Q
Q
Chilled Fluid Set Point                                  Transducer Calibration — Press               and scroll down to
                                                                        view the transducer calibration information. See Table 19
KEYPAD ENTRY DISPLAY RESPONSE     COMMENTS                              for a complete list, and the Pressure Transducers section on
             COOLING          Change set point from                     page 59 for a description of this subfunction.
                              default to 48 F.
             Cool Set point 1                                           Manual Control Mode — This control allows the user to
             44.0 F default                                             have full control over the compressors, loaders, and the mini-
             Cool Set point 1 Set point change                          mum load valve (if installed) of the machine. Normal safe-
             48.0 F           complete                                  ties such as high pressure, oil level and pressure, and CPM
                                                                        related alarms are NOT bypassed in this control mode. The
SERVICE FUNCTION — This function allows the techni-                     capacity control function and overrides ARE bypassed when
cian to view and input configuration data. Factory configu-               using the manual control mode. To enter this mode, switch
ration data, field configuration data, and service configura-              the LOR switch to OFF. Press             at the HSIO. The dis-
tion data may be viewed or entered through the keypad and
display module. See Table 19 for a complete listing of con-             play will read Manual Control Enable - Disable. Press
figurable items. Whenever a processor module is replaced in              and switch the LOR switch to Local. The display will change
the field, the complete list of configuration codes should be             to Manual Control Enable - Enable. The Disable and Enable
checked for correct settings. The current software version              will appear on the second line of the display. See Table 19
can be displayed. See Table 20.                                         for a complete list of this function.
   Scroll down in this function to display configuration in-                Scroll down and press             to start the desired com-
formation including number of compressors, tonnage, and                 pressor. The control will start the compressor if the pre-lube
compressor must-trip amps.                                              cycle is passed, just as in normal operation. Press           to
Password Protection of HSIO Configurable Service Points
                                                                        add loaders as desired and press             to turn off loaders
— To modify configurations and values and to use the manual
control subfunction, the password must be entered before the            and compressors. The Minimum Load Valve can be ener-
first change can be made. The default password is set to                 gized using the same procedure.
               . See Table 21 for an example of how to                  Dual Chiller Configuration — Press              to enter the Dual
enter the password to change the Lead/Lag configuration.                 Chiller control configuration. This method of control is for
                                                                        a stand-alone Master/Slave combination of chillers and will
Options Configuration Tables 1 and 2 — These subfunc-                    NOT work with the Flotronic™ System Manager (FSM).
tions can be accessed by pressing     or        and scroll-             The Minus One Pass Cooler option is required for this
ing down to display the configuration options. See Table 19              configuration.
for a complete list of these options.                                      The chillers should be piped for series flow through the
                                                                        coolers. The Master chiller must be downstream from the
Temperature Reset, Demand Limit and Head Pressure PID                   Slave chiller leaving water. Both the Master and Slave chiller
Configurations — Press               and scroll down to view the         must be connected to the same CCN Level II communica-
configuration information. See Table 19 for a complete list.             tions bus with different addresses. To enable the dual chiller
Factory Configuration Codes — Pressing                     allows        configuration the CCN Enable function                must be set
entry into the factory and service configuration codes                   to Enable for each chiller, otherwise each chiller will oper-
subfunction. Under this subfunction, there are 5 configura-              ate independently. This value can be activated through the
tion codes that are downloaded at the factory. Each code is             HSIO or through a CCN device. Both chillers should be con-
made up of 8 digits. If the processor module is replaced in             figured for Close Control            and require flow switches
the field, these 5 configuration codes should be checked us-              to be installed. For cooler pump control, wire both Master
ing the keypad and HSIO display module. See Table 22 for                and Slave chiller outputs to the cooler pump starter. All sys-
a description of the factory configuration codes (codes 1 through        tem inputs (temperature reset, demand limit, dual set point,
3) and service configuration codes (codes 4 and 5).                      etc.) should be connected to the Master chiller. If Lead/Lag
   The factory and service configuration codes are found by              Balance is disabled, the Master chiller will always be the
                                                                        lead chiller. If Lead/Lag Balance is enabled, the control will
pressing           . These are preset from the factory. They can        alternate between the Master and Slave chillers to keep their
be verified by following the description in Table 22. These              respective run hours balanced within the value configured
codes MUST be checked and corrected in the field if the                  for Lead/Lag Balance Delta. The desired leaving fluid set
PSIO-1 module is replaced.
                                                                        point           for the Duplex chiller must be configured in
NOTE: The LOCAL/OFF/REMOTE switch must be in the
OFF position to change configuration codes.                              the Master chiller. CCN Control of the chillers can be dis-
    A label is applied to a control box panel with a list of            abled locally through the HSIO by entering               and en-
factory and service codes for particular units. Table 23 shows          abling the Disable CCN Control value. This value must be
how to configure a new PSIO-1 module for use in a 30HXC-                 disabled before the chiller will return to Duplex control.
106---501CA water cooled chiller.
                                                                   30
                             Table 19 — Service Function and Subfunction Directory
       SUBFUNCTION            KEYPAD ENTRY               DISPLAY                           COMMENT
  1 Service Configuration                       Software CESR_500100 Ver
                                               xxx
                                               Unit Type                  1 = Air-cooled, 2 = Water-cooled
                                               x                          3 = Split system
                                               Number of Cir A Comp
                                               x
                                               Compressor A1 Tonnage
                                               xx
                                               Compressor A2 Tonnage
                                               xx
                                               Oil Switch Configuration
                                               x
                                               Number of Cir B Comp
                                               x
                                               Compressor B1 Tonnage
                                               xx
                                               Compressor B2 Tonnage
                                               xx
                                               Max. Cond. Temp Setpoint   30GX = 154 F (68 C)
                                               xxx.x dF                   30HXA = 152 F (67 C)
                                                                          30HXC = 122 F (50 C)
                                               MOP Set point              Default = 52 F (11.1 C)
                                               xx.x dF
                                               Fan Staging Select         Displays ‘‘Not Used’’ or a
                                               x                          number. See Table 5
                                               CPM Board Used?
                                               Yes
                                               Compr. A1 Must Trip Amps   Value from CPM module. See Appendix A.
                                               xxx.x
                                               Compr. A2 Must Trip Amps   Value from CPM module. See Appendix A.
                                               xxx.x
                                               Compr. B1 Must Trip Amps   Value from CPM module. See Appendix A.
                                               xxx.x
                                               Compr. B2 Must Trip Amps   CURRENTLY NOT USED
                                               xxx.x
  2 Options Configuration 1                     Cooler Fluid Select        1 = Water (Default), 2 = Medium Temp Brine
                                               x                          3 = Low Temp Brine (HX only)
                                               Min. Load Valve Select     Displays Enable/Dsable
                                               x                          Default: Dsable
                                               Loading Sequence Select    1 = Equal circuit, 2 = Staged circuit
                                               x                          Default: 2. See page 6
                                               Lead/Lag Sequence Select   1 = Automatic (Default), 2 = Circuit A leads,
                                               x                          3 = Circuit B leads
                                               Head Press. Control Type   0 = None (Default, HX), 1 = Air cooled
                                               x                          (Default, GX), 2 = Water cooled
                                               Motormaster Select         0 = None (Default), 1 = Direct control
                                               x
                                               Water Valve Type           0 = None (Default), 1 = 4-20 mA, 2 = 0-10 V,
                                               x                          3 = 20-4 mA, 4 = 10-0 V
                                               Ext. Reset Sensor Select   0 = Space Temp Thermistor (Default)
                                               x                          1 = Outside Air Thermistor
                                               Cooler Pump Interlock      0 = No interlock
                                               x                          1 = Interlock enabled (Default)
                                               Cooler Pump Control        0 = Not controlled (Default)
                                               x                          1 = On/Off Control
                                               Condenser Pump Control     0 = Not controlled (Default)
                                               x                          1 = On/Off Control
                                                                          2 = Off when stages equal 0 (unit off)
                                               Condenser Flow Switch      Displays Enable/Dsable
                                               x                          Default: Dsable
                                               Condenser Water Sensors    0 = Not used (Default), 1 = Used
                                               x
                                               Heat Reclaim Sensors       CURRENTLY NOT SUPPORTED
                                               x
  3 Options Configuration 2                     Cooling Setpoint Select    0 = Single set point (Default), 1 = Dual
                                               x                          set point (switch controlled), 2 = Dual
                                                                          set point (clock controlled)
                                               Heating Setpoint Select    0 = Single set point (Default), 1 = Dual
                                               x                          set point (switch controlled), 2 = Dual
                                                                          set point (clock controlled)
                                                                          CURRENTLY NOT SUPPORTED
See Legend on page 34.
                                                        31
                         Table 19 — Service Function and Subfunction Directory (cont)
        SUBFUNCTION               KEYPAD ENTRY          DISPLAY                                  COMMENT
3 Options Configuration 2 (cont)                  Ramp Load Select           0 = Disabled, 1 = Enabled (Default)
                                                 x                          See page 8
                                                 Clock Control Select       0 = No clock control (Default)
                                                 x                          1 = Local clock control
                                                                            65 = CCN Clock Control
                                                 Ice Configuration Select    0 = Disabled (Default)
                                                 x                          1 = Clock Control
                                                                            2 = Demand Limit Control
                                                 OAT Sensor Select          0 = Disabled, 1 = Enabled
                                                 x                          Default: 0
                                                 Remote Alarm Select        0 = Disabled, 1 = Enabled
                                                 x                          Default: 0
                                                 Alarm Reset Select         0 = Not selected, 1 = Selected
                                                 x                          (Default, allows use of LOR
                                                                            switch to reset alarms)
                                                 Close Control Select       0 = Disabled, 1 = Enabled
                                                 x                          Default: 0. See page 7
                                                 Deadband Multiplier        Default: 1.0
                                                 x.x
                                                 Current Unbalance Alarm    Alarm at 10% imbalance; 0 = Disabled, 1 = Enabled
                                                 x                          Default: 1
                                                 Voltage Unbalance Alarm    Alarm at 3% imbalance; 0 = Disabled, 1 = Enabled
                                                 x                          Default: 1
4 Reset Configuration Table                       COOLING RESET TYPE         See Demand Limit section, page 39
                                                 1
                                                 Degrees Reset at 20 mA     Default: 0
                                                 xx.x dF
                                                 COOLING RESET TYPE
                                                 2
                                                 Remote temp=No Reset       Default: 20
                                                 xx.x dF
                                                 Remote temp=Full Reset     Default: 125
                                                 xx.x dF
                                                 Degrees Reset              Default: 0
                                                 xx.x dF
                                                 COOLING RESET TYPE
                                                 3
                                                 CHW Delta T=No Reset       Default: 15
                                                 xx.x dF
                                                 CHW Delta T=Full Reset     Default: 0
                                                 xx.x dF
                                                 Degrees Reset              Default: 0
                                                 xx.x dF
                                                 COOLING RESET
                                                          32
                            Table 19 — Service Function and Subfunction Directory (cont)
          SUBFUNCTION                KEYPAD ENTRY           DISPLAY                             COMMENT
 4 Reset Configuration Table (cont)                   Demand Limit Select       0 = None (Default), 1 = Two step switch,
                                                     x                         2 = 4-20 mA, 3 = CCN Loadshed
                                                     Loadshed Group Number     0-99, Default: 0
                                                     x
                                                     Loadshed Demand Delta     0-60%,Default: 0
                                                     xxx%
                                                     Maximum Loadshed Time     0-120 min, Default: 60 min
                                                     xx min
                                                     WATER VALVE PID
CIRCUIT A PRESSURE
                                                     Discharge Pressure
                                                     xxx.x PSI
                                                     Suction Pressure
                                                     xxx.x PSI
                                                     A1 Oil Pressure
                                                     xxx.x PSI
                                                     A2 Oil Pressure
                                                     xxx.x PSI
                                                     Economizer Pressure
                                                     xxx.x PSI
                                                     CALIBRATION OFFSET
CIRCUIT B PRESSURE
                                                     Discharge Pressure
                                                     xxx.x PSI
                                                     Suction Pressure
                                                     xxx.x PSI
                                                     B1 Oil Pressure
                                                     xxx.x PSI
                                                     B2 Oil Pressure
                                                     xxx.x PSI
                                                     Economizer Pressure
                                                     xxx.x PSI
                                                     Calibrate All at 0 PSIG
                                                     No
                                                     Last Calibration Date
                                                     mmm dd - yy
See Legend on page 34.
                                                          33
                              Table 19 — Service Function and Subfunction Directory (cont)
        SUBFUNCTION                           KEYPAD ENTRY               DISPLAY                        COMMENT
   8 Manual Control Table                                         Manual Control Enable      LOR switch should be in
                                                                  Dsable                     OFF position
                                                                  Password Protected         Will be displayed if not entered
                                                                  Enter:                     earlier in current HSIO use
                                                                  Manual Control Enable
                                                                  Dsable
                                                                  Manual Control Enable      Switch LOR switch to Local
                                                                  Enable                     before proceeding
                                                                  Circuit A Compressor 1
                                                                  Off
                                                                  Circuit A Compressor 1     Provided no alarms exist,
                                                                  On                         control will attempt circuit
                                                                                             start within 2 minutes.
                                                                                             Press             to stop circuit.
                                                                  Circuit A Compressor 2               to enable,
                                                                  Off
                                                                                                       to stop
                                                                  Circuit A Loader 1                   to enable,
                                                                  Off
                                                                                                       to stop
                                                                  Circuit A Loader 2
                                                                  Off                                  to enable,
                                                                                                       to stop
                                                                  Circuit A Min Load Valve             to enable,
                                                                  Off
                                                                                                       to stop
                                                                  Circuit B Compressor 1
                                                                  Off                                  to enable,
                                                                                                       to stop
                                                                  Circuit B Compressor 2               to enable,
                                                                  Off
                                                                                                       to stop
                                                                  Circuit B Loader 1
                                                                  Off                                  to enable,
                                                                                                       to stop
                                                                  Circuit B Loader 2                   to enable,
                                                                  Off
                                                                                                       to stop
                                                                  Circuit B Min Load Valve
                                                                  Off                                  to enable,
                                                                                                       to stop
   9 Dual Chiller Configuration                                    MST SLV
                                                             34
           Table 20 — Displaying Current Software Version
                  KEYPAD
  FUNCTION        ENTRY                  DISPLAY                      COMMENT
                                                                Carrier Software Part
  Software                     Software CESR_500100 Ver         Number, where XXX is
  Version                      XXX                              the revision number.
                                           35
                                 Table 22 — Factory and Service Configuration Code Values
   UNIT MODEL NUMBER               CONF. CODE 1*            CONF. CODE 2           CONF. CODE 3             CONF. CODE 4   CONF. CODE 5
       30GX080                       11460010                 13900000               00000170                 15400521       12000093
       30GX090,105                   11560010                 13900000               00000180                 15400521       12000093
       30GX106                       11560010                 13900000               00000180                 15400521       14000095
       30GX115                       11660010                 13900000               00000190                 15400521       14000095
       30GX125                       11660010                 14600000               00000161                 15400521       14000095
       30GX136                       11660010                 15600000               00000162                 15400521       14000095
       30GX150                       11560010                 18000000               00000095                 15400521       16000097
       30GX151                       11800010                 15600000               00000176                 15400521       07000088
       30GX160                       11660010                 18000000               00000105                 15400521       16000097
       30GX161                       11800010                 16600000               00000177                 15400521       07000088
       30GX175                       11800010                 18000000               00000119                 15400521       07000088
       30GX176                       11800010                 18000000               00000119                 15400521       03000084
       30GX205                       12663910                 18000000               00000145                 15400521       07000088
       30GX206                       12803910                 16600000               00000217                 15400521       09000090
       30GX225                       12804610                 18000000               00000166                 15400521       07000088
       30GX226                       12804610                 18000000               00000166                 15400521       09000090
       30GX250                       12806610                 18000000               00000186                 15400521       09000090
       30GX251                       12808010                 16600000               00000258                 15400521       05000086
       30GX265                       12808010                 18000000               00000200                 15400521       05000086
       30HXA076                      31390010                 13900000               00000183                 15200521       02000063
       30HXA086                      31460010                 13900000               00000190                 15200521       02000063
       30HXA096                      31560010                 13900000               00000200                 15200521       02000063
       30HXA106                      31660010                 13900000               00000210                 15200521       02000063
       30HXA116                      31660010                 14600000               00000181                 15200521       02000063
       30HXA126                      31660010                 15600000               00000182                 15200521       02000063
       30HXA136                      31800010                 15600000               00000196                 15200521       02000063
       30HXA146                      31800010                 16600000               00000197                 15200521       02000063
       30HXA161                      31800010                 15600000               00000196                 15200521       02000063
       30HXA171                      31660010                 18000000               00000125                 15200521       02000063
       30HXA186                      31800010                 18000000               00000139                 15200521       02000063
       30HXA206                      32663910                 18000000               00000165                 15200521       02000063
       30HXA246                      32805610                 18000000               00000196                 15200521       02000063
       30HXA261                      32806610                 18000000               00000206                 15200521       02000063
       30HXA271                      32808010                 18000000               00000220                 15200521       02000063
       30HXC076                      21390010                 13900000               00000173                 12200521       00000058
       30HXC086                      21460010                 13900000               00000180                 12200521       00000058
       30HXC096                      21560010                 13900000               00000190                 12200521       00000058
       30HXC106                      21660010                 13900000               00000200                 12200521       00000058
       30HXC116                      21660010                 14600000               00000171                 12200521       00000058
       30HXC126                      21660010                 15600000               00000172                 12200521       00000058
       30HXC136                      21800010                 15600000               00000186                 12200521       00000058
       30HXC146                      21800010                 16600000               00000187                 12200521       00000058
       30HXC161                      21800010                 15600000               00000186                 12200521       00000058
       30HXC171                      21660010                 18000000               00000115                 12200521       00000058
       30HXC186                      21800010                 18000000               00000129                 12200521       00000058
       30HXC206                      22663910                 18000000               00000155                 12200521       00000058
       30HXC246                      22805610                 18000000               00000186                 12200521       00000058
       30HXC261                      22806610                 18000000               00000196                 12200521       00000058
       30HXC271                      22808010                 18000000               00000210                 12200521       00000058
*Unit Type will be listed as air cooled, water cooled, or remote split system. Unit type is first digit in
 Configuration Code 1 and is 1 for 30GX units, 2 for 30HXC units, and 3 for 30HXA cooling only chillers.
 For other options, see Table 19 under the Service subfunction. A label listing configuration codes is
 located on the control box door or panel.
                                                                         36
                                         Table 23 — Entering Configuration Codes
                                    KEYPAD ENTRY                                     DISPLAY RESPONSE
                                                                                     FACTORY CODES
                                                                                      Configuration Code 1
                                                                                      00000000
                                                                                      Configuration Code 1
                                                                                      21660010
                                                                                      Configuration Code 2
                                                                                      00000000
                                                                                      Configuration Code 2
                                                                                      13900000
                                                                                      Configuration Code 3
                                                                                      00000000
                                                                                      Configuration Code 3
                                                                                      00000200
                                                                                      SERVICE CODES
                                                                                      Configuration Code 4
                                                                                      00000000
                                                                                      Configuration Code 4
                                                                                      12200521
                                                                                      Configuration Code 5
                                                                                      00000000
                                                                                      Configuration Code 5
                                                                                      00000058
SCHEDULE FUNCTION — This function provides a means                     Dual Set Point Control — This feature can be enabled to
to automatically switch the chiller from an occupied mode              allow the use of a second or unoccupied cooling set point.
to an unoccupied mode. Refer to Table 24 for a complete                The function can be either switch controlled or clock con-
description of the function.                                           trolled. To enable switch control, set the Cooling Setpoint
   The schedules consist of 8 user-configurable occupied time           selection under             to 1. See page 72 or 73 of Field
periods. The control supports time schedules for local con-            Wiring section, depending on unit type, for switch input wir-
trol, remote control and ice building. These time periods can          ing to the PSIO-2 module. Configure Cool Setpoint 2 under
be flagged to be in effect or not in effect on each day of the
week. The day begins at 00.00 and ends at 24.00. The ma-                         to the desired value. The unit will then control leav-
chine is in unoccupied mode unless a scheduled time period             ing water temperature to Cool Setpoint 2 when the switch
is in effect. If an occupied period is to extend past midnight,        input is closed. To enable clock control, set the Cooling
it must be programmed in the following manner: occupied
period must end at 24:00 hours (midnight); a new occupied              Setpoint selection under           to 2. Set Cool Setpoint 2 to
period must be programmed to begin at 00:00 hours.                     the desired unoccupied value. Using            , configure lo-
NOTE: This is true only if the occupied period starts at 00:00         cal operating schedules for the desired occupied and unoc-
(midnight). If the occupied period starts at a time other than         cupied time periods. The unit will then control leaving water
midnight, then the occupied period must end at 24:00 hours             temperature to Cool Setpoint 2 during unoccupied time
(midnight) and new occupied period must be programmed                  periods.
to start at 00:00 in order for the chiller to stay in the occu-
pied mode past midnight. Each time schedule can be over-
ridden to keep the chiller in an Occupied mode for 1, 2, 3 or
4 hours on a one-time basis.
                                                                  37
                                Table 24 — Schedule Function and Subfunction Directory
       SUBFUNCTION                        KEYPAD ENTRY                           DISPLAY                          COMMENT
 1 Ice Build Schedule*                                                    SCHEDULES: OCCPC01S          Extended Occupied Time
                                                                          Timed Override: 00
                                                                          SCHEDULES: OCCPC01S          Two hour override entered
                                                                          Timed Override: 02
                                                                          MTWTFSSH OCC UNOCC           Displays current stored schedule
                                                                          01- 00000000 00:00 00:00     (First 2 numbers are schedule, 01-08)
                                                                          MTWTFSSH OCC UNOCC           Monday-Friday now occupied
                                                                          01- 11111000 00:00 00:00
                                                                          MTWTFSSH OCC UNOCC           Occupied time now set
                                                                          01- 11111000 21:00 00:00
                                                                          MTWTFSSH OCC UNOCC           Unoccupied time now set
                                                                          01- 11111000 21:00 06:30     Ice Build schedule completed
                                                                          MTWTFSSH OCC UNOCC           Can enter up to 7
                                                                          02- 00000000 00:00 00:00     additional ice build schedules
 2 Local Schedule†                                                        SCHEDULES: OCCPC02S          Extended Occupied Time
                                                                          Timed Override: 00
                                                                          MTWTFSSH OCC UNOCC           Displays current stored schedule
                                                                          01- 00000000 00:00 00:00     (First 2 numbers are schedule, 01-08)
                                                                          MTWTFSSH OCC UNOCC           Monday-Friday now occupied
                                                                          01- 11111000 00:00 00:00
                                                                          MTWTFSSH OCC UNOCC           Occupied time now set
                                                                          01- 11111000 06:30 00:00
                                                                          MTWTFSSH OCC UNOCC           Unoccupied time now set
                                                                          01- 11111000 06:30 21:00     Local schedule completed
                                                                          MTWTFSSH OCC UNOCC           Can enter up to 7
                                                                          02- 00000000 00:00 00:00     additional local schedules
 3 Remote Schedule                                                        SCHEDULES: OCCPC65S          Extended Occupied Time
 (Currently Not                                                           Timed Override: 00
 Used)                                                                    MTWTFSSH OCC UNOCC           Displays current stored schedule
                                                                          01- 00000000 00:00 00:00     (First 2 numbers are schedule, 01-08)
                                                                          MTWTFSSH OCC UNOCC           Monday-Friday now occupied
                                                                          01- 11111000 00:00 00:00
                                                                          MTWTFSSH OCC UNOCC           Occupied time now set
                                                                          01- 11111000 06:30 00:00
                                                                          MTWTFSSH OCC UNOCC           Unoccupied time now set
                                                                          01- 11111000 06:30 21:00     Remote schedule completed
                                                                          MTWTFSSH OCC UNOCC           Can enter up to 7
                                                                          02- 00000000 00:00 00:00     additional remote schedules
 4 Holiday Configuration**                                                 HOLIDAYS : HOLDY_01          Can configure holiday start day
                                                                          Starts on 00/00 00 days      and duration
                                                                          HOLIDAYS : HOLDY_01          Start of holiday set
                                                                          Starts on 12/23 00 days
                                                                          HOLIDAYS : HOLDY_01          Holiday duration set
                                                                          Starts on 12/23 10 days
 5-33 Holiday Configuration            through                             HOLIDAYS : HOLDY_02          Allows configuration of 29
                                                                          Starts on 00/00 00 days      additional holiday periods
*Ice configuration select must be set to 1 for clock control. The ice configuration can be accessed by pressing          and scrolling down.
†Clock control select must be set to 1 for clock control. The clock control can be accessed by pressing and scrolling down.
**The BROADCAST function (BRODEFS table) must be activated (change to YES and download) when using the LID-2B controller, Building
Supervisor or ComfortWorks™ software for the control to recognize holidays.
                                                                     38
Temperature Reset — The control system is capable                       RETURN FLUID TEMPERATURE RESET — In this ex-
of providing leaving fluid temperature reset based on return             ample, the unit set point is reset from full load based on the
fluid temperature. Because the temperature difference be-                chilled fluid return temperature. The example uses a reset
tween leaving and return temperature is a measure of the                value of 10 degrees at full reset. Full reset is at a 2-degree
building load, return fluid temperature reset is essentially an          temperature difference across the cooler and no reset would
average building load reset method.                                     be at a 10° F difference across the cooler. See Fig. 10 and
   Under normal operation, the chiller maintains a constant             Table 28.
leaving fluid temperature approximately equal to the chilled             Demand Limit — Demand Limit is a feature that allows
fluid set point. As building load drops from 100% down to                the unit capacity to be limited during periods of peak energy
0%, entering cooler fluid temperature drops in proportion to             usage. There are 3 types of demand limiting which can be
load. Thus, the temperature drop across the cooler drops from           configured. The first type is through 2 switch inputs, which
a typical 10° F (5.5° C) at full load to a theoretical 0° F             will reduce the maximum capacity to 2 user-configurable per-
(0° C) at no load. See Fig. 8.                                          centages. The second type is by a 4 to 20 mA signal input
   At partial load, leaving chilled fluid temperature may be             which will reduce the maximum capacity linearly between
lower than required. If this is allowed to increase (reset), the        100% at a 4 mA input signal (no reduction) down to the user-
efficiency of the chiller increases. Amount of reset can be             configurable level at a 20 mA input signal. The third type
defined as a function of cooler temperature drop. This is a              uses the CCN Loadshed module and has the ability to limit
simple linear function that requires 3 pieces of input data for         the current operating capacity to maximum and further re-
the set function that will vary depending on measurement                duce the capacity if required.
method used. See the following sections and Table 25.                      To use Demand Limit, select the type of demand limiting
NOTE: Reset set points are not accessible unless the reset              to use. Then configure the Demand Limit set points based on
function is enabled first. The Control Point will be recalcu-            the type selected.
lated taking into account the set point plus the amount of
reset. This is done as a field configuration. Select one of the           DEMAND LIMIT (Switch Controlled, 30GX only) — In this
3 choices for type of reset: Return Fluid Reset, External Tem-          example, demand limit by switch control will be configured
perature Reset, or 4 to 20 mA Signal Reset. See Table 25.               and the switch set points will be set at 75% and 40%. Ca-
                                                                        pacity steps are controlled by 2 relay switch inputs field wired
   If dual set point control is enabled, the amount of reset is         to PSIO-2, terminal 28 for switch 1 and terminal 25 for switch
applied to whichever set point is in effect at the time.                2. See Table 29.
   Tables 26-28 demonstrate how to activate reset.                         For Demand Limit by switch control, closing the first stage
EXTERNAL TEMPERATURE RESET — In this example,                           demand limit contact will put the unit on the first demand
the unit set point is reset from full load at 90 F (32 C) to a          limit level. The unit will not exceed the percentage of ca-
maximum reset value of 10° F (5.5° C) at 25 F (−6.7 C)                  pacity entered as Demand Switch 1 set point. Closing con-
outdoor ambient. This means that if the chilled fluid set point          tacts on the second demand limit switch prevents the unit
is 44 F (6.7 C), there is no reset if the temperature is 90 F           from exceeding the capacity entered as Demand Switch 2
(32 C). At a temperature of 25 F (−6.7 C), the chilled fluid             set point. The demand limit stage that is set to the lowest
set point would be reset to 54 F (12.2 C). See Fig. 8 and               demand takes priority if both demand limit inputs are closed.
Table 26. A field-supplied outdoor air thermistor must be con-           If the demand limit percentage does not match unit staging,
nected to PSIO-2 as shown in Fig. 37.                                   the unit will limit capacity to the closest capacity stage.
   To activate this function for space temperature reset leave             To Disable Demand Limit: Enter                    as shown
both the External Reset Sensor Select and the OAT Sensor                in Table 29. Scroll down to Demand Limit Select and press
Select at 0, and change the Select/Enable Reset Type to 2,
following the procedure in Table 26.                                              to select no Demand Limit control.
EXTERNALLY POWERED RESET (4 to 20 mA) — In this
example, the unit set point is reset from full load at 4 mA to
a maximum reset value of 10° F (5.5° C) at 20 mA. See
Fig. 9 and Table 27.
                                                                   39
 Fig. 8 — Cooling External Temperature Reset
40