Version : Beta 3.
                                              IEEE Lead Acid Battery Sizing
    Enquiry Details
                 Enquiry Number                    :
                 Date                              : March 22, 2024
                 Customer                          :
                 Project                           :
    Sizing Inputs             ( IEEE 485 Based )
                 Nominal System Voltage            :     192.00 V
                 Minimum System Voltage            :     172.80 V
                 Maximum System Voltage            :     216.00 V
                 Minimum Cell Voltage              :      1.800 V
                 Number of Blocks                  :         16 Nos
                 Minimum Temperature               :    25.00 °C
                 Design Margin                     :       1.00
                 Aging Factor                      :       1.25
                 Spare Capacity Factor             :       1.00
                 Cell Type                         :   12V SMF (Optimuz Series)
                 Power Factor                      :       0.80
                 Inverter Efficiency               :      90.00 %
               Load Profile : Power ( KVA )
                  S. No.            Load (KVA)                    Duration (mins)         Equivalent Amps
                        1              5.00                            30.00                        25.72
Page 1 of 2                 The document becomes contractual only after HBL acceptance and acknowledgement of a purchase order
 Version : Beta 3.0
                                                      Battery sizing calculation sheet IEEE 485
Minimum Expected                 Minimum
Temperature : 25°C               Cell Voltage: 1.800 V        Cell Type: 12V SMF (Optimuz Series)            Sized By:
   (1)         (2)            (3)               (4)                (5)                       (6)                            (7)
Period        Load          Change in         Duration           Time To End of           Capacity Rating           Required Section Size
                              Load            of Period              Section                  Factor              (3) x (6) =Rated Amp hrs
           (amperes)        (amperes)         (minutes)              (minutes)             t Min Rate(Kt)       Pos. Values      Neg. Values
Section 1 - First 1 Period Only - if A2 is greater than A 1, go to Section 2
    1    A1 = 25.72     A1-0 = 25.72        M1 = 30        t=M1= 30                                  1.092               28.09           0.00
                                                                           Section   1   Sub Total                       28.09           0.00
                                                                                         Total                           28.09
Uncorrected Size (US) (8) 28.09 Ah x Design Margin (9) 1.00 x Aging Factor (10) 1.25 x Temperature factor (11) 1 x Spare
capacity factor (12) 1 / State of Charge Factor 1.00 = (13) 35.11 Ah
When the cell size (13) is greater than a standard cell size, the next larger cell is required.
Required cell size (14) 35.11 Ampere Hours. Therefore, cell (15) OPTI 42 is required
    Battery Proposal
              Calculated Capacity          : 35.11
              Proposed Battery Model       : 1 x 16 x OPTI 42
              Nominal Capacity             : 42 Ah
    Battery Settings
         1. Minimum System Voltage = Number of Blocs x 6 x ECV = 172.8 V
         2. Maximum System Voltage during Float = Number of Blocs x 6 x 2.28 = 218.88 V
         3. Maximum System Voltage during Boost = Number of Blocs x 6 x 2.33 = 223.68 V
Page 2 of 2               The document becomes contractual only after HBL acceptance and acknowledgement of a purchase order