Civil Engineers' Guide to Damp Proofing
Civil Engineers' Guide to Damp Proofing
Structure
       11.1 Introduction
             Objdvea
       11.2 Principles of Water Proofing
       11.3 Procedure for Damp Proofing~WaterProofing
       11.4 Dampness and Leakage
             1 1.4.1 Signs of Dampness
             11.4.2 Detection of Dampaess
       11.5 Causes of Dampness
             11.5.1 Condensation
             1 1.5.2 Rain Penchation
             1 1.5.3 Built-in Water
             1 1.5.4 Pipe Leakage
             11.5.5 Spillage
             11.5.6 Seepage
             I 1.5.7 Rising Dampness
             11.5.8 Hygroscopic Salts
       11.6 Prevention of Dampness
             11.6.1 Planning and W i n Stage
             1 1.6.2 Constmction Stage
             1 1.6.3 Remedial Meatjures and Treatment
       11.7 Dampness in Old Structure and Remedial Measures
       11.8 Water Proofing
             1 1.8.1 Integral Water Proofing
             1 1.8.2 SurfaceTreatments
             1 1.8.3 Metallic Water Proofing
       11.9 Different Methods of Waterproofing and Case Studies
             1 1.9.1 Water Proofing Basements
             1 1.9.2 Polyma Plaster for Roof and H m - PROOFSOL
             1 1.9.3 Wat,er Proofing of Roofs -Nina Industries Method
             11.9.4 \V&r Proofing by Algiproothg Method
             1 1.9.5 Case Studies
       11.10 Spectrum of New Water Proofmg MaterialslSystems
       11.11 Summary
       11.12 Answers to SAQs
11.1 INTRODUCTION
You have already learnt about strengthening of stone and brick masonry and about repair
of floors, in previous blocks. Now in this unit, dampness and water leakage in buildings
their causeslreasons and ways and methods to avoidlprevent them is dealt with.
Dampness and water leakages in buildings is a serious concern of Civil Engineers all over
the world. In spite of proper supervision during construction, buildings are still affected
by these problems. Building materials such as bricks, concrete, plaster, timber etc., have a
moisture content which under normal circumstances is no cause for concern. ?be rise in
moisture content of these materials to a level where it becomes visible or when it causes
deterioration is the real dampness.
Objectives
At the end of this unit, you should be able to:
           know methods to detect dampness,
           find the causes for dampness,
           know the methods adopted to prevent dampness, and
Repair & Preventive                 understand the various types of water proofing methods.
Maintenance Techniques
                         Thus you will be able to guide the artisans to take care during construction to avoid
                         dampnegs and provide correct water proofing.
                         Definition
                                                                                                               I
                               Dampness is defiid as presence of moisture in air or on surface or diffused     I
                               tbrough solid. Any indication of slight wetness or moisture is termed as dampness.
I
     The leakage of water from water supply line or drains and trenches. Leakage from a water
     supply line or rainwater pipes or a drainage systems, if not attended to in time, proves to
     be an effective source of dampness. Such leakages should immediately be repaired and
     water collecting near the fault point drained off.
'    11.5.5 Spillage
I
     The spillage of water from industrial and domestic activities is an active source of
     dampness. similarly, waste waters are contributed by dwellings and industrial buildings
I
I
Rep& & Preventive       als?. To check spillage of water, remedial measures like the provision of proper drainagc
MsintenaoceTechniques   should be ensured.
                        11.5.6 1 Seepage
                        The passage of wateran or in the ground through structure wholly or partly laid
                        undergnbund. Seepage in buildings takes place due to passage of water wholly or partly
                        below the ground water. Proper care during construction can make the structure
                        ~eepage~fiee. External and internal drainage systems should be fitted with all possible
                        care.
                        11.5.7 Rising Dampness
                        The sloy rise of water from the ground up into the wallslfloors due to defective or missing
                        damp-proofing coursesltreatments. In the absence of damp-proof course or presence of
                        defectivie damp-proofing material, dampness odcurs internally or externally. In such cases,
                        new              course should replace the old one or building chemicals available in the
                        market $nay be groutedinjected to form a preventive layer.
                        11.5.8 Hygroscopic Salts
                        Hygroscopic salts assist in moisture migration and cause deterioration of the construction
                        materials. In porous construction materials, excess water, accelerates the reaction.
                        Excessive wetting of construction materials should therefore be avoided. Care should 4e
                        taken td ensure that factors responsible for it are checked in advance. AU kinds of
                        dampnetss due to salt should be dealt with by removing the stained plaster. Affected
                        mortar joints should be raked and redone properly with water proofing additives wherever
                        require&
                        Damp~wssassociated with hygroscopic salts can be attributed to the following:
                               i)    Contaminated Sand or Gravel :Presence of salts contaminating sand/gravel
                                     in mortar and concrete mixes.
                               )     Calclum Chlorlde :'Ihe presence of calcium chlpide used as a quick setting
                                     agent in concrete or mortar mixes:
                               iii) Composltlon of Floor :Magnesium oxychloride in floors which have broken
                                     down into chlorides:
                               iv) Industrial Contamlnatlon :The presence of salts from industrial processes;
                               v) Animal Contamlnatlon :The presence of salts from animal waste (either in
                                     stables or indirectly, from leaky drains);
                               vi) Flooding :Large deposits of silt and mud containing salts, brought in by
                                     floods etc.
I   ii)    Water Stops: Special attention is required in respect of water stops provided in
           RCC members. Joints should be perfect with welding. It is preferable to do the
           fabrication on ground and then erect it at site before concreting.
    iii)   Voids in Materials: When different materials are involved like concrete and
           brickwork, brickwork and wood etc. there are possibilities of voids being created
           due to reasons like thermal expansion, variations in the environmental conditions,
           stresses, deflection etc. Once voids are formed, a path of least resistance for the
           passage of water will result. Water entering through the voids corrode the
           reirforcement and further deterioration of concrete takes place.
    iv)    Expansion/Construction Joints: The basic approach required is that of forming
           proper bond to ensure voidfree joints and junctions. In case of construction joints,
           the standard specifications of cleaning the surface and providing a layer of rich
           cement sliury before laying fresh concrete should be strictly followed. The
           importance and the necessity to thoroughly clean the joints and to ensure perfect
           bond must be well understood and specifications meant for the purpose must be
           scrupulously followed. In the case of expansion joints there should be cover over
           the joints location and the gap filled up with proper sealants.
    11.6.3 Remedial Measures and Treatment
    The cure for dampness depends on a correct diagnosis. An experienced and
    knowledgeable person can easily identify the cause and suggest suitable remedial
    measures.
    1) Treatment of Foundation on Poor Soils :Where the subsoil water is not properly
    drained (in clay or peat soil) the structure should be disconnected from the face of the
    ground excavation and a trench made all round for a width of about 60 cm taken down to a
    point at least as low as the underside of the concrete footings. The bed of the trench
    should be provided with a good slope at each end and the trench filled with coke, gravel, or
    stone, graded with fines to fill the voids. An open jointed land drain may be laid at the
    bottom to collect and drain out the sub-soil water. A water proof coat should be given
    outside the structure foundations (on the external face of the walls) and continued through
    the thickness of walls (under the walls over the foundation concrete) and under the floor.
    A 75 mm layer of water proofed cement concrete can be laid all around. Dampness can
    also sometimesbe reduced by leaving out an air gap around the external wall of the
    foundations.
    Where sub-soil drainage has been ignored and necessary precautions have not been taken,
    water will stand above the foundations, and the warmth of the interior of the building
    acting through porous concrete floors will set up suction of moisture which will eventually
    give rise to dampness in the floors and the walls. Where the sub soil water is near the
    ground surface and cannot be lowered by underground drainage owing to the flatness of
    the ground or any other reasons, the height of the plinth should be kept sufficiently high.
    2) Damp-proof Course: One of the following specifications may be adopted for a
    damp-proof course, according to the type of the construction and the nature of the ground :
    i)   Two courses of dense bricks in 1:3 cement mortar :Bricks should have a water
          absorption of not more than40 percent. It is advantageous to leave the vertical
         joints unfilled as moisture rises through the mortar joints.
    ii)  A layer of well burnt brick soaked in hot tar and pitch will suit for low cost
         buildings.
    iii) Non-porous stone slabs 50 mm thick laid for the full width of the walls over a bed
         of cement mortar.
    iv)    Two layers of non-porous slates laid to break joint, each layer being bedded and set
           solidly in cement mortar 1:3.
    v)     12 mm cement plaster 1:3 with water-proofing compound laid above the plinth
           masonry with one or two thick coats of hot coal tar applied over the mortar after the
Rcpsdr Lprrmtlve                     dmtar.has fully dried. Dry sharp sand should be sprinkled over the hot tar. Five
MdatmamceTmbaiqo*a.
                                     permt of Pudlo by weight of cement can be used for water-proofmg the mortar.
                             vi) 40 to 50 m m cement concrete 1:2:4 : Two coats of asphalt or hot coal tar should
                                     be applied over the cement concrete when the concrete has been fully cured and
                                     dri& Mastic asphalt in one or two layers is generally consider4 best where
                                     h#draulic pressure is encountered. The asphalt used should not melt or soften in the
                                     hDttest days and should not get squeezed out due to pressure of the masonry over it.
                             The danlp-proof course should be laid flush with the floor surface and should not be
                             carried m S s doorways or other openings. The upper layer of cement concrete floors
                             should be continued over such openings and should be laid at the same time along the
                             floors. The asphalt or tar layer should be laid under the &mete at the opening. Where
                             concrete is laid on bitumen or tar, the surface of the bitumen or tar must be sprinkled with
                             dry sand.
                             The position of the dampproof course is also an important factor and it should be laid at
                             such a h6ight that it is above the normal level to which water splashes from the ground
                             when it is raining. A damp proof course should not be less than 15 cm above the highest
                             level of tbe ground. In Northern India plinths are usually kept 45 to 60cm above ground
                             level for good buildings under n        d conditions.
                             3) ~reatmenbof Floors: The floors should be laid an some clry ftlling. A hardcore filling
                           - of stones with smaller stones to fill in voids is quite suitable. The filling should be well
                             rammed but wt unduly consolidated. It is considered that a thin layer of cinders and coal
                          ' tar well rammed under a tilkd floor prevents the rise of damp and "kalar" or
                             efflorescence. A Nling of 75 to 150mm of dry coarse sand under the floor masonry is
                             usually s-ed,       but this is suitable for dry locations only. Where there is possibility of
                             moisture penetrating the floor, it will be necessary t? lay a liquid-proof membrane before a
                             concrete goor is laid. P m u s concrete attracts moispe from wet soil. Even dense cement
                             concrete W e d with water proofw compound is not a complete barrier to moisture; the
                             passage of water as liquid may be prevented, but moisture can still reach the top of the
                             concrete as vapour and condense there if an impervious finish covers the surface.
                             4) Treatment of Walls: Rain can penetrate through solid brick walls as there is a limit to
                      '
                             the amount of raiuthat a wall can keep out, moisture is conveyed from the exterior to the
                             interior dqe to the porosity of the bricks. More rapid penetration is through the mortar
                            joints, and an efficient pointing on the exterior will greatly resist the passage of water. Ttae
                             simple flu$h pointing will offer a good protection. Sometimes the soffits of all horizontal
                             courses are slightly throated. Cavity walls afford sound protection and ensure a dry interior
                             even if m o w material is used for outside. The application of a porous rendering on the
                             external surface will do much to prevent direct penetration.
                             A porous finish will absorb water in wet weather and will permit free evaporation when
                             the weather improves. A dense impeqious rendering is less efficient than a porous one as
                             it will more effectively prevent moisture drying out rather than prevent it getting in, and is
                             also more liable to crack A porous rendering is less liable to crack and will not cause the
                             entrapment of moisture within the wall. An external treatment unless it is porous will also
                             be liable b aggravate dampness if it is due to raising ground moisture, indirect penetration
                             of rain or due to diliquescentsalts. A mortar of cement: 1ime:sand in the proportiom of
                             1 2 9 or 1:1:6 is usually recommended.
                             a) Efflorescence: Where soluble salts are present in excessive quantities in the bricks or
                                  the moftar they absorb moisture either from the air or water during cmbruction.
                                 These are brought to the surface in solution and deposited in concentrated patches
                                  either as a white powder or as translucent crystals, as the moisture dries out. Tbis
                                 crystallbe growth either flakes off or is reduced to a powder which can be brushed off.
                                 Attempts to seal back efflorescence are not usually successful and it is advisable to
                                  allow tl$eefflorescepce to expand itself as the wall dries before attempting any
                                 treatmebt at rendering or white washing the walls.
                             b) Lintels and Sills: All soffits or undersides of lintels and sills should be throated. The
                                 mere drafting of a line does not constitute a throating; there should be deep and wide
                                 chase a t in the soffit which should be returned at the ends of the sill. The top of a
                                 window sill should be sloped outwards and weather bar or water bar (of metal) should
                                 be fitted between the stpne sill and the wood sill (or window frame) which will stop
                                  the passage of water passing between the sill and the wood frame.
        c) Widows: Shrinkage of unseasoned wood and importance of properly designed
           window frames should not be ignored. Frames should be so rebated, and which shauld
           be deep enough, as to exclude the weather and afford good protection. Double rebated
           frames are better in severe weather condition. Widows opening outside are
           prefereable. A "hood" of simple form with groove to serve as throating can be fmed
           on the head of the window frame. Where the windows open Wide, the inner sill
           should be made to slope outwards and a small hole kept in the centre passing under the
           window frame through which any water that has penetrated inside the window can
           flow out.
           In places liable to heavy storms it would be advisable tn
           window and door openings instead of simple sun-shades.
                                                                     ,.-    '": Smds over all
                         Regardless of the reasons, once the concrete or plaster has already started leaking only
                         surface treatments a n make it waterproof, without breaking and redoing the substrate.
                         Surface treatments are also provided as a precautionary measure to avoid possible
                         problems that may occur later in the concrete or surface.
                         Water proofing treatments are broadly divided into two categories.
                                 a) Integral water proofing
                                 b) Surfacd treatments.
                         The various types of water proofing are illustrated in this chart.
                                                                                                                                  Water & Damp P m o h g
                                                     WATER PROOFING
                         INTEG~L
                                     r-+                               SURFACE TREATMENTS
                                 I
            ~ e r m e a b i l i ~ Water          I                       I                  I                I
              Reducers Repellanb          BOqdingAgenFI             Capillary       Tar-felts Potymer   protective
                  I                                               Crystallization        Sheeb          Ccltings
*
    11.8.2 Surface Treatments
     Surface treatments are normally done after the concreting and cementing work is
     completed, or even after the completion of the building. The object is to treat the surface
     subsequently,overcoming the defects, and making the surface Oater proof.
     Surface treatments can be broadly classified in the following categories:
     i) Brick Bat Coba and Tiling
     The surface of RCC slab shall be wire brushed and cleaned of all dust and foreign matter
     to lay brick jelly concrete. Brick aggregate shall be obtained from well burnt hard broken
     brick? and shall generally be varying in sizes from 20 mrn to 5 rnm and well graded
     (under-burnt brick shall not be used). Brick aggregate shall be soaked in water for a
     sufficiently long period before mixing with lime. Brick jelly concrete shall be made in the
     proportion-of 1 m3 of brick aggregate to 0.37 m3 of slaked lime. No sand shall be added.
    The brick jelly concrete shall be used when it is quite fresh. Brick jelly concrete shall be
     spread over the slab to the cross-section and the surface shall be formed to slopes as
     required. It is intended that the finished thickness of brick bat coba at the lower ends of
    the slope i.e., at the points where the thickness of coba is minimum, shall be about 20 mm
     and 25 mm. Consolidation shall be done by beating the surface with wooden beaters
    weighing 1to 2 kgs and beating shall be continued till the beaters rebound readily and do
    not make any impression on the surface. During the process of beating, the surface shall
    be constantly kept wet by sprinkling with a mixture of Gur and boiled solution of bael
    fruit. This mixture shall be prepared atleast ten days before it is required.
    After brick jelly concrete has hardened or after 6 days a layer of flat tiles (machine pressed
    tiles) of approved thickness shall be laid in cement mortar 1:3 mixed with crude oil as
    described below. The surface shall be roughened and cleaned of all dust and other foreign
    matter. It shall then be wetted before applying the mortar.
    The flat tiles shall be immersed in water for two hours before being used. The cement and
     sand $hall be first mixed dry. The cement shall be weighed for each mix to ascertain its
    weight in order to fix the quantity of non-volatile crude oil to be added, which should be
     5% of the weight of cement. The dry mixture shall be worked up well with the required
    quantity of crude oil and then water added and the mortar further well worked with the
    trowel. The tile shall be bedded properly in this mortar with joints of about 8 mm to
     10 mm width with their logitudinal lines of joints truely parallel and horizontal and at right
    angles to the transversejoints by less than 5cm. Before the work dries up completely the
    joints shall be raked out and pointed over with cement mortar 1:3, mixed with crude oil.
    (with crude oil being 5% of the weight of cement) prepared as above. The joints shall be
Repair & Preventive   well rapped over with thin bar trowel and the excess of mortar scrapped off until the
Maintem~c~Tdques      surface of the pointing attains a black polish and become hard. The tile work shall be
                      cured for atleast seven days during which period shall be suitably protected from damages.
                      Nowadays instead of brick coba, well burnt brick bats are arranged over the concrete slab
                      of roof providing sufficient slope towards the roof drainage pipes and the Interspaces are
                      filled with CM 1:3 mixed with water proof111g chemicals marketed by different agencies
                      and the top plastered with the same mix and thread lined to avoid surface cracks.
                      ii) Tarfelts/Polyrners Sheets
                      This type of treatment involves the laying of factory-made sheets or felts, which are
                      available in tolls of specific widths. This is laid on the surface over a layer of molten tar,
                      or similar adhesive and over-lapped at the joints. 'Ihe entire surface is thus covered with
                      the sheets. Joints are a vulnerable part of this treatment, apart from the weak bond given
                      by the bitumen. Water which may enter from the joints/punctures, etc., may subsequently
                      cause blistering and puncture of the felts. The use of surface is also restrictive. Further,
                      bitumen, which is a petroleum bi-product, is devoid of necessary oils and plasticisers,
                      which reduces its effectiveness. Weathering, Ultra Voilet (UV)radiation and temperature
                      changes alsol cause deterioration and brittleness of the tarfelt, which results in cracking.
                      The built up membranes are essentially bitumen saturated felts and asphalt or coal tar
                      coatings to ppluce a layered system that protects a structure from water penetration.
                      In a built up membrane system, the felts are used as a reinforcement to stabilise bitumen
                      layers. They provide the strength required to span irregularities in the substrate and to
                      'distribute strains over a greater dimension.
                      Felts are bitumen saturated and include:
                              a) Organic felts made from wood fibre pulp to which scrap paper and small
                                     percentage of rag have been added.
                              b) Inorganic glass fibre felts and glass mats. The organic felts are saturated with
                                     coal tar pitch or asphalt. The glws mat felts are treated with asphalt or coat
                                     tar. The remaining felts are saturated with asphalt.
                      Overheating bihunen during application results in the loss of oils by distillation and
                      produces a ttlin film, when applied, that does not provide adequate cementing action. 'Ihe
                      temperature range for heating coal tar pitch is 325' to 375' F and for asphalt 400' to 430'
                      F;underheating below this range results in a loss of application workability and cementing
                      capability.
                      Single Ply Materials
                      The problem associated with built up membrane systems gave rise to the development of
                      synthetic sheet single ply systems.
                      Sheet membranes are generally available in roll form in various lengths and in widths of
                       lm minimum and thickness of 30 to 60 mil. Joints in single ply systems are made by heat,
                      fusion, torching solvent welding, tacky tapes or adhesives.
                      Single ply Waterproofing materials are costly items and hence are used only in special
                      environment$like U.V., Ozone and high temperature etc.
                              a) weoprene :This is the oldest of the synthetic rubbers having been introduced
                                     in the early 1930. It is based on polymers of chloroprene.
                              b) Ethylene-Propylene-Diene-Monomer(E.P.D.M.) :This synthetic product
                                     is available since about 1963 when it was introduced to overcome some of the
                                     shortcomingsof butly rubber.
                              c) Chlorinated Po$ Ethylene (C.P.E.) : These sheets are available with or
                                     Without polyester reinforcement. 'Ihe weather proofing materials have been
                                     exposed to extremes of weather in Arizona and Florida for over 10 years.
                              d) Polyisobutylene(P.I.B.): It is a waterproofing synthetic material generady
                                     bonded to a non-oven synthetic felt reinforcement that permits installation
                                     using asphalts or contact adhesives.
                              e) Polyvinyl Chloride (P.V.C.) Membrane: It is made of P.V.C resins and
                                     plasticizers apd is available with or without reinforcement. It has been in use
44                                   for over 20 years. Some non r e i n f a d P.V.C will shrink as much as 5%. It
              is not compatible with tar or asphalt. Lap seams are made by solvent welding      Water & Damp Proof&
              and sealing.
       f)     Modifled Bitumen/Laminatesand Composites: In addition to synthetic
              membranes described above, there are proprietory single ply membranes that
              are made by the addition of rubberizing ingredients to asphaltic materials. In
              the manufacture of modified bitumens, a synthetic polymer such as
             polypropylene or styrene butadiene is blended with asphalt. The
              manufacturing process is critical since good dispersion of rubber and bitumen
              is essential, to obtain a good quality single ply membrane. Some products of
              this marriage produce a tacky membrane which allows the materials to be self
              adhering. Others produce combination laminates using polyethelene sheets
              reinforcing materials and aluminium foil in the composites.
iii) Capillary CrystalIization
       This process involves the application of liquid chemicals on the surface of the
       concrete. These chemicals enter the pores of the cmcreteJplaster and there after
       crystalise, thus reducing and seaIing the pores. One major limitation is that the
       concretelplasteris prone to further damage, development of cracks, wear and tear
       and possible leakage.
iv) Protective Surface Coatings
       Waterproofing by the u!! of surface coatings is the latest type of treatment and is
       gaining immense popularity, due to its effectiveness and ease of application apart
       from the economy of use. However, proper care in selecting the adequate treatment
       and its proper application play an important part in effective water proofing.
       Protective coatings are generally based on epoxy, bitumen, rubberised silicons,
       polyurethanes etc.
Liquid agplied systems are available in both single component types and two component
types. They are applied by brush roller, sqeegee, trowel or spraying to form a seamless
waterproofiing membrane. The single component types solidify through evaporation of a
solvent or water or by chemical cure. The two components type solidify by chemical cure.
The Unicormity of thickness and free'dom from bubbles and punching obtained with a
liquid system is a function of the quality of work involved and the surface roughness of the
substrate.
       a) Epoxy coatings have very good bonding properties with the substrate, and
             form an impermeable membrane over the entire surface. Despite their good
              abrasion resistance properties and resistance to mild acids and chemicals,
             epoxies, being rigid in nature, cannot withstand the expansion and contraction
             of the surface and develop cracks. Epoxies are also not recommended for
             external applications due to their weak resistance to Ultravoilet radiation.
             They are also very expensive.
       b) Bitumen based coatings are normally modified with polymers, oils and
             plasticisers and can be considered as an economical method for water
             proofing. The additives only give limited resistance to heat, W , etc and the
             treatment tend to become brittle leading to crack formation.
       c) Rubberised compounds have good elasticity, easily bond with the surface
             and expand and contract without cracking. These compounds, however,
             deteriorate fast with the effects of W and ozone, causing toss of these very
             properties and rendering the system ineffective.
       d) Silicon based emulsion and coatings are colourless coatings which do not
             change the appearance of the surface, while making the surface water
             'repellent. Their biggest drawback is the lack of crack bridging capacity.
             Silicons are thus not suitable for flat terraces or horizontal surfaces. At the
             most they may be used on vertical walls for water repellency.
       e) Polyurethanecoatings are by far the most effective surface coatings
             available. They allow for good adhesion to the substrate, formibg a
             monolithic membrane, which is totally impervious to water and has the
             elasticity to withstand expansion and contraction of the surface. W
             resistance, resistance to mild acids, slats, etc., help polyurethane coatings to
             withstand external forces for long periods.
1:.pa(r & &-el ezd.;vr   11.8.3 Metallic Waterproofing
M:~irknanceTechniques
                         Metallic wart em roof in^! is a system of waterproofing, the interior surface below grade
                         concrete wdlsand floors that may be subject to hydrostatic heads of watt%. It is usually
                         employed ib confined sites or where it is impossible to apply membranes on exterior
                         surfaces as when buildings adjoin one another. The system is built up to about 2mm to
                         4mrn thick and then covered with a ~rotectivecoat of mortar. This method of
                         waterproofing is based on the fact that when water enters the system, the powdered iron
                         expands and prevents the intrusion of water. The mechanical bond of the metallic water
                         proofing to the concrete substrate allows the system to be installed opposite sides from
                         which the hydrostatic water head exists.
                         Any waterproofing system has to be decided based on the following properties:
                                 Liquid system with good bond and penetration,
                                 Monplithic membrane formed over an unlimited area,
                                 Water impermeable,
                                 Good resistance to hydrolysis,
                                Goodl elasticity, preventing cracking and warping,
                                UV resistance,
                                Abrasion resistance permitting normal use and atmospheric corrosion,
                                Resi$tance to algae, mild acids and alkalies, and
                                Easy application and maintenance.
                         For a waterproofing treatment by surface coatings to be successful, it is essential that the
                         application be done with proper care. The substrate should be clean and dry. All algae
                         formations, loose particulates, dust, etc., should be wire brushed and removed before the
                         treatment is applied. Cracks and joints need to be properly detailed as per the
                         specificationsto avoid their re-opening. Application plays as iniportant a part in the
                         success of a treatment as the material itself.
                         The followit.lg sketches furnished below explain the incorrect and correct methodlway of
                         carrying o~d/~rovidiin~  a LeaWDamp Proof construction in buildings/structures:
                         a)     Condrete slab is not cast properly and not provided with slope.
r Correct r b p e
                                                                                         I
                                      k a k a g e s and dampness                             Mftclcnt drainage     I
                                             o a u r here                                    a v o ~ d rleakages
                                              Incorrect                                         Correct
                                                                           Figure 11.1
                                                     4 Seepage  through
                                                        top t c parapet
                                                           Plastered top
                                                            of parapet
                                                                                                               R I P Outlet
                                                                                                               slightly
                                                                                                               belo w to
                                                                      Top prdlle                                   a w ~ drmter
                                                                       of slab                                     stagnattng
                                                                       levelled
                               after the&~"s
                               have stopped
                                                   -
                                          '    lncorrect                                       Correct
c)        Proper construction of parapet wall.                                                                  Water & Damp I'rclofi~rg
and beams
                                                                             ('arrccl
                                                         figure 1 1 3
d)        Proper casting of terrace slab.
     Parapet      v(l"
                                                             -FK         I
                                                                         L----
                                                                               - ---
                                                                              Colum~--l below
                                                                        RWDown-i
                                                                        takepcpe ;
                                                                                          Wall
                                                                                        1--1
                                                                                               I
                                                                                               I
                                                                                                   Terrace
                                                                                        .      !
c r o w e d pcpc n d l i t l i G ~ t
i o m t n l a c n and g e l s
frequently block
                l~~corrcct                                                     COI-I.FF~
                                                        figure 115
f)        Proper sloping of the slablfloor to go into rain water down take pipe.
                                                                        R.C.Coptng,
                                                      BKBAT CQBAIald
                                                      to p r
 underscde of
   slab
          Iscorrect
 Repair & Preventive     g)     Proper casting of slab with full bearing.
,M&tenance Techniques
                                                                          Flpm 11.7
                         h)     Roper casting of verandah slab.
                                   lncorreet                                             Correct
                                                                          R p r e 11.8
                         i)     Leakages through water closets.
                                              Jo~ntrbetween
                                             floor lnnh and
                                Jotnt khveen
                              floor lanrrh and\  I-"
R p r e 11.9
               Leak l
           through f?oorlng
          and Na hanl trap       'm
           Leakage through
            joint between
            wall plecc and
            r1aht angle bend
                                                                                           -
                                                                                    Long G hahanl
                                                                                          trap
             Incorrect                                                              Correct
                                                                                     (a)
                                            Figure 11.11
     Sinks and wash basins.
                                            Figure 11.12
m)   Detail of expansion joint (recommended).
                                Copper
                               plate l 5 m m       l b m m t h ~ e klead flqshlng
                                     \             f lred on one side only
                                                                         fborlng
                                                                         CCBA
                                         Lt.w.~atten fcred on
                                            one scde only
                                                             cbcm th~cktl'oorlng
                                                             fB B CCBA
                                                                 CC Slab
                                            L T.W. Plate f l i e d on
                                                       ow sldc
                                                                      --
                                               Figure 11.13
Repair & Preventive
ilaintenanceTechniques   11.9 DIFFERENT METHODS OF WATER PROOFING
                              AND CASE STUDIES
                         11.9.1 Water Proofing Basements
                         This treatment is provided by the specialist agency. It is necessary to have a water free
                         surface to make the treatment effective. A levelling course of PCC 1:5:10 of 80 mrn thick
                         is laid over a well compacted layer of 150 mm thick sand. The waterproof treatnient is
                         provided above the levelling coufse as indicated below:
                         a)      Cement slurry with special waterproofing chemical compound is applied over
                                 levelling oourse.
                         b)      CM 1:4 layer of 20 mm thick with waterproof compound is laid on the levelling
                                 course.
                         c)      Again cement slurry with waterproof compound is smeared.
                         d)      Then 20 n)m stone aggregate is pressed in CM 1:4 of 25 mm thick mixed with
                                 waterproof compound.
                         e)      Another course of CM 1:4 20 mm thick, with waterproof compound is then laid.
                         f)      One layer d 20130 mm thick shahabad stone slabs are provided with joints pointed
                                 with cement mortar mixed with waterproof compound.
                         g)      Cement slurry with waterproofing compound is again smeared.
                         h)      A plastering course in CM 1:4 with waterproof compound 10115 mrn thick is then
                                 provided.
                         i)      Finally, the surface is finished with cement punning with waterproof compound.
                         The average thiclmess of this treatment is about 100 mm on the floor and 50 mm in the
                         walls. In walls, the treatment is the same except the layer of providing 20 mm stone
                         aggregates in CM is omitted. Before a day's works is commenced, cement slurry mixed
                         with special compound is poured in the joint over the previous day's work after cleaning
                         and washing.
                         11.9.2 Polymer Plasterlfor Roof and Floor - PROOFSOL
                         Concrete material made by partial substitution of binder in cement concrete by polymers is
                         known as polymer modifed mortar and concrete. Mostly polymers in dispersion form
                         (latex or emulsiod) are added to cement mortar or concrete during mixing. Polymer film is
                         formed in cured @lymer modified mortar and concrete and enhances cement aggregate
                         bond.
                         In polymer cement concrete, the chemicals are used in much larger amount and also the
                         polymers in the concrete may supplement the cement in binding the material aggregate.
                         The polymer latex film through its high tensile strength and elongation, effectively holds
                         propagating micro cracks and holds existing micro cracks together. An important aspect
                         of polymer latex modified concrete is its improved durability over conventional concrete.
                         This is partly due to reduced porosity as a result of lower water cement ratio and partial
                         filling of pores by polymer, but existing pores also tend to be sealed by a continuous
                         polymer film.
                         Admixture of PROOFSOL in concrete and mortar making is an additional safeguard to
                         render the concrete and mortar mix waterproof. 2% by weight shall be ample for all
                         normal concreting. PROOFSOL is marketed in the form of powder.
                         Where the surface of wall to be treated is fairly even, two coats of rendering suffice. If the
                         surface is very roqgh and uneven, three coats may be necessary. The first coat should be
                         10 rnm thick being applied to level up the surface.
                         All the joints in thp masonry should be thoroughly raked out. The surface of the wall may
                         be cleaned, washei3 down with water to ensure good key for the rendering. Before
                         applying backing eoat, the wall surface may be made uniformly moist but not dripping
                         wet. A thin coat of neat cement slurry of cream consistency should be applied over small
                         areas at a time just a little ahead with the application of first coat.
                         The first coat coaists of 1 part of cement mixed with 2% of PROOFSOL and 3 parts of
                         clean sand graded 3 mm down. The surface should be made even with a wooden float and
        as soon as it has hardened suficiently, the surface should be combed to provide good bond.     Water & Damp Roofin;
        It should be cured for 48 hours before the application of next coat.
I
        In three coat work, the second one should be similar to the fist one. The finishing coat of
        plqter should be 10 rnrn to 12 mm thick. It should consist of the same mix as the base
        coat, its surface should be rendered even with a wooden float and then f i s h e d smooth
        with steel trowel. The surface should be cured by keeping it continuously wet for about 12
        days.
        Generqlly, a 25 rnm thick plaster with the above water-proofing compound as per the
        directions specified will yield good result.
        Waterproofing Using Epoxy
        The items in sequence are indicated below:
               a)    The surface shall be cleaned by wire brushing
              b)     Bond coat is laid using epoxy resin and epoxy harcbner in ;he propotion of 2: 1
                     and applying on the surface at the rate of 0.5 kglsqm
              c)     A coat of plaster is done within 2 to 2 112 hours with CM 1:4 a d 2 iO 10 mm
                     thick. Curing should be done for not less than 10 days.
              d)     Binder coat1DEBKOT as frnal coat is laid using as above i.e., 2:l and
                     applying on the surface 0.6 kglsqm with an inter layer of fibre glass fabric
    *
                     pieces of specification 30 gmslsqm.
        In case porous concrete grouting is to be done, it is essential to have grouting at the
        constructionjoints. Grouting is to be done using lkg of epoxy resin, 550 gms of epoxy
        hardner and 50 gms of dilutant mixed together, of grouting pressure of 8 kgtsqm or
        refusal. Generally grouting along construction joints will be at 1.5 m etc.
        11.9.3 Water Proofing of Roof - Nina Industries Method
        This consists of providing average 110 mm thick cement base waterproof treatment with
        brick-bat-coba bedding. The steps are
               a) Cleaning the surface.
              b)     Giving a coat of chemical wash mixed with cement.
              c)    Providing all round terrace, small waterproof watts (roundings) as a
                    preliminary.
              d)    Providing 10 mm thick cement mortar pad with admixture.
              e)    Placing brick bats of varying sizes average 75 mm,to a proper slope and
                    grouting their joint with cement mortar and 2% proofsol.
              f)    Providing plain cement concrete paving smooth finished 25mm thick
                    with admixture of proofsol good for common use.
              g)    Providing all around the terrace, large water-proof watts (roundigs) in PCC
                    one foot high above the finished floor level.
              h)    Finishing and curing 14 days.
        11.9.4 Water Proofing by Algiproofing Method
        Algiproof is a wterprooflweatherproofcompound manufactured by Brahmavar Chemicals
        Pvt. Ltd. Brahmavar, Karnataka for use as an intergral cement admixture in all concrete,
        mortars, including guniting and cement pressure grouting work. Algiproof is essentially a
        dry chemical powder and has to be dissolved in water to prepare the stock solution atleast
        10-12 hours prior to its actual use and should not be directly used in dry powder form.
        Before use, the solution has to be stirred well to get uniform smooth consistency and to be
        free from undissolved particles.
        Preparation
        1 kilo of dry powder i 3 dissolved in 30 litres of clean water and stirred well for 10-15
        minutes. In case of mechanical mixing, first water is added tO the mixing drum, then
        algiproof stock solution followed in turn by aggregate sand and cement for concrete and
        in respect of mortar sand and cement.
Repair & Preventive      Use on New Works
Maintenance Techniques
                         The consreting or plastering works, as the case may be, are to be carried out as per sound
                         engineeing practices. Water cement ratio has to be strictly followed. All air voids are to
                         be removed by proper trowellinglcompactioa After the initial set has taken place, the
                         surfaces are to be trowelled again to obtain hard, dense smooth sukface. Sprinkling of
                         cement has to be avoided, which may result in cracks. As far as possible, the newly
                         concreted surface while it is green, cement sand algiproof plastering of CM 1:5,12 mm
                         thick (1 kg algiproof for every 10 bags of cement) is done. In case of water retaining
                         structures, rich mortar with CM 1:3 can be used. After initial set, the surface has to be
                         trowelled. Similarly, for new plaster, algiproof is used as admixture which will also act as
                         a dampproofing agent.
                         11.9.5 Case Studies
                         a) Waterproofing Deep Well
                         A facility known as Cast Cure Facility in which the two distinct operations of casting and
                         curing of the propellant will be carried out in one and the same facility. For this purpose, a
                         cast cure well is built with 7.5 metre internal diameter and about 6.5 metre deep clear from
                         the finished floor level. This is a RCC circular well with 60 cm thick RCC steining. The
                         sub soil water level in the vicinity is 1.5.M below ground level.
                         One of the stringent requirements of the cast cure facility is that the cast cure well should
                         be absolutely dry and free from any moistule as the presence of moisture will increase the
                         relative humidity during the curing of the propellant.
                         The u n d e r g m d structure was cast with usual RCC kerb like water supply wells in stages
                         above ground level and well sinking was resorted to duly employing compressors, and
                         well sinkers with helmets. After the sinking process was completed, the bottom of the
                         well was plugged with M-20 concrete for a depth of 2 m. This concreting operation for
                         plugging the bottom of the well was carried out under water, making use of a concrete
                         placing bucket with an openable bottom flap door. This door can be operated for opening
                         and closing fiom the ground level on top of the well. After the completion of concrete
                         plugging and curing, the water inside the well was pumped out and the raft slab above
                         plugging concrete was then completed. Necessary water stops were provided at the
                         constructionjoints to avoid seepage of water inside the well. Similarly, sufficient grooves
                         were provided in the inner face of the well steining to enable the plugging concrete to have
                         effectivekey with the steining (Figure 11.14).
                       ~ B o r r h d-           -
                                                                                         Pnrcnt lkitment
                             PIgon l L l 5 r ~ J m d a m A l r T n a a d s
 Being an underground structure, the tunnels have been provided with 5 course hessain
 based felt treatment to ensure water tightness of the tunnels. However, in c o m e of time,
 the waterproof treatment was found to be not effective and water leakages were found
 through the walls, ceiling and floors, thus affecting quality of conditioned air supplied to
 the clean room.
 The following methods to overcome the problem were examined.
 i) / To treat the tunnel from outside by exposing the external surface of the tunnels.
 ii)    Carrying out the treahnent externally at locations ,whereexposure of tunnels or
        structures are possible and treat the areas not accessable internally.
 iii) By treating the internal surfaces after the removal of vapour barrier and IW acoustic
        treatment.
 The following procedure was adopted for the repair work:
 i)     Removal of existing acoustic treatment-andvapour barrier treatment.
 ii)    Removal of the bitumen used as an adhesive in vapour barrier treatment and expose
        the RCC surface by removing the plaster by sand blasting method and chipping
        method and cleaning loose particles and dirt.
 iii) Epoxy injection grouting using epoxy resin Debeckot 505 C, Hardner EH 408 and
        dilutent 'C' in 1000: 550:50 grams ratio (total 1.6 kgs per batch was carried out at
        constructionjoints, at intervals of 1.5m horizontally and vertically and also at
        vulnerable points shown dampnessAeakage. Using rotary electric drills 100 mm
        deep holes were drilled in RCC and PVC pipes of length 125 mrn inserted into the
Repair & Preventive            holes and fixed with epoxy putty with PVC pipe projection 50 mm outside the RCC
MaintenanceTechniques
                               surface. The epoxy putty was allowed to set for 10 hours. The grouting was carried
                               out at 8 kg/sq.cm pressure using an air compressor having a capacity of
                               12 kg/sq.mm. During the actual operation, as high as 14300 points at closer
                               intervals were grouted consuming 3300 kgs of grout material as large leakages had
                               been noticed during the course of work. The maximum consumption per point was
                               32 kgs and minimum was 30 grams and average was 230 grams per point.
                               During the repair work, flooding was done through trenches dug near the junction           4
                               of top of side walls and roof slab to create a near monsoon condition.
                        iv)   Aftdr grouting points was completed, the bond coat of Dr. Beck's epoxy system
                              contisting of Debeckot 520F and Hardner EH 408 in 2:1 proportion added with
                              suitable thinner for brushability was carried out on RCC and plastering to the
                              required thickness in CM 1:4 to get the level surface to relieve the binder coat. The
                              plastered surface was cured for 10 days at tunnel ambient temperature.
                        v)    Then a binder coat consisting of Beak's epoxy system resin Debeckd 520F and
                              Hardner EH 408 in proportion 2:1 was applied over the plastered surface. Over this
                              coat of epoxy layer, fibre glass tissue mat of 30 gms grade was applied to contain
                              the $poxy layer. The binder coat is air cured for 48 to 72 hours at tunnel
                              tewrature.
                        The s y s d was found to be quite effective as no leakage was found in the tunnel even
                        during heavy rains.
                        Dampness and water leakages in buildingslstructures will cause harmful effects such as
                        unsightly stains,bad smell, detachment of paint films, wall papers, plasters, corrosion of
                        reinforcemeets, effluorescence,decay of materials etc. They further cause severe
                        structural damage to the various components. The treatmentslprevention can be done by
                        using various integral water proofing and surface treatment materials. Wide variety of
                        materials available permit the use of specific treatments for any type of condition.