850 Gea12739g HR
850 Gea12739g HR
WORLDWIDE
• Advanced breaker diagnostics with high-end fault and disturbance recording • Enhanced relay draw-out construction
• Integrated arc flash detection using light sensors supervised by over current to reduce incident
  energy and equipment damage                                                                                Exceptional Quality
• High-end cyber security such as AAA, Radius, RBAC, and Syslog enabling NERC® CIP requirements
• Draw-out design simplifies testing, commissioning and maintenance, thereby increasing process
                                                                                                             & Reliability
  uptime                                                                                                     • IPC A-610-E Class 3 manufacturing standards
• Optional Wi-Fi connectivity minimizes system configuration and provides safe relay programming             • Highest reliability standards for electronics
  and diagnostic retrieval                                                                                     testing
• Relay environmental diagnostic information helps reduce system downtime                                    • 100% Environmental Stress Screening and full
                                                                                                               functional testing
• Wide range of feeder applications for utility, oil & gas, mining & metals, process industry, commercial,   • Standard Harsh Conformal Coating
  and water wastewater
• Comprehensive protection and management of incoming and outgoing feeders                                   Uncompromising
• Fast protection pass enables use for load shedding schemes
• Advanced communications and flexlogic for reliable automatic bus transfer schemes
                                                                                                             Service & Support
                                                                                                             • Covered under GE’s 10 year warranty plan
• High speed fault detection for arc flash mitigation
                                                                                                             • Designed, tested and assembled by GE
850 Feeder Protection System
2                                                                 GEDigitalEnergy.com
                                                                                                                              850 Feeder Protection System
The Multilin 8 Series is designed to solve the challenges that customers face in    With advanced communications the Multilin 8 Series integrates easily and
running their day-to-day operations including maximizing system and process         seamlessly into new or existing DCS/SCADA system, along with other Multilin
uptime, simplifying system integration and maintenance, and extending               protection devices, providing a comprehensive solution for the end-to-end
the life of critical assets. Utilizing advanced design practices (IPC A-610         electrical system within the operations.
standards), superior technology (elimination of all electrolytic capacitors), and
state-of-the art test and manufacturing facilities (every device endures 100%
Environmental Stress Screening), GE is raising the bar on system performance
and reliability.
                                                                        GEDigitalEnergy.com                                                                  3
850 Feeder Protection System
Exceptional Quality & Reliability                                                       The Multilin 8 Series products have an integrated protection integrity engine
                                                                                        that utilizes customized algorithms, providing advanced diagnostics to ensure
Industry-leading quality, reliability and design processes are at the core of
                                                                                        asset protection is not compromised.
GE’s next generation protective relay platform. With significant investments in
state-of-the-art type test facilities that simulate a complete range of operating       Maintaining and safeguarding the electrical supply of an operation is critical
environments and designed to the IPC A-610 Class 3 standard, adhering to the            to ensuring maximum process availability and performance.
highest reliability standards and ensuring rugged performance, each device
                                                                                        The 8 Series incorporates the latest cyber security features, including
completes one hundred percent Electrical Stress Screening prior to shipping
                                                                                        password complexity, RADIUS authentication, role-based access control
from GE’s facility.
                                                                                        (RBAC), customers to comply with NERC CIP and NISTIR 7628 requirements.
The Multilin 8 Series Protection Relays are manufactured in an ISO® 9001:2008
                                                                                        Understanding that customers need protection and control devices that
certified manufacturing facility.
                                                                                        must reliably operate in extremely harsh and challenging environments, GE
                                                                                        delivers the Multilin 850 with harsh conformal coating on all printed circuit
Pioneering Technology & Design                                                          boards and a patented environmental awareness module that provides real-
                                                                                        time detection of environmental factors that affect product life, as part of its
The Multilin 850 is part of the 8 Series platform that provides comprehensive,
                                                                                        standard offering, delivering higher reliability and extended relay life.
high performance protection and control for critical assets in Industrial and
utility environment.
1 2
3 4 5
4                                                                       GEDigitalEnergy.com
                                                                                                                               850 Feeder Protection System
                                                                      GEDigitalEnergy.com                                                                        5
850 Feeder Protection System
6                                                                        GEDigitalEnergy.com
                                                                                                                             850 Feeder Protection System
Metering
The Multilin 850 offers high accuracy power quality monitoring for fault and
system disturbance analysis. The Multilin 8 Series delivers unmatched power
system analytics through the following advanced features and monitoring
and recording tools:
The 850 monitoring system performance with oscillography and event records
                                                                     GEDigitalEnergy.com                                                                    7
850 Feeder Protection System
D400 D400
                                                                                                EnerVista Launchpad
                                                                                                EnerVista Launchpad is a powerful software package that provides
                                                                                                users with all of the setup and support tools needed for configuring and
                                                                                                maintaining Multilin products. The setup tools within Launchpad allow
                                                                                                for the configuration of devices in real-time, by communicating via serial,
8                                                                                   GEDigitalEnergy.com
                                                                                                                                      850 Feeder Protection System
Ethernet or modem connections, or offline by creating device setting files                Application Challenge: Modern Feeder Protection
to be sent to devices at a later time. Included in Launchpad is a document
archiving and management system that ensures critical documentation is                    Challenge:
up-to-date and available when needed.                                                     Utilities and industrial facilities depend on reliable and secure electricity
8 Series Setup Software                                                                   services to keep their operations running. Regardless of the type of source,
                                                                                          a fully integrated protection & control scheme is critical to maintaining
8 Series Setup Software is single setup and configuration across the platform             uninterrupted power to the entire facility.
and can reduce device setup and configuration time.
                                                                                          Solution:
                                                                                          The Multilin 8 Series offers the ideal solution for protecting, monitoring
Application Challenge: Intelligent Load Shedding
                                                                                          and controlling electrical cables and overhead lines from disturbances
Challenge:                                                                                or faults. With a fast protection pass, running every 2 msec, the 8 Series
                                                                                          provides unmatched overcurrent, overvoltage, undervoltage, and frequency
In a multiple power source network, it may happen that some power sources
                                                                                          protection. Supporting the latest in industry standard communication
are lost utility circuit creating deficit of the power even with a presence of
                                                                                          protocols, including IEC 62439/PRP and IEC 61850, the Multilin 8 Series easily
in-facility generator. In these partially islanding situations the deficit of active
                                                                                          integrates into new or existing networks.
power may result in a sudden drop of system frequency resulting in power
system instability, bringing the processes and operations to a halt.
                                                                                          Simplified Setup and On-Going Maintenance
Solution:                                                                                 The robust 850 streamlines user workflow processes and simplifies
Being able to dynamically balance and maintain loads in this type of                      engineering tasks, such as configuration, wiring, testing, commissioning, and
separation scenario requires an intelligent device that has advanced                      maintenance. Building on the history of simplified setup and configuration,
communications, automation and control logic capabilities. The Multilin                   the 850 Feeder Protection Relay has implemented simplified setup screens
850 provides distribution networks and industrial facilities with the system              to minimize relay setup time. In addition, for local programming, the 850
stability functionality and cost saving options, required to maintain power               comes with a fully functional GCP, which allows users to locally monitor the
system availability and process continuity. With advanced protection features             asset.
including underfrequency, overfrequency, frequency rate of change, sensitive
reverse power, underfrequency restoration and other elements plus superior                Ease-of-Use
communications enabling sharing data with other IEDs, distribution utilities
                                                                                          Continuing its legacy in providing easy-to-use protective relay solutions,
and industrial facilities rely on Multilin’s 850 to deliver reliability, efficiency and
                                                                                          the 850 is designed to minimize product and system configurability
security to the power system.
                                                                                          requirements, for quicker physical installations, easier and simplified setup
                                                                                          and configuration.
1 Easy to Use - Draw-out case 2 Easy to Configure - 1 simple step 3 Detailed Diagnostics
                                                                             GEDigitalEnergy.com                                                                      9
850 Feeder Protection System
Full Color Graphical HMI Front Display                                         The 850 front panel provides 14 LED indicators and 3 LED pushbutton
                                                                               indicators. 10 LED’s are user- programmable, while “In service” and “Pickup”
A large, full color Graphic Control Panel (GCP) ensures clear representation
                                                                               LED’s are non-programmable. “Trip” and “Alarm” LED’s are not color
of critical status and measurements. When the keypad and display are not
                                                                               programmable but can be assigned with selected operands.
being used, the GCP will automatically revert to screen saver mode, which
will turn off the display until one of the local pushbuttons is pushed.        User-programmable LED’s can be turned on by a selection of FlexLogic
                                                                               operands representing protection, control or monitoring elements. Each
The GCP can be used to view device and system status, alarms and event
                                                                               LED can be configured to be self-reset or latched and labeled based on
logs, and metering information. The GCP and navigation keys simplify relay
                                                                               the application and user requirements. User-programmable LED’s can be
configuration and setup, allowing users to make setting changes directly
                                                                               selected to be either Red, Green or Orange to give the distinctive indication
through the front panel.                                                       of selected operations.
             Online Device
             Configuration
            and Monitoring
10                                                                 GEDigitalEnergy.com
                                                                                                850 Feeder Protection System
Front View
        Menu path display indicating
      location within menu structure
                      Graphic Control
                          Panel (GCP)
Rear View
                    Grounding screw                                                    Standard serial and RJ45
                       Power supply                                                    Ethernet module
                                RTDs
                                                                                       Advanced communications
                                                                                       module (fiber optic port)
                    Digital I/O,DCMA,
                    Arc Flash sensors
                                                                                       CT, VT inputs
                                                                      7.15”
Dimensions & Mounting
9.90” 8.84”
                                                                                  5”
                                                                               7.5
                                                8.42”                     5”
                                                                       1.5
                                                GEDigitalEnergy.com                                                      11
850 Feeder Protection System
Solution
The Multilin 850 offers seamless automated bus transfer scheme solutions,                                         TCB1
maximizing system availability and process uptime. Using a minimal CB3 CB4 CB5 CB6
amount of programming, the 850 eliminates the need for any discrete
devices and device inter-wiring by integrating all the functions directly into
the intelligent device. With advanced communications including embedded
support for IEC 61850 peer-to-peer communications, inter-relay wiring and
physical I/O can be eliminated. The 850 provides a reliable, automatic bus
transfer solution that is easy to design, configure, and maintain.
Solution
                                                                                           Fault 1
With embedded support for IEC 61850, the 850 provides high-speed                                            CB2
data exchange between relays for fast reaction to system issues. As a
coordinated system, interlocked protection can be enabled, to provide
the necessary bus protection. Fast clearance can be achieved for a fault
                                                                                                                                     CB3
that occurs at any feeder or bus location by quickly exchanging signals to
discriminate the fault location.
                                                                                                                                     Fault 2
12                                                                   GEDigitalEnergy.com
                                                                                                                                  850 Feeder Protection System
Solution
For customers wanting a reliable and customized auto-reclose scheme,             850 relay can be programmed to change protection setting every time the
a device with integrated logic capabilities is necessary. The 850 offers         downstream reclosure operates and also maintain same reclosure count
comprehensive protection and auto-reclose functions integrated in one box.       as downstream reclosure.
One such application where dynamic setting group change ability is ideal,                              52                                            52
is with a parallel feeder application where two lines are in service and carry
a portion of the required load. If there is an unplanned outage with one of
the feeder lines, such that all loads are now supplied by one feeder, key
protection settings would need to be adjusted to ensure proper coordination                            52                                            52
with downstream devices and deliver secure reliable service.
                                                                                                                            52
Solution:
The Multilin 850 offers effective, reliable management of feeders. With
dynamic, sensitive settings, the 850 provides secure and dependable
protection. With six setting groups the 850 provides the sensitive settings
                                                                                                                           52
range and groups required to ensure no compromise is made to meet
changing system conditions. These setting groups can be enabled
automatically or manually to address system needs, ensuring greater
system reliability and efficiency.
                                                                     GEDigitalEnergy.com                                                                                13
850 Feeder Protection System
Typical Wiring
                                                                                                                                                                                                                                           L
                                                                                                                                                                                                                                           O
                                                                                                                                                                      52                                                                   A
                                                                                                              WYE VT                                                                                                                       D
                                                                                                                                                 SEE VT WIRING IN
                                                                                                            CONNECTION
                                                                                                                                                 INSTRUCTION MANUAL
                                                                                                                                                                                                                                                CONTROL
                                                                                                                                                                                                                                                POWER
                                                                             SEE GROUND
                                                                             INPUT WIRING IN
                                                                             INSTRUCTION MANUAL
BUS IA N IB N IC N IG N Isg N VA VA VB VB VC VC VX VX
                                                                                                                                                                                                                 GROUND
                                                                                                                                                                                                       NEUTRAL
                                                                                                                                                                                SLOT A
                                                                                                                                                                                                LINE
                                                PHASE A PHASE B PHASE C                    GROUND
                                                             CURRENT INPUTS                                                   VOLTAGE INPUTS                                                    PWR SUPPLY
                                                                                                                                                                                                                                COIL
                                                F15     DIGITAL INPUT 3                                                                                                                                                   52a                          SEE TRIP AND
                                                                                                                                                                                                        V        F3                                     CLOSE COIL
                                                F16     DIGITAL INPUT 4
                                                F17     DIGITAL INPUT 5
                                                                                                                                                                                                                 F4                         CLOSE     MONITORING
                                                F18     DIGITAL INPUT 6
                                                                                                                                                                                         CLOSE                   F5             CLOSE
                                                                                                                                                                                                                                 COIL       CIRCUIT IN INSTRUCTION
                                                                                                                                                                                                                          52b                             MANUAL
                                                                                                                                                                                                        V        F6
                                                                                                                                                                      OUTPUT RELAYS
                                                F19     DIGITAL INPUT 7
                                                F20     COMMON                                                                                                                                                   F7
                                                F21     +24 V                                                                                                                          AUXILIARY                 F8
                                                                                                                                                                                                                 F9
                                                                                                                                                                                                                 F10
                                                                                                                                                                                       AUXILIARY                 F11
                                                                                                                                                                                                                 F12      OUTPUT CONTACTS
                                                                                                                                                                                                                           SHOWN WITH NO
                                                                                                                                                                                       CRITICAL                  F22      CONTROL POWER
                                                                                                                                                                                       FAILURE                   F23
                                                                                                                                                                                        RELAY
                                                                                                                                        SLOT F: I/O_A                                                            F24
                     ETHERNET
        [BACK PANEL ETHERNET PORT RJ45 OR ST]
                         USB
                                                                       850 Feeder Protection System
                 [FRONT PANEL LOCAL
                                                                Rear Panel
                 PROGRAMMING PORT]
                                                       ETHERNET             ETHERNET
                                                                                                                           SLOT D: COMMUNICATIONS
                                                         RJ45             FIBER1                   FIBER2
ST ST
                                                        Front Panel
      PERSONAL
                                                                 USB
      COMPUTER                                                                                                       COMMUNICATIONS RESERVED          CAN
                                                              TYPE B                                                                                                                                                                    OPEN DELTA VT CONNECTION
                                                                                                                     IRIG-B     RS485
                                                                                                                                      COM
                                                                WIFI                                                 D1 D2 D3 D4 D5 D6 D7 D8 D9 D10
                               ACCESS POINT
892771A4.cdr
14                                                                                                                   GEDigitalEnergy.com
                                                                                                                                                                                                                                           850 Feeder Protection System
Approvals                                                                                                                                                                  Environmental
                       Applicable Council Directive                                                 According to                                                           Ambient temperatures:
                       Low voltage directive                                                        EN60255-5 / EN60255-27                                                 Storage/Shipping:                            - 40C to 85C
CE compliance                                                                                       EN60255-26 / EN50263                                                   Operating:                                   -40C to 60C
                       EMC Directive
                                                                                                    EN61000-6-2 / EN61000-6-4                                                                                           Operating up to 95% (non condensing) @ 55C (As per
                                                                                                                                                                           Humidity:
                       cULus                                                                        UL508                                                                                                               IEC60068-2-30 Variant 2, 6days)
North America                                                                                       UL1053                                                                 Altitude:                                    2000m (max)
                                                                                                    C22.2.No 14                                                            Pollution Degree:                            II
                       Manufactured under a registered quality                                                                                                             Overvoltage Category:                        III
ISO                                                                                                 ISO9001
                       program                                                                                                                                             Ingress Protection:                          IP54 Front
                                                                                                                                             GEDigitalEnergy.com                                                                                                                          15
Ordering
850 E ** NN ** H * * A * * G * * * * * * * * * N Description
Base Unit 850 English Language; High Voltage PS, Graphical Control Panel
 Language                       E                                                                                                            English
 Phase Currents -                    P1                                                                                                      1A three phase current inputs
 Bank 1/2                            P5                                                                                                      5A three phase current inputs
 Phase Currents -                         NN                                                                                                 No phase current inputs
 Bank 3
 Ground Currents                                G1                                                                                           1A ground input
                                                G5                                                                                           5A ground input
                                                S1                                                                                           1A ground + 1A sensitive ground input
                                                S5                                                                                           5A ground + 5A sensitive ground input
                                                D1                                                                                           1A ground + 1A ground input
                                                D5                                                                                           5A ground + 5A ground input
 Power Supply                                         H                                                                                      110 - 250 V dc/110 - 230 Vac
 Slot B - LV I/O                                            N                                                                                None
                                                            R                                                                                6 X RTDs (PT100, NI100, NI120)
                                                            S                                                                                6 X RTDs (PT100, NI100, NI120, CU10)
 Slot C - LV I/O                                                  N                                                                          None
                                                                  R                                                                          6 X RTDs (PT100, NI100, NI120)
                                                                  S                                                                          6 X RTDs (PT100, NI100, NI120, CU10)
 Slot F - HV I/O                                                       A                                                                     2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low / High voltage, Int/
                                                                                                                                             Ext supply)
 Slot G - HV I/O                                                               N                                                             None
                                                                               A                                                             2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low / High voltage, Int/
                                                                                                                                             Ext supply)
                                                                               L                                                             7 DcmA O/P + 4 DcmA I/P + 1 RTD
Slot H - HV I/O                                                                    N                                                         None
                                                                                   F                                                         10 Digital Inputs + 4 Arc flash inputs
                                                                                                                                             2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low / High voltage,
                                                                                   A                                                         Int/Ext supply)
 Faceplate                                                                             G                                                   Color Graphical Display
 Current Protection                                                                        S                                               Basic = 50P, 50N, 50G, 51P, 51N, 51G
                                                                                           M                                               Standard = Basic + 50SG, 50_2, 51SG, 51_2, RGF
                                                                                           A                                               Advanced = Standard + 49,67P, 67N, 67G, 67SG, 67_2, Load
                                                                                                                                           Encroachment, Broken Conductor, Fast U/F
 Voltage Monitoring                                                                            S                                           Standard = 27P, 27X, 59P, 59N, 59X, 81O, 81U
 & Protection                                                                                  P                                           Advanced = Standard + 25, 32, 32N, 55, 59_2, 81R
 Control                                                                                           B                                       Basic = Setpoint Group Control, Virtual Inputs, Trip Bus, Breaker Control
                                                                                                   F                                       Standard = Basic + Flexlogic, CLP, 50BF
                                                                                                   C                                       Advanced = Standard + Autorelcose, Bus Transfer (Requires voltage
                                                                                                                                           option P)
 Monitoring                                                                                            B                                   Basic = Breakers Coil Monitoring, Breaker Arcing, Harmonics, THD,
                                                                                                                                           Demand, Trip Counters
                                                                                                       C                                   Basic + Advanced Breaker Health
 Communications                                                                                             S     E                        Standard = Front USB, 1 x Rear RS485 : Modbus RTU, DNP3.0,
                                                                                                                                           IEC60870-5-103 + 1 x Ethernet: Modbus TCP, DNP3.0 TCP
                                                                                                            1     E                        Advanced = Front USB, 1 x Rear RS485 + 2 x Ethernet Fiber, MODBUS
                                                                                                                                           RTU / TCP, DNP3.0, IEC 60870-5-103/104, 1588, SNTP
                                                                                                            1     P                        Advanced + PRP
                                                                                                            2     A                        Advanced + IEC 61850
                                                                                                            2     E                        Advanced + PRP + IEC 61850
 Fiber Optic                                                                                                           N                   None
 Connector                                                                                                             S                   ST, Multi-mode 850nm
 Wireless                                                                                                                    N             None
 Communication                                                                                                               W             WiFi 802.11
 Security                                                                                                                          B       Basic
                                                                                                                                   A       Advanced - CyberSentry
 Future Option                                                                                                                           N Not available
                                                                                                           GEDigitalEnergy.com
                                                                                                           IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
                                                                                                           trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
                                                                                                           Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
                                                                                                           NIST is a registered trademark of the National Institute of Standards and Technology.
                                                                                                           GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
                                                                                                           Company.
                                                                                                           GE reserves the right to make changes to specifications of products described at any time without notice
                                                                                                           and without obligation to notify any person of such changes.
                                                                                                                                                                                                       GEA-12739G(E)
                                                                                                                                                                                                             English