The accessories that are available, as for
example inspection openings, steel grilles,
plenum boxes, ceiling diffusers, splitter
attenuators, bends, tees and connecting
collars, are listed in the test certificate.
Smoke extraction duct of
sheet steel
Test certificate P-TUM-411 and
P-3464/ss95-MPA BS
Functional endurance of
120 min at 600'C
General
Essential advantages
. Smoke extraction duct of sheet steel for
the usage within the smoke exhaust
zone or fire compartment, on which no
fire resistance time requlrements have
been placed.
. Tested in accordance with DIN V
18232-6 and prEN 1366-9 600 'C -
120 min (requirement of the standard:
600 "C - 60 min or 400 "C - 120 min).
. category 1and2 temperature stress in
accordance with DIN V 18232-6.
. Pressure level 1 in accordance with
DIN V '18232-6 for an overpressure
inside the smoke extraction ducts,
pressure level 3 in accbrdance with DIN
V 18232-6 for an underoressure inside
the smoke extraction ducts and
pressure level 3 in accordance with DIN
V 18232-O for an overoressure or
underpressure inside the air supply
ducts.
. The smoke extraction ducts are
suitable at ambient temperalure for
-1500 Pa (underpressure) and +500 Pa
(overpressure).
With temperature stress from at the
most 600 'C/120 min up to -500 Pa
(underpressure). For the usage as air
supply duct -1500 Pa (underpressure)
and +1500 Pa (overpressure).
The leakage of the smoke extraction
ducls shall not exceed the value of 3,75
m3/h oer m2 internal surface at -1500
Pa (underpressure).
. Smoke extraction ducts of sheet steel
satisfy the regulatory building products
list A (edition 200111).
. Smoke extraction ducts and fittings of Scope of delivery and dimensions
sheet steel are manufactured from
galvanized sheet, grade Fe P02 G275 Smoke extraction ducts of sheet steel are delivered as a complete system. This means that
NA, with stiffeners. The number and the adequate mounting accessories are delivered together with each duct, fitting, smoke
location of the supports are mounted in control damper or compensator.
accordance with the test certificate This consists of the hangers including fire safety dowels and threaded rods up to a length of
related to the dimensions. 1,5 m, the fitting parts including corner fixings, screw-in clips and temperature-resistant,
30 mm light profile frame, corners adhesive sealing tape.
sealed against fire and smoke,
longitudinal seams folded, 1 mm sheet Available clear dimensions in lmml
thickness in accordance with EN B 201 zaz 318 357 400 449 FN? coc 634 711 797 894 003
1 1125 1250 1 251-1 500
10142110143. Light sheet arrangement H 201 zcz 318 5JT 400 449 JUJ 565 634 711 797 850 900 950 | 000 797
in accordance with DIN 18379. Intermediate sizes on reouesl
64
Vertical deviations Design of bends and tee fittings
Inside the flue of horizontal smoke extraction, Bends and tee fittings are allowed to be
ducts bend fillings and vertically arranged manufactured in the same way as the smooth
smooth fittings are allowed to be arranged for fittings (sheet steel ducts) The same limits of
a vertical deviation of up to 2500 mm. The dimension apply as for smooth fittings; the
Smoke extraction duct of vertical duct sections shall be bedded on length of the bend shall be measured in the
consoles at a maximum distance of 1500 mm. duct axis
sheet steel
lnclined ducts Design of connecting pieces for the
Ducts that deviate up to 10'from the vertical installation of smoke control dampers
Test certificate P-TUM41 1
centre line shall be installed in the same way Openings with stiffeners are allowed lo be
as vertical ducts More inclined ducts shall be made into the smooth fittings (sheet steel
Functional endurance of installed in the same way as horizontal ducts ducts) to connect RKE smoke control
with vertical suspensions Ducts that deviate damoers
120 min at 600 "C over 10' from the horizontal line shall be
doubled at the suspensions, such that the For further details, see the test certificate.
Directions for installing and ducts on the traverses of the susDensions
cannot shift (horizontally)
suspension
.i/,
I f
,l
wsK |]0q
u.ru |
I 2 II I
I
i Maximum WSK 600 distances > 5 m < 10 m
Fire-resistant smoke
extractionduct j -,j
Only permitted for single compartments, i.e the smoke zone and/or fire compartment with smoke extraction ducts of sheet steel are not allowed
to be lead through fire-resistant walls or fire walls into other fire compartments.
a, @
The suspension shall be performed with L- Non-combustible sealings shall be used to M8 fire safety
profi les (35/35/4) or C-profiles (30t20t 1,7 S). interconnect the duct pieces. dowel; the maximum
The maximum tensile load is 7S0 N A 20,5 tensile load for L- or
N/mm'?(M8). The duct pieces are connected with Mg C-profiles is F = 750 N
The threaded rods shall have a maximum screws, washers and nuts at the four 4 2o,s N/mm'
lateral distance of 50 mm to the smoke corners. Connectors are also affixed on all
extraction duct of sheet steel sides of the duct connecting profile at a
distance of 200 mm.
Alternatively, sliders can also be used for
the suspension. Please note that in this
case the maximum tensile load is onlv 300
N 4 8.2 N/mm'?.
F = max. 300 N
4 8,2 N/mm'zwhen
using the slider
65