                 SPECIFICATION
                  CFE K0000-04
                                                  MAY 2015
                                            REVIEW AND REPLACE THE
                                           EDITION OF NOVEMBER 2007
                   MEXICO
                                   TRANSFORMACIÓN MONOFÁSICOS TIPO                        ESPECIFICACION
                                PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                             SUBTERRÁNEA                                    CFE K0000-04
CONT IN Yo d EITHER
1 OBJECTIVE 1
2             FIELD APPLICATION                                                                               1
3             RULES THAT APPLY                                                                                1
4.8 Protection 9
4.9 Oil 12
4.10 Bushings 12
4.12 Accessories 12
4.14 Drawings 13
5 CONDITIONS OF OPERATION 14
8             CONTROL OF QUALITY                                                                             14
8.1           Tests                                                                                          15
9 MARKED 16
    790712    Rev     791123    880315    920115   640114   961004   980306   990306   991008   050121   050812
    071130   150529
                                 TRANSFORMACIÓN MONOFÁSICOS TIPO                         ESPECIFICACION
                              PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                           SUBTERRÁNEA                                     CFE K0000-04
9.6 ID Internal 17
9.7        ID External                                                                                      17
9.8        Signs Preventive of Risk                                                                         17
TABLE 1 Single-phase pedestal-type transformers up to 100 kVA for underground distribution 2 TABLE 2
 790712     Rev     791123    880315   920115   640114   961004     980306   990306   991008   050121   050812
 071130   150529
                                   TRANSFORMADORES MONOFÁSICOS TIPO                              ESPECIFICACION
                                 PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                              SUBTERRÁNEA                                          CFE K0000-04
                                                                                                                   1 de 24
1            PURPOSE
Establish the characteristics that they must achieve the transformers of distribution single-phase until 100 kVA type
pedestal that They installed in the networks of distribution underground of the Federal Commission of Electricity (CFE).
2             APPLICATION FIELD
HE apply to transformers with cooling natural in oil mineral, single-phase until 100 kVA, for operate insystems with
nominal voltages up to 34.5 kV.
ISO ISO 261-1998 General Purpose Metric Screw Threads - General Plan.
    790712    Rev     791123     880315   920115   640114     961004       980306   990306    991008     050121    050812
    071130   150529
                                         TRANSFORMADORES MONOFÁSICOS TIPO                                         ESPECIFICACION
                                       PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                                    SUBTERRÁNEA                                                     CFE K0000-04
2 de 24
NOTE:            In case of that the documents previous be reviewed either modified, has to be used the edition current in the date of
                 publication of the announcement to the tender, except that the CFE indicate something else
The transformers to the that he refers this specification he indicate in the TABLE 1 and 1A, and they must achieve
with itindicated in the present and it applicable of the rule NMX-J-285-ANCE. They must be of the type of forehead dead.
TABLE 1 - Transformers single-phase type pedestal until 100 kVA for distribution underground
                                                                                                                                 Continúa…
    790712       Rev       791123      880315     920115       640114      961004      980306     990306      991008    050121     050812
    071130      150529
                                      TRANSFORMADORES MONOFÁSICOS TIPO                                     ESPECIFICACION
                                    PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                                 SUBTERRÁNEA                                                 CFE K0000-04
3 de 24
Continuación…
790712          Rev        791123   880315        920115   640114      961004     980306    990306      991008    050121     050812
071130         150529
                                      TRANSFORMADORES MONOFÁSICOS TIPO                                  ESPECIFICACION
                                    PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                                 SUBTERRÁNEA                                              CFE K0000-04
4 de 24
Continuación…
4.1.1 Altitude
The transformers single-phase to that he refers this specification they must be built for operate to 2 300 m
snm
The transformers to that he refers this specification they must be designed for operate to a a m b i e n t
temperature maximum of 40 °C and to a temperature half of 30 °C in a period of 24 h.
 790712        Rev        791123   880315       920115    640114    961004    980306       990306    991008   050121   050812
 071130       150529
                                   TRANSFORMADORES MONOFÁSICOS TIPO                           ESPECIFICACION
                                 PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                              SUBTERRÁNEA                                       CFE K0000-04
5 de 24
The capabilities nominal are: (25, 37.5, 50, 75 and 100) kVA.
The rated voltage primaries are: (13 200YT/7 620) V, (22 860YT/13 200) V and (33 000YT/19 050) V.
4.2.3 Connections
4.2.4 Impedance
The impedance voltage must be measured at nominal current and frequency. The impedance expressed in percent of
the impedance voltage and with respect to the nominal voltage is corrected to the reference temperature of 75 °C for
transformers type warm and 85 °C for transformers normal and has to achieve with the values indicated in the rule
NMX-J-285-ANCE.
The bidder must report the impedance value along with the proposal. Value that should be considered for the evidence
of acceptance.
The excitation current should not be more than 1.0%. The bidder must inform the value of the excitation current
together with the proposal.
The values of losses in maximum vacuum Pv and totals Pt they must achieve with the rule NMX-J-285-ANCE.
4.2.7 Efficiency
The efficiency of the transformers covered by this specification, at nominal load and considering factor of unitary
power, must comply with what is indicated in the NOM-002-SEDE standard. The bidder must indicate the value of the
efficiency together with his proposal.
4.2.8 Polarity
The switches employees in secondary protection They should have losses minors to those established in the TABLE
2.
 790712      Rev        791123   880315    920115     640114    961004   980306   990306   991008   050121   050812
 071130     150529
                                     TRANSFORMADORES MONOFÁSICOS TIPO                                      ESPECIFICACION
                                   PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                                SUBTERRÁNEA                                                 CFE K0000-04
6 de 24
NOTE: These losses No HE find included in the losses totals indicated in the rule NMX-J-285-ANCE.
Guarantee nominal values of: excitation losses and voltage losses must be provided. load, which must comply with the
provisions of this specification and are subject to bidding and penalties according to the CFE specification K0000-03.
The object transformers of this specification they must be for a elevation of Temperature of 65 °C.
The CFE may request a temperature increase of 55 °C, subject to bidding with those of 65 °C in equal quantities.
conditions.
In the Particular Characteristics it must be indicated when they are required. If not done, it is understood that the
transformers required are for install in environments with temperature normal as HE describe in he subsection 4.1.2.
Warm pad-type transformers used in hot climate areas where the maximum temperature of the ambient exceeds 40°C
and the average ambient temperature during any 24-h period exceeds 30°Cthey must comply with it following:
Elevation of temperature average of the windings of 55 °C, with ability thermal of the isolations of 65 °C.
The transformers object of this specification they must achieve with it indicated to continuation.
             a)      Where No he specify, the location of the different items (fuses, crank of operation, among others)
                     must be such that it does not prevent or be impeded its operation and/or replacement, by the the
                     rest items of the transformer neither by the cables once that these be installed.
             b)      He background and he clear minimum of the cabinet must have the following dimensions.
                                           Voltage           Distance             Clear
                                               kV              (cm)               (cm)
                                            fifteen             33                27.94
                                            25.33             40.64               35.56
             c)      The cabinet shall have grade 316 stainless steel hinges at the top, positioned in such shape that
                     he cabinet No can break off and has to be folding toward above for that
 790712      Rev       791123     880315      920115     640114      961004     980306      990306     991008   050121   050812
 071130     150529
                                   TRANSFORMADORES MONOFÁSICOS TIPO                               ESPECIFICACION
                                 PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                              SUBTERRÁNEA                                           CFE K0000-04
7 de 24
                    rest on top of tank. It must have flashings so that when opened, the Deposited water is not poured
                    onto the accessories and cables of the transformer. You must have a device located at the bottom
                    and center of the cabinet to open or close it and count with a holder padlock.
            d)      When the force required to be applied to the cabinet to open it is greater than 245.16 N, it It must be
                    made up of two sections with grade 316 stainless steel hinges on the back. top, positioned in such a
                    way that the cabinet sections cannot be detached and must be be foldable upwards so that they
                    rest on the top of the tank. One for the down tension and another for the half voltage, which should
                    not be opened without first opening the low voltage. The union between sections for the half and the
                    low voltage must be such that it does not allow the entry of water inside. The two sections of the
                    cabinet must have flashings so that when they are open, the deposited water does not spill on the
                    accessories and cables of the transformer. Has to have a device located at the bottom and center of
                    the cabinet to open or close when himself and count on a holder padlock.
            e)      The bridges of half tension should be made with flexible copper cables of the porta type electrode,
                    that have one section cross of the ampacity appropriate.
            f)      The connections between shoes and bridges must be soldered or by means of connectors
                    compression.
            g)      The nuts used in electrical connections must be safety type and have locknut or any half that
                    prevent he loosen
            h)      He tank and The gabinet they must achieve with what is indicated in he paragraph 4.13 and with he
                    subsection 4.5.7
            i)      The tank cover must be welded, without hand register and with a slope of 1° to 2° to avoid the
                    accumulation of water in the surface,.
j) The cabinet lid should have a slope of 1° to 2° to prevent water accumulation in the surface.
            k)      Screws in contact with the environment must be made of grade stainless steel. 304 or 316, their
                    corresponding nuts and sheaves they must be of steel grade stainless 304.
            l)      The tightening screws of the nozzle flanges half and low voltage must have a locknut either any
                    half that prevent that HE loosen
            m)      The expulsion fuses must be provided with anti-spill trays to prevent the take them out, he oil HE
                    leak about the cables.
            n)      The lock must be provided with a padlock holder and be such that it cannot be used as a nest of
                    animals and insects.
These equipment No They carry changing table of derivations to less that the CFE it require in whose case HE has to
indicate inthe Characteristics Individuals.
When it require, he changing table of derivations has to be of operation abroad and achieve with it indicated in the
rule NMX-J-285-ANCE.
 790712     Rev       791123    880315     920115    640114    961004    980306     990306    991008    050121      050812
 071130    150529
                                   TRANSFORMADORES MONOFÁSICOS TIPO                               ESPECIFICACION
                                 PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                              SUBTERRÁNEA                                              CFE K0000-04
8 de 24
All permanent current-carrying connections, except threaded connections, must be joined by welding or through
connectors type compression.
He core has to meet electrically connected to the tank in a only spot by half of a driver of copper.
The conductor of the windings in half and low voltage must be made of copper and/or aluminum, with the mechanical
resistance necessary for bear the efforts of short circuit of agreement with the rules NMX-J-169-ANCE and NMX-J-
285-ANCE.
The insulation must be compatible with the transformer oil, its thermal class must be at least 105, according to the
NMX-J-153-ANCE standard; In addition, its dielectric, chemical, mechanical, thermal characteristics, among others,
they must be properly selected for he correct functioning of the transformers here specified.
Has to count with a base that medium he weight of the transformer and that allow move it to it long of their axles
longitudinal and transversal by half of rollers.
All the zones of the cabinet in contact with he pedestal they must be designed for reduce to the maximum his
corrosionand comply with he paragraph 4.13.
He tank and he cabinet they must be manufactured of a material whose characteristics comply with any of the
steels AISI-1018, AISI-1025 AND ASTM A-36.
In a coastal or pollution zone, grade 304, 316 or metallized stainless steel should be used, as indicated. indicate in
Features Individuals and according to the TABLE 3.
These equipment No they will carry indicator of failure to less that CFE it require in whose case HE has to indicate
in the
Characteristics Individuals.
In case of have indicator of failure the covers either indicators luminous they must be installed in the wall frontal
either side of the cabinet, of the side of half voltage (corner superior left) and protected for avoid damage by
vandalism, of such shape that HE can appreciate he state of the indicator without open the door of the cabinet.
(See figure 4).
 790712      Rev      791123     880315    920115    640114     961004     980306    990306    991008     050121   050812
 071130     150529
                                   TRANSFORMADORES MONOFÁSICOS TIPO                           ESPECIFICACION
                                 PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                              SUBTERRÁNEA                                        CFE K0000-04
9 de 24
The ropes of nuts, screws and plugs they must correspond to the of the system international of units (NOM-008-SCFI)
and be of agreement with the rule ISO 261.
The interior of the tank must be free of debris, burrs or any other foreign element, which is deposited in the
background of the tank, in the reels either stay suspended in he oil.
He tank of the transformer has to be built for bear, completely assembly, a pressure internal of 69 kPa during 2 h,
either a pressure internal minimum of fifty kPa during 3 h, without introduce a deformation final elderlyOf 2 %.
The transformer must have a cabinet in which the medium and low voltage terminals are housed, as well as the
accessories, which must prevent the entry of water that affects the operation of the transformer. Should not have
screws exposed or other fastening means that can be removed from the outside nor holes through which can be
introduced foreign objects like rods either wires.
The thickness of the cabinet sheet must be according to the supplier's design and have the mechanical resistance
necessary for bear he driving normal, so much in he transport as in he mounting, without that suffer deformation
some owing pass the evidence that indicate in this specification.
All areas of the cabinet in contact with the pedestal must be designed to minimize corrosion and achieve with the
paragraph 4.13.
The disconnector for ring operation must be provided by separable insulated connectors type elbow operation. with
burden for 200 TO.
The connections and internal elements of the transformer that are part of the ring must be designed to bear the current
keep going and of failure of the ability of the ring.
The endurance maximum measure between the Bushings of the side to and of the side b has to be equal or less to 200
 .
4.8 Protection
 790712      Rev     791123     880315    920115   640114     961004    980306   990306    991008    050121    050812
 071130    150529
                                    TRANSFORMADORES MONOFÁSICOS TIPO                                  ESPECIFICACION
                                  PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                               SUBTERRÁNEA                                              CFE K0000-04
10 de 24
Transformers must have two fuses connected in series and properly coordinated each other. Both fuses they must be
submerged in oil in he inside of the tank which are described at continuation:
             a)      Fuse of expulsion "FE" of double element type bayonet operation internal, that can bereplaced
                     externally by medium pole with the characteristics indicated in the TABLE 4.
             b)      Fuse limiter of current "FLC" of sand silver of interval partial with characteristics indicatedin the
                     TABLE 5.
He fuse of expulsion "FE" has to operate only when happen a failure of low current internal in he transformer and/or an
open fault in the low voltage network and have the capacity to interrupt load current of according to it indicated in the
TABLE 4.
He fuse limiter of "FLC" current of interval partial has to interrupt high currents.
 790712      Rev       791123     880315    920115     640114     961004     980306    990306     991008     050121     050812
 071130     150508
                                    TRANSFORMADORES MONOFÁSICOS TIPO                                ESPECIFICACION
                                  PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                               SUBTERRÁNEA                                            CFE K0000-04
11 de 24
When indicated in the Particular Characteristics , a thermal switch or thermomagnetic in the secondary, immersed in
oil, placed on the low voltage side according to the capacity of the transformer and coordinated with the single element
expulsion fuses and interval current limiter partial whose general characteristics are contained in tables 4 and 5
described above, and must comply with the following:
             a)      For 25 kVA transformers, it must have a low voltage thermal switch, which has thermal trip against
                     overloads and short circuits. Its interrupting capacity must be as minimum 6 000 TO symmetrical
                     effective.
             b)      For transformers of (37.5, 50, 75 and 100) kVA, it must have a thermomagnetic switch of low
                     voltage, which has instantaneous trip for short circuit protection, and its capacity interruptive must be
                     as minimum of 10 000 TO symmetrical effective.
The switches indicated in the points to) and b) they must count with it following:
             a)      Have emergency control that allows the transformer to temporarily carry an overload of
                     approximately 10 % of his Rated capacity,
             b)      The operating handle must be located in the low voltage compartment and be constructed for
                     operate with pole.
When the transformer is supplied with a thermal or thermomagnetic switch, they must be included on the data plate.
the following characteristics of the switch: brand, type, number of Catalogue, voltage nominal, Rated capacity,
 790712      Rev       791123     880315    920115     640114     961004     980306   990306    991008     050121    050812
 071130     150529
                                  TRANSFORMADORES MONOFÁSICOS TIPO                               ESPECIFICACION
                                PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                             SUBTERRÁNEA                                           CFE K0000-04
12 de 24
ability interruptive (amps symmetrical) and he level essential of isolation to the impulse. Additionally he has to include
his location in the diagram unifilar The data of the switch they can include in a plate for separate.
4.9 Oil
The supplier must supply the transformers with the necessary insulating oil, which must be of the specified type. in the
rule NMX-J-123-ANCE.
4.10 Bushings
The Bushings half and low voltage must be removable, to be able to be removed from the outside. No they must weld
to the wall of the tank for it that they must be installed through a system screwable.
It must have two well-type Bushings installed in a horizontal position in such a way that the oil from the equipment
covers completely the internal part of the terminal in accordance with the provisions of the CFE 55000-99 specification,
located as indicated in figure 2. The Bushings must be protected with covers weatherproof during transportation or
storage.
It must have two well-type Bushings installed in a horizontal position in such a way that the oil from the equipment
covers completely the part internal of the terminal.
It must have three bolt-type Bushings of dimensions, driving capacity and rope suitable for can install straight
connectors for at least 4 circuits, compatible with various brands and localized as he indicates in the figure 2. He
supplier has to provide these connectors.
The low voltage neutral must exit through an insulated bushing and must be connected externally to the tank by half of a
bridge removable of copper flexible, proportionate by the supplier.
The transformers referred to in this specification must not exceed the maximum dimensions indicated in the rule NMX-
J-285-ANCE.
4.12 Accessories
A 25.4 mm diameter nipple with a weatherproof material plug must be placed on the wall of the tank and on the side of
low voltage for he fill and proof of air tightness.
The joints (gaskets) must be made of an elastomeric material that meets the characteristics indicated in the table 12 of
the NMX-J-285-ANCE standard, compatible with the insulating liquid, according to the method and limits indicated in
he Appendix B of the rule NMX-J-285-ANCE.
 790712      Rev      791123    880315    920115    640114     961004    980306    990306    991008     050121    050812
 071130    150529
                                      TRANSFORMADORES MONOFÁSICOS TIPO                           ESPECIFICACION
                                    PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                                 SUBTERRÁNEA                                      CFE K0000-04
13 de 24
The valve relief manual and automatic, has to achieve with it indicated in the rule NMX-J-285-ANCE.
a) Hooks for lift the transformer complete, the which they must be removable.
            b)      He has to place a nipple of 25.4 mm of diameter with plug of material to proof of outdoor,in the
                    wall of the tank and of the side low voltage for sewer system and sampling.
The tank and the transformer cabinet must have a coating that protects them against corrosion, which in turn time, has
to comply with the values indicated in the rule NMX-J-285.
The supports of the core-coil assembly must be free of oxidation and must not necessarily have covering.
Alternatively he can use he color Munsell 7GY 3.29/1.5 (“ANSI” pedestal green): L* = 31.07, a*= -7.73, b* = 8.11,
which must comply with the standardized “CIELAB” alternative color scale, with the observer at two degrees and light
of day.
For all colors the maximum acceptable color difference is 2.5 measured according to reference [1] of the chapter 11 of
this specification.
In any case, the supplier must provide a written guarantee corresponding to the treated surface, so as not to require
maintenance during 10 years.
4.14 Drawings
Before proceeding to manufacture the prototype, the supplier must deliver to the Normalization Management
Distribution, a game of the following drawings, for your review and approval, according to the Procedure of delivery
and revision of plans of transformers of distribution underground.
- Data,
 790712     Rev         791123      880315   920115   640114   961004   980306   990306    991008     050121    050812
 071130    150529
                                       TRANSFORMADORES MONOFÁSICOS TIPO                          ESPECIFICACION
                                     PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                                  SUBTERRÁNEA                                      CFE K0000-04
14 de 24
e) Of dimensions generals,
The drawings they must comply with it described in he Appendix to of this specification.
He made to approve the drawings No exempt to the supplier of the responsibility and obligation of correct any flaw
either deficiency that means danger either evil operation and that there would not have been been noticed in the
drawing review.
Subsequently, he supplier has to introduce to the Management of LAPEM either the person physical either moral that HE
designate witheach prototype a game of approved drawings.
The transformers they must be designed and manufactured for reach a life useful expected of when lesstwenty
years, low the conditions of operation and atmosphere defined in the present specification.
By each place of delivery, he supplier has to deliver with his equipment, a manual of operation and maintenance
writings in language spanish from according to it indicated in the rule of reference NRF-002-CFE.
In the manuals HE they must include the recommendations of overload and The pairs of
squeeze in.He bidder must provide to the CFE the data That request in it Appendix B.
5 CONDITIONS OF OPERATION
No applies.
No Apply.
No applies.
8 CONTROL OF QUALITY
The CFE represented by the Management of the LAPEM either the person physical either moral that this designate,
has to verify thatall the transformers comply with the evidence of prototype and of acceptance contained in this chapter.
    790712     Rev         791123    880315    920115     640114   961004   980306   990306   991008   050121    050812
    071130    150529
                                       TRANSFORMADORES MONOFÁSICOS TIPO                           ESPECIFICACION
                                     PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                                  SUBTERRÁNEA                                       CFE K0000-04
15 de 24
8.1 Evidence
All tests must be carried out on all transformers, in accordance with the NMX-J-123-ANCE standards, NMX-J-169-
ANCE and NMX-J-285-ANCE, in the order that HE enunciate to continuation:
The transformer supplier is responsible for carrying out the evaluation and monitoring of the quality of its subsuppliers,
as well as being responsible for the quality and the consequences derived from defects that they could introduce
oneself in any of the supplied components by third parties.
They must be carried out the following sampling tests in accordance with standard NMX-Z-012, part 1, 2 and 3, to
which transformers in presence of the staff of LAPEM of control of Quality either representative:
a) Characteristics physical.
g) Voltage Induced.
a) Short circuit.
16 de 24
Besides of achieve with these essays, has to of satisfy the evidence of acceptance.
Any changes made by the supplier in the materials or design of the transformer invalidate the testing.prototype.
The absorption rate test is not applicable to transformers with thermal or thermomagnetic switching in low voltage, in
the test resistance of isolation of low against high further tank.
The values of acceptance for the evidence of the isolations of the core – coil:
              a)      Endurance of isolation
                      minimum:                                     1 000 MΩ by kV to twenty °C
              b)      Index of absorption
                      ((60/30)s) minimum:                          1.2
9 MARKED
Each transformer must have a plate that permanently shows the equipment data which must contain as minimum the
information That indicates in the rule NMX-J-285-ANCE, So as he number of the contract.
An additional data plate must be provided to the data plate, permanently indicating the torques tightening of the screws
used to fasten the Bushings half and low voltage and in general where they exist together.
The characteristics of the fuses they must mark in the data plate of the transformer either in a plate additional.
9.4 ID of Bushings
The nozzle identifications must be permanent with a height of no less than 15 mm and placed in a that are not covered
by cables or connection accessories, the letters must be of a color that contrasts with that of the transformer.
In the prototype transformer, in the tank, the cover and the upper internal frame that fixes the core-coil assembly The
serial number of the transformer must be marked, with a strike number, at least 10 mm high, additionally to indicate it
in the plate of data.
    790712    Rev       791123    880315       920115   640114   961004   980306     990306    991008    050121       050812
    071130   150529
                                 TRANSFORMADORES MONOFÁSICOS TIPO                               ESPECIFICACION
                               PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                            SUBTERRÁNEA                                           CFE K0000-04
17 de 24
9.6 ID Internal
Internal points and terminals that are connected must be marked with matching numbers or letters. with those marked
on the plate. These identifications must be made using plastic tapes or labels, cardTABLE compressed either
materials Similar engraved to low relief either about relief No minor to 5 mm, clamped to each terminal or
recorded directly on it so that they can be easily seen. They can also be used ribbons engraved, but never painted
numbers or attached labels.
9.7 ID External
On the transformer tank, near the low voltage bushings, the nominal capacity data must appear. in kVA, with letters
and numbers not less than 65 mm Tall and painted in color that contrast with that of transformer.
On the outside of the transformer, on the upper front of the cabinet, 50 mm from the upper edge, it must be placed a
warning preventive permanent and reflective equal to the indicated in the figure 6.
He supplier has to send the transformers duly protected, with a base of wood of perimeter complete with
dimensions of 25 mm per side and with a minimum clearance between the base and the floor of 25 mm to avoid
crashes and frictions between the teams during he transport, driving and storage.
11 BIBLIOGRAPHY
[1]         ASTM – d2244-2002                               Standard practice for Calculation of Color Tolerances and
                                                            Color Differences from Instrumentally Measured Color
                                                            Coordinate.
12 CHARACTERISTICS INDIVIDUALS
In accordance with what is established in this specification and the conditions of use imposed by the user, it is made
necessary indicate in he Format exhibit, CPE-327 of the Characteristics Individuals, that complement the
requirements of specification.
 790712     Rev      791123    880315    920115    640114      961004   980306    990306     991008   050121    050812
 071130    150529
                           SINGLE PHASE PEDESTAL TYPE TRANSFORMERS UP TO 100kVA                     SPECIFICATION
                                     FOR DISTRIBUTION UNDERGROUND                                       CFE K0000-04
18 of 24
790712 Rev 791123 880315 920115 640114 961004 980306 990306 991008 050121 050812
071130   150529
                             TRANSFORMADORES MONOFÁSICOS TIPO                         ESPECIFICACION
                           PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                        SUBTERRÁNEA                                    CFE K0000-04
19 de 24
790712    Rev     791123   880315   920115   640114   961004    980306   990306   991008   050121    050812
071130   150529
                               TRANSFORMADORES MONOFÁSICOS TIPO                              ESPECIFICACION
                             PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                          SUBTERRÁNEA                                          CFE K0000-04
20 de 24
790712     Rev      791123   880315      920115   640114   961004    980306      990306   991008   050121    050812
071130    150529
                                    TRANSFORMADORES MONOFÁSICOS TIPO                              ESPECIFICACION
                                  PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                               SUBTERRÁNEA                                          CFE K0000-04
21 de 24
APPENDIX TO
Is requirement indispensable that he supplier present blueprints for the authorization by part of CFE, the which they must
include as minimum the following information:
            a)      Drawings, sizing the main parts of the product, in their “plan”, “front” views (elevation) and a "side",
                    with notes in mm and No necessarily to scale.
            b)      List of component parts, referencing the concept number for ID in he drawing, indicating the
                    number of pieces, description of the concept and also indicating the brand, the catalog number and
                    the corresponding reference CFE specification number. When the concept be a electrical operating
                    element, indicate by separated in the same plane, in shape of TABLE the characteristics electrical
                    main and draw he detail correspondent.
            c)      All the information has to be in language Spanish, with units of extent of the System International of
                    Units.
            d)      The plans must have in the reference table at least the name of the product with the main nominal
                    characteristics, brand, model, type, supplier catalog number and when it is a prototype indicate it,
                    the CFE specification number, as well as the signatures of the relevant officials of the supplier;
                    authorization and validity dates. Immediately Above this box, a vertical blank space of (100 X 125)
                    mm should be left for stamps and satisfactory signatures. By folding the plan to letter size, the
                    reference table and the space for seal, they must meet in front.
            e)      The drawings that complement the information of “General Dimensions” and “Interior Set”, they
                    must introduce oneself by separate either in a single flat and are the following:
f) Plates data: Must achieve with which establishes the rule NMX-J-285-ANCE.
            g)      The “General Dimensions” and “Interior Set” plans must be of a manageable size, multiple of size
                    letter and maximum to double letter.
h) The protection coordination sheet must be in double letter size, and may also be in size letter.
 790712     Rev         791123    880315    920115    640114    961004    980306    990306     991008    050121     050812
 071130    150529
                                 TRANSFORMADORES MONOFÁSICOS TIPO                              ESPECIFICACION
                               PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                            SUBTERRÁNEA                                          CFE K0000-04
22 de 24
APPENDIX b
INFORMATION TECHNIQUE
REQUIRED
                                                                                                         23 de 24
Compliant with the together (packaging)
                                                                                            Keep going…
 790712     Rev      791123   880315      920115   640114   961004   980306   990306   991008   050121    050812
 071130    150529
                                   TRANSFORMADORES MONOFÁSICOS TIPO                             ESPECIFICACION
                                 PEDESTAL HASTA 100 kVA PARA DISTRIBUCIÓN
                                              SUBTERRÁNEA                                         CFE K0000-04
24 de 24
Continuation…
Bidder: Representative:
 790712      Rev      791123     880315     920115    640114   961004     980306    990306   991008   050121     050812
 071130     150529
                                             COMMISSION FEDERAL OF ELECTRICITY
                                             CHARACTERISTICS INDIVIDUALS FOR: TRANSFORMERS SINGLE PHASE TYPE
                                             PEDESTAL UNTIL 100 kVA FOR DISTRIBUTION UNDERGROUND
CHARACTERISTICS
Description short:
             For the manufacturing of tank and of the cabinet select one of the combinations of material That indicate to
             continuation:
                       1                            Stainless                            Stainless
CPE - 327
2 Metallized Stainless
3 Metallic Metallic
Others accessories:
Others modifications:
            790712     Rev        791123   880315      920115     640114   961004   980306    990306   991008   050121      050812
            071130    150529
           TRANSFORMADORES MONOFÁSICOS TIPO SUMERGIBLE                                           ESPECIFICACIÓN
            HASTA 100 KVA PARA DISTRIBUCIÓN SUBTERRÁNEA                                          CFE K0000-04
1 of 2
FE OF ERRATA
PAGE 1 OF 24
SAYS:
HAS TO SAY:
PAGE eleven OF
24SAYS:
 790712    Rev     791123     880315   920115    640114       961004     980306   990306    991008    050121    050812
 071130   150529
           TRANSFORMADORES MONOFÁSICOS TIPO SUMERGIBLE                                         ESPECIFICACIÓN
            HASTA 100 KVA PARA DISTRIBUCIÓN SUBTERRÁNEA                                        CFE K0000-04
2 of 2
HAS TO SAY:
 790712    Rev     791123     880315    920115     640114     961004     980306   990306    991008   050121   050812
 071130   150529