic scheme
1. Single Busbars : This type of layout is meant only for small st
8 shown in Fig. 5 his and following figure G, C, B and S denote generators
Se os couch ectively while T denotes a step-up
Gitcuit breaker and switch (or isolator) resp
transformer], such a large number of circuit breakers.
Prese t favour
ee Be transformers may, therefore, be a in
yenerator one
i n unit system (where one g
Some cases. The preferred practice © nant ‘oauey atl
it to hv. voltage
former are connected as @ unit f° sof blah ollage cael
ne se ‘
Gear altogether and have only © « bus-barsitbecomes necessary
ected to the
lines conn t cause a complete
€ generators and oa ‘on one section does not
lize the layout so
andis
This ircuit breaker (called bus couplet)
can be done by a¢!
© bus-bar sections sO tied uP
Ui breakers on low voltage side
are shown in Fig: 5:4:cB}
FIG 5.3: Single Bus-bar
Bus Section
Bus Coupler
FIG 5.4: Two Bus-Bar Sections
Bus Section
2. Duplicate Busbars ; In this layout the plant is split into two entirely se
which can be worked at different voltages, if desired. Both Lu and h.v. b
busbars alone may be duplicated, This is the ost flexible layout and is mean
generating and/or transforming stations,
Fig. 5.5 shows this type of layout In the case of a large generating station hé
generators and two Outgoing lines connected through step-up transformers.|
HL Bus a
i
/ 8 fine
Outgoing Lines
FIG 5.5: Duplicate Busbars
DERSTANDING PROTECTION OF TRANSMISSION t
DERS 3 ri
i The transmission lines are used for power transmission over longer distances, so the
type of protective devices used are of different nature. Also, the transmission lines
operate at much higher voltages than the feeders.
The cable feeders are generally used for distribution system and they may operate as
radial feeders or parallel feeders or in a ring main, Before any protection fora particular
feeder can be decided, it is necessary to realize its importance in maintaining supply.
IRE PROTECTION
Pilot relaying schemes are used for the protection of transmission line sections.
In these schemes, some electrical quantities at the two ends of the transmission line are
compared and hence they require some sort of inter connecting channel over which
information can be transmitted from one end to the other. Such an interconnecting1s which are used
anced voltage Principle.
Jating Current Differenti
angement for the circulating CUT
arr
ne at each end. Under healt
1 and circulate in pilot wires,
schematic
Fig. 5.6 shows the Pe
crs ‘are connected in each protected lin aes
: re
fault conditions the secondary currents are eq) 7
Protected Line
Pilot Wires
FIG 5.6: Schematic Diagram of Circulating Current Principle
Under normal conditions and in case of external faults, differential current of
is zero and relay does not operate. During internal faults this balance is distur
differential current flows through the relay operating coils
Fig. 5.7 she
# ®:7 shows a schematic diagram of the balanced voltage principle. Ident
are connect
bes mt 'n each protected line, one at each end. The pair of C.1's in eae
ected in series with a relay in such a way tl
secondar hat under normal conditio
Ny voltages are equal and in opposition i
., they balance each othe
scheme, current
* does not normally circulate throu
ugh pilot wires.Pilot Wites
OC : Operating Coit
Relay RC : Restraining Coit
Relay
FIG 5.7 : Schematic Diagram of Balanced Voltage Principle
CT's
Pilot Wires
a ‘ae
we SREY
FIG 5.8: Merz-Price Voltage Balance Scheme for all 3-phases of the Line
Under normal conditions and in case of external faults, current entering the line at one
end is equal to that leaving it at the other end. Therefore induced voltages in the
| secondaries of C.T’s are equal and opposite hence no current flows through the relays.
| In case of internal faults, secondary voltages of C.T’s become un equal and circulating
current will flows through the pilot wires and operating coils of the relays.
Fig. 5.8 shows the connections of merz-price voltage balance scheme for all the three
Phases of the line.system can be used for ring mains as well as paral
Pb. 7 tO} This system provides instantaneous protection for one
Disadvantages :
(a) Accurate matching of C.Ts is very essential
(b) If there is a break in the pilo-wire circuit, the system will not opersid
(c)_ This system is very expensive owing to the greater length of pilot wires
(a) The system does not Provide back up protection or over load Protection.
(e) Because of current transformer equality difficulty the system is not used
33 kV,
X71 _ Translay Scheme of Pilot Wire Protection
This system is similar to voltage balance system except that here balance or opposition |
is between the voltages induced in the secondary windings wound on the relay magnets.
and not between the secondary voltages of the line current transformers.
cr, cr
Power Flow Jon}
cB.
Distance protection is widely used protective scheme for the protection of high and
extra high voltage (EHV) transmission and sub-transmission lines.
Vv j
A distance relay measures the ratio ‘7 at relay location which gives the measure
distance between the relay and fault location. The impedance (resistance/repoint of fault.
v
If the ratio Tis less Peng (the impedance of the line section being protected) the
relay will trip instantly. If “7 is greater than Z it indicates that the fault is beyond the
protected line and the relay will not trip.
There are two types of distance relays :
L Definite distance. relay. 2. Time-distance relay,
fe
finite Distance Relay : Application of distance relays for the protection of
transmission lines is shown in Fig. 5.10. G is generating station, substations S}, Sz and
Sq are in series. Let the impedance of line GS; be Z1, $1 Sa be Zp, S2 S3 be Z3. The
relays at G, 51, Sz and $3 are set to operate for impedance less than Z1, Zz, Z3 and Zq
respectively.
zy
(e )
pee
FIG 5.10 : Distance or Impedance Protection
Suppose a fault takes place at point P between Substations Sz and Ss. The total fault
loop impedance from generating station up to fault pointigZ; + Zp +Z, from substation
S; to fault is Zp + Z and from substation Sz to fault is Z. Therefore the relays at generating
station and substation $1 will not operate, but the fault loop impedance for relay at
substation Sp becomes less than Zs (because Z is less than Zs), therefore, relay at
substation Sp will operate. Similarly, in case of fault occurring between S1 and S2y
telay at S; will operate In this manner, instantaneous protection can be obtained for
all conditions of operation,
2. Time Distance Relay : Fig. 5.11 represents a simple power system with time distance
telays at power station and substations A, B and C.FIG 5.11; Time Distance Relay
Fig. 5.12 illustrates the characteristics curves of the relays installed at the
each section. Let there be a fault in between sub-station B and C at point
distance relay at sub-stations B will trip in 0.5 sec. While the relay at sub
at power station will operate in 1.05 and 1.53 sec. respectively. In order
may be cleared by the nearest circuit breaker first the circuit breaker oper
should also be included; and if the current breaker opening time is assumed to’
sec.after its trip contacts energize, the breaker operation time fi
represented by dotted lines for sub-stations A and B.
F
Power Sub-Station ane
on Sub-Station
Station A
B .
FIG 6.12 : Characteristic Curves of the Relays Installed at the Beginning of Each Gail
Further it will be obvious that the distance relays at sub-station A and at power:
ull act as back up relays for fault at point F, Le,, lf the relay at statiog a a
the relay of sub-station A will tip the circuit after 13 sec (including time o
operation) and even relay at substation A fails to operate, then the relay at
station will trip the circuit in 1.53 sec.
10 PROTECTION OF FEEDERS ‘ 2
The feeder means the connecting link between two circuits. The feeder could bet
form of transmission line, short, meclium orlong, or this could be a distributio{a) Radial feeders
(b) Parallel feeders,
(c) Ring mains.
$10.1 Protection of Radial } Feeders b by Time Graded Over Current Protective Relays
The main characteristic of a radial sytem is that power an dow ony
in one direction,
that continuity of
lt
from generator or supply end to the load. It has the disadvantage i
supply cannot be maintained at the receiving end in the event of faul
Time-graded protection of a radial feeder can be achieved
by using definite time relays.
Fig. 5.13 shows the over curren
t protection of a radial feeder by definite time relays
Here a generating station supplies three sub stations. At all substations an over current
relay has been used with a definite minimum time setting. The time setting is such
that it is least for the relay of the last substation and is maximum for that of the
generating station. The relay 4 has an operating time of 0.8 second while for other
relays, time delay is successively increased by 0.4 second. Normally the time delay
step lies between 0.3 sec and 0.5 sec.
ee: = : >
[16 See
a
FIG 5.13: Time Grading for Raidal Feeder
Swann: xx0e oracorme or senor suesie sfesfeudtocaure in the pection GD, then 000 We eeoRa
No. 4 will operate because time of operation of this relay is the mini
only section CD of the system will be isolated. If the relay No. 4 fails to tip
No. 3 wil operate after a tme delay, of 0:4 second Ney after 1.2 second
occurrence of fault
‘The disadvantage of this system is that if there are @ number of feeders in
tripping time for faults near the supply end becomes high (2 seconds in this
main application is in systems where the fault levels at the various locations do not
greatly.
In addition to the discrimination of timings, another important requirement of the
vs that it should posses inverse-time characteristics [¢., mo severe the fault,
quickly the relay should operate. The relays used in a particular system should be
that they should not cross each other no matter what the severity of the fault may}
5.11 PROTECTION OF PARALLEL FEEDERS BY DIRECTIONAL RI
up:
AB:
cp:
When continuity of supply is required two parallel feeders may be installed. Ifa fa
occurs on one feeder, it can be isolated from the system and continuity of supply
be maintained through another feeder.
Feeder-1
Non directional relays
Directional relays
FIG 5.14: Protective Scheme for Parallel Feeder
Fig. 5.14 shows an over current protective scheme for parallel feeders. At the $2
end of the feeders (at A and B), time graded non directional over oil relays
required. The symbol <> indicates a non-directional relay. At the other end of
(at C and D), directional relays (reverse power relays) are required.
The directional relays should be instantaneous type and operate only when P
flows in the reverse direction ie,, in the direction of arrow at C and D.Fa
B until its over load relay
'y Operates
thus completely isolatin ipplying
g the faulty feeder and su
_ power through healthy feeder. This method of protection is satisfactory when fault
is heavy.
and trips the circuit breaker,
Necessity of Directional Over Current Relays at C and D : If non-directional relays
are used at C and D, both relays placed at C and D will trip for a fault at F. This is not
desired as the healthy feeder is also tripped. Due to this very reason relays at C and D
are directional over current relays.
For faults at feeders, the direction of current at A and B does not change and hence:
relays used at A and B are non-directional
ROTECTION OF RING MAIN FEEDERS
AP The system of interconnection between a series of power stations by an alternative
route is called ring main system. In case of damage of any section of the ring, that
section may be disconnected for repairs and power will be supplied from both ends of
the ring, thereby maintaining continuity of supply.
Fig. 5.15 shows an over current scheme for the protection of a ring feeder. Compared.
with radial feeders, the protection of ring feeders is costly and complex.
1.5 Seconds. (05 Second
| 10secona
fiona
1.5 Seconds 0.5 Second
FIG 5.15: Protection of Ring Feeder
In Fig. 5.12, G is the generating station and A, B, C and D are substations. At the
erating station, the power flows only in one direction ie., away from the bus-bars,
Non-directional time lag over load relays are used. At both the ends of the substationsaway from the substation.
In the network shown while going round the ring in the direction
on the further side of each sub-station are set with decreasing time lag re
example, at generating station 2 seconds, at substations A, B, C and D are
sec, 0.5 sec and instantaneous respectively. Similarly when going round the
opposite direction, the relays on the outgoing sides would be as under :
Generating station,
G = 2sec, Substations
D = 15sec.
C = 10sec,
B = 0.5sec and
A = Instantaneous
Suppose a fault occurs at point F. In that case the power is fed into the fault th
two paths ABF and DCF. The relays between B and F & C and F will operate.
way the fault on any section will cause the relays on that section only to operate
the healthy sections shall be operating un interruptedly.
The time grading can not be crosser than 0.33 or 0.5 second and as the
time that can be fed is 2 or 2.5 seconds, the maximum number of sectio
can be protected in this way are six.