30GX
30GX
MENU
     ITEM   STATUS                    TEMP                     PRESSURES                 SETPOINTS                INPUTS                        OUTPUTS        CONFIG                  ALARMS                  ALARMS HIST              RUNTIMES
     0      Default display           Evaporator water         Discharge pressure,       Cooling setpoint 1       Contact 1: remote on/off      SUB-MENU:      SUB-MENU:               Number of active        Historic alarm code 1    SUB-MENU:
                                      entering temp.           circuit A                                                                        Outputs 1      User Configuration      alarms/resets                                    Runtimes
                                                                                                                                                [OUTPUTS1]     [USEr]
     1      Active modes              Evaporator water         Suction pressure,         Cooling setpoint 2       Contact 2: remote             SUB-MENU:      SUB-MENU:               Active alarm code 1**   Historic alarm code 2    SUB-MENU:
                                      leaving temp.            circuit A                                          setpoint                      Outputs 2      Service Configuration                                                    Maintenance
                                                                                                                                                                                                                                                      4.5 - Menu tree structure
                                                                                                                                                [OUTPUTS2]     [SErviCE]
     2      Chiller occupied/         Condenser water          Oil pressure,             Heating setpoint         Contact 3: remote             -              SUB-MENU:               Active alarm code 2**   Historic alarm code 3    -
            unoccupied                entering temperature     compressor A1                                      heating/cooling                              Factory Configuration
                                                                                                                                                               [FACtorY]
     3      Minutes left              Condenser water          Oil pressure,             Condensing setpoint      Contact 4: remote heat        -              -                       Active alarm code 3**   Historic alarm code 4    -
                                      leaving temperature      compressor A2                                      reclaim operation
     4      Cooling/heating           Heat reclaim water       Oil differential pressure, Heat reclaim setpoint   Demand limit selection        -              -                       Active alarm code 4**   Historic alarm code 5    -
            selection                 entering temperature     compressor A1
     5      Heat reclaim selection    Heat reclaim water       Oil differential pressure, Demand limit            Water flow control and        -              -                       Active alarm code 5**   Historic alarm code 6    -
                                      leaving temperature      compressor A2              setpoint in %           customer interlock
     6      Unit capacity in %        Saturated discharge      Economizer A1             Cooling mode ramp        Evaporator pump fault         -              -                       -                       Historic alarm code 7    -
                                      temperature, circuit A   pressure                                           detection
     7      Capacity circuit A in %   Saturated suction        Economizer A2             Heating mode ramp        Water flow control,           -              -                       -                       Historic alarm code 8    -
                                      temperature, circuit A   pressure                                           condenser
     8      Capacity circuit B in %   Gas discharge            Discharge pressure,       Cooling - threshold      Control box thermostat        -              -                       -                       Historic alarm code 9    -
                                      temperature, circuit A   circuit B                 for zero reset           and phase reversal
                                                                                                                  interlock control
     9      Present demand limit      Discharge superheat,     Suction pressure,         Cooling - threshold      Oil level, circuit A          -              -                       -                       Historic alarm code 10   -
            in %                      circuit A                circuit B                 for max. reset
     10     Present lag limit in %    Temperature motor A1     Oil pressure,             Cooling - max. reset     Oil level, circuit B          -              -                       -                       -                        -
                                                               compressor B1             value
     11     Setpoint in local         Temperature motor A2     Oil pressure,             Heating - threshold      External 0-10 V d.c. signal   -              -                       -                       -                        -
            control                                            compressor B2             for zero reset
     12     Setpoint occupied/        Saturated discharge      Oil differential pressure, Heating - threshold     Compressor current A1         -              -                       -                       -                        -
            unoccupied mode           temperature, circuit B   compressor B1              for max. reset
     13     Active setpoint           Saturated suction        Oil differential pressure, Heating - max. reset    Compressor current A2         -              -                       -                       -                        -
                                      temperature, circuit B   compressor B2              value
     14     Control point             Gas discharge            Economizer B1             -                        Compressor current B1         -              -                       -                       -                        -
                                      temperature, circuit B   pressure
     15     Controlled water          Discharge superheat,     Economizer B2             -                        Compressor current B2         -              -                       -                       -                        -
            temperature               circuit B                pressure
     16     Condensing point          Temperature motor B1     Remote discharge          -                        Total compressor              -              -                       -                       -                        -
                                                               pressure, circuit A                                operating current
     17     Heat reclaim indicator,   Temperature motor B2     Remote discharge          -                        -                             -              -                       -                       -                        -
            circuit A                                          pressure, circuit B
     18     Heat reclaim indicator,   Outdoor temperature      Heat reclaim pressure,    -                        -                             -              -                       -                       -                        -
            circuit B                                          circuit A
     19     -                         Water loop               Heat reclaim pressure,    -                        -                             -              -                       -                       -                        -
                                      temperature, master/     circuit B
                                      slave assembly
     NOTE: The items in brackets show what is displayed on the user interface.                                                                  **   Displayed if the alarm exists
                                                                                                                                                -    Not in use
4.5.1 - Description of the Information menu
INFORMATION MENU (3)
ITEM    FORMAT          UNITS     DESCRIPTION
0                                 Automatic display mode. It cycles through the following displays:
        ±nn.n           °C        1:          Controlled water temperature: temperature of the water that the unit tries to maintain at the control point.
                                  2:          Unit operating type
        LOFF            -                     Local Off
        L-On            -                     Local On
        L-Sc            -                     Local On - based on unit clock.
        CCn             -                     CCN Control.
        rEM             -                     Remote Control
        MASt            -                     Master unit
                                  3:          Unit status
        OFF             -                     Off: Unit is stopped and not authorised to start.
        rEADY           -                     Ready: Unit is authorised to start
        dELAY           -                     Delay: Unit is in delay at start-up. This delay is active after the unit has been switched on. The delay can be
                                              configured in the User Configuration menu.
        StOPPing        -                     Stopping: Unit is currently stopping.
        running         -                     On: Unit is running or authorised to start.
        triPout         -                     Fault shutdown.
        OvErridE        -                     Limit: The operating conditions do not allow total unit operation.
                                  4.          Unit occupied/unoccupied status
        OCCUPIEd   -                          Occupied: Unit in occupied mode
        UNOCCUPIEd -                          Unoccupied: Unit in unoccupied mode
                                  5.          Heating/cooling operating mode
        COOL            -                     Cooling: Unit operates in cooling mode
        HEAT            -                     Heating: Unit operates in heating mode
        rECLAIM         -                     Cooling: Unit is in auto cooling and heat reclaim demand is active
                                  6.          Alarm mode
        ALArM           -                     Alarm: Unit is totally stopped because of failure.
        ALErt           -                     Alert: Unit is in failure but not completely stopped.
                                  7.          Master/Slave status
        MAStEr          -                     Master: The master/slave control is active and the unit is the master
        SLAvE           -                     Slave: The master/slave control is active and the unit is the slave
1 [1]   nn              -         Active mode codes. Each active mode is displayed in turn. This Item is masked when nil. Pressing the enter button when a mode
                                  code is displayed causes a character text expansion to be scrolled accross the four-digit display. See the description in the following
                                  table
                                                                                                                                                                           13
DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU)
MODE #     MODE NAME                                DESCRIPTION
7          Delay at start-up active                 The delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is active.
                                                    The delay is configured in the User1 configuration menu.
8          2nd cooling setpoint active              The second cooling setpoint is active. See section 5.7.1
9          Setpoint reset active                    In this mode, the unit uses the reset function to adjust the leaving or entering water temperature setpoint. See
                                                    section 5.7.2.
10         Demand limit active                      In this mode, the capacity at which the unit is allowed to operate is limited. See section 5.8.
11         Ramp loading active                      Ramp loading is active. In this mode, the controlled high or low water temperature value (in °C/min) in heating mode
                                                    is limited to a preset value in order to prevent compressor overload. The ramp function must be configured (see
                                                    User1 configuration menu). The ramp values can be modified (see setpoint menu).
12         Low entering water temperature           The unit is in heating mode and the temperature of the evaporator leaving water is lower than the lesser of the two
           protection in heating mode               cooling setpoints. A capacity stage is removed. This mode only applies to heat pumps.
13,14      Low suction temperature protection       13 = circuit A & 14 = circuit B. Protection for evaporator suction low temperature circuit is active. In this mode,
                                                    circuit capacity is not authorised to rise if the unit is in cooling mode, and saturated suction temperature in the
                                                    circuit is lower than the frost protection threshold.
15,16      Low discharge superheat protection       15 = circuit A & 16 = circuit B.
                                                    In this mode the circuit capacity is not authorised to rise.
17,18      High pressure protection                 17 = circuit A & 18 = circuit B. The circuit is in high pressure protection mode because the HP protection threshold
                                                    has been exceeded. The circuit capacity is not authorised to rise and any slave compressor can be stopped in
                                                    order to prevent a high pressure break.
19,20      High current protection                  19 = circuit A & 20 = circuit B. Circuit capacity is not allowed to rise, as the compressor has reached the high
                                                    current protection threshold and could be shut down.
21         Heat reclaim active                      Circuit A or circuit B operates in heat reclaim mode and not in standard cooling mode (pumpdown phase is activated).
22         Evaporator heater active                 Mode active if risk of frost exists.
23         Evaporator pump reversal active          Two evaporator water pumps installed on the unit and pump reversal is active. See section 5.3
24         Periodic evaporator pump start-up        The unit is shut down and is started every day at 14:00 hours for 2 seconds. This function must be configured in the
                                                    User1 menu. See sections 5.3 and 4.5.7.3.
25         Low night-time capacity                  Unit capacity is limited. The period when this mode starts, as well as the limited capacity in night-time mode are
                                                    controlled in Costomer 1 menu.
26         Unit under SM control                    Unit is under control of a System Manager (FSM or CSM III).
27         Master/slave link active                 Unit is connected to a secondary unit by a master slave link and either:
                                                    - the unit is configured as a master and this master is operating, or
                                                    - the unit is configured as a slave and this slave is operating.
4.5.2 - Description of the Temperatures menu 4.5.3 - Description of the Pressures menu
14
4.5.4 - Description of the Setpoints menu
Legend
1 This item is displayed in certain unit configurations only.
2 All points contained in this table can be modified.
*  Those setpoints can be used for entering or leaving water temperature control. By default the unit controls the evaporator entering fluid temperature.
   Leaving fluid temperature control requires a parameter modification in the Service Configuration menu.
** These parameters are only accessible when reset based on OAT or delta T has been selected in the User Configuration 1 menu. See section 4.5.7.3.
Note:
Three setpoint reset configuration modes can be selected in the Customer 1
menu:
1 Reset using an external 0-10 V d.c. signal
2 Reset using Delta T
3 Reset by external temperature sensor (air-cooled units only)
    The items with zero reset or maximum reset are based on these three modes.
*   MCT = Maximum Condensing Temperature (depending on the application)
                                                                                                                                                                          15
4.5.5 - Description of the Inputs menu
Legend
1 This item is displayed in certain unit configurations only
2 Access to this menu is read-only
*  Active in all operating types
   See section 3.4
16
4.5.6 - Description of the Outputs/Tests menu
4.5.6.1 - General
This menu displays the status of the controller outputs. More-
over, when the machine is fully stopped (LOFF) the outputs
can be activated for manual or automatic tests (the access to the
tests is password controlled).
                                                                                                                                                                             17
OUTPUTS STATUS 2 AND TESTS MENU [2] [3]
ITEM     FORMAT        UNITS                DESCRIPTION
0		                                         This item returns you to the previous menu.
1 [1] tESt             0-8                  Fan contactor status/test, circuit A
		                                          This item permits display of the number of fan stages. It also permits them to be tested in a sequentially. In test mode the
		                                          direction arrows permit successive display from 0 to 8, so as to authorise the forcing the outputs.
2 [1]    tESt          0-8                  Fan contactor status/test, circuit B
                                            This item permits display of the number of fan stages. It also permits them to be tested in a sequentially. In test mode the
				                                        direction arrows permit successive display from 0 to 8, so as to authorise the forcing the outputs.
3 tESt                                      Alarm command status/test
		                     -                    b1 = alarm circuit A
		                     -                    b2 = alarm circuit B
                                            In test mode the direction arrows permit successive display of 01 and 10, so as to in turn force authorisation of each alarm
		                                          output.
4 tESt                 %                    EXV position, circuit A
		                                          In the test mode the direction arrows permit forcing the valve to its fully open position.
5 tESt                 %                    EXV position, circuit B
		                                          In the test mode the direction arrows permit forcing the valve to its fully open position.
6 [1]    tESt          %                    Variable speed fan, circuit A or condenser water valve position in %
7 [1]    tESt          %                    Variable speed fan, circuit B or condenser water valve position in %
8 On                   -                    Evaporator water pump No. 1 command status. Not displayed if unit does not control a pump.
  Stop                 -                    On: the pump operates
  tESt                 -                    Stop: the pump has stopped
  FAIL                 -                    Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump
  Good                 -                    without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it
  Forc                 -                    is then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with ‘Forc’ if its
		                                          status is forced by CCN.
		                                          During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display
		                                          appears:
		                                          - Fail: displayed if the test has failed, because the pump is not started
		                                          - Good: displayed if the test succeeds
9 On                   -                    Evaporator water pump No. 2 command status. Not displayed if unit does not control a pump.
  OFF                  -                    On: the pump operates
  tESt                 -                    Stop: the pump has stopped
  FAIL                 -                    Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump
  Good                 -                    without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it
  Forc                 -                    is then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with ‘Forc’ if its
		                                          status is forced by CCN.
		                                          During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display
                                            appears:
                                            - Fail: displayed if the test has failed, because the pump is not started
		                                          - Good: displayed if the test succeeds
10On                   -                    Condenser pump status/test
  OFF                  -                    On: the pump operates
  tESt                                      Stop: the pump has stopped
  FAIL                                      Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump
  Good                                      without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it
  Forc                                      is then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with ‘Forc’ if its
		                     -                    status is forced by CCN.
                                            During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display
                                            appears:
                                            - Fail: displayed if the test has failed, because the pump is not started
		                                          - Good: displayed if the test succeeds
11[1] nn                                    Evaporator heater and heat reclaim condenser status
		                     -                    b1 = evaporator heater
		                     -                    b2 = heat reclaim condenser heater
12[1]    tESt          %                    Condenser water valve position in heat reclaim mode
13[1]		                                     Solenoid valve status/test, heat reclaim function
		                     -                    b1 = heat reclaim coil shutoff solenoid valve, circuit A
		                     -                    b2 = heat reclaim coil drain solenoid valve, circuit A
		                     -                    b3 = heat reclaim coil shutoff solenoid valve, circuit B
		                     -                    b4 = heat reclaim coil drain solenoid valve, circuit B
		                                          In test mode the direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force
		                                          authorisation of each output.
14       YES                                Used only for local interface
         no                                 Cause all diodes and blocks to light up or flash, to verify that they are operating correctly
         tESt
Legend
1 This item is displayed in certain unit configurations only
2 A test is only possible if the units are in local off mode and if all compressors have stopped
3 The password is only valid for the test. ‘Test’ is displayed during the test, alternating with the item number
18
4.5.6.3 - Manual tests                                                                  4.5.7.2 - Password
This function allows the user to test the outputs individually, if                      A password must be entered in order to access the test function
the machine is completely shut down (LOFF). To carry out a                              or to modify a configuration. It is automatically requested, if
manual test use the arrow keys to access the output to be tested                        necessary: ‘EntEr PASS’ is displayed on the 4-digit display and
and press the Enter key (longer than 2 seconds) to activate the                         the configuration menu LED flashes, indicating that the modifi-
modification mode. The password is automatically requested, if                          cation mode is active. Press the arrow keys until the value ‘11’
it has not previously been verified. The Outputs/Test LED on                            is displayed on the 4-digit display. Press Enter to validate this.
the user interface begins to flash. Enter the desired test value and                    The configuration menu LED stops flashing. If the password is
again press Enter to start the test. ‘TESt’ is displayed on the 4-                      correct, ‘Good’ is displayed. If the password is incorrect,
digit display alternately with the value tested. The Outputs/Test                       ‘PASS incorrEct’ is displayed. The User password has a default
LED stops flashing. Press the Enter key or an arrow key to stop                         value of 11.
the test.
                                                                                        This value can be modified through the Service configuration.
4.5.7 - Description of the Configuration menu                                           The password can be entered if the unit is fully stopped, other-
                                                                                        wise ‘ACCES dEniEd’ (access denied) will be displayed on the
4.5.7.1- General                                                                        4-digit display. The controller automatically deactivates the
This menu can be used to display and modify all configurations:                         password after 5 minutes without activity (i.e. no buttons
Factory, Service and User. Only the User Configuration can be                           pressed) or after powering up.
modified by the end-user. The Factory, Service and master/slave
configurations are not described in this document. A configura-
tion can only be modified if the unit is fully stopped (LOFF).
                                                                                                                                                                      19
4.5.7.3 - Description of the User 1 Configuration sub-menu
                                                                                                                                                              21
4.5.7.4 - Description of the User 2 Configuration sub-menu
4.5.7.5 - Description of Date and Time configuration sub-                                    4.5.7.6 - Description of the Time Schedules sub-menus
menu                                                                                         The control provides two timer programs. If the CCN/clock
                                                                                             board is not installed, the two schedules are permanently in
DATE & TIME CONFIGURATION SUB-MENU
                                                                                             occupied mode.
ITEM         FORMAT            COMMENTS
0            dAtE MEnu         When selected this item authorises return to the
                               previous menu.                                                The first timer program (schedule #1) provides a means to
1            n1n2n3n4          Current time setting.                                         automatically switch the unit from an occupied mode to an
             00:00 to 23:59    n1n2: hours (00 to 23). The first time the Enter button is    unoccupied mode: the unit is started during occupied periods.
                               continuously pressed, the first two characters in the
                               4-digit display flash so that hours can be adjusted.
		                             n3n4: minutes (00 to 59). Continuous pressing of the          The second timer program (schedule #2) provides a means to
                               Enter key again causes the last two characters to             automatically switch (when auto mode is selected) the active
                               flash and minutes can be adjusted.
2		                            Current day of week setting.
                                                                                             setpoint from an occupied setpoint to an unoccupied setpoint.
   «Mon»                       Monday                                                        Cooling or heating setpoint 1 is used during occupied periods.
   «tUe»                       Tuesday                                                       Cooling setpoint 2 is used during unoccupied periods. For
   «uEd»                       Wednesday
   «tHu»                       Thursday                                                      additional information on setpoint activation see section 5.7.1.
   «FrI»                       Friday
   «SAt»                       Saturday
   «Sun»                       Sunday                                                        Each schedule consists of eight time periods set by the
3            n1n2n3n4          Current day and month setting.                                operator. These time periods can be flagged to be in effect or
             01:01 to 31:12    n1n2:day (01 to 31). The first time the Enter button is       not in effect on each day of the week plus a holiday period (see
                               continuously pressed, the first two characters in the
                               4-digit display flash so that day can be adjusted.            section 4.5.7.7 on public holidays). The day begins at 00.00
		                             n3n4:month (01 to 12). Continuous pressing of the             hours and ends at 24.00 hours.
                               Enter key again causes the last two characters to
                               flash so that month can be adjusted.
4            nnnn              Current year setting.
                                                                                             Program is in unoccupied mode unless a schedule time period is
                                                                                             in effect. If two periods overlap and are both active on the same
                                                                                             day, the occupied mode takes priority over the unoccupied
                                                                                             period.
                                                                                             Each of the eight periods can be displayed and changed with the
                                                                                             aid of a sub-sub-menu. The table below shows how to access the
                                                                                             period configuration. Method is the same for the time schedule
                                                                                             #1 or the time schedule #2.
22
6.4 - Alarm codes
The following list gives a complete description of each alarm code and its possible cause.
Alarm   Description                                    Why was this alarm             Action taken by the control       Reset type                 Probable cause
code                                                   generated?
1       Evaporator entering fluid thermistor failure   Thermistor outside range       Unit shut down                    Auto, if the temperature   Thermistor or wiring fault or
                                                       -40 to 118°C                                                     measured by the sensor     cable/wire damaged
                                                                                                                        becomes normal again
2       Evaporator leaving fluid thermistor failure    Ditto                          Unit shut down                    Ditto                      Ditto
3       Condenser entering fluid thermistor failure    Ditto                          None, simple message              Ditto                      Ditto
4       Condenser leaving fluid thermistor failure     Ditto                          None in cooling mode           Ditto                         Ditto
                                                                                      Unit shut down in heating mode
5       Condenser entering fluid thermistor failure    Ditto                          None, simple message              Ditto                      Ditto
6       Condenser leaving fluid thermistor failure     Ditto                          None                              Ditto                      Ditto
7       Outdoor temperature sensor fault               Ditto                          Reset based on deactivated        Ditto                      Ditto
                                                                                      outdoor sensor
8       CHWS (master/slave) fluid thermistor fault     Ditto                          Master/slave function             Ditto                      Ditto
                                                                                      deactivated
9       Compressor A1, discharge gas sensor            Ditto                          Compressor A1 shut down           Ditto                      Thermistor, solenoid, motor
                                                                                                                                                   cooling or wiring fault
10      Compressor A2, discharge gas sensor            Ditto                          Compressor A2 shut down           Ditto                      Ditto
11      Compressor B1, discharge gas sensor            Ditto                          Compressor B1 shut down           Ditto                      Ditto
12      Compressor B2, discharge gas sensor            Ditto                          Compressor B2 shut down           Ditto                      Ditto
13      External 0-10 V dc signal fault                Signal outside range           1- Loadshed: not used             Ditto                      Defective input or wiring fault
                                                                                      2- Demand limit: deactivated
14      Discharge pressure transducer failure,         Measured signal = 0 V dc       Circuit A shut down               Ditto                      Defective transducer, wiring fault
        circuit A
15      Discharge pressure transducer failure,         Ditto                          Circuit B shut down               Ditto                      Ditto
        circuit B
16      Suction pressure transducer failure, crt A     Ditto                          Circuit A shut down               Ditto                      Ditto
17      Suction pressure transducer failure, crt B     Ditto                          Circuit B shut down               Ditto                      Ditto
18      Oil pressure transducer failure, compr A1      Ditto                          Compressor A1 shut down           Ditto                      Ditto
19      Oil pressure transducer failure, compr A2      Ditto                          Compressor A2 shut down           Ditto                      Ditto
20      Oil pressure transducer failure, compr B1      Ditto                          Compressor B1 shut down           Ditto                      Ditto
21      Oil pressure transducer failure, compr B2      Ditto                          Compressor B2 shut down           Ditto                      Ditto
22      Economizer A1 transducer failure               Ditto                          Circuit A shut down for unit      Ditto                      Ditto
                                                                                      with economizer. Otherwise
                                                                                      compressor A1 shut down.
23      Economizer A2 transducer failure               Ditto                          Compressor A2 shut down           Ditto                      Ditto
24      Economizer B1 transducer failure               Ditto                          Circuit B shut down for unit      Ditto                      Ditto
                                                                                      with economizer. Otherwise
                                                                                      compressor B1 shut down.
25      Economizer B2 transducer failure               Ditto                          Compressor B2 shut down           Ditto                      Ditto
26      Pressure sensor failure - coil pump down       Ditto                          Circuit A remains in cooling      Ditto                      Ditto
        circuit A                                                                     mode
27      Pressure sensor failure - coil pump down       Ditto                          Circuit B remains in cooling      Ditto                      Ditto
        circuit B                                                                     mode
28      Fault in the motor cooling valve position      Ditto                          None                              Ditto                      Ditto
        sensor, circuit A
29      Fault in the motor cooling valve position      Ditto                          None                              Ditto                      Ditto
        sensor, circuit B
30      Loss of communication with SCPM A1             SCPM A1 board does not         Compressor A1 shut down           Ditto                      Wiring fault, incorrect address or
        board                                          respond                                                                                     defective board
31      Loss of communication with SCPM A2             SCPM A2 board does not         Compressor A2 shut down           Ditto                      Ditto
        board                                          respond
32      Loss of communication with SCPM B1             SCPM B1 board does not         Compressor B1 shut down           Ditto                      Ditto
        board                                          respond
33      Loss of communication with SCPM B2             SCPM B2 board does not         Compressor B2 shut down           Ditto                      Ditto
        board                                          respond
34      Loss of communication with EXV board           4xDO board associated with Unit shut down                        Ditto                      Ditto
                                                       the EXV does not respond
35      Loss of communication with fan board #1        4xDO board controlling the     Unit shut down if number of fan   Ditto                      Ditto
                                                       first four fan stages does     stages by circuit is lower than
                                                       not respond                    three. Otherwise circuit A shut
                                                                                      down.
36      Loss of communication with fan board # 2       4xDO board controlling the     Circuit B shut down               Ditto                      Ditto
                                                       fan stages of circuit B does
                                                       not respond
37      Loss of communication with auxiliary           Board does not respond         Unit shut down if heating mode    Automatic                  Bus wiring fault, incorrect
        board type 1                                                                  has been selected.                                           address or defective board
38      Loss of communication with heat reclaim        Analogue board does not        Unit shut down if heat reclaim    Automatic if board is      Auxiliary board faulty
        or                                             respond                        mode is selected.                 again detected             Faulty connection
        evaporator heater board
39      ‘CCN/clock board’ fault                        CCN/clock board is no          Unit shut down                    Ditto                      Defective CCN/clock board
                                                       longer detected
40**    Control box thermostat fault or phase          Sensor overheated              Unit shut down                    Auto if the same alarm   Badly ventilated control box
        reversal                                                                                                        has not tripped the same
                                                                                                                        day
32
Alarm Description                               Why was this alarm                 Action taken by the control   Reset type                 Probable cause
code                                            generated?
41     Unit emergency stop                      CCN command to stop the unit       Unit shut down                CCN/Automatic              Control network
                                                received
42     Initial factory configuration required   All factory parameters are 0       Unit cannot start             Auto                       No factory configuration
43-n   Illegal initial factory configuration    Bad factory configuration          Ditto                         Ditto                      Factory configuration error
43-1   Compr A capacity too high
43-2   Compr B2 configured and compressor
       B1 absent
43-3   Fan configured for a water-cooled
       condenser
43-4   Fans not configured
43-5   Heat reclaim option configured and
       reclaim sensors configured
44     Discharge pressure circuit A too high    SCT>loadshed threshold. Max.       Circuit A shut down           Auto in the 10mn that      Transducer/high pressure switch
                                                satur. condensing pressure                                       follow                     or fan circuit defective, water flow
                                                (mct_sp) if only one capacity                                                               obstructed in the condenser,
                                                stage remains in operation                                                                  water entering temperature or
                                                                                                                                            condenser air too high
45     Discharge pressure circuit B too high    SCT>loadshed threshold. Max.       Circuit B shut down           Ditto                      Ditto
                                                satur. condensing pressure
                                                (mct_sp) if only one capacity
                                                stage remains in operation
46     Oil solenoid failure, compressor A1      Oil pressure differential >17kPa   Compressor A1 not authorised Auto if the same alarm   Oil valve defective
                                                during the period following        to start                     has not tripped the same
                                                pump start-up and before                                        day
                                                opening of the oil solenoid (see
                                                prelubrication)
47     Oil solenoid failure, compressor A2      Ditto                              Compressor A2 not authorised Ditto                       Ditto
                                                                                   to start
48     Oil solenoid failure, compressor B1      Ditto                              Compressor B1 not authorised Ditto                       Ditto
                                                                                   to start
49     Oil solenoid failure, compressor B2      Ditto                              Compressor B2 not authorised Ditto                       Ditto
                                                                                   to start
50     Pre-start oil pressure, compressor A1    Oil pump does not sufficiently     Compressor A1cannot start     Ditto                      Low oil level, oil pump, oil
                                                increase the pressure during                                                                solenoid or oil transducer failure
                                                several prelubrication cycles
51     Pre-start oil pressure, compressor A2    Oil pump does not sufficiently     Compressor A2 cannot start    Ditto                      Ditto
                                                increase the pressure during
                                                several prelubrication cycles
52     Pre-start oil pressure, compressor B1    Oil pump does not sufficiently     Compressor B1 cannot start    Ditto                      Ditto
                                                increase the pressure during
                                                several prelubrication cycles
53     Pre-start oil pressure, compressor B2    Oil pump does not sufficiently     Compressor B2 cannot start    Ditto                      Ditto
                                                increase the pressure during
                                                several prelubrication cycles
54     Oil level circuit A low                  Oil level control contact open     Circuit A shut down           Manual                     Oil level detector defective, oil
                                                during operation                                                                            quantity insufficient
55     Oil level circuit B low                  Oil level control contact open     Circuit B shut down           Manual                     Ditto
                                                during operation
56     Low saturated suction temp, circuit A    SST under defrost theshold* for    Circuit A shut down           Auto if the same alarm   Low refrigerant charge, filter drier
                                                3 minutes                                                        has not tripped the same obstructed, expansion valve and
                                                                                                                 day                      transducer defective, low water
                                                                                                                                          flow, low evaporator water
                                                                                                                                          temperature
57     Low saturated suction temp, circuit B    SST under defrost threshold* for Circuit B shut down             Ditto                      Ditto
                                                3 minutes
58     High saturated suction temp, circuit A   After 90 seconds of operation if   Circuit A shut down           Manual                     Expansion valve, liquid level
                                                SST > 12.8°C & EXV < 1%                                                                     sensor or transducer defective,
                                                                                                                                            high evaporator temp.
59     High saturated suction temp, circuit B   After 90 seconds of operation if   Circuit B shut down           Manual                     Ditto
                                                SST > 12.8°C & EXV < 1%
60     Low discharge superheat, circuit A       Superheat <2.8 K for 10 minutes Circuit A shut down              Auto if the same alarm   Thermistor, transducer, EXV or
                                                                                                                 has not tripped the same economizer defective
                                                                                                                 day
61     Low discharge superheat, circuit B       Superheat <2.8 K for 10 minutes Circuit B shut down              Ditto                      Ditto
62     Max. oil pressure difference,            (Discharge pressure - oil          Compressor A1 shut down       Manual                     Obstructed oil filter, oil solenoid or
       compressor A1                            pressure) >340 kPa for more                                                                 shut-off valve blocked, or manual
                                                than 6 seconds                                                                              oil valve closed
63     Max. oil pressure difference,            (Discharge pressure - oil          Compressor A2 shut down       Manual                     Ditto
       compressor A2                            pressure) >340 kPa for more
                                                than 6 seconds
64     Max. oil pressure difference,            (Discharge pressure - oil          Compressor B1 shut down       Manual                     Ditto
       compressor B1                            pressure) >340 kPa for more
                                                than 6 seconds
65     Max. oil pressure difference,            (Discharge pressure - oil          Compressor B2 shut down       Manual                     Ditto
       compressor B2                            pressure) >340 kPa for more
                                                than 6 seconds
66     Loss of commuincation with System        The unit is controlled by a       Unit returns to autonomous     Auto                       Defective CCN BUS wiring or
       Manager                                  System Manager (Flotronic or      operating mode                                            system module failure
                                                Chiller) and communication with
                                                this module is lost for more than
                                                two minutes
67     Loss of communication with master or     The master/slave link is broken    Unit returns to autonomous    Auto                       Defective CCN BUS wiring or loss
       slave unit                               due to a loss of communication     operating mode                                           of supply
                                                between the two units for more
                                                than 2 minutes
                                                                                                                                                                                 33
Alarm Description                                Why was this alarm                  Action taken by the control       Reset type                 Probable cause
code                                             generated?
68      Low oil pressure compr A1                Oil pressure differential below     Compressor A1 shut down           Auto if the same alarm   Low condenser air or water
                                                 the setpoint (dynamically                                             has not tripped the same temperature, oil filters obstructed,
                                                 calculated) for 15 seconds                                            day                      oil valve blocked, oil solenoid and
                                                                                                                                                oil pressure transducer defective
69      Low oil pressure compr A2                Oil pressure differential below     Compressor A2 shut down           Ditto                      Ditto
                                                 the setpoint (dynamically
                                                 calculated) for 15 seconds
70      Low oil pressure compr B1                Oil pressure differential below     Compressor B1 shut down           Ditto                      Ditto
                                                 oil setpoints 1 or 2 (see alert
                                                 criteria for low oil pressure and
                                                 setpoint)
71      Low oil pressure compr B2                Oil pressure differential below     Compressor B2 shut down           Auto if the same alarm   Ditto
                                                 the setpoint (dynamically                                             has not tripped the same
                                                 calculated) for 15 seconds                                            day
72      Evaporator frost protection              1 - Evaporator EWT or LWT           Unit shut down. Evaporator        Ditto                      Defective thermistor, low water
                                                 below defrost setpoint              pump and if applicable heater                                flow
                                                 2 - On units equipped with an       start-up, if unit has shut down
                                                 evaporator heater, heater           air-cooled units)
                                                 operates for more than 15
                                                 minutes but does ot heat the
                                                 evaporator
73      Condenser frost protection, circuit A    For water-cooled units and fluid    Unit shut down. Condenser         Automatic                  Discharge pressure transducer
                                                 type = water, if SCT<1,1°C          pump start-up, if unit has shut                              defective, refrigerant leak or low
                                                                                     down                                                         condenser water temperature
74      Condenser frost protection, circuit B    For water-cooled units and fluid    Unit shut down. Condenser         Automatic                  Ditto
                                                 type = water, if SCT<1,1°C          pump start-up, if unit has shut
                                                                                     down
75      Evaporator water flow control failure    1 - Control not closed, before      Unit shut down. Pump shut         Manual                     Evaporator pump control or water
                                                 end of the start-up delay or        down                                                         flow switch failure
                                                 open during operation
                                                 2 - Pump shut down for 2 mins
                                                 and water flow contact closed
76      Condenser water flow loss                Water flow switch (water-cooled     Unit shut down                    Manual                     Condenser pump, low water flow,
                                                 units) not closed during the                                                                     water flow switch
                                                 minute after start-up
77      High current, compressor A1              Current higher than threshold       Compressor A1 shut down           Auto after 10 mn delay     Operation above the compressor
                                                 value detected                                                                                   capacity
78      High current, compressor A2              Ditto                               Compressor A2 shut down           Ditto                      Ditto
79      High current, compressor B1              Ditto                               Compressor B1 shut down           Ditto                      Ditto
80      High current, compressor B2              Ditto                               Compressor B2 shut down           Ditto                      Ditto
81      Pump 1 fault                             Evaporator water pump contact       Unit shut down                    Manual                     Pump overheat or bad pump
                                                 open, when the pump has                                                                          connection
                                                 received a command to run
82      Pump 2 fault                             Ditto                               Ditto                             Manual                     Ditto
83      Heat reclaim mode fault, circuit A       1. Interlock not closed 1 minute    Circuit A remains in cooling      Manual                     1. Water flow switch defective.
                                                 after condenser pump start-up       mode                                                         2. Leak or heat reclaim shutoff or
                                                 or open during heat reclaim                                                                      drain solenoid valve open.
                                                 operation
                                                 2. More than two consecutive
                                                 pumpdown sequences not
                                                 successful.
84      Heat reclaim mode fault, circuit B       Ditto                               Circuit B remains in cooling      Manual                     Ditto
                                                                                     mode
85      Water flow fault, heat reclaim           Water flow detector (water-         Unit remains in cooling mode      Manual                     Ditto
        condenser                                cooled units) not closed for one
                                                 minute
86-nn   Master/slave configuration fault         Bad master/slave configuration      Master/slave control not          Auto/manual for heating/   Master/slave configuration error
                                                                                     allowed                           cooling mode fault
87-n    Maintenance alert                        A maintenance alert is active       None                              Manual
87-1    Charge too low
87-2    Water loop too low
87-3    Air filter maintenance delay elapsed
87-4    Pump 1 maintenance delay elapsed
87-5    Pump 2 maintenance delay elapsed
87-6    Water filter maintenance delay elapsed
34
Alarm    Function                    Description                           Action                              Reset                 Note
1xx      Defect compressor A1        See SCPM subcodes below               See SCPM subcodes below             Manual
2xx      Defect compressor A2        See SCPM subcodes below               See SCPM subcodes below             Manual
3xx      Defect compressor B1        See SCPM subcodes below               See SCPM subcodes below             Manual
4xx      Defect compressor B2        See SCPM subcodes below               See SCPM subcodes below             Manual
35