Introduction to Doble
Transformer Testing
Doble Engineering Diagnostics
Toolbox
Why do we test?...
Doble Conference 2009 2
To try to prevent this!...
Doble Conference 2009 3
Transformers fail because…
• Transformers are subject to immense stresses
during service – impact, nearby or internal
faults, overloads
• These stresses may cause winding deformation,
core damage, insulation deterioration
• Allowing a transformer to enter service without
detecting these types of problem is risking
catastrophic failure
• An adequate Diagnostics Toolbox allows
condition assessment in a timely manner.
Doble Conference 2009 4
Transformer Condition Assessment...
Doble Test philosophy:
a single test does not tell the whole story
– Review multiple tests to get the “big picture”
– Acceptable test protocol
– Diagnose the transformers condition
– Find the cause and understand the symptoms
– Doble Engineering Diagnostics Toolbox
Doble Conference 2009 5
Identifying Failure Modes…
Transformers fail for two broad reasons:
• Quality of Insulation: something is
contaminated and then flashes over
– Contamination, Corrosion, Wet
• Physical Integrity: something is deformed,
no longer operates within design
specifications and then fails
– Deformed, shorted, broken
Consider which tests you would choose...
Doble Conference 2009 6
Doble Testing Protocol for Transformers
• Power Factor & Capacitance:
– Insulation Deterioration - Winding Distortion
• Excitation Current:
– Core or Winding Problems (open circuit, multiple
core grounds, shorted turns, shorted laminations)
– LTC Problems
– Manufacturing Defects
• High Voltage TTR:
– Shorted Turns - Open Circuits
Doble Conference 2009 7
Doble Testing Protocol for Transformers
(cont.)
• Leakage Reactance:
– Winding Distortion
– Nameplate Impedance Confirmation
• Frequency Response Analysis (SFRA):
– Shorted Turns
– Coil and Core Movement
– Localized Winding Distortion
• Materials Laboratory Analysis:
– Incipient Fault Detection
– Insulation Deterioration
Doble Conference 2009 8
Broad and Narrow Focused Test
– Broad
• Power Factor and Capacitance
• Excitation Current
• TTR (High Voltage and Low Voltage)
• Dissolved Gas Analysis (DGA)
– Narrow
• Sweep Frequency Response Analysis (SFRA)
• Leakage Reactance
These independent diagnostic methods have their place in ascertaining
transformer condition
Doble Conference 2009 9
Power Factor and
Capacitance
The Traditional Doble Test
Power and Distribution Transformers
The Doble Test as applied to transformers is the most comprehensive
tests for insulation assessment
Moisture/Contamination
Doble Test Carbonization
Mechanical Failure
The test technique makes it possible to segregate the specimen into
major components for more effective analysis of test results
Doble Conference 2009 11
Transformer General Types
Power and distribution transformers may be either single-phase
or three-phase
• Two-Winding
• Three-Winding
• Autotransformer (with or without a tertiary winding)
They may be liquid-insulated, gas-insulated, or dry-type
For test purposes, the procedure used depends on the
number of accessible, separate windings
Doble Conference 2009 12
Doble Tests Performed on Transformers
• Power Factor and Capacitance
• Overall Insulation
• High-Voltage windings
• Low-Voltage windings
• Inter-winding
• Bushings
• Main Core Insulation
• Tap Insulation
• Hot-Collar
• Oil
• Other Doble Protocol Tests
• Dielectric loss measurements on arresters
• Single phase Excitation Currents
• Single phase High Voltage TTR tests
• Leakage Reactance (three-phase and per phase)
• Sweep Frequency Response Analysis (SFRA)
Doble Conference 2009 13
Deterioration of Insulation. . .
Basically loss of Dielectric Strength
• Changes in original characteristics:
– Electrical
– Mechanical
– Chemical
• Detected by:
– Destructive Tests
– Non-Destructive Tests
Doble Conference 2009 14
Doble Test Parameters. . .
• Current
• Dielectric Loss
• Capacitance (Total Charging Current)
• Power Factor
• Power Factor Change with Test Voltage
Doble Conference 2009 15
Transformers Overall
Tests Procedures
(Two-Winding)
Doble Conference 2009 16
Transformer Insulation System
For simplicity, transformer
High insulation is grouped into three
Voltage representative insulation
Windings systems
CH
CH
CHL CL
CL CHL
Low Rather than measure all the
Voltage insulation systems together, the
Windings Doble Test allows the testers
to measure them individually.
Doble Conference 2009 17
Core Transformer Winding Details
Doble Conference 2009 18
Physical Representation of 3-Phase
2-Winding Transformer
High-Voltage
Windings
Low-Voltage
Windings
CH CHL CL One of
Core
Leg Three
Phases
Shown
Transformer Tank
Doble Conference 2009 19
Dielectric Representation of 3-Phase
2-Winding Transformer
High
CH
Tank and
CHL Core
CL
Low
Doble Conference 2009 20
Insulation subsystems components
CH - Insulation between the High Voltage
Winding Conductors and Grounded
Tank & Core
– High Voltage Bushings
– Winding Insulation
– Structural Insulating Members
– DETC Insulation
– Insulating Fluid
Doble Conference 2009 21
Insulation subsystems components
CL - Insulation Between the Low Voltage
Winding Conductors and Grounded
Tank & Core
– Low Voltage Bushings
– Winding Insulation
– Structural Insulating Members
– LTC Insulation
– Insulating Fluid
Doble Conference 2009 22
Insulation subsystems components
CHL - Insulation between the High and
Low Voltage Windings
– Winding Insulation Barriers
– Structural Insulating Members
– Insulating Fluid
Doble Conference 2009 23
The Overall Test
Before you start the overall test:
• Short Circuit High Voltage Windings
• Short Circuit Low Voltage Windings
• Disconnect the neutral bushing from ground
CH
CHL
CL
This is one of the most
common sources of error
in test results!
Ensure that the Neutral
Bushing is also shorted and
disconnected from Ground
Doble Conference 2009 24
Two Winding Transformer
H1 H2 H3 High Low
H2 CHL
X2
X1
X0
X1 X2 X3 H1 H3
X3
X0
CH CL
Tank & Core
Doble Conference 2009 25
Two-Winding Transformer
Test Procedure (HV side)
HV Cable
High Low
Tank & Core
Test Set
Ground
Lead
Low Voltage
Guard Lead
I & W Meter
Doble Conference 2009 26
Test No. 1: Measure CH + CHL
ICHL
HV Cable
High Low
ICH
Tank & Core
Test Set
ICH
GST-Ground Ground ICHL
Lead
ICH + ICHL
Low Voltage Lead
Guard
I & W Meter
Doble Conference 2009 27
Test No. 2: Measure CH
ICHL
HV Cable
High Low
ICH
Tank & Core
Test Set
ICH
GST-Guard Ground ICHL
Lead
ICH
Low Voltage Lead
Guard
I & W Meter
Doble Conference 2009 28
Test No. 3: Measure CHL
ICHL
HV Cable
High Low
ICH
Tank & Core
Test Set
ICH
UST Ground ICHL
ICH Lead
ICHL
Low Voltage Lead
Guard
I & W Meter
Doble Conference 2009 29
Test No. 4
Test Summary and Calculated CHL
ILINE4 = ITEST1 - ITEST2
WLINE4 = WTEST1 - WTEST2
%PFLINE4 = 10 * WLINE4 / ILINE4
CAPLINE4 = CAPTEST1 - CAPTEST2
Doble Conference 2009 30
Two-Winding Transformer
Test Procedure (Low side)
HV Cable
High Low
Tank & Core
Test Set
Low Voltage
Lead
Ground Lead
Guard
I & W Meter
Doble Conference 2009 31
Test No. 5: Measure CL + CHL
HV Cable
High Low
ICHL
Tank & Core
Test Set
Low Voltage ICL
GST-Ground Lead
ICL + ICHL Ground Lead
Guard
I & W Meter
Doble Conference 2009 32
Test No. 6: Measure CL
HV Cable
High Low
ICHL
Tank & Core
Test Set
Low Voltage ICL
GST-Guard Lead
ICL Ground Lead
Guard
I & W Meter
Doble Conference 2009 33
Test No. 7: Measure CHL
HV Cable
High Low
ICHL
Tank & Core
Test Set
Low Voltage ICL
UST Lead
ICHL Ground Lead
Guard
I & W Meter
Doble Conference 2009 34
Test No. 8
Test Summary and Calculated CHL
ILINE8 = ITEST5 - ITEST6
WLINE8 = WTEST5 - WTEST6
%PFLINE8 = 10 * WLINE8 / ILINE8
CAPLINE8 = CAPTEST5 - CAPTEST6
Doble Conference 2009 35
Transformers Overall
Tests Procedures
(Three-Winding)
Doble Conference 2009 36
Dielectric Representation of 3-Phase
3-Winding Transformers
High
CH
CHL
Tank
CHT Low and
Core
CL
CLT
Tert
CT
Doble Conference 2009 37
Comparison between Insulation
subsystems components (2W vs. 3W)
High
CH
Tank
CHL and
Core
CL
Low
High
CH
CHL
Tank
CHT Low and
Core
CL
CLT
Tert
CT
Doble Conference 2009 38
Insulation subsystem components
CH : CL : CT
Insulation between the Winding Conductors
and the Grounded Tank and Core
– Winding Insulation
– High, Low, Tertiary Voltage Bushings
– Structural Insulating Members
– DETC Insulation
– LTC
– Insulating Fluid
Doble Conference 2009 39
Insulation subsystem components
CHL : CHT : CLT
Insulation Between Two Windings or
Inter-winding Insulation
– Winding Insulation Barriers
– Structural Insulating Members
– Insulating Liquid
Doble Conference 2009 40
Three-Winding Transformer
Test procedure (HV side)
HV Cable
Test Set
High
CH
CHL
CL Tank
Low
Low Voltage Lead and
Core
CLT CHT
Low Voltage Lead
Guard Tert
I & W Meter
Ground Lead CT
Doble Conference 2009 41
Test #1: Measure CH+CHL
Test Set HV Cable
High
GST CH
Guard R CHL
Ground B Tank
Low Voltage Lead Low and
ICH + ICHL CL Core
CLT CHT
Low Voltage Lead
Guard Tert
I & W Meter
Ground Lead CT
Doble Conference 2009 42
Test #2: Measure CH
Test Set HV Cable
High
CH
GST
Guard-RB CHL
Low Voltage Lead Tank
Low and
ICH CL Core
CLT CHT
Low Voltage Lead
Guard Tert
I & W Meter
Ground Lead CT
Doble Conference 2009 43
Test #3: Measure CHL
HV Cable
Test Set
High
CH
UST-B
CHL
Ground R
Tank
Low Voltage Lead
Low and
ICHL CL Core
CLT CHT
Tert
Guard Low Voltage Lead
I & W Meter Ground Lead CT
Doble Conference 2009 44
Test No. 4
Test Summary and Calculated CHL
ILINE4 = ITEST1 – ITEST2
WLINE4 = WTEST1 – WTEST2
%PFLINE4 = 10 * WLINE4 / ILINE4
CAPLINE4 = CAPTEST1 – CAPTEST2
Doble Conference 2009 45
Three-Winding Transformer
Test Procedure (LV side)
Rotate Test Leads
Test Set Low Voltage Lead
High
CH
HV Cable CHL
CL Tank
Low and
Core
CLT CHT
Low Voltage Lead
Guard
Tert
I & W Meter CT
Ground Lead
Doble Conference 2009 46
Test #5: Measure CL+CLT
Test Set Low Voltage Lead
High
GST CH
Guard R
Ground B CHL
CL Tank
HV Cable
Low and
ICL + ICLT Core
CLT CHT
Low Voltage Lead
Tert
Guard
I & W Meter
Ground Lead CT
Doble Conference 2009 47
Test #6: Measure CL
Test Set Low Voltage Lead
High
CH
GST
Guard BR CHL
HV Cable Tank
Low and
ICL CL Core
CLT CHT
Low Voltage Lead
Guard
Tert
I & W Meter Ground Lead CT
Doble Conference 2009 48
Test #7: Measure CLT
Test Set Low Voltage Lead
High
CH
UST-B
CHL
Ground R
HV Cable Tank
Low and
ICLT CL Core
CLT CHT
Low Voltage Lead
Guard Tert
I & W Meter Ground Lead CT
Doble Conference 2009 49
Test No. 8
Test Summary and Calculated CLT
ILINE8 = ITEST5 – ITEST6
WLINE8 = WTEST5 – WTEST6
%PFLINE8 = 10 * WLINE8 / ILINE8
CAPLINE8 = CAPTEST5 – CAPTEST6
Doble Conference 2009 50
Three-Winding Transformer
Test Procedure (TV side)
Rotate Test Leads
Test Set Low Voltage Lead
High
CH
CHL
CL
Low Voltage Lead Low
CLT CHT
HV Cable
Guard
Tert
I & W Meter CT
Ground Lead
Doble Conference 2009 51
Test #9: Measure CT+CHT
Test Set Low Voltage Lead
High
GST CH
Guard R CHL
Ground B
CL
Low Voltage Lead
Low Tank
and
ICT + ICHT
Core
CL CHT
HV Cable T
Guard
Tert
I & W Meter CT
Ground Lead
Doble Conference 2009 52
Test #10: Measure CT
Test Set Low Voltage Lead
High
CH
GST
Guard BR CHL
CL
Low Voltage Lead
Low Tank
and
ICT Core
CLT CHT
HV Cable
Guard
Tert
I & W Meter CT
Ground Lead
Doble Conference 2009 53
Test #11: Measure CHT
Test Set Low Voltage Lead
High
CH
UST-B
Ground R CHL
CL
Low Voltage Lead Tank
Low and
ICHT Core
CLT CHT
HV Cable
Tert
Guard
I & W Meter CT
Ground Lead
Doble Conference 2009 54
Test No. 12
Test Summary and Calculated CHT
ILINE12 = ITEST9 – ITEST10
WLINE12 = WTEST9 – WTEST10
%PFLINE12 = 10 * WLINE12 / ILINE12
CAPLINE12 = CAPTEST9 – CAPTEST10
Doble Conference 2009 55
Test #13: Measure CH +CL +CT
HV Cable
Test Set
High
CH
GST
Ground CHL
CL
Low Tank
and
ICH + ICL + ICT
Core
CLT CHT
Tert
Guard
I & W Meter
Ground Lead CT
Doble Conference 2009 56
Transformers Overall
Tests Procedures
(Autotransformers with and
without Tertiary)
Doble Conference 2009 57
Auto-Transformer Without Tertiary
(or Tertiary Winding Not Accessible)
H1 H2 H3
High and Low
H2
X2
H1 X1
X1 X2 X3 H0X0 X3
X0 H3
CH
Tank & Core
Doble Conference 2009 58
Auto-Transformer Without Tertiary
(or Tertiary Winding Not Accessible)
Doble Conference 2009 59
Auto-Transformer With Accessible
Tertiary Winding
H1 H2 H3
High and Low
H2 Tertiary
CHT
X2 Y2
H1 X1
Y3
H0X0 X3
Y2 X1 X2 X3
Y1 H3 Y1 Y3
H0X0
CH CT
Tank & Core
Doble Conference 2009 60
Auto-Transformer With
Accessible Tertiary Winding
Doble Conference 2009 61
Transformers Overall
Tests Procedures
(Safety Considerations)
Doble Conference 2009 62
Apparatus and Personal Safety
• Follow Your Company’s De-Energizing and Safety
Tagging Procedures
• Work Between Installed Safety Grounds
• The Transformer Must be Disconnected From the
Power System
• The Transformer Tank Must Be Properly Grounded
• Do Not Stand on Apparatus While the Test Voltage
is Applied
• Both Doble Test Set Safety Switches Must be
Installed and Operational
Doble Conference 2009 63
Apparatus and Personal Safety
Do Not Hold the High Voltage Cable While Test
Voltage is Applied (Reference: 1995 Paper, Page
1-2.1 David Train & Lawrence Melia).
Doble Conference 2009 64
Transformers Overall
Tests Procedure
(General Considerations)
Doble Conference 2009 65
Transformer Overall Tests
Recommended Doble Power-Factor Test Voltages for
Liquid-Filled Power and Distribution Transformers
Winding Rating L-L (kV) Test Voltage (kV)
12 and Above 10
5.04 to 8.72 5
2.4 to 4.8 2
Below 2.4 1
Doble Conference 2009 66
Transformer Overall Tests
Recommended Doble Power-Factor Test Voltages for Liquid-
Filled Type Power and Distribution Transformers Tested in
the Absence Of Insulating Fluid and Under Atmospheric or
Greater Absolute Pressure
• Determine - by direct measurement - that the Gas space and fluid
contain safe combustible gas levels for testing
• Purge with dry nitrogen to obtain <2% oxygen
• Never apply test voltage to a transformer whose windings are
under vacuum or partial vacuum
• Low test voltage is sufficient to assess the general level of dryness
of a transformer insulation system
• Maintain adequate clearance between all energized, floating and
grounded conductors when testing with some or all of the
transformer leads, core, and coils out of the insulating fluid
• Do not apply test voltages that exceed those recommended for
transformers with the insulating fluid removed
Doble Conference 2009 67
Transformer Overall Tests
Recommended Doble Power-Factor Test Voltages for Liquid-
Filled Type Power and Distribution Transformers Tested in the
Absence Of Insulating Fluid and Under Atmospheric or Greater
Absolute Pressure
Transformer Winding Rating L-L (kV) Test Voltage (kV)
Delta Windings
161 and Above 10
115 to 138 5
34 to 69 2
12 to 25 1
Below 12 0.5
Wye Windings and Single Phase w/ Neutral
12 and Above 1
Below 12 0.5
Doble Conference 2009 68
Transformer Overall Tests
Recommended Doble Power-Factor Test Voltages for
Dry-Type Power and Distribution Transformers
Transformer Winding Rating L-L (kV) Test Voltages (kV)
Delta and ungrounded Wye Windings
Above 14.4 2 and 10
12 to 14.4 2, L-to-G, 10
5.04 to 8.72 2 and 5
2.4 to 4.8 2
Below 2.4 1
Grounded Wye Windings
2.4 and Above 2
Below 2.4 1
Doble Conference 2009 69
Overall Tests Results Analysis
Data Interpretation of Modern Oil-Filled Power
Transformers (percent Power Factor
Temperature Corrected to 20°C)
• Less or equal to 0.5% -- GOOD (acceptable)
• >0.5% up to 0.7% -- DETERIORATED
• >0.7% up to 1.0% -- INVESTIGATE
• Greater than 1.0% -- BAD (unacceptable)
GENERAL GUIDELINES!
Doble Conference 2009 70
Overall Tests Results Analysis
Considering Age and Application
Rating Type New Used
0 - 500 KVA Distribution 1.0% 2.0%
> 500 KVA Power 0.5% 1.0%
For Geometry of the Specimen
Change in Charging Current Rating
0 - 3% G (acceptable)
3 - 5% D (deteriorated)
5 - 10% I (investigate)
10% B (unacceptable)
RECOMMENDED LIMITS!
Doble Conference 2009 71
Other Analysis Considerations
• Previous Test Results (Rate of Change)
• Test Temperatures
• Reason for Test: Acceptance, Routine or
Suspect
• Other Test Results, e.g.
– High P.F. Readings Tip-Up, Lab Results (DGA,
Quality)
– Change in Capacitance LRT and/or SFRA
Doble Conference 2009 72
Example of Analysis for Oil Filled
Power Transformers CH
CH Power Factors for Power Transformers
Number of Transformers
300
240
250
200 180
150 120
100 80
60
50 20 25 20 15
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
% Power Factor at 20 Degrees C
Doble Conference 2009 73
Analysis for Dry Type Transformers
• Limits Are Determined Based on Manufacturer and
Rating
• Based on a Recent Tabulation (1999), the Following
General Guidelines Can Be Used:
Epoxy-Encapsulated
Ventilated Transformers
Transformers
CHL 2.0%
CHL 1.0%
CH 3.0%
CH 3.0%
CL 4.0%
CL 2.0%
Doble Conference 2009 74
Analysis Example
Which transformer would you be more concerned with?
____________________________________________________________
Years 5 10 15 20 25 30
CH %P.F.
#1 .3 .31 .32 .36 .39 .46
#2
.3 .31 .32 .32 .33 .46
Doble Conference 2009 75
Diagnostic Field Testing Standards
• IEEE Std 62 - 1995
– Guide for Diagnostic Field Testing of Electric Power
Apparatus – Part 1: Oil Filled Power Transformers,
Regulators, and Reactors
• Section 3 Definitions (3.6: Power Factor - Dielectric)
• Section 6 Tests and test techniques
– 6.1.2 Ratio/Polarity/Phase
– 6.1.3 Exciting Current
– 6.1.4 Short Circuit Impedance
– 6.1.6 Capacitance, Power Factor, and Dissipation Factor
– 6.3 Insulating Fluids (Transformer-Grade mineral Oil)
– Annex A (informative): Power Factor measurements
Doble Conference 2009 76
Transformers Excitation Current
Test Procedures
Doble Conference 2009 77
Transformer Excitation Current Test
The Doble Excitation Current Test has
been effective in finding:
• Abnormal core grounds
• Winding faults: shorts, open
circuits
• LTC problems
• Manufacturing defects
Doble Conference 2009 78
Excitation Current Principles: No Load
Iexcitation = Imag
mag
+
V1 V2
-
1) When an AC Voltage Source, such as a Doble Test Set, is placed on a
transformer, a small current will flow.
2) This small current is the Magnetizing Current: the current required to
magnetize the Transformer core with the Magnetic Flux mag. This
Magnetizing Current is the Excitation Current we measure and record.
3) This Magnetic Flux will induce a voltage across the secondary
windings: V2
Doble Conference 2009 79
Excitation Current Principles: Load
Iexcitation = Imag + + 2
mag
2 I2
I2
+
V1 V2 R2
-
1) When a Load is placed on the secondary windings a current will flow
I2=V2/R2 [ Ohm’s Law ]
2) The Current I2 will in-turn create an Opposing Magnetic Flux 2.
3) The Generator, which regulates voltage at a set level, will provide more
current to maintain the core magnetized equal to the opposing flux
Iexcitation =Imag + I2
Doble Conference 2009 80
Excitation Current Principals:
Finding a Turn-to-Turn Fault
Imag+ If mag+ fault
HV fault X1
UST H1
E1 + Ifault
- LV
H0 X0
1) If a fault develops in the secondary windings, this fault will act as a
load across the faulted windings drawing a current Ifault
2) As a result, the Excitation Current will go up due to the opposing flux
created by the fault [Φfault]
Result: A Fault will cause Excitation Current to Increase
Doble Conference 2009 81
Excitation Current Principals:
Finding Grounded Windings
mag+ fault
Iexcitation=Imag+ Ifault fault X1 Ground Fault
UST HV H1
+
Ifault
-
LV H0 Xo
Neutral Ground
1) If the secondary winding has a grounded neutral and one of the windings
develops a fault to ground, grounded windings will draw a fault current
2) As a result, the Excitation Current will go up due to the opposing flux created
by the fault [Φfault]
Result: A grounded winding on a transformer with a grounded
neutral will cause the Excitation Current to go up.
Doble Conference 2009 82
Excitation Current Principals:
Effect of Preventive Autotransformer
Iexcitation=Imag+ IAT
mag+ AT
AT X1
UST HV H1
+ IA
-
LV H0 Xo
When an autotransformer is connected across two taps it acts as a
load and the primary current goes up.
Result: When a LTC transitioning device such as a Preventive
Autotransformer is in the bridging position the
excitation current goes up.
Doble Conference 2009 83
Excitation Current Testing
Excitation Current test results present patterns:
• Three Phase Transformers:
– Between phases
(Two Similar Highs and One Low)*
– Within each Phase
(When Tap Changers are present)**
• Single Phase Transformers
– Reverse measurement for confirmation
* There are exceptions
** Pattern will depend on Tap Changer type and Manufacture
Doble Conference 2009 84
Excitation Current: “The Pattern”
In a magnetic core, the Reluctance of the steel acts much
the same to resist magnetic flux as a resistor does to current.
A magnetic core can be represented by a Reluctance Circuit
=
(a) Ferrous Core (b) Reluctance Circuit
Doble Conference 2009 85
Excitation Current: “The Pattern”
For simplicity assume that each section has a reluctance of 1
A 1 B 1 C
1 1
1 1
In this example we have a three Phase three legged core
Doble Conference 2009 86
Excitation Current: “The Pattern”
When you energize Phase A the equivalent reluctance circuit becomes:
P1
P1
HV
HV
3.75
-
P2 P2
A B C
-
The same holds true when you energize Phase C
Doble Conference 2009 87
Excitation Current: “The Pattern”
For Phase B the equivalent reluctance circuit becomes:
P1 P1
HV
B 2.5
-
P2 P2
For our example, phases A and C have equivalent reluctance of 3.75 ; Phase B
has equivalent reluctance of 2.5 confirming the expected pattern of Two Highs
and One Low measurement.
This general pattern holds true for most three phase transformers.
Doble Conference 2009 88
Excitation Current: Test Procedure
• Remove the short-circuit jumpers, these are single
phase tests
• Set up the Test connections on the high side,
observe SAFETY for the other winding(s)
• Proceed according to transformer winding
configuration (Delta or Wye)
• Ground any terminals that are normally grounded
during the test (i.e. neutral on a Wye transformer)
on the winding(s) that are not being energized
• All tests are performed in the UST Mode
Doble Conference 2009 89
Excitation Current: Test Procedure
When Tap Changers are present, test as follows:
Benchmark or Base Measurement: On a Routine Basis:
• LTC only: all positions • NLTC only: as found or position
regularly tapped
• NLTC only: all positions • LTC only: one full range plus neutral
and one position in opposite range
• LTC and NLTC combination: • NLTC and LTC combination:
all LTC positions with NLTC in NLTC in regularly tapped position or as
center position; then all positions found testing the LTC one full range
in NLTC with LTC in neutral plus neutral and one position in opposite
range
Doble Conference 2009 90
Excitation Current: Test Voltage
• Perform tests at the highest Voltage possible
• Test each Phase at the same Voltage
• Perform subsequent tests at the same Voltage for
comparison
• If a Preventive Autotransformer is included in the
transformer, it might not be possible to excite that
position of the LTC. In this event, testing might be
possible with the Preventive Autotransformer bypassed
or at a lower voltage
• If the test set trips, choose a lower Voltage and repeat
all three phases
• Never allow test voltage to exceed rated L-L for Delta
and L-G for Wye
Doble Conference 2009 91
Excitation Current Test Procedure:
Managing field equipment resources
• Be aware of test equipment limitations
• Have consistent procedures
• Document special conditions, be specific
• If the Test set trips, choose a lower Voltage and repeat
all three phases
Example
M4K is rated for 300 mA at 10 kV
10 kV 300 mA
9 kV 333 mA
8 kV 375 mA
7 kV 429 mA
6 kV 500 mA
5 kV 600 mA
Doble Conference 2009 92
Excitation Current Test Procedure:
Test Voltage for Three Phase Units
Remember this:
=
(a) Ferrous Core (b) Reluctance Circuit
Because test must comply with:
• Test at the highest Voltage possible
• Test each Phase at the same Voltage
Phase demanding the highest current should be tested first
Doble Conference 2009 93
Excitation Current Test Procedure:
How to determine Phase B
Doble Conference 2009 94
Excitation Current Test Procedure:
Delta-Connected Winding
HV
H1
UST Test Measure
I1-2 I1-3 1 H1-H2
2 H2-H3
3 H3-H1
H3
H2
LV
When Low Voltage side is Wye configuration, remember to
ground the Neutral
Doble Conference 2009 95
Excitation Current Test Procedure:
Wye-Connected Winding
HV
H1
UST I1-0 Test Measure
1 H1-H0
2 H2-H0
LV H0
3 H3-H0
H2 H3
When Low Voltage side is Wye configuration, remember to
ground the Neutral
Doble Conference 2009 96
Excitation Current Test Procedure:
Single Phase
HV
H1 Two test required
UST Test Measure
I1-0
1 H1-H0
LV H0 2 H0-H1
Remember that the Excitation Current test is the only test where
the short circuit jumpers are taken off the bushings
Doble Conference 2009 97
Excitation Current: Analysis of Test
Results
• Check the pattern: two similar high readings and one
low reading is normal (though there are exceptions)
• When Tap Changers are present, consider the pattern
within the phase
• For three-phase units, compare both high readings
with the following criterion:
– Readings <= 50 mA, difference should not exceed 10%
– Readings > 50 mA, differences should not exceed 5%
• For single phase units both readings should be
compared using the same above criterion
• Compare Normal test to alternate tests; results should
be similar for a winding in good condition
Doble Conference 2009 98
Excitation Current: Analysis of Test
Results
• Compare Normal test to alternate tests; results should
be similar for a winding in good condition
• Compare readings to previous results. Ensure that the
same voltage was used for both tests for consistent
numerical comparison
• If the core is magnetized an irregular pattern (high,
medium, low readings) will be present and you will be
unable to compare results effectively. A true problem
could be masked, therefore core should be
demagnetized and test should be repeated
• If unusual results are obtained, consider performing an
alternate test to further investigate
Doble Conference 2009 99
Transformer Turn Ratio
Measurement Doble Test
Procedures
Doble Conference 2009 100
Transformer Ratio Doble Test
• Turn Ratio of a Transformer is the ratio of the number
of turns in the HV winding to that in the LV winding
• Testing this Turn Ratio is part of recommended test
• Two test methods available:
– Voltmeter method (considered low Voltage test)
– Capacitance & Power Factor method (considered high Voltage
test 10–12 KV)
• Consider both as each identifies different failure modes
• If Tap Changers are present, test must include tap
positions and full winding
Doble Conference 2009 101
Transformer Ratio Doble Test
• This is considered a single phase test
• Special procedures for cases such as inaccessible
neutrals in 3-phase Wye connections units
• Turn Ratio tolerance should be within 0.5% of the
nameplate specification
• For 3-phase Wye connection this tolerance applies to
the phase-to-neutral Voltage (if not in nameplate
calculate by dividing the phase-to-phase voltage by √3)
• Comparison method also applicable
Doble Conference 2009 102
Doble Transformer Turn Ratio
The Doble Method
(considered the HV method)
HV Lead
UST
Doble TTR
CTRUE
Capacitor
IC
CTRUE=
10 kV x
LV Lead
Doble Conference 2009 103
Doble Transformer Turn Ratio:
Single Phase
Doble TTR
Capacitor
HV Lead
UST CTRUE
LV Lead
IC/N
C APPARENT = N= C TRUE / C APPARENT
10 kV x
Doble Conference 2009 104
Doble Transformer Turn Ratio:
3-Phase Delta-Wye
H2 X2
X1
X0
HV Lead
H3
H1 X3
UST
LV Lead
Test No. 1: H1 – H3 to X1 – X0 (Schematic shown)
Test No. 2: H2 – H1 to X2 – X0
Test No. 3: H3 – H2 to X3 – X0
Doble Conference 2009 105
Doble Transformer Turn Ratio:
3-Phase Wye-Delta
H2 X2
X1
H0
HV Lead
H1 H3 X3
UST
LV Lead
Test No. 1: H1 – H0 to X1 – X2 (Schematic shown)
Test No. 2: H2 – H0 to X2 – X3
Test No. 3: H3 – H0 to X3 – X1
Doble Conference 2009 106
Transformer Leakage Reactance
Doble Test
Doble Conference 2009 107
Benefits of Leakage Reactance Test
• Assess physical condition of the
transformer (Geometry of Specimen)
• Investigate Winding Deformations
– Due to through Faults
– Due to rough transportation handling
• Confirm Nameplate Impedance
• Establish Impedance on a per-phase basis
Doble Conference 2009 108
Leakage Reactance Principals
The combined action of both currents results in some of the flux
being present in the unit permeability space
L
The unit permeability space includes the space between the
windings, within the windings & between the windings and the tank
Doble Conference 2009 109
Leakage Reactance Principals:
Leakage Flux
• The “primary” winding is linked by the
magnetizing flux and almost all the leakage flux
• The “secondary” winding is linked by the
magnetizing flux but very little of the leakage
flux
• Therefore the “primary” has a greater Voltage
induced in each of its turns under load than the
“secondary” winding
• We can account for this Voltage drop by
inducing a Leakage Reactance
Doble Conference 2009 110
Leakage Reactance Equivalent Circuit
R DC-1 R L-1 L 1 L 2 R L-2 R DC-2
Lm Rm
E1 CUST E2
Short-Circuit Impedance
R DC-1 R L-1 L 1 L 2 R L-2 R DC-2
E1 Leakage Reactance E2
Doble Conference 2009 111
Leakage Channel
The leakage flux path includes the regions occupied by the windings.
The leakage reactance may be sensitive to deformations in the
windings.
Top yoke
Leakage channel
Outer winding
Core leg
Inner winding
Bottom yoke
Doble Conference 2009 112
Leakage Reactance Equivalent Circuit
• Leakage Reactance for most transformers is constant
• Leakage Reactance can be measured without the
presence of the “full load” leakage flux that requires full
load current
• As in Short Circuit Impedance, Leakage Reactance can
be expressed in Ohms but:
– Can vary over several orders of magnitude
– Values may vary when measured from different sides of the
Transformer
• Preferred expression is in terms of Percent or per unit
(as Impedance in nameplate)
Doble Conference 2009 113
Leakage Reactance and other tests
• Capacitance:
– Sensitive to temperature and contamination
– Normally involves all three phases
• Excitation Current:
– More sensitive to Core problems than winding
deformations
• Leakage Reactance:
– Not sensitive to temperature and contamination
– Can be performed on a Per-Phase basis
– Better sensitivity to winding deformations
– Can compare test results to Nameplate Impedance
Doble Conference 2009 114
Leakage Reactance Test Procedures
Two parts test process:
• Three-Phase Equivalent Test
– LV side short-circuited
– Nameplate confirmation measurement
• Per-Phase Tests
– Corresponding LV side connection short-circuited
(minding your vectors)
– To establish Per-Phase Benchmarks measurements
(less physical area, better focus)
Doble Conference 2009 115
Leakage Reactance Test Procedures
Divided in two steps:
• Initial Test
– Three-Phase Equivalent measurements (for
nameplate confirmation)
– Per-Phase measurements (for individual benchmark
of each phase)
• Subsequent Tests
– Only Per-Phase tests for comparison to established
Benchmark
Doble Conference 2009 116
Test Connections:
(Doble M4000 – M4110)
Doble Conference 2009 117
Measured During Test
• Current (injected and measured)
• Voltage (measured through sensing leads)
• Losses (Watts)
• Power-Factor (Percentage)
• Inductance (Henrys)
• Resistance (Ohms)
• Impedance (Ohms)
• Reactance (Ohms)
All should be consistent in all Phases for all Tests
Doble Conference 2009 118
Test Procedures: Three-Phase
Equivalent Connections
D-Y H1 H2 H3 X1 X2 X3 X0
Instrument
Test 1: H1 – H2 (schematic shown)
Test 2: H2 – H3
Test 3: H3 – H1
No Change on Low Voltage Connections
Doble Conference 2009 119
Test Procedures: Three-Phase
Equivalent Connections
Y-D
X1 X2 X3
H1 H2 H3 H0
Instrument
Test 1: H1 – H2 (schematic shown)
Test 2: H2 – H3
Test 3: H3 – H1
No Change on Low Voltage Connections
Doble Conference 2009 120
Test Procedures: Per-Phase Test
Connections
Y-D H1 H2 H3 H0
X1 X2 X3
Instrument
Test 1: H1 – H0 Short: X1 – X3 (schematic shown)
Test 2: H2 – H0 Short: X2 – X1
Test 3: H3 – H0 Short: X3 – X2
Doble Conference 2009 121
Test Procedures: Per-Phase Test
Connections
D-Y
H1 H2 H3 X1 X X X0
2 3
Instrument
Test 1: H1 – H3 Short: X1 – X0 (schematic shown)
Test 2: H2 – H1 Short: X2 – X0
Test 3: H3 – H2 Short: X3 – X0
Doble Conference 2009 122
Considerations for Leakage Reactance
Test Procedure
• Short circuiting cables (cable jumpers)
– Resistance = < winding leads
– Consider current carrying capacity
– Minimize inductance (minimize the length)
• Tap Changers positions (DETC and/or LTC)
• Test Voltage
– Manufacturers use 2 – 15 % Nominal Voltage
– Field testing at 120 or 240 volts
• Type of Test 1 versus 3
Doble Conference 2009 124
Analysis of Test Results Initial Test
• Purpose of the Initial Test
– 3 Phase Equivalent: Compare With Nameplate
(Factory Test)
– Per-Phase: Establish a Benchmark
• When deviations are found may be related to
– Different instrumentation and test procedures
– Type of test (1 versus 3)
– Winding deformations
Doble Conference 2009 125
Analysis of Test Results Initial Test
• First or Initial 3-Phase Equivalent Test result
should be within ± 3% of Nameplate
• First or Initial Per-Phase Test results should
be within ± 3% of their average
• Winding deformation is unlikely if all three
Per-Phase Test results compare favorably
to each other
• Subsequent Per-Phase Test results should
be within ± 2% of Benchmark
Doble Conference 2009 126
Diagnostic Field Testing Standards
• IEEE Std 62 - 1995
– Guide for Diagnostic Field Testing of Electric Power
Apparatus – Part 1: Oil Filled Power Transformers,
Regulators, and Reactors
• Section 3 Definitions (3.6: Power Factor - Dielectric)
• Section 6 Tests and test techniques
– 6.1.2 Ratio/Polarity/Phase
– 6.1.3 Exciting Current
– 6.1.4 Short Circuit Impedance
– 6.1.6 Capacitance, Power Factor, and Dissipation Factor
– 6.3 Insulating Fluids (Transformer-Grade mineral Oil)
– Annex A (informative): Power Factor measurements
Doble Conference 2009 127
DTA Transformers Tests
Procedures
(Useful tips for DTA users)
Doble Conference 2009 128
Transformer Programs
Doble Conference 2009 129
Transformer Tests
• Overall
• Bushings (C1, C2, Hot Collar)
• Excitation Current
• Doble Turns Ratio
• Turn Ratio
• Leakage Reactance
• Insulating Fluid
• Surge Arresters
From Doble Test Assistant
Doble Conference 2009 130
Transformer Identification Panel
Doble Conference 2009 131
Transformer Identification Panel
Files are Located in Directory C:\doble\dta
Doble Conference 2009 132
Transformer Identification Panel
Doble Conference 2009 133
Transformer Identification Panel
If using the Temperature Sensor DO NOT
Enter the Air Temperature. “Prb” notation
will be shown. When the first test is run the
probe will measure the ambient temperature and
humidity.
Doble Conference 2009 134
Transformer Identification Panel
Items required to be entered to get a proper
temperature correction factor.
Doble Conference 2009 135
Two-Winding Transformer
Overall Test Sheet
Doble Conference 2009 136
Overall Test Temperature Correction
Doble Conference 2009 137
Overall Test Temperature Correction
161
161 kV kV
1.57 0.95
0.41 0.70
Doble Conference 2009 138
Insulation Ratings: Doble Test Assistant
Good condition, acceptable for service until
G the next scheduled test.
Deteriorated. Not as good as before.
D Re-test in a year or less to monitor
insulation condition.
Investigate. Test results show problems
I with the specimen or test procedures.
Perform additional tests or maintenance.
Bad. Not suitable for service.
B Remove from service until condition
is clarified or replace specimen.
Questionable. Nameplate data is incomplete
Q and DTA can not determine rating.
Doble Conference 2009 139
Let’s avoid this!...
Doble Conference 2009 140