NHP Technical Catalogue
NHP Technical Catalogue
The Terasaki Electric Company, Japan, was founded in 1923 in the industrial
city of Osaka. In its early beginnings it started with the manufacture of
air circuit breakers. Terasaki later expanded its operations in the late 40s
when they entered the marine industry manufacturing a complete line of
moulded case circuit breakers.
Terasaki is world famous for its installations of marine switchgear, including
air and moulded case circuit breakers in a majority of the world’s
ocean-going marine vessels.
Terasaki has developed systems beyond basic switchgear requirements for
guidance and monitoring of ships on the high seas.
Terasaki is very proud of its achievements in this area, proving that quality
and reliability of Terasaki products is recognised where service conditions
are sometimes arduous and severe.
In the 1960s Terasaki expanded their production facilities to enable them
to enter the industrial market as well as continuing to expand within the
well established marine business. Terasaki have a total of four factories
throughout Japan, mainly in the Osaka area, as well as affiliated companies
in the UK, Malaysia, Spain, Italy, Finland, Sweden, Brazil and China.
Terasaki were the pioneers and the first circuit breaker company to
introduce current limiting circuit breakers to the world in 1963 utilising the
contact repulsion principle, which was first introduced in the
TL range of moulded case circuit breakers.
NHP was appointed sole agent for Terasaki products in Australia in 1979
and in New Zealand in 1999. From that time until now, NHP has established
Terasaki products as a standard in the market.
This price list catalogue is segregated into sections. A guide to the contents of each
Explanation of Terms
section is situated at the front of the price list catalogue, and the first page of each
section has its own index for easier product selection.
A product listing index is situated at the front of this price list.
Each page has a bold section number for prompt page location and is identified
by both its section number and its page number eg. 1-16 signifies this is section 1
page 16. All catalogue numbers are bold and shaded.
All prices are in $AUS (exclusive of GST)
Prices for equipment fitted with coils, apply to standard voltages only.
Non-standard voltages shown are available on request at additional cost.
An alphanumeric index by catalogue number is located at the rear of the price list
catalogue. Items prefixed I in the alphanumeric index are available on indent only.
These items are not stocked and will be brought in only on a customer request, the
item can not be returned for credit. For more infomation on indent items please
contact NHP customer service. Items prefixed A in the alphanumeric index are
assembled to customer order/ requirements.
Current NHP standard conditions of sale apply to this price list catalogue.
The prices in this price list catalogue are recommended prices only (exclusive of
GST) and there is no obligation on resellers to comply with the recommendation.
Page contents
Product
group Miniature circuit breakers
Din-T6
Section 1 2-in-1 Double the capacity of your load centre
Footnotes, as
Section and page
necessary, are
number
referenced to
e.g. section 1, Notes: 16 mm tunnel terminals.
Not suitable for chassis mounting. the bottom of
page 16. Compatible with NHP Terasaki auxiliaries and accessories.
2
Valid until August 2014
3
Valid until August 2014
5
Valid until August 2014
6
Valid until August 2014
7
Valid until August 2014
National Manufacturing and Distribution Centre
SIZE
Warehouse 7,000 m2
Manufacturing 5,000 m2
STAFF
270+ Employees
OPERATING HOURS
6.00am - 11.30pm, Monday-Friday
STOCKHOLDING
- 45,000+ line items (20,000
stocked)
- Approximately $70 M
ITEM THROUGHPUT
- Approximately 5,500 per day NHP NATIONAL MANUFACTURING AND DISTRIBUTION CENTRE
(6,000 lines throughout
Australasia)
FACTS
r 0SEFSTSFMFBTFEGPSQJDLJOH
before 3.00 pm are despatched
the same day.
r 5IF4VQQMZ$IBJOUFBNTUSJWFT 2011 let
to achieve 95 % customer
Book
Tour
Facility
rton
Lave
8
Valid until August 2014
Creating a sustainable future
Adopting emerging technologies to support sustainable practices
A major push towards more
sustainable practices by many in
the industrial electrical industry
is today clear for all and a major
focus at NHP is to provide
sustainable solutions for our
customers as well as throughout
our own operations.
In 2010 we designed and
constructed our very own
4VTUBJOBCJMJUZ$FOUSFMPDBUFE
at our existing National
Manufacturing and Distribution
Centre in Laverton, Melbourne.
Housing cutting-edge technology
and equipment enabling research
& development and testing, the
Centre aids investigation into
ways to effectively introduce and
manage sustainable practices.
4VTUBJOBCMFUFDIOPMPHJFTXJUIJO
the centre include:
r A horizontal axis wind
generator
r 4PMBSQIPUPWPMUBJDTZTUFNT
r Grid interactive systems
r 0GGHSJEIZCSJETZTUFNT ONE OF NHP’S ELECTRIC CARS ON DISPLAY AT THE
SUSTAINABILITY CENTRE IN LAVERTON, MELBOURNE
r Dual axis solar tracker, and
r Energy Management & control
systems
NHP are also proud participants
in the Victorian Government’s
electric vehicle trial which will provide
valuable insights to assist in future
business planning, as well as help
the wider community understand
the process, timelines and barriers
4DBOUIF23
for transitioning to electric vehicle code to Book
technologies in the future. B-JWF5PVS
5IFTFJOJUJWJBUJWFTIJHIMJHIUPVS
commitment to sustainable practices
across all facets of the workplace.
0VSBJNJTUPSFNBJOBUUIFGPSFGSPOU
of the industry, as leaders in
providing alternative energy solutions
for commercial and industrial
applications.
4DBOUIF
4DBO UIFF
Working closely with Melbourne QR code
co
for further
6OJWFSTJUZ 3.*56OJWFSTJUZBOE information
Victoria University, NHP is also proud on our electric
car trial.
to educate young electrical engineers
in this growing and important
industry sector.
9
Valid until August 2014
Products and Brands
To assist customers in finding what they want, we have classified
our extensive product range into the following categories.
1. Market Categories
ampcom
SPECTRUM CONTROLS
WAGO AUCOM
ESA SANTERNO
MITSUBISHI GHISALBA
CARLO GAVAZZI MICROELETTRICA
POWER DISTRIBUTION
POWER QUALITY
& PROTECTION
ALLEN-BRADLEY ELECTRONICON
ERICO BELUK
WOHNER
SELCO
10
Valid until August 2014
COSMOTEC
STEGO BOCCHIOTTI
IBOCO ERICO
GRASSLIN
11
Valid until August 2014
OPERATOR
CONTROL DEVICES SAFETY PRODUCTS
ELEKTRA
SPOHN + BURKHARDT
TER
STEUTE
12
Valid until August 2014
HAZARDOUS AREA
METERING
EQUIPMENT
WAGO
STEUTE
ALLEN-BRADLEY
RENEWABLE ENERGY
SERVICES & TRAINING
PRODUCTS
13
Valid until August 2014
Products and Brands
2. Application Classes
HAZARDOUS AREA
SAFETY
EQUIPMENT
WAGO
STEUTE
STEUTE
ALLEN-BRADLEY
KATKO
PROCESS CONTROL
14
Valid until August 2014
3. Application Solutions
15
Valid until August 2014
QR CODE
16
Valid until August 2014
4DBOUIF23DPEFCFMPXPSHPUP
www.nhp.com.au to download the
latest NHP catalogues and price lists.
WEB
17
Valid until August 2014
Information at your fingertips
The latest NHP and industry news is never far away
through NHP’s communications technology platforms
Please scan
the QR code Scan the QR code to view our new
to view our interactive pulp and paper website
corporate
website.
Indu
stria
Solutio l Elec
trica
ns for l and
Auto
the Con SOLUT mati
on
WA ION
stru Prod
TER S
cctio ucts
, Syst
&n WA FOR
IndSTE ems
TH
ustry and
WA E
Solu
olu
lutio
tion
TER
SO
nss
LUINDUS
Elec TIO TRY
tric
al NS
Swi FO
tch
gea R ED
r and
UC
Aut AT
om
atio IONA
n Sys
tem
L FA
s CIL
ITIES
Sales
Sal
SSa
aless
SSale
Sales (Au
(Aus)
(A
Aus)
es (NZ)us)
ales s)) 130
NZ 1300 13300
000 N
0800 NHP
0800 NHHPP
H
NHP
N
NH
0 NH
N HPP HP
NHP
H
NHP
NH
N HPP
Sales
1300
NHP
NHP
nhp
.com
.au
Sale nhp.co
s 1300 nhp-n m m.au
0 NHP z.com
z.co
DPOWFOJFOUMPDBUJPO4DBOUIF23 subscribe to
code to view NHP’s mobile content NHP Connect
18
Valid until August 2014
Events
Setting the industry standard for events
4DBOUIF23
code to view
NHP’s past
and upcoming
events
19
Valid until August 2014
NHP Electrical Engineering Products
20
Valid until August 2014
CORP-PROJECTS-ADS-CPB
THINK MAJOR PROJECTS. THINK NHP.
When it comes to Major Projects, our staff
involvement is always driven by long term results,
actively seeking to support you with the right
product and technical solutions before, during and
after project completion.
1
Miniature circuit breakers (MCBs) and accessories
Miniature Circuit Breaker selection guide .....................................................................1 - 2
Safe-T Series 6 kA miniature circuit breakers ...............................................................1 - 6
Safe-T Series 6 kA miniature circuit breakers with shunt trip ...........................1 - 8
Safe-T Switchboard hardware and accessories ..........................................................1 - 9
Safe-T Single pole width RCCBs SRCB (RCBO) .........................................................1 - 10
Safe-T Earth leakage relay (ELR) ........................................................................................1 - 11
Din-T Series general features ..............................................................................................1 - 12
Din-T 6 Series 6 kA miniature circuit breakers .........................................................1 - 14
Din-T series 6 kA 2-in-1 ...........................................................................................................1 - 16
Din-T Series 6 kA for DC applications ............................................................................1 - 17
Din-T 10 Series 10 kA miniature circuit breakers ....................................................1 - 19
Din-T 10H Series 10 kA miniature circuit breakers ................................................1 - 22
Din-T 15 Series 15 kA miniature circuit breakers ....................................................1 - 23
Din-T 6 easy-fit .............................................................................................................................1 - 24
Din-Safe safety switches ........................................................................................................1 - 25
Din-Safe single pole .................................................................................................................1 - 28
Din-Safe MCBs (RCBO) ............................................................................................................1 - 30
Din-Safe-M add on earth leakage modules ..............................................................1 - 32
Accessories – mounting ........................................................................................................1 - 35
Main switch 63 – 100 A ..........................................................................................................1 - 38
Din-T shunt and undervoltage trip .................................................................................1 - 39
Din-T auxiliary contacts & Din-T motor operator DTMD ...................................1 - 40
Din mount housing, panelboard switch & kilowatt meters ...........................1 - 42
Din busbar comb .......................................................................................................................1 - 43
Changeover switch, pushbuttons ...................................................................................1 - 44
LockDIN™ .........................................................................................................................................1 - 46
Meter Isolator ................................................................................................................................1 - 48
Accessories for Din-T series MCBs ...................................................................................1 - 50
Din-T contactors and hour run counter ......................................................................1 - 52
Din-T impulse switches ..........................................................................................................1 - 55
CA 8 contactors and emergency lighting test unit .............................................1 - 56
Surge diverters .............................................................................................................................1 - 57
Dimensions – Safe–T & Din–T ............................................................................................1 - 61
Time switches ...............................................................................................................................1 - 68
2
Panelboards, loadcentres and accessories busbar
Chassis assemblies
Pole Covers to suit Safe-T and Din-T series ...................................................................2 - 2
Loadcentres
Insulated – ILC series ..................................................................................................................2 - 3
Insulated – Din-T surface mount ........................................................................................2 - 4
Insulated – Din-T flush mount ..............................................................................................2 - 5
Insulated – Din-Modula 150 series ....................................................................................2 - 6
22
Valid until August 2014
Section Contents
Insulated – Din-Modula weatherproof series .............................................................2 - 8
Metal – NLC for Din-T MCBs ...................................................................................................2 - 9
Metal – TLC for Safe-T MCBs ................................................................................................2 - 10
CONCEPT
Panelboards – introduction .................................................................................................2 - 11
Panelboards – quick reference table .............................................................................2 - 12
CONCEPT economical panelboards ...............................................................................2 - 14
$0/$&15r1-64NVMUJQVSQPTFQBOFMCPBSET ............................................................2 - 17
$0/$&15r1-64(SJ[[#BSJTPMBUJPO ..................................................................................2 - 24
$0/$&15r1-64FOFSHZNFUFSJOH ....................................................................................2 - 26
$0/$&15r1-644BGF5 .............................................................................................................2 - 27
$0/$&15r1-64BDDFTTPSZNPEVMFT ...............................................................................2 - 29
$0/$&15r1-64PQUJPOTBOEBDDFTTPSJFT ....................................................................2 - 30
$0/$&15r13&.*&3QSFNJVNQBOFMCPBSET ...............................................................2 - 32
$0/$&15r13&.*&3(SJ[[#BSJTPMBUJPO ..........................................................................2 - 37
$0/$&15r13&.*&3 ................................................................................................................2 - 40
$0/$&15r13&.*&34BGF5 .....................................................................................................2 - 45
$0/$&15r13&.*&3.$$#.....................................................................................................2 - 47
$0/$&15r13&.*&3BDDFTTPSZNPEVMFT .......................................................................2 - 48
$0/$&15r13&.*&3PQUJPOTBOEBDDFTTPSJFT ............................................................2 - 50
$0/$&15r506()IFBWZEVUZQBOFMCPBSET .............................................................2 - 52
Panelboard hardware to suit the CONCEPT range ...............................................2 - 56
NC chassis .......................................................................................................................................2 - 58
GB chassis .......................................................................................................................................2 - 62
CD chassis .......................................................................................................................................2 - 65
CT chassis ........................................................................................................................................2 - 67
KATKO
Panelboard DIN switch-fuse & fuse links .....................................................................2 - 69
Modular panelboard features ............................................................................................2 - 70
3
TemBreak 1 and 2 MCCBs
Introduction to TemBreak 2 ....................................................................................................3 - 2
Internal accessory installation TemBreak 1 and 2 .....................................................3 - 8
Technical reference tables ....................................................................................................3 - 12
MCCB types and setting ranges .......................................................................................3 - 16
MCCBs by amp rating
T2SW Add on CT block for MCCBs ..................................................................................3 - 20
0.7 A – 12 A (XM30PB) ............................................................................................................3 - 21
125 A ..................................................................................................................................................3 - 24
160 A / 250 A ................................................................................................................................3 - 42
400 A ..................................................................................................................................................3 - 69
630 A ..................................................................................................................................................3 - 85
630 A / 800 A .............................................................................................................................3 - 103
1000 A ............................................................................................................................................3 - 113
1250 A ............................................................................................................................................3 - 121
1600 A ............................................................................................................................................3 - 122
23
Valid until August 2014
4
Chassis assemblies for the TemBreak range
Chassis assemblies overview .................................................................................................4 - 2
XA / XB, PXB series .......................................................................................................................4 - 3
XB SS series .......................................................................................................................................4 - 7
XC series ..............................................................................................................................................4 - 9
Chassis to suit 125 – 250 AF MCCBs ..............................................................................4 - 11
Terminal covers ...........................................................................................................................4 - 12
HC High-current chassis
to suit TemBreak 2 125 – 630 AF MCCBs .....................................................................4 - 15
to suit TemBreak 1 630 – 1250 AF MCCBs .................................................................. 4 - 1s
5
MCCB transfer switches and controllers
Terasaki
Transfer switch types ..................................................................................................................5 - 2
Transfer switch selection ..........................................................................................................5 - 7
Transfer switch component ordering ...........................................................................5 - 12
Logic panel selection ...............................................................................................................5 - 28
Transfer switch options ..........................................................................................................5 - 34
Accessories to suit 125 – 630 AF MCCB .......................................................................5 - 36
6
TemBreak 1, 630 A – 1600 A and 1000 V mining MCCBs
Selection and location guide for MCCBs .......................................................................6 - 2
2013 stocking guide for 125 A – 400 A TemBreak 1 MCCBs ..............................6 - 3
MCCBs and accessories
VS125NJ 1000 V MCCB ...............................................................................................................6 - 5
VS250NJ 1000 V MCCB ...............................................................................................................6 - 6
24
Valid until August 2014
Section Contents
XV400NE 1000 V MCCB .............................................................................................................6 - 9
XS/XH630/800 ..............................................................................................................................6 - 13
XV630/800 1000 V MCCB ......................................................................................................6 - 24
XS1250SE .........................................................................................................................................6 - 28
XV1250NE 1000 V MCCB ........................................................................................................6 - 30
XS1600SE .........................................................................................................................................6 - 31
TL630NE ...........................................................................................................................................6 - 32
TL800NE ...........................................................................................................................................6 - 33
TL1250NE ........................................................................................................................................6 - 34
7
TemPower2 air circuit breakers (ACBs)
Introduction, standards .............................................................................................................7 - 2
Stocked AR ACBs ...........................................................................................................................7 - 4
Standard accessories ..................................................................................................................7 - 6
ACB ordering information .......................................................................................................7 - 9
Specifications ................................................................................................................................7 - 10
Main power circuit terminal specifications ...............................................................7 - 11
Performance specification of AR and AR-H ACB ....................................................7 - 12
Overcurrent Release (OCR) Specification ....................................................................7 - 16
Tripping options .........................................................................................................................7 - 26
Serial communication options ..........................................................................................7 - 30
TemRelay external alarm module ....................................................................................7 - 32
TemVision remote monitoring and control ..............................................................7 - 32
TemPower Rack remote racking .......................................................................................7 - 33
NHP Servicing ...............................................................................................................................7 - 34
Retrofitting and installation kits ........................................................................................7 - 35
Dimensions ....................................................................................................................................7 - 37
Providing solutions ...................................................................................................................7 - 38
Arc detecting relay system ..................................................................................................7 - 39
Arc D-Tect ordering infomation ........................................................................................7 - 44
8
Earth leakage relays
Surface mounting type TZS series .....................................................................................8 - 2
DIN Rail mounting type RD3A series ................................................................................8 - 4
DIN Rail mounting type RD1B series ................................................................................8 - 5
Panel mounting type RD1DF series ..................................................................................8 - 6
Panel mounting type RD1EP series ...................................................................................8 - 7
Panel mounting type RD3E2 series ...................................................................................8 - 8
Panel mounting type RD1G2 series ...............................................................................8 - 10
Mining earth leakage relay
Panel mount mining relays, DSRM72 and DSR48T Series ................................8 - 12
Remote current transformer (toroid) TD and DSR Series ..................................8 - 14
Accessories .....................................................................................................................................8 - 15
25
Valid until August 2014
9
Technical reference data
Din-T MCB: Ratings table ..........................................................................................................9 - 2
Din-T MCB: Effects of frequency ..........................................................................................9 - 3
Din-T MCB: Time current curves ..........................................................................................9 - 4
Din-T MCB: B, C and D curve definitions ........................................................................9 - 7
Din-T MCB: Temperature compensation curves ........................................................9 - 8
DC current circuit breaker selection table ....................................................................9 - 9
MCB Fuse-fault current limiting ........................................................................................9 - 10
Selectivity/Cascade: MCB & MCCB ..................................................................................9 - 11
Watts loss – MCCBs ...................................................................................................................9 - 21
Short circuit current calculator ..........................................................................................9 - 22
Short circuit co-ordination ...................................................................................................9 - 24
Motor circuit: application tables .......................................................................................9 - 38
Motor starting: Motor rated currents ............................................................................9 - 45
MCCB 380/415 V clearance requirements ..................................................................9 - 47
Electrical mathematical formulae ....................................................................................9 - 50
TemBreak 2 Electronic OCR & MCCBs ...........................................................................9 - 51
MCCB Cross reference .............................................................................................................9 - 67
RCD/Earth Leakage applications and AS/NZS Standards ................................9 - 68
IP Ratings chart ............................................................................................................................9 - 70
NHP Technical News publications ...................................................................................9 - 71
26
Valid until August 2014
Section 1
1
Miniature circuit breakers and accessories (MCBs)
Page
Miniature Circuit Breaker selection guide 1-2
Safe-T Series 6 kA miniature circuit breakers 1-6
Safe-T Series 6 kA miniature circuit breakers with shunt trip 1-8
Safe-T Switchboard hardware and accessories 1-9
Safe-T Single pole width RCCBs SRCB (RCBO) 1 - 10
Safe-T Earth leakage relay (ELR) 1 - 11
Din-T Series general features 1 - 12
Din-T 6 Series 6 kA miniature circuit breakers 1 - 14
Din-T series 6 kA 2-in-1 1 - 16
Din-T Series 6 kA for DC applications 1 - 17
Din-T 10 Series 10 kA miniature circuit breakers 1 - 19
Din-T 10H Series 10 kA miniature circuit breakers 1 - 22
Din-T 15 Series 15 kA miniature circuit breakers 1 - 23
Din-T 6 easy-fit 1 - 24
Din-Safe safety switches 1 - 25
Din-Safe single pole 1 - 28
Din-Safe MCBs (RCBO) 1 - 30
Din-Safe-M add on earth leakage modules 1 - 32
Accessories - mounting 1 - 35
Main switch 63 - 100 A 1 - 38
Din-T shunt and undervoltage trip 1 - 39
Din-T auxiliary contacts & Din-T motor operator DTMD 1 - 40
Din mount housing, panelboard switch & kilowatt meters 1 - 42
Din busbar comb 1 - 43
Changeover switch, pushbuttons 1 - 44
LockDIN™ 1 - 46
Meter Isolator 1 - 48
Accessories for Din-T series MCBs 1 - 50
Din-T contactors and hour run counter 1 - 52
Din-T impulse switches 1 - 55
CA 8 contactors and emergency lighting test unit 1 - 56
Surge diverters 1 - 57
Dimensions - Safe-T & Din-T 1 - 61
Time switches 1 - 68
1-1
Valid until August 2014
Miniature circuit breakers
18 mm 27 mm 18 mm 18 mm 18 mm
36 mm 54 mm 18 mm 36 mm -
54 mm 81 mm 36 mm - 54 mm
72 mm 108 mm 36 mm 81 mm -
DIN rail DIN rail DIN rail DIN rail DIN rail
0.5 A - 63 A 80 A-125 A 2 A-40 A 0.5 A-63 A 6 A-63 A
15 kA - 50 kA 10 kA 6 kA 6 kA T15 6 kA
C C&D C B&C C
240/415 V 240/415 V 240/415 V 240/415 V 240/415 V
48 V 1P 125 V 2P - 250 V 1P -
110 V 2P 250 V 4P 500 V 2P
880 V 4P
Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes
No No No No No
Yes Yes Yes Yes Yes
Yes Yes No Yes No
Pin Pin Pin Fork/Pin -
Fork/Pin Pin Pin Fork/Pin Pin
35 mm2 70 mm2 16 mm2 35 mm2 4 mm2
6 A-20 A
35 mm2
25 A - 63 A
35 mm2 70 mm2 16 mm2 35 mm2 35 mm2
Din-Safe Din-Safe
Residual Current Devices Safe-T SRCB DSRCD DSRCBS
Standard (AS/NZS) ) 1
3111 /3190 )2
61008 61009
No. poles & module width 1P + N - 25 mm 2P - 36 mm, 1P + N - 18 mm
4P - 72 mm
Mounting Clip tray DIN rail DIN rail
Current ratings 10 A, 40 A, 63 A, 6 A, 10 A,
16 A, 80 A, 100 A & 16 A, 20 A,
20 A 125 A 25 A & 32 A
Trip senstivity 10 mA & 30 mA, 30 mA
30 mA 100 mA,
300 mA,
500 mA
Sensitivity type AC AC, A, AI, S & B AC & A
Short circuit rating (kA) 6 kA Inc -10 kA MCB 6 kA
or fuse backup
Curve types General - B&C
Rated AC voltage 240 V 240 V/415 V 240 V
Sealable in ON-Off position No Yes Yes
Trip-free mechanism Yes Yes Yes
Centre trip position Yes No No
Padlock- non captive No Yes Yes
Padlock- captive Yes No No
Busbar connection- On-top Fork Pin -
Busbar connection- OFF-bottom Fork Fork/Pin Pin
Terminal size- On-top - 50 mm2 16 mm2
A AC & A AC & A AC AC
Inc - 10 kA MCB
10 kA 10 kA 10 kA - or fuse backup
C C C - -
240 V 110 V/240 V 110 V/240 V 240 V/415 V 240 V/415 V
Yes Yes Yes No Yes
Yes Yes Yes Yes Yes
No No No No No
Yes Yes Yes No Yes
Yes Yes Yes No No
- Pin - - -
Fork/Pin Fork/Pin Fork/Pin - Pin
25 mm2 25 mm2 25 mm2 32 A- 16 mm2 50 mm2
63 A- 25 mm2
35 mm2 35 mm2 35 mm2 - 50 mm2
Safe-T series
1 6-100 A
6 kA
Q Standard AS 3111 AS 2184 1)
Q Approval No. V99347
Q UL 489 fluorescent switching duty 1)
Q Lloyd’s register
Q Current range 6 -100 A 1, 2, 3 and 4 pole
Q Clip-tray mounting. Suits CT type busbar chassis
Q General purpose light and power distribution
Technical data
Interrupting capacity: 6 kA at 250 V AC (sym) 1 pole
6 kA at 400 V AC (sym) 2 & 3 pole
5 kA at 125 V DC 2 pole
Thermal setting: Fixed (40 °C)
Magnetic setting: Fixed
Tropic proofed: Standard
Shunt Trip - Coil rating Warnings
Current peak Short time rated coil.
Voltage (V) (A)
Coil burnout will
120-440 V AC 4.88 (440 V)
result if coil remains
48-250 V DC 2.32 (250 V) energised.
Shunt trip wiring
diagram
Safe-T series
6-100 A 1
Amp 1 pole 2 pole
rating Cat. No. Price $ Cat. No. Price $
6 SAFET6106 SAFET6206
10 SAFET6110 SAFET6210
16 SAFET6116 SAFET6216
20 SAFET6120 SAFET6220
25 SAFET6125 SAFET6225
32 SAFET6132 SAFET6232
40 SAFET6140 SAFET6240
50 SAFET6150 SAFET6250
63 SAFET6163 SAFET6263
80 SAFET6180 SAFET6280
100 SAFET61100 SAFET62100
63 SAFET6163NA 2) SAFET6263NA 2)
100 SAFET61100NA 2) SAFET62100NA 2)
Amp 3 pole 3P + N 1)
rating Cat. No. Price $ Cat. No. Price $
6 SAFET6306 SAFET6406
10 SAFET6310 SAFET6410
16 SAFET6316 SAFET6416
20 SAFET6320 SAFET6420
25 SAFET6325 SAFET6425
32 SAFET6332 SAFET6432
40 SAFET6340 SAFET6440
50 SAFET6350 SAFET6450
63 SAFET6363 SAFET6463
80 SAFET6380 SAFET6480
100 SAFET63100 SAFET64100
63 SAFET6363NA 2) SAFET6463NA 2)
100 SAFET63100NA 2) SAFET64100NA 2)
Notes: 1) Neutral pole is switched but does not provide overcurrent or short circuit
protection.
2
) NA – Non-Auto MCB without overcurrent or short circuit protection, suitable
for main switch.
Refer page 9 - 10 for back-up fuse data. Accessories refer page 1 - 9.
Safe-T series
1 6-100 A fitted with shunt trip
Amp 3 pole 3P + N 1)
rating Cat. No. Price $ Cat. No. Price $
6 SAFET6306SHT SAFET6406SHT
10 SAFET6310SHT SAFET6410SHT
16 SAFET6316SHT SAFET6416SHT
20 SAFET6320SHT SAFET6420SHT
25 SAFET6325SHT SAFET6425SHT
32 SAFET6332SHT SAFET6432SHT
40 SAFET6340SHT SAFET6440SHT
50 SAFET6350SHT SAFET6450SHT
63 SAFET6363SHT SAFET6463SHT
80 SAFET6380SHT SAFET6480SHT
100 SAFET63100SHT SAFET64100SHT
63 SAFET6363NASHT 2) SAFET6463NASHT 2)
100 SAFET63100NASHT 2) SAFET64100NASHT 2)
Operation
For remote tripping of Safe-T MCB (1 to 4 poles), manual resetting of MCB
required. Inline shunt trip requires no extra pole spaces; refer to page 1 - 10
for connection diagram.
Application
Emergency stop and isolation of industrial socket outlets.
Notes: 1) Neutral pole is switched but does not provide overcurrent or short circuit
protection.
2
) NA – Non-Auto MCB without overcurrent or short circuit protection, suitable
for main switch.
Backup fuse data, refer to page 9-10.
Accessories to suit Safe-T MCBs, refer to page 1 - 9.
Safe-T series
Options, hardware and accessories 1
Description Cat. No. Price $
Handle lock Yellow TAA5LY 1)
1 pole TKB50SGL 1)
Padlock attachment
3 pole TKC50SG 1)
Padlock attachment 12 pack and resin SAFETLCK 12 1)
kits (captive) 24 pack and resin SAFETLCK 24 1)
35 mm2 Safe-T (6-63 A) 7T1ST 1)
Tunnel terminal 70 mm2 Safe-T
7T2ST 1)
(80-100 A)
T-off plastic caps TH250TOPC
Pole fillers SAFETPF
Clip-tray (per 12 pole pieces) TDB50SG12
Link bar (1 phase) 18 pole LB18
Link bar (3 phase) 12 pole LB3PH12
120 A 18 pole LB3PH18
TKC50SG
Tunnel terminals TAA5LY Locking attachments
Adaptors - allows
SRCB to be fitted Padlock
to Heinemann and attachment
Eaton chassis kit
Technical data
Q Operation: Instantaneous
Q Frequency: 40-60 Hz
Q Output ratings: I peak 8 A,
I average 0.5 A
Q Toroid window: 4 x 35 mm2
(aperture diameter
35 mm)
Q Dimensions: H = 152 mm
W = 25 mm
D = 60 mm
Q Weight: 0.16 kg
Din-T series
General features
Din-T series
General features 1
Handle
Sealable and padlockable with quick-make and quick-break type mechanism.
The handle is sealable in ON and OFF position. Due to the free-tripping
mechanism, the MCB contacts open through overload or short circuit even
when the handle is sealed in the ON position on all types.
Input terminal (‘OFF’ side)
Box terminal with lifting screw for copper and aluminium conductors:
maximum capacity 1 x 35 mm2 or 2 x 16 mm2.
When unscrewing the screw, the head lifts; however, on pushing the screw
head, the box terminal opens. This system enables the MCBs to be linked with
a cable and fork or pin type bus comb. The MCB is delivered with a half open
box terminal and a lifted screw head.
Output terminal (‘ON’ side)
Box terminal with captive terminal screw for copper and aluminium conductors:
max. 1 x 35 mm2 or 2 x 16 mm2.
The box terminals are always delivered in the open position. Output terminal
screw has IP 20 protection against direct finger contact by standard design.
Arc chamber
Contains arc extinction plates, (de-ionising type) designed to break up and
dissipate the arc which is generated during interruption of all types of faults.
Electromagnet
Operating the plunger which opens the contacts instantaneously.
Arc magnetic blowout system
Short circuit currents do not flow through the bi-metal but are directed by the
blowout magnet in such a way that the arc is transferred to a special arc run-
ner, therefore taking the bi-metal out of the circuit, which ensures the thermal
trip characteristics remain unchanged after an MCB has been exposed to a
fault current.
Q This combination of the electromagnet (with a plunger rapidly opening
the contacts), the blowout magnet and the arc chamber, results in an
extremely high short circuit breaking capacity, and very low let through
energy.
Catalogue Number construction for Din-T MCBs (6, 10, 10H and 15)
DTCB - XX - X - XX - X
CurveType
Current (A) B 3 In - 5 In
Product
series code Short circuit 05 0.5 C 5 In - 10 In
Din-T6
1 Series 2-63 A
6 kA 'C' curve
Q Standard AS/NZS 60898
Q Approval No. N17481
Q Current range 2-63 amps 1, 2 and 3 pole
Q Sealable and lockable handle
Q DIN rail mounting
Q Padlockable in OFF position
Q Suits CD, NC or GB chassis
Q General purpose light, power and motor starting
Curve type: C (5 – 10 In)
Single pole
In (A) Cat. No. Price $ In (A) Cat. No. Price $
2 DTCB6102C 20 DTCB6120C
4 DTCB6104C 25 DTCB6125C
6 DTCB6106C 32 DTCB6132C
10 DTCB6110C 40 DTCB6140C
13 DTCB6113C 50 DTCB6150C
16 DTCB6116C 63 DTCB6163C
Double pole
In (A) Cat. No. Price $ In (A) Cat. No. Price $
2 DTCB6202C 20 DTCB6220C
4 DTCB6204C 25 DTCB6225C
6 DTCB6206C 32 DTCB6232C
10 DTCB6210C 40 DTCB6240C
13 DTCB6213C 50 DTCB6250C
16 DTCB6216C 63 DTCB6263C
Triple pole
In (A) Cat. No. Price $ In (A) Cat. No. Price $
2 DTCB6302C 20 DTCB6320C
4 DTCB6304C 25 DTCB6325C
6 DTCB6306C 32 DTCB6332C
10 DTCB6310C 40 DTCB6340C
13 DTCB6313C 50 DTCB6350C
16 DTCB6316C 63 DTCB6363C
Notes: The LINE-side is the OFF or bottom of the MCB, and connects to CD, NC
or GB chassis tee-offs.
Suitable for the following side mounted accessories:
– AUX/ALM switches – refer page 1 - 40
– Shunt trip and UVT Trip – refer page 1 - 39
– Clip-on RCD module and Din-Safe-M module- refer page 1 - 32
– Din-T terminals and accessories – refer page 1 - 50
Din-T6
Series 2-63 A 1
6 kA ‘D’ curve
Q Standard AS/NZS 60898
Q Approval No. N17481
Q Current range 2-63 amps 1, 2 and 3 pole
Q Sealable and lockable handle
Q DIN rail mounting
Q Padlockable in OFF position
Q Suits CD, NC or GB chassis
Q Motor starting and transformer applications
Curve type: D (10 – 20 In)
Single pole
In (A) Cat. No. Price $ In (A) Cat. No. Price $
2 DTCB6102D 20 DTCB6120D
4 DTCB6104D 25 DTCB6125D
6 DTCB6106D 32 DTCB6132D
10 DTCB6110D 40 DTCB6140D
13 DTCB6113D 50 DTCB6150D
16 DTCB6116D 63 DTCB6163D
Double pole
In (A) Cat. No. Price $ In (A) Cat. No. Price $
2 DTCB6202D 20 DTCB6220D
4 DTCB6204D 25 DTCB6225D
6 DTCB6206D 32 DTCB6232D
10 DTCB6210D 40 DTCB6240D
13 DTCB6213D 50 DTCB6250D
16 DTCB6216D 63 DTCB6263D
Triple pole
In (A) Cat. No. Price $ In (A) Cat. No. Price $
2 DTCB6302D 20 DTCB6320D
4 DTCB6304D 25 DTCB6325D
6 DTCB6306D 32 DTCB6332D
10 DTCB6310D 40 DTCB6340D
13 DTCB6313D 50 DTCB6350D
16 DTCB6316D 63 DTCB6363D
Notes: The LINE-side is the OFF or bottom of the MCB, and connects to CD, NC
or GB chassis tee-offs.
Suitable for the following side mounted accessories:
– AUX/ALM switches – refer page 1 - 40
– Shunt trip and UVT Trip – refer page 1 - 39
– Clip-on RCD module and Din-Safe-M module- refer page 1 - 32
– Din-T terminals and accessories – refer page 1 - 50
Din-T6
1 2-in-1 Double the capacity of your load centre
6 kA ‘C’ curve
Q Standard AS/NZS 60898
Q Approval No. NSW24783
Q Current range 2 - 40 A
Q C curve tripping characteristics
Q Saves up to 50 % space
Q DIN rail mounting
Q General purpose light and power
Curve type: C (5 – 10 In) 1P + 1P 3 Pole
1 pole + 1 pole 2 pole
Single module width (18 mm) Single module width (18 mm)
In (A) Cat. No. Price $ In (A) Cat. No. Price $
2 DTCBD61102C 2 DTCBD6202C
4 DTCBD61104C 4 DTCBD6204C
6 DTCBD61106C 6 DTCBD6206C
10 DTCBD61110C 10 DTCBD6210C
16 DTCBD61116C 16 DTCBD6216C
20 DTCBD61120C 20 DTCBD6220C
Must be same phase. 25 DTCBD6225C
32 DTCBD6232C
40 DTCBD6240C
3 pole 4 pole
Double module width (36 mm) Double module width (36 mm)
In (A) Cat. No. Price $ In (A) Cat. No. Price $
2 DTCBD6302C 2 DTCBD6402C
4 DTCBD6304C 4 DTCBD6404C
6 DTCBD6306C 6 DTCBD6406C
10 DTCBD6310C 10 DTCBD6410C
16 DTCBD6316C 16 DTCBD6416C
20 DTCBD6320C 20 DTCBD6420C
25 DTCBD6325C 25 DTCBD6425C
32 DTCBD6332C 32 DTCBD6432C
40 DTCBD6340C 40 DTCBD6440C
Din-T DC
Series 0.5-63 A 1
6 kA ‘C’ curve
Q Standard AS/NZS 60898
Q Approval No. NSW 24265
Q Current range 0.5 - 63 A 1P and 2P
Q C curve tripping characteristic
Q DC Voltage 250 V 1P, 500 V 2P
Q AC Voltage 230 V 1P, 400 V 2P
Q Sealable and lockable handle
Q DIN rail mounting 1 Pole 2 Pole
Q Suit CD, NC and GB chassis
Q Industrial applications
Operation
Din-T DC MCBs are equipped with a permanent magnet which aids arc
extinguishing under fault conditions, making this range of MCBs suitable for
voltages up to 250 V DC (1 pole), 500 V DC (2 pole) and 880 V DC (4 pole).
Din-T DC 1P and 2P MCBs are also suitable for AC voltages. Polarity labeling
must be respected due to the permanent magnet in the MCB.
Curve type: C (5 – 10 In)
Single pole Double pole
In (A) Cat. No. Price $ In (A) Cat. No. Price $
0.5 DTCBDC105C
1 DTCBDC101C 1 DTCBDC201C
2 DTCBDC102C 2 DTCBDC202C
4 DTCBDC104C 4 DTCBDC204C
6 DTCBDC106C 6 DTCBDC206C
10 DTCBDC110C 10 DTCBDC210C
16 DTCBDC116C 16 DTCBDC216C
20 DTCBDC120C 20 DTCBDC220C
25 DTCBDC125C 25 DTCBDC225C
32 DTCBDC132C 32 DTCBDC232C
40 DTCBDC140C 40 DTCBDC240C
50 DTCBDC150C 50 DTCBDC250C
63 DTCBDC163C 63 DTCBDC263C
Connection diagrams
Load Load
DC Supply
DC Supply
Din-T DC
1 Series 0.5-63 A
6 kA ‘B’ curve
Q Standard AS/NZS60898
Q Approval No. NSW 24265
Q Current range 10 - 63 A 4P
Q B curve tripping characteristic
Q DC Voltage 880 V 4P (1000 V PV systems)
s)
Q Sealable and lockable handle
Q DIN rail mounting
Q Industrial applications
Operation
Din-T DC MCBs are equipped with a permanent magnet which aids arc
extinguishing under fault conditions, making this range of MCBs suitable for
voltages up to 250 V DC (1 pole), 500 V DC (2 pole) and 880 V DC (4 pole).
Din-T DC 1P and 2P MCBs are also suitable for AC voltages. Polarity labeling
must be respected due to the permanent magnet in the MCB.
Curve type: B (3 – 5 In)
Four pole
In (A) Cat. No. Price $
10 DTCBDC410B
16 DTCBDC416B
20 DTCBDC420B
Connection diagram
DC Supply
Din-T10
Series 6-63 A 1
10 kA ‘B’ curve
Q Standard AS/NZS 60898
Q Approval No. N17481
Q Current range 6 - 63 A 1, 2, and 3 pole
Q Sealable and lockable handle t
Grea g
Q DIN rail mounting n
for lo runs
Q Padlockable in OFF position
cable park
Q Suits NC, CD or GB type chassis (Car g)
in
Q Resistive load applications light
Triple pole
In (A) Cat. No. Price $
6 DTCB10 3 06B
10 DTCB10 3 10B
16 DTCB10 3 16B
20 DTCB10 3 20B
25 DTCB10 3 25B
32 DTCB10 3 32B
40 DTCB10 3 40B
50 DTCB10 3 50B
63 DTCB10 3 63B
Notes: The LINE-side is the OFF or bottom of the MCB, and connects to NC, GB
or CD chassis tee-offs.
A range of UL standard MCBs is available on indent (Ref DTCBUL10...C)
Suitable for the following side mounted accessories:
– AUX/ALM switch – refer page 1 - 40
– Shunt trip and UVT trip – refer page 1 - 39
– Clip-on RCD module - refer page 1 - 32
– Din-T terminals and accessories – refer page 1 - 50
Din-T10
1 Series 0.5 - 63 A
10 kA ‘C’ curve
Q Standard AS/NZS 60898
Q Approval No. N17481
Q Current range 0.5 - 63 A 1, 2, 3 and 4 pole
Q Sealable and lockable handle
Q DIN rail mounting
Q Padlockable in OFF position
Q Suits NC, CD or GB chassis
Q General purpose light, power and motor starting
Din-T10
Series 0.5 - 63 A 1
10 kA ‘D’ curve
Q Standard AS/NZS 60898
Q Approval No. N17481
Q Current range 0.5 - 63 A 1, 2, 3 and 4 pole
Q Sealable and lockable handle
Q DIN rail mounting
Q Padlockable in OFF position
Q Suits NC, CD or GB type chassis
Q Motor starting and transformer applications
Curve type: D (10 – 20 In)
Din-T10H
1 Series 80-125 A
10 kA ‘C’ Curve
7.5 kA ‘D’ Curve
Q Standard AS/NZS 60947 - 2
Q Current range 80 - 125 A 1, 2, 3 and 4 pole
Q Module width = 27 mm
Q DIN rail mounting
Q Suits NCH or CDH hybrid type chassis
Q Industrial applications
Curve type: C (5 – 10 In)
Single pole Double pole
In (A) Cat. No. Price $ In (A) Cat. No. Price $
80 DINT10H180C 80 DINT10H280C
100 DINT10H1100C 100 DINT10H2100C
125 DINT10H1125C 125 DINT10H2125C
Notes: The LINE-side is the OFF or bottom of the MCB, and connects to NCH or
CDH chassis tee-offs.
Din-T10H MCBs do not fit NC or CD chassis with 18mm pole pitch.
All poles include overcurrent and short circuit protection.
Suitable for the following side mounted accessories:
– AUX/ALM switch – refer page 1 - 40
– Shunt trip – refer page 1 - 39
– Din-T terminals and accessories – refer page 1 - 50
Din-T15
Series 6 - 63 A 1
15 kA, 20 kA, 25 kA, 50 kA ‘C’ curve
Q Standard AS/NZS 60947 - 2
Q Current rating 6 - 63 A 1, 2, 3 and 4 pole
Q Sealable and lockable handle
Q DIN rail mounting
Q Suits NC or CD type chassis
Q Industrial applications
Curve type: C (5 – 10 In)
Single pole Double pole
In (A) Cat. No. Price $ In (A) Cat. No. Price $
6 DTCB15 1 06C 6 DTCB15 2 06C
10 DTCB15 1 10C 10 DTCB15 2 10C
13 DTCB15 1 13C 13 DTCB15 2 13C
16 DTCB15 1 16C 16 DTCB15 2 16C
20 DTCB15 1 20C 20 DTCB15 2 20C
25 DTCB15 1 25C 25 DTCB15 2 25C
32 DTCB15 1 32C 32 DTCB15 2 32C
40 DTCB15 1 40C 40 DTCB15 2 40C
50 DTCB15 1 50C 50 DTCB15 2 50C
63 DTCB15 1 63C 63 DTCB15 2 63C
Din-T6
1 Easy-Fit MCB and RCCBs – Tool-free connection
6 kA ‘C’ curve
Q Standard AS/NZS 60898 NEW
Q Approval No. NSW 24783
Q Current range 2 - 63 A
Q C curve tripping characteristic
Q Cable clamping technology
Q Line side- Plug in or screw in busbar comb
Q Load side- Screw-less cable connection up to 20 A
Q DIN rail mounting
Q General purpose light and power
Curve type: C (5 – 10 In)
Single pole Triple pole
Din-Safe RCD
Q Standard AS/NZS 61008 ced
Redu tion
Q Approval No NSW 17482 lla
insta e
Q Current range 40 - 63 A tim
Q 2 pole and 4 pole configurations
Q 30 mA sensititvity
Q Cable clamping technology
Q Line side- Screw terminal
Q Load side- Screw terminal or plug in busbar comb
Q DIN rail mounting
Amp
No. poles Trip sens. rating Voltage Cat. No. Price $
40 A 240 V DSRCDE24030
2P (1P+N) 30 mA
63 A 240 V DSRCDE26330
40 A 240/415 V DSRCDE44030
4P (3P+N) 30 mA
63 A 240/415 V DSRCDE46330
Din-Safe
Safety switches (RCCB) 1
Q Standard AS/NZS 61008
Q H
Approval No. N17482 imm igh
u
Q Current ratings 40, 63, 80 and 100 A typenity
Q 2 and 4 pole configuration
Q Accepts Din-T side mounting accessories
Q Handle sealable and padlockable
No. poles Trip sens. Amp rating Voltage Cat. No. Price $
40 A 240 V DSRCD24030
30 mA 63 A 240 V DSRCD26330
80 A 240 V DSRCD28030
2P (1P+N) 40 A 240 V DSRCD240100
100 mA 80 A 240 V DSRCD280100
40 A 240 V DSRCD240300
300 mA 80 A 240 V DSRCD280300
40 A 415 V DSRCD44030
63 A 415 V DSRCD46330
30 mA 80 A 415 V DSRCD48030
100 A 415 V DSRCD410030
40 A 415 V DSRCD440100
4P (3P+N) 63 A 415 V DSRCD463100
100 mA 80 A 415 V DSRCD480100
100 A 415 V DSRCD4100100
40 A 415 V DSRCD440300
300 mA 100 A 415 V DSRCD4100300
500 mA 100 A 415 V DSRCD4100500
Din-Safe
1 Safety switches (RCCB)
Type A RCD
No. poles Trip sens. Amp rating Voltage Cat. No. Price $
40 A 240 V DSRCD24030A
30 mA 63 A 240 V DSRCD26330A
2P (1P+N) 80 A 240 V DSRCD28030A
40 A 240 V DSRCD240100A
100 mA 80 A 240 V DSRCD280100A
40 A 415 V DSRCD44030A
30 mA 63 A 415 V DSRCD46330A
4P (3P+N) 100 A 415 V DSRCD410030A
63 A 415 V DSRCD463100A
100 mA 80 A 415 V DSRCD480100A
Type B
30 mA 63 A 240 V DSRCD46330B
100 mA 63 A 240 V DSRCD463100B
4P (3P+N)
500 mA 125 A 415 V DSRCD4125500B
300 mA 63 A 415 V DSRCD463300BS 1)
Notes: 1
) Selective type.
30 mA tripping characteristics: 0.5 x Δn = no tripping, 1 x Δn = T ≤300 mS,
2 x Δn = T ≤150 mS, 5 x Δn = T ≤40 mS
Din-Safe
Safety switches (RCCB) 1
Connection details
110/240
Circuit diagrams
Dimensions (mm)
Din-Safe
1 Compact single pole width residual current circuit breaker
(RCBO) Same dimensions as a standard MCB
6 kA
Q Standard AS/NZS 61009
Q Approval No. NSW24576
Q Current range 6 - 32 A
Q C curve tripping characteristic
Q Short circuit, overcurrent and earth leakage protection
Q Sensitivity 30 mA
Q DIN rail mounting
Q Dual DIN clip
Q Suits NC, CD and GB chassis
Q Suitable for loadcenters and panelboards
Q General purpose light and power
Curve type: C (5 – 10 In)
Short
Trip No. of circuit
sens. poles Voltage cap. In (A) Cat. No. 1) Price $
6 DSRCBS0630C
10 DSRCBS1030C
240 V 16 DSRCBS1630C
30 mA 1 pole 6 kA
AC 20 DSRCBS2030C
25 DSRCBS2530C
32 DSRCBS3230C
Curve type: B (3 – 5 In)
Short
Trip No. of circuit
sens. poles Voltage cap. In (A) Cat. No. 1) Price $
6 DSRCBS0630B
10 DSRCBS1030B
240 V 16 DSRCBS1630B
30 mA 1 pole 6 kA
AC 20 DSRCBS2030B
25 DSRCBS2530B
32 DSRCBS3230B
Dimensions (mm) Connection diagram
Notes: 1) Insert 'A' at end of part number for Type A RCD e.g. DSRCBS-20-30-CA.
Nuisance tripping may be experienced in VFD and motor starting
applications, refer NHP.
Din-Safe
Single pole width residual current circuit breaker (RCBO) 1
10 kA H
imm ighh e
Q Standard AS/NZS 61009 u ighr
him
armmunnity to
Q Approval No. N17482 o it
harm nicys to
onic
Q One module wide (18 mm) s
Q Short circuit, overcurrent and earth leakage protection
Q Short circuit capacity 10 kA
Q Sensitivity 10 and 30 mA
Q Suits NC, CD or GB chassis
Q Type ‘A’ RCD
Curve type: C (5 – 10 In)
Short
Trip No. of circuit
sens. poles Voltage cap. In (A) Cat. No. 1)2) Price $
6 DSRCBH0630A
10 DSRCBH1030A
16 DSRCBH1630A
30 mA 1 Pole 240 V AC 10 kA 20 DSRCBH2030A
25 DSRCBH2530A
32 DSRCBH3230A
40 DSRCBH4030A
6 DSRCBH0610A
10 DSRCBH1010A
16 DSRCBH1610A
10 mA 1 Pole 240 V AC 10 kA 20 DSRCBH2010A
25 DSRCBH2510A
32 DSRCBH3210A
40 DSRCBH4010A
line side
Notes: The LINE-side is the OFF or bottom of the MCB, and connects to chassis tee-offs.
1
) Neutral not switched.
2
) Will not accept Din-T side mounting accessories.
30 mA tripping characteristics: 0.5 x I6n = no tripping, 1 x I6n = T )300 mS
2 x I6n = T )150 mS, 5 x I6n = T )40 mS
Nuisance tripping may be experienced in VFD and motor starting
applications refer NHP.
GST not included NHP Sales 1300 NHP NHP 1 - 29
Price schedule ‘T3’ www.nhp.com.au
Valid until August 2014
Residual current devices
Din-Safe
1 MCB (RCBO)
Type A RCD
Trip No. of Voltage
sens. poles (AC) Phase In (A) Cat. No. Price $
10 DSRCB1030A
16 DSRCB1630A
20 DSRCB2030A
30 mA 2 Pole 110/240 1 P+N
25 DSRCB2530A
32 DSRCB3230A
40 DSRCB4030A
6 DSRCB0610A
10 DSRCB1010A
10 mA 2 Pole 110/240 1 P+N
16 DSRCB1610A
20 DSRCB2010A
10 DSRCB10100A
100 mA 2 Pole 110/240 1 P+N 16 DSRCB16100A
20 DSRCB20100A
Din-Safe
MCB (RCBO) 1
10 kA MCB with Pigtail (RCBO)
Q Standard AS/NZS 61009
Q Approval No. N17482
Q Un-switched neutral
Q Suits NC, CD or GB chassis
Complete with revised terminal configuration and neutral
pigtail, will fit standard Din-T 3 ph chassis.
Curve type: C (5 – 10 In)
Type AC RCD
Trip No. of Voltage
sens. poles (AC) Phase In (A) Cat. No. Price $
6 DSRCB0630P
10 DSRCB1030P
16 DSRCB1630P
30 mA 2 Pole 110/240 1P+N 20 DSRCB2030P
25 DSRCB2530P
32 DSRCB3230P
40 DSRCB4030P
Din-Safe-M
1 Add-on earth leakage modules
Notes: 1) 1P+N and 3P+N type supply neutral connected by ‘pigtail’ cable.
2
) Dimensions of Din-Safe-M unit only; add MCB width for total installed
width.
3
) ‘MCB rating’ refers to the max. MCB rating the module can be fitted to.
4
) 1P + N suitable for 415 V 2P applications.
Not suitable for Din-T10H MCBs.
Din-Safe-M
Modules to be combined with Din-T MCBs 1
Operation
The combined Din-T MCB/Din-Safe-M earth leakage module has two operat-
ing toggles which indicate the reason for the trip action taking place.
Q When an overload or short circuit occurs the Din-T MCB will operate. In
this case the Din-Safe-M toggle will remain in the ON position.
Q If an earth leakage fault occurs both toggles will move to the OFF position.
In order to reset the MCB the Din-Safe-M unit must be reset first.
Q In both instances – if the cause of the trip operation has not been rectified,
a trip operation will occur as soon as the MCB is turned to the ON position.
The trip free mechanism of the MCB ensures that a successful trip
operation takes place even when the toggle is held in the ON position.
Assembly
Q Place the MCB and Din-Safe-M unit on a flat surface. Be sure that both the
MCB and the Din-Safe-M toggles are in the ON position.
Q Slide the two units towards each other inserting the connecting bars or
links into the MCB tunnel terminal, ensuring no undue pressure is applied
to the metal tripping pin of the Din-Safe-M unit.
Q Push in the connecting clips, locking the unit together.
Q Check that the MCB trips when the toggle on the Din-Safe-M is moved to
the OFF position.
Q Tighten the busbar connections between the MCB and the Din-Safe-M and
fit the insulating cover supplied.
Q If the pigtail and N connections are reversed, the breaker will trip as soon
as load is energised. Reset Din-Safe-M module before switching MCB ‘ON’.
Q In the case of a three phase 3 wire system (no neutral) use 3 phase models.
3P+N models will operate satisfactorily but test button will only function if
neutral pigtail is connected.
+ =
Q Din-Safe-M modules are an earth leakage module only. To complete
the functional unit a Din-T6, Din-T10 or Din-T15 MCB must be added as
shown.
Din-Safe-M
1 Modules to be combined with Din-T MCBs
Testing
The MCB/Din-Safe-M combination must be connected with the line conduc-
tors to the LINE side (OFF/Bottom side) of the MCB and the load conductors
connected to the Din-Safe-M terminals. The MCB/Din-Safe-M combination
must be tested with the supply connected before connecting the load.
First switch the Din-Safe-M unit ‘ON’ then the MCB. When the test button is
pressed, both handles should trip. It is recommended that the test button
is operated periodically to test the detection and tripping functions of the
combined unit.
Q Both 1P+N and 3P+N models have a neutral pigtail connection. 3P
modules have no neutral connection at all.
Connection diagram
Load
Accessories
Mounting of add-on devices onto MCBs, RCCBs and RCBOs 1
Din-T, Change
DC, Din-T DSRCB, -over
Type/Description 6, 10, 15 10H DSRCD DSRCM DINTMS switch
DTAUXAL L-R – R R L-R L-R
Signal or AUX contact
DTAUXALG
Signal or AUX contact, L-R – R R L-R L-R
gold
DINT10HHS
Signal or AUX + AUX – R – – – –
contact
DTPBS L-R – R – – –
Panelboard switch
DINTSHT – L – – – –
Shunt trip
DTSHT L-R – R R – –
Shunt trip
DTUVT L-R – R R – –
Undervoltage trip
DTMD L-R – R R – –
Motor operator
Accessories
1 Mounting on the left-hand side
Accessories
Mounting on the right-hand side 1
Notes: DSRCBH and DSRCBS - Single pole RCD/MCB will not accept side mounted
accessories.
DINTMS - Main switches will accept side mounting auxiliary contacts only.
Din-TMS 63-100 A
1 Main switch DIN rail mount
A
- 100
63 A unts to
e m o
sid is
hass
NC c A side
3 A - 80 to
6 nts
mou ssis
ha
CD c
Dimensions (mm)
Din-T
Shunt and undervoltage trip 1
Din-T shunt trip
Q Couples to left or right side of MCB
Q Modular width – 18 mm
Q Busbar cavity both ends
Q Field assembly
Q Continuously rated
Q Terminals for remote indication
Operation
The shunt trip makes it possible to remotely switch the DTSHT 110415V
MCB by energising C1 & C2 terminals of the shunt trip.
Shunt trip - Din-T6, 10 & 15
Rated Current Operating
voltage rating time (ms) Cat. No. Price $
110 to 415 V AC 110 V - 0.3 A 10
110 to 125 V DC 240 V - 0.6 A 4 DTSHT110415V
415 V - 1.0 A 2
24 to 60 V AC 24 V – 1.0 A 10 DTSHT2460V
24 to 48 V DC 48 V – 2.0 A 4
Din-T
1 Auxiliary contacts for MCBs
Notes: 1) DTAUXAL type contact fits right side only on 2P RCBO and 2/4P RCCB.
2
) Auxiliary contacts for Din-T10H MCBs are not stackable and fit to right
side only.
3
) Fit right hand side only.
Din-T
Motor operator for MCBs 1
Din-T motor operator DTMD
Q Suitable for Din-T 6, 10 & 15
Q Suitable for 2P RCBO and 2P & 4P RCCB
Q Field fittable, includes all fitting accessories
Q Fits left or right side of device
Q Padlockable in the OFF position
Q Manual operation is possible
DTMD240VAC
Rated
voltage Module width Cat. No. Price $
240 V AC 3 DTMD240VAC
Technical
Rated voltage Un 240 V AC
Impulse to switch ON/OFF >50 ms
Closing time 500 ms
Opening time 200 ms
Electrical endurance 10,000 ops
Terminal capacity 2.5 mm2
Weight 380 g
Notes: DTMD240VAC fits right side only on 2P RCBO and 2/4P RCCB.
DTMD240VAC is not suitable for use with Din-T10H MCBs.
Notes: 1) ‘DTSP’ - 0.5 module width spacer available if required when DTPBS used.
2
) CE4DT Price Schedule 'Y8'.
Busbar comb
Din-T MCBs 1
80 A 4)
Pin type busbars
1 Phase 1) 3 Phase
No. of poles Cat. No. Price $ Cat. No. Price $
8 Way IBC108P –
12 Way IBC112P ICL123
15 Way IBC115P ICL153
18 Way IBC118P ICL183
21 Way IBC121P ICL213
55 Way IBC155P –
57 Way – ICL573
ICL123 ICLTOC
T-off cap (strip of 5)
ICL573F
Din-T
1 Modular changeover switch
Without OFF I - II
No. of
In (A) No. of Poles Modules Connection Cat. No. Price $
P
32 1 1 DTCS3212
P
32 2 1 P DTCS3222
With OFF I - O - II
No. of
In (A) No. of Poles Modules Connection Cat. No. Price $
P
32 1 1 DTCS3213
P
32 2 1 P
DTCS3223
Din-T
Pushbuttons and pilot lights
Q Modular size
Q DIN rail mounting
Q Terminal protection IP 20
Q Contacts, 16 A @ 250 V AC
No. of No. of
Description Poles Modules Contacts Cat. No. Price $
Pushbutton 2 1 N/O + N/C DTPB11
Pushbutton 1 1 N/O DTPB10L 1)
illuminated
Pilot light base 1 1 DTPLB 2)
Lamp 240 V - - DTPLL240
neon
Lamp 24 V - - DTPLL24
(filament)
Lens red - - DTPLLRD
Lens green - - DTPLLGR
Lens orange - - DTPLLOR
Lens clear - - DTPLLCL
Notes: 1) Order lens separately. 240 V lamp built-in and cannot be changed.
2
) Order lens and lamp separately.
POWER PROTECTION
11-0$,%*/.$#$1#
r %FTJHOFETQFDJñDBMMZGPSUIFNJOJOHJOEVTUSZ
r &BTZUPJOTUBMMBOESFUSPñUUPFYJTUJOH
$PODFQUr1SFNJFSBOE$PODFQUr506()
QBOFMCPBSET
r $BOCFVTFEXJUI%*/TBGF3$#0T
r "DDFQUTNNQBEMPDLT IBTQTBOE
TDJTTPSBSSBOHFNFOUT
r $BOPOMZCFVTFEXJUIUIF/)1%*/5SBOHF
r $BOCFVTFEXJUI BOEQPMF%*/5.$#T
/)1/)1OIQDPNBV /)1/)1OIQO[DPN
Valid until August 2014
Miniature circuit breakers
LOCK DIN™
1
Din-T lockdogs provide a captive locking attachment for Din-T MCBs and
RCDs.
The system is designed to be used in conjunction with Concept Premier and
Concept Tough Panelboards. If a switchboard is being specifically designed
to accommodate the new LOCK DIN™, then extra depth is required between
escutcheon and door to accommodate the padlocks being used on site.
The LOCK DIN™ is designed to be clipped onto the line side of the MCB.
This requires the line terminal screw to be tightened before installation. The
escutcheon cut out needs to be increased by 16 mm over the line terminal to
allow for the extended profile of the MCB with the LOCK DIN™ fitted.
DTLLA DTLLB
LOCK DIN™
1
Description Cat. No. Price $
Locking devices
LH locking assembly for MCBs and single pole DTLLA
RCBOs
RH locking assembly for MCBs and single pole DTLLARH
RCBOs
LH locking assembly for 2 pole RCBOs DTLLAB
RH locking assembly for 2 pole RCBOs DTLLABRH
Locking assembly for DINT-10H MCB DTLLA10H
12 pack LH locking assembly for MCBs and single DTLLABULK
pole RCBOs
12 pack RH locking assembly for MCBs and single DTLLARHBULK
pole RCBOs
Pole fillers and blanking devices
12 pack locking blank for MCBs and single pole DTLLB
RCBOs
Locking blank for DSRCM (add on RCCB), 3 pole DTLCM
MCBs
Dummy MCB (for total touch protection) DTLDM
12 pack pole filler (extended length to suit 63 mm DTLPF
cutout)
Escutcheons and labels
Concept premier escutcheon size 1 24 way to suit
LockDIN CPPES100DTL
Concept premier escutcheon size 2 48 way to suit CPPES200DTL
LockDIN
Concept premier escutcheon size 3 60 way to suit CPPES300DTL
LockDIN
Concept premier escutcheon size 4 84 way to suit CPPES400DTL
LockDIN
Concept premier escutcheon size 5 96 way to suit CPPES500DTL
LockDIN
Concept tough escutcheon size 2 48 way to suit CTES248RDCOLD
LockDIN
Concept tough escutcheon size 3 96 way to suit CTES396RDCOLD
LockDIN
Centre escutcheon label 1 - 48 LABLE148DT
Centre escutcheon label 49 - 96 LABLE4996DT
Meter Isolator
1 LOCK DINTM
The Lockable Meter Isolator from NHP utilises the captive locking system
known as LOCK DIN™. LOCK DIN™ has been designed for safe and secure
captive locking of Terasaki DIN-T MCBs. When you combine LOCK DIN™ with a
sealable enclosure and Terasaki MCB you have a complete system suitable for
meter isolation and supply capacity/ service protection. ) 1
Notes: 1) As the service and installations rules vary from region to region please
consult these to check suitability.
2
) Insert 80, 100 or 125 for required amp rating.
Meter Isolator
LOCK DINTM 1
Enclosures only, to suit meter isolator
To suit Enclosure type Cat. No. Price $
1 P MCB <63 A DTPC (2 pole) DTPC2LD
1-3 P MCB <63 A DTPC (4 pole) DTPC4LD
1-3 P MCB <63 A ILC (4 pole) ILC4SLD
1-3 P MCB 80-125 A ILC (4 pole) ILC4SLD10H
2 P RCBO 6-40 A DTPC ( 2 pole) DTPC2LDRCBO
DTPC enclosure
Dimensions (mm)
No. of poles Height Width Depth
2 pole 139 51 61
4 pole 139 88 61
ILC enclosure
Dimensions (mm)
No. of poles Height Width Depth
4 pole 175 90 100
DTTAX16PN3
DTLDH
MCB + DCLD6
DTPF captive padlock
DTTAX25SP
DTSP DTTAX25PN
DTTLT35SP DTTC 35
DTTLT35PN DIN10HTC
DTTLT35LPN DTLD DTCF 35
ICLTOC
T-off cap
(strip of 5)
DTTAX25PN DTCF35
Axial pin terminal 35 mm2 main
ICL Endcap ICL busbars 25 mm2 insulated terminal
Din-T
1 Series contactors
Din-T
Series contactors 1
Technical data
Type DTC20 DTC24 DTC40 DTC63
Rated continuous current Ith 20 A 24 A 40 A 63 A
AC 1/AC 7a switching of heaters
Rated operational current Ie 1) 20 A 24 A 40 A 63 A
Rated output AC 1 240 V 1ø 4 kW 5.3 kW 8.7 kW 13.3 kW
415 V 3ø – 16.0 kW 26.0 kW –
AC 3/AC 7b switching of motors
Rated operational current Ie 1) 9A 9A 22 A 30 A
Rated output AC 3 240 V 1ø 1.3 kW 1.3 kW 3.7 kW 5.0 kW
415 V 3ø – 4.0 kW 11.0 kW 15.0 kW
AC 5a switching of electric discharge lamp controls 2) (uncompensated)
Rated operational current Ie 1) 8A 10 A 30 A 44 A
AC 5b switching of incandescent lamps 2)
1
Rated operational current Ie ) 6A 7A 15 A 22 A
Switching on capacity
cos_ = 0.95 at 220-230 V 1 phase 100 A – – –
cos_ = 0.65 at 380-400 V 3 phase – 90 A 220 A 300 A
Switching off capacity
cos_ = 0.95 at 220-230 V 1phase 80 A – – –
cos_ = 0.65 at 380-400 V 3phase – 72 A 176 A 240 A
Ohmic loss per contact In 1.0 W 1.5 W 3.0 W 6.0 W
Endurance and mechanical switching
Max. switching frequency at AC 300 h 300 h 300 h 300 h
1/AC 7a
Max. switching frequency at AC 600 h 600 h 600 h 600 h
3/AC 7b
Mechanical service life 106 106 106 106
Electrical service life at AC 1/AC 7a 150,000 150,000 150,000 150,000
Electrical service life at AC 3/AC 7b 150,000 500,000 170,000 240,000
Terminal capacity max. 1x10 mm2 2x4 mm2 1x25 mm2 2x10 mm2
Magnetic control system
85…110 % x Un
Control voltage range
Rated operating frequency 50 / 60 Hz DC, 40…450 Hz
Operating temperature range -22 ºC to +55 ºC 3)
Max. pull-in coil power loss 8 VA/5 W 4 VA/4 W 5 VA/5 W 65 VA/65 W
Max. holding coil power loss 3.2 VA/1.2 W 4 VA/4 W 5 VA/5 W 4.2 VA/4.2 W
Switching on delay 9...12 ms <40 ms <40 ms <40 ms
Switching off delay 10...12 ms <40 ms <40 ms <40 ms
Terminal capacity max. 1 x 4 mm2 or 2 x 2.5 mm2
Notes: 1) When parallel switching 2 current paths the rated current le will be
multiplied by 1.6.
2
) For additional lamp switching data refer to NHP.
3
) If several contactors are mounted side by side in a row fit a half-module
spacer (Cat. No. DTSP) between every second contactor.
Din
1 Series contactors
Application
Din contactors are electromagnetically controlled switches used to control
single or multiphase high power loads while the control itself can be low
power. Applications include switching and control of lighting equipment,
heating, ventilation, pumps, heat pumps and other equipment.
Current Contact No. of
Ith config. Coil volts Mods. Cat. No. Price $
20 A 2 N/O 24 V AC 1 DTC202024L
20 A 2 N/O 240 V AC 1 DTC2020240L
25 A 4 N/O 12 V AC 2 DTC254012L
25 A 4 N/O 240 V AC 2 DTC2540240L
25 A 4 N/C 240 V AC 2 DTC2504240L
40 A 4 N/O 240 V AC 3 DTC4040240L
63 A 4 N/O 240 V AC 3 DTC6340240L
Technical data
Type DTC20...L DTC25...L DTC40...L DTC63...L
Rated continuous current Ith 20 A 25 A 40 A 63 A
AC 1/AC 7a switching of heaters
Rated operational current Ie 20 A 25 A 40 A 63 A
Rated output kW 4 5.4 8.4 13
AC 7b
Rated operational current Ie 7A 8.5 A 15 A 25 A
Rated output kW 1.2 1.5 2.4 3.8
Switching on capacity (A)
AC 1/7a cos ø 0.8 Ue 1.05 30 37.5 60 94.5
AC 7b cos ø 0.45 Ue 1.05 160 200 320 504
Performance
AC 1/7a cos ø 0.8 Ue 1.05 20 25 40 63
AC 7b cos ø 0.45 Ue 0.17 4 5.4 8.4 13
General
Terminal capacity mm2 6 10 25 25
Control voltage range 85 - 110% x Un
Frequency 50 Hz
Rated insulation voltage 500 V
Pick up time 50 mS
Mechanical life >3x104
Electrical life >1x105
Din-T
Impulse switch 1
Din-T impulse switch
Q Standard IEC 60669-2-2
Q Visual indication of contact position
Q Manual or electrical operation
Q Terminal protection IP 20
Q 16 A 240 V AC contact rating
Function
Impulse switches are electromechanical switches used to control medium
power loads while the control itself remains low power. The device switches
between 2 stable positions each time a brief pulse is required to switch posi-
tions. The device can also be switched manually.
Coil No. of No. of
Diagram Voltage poles mods. In Cat. No. 1) Price $
12 V AC 1 1 16 A DTIS1012VAC
24 V AC 1 1 16 A DTIS1024VAC
48 V AC 1 1 16 A DTIS1048VAC
240 V AC 1 1 16 A DTIS10240VAC
12 V DC 1 1 16 A DTIS1012VDC
24 V DC 1 1 16 A DTIS1024VDC
12 V AC 2 1 16 A DTIS2012VAC
24 V AC 2 1 16 A DTIS2024VAC
48 V AC 2 1 16 A DTIS2048VAC
240 V AC 2 1 16 A DTIS20240VAC
12 V DC 2 1 16 A DTIS2012VDC
24 V DC 2 1 16 A DTIS2024VDC
12 V DC 2 1 32 A DTIS123212VDC
12 V AC 2 1 16 A DTIS1112VAC
24 V AC 2 1 16 A DTIS1124VAC
48 V AC 2 1 16 A DTIS1148VAC
240 V AC 2 1 16 A DTIS11240VAC
12 V DC 2 1 16 A DTIS1112VDC
24 V DC 2 1 16 A DTIS1124VDC
12 V DC 2 1 32 A DTIS113212VDC
Add on power contact 2)
Coil No. of No. of
Diagram Voltage poles mods. In Cat. No. 1) Price $
2 1 16 A DTIS2NO
2 1 16 A DTIS2CO
2 1 32 A DTIS132PWR
Notes: 1) When stacking in rows ensure adequate ventilation, insert spacer (DTSP)
every second device.
2
) Only suitable for 32 A DTIS.
32 A unit available - refer NHP.
Parallel
Parallel
Parallel
Parallel
2 Pole
3 Pole
2 Pole
3 Pole
4 Pole
Heating loads AC 1
ELTS ELTK
Notes: 1) For further information refer to Part A Section 1 Price List Catalogue.
2
) Supplied with 1 N/O auxiliary contact. For 1 N/C auxiliary contact
specify 01 instead of 10 when ordering.
3
) Price is for standard AC coil voltage. Specify voltage when ordering
4
) Cat. No. ELTS and ELTK use Price Schedule 'A4'
PSC Series
The PSC pluggable range consists of Class 1+2 (according to IEC 61643-11)
surge protective devices (lightning arrestor) (10/350 μs) and surge protector
(8/20 μs) with low Up (protection of downstream equipments) for single-
phase and three-phase electrical power networks.
These units are ideal for protection of service entrances and distribution panels
in areas exposed to lightning activity or externally generated heavy transients.
No. of
phasesIimp Imax Connection IN Uc Up Cat. No.
1P 12.5 kA 65 kA L-N 20 kA 275 V ≤ 1.3 kV CPTPSC1-12/230IR
2
) Uc listed above is between L-N. The Uc between N-PE is 255 V.
3
) Iimp listed above is between L-N. The Iimp between N-PE is 25 kA
4
) Iimp listed above is between L-N. The Iimp between N-PE is 50 kA.
5
) Iimp listed above is between L-N. The Iimp between N-PE is 100 kA.
Dimensions (mm)
76 18 36
45
72
45
72
90
48.7
72 155
CPTPSC412230IR CPTPSC425400IR
CPTPSC225230IR
Notes: 1) Up listed above is between L-N. The Up between N-PE is ≤1.5 kV.
2
) Uc listed above is between L-N. The Uc between N-PE is 255 V.
3
) Uc listed above is between L-N. The Uc between N-PE is 265 V.
GST not included NHP Sales 1300 NHP NHP 1 - 59
Price schedule ‘E9’ www.nhp.com.au
Valid until August 2014
Accessories
Dimensions (mm)
70 18 36
45
72
90
45
72
48.7
All PSM models 1P PSM models 1P+N PSM models
72
45
72
1
Safe-T (6-63 A) MCBs
1
Safe-T (6-63 A)
Safe-T (80-100 A)
1
Safe-T (SRCB) RCBO
1
Din-T 6, 10, 15 / Din-T DC - MCBs
1
Din-Safe – Add-on earth leakage module
1 P + N (32 & 63 A) 3 P + N (32 A) 3 P + N (63 A) 3 P (63 A)
To suit: To suit:
Din-T 6, 10, 15, Din-T DC Din-T 10H
1
Auxiliary contacts for MCBs
Pic
1
Din-T - pushbutton
Specifications
Supply voltage: 220 - 240 V 50 Hz
Contact rating: 16 A / 240 V AC 1
(resistive load)
* Other voltages available, contact NHP. TAL371 PRO
2-1
Valid until August 2014
Pole covers
Pole covers
Safe-T and Din-T
2 Q Degree of protection IP 30
Q Surface mounting
Q Colour – Black
Q Supplied complete with clip tray
Dimensions (mm)
Pole capacity H W D
1 160 30 64
3 160 80 64
Insulated loadcentres
ILC series
Optional accessories
Description Cat. No. Price $
Comb type REFER PAGE
busbars
Main switches REFER PAGE
4 x 10 mm2 ILC 4EN
Earth and neutral bar kit 2 x 16 mm2 + 8 x
10 mm2 ILC 8EN
Lead sealing bracket ILCSB
Technical data
Q Maximum load 120 amp
Q Maximum operating voltage 415 V AC
Q Degree of protection IP 43
Q Material: self-extinguishing halogen-free polystyrene
Q Colour: Base: Grey RAL 7035
Door: Clear
Dimensions (mm)
Cat. No. H W D
ILC 4S 175 90 100
ILC 8S 175 170 120
Insulated loadcentres
DIN-T – surface mount
Dimensions
Pole capacity Width (mm) Height (mm) Depth (mm)
8 185 200 94
12 256 200 97
18 363 220 97
24 269 326 97
36 306 473 102
Insulated loadcentres
DIN-T – flush mount
Dimensions
Pole capacity Description Width (mm) Height (mm) Depth (mm)
12 Base 270 211 66
12 Cover 304 246 29
18 Base 380 232 76
18 Cover 412 267 29
24 Base 270 304 76
24 Cover 305 358 29
36 Base 308 470 76
36 Cover 342 503 29
Insulated loadcentres
Din-Modula 150 series
2 DIN equipment
Q IP 40 protection rating
Q Totally insulated
Q Maximum 100 amp load
Q 150 mm centre distance between DIN rails
with 30 mm behind the mounting frame
Q The range consists of 36, 54 and 72 pole
enclosures
Q Neutral and earth bars rated at 100 amps
These enclosures have generous 150 mm wiring space between and 30
mm behind equipment rails. The removable mounting frame serves to ease
cabling and wiring greatly. Din-Modula 150 is designed for indoor use and to
accept the Din-T 6, 10, 10H and 15 MCB range, time switches, contactors and
main switches.
Technical data
Q Material: Base: Grey impact resistant polystyrene
Door: Clear polycarbonate
Q Halogen free
Ordering details
No. Pole Neutral Earth Surface
of rows cap. bar bar Cat. No. 1) Price $
2 36 1 x 18 1 x 18 DM15036
3 54 2 x 18 1 x 24 DM15054
4 72 2 x 18 1 x 36 DM15072
Optional accessories
Description Cat. No. Price $
Neutral19-36 DM150NAA
Neutral 37-54 DM150NAB
Neutral 55-72 DM150NAC
Locking device DM150LD
Coupling kit DM150JK
Dimensions (mm)
Cat. No. H W D
DM15036 450 355 142
DM15054 600 355 142
DM15072 750 355 142
Insulated loadcentres
MCE weatherproof series
Ordering details
No. Pole
of rows capacity Cat. No. Price $
1 5 MCEPCN5MFM
1 9 MCEPCN9MFM
No earth or neutral bars
Dimensions (mm)
Pole capacity H W D
5 200 116 105
9 200 190 105
Insulated loadcentres
Din-Modula weatherproof series
2 Q
Q
Q
IP 55-IK07 protection
Maximum 120 amp load
Padlocking possible
Q Door changeable left or right side
Q Totally insulated
Q Halogen free
Ordering details
No. Pole Neutral Earth
of rows cap. bar bar Cat. No. Price $
1 12 8/4 8 DMWP12
2 24 18/6 18 DMWP24
3 36 24/12 18 DMWP36
Optional accessories
Description Cat. No. Price $
Locking device DMWPLD
connection set DMWPCS
Dimensions (mm)
Pole capacity H W D
12 250 285 138
24 375 285 138
36 500 285 138
Metal loadcentres
NLC loadcentres for ‘Din-T’ MCBs
Dimensions (mm)
Pole cap. A 3) B C 3)
8 268 192 245
12 343 267 245
15 418 342 245
18 493 417 245
21 568 492 245
24 693 549 245
2
) Door has provision for lock. Lock kit ordered separately.
3
) Dimensions ‘A’ and ‘C’ increased by 50 mm when flush mounted.
With door depth = 98 mm.
4
) Accepts DSRCBH single pole RCDs.
Metal loadcentres
TLC loadcentres for ‘Safe-T’ MCBs
2 Q
Q
Q
Polyester powder coated N42 grey
Earth and neutral bars provided
Circuit schedule labels provided
Q MCB clip tray fitted
Q IP 30 (IP 40 with door)
Q Australian made
Q Commercial and light industrial applications
Ordering details
Surface
mount
Pole enclosure 2) Door 1)
cap. Cat. No. Price $ Cat. No. Price $
6 TLC6S LD6/8
12 TLC12S LD12/15
18 TLC18S LD18/21
Dimensions (mm)
Pole cap. A B C
6 268 192 245
12 418 342 245
18 568 492 245
CONCEPT
The NHP CONCEPT family range of panelboards keeps a
common and attractive appearance throughout the range.
2
CONCEPT
The economical panelboard:
The ‘CONCEPT’ panelboard is designed for those wanting a visually attractive,
economical panelboard, but also offering a robust enclosure with an excellent
range of standard features. This type of panelboard is designed to be stocked
nationally as an ‘off the shelf’ panelboard.
CONCEPT•PLUS
The multipurpose panelboard:
For those wanting an ‘off the shelf’ panelboard which offers a large range
of features and options. The CONCEPT•PLUS is a multipurpose panelboard
that offers among its many features: indoor rated panelboard with dust seal
option, six modular sizes, and accessory boxes that can be added to extend
the height or width of the panelboard. CONCEPT•PLUS panelboards are
available for either DIN or NEMA (Safe-T) MCBs.
CONCEPT•PREMIER
The premium panelboard:
The CONCEPT•PREMIER panelboard range has all the features of
CONCEPT•PLUS, but also includes important additional features, such as a
greater box depth, weatherproof rating, the option of stainless steel
enclosures, a floor mounting plinth, plus others.
CONCEPT•PREMIER panelboards are available for Safe-T, Din-T, 125 A and
250 A MCCBs or combinations thereof.
CONCEPT•TOUGH
The heavy-duty panelboard:
The CONCEPT•TOUGH panelboard range has all the features of
CONCEPT•PREMIER plus more, the CONCEPT•TOUGH has an increase in
depth, width and material thickness for extra strength. The increase in depth
allows the use of a wider range of padlock/locking facilities on isolators and
circuit breakers between the door and escutcheon. This extra depth also
allows larger accessory items to be mounted below the escutcheon such
as contactors and change-over switches. The CONCEPT•TOUGH has a vast
amount of wiring space and very generously sized glandplate entry and exit
points due to the extra width. This package is all put together in a rigid 2 mm
fully welded construction for those extra tough applications.
2
Enclosure Details & Accessory Spacing
Width 485 mm 585 mm
Depth 151 mm 185 mm
IP Rating IP 40 IP 42 1)
Material 1 mm 1.6 mm
Pole capacity 24 - 60 18 - 96
Colours available (doors) Grey & Orange Grey & Orange
Spare DIN rail - rail mounting space 12 Poles 18 Poles
Largest contactor under PB escutcheon CA 7-43 CA 7-85
Largest contactor in accessory module – CA 6-180
Main Switches, Busbars, Earth & Neutral Bars
STD Main switch rating 160 A or 250 A 160 or 250 A standard
Maximum main switch sizes available 250 A 400 A
Dual Earth & Neutral bars - -
Lock type on door (keylock) Flush Flush
Chassis type Din chassis NC - GB - CT
Common Features
Horizontal DIN rail
Knockouts for MCBs & accessories
Door reversible RHS to LHS
Door hinged independent of escutcheon
Optional Accessories & Features
Emergency lighting kits – option
Split chassis – option
Special colours – option
Rain & dust hood – –
Custom ‘modular’ assemblies – option –
Accessory / header boxes – option –
Brass or aluminium gland plates – option –
Removable gland plates – standard –
Can fit MCCBs – option –
Fault current limiter DIN fuses – option –
Flush surround kits – option
Hinged escutcheon – optional
Dust seal – optional
Floor mounting plinth – option –
Wall mounting brackets – option – –
‘3 point locking’ door – on Lge encl. )
2
– –
Stainless steel enclosure – option – –
Notes: For a more complete listing of accessory details refer to accessory pages
relating to individual panelboards.
1
) Dust seal option - IP52B.
2
) On large enclosures ≥ 1000 mm.
2
125 & 250 A MCCBs 125 & 250 A MCCBs
Enclosure Details & Accessory Spacing
Width 640 mm 800 mm
Depth 240 mm 300 mm
IP Rating IP 66 IP 66
Material 1.6 mm 2.0 mm
Pole capacity 18 - 96 18 - 96
Colours available (doors) Grey & Orange Grey & Orange
Spare DIN rail rail mounting space 18 Poles 18 Poles
Largest contactor under PB escutcheon CA 6-180 CA 6-180
Largest contactor in accessory module CA 6-420 CA 6-420
Main Switches, Busbars, Earth & Neutral Bars
STD Main switch rating 160 or 250 A standard –
Maximum main switch sizes available < 800 A < 800 A
Dual Earth & Neutral bars
Lock type on door (keylock) T-handle, flush Chrome plated
(series 2) LHandle
Chassis type CD-NC-GB-XA-XB CD-NC-GB-XA-XB
Common Features
Horizontal DIN rail
Knockouts for MCBs & accessories
Door reversible RHS to LHS –
Door hinged independent of escutcheon
Optional Accessories & Features
Emergency lighting kits – option
Split chassis – option
Special colours – option
Rain & dust hood
Custom ‘modular’ assemblies – option
Accessory / header boxes – option accessory only
Brass or aluminium gland plates – option
Removable gland plates – standard
Can fit MCCBs – option
Fault current limiter DIN fuses – option
Flush surround kits – option –
Hinged escutcheon standard standard
Dust seal standard standard
Floor mounting plinth – option
Wall mounting brackets – option standard
‘3 point locking’ door – on Lge encl. )
1
Stainless steel enclosure – option
Notes: For a more complete listing of accessory details refer to accessory pages
relating to individual panelboards.
1
) On large enclosures ≥ 1000 mm.
CONCEPT
The economical panelboard for Din-T MCBs
The c
Q Standard AS/NZS 3439-3 onc
econ ept
o
Q Type tested busbar system pane my
2
lboard
Q Compact 160 A or 250 A main switch
Q Door fitted independent of escutcheon
Q Left or right hand door hinging
Q Lockable door
Q Australian made
Q Commercial and industrial applications
Application
The Concept range is an economical panelboard designed for the commercial
and light industrial sectors. It will accept Din-T circuit breakers and associated
accessory devices.
Features
Q Two-tone colour scheme, make a colour change by simply changing the
door colour.
Q The door is field changeable from right to left hinged and is totally
independent of the escutcheon.
Q Gloss white escutcheon has been dished to allow a wide range of
accessories to fit under the door.
Q Knockouts provided in the escutcheon for up to 12 modules of extra
standard DIN rail equipment.
Q Compact main switch with a 160 A or 250 A rating.
Q Earth and neutral bars, circuit identification and schedule cards supplied.
Technical data
Material type: 1 mm steel
Finish: Polyester powder coated
Colour (AS 2700-1995): Base – charcoal gloss
Door – N42 storm grey or X15 orange
Escutcheon – bright white gloss
Protection degree: IP 30 without door
IP 40 with door, IP42 with rain hood
Busbar ratings: 250 A
20 kA for 0.2 seconds
Main Switch: 160 A 3 pole 415 V AC top mount
250 A 3 pole 415 V AC top mount
CONCEPT
The economical panelboard for Din-T MCBs
CONCEPT
Surface mount panelboard with grey door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Box
switch cap. size Height (mm) Cat. No. Price $
24 1 700 CON 24 M160 G
36 2 800 CON 36 M160 G
160 A
48 3 900 CON 48 M160 G
60 4 1000 CON 60 M160 G
24 1 700 CON 24 M250 G
36 2 800 CON 36 M250 G
250 A
48 3 900 CON 48 M250 G
60 4 1000 CON 60 M250 G
CONCEPT
The economical panelboard for Din-T MCBs
Accessories
Description Cat. No. Price $
CONCEPT%PLUS
Multi-purpose panelboards
for Din-T or Safe-T MCBs
Q Standard AS/NZS 3439-3
Q IP 42
Q
Q
Q
6 modular sizes up to 96 poles
Accessory module
Type tested busbar chassis system
2
Q Compact 250 A main switch
Q Generous wiring room
Q Removable gland plates
Q Door fitted independent of escutcheon
Q Flush door handle
Q Left or right hand door hinging
Q Commercial and industrial applications
Application
The Concept Plus range of panelboards provide a unique enclosure system for
the NHP range of Din-T and Safe-T MCBs and associated accessory devices.
Features
Q Two-tone colour scheme, make a colour change simply by changing the
door colour
Q The door is field changeable from right to left hinged and is totally
independent of the escutcheon
Q Gloss white escutcheon has been dished to allow a wide range of
accessories to fit under the door
Q Knockouts provided in the escutcheon for up to 18 modules of standard
DIN rail equipment
Q Removable gland plates aid on-site installation of cables
Q New compact main switch with a fully enclosed rating of 160 A and 250 A
Q Earth and neutral bars, circuit identification and schedule cards supplied
standard
Technical data
Material type: 1.6 mm steel, polyester powder coated
Colour (AS 2700-1995): Base - Charcoal gloss
Door - N42 Storm grey or X15 orange
Escutcheon - bright white
Protection degree: IP 42 - with door (Dust seal option)
Busbar ratings: SafeT - 250 A CT (355 A option)
Din-T - 250 A NC (400 A option)
Din-T - 250 A Grizz-Bar
Main switch (options): Safe-T 100 A Non-auto (chassis mount CST)
Din-T M/S 100 A (chassis mount CDT)
160 A 3 pole 415 V AC (top mount)
250 A 3 pole 415 V AC (top mount)
200 A MCCB (top mount)
Neutral and earth bars: 2 x 8 mm studs; tunnel terminals with 2 screws
10 kA 1 second.
CONCEPT%PLUS 2
Multi-purpose panelboards
for Din-T MCBs
CONCEPT•PLUS 2
Din-T – Surface mount with grey door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Box Height
switch capacity size (mm) Cat. No. Price $
18 1 700 CDT 18G2
24 1 700 CDT 24G2
36 2 900 CDT 36G2
– 48 2 900 CDT 48G2
60 3 1100 CDT 60G2
72 4 1300 CDT 72G2
84 4 1300 CDT 84G2
96 5 1500 CDT 96G2
18 1 700 CDT 18M160G2
24 1 700 CDT 24M160G2
160 A 36 2 900 CDT 36M160G2
48 2 900 CDT 48M160G2
60 3 1100 CDT 60M160G2
18 1 700 CDT 18M250G2 1)
24 1 700 CDT 24M250G2 1)
36 2 900 CDT 36M250G2
48 2 900 CDT 48M250G2
250 A
60 3 1100 CDT 60M250G2
72 4 1300 CDT 72M250G2
84 4 1300 CDT 84M250G2
96 5 1500 CDT 96M250G2
CONCEPT%PLUS 2
Multi-purpose panelboards
for Din-T MCBs
CONCEPT•PLUS 2
Din-T – Surface mount with orange door
Suits Din-T MCBs (DIN) refer to section one
Main Box Height
switch Pole cap. size (mm) Cat. No. Price $
18 1 700 CDT 18O2
24 1 700 CDT 24O2 2)
36 2 900 CDT 36O2 2)
– 48 2 900 CDT 48O2 2)
60 3 1100 CDT 60O2 2)
72 4 1300 CDT 72O2
84 4 1300 CDT 84O2
96 5 1500 CDT 96O2
18 1 700 CDT 18M160O2
24 1 700 CDT 24M160O2 2)
160 A 36 2 900 CDT 36M160O2 2)
48 2 900 CDT 48M160O2
60 3 1100 CDT 60M160O2 1)
18 1 700 CDT 18M250O2 1)
24 1 700 CDT 24M250O2 1)2)
36 2 900 CDT 36M250O2 2)
48 2 900 CDT 48M250O2 2)
250 A
60 3 1100 CDT 60M250O2 2)
72 4 1300 CDT 72M250O2 2)
84 4 1300 CDT 84M250O2 2)
96 5 1500 CDT 96M250O2 1)2)
CONCEPT%PLUS 2
Multi-purpose panelboards
for Din-T MCBs
NEW
2
Extra row
horizontal
DIN Rail
24 Poles
CONCEPT•PLUS 2
Din-T – Surface mount with grey door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Box Height
switch capacity size (mm) Cat. No. Price $
18 1 700 CDTE18G2
36 2 900 CDTE36G2
–
48 3 1100 CDTE48G2
72 4 1300 CDTE72G2
96 5 1500 CDTE96G2
18 1 700 CDTE18M160G2
36 2 900 CDTE36M160G2
160 A 48 3 1100 CDTE48M160G2
72 4 1300 CDTE72M160G2
96 5 1500 CDTE96M160G2
18 1 700 CDTE18M250G2
36 2 900 CDTE36M250G2
250 A 48 3 1100 CDTE48M250G2
72 4 1300 CDTE72M250G2
96 5 1500 CDTE96M250G2
CONCEPT%PLUS 2
Multi-purpose panelboards
for Din-T MCBs
NEW
2
Extra row
horizontal
DIN Rail
24 Poles
CONCEPT•PLUS 2
Din-T – Surface mount with orange door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Box Height
switch capacity size (mm) Cat. No. Price $
18 1 700 CDTE18O2
36 2 900 CDTE36O2
– 48 3 1100 CDTE48O2
72 4 1300 CDTE72O2
96 5 1500 CDTE96O2
18 1 700 CDTE18M160O2
36 2 900 CDTE36M160O2
160 A 48 3 1100 CDTE48M160O2
72 4 1300 CDTE72M160O2
96 5 1500 CDTE96M160O2
18 1 700 CDTE18M250O2
36 2 900 CDTE36M250O2
250 A 48 3 1100 CDTE48M250O2
72 4 1300 CDTE72M250O2
96 5 1500 CDTE96M250O2
CONCEPT%PLUS 2
Multi-purpose panelboards
for Din-T MCBs
CONCEPT•PLUS 2
MCC
Din-T – Surface mount with grey door
NEW B
NC BUSBAR CHASSIS
Enclosed busbar distribution
system for Din-T, MCBs and RCBOs.
POWER PROTECTION
CONCEPT%PLUS 2
Multi-purpose panelboards
for Din-T
T MCBs C/W isolation chassis
sis
NEW
ar
Grizz-B
2 Isolati
on
chassis
CONCEPT•PLUS 2
Din-T – Surface mount with
th grey door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Box Height
switch capacity size (mm) Cat. No. Price $
24 1 700 CDG 24G2
36 2 900 CDG 36G2
48 2 900 CDG 48G2
– 60 3 1100 CDG 60G2
72 4 1300 CDG 72G2
84 4 1300 CDG 84G2
96 5 1500 CDG 96G2
24 1 700 CDG 24M160G2 1)
36 2 900 CDG 36M160G2 1)
160 A
48 2 900 CDG 48M160G2 1)
60 3 1100 CDG 60M160G2 1)
24 1 700 CDG 24M250G2 1)
36 2 900 CDG 36M250G2 1)
48 2 900 CDG 48M250G2 1)
250 A 60 3 1100 CDG 60M250G2 1)
72 4 1300 CDG 72M250G2 1)
84 4 1300 CDG 84M250G2 1)
96 5 1500 CDG 96M250G2 1)
CONCEPT%PLUS 2
Multi-purpose panelboards
for Din-T
T MCBs C/W isolation chassis
is
CONCEPT•PLUS 2
Din-T – Surface mount with
th orange door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Box Height
switch capacity size (mm) Cat. No. 2) Price $
24 1 700 CDG 24O2
36 2 900 CDG 36O2
48 2 900 CDG 48O2
– 60 3 1100 CDG 60O2
72 4 1300 CDG 72O2
84 4 1300 CDG 84O2
96 5 1500 CDG 96O2
24 1 700 CDG 24M160O2 1)
36 2 900 CDG 36M160O2 1)
160 A
48 2 900 CDG 48M160O2 1)
60 3 1100 CDG 60M160O2 1)
24 1 700 CDG 24M250O2 1)
36 2 900 CDG 36M250O2 1)
48 2 900 CDG 48M250O2 1)
250 A 60 3 1100 CDG 60M250O2 1)
72 4 1300 CDG 72M250O2 1)
84 4 1300 CDG 84M250O2 1)
96 5 1500 CDG 96M250O2 1)
CONCEPT%PLUS 2
Energy metering panelboards
for Din-T MCBs NEW
DESI
Q Standard AS/NZS 3439-3 GN
Q Dual metering, separate light and power
2 (Greenstar V3.0)
Q kWh, kvarh
Q RS 485 Comms or pulsed output
Q EM21 72R Energy meter
Q Retro fit kits available
Q IP 42 Impr
ove
Q Commercial and industrial applications y
NABour
GREE ERS,
N
ratinSTAR
g
Application
The Concept•Plus energy metering range of panelboards have been designed
to meet the energy metering requirements of today’s market.
CONCEPT•PLUS
160 A Energy metering panelboards with grey door
CT connect meters rated 150 A for light circuits and 150 A for power circuits
Pole Box Light Power Main
capacity size poles poles switch Cat. No. Price $
36 1100 mm12 24 160 A CDM36M160G2
48 1300 mm18 30 160 A CDM48M160G2
60 1300 mm18 42 160 A CDM60M160G2
CONCEPT•PLUS
250 A Energy metering panelboards with grey door
CT connect meters rated 150 A for light circuits and 250 A for power
circuits
Pole Box Light Power Main
capacity size poles poles switch Cat. No. Price $
60 1300 mm18 42 250 A CDM60M250G2
72 1500 mm24 48 250 A CDM72M250G2
84 1500 mm30 54 250 A CDM84M250G2
96 1700 mm36 60 250 A CDM96M250G2
CONCEPT•PLUS
Retro fit energy metering kits with grey door
Main Power
switch Box size Light poles Cat. No. 1) Price $
- 400 mm - 250 A CDMRFG
250 A 600 mm - 250 A CDMRFSM250AG6
250 A 600 mm 125 A 250 A CDMRFDM250AG6
Width = 585 mm, depth = 185 mm, includes (door = 20 mm)
Notes: 1) Delete M160 and M250 if no main switch is required. Replace G with O
for Orange door.
For other combinations or options refer to NHP.
Metering boards are not suitable for utility metering.
CONCEPT%PLUS
Multi-purpose panelboards
for Safe-T MCBs
CONCEPT•PLUS
Safe-T – Surface mount with grey door
Suits Safe-T-MCBs (NEMA) refer section one
No
Main Box Height M/S
switch Pole cap. size (mm) Cat. No. Price $
24 1 700 CST 24G
36 2 900 CST 36G
48 3 1100 CST 48G
–
60 4 1300 CST 60G
72 5 1500 CST 72G
96 6 1700 CST 96G
24 1 700 CST 24M160G 1)
36 2 900 CST 36M160G 1)
160 A
48 3 1100 CST 48M160G 1)
60 4 1300 CST 60M160G 1)
24 1 700 CST 24M250G 1)
36 2 900 CST 36M250G 1)
48 3 1100 CST 48M250G 1)
250 A
60 4 1300 CST 60M250G 1)
72 5 1500 CST 72M250G 1)
96 6 1700 CST 96M250G 1)
CONCEPT%PLUS
Multi-purpose panelboards
for Safe-T MCBs
CONCEPT•PLUS
Safe-T – Surface mount with orange door
Suits Safe-T-MCBs (NEMA) refer section one
No
Main Box Height M/S
switch Pole cap. size (mm) Cat. No. Price $
24 1 700 CST 24O
36 2 900 CST 36O
– 60 4 1300 CST 60O
72 5 1500 CST 72O
96 6 1700 CST 96O
24 1 700 CST 24M160O 1)
160 A 36 2 900 CST 36M160O 1)
60 4 1300 CST 60M160O 1)
24 1 700 CST 24M250O 1)
36 2 900 CST 36M250O 1)
250 A 60 4 1300 CST 60M250O 1)
72 5 1500 CST 72M250O 1)
96 6 1700 CST 96M250O 1)
CONCEPT%PLUS 2
Multi-purpose panelboards accessory modules
CONCEPT•PLUS 2 (Series 2)
Accessory modules with grey door 1)
Box
size
0
Height
(mm)
400
Pole cap
24 (1 row 24 way)
Cat. No. with
escutcheon
CPACC24G2
Price $ 2
0 400 48 (2 row 24 way) CPACC48G2
H 600 72 (3 row 24 way) CPACC72G2
Box Height Cat. No. without
size (mm) escutcheon 2) Price $
0 400 CPACCSOG2
H 600 CPACCSHG2
Cat. No.
Box with blank
size Height (mm) escutcheon 2) Price $
0 400 CPACCSOGE2
H 600 CPACCSHGE2
1 700 CPACCS1GE2
2 900 CPACCS2GE2
3 1100 CPACCS3GE2
4 1300 CPACCS4GE2
5 1500 CPACCS5GE2
6 1700 CPACCS6GE2
Width = 585 mm, Depth = 185 mm includes door. (Door = 20 mm)
Height (mm) Cat. No. Price $
94 mm CPBGTS1
194 mm CPBGTS2
294 mm CPBGTS3
494 mm CPBGTSH
594 mm CPBGTS4
994 mm CPBGTS6
Gear trays for Concept Plus must be 100 mm shorter than enclosure size.
Earth and neutral bar kit to suit accessory module
No. of ways Cat. No. Price $
24 CEN24
36 CEN36
48 CEN48
60 CEN60
72 CEN72
84 CEN84
96 CEN96
Includes 2 bars mounting supports and fasteners.
Notes: 1) For orange enclosure replace G with O e.g. CPACC24G2 with CPACC24O2
2
) Gear tray not included.
CONCEPT%PLUS
Multi-purpose panelboards options and accessories
Notes: 1) Kits include control switch, timer, 24A 4P N/C contactor, labels and wiring
digram to AS2293.1
2
) Can be field fitted utilising horizontal DIN knockouts at top of board.
3
) Safety service enclosure mechanically seperates MCB from remainder of
switchboard.
CONCEPT%PLUS
Multi-purpose panelboards options and accessories
Notes: 1) MCCB mounts through top horizontal escutcheon slot and connects
directly to chasssis with spacers, move chassis down 1 pole space to fit.
2
) MCCB mounts through top horizontal escutcheon slot and connects to
chasssis with busbar, move chassis down 7 pole spaces to fit. 108mm
spacing from centre of chassis and MCCB connection points.
CONCEPT%PLUS
Multi-purpose panelboards options and accessories
2
CPESC
Floor mount Plinth (100mm Height) 2) CPPLINTH
80A- CD or NC
DINTMS803
Main Switch- chassis
Chassis mount Isolator 100A- NC chassis DINTMS1003
100A- CT chassis SAFET63100NA
125A 3Pole DINT10H3125C
Feeder MCB/ MCCB
160A 3 Pole S160NJ3160
Other main switches refer to NHP REFER NHP
Flush surround kit (supplied loose) 45mm width
Size 1 CPBFK1
Size 2 CPBFK2
Size 3 CPBFK3
Size 4 CPBFK4
Size 5 CPBFK5
Size 6 CPBFK6
White liners (QTY 2 required per enclosure)
Size H CPWILH2
Size 0 CPWIL02
Size 1 CPWIL12
Convert interior of board Size 2 CPWIL22
without having to respray Size 3 CPWIL32
Size 4 CPWIL42
Size 5 CPWIL52
Size 6 CPWIL62
Notes: 1) QTY 1 required for size 1-4 enclosure, QTY 2 required for size 5-6
enclosure.
2
) Plinth is design for bottom cable entry, if panelboard is free standing
additional support is required.
CONCEPT%PLUS
Multi-purpose panelboards options and accessories
CONCEPT•PREMIER
Suits Din-T and Safe-T MCBs, E125, S125 and S160,
S250 MCCBs
Q Standard AS/NZS 3439-3
Q IP 66 rated enclosure IP 66
2 Q
Q
Q
1.6 mm fully welded construction
316 Stainless steel option
7 modular sizes 600 mm to 2000 mm
Q Very generous amount of wiring room
Q Accesssory module
Q Type tested busbar/chassis system
Q Removable gland plates (with gaskets)
Q 3 point door locking on sizes 1000 mm and above
Q T handle door lock
Q Flush handle door lock (series 2)
Q Australian made
Q Commercial, industrial and heavy industrial applications
Application
The CONCEPT•PREMIER range of Panelboards provides a unique enclosure
system for NHP Din-T and Safe-T MCBs and E125, S125 and S160, S250 MCCBs.
Features
Q Two-tone colour scheme, make a colour change by simply changing the
door colour
Q The door is field changeable from right to left hinged and is totally
independent of the escutcheon
Q Gloss white hinged escutcheon has been dished to allow a wide range of
accessories to fit under the door
Q D handles fitted to the lift-off escutcheon to allow easy fitting and removal
Q Knockouts provided in the escutcheon for up to 18 modules of standard
DIN rail equipment (Din-T & Safe-T Panelboards only)
Q Removable gland plates aid on-site installation of cable and trunking
systems
Q Compact main switch with a fully enclosed rating of 160 A and 250 A
(Din-T and Safe-T Panelboards only)
Q Mount up to a CA 6-170 contactor behind the escutcheon or a CA 6-420 in
an accessory module wihout an escutcheon
Q Dual earth and neutral bars, circuit identification and schedule cards
supplied standard
Q 30 % Larger gland plate opening in series 2
s2
serie 3
New Mid 201
a b le ndle
Avail door ha
Flush Chassis
NC r
large
30 % plate
n d
Gla ing
open
CONCEPT•PREMIER
Suits Din-T and Safe-T MCBs, E125, S125 and S160,
S250 MCCBs
Technical data
Material type: 1.6 mm steel, polyester powder coated
Colour
1.6 mm 316 Stainless steel option
Base – Charcoal gloss
2
(AS 2700-1995): Door – N42 Storm Grey or X15 Orange (other colours refer
NHP)
Escutcheon – Bright white gloss
Protection degree: IP 30 – without door
IP 66 – with door
Busbar ratings: SafeT - 250 A CT (355 A option)
Din-T - 250 A CD (355 A option)
Din-T - 250 A NC (400 A option)
Din-T - 250 A GB
S125 MCCB - 630 A XA (800 A option)
Main Switch Safe-T 100 A non-auto (chassis mount Safe-T)
(options): Din-T M/S 80/100 A (chassis mount Din-T)
160 A, 250 A, 400 A, 630 A, & 800 A 3 pole 415 V AC
Neutral and (top mount)
earth bars: Din-T & Safe-T Panelboards - (dual bars) 2 x 8 mm studs &
2 screw tunnel terminals (16 mm)
MCCBs Panelboards - 2 x 10 mm studs, 8 x 8 mm studs & 1
screw tunnel terminals (35 mm)
CONCEPT•PREMIER
The premium panelboard suits Din-T MCBs
CONCEPT•PREMIER
Din-T – Surface mount with grey door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
18 1 800 CPD 18G
24 1 800 CPD 24G
36 2 1000 CPD 36G
48 2 1000 CPD 48G
–
60 3 1200 CPD 60G
72 4 1400 CPD 72G
84 4 1400 CPD 84G
96 5 1600 CPD 96G
18 1 800 CPD 18M160G 1)
24 1 800 CPD 24M160G
160 A 36 2 1000 CPD 36M160G 1)
48 2 1000 CPD 48M160G 1)
60 3 1200 CPD 60M160G 1)
18 1 800 CPD 18M250G 1)
24 1 800 CPD 24M250G 1)
36 2 1000 CPD 36M250G 1)
48 2 1000 CPD 48M250G
250 A
60 3 1200 CPD 60M250G 1)
72 4 1400 CPD 72M250G 1)
84 4 1400 CPD 84M250G 1)
96 5 1600 CPD 96M250G 1)
Width = 640 mm, Depth = 240 mm includes door. (Door = 20 mm)
Notes: 1) Main switches are supplied loose. i.e. CPD 24 M250 G = CPD 24G +
CDT250MS.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER
The premium panelboard suits Din-T MCBs
CONCEPT•PREMIER
Din-T – Surface mount with orange door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. 2) Price $
18 1 800 CPD 18O
24 1 800 CPD 24O
36 2 1000 CPD 36O
48 2 1000 CPD 48O
–
60 3 1200 CPD 60O
72 4 1400 CPD 72O
84 4 1400 CPD 84O
96 5 1600 CPD 96O
18 1 800 CPD 18M160O 1)
24 1 800 CPD 24M160O 1)
160 A 36 2 1000 CPD 36M160O 1)
48 2 1000 CPD 48M160O 1)
60 3 1200 CPD 60M160O 1)
18 1 800 CPD 18M250O 1)
24 1 800 CPD 24M250O 1)
36 2 1000 CPD 36M250O 1)
48 2 1000 CPD 48M250O 1)
250 A
60 3 1200 CPD 60M250O 1)
72 4 1400 CPD 72M250O 1)
84 4 1400 CPD 84M250O 1)
96 5 1600 CPD 96M250O 1)
Width = 640 mm, Depth = 240 mm includes door. (Door = 20 mm)
Notes: 1) Main switches are supplied loose. i.e. CPD 24 M250 O = CPD 24O +
CDT250MS.
2
) Enclosures with orange base replace “O” with “OO” e.g. CPD36OO.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER SS
The premium panelboard suits Din-T MCBs
CONCEPT•PREMIER
Din-T – Surface mount with stainless steel door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
18 1 800 CPD 18SS
24 1 800 CPD 24SS
36 2 1000 CPD 36SS
48 2 1000 CPD 48SS
–
60 3 1200 CPD 60SS 2)
72 4 1400 CPD 72SS 2)
84 4 1400 CPD 84SS 2)
96 5 1600 CPD 96SS 2)
18 1 800 CPD 18M160SS 1)
24 1 800 CPD 24M160SS 1)
160 A 36 2 1000 CPD 36M160SS 1)
48 2 1000 CPD 48M160SS 1)
60 3 1200 CPD 60M160SS 1)
18 1 800 CPD 18M250SS 1)
24 1 800 CPD 24M250SS 1)
36 2 1000 CPD 36M250SS 1)
48 2 1000 CPD 48M250SS 1)
250 A
60 3 1200 CPD 60M250SS 1)
72 4 1400 CPD 72M250SS 1)
84 4 1400 CPD 84M250SS 1)
96 5 1600 CPD 96M250SS 1)
Width = 640 mm, Depth = 240 mm includes door. (Door = 20 mm)
Notes: 1) Main switches are supplied loose. i.e. CPD 24 M250 SS = CPD 24SS +
CDT250MS.
2
) Made to order.
- Stainless steel panelboards are fully assembled from stocked components.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER
The premium panelboard suits Din-T MCBs
C/W
W isolation chassis
chas
NEW
2
ar
Grizz-B
on
Isolati
chassis
CONCEPT•PREMIER
Din-T – Surface mount with grey
rey door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. 3) Price $
24 1 800 CPG 24G 2)
36 2 1000 CPG 36G 2)
48 2 1000 CPG 48G 2)
– 60 3 1200 CPG 60G 2)
72 4 1400 CPG 72G 2)
84 4 1400 CPG 84G 2)
96 5 1600 CPG 96G 2)
24 1 800 CPG 24M160G 1)
36 2 1000 CPG 36M160G 1)
160 A
48 2 1000 CPG 48M160G 1)
60 3 1200 CPG 60M160G 1)
24 1 800 CPG 24M250G 1)
36 2 1000 CPG 36M250G 1)
48 2 1000 CPG 48M250G 1)
250 A 60 3 1200 CPG 60M250G 1)
72 4 1400 CPG 72M250G 1)
84 4 1400 CPG 84M250G 1)
96 5 1600 CPG 96M250G 1)
Notes: 1) Main switches are supplied loose. i.e. CPG 24 M250 G = CPG 24G +
EVA3250H.
2
) Made to order.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
3
) For padlock mechanism model, add LM to end of Cat. No.,
e.g. CPG 24G LM.
CONCEPT•PREMIER
The premium panelboard suits Din-T MCBs
C/W isolation chass
chassis
NEW
2
ar
Grizz-B
on
Isolati
chassis
CONCEPT•PREMIER
Din-T – Surface mount with orange
ange door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. 3) Price $
24 1 800 CPG 24O 2)
36 2 1000 CPG 36O 2)
48 2 1000 CPG 48O 2)
– 60 3 1200 CPG 60O 2)
72 4 1400 CPG 72O 2)
84 4 1400 CPG 84O 2)
96 5 1600 CPG 96O 2)
24 1 800 CPG 24M160O 1)
36 2 1000 CPG 36M160O 1)
160 A
48 2 1000 CPG 48M160O 1)
60 3 1200 CPG 60M160O 1)
24 1 800 CPG 24M250O 1)
36 2 1000 CPG 36M250O 1)
48 2 1000 CPG 48M250O 1)
250 A 60 3 1200 CPG 60M250O 1)
72 4 1400 CPG 72M250O 1)
84 4 1400 CPG 84M250O 1)
96 5 1600 CPG 96M250O 1)
Notes: 1) Main switches are supplied loose. i.e. CPG 24 M250 O = CPG 24O +
EVA3250H.
2
) Made to order.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
3
) For padlock mechanism model, add LM to end of Cat. No.,
e.g. CPG 240 LM.
CONCEPT•PREMIER
The premium panelboard suits Din-T MCBs
Made
to
order
400 A
Chassis 2
CONCEPT•PREMIER
Din-T – Surface mount with grey
rey door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
48 4 1400 CPD 48M400G
400 A 60 5 1600 CPD 60M400G
Isolator 72 5 1600 CPD 72M400G
Socomec
SLB400 84 6 1800 CPD 84M400G
96 6 1800 CPD 96M400G
48 4 1400 CPD 48M300G
300 A 60 5 1600 CPD 60M300G
Isolator 72 5 1600 CPD 72M300G
Terasaki
S400NN 84 6 1800 CPD 84M300G
96 6 1800 CPD 96M300G
48 4 1400 CPD 48MCCB300G
300 A 60 5 1600 CPD 60MCCB300G
MCCB
72 5 1600 CPD 72MCCB300G
Terasaki
S400CJ 84 6 1800 CPD 84MCCB300G
96 6 1800 CPD 96MCCB300G
CONCEPT•PREMIER 2
The premium panelboard suits Din-T MCBs
2
Series
2
sis Available
NC cha
andle mid 2013
flush h
CONCEPT•PREMIER
Din-T – Surface mount with grey door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
18 1 800 CPD 18G2
24 1 800 CPD 24G2
36 2 1000 CPD 36G2
48 2 1000 CPD 48G2
–
60 3 1200 CPD 60G2
72 4 1400 CPD 72G2
84 4 1400 CPD 84G2
96 5 1600 CPD 96G2
18 1 800 CPD 18M160G2 1)
24 1 800 CPD 24M160G2 1)
160 A 36 2 1000 CPD 36M160G2 1)
48 2 1000 CPD 48M160G2 1)
60 3 1200 CPD 60M160G2 1)
18 1 800 CPD 18M250G2 1)
24 1 800 CPD 24M250G2 1)
36 2 1000 CPD 36M250G2 1)
48 2 1000 CPD 48M250G2 1)
250 A
60 3 1200 CPD 60M250G2 1)
72 4 1400 CPD 72M250G2 1)
84 4 1400 CPD 84M250G2 1)
96 5 1600 CPD 96M250G2 1)
Width = 640 mm, Depth = 240 mm includes door. (Door = 20 mm)
Notes: 1) Main switches are supplied loose. i.e. CPD 24 M250 G = CPD 24G +
EVA3250H.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER 2
The premium panelboard suits Din-T MCBs
2
Series
2
sis Available
NC cha
andle mid 2013
flush h
CONCEPT•PREMIER
Din-T – Surface mount with orange door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
18 1 800 CPD 18O2
24 1 800 CPD 24O2
36 2 1000 CPD 36O2
48 2 1000 CPD 48O2
–
60 3 1200 CPD 60O2
72 4 1400 CPD 72O2
84 4 1400 CPD 84O2
96 5 1600 CPD 96O2
18 1 800 CPD 18M160O2 1)
24 1 800 CPD 24M160O2 1)
160 A 36 2 1000 CPD 36M160O2 1)
48 2 1000 CPD 48M160O2 1)
60 3 1200 CPD 60M160O2 1)
18 1 800 CPD 18M250O2 1)
24 1 800 CPD 24M250O2 1)
36 2 1000 CPD 36M250O2 1)
48 2 1000 CPD 48M250O2 1)
250 A
60 3 1200 CPD 60M250O2 1)
72 4 1400 CPD 72M250O2 1)
84 4 1400 CPD 84M250O2 1)
96 5 1600 CPD 96M250O2 1)
Width = 640 mm, Depth = 240 mm includes door. (Door = 20 mm)
Notes: 1) Main switches are supplied loose. i.e. CPD 24 M250 O = CPD 24O +
EVA3250H.
- Enclosures with orange base replace “O” with “OO” e.g. CPD36OO.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER 2 SS
The premium panelboard suits Din-T MCBs
2
Series
2
sis Available
NC cha
andle mid 2013
flush h
CONCEPT•PREMIER
Din-T – Surface mount with stainless steel door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
18 1 800 CPD 18SS2
24 1 800 CPD 24SS2
36 2 1000 CPD 36SS2
48 2 1000 CPD 48SS2
–
60 3 1200 CPD 60SS2 2)
72 4 1400 CPD 72SS2 2)
84 4 1400 CPD 84SS2 2)
96 5 1600 CPD 96SS2 2)
18 1 800 CPD 18M160SS2 1)
24 1 800 CPD 24M160SS2 1)
160 A 36 2 1000 CPD 36M160SS2 1)
48 2 1000 CPD 48M160SS2 1)
60 3 1200 CPD 60M160SS2 1)
18 1 800 CPD 18M250SS2 1)
24 1 800 CPD 24M250SS2 1)
36 2 1000 CPD 36M250SS2 1)
48 2 1000 CPD 48M250SS2 1)
250 A
60 3 1200 CPD 60M250SS2 1)
72 4 1400 CPD 72M250SS2 1)
84 4 1400 CPD 84M250SS2 1)
96 5 1600 CPD 96M250SS2 1)
Width = 640 mm, Depth = 240 mm includes door. (Door = 20 mm)
Notes: 1) Main switches are supplied loose. i.e. CPD 24 M250 SS2 = CPD 24SS2 +
EVA3250H.
2
) Made to order.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER 2
The premium panelboard suits Din-T MCBs
C/W isolation chassis
chassi
2
Series
2
sis Available
NC cha
andle mid 2013
flush h
CONCEPT•PREMIER
Din-T – Surface mount with grey door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
24 1 800 CPG 24G2 2)
36 2 1000 CPG 36G2 2)
48 2 1000 CPG 48G2 2)
– 60 3 1200 CPG 60G2 2)
72 4 1400 CPG 72G2 2)
84 4 1400 CPG 84G2 2)
96 5 1600 CPG 96G2 2)
24 1 800 CPG 24M160G2 1)
36 2 1000 CPG 36M160G2 1)
160 A
48 2 1000 CPG 48M160G2 1)
60 3 1200 CPG 60M160G2 1)
24 1 800 CPG 24M250G2 1)
36 2 1000 CPG 36M250G2 1)
48 2 1000 CPG 48M250G2 1)
250 A 60 3 1200 CPG 60M250G2 1)
72 4 1400 CPG 72M250G2 1)
84 4 1400 CPG 84M250G2 1)
96 5 1600 CPG 96M250G2 1)
Notes: 1) Main switches are supplied loose. i.e. CPG 24 M250 G2 = CPG 24G2 +
EVA3250H.
2
) Made to order.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER 2
The premium panelboard suits Din-T MCBs
C/W isolation chassis
2
Series
2 NC cha
sis Available
andle mid 2013
flush h
CONCEPT•PREMIER
Din-T – Surface mount with orange
range door
Suits Din-T MCBs (DIN) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
24 1 800 CPG 24O2 2)
36 2 1000 CPG 36O2 2)
48 2 1000 CPG 48O2 2)
– 60 3 1200 CPG 60O2 2)
72 4 1400 CPG 72O2 2)
84 4 1400 CPG 84O2 2)
96 5 1600 CPG 96O2 2)
24 1 800 CPG 24M160O2 1)
36 2 1000 CPG 36M160O2 1)
160 A
48 2 1000 CPG 48M160O2 1)
60 3 1200 CPG 60M160O2 1)
24 1 800 CPG 24M250O2 1)
36 2 1000 CPG 36M250O2 1)
48 2 1000 CPG 48M250O2 1)
250 A 60 3 1200 CPG 60M250O2 1)
72 4 1400 CPG 72M250O2 1)
84 4 1400 CPG 84M250O2 1)
96 5 1600 CPG 96M250O2 1)
Notes: 1) Main switches are supplied loose. i.e. CPG 24 M250 O2 = CPG 24O2 +
EVA3250H.
2
) Made to order.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER
The premium panelboard suits Safe-T MCBs
CONCEPT•PREMIER
Safe-T – Surface mount with grey door
Suits Safe-T MCBs (NEMA) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
24 1 800 CPS 24G 2)
36 2 1000 CPS 36G
48 3 1200 CPS 48G
– 60 4 1400 CPS 60G
72 5 1600 CPS 72G 2)
84 6 1800 CPS 84G 2)
96 6 1800 CPS 96G 2)
24 1 800 CPS 24M160G 1)
36 2 1000 CPS 36M160G 1)
160 A
48 3 1200 CPS 48M160G 1)
60 4 1400 CPS 60M160G 1)
24 1 800 CPS 24M250G 1)
36 2 1000 CPS 36M250G 1)
48 3 1200 CPS 48M250G 1)
250 A 60 4 1400 CPS 60M250G 1)
72 5 1600 CPS 72M250G 1)
84 6 1800 CPS 84M250G 1)
96 6 1800 CPS 96M250G 1)
Notes: 1) Main switches are supplied loose. i.e. CPS 24 M250 G = CPS 24G +
EVA3250H.
2
) Made to order.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER
The premium panelboard suits Safe-T MCBs
CONCEPT•PREMIER
Safe-T – Surface mount with orange door
Suits Safe-T MCBs (NEMA) refer to section one
Main Pole Height
Switch capacity Box size (mm) Cat. No. Price $
24 1 800 CPS 24O 2)
36 2 1000 CPS 36O 2)
48 3 1200 CPS 48O 2)
–
60 4 1400 CPS 60O 2)
72 5 1600 CPS 72O 2)
96 6 1800 CPS 96O 2)
24 1 800 CPS 24M160O 1)
36 2 1000 CPS 36M160O 1)
160 A
48 3 1200 CPS 48M160O 1)
60 4 1400 CPS 60M160O 1)
24 1 800 CPS 24M250O 1)
36 2 1000 CPS 36M250O 1)
48 3 1200 CPS 48M250O 1)
250 A
60 4 1400 CPS 60M250O 1)
72 5 1600 CPS 72M250O 1)
96 6 1800 CPS 96M250O 1)
Width = 640 mm, Depth = 240 mm includes door. (Door = 20 mm)
Notes: 1) Main switches are supplied loose. i.e. CPS 24 M250 O = CPS 24O +
EVA3250H.
2
) Made to order.
- Larger main switches and other options and accessories available.
- Refer NHP for delivery confirmation regarding types with main switches.
CONCEPT•PREMIER CPX
The premium panelboard
Suits E125, S125 MCCBs
s2
Serie nd of The
2 at e . pane MCCB
2
A d d lboa
No
Cat. handle rd
door nd
Flush larger gla
g
30 % e openin
plat
CONCEPT•PREMIER CPX
MCCB - Surface mount with grey door
Pole cap. Box size Height (mm) Cat. No. Price $
18 2 1000 CPX18G 1)
24 2 1000 CPX24G 1)
36 3 1200 CPX36G 1)
42 4 1400 CPX42G
48 4 1400 CPX48G
60 5 1600 CPX60G
72 6 1800 CPX72G
CONCEPT•PREMIER CPX
MCCB - Surface mount with orange door
Pole cap. Box size Height (mm) Cat. No. Price $
18 2 1000 CPX18O 1)
24 2 1000 CPX24O 1)
36 3 1200 CPX36O
42 4 1400 CPX42O
48 4 1400 CPX48O
60 5 1600 CPX60O
72 6 1800 CPX72O
CONCEPT•PREMIER CPX
MCCB - Surface mount stainless steel
Pole cap. Box size Height (mm) Cat. No. Price $
18 2 1000 CPX18SS
24 2 1000 CPX24SS
36 3 1200 CPX36SS
42 4 1400 CPX42SS
48 4 1400 CPX48SS
60 5 1600 CPX60SS
72 6 1800 CPX72SS
Width = 640 mm, Depth = 240 mm includes door. (Door = 20 mm)
CONCEPT•PREMIER
The premium panelboard options and accessories
Accessory modules
With
2
Box Height Pole escutcheon
size (mm) cap. Cat. No. 1) Price $
H 600 24 CPPACC24G
H 600 48 CPPACC48G
Without
Box Height escutcheon
size (mm) Cat. No. 1) 2) Price $
H 600 CPPACCG
With blank
Box Height escutcheon
size (mm) Cat. No. 1) 2) Price $
H 600 CPPACCGE
1 800 CPPACCS1GE
2 1000 CPPACCS2GE
3 1200 CPPACCS3GE
4 1400 CPPACCS4GE
5 1600 CPPACCS5GE
6 1800 CPPACCS6GE
7 2000 CPPACCS7GE
Width = 640 mm Depth = 240 mm includes door (Door = 20 mm)
Gear trays to suit Accessory Module
White mounting plate
Height (mm) Cat. No. Price $
94 CPBGTS1
194 CPBGTS2
294 CPBGTS3
494 CPBGTSH
594 CPBGTS4
994 CPBGTS6
Gear trays for Concept Premier must be 200 mm shorter than enclosure size.
Earth and neutral bar kit to suit Accessory Module
No Ways Cat. No. Price $
24 CEN24
36 CEN36
48 CEN48
60 CEN60
72 CEN72
84 CEN84
96 CEN96
Includes 2 bars, mounting supports and fasteners.
Notes: 1) Replace “G” with “O” for orange door, replace “G with “SS” for stainless
steel.
2
) Gear tray not included.
CONCEPT•PREMIER 2
The premium panelboard options Ser
ava ies 2
and accessories mid ilable
2013
Accessory modules
With
2
Box Height Pole escutcheon
size (mm) cap. Cat. No. 1) Price $
H 600 24 CPPACC24G2
H 600 48 CPPACC48G2
Without
Box Height escutcheon
size (mm) Cat. No. 1) Price $
H 600 CPPACCG2
With blank
Box Height escutcheon
size (mm) Cat. No. 1) Price $
H 600 CPPACCGE2
1 800 CPPACCS1GE2
2 1000 CPPACCS2GE2
3 1200 CPPACCS3GE2
4 1400 CPPACCS4GE2
5 1600 CPPACCS5GE2
6 1800 CPPACCS6GE2
7 2000 CPPACCS7GE2
Notes: 1) Replace “G” with “O” for orange door, replace “G with “SS”
for stainless steel.
CONCEPT•PREMIER
The premium panelboard options and accessories
2
rotary control switch CPELK1
Emergency (unwired)
lighting rotary control switch CPELK1W
kits (wired loom)
Key switch (unwired) CPELK2
Size H CPPFKH
Size 1 CPPFK1
Flush kits Size 2 CPPFK2
(supplied Size 3 CPPFK3
loose)
45 mm Size 4 CPPFK4
Flush kit width Size 5 CPPFK5
CPPFK Size 6 CPPFK6
Size 7 CPPFK7
Mild Single width CPPWC
Weather- steel Double width CPPWCD
proof cover Stainless Single width CPPWCSS
steel Double width CPPWCDSS
Weather- Mild Single width CPPPLINTHS
Floor
proof mounting steel Double width CPPPLINTHD
rainhood plinth 2) Stainless Single width CPPPLINTHSSS
(100 mm) steel Double width CPPPLINTHDSS
Wall Mild steel CPPWBMS
mounting
brackets Stainless steel CPPWB
Weather- Brass 3 mm CPPGPB
proof Gland Brass 5 mm CPPGPB5
rainhood plates Aluminium 3 mm CPPGPA
Aluminium 6 mm CPPGPA6
Size H CPPWILH
Size 1 CPPWIL1
White Size 2 CPPWIL2
liners 1) Size 3 CPPWIL3
2 required Size 4 CPPWIL4
per board Size 5 CPPWIL5
Size 6 CPPWIL6
Size 7 CPPWIL7
Gland plate Series 1 305.00003
gasket Series 2 TBA
CONCEPT•PREMIER
The premium panelboard
Options and accessories
Accessories
Description Cat. No. Price $
Top mount
main switch kit
160 A 3 pole
CPD
CPG, CPS
CPD
CDT160MS
EVA3160H
CDT250MS
2
(supplied loose) 250 A 3 pole
CPG, CPS EVA3250H
Blue cover to suit 160 A and 250 A isolator 1LS2VS
CPD CD chassis STKCD
CT chassis
Split chassis kits CPS STK250NDTH
250 A
CT chassis
CPS STK300TH
355 A
250 A MCCB to CD chassis CD250CKT2
200 A MCCB to NC chassis NCCK200CPP
(Direct)
Connection kits 250 A MCCB to NC chassis NCCK250CPP
(TAG)
400 A MCCB to NC chassis (TAG) NCCK400CPP
400 A SLB to NC chassis (TAG) NCCK4002CPP
Support bracket to mount S250 CPPBS250
Din-T DTPF
Safe-T SAFETPF
Pole Fillers
S 125 XAB2
S 250 XAB3
CL001 CPPDCL001
Door handles (T handle)
92268 CPPD92268
CD-Din-T CD250TOPC
NC-Din-T NC250TOPC
Tee-off plastic caps
GB-Din-T GBTOC
Safe-T TH250TOPC
CL001 KEYCL001
Spare Key (set of 2)
92268 KEY92268
NSW PWD E lock (series 1) CPPPWDNSW
Traffolite labelling available REFER NHP
Special paint REFER NHP
colour
PVC wiring duct REFER NHP
REFER PAGE
kWh meter –
1 - 42
IPP mounting kit CPPIP66
CONCEPT•TOUGH
The heavy-duty panelboard
Suits Din-T MCBs, E125, S125 and S160, S250 MCCBs
Q Standard AS/NZS 3439.3
Q IP 66 rated enclosure
CONCEPT•TOUGH
The heavy-duty panelboard
Suits Din-T MCBs, E125, S125 and S160, S250 MCCBs
Technical data
Material type: 2.0 mm steel, polyester powder coated
6 mm Aluminium gland plates
2.0 mm 316 Stainless steel option 2
Colour Base – Orange gloss / Charcoal gloss
(AS 2700-1995): Door – X15 Orange or N42 Storm Grey
(other colours refer NHP)
Escutcheon – Bright white gloss
Protection degree: IP 40 – without door
IP 66 – with door
Busbar ratings: Din-T Panelboards - 250 A CD chassis (355 A option)
- 250 A NC chassis (400 A option)
S 125 MCCBs Panelboard - 630 A (std), 36 kA for 1 second
- 800 A (optional)
Main switch Din-T M/S 80/100 A (chassis mount Din-T)
(options): 160 A, 250 A, 400 A, 630 A & 800 A 3 pole 415 V AC
(top mount)
Neutral and Din-T Panelboards - (dual bars) 2 x 8 mm studs & 2 screw
Earth bars: tunnel terminals (16 mm)
S 125 MCCBs Panrlboard 2 x 10 mm studs, 8 x 8 mm studs
& 1 screw tunnel terminals (35 mm) 400 A
CONCEPT•TOUGH
The heavy-duty panelboard
Suits Din-T MCBs
2
CONCEPT•TOUGH
Din-T - Surface mount orange
Pole capacity Box size Height (mm) Cat. No. 1) Price $
18 2 1000 CTD18O
24 2 1000 CTD24O
36 2 1000 CTD36O
48 2 1000 CTD48O
60 3 1500 CTD60O
72 3 1500 CTD72O
84 3 1500 CTD84O
96 3 1500 CTD96O
CONCEPT•TOUGH
Din-T - Surface mount stainless steel-orange
Pole capacity Box size Height (mm) Cat. No. 1) Price $
18 2 1000 CTD18SSO
24 2 1000 CTD24SSO
36 2 1000 CTD36SSO
48 2 1000 CTD48SSO
60 3 1500 CTD60SSO
72 3 1500 CTD72SSO
84 3 1500 CTD84SSO
96 3 1500 CTD96SSO
Delete “O” for raw stainless enclosure e.g. CTD18SS.
CONCEPT•TOUGH
Accessory modules with orange doors
Pole capacity Box size Height (mm) Cat. No. 1) Price $
0 1 500 CTACCO
24 1 500 CTACC24HO 2)
24 1 500 CTACC24O
Width = 800 mm, Depth = 300 mm includes door. (Door = 20 mm)
CONCEPT•TOUGH
The heavy-duty panelboard
Suits E125, S125 MCCBs
CONCEPT•TOUGH
MCCB - Surface mount with orange door
Main Pole Box Height
switch capacity size (mm) Cat. No. Price $
18 2 1000 CTX18O
24 2 1000 CTX24O
36 3 1500 CTX36O
–
48 3 1500 CTX48O
60 3 1500 CTX60O
72 4 2000 CTX72O
18 3 1500 CTX18M400O
24 3 1500 CTX24M400O
400 A 36 3 1500 CTX36M400O
S400CJ 48 4 2000 CTX48M400O
60 4 2000 CTX60M400O
72 4 2000 CTX72M400O
CONCEPT•TOUGH
MCCB - Surface mount stainless steel-orange
Main Pole Box Height
switch capacity size (mm) Cat. No. Price $
18 2 1000 CTX18SSO
24 2 1000 CTX24SSO
36 3 1500 CTX36SSO
–
48 3 1500 CTX48SSO
60 3 1500 CTX60SSO
72 4 2000 CTX72SSO
Width = 800 mm, Depth = 300 mm includes door. (Door = 20 mm)
Delete “O” for raw stainless steel enclosure e.g. CTX18SS.
Panelboard hardware
to suit the CONCEPT family of panelboards
with Din-T or Safe-T MCBs
Earth and neutral bars - 165 A
No. Single screw Double screw
2
tunnels Numbering Cat. No. Price $ Cat. No. Price $
18 1-18 TGPEN181S TGPEN182S
24 1-24 TGPEN241S TGPEN242S
30 1-30 - TGPEN302S
36 1-36 - TGPEN362S
42 1-42 - TGPEN422S
48 1-48 - TGPEN482S
60 1-60 - TGPEN602S
72 1-72 - TGPEN722S
84 1-84 - TGPEN842S
96 1-96 - TGPEN962S
Panelboard hardware
to suit the CONCEPT family of panelboards
with Din-T or Safe-T MCBs
2
Pole Double screw Double screw
capac- Numbering odd numbers even numbers
ity (odd/even) Cat. No. Price $ Cat. No. Price $
9 1-17 & 2-18 CPEN9ODD CPEN9EVE
18 1-35 & 2-36 CPEN18ODD CPEN18EVE
24 1-47 & 2-48 CPEN24ODD CPEN24EVE
30 1-59 & 2-60 CPEN30ODD CPEN30EVE
36 1-71 & 2-72 CPEN36ODD CPEN36EVE
48 1-95 & 2-96 CPEN48ODD CPEN48EVE
300 A bars- 2 x M10 & 2 x M8 studs and 6 x 25 mm tunnel terminals, remainder
2 screw 16 mm terminals.
(Studs suitable for 2 x 185 mm lugs and 50 mm and 70 mm lugs)
Extras
Description Cat. No. Price $
Neutral bar extension - suits 165 A E/N bars
NEB185
- connection 2 x 185 mm lugs
Neutral bar extension - 300 A - suits 165 A E/N NEB33S
Neutral bar mounting insulators (pair) TGPINS
Neutral bar insulated support (each) CPBMN
A4 Schedule card CPSCHEDULECARD
Schedule card holder (plastic) CPSCHEDULEHOLD
Touch-up paint charcoal spray can 150 g 392.00001
Touch-up paint grey spray can 150 g 392.35554
Touch-up paint orange spray can 150 g 392.35555
Touch-up paint bright white spray can 150 g 392.00002
NC Chassis
Concept Panelboard busbar chassis assemblies
for Din-T MCBs
Q Standard AS/NZS 3439-1
Q Current rating 250 A and 400 A
2 Q
Q
Q
Encapsulated busbar (no insulation coating required)
Withstand rating 250 A / 25 kA 0.1s (20 kA 0.3s)
Withstand rating 400 A / 30 kA 0.1s (25 kA 0.3s)
Q Busbar direct connect to 160 A & 250 A switch
Q Top and bottom feed standard (top feed only pictured)
Q Tee-offs 50 % capped New
Enclo
Q IP 20 (maintained when fitted with 160 A & 250 A switch) s
Busb ed
a
Q IP 20 Connection kits to 250 A MCCB Syst r
em
Q Interchangeable with CD chassis
Application
The Concept range of busbar chassis assemblies have been specifically
designed for incorporation into the Concept family of panelboards, providing
a secure mounting platform and connection system for the NHP Din-T range
of MCBs. The busbars are fully enclosed therefore not requiring an insulated
coating for electrical isolation. The new NC chassis are type tested and are
mounted on a box section steel pan, powdercoated white.
CONCEPT Din-T - 250 chassis
Suits Din-T MCBs (18 mm pole pitch)
Pole Cut-out Pan height 250 A
capacity length (mm) (mm) 2) Cat. No. 1) Price $
12 111 134 NC212/183U
18 165 188 NC218/183U
24 219 242 NC224/183U
30 273 296 NC230/183U
36 327 350 NC236/183U
42 381 404 NC242/183U
48 435 458 NC248/183U
54 489 512 NC254/183U
60 543 566 NC260/183U
72 651 674 NC272/183U
78 705 728 NC278/183U
84 759 782 NC284/183U
96 867 890 NC296/183U
Notes: 1) For top fed chassis delete “U“ and replace with “TF“ e.g. NCTF212183TF
2
) Add 40 mm for flared busbar at top and 56 mm for bottom of chassis.
For split chassis, order special chassis or order two top fed chassis and
mount bottom chassis upside down and fit new label. See accessories for
Cat. No.
OFF (line) side of MCB connects to chassis tee-off.
Combinations other than those listed above can be special ordered refer to NHP.
NC Chassis
Concept Panelboard busbar chassis assemblies
for Din-T MCBs
CONCEPT Din-T - 400 A chassis
Suits Din-T MCBs (18 mm pole pitch)
Pole
capacity
12
Cut-out
length (mm)
111
Pan height
(mm) 2)
134
Cat. No. 1)
NC412/183U
400 A
Price $ 2
18 165 188 NC418/183U
24 219 242 NC424/183U
30 273 296 NC430/183U
36 327 350 NC436/183U
42 381 404 NC442/183U
48 435 458 NC448/183U
54 489 512 NC454/183U
60 543 566 NC460/183U
72 651 674 NC472/183U
78 705 728 NC478/183U
84 759 782 NC484/183U
96 867 890 NC496/183U
108 975 998 NC4108/183TF
Notes: 1) For top fed chassis delete “U“ and replace with “TF“ e.g. NCTF212183TF
2
) Add 40 mm for flared busbar at top and 56 mm for bottom of chassis.
For split chassis, order special chassis or order two top fed chassis and
mount bottom chassis upside down and fit new label. See accessories for
Cat. No.
OFF (line) side of MCB connects to chassis tee-off.
Combinations other than those listed above can be special ordered refer to NHP.
NC Chassis
Concept Panelboard busbar chassis assemblies
for Din-T MCBs
CONCEPT Din-T - 400 A chassis
Suits Din-T10H MCBs (27 mm pole pitch)
2 Pole capacity
6
Cut-out ‘C‘
length (mm)
84
Pan height
(mm) 2)
107
Cat. No. 1)
NCH46/273U
400 A
Price $
‘C’
47 119 47
Notes: 1) For top fed chassis delete “U“ and replace with “TF“ e.g. NC224184TF.
2
) Add 55 mm for flared busbar at top and bottom of chassis.
4 pole and other special configurations available to special order refer NHP.
OFF (line) side of MCB connects to chassis tee-off.
Combinations other than those listed above can be special ordered refer to NHP.
NC Chassis
Concept Panelboard busbar chassis assemblies
for Din-T MCBs
Accessories for NC chassis
250 A
2
Description Cat. No. Price $
Tee-off cap (18 mm tee-off) NC250TOPC
Tee-off cap (27 mm tee-off) NC250HTOPC
Busbar cap (each) NCBBC
3P back cover NCBC
4P back cover NCBC4
Label 24 pole (Red, White, Blue) NCL243
Label 24 pole (Custom-field modifiable) NCL24C
Label 18 pole (Red, White, Blue) 27 mm pitch NCH123
Connection kits
S160, E/S 250 MCCB direct connect to NC NCCK200
Chassis
S160, E/S 250 MCCB TAG connect to NC chassis NCCK250
E/S 400 MCCB TAG connect to NC chassis NCCK400
SLB 400 TAG connect to NC chassis NCCK4002
Support bracket to mount S250 NCS250GT
Support bracket 400 A chassis NCCK400 CPPBNC400GT
GB Isolation Chassis
Concept Panelboard busbar chassis assemblies
for Din-T MCBs
Q Standard AS/NZS 3439.1
Q Current rating 250 A 3P & 4P NEW
2
on
Q Tee-Off isolator (AC20) Isolati
Q Integrated and switchable 4th pole chassis
Q Padlocking option
Q Enclosed busbar
Q 1, 2, 3 & 4 pole toggle conversion kit
Q Withstand rating 250 A lcw 25 kA 0.1S and 10 kA 1.0S
Q Withstand rating 250 A Icc 63 kA- S250PE
Q Busbar direct connect 160 A & 250 A switch
Q IP 20 direct connect switch and MCCB connection kits
Q Interchangeable with NC or CD chassis
GB Isolation Chassis
Concept Panelboard busbar chassis assemblies
for Din-T MCBs
CONCEPT Din-T - 250 A chassis 4 pole
Suits Din-T 2P RCBOs (18 mm pole pitch)
Pole
Connection capacity
Cut-out ‘C’
length
(mm)
Pan
Height
(mm) 2) Cat. No. 1) Price $
2
24 218 248 GB224184TF
Top 48 434 464 GB248184TF
Feed 1) 72 650 680 GB272184TF
96 866 896 GB296184TF
24 218 248 GB224184U
Universal 48 434 464 GB248184U
Feed 72 650 680 GB272184U
96 866 896 GB296184U
Chassis colours - Red, Black, White, Black, Blue, Black
GB Isolation Chassis
Concept Panelboard busbar chassis assemblies
for Din-T MCBs
CONCEPT Din-T - 250 A chassis
Suits 1P Din-T MCBs (18 mm pole pitch)
2 Pole
Connection capacity
Cut-out ‘C’
length
mm
Pan
Height
(mm) 2) Cat. No. Price $
24 218 248 GB224181TF
Top 48 434 464 GB248181TF
Feed 1) 72 650 680 GB272181TF
96 866 896 GB296181TF
Chassis colours - Red
CD Chassis
Concept•Plus and Concept•Premier busbar
chassis assemblies for Din-T MCBs
Q Standard AS/NZS 3439.1
Q Current rating 250 A and 355 A
Q
Q
Q
Withstand rating 250 A / 20 kA for 0.2 sec (9 kA for 1 sec)
Withstand rating 355 A / 25 kA for 0.3 sec (20 kA for 1 sec)
Splayed busbar to suit 160 A & 250 A switch
2
Q Top and bottom feed
Q Tee-offs stripped and 50 % capped
Q Top power feed stripped and capped
Q Full 35 mm DIN rail, improved MCB mounting security
Q Improved insulation coating
Application
The Concept range of busbar chassis assemblies have been specifically
designed for incorporation into the Concept•Plus and Concept•Premier range
of multipurpose panelboards, providing a secure mounting platform and
connection system for the NHP Din-T range of MCBs. The busbars are fully
dipped and type tested and are mounted on a box section steel pan, powder
coated white.
Notes: 1) Add 32.5 mm for flared busbar at top and bottom of chassis.
4 pole and other special configurations available to special order refer
NHP.
‘OFF’ (line) side of MCB connects to chassis tee-off.
Use insulated tool provided to disengage DIN clip when removing
MCB from chassis. DIN clip can be removed and discarded when
mounting MCB on CD chassis.
CD Chassis
Concept•Plus and Concept•Premier busbar
chassis assemblies for Din-T MCBs
CONCEPT Din-T - 400 A chassis
Suits Din-T MCBs (18 mm pole pitch)
2 Pole
capacity
Cut-out ‘C’
length
(mm)
Pan height
(mm) 1) Cat. No.
355 A
Price $
12 110 152 CD312/183U
18 164 206 CD318/183U
24 218 260 CD324/183U
30 272 314 CD330/183U
36 326 368 CD336/183U
42 380 422 CD342/183U
48 434 476 CD348/183U
54 488 530 CD354/183U
60 542 584 CD360/183U
72 650 692 CD372/183U
78 704 746 CD378/183U
84 758 800 CD384/183U
96 866 908 CD396/183U
Accessories CD chassis
Notes: 1) Add 32.5 mm for flared busbar at top and bottom of chassis.
4 pole and other special configurations available to special order refer
NHP.
‘OFF’ (line) side of MCB connects to chassis tee-off.
Use insulated tool provided to disengage DIN clip when removing
MCB from chassis. DIN clip can be removed and discarded when
mounting MCB on CD chassis.
CT Chassis
Concept•Plus and Concept•Premier busbar
chassis assemblies for Safe-T MCBs
Q Standard AS/NZS 3439.1
Q Current rating 250 A and 355 A
Q
Q
Q
Withstand rating 250 A / 20 kA for 0.2 sec
Withstand rating 355 A / 20 kA for 1 sec
Splayed busbar to suit 160 A & 250 A switch
2
Q Top and bottom feed
Q Tee-offs stripped and 50 % capped
Q Top power feed stripped and capped
Q 25 mm pole pitch, Safe-T MCBs
Q Improved insulation coating
CT Chassis
Concept•Plus and Concept•Premier busbar
chassis assemblies for Safe-T MCBs
Cut-out ‘C’
Pole length Pan height 355 A
2
capacity (mm) (mm) 1) 2) Cat. No. Price $
12 147 221 CT 312/253
18 222 296 CT 318/253
24 297 371 CT 324/253
30 372 446 CT 330/253
36 447 521 CT 336/253
42 522 596 CT 342/253
48 597 671 CT 348/253
60 747 821 CT 360/253
72 897 971 CT 372/253
84 1047 1121 CT 384/253
96 1197 1271 CT 396/253
Accessories CT chassis
Description Cat. No. Price $
Split tariff kit 250 A (supplied loose) STK250ND/TH
Split tariff kit (supplied and fitted) REFER NHP
Plastic tee-off cap 250/355 A TH250TOPC
‘C’
52 123 52
Features
Q Compact size suited for panelboard use
Q Fuse covers are supplied standard
Q Non-captive escutcheon mounting handle
supplied standard
2
Ordering details
Description Cat. No. Price $
160 A fuse switch 3 P ISO 3160SFH
200 mm extension shaft 1) L2000KT
Technical data
Fuse switch ratings ISO 3160 SFH
Rated insulation voltage, Ui (V) 1000
Rated impulse withstand voltage, Uimp (kV) 12
Rated thermal current, Ith (A) 160
Rated operational voltage, Ue (V) 690
Rated operational current, Ie (A)
AC 21/22 415 V 160
AC 23 415 V 125
Rated fused short circuit current
Back-up fuse (A) 160
RMS value (kA) 50
Peak value (kA) 11
Rated short circuit making capacity (kA) 11
Rated breaking capacity (A) 1000
Mechanical data
Electrical endurance (no. of ops) 2000
Mechanical endurance (no. of ops) 20000
Terminals/bolt size Cu (mm2) 6-70
Maximum terminal torque (Nm) 4.5
Fuse type DIN size 00
Weight, less fuses (kg) 1.5
Modular panelboards
Incoming supply
Surge terminations
suppressor Maximum IP
option Rating
CONCEPT•PLUS:
IP 52 (option)
CONCEPT•PREMIER:
Double screw IP 66
earth and
neutral bars Hinged escutcheon
CONCEPT•PLUS:
Chassis Option
rated to CONCEPT•PREMIER:
250 A, Standard
400 A
(355 A option) Stainless Steel
Option
CONCEPT•PREMIER
Generous space
Chassis allowance for
can be cable duct.
split in the
field Dished
Removable escutcheon with
tee-off end knock-outs for
caps MCB and
accessories
Aluminium
or brass Splayed busbars Relay or Choice of door colours.
gland plate top & bottom timer option Grey or orange doors
option (Din-T) standard.
Top (Safe-T)
Maximum contactor size in panelboard CONCEPT•PLUS: Din-T or Safe-T
CONCEPT•PLUS: CA 7-85 (85 A AC 3) CONCEPT•PREMIER: Din-T, Safe-T
CONCEPT•PREMIER: CA 6-180 (170 A AC 3) 125 A or 250 A MCCBs
*The above modular panelboard represents one possible combination of enclosures and equipment.
3-1
Valid until August 2014
MCCBs
800 A 3200 A
TemBreak 2
3
Switch-Disconnectors. All internal accessories are common to all frame
sizes.
Catalogue Number construction
S 125 G J
Model Type
E - Economical C - Low breaking capacity
S - Standard N - Medium breaking
Frame capacity
H - High Rating (A) G - High breaking
L - Limiting 100 capacity
ZS - Earth 125 R - Higher breaking
leakage 160 capacity
250 P - Extra high breaking
400 capacity
630
800
1000
1250 Type
1600 F - Fixed thermal, fixed magnetic
J - Adjustable thermal, adjustable
magnetic
E - Electronic protection
N - No protection
About TemBreak 2
About TemBreak 2
3
5. Increased Thermal-Magnetic flexibility
Overload protection is adjustable
between 63 % and 100 % of the
rating.
Short-circuit protection is
adjustable on all thermal
magnetic models.
Short-circuit protection settings
are suitable for motor starting on
all models, including the compact
125 A and 250 A frames.
About TemBreak 2
About TemBreak 2
Coloured indicators display the ON or OFF status. The indicators are fully
3
covered if the breaker trips, so that black is the only visible colour.
11. Direct opening
Under the heading “Measures to minimise the
risk in the event of failure”, IEC 60204-1 Safety of
Machinery-Electrical Equipment of Machinery
includes the following recommendation:
Q “-the use of switching devices having positive
(or direct) opening operation.”
Q MCCBs, motors, auxiliaries, alarms (heavy duty)
are all direct opening
12. ZS Integral Earth Leakage MCCB
The Terasaki earth leakage MCCB is contained
within a standard 125/160/250/ 400/ 630/ 800 A
frame size.
3
Standard TemBreak 2 MCCBs 125 A - 1600 A
Permissible combinations and locations
Frame 125 160 and 400 and 800 and 1250 and
size (A) 250 630 1000 1600
3
ZS125 1) S1600
ZS250 1) ZS630 1) ZS800 1)
H125
H H160 H400 H800
H250
L125
L L160 L400 L800
L250
AUX
ALA
SHT
AUX
ALA
UVT
AUX
ALA
SHT
AUX
ALA
UVT
Notes: 1) Certain MCCB models will be stocked with the extra auxiliary option. They
are S125GJ, S160NJ (20 / 32 A) S160GJ, S250GJ. Other MCCB “EA” types are
available on indent.
ZS integral Earth leakage MCCBs only accept auxiliaries and alarms.
See table above for auxilary and alarm options.
SHT rating
AC 100 ~ 115 V
AC 200 ~ 480 V
AC 24 V
AC 48 V
DC 12 V
DC 24 V
DC 30 V
DC 48 V
DC 60 V
DC 100 ~ 115 V
DC 125
DC 200 ~ 230 V
Notes: 2 pole type is the same as the 3 pole type with the centre pole omitted.
If provided with UVT for AC, use the UVT controller.
3 12.5 – 160
32 – 160
100 – 160
36
65
125
100 – 160 200
12.5 – 250 25
160 – 250 36
160 – 250 65
16 – 250 70
160 – 250 125
16 – 250 125
160 – 250 200
252 – 400 25
160 – 400 36
160 – 400 50
100 – 400 50
160 – 400 70
100 – 400 70
100 – 400 85
100 – 400 125
252 – 400 200
252 – 630 36
252 – 630 50
252 – 630 70
Isolator switches Short time rating for 0.3 seconds Icw (kA)
125 2
160 3
250 3
400 5
630 5
Colour Key
MCCB labels are similarly colour coded via a coloured rectangle around the
catalogue number on the breaker.
Motor Circuit Range - XM High kA range - H
Economy Range - E Limitor Range - L
Standard range - S Isolators/ Non-auto - N
S125NN
S160NN
S250NN
S400NN
S630NN
3
396 - 800 50
396 - 800 65 70
252 - 800 70
250 - 800 125
250 - 800 200
400 - 1000 70
500 - 1250 85
640- 1600 85
3
Yes - S800NJ
Yes - S800RJ
- Yes S800RE
- Yes H800NE
- Yes L800NE
- Yes S1000NE
- Yes S1250GE
- Yes S1600NE
S800NN
S1000NN
S1250NN
S1600NN
3
12.5 – 125 125 85 0.63 – 100% 6 – 10 or 12M
12.5 – 125 200 150 0.63 – 100% 6 – 10 or 12M
16 – 160 25 19 Fixed Fixed
12.5 – 160 3) 36 36 0.63 – 100% 6 – 12M
32 – 160 65 36 0.63 – 100% 6 – 12M
100 – 160 125 85 0.63 – 100% 6 – 12M
100 – 160 200 150 0.63 – 100% 6 – 12M
12.5 – 250 25 19 0.63 – 100% 6 – 10 or 12M
160 – 250 36 36 0.63 – 100% 6 – 10M
160 – 250 65 36 0.63 – 100% 6 – 10M
16 – 250 70 70 – –
160 – 250 125 85 0.63 – 100% 6 – 10M
16 – 250 125 85 – –
160 – 250 200 150 0.63 – 100% 6 – 10M
252 – 400 25 25 0.63 – 100% 6 – 12M
160 – 400 36 36 0.63 – 100% 6 – 12M
160 – 400 50 50 0.63 – 100% 6 – 12M
100 – 400 50 50 – 6 – 12M
160 – 400 70 50 0.63 – 100% 6 – 12M
100 – 400 70 50 – –
160 – 400 85 85 – –
100 – 400 125 85 – –
100 – 400 200 150 – –
252 – 630 36 36 – –
252 – 630 50 50 – –
252 – 630 70 50 – –
Rated short-
Isolator Short time rating circuit making
switches for 0.3 seconds Icw(kA) capacity Icm (kA)
125 2 3.6
160 3 6
250 3 6
400 5 9
630 5 9
Notes: 1) The STD settings are not adjustable, however by selecting different
curve types,the STD setting will vary between 2.5 – 10 x IR : for 250/400 A
MCCBs and 2.5 – 8 x IR : for 630 A MCCBs.
3
) 20-32 A trip unit versions rated 30 kA.
3
– – H125NJ 165 105 103
– – L125NJ 165 105 103
– – S160NF 165 35 68
– – S160NJ 165 105 68
– – S160GJ 165 105 68
– – H160NJ 165 105 103
– – L160NJ 165 105 103
– – E250NJ 165 105 68
– – S250NJ 165 105 68
– – S250GJ 165 105 68
40 – 100% 2.5, 5, 10 / 13 or 14 S250PE 165 105 103
– – H250NJ 165 105 103
40 – 100% 2.5, 5, 10 / 13 or 14 H250NE 165 105 103
– – L250NJ 165 105 103
– – E400NJ 260 140 103
– – S400CJ 260 140 103
– – S400NJ 260 140 103
40 – 100% 2.5, 5, 10 / 13 or 14 S400NE 260 140 103
– – S400GJ 260 140 103
40 – 100% 2.5, 5, 10 / 13 or 14 S400GE 260 140 103
40 – 100% 2.5, 5, 10 / 13 or 14 S400PE 260 140 103
40 – 100% 2.5, 5, 10 / 13 or 14 H400NE 260 140 140
40 – 100% 2.5, 5, 10 / 13 or 14 L400NE 260 140 140
40 – 100% 2.5, 5, 8 / 10 or 14 E630NE 260 140 103
40 – 100% 2.5, 5, 8 / 10 or 14 S630CE 260 140 103
40 – 100% 2.5, 5, 8 / 10 or 14 260 140 103
S125NN 155 90 68
S160NN 165 105 68
S250NN 165 105 68
S400NN 260 140 103
S630NN 260 140 103
Notes: 2) The Instantaneous settings are not adjustable, however by selecting
different curve types, the INST instantaneous setting will vary from 13
or 14 x IR: for 400 A MCCBs and 10 or 14 x IR for 630 A MCCBs. Refer curve
examples & setting data in Section 9.
3
500 - 630 50 - - 6 - 10M -
396 - 800 36 36 0.63 – 100% 5 - 10M -
396 - 800 50 50 0.63 – 100% 5 - 10M -
700 - 800 50 - - 6 - 10M -
396 - 800 70 50 0.63 – 100% 5 - 10M -
252 - 800 70 50 - - 40 - 100%
250 - 800 125 94 - - 40 - 100%
250 - 800 200 150 - - 40 - 100%
400 - 1000 70 50 - - 40 - 100%
500 - 1250 85 65 - - 40 - 100%
640- 1600 85 65 - - 40 - 100%
1000-2000 85 64 - - 50 - 100%
1250-2500 85 64 - - 50 - 100%
1600-3200 85 64 - - 50 - 100%
Isolator switches
Short time rating for Rated short-circuit
0.3 seconds ICW (kA) Making capacity ICM (kA)
800 10 17
1000 10 17
1250 15 32
1600 20 45
3
- ZS630NF 273 210 103
- S800CJ 273 210 103
- S800NJ 273 210 103
- ZS800NF 273 210 103
- S800RJ 273 210 103
2.5, 5, 10 / 12 or 14 S800RE 273 210 103
2.5, 5, 10 / 12 or 14 H800NE 273 210 140
2.5, 5, 10 / 12 or 14 L800NE 273 210 140
2.5, 5, 10 / 10 or 14 S1000NE 273 210 103
2.5, 5, 10 / 12 or 14 S1250GE 370 210 120
2.5, 5, 10 / 12 or 14 S1600NE 370 210 140
LSI Adjustable XS2000NE 450 320 185
LSI Adjustable XS2500NE 450 320 185
LSI Adjustable XS3200NE 450 320 185
3
Ordering details
Optional
load side
Suit Pri- T2SW block terminal cover
MCCB type Poles mary Cat. No. Price $ Cat. No. Price $
E125, S125 3 125 A T2SW3P1251255K T2SW3P125TC
E125, S125 4 125 A T2SW4P1251255K T2SW4P125TC
H125, E/S/ 3 150 A T2SW3P2501505K T2SW3P250TC
H16/25
H125, E/S/ 3 250 A T2SW3P2502505K T2SW3P250TC
H16/25
H125, E/S/ 4 150 A T2SW4P2501505K T2SW4P250TC
H16/25
H125, E/S/ 4 250 A T2SW4P2502505K T2SW4P250TC
H16/25
E/S/H400, 3 400 A T2SW3P6304005K T2SW3P630TC
E/S630
E/S/H400, 3 600 A T2SW3P6306005K T2SW3P630TC
E/S630
E/S/H400, 4 400 A T2SW4P6304005K T2SW4P630TC
E/S630
E/S/H400, 4 600 A T2SW4P6306005K T2SW4P630TC
E/S630
Notes: 1) Voltage lugs supplied for mounting on external bars for 125 A 3 pole
block.
2
) Height excludes connection bars
3
) Refer NHP for additional dimension data
85 kA
Current rating: 0.7 – 12 A
Approvals and tests: Standards: AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity: Symmetrical amps (kA RMS)
Trip unit: Fixed hydraulic-magnetic
AC use
Voltage Icu kA
400/415 85
Ics kA
85
3
Dimensions (mm)
Poles 3
H 148
W 78
D (less toggle) 97
Weight (kg) 1.3
3 48 V AC SHT
12 V DC SHT
2H1932BBA
2H1932BDA
125 V DC SHT 2H1932BGA
200 V DC SHT (200 – 230 V) 2H1932BHA
Auxiliary AUX SW right/left hand 1C UXXB0001D
switches AUX SW right/left hand 2C UXXB0003C
Alarm switches Alarm SW right/left hand UXLB0006C
Alarm & Alarm/AUX SW right/left UXLB0008C
auxiliary switches hand 1C
External accessories - user fit
Cat. No. Price $
Solderless 3 P solderless terminals (6) TXBD0009A
terminals
IP55 Grey variable depth handle + T1HS03R5GM
357 mm shaft
T1HS escutcheon plate option: T2HSESC100
100 mm2
90 mm T pin shaft for T2HS - T2HS250SHAFT
Handle no flexi coupling
operators IP65 Grey variable depth handle +
420 mm shaft T1HP03R6BNA4
Padlock attachment for T2HP/HS T1HP30PALK
mechanism
IP55 direct mount fixed depth TFJ21PB
handle
Prosafe shot bolt lock HS handles TKNHPXX
xx code
Trapped Prosafe standard key xx code for TKNHPKEYXX
Key above
interlock Cam for T2HS handle shafts
Key codes A to Z are available. Specify 14997702
by changing the key code above.
TemPlug 3 P Templug UPX330PB 1)
Terminal Line side terminal screw cover XM30TSC
Cover
POWER PROTECTION
115&3"4",*$"1-0$,$1#
r 5ISFFUZQFT5)-$"1 5)-$"1
5)-$"1
r "MTPBWBJMBCMFGPS1PMF.$$#T
r $POTJTUTPGBGVMMZNPVMEFEGSPOUDPWFSXJUI
CVJMUJOQBEMPDLBCMFóBQ
r 0íQPTJUJPOQBEMPDLBCMFBTTUBOEBSE
r ,OPDLPVUQSPWJEFEGPS0/QPTJUJPOQBEMPDLJOH
r *OUFSOBMBDDFTTPSZñUUJOHOPUBíFDUFE
r -PDLJOHOPUQBEMPDLTJ[FEFQFOEBOU
r 4VJUTPOFMPDLVQUPNN
r "DDFQUTNVMUJQMFQBEMPDLIBTQT
r 9,"DBQUJWFMPDLTGPS.$$#TUP"BMTPBWBJMBCMF
r $BOCFñFMEñUUFE
r 4VJUT.$$#TVQUP"
r 4VJUT;4FBSUIMFBLBHF.$$#T
r "DDFQUTBDPNQSFTTJPOTFBM
/)1/)1OIQDPNBV /)1/)1OIQO[DPN
Valid until August 2014
MCCBs
25 kA
Current rating: 12.5 – 125 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Voltage Icu Ics
3 AC use
DC use
380/415 25
250 25
19
19
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
Dimensions (mm)
Poles 3
H 155
W 90
D (less toggle) 68
Toggle cut-out 104
25 kA
Current rating: 16 – 125 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Ampere 1 pole
Rating NRC Ir Im Cat. No. Price $
16 16 208 S125 NF 1 16
20 20 260 S125 NF 1 20
25 25 325 S125 NF 1 25
32 32 420 S125 NF 1 32
40 40 520 S125 NF 1 40
50 50 650 S125 NF 1 50
63 63 820 S125 NF 1 63
80 80 1040 S125 NF 1 80
100 100 1300 S125 NF 1 100
125 125 1550 S125 NF 1 125
Optional Optional
terminal covers captive lock
attachment
Notes: For Interpole Barriers, Terminal Covers and Padlock attachments refer to
accessories pages.
Ir: thermal rating
Im: magnetic rating
NRC: Nominal rated current
S125NF will not accept rear connection studs. (S160NF types do)
65 kA
Current rating: 15 – 100 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 AC use
230 85
380/415 65
85
33 Black TemBreak 2
MCCB
DC use 40 40
Accessories
Has mounting provision for any 1 (one) of the following: TemBreak 2
accessories UVT or Shunt or a combination of up to 2 Auxiliaries plus 1 Alarm.
Will accept standard TemBreak 2 external accessories such as: interpole
barriers, terminal connection options, toggle locks, and 2 pole terminal
covers.
Refer accessories pages. Will not accept motors or handles due to the 60 mm
width of the MCCB.
Ampere 2 pole
Rating NRC Ir Im Cat. No. Price $
15 15 180 S100 GF 2 15
20 20 240 S100 GF 2 20
30 30 360 S100 GF 2 30
40 40 480 S100 GF 2 40
50 50 600 S100 GF 2 50
60 60 720 S100 GF 2 60
75 75 900 S100 GF 2 75
100 100 1200 S100 GF 2 100
36 kA
Current rating: 12.5 – 125 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
65 kA
Current rating: 12.5 – 125 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 AC use
DC use
380/400 65
250 40
36
40
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
Poles 3 4
H 155 155
W 90 120
D (less toggle) 68 68
Toggle cut-out 104 104
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
20 12.5 – 20 120 – 240 S125 GJ 3 20 2)
32 20 – 32 192 – 384 S125 GJ 3 32 2)
50 32 – 50 300 – 600 S125 GJ 3 50 2)
63 40 – 63 378 – 756 S125 GJ 3 63 2)
100 63 – 100 600 – 1200 S125 GJ 3 100 2)
125 80 – 125 750 – 1250 S125 GJ 3 125 2)
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
20 12.5 – 20 120 – 240 S125 GJ 4 20 2)
32 20 – 32 192 – 384 S125 GJ 4 32 2)
50 32 – 50 300 – 600 S125 GJ 4 50 2)
63 40 – 63 378 – 756 S125 GJ 4 63 2)
100 63 – 100 600 – 1200 S125 GJ 4 100 2)
125 80 – 125 750 – 1250 S125 GJ 4 125 2)
70 kA
Current rating: 12.5 – 125 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Voltage Icu Ics
AC use
Trip unit:
690 V 70 33
125 kA
Current rating: 12.5 – 125 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 AC use
DC use
380/415 125
250 40
85
40
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
Dimensions (mm)
Poles 3 4
H 165 155
W 105 140
D (less toggle) 105 103
Toggle cut-out 104 104
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
20 12.5 – 20 120 – 240 H125 NJ 3 20
32 20 – 32 192 – 384 H125 NJ 3 32
50 32 – 50 300 – 600 H125 NJ 3 50
63 40 – 63 378 – 756 H125 NJ 3 63
100 63 – 100 600 – 1200 H125 NJ 3 100
125 80 – 125 750 – 1250 H125 NJ 3 125
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
20 12.5 – 20 120 – 240 H125 NJ 4 20
32 20 – 32 192 – 384 H125 NJ 4 32
50 32 – 50 300 – 600 H125 NJ 4 50
63 40 – 63 378 – 756 H125 NJ 4 63
100 63 – 100 600 – 1200 H125 NJ 4 100
125 80 – 125 750 – 1250 H125 NJ 4 125
200 kA
Current rating: 12.5 – 125 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
20 12.5 – 20 120 – 240 L125 NJ 3 20
32 20 – 32 192 – 384 L125 NJ 3 32
50 32 – 50 300 – 600 L125 NJ 3 50
63 40 – 63 378 – 756 L125 NJ 3 63
100 63 – 100 600 – 1200 L125 NJ 3 100
125 80 – 125 750 – 1250 L125 NJ 3 125
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
20 12.5 – 20 120 – 240 L125 NJ 4 20
32 20 – 32 192 – 384 L125 NJ 4 32
50 32 – 50 300 – 600 L125 NJ 4 50
63 40 – 63 378 – 756 L125 NJ 4 63
100 63 – 100 600 – 1200 L125 NJ 4 100
125 80 – 125 750 – 1250 L125 NJ 4 125
3
Shunt trips Internal accessories are common for MCCBs 125 A to 630 A.
All have screw terminals except those indicated below with wire
leads.
For 2, 3 and 4 pole MCCBs
110 V AC T2SH00A10TA 1)
230 – 240 V AC T2SH00A20TA 1)
SH 400 – 415 V AC T2SH00A40TA 1)
12 V DC T2SH00C01TA 1)
24 V DC (Suits 24 V AC) T2SH00D02TA 1)
48 V DC T2SH00D04TA 1)
110 V DC T2SH00D10TA 1)
230 V DC T2SH00D20TA 1)
Undervolt- Instantaneous operation
age trips 110 V AC T2UV00A10NTA
200 – 240 V AC T2UV00A20NTA
380 – 450 V AC T2UV00A40NTA
UV 24 V DC T2UV00D02NTA
110 V DC T2UV00D10NTA
230 V DC T2UV00D20NTA
Time delayed operation (500 ms) – refer NHP
Auxiiary General type (2 A @ 240 V Inductive)
& Alarm 1 C/O Auxiliary T2AX00M3STA
switches 1 C/O Auxiliary – with 0.7 m wire T2AX00M3SWA
leads
1 C/O Alarm T2AL00M3STA
1 C/O Alarm – with 0.7 m wire T2AL00M3SWA
leads
AX Heavy-duty type (4 A @ 240 V Inductive)
1 N/O Auxiliary T2AX00B1STA
AL 1 N/C Auxiliary T2AX00B2STA
1 N/O Alarm T2AL00B1STA
1 N/C Alarm T2AL00B2STA
Micro switching type (very low voltages)
1 C/O Auxiliary T2AX00M3RTA
1 C/O Alarm T2AL00M3RTA
3
110 V DC T2MC12D10NB
MC H125, L125
110 V AC T2MC25A10NB
230 – 240 V AC T2MC25A24NB
24 V DC T2MC25D02NB
48 V DC T2MC25D04NB
110 V DC T2MC25D10NB
Motor connection cable loom for electrical interlocking for
transfer switches
Motor T2MC12 cable 500 mm
125/250AF T2MM25L05A
Accessories
T2MC12 cable 1500 mm T2MM25L15A
125/250AF
Motor options: Contact NHP for key locking and auto-reset.
MCCB identification labels T12CAPLAB
Door mounted
escutcheon
plate
T2 HB Direct T2 MC Motor
mounted handle operator
3
4 pole left side section T2ML12L4A
ML MCCB identification labels T12CAPLAB
H125, L125
Common 3 or 4 pole right side T2ML25RA
section
3 pole left side section T2ML25L3A
4 pole left side section T2ML25L4A
MCCB identification labels T12CAPLAB
3 Cable
3 pole
4 pole
T2MS253LFA
T2MS254LFA
Allows an MCCB to be mounted horizontally, vertically or
interlock diagonally. Accepts Motors and handles.
Suitable for 3 or 4 pole MCCBs
E125, S125 MCCB types
Interlock kit less wire T2MW12CA 1)
MCCB identification labels T12CAPLAB
H125, L125
MW Interlock kit less wire T2MW25CA
MCCB identification labels T12CAPLAB
Wire for above interlocks T2MW00SA 2)
Wire 1.0 M
Wire 1.5 M T2MW00LA 2)
Slide interlock on
MCCBs, T2MS
T2CS Flush IP20 Cover T2CF Short terminal Single pole terminal cover
3 Terminal
and cover
A clip that provides additional terminal cover position locking also
allows a sealing device to be fitted.
locking clip All sizes 125, 250, 400, 630 AF T2CF00L
Interpole Suits MCCB types
Barriers 1) 2) E125, S125
Interpole barrier (Qty 2) T2BA123SHA
BA H125, L125
Interpole barrier (Qty 2) T2BA253LHA
Toggle locks Non Captive: Fits up to 3 padlocks or a multiple lock device
2, 3 and 4 pole E/S125 lock T2HL25B
1 pole S125NF lock UXKB0013A
Captive: Allows a single padlock or multiple padlock device
E125, S125
HL For 3/4 pole MCCBs 1 x 8 mm T2HL12CAP
hole
For 1 pole MCCBs, 1 x 8 mm hole T2HLS125NFCAP
H125, L125
Lock with one 8 mm hole T2HL25CAP
Notes: 1) Line side interpole barriers or terminal covers must be installed with
MCCBs.
2
) Interpole Barriers are supplied with MCCBs as standard; 2 barriers with 3
pole MCCBs, and 3 barriers with 4 pole MCCBs.
ProSafe key
Interlock and cam
3
4 pole kit, set of 8 studs T2RP254LA
TemPlug Suits MCCB types
TemPlug MCCB line-side
plug-in attachment
E125, S125
UP 3 pole TemPlug T2UPX3125
H125, L125
3 pole TemPlug (65 kA limit) T2UPXE3250
Templugs suit 6.3 mm busbar as standard, 10 mm types indent
OCR
sealing cover 125/250 A thermal magnetic T2SF25NTA
SF
PM Plug-in MCCBs (refer rear of section 3)
3
Adaptor E125, S125
DA Metal DIN rail adaptor T2DA12A
Door flange Provides an attractive panel cut-out surround for MCCBs or motors
Suits MCCB types
E/S/H/L125
DF MCCB IP 30 gland and gasket T2DF25A
MOTOR IP 30 gland and gasket T2DM25A
Door A kit that allows an MCCB to be mounted directly onto a door
mounting
flush plate 3 pole kit E125, S125 T2FP12S3B
FP 4 pole kit E125, S125 T2FP12S4A
Wire lead
terminal 125/250 AF left side T2TF25LGA
block
TF 125/250 AF right side T2TF25RGA
T2PF T2DF/DM
T2TF T2DA
DIN rail
Wire lead
adapter
terminal block
Notes: 1) 1 strip is 8 off, 9 mm segments. Order 2 strips for each 125 A MCCB.
25 kA
Current rating: 16 – 160 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 AC use
230
125
25
15
19
8
DC use 125 15 –
Ampere 1 pole
Rating NRC Ir Im Cat. No. Price $
16 16 160 S160 NF 1 16
20 20 200 S160 NF 1 20
25 25 250 S160 NF 1 25
32 32 320 S160 NF 1 32
40 40 400 S160 NF 1 40
50 50 500 S160 NF 1 50
63 63 630 S160 NF 1 63
80 80 800 S160 NF 1 80
100 100 1000 S160 NF 1 100
125 125 1250 S160 NF 1 125
160 160 1600 S160 NF 1 160
Optional Optional
terminal captive lock
covers attachment
Notes: For Shunt Trips, Interpole Barriers and Terminal Covers refer to accessories
pages.
Ir: thermal rating
Im: magnetic rating
NRC: Nominal rated current
S160NF will accept rear terminal studs.
30 / 36 kA
Current rating: 12.5 – 160 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
20 – 32 A: 50 – 250 A:
AC use
Voltage Icu
380/415 30
Ics
25 AC use
Voltage Icu
380/415 36
Ics
36
3
DC use 250 40 40 DC use 250 40 40
Trip unit: Adj thermal (0.63 Ir to 100 % Ir) and adj magnetic
Dimensions (mm)
Poles 3
H 165
W 105
D (less toggle) 68
Toggle cut-out 104
3 Pole
Ampere Ir 1) Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
20 12.5 – 20 120 – 240 S160 NJ 3 20 2)
32 20 – 32 192 – 384 S160 NJ 3 32 2)
50 32 – 50 300 – 600 S160 NJ 3 50
63 40 – 63 378 – 756 S160 NJ 3 63
100 63 – 100 600 – 1200 S160 NJ 3 100
125 80 – 125 750 – 1500 S160 NJ 3 125
160 100 – 160 960 – 2080 S160 NJ 3 160
Notes: 1) Adj. Ir: Adjustable thermal setting - Adj. Im: Adjustable magnetic setting
2
) To obtain MCCBs that accept additional internal auxiliary circuits add “EA”
to the above Cat. No.’s. E.g.: S125GJ3125EA.
Some types are stocked. Refer to NHP for availability. Refer page 3 - 9 for
details.
NRC: Nominal rated current
Magnetic only MCCBs are available on request.
65 kA
Current rating: 32 – 160 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 AC use
DC use
380/415 65
250 40
36
40
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
Dimensions (mm)
Poles 3 4
H 165 165
W 105 140
D (less toggle) 68 68
Toggle cut-out 104 104
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. 2) Price $
50 32 – 50 300 – 600 S160 GJ 3 50
63 40 – 63 378 – 756 S160 GJ 3 63
100 63 – 100 600 – 1200 S160 GJ 3 100
125 80 – 125 750 – 1500 S160 GJ 3 125
160 100 – 160 960 – 2080 S160 GJ 3 160 2)
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. 2) Price $
50 32 – 50 300 – 600 S160 GJ 4 50
63 40 – 63 378 – 756 S160 GJ 4 63
100 63 – 100 600 – 1200 S160 GJ 4 100
125 80 – 125 750 – 1500 S160 GJ 4 125
160 100 – 160 960 – 2080 S160 GJ 4 160 2)
125 kA
Current rating: 100 – 160 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
160 100 – 160 960 – 2080 H160 NJ 3 160
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
160 100 – 160 960 – 2080 H160 NJ 4 160
200 kA
Current rating: 100 – 160 A
Approvals and Tests: Standards AS/NZS 3947-2
and IEC 60947-2
Interrupting capacity:
3 AC use
DC use
380/415 200
250 40
150
40
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
160 100 – 160 960 – 2080 L160 NJ 3 160
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
160 100 – 160 960 – 2080 L160 NJ 4 160
25 kA
Current rating: 12.5 – 250 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
36 kA
Current rating: 160 – 250 A
Approvals and Tests: Standards AS/NZS 3947-2
and IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 380/415 36 36
DC use 250 40 40
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
(6 Im to 10 Im)
Dimensions (mm)
Poles 3 4
H 165 165
W 105 140
D (less toggle) 68 68
Toggle cut-out 104 104
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 2500 S250 NJ 3 250
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 2500 S250 NJ 4 250
65 kA
Current rating: 160 – 250 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 380/415 65 36
DC use 250 40 40
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
(6 Im to 10 Im)
Dimensions (mm)
Poles 3 4
H 165 165
W 105 140
D (less toggle) 68 68
Toggle cut-out 104 104
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. 2) Price $
250 160 – 250 1500 – 2500 S250 GJ 3 250
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. 2) Price $
250 160 – 250 1500 – 2500 S250 GJ 4 250
3
Q Electronic overcurrent protection, for general and selectivity applications
Q The number of characteristic curves will vary depending on the MCCB
type
Q Long Time, Short Time & Instantaneous trip times vary depending on the
characteristic curve selected
Q Base current Ir is adjustable from 40 % – 100 % of the nominal rated
current In.
(dial settings are via incremental steps)
OCR Options:
Q Ground fault trip on 400-1600 A models
Q Neutral pole protection for 4 pole MCCBs
Q Pre-trip alarm
Q Special curve characteristics are available Curve
Nominal Rated current characteristic Option
current multiplier selector indicator
rating selector switch switch markers
Right:
Typical OCR
adjustment
and setting
detail shown
on electronic
MCCBs
(400/630 A
shown)
70 kA
Current rating: 16 – 250 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 380/415 70 70
Overcurrent relay:
Q Electronic, for general and selectivity applications
Q 5 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40 % – 100 % of the nominal rated current
In.
OCR Options:
Q Neutral pole protection for 4 pole MCCBs only
Q Pre-trip alarm
Dimensions (mm)
Poles 3 4
H 165 165
W 105 140
D (less toggle) 103 103
Toggle cut-out 104 104
3 Pole
Ampere Adj. Ir
Rating NRC Min. – Max. Cat. No. 1) Price $
40 16 – 40 S250 PE 3 40
125 50 – 125 S250 PE 3 125
250 100 – 250 S250 PE 3 250
4 Pole
Ampere Adj. Ir
3 Rating NRC
40
125
Min. – Max.
16 – 40
50 – 125
Cat. No. 1)
S250 PE 4 40
S250 PE 4 125
Price $
Notes: 1) The STD and Instantaneous pickup current (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different Ir settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR, curve 3 Isd
= 5 x IR, curves 4 – 5 Isd = 10 x IR. IR dial setting 0.4 – 0.9 Ii = 14 x IR and IR dial
setting 0.95 – 1.0 Ii = 10 x IR. Refer curve examples and setting data in Section 9.
NRC = Nominal rated current, IR = Current adjustment dial setting,
STD = Short Time Delay, INST = instantaneous
2
) To order a MCCB with the above options insert the required option after
the pole to make up the Cat. No. E.g.: S250PE 4 APN 250 is a S250PE 4
Pole 250 A MCCB c/w Pre-trip Alarm and Neutral Protection.
125 kA
Current rating: 100 – 250 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 Pole
Ampere Adj. Ir Adj. Im 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 2500 H250 NJ 3 250
4 Pole
Ampere Adj. Ir Adj. Im 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 2500 H250 NJ 4 250
Notes: 1) The STD and Instantaneous pickup currents (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR,
curve 3 Isd = 5 x IR, curve 4 - 7 Isd = 10 x IR . IR dial setting 0.4 – 0.9 Ii = 14 x IR
and IR dial setting 0.95 – 1.0 Ii = 13 x IR. Refer curve examples & setting data
in section 9.
2
) To order a MCCB with the above options add the required amp rating to
the end of the catalogue number to complete it. Eg: S250PE 4 AN 250 is a
S250PE 4 Pole 250 A MCCB c/w Neutral Protection.
NRC = Nominal rated current, IR = Current adjustment dial setting,
STD = Short Time Delay, INST = instantaneous
For additional information on installation, options and applications refer
Section 9, Part C
125 kA
Current rating: 16 – 250 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 Pole
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. 1) Price $
40 16 - 40 H250 NE 3 40
125 50 – 125 H250 NE 3 125
250 100 – 250 H250 NE 3 250
4 Pole
3
Ampere Adj. Ir 4 pole
Rating NRC Min. – Max. Cat. No. 1) Price $
40 16 - 40 H250 NE 4 40
125 50 - 125 H250 NE 4 125
250 100 – 250 H250 NE 4 250
Dimensions (mm)
Poles 3
H 165
W 105
D (less toggle) 103 T2ED
Toggle cut-out 48
105 on chassis
Ampere Adj. Ir 3 pole 4 pole
Rating NRC Min. – Max. Cat. No. 1) Price $ Price $
40 16 - 40 H250 NE 3 40 AC
H250 NE 4 40 AC
125 50 - 125 H250 NE 3 125 AC
H250 NE 4 125 AC
250 100 - 250 H250 NE 3 250 AC
H250 NE 4 250 AC
200 kA
Current rating: 100 – 250 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 AC use
DC use
380/415 200
250 40
150
40
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
(6 Im to 10 Im)
Dimensions (mm)
Poles 3 4
H 165 165
W 105 140
D (less toggle) 103 103
Toggle cut-out 104 104
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 2500 L250 NJ 3 250
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 2500 L250 NJ 4 250
SH
12 V DC
24 V DC (Suits 24 V AC)
48 V DC
T2SH00D01TA 1)
T2SH00D02TA 1)
T2SH00D04TA 1)
3
110 V DC T2SH00D10TA 1)
230 V DC T2SH00D20TA 1)
For 1 pole S160NF MCCBs
110 V AC T2SH16A10WA
230 – 240 V AC T2SH16A20WA
24 V DC T2SH16D02WA
110 V DC T2SH16D10WA
230 V DC T2SH16D20WA
Undervoltage Instantaneous operation
trips 110 V AC T2UV00A10NTA
200 – 240 V AC T2UV00A20NTA
UV 380 – 450 V AC T2UV00A40NTA
24 V DC T2UV00D02NTA
110 V DC T2UV00D10NTA
230 V DC T2UV00D20NTA
Time delayed operation (500 ms) - refer NHP
Auxiliary & General type (2 A @ 240 V Inductive)
alarm switches 1 C/O Auxiliary T2AX00M3STA
1 C/O Auxiliary – with 0.7 m T2AX00M3SWA
wire leads
1 C/O Alarm T2AL00M3STA
1 C/O Alarm – with 0.7 m wire
AX leads T2AL00M3SWA
Heavy-duty type (4 A @ 240 V Inductive)
1 N/O Auxiliary T2AX00B1STA
AL 1 N/C Auxiliary T2AX00B2STA
1 N/O Alarm T2AL00B1STA
1 N/C Alarm T2AL00B2STA
Micro switching type (very low voltages)
1 C/O Auxiliary T2AX00M3RTA
1 C/O Alarm T2AL00M3RTA
3
110 V DC T2MC25D10NB
Motor connection cable loom for electrical interlocking
Motor T2MConly
25 cable 500 mm, 250AF T2MM25L05A
Accessories T2MC 25 cable 1500 mm, 250AF T2MM25L15A
only
Motor options: Contact NHP for key locking and auto-reset.
MCCB identification labels T25CAPLAB
T2SH
Shunt trip
T2AX
T2AL
Auxiliary &
Alarm
switches
T2MC
Motor operators
T2UV
250 A motor
Undervoltage
fitted to MCCB
trip
Cable
3 pole
4 pole
T2MS253LFA
T2MS254LFA
Allows an MCCB to be mounted horizontally, vertically or diagonally.
3
interlock Accepts Motors and handles.
Suitable for 3 or 4 pole MCCBs
S/H/L160, E/S/H/L250
Interlock kit less wire T2MW25CA 1)
MW Wire for above interlocks T2MW00SA 2)
Wire 1.0 M
Wire 1.5 M T2MW00LA 2)
MCCB identification labels T25CAPLAB
T2MW T2MS
Cable interlock Slide type
3
Short S160, E250, S250 – except S250-PE
terminal 3 pole cover set of 2, 30 mm long T2CF253SSNBA
covers
FC 4 pole cover set of 2, 30 mm long T2CF254SSNBA
CF
Standard S160, E250, S250 – except S250-PE
terminal 1 pole cover set of 2, 55 mm long T2CF161SLNG
covers FC
3 pole cover set of 2, 55 mm long T2CF253SLNG
4 pole cover set of 2, 55 mm long T2CF254SLNG
CF H/L160, S250-PE, H/L250
3 pole cover set of 2, 55 mm long T2CF253LLNG
4 pole cover set of 2, 55 mm long T2CF254LLNG
T2CF Standard term covers Single pole terminal T2CF Short terminal covers
cover
P for
Refer NH
250 A
new 160/
rs
wide cove
Interpole
Barriers 1) 2)
All sizes 125, 250, 400, 630 AF
Suits MCCB types
S160, E250, S250 – except S250-PE
T2CF00L
3
Interpole barrier (Qty 2) T2BA253SHA
BA H/L160, S250-PE, H/L250
Interpole barrier (Qty 2) T2BA253LHA
Toggle locks Non Captive: Fits up to 3 padlocks or a multiple lock device
All 250 AF MCCBs (1 - 4 pole)
Lock with 5 mm x 16.5 mm slot T2HL25B
HL Captive: Allows a single padlock or multiple padlock device
Suits 3/4 pole 250 AF MCCBs
Lock with one 8 mm holes T2HL25CAP
For 1 pole MCCBs, 1 x 8 mm hole T2HLS160NFCAP
Notes: 1) Line side interpole barriers or terminal covers must be installed with
MCCBs.
2
) Interpole Barriers are supplied with MCCBs as standard; 2 barriers with
3 pole MCCBs, and 3 barriers with 4 pole MCCBs.
T2FW Tunnel
terminals
3
TemPlug Suits MCCB types TemPlug MCCB line-side plug-in attachment
S160, E/S/250
3 pole TemPlug T2UPX3250
UP S250PE
T2UPXE3250
3 pole TemPlug
T2RP
T2UP T2SF
T2RP rear connect
T2UP Templug OCR sealing kit.
studs
Suitable for a
compression sealing
device.
Notes: 1) S160NF single pole MCCBs will accept T2RP25 rear connect studs.
3
S/H/L160, E/S/H/L250
DF MCCB IP 30 gland and gasket T2DF25A
MOTOR IP 30 gland and gasket T2DM25A
Door A kit that allows an MCCB to be mounted directly onto a door
mounting S160, E250, S250 – except for S250PE
flush plate
3 pole kit T2FP25S3B
FP 4 pole kit T2FP25S4A
Wire lead 250 AF left side T2TF25LGA
terminal
block 250 AF right sideblock T2TF25RGA
TF
T2DF/DM
Door flange
T2PF
Pole fillers
T2TF
Wire lead terminal block
25 kA
Current rating: 252 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 380/415 25 25
DC use 250 25 19
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
(6 Im to 13 Im)
Dimensions (mm)
Poles 3
H 260
W 140
D (less toggle) 103
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
400 250 – 400 2400 – 4800 E400 NJ 3 400
36 kA
Current rating: 160 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 380/415 36 36
DC use 250 40 40
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
(6 Im to 12 Im)
Dimensions (mm)
Poles 3
H 260
W 140
D (less toggle) 103
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 3000 S400 CJ 3 250
400 250 – 400 2400 – 4800 S400 CJ 3 400
50 kA
Current rating: 160 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 3000 S400 NJ 3 250
400 250 – 400 2400 – 4800 S400 NJ 3 400
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 3000 S400 NJ 4 250
400 250 – 400 2400 – 4800 S400 NJ 4 400
50 kA
Current rating: 100 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 380/415 50 50
Overcurrent relay:
Q Electronic, for general and selectivity applications
Q 7 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40 % – 100 % of the nominal rated
current In.
Q STD setting 2.5 – 10 (x Ir) ) 1
OCR Options:
Q Refer S400GE
Dimensions (mm)
Poles 3 4
H 260 260
W 140 185
D (less toggle) 103 103
3 Pole
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. Price $
250 100 – 250 S400 NE 3 250
400 160 – 400 S400 NE 3 400
4 Pole
Ampere Adj. Ir 4 pole
Rating NRC Min. – Max. Cat. No. Price $
250 100 – 250 S400 NE 4 250
400 160 – 400 S400 NE 4 400
Notes: 1
) For additional information on OCR setting and options refer section 9
or Part C catalogue.
70 kA
Current rating: 250 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 380/415 70 50
DC use 250 TBA
Trip unit: Adjustable thermal (0.63 Ir to 100 % Ir) and adjustable magnetic
(6 Im to 12 Im)
Dimensions (mm)
Poles 3 4
H 260 260
W 140 185
D (less toggle) 103 103
3 Pole
Ampere Adj. Ir 1) Adj. Im 1) 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 3000 S400 GJ 3 250
400 250 – 400 2400 – 4800 S400 GJ 3 400
4 Pole
Ampere Adj. Ir 1) Adj. Im 1) 4 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
250 160 – 250 1500 – 3000 S400 GJ 4 250
400 250 – 400 2400 – 4800 S400 GJ 4 400
70 kA
Current rating: 100 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 380/415 70 50
Overcurrent relay:
Q Electronic, for general and selectivity applications
Q 7 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40 % – 100 % of the nominal rated
current In.
Q STD setting 2.5 – 10 (x Ir) 1)
Q INST setting 13 – 14 (x Ir) 1)
OCR Options:
Q Ground fault trip (400 A OCR only)
Q Neutral pole protection for 4 pole MCCBs ONLY
Q Pre-trip alarm
Dimensions (mm)
Poles 3 4
H 260 260
W 140 185
D (less toggle) 103 103
Notes: 1) Add overcurrent relay sensor AMP rating where “+” is shown.
3 Pole
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. Price $
S400 GE 3 250
250 100 – 250
S400 GE 3 400
4 Pole
Ampere Adj. Ir 4 pole
3
Rating NRC Min. – Max. Cat. No. Price $
S400 GE 4 250
250 100 – 250
S400 GE 4 400
Notes: 1) For additional information on OCR setting and options refer section 9 or
Part C catalogue.
2
) Where a neutral is present, a 4th Neutral pole CT is required for 3 pole
GF MCCBs, and must be ordered separately using Cat. No.: T2GB40N04A.
Refer page 3 - 100.
70 kA
Current rating: 100 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Voltage Icu Ics
3
AC use 415 70 50
Dimensions (mm)
Poles 3 4
H (less attached busbar) 260 260
W 140 185
D (less toggle) 103 103 T2ED
70 kA
Current rating: 100 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Voltage Icu Ics
3
AC use 690 70 50
Dimensions (mm)
Poles 3
H (less attached busbar) 260
W 140
D (less toggle) 140
3 Pole
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. Price $
250 100 – 250 L400 PE 3 250 RC
400 252 – 400 L400 PE 3 400 RC
85 kA
Current rating: 100 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 380/415 85 85
Overcurrent relay:
Q Electronic, for general and selectivity applications
Q 7 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40 % – 100 % of the nominal rated
current In.
Q STD setting 2.5 – 10 (x Ir) )
1
OCR Options:
Q Ground fault trip (400 A OCR only)
Q Neutral pole protection for 4 pole MCCBs ONLY
Q Pre-trip alarm
Notes: 1) Add overcurrent relay sensor AMP rating where “+” is shown.
Dimensions (mm)
Poles 3 4
H 260 260
W 140 185
D (less toggle) 103 103
3 Pole
3
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. Price $
250 100 – 250 S400 PE 3 250
400 160 – 400 S400 PE 3 400
4 Pole
Ampere Adj. Ir 4 pole
Rating NRC Min. – Max. Cat. No. Price $
250 100 – 250 S400 PE 4 250
400 160 – 400 S400 PE 4 400
Notes: 1) For additional information on OCR setting and options refer section 9 or
Part C catalogue.
2
) Where a neutral is present, a 4th Neutral pole CT is required for 3 pole
GF MCCBs, and must be ordered separately using Cat. No.: T2GB40N04A.
Refer to page 3 - 100.
125 kA
Current rating: 100 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Overcurrent relay:
Q Electronic, for general and selectivity applications
Q 7 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40 % – 100 % of the nominal rated
current In.
Q STD setting 2.5 – 10 (x Ir) 1)
Q INST setting 13 – 14 (x Ir) 1)
OCR Options:
Q Ground fault trip (400 A OCR only)
Q Neutral pole protection for 4 pole MCCBs
Q Pre-trip alarm
Notes: 1) Add overcurrent relay sensor AMP rating where “+” is shown.
Dimensions (mm)
Poles 3 4
H 260 260
W 140 185
D (less toggle) 140 140
3 Pole
3
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. Price $
250 100 – 250 H400 NE 3 250
400 160 – 400 H400 NE 3 400
4 Pole
Ampere Adj. Ir 4 pole
Rating NRC Min. – Max. Cat. No. Price $
250 100 – 250 H400 NE 4 250
400 160 – 400 H400 NE 4 400
Notes: 1) For additional information on OCR setting and options refer section 9 or
Part C catalogue.
2
) Where a neutral is present, a 4th Neutral pole CT is required for 3 pole
GF MCCBs, and must be ordered separately using Cat. No.: T2GB40N04A.
Refer to page 3 - 100.
125 kA
Current rating: 100 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Voltage Icu Ics
3
AC use 415 125 85
XOW Over Current Relay:
Q Ammeter or Energy Metering types
Q Adjustable LSI setting for grading applications
Q Base current adjustable from 40% - 100% of In New
ing
MCCB Standard features:
meter
H400NE _ X1L M B
CC
Q Ammeter, Adjustable LSI
Q Trip event log, Alarm event log, Test function
H400NE _ X1S
Q Energy (multifunction) meter: A, V, P, kW, kWh, E, Pf, F, H
Q Adjustable LSI
Q Backlit LCD display
Q Ground fault, Pre trip alarm, Phase rotation & Neutral pole protection
Q Trip and Alarm event log, Test function, Trip indication contact output
Q Modbus RTU 485 communications
Q External door mounting meter option (T2ED not incl. in below pricing)
Dimensions (mm)
Poles 3 4
H (less attached busbar) 260 260
W 140 185 T2ED
D (less toggle) 103 103
Ampere Ir Adj. 3 pole 4 pole
Rating NRC Min. Max. Cat. No. Price $ Price $
250 100 250 H400 NE 3 250 X1L
MCCB H400 NE 4 250 X1L
with
ammeter 400 160 400 H400 NE 3 400 X1L
H400 NE 4 400 X1L
250 100 250 H400 NE 3 250 X1S
MCCB
with H400 NE 4 250 X1S
energy 400 160 400 H400 NE 3 400 X1S
meter
H400 NE 4 400 X1S
Notes: NRC: Nominal rated current, Ir: Current adjustment dial setting,
STD= Short Time Delay, INST = instantaneous
For additional information on installation, options and applications refer
Section 9, Part C catalogue or NHP.
3 - 82 NHP Sales 1300 NHP NHP GST not included
www.nhp.com.au
Price schedule ‘T2’
Valid until August 2014
MCCBs
200 kA
Current rating: 100 – 400 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Notes: 1) Add Over Current Relay sensor AMP rating where “+” is shown.
Dimensions (mm)
Poles 3 4
H 260 260
W 140 185
D (less toggle) 140 140
3 Pole
Ampere Adj. Ir 3 pole
3 Rating NRC
250
400
Min. – Max.
100 – 250
160 – 400
Cat. No. 1)
L400 NE 3 250
L400 NE 3 400
Price $
4 Pole
Ampere Adj. Ir 4 pole
Rating NRC Min. – Max. Cat. No. 1) Price $
250 100 – 250 L400 NE 4 250
400 160 – 400 L400 NE 4 400
Notes: 1) Add Over Current Relay sensor AMP rating where “+” is shown.
2
) For additional information on OCR setting and options refer section 9 or
Part C catalogue.
3
) Where a neutral is present, a 4th Neutral pole CT is required for 3 pole
GF MCCBs, and must be ordered separately using Cat. No.: T2GB40N04A.
Refer to page 3 - 100.
CORP-PRODUCTS-ADS-CPB
THINK PRODUCTS AND SOLUTIONS.
THINK NHP.
NHP’s Products Team is backed by years of experience
from dedicated engineers and specialists, focused on
providing Australasia’s most comprehensive product
range and project solutions.
Products Team
As well as extensive application, technical and product
knowledge, our high quality Products Teams are determined
to provide customised motor starters and controllers to
specification, by listening to you and your needs.
Together with NHP’s Service Team, NHP is able to offer
assistance with commissioning and site maintenance work.
36 kA
Current rating: 252 – 630 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3 AC use 380/415 36 36
Overcurrent relay:
Q Electronic, for general and selectivity applications
Q 6 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40 % – 100 % of the nominal rated
current In.
Q STD setting 2.5 – 8 (x Ir) ) 1
OCR Options:
Q Ground fault trip
Dimensions (mm)
Poles 3
H 260
W 140
D (less toggle) 103
3 Pole
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. Price $
630 252 – 630 E630 NE 3 630
Notes: 1) The STD and instantaneous pickup current (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different Ir settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR, curve 3
Isd = 5 x IR, curve 4 - 6 Isd = 8 x IR. IR dial setting 0.4 – 0.63 Ii = 14 x IR,
0.8 li = 12 x IR, 0.85 - 0.9 li = 12 x IR, 0.95– 1.0 Ii = 10 x IR. Refer curve
examples and setting data in Section 9.
NRC = Nominal rated current, IR = Current adjustment dial setting,
STD = Short Time Delay, INST = instantaneous
50 kA
Current rating: 252 – 630 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Dimensions (mm)
Refer page 3 - 86
3 Pole
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. Price $
630 252 – 630 S630 CE 3 630
4 Pole
Ampere Adj. Ir 4 pole
Rating NRC Min. – Max. Cat. No. Price $
630 252 – 630 S630 CE 4 630
Notes: 1) The STD and instantaneous pickup currents (Isd & Ii) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR, curve 3
Isd = 5 x IR, curve 4 - 6 Isd = 8 x IR. IR dial setting 0.4 – 0.63 Ii = 14 x IR,
0.8 li = 12 x IR, 0.85 - 0.9 li = 12 x IR, 0.95 – 1.0 Ii = 10 x IR. Refer curve
examples and setting data in Section 9.
NRC = Nominal rated current, IR = Current adjustment dial setting,
STD = Short Time Delay, INST = instantaneous
POWER PROTECTION
115&3"4",*5)4 )"/%-& $1#
115&3"4",*5)4)"/%-&$1#
r *1SBUFEQMBTUJDIBOEMF
*1 SBUFE QMBTUJD IBOEMF r 0/QBEMPDLJOHPQUJPOBM
0/ QBEMPDLJOH PQUJPOBM rr "MMIBOEMFNFDIBOJTNT
"MM IBOEMF NFDIBOJTNT
r -POH
-POHWBSJBCMFEFQUITIBGU
WBSJBCMF EFQUI TIBGU WJBPOTJUFIBOEMF
WJB PO TJUF IBOEMF BMMPX.$$#EJBMTFUUJOH
BMMPX .$$# EJBM TFUUJOH
TVQQMJFETUBOEBSE
TVQQMJFE TUBOEBSE NPEJñDBUJPO WJFXJOHBOEBDDFTT
WJFXJOH BOE BDDFTT
)FBWZEVUZNFUBMMPDLJOH
r )FBWZ EVUZ NFUBM MPDLJOH r "DDFQUTVQUPUISFF
"DDFQUT VQ UP UISFF r 'PS*1BQQMJDBUJPOT
'PS *1 BQQMJDBUJPOT
MFWFSTUBOEBSE NNMPDLTPSNVMUJMPDL 5)15)1IBOEMFTBSF
r *OUFSOBMEPPSJOUFSMPDLJOH EFWJDFT BWBJMBCMF
DPNQPOFOUTBSFBMMNFUBM r %PPSPQFOTXIFOIBOEMF r 0/JOEJDBUJPOóBHPO
r "MMIBOEMFTNPVOUJOB JTTXJUDIFEUP0'' IBOEMFNFDIBOJTN
NNIPMF QPTJUJPO r 1SPTBGFUSBQQFELFZ
r 4IPSUMFWFSIBOEMFTPO r %PPSXJMMOPUPQFOXIFO JOUFSMPDLPQUJPOT
.$$#TUP" MPOHFS IBOEMFJTQBEMPDLFE0''
UZQFT" r %PPSEFGFBUGVODUJPO
r NNPSNN TUBOEBSE
FTDVUDIFPOQMBUFTBSF r 1BEMPDLPQUJPOGPSIBOEMF
PQUJPOBM NFDIBOJTNNPVOUFEPO
r )BOEMFTBSFQBEMPDLBCMF MCCB
JOUIF0''QPTJUJPOBT r %PPSEFGFBUOPO
TUBOEBSE GVODUJPOBMXIFO
QBEMPDLFE0''
/)1/)1OIQDPNBV /)1/)1OIQO[DPN
Valid until August 2014
MCCBs
70 kA
Current rating: 252 – 630 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Overcurrent relay:
50
3
Q Electronic, for general and selectivity applications
Q 7 dial selectable characteristic curves suited for a variety of
applications
Q Base current Ir is adjustable from 40 % – 100 % of the nominal rated
current In.
Q STD setting 2.5 – 8 (x Ir) ) 1
OCR Options:
Q Ground fault trip
Q Neutral pole protection for 4 pole MCCBs ONLY
Q Pre-trip alarm
Notes: 1) The STD and instantaneous pickup currents (Isd & Ii) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR, curve 3
Isd = 5 x IR, curve 4 - 6 Isd = 8 x IR. IR dial setting 0.4 – 0.63 Ii = 14 x IR,
0.8 li = 12 x IR, 0.85 - 0.9 li = 12 x IR, 0.95 – 1.0 Ii = 10 x IR. Refer curve
examples and setting data in Section 9.
NRC = Nominal rated current, IR = Current adjustment dial setting,
STD = Short Time Delay, INST = instantaneous
Dimensions (mm)
Refer page 3 - 86
3 Pole
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. Price $
630 252 – 630 S630 GE 3 630
3
4 Pole
Ampere Adj. Ir 4 pole
Rating NRC Min. – Max. Cat. No. Price $
630 252 – 630 S630 GE 4 630
Notes: 1) To order a MCCB with the above options insert the required option after the
pole to make up the Cat. No. E.g.: S630GE 3 AG 630 is a S630GE 3 Pole 630 A
MCCB c/w Ground Fault protection.
2
) Where a neutral is present, a 4th Neutral pole CT is required for 3 pole
GF MCCBs and must be ordered separately using Cat. No.: T2GB40N06A.
Refer to page 3 - 100.
70 kA
Current rating: 252 – 630 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Voltage Icu Ics
3
AC use 415 70 50
Dimensions (mm)
Poles 3 4
H (less attached busbar) 260 260
W 140 185
D (less toggle) 103 103 T2ED
Notes: NRC: Nominal rated current, Ir: Current adjustment dial setting,
STD= Short Time Delay, INST = instantaneous
For additional information on installation, options and applications refer
Section 9, Part C catalogue or NHP.
GST not included NHP Sales 1300 NHP NHP 3 - 91
Price schedule ‘T2’ www.nhp.com.au
Valid until August 2014
MCCBs
3
External accessories Cat. No. Price $
Shunt trips Internal accessories are common for MCCBs 125 A to 630 A.
All have screw terminals except those indicated below with
wire leads as standard
For 3 and 4 pole MCCBs
110 V AC T2SH00A10TA 1)
230 – 240 V AC T2SH00A20TA 1)
SH 400 – 415 V AC T2SH00A40TA 1)
12 V DC T2SH00D01TA 1)
24 V DC (Suits 24 V AC) T2SH00D02TA 1)
48 V DC T2SH00D04TA 1)
110 V DC T2SH00D10TA 1)
230 V DC T2SH00D20TA 1)
Undervoltage Instantaneous operation
trips 110 V AC T2UV00A10NTA
200 – 240 V AC T2UV00A20NTA
UV 380 – 450 V AC T2UV00A40NTA
24 V DC T2UV00D02NTA
110 V DC T2UV00D10NTA
230 V DC T2UV00D20NTA
Time delayed operation (500 ms) – refer NHP
Auxiliary & General type (2 A @ 240 V Inductive)
Alarm 1 C/O Auxiliary T2AX00M3STA
switches
1 C/O Auxiliary – with 0.7 m wire T2AX00M3SWA
leads
1 C/O Alarm T2AL00M3STA
1 C/O Alarm – with 0.7 m wire T2AL00M3SWA
AX leads
Heavy-duty type (4 A @ 240 V Inductive)
1 N/O Auxiliary T2AX00B1STA
AL 1 N/C Auxiliary T2AX00B2STA
1 N/O Alarm T2AL00B1STA
1 N/C Alarm T2AL00B2STA
Micro switching type (very low voltages)
1 C/O Auxiliary T2AX00M3RTA
1 C/O Alarm T2AL00M3RTA
Manual Manual
charging Spring status charging
Allen key Point
ON / OFF /
TRIPPED
indicator
Optional ON / OFF
key lock pushbuttons
Padlockable
locking lever
Manual charge Power
shutter lever indicator
HB
3 Door
interlocking
variable
E400, S400, H400, L400, E630, S630
Grey IP55 handle + 320 mm shaft T2HS40R5GM
Red/yellow IP55 handle +
320 mm shaft T2HS40R5RM
depth
handles Large escutcheon plate option: T2HSESC100
2
100 mm
HS 390mm T pin shaft for T2HS -
no flexi coupling T2HS400SHAFT
Grey/black IP65 handle + T2HP40R6BN
445 mm shaft
Red/yellow IP65 handle + T2HP40R6RN
HP 445 mm shaft
Padlock attachment for T2HP/HS T2HP40PALK
mechanism
MCCB identification labels T40CAPLAB
Notes: Handles supplied with key locks available on request for T2HP handles.
3
interlock Suitable for 3 or 4 pole MCCBs
E400, S400, H400, L400, E630, S630 1)
Interlock kit less wire for T2MW40CB
motorised operation
Interlock kit less wire for manual T2MWH40CB
handle operation
MW Wire for above interlocks T2MW00SA 2)
Wire 1.0 M
Wire 1.5 M T2MW00LA 2)
MCCB identification labels T40CAPLAB
Rear walking beam interlock T2MB403
MB (NHP factory fit) T2MB404
T2MB availability to be announced.
T2MWH4CB
T2MW50CB
Interlock and
Interlock
handle
and motor
TSCF403SLNG
Narrow covers include as
standard: T2CF403SLNG Narrow cover,
- Locking clip for seal device which is the same width as
- IP 20 inserts with knock outs the MCCB.
Notes: 1) For 400/630 A MCCBs, ‘Flush’ and ‘rear’ covers are the same item.
2
) Locking clip T2FOOL tool supplied standard.
BA
T2BA
Interpole barriers
Notes: 1) Line side interpole barriers or terminal covers must be installed with
MCCBs.
2
) Interpole Barriers are supplied with MCCBs as standard; 2 barriers with 3
pole MCCBs, and 3 barriers with 4 pole MCCBs.
3
) For 400/630 A MCCBs, “flush” and “rear” covers are the same item.
UP E400, S400
3 pole TemPlug T2UPX3400
E630, S630
3 pole TemPlug T2UPX3630
Templugs suit 6.3 mm busbar (10 mm optional)
External 400 A CT T2GB40N04A
neutral CT 630 A CT T2GB40N06A
GB
Electronic 110 V AC TNS2110V
OCR checker 230 V AC TNS2240V
PM Plug-in MCCB (refer rear of section 3) Now
DR Draw-out MCCB availa
b
Refer le -
NHP
3
flush plate E400, S400, E630, S630
3 pole kit T2FP40S3A
FP 4 pole kit T2FP40S4A
Wire lead left side T2TF40LGA
terminal right side T2TF40RGA
block
TF
OCR Sealing
cover 400AF - 1600AF OCR Covers have
sealing as standard. -
SF
TNS T2DF/DM
Electronic OCR checker Door flange
T2TF T2FP
Wire lead Door
terminal mounting
block flush plate
MOULDED CASE
CIRCUIT BREAKERS
2000 A to 3200 A
POWER PROTECTION
115&3"4",*.$$#"$1#
r $VSSFOUMJNJUJOH
r 5SVF3.4NPOJUPSJOH
r *UTXJUDIUPBTTJTUJOPCUBJOJOHTFMFDUJWJUZ
r 1PXFSGVMJOUFSSVQUJOHDBQBDJUJFT
r MDXGPSTFDPGL"
r -JNJUBUJPOPGTZTUFNEBNBHF
r &MFDUSPOJDUSJQVOJUXJUIMPOH TIPSUBOE
JOTUBOUBOFPVTBEKVTUNFOUT
r "EKVTUNFOUSBOHFPGOPNJOBM
DVSSFOUSBUJOH
r 4UBOEBSET"4/;4
/)1/)1OIQDPNBV /)1/)1OIQO[DPN
Valid until August 2014
MCCBs
36 kA
Current rating: 630 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 415 36 36
DC use 250 50 50
Trip unit:
Q Adjustable thermal: 63% Ir to 100% Ir
Q Adjustable magnetic: 5 to 10 x Im
Dimensions (mm)
Poles 3
H 273
W 210
D (less toggle) 103
3 Pole
Ampere Adj. Ir Adj. Im 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
630 396 - 630 3150 - 6300 S800 CJ 3 630
800 504 - 800 4000 - 8000 S800 CJ 3 800
50 kA
Current rating: 630 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 415 50 50
DC use 250 50 50
Trip unit:
Q Adjustable thermal: 63% Ir to 100% Ir
Q Adjustable magnetic: 5 to 10 x Im
Dimensions (mm)
Poles 3 4
H 273 273
W 210 280
D (less toggle) 103 103
3 Pole
Ampere Adj. Ir Adj. Im 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
630 396 - 630 3150 - 6300 S800 NJ 3 630
800 504 - 800 4000 - 8000 S800 NJ 3 800
4 Pole
Ampere Adj. Ir Adj. Im 3 pole
Rating NRC Min. – Max. Min. – Max. Cat. No. Price $
630 396 - 630 3150 - 6300 S800 NJ 4 630
800 504 - 800 4000 - 8000 S800 NJ 4 800
70 kA
Current rating: 630 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 415 70 50
DC use 250 50 50
Trip unit:
Q Adjustable thermal: 63% Ir to 100% Ir
Q Adjustable magnetic: 5 to 10 x Im
Dimensions (mm)
Poles 3 4
H 273 273
W 210 280
D (less toggle) 103 103
Ampere
Rating Adj. Ir Adj. Ir 3 pole 4 pole
NRC Min. – Max. Min. – Max. Cat. No. 1) Price $ Price $
S800 RJ 3 630
630 396 - 630 3150 - 6300
S800 RJ 4 630
S800 RJ 3 800
800 504 - 800 4000 - 8000
S800 RJ 4 800
50 kA
Current rating: 252 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 415 50 50
Dimensions (mm)
Poles 3 4
H 273 273
W 210 280
D (less toggle) 103 103
Notes: 1) The STD and Instantaneous pickup currents (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curves 1 & 2 Isd = 2.5 x IR, curve 3 Isd
= 5 x IR, curves 4 - 7 Isd = 10 x IR . IR dial setting 0.4 – 0.8 Ii = 14 x IR and IR
dial setting 0.9 – 1.0 Ii = 12 x IR.
NRC: Nominal rated current
Adj. Ir: Adjustable thermal setting
Adj. Im: Adjustable magnetic setting
Replaces: XS630SE and XS800SE. Note: check exact ratings or dimensions to
suit your application requirement .
70 kA
Current rating: 252 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Voltage Icu Ics
AC use 415 70 50
Over Current Relay:
Q Electronic, for general & selectivity applications 3
Q 7 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40% - 100% of the nominal rated current In
Q STD setting 2.5 – 10 (x IR) 2)
Dimensions (mm)
Q INST setting 14 (Max 12 x In) 2)
Poles 3 4
OCR options:
H 273 273
Q Ground Fault Trip W 210 280
Q Neutral Pole protection D (less toggle) 103 103
Q Pre-Trip Alarm
Ampere Adj. Ir 3 pole 4 pole
Rating NRC Min. – Max. Cat. No. 1) Price $ Price $
S800 RE 3 630
630 252 - 630
S800 RE 4 630
S800 RE 3 800
800 320 - 800
S800 RE 4 800
Price Adder for OCR options. MCCB Cat. No. with 3 pole 4 pole
Add to above MCCB price option Price $ Price $
3 P OCR options: PTA 3) S800 RE 3 AP #
GF 3) S800 RE 3 AG #
PTA + GF 3) S800 RE 3 APG #
4 P OCR options: PTA 3) S800 RE 4 AP #
AP 3) S800 RE 4 AN #
PTA + NP 3) S800 RE 4 APN #
GF + NP 3) S800 RE 4 AGN #
Notes: 1) “#” add OCR trip unit rating where shown with OCR options.
2
) The STD and Instantaneous pickup currents (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR,
curve 3 Isd = 5 x IR, curve 4 - 7 Isd = 10 x IR .
IR dial setting 0.4 – 0.8 Ii = 14 x IR and IR dial setting 0.9 – 1.0 Ii = 12 x IR.
3
) To order a MCCB with the above options insert the required amp rating
after the option to make up the Cat. No. Eg: S800RE 4 AGN 800 is an
S800RE 4 Pole 800 A MCCB c/w Neutral Protection and Ground Fault
protection.
For additional information on OCR settings, options and applications refer
section 9 or part C catalogue.
Replaces: XH630SE and XH800SE. Note: check exact ratings or dimensions
to suit your application requirement.
70 kA
Current rating: 320 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 415 70 50
XOW Over Current Relay:
Q Ammeter or Energy Metering types
Q Adjustable LSI setting for grading applications
Q Base current adjustable from 40% - 100% of In New
ing
MCCB Standard features:
meter
S800RE _ X1L MCCB
Q Ammeter, Adjustable LSI
Q Trip event log, Alarm event log, Test function
S800RE _ X1S
Q Energy (multifunction) meter: A, V, P, kW, kWh, E, Pf, F, H
Q Adjustable LSI
Q Backlit LCD display
Q Ground fault, Pre trip alarm, Phase rotation & Neutral pole protection
Q Trip and Alarm event log, Test function, Trip indication contact output
Q Modbus RTU 485 communications
Q External door mounting meter option (T2ED not incl. in below pricing)
Dimensions (mm)
Poles 3 4
H 273 273
W 210 280
D (less toggle) 103 103 T2ED
Ampere
Rating Ir Adj. 3 pole 4 pole
NRC Min.–Max. Cat. No. 1) Price $ Price $
MCCB with S800 RE 3 800 X1L
ammeter 800 320 - 800
S800 RE 4 800 X1L
MCCB with 800 S800 RE 3 800 X1S
energy meter 320 - 800
S800 RE 4 800 X1S
125 kA
Current rating: 252 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Voltage Icu Ics
AC use 415 125 94
Over Current Relay:
Q Electronic, for general & selectivity applications 3
Q 7 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40% - 100% of the nominal rated current In
Q STD setting 2.5 – 10 (x IR) 2)
Dimensions (mm)
Q INST setting 14 (Max 12 x In) 2)
Q OCR Options: Poles 3 4
Q Ground Fault Trip H 273 273
Q Neutral Pole protection W 210 280
Q Pre-Trip Alarm D (less toggle) 103 103
Ampere Adj. Ir 3 pole 4 pole
Rating NRC Min. – Max. Cat. No. 1) Price $ Price $
H800 NE 3 630
630 252 - 630
H800 NE 4 630
H800 NE 3 800
800 320 - 800
H800 NE 4 800
Price Adder for OCR options. MCCB Cat. No. with 3 pole 4 pole
Add to above MCCB price option Price $ Price $
3 P OCR options: PTA 3) H800 NE 3 AP #
GF 3) H800 NE 3 AG #
PTA + GF 3) H800 NE 3 APG #
4 P OCR options: PTA 3) H800 NE 4 AP #
AP 3) H800 NE 4 AN #
PTA + NP 3) H800 NE 4 APN #
GF + NP 3) H800 NE 4 AGN #
Notes: 1) “#” add OCR trip unit rating where shown with OCR options.
2
) The STD and Instantaneous pickup currents (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR,
curve 3 Isd = 5 x IR, curve 4 - 7 Isd = 10 x IR .
IR dial setting 0.4 – 0.8 Ii = 14 x IR and IR dial setting 0.9 – 1.0 Ii = 12 x IR.
3
) To order a MCCB with the above options insert the required amp rating
after the option to make up the Cat. No. Eg: H800NE 4 AGN 800 is an
H800NE 4 Pole 800 A MCCB c/w Neutral Protection and Ground Fault
protection.
For additional information on OCR settings, options and applications refer
section 9 or part C catalogue.
Replaces: TL630NE and TL800NE. Note: check exact ratings or dimensions to
suit your application requirement.
125 kA
Current rating: 320 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 415 125 94
XOW Over Current Relay:
Q Ammeter or Energy Metering types
Q Adjustable LSI setting for grading applications
Q Base current adjustable from 40% - 100% of In New
ing
MCCB Standard features: meter
H800NE _ X1L MC B
C
Q Ammeter, Adjustable LSI
Q Trip event log, Alarm event log, Test function
H800NE _ X1S
Q Energy (multifunction) meter: A, V, P, kW, kWh, E, Pf, F, H
Q Adjustable LSI
Q Backlit LCD display
Q Ground fault, Pre trip alarm, Phase rotation & Neutral pole protection
Q Trip and Alarm event log, Test function, Trip indication contact output
Q Modbus RTU 485 communications
Q External door mounting meter option ((T2ED not incl. in below pricing)
Dimensions (mm)
Poles 3 4
H 273 273
W 210 280
D (less toggle) 140 140 T2ED
Ampere
Rating Ir Adj. 3 pole 4 pole
NRC Min.–Max. Cat. No. Price $ Price $
MCCB with H800 NE 3 800 X1L
ammeter 800 320 - 800
H800 NE 4 800 X1L
MCCB with 800 H800 NE 3 800 X1S
energy meter 320 - 800
H800 NE 4 800 X1S
200 kA
Current rating: 252 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
Voltage Icu Ics
AC use 415 200 150
Over Current Relay:
Q Electronic, for general & selectivity applications 3
Q 7 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40% - 100% of the nominal rated current In
Q STD setting 2.5 – 10 (x IR) 2)
Dimensions (mm)
Q INST setting 14 (Max 12 x In) 2)
Poles 3 4
OCR options:
H 273 273
Q Ground Fault Trip W 210 280
Q Neutral Pole protection D (less toggle) 140 140
Q Pre-Trip Alarm
Ampere Adj. Ir 3 pole 4 pole
Rating NRC Min. – Max. Cat. No. 1) Price $ Price $
L800 NE 3 630
630 252 - 630
L800 NE 4 630
L800 NE 3 800
800 320 - 800
L800 NE 4 800
Price Adder for OCR options. MCCB Cat. No. with 3 pole 4 pole
Add to above MCCB price option Price $ Price $
3 P OCR options: PTA 3) L800 NE 3 AP #
GF 3) L800 NE 3 AG #
PTA + GF 3) L800 NE 3 APG #
4 P OCR options: PTA 3) L800 NE 4 AP #
AP 3) L800 NE 4 AN #
PTA + NP 3) L800 NE 4 APN #
GF + NP 3) L800 NE 4 AGN #
Notes: 1) “#” add OCR trip unit rating where shown with OCR options.
2
) The STD and Instantaneous pickup currents (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR,
curve 3 Isd = 5 x IR, curve 4 - 7 Isd = 10 x IR .
IR dial setting 0.4 – 0.8 Ii = 14 x IR and IR dial setting 0.9 – 1.0 Ii = 12 x IR.
3
) To order a MCCB with the above options insert the required amp rating
after the option to make up the Cat. No. Eg: L800NE 4 AGN 800 is an
L800NE 4 Pole 800 A MCCB c/w Neutral Protection and Ground Fault
protection.
For additional information on OCR settings, options and applications refer
section 9 or part C catalogue.
70 kA
Current rating: 252 – 800 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics Rear connect only
AC use 690 70 50
Over Current Relay:
Q Electronic, for general & selectivity applications
Q 7 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40% - 100% of the nominal rated current In
Q STD setting 2.5 – 10 (x IR) 1)
Q INST setting 14 (Max 12 x In) 1)
Dimensions (mm)
Poles 3
H 273
W 210
D (less toggle) 140
3 Pole
Ampere Adj. Ir 3 pole
Rating NRC Min. – Max. Cat. No. Price $
630 252 - 630 L800 PE 3 630 RC
800 320 - 800 L800 PE 3 800 RC
Notes: 1) The STD and Instantaneous pickup currents (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curves 1 & 2 Isd = 2.5 x IR,
curve 3 Isd = 5 x IR, curves 4 - 7 Isd = 10 x IR.
IR dial setting 0.4 – 0.9 Ii = 14 x IR and IR dial setting 0.95 – 1.0 Ii = 13 x IR.
Not suitable for reverse connection either individually or on a chassis.
Suitable for general motor starting and power distribution applications
Refer NHP for 4 pole version availability.
Refer NHP for additional information.
NRC: Nominal rated current
Adj. Ir: Adjustable thermal setting
Adj. Im: Adjustable magnetic setting
MCCBs are rear connect or plug-in only.
50 / 70 kA
Current rating: 400 – 1000 A
Approvals and Tests: Standards AS/NZS 3947-2
and IEC 60947-2
Interrupting capacity:
S1000SE S1000NE
Voltage Icu Ics Icu Ics
AC use 415 50 38 70 50 Reduced
frame size 3
Over Current Relay:
Q Electronic, for general & selectivity applications
Q 7 dial selectable characteristic curves suited for a variety of applications
Q Base current Ir is adjustable from 40% - 100% of the nominal rated current In
Q STD setting 2.5 – 10 (x IR) 1)
Q INST setting 14 (Max 12 x In) 1) Dimensions (mm)
OCR Options: Poles 3 4
Q Ground Fault Trip H 273 273
Q Neutral Pole protection W 210 280
Q Pre-Trip Alarm D (less toggle) 103 103
Price Adder for OCR options. MCCB Cat. No. with 3 pole 4 pole
Add to above MCCB price option Price $ Price $
3 P OCR options: PTA 2) S1000 NE 3 AP #
GF 2) S1000 _ _ 3 AG #
PTA + GF 2) S1000 NE 3 APG #
4 P OCR options: PTA 2) S1000 NE 4 AP #
NP 2) S1000 NE 4 AN #
PTA + NP 2) S1000 NE 4 APN #
GF + NP 2) S1000 _ _ 4 AGN #
Notes: 1) 1. The STD and Instantaneous pickup currents (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR,
curve 3 Isd = 5 x IR, curve 4 - 6 Isd = 8 x IR . IR dial setting 0.4 – 0.63 Ii = 14 x
IR and IR dial setting 0.8 – 1.0 Ii = 10 x IR.
2
) To order a MCCB with the above options insert the required amp rating
after the option to make up the Cat. No. Eg: S1000NE 4 AGN 1000 is an
S1000NE 4 Pole 1000 A MCCB c/w Neutral Protection and GF.
Replaces: XH800SE and XS1250SE 1000A.
70 kA
Current rating: 400 - 1000 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
3
Voltage Icu Ics
AC use 415 70 50
XOW Over Current Relay:
Q Ammeter or Energy Metering types
Q Adjustable LSI setting for grading applications
Q Base current adjustable from 40% - 100% of In New
ing
MCCB Standard features:
meter
S1000NE _ X1L M B
CC
Q Ammeter, Adjustable LSI
Q Trip event log, Alarm event log, Test function
S1000NE _ X1S
Q Energy (multifunction) meter: A, V, P, kW, kWh, E, Pf, F, H
Q Adjustable LSI
Q Backlit LCD display
Q Ground fault, Pre trip alarm, Phase rotation & Neutral pole protection
Q Trip and Alarm event log, Test function, Trip indication contact output
Q Modbus RTU 485 communications
Q External door mounting meter option (T2ED not incl. in below pricing)
Dimensions (mm)
Poles 3 4
H 273 273
W 210 280
D (less toggle) 103 103
T2ED
Ampere
Rating Ir Adj. 3 pole 4 pole
NRC Min.–Max. Cat. No. Price $ Price $
MCCB with S1000 NE 3 1000 X1L
ammeter 1000 400 - 1000
S1000 NE 4 1000 X1L
MCCB with 1000 S1000 NE 3 1000 X1S
energy meter 400 - 1000
S1000 NE 4 1000 X1S
3
Internal accessories Cat. No. Price $
Shunt trips Internal accessories are common for MCCBs 800 A to 1600 A.
All have screw terminals except those indicated below with
wire leads as indicated.
For 3 and 4 pole MCCBs
110 V AC T2SH00A10TA
230 – 240 V AC T2SH00A20TA
SH 400 – 415 V AC T2SH00A40TA
12 V DC T2SH00D01TA
24 V DC (suits 24 V AC) T2SH00D02TA
48 V DC T2SH00D04TA
110 V DC T2SH00D10TA
230 V DC T2SH00D20TA
Undervoltage Instantaneous operation
trips 110 V AC T2UV80A10NTA
200 – 240 V AC T2UV80A20NTA
UV 380 – 450 V AC T2UV80A40NTA
24 V DC T2UV80D02NTA
110 V DC T2UV80D10NTA
230 V DC T2UV80D20NTA
Time delay types are available – refer NHP for details.
Auxiliary & General type (2 A @ 240 V Inductive)
Alarm 1 C/O Auxiliary with terminals T2AX00M3STA
switches
1 C/O 1st Auxiliary with 700 mm leads T2AX00M3SWA
1 C/O 2nd Auxiliary with 700 mm leads T2AX00M4SWA
1 C/O 3rd Auxiliary with 700 mm leads T2AX00M5SWA
1st, 2nd, 3rd aux have different numbered wire leads, otherwise identical.
AX 1 C/O Alarm T2AL00M4STA
1 C/O Alarm with 700 mm wire leads T2AL00M5SWA
AL Heavy-duty
1 N/O Auxiliary
type (4 A @ 240 V Inductive)
T2AX00B1STA
1 N/C Auxiliary T2AX00B2STA
1 N/O Alarm T2AL00B1STA
1 N/C Alarm T2AL00B2STA
Micro switching type (very low voltages and currents)
1 C/O Auxiliary T2AX00M3RTA
1 C/O Alarm T2AL00M3RTA
3
Slide type - manual operation, padlockable. Does not allow motors,
handles or other front mounted accessories to be fitted.
Suitable for front or rear connection.
S800, S1000
3 pole T2MS803SFA
MS 4 pole T2MS804SFA
H800
3 pole T2MS803LFA
4 pole T2MS804LFA
Cable interlock – allows an MCCB can be mounted horizontally,
vertically or diagonally. Accepts Motors and handles.
Suitable for 3 or 4 pole MCCBs
800 A to 1000 A
Interlock kit less wire T2MW80CA
Wire for above interlocks
ML Wire 1.0 m T2MW00SA
Wire 1.5 m T2MW00LA
Rear walking beam interlock
S800 3P T2MB803
MB S800 4P T2MB804
S1000 3P T2MB103
S1000 4P T2MB104
MB interlock availability to be announced.
3 Terminal
covers for
S800, S1000, H800
plug in base 3 pole cover set T2CB803G
4 pole cover set T2CB804G
CB
Extended Terminal covers are the same width as the MCCB
terminal S800, S1000, H800
covers FC
3 pole cover set T2CF803SLNG
CF 4 pole cover set T2CF804SLNG
Terminal 800 A to 1000 A
cover locking A clip that provides additional
clip terminal cover locking, and also T2CF00LA
allows a lead seal to be fitted
Interpole S800, S1000, H800
Barriers 1) 2) Interpole barrier (Qty 2) T2BA403SHA
Notes: 1) Line side interpole barriers or terminal covers must be installed with
MCCBs.
2
) Interpole Barriers are supplied with MCCBs as standard; 2 barriers
with 3 pole MCCBs, and 3 barriers with 4 pole MCCBs.
3
800 A, 1000 A (Availability to be announced)
Lock with single 8 mm hole T2HL80CAP
Motor 800 - 1000 A
operators 110 - 240 V AC T2MC80A10NA
24 - 48 V DC T2MC80D10NA
Electrical interlocking connector between motor operators
3
Plug in Plug in MCCB base kit. Includes MCCB plugs and other parts for
MCCBs converting an MCCB to a plug in MCCB. Mounting bases are ordered
seperately.
MCCB conversion kits:
S800, S1000
3 pole kit REFER NHP
4 pole kit REFER NHP
Plug in bases, IP20, includes rear insulation screen. The base includes
terminal studs which are suitable for front or rear connection.
Interpole barriers can be used with these bases, but not terminal
covers.
Plug in mounting bases:
S800, S1000
3 pole kit T2PM80A3A
PM 4 pole kit T2PM80A4A
Control wiring plugs and sockets for plug in MCCBs
3 pin plug for aux/alarms – MCCB 2H6959CAA1
side
3 pin plug for shunt/UVT – MCCB 2H6959CBA1
side
3 pin socket for panel mount T2TP003A
base
Extension bars
3 pole kit T2PF803HA
4 pole kit T2PF804HA
50 / 85 kA
Current rating: 500 – 1250 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
S1250SE S1250GE
Voltage Icu Ics Icu Ics
AC use 415
Price Adder for OCR options. MCCB Cat. No. with 3 pole 4 pole
Add to above MCCB price option Price $ Price $
3 P OCR options: PTA 2) S1250 GE 3 AP #
GF 2) S1250 _ _ 3 AG #
PTA + GF 2) S1250 GE 3 APG #
4 P OCR options: PTA 2) S1250 GE 4 AP #
NP 2) S1250 GE 4 AN #
PTA + NP 2) S1250 GE 4 APN #
GF + NP 2) S1250 _ _ 4 AGN #
Notes: 1) The STD and Instantaneous pickup currents (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR,
curve 3 Isd = 5 x IR, curve 4 - 6 Isd = 8 x IR . IR dial setting 0.4 – 0.63 Ii = 14 x
IR and IR dial setting 0.8 – 1.0 Ii = 10 x IR.
2
) To order a MCCB with the above options insert the required amp rating
after the option to make up the Cat. No. Eg: S1250GE 4 AGN 1250 is an
S1250GE 4 Pole 1250 A MCCB c/w Neutral Protection and GF.
Replaces: XS1250SE.
50 / 85 kA
Current rating: 640 – 1600 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity:
S1600SE S1600NE
Voltage Icu Ics Icu Ics
3 AC use 415
Over Current Relay:
50 38 85 65
Price Adder for OCR options. MCCB Cat. No. with 3 pole 4 pole
Add to above MCCB price option Price $ Price $
3 P OCR options: PTA 2) S1600 NE 3 AP #
GF 2) S1600 _ _ 3 AG #
PTA + GF 2) S1600 NE 3 APG #
4 P OCR options: PTA 2) S1600 NE 4 AP #
AP 2) S1600 NE 4 AN #
PTA + NP 2) S1600 NE 4 APN #
GF + NP 2) S1600 _ _ 4 AGN #
Notes: 1) The STD and Instantaneous pickup currents (Isd & Ii ) settings are not
individually adjustable, however by selecting different curve types and
different IR settings the values will vary. Curve 1 & 2 Isd = 2.5 x IR,
curve 3 Isd = 5 x IR, curve 4 - 6 Isd = 8 x IR . IR dial setting 0.4 – 0.63 Ii = 14 x
IR and IR dial setting 0.8 – 1.0 Ii = 10 x IR.
2
) To order a MCCB with the above options insert the required amp rating
after the option to make up the Cat. No. Eg: S1600NE 4 AGN 1600 is an
S1600NE 4 Pole 1600 A MCCB c/w Neutral Protection and GF.
Replaces: XS1600SE.
3
Internal accessories Cat. No. Price $
Shunt trips Internal accessories are common for MCCBs 800 A to 1600 A.
All have screw terminals except those indicated below with
wire leads as indicated.
For 3 and 4 pole MCCBs
110 V AC T2SH00A10TA
230 – 240 V AC T2SH00A20TA
SH 400 – 415 V AC T2SH00A40TA
12 V DC T2SH00D01TA
24 V DC (suits 24 V AC) T2SH00D02TA
48 V DC T2SH00D04TA
110 V DC T2SH00D10TA
230 V DC T2SH00D20TA
Undervoltage Instantaneous operation
trips 110 V AC T2UV80A10NTA
200 – 240 V AC T2UV80A20NTA
UV 380 – 450 V AC T2UV80A40NTA
24 V DC T2UV80D02NTA
110 V DC T2UV80D10NTA
230 V DC T2UV80D20NTA
Time delay types are available – refer NHP for details.
Auxiliary & General type (2 A @ 240 V Inductive)
Alarm 1 C/O Auxiliary with terminals T2AX00M3STA
switches
1 C/O 1st Auxiliary with 700 mm leads T2AX00M3SWA
1 C/O 2nd Auxiliary with 700 mm leads T2AX00M4SWA
1 C/O 3rd Auxiliary with 700 mm leads T2AX00M5SWA
1st, 2nd, 3rd aux have different numbered wire leads, otherwise identical.
AX 1 C/O Alarm T2AL00M4STA
1 C/O Alarm with 700 mm wire leads T2AL00M5SWA
AL Heavy-duty
1 N/O Auxiliary
type (4 A @ 240 V Inductive)
T2AX00B1STA
1 N/C Auxiliary T2AX00B2STA
1 N/O Alarm T2AL00B1STA
1 N/C Alarm T2AL00B2STA
Micro switching type (very low voltages and currents)
1 C/O Auxiliary T2AX00M3RTA
1 C/O Alarm T2AL00M3RTA
Notes: 1) Line side interpole barriers or terminal covers must be installed with
MCCBs.
2
) Interpole Barriers are supplied with MCCBs as standard; 2 barriers
with 3 pole MCCBs, and 3 barriers with 4 pole MCCBs.
3
1250 A, 1600 A
Lock with two 8 mm holes T2HLX6CAP
Motor 1250 A, 1600 A
operators 110 V AC T2MCX6A10NA
MC 240 V AC T2MCX6A24NA
24 V DC T2MCX6D02NA
Rear connect 1250 A, 1600 A (factory fit only)
terminal studs3 pole kit, set of 6 studs (1250 A) T2RPX33SB
4 pole kit, set of 8 studs (1250 A) T2RPX34SB
RP 3 pole kit, set of 6 studs (1600 A) T2RPX63SB
4 pole kit, set of 8 studs (1600 A) T2RPX64SB
TemBreak 1 series
Electronic XS2000NE
85 kA
Current rating: 1000 – 2000 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity: Symmetrical amps (kA RMS)
3
Voltage Icu kA Ics kA
AC use 400/415 1) 85 64
Trip unit:
Adjustable long, short and instantaneous trip
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3 4
H 2) 450 450
W 320 429
D (less toggle) 185 185
Weight (kg) 55.0 67
Amp rating
NRC Min. Max. Cat. No. Price $
3 Pole
2000 1000 2000 XS2000NE 20003 RC
4 Pole
2000 1000 2000 XS2000NE 20004 RC
Ground Fault Trip MCCBs 3)
3 Pole
2000 1000 2000 XS2000NE 20003L
4 Pole
2000 1000 2000 XS2000NE 20004L
TemBreak 1 series
Electronic XS2500NE
85 kA
Current rating: 1250 – 2500 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity: Symmetrical amps (kA RMS)
Voltage Icu kA Ics kA
3
AC use 400/415 1) 85 64
Dimensions (mm)
Poles 3 4
H 2) 450 450
W 320 429
D (less toggle) 185 185
Weight (kg) 66.0 78
Amp rating
NRC Min. Max. Cat. No. Price $
3 Pole
2500 1250 2500 XS2500NE 2500 RC3
4 Pole
2500 1250 2500 XS2500NE 2500 RC4
Ground Fault Trip MCCBs 2)3)
3 Pole
2500 1250 2500 XS2500SE 25003L
4 Pole
2500 1250 2500 XS2500SE 25004L
TemBreak 1 series
Electronic XS3200NE
85 kA
Current rating: 1600 – 3200 A
Approvals and Tests: Standards AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity: Symmetrical amps (kA RMS)
3
Voltage Icu kA Ics kA
AC use 400/415 85 64
ICW for 0.5 sec 38
3 Pole
Amp
rating 3 pole
NRC Min. Max. Cat. No. Price $
3200 1600 3200 XS3200NE32003 RC
3
415 V AC 2H1541BAB
24 V AC 2H1532BAA
48 V AC 2H1533BAA
AC coil 1) 2H1509BAA
100-230 V DC coil 2) 2H1510BAA
24 V DC coil 2) 2H1511BAA
48 V DC coil 2) 2H1512BAA
60 V DC coil 2) 2H1513BAA
110 V AC instantaneous UXUB0013B
controller
Undervoltage
trips 240 V AC instantaneous UXUB0014B
controller
440 V AC instantaneous UXUB0015B
controller
110 V AC time delay controller UXUB0016B
240 V AC time delay controller UXUB0017B
440 V AC time delay controller UXUB0018B
200-230 V DC controller UXUB0038B
AUX SW right hand 1C UXXB0013C
AUX SW right hand 2C UXXB0014C
Auxiliary AUX SW right hand 3C UXXB0015C
switches AUX SW right hand 4C UXXB0016C
AUX SW right hand 5C UXXB0017C
AUX SW right hand 6C UXXB0018C
Alarm switch ALT SW right hand UXLB0012C
ALT/AUX right hand 1C UXLB0019D
Alarm & ATL/AUX right hand 2C UXLB0020C
auxiliary
switch ATL/AUX right hand 3C UXLB0021C
ATL/AUX right hand 5C UXLB0023C
3 Fault
indication LED’s mounted at top of OCR FILED
Notes: 1) When an XS2000NE MCCB is configured for “front connection”, the Front
Connect busbar kits TXRD0003A & 4A already include mounting screws
for the FC terminals.
The TXRD0005A mounting bolts, which also include spacers, are required
to mount the MCCB itself. TXRD0005A is always required for FC 2000A
MCCBs, but not RC.
2
) Order one interlock mechanism per breaker.
3
) Extension shaft handle not available.
3
Q Standard 125 A or 250 A frame
Q Thermal magnetic trip unit ratings:
12 A - 125 A (125 AF), 100 - 250 A (250 AF)
Q Fixed magnetic characteristic
Q 65 kA fault interruption rating @ 400 / 415 V
Q Complies with AS 2081:2011
65 kA
Current rating: 20 – 250 A
Approvals and Tests: AS/NZS 3947-2, IEC 60947-2,
Annex B, EN/IEC 60755
AS 2081:2011 compliance
Operating voltage: 200 - 580 V 50/60 Hz
3
Interrupting capacity:
Voltage Icu kA Ics kA
AC use 380/415 65 36
DC use 250 V 40 40
Trip unit: Adjustable thermal (0.63 lr to 100 % lr) and fixed magnetic
Earth leakage characteristic: Type ‘A’ - suitable for AC and residual pulsating
DC currents.
Earth leakage adjustments: - 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A.
- NT ), 0, 60, 200, 400, 700 mS
1
Dimensions (mm)
Poles 3 4
H 155 155
W 90 120
D (less toggle) 68 68
Toggle cut-out 104 104
3
3 Pole
Amp
rating Adj. lr 1) Fixed lm 1) 3 pole
NRC Min. – Max. (Amps) Cat. No. 2) Price $
20 12 - 20 240 ZS125 GJ 3 20
32 20 - 32 384 ZS125 GJ 3 32
50 32 - 50 600 ZS125 GJ 3 50
63 40 - 63 756 ZS125 GJ 3 63
100 63 - 100 1200 ZS125 GJ 3 100
125 80 - 125 1250 ZS125 GJ 3 125
Notes: 1) NRC: Nominal rated current. Adj. lr: Adjustable thermal setting
Fixed lm: Fixed magnetic setting NT: No Trip
Dimensions (mm)
Poles 3 4
H 165 165
W 105 140
D (less toggle) 68 68
Toggle cut-out 104 104
3
3 Pole
Amp rating Adj. lr 1) Fixed lm 1)
NRC Min. – Max. (Amps) Cat. No. Price $
160 100-160 1760 ZS250 GJ 3 160
250 160-250 2750 ZS250 GJ 3 250
4 Pole
160 100-160 1760 ZS250 GJ 4 160
ZS250 GJ 4 160 SN
250 160-250 2750 ZS250 GJ 4 250
ZS250 GJ 4 250 SN
The ZS 400 – 800A Earth Leakage Circuit Breaker from Terasaki offers machine
protection within a standard 400 A, 630 / 800 A MCCB frame size.
The full functionality of a standard thermal-magnetic overload / short circuit
protection MCCB is maintained.
Standard Features
Q AS/NZS 60947.6, JIS Standards compliance
Q Thermal/magnetic MCCB
Q 3 or 4 pole 400 A, 630/800 A 3 pole only
Q Switching utilisation up to 110 to 440 V AC 3
Q Suitable for use at 40/50/60 Hz
Q Trip unit ratings: 250 A – 400 A (400 AF),
500 A – 800 A (800AF)
Q Fixed thermal setting, adjustable magnetic setting
Q 70 kA / 50kA fault interruption rating 400 AF / 800 AF
Q Harmonics inhibition
Q Megger / Dielectric test voltage: 500 V DC Maximum
Earth Leakage features
Q Yellow ground fault TRIP indication flag
Q Grey TEST button
Q Green ’Power ON’ LED
Q Adjustable thermal characteristic dial setting from 63 - 100 % of IR
Q Adjustable earth leakage ranges: 100 mA, 200 mA, 500 mA,
Q Trip time selection: Fixed
Q Type “AC” earth leakage device suitable for AC currents
Options, Internal and external accessories
Q Accessories are a customer fit.
Q Auxiliaries & Alarms can be used. The quantities refer to standard MCCB
quantity configurations
Q Cannot fit Shunt & UVTs
Q Standard MCCB external accessories can be installed, except for T2ML link
and T2MW wire interlocks.T2MS slide interlocks can be installed
Q Will fit to XC and HC chassis
3
Earth leakage (RCD) Test button
Current sensitivity
Trip button
H
3
(excludes
attached bubar)
Dimensions
Outline
Dimensions (mm) ZS400GF ZS630NF ZS800NF
H 260 273 273
W 140 3P / 185 4P 210 3P 210 3P
D 103 103 103
70 kA
Current rating: 250 – 400 A
Approvals and Tests: AS/NZS 3947-2, IEC 60947-2,
AS/NZS 2081: 2011, JIS C 8201
Operating voltage: 110 – 440 V 50/60 Hz
Interrupting capacity:
3
New
400
Voltage Icu Icu ZS EL AF
AC use CB
380/415 70
50 kA
Current rating: 500 – 800 A
Approvals and Tests: AS/NZS 3947-2, IEC 60947-2,
AS/NZS 2081: 2011, JIS C8201
Operating voltage: 110 – 440 V 50/60 Hz
Interrupting capacity:
AC use
Voltage Icu
380/415
Icu
50
3
Trip unit: Fixed thermal, adjustble magnetic 5 to 10 x Ii
Earth leakage characteristic: Type “AC” - suitable for AC currents.
Earth leakage adjustments: 100 mA, 200 mA, 500 mA
Fixed operating time: 0.1 second maximum
Options:
TemBreak 2, 630 - 800 A internal and external accessories can be installed,
except for shunts, UVTs, Trip Control Units, T2ML / MW Interlocks
Neutral Pole
ZS ELCBs are available with switched neutral poles.
Dimensions
Poles 3 4
H (less attached busbars) 273 273
W 210 280
D (less toggle) 103 103
Ampere Fixed Ir 1) Adj. Ii 1)
Rating NRC Amps Amps Cat. No. Price $
500 500 2500 - 5000 ZS630 NF 3 500 4920.00
600 600 3000 - 6000 ZS630 NF 3 600 5200.00
630 630 3150 - 6300 ZS630 NF 3 630 5200.00
700 700 3500 - 7000 ZS800 NF 3 700 5900.00
800 800 4000 - 8000 ZS800 NF 3 800 6200.00
3
Q Rated impulse withstand voltage Uimp = 8 kV
3 Pole
Rated short-
Amp Short time circuit making
rating rating kA for capacity 3 pole
NRC 0.3 sec (Icw) (Icm)(kA) Cat. No. Price $
125 2 3.6 S125NN3
160 3 6 S160NN3
250 3 6 S250NN3
400 5 9 S400NN3
630 5 9 S630NN3
800 10 15 S800NN3
1250 15 32 S1250NN3
1600 20 45 S1600NN3
2000 35 90 XS2000NN3RC
2500 1) 35 90 XS2500NN3RC
4 Pole
Rated short-
Amp Short time circuit making
rating rating kA for capacity 4 pole
NRC 0.3 sec (Icw) (Icm)(kA) Cat. No. Price $
125 2 3.6 S125NN4
160 3 6 S160NN4
250 3 6 S250NN4
400 5 9 S400NN4
630 5 9 S630NN4
800 10 15 S800NN4
1250 15 32 S1250NN4
1600 20 45 S1600NN4
2000 1) 35 90 XS2000NN4RC
2500 1) 35 90 XS2500NN4FC
New
M
to 10 CCBs
00 V
avail DC
able
Notes: 1) All standard thermal magnetic MCCBs are rated to switch DC currents up
to 250 V DC.
2
) Connect poles in series for 350 V DC and above.
The time constant (L/R) of the circuit should be less than 2 ms at or below
rated current, less than 7 ms for short circuit equal and below 10 kA, less
than 15 ms for short circuits over 10 kA, the connections should be as
shown in the diagrams on following page.
Ratings
DC Breaking capacity (kA) Poles Current
1
350 V 500 V 600 V ) OCR type adjust. Cat. No.
10 – – 3 Therm Mag 63-100 % Ir S125ND
10 7.5 5 4 Therm Mag 63-100 % Ir S125ND
10 – – 3 Therm Mag 63-100 % Ir S160ND
10 7.5 5 4 Therm Mag 63-100 % Ir S160ND
3
10 – – 3 Therm Mag 63-100 % Ir S250ND
10 7.5 5 4 Therm Mag 63-100 % Ir S250ND
20 15 15 3 Therm Mag 63-100 % Ir S400ND
30 20 20 3 Therm Mag 50-100 % Ir S800ND
Ampere DC Utilisation
rating Device type Part Prefix voltage
20 - 2500 MCCB S125 - 2500 ND 600 V
250 - 800 MCCB PVS 400 - 800 NDL 750 V
250 - 800 MCCB PVS 400 - 800 NDH 1000 V
160 - 800 Isolator PVS 160 - 800 NNL 800 V
160 - 800 Isolator PVS 400 - 800 NNH 1000 V
3 and 4 pole series connection
The following wiring connection diagrams should be followed to obtain the
kA switching rating levels indicated in the table above.
3 pole in series
OFF
ON
L
O
A
D
4 pole in series
L
O
A
D
OFF
ON
3
3 pole
3 Pole 3 pole
Amp rating NRC Trip Unit Type Cat. No. 2) 3) Price $
1000 ) 4
Thermal Magnetic XS1000ND10003FC
1250 Magnetic only XS1250ND12503FC 2)3)
1600 Magnetic only XS1600ND16003FC 1)3)
2000 Magnetic only XS2000ND20003RC
2500 Magnetic only XS2500ND25003RC
External accessories
Plug-in MCCBs 4)
A range of MCCBs are stocked with a rear mounted pre-fitted plug-in section
that plugs into the panel mounted base section. The panel mounted base
section is ordered separately. The TemBreak 2 plug-in bases include a safety
interlock system where the MCCB must be switched OFF to allow MCCB
removal. The plug-in base allows for the fitting of up to 4 terminal blocks
when auxiliaries, alarms, shunts or UVTs are used. Rear connect terminal
3
covers can be used on the front of the MCCB for IP 20 ingress protection.
Standard MCCB conversion to plug-in – NHP can convert standard MCCB to
plug-in use.
MCCBs complete with base plug (3 pole types below are stocked) 1)
MCCB Ampere 400/415 V 6) 3 pole
Rating NRC kA rating Cat. No. Price $
20 36 kA S125NJ320PM
32 36 kA S125NJ332PM
50 65 kA S125GJ350PM
63 65 kA S125GJ363PM
100 65 kA S125GJ3100PM
125 65 kA S125GJ3125PM
160 65 kA S160GJ3160PM
250 65 kA S250GJ3250PM
PM 400 70 kA S400GE3400PM
630 (530 A) 2) 70 kA S630GE3630PM
MCCB panel mounting bases
3 pole kit for 125 AF 3) T2PM12A3A
4 pole kit for 125 AF 3) T2PM12A4A
3
3 pole kit for 160/250 AF ) T2PM25A3A
3
4 pole kit for 160/250 AF ) T2PM25A4A
3 pole kit for 400/630 AF 3) T2PM40A3A
T2PM base 4 pole kit for 400/630 AF 3) T2PM40A4A
+ MCCB Control wiring terminals for plug-in MCCBs 3) 4) 5)
3 pin plug for aux/alarm - 2H6959CAA1
MCCB side
3 pin plug for shunt/UVT - 2H6959CBA1
MCCB side
3 pin socket for panel mount T2TP003A
section
3
4 pole kit of 4 bars T2PF254BA
S400, S630
3 pole kit of 3 bars T2PF403BA
4 pole kit of 4 bars T2PF404BA
TemBreak 2 MCCB
3 Ampere
Range Icu
TemBreak 2 415 V kA
Ics
Thermal-
able
TemBreak 2
Mag. Adjust- Electronic Catalogue
Adjustment Number
12.5 – 125 25 19 Yes – E125NJ
16 – 125 25 13 No – S125NF
15 – 100 65 33 No – S100GF
12.5 – 125 36 36 Yes – S125NJ
12.5 – 125 65 36 Yes – S125GJ
12.5 – 125 125 85 Yes – H125NJ
12.5 – 125 200 150 Yes – L125NJ
16 – 160 25 19 No – S160NF
12.5 – 160 36 36 Yes – S160NJ
32 – 160 65 36 Yes – S160GJ
100 – 160 125 85 Yes – H160NJ
100 – 160 200 150 Yes – L160NJ
12.5 –250 25 19 Yes – E250NJ
160 – 250 36 36 Yes – S250NJ
160 – 250 65 36 Yes – S250GJ
16 – 250 70 70 – Yes S250PE
160 – 250 125 85 Yes – H250NJ
16 – 250 125 85 – Yes H250NE
160 – 250 200 150 Yes – L250NJ
100 – 400 25 25 Yes – E400NJ
160 – 400 36 36 Yes – S400CJ
160 – 400 50 50 Yes – S400NJ
100 – 400 50 50 – Yes S400NE
160 – 400 70 50 Yes – S400GJ
100 – 400 70 50 – Yes S400GE
100 – 400 85 85 – Yes S400PE
100 – 400 125 85 – Yes H400NE
100 – 400 200 150 – Yes L400NE
252 – 630 36 36 – Yes E630NE
252 – 630 50 50 – Yes S630CE
252 – 630 70 50 – Yes S630GE
Notes: The above equivalents are approximate only. Physical sizes may vary slightly
as well as kA ratings.
TemBreak 1 MCCB
Notes: MCCBs with the same colours have the same outline dimensions, though in
the case of 400 AF & 630 AF, main terminal heights vary.
TemBreak 2 MCCB
3 Ampere
Range Icu
TemBreak 2 415 V kA
Ics
Thermal-
Mag Adjust-
able
TemBreak 2
Electronic Catalogue
Adjustment Number
125 2 – – – S125NN
160 3 – – – S160NN
250 3 – – – S250NN
400 5 – – – S400NN
630 5 – – – S630NN
TemBreak 1 MCCB
Notes: The above equivalents are approximate only. Physical sizes may vary slightly
as well as
kA ratings.
4-1
Valid until August 2014
MCCB Chassis
Features
Q Complies with AS/NZS 3439, AS/NZS 3000 - 2007
Q Suits TemBreak MCCBs 125-250 A
Q Top and bottom fed
Q Busbars fully insulated
Q Side mounting rail now standard for quicker mounting on all chassis
Q XA and XB chassis now rated up to : 36 kA for 1 second
40 kA for 0.5 seconds
XA 630 and XA 800
Suits E125, S125, ZS125 MCCBs
Cutout 1) Pan
No. Height Height 630 A 800 A
Poles (mm) (mm) Cat. No. Price $ Cat. No. Price $)
6 92 90 XA6306U XA8006U
12
18
182
272
180
270
XA63012U
XA63018U
XA80012U
XA80018U
4
24 362 360 XA63024U XA80024U
30 452 450 XA63030U XA80030U
36 542 540 XA63036U XA80036U
42 632 630 XA63042U XA80042U
48 722 720 XA63048U XA80048U
60 902 900 XA63060U XA80060U
72 1082 1080 XA63072U XA80072U
XB 800
Suits S160, S250NJ, S250GJ, ZS250 MCCBs (not S250PE)
No. Cutout 1) Pan 800 A
Poles Height (mm) Height (mm) Cat. No. Price $)
6 107 105 XB8006U
12 212 210 XB80012U
18 317 315 XB80018U
24 422 420 XB80024U
30 527 525 XB80030U
36 632 630 XB80036U
42 737 735 XB80042U
48 842 840 XB80048U
60 1052 1050 XB80060U
72 1262 1260 XB80072U
Notes: 1
) The length of the escutcheon cut-out.
2
) Busbars extend 50 mm beyond the pan length at the top and bottom
on XA, XB, XC chassis.
Features
Q Complies with AS/NZS 3439, AS/NZS 3000 - 2007
Q Suits TemBreak MCCBs 125-250 A
Q Top and bottom fed
Q Busbars fully insulated
Q Side mounting rail now standard for quicker mounting
on all chassis
Q XA and XB chassis now rated up to : 36 kA for 1 second
40 kA for 0.5 seconds
XB 800
Suits S160, S250NJ, S250GJ, ZS250 MCCBs (not S250PE)
No. Cutout 1) Pan 800 A
Poles Height (mm) Height (mm) Cat. No. Price $
8 142 175 XB8008U4POLE
16 282 315 XB80016U4POLE
24 422 455 XB80024U4POLE
32 562 595 XB80032U4POLE
40 702 735 XB80040U4POLE
48 842 875 XB80048U4POLE
Features
Q Single sided MCCB mounting
Q Different chassis for left or right side MCCB mounting
Q Complies with AS/NZS 3439, AS/NZS 3000 - 2007
Q Suits TemBreak, 160 / 250 A Frame MCCBs
Q Current ratings of MCCBs range 12 A to 250 A
Q Top and bottom fed
Q Busbars fully insulated
Q Side mounting rail now standard for quicker mounting on
all chassis
Q XA and XB chassis now rated up to : 36 kA for 1 second
40 kA for 0.5 seconds
Single Sided Chassis
Suits S160NJ, E250NJ, S250NJ, S160GJ, S250GJ, ZS250 MCCBs
(not S250PE) 4
XB SSL 800
LEFT hand single sided 3 pole (MCCB loadside connections at LEFT)
Pan
No. Cutout 1) Height 800 A
Poles Height (mm) (mm) Cat. No. 2) Price $
3 107 105 XBSSL 800 3U
6 212 210 XBSSL 800 6U
9 317 315 XBSSL 800 9U
12 422 420 XBSSL 800 12U
15 527 525 XBSSL 800 15U
18 632 630 XBSSL 800 18U
21 737 735 XBSSL 800 21U
24 842 840 XBSSL 800 24U
30 1052 1050 XBSSL 800 30U
36 1262 1260 XBSSL 800 36U
) Busbars extend 50 mm beyond the pan length at the top and bottom
2
XB SSR 800
RIGHT hand single sided 3 pole (MCCB loadside connections at RIGHT)
Pan
No. Cutout 1) Height 800 A
Poles Height (mm) (mm) Cat. No. 2) Price $
3 107 105 XBSSR 800 3U
6 212 210 XBSSR 800 6U
9 317 315 XBSSR 800 9U
12 422 420 XBSSR 800 12U
15 527 525 XBSSR 800 15U
18 632 630 XBSSR 800 18U
21 737 735 XBSSR 800 21U
24 842 840 XBSSR 800 24U
30 1052 1050 XBSSR 800 30U
4 36 1262 1260 XBSSR 800 36U
) Busbars extend 50 mm beyond the pan length at the top and bottom
2
Features
Q Complies with AS/NZS 3439, AS/NZS 3000 - 2007
Q Suits TemBreak MCCB amp ratings 20 A - 400 A
Q Top and bottom fed
Q Busbars fully insulated
Q Side mounting rail now standard for quicker
mounting on all chassis
Q XC chassis now rated up to : 50 kA for 1 second
65 kA for 0.5 second
Q Now stocked with combinations of 250 A and
400 A tee offs 40 kA for 0.5 seconds
XC 1000
Suits S160, E250, S250NJ, S250GJ, ZS250 MCCBs 2) (not S250PE)
No.
Poles
6
Cutout 1)
Height (mm)
107
Pan
Height (mm)
170
Cat. No.
XC10006U
1000 A
Price $ 4
12 212 275 XC100012U
18 317 380 XC100018U
24 422 485 XC100024U
30 527 590 XC100030U
36 632 695 XC100036U
42 737 800 XC100042U
48 842 905 XC100048U
XC 1000 Chassis
Suits 250 A and 400 A MCCBs 1) (not S250PE)
As an alternative to a larger high current chassis, where only up to 2 x 400 A
and up to 12 x 68 mm deep 250 A MCCBs need to be installed, the
configurations of stocked XC chassis below can be used.
Pan Chassis configured 1000 A
Height (mm) for MCCBs below 1) 2) Cat. No. Price $
415 1 x 400 A and 4 x 250 A XC10001X4R12U
625 1 x 400 A and 8 x 250 A XC10001X4R24U
835 1 x 400 A and 12 x 250 A XC10001X4R36U
555 2 x 400 A and 4 x 250 A XC10002X4R12U
765 2 x 400 A and 8 x 250 A XC10002X4R24U
975 2 x 400 A and 12 x 250 A XC10002X4R36U
Chassis
to suit 125 – 250 AF MCCBs
Testing
4
TemWay chassis have been unconditionally type tested (without MCCBs
fitted) at the above short time kA ratings (Icw).
MCCB dimensions (mm) MCCB dimensions (mm)
H W D H W D
E125, S125NJ/GJ, ZS125 E400, S400
1 pole 155 30 68 1 pole – – –
3 pole 155 90 68 3 pole 260 140 103
S160, S250NJ/GJ, ZS250
1 pole 165 40 68
3 pole 165 105 68
104 mm 80 mm 104 mm
H )
3
Installation considerations
Q MCCBs on the chassis are to be reverse connected, that is, connect the
‘bottom’ of breaker to the chassis tee offs
Q Terminal or interpole barriers or “other adequate insulation material”
must be fitted at MCCB load side, (top of MCCB) which is the gas venting
end of the MCCB
4 T2CF Short
terminal
cover
T2CS flush
terminal
cover
T2CF Standard (optional)
terminal cover
T2BA No cover
Interpole barriers (optional)
XBSSL8009U
Single Sided Chassis
XB80018U
Double Sided Chassis
Cover
Suit MCCB types length Cat. No. Price $
Flush E125, S125
IP 20
covers 1 pole cover - set of 2 - T2CS121SG
(FC) 2 pole cover - set of 2 - T2CS122SG
3 pole cover - set of 2 - T2CS123SG
4 pole cover - set of 2 - T2CS124SG
H125, S160, H160, E250, S250, H250
1 pole cover - set of 2 - T2CS251SG
3 pole cover - set of 2 - T2CS253SG
4 pole cover - set of 2 - T2CS254SG
E400, S400, H400, E630, S630
3 pole cover set T2CR403SG
- RC cov c/w cut-outs
Start
4 pole cover set
- RC cov c/w cut-outs T2CR404SG 4
E125, S125
terminal 3 pole cover set of 2 22 mm T2CF123SSNBA
covers
(FC) 4 pole cover set of 2 22 mm T2CF124SSNBA
S160, E250, S250 – except S250PE
3 pole cover set of 2 30 mm T2CF253SSNBA
4 pole cover set of 2 30 mm T2CF254SSNBA
Extended E125, S125
terminal
covers 1 pole cover – set of 2 40 mm T2CF121SLNG
(FC) 3 pole cover – set of 2 40 mm T2CF123SLNG
4 pole cover – set of 2 40 mm T2CF124SLNG
S160, E250NJ, S250NJ, S250GJ (not S250PE)
1 pole cover – set of 2 55 mm T2CF161SLNG
3 pole cover – set of 2 55 mm T2CF253SLNG
4 pole cover – set of 2 55 mm T2CF254SLNG
H125, H160, S250PE, H250
3 pole cover – set of 2 55 mm T2CF253LLNG
4 pole cover – set of 2 55 mm T2CF254LLNG
E400, S400, H400, E630, S630
3 pole cover – narrow – 80 mm T2CF403SLNG
set of 2
3 pole cover – wide – 110 mm T2CF403SWNG
set of 2
XS630, XH630, XS800, XH800
3 pole cover – set of 2 130 mm 2H1417DAB
400/630 IP20 pole insert - order 1 per
A narrow terminal - 2A1787DBA
and wide XS1250
terminal
cover 3 pole cover – set of 2 130 mm 2H1419DAB
options IP20 pole insert - order 1 per
shown terminal - 2A1787DBA
Features
Q Double sided 3 pole MCCB chassis
Q Compact single sided chassis 3 or 4 pole
Q 1250 A, 1600 A or 2200 A rated main bars
Q 11 enclosure sizes for economical chassis sizing
Q Front connect tags supplied as standard
Q Complies with AS/NZS 3439, AS/NZS 3000 - 2007
Q Form of separation 4bih. AS/NZS 3439.1 : 2000
(Annex ZF)
Q Circuit breakers are reverse fed as standard
Q 4th pole neutral bars 100 % rated
Q Accepts MCCBs rated 12 A to 1250 A
Q Ordering: choose from pre-assembled types, or
custom assembly
Stocked assembled chassis selection - Suit MCCB amp frames shown
below:
4
Main
bar
rating Chassis800 A 630 A 400 A 250 A
(A) Size 6 units 5 units 4 units 3 units Cat. No. Price $
1600 A DS - 2 x 630 2 x 400 4 x 250 HCSTD1DS16153
1600 A DS - 4 x 630 - 8 x 250 HCSTD2DS16243
1600 A SS left - 1 x 630 1 x 400 2 x 250 HCSTD3SSL16153
1600 A SS right- 1 x 630 1 x 400 2 x 250 HCSTD4SSR16153
1600 A SS left - 1 x 630 1 x 400 4 x 250 HCSTD5SSL16213
1600 A SS right- 1 x 630 1 x 400 4 x 250 HCSTD6SSR16213
2200 A SS left 1 x 800 1 x 630 1 x 400 3 x 250 HCSTD7SSL22243
2200 A SS right1 x 800 1 x 630 1 x 400 3 x 250 HCSTD8SSR22243
Ordering notes
4
1
) Add tee offs as required to the chassis enclosure to complete the chassis
components list.
2
) Note: If MCCB below 32 A and a kA rating above 30 kA are required, use
H125NJ320 and H125NJ332 with 250 A Tee Off Catalogue Number above.
3
) 400 A MCCBs fitted with a same width narrow cover are 4 units in width.
4
) 630 A MCCBs fitted with a ‘wide’ width cover are 5 units in width.
5
) For ordering, use order from chassis catalogue or contact NHP.
6
) All MCCBs to be reverse fitted on chassis.
Example: Chassis
MCCBS: Single sided chassis components Quantity
800 A Chassis box 1600 A, less HC16183 1
tee offs
800 A left load tee off set HCL800 1
630 A
630 A left load tee off set HCLW630 1
400 A 400 A left load tee off set HCLN630 1
250 A 250 A left load tee off set HCL250 1
250 A left load tee off set HCL250 1
250 A
Testing
The HC chassis has been unconditionally type tested (no MCCBs fitted) in
Australia, at a short time rating of 65 kA for 1 second.
Notes: 1) Refer to NHP for HC chassis with new TemBreak 2 800 A - 1250 A MCCBs.
Bottom or top extended main bar are optional.
For MCCB terminal cover selection use refer pages 4 - 13 and 4 - 14
Chassis to suit:
TemBreak 2 125 A - 630 AF, TemBreak 1 630 A - 1250 A
5-1
Valid until August 2014
Transfer switches
Transfer Switches
MTS
BTS
ATS
Normal
Left
3P Emergency
Right
3P
Changeover
logic panel / + 5
Controller
OR Electronic controller
with interface panel
(TL101CIP)
Relay/Timer
Controller
(TLP2)
TemBreak 1 transfer switches are factory assembled, and range from 400
A to 2500 A. The switches are interlocked via rear mounted walking beam
interlock, or are available with a rod or cable interlock in sizes 400 A to 2500 A.
Common loadside busbars (CLSBB) are an option.
A basic transfer switch fitted with motors, can be coupled with a TemLogic
control panel TL101 electronic controller or TLP1 relay controller that will
automatically changeover to a standby power supply in the event of power
failure. The transfer switches are fitted with a mechanical interlock so as to
prevent both breakers from being switched to the ON position at the same
time.
Basic types
MTS
BTS
ATS
Logic panel +
Electronic controller
plus interface panel
(TL101CIP)
5
OR
E125, S125, H125, L125, S160, H160, L160, E250, S250, H250, L250, E400,
S400, H400, L400, E630, S630, XS630, XH630, XS800, XH800, XS1250, XS1600,
XS2000, XS2500
5 S160GJ
S160GJ
S160GJ
40-63 65
63-100 65
100-160 65
279 340 180
BTSS16GJ6334
BTSS16GJ10034
BTSS16GJ16034
BTSS16GJ6343
BTSS16GJ10043
BTSS16GJ16043
S250GJ 160-250 65 BTSS2GJ25034 BTSS2GJ25043
S250PE 50-125 70 BTSS2PE12534 BTSS2PE12543
279 340 215
S250PE 100-250 70 BTSS2PE25034 BTSS2PE25043
S400NJ 160-250 50 BTSS4NJ25034 BTSS4NJ25043
S400NJ 250-400 50 BTSS4NJ40034 BTSS4NJ40043
S400GJ 160-250 70 BTSS4GJ25034 BTSS4GJ25043
S400GJ 250-400 70 BTSS4GJ40034 BTSS4GJ40043
360 415 244
S400NE 100-250 50 BTSS4NE25034 BTSS4NE25043
S400NE 160-400 50 BTSS4NE40034 BTSS4NE40043
S400GE 100-250 70 BTSS4GE25034 BTSS4GE25043
S400GE 160-400 70 BTSS4GE40034 BTSS4GE40043
S630CE 315-630 50 BTSS6CE63034 BTSS6CE63043
S630GE 315-630 70 BTSS6GE63034 BTSS6GE63043
Notes: Transfer switches are stocked off the shelf in sizes 125 A to 630 A in some
sizes, while others are made to order. Contact NHP for availability.
Refer following pages for information on TLP2 logic and TL101 electronic
changeover controllers.
Transfer switch ‘kits’ are also available for quick on-site assembly of the
above transfer switches. Refer following pages.
Wire interlocks must be used for transfer switches combining MCCBs of
different frame size (different heights).
1
Manual transfer switches
3 and 4 pole
Features / options:
Q 3 or 4 pole types
Q Rear walking beam interlock used
Q Pre-assembled and wired on a mounting plate
Q Will accept handles
Q Common load side busbar option
Q Conforms to AS/NZS 60947.6.1
MTS selection chart and catalogue numbers
Inter- Overall
rupting (3 pole) 2)
capac- dimensions
ity (mm) 3 pole 4 pole
MCCBs Ampere (400 V) MTS MTS
used range Icu Ics W H 1) D Cat. No. 3) Cat. No. 3)
XS630NJ 250-400 50 25 550 433 182 MS6N433 MS6N444
XS630NJ 400-630 50 25 550 433 182 MS6N633 MS6N644
XS630SE 315-630 50 25 550 433 182 MS6S633 MS6S644
XH630SE 315-630 65 33 550 433 182 MH6S633 MH6S644
XS800NJ 500-800 50 25 550 433 182 MS8N833 MS8N844
5
XS800SE 400-800 50 25 550 433 182 MS8S833 MS8S844
XH800PE 400-800 65 50 550 433 182 MH8P833 MH8P844
XS1250SE 500-1000 85 65 553 570 198 MS12S1033 MS12S1044
XS1250SE 625-1250 85 65 553 550 198 MS12S1233 MS12S1244
XS1600SE 800-1600 100 75 553 570 198 MS16S1633 MS16S1644
XS2000SE 1000-2000 85 64 774 450 361 MS20E2033 MS20E2044
XS2500SE 1250-2500 85 64 774 450 361 MS25E2533 MS25E2544
ON
F
OF
ON
F
OF
1
Basic transfer switches (BTS) with motor
3 and 4 pole
Features / options:
Q Motor driven MCCBs
Q 3 or 4 pole types
Q Rear walking beam interlock used
Q Pre-assembled and wired on a mounting plate
Q Automatic changeover controller option
Q A choice of Relay-Logic, or electronic controllers
Q Common load side busbar option
Q Conforms to AS/NZS 60947.6.1
Application notes:
Q When a TL101CIP electronic controller plus interface panel is used with a
TemBreak 1 transfer switch, an interconnection wire loom consisting of
2 cables is also required. This wire loom connects between the interface
panel and the standard terminals on the transfer switch. The Cat. No. of
the interconnection cable is “TLP2L1CABLE”. The cables are 0.5 m long.
Longer cable lengths are an option up to 2 metres. Refer page 5 - 32.
Q When TLP1 relay controllers are used, an interconnection cable is not
required.
Q TLP2 relay controllers for TemBreak 2 transfer switches cannot be used
POWER PROTECTION
TRASNFER SWITCH
INTERFACE PANEL
5 2
Link mechanical interlock
For 3 or 4 pole MCCB right side
For 3 pole MCCB left side
For 4 pole MCCB left side
3 Left & right side 1 C/O alarm switches Wire type alarm
Left & right side 2 C/O auxiliary
4 Wire type auxiliary
switches
5 240 V AC Motor operator Other voltages available
6 Interlock connection wire For motor electrical interlocking 4)
7 WAGO male connector - Left For TLP2 / TL101 controllers only
8 WAGO male connector - Right For TLP2 / TL101 controllers only
9 Optional 3 & 4P mounting plate With pre threaded mounting holes
Notes: 1) The left and right side MCCBs have to be the same depth for correct
interlocking function.
2
) Where E / S and H / L MCCBs of a different height need to be interlocked,
a Cable Interlock must be used. Refer following pages.
3
) MCCB marker and capacity size labels can be ordered for mounting on
motors etc. Use ratings label sheet Cat. No. T25CAPLAB.
4
) One electrical interlock wiring loom is required between motors on
motorised transfer switches.
Component quantity
BTS Cat. No.
2 E125, S125NJ/GJ
1 T2ML12RA
1 T2ML12L3A
1 T2ML12L4A
2 T2AL00M3SWA
4 T2AX00M3SWA
2 T2MC12A24NB
1 T2MM25L05A
1 231-612-019-000
1 231-642-019-000
1 T2SB123334
1 T2SB124344
2 H125NJ, L125NJ
1
1
1
T2ML125RA
T2ML125L3A
T2ML125L4A
5
2 T2AL00M3SWA
4 T2AX00M3SWA
2 T2MC25A24NB
1 T2MM25L05A
1 231-612-019-000
1 231-642-019-000
1 T2SB2533344344
Electrical interlocking
lead T2MM
Notes: 1) The left and right side MCCBs have to be the same depth for correct
interlocking function.
2
) Where E / S and H / L MCCBs of a different height need to be interlocked,
a Cable Interlock must be used. Refer following pages.
3
) MCCB marker and capacity size labels can be ordered for mounting on
motors etc. Use ratings label sheet Cat. No. T25CAPLAB.
4
) One electrical interlock wiring loom is required between motors on
motorised transfer switches.
Component quantity
BTS Cat. No.
2 S160NJ / GJ
ES250NJ / GJ
2 H160,S250PE
H250NJ / NE
1 T2ML25RA
1 T2ML25L3A
1 T2ML25L4A
2 T2AL00M3SWA
4 T2AX00M3SWA
2 T2MC25A24NB
1 T2MM25L05A
1 231-612-019-000
1 231-642-019-000
1 T2SB253334344
5
Electrical interlocking
lead T2MM
5
7 Interlock connection wire For motor electrical interlocking
8 WAGO male connector - Left For TLP2 / TL101 controllers only
9 WAGO male connector - Right For TLP2 / TL101 controllers only
10 Optional 3P: 3P mounting plate With pre threaded mounting holes
11 Optional 4P: 4P / 4P: 3P mounting With pre threaded mounting holes
plate
Component quantity
BTS Cat. No.
2 E400NJ
S400CJ
S400NJ
S400NE
S400GJ
S400GE
2 H400NE
L400NE
1 T2ML40RB
1 T2ML40L3B
1 T2ML40L4B
_ T2MLH40RB
_ T2MLH40L3B
_ T2MLH40L4B
2 T2AL00M3SWA
4 T2AX00M3SWA
2 T2MC40A10NB
5
1 T2MM40L06A
1 231-612-019-000
1 231-642-019-000
1 T2TSB403334MP
1 T2TSB404344MP
5
9 Optional 3P: 3P mounting plate With pre threaded mounting holes
10 Optional 4P: 4P / 4P: 3P mounting With pre threaded mounting holes
plate
Notes: 1) The Left and Right side MCCBs have to be the same depth for correct
interlocking function.
2
) Where E / S and H / L MCCBs of a different height need to be interlocked,
a Cable Interlock must be used. Refer following pages.
3
) MCCB marker and capacity size labels can be ordered for mounting on
motors etc. Use ratings label sheet Cat. No. T40CAPLAB.
4
) One electrical interlock wiring loom is required between motors on
motorised transfer switches.
5
) 400 A / 630 A link interlocks must use handles for manual transfer
switches.
6
) An alternative interlock type is the manual ‘slide interlock’, which does
not require a handle to be fitted. Refer S630 Accessories in Section 3.
Component quantity
BTS Cat. No.
2 E630NE
S630CE / GE
1 T2ML40RB
1 T2ML40L3B
1 T2ML40L4B
_ T2MLH40RB
_ T2MLH40L3B
_ T2MLH40L4B
2 T2AL00M3SWA
4 T2AX00M3SWA
2 T2MC40A10NB
1 T2MM40L06A
1 231-612-019-000
1 231-642-019-000
5
1 T2TSB403334MP
1 T2TSB404344MP
5
Item Description Comment
1 Left and right side MCCBs MCCB depth 103 mm 1)
2 Cable mechanical interlock For 3 or 4 pole MCCBs
1.0 m length of cable - option 1
1.5 m length of cable - option 2
3 Left & right side 1 C/O alarm switches Wire type alarm
4 Left & right side 2 C/O auxiliary Wire type auxiliary
switches
5 240 V AC Motor operator Other voltages available
6 Interlock connection wire For motor electrical interlocking 4)
7 WAGO male connector - Left For TLP2 / TL101 controllers only
8 WAGO male connector - Right For TLP2 / TL101 controllers only
9 Optional 3P:3P mounting plate With pre threaded mounting holes
10 Optional 4P:4P / 4P:3P mounting With pre threaded mounting holes
plate
1 1 T2MW12CA
1 1 T2MW00SA
1 1 T2MW00LA
- 2 T2AL00M3SWA
- 4 T2AX00M3SWA
- 2 T2MC12A24NB
- 1 T2MM25L15A
- 1 231-612-019-000
- 1 231-642-019-000
1 1 T2SB123334
1 1 T2SB124344
Component quantity
5
MTS BTS Cat. No.
2 2 H125NJ, L125NJ
1 1 T2MW25CA
1 1 T2MW00SA
1 1
T2MW00LA
- 2 T2AL00M3SWA
- 4 T2AX00M3SWA
- 2 T2MC25A24NB
- 1 T2MM25L15A
- 1 231-612-019-000
- 1 231-642-019-000
1 1 T2SB253334
1 1 T2SB254344
3 Left & right side 1 C/O alarm switch Wire type alarm
4 Left & right side 2 C/O auxiliary Wire type auxiliary
switches
5 240 V AC Motor operator Other voltages available
6 Interlock connection wire For motor electrical interlocking 4)
7 WAGO male connector - Left For TLP2 / TL101 controllers only
8 WAGO male connector - Right For TLP2 / TL101 controllers only
5 9
10
Optional 3P:3P mounting plate
Optional 4P:4P / 4P:3P mounting
plate
With pre threaded mounting holes
With pre threaded mounting holes
Component quantity
MTS BTS Cat. No.
2 2 S160NJ / GJ
ES250NJ / GJ
2 2 H160, S250PE
H250NJ / NE
1 1 T2MW25CA
1 1 T2MW00SA
1 1 T2MW00LA
- 2 T2AL00M3SWA
- 4 T2AX00M3SWA
- 2 T2MC25A24NB
- 1 T2MM25L15A
- 1 231-612-019-000
- 1 231-642-019-000
1
1
1
1
T2SB253334
T2SB254344 5
3 Left & right side 1 C/O alarm switch Wire type alarm
4 Left & right side 2 C/O auxiliary Wire type auxiliary
5
switches
5 240 V AC Motor operator Other voltages available
6 Interlock connection wire For motor electrical interlocking 4)
7 WAGO male connector - Left For TLP2 / TL101 controllers only
8 WAGO male connector - Right For TLP2 / TL101 controllers only
9 Optional 3P:3P mounting plate With pre threaded mounting holes
10 Optional 4P:4P / 4P:3P mounting With pre threaded mounting holes
plate
Component quantity
MTS BTS Cat. No.
2 2 E400NJ
S400CJ
S400NJ
S400NE
S400GJ
S400GE
2 2 H400NJ / NE
L400NJ / NE
– 1 T2MW40CB
– 1 T2MWH40CB
1 1 T2MW00SA
1 1 T2MW00LA
- 2 T2AL00M3SWA
- 4 T2AX00M3SWA
-
-
2
1
T2MC40A10NB
T2MM40L21A
5
- 1 231-612-019-000
- 1 231-642-019-000
1 1 T2TSB403334MP
1 1 T2TSB404344MP
3 Left & right side 1 C/O alarm switches Wire type alarm
4 Left & right side 2 C/O auxiliary Wire type auxiliary
switches
5 240 V AC Motor operator Other voltages available
6 Interlock connection wire For motor electrical interlocking 4)
7 WAGO male connector - Left For TLP2 / TL101 controllers only
8 WAGO male connector - Right For TLP2 / TL101 controllers only
9 Optional 3P:3P mounting plate With pre threaded mounting holes
5
10 Optional 4P:4P / 4P:3P mounting With pre threaded mounting holes
plate
Component quantity
MTS BTS Cat. No.
E630NE
2 2 S630CE / GE
T2MW00CB
1 1 T2MWH40CB
1 _ T2MW00SA
1 1
1 1 T2MW00LA
- 2 T2AL00M3SWA
- 4 T2AX00M3SWA
- 2 T2MC40A10NB
- 1 T2MM40L21A
- 1 231-612-019-000
- 1 231-642-019-000
1 1 T2TSB403334MP
5
1 1 T2TSB404344MP
Notes: 1) NHP has limited the number of gear tray plates to three (3) standard
sizes, which cover all optional features.
2
) NHP stock basic TLP2 logic panels. All others are built to order.
Standard and custom logic panel ordering sheet, refer Catalogue Part C.
Due to component and wiring differences, TemBreak 1 logic panels are not
configured to work with TemBreak 2 Transfer Switches and vice versa.
Do not use TLP1 with TemBreak 2 Motor operators otherwise motor
burnout will occur. Use TLP2 for TemBreak 2.
1
Automatic transfer switches (ATS)
Logic controller for Tembreak 1
Timer / Relay logic controller
NHP offers a choice of electromagnetic (relay) logic panels with various op-
tions, or a PLC controller type. The basic timer/ relay logic controller includes
the following standard features:
Q Voltage and phase sequence sensing relay
Q Time delay normal to emergency and back
Q Common power supply relays
Q Normal supply phase sequence relay
Q Control wiring terminals
Q A 4 position mode selector switch is provided loose
(Manual / Automatic / Test / Off) - SSW1
Q Optional PLC logic panel (TLPC1)
TLP logic controller and options
Description Cat. No. 1) Price $
Logic Panel for Tembreak 1 ATS TLP1
5
2 Emergency supply phase sequence EPSR / EVSR
and voltage sensing relays
3 Emergency supply frequency relay EFR
4 Engine run-on time delay ERTD
5 Engine start time delay ESTD
6 Inhibit return control (Prevents auto- IRC
return to normal from emergency)
7 Cranking limiter time delay CLTD
8 Additional mode ‘Normal supply’ SSW2
Additional contacts for remote
9 indication of mode switch position SSW3
(includes option 8)
10 Alarm lock-out relay (Prevents breaker ALR
closure after MCCB trip.)
11 Changeover time delay COTD
(required for ACB C/O switch)
13 Mains stability timer MST
14 Surge protection – single phase SPD1
15 Surge protection – 3 phase SPD3
Notes: 1) NHP has limited the number of gear tray plates to three (3) standard
sizes, which cover all optional features.
2
) NHP stock basic TLP1 logic panels. All others are built to order.
Standard and custom logic panel ordering sheet, refer catalogue Part C.
Do not use TLP1 with TemBreak 2 Motor operators otherwise motor
burnout will occur. Use TLP2 for TemBreak 2.
TemLogic
TL101 Transfer switch controller
TL101 Provides:
Control of minimum voltage, maximum voltage, phase loss, FOR
TEM
B
asymmetry, minimum frequency, maximum frequency, with & TE REAK 1
MBR
independent enable and delay. TRAN EAK 2
S
SWIT FER
Front panel operation and display CHE
S
5
Refer Part C Section 8 or TL101 manual.
Technical features
Q Flush mount 144 mm housing
2
TemLogic
TL101 Transfer switch controller
Interface panel
The interface panel provides short circuit protection via fuses between the
transfer switch and TL101 controller. The interface panel comes complete with
pre-terminated cable looms, enabling fast ‘plug ‘n’ play’ electrical connection
between system components.
Ordering details - controller and interface panel
Heading Cat. No. Price $
TemLogic2 TL101 controller only TL101240V
TemLogic2 TL101 controller plus interface TL101CIP
panel 2)
TL102 controller plus interface panel. RS 485 TL102CIP
comms included.
TemBreak 1 Transfer switch inter-connection
cable TLP2L1LCABLE 1)
(0.5 m standard length or refer next page)
1
Basic Transfer Switch (BTS)
Inter-connection cable for Tembreak 1 transfer switches using
TLP1 controllers
TLP2L1LCABLE
For use with a TL101 CIP (electronic controller and interface panel) when used
with a TemBreak 1 transfer switch.
The connector cable connects to the standard BTS control wiring terminals.
5
)
TemLogic
Temlogic controller types
For Tembreak 1 and 2 transfer switches
This page is a cross reference of features and options. For more specific infor-
mation on each controller type, refer to the previous pages.
CONTROLLER TYPES Electronic
Features and options cross Relay/Timer Relay/Timer controller
reference 1) controller controller unit
to suit to suit to suit
TemBreak 1 TemBreak 2 TemBreak 1
Standard and optional Cat. MCCBs MCCBs or 2 MCCBs
features No. TLP1 TLP2 TL101
Normal voltage sensing phase (NVSR)
failure relay
Time delay emergency to (TDEN)
normal
Time delay normal to (TDNE)
emergency
Common power supply relay (CPSR)
2 Emergency supply phase (EPSR) 0 0
sequence relay
Emergency supply voltage (EVSR) 0 0
sensing relay
3 Emergency supply frequency (EFR) 0 0
5
relay
4 Engine run-on time delay (ERTD) 0 0
5 Engine start time delay (ESTD) 0 0
6 Inhibit return control (IRC) 0 0
7 Cranking limiter time delay (CLTD) 0 0 –
8 Additional mode selection (SSW2) 0 0
‘Normal supply’
9 Additional contacts for (SSW3) 0 0
remote indication of mode
switch position
10 Alarm lock-out relay (ALR) 0 0
11 Changeover time delay (COTD) 0 0
13 Mains stability timer (MST) 0 0
Interface with building management – 1) – 1)
system
Load shedding control – –
14 Surge protection single phase(SPD1) 0 0 0
15 Surge protection 3 phase (SPD3) 0 0 0
16 Modbus communications – – TL102
required
(RS485)
Notes: 1) PLC logic panels: TLPC2 and TLPC1 are available as options. Refer NHP.
NHP PLC logic panels are ideally suited to BMS applications due to the
multiple I/O of the PLC providing status to the BMS.
TemLogic
Basic Transfer Switches (BTS) and
Manual Transfer Switches (MTS)
Options and accessories
Common loadside busbars – for connection to BOTTOM of MCCBs 2)
Tembreak 2: 250 – 630 A, Tembreak 1: 630 – 1250 A
3 pole CLSBB
Dimensions (mm)
Busbar Amp 3 pole set
Rating H W D Cat. No.
250 A 1) 349 340 176 T2CLSBB25033
400 A 1) 485 415 248 T2CLSBB40033
630 A 1) 505 415 248 T2CLSBB63033
630/800 A 633 550 341 CLSBB63033
1000/1250 950 553 301 CLSBB125033
4 pole CLSBB
Dimensions (mm)
Busbar Amp 4 pole set
Rating H W D Cat. No.
250 A 1) 349 340 176 T2CLSBB25044
400 A 1) 485 460 248 T2CLSBB40044
630 A 1) 505 460 248 T2CLSBB63044
5
630/800 A 633 690 341 CLSBB63044
1000/1250 950 693 301 CLSBB125044
Accessories
to suit 125 - 630 AF MCCBs External accessories
MCCB rating labels
Can be used to identify the MCCBs ratings and type
when a motor or interlock is fitted to an MCCB.
125 AF T12CAPLAB
160/250 AF T25CAPLAB
400/630 AF T40CAPLAB
Left side Marker Rights side Marker Per label
MCCB types label Cat. No. label Cat. No. Price $
E125NJ 2H4322SAB 2H4324SAA
S125NJ 2H4223SAB 2H4218SAA
S125GJ 2H4223SAB 2H4219SAA
H125NJ 2H4299SAA 2H4307SAA
5
L125NJ 2H4300SAA 2H4308SAA
S160NJ 2H4227SAB 2H4221SAB
S160GJ 2H4227SAB 2H4222SAB
H160NJ 2H4299SAA 2H4307SAA
L160NJ 2H4300SAA 2H4308SAA
E250NJ 2H4224SAB 2H4220SAA
S250NJ 2H4227SAB 2H4221SAB
S250GJ 2H4227SAB 2H4222SAB
S250PE 2H4277SAB 2H6972SAA
H250NJ 2H4299SAA 2H4307SAA
H250NE 2H4299SAA 2H6973SAA
L250NJ 2H4300SAA 2H4308SAA
E400NJ 2H5161SAB 2H5162SAA
E400CJ 2H5153SAB 2H5331SAA
S400NJ 2H5153SAB 2H5154SAA
S400GJ 2H5153SAB 2H5155SAA
S400GE 2H5153SAB 2H6198SAA
E630NE 2H5161SAB 2H6871SAA
S630CE 2H5153SAB 2H6872SAA
S630GE 2H5153SAB 2H6873SAA
Isolator switches
S125NN 2H4645SAB 2H4648SAB
S160NN 2H4650SAC 2H4653SAB
S250NN 2H4650SAC 2H4653SAB
S400NN 2H5364SAC 2H5365SAB
S630NN 2H5364SAC 2H5365SAB
6-1
Valid until August 2014
MCCBs
TemBreak 1 – selection and location guide
6 400-800
400-800
400-800
50
65
65
Electronic
Electronic
Electronic
50-100 %
50-100 %
50-100 %
XS800SE
XH800SE
XH800PE
6
6
6
500-1250 85 Electronic 50-100 % XS1250SE 6
800-1600 100 Electronic 50-100 % XS1600SE 6
1000-2000 85 Electronic 50-100 % XS2000NE 3
1250-2500 85 Electronic 50-100 % XS2500NE 3
12.5-100 85 Thermal magnetic 63-100 % TL100NJ -
100-250 85 Thermal magnetic 63-100 % TL250NJ -
200-400 85 Electronic 50-100 % TL400NE -
315-630 125 Electronic 50-100 % TL630NE 6
400-800 125 Electronic 50-100 % TL800NE 6
500-1250 125 Electronic 50-100 % TL1250NE 6
630-2500 20-40Magnetic 63-100 % XS-ND 3
15-100 10 Thermal magnetic Fixed TL100EM 6
80-400 12.5 Electronic 50-100 % XV400NE 6
200-630 18 Electronic 50-100 % XV630PE 6
400-800 18 Electronic 50-100 % XV800PE 6
200-1250 20 Electronic 50-100 % XV1250NE 6
Notes: TemBreak 1 and 2 cross reference chart, refer section 3.
This table can be used as a guide for situations where an older TemBreak 1
MCCB must be used. TemBreak 1 consists of the ‘TemBreak’ and ‘TemBreak
PLUS’ series of MCCBs.
The breakers marked ‘stocked’ can be used to replace those others which are
not stocked. The stocked types will typically have a higher kA rating. 2)
Mining MCCBs
Base current TB1 type stocked MCCB type
Amps kA rating OCR type adjustment in 2014 Cat. No.
15-100 10 Therm MagFixed stocked TL100EM
80-400 12.5 Therm MagFixed stocked XV400NE
200-630 18 Electronic 50-100 % stocked XV630PE
400-800 18 Electronic 50-100 % stocked XV800PE
200-1250 20 Electronic 50-100 % stocked XV1250NE
6 kA
Current rating: 12.5-125 A
Approvals and tests: Standards AS/NZS 3947-2, and
IEC60947-2
Interrupting capacity:
Voltage Icu kA Ics kA Types
AC 1100 4 4 20 A, 32 A
use 1100 6 4 50 A, 63 A, 100 A, 125 A
Trip unit:
Adjustable thermal: 63 % Ir to 100% Ir
Adjustable magnetic: 6 x Im to 12 x Im for 20 – 100 A trip unit types
6 x Im to 10 x Im for 125 A trip unit types
Dimensions (mm)
NEW
Poles 3
H 155
W 90
D (less toggle) 68
6
20 12.5 20 120 240 VS125NJ320
32 20 32 192 384 VS125NJ332
50 32 50 300 600 VS125NJ350
63 40 63 378 756 VS125NJ363
100 63 100 600 1200 VS125NJ3100
125 80 125 750 1250 VS125NJ3125
Notes:
• The rear insulation barrier, interpole barriers, and terminal screw caps supplied
with the MCCB, must be used for MCCB installation.
• Terminal covers are optional, though either terminal covers or interpole
barriers must be used on the MCCB line-side.
• For internal and external accessory selection refer TemBreak 2 standard
125/250 AF accessories, section 3.
• NRC: Nominal rated current
• Adj. Ir: Adjustable thermal setting
• Adj. Im: Adjustable magnetic setting
• Replaces: TL100EM. Check exact ratings and dimensions to suit your
application requirement.
6 kA
Current rating: 100 – 250A
Approvals and tests: Standards AS/NZS 3947-2, and
IEC60947-2
Interrupting capacity:
Voltage Icu kA Ics kA
AC use 1100 6 4
Trip unit:
Adjustable thermal: 63% Ir to 100% Ir
Adjustable magnetic: 6 x Im to 13 x Im for 160 A trip unit types NEW
6 x Im to 10 x Im for 250 A trip unit types
Dimensions (mm)
Poles 3
H 165
W 105
D (less toggle) 68
6
160 100 160 960 2080 VS250NJ3160
250 160 250 1500 2500 VS250NJ3250
Notes:
• The rear insulation barrier, interpole barriers, and terminal screw caps supplied
with the MCCB, must be used for MCCB installation.
• Terminal covers are optional, though either terminal covers or interpole
barriers must be used on the MCCB line-side.
• For internal and external accessory selection refer TemBreak 2 standard
125/250 AF accessories, section 3.
• NRC: Nominal rated current
• Adj. Ir: Adjustable thermal setting
• Adj. Im: Adjustable magnetic setting
TemBreak 1000 V
mining circuit breakers TL100EM
50 kA
Current rating: 15-100 A
Approvals and tests: Complies with AS 2184 /
AS/NZS 3947-2
Complies with IEC 60947-2
Interrupting capacity: 10 kA at 900 V AC (sym)
6.5 kA at 1100 V AC (sym) 1)
Trip unit: Fixed
Thermal setting: Fixed 40 °C industrial
45 °C and 50 °C marine
Magnetic setting: Fixed
Dimensions (mm)
Poles 3
H 165
W 105
D (less toggle) 125
Weight (kg) 3.2
6
40 TL100EM 40 3K
50 TL100EM 50 3K
60 TL100EM 60 3K
75 TL100EM 75 3K
100 TL100EM 100 3K
Refe
r
page previous
sf
VS12 or new
1000 5/250
V MC
CBs
Accessories
to suit TL100EM / F
Internal accessories
Description Cat. No. Price $
Shunt trips 110 V AC sht (100-115 V) 7VF 2M1
240 V AC sht (200-480 V) 7VF 2M2-B
48 V DC sht 7VF 2M6
24 V DC sht 7VF 2M7
Undervoltage 440 V AC 7UF 2D5B
trips 110 V AC 7UF 2D6B
240 V AC 7UF 2D7B
110 V DC 7UF 2FD1
24 V DC 7UF 2FD2
Auxiliary AUX SW right hand 1C 7XA 2D31B
switches AUX SW left hand 1C 7XA 2D41B
Alarm switches ALT SW right hand 7AB 2D11B
External accessories
Description Cat. No. Price $
Rear connect 3 P RC studs (6) 7RC 2LE
studs
Handle Door interlocking handle kit TFH 22D
operators IP 55 handle kit (plastic) TL100EMR5GM
IP 65 handle kit (plastic) TL100EMR6BN 1)
IP 65 handle kit (metal) YASD22D
IP 55 direct mounting handle TFJ 22LU
kit
TemBreak 1000 V
mining circuit breakers Electronic XV400NE
12.5 kA
Current rating: 80-400 A
Approvals and tests: Standards AS/NZS 3947-2
Complies with IEC 60947-2
Interrupting capacity: 12.5 kA at 1000/1100 V AC,
(IEC 60947-2)
Trip unit:
Trip unit: Fixed
LTD adjustment: I : 0.8-1
1
t: 5-30 s
STD adjustment: I : 2-10
2
t: 0.1-0.3 s
INST adjustment: I : 3-12
3
Dimensions (mm)
Poles 3
H 260
W 140
D (Less toggle) 103
Weight (kg) 5.0
Amp
rating
NRC ASR Min. ASR Max. Cat. No. Price $
160 80 160 XV400NE 160 3K 2)
250
400
125
200
250
400
XV400NE 250 3K 2)
XV400NE 400 3K 2) 6
XV400 MINING BREAKERS MUST
USE LINE-SIDE TERMINAL COVERS,
TERMINAL BOLT COVERS and REAR
INSULATION PLATES.
All items supplied with breaker 1) 3)
Notes: 1) Applicable for front connect MCCBs. Contact NHP for rear connect
details.
2
) For FAULT INDICATION option add ‘FI’ and nominate control voltage.
3
) Installation and incoming connection information is supplied
with each MCCB or can be requested from NHP.
NRC: Nominal rated current
ASR: Adjustable setting range
Overcurrent trip combinations: (specify combinations req.)
LSI - standard,
LS - optional,
LSIP - optional (pre-trip alarm).
Special current ratings available on indent, refer NHP.
Accessories
to suit 400 AF
Internal accessories
Description Cat. No. Price $
Shunt trips 110 V AC/DC (100 - 115 V) 2H1305BAA
240 V AC (200 - 480 V) 2H1306BAA
12 V DC 2H1307BAA
24 V DC 2H1308BAA
48 V DC 2H1309BAA
24 V AC 2H1311BAA
Undervoltage AC coil 1) 2H1492BAA
trips 100-230 V DC coil 2) 2H1493BAA
24 V DC coil 2) 2H1494BAA
48 V DC coil 2) 2H1495BAA
60 V DC coil 2) 2H1496BAA
110 V AC instantaneous UXUB0013B
controller
240 V AC instantaneous UXUB0014B
controller
440 V AC instantaneous UXUB0015B
controller
110 V AC time delay controller UXUB0016B
240 V AC time delay controller UXUB0017B
440 V AC time delay controller UXUB0018B
200-230 V DC controller UXUB0038B
Auxiliary AUX SW right hand 1C UXXB0004D
switches AUX SW right hand 2C UXXB0005D
6
AUX SW right hand 3C UXXB0006D
Alarm switch ALT SW right hand UXLB0009D
ALT/AUX SW right hand 1C UXLB0013D
Alarm & ALT/AUX SW right hand 2C
auxiliary switch UXLB0014D
Pre-trip alarm For electronic OCR MCCBs only Pre-trip alarm
Fault indication Side of breaker mounted module.
& contacts Electronic MCCBs only FI
Accessories
to suit 400 AF
External accessories
Description Cat. No. Price $
Attached 3 P attached busbars (6 in kit) 2H1384DAA
busbars 4 P attached busbars (8 in kit) 2H1385DAA
Screw tunnel 3 P solderless terminals (6 in kit) 2H2012DAB
terminals 4 P solderless terminals (8 in kit) 2H2012DBB
Rear connect 3 P RC studs (6 in kit) UXRC0006C
studs 4 P RC studs (8 in kit) UXRC0007C
Motor 110 V AC motor 11) UXMC0001B
operators 110 V DC motor 11) UXMC0003B
(XMC4)
24 V DC motor 11) UXMC0004B
240 V AC motor 11) UXMC0005B
Motor base support 11) UXMD0001B
Mechanical 3 P mechanical interlock 3) UXKC0001B
interlocks 3/4 P mechanical interlock 4) UXKC0002B
4 P mechanical interlock 5) UXKC0003B
Cable Interlock cable (wire) UXKC0020A
mechanical
interlocks Cable interlock mechanism 6) UXKC0021B
Handle IP 55 grey vari-depth handle + T1HS40R5GM
operators 320 mm shaft
T1HS escutcheon plate option: T2HSESC100
100 mm2
390 mm T pin shaft for T1HS - T2HS400SHAFT
no flexi coupling
IP 65 grey vari-depth handle T1HP40R6BNA4
6
+ shaft
IP 65 vari-depth metal handle YASD34
+ shaft
Padlock attachment for T2HP/ T1HP40PALK
HS mechanism
IP 55 direct mount fixed depth TFJ34XU
handle 7)
T1HS handle shaft cam for 1499 7702
Prosafe and Fortress locks
Toggle Toggle lock – non captive 2H1956BAA
locks (Padlockable)
Toggle -lock – captive XKA4
(Padlockable)
Resin for XKA4 LOCTITE 480
Accessories
to suit 400 AF
External accessories
Description Cat. No. Price $
Terminal 3 P front connecting terminal 2H1413DAB
covers cover - busbar connect type
4 P front connecting terminal 2H1414DAB
cover - busbar connect type
3 P front connecting terminal 2H1415DAB
cover - cable connect type
4 P front connecting terminal 2H1416DAB
cover - cable connect type
IP 20 protective cover - busbar 2A1787DBA
connect type 8)
IP 20 protective cover - cable 2A1788DAA
connect type 8)
3 P rear connecting terminal UXPD0011B
cover
4 P rear connecting terminal UXPD0012A
cover
Accessory lead Accessory lead terminal UXYD0001A
terminal Terminal and bolt 9) UXYD0002A
TemPlugs 13) 3 P TemPlug 400 A 12) UPX3440
Interpole Interpole barrier 10) UXQH0004B
barrier
OCR Tamperproof cover for OCR XS400OCRSK
sealing kit adjustment dials
Ordering details
Ampere Short time 3 pole
rating rating (kA) Cat. No. 1) Price $
630/800 10 kA for 0.3 sec XS800NN3
Dimensions (mm)
Ampere Height Width Depth Weight (kg)
rating 3
) 3P 4P 3P 4P
630/800 273 210 280 103 9.00 12.2
TemBreak 1 series
Current limiting thermal magnetic type
XS630NJ
50 kA
Current rating: 250 – 630 A
Approvals and Tests: Standards: AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity: Symmetrical amps (kA RMS)
3 Pole
Amp
rating
6
3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
400 250 400 XS630NJ 400 3
630 400 630 XS630NJ 630 3
3 Pole
Amp
rating
NRC
400
ASR Min.
250
ASR Max.
400
Cat. No.
XH630PJ 400 3
3 pole
Price $ 6
630 400 630 XH630PJ 630 3
Trip unit:
Electronic trip unit: Adjustable long, short and instantaneous trip.
Trip unit: Fixed.
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3 4
H 1) 273 273
W 210 280
D (less toggle) 103 103
Weight (kg) 9.6 12.2
3 Pole
Amp rating 3 pole
6
NRC ASR Min. ASR Max. Cat. No. Price $
630 315 630 XS630SE 630 3
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
630 315 630 XS630SE 630 4
Ground Fault Trip MCCB 2)
3 Pole
Amp rating 3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
630 315 630 XS630SE 6303LSIG
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
630 315 630 XS630SE 6304LSIG
6
NRC ASR Min. ASR Max. Cat. No. Price $
630 315 630 XH630SE 630 3
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
630 315 630 XH630SE 630 4
Ground Fault Trip MCCB 2)
3 Pole
Amp rating 3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
630 315 630 XH630SE6303LSIG
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
630 315 630 XH630SE6304LSIG
THERMAL/MAGNETIC
CIRCUIT BREAKERS
Terasaki thermal/magnetic circuit breakers offer
superior protection when harmonics exist in a network.
POWER PROTECTION
115&3"4",*.$$#T$1#
Terasaki thermal/magnetic
/magnetic circuit breakers:
r 3FTQPOEEJSFDUMZUPUIFIFBUQSPEVDFECZUIF
USVF3.4WBMVFPGUIFMPBEDVSSFOU
r &OTVSFQSPUFDUJPOJSSFTQFDUJWFPGUIFIBSNPOJD
EJTUPSUJPOBOZGVUVSFMPBETNBZDBVTF
r 1SPUFDUVQUPUIFJOñOJUFIBSNPOJD
r "SFTVJUBCMFGPS%$BQQMJDBUJPOT
/)1/)1OIQDPNBV /)1/)1OIQO[DPN
Valid until August 2014
MCCBs
TemBreak 1 series
Current limiting thermal magnetic type
XS800NJ
50 kA
Current rating: 500 – 800 A
Approvals and Tests: Standards: AS/NZS 3947-2 and
IEC 60947-2
Interrupting capacity: Symmetrical amps (kA RMS)
3 Pole
Amp
rating 3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
6
800 500 800 XS800NJ 800 3
4 Pole
Amp
rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
800 500 800 XS800NJ 800 4
3 Pole
Amp
rating 3 pole
6 NRC
800
ASR Min.
500
ASR Max.
800
Cat. No.
XH800PJ 800 3P
Price $
4 Pole
Amp
rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
800 500 800 XH800PJ 800 4P
Trip unit:
Electronic trip unit: Adjustable long, short and instantaneous trip.
Trip unit: Fixed.
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3 4
H 1) 273 273
W 210 280
D (less toggle) 103 103
Weight (kg) 9.7 12.2
3 Pole
Amp rating
6
3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
800 400 800 XS800SE 800 3
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
800 400 800 XS800SE 800 4
Ground Fault Trip MCCB 2)
3 Pole
Amp rating 3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
800 400 800 XS800SE8003LSIG
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
800 400 800 XS800SE8004LSIG
Trip unit:
Electronic trip unit: Adjustable long, short and instantaneous trip.
Trip unit: Fixed.
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3 4
H 1) 273 273
W 210 280
D (less toggle) 103 103
Weight (kg) 9.7 12.2
3 Pole
Amp rating 3 pole
6 NRC
800
4 Pole
ASR Min.
400
ASR Max.
800
Cat. No.
XH800SE 800 3
Price $
2
) GF MCCBs require a 4th Neutral CT to be ordered for 3 and 4 pole MCCB
applications. (If a neutral is present) Refer accessories.
NRC: Nominal rated current.
ASR: Adjustable setting range.
Trip unit:
Electronic trip unit: Adjustable long, short and instantaneous trip.
Trip unit: Fixed.
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3 4
H 1) 273 273
W 210 280
D (less toggle) 103 103
kg 9.7 12.2
3 Pole
Amp rating
NRC ASR Min. ASR Max. Cat. No. Price $
6
800 400 800 XH800PE 800 3
4 Pole
Amp rating
NRC ASR Min. ASR Max. Cat. No. Price $
800 400 800 XH800PE 800 4
18 kA
Current rating: 200-800 A
Approvals and tests: Standards AS 2184, AS/NZS 3947-2
Complies with IEC 60947-2
Interrupting capacity: 18 kA at 1000 V AC 1) (IEC 60947-2)
12.5 kA at 1100 V AC 2)
Trip unit:
Trip unit: Fixed
LTD adjustment: I : 0.8-1
1
t: 5-30 s
STD adjustment: I : 2-10
2
t: 0.1-0.3
INST adjustment: I : 3-12
3
Dimensions (mm)
Poles 3
H 3) 273
W 210
D (Less toggle) 103
Weight (kg) 11.00
Amp
rating
NRC ASR Min. ASR Max. Cat. No. Price $
6 400
630
200
315
400
630
XV630PE 400 3K 4)
XV630PE 630 3K 4)
800 400 800 XV800PE 800 3K 4)
Accessories
to suit 630-800 AF
Internal accessories
Description Cat. No. Price $
Shunt trips 110 V AC/DC 2H1515BAA
240 V AC 2H1516BAA
12 V DC 2H1517BAA
24 V DC 2H1518BAA
48 V DC 2H1519BAA
200 V DC 2H1520BAA
24 V AC 2H1521BAA
48 V AC 2H1522BAA
Undervoltage AC coil 1) 2H1503BAA
trips 100-230 V DC coil 2) 2H1504BAA
24 V DC coil 2) 2H1505BAA
48 V DC coil 2) 2H1506BAA
60 V DC coil 2) 2H1507BAA
110 V AC instantaneous UXUB0013B
controller
240 V AC instantaneous UXUB0014B
controller
440 V AC instantaneous UXUB0015B
controller
110 V AC time delay controller UXUB0016B
240 V AC time delay controller UXUB0017B
440 V AC time delay controller UXUB0018B
200-230 V DC controller UXUB0038B
6
Undervoltage AUX SW right hand 1C UXXB0007D
trips AUX SW right hand 2C UXXB0008D
AUX SW right hand 3C UXXB0009D
Alarm switch ALT SW right hand UXLB0010D
Alarm & ALT/AUX SW right hand 1C UXLB0015D
auxiliary
switches ALT/AUX SW
right hand 2C UXLB0016D
6
T1HS escutcheon plate option: T2HSESC100
100 mm2
390 mm T pin shaft for T2HS - no T2HS400SHAFT
Handle flexi coupling
operators IP 65 Grey variable depth
handle + 420 mm shaft T1HP80R6BNA4
Padlock attachment for T1HP/HS T1HP80PALK
mechanism
IP 55 direct mount fixed depth TFJ36XU
handle
Handle Extends length of toggle UXKB0002A
extension
Toggle lock – non captive UXKB0002A
(Padlockable)
Toggle & Toggle lock – captive
handle locks (Padlockable) XKA6
Resin for XKA6 LOCTITE 480
TemPlug
Interpole
Mounting bolts
TemPlug 800 A rated 3)
XDM6-4
UPX3800 6
barrier Interpole barrier UXQH0004B
OCR Tamperproof cover for OCR XS630OCRSK
sealing kit adjustment dials
Prosafe shot bolt lock HS handles TKNHPXX
xx code
Prosafe standard key xx code TKNNHPKEYX_
ProSafe shot for above
bolt interlock Cam for T2HS handle shafts
Key codes A to Z are available. 14997702
Specify by changing the key code
above.
Trip unit:
Electronic trip unit: Adjustable long, short and instantaneous trip.
Trip unit: Fixed.
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3 4
H 1) 370 370
W 210 280
D (less toggle) 120 120
Weight (kg) 22 28
3 Pole
Amp rating 3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
1000 500 1000 XS1250SE 1000 FC3
1250 625 1250 XS1250SE 1250 FC3
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
1000 500 POA
1000 XS1250SE 1000 FC4
1250 625 1250 XS1250SE 1250 FC4
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
1000 500 1000 XS1250SE 10004LG
1250 625 1250 XS1250SE 12504LG
Notes: 1) GF MCCBs require a 4th Neutral CT to be ordered for 3 and 4 pole MCCB
applications. (If a neutrel is present) Refer accessories.
NRC: Nominal rated current.
ASR: Adjustable setting range.
20 kA
Current rating: 200-1250 A
Approvals and tests: Standards AS/NZS 3947-2,
IEC 60947-2
Interrupting capacity: 20 kA at 1000/1100 V AC
(IEC 60947-2)
Trip unit:
Trip unit: Fixed
LTD adjustment: I : 0.8-1
1 t: 5-30 s
STD adjustment: I : 2-10
2 t: 0.1-0.3 s
INST adjustment: I : 3-12
3
Dimensions (mm)
Poles 3
H 1) 370
W 210
D (Less toggle) 120
Weight (kg) 22.0
4 pole POA
Amp rating NRC ASR Min. ASR Max. Cat. No. Price $
6 400
800
1000
200
400
500
400
800
1000
XV1250NE 400 3 K 2)
XV1250NE 800 3 K 2)
XV1250NE1000 3 K 2)
1250 630 1250 XV1250NE1250 3 K 2)
XV1250 MINING BREAKERS MUST USE
either line-side terminal covers
OR
interpole barriers, and a rear
insulation plate
(All supplied with breaker) 3)
Notes: 1) H excludes attached busbar.
2
) For FAULT INDICATION option add “FI” and nominate control voltage.
3
) Installation information is supplied with MCCBs or refer NHP prior to
purchase.
NRC: Nominal rated current.
ASR: Adjustable setting range.
Overcurrent trip combinations: (specify combinations req.)
LSI - standard,
LS - optional,
LSIP - pre-trip alarm,
LSIG - trip indicators - optional.
Trip unit:
Electronic trip unit: Adjustable long, short and instantaneous trip
Trip unit: Fixed.
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3 4
H 1) 370 370
W 210 280
D (less toggle) 140 140
Weight (kg) 27 35
3 Pole
6
Amp rating 3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
1600 800 1600 XS1600SE 1600 FC3
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
1600 800 1600 XS1600SE 1600 FC4
Ground Fault Trip MCCBs 2)
3 Pole
Amp rating 3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
1600 800 1600 XS1600SE 16003LG
4 Pole
Amp rating 4 pole
NRC ASR Min. ASR Max. Cat. No. Price $
1600 800 1600 XS1600SE 16004LG
Notes: 1) H excludes attached busbar.
2
) GF MCCBs require a 4th Neutral CT to be ordered for 3 and 4 pole MCCB
applications. (If a neutrel is present) Refer accessories.
NRC: Nominal rated current.
ASR: Adjustable setting range.
Trip unit:
Electronic trip unit: Adjustable long, short and instantaneous trip
Trip unit: Fixed.
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3
H 1) 370
W 210
D (less toggle) 140
Weight (kg) 25.8
4 pole
6 3 Pole
Amp
rating 3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
630 315 630 TL630NE 630 3
Trip unit:
Electronic trip unit: Adjustable long, short and instantaneous trip
Trip unit: Fixed.
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3
H 1) 370
W 210
D (less toggle) 140
Weight (kg) 25.8
4 pole
3 Pole
Amp 6
rating 3 pole
NRC ASR Min. ASR Max. 2
) Cat. No. Price $
800 400 800 TL800NE 800 3
Trip unit:
Electronic trip unit: Adjustable long, short and instantaneous trip
Trip unit: Fixed.
LTD adjustment: I1: 0.8 – 1 t: 5 – 30 s
STD adjustment: I2: 2 – 10 t: 0.1 – 0.3 s
Instantaneous Adj: I3: 3 – 12 NRC
OCR options: Pre-trip alarm, fault indication and contacts, ground fault trip
Dimensions (mm)
Poles 3
H 1) 370
W 210
D (less toggle) 140
Weight (kg) 26
4 pole
6
3 Pole
Amp
rating 3 pole
NRC ASR Min. ASR Max. Cat. No. Price $
1000 500 1000 TL1250NE 1000 3 FC
1250 625 1250 TL1250NE 1250 3 FC
Auxiliary
switches
AUX SW right hand 2C / 3 P
AUX SW right hand 3C / 3 P
AUX SW right hand 1C / 4 P
UXXB0011D
UXXB0012D
UXXB0023D
6
AUX SW right hand 2C / 4 P UXXB0024D
AUX SW right hand 3C / 4 P UXXB0025D
Alarm ALT SW right hand / 3 P UXLB0011D
switches ALT SW right hand / 4 P UXLB0024D
ALT/AUX right hand 1C / 3 P UXLB0017D
Alarm & ALT/AUX right hand 2C / 3 P UXLB0018D
auxiliary
switches ALT/AUX right hand 2C / 4 P UXLB0025D
ALT/AUX right hand 1C / 4 P UXLB0026D
UXKC0007D
connect
3 P mech I/lock / 1600 A rear UXKC0026C
connect
Mechanical 4 P mech I/lock / 1600 A rear
interlocks connect UXKC0027C
Interlock cable (wire) UXKC0020A
Interlock mechanism 1250 A UXKC0023B
Cable type 1)
Interlock mechanism 1600 A UXKC0024B
Cable type 1)
6
Accessory
lead terminal Terminal and bolt 3) UXYD0002A
Interpole
barrier Interpole barrier 4) UXQH0004B
APPLICATION, INSTALLATION
AND INSTRUCTION GUIDES
POWER PROTECTION
115&3"4",**/45$1#
Internal accessories
r "VYJMJBSZTXJUDIFT r 4IVOUUSJQT
r "MBSNTXJUDIFT r 6OEFSWPMUBHFUSJQT
External accessories
r 0QFSBUJOHIBOEMFT r 5FN1MVH
r .PUPSPQFSBUPST r 1MVHJO.$$#CBTFT
r .FDIBOJDBMJOUFSMPDLT r 5PHHMFMPDLTBOEMPDLJOHEFWJDFT
r *OUFSQPMFCBSSJFST r 3FBSDPOOFDUJPOUFSNJOBMTUVET
r 5FSNJOBMDPWFST r 5VOOFMDMBNQUFSNJOBMT
r 'MVTIQMBUFT r "UUBDIFEóBUCBS
/)1/)1OIQDPNBV /)1/)1OIQO[DPN
Valid until August 2014
Section 7
TemPower 2 Air Circuit Breakers and
Arc Detection Relays
Page
Introduction, standards 7-2
Stocked AR ACBs 7-4
Standard accessories 7-6
ACB ordering information 7-9
Specifications 7 - 10
Main power circuit terminal specifications 7 - 11
Performance specification of AR and AR-H ACB 7 - 12
Overcurrent Release (OCR) Specification 7 - 16
Tripping options 7 - 26
Serial communication options 7 - 30
TemRelay external alarm module 7 - 32
TemVision remote monitoring and control 7 - 32
TemPower Rack remote racking 7 - 33
NHP Servicing 7 - 34
Retrofitting and installation kits 7 - 35
Dimensions 7 - 37
Providing solutions 7 - 38
Arc detecting relay system 7 - 39
Arc D-Tect ordering infomation 7 - 44
(AR6)
7
(AR4)
(AR3)
(AR2)
7-1
Valid until August 2014
Air circuit breakers
Introduction
3 Pole model
7
Standard 800 - 2000 A2500 - 3200 A 4000 A 5000 - 6300 A
series
1600 - 1600 - 3200 A
High fault 2000 A
series
Size AR2 Size AR3 Size AR4 Size AR6
Based Standards
AS 3947-2 Australian Standard
IEC 60947-2 International Electrotechnical Commission
EN60947-2 European Standard
JIS C8372 Japanese Industrial Standard
NEMA PUB NO.SG3 National Electrical Manufacturers Association
ANSI C37.13 American National Standard Institute
Certification and Authorisation
ASTA, UK ASTA Certification Services
NK, Japan Nippon Kaiji Kyokai
LR, UK Lloyd’s Register of Shipping
ABS, USA American Bureau of Shipping
GL, Germany Germanischer Lloyd
BV, France Bureau Veritas
Auxiliary
switch
terminal block
For easy wiring
access, control Connection
voltage, auxiliary to the control
and position circuit
switch terminals
are all mounted
at the front
on the ACB
Manual
body. Due to a
7
operation
general increase
in the level of
harmonics in Breaker fixing
modern power bolt (optional)
distribution
systems, the
neutral phase
Draw-out
is fully rated as
operation
standard on
4P models. Over current Interlocking
release (OCR) mechanisms
available
(optional)
Stocked ACBs
400/415 V
Current interrupting ACB body
Description rating (A) capacity (kA) Cat. No. Price $
1250 65 ARB2123STD
1600 65 ARB2163STD
2000 65 ARB2203STD
AR-S ACB body
2500 85 ARB3253STD
3200 85 ARB3323STD
4000 100 ARB4403STD
Notes: The above specification is fixed. If different accessories are required (e.g.
UVT, OCR, different shunt voltage) please contact NHP sales to place a fully
manufactured order.
‘LSI+GF’: long time delayed trip, short time delayed trip, instantaneous trip,
ground fault trip
1
) This function provides ground fault protection to TN-C or TN-S power
distribution systems on the load side.
2
) The ground fault protection setting is set to enabled as default. If GF is
not required GF must be set to OFF by the user before ACB energisation.
Stocked ACBs
Notes: 1) The stock carriages are suitable for use with the NHP ‘stock body’ shown
on the previous page. If you require a different ACB specification to that
listed on the previous page please contact NHP sales to place a fully
manufactured order.
Standard accessories
Standard accessories
Notes: TEMPro PREMIER pricing is POA. Please contact NHP estimating with
required specification.
Standard accessories
Notes: TEMPro PREMIER pricing is POA. Please contact NHP estimating with
required specification.
Specifications
(AR6)
(AR4)
7 (AR2)
(AR3)
AR650 / AR663
Ampere
ACB
mounting Horizontal Vertical
Front
connect
7
rating (A) ACB type method terminals terminals terminals
5000 A AR650 Draw-out
6300 A AR663 Draw-out
7
Notes: 1) Values in open air at 40º C (45º C for marine applications).
2
) Values of AR208S, AR212S, AR216S for draw-out type with horizontal
terminals, values of the other ACBs for draw-out type with vertical
terminals.
3
) For 2 pole ACBs use outside poles of 3 pole ACB.
4
) 4 Pole ACBs without Neutral phases protection can not apply IT earthing
system.
5
) Contact NHP for the details.
6
) For 500 V AC.
7
) Please contact NHP for DC applications.
When the INST trip function is set to NON, the MCR function should be
enabled, otherwise, the rated breaking capacity is reduced to the rated
latching current.
Notes: 1) Trip variables can be viewed after an event via the LCD providing control
power is constantly available.
2
) LTD-Long time delay trip, STD-Short time delay trip, INST-Instantaneous
trip, GF-Unrestricted ground fault (not available for ‘S’ curve model OCR).
3
) This function provides ground fault protection to TN-C or TN-S power
distribution systems on the load side.
Notes: 1) Line voltage and phase voltage cannot be displayed at the same time.
2
) LTD-Long time delay trip, STD-Short time delay trip, INST-Instantaneous
trip, GF-Unrestricted ground fault (not available for ‘S’ curve model OCR).
7
The LCD flashes
on and off when
alarm / trip event
Inbuilt current occurs
meter for TEMPro
PLUS
or inbuilt energy
Soft rubber
analyser for TEMPro
3200 keys for menu
PREMIER
navigation
Easy identification
Setting adjustment of the CT rated
confirmation button current and the
Test port for secondary set rated current
injection test. Requires
ANU-1 OCR checker
Notes: Indicative picture only
The TEMPro PLUS and TEMPro PREMIER OCR range is available in three model
variations:
Q Standard protection curve, or ‘L’ type – designed for general feeder
applications and will achieve most selectivity and protection
requirements.
Q High selectivity curve or ‘R’ type - offers 3 curve characteristics to IEC60255
and is used when selectivity can not be achieved with other system
protective devices (i.e. fuses or other relays).
Q Generator protection curve or ‘S’ type. – Specifically designed for generator
and marine applications.
It is recommended that all general feeder circuits be protected by the ‘L’ type
unless the results of a selectivity study indicate that an ‘R’ type is required to
discriminate with another system protective device. The application curve type
must be specified at the time of order.
7
R type is used for high selectivity applications and offers 3 curve
characteristics to IEC 60255.
7
Electric energy (kWh), Power factor (cos
Ø), Frequency (Hz)
TEMPro PREMIER ONLY
Notes: 1) This function provides ground fault protection to TN-C or TN-S power
distribution systems on the load side.
= standard = not available
CORP-PROJECTS-ADS-CPB
THINK MAJOR PROJECTS. THINK NHP.
When it comes to Major Projects, our staff
involvement is always driven by long term results,
actively seeking to support you with the right
product and technical solutions before, during and
after project completion.
Standard features
Application Basic
OCR protection LCD protection 2)
type Cat. No. curve 1) monitoring LTD STD INST GF 5)
AGR-21B-L-PG ‘L’ Current meter
(A)
TEMPro Current meter
PLUS
AGR-21B-R-PG ‘R’ (A)
AGR-21B-S-PS ‘S’ Current meter
(A)
AGR-31B-L-PG ‘L’ Energy analyser
TEMPro
PREMIER AGR-31B-R-PG ‘R’ Energy analyser
AGR-31B-S-PS ‘S’ Energy analyser
MCR
PTA
1-channel PTA
Alarm contact output from OCR
LCD/ COMMUNICATIONS
Field test facility & MODBUS
7
Notes: 1) L/R/S refers to the application protection curve, please specify at time of
ordering.
2
) LTD-Long time delay trip, STD-Short time delay trip, INST-Instantaneous
trip, GF-Unrestricted ground fault, (load side GF).
3
) Trip variables can be viewed after an event via the LCD providing control
power is constantly available.
The OCR does not require control power to operate as a protective
device, however it is recommended.
Refer to the table above to see how absence or loss of control power
affects the operation of the OCR.
4
) RPT- Reverse power trip. AGR-31BS-PS becomes AGR-31BS-PR with RPT.
5
) This function provides ground fault protection to TN-C or TN-S power
distribution systems on the load side.
= Standard, = Not available, OPT = Optional
Required
Required
Required
Required
Required
Operation
Operates normally.
Operates normally.
When the CT rated primary current (ICT) is less than 800 A and the GF pick-up
current is set to 10 %, the GF becomes inoperative.
Operates as INST.
Is inoperative. (Has a 40 ms operation)
Is inoperative.
No display when no other power source is available. Communications is disabled.
Is inoperative.
The TEMPOWER 2 AR ACB has two methods of remote tripping of the main
contacts:
Q Shunt trip coil
Q Undervoltage Trip (UVT) Device
Shunt trip coil
The shunt trip coil is available in three varieties;
Q single shunt - short time rated (STR) and should be
wired in series with a N/C auxiliary contact.
Q single shunt - which is continuously rated (CR)
Q double shunt - which is short time rated and should
be wired in series with a N/C auxiliary contact.
Shunt coils are available in different voltages and are factory fit accessories /
NHP service site visit. Below is a basic list of shunt coils, for voltages not shown
on this list please contact your NHP representative.
Single shunt coil
Rated Voltage (CR) Double shunt coil Single shunt (STR)
AC 110 V
AC 220 V
AC 240 V
DC 24 V
DC 48 V
DC 100 V
DC 110 V
Continuously rated shunt trip and undervoltage trip can not be fitted to
the same ACB. However, the STR shunt trip can be used together with an
undervoltage trip.
Notes: Double shunts require a special wiring loom to be fitted during manufacture.
UVT cannot be fitted with a double shunt.
- Stocked - Not available
Available on indent only.
Tripping options
1
)
Tripping options
Communications facility
As standard the TEMPro PLUS and TEMPro PREMIER are equipped with a
MODBUS communications facility conforming to the following network
interface I/O specifications:
TEMPro OCR
Protocol MODBUS
Transmission standard RS-485
Transmission method Two wire (half duplex)
Topology Multi drop bus
Transmission rate 19.2 kbps maximum
Transmission distance 1.2 km max. (at 19.2 kbps)
Data format Modbus-RTU
Maximum number of data nodes 32
7
RS 485
Modbus Network
Notes: 1) ACBs must be fitted with a remote tripping device and charging motor.
For TemVision Pro information, refer to NHP.
TEMPro TEMPro
Data variable Description PLUS PREMIER
max./min. reset Recorded max./min. variable
open/close status Indicates the state of the main
contacts
diagnosis - system alarm status Is the system alarm active?
OL pickup status Is the overload status true?
STD pickup status Is the short time delay status
true?
INST pickup status Is the Instant status true?
GFT pickup status Is the UREF status true?
Line side earth fault status 1) Is the status true?
current - Ia Phase current A (A)
current - Ib Phase current B (A)
current - Ic Phase current C (A)
current - IN (A) (4P ACB as a special spec.)
current - Ig Phase current GF (A)
line voltage - Vab –
line voltage - Vbc –
line voltage - Vca –
power factor - Pf –
frequency - F Supply frequency
fault trip time Speed of trip
diagnosis - MHT disconnect Is tripping coil connected?
status
active power - P (kW)
total real energy - EP (High- (kWh)
High)
7
maximum current - I Maximum phase current
recorded
maximum current - Iinst Maximum inst. current recorded
maximum active power - Pmax (kW)
fault current value (A)
maximum voltage Maximum voltage recorded
7
TemVision Pro 6” screen TemVision Max 10” screen
Maximum 6 ACBs Maximum 15 ACBs
NHP have developed a remote racking device for Terasaki AR ACBs to help
improve operator safety in switchrooms.
Features
Q Racks ACBs between connected, test and isolated positions
Q Remote operation of ACB on/off controls
Q Controlled by a pendant attached to a 10 metre lead
Q Integrated lifting trolley for ACB bodies
Q Rechargeable battery power supply
Q Requires no modification to ACBs - can be used on existing
installations
7
Description Cat. No. Price $
TemPower Rack unit ARTEMPOWERRACK
Price schedule ‘T4 ’ GST not included NHP Sales 1300 NHP NHP 7 - 33
www.nhp.com.au
Valid until August 2014
Air circuit breakers
AR212S
AR216S
AR220S
AR325S
AR332S
AR440S
With
maintenance 30000 30000 25000 20000 20000 15000
30000
Mechanical
Without
Endu- maintenance 15000 15000 12000 10000 10000 8000
rance in 15000
number
of
ONOFF
cycles 1) AC 460 V 12000 12000 10000 7000 7000 3000
Electrical
Without
maintenance
AC 690 V 10000 10000 7000 5000 5000 2500
7
For further information on the available services and pricing please contact
the NHP service department.
Notes: 1) Expected service life based on endurance test. The service life of ACB
depends on the working and environmental conditions. Refer to NHP for
the AR ACB “Maintenance, Inspection and Parts Replacement” guide for
further information.
Existing /
Obsolete Terasaki AR ACB
air circuit equivalent frame
breaker size 1) Kit type Cat. No. Price $
Terasaki AR212S, 3P Installation
CONTACT NHP
AT12, 3P, V/V
Terasaki AR212S, 3P Installation
CONTACT NHP
AT12, 3P, H/H (HH T&B)
Terasaki AR216S, 3P Installation
CONTACT NHP
AT16, 3P, V/V (VV T&B)
Terasaki AR216S, 3P Installation
CONTACT NHP
AT16, 3P, H/H (HH T&B)
Terasaki AR220S, 3P Installation
7
CONTACT NHP
AT20, 3P, V/V (VV T&B)
Terasaki AR325S, 3P Installation
CONTACT NHP
AT25, 3P, V/V (VV T&B)
Terasaki AR332S, 3P Installation
CONTACT NHP
AT32, 3P, V/V (VV T&B)
Nilsen AR208S, 3P Retrofit
CONTACT NHP
NAB1 D8 3P (HV T&B)
Nilsen AR212S, 3P Retrofit
CONTACT NHP
NAB1 D12 3P (HH T&B)
Nilsen AR216S, 3P Retrofit
CONTACT NHP
NAB1 D16 3P (HH T&B)
Nilsen AR220S, 3P Retrofit
CONTACT NHP
NAB1 D20 3P (HH T&B)
Existing /
Obsolete Terasaki AR ACB
Air circuit equivalent frame
breaker size 1) Kit type Cat. No. Price $
Nilsen AR325S, 3P Retrofit
CONTACT NHP
NAB1 D25 3P (HH T&B)
Nilsen AR332S, 3P Retrofit
CONTACT NHP
NAB1 D31 3P (HH T&B)
Nilsen AR440S, 3P Retrofit
CONTACT NHP
NAB1 D40 3P (HH T&B)
Nilsen AR212S, 3P Retrofit
CONTACT NHP
NAB2 CBM 3P (VV T&B)
NAB2 3P Required for use for Retrofit
CONTACT NHP
Jig Set Nilsen NAB2 Kit
Nilsen AR208S, 3P Retrofit
CONTACT NHP
AB5/AB7 3P (HH T&B)
Nilsen AR216S, 3P Retrofit
CONTACT NHP
AB5/AB7 3P (HH T&B)
Nilsen AR332S, 3P Retrofit
CONTACT NHP
AB5/AB7 3P (HH T&B)
Unelec AR208S, 3P Retrofit
CONTACT NHP
C9/8W 3P (VV T&B)
Unelec AR212S, 3P Retrofit
CONTACT NHP
C9/12W 3P (VV T&B)
Unelec AR216S, 3P Retrofit
CONTACT NHP
C9/16W 3P (VV T&B)
Unelec AR220S, 3P Retrofit
CONTACT NHP
C9/20W 3P (VV T&B)
Unelec AR332S, 3P Retrofit
CONTACT NHP
C9/31W 3P (HH T&B)
AEG AR216S, 3P Retrofit
CONTACT NHP
1600A 3P (HH T&B)
Hundtwebr AR216S, 3P Retrofit
CONTACT NHP
LH16 3P (VV T&B)
Hundtwebr AR220S, 3P Retrofit
7
CONTACT NHP
LH20 3P (VV T&B)
Hawker AR216S, 3P Retrofit
CONTACT NHP
CNP/16W 3P (HH T&B)
Hawker AR220S, 3P Retrofit
CONTACT NHP
CNP/20W 3P (HH T&B)
Outline dimensions
7
draw- only
able 1)
Notes: 1) Weights are based on normal specifications with the OCR and standard
accessories.
Consultant
Q Approvals and test: IEC 60947, AS3947-2 and A.S.T.A.
certified
Q Time Current Characteristics to IEC 60255-3 (SI, VI, EI curves)
Q Restricted and Unrestricted ground fault protection in one
relay
Q LSI characteristic curves as standard
Q True r.m.s. protection up to 19th harmonic
Q Sophisticated undervoltage/phase failure protection
Q Integral reverse power protection and load shedding relay
Q Only Terasaki can offer Icw = 100 kA/ 1 second in a small
3200 A frame size
Q TemPower 2 ACB suffers no loss in performance when
tripped through an external protection relay
Q Super fast clearance times under fault
7 End user
Q System alarms that indicate tripping coil health
Q Built in relay tester - can check on line without tripping
ACB
Q Contact temperature monitoring options
Q Fault diagnosis - type of fault, magnitude, tripping time &
trip history
Q High making capacity for operator safety
Q Communication to B.M.S. or S.C.A.D.A. system
Q Main contacts can be changed within 15 minutes per pole
Q Full technical support and ACB commissioning available
via NHP
Q Product servicing available from Australia’s only Terasaki
trained and certified ACB technicians
Arc D-Tect
D1000 Arc Fault Protection system
Arc D-Tect
Arc detecting relay system
D1000 Functionality
The D1000 arc protection system is an advanced and fast arc protection
system, offering the following features and functionality:
Q Compact unit - arc fault and overcurrent protection
Q High speed arc fault detection less than 1ms
Q Over-current protection with detection within 1ms
Q Combines optical fibre and point sensors
Q Real-time event logging
Q Self-supervision of sensors and protection unit
Q Easy installation and configuration via USB
D1000 Arc flash protection unit
The D1000 is a stand-alone and high speed arc protection unit for electrical
power distribution systems. D1000 supports both point and fibre sensor
technologies for arc flash detection and supports up to six sensors. The
sensors can be combined in any combination, depending on the application
and requirements.
Easy configuration
The D1000 is easy to install and set-up and in case any changes are needed
this is easily done via the USB interface accessible from the front. The built-in
user-friendly menu system is embedded in the D1000 unit and activates
automatically when the unit is connected to a PC.
The built-in light sensor on the front makes it easy to adjust and verify that
all sensors are correctly installed and equally sensitive. With the TRIP LEVEL
adjustment on the front plate the sensitivity to light can be adjusted. The light
range is 10-25,000 lux enabling use of sensors under different light conditions,
indoor light, sunlight etc.
In small installations, the calibration TEST sensor can be used as a single arc
detecting sensor, providing additional protection without added cost. Setup
of the overcurrent detection, is easily done through the USB interface.
Arc D-Tect
Arc detecting relay system
Easy installation
The D1000 system is easy to install and made to implement in new switchgear
installations as well as retrofit projects. Both the D1000 unit and sensors are
quick and easy to install. A general guideline is to mount 1-2 sensors per
cubicle or chamber. It is important to cover all horizontal/vertical busbars (1)
as well as breaker compartments (2) and drawers. Example is shown below:
D1000 relays can be linked (up to 4 relays) to provide expanded installation
and sensing requirements.
Arc D-Tect
Arc detecting relay system
24 V battery
Back up Internal or external
Supply trip voltage
100-230 V
L1 L2 L3
Trip
5A
CTs
3-Phase
over current
protection (use Power source
Point
optional)
sensor
w. cable
check
wire length
A1000 Point 10 m
sensor
w. cable
7
check
A1000 Point sensor
w. cable
check
A1000 Point Fibre
w. cable
check
A2000
Fibre optic
cable
Arc D-Tect
Arc detecting relay system
7
Detection area 360°
Length 5 m flexible fibre optic cable (plus 10 m of wiring
cable)
Circuit check Built-in – LED for visual feedback
Dimensions (WxHxD) 32x52x21 mm
A2000 Sensor A2000.0010
Type Fibre optical sensor
Detection area 360°
Length 8 m flexible fibre optic cable (plus 10 m of wiring
cable)
Circuit check Built-in – LED for visual feedback
Dimensions (WxHxD) 32x52x21 mm
Approvals/standards
EMC standards EN60255-26
Enclosure IP 20
Arc D-Tect
D1000 Arc-fault protection system
New
Prod
uc t
Catalogue Numbers and ordering
Cat. No. Price $
D1000 Arc protection unit D1000 0010
A1000 Arc point sensor 10 m A1000 0010
A2000 Arc fibre cable sensor 5 m A2000 0020
A2000 Arc fibre cable sensor 8 m A2000 0010
D1000 DIN rail mounting clips D1000DINCLIPS
7
Efficent self-supervision
Notes: Old sensor types ADR/ A0200/ A0300 can be used with the new D1000 relay.
Refer NHP for connection details.
8-1
Valid until August 2014
Earth leakage relays
TZS series
Features
Q Adjustable time range 0.3 - 2 s
Q Sensitivity (adj.) 30 mA - 1 amp.
Q Immune to false tripping via harmonics
Q High vibration withstand
Q Output C/O contact
Q Indication - LED
Q Reset function - electrical
TZS relay
Adj. Adj. time
Mounting Voltage sensitivity range Cat. No. Price $
120/240 30 mA-1
Surface 0.3-2 s TZS AD120240V
V AC amp
400/440 30 mA-1
Surface 0.3-2 s TZS AD415440V
V AC amp
30 mA-1
Surface 24 V AC 0.3-2 s TZS AD24VAC
amp
Flush
(collar only) – – – TPD OSZ
Tripping times
Rated operating time Operating time range Non-operating time range
(sec) (sec) (sec)
0.3 0.2 - 0.36 0.15
0.5 0.4 - 0.6 0.38
1 0.8 - 1.2 0.7 - 1.25
2 1.3 - 2.0 0.7 - 1.25
Standard features
Earth leakage detection current operated type
Internally mounted contact 1 C/O
Earth leakage indication LED
Reset function (electrical) Yes
Test button Yes
Remote reset (power source) 1 VA
Dimensions (mm) W/H/D 60/104/78
Weight (kg) (relay only) 0.22
TZS series
8
Dimensions (mm)
Wiring diagram
Features
Q Panel mounting 72 mm
Q Adjustable time: 0, 0.15, 0.25, 0.5, 1.0, 2.5, 5, sec
Q Adjustable trip current-.03, .05, .075, 0.1, 0.15, 0.2, 0.3 A, in 3 ranges x 1, x
10 x 100
Q Digital indication of residual current - 3 digits
Q N/O contact-selectable between alarm pre-set 50 % IΔn and extra trip
contact
Q Trip - one changeover contact
Q Local and remote reset/test 2)
8
Notes: 1) Relay can operate as an earth leakage relay or as a digital meter with
trip contacts and current setting disabled. This monitor function is ideal
when first selecting the current settings and monitoring the installation.
2
) Remote test on AC version only.
Refer page 9 - 68 for AS/NZS requirements when using earth leakage relays.
Dimensions (mm)
Features
Q Panel mounting 96 mm
Q Adjustable time delay - 0, 0.15, 0.25, 0.5, 1.0, 2.5, 5 sec
Q Adjustable trip current - 0.03, 0.05, 0.75, 0.1, 0.15, 0.2, 0.3 A in range x 1, x
10, x 100
Q Field selectable negative/positive security
Q Trip – 1 changeover contact
Q Local and remote reset/test
Q Changeover contact selectable between alarm preset 50 % IΔn and extra
trip contact
8 415 V AC RD1G215
Notes: Refer page 9 - 68 for AS/NZS requirements when using earth leakage relays.
Features
Q Units supplied complete with separate test device DSR48T
Q Panel mounting 72 mm
Q Adjustable trip current -7 steps: 0.03, 0.06, 0.1, 0.2, 0.3, 0.4 & 0.5
Q Adjustable trip time -7 steps: 0.05, 0.1, 0.15, 0.2, 0.3, 0.4 & 0.5
Q Choice of output contacts 2 x AL or 1 x AL + 1 x Power Fail
Q Negative/Positive security
Q Complies with standard AS/NZS 2081:2011
Q Latching contact
8 24 V DC
110 V AC
Relay only
Relay only
DSRM7224 2)
DSRM72110
240 V AC Relay only DSRM72240
110 V AC Test unit DSR48TD110
240 V AC Test unit DSR48TD240
A1.2
A1.aux
For correct working according to AS/NZS 2081:2011 the device shall be set as
positive security Ne.
DSR48TD - Test device
DSRM72 - Relay
8
Remote toroids
Type TD Series
TD series
Only TD type toroids are to be used in conjunction with
the NHP range of RD residual current relays. Care should be
taken to select a toroid size closest to the diameter of the
cables being protected. Also ensure the minimum possible
distance between the toroid and relay to ensure maximum
accuracy.
Closed core toroids (2 wire)
Overall dimensions
Min. Max. Internal (mm)
IΔn Nom. In diameter
(A) 1) In (A) (A) 2) (mm) A B C Cat. No. Price $
0.03 65 390 28 59 59 47 TDGA2
0.03 70 420 35 113 92 56 TDGB2
0.03 90 540 60 112 105 56 TDGH2
0.03 170 1020 80 160 125 56 TDGC2
0.1 250 1500 110 198 165 56 TDGD2
0.3 250 1500 140 234 200 56 TDGE2
0.3 400 2400 210 323 290 64 TDGF2
8
A C
Notes: 1) Lowest value of IΔn to be set on relay with this toroid connected.
2
) Values shown are valid only for conductors passing exactly in the middle
of the toroid.
Remote toroids
Type DSR Series
DSR series
Only the DSR type toroids are to be used in conjunction with the NHP range
of DSRM mining relays. The four wire toroid is vital for compliance to AS/
NZS 2081:2011.
Closed core toroids (4 wire)
Overall dimensions
Min. Max. Internal (mm)
IΔn Nom. In diameter
(A) 1) In (A) (A) 2) (mm) A B C Cat. No. Price $
0.03 70 420 35 113 92 56 DSR35DEL
0.03 170 1020 80 160 125 56 DSR80DEL
0.1 250 1500 110 198 165 56 DSR110DEL
0.3 250 1500 140 234 200 56 DSR140DEL
0.3 400 2400 210 323 290 64 DSR210DEL
Accessories
Cat. No. Price $
IP 65 - Front cover to suit 48 x 48 panel mount relay RD4848C
IP 65 - Front cover to suit 72 x 72 panel mount relay RD7272C
IP 65 - Front cover to suit 96 x 96 panel mount relay RD9696C
72 x 72 mm to 96 x 96 mm adapter plate RD7296A
A C
Notes: 1) Lowest value of IΔn to be set on relay with this toroid connected.
2
) Values shown are valid only for conductors passing exactly in the middle
of the toroid.
TL101 TRANSFER
SWITCH CONTROLLER
The soft touch TL101 controller automatically or
manually switches a load from a main line to an
emergency supply in the event of a power failure.
POWER PROTECTION
115&3"4",*&"35)-&","(&-0$,$1#
r (FOVJOFYNNDPOUSPMMFSTPMVUJPO
r 6TFSGSJFOEMZEJTQMBZBOENFOVTFMFDUJPO
r -BSHFTFMFDUJPOPGGVODUJPOTBOEPQUJPOTBTTUBOEBSE
/)1/)1OIQDPNBV /)1/)1OIQO[DPN
Valid until August 2014
Innovators in Protection Technology
Section 9
9
9-1
Valid until August 2014
Innovators in Protection Technology Technical reference
Din-T MCB
Features
Din-T 6 Din-T 10 Din-T 15 Din-T 10H
Decription 2 to 63 A 0.5 to 63 A 6 to 63 A 80 to 125 A
No. of poles 1 2 3 1 2 3 4 1 2 3 4 1 2 3 4
Protected poles 1 2 3 1 2 3 4 1 2 3 4 1 2 3 4
Width (mm) 18 36 54 18 36 54 72 18 36 54 72 27 54 81 108
Depth (mm) 4) 68 68 68 70
Rated voltage 240/415 V AC 240/415 V AC 240/415 V AC 240/415 V AC
Max. current In 63 A 63 A 63 A 125 A
Calibration 30 30 40 40
temp. °C
No. of operations
220 V In 10000 10000 4000 4000
COS=0.9
415 V In 10000 10000 4000 4000
COS=0.9
Insulation >10 Mohm >10 Mohm >10 Mohm >10 Mohm
resistance
Dielectric >2.5 kV >2.5 kV >2.5 kV >2.5 kV
rigidity
Terminal
capacity
line mm2 35 35 35 70
load mm2 35 35 35 70
DC application 3)
Din-T 6 Din-T 10 Din-T 15 Din-T 10H
Decription 2 to 63 A 0.5 to 63 A 6 to 63 A 80 to 125 A
Max. voltage 48 110 1) - - 48 110 1) - - 48 110 1) - - 125 1) 250 2) - -
No. operations
at T≤15 ms 10000 10000 10000 40000
Short circuit kA
at T≤15 ms 20 25 - - 25 30 - - 25 30 - - 10 - 10 -
9
1
) Series connection 2 pole MCB.
2
) Series connection 4 pole MCB.
3
) For DC switching at 250 V and 500 V DC refer latest edition of Part C
catalogue for ratings information.
4
) Depth measurement, excluding toggle.
9
GST not included NHP Sales 1300 NHP NHP 9-3
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
9
9-4 NHP Sales 1300 NHP NHP GST not included
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
9
GST not included NHP Sales 1300 NHP NHP 9-5
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
9
9-6 NHP Sales 1300 NHP NHP GST not included
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
Thermal release
The release is initiated by a bimetal strip in the event of overload. The standard
defines the range of releases for specific overload values. Reference ambient
temperature is 30 °C.
9
GST not included NHP Sales 1300 NHP NHP 9-7
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
110 V 500 V
Circuit 48 V 2 poles 250 V 2 poles
Breaker Rated Current 1 pole in series 1 pole in series
Type (A) lcu (kA) lcu (kA) lcu (kA) lcu (kA)
Din-T 6 0.5......63 A 20 25 – –
Din-T 10 0.5......63 A 25 30 – –
Din-T DC 0.5......63 A – – 6 6
Din-T 15 6 .........25 A 25 30 – –
Din-T 10H 80.... 125 A 10 10 – –
Safe-T 6 ...... 100 A – 5 – –
Load
Notes: 1) Minimum fuse size is based on grading under overload of one MCB with
oneset of fuses. Where a single set of fuses protects more than one MCB,
the minimum fuse size shall be increased to allow for load biasing effects.
2
) Maximum fuse size based on testing to AS 3439.1 clause 8.2.3.
3
) For specific kA ratings applicable to MCBs, refer page 1-23 ratings chart.
Tables based on the following maximum pre-arcing I2t for both BS 88 and
DIN fuses:
125 A - 0.4 x 105, 160 A - 0.62 x 105, 200 A - 1.2 x 105, 250 A - 2.1 x 105.
Suitable fuses include NHP, GEC, Siemens and Bovara-Crady.
Fuses with higher current ratings may be used provided I2t values are equal
9
to, or less than the levels above. Semi-conductor fuses have very low I2t
values and may suit some applications.
Attention is also drawn to AS 3000 clause 7.10.4.4 regarding the use of
fault current limiters in installations containing fire and smoke control
equipment, evacuation equipment and lifts.
Selectivity
The principle of Selectivity (Discrimination) is based upon an analysis of
several circuit breaker characteristics. These include time-current (tripping)
curves, peak-let-through current (Ipeak) and energy let-through (I2t).
The figures stated give the maximum selectivity level with the two nominated
breakers in series under short-circuit conditions. For an indication on
selectivity under overloads refer to the circuit breaker tripping/characteristic
curves, or use the NHP TemCurve selectivity analysis software package.
Selectivity can be enhanced beyond the breaking capacity of the downstream
breaker provided it is backed up by an appropriately selected upstream
breaker, which should not trip (unlatch) under the stated short circuit current.
Cascade
Cascading is achieved by using an upstream device to assist (back-up) a
downstream device in clearing a fault current. This principal is necessary
should the downstream device be required to clear a prospective short circuit
current greater than the devices’ breaking capacity.
In most cascading applications it is generally necessary for the upstream
breaker to trip (unlatch), as well as the downstream breaker to give adequate
back-up protection. As such, cascade is commonly used in feeding and
protecting non-essential loads, such as basic lighting.
For more information on selectivity and cascading please refer to the latest
NHP Part C catalogue.
Cascade / back-up applications
Upstream: MCB
Downstream: MCB
9
GST not included NHP Sales 1300 NHP NHP 9 - 11
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
6 0.07 0.10 0.15 0.18 0.23 0.27 0.35 0.45 1.5 1.6 1.7
10 – – 0.15 0.18 0.23 0.27 0.35 0.45 1 1.1 1.2
Down- 16 – – – – 0.23 0.27 0.35 0.45 1 1.1 1.2
stream 20 – – – – 0.23 0.27 0.35 0.45 1 1.1 1.2
B curve
Din-T 10 25 – – – – – 0.27 0.35 0.45 0.9 1.1 1.1
32 – – – – – 0.27 0.35 0.45 0.9 1 1
40 – – – – – – – – – 0.9 0.9
50 – – – – – – – – – – –
63 – – – – – – – – – – –
6 0.07 0.10 0.15 0.18 0.23 0.27 0.35 0.45 1 1.1 1.2
Down- 10 – – 0.15 0.18 0.23 0.27 0.35 0.45 1 1.1 1.2
stream 16 – – – – – 0.27 0.35 0.45 1 1.1 1.2
C curve 20 – – – – – 0.27 0.35 0.45 1 1.1 1.1
Din-T 6
Din-T 10 25 – – – – – 0.27 0.35 0.45 0.9 1 1.1
Din-T 15 32 – – – – – – 0.35 0.45 0.9 0.9 1
40 – – – – – – – 0.45 – – 0.9
50 – – – – – – – – – – –
63 – – – – – – – – – – –
9
Notes: T = Total selectivity
9
415 V
(DSRCD) 80 100 100 80 50 40 25 16 10
100 100 100 80 50 40 25 16 10
DIN-T15 40 15 - /25 25 /25 25 /25 25 /25 25 /25 25 /25 30 /30 30 /30 30 /30 30 /30 30 /30 30 /30 - /30
50 & - /25 - /25 25 /25 25 /25 25 /25 25 /25 30 /30 30 /30 30 /30 30 /30 30 /30 30 /30 - /30
63
9
Notes: XX Selectivity YY Cascade
9 - 14 NHP Sales 1300 NHP NHP GST not included
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
125 kA
70 kA & H250NJ- 36 kA 50 kA 70 kA
S250PE H250NE S400CJ S400NJ - S400NE S400GE
80 100 125 160 200 250 100 200 250 400 100 200 250 400 100 200 250 400
36/36 36/3636/3636/3636/3636/36
30/30 30/3030/3030/3030/3030/30
30/30 30/3030/3030/3030/3030/30
- /30 30/3030/3030/3030/3030/30
9
GST not included NHP Sales 1300 NHP NHP 9 - 15
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
Upstream MCCBs 1)
H250NE
H400NE
S400NE
E630NE
S400GE
L400NE
S630CE
S250PE
S400PE
Down-
stream kA
MCCB (RMS) 70 125 50 70 85 125 200 36 50
E125NJ 25 25 / 50 25 / 65 25 / 36 25 / 50 25 / 50 25 / 65 25 / 85 25 / 36 25 / 36
S125NJ 36 36 / 65 36 / 85 36 / 50 36 / 65 36 / 65 36 / 85 36 /125 36 / 36 36 / 50
S125GJ
65 65 / 70 65 /125 50 / 50 65 / 70 65 / 85 65 /125 65 /150 36 / 36 50 / 50
ZS125GJ
H125NJ 125 70 / 70 125/125 50 / 50 70 / 70 85 / 85 125 /125 125 /200 36 / 36 50 / 50
S160NJ 36 - / 65 - / 85 36 / 50 36 / 65 36 / 65 36 / 85 36 /125 36 / 36 36 / 50
S160GJ 65 - / 70 - /125 50 / 50 65 / 70 65 / 85 65 /125 65 /150 36 / 36 50 / 50
H160NJ 125 - / 70 - /125 - / 50 - / 70 - / 85 125 /125 125 /200 36 / 36 50 / 50
E250NJ 25 - / 50 - / 85 25 / 36 25 / 50 25 / 50 25 / 65 25 / 85 25 / 36 25 / 36
S250NJ 36 - / 65 - / 85 36 / 50 36 / 65 36 / 65 36 / 85 36 /125 36 / 36 36 / 50
S250GJ
65 - / 70 - /125 50 / 50 65 / 70 65 / 85 65 /125 65 /150 36 / 36 50 / 50
ZS250GJ
S250PE 70 - /125 - / 50 - / 70 - / 85 70 /125 70 /150 36 / 36 50 / 50
H250NJ 125 - / 50 - / 70 - / 85 125 /125 125 /200 36 / 36 50 / 50
H250NE 125 - / 50 - / 70 - / 85 125 /125 125 /200 36 / 36 50 / 50
E400NJ 25 - / 36 - / 50 - / 50 - / 65 - / 85 10 / 36 10 / 36
S400CJ 36 - / 50 - / 65 - / 65 - / 70 - /100 10 / 36 10 / 50
S400NE 50 - / 50 - / 70 - / 50 - / 50 10 / 36 10 / 50
S400NJ 50 - / 70 - / 70 - / 85 - /125 10 / 36 10 / 50
S400GJ/GE 70 - / 85 - /125 - /150 10 / 36 10 / 50
S400PE 85 - / 85 - /125 - /150 10 / 36 10 / 50
H400NE 125 - / 85 10 / 36 10 / 50
E630NE 36
E630CE 50
S630GE 70
XS630CJ 42
XS630NJ 65
XS630PJ 85
XS630SE 50
XH630SE 65
XH630PE 65
XS800NJ 65
XS800SE 50
XJ800PJ 85
XH800SE 65
XH800PE 65
9 XS1250SE 65
XS1600SE 85
Notes: XX Selectivity YY Cascade
XS2000NE
XS2500NE
XS3200NE
TL1250NE
XS1250SE
XS1600SE
XH630SE
XH800SE
TL630NE
TL800NE
XS630SE
XS800SE
S630GE
Cascade table
Upstream-Downstream MCCBs (Thermal magnetic upstream)
H125NJ
H160NJ
S125NJ
S160NJ
E125NJ
S125GJ
S160GJ
L125NJ
L160NJ
Upstream MCCBs
125GJ
ZS-
DownstreamkA
MCCBs (RMS) 25 36 65 125 200 36 65 125 200
E125NJ 25 25 36 50 65 85 36 50 65 85
S125NJ 36 – 36 65 85 125 36 65 85 125
S125GJ 65 – – 65 125 150 36 65 125 150
H125NJ 125 – – 65 125 200 36 65 125 200
S160NJ 36 – – 65 36 36 36 65 85 125
S160GJ 65 – – – – – – 65 125 150
H160NJ 125 – – – – – – 65 125 200
E250NJ 25 – – – – – – 25 25 25
S250NJ 36 – – – – – – 65 36 36
S250GJ 65 – – – – – – – – –
S250PE 70 – – – – – – – – –
H250NJ 125 – – – – – – – – –
E400NJ 25 – – – – – – – – –
S400CJ 36 – – – – – – – – –
S400NJ 50 – – – – – – – – –
S400GJ 70 – – – – – – – – –
H400NJ 125 – – – – – – – – –
9 Notes: 1) Ratings have not been verified where a dash “–” is shown.
All pick-up and time delay settings are to be set at a maximum for upstream
MCCBs.
H250NJ
H400NJ
S250NJ
S400NJ
E250NJ
S250GJ
S400GJ
L250NJ
L400NJ
S400CJ
800NJ
250GJ
XS-
ZS-
9
GST not included NHP Sales 1300 NHP NHP 9 - 19
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
TemBreak MCCB
Socomec
Load-
break (kA) (kA) (kA)
switch MCCB rms MCCB rms MCCB rms
SLB630 E630NE 35 S630CE 35 TL630NE 24
SLB800 XS800NJ 40 XH800PJ 40 TL800NE 28
SLB1000 XS1250SE 45 XS1600SE 45 TL1250NE 45
SLB1250 XS1250SE 65 XS1600SE 75 TL1250NE 70
SLB1600 XS1600SE 75 XS2000NE 60 - -
SLB2000 XS2000NE 60 XS2500NE 60 - -
SLB2500 XS2500NE 60 - - - -
9
current level applications, due to the upstream Terasaki TemBreak MCCB
reducing the peak let-through current.
Example: SLB250 can be used in a 30 kA application if there is an upstream
S250NJ MCCB.
For other combinations please refer to NHP.
C/B rating
MCCBs Amps AC Watts DC Watts
TemBreak 2 MCCBs
E/S125 NJ - GJ, VS125NJ 125 38 34
S160 NJ - GJ, VS250NJ (160 A) 160 40 36
E/S250 NJ - GJ, VS250NJ 250 55 49
S250PE 250 82 73
E/S400 CJ - NJ - GJ 400 75 67
E/S400 NE - GE 400 70 62
E/S630 NE - CE - GE-PE 630 133 119
TemBreak 1 MCCBs
XS/XH400SE, XV400NE 400 69 62
XS/XH630SE, XV630PE 630 109 97
XS800NJ 800 150 134
XS/XH800SE, XV800PE 800 151 134
XS1250SE, XV1250NE 1250 194 173
XS1600SE 1600 189 169
XS2000NE 2000 228 204
XS2500NE 2500 357 319
XS3200NE 3200 585 522
Notes: 1) Values are valid for the maximum ampere trip units per breaker type.
9
(E.g. S125GJ : 125 A) The above watts losses are for 3 poles combined.
60 58 57 57 57 56 54 48 46 44 40 37 27
50 49 48 48 48 47 45 41 40 38 35 33 25
40 39 39 39 39 38 37 34 33 32 30 28 22
35 34 34 34 34 34 33 30 30 29 27 26 21
30 29 29 29 29 29 28 27 26 25 24 23 19
25 25 25 24 24 24 24 23 22 22 21 20 17
20 20 20 20 20 20 19 18 18 18 17 17 14
15 15 15 15 15 15 15 14 14 14 13 13 12
10 9.9 9.9 9.9 9.9 9.9 9.8 9.6 9.5 9.4 9.2 9.1 8.3
7 7.0 7.0 7.0 7.0 6.9 6.9 6.8 6.8 6.7 6.6 6.5 6.1
5 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.9 4.8 4.8 4.5
4 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.9 3.9 3.8 3.7
3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8
2 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9
1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
9 Example
Cable with cross-section 95 mm2 Cu, 45 m length, and short-circuit current at the
transformer terminals of 30 kA. Estimated short-circuit current of 12 kA at the end of
the cable.
What is co-ordination?
The motor starter consists of a combination of contactor, overload relay and
short circuit protective device (SCPD) being either fuses or circuit breakers.
During motor starting and at normal loading, the overload relay protects
both the motor and cables by tripping the contactor in a time inversely
proportional to the current. However, under short circuit conditions, the
response time would be too long and the fuses or circuit breaker must take
over to interrupt the fault current therefore limiting energy passed through
the starter components. When this is successfully achieved, the combination
is said to be co-ordinated.
The primary function of co-ordination is to ensure that the selected
components result in safe interruption of fault currents while minimising
damage to the starter components themselves.
Why is co-ordination important?
Contactors are designed to switch loads frequently. They can carry the high
starting currents of motors, but at short circuit levels, the extremely high
current can force the contacts open due to electro- dynamic effects (it is
this effect that is needed at normal operating currents to extinguish the arc
quickly). Large short circuit currents can therefore lift the contacts possibly
resulting in contact welding or further damage to the starter components.
The importance of selecting the correct SCPD is to minimise the effects of
short circuits, provide safe interruption and a level of performance to meet
the criteria for Type ‘2’
co-ordination.
Precise contactor control
While the correct selection of SCPD is of prime importance to ensure reliable
operation under short circuit conditions, there are other malfunctions
which can occur in a control circuit that can create contact welding due to
uncontrolled and repetitive switching of the coil circuit (this is referred to as
‘contact chatter’). This is particularly important with high current contactors
where the switching currents of the respective motors are particularly high.
The electronically controlled mechanism ‘ECM’ of the CA 6 contactors
prevent uncontrolled switching under all voltage conditions by providing
precise control over the magnet system, thus preventing contact chatter and
minimising contact bounce. Contactors of the
CA 5 series are provided with a delayed release mechanism to prevent contact
chatter under low voltage conditions.
9
9 - 24 NHP Sales 1300 NHP NHP GST not included
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology
Terasaki ‘TemBreak’
tested with
Sprecher + Schuh
contactors to
IEC 60947
CA-6-110
CA-6-95
NOW
Availability
AVAILABLE
early 2013
9
earth leakage relay MCCBs if required.
t 3FGFSUP/)1GPSPUIFSEFWJDFDPNCJOBUJPOT
t 5IFBCPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPGY
FLC for 5 seconds. The instant trip point of MCCBs must be considered
when used with high inrush, high efficiency motors.
Notes: t 5IFSNBMPSFMFDUSPOJDPWFSMPBESFMBZTNBZCFVTFE
t 9.1#DBOCFSFQMBDFEXJUI4(+BOE$"$"
t $PNCJOBUJPOTCBTFEPOUIFPWFSMPBEUSJQQJOHCFGPSFUIFDJSDVJUCSFBLFS
at overload currents up to the motor locked rotor current.
t &MFDUSPOJD.$$#TNBZCFDIBOHFEUPUIFSNBMNBHOFUJDUZQFTJGSFRVJSFE
t 4BNFAMPPLIBOEMFTDBOCFVTFEPO9.1#BOE4".$$#T
t 4(+BOE4(+.$$#TDBOCFDIBOHFEUP;4(+BOE;4(+
9
earth leakage relay MCCBs if required.
t 3FGFSUP/)1GPSPUIFSEFWJDFDPNCJOBUJPOT
t 5IFBCPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPGY
FLC for 5 seconds. The instant trip point of MCCBs must be considered
when used with high inrush, high efficiency motors.
9
t 3FGFSUP/)1GPSPUIFSEFWJDFDPNCJOBUJPOT
t 5IFBPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPGY'-$
for 5 seconds.
The instant trip point of MCCBs must be considered when used with high
inrush, high efficiency motors.
Notes: t 5IFSNBMPSFMFDUSPOJDPWFSMPBESFMBZTNBZCFVTFE
t 9.1#DBOCFSFQMBDFEXJUI)(+BOE$"JGSFRVJSFE
t $PNCJOBUJPOTCBTFEPOUIFUIFSNBMPWFSMPBETSFMBZUSJQQJOHCFGPSFUIF
circuit breaker at overload currents up to the motor locked rotor current.
t 5IFSNBMNBHOFUJD.$$#TNBZCFDIBOHFEUPFMFDUSPOJDUZQFTJG
required.
9
t 4BNFMPPLIBOEMFTDBOCFVTFEPO9.1#BOE4".$$#T
t 3FGFSUP/)1GPSPUIFSEFWJDFDPNCJOBUJPOT
t 5IFBCPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPGY
FLC for 5 seconds. The instant trip point of MCCBs must be considered
when used with high inrush, high efficiency motors.
Notes: t 5 IFSNBMPSFMFDUSPOJDPWFSMPBESFMBZTNBZCFVTFE
t $PNCJOBUJPOTCBTFEPOUIFPWFSMPBETSFMBZUSJQQJOHCFGPSFUIFDJSDVJU
breaker at overload currents up to the motor locked rotor current.
t 5IFSNBMNBHOFUJD.$$#TNBZCFDIBOHFEUPFMFDUSPOJDUZQFTJG
required.
9
t 4BNFAMPPLIBOEMFTDBOCFVTFEPOBMM.$$#T
t 3FGFSUP/)1GPSPUIFSEFWJDFDPNCJOBUJPOT
t 5IFBCPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPGY
FLC for 5 seconds. The instant trip point of MCCBs must be considered
when used with high inrush, high efficiency motors.
Notes: t 5IFSNBMPSFMFDUSPOJDPWFSMPBESFMBZTNBZCFVTFE
t $PNCJOBUJPOTCBTFEPOUIFUIFSNBMPWFSMPBETSFMBZUSJQQJOHCFGPSFUIF
circuit breaker at overload currents up to the motor locked rotor current.
t .$$#T"IBWFB(SPVOE'BVMUPQUJPOGJUUFE5IJTXJMMOPUTFOTF
9
small earth leakage (residual currents)
t 3FGFSUP/)1GPSPUIFSEFWJDFDPNCJOBUJPOT
t 5IFBCPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPGY
FLC for 5 seconds. The instant trip point of MCCBs must be considered
when used with high inrush, high efficiency motors.
9
t $PNCJOBUJPOTCBTFEPOUIFUIFSNBMPWFSMPBETSFMBZUSJQQJOHCFGPSFUIF
circuit breaker at overload currents up to the motor locked rotor current.
t 5IFBCPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPGY
FLC for 5 seconds. The instant trip point of MCCBs must be considered
when used with high inrush, high efficiency motors.
9 Notes: t 5 IFBCPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPGY
FLC for 5 seconds.
Notes: t 5IFSNBMPSFMFDUSPOJDPWFSMPBESFMBZTNBZCFVTFE
9
t 3FGFSUP/)1GPSPUIFSEFWJDFDPNCJOBUJPOT
t 5IFBCPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPGY
FLC for 5 seconds.
t 5IFGVTFNBYJNVNJOSVTIDVSSFOUNVTUCFDPOTJEFSFEXIFOVTFEXJUI
high inrush, high efficiency motors.
Notes: t $
&1PWFSMPBEBEEPONPEVMFTBSFBWBJMBCMFGPS1SPGJCVT %FWJDF/FU
Ethernet, Ground Fault, remote reset, jam protection, and a thermister
protection relay. A CEP7 overload will accept one only add-on module.
t $&'$5PWFSMPBETDBOSFQMBDF$&1PWFSMPBETJGSFRVJSFE
t 'PS$&1$PWFSMPBEVTF 7SBUFE$5TNVTUCFVTFE
t $PNCJOBUJPOTCBTFEPOUIFPWFSMPBESFMBZUSJQQJOHCFGPSFUIFDJSDVJU
breaker at overload currents up to the motor locked rotor current.
t 4BNFAMPPLIBOEMFTDBOCFVTFEPO.$$#T3FGFS/)1GPSPUIFSEFWJDF
9
combinations.
t 5IFBCPWFDPNCJOBUJPOTBSFEFTJHOFEGPSNPUPSTXJUIBOJOSVTIPG
7 x FLC for 5 seconds.
The instant trip point of MCCBs must be considered when used with high
inrush, high efficiency motors.
TEMCURVE 6 - CIRCUIT
BREAKER SELECTIVITY
APPLICATION SOFTWARE
The latest version of TemCurve 6 includes advanced new features
making it a versatile application tool for use with Terasaki MCBs, MCCBs,
ACBs, NHP fuses as well as generic IEC protection relay curves.
POWER PROTECTION
115&3"4",*.$$#"$1#
11
TemCurve 6 includes:
r $JSDVJUMJOFEJBHSBNT
r $BCMFGBVMUDBMDVMBUJPOT
r 5FN$VSWFñMFTIBSJOH
r %JTUSJCVUJPOTDIFNBUJD r *OUFSOFUVQEBUFDBQBCJMJUZ
r 4VQQMZGBVMUDBMDVMBUJPOT r &OFSHZMFUUISPVHIDVSWFT
r 4VQQMZWPMUBHFPQUJPOT r 4VQQMZEFWJDFUZQF
r $BUBMPHVFEBUBQSJOUT PQUJPOT
r 5JNFDVSSFOUDVSWFT r &YQPSUTUP"VUP$BE
r %FWJDFQIPUPT r $JSDVJUCSFBLFS
r 6TFSEFñOFEDVSWFT TFUUJOHEFUBJM
r .PUPSTUBSUBQQMJDBUJPOT r $BMDVMBUPS
/)1/)1OIQDPNBV /)1/)1OIQO[DPN
Valid until August 2014
Innovators in Protection Technology Technical reference
ZS125
E125
S125
Motor Approx. FLC Din-T H125
Rating (kW) (Amps) C & D curve Safe-T L125
0.37 1.1 4 6
0.55 1.5 4 6 20
0.75 1.8 6 6 20
1.1 2.6 10 6 20
1.5 3.4 10 10 20
2.2 4.8 16 16 20
3.0 6.5 20 16 20
4 8.2 25 20 20
4.5 9 32 25 20
5.5 11 32 32 32
7.5 14 40 40 32
10 19 50 50 50
11 21 50 50 50
15 28 63 63 63
18.5 34 100 1) 80 100
22 40 125 1) 100 100
25 46 125 1) 100 100
30 55 125
37 66 125
45 80 125
55 100
75 135
90 160
110 200
132 230
160 270
185 320
200 361
220 380
250 430
280 480
300 510
375 650
450 750
160
160
160
160 250
250 250
250 250
400 400
400 400
400 400
400 2) 630
400 2) 630
630 800 2)
630 800
630 2) 800
630 2) 800
800 2)
1000
Notes: t 5IF%0-UBCMFJTCBTFEPOIPMEJOH'-$DPOUJOVPVTMZBOE
600 % FLC for 10 seconds. For non-standard drives consult NHP.
t -PXFSDJSDVJUCSFBLFSSBUJOHTBSFQPTTJCMFJONPTUBQQMJDBUJPOT3FGFS
to Type ‘2’co-ordination tables for specific circuit breaker/overload
9
combinations.
t "EKVTUBCMFNBHOFUJDUSJQTTFUUPIJHI5IFSNBMNBHOFUJD5FN#SFBL
adjustable 63 % – 100 % of NRC (nominal rated current).
t %JO5.$#TBSFDBMJCSBUFEUP*&$$VSWFA$A%4FMFDUFETJ[FTPG
‘D’ Curve are available from stock, refer NHP.
ZS125
E125
S125
Motor rating Approx. FLC Din-T H125
(kW) (Amps) C & D curve Safe-T L125
0.37 1.1 4 6
0.55 1.5 4 6 20
0.75 1.8 4 6 20
1.1 2.6 6 6 20
1.5 3.4 10 6 20
2.2 4.8 10 10 20
3.0 6.5 16 16 20
4 8.2 20 16 20
4.5 9 20 16 20
5.5 11 25 20 20
7.5 14 32 25 20
10 19 40 40 32
11 21 50 40 32
15 28 50 50 50
18.5 34 63 63 50
22 40 80 1) 63 63
25 46 100 1) 80 100
30 55 125 1) 100 100
37 66 125 1) 100
45 80 125
55 100
75 135
90 160
110 200
132 230
160 270
185 320
200 361
220 380
250 430
280 480
300 510
375 650
450 750
9
If co-ordination to IEC 60947-4-1 is required refer to co-ordination tables.
Reduced voltage table is based on holding 120 % FLC continuously and 350 %
FLC for 20 seconds.
Din-T MCBs are calibrated to IEC 898 Curve ‘C’ & ‘D’. Selected sizes of ‘D’
Curve are available from stock refer NHP.
ZS800
S800CJ
ZS250 S800NJ
S160 S800RJ
H160 S800 (630 A) S800NE
L160 ZS400 ZS630 S800RE
S250 E400 E630 H800NE
E250 S400 S630 XS800NJ S1000NE
H250 H400 XH630 XH800SE S1250NE/1250
L250 L400 XS630 XS800SE XS1250SE/1000
160
160
160 250
160 250
250 250
250 250
250 250 400
400 400
400 400
400 400 800 2)
400 2) 630 800 2)
630 800
630 800
630 800
630 800
800 2)
1000
9
GST not included NHP Sales 1300 NHP NHP 9 - 41
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
ZS125
E125
S125
Motor rating Approx. FLC Din-T H125
(kW) (Amps) C & D curve Safe-T XM30PB L125
0.37 1.1 4 6 3.6
0.55 1.5 6 6 3.6
0.75 1.8 6 6 5 20
1.1 2.6 10 6 7.4 20
1.5 3.4 16 10 10 20
2.2 4.8 20 16 12 20
3 6.5 25 20 20
4 8.2 32 25 32
4.5 9 32 32 32
5.5 11 40 40 32
7.5 14 50 50 50
10 19 63 50 50
11 21 63 63 63
15 28 100 1) 80 100
18.5 34 125 1) 100 100
22 40 125
25 46 125
30 55
37 66
45 80
55 100
75 130
90 155
110 200
132 225
160 270
185 320
200 361
220 380
250 430
280 480
300 510
375 650
450 750
9
2
) Electronic TemBreak MCCB only.
DOL table is based on holding 125 % FLC continuously and 600 % FLC for at
least 20 seconds.
Din-T MCBs are calibrated to IEC 60898 Curve ‘C’ & ‘D’. Selected sizes of ‘D’
Curve are available from stock refer NHP.
S800CJ
S800NJ
ZS250 S800RJ
S160 S800NE
H160 S800RE
L160 ZS400 ZS630 H800NE
S250 E400 E630 ZS800 S1000NE
E250 S400 S630 XS800NJ S1250NE/1250
H250 H400 XH630 XH800SE XS1250SE
L250 L400 XS630 XS800SE /1000
160
160
250 250
250 250
400
400
400 630
400 630
400 630
400 2) 630
630 800
630 800
630 800
800
800
800 2) 1000
1000
9
GST not included NHP Sales 1300 NHP NHP 9 - 43
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
Full Load
Current
Motor Size (kW) Amperes (A) MCCB Voltage (V)
0.37–10 0.4–7.5 VS125NJ 20 1000
11.0 9.0 VS125NJ 20 1000
15–18.5 12–14.5 VS125NJ 32 1000
22–33 17–23 VS125NJ 50 1000
37–50 28–38 VS125NJ 50 1000
55–80 40–57 VS125NJ 63 1000
90–110 65–78 VS125NJ 100 1000
150 102 VS125NJ 160 1000
185–220 138–160 VS125NJ 250 1000
220–500 160–350 XV400NE/400K 1000
Sprecher + Schuh
1000 V CA 6 Contactor
(Refer Part A for more information)
9 Notes: This table should be used as a selection guide for standard applications only.
1000 V Type 2 co-ordination chart available. Refer NHP.
9
(8 pole): +5 %…+20 %
2
) The power factor is usually around 0.8, but this varies with the size and
speed of the motor.
Efficiency ranges from 85 % in small motors
to 90 % and over for large motors.
WARNING:
EXPOSED CONDUCTORS INCLUDING TERMINALS AT ATTACHED
BUSBARS MUST BE INSULATED TO AVOID POSSIBLE SHORT-CIRCUITING
OR EARTHING DUE TO FOREIGN MATTER COMING INTO CONTACT WITH
THE CONDUCTORS.
Notes: When using the terminal bar (optional), the specified insulating distance
9
must be maintained.
All dimensions in mm.
When earthed metal is installed within proximity of the breakers the correct
insulating distance must be maintained (refer to Table 1 over the page).
This distance is necessary to allow the exhausted arc gases to disperse.
Notes: 1) Insulate the exposed conductor until it overlaps the moulded case at the
terminal, or the terminal cover. All dimensions in mm.
MCCB type A B1 B2 C D
XM30PB 30 10 10 0 25
XH125NJ 75 45 25 0 25
XS250NJ 80 60 30 0 25
XH250NJ 100 60 30 0 25
XS400NJ
XH400SE 100 70 40 0 30
XS630NJ
XS630SE
XS800NJ 120 70 40 0 30
XS800SE
XH630SE
XH800SE 150 80 50 0 40
XH800PE
XS1250SE 150 70 40 0 30
XH630PJ
XH800PJ
XS1600SE 150 150 100 0 100
XS2000NE
XS2500NE
Notes: 1) Insulate the exposed conductor until it overlaps the moulded case at the
9
terminal, or the terminal cover. All dimensions in mm.
Electrical formulae
– For obtaining kW, kVA, HP, and Amperes
Alternating Cur-
rent Two-phase
Wanted Single-phase Four-wire Three-phase Direct current
Kilowatts Ι x E x PF Ι x E x 2 x PF Ι x E x 1.73 x PF ΙxE
1000 1000 1000 1000
kVA ΙxE ΙxEx2 Ι x E x 1.73 ΙxE
1000 1000 1000 1000
Horse- Ι x E x % Eff. Ι x E x 1.73 x % Eff.
x PF Ι x E x 2 x % Eff. x PF x PF Ι x E x % Eff.
power 746 746
746 746
Amperes kVA x 1000 kVA x 1000 kVA x 1000 kVA x 1000
from kVA E 2xE 1.73 x E E
9
9 - 50 NHP Sales 1300 NHP NHP GST not included
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
Notes: Additional setting and options information can be found in the 2010 - 2011
9
Part C catalogue.
Curve selection
The predetermined curve characteristic dial on TemBreak 2 MCCBs simplifies
the OCR tripping settings by reducing the number of often misunderstood
variables that need to be specified. This enables users of various technical
abilities to set the OCR to match the required electrical load and service
application. For example if an electrical contractor was required to configure
a S400 A TemBreak 2 MCCB for use in a three phase Squirrel-cage motor
application, curve 5 would be the correct setting as for most applications it
provides class 10 general purpose motor protection.
Curve types provided as standard on TemBreak 2 electronic MCCBs:
250 A and 400 A MCCBs: 7 selectable curves 16 A – 400 A
630 A: 6 selectable curves 252 A – 630 A (Curve type 7
not available)
800 - 1600 A 7 selectable curves 630 A - 1600 A.
Although each of the curves can be said to be targeted towards particular
applications, the use of the curves can be extended to any other use where
that curve suits. For example, curve 1 is ideal for many generator applications,
though curve 1 can also be used for any other application that suits the curve.
General applications by curve type:
Short circuit
Primary (SC)/ motor
Application start type Application 2 Application 3
Generator Low level SC Heating, resistive
Curve 1 Long cable runs
protection loads
Generator Low level SC General, heating,
Curve 2 Long cable runs
protection resistive
General
Curve 3 Med. level SC Long cable runs Lighting
distribution
General
Curve 4 Std. level SC Various motor starting Lighting
distribution
Motor start -
Curve 5 standard run up Class 10 Transformers Lighting
time
Curve 6 Motor start - Class 20 Capacitor switching Lighting
longer run up time
Motor start -
Curve 7 extra run up time Class 30 Capacitor switching –
9
Notes: Curve 4 is the MCCB factory default setting for new MCCBs out of the box.
Curve comparison
The predetermined curve characteristic dial on TemBreak 2 MCCBs enables
easy OCR configuration to match the electrical characteristics of the load.
Tabular representation
Curve selection dial ONLY
Character- LTD (sec) STD Characteristics
istic curve
selection dial 200 % 600 %
position overload overload In < 630 A In ≥ 630 A Delay (sec)
1 11 – 2.5 x IR 2.5 x IR 0.1
2 21 – 2.5 x IR 2.5 x IR 0.1
3 21 – 5 x IR 5 x IR 0.1
4 53 5 10 x IR 8 x IR 0.1
5 108 10 10 x IR 8 x IR 0.2
6 200 19 10 x IR 8 x IR 0.2
29
(Not
7 308 10 x IR 8 x IR 0.2
applicable
for 630 A)
9
Notes: 1) The standard setting of In is 100 % of In. For any other setting, specify
when ordering.
2
) When neutral pole protection is installed the breaker must be set at 100
% of its In rating for the neutral protection to function. For other settings
contact NHP.
Optional Functions
CurveApplication Description LTD STD
1 Generator / heating / The characteristic curve Fastest Fastest
resistive loads features faster tripping times tripping time tripping time
(LOW short cct level) during overload situations & during an during a low
low level short circuit faults. overload level short
circuit
9
current is experienced. Use- level short
motors with difficult starting circuit
conditions that are driving
high inertia loads.
Optional functions
Pre-Trip Alarm (PTA)
An LED and volt-free output contact are activated after a time delay, tp, if the
load current exceeds the preset threshold, Ip. The default time delay, tp is set to
40 seconds and the load current threshold, Ip, is 80% of the rated current.
For example a S250PE TemBreak 2 MCCB with a IRated setting of 125 A would
have a pre-trip alarm threshold of Ip (0.8) x IRated(125) = 100 A.
Ground Fault Trip (GF)
This function trips the MCCB after a time delay, tg, if the ground fault current
exceeds the preset threshold, Ig. Ground fault protection can be enabled and
disabled by operating a DIP switch on the OCR. The default time delay, tg is
set to 0.2 seconds and the load current threshold, Ig, is 20 % of the nominal
current.
For example, an S400GE TemBreak 2 MCCB with a nominal current (In) 400 A
would have a ground fault trip threshold of Ig (0.2) x In (400 A) = 80 A.
When 3 pole GF MCCBs are used, a 4th neutral pole CT will be required. Refer
MCCB accessories. 4 pole GF MCCBs do not require a 4th CT as the neutral
pole protection CT is used. As a general note, 4 wire systems are used in
Australia and New Zealand, and this is why a 4th CT is required for 3 and 4
pole applications.
The MCCB OCR facia showing GFT option below. A DIP switch allows the GFT
to be switched OFF or ON, while a ‘pick up’ LED indicates that the 20 % of
rated current activation point for GFT has been reached.
9
characteristic, therefore tN = tR. The load current threshold, IN, is 100 % of the
nominal current.
For example a S250PE A TemBreak 2 MCCB with a nominal current, In, of 250 A
would have neutral protection threshold of IN (1.0) x In (250) = 250 A.
GST not included NHP Sales 1300 NHP NHP 9 - 55
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
Optional functions
Option ordering
Optional functions must be specified at the time of order. Options can be
selected by identifying the appropriate ‘code’ from the table below and
appending this code after the MCCB type designation. For example, to select
a 4 pole, 400 AF MCCB, front connect, with a nominal current (In) of 250 A,
featuring a Pre-Trip Alarm (P) option the correct description would be:
Cat. No. example: S400GE3 AP 400 3 Pole: with the pre-trip alarm option
Optional Functions
Neutral
Ground Protection Pre-Trip
In Poles Code Fault (GF) (NP) Alarm (PTA)
3 AP – – Yes
4 AP – – Yes
250 A
4 AN – Yes –
4 APN – Yes Yes
3 AP – – Yes
3 AG Yes – –
3 APG Yes – Yes
400 A 4 AP – – Yes
4 AN – Yes –
4 APN – Yes Yes
4 AGN Yes Yes –
3 AP – – Yes
3 AG Yes – –
3 APG Yes – Yes
630 - 1600 A 4 AP – – Yes
4 AN – Yes –
4 APN – Yes Yes
4 AGN Yes Yes –
9
9 - 56 NHP Sales 1300 NHP NHP GST not included
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
Generator Protection
Curve 1 In = 250 A, IR select dial = 0.8, S/H 250
Electronic OCR MCCB
Tripping Time (Sec)
100
1000
10000
Notes: The above curves are worked examples for an electronic MCCB with a 250
A rated overcurrent relay (OCR). The same curve and setting data will also
9
apply to TemBreak 2 MCCBs with other ampere ratings.
Sharing the same short circuit tripping time characteristics as the generator
protection curve, the General Feeder LOW SCP curve 2 has greater tolerance
to allow for overloads caused by small inrush currents.
From the curve below, an S250 TemBreak 2 MCCB with a rated current of
IN (250 A) x IR (0.8) = 200 A features:
Q Approximate trip time of 21 seconds during a 200 % of rated current
(400 A) overload
Q Approximate trip time of 0.1 seconds during a 250 % of rated current
(500 A) low level short circuit
Q Instantaneous (no intentional delay) threshold of 1400 % of rated current
(2800 A).
100
1000
10000
9 Notes: The above curves are worked examples for an electronic MCCB with a 250
A rated overcurrent relay (OCR). The same curve and setting data will also
apply to TemBreak 2 MCCBs with other ampere ratings.
Featuring a shallower overload time trip curve and higher short circuit current
protection characteristics than curve 2, curve 3 allows greater tolerance
during overload and short circuit conditions.
From the curve below, an S250 TemBreak 2 MCCB with a rated current of
In (250 A) x IR (0.8) = 200 A features:
Q Approximate trip time of 21 seconds during a 200 % of rated current
(400 A) overload
Q Approximate trip time of 0.1 seconds during a 500 % of rated current
(1000 A) low level short circuit
Q Instantaneous (no intentional delay) threshold of 1400 % of rated current
(2800 A).
100
1000
10000
Notes: The above curves are worked examples for an electronic MCCB with a 250
A rated overcurrent relay (OCR). The same curve and setting data will also
9
apply to TemBreak 2 MCCBs with other ampere ratings.
This curve contains a shallower overload time trip curve and a higher short
circuit current protection characteristic compared to the previous curve 3.
From the curve below an S250 TemBreak 2 MCCB with a rated current of
In (250 A) x IR (0.8) = 200 A features:
Q Approximate trip time of 58 seconds during a 200 % of rated current
(400 A) overload
Q Approximate trip time of 5 seconds during a 600 % of rated current
(1200 A) overload
Q Approximate trip time of 0.1 seconds during a 1000 % of rated current
(2000 A) low level short ciruit
Q Instantaneous (no intentional delay) threshold of 1400 % of rated current
(2800 A).
100
1000
10000
9 Notes: The above curves are worked examples for an electronic MCCB with a 250
A rated overcurrent relay (OCR). The same curve and setting data will also
apply to TemBreak 2 MCCBs with other ampere ratings.
100
1000
10000
9
Percent Of Rated Current
Notes: The above curves are worked examples for an electronic MCCB with a 250
A rated overcurrent relay (OCR). The same curve and setting data will also
apply to TemBreak 2 MCCBs with other ampere ratings.
100
1000
10000
10000
100
1000
9
Percent Of Rated Current
Notes: The above curves are worked examples for an electronic MCCB with a 250
A rated overcurrent relay (OCR). The same curve and setting data will also
apply to TemBreak 2 MCCBs with other ampere ratings.
Rated Current
100
1000
10000
Current (A)
Rated Current
100
1000
10000
Current (A)
Notes: The above curves are worked examples for an electronic MCCB with a 250
A rated overcurrent relay (OCR). The same curve and setting data will also
9
apply to TemBreak 2 MCCBs with other ampere ratings.
POWER PROTECTION
115&3"4",*&"35)-&","(&$1#
/)1/)1OIQDPNBV /)1/)1OIQO[DPN
Valid until August 2014
Innovators in Protection Technology Technical reference
Fixed
125-225 18 TO225CB therm. Fixed XE225NS – E250NJ 25
fixed mag.
100-160 35 TO225BA Adj. therm. S160NJ 36
fixed mag. 63-100 % XS250NJ ) –
1
160-250 S250NJ
100-160 50 TG225B Adj. therm. S160GJ 65
fixed mag. 63-100 % XH250NJ ) –
1
160-250 S250GJ
160-250 35 Adj. therm.
TO400BA fixed mag. 63-100 % XS400CJ – S400CJ 36
250-400
160-250 50 Adj. therm.
TG400B adj. mag. 63-100 % XS400NJ ) – S400NJ 50
1
250-400
125-250 50 Electronic
TTE400 LSI 50-100 % XS400NE XS400SE S400SE 50
200-400
125-250 65 TTE400 Electronic XH400SE
50-100 % XH400NE S400GE 70
200-400 LSI 1
)
250-400 45 Adj. therm.
TO600BA adj. mag. 63-100 % XS630CJ – XS630NJ 50
400-630
250-400 65 TG600B Adj. therm.
adj. mag. 63-100 % XS630NJ ) – XS630NJ 50
1
400-630
315-630 50 TTE630 Electronic 50-100 % XS630NE XS630SE 1) S630CE 50
315-630 65 TTE630 Electronic 50-100 % XH630NE 1XH630SE S630GE 70
)
Adj. therm. 63-100 % XS800NJ 1) –
500-800 65 TO800BA XS800NJ 50
adj. mag.
Adj. therm. XS1250SE XS1250SE 85
500-800 85 TG800B 63-100 % XS1250NE
adj. mag. 1
)
400-800 50 TTE800 Electronic 50-100 % XS800NE XS800SE 1) XS800SE 50
400-800 65 TTE800 Electronic 50-100 % XH800NE 1XH800SE XH800SE 65
)
630- 85 TO1000B Electronic 50-100 % XS1250NE 1XS1250SE XS1250SE 85
1250 TO1200B )
800- 100 TO1600B Electronic 50-100 % XS1600NE 1XS1600SE XS1600SE 100
1600 )
1000- 100 TTE2000 Electronic 50-100 XS2000NE – 1) XS2000NE 85
2000 TO2000 %
1250- 100 TO2500 50-100
Electronic % XS2500NE – 1) XS2500NE 85
2500
1600- 100 TO3200 50-100
Electronic % - 2009 XS3200NE 85
9
3200
Introduction 1982 – – 1990 2000 2006/07
date:
Notes: 1) Stocked
1. Equipment Protection
Terasaki Earth Leakage relays are suitable for earth fault protection of
equipment and limitation of touch voltages where automatic disconnection
of supply is required.
Typically this is achieved by shunt tripping another protective device such as
an upstream circuit breaker.
Earth leakage relays are used in particular where ground (earth) fault
detection is required
or the Fault Loop Impedance is of such a level that the over-current device
(circuit breaker) does not achieve automatic disconnection within the times
prescribed in the Wiring Rules.
2. Personnel Protection
Earth leakage relays are NOT suitable for personnel protection against direct
contact as specified in the Wiring Rules, e.g. for socket outlets and lighting
circuits. For these applications an RCD (10 mA or 30 mA) must comply with
the relevant standards (AS 3190, AS/NZS 61008 or AS/NZS 61009) and be
approved by the relevant authorities. Terasaki earth leakage relays are not
designed to meet the requirements of this approval.
For personnel protection Safe-T and Din-T devices such as the ELR relay, SRCB,
SAFETRCB6, DSRCD, DSRCB, DSRCM & DSRCBH are all suitable. These are
approved devices and meet the relevant standards.
9
RCD devices
3. Mining Protection
Terasaki Earth Leakage Relays are suitable for mining applications, with the
exception of coal and shale mine applications as governed by AS 2081:2011
- Electrical Equipment for coal and shale mines: “Earth Leakage protection for
use on earth-fault current limited systems (IT systems)”.
This is because Terasaki Earth Leakage Relays are not designed to comply with
certain technical requirements of the above mining standard.
Terasaki Earth Leakage Relays that DO comply with AS 2081.3 and the
DSRM72 relay.
Circuit breaker based 10 mA and 30 mA RCD devices do not need to comply
with AS 2081.3, as this standard accepts devices that meet the personnel
protection standards: AS 3190, AS/NZS 61008 or AS/NZS 61009. As such the
following Safe-T and Din-T devices are suitable: ELR relay, SRCB, SAFETRCB6,
DSRCD, DSRCB, DSRCM & DSRCBH.
ZS earth leakage MCCBs also comply with the standard AS 2081:2011.
9
GST not included NHP Sales 1300 NHP NHP 9 - 69
www.nhp.com.au
Valid until August 2014
Innovators in Protection Technology Technical reference
9
Protected against
long periods of
8
immersion
under pressure.
9
reduce their effects.
Alphanumeric Index
I 2H1212BAA 6 - 35 NT30141
2H1299CAC 6 - 26 NT20138
I 2H1301CAC 6 - 26 NT20138
2H1302CAC 6 - 26 NT20138
2H1303CAC 6 - 26 NT20138
2H1305BAA 6 - 10 NT20138
2H1306BAA 6 - 10 NT20138
I 2H1307BAA 6 - 10 NT20138
2H1308BAA 6 - 10 NT20138
2H1309BAA 6 - 10 NT20138
2H1311BAA 6 - 10 NT20138
2H1384DAA 3 - 99 NT20138
2H1384DAA 6 - 11 NT20138
2H1385DAA 6 - 11 NT20138
2H1413DAB 6 - 12 NT20138
2H1414DAB 6 - 12 NT20138
2H1415DAB 6 - 12 NT20138
2H1416DAB 6 - 12 NT20138
2H1417DAB 4 - 13 NT20138
2H1417DAB 6 - 27 NT20138
2H1418DAB 6 - 27 NT20138
2H1419DAB 4 - 13 NT20138
2H1419DAB 6 - 37 NT20138
2H1420DAB 6 - 37 NT20138
2H1492BAA 6 - 10 NT20138
I 2H1493BAA 6 - 10 NT20138
2H1494BAA 6 - 10 NT20138
I 2H1495BAA 6 - 10 NT20138
I 2H1496BAA 6 - 10 NT20138
2H1503BAA 6 - 25 NT20138
2H1504BAA 6 - 25 NT20138
2H1505BAA 6 - 25 NT20138
I 2H1506BAA 6 - 25 NT20138
I 2H1507BAA 6 - 25 NT20138
2H1509BAA 3 - 131 NT20138
I 2H1510BAA 3 - 131 NT20138
2H1511BAA 3 - 131 NT20138
I 2H1512BAA 3 - 131 NT20138
I 2H1513BAA 3 - 131 NT20138
2H1515BAA 6 - 25 NT20138
2H1516BAA 6 - 25 NT20138
I 2H1517BAA 6 - 25 NT20138
2H1518BAA 6 - 25 NT20138
I 2H1519BAA 6 - 25 NT20138
I 2H1520BAA 6 - 25 NT20138
2H1521BAA 6 - 25 NT20138
I 2H1522BAA 6 - 25 NT20138
2H1526BAA 3 - 131 NT20138
2H1527BAA 3 - 131 NT20138
Alphanumeric Index
2H4308SAA 5 - 36 NT20138
2H4308SAA 5 - 36 NT20138
2H4308SAA 5 - 36 NT20138
2H4322SAB 5 - 36 NT20138
2H4324SAA 5 - 36 NT20138
2H4645SAB 5 - 36 NT20138
2H4648SAB 5 - 36 NT20138
2H4650SAC 5 - 36 NT20138
2H4650SAC 5 - 36 NT20138
2H4653SAB 5 - 36 NT20138
2H4653SAB 5 - 36 NT20138
2H5153SAB 5 - 36 NT20138
2H5153SAB 5 - 36 NT20138
2H5153SAB 5 - 36 NT20138
2H5153SAB 5 - 36 NT20138
2H5153SAB 5 - 36 NT20138
2H5153SAB 5 - 36 NT20138
2H5154SAA 5 - 36 NT20138
2H5155SAA 5 - 36 NT20138
2H5161SAB 5 - 36 NT20138
2H5161SAB 5 - 36 NT20138
2H5162SAA 5 - 36 NT20138
2H5331SAA 5 - 36 NT20138
2H5364SAC 5 - 36 NT20138
2H5364SAC 5 - 36 NT20138
2H5365SAB 5 - 36 NT20138
2H5365SAB 5 - 36 NT20138
2H6198SAA 5 - 36 NT20138
I 2H6843CAB 3 - 147 NT20138
I 2H6844CAB 3 - 147 NT20138
I 2H6845CAA 3 - 147 NT20138
I 2H6846CAA 3 - 147 NT20138
I 2H6847CAAK 3 - 147 NT20138
I 2H6848CAAK 3 - 147 NT20138
2H6871SAA 5 - 36 NT20138
2H6872SAA 5 - 36 NT20138
2H6873SAA 5 - 36 NT20138
I 2H6940CAB 3 - 147 NT20138
I 2H6940CBA 3 - 147 NT20138
I 2H6941CAB 3 - 147 NT20138
I 2H6941CBA 3 - 147 NT20138
2H6959CAA1 3 - 120 NT20138
2H6959CAA1 3 - 146 NT20138
2H6959CBA1 3 - 120 NT20138
2H6959CBA1 3 - 146 NT20138
2H6972SAA 5 - 36 NT20138
2H6973SAA 5 - 36 NT20138
I 2H7234CAAK 3 - 147 NT20138
I 2H7235CAAK 3 - 147 NT20138
Alphanumeric Index
A ARC2203VVSTD 7-5 NT40143
A ARC3323HHSTD 7-5 NT40143
A ARC3323HVSTD 7-5 NT40143
A ARC3323VHSTD 7-5 NT40143
A ARC3323VVSTD 7-5 NT40143
A ARC4403VVSTD 7-5 NT40143
I A ARCOMMSMOD2ETH 7 - 30 NZ00150
I A ARCOMMSMODDEV 7 - 30 NZ00150
I A ARCOMMSMODPRO 7 - 30 NZ00150
I A ARTEMPOWERRACK 7 - 33 NZ00150
B
I A BH6S633 5 - 10 NZ00150
I A BH6S644 5 - 10 NZ00150
I A BH8S833 5 - 10 NZ00150
I A BH8S844 5 - 10 NZ00150
I A BS12S1033 5 - 10 NZ00150
I A BS12S1044 5 - 10 NZ00150
I A BS12S1233 5 - 10 NZ00150
I A BS12S1244 5 - 10 NZ00150
I A BS16S1633 5 - 10 NZ00150
I A BS16S1644 5 - 10 NZ00150
I A BS20E2033 5 - 10 NZ00150
I A BS20E2044 5 - 10 NZ00150
I A BS25E2533 5 - 10 NZ00150
I A BS25E2544 5 - 10 NZ00150
I A BS6N433 5 - 10 NZ00150
I A BS6N444 5 - 10 NZ00150
I A BS6N633 5 - 10 NZ00150
I A BS6N644 5 - 10 NZ00150
I A BS6S633 5 - 10 NZ00150
A BS8N833 5 - 10 NZ00150
I A BS8N844 5 - 10 NZ00150
I A BS8S833 5 - 10 NZ00150
I A BS8S844 5 - 10 NZ00150
A BTSS16GJ16033 5-7 NT20138
I A BTSS16GJ16034 5-8 NT20138
I A BTSS16GJ16044 5-7 NT20138
I A BTSS16GJ16044 5-7 NT20138
I A BTSS16NJ10033 5-7 NT20138
A BTSS16NJ16033 5-7 NT20138
I A BTSS16NJ6333 5-7 NT20138
I A BTSS1GJ10033 5-7 NT20138
I A BTSS1GJ10034 5-8 NT20138
I A BTSS1GJ10044 5-7 NT20138
I A BTSS1GJ10044 5-7 NT20138
A BTSS1GJ12533 5-7 NT20138
I A BTSS1GJ12534 5-8 NT20138
I A BTSS1GJ12544 5-7 NT20138
I A BTSS1GJ12544 5-7 NT20138
Alphanumeric Index
CA891024VAC 1 - 56 NA10007
CA8910415VAC 1 - 56 NA10007
CA891048VAC 1 - 56 NA10007
CD212/183U 2 - 65 NT40143
CD218/183U 2 - 65 NT40143
CD224/183U 2 - 65 NT40143
CD230/183U 2 - 65 NT40143
CD236/183U 2 - 65 NT40143
CD242/183U 2 - 65 NT40143
CD248/183U 2 - 65 NT40143
A CD250CKT2 2 - 31 NT40143
A CD250CKT2 2 - 51 NT40143
CD250TOPC 2 - 51 NT40143
CD250TOPC 2 - 66 NT40143
CD254/183U 2 - 65 NT40143
CD260/183U 2 - 65 NT40143
CD272/183U 2 - 65 NT40143
CD278/183U 2 - 65 NT40143
CD284/183U 2 - 65 NT40143
CD296/183U 2 - 65 NT40143
I CD312/183U 2 - 66 NT40143
CD318/183U 2 - 66 NT40143
CD324/183U 2 - 66 NT40143
I CD330/183U 2 - 66 NT40143
CD336/183U 2 - 66 NT40143
CD342/183U 2 - 66 NT40143
CD348/183U 2 - 66 NT40143
I CD354/183U 2 - 66 NT40143
CD360/183U 2 - 66 NT40143
CD372/183U 2 - 66 NT40143
I CD378/183U 2 - 66 NT40143
CD384/183U 2 - 66 NT40143
CD396/183U 2 - 66 NT40143
I A CDG 24G2 2 - 24 NT40143
I A CDG 24M160G2 2 - 24 NT40143
I A CDG 24M160O2 2 - 25 NT40143
CDG 24M250G2 2 - 24 NT40143
CDG 24M250O2 2 - 25 NT40143
I A CDG 24O2 2 - 25 NT40143
I A CDG 36G2 2 - 24 NT40143
I A CDG 36M160G2 2 - 24 NT40143
I A CDG 36M160O2 2 - 25 NT40143
I A CDG 36M250G2 2 - 24 NT40143
I A CDG 36M250O2 2 - 25 NT40143
I A CDG 36O2 2 - 25 NT40143
I A CDG 48G2 2 - 24 NT40143
I A CDG 48M160G2 2 - 24 NT40143
I A CDG 48M160O2 2 - 25 NT40143
I A CDG 48M250G2 2 - 24 NT40143
Alphanumeric Index
A CDT 24MCCB200G2 2 - 22 NT40143
A CDT 24O2 2 - 19 NT40143
A CDT250MS 2 - 51 NT40143
CDT 36G2 2 - 18 NT40143
CDT 36M160G2 2 - 18 NT40143
A CDT 36M160O2 2 - 19 NT40143
A CDT 36M250G2 2 - 18 NT40143
A CDT 36M250O2 2 - 19 NT40143
A CDT 36O2 2 - 19 NT40143
A CDT 42MCCB160G2 2 - 22 NT40143
A CDT 42MCCB200G2 2 - 22 NT40143
CDT 48G2 2 - 18 NT40143
CDT 48M160G2 2 - 18 NT40143
A CDT 48M160O2 2 - 19 NT40143
A CDT 48M250G2 2 - 18 NT40143
A CDT 48M250O2 2 - 19 NT40143
A CDT 48O2 2 - 19 NT40143
A CDT 60G2 2 - 18 NT40143
A CDT 60M160G2 2 - 18 NT40143
CDT 60M160O2 2 - 19 NT40143
A CDT 60M250G2 2 - 18 NT40143
A CDT 60M250O2 2 - 19 NT40143
A CDT 60MCCB160G2 2 - 22 NT40143
A CDT 60MCCB200G2 2 - 22 NT40143
A CDT 60O2 2 - 19 NT40143
A CDT 72G2 2 - 18 NT40143
A CDT 72M250G2 2 - 18 NT40143
A CDT 72M250O2 2 - 19 NT40143
A CDT 72O2 2 - 19 NT40143
A CDT78MCCB160G2 2 - 22 NT40143
A CDT78MCCB200G2 2 - 22 NT40143
A CDT 84G2 2 - 18 NT40143
A CDT 84M250G2 2 - 18 NT40143
A CDT 84M250O2 2 - 19 NT40143
A CDT 84O2 2 - 19 NT40143
A CDT 96G2 2 - 18 NT40143
A CDT 96M250G2 2 - 18 NT40143
CDT 96M250O2 2 - 19 NT40143
A CDT 96MCCB160G2 2 - 22 NT40143
A CDT 96MCCB200G2 2 - 22 NT40143
A CDT 96O2 2 - 19 NT40143
A CDTE18G2 2 - 20 NT40143
A CDTE18M160G2 2 - 20 NT40143
A CDTE18M160O2 2 - 21 NT40143
A CDTE18M250G2 2 - 20 NT40143
A CDTE18M250O2 2 - 21 NT40143
A CDTE18O2 2 - 21 NT40143
A CDTE36G2 2 - 20 NT40143
A CDTE36M160G2 2 - 20 NT40143
Alphanumeric Index
A CON 36 M160 O 2 - 15 NT40143
A CON 36 M250 G 2 - 15 NT40143
I A CON 36 M250 O 2 - 15 NT40143
A CON 48 M160 G 2 - 15 NT40143
A CON 48 M160 O 2 - 15 NT40143
A CON 48 M250 G 2 - 15 NT40143
I A CON 48 M250 O 2 - 15 NT40143
A CON 60 M160 G 2 - 15 NT40143
A CON 60 M160 O 2 - 15 NT40143
A CON 60 M250 G 2 - 15 NT40143
I A CON 60 M250 O 2 - 15 NT40143
CONFK1 2 - 16 NT40143
CONFK2 2 - 16 NT40143
I CONFK3 2 - 16 NT40143
I CONFK4 2 - 16 NT40143
COTD 5 - 29 NT30141
A CPACC24G2 2 - 29 NT40143
CPACC48G2 2 - 29 NT40143
CPACC72G2 2 - 29 NT40143
A CPACCS1GE2 2 - 29 NT40143
A CPACCS2GE2 2 - 29 NT40143
A CPACCS3GE2 2 - 29 NT40143
A CPACCS4GE2 2 - 29 NT40143
A CPACCS5GE2 2 - 29 NT40143
A CPACCS6GE2 2 - 29 NT40143
A CPACCSHG2 2 - 29 NT40143
CPACCSHGE2 2 - 29 NT40143
CPACCSOG2 2 - 29 NT40143
CPACCSOGE2 2 - 29 NT40143
CPBFK1 2 - 30 NT40143
CPBFK2 2 - 30 NT40143
CPBFK3 2 - 30 NT40143
CPBFK4 2 - 30 NT40143
CPBFK5 2 - 30 NT40143
I CPBFK6 2 - 30 NT40143
CPBGTS1 2 - 29 NT40143
CPBGTS1 2 - 48 NT40143
CPBGTS2 2 - 29 NT40143
CPBGTS2 2 - 48 NT40143
CPBGTS3 2 - 29 NT40143
CPBGTS3 2 - 48 NT40143
CPBGTS4 2 - 29 NT40143
CPBGTS4 2 - 48 NT40143
CPBGTS6 2 - 29 NT40143
CPBGTS6 2 - 48 NT40143
CPBGTSH 2 - 29 NT40143
CPBGTSH 2 - 48 NT40143
CPBMN 2 - 57 NT40143
CPBS250 2 - 31 NT40143
Alphanumeric Index
CPD 36M250SS2 2 - 42 NT40143
A CPD 36O 2 - 35 NT40143
CPD 36O2 2 - 41 NT40143
A CPD 36SS 2 - 36 NT40143
CPD 36SS2 2 - 42 NT40143
A CPD 48G 2 - 34 NT40143
CPD 48G2 2 - 40 NT40143
CPD 48M160G 2 - 34 NT40143
CPD 48M160G2 2 - 40 NT40143
CPD 48M160O 2 - 35 NT40143
CPD 48M160O2 2 - 41 NT40143
CPD 48M160SS 2 - 36 NT40143
CPD 48M160SS2 2 - 42 NT40143
A CPD 48M250G 2 - 34 NT40143
CPD 48M250G2 2 - 40 NT40143
CPD 48M250O 2 - 35 NT40143
CPD 48M250O2 2 - 41 NT40143
CPD 48M250SS 2 - 36 NT40143
CPD 48M250SS2 2 - 42 NT40143
A CPD 48M300G 2 - 39 NT40143
A CPD 48M400G 2 - 39 NT40143
A CPD 48MCCB300G 2 - 39 NT40143
A CPD 48O 2 - 35 NT40143
CPD 48O2 2 - 41 NT40143
A CPD 48SS 2 - 36 NT40143
CPD 48SS2 2 - 42 NT40143
A CPD 60G 2 - 34 NT40143
CPD 60G2 2 - 40 NT40143
CPD 60M160G 2 - 34 NT40143
CPD 60M160G2 2 - 40 NT40143
CPD 60M160O 2 - 35 NT40143
CPD 60M160O2 2 - 41 NT40143
I A CPD 60M160SS 2 - 36 NT40143
CPD 60M160SS2 2 - 42 NT40143
CPD 60M250G 2 - 34 NT40143
CPD 60M250G2 2 - 40 NT40143
CPD 60M250O 2 - 35 NT40143
CPD 60M250O2 2 - 41 NT40143
I A CPD 60M250SS 2 - 36 NT40143
CPD 60M250SS2 2 - 42 NT40143
A CPD 60M300G 2 - 39 NT40143
A CPD 60M400G 2 - 39 NT40143
A CPD 60MCCB300G 2 - 39 NT40143
A CPD 60O 2 - 35 NT40143
CPD 60O2 2 - 41 NT40143
I A CPD 60SS 2 - 36 NT40143
CPD 60SS2 2 - 42 NT40143
A CPD 72G 2 - 34 NT40143
CPD 72G2 2 - 40 NT40143
Alphanumeric Index
I CPDHANDLENOLOCK 2 - 16 NT40143
I CPDHANDLENOLOCK 2 - 30 NT40143
I CPDHANDLEPADLCK 2 - 16 NT40143
I CPDHANDLEPADLCK 2 - 30 NT40143
CPDRUBBER 2 - 30 NT40143
CPECS 2 - 30 NT40143
A CPELK1 2 - 16 NT40143
A CPELK1 2 - 30 NT40143
A CPELK1 2 - 50 NT40143
A CPELK1W 2 - 16 NT40143
A CPELK1W 2 - 30 NT40143
A CPELK1W 2 - 50 NT40143
A CPELK2 2 - 16 NT40143
A CPELK2 2 - 30 NT40143
A CPELK2 2 - 50 NT40143
CPEN18 2 - 56 NT40143
CPEN18EVE 2 - 57 NT40143
CPEN18ODD 2 - 57 NT40143
CPEN24 2 - 56 NT40143
CPEN24EVE 2 - 57 NT40143
CPEN24ODD 2 - 57 NT40143
CPEN30EVE 2 - 57 NT40143
CPEN30ODD 2 - 57 NT40143
CPEN36 2 - 56 NT40143
CPEN36EVE 2 - 57 NT40143
CPEN36ODD 2 - 57 NT40143
CPEN48 2 - 56 NT40143
CPEN48EVE 2 - 57 NT40143
CPEN48ODD 2 - 57 NT40143
CPEN60 2 - 56 NT40143
CPEN72 2 - 56 NT40143
CPEN84 2 - 56 NT40143
CPEN96 2 - 56 NT40143
CPEN9EVE 2 - 57 NT40143
CPEN9ODD 2 - 57 NT40143
A CPESC 2 - 30 NT40143
CPEXTLK1 2 - 31 NT40143
CPEXTLK2 2 - 31 NT40143
CPEXTLKC 2 - 31 NT40143
I A CPG 24G 2 - 37 NT40143
A CPG 24G2 2 - 43 NT40143
I A CPG 24M160G 2 - 37 NT40143
A CPG 24M160G2 2 - 43 NT40143
CPG 24M160O 2 - 38 NT40143
A CPG 24M160O2 2 - 44 NT40143
CPG 24M250G 2 - 37 NT40143
A CPG 24M250G2 2 - 43 NT40143
CPG 24M250O 2 - 38 NT40143
A CPG 24M250O2 2 - 44 NT40143
Alphanumeric Index
A CPG 84M250G2 2 - 43 NT40143
CPG 84M250O 2 - 38 NT40143
A CPG 84M250O2 2 - 44 NT40143
I A CPG 84O 2 - 38 NT40143
A CPG 84O2 2 - 44 NT40143
I A CPG 96G 2 - 37 NT40143
A CPG 96G2 2 - 43 NT40143
CPG 96M250G 2 - 37 NT40143
A CPG 96M250G2 2 - 43 NT40143
CPG 96M250O 2 - 38 NT40143
A CPG 96M250O2 2 - 44 NT40143
I A CPG 96O 2 - 38 NT40143
A CPG 96O2 2 - 44 NT40143
CPGPA 2 - 30 NT40143
CPGPB 2 - 30 NT40143
CPGPS 2 - 30 NT40143
CPIP52G 2 - 30 NT40143
A CPPACC24G 2 - 48 NT40143
CPPACC24G2 2 - 49 NT40143
CPPACC48G 2 - 48 NT40143
CPPACC48G2 2 - 49 NT40143
A CPPACCG 2 - 48 NT40143
CPPACCG2 2 - 49 NT40143
CPPACCGE 2 - 48 NT40143
CPPACCGE2 2 - 49 NT40143
A CPPACCS1GE 2 - 48 NT40143
CPPACCS1GE2 2 - 49 NT40143
A CPPACCS2GE 2 - 48 NT40143
CPPACCS2GE2 2 - 49 NT40143
A CPPACCS3GE 2 - 48 NT40143
CPPACCS3GE2 2 - 49 NT40143
A CPPACCS4GE 2 - 48 NT40143
CPPACCS4GE2 2 - 49 NT40143
A CPPACCS5GE 2 - 48 NT40143
CPPACCS5GE2 2 - 49 NT40143
A CPPACCS6GE 2 - 48 NT40143
CPPACCS6GE2 2 - 49 NT40143
A CPPACCS7GE 2 - 48 NT40143
CPPACCS7GE2 2 - 49 NT40143
CPPBNC400GT 2 - 61 NT40143
CPPBS250 2 - 51 NT40143
CPPD92268 2 - 51 NT40143
CPPDCL001 2 - 51 NT40143
CPPES100DTL 1 - 47 NT40143
CPPES200DTL 1 - 47 NT40143
CPPES300DTL 1 - 47 NT40143
CPPES400DTL 1 - 47 NT40143
CPPES500DTL 1 - 47 NT40143
I CPPFK1 2 - 50 NT40143
Alphanumeric Index
A CPS 60G 2 - 45 NT40143
CPS 60M160G 2 - 45 NT40143
CPS 60M160O 2 - 46 NT40143
CPS 60M250G 2 - 45 NT40143
CPS 60M250O 2 - 46 NT40143
A CPS 60O 2 - 46 NT40143
A CPS 72G 2 - 45 NT40143
CPS 72M250G 2 - 45 NT40143
CPS 72M250O 2 - 46 NT40143
A CPS 72O 2 - 46 NT40143
A CPS 84G 2 - 45 NT40143
CPS 84M250G 2 - 45 NT40143
A CPS 96G 2 - 45 NT40143
CPS 96M250G 2 - 45 NT40143
CPS 96M250O 2 - 46 NT40143
A CPS 96O 2 - 46 NT40143
CPSCHEDULECARD 2 - 57 NT40143
CPSCHEDULEHOLD 2 - 57 NT40143
CPTPSC1-100N 1 - 57 NE90129
CPTPSC1-12/230IR 1 - 57 NE90129
CPTPSC-12-230MOD 1 - 57 NE90129
CPTPSC1-25/230IR 1 - 57 NE90129
CPTPSC1-25N 1 - 57 NE90129
CPTPSC1-50N 1 - 57 NE90129
CPTPSC2-12/230IR 1 - 57 NE90129
CPTPSC2-25/230IR 1 - 57 NE90129
CPTPSC-25-230MOD 1 - 57 NE90129
CPTPSC4-12/400IR 1 - 57 NE90129
CPTPSC4-25/400IR 1 - 57 NE90129
CPTPSM1- 20/230 IR 1 - 59 NE90129
CPTPSM1- 20N 1 - 59 NE90129
CPTPSM1- 40/230 IR 1 - 59 NE90129
CPTPSM1- 40N 1 - 59 NE90129
CPTPSM-20-230MOD 1 - 59 NE90129
CPTPSM2- 20/230 IR 1 - 59 NE90129
CPTPSM2- 40/230 IR 1 - 59 NE90129
CPTPSM-40-230MOD 1 - 59 NE90129
CPTPSM4- 20/400 IR 1 - 59 NE90129
CPTPSM4- 40/400 IR 1 - 59 NE90129
CPWIL0 2 - 30 NT40143
CPWIL02 2 - 30 NT40143
CPWIL1 2 - 30 NT40143
CPWIL12 2 - 30 NT40143
CPWIL2 2 - 30 NT40143
CPWIL22 2 - 30 NT40143
CPWIL3 2 - 30 NT40143
CPWIL32 2 - 30 NT40143
CPWIL4 2 - 30 NT40143
CPWIL42 2 - 30 NT40143
Alphanumeric Index
CSB36FT 2-5 NT10135
CSB36FW 2-5 NT10135
CSB36ST 2-4 NT10135
CSB36SW 2-4 NT10135
CSPC1 2-2 NT30141
A CST160MS 2 - 30 NT40143
A CST 24G 2 - 27 NT40143
A CST 24M160G 2 - 27 NT40143
CST 24M160O 2 - 28 NT40143
CST 24M250G 2 - 27 NT40143
CST 24M250O 2 - 28 NT40143
A CST 24O 2 - 28 NT40143
A CST250MS 2 - 30 NT40143
A CST 36G 2 - 27 NT40143
A CST 36M160G 2 - 27 NT40143
A CST 36M160O 2 - 28 NT40143
CST 36M250G 2 - 27 NT40143
CST 36M250O 2 - 28 NT40143
A CST 36O 2 - 28 NT40143
A CST 48G 2 - 27 NT40143
A CST 48M160G 2 - 27 NT40143
CST 48M250G 2 - 27 NT40143
A CST 60G 2 - 27 NT40143
A CST 60M160G 2 - 27 NT40143
CST 60M160O 2 - 28 NT40143
CST 60M250G 2 - 27 NT40143
A CST 60M250O 2 - 28 NT40143
A CST 60O 2 - 28 NT40143
A CST 72G 2 - 27 NT40143
CST 72M250G 2 - 27 NT40143
CST 72M250O 2 - 28 NT40143
A CST 72O 2 - 28 NT40143
I A CST 96G 2 - 27 NT40143
CST 96M250G 2 - 27 NT40143
CST 96M250O 2 - 28 NT40143
I A CST 96O 2 - 28 NT40143
CT 212/253 2 - 67 NT40143
CT 218/253 2 - 67 NT40143
CT 224/253 2 - 67 NT40143
CT 230/253 2 - 67 NT40143
CT 236/253 2 - 67 NT40143
CT 242/253 2 - 67 NT40143
CT 248/253 2 - 67 NT40143
CT 260/253 2 - 67 NT40143
CT 272/253 2 - 67 NT40143
CT 284/253 2 - 67 NT40143
CT 296/253 2 - 67 NT40143
I CT 312/253 2 - 68 NT40143
I CT 318/253 2 - 68 NT40143
Alphanumeric Index
D
D1000 0010 7 - 44 NB20067
D1000DINCLIPS 7 - 44 NB20067
DCLD6 1 - 50 NT30141
DINT10H1100C 1 - 22 NT10136
I DINT10H1100D 1 - 22 NT10136
DINT10H1125C 1 - 22 NT10136
DINT10H1125D 1 - 22 NT10136
DINT10H180C 1 - 22 NT10136
DINT10H180D 1 - 22 NT10136
DINT10H2100C 1 - 22 NT10136
I DINT10H2100D 1 - 22 NT10136
DINT10H2125C 1 - 22 NT10136
I DINT10H2125D 1 - 22 NT10136
DINT10H280C 1 - 22 NT10136
DINT10H280D 1 - 22 NT10136
DINT10H3100C 1 - 22 NT10136
DINT10H3100D 1 - 22 NT10136
DINT10H3125C 1 - 22 NT10136
DINT10H3125C 2 - 31 NT10136
DINT10H3125D 1 - 22 NT10136
DINT10H380C 1 - 22 NT10136
DINT10H380D 1 - 22 NT10136
DINT10H4100C 1 - 22 NT10136
I DINT10H4100D 1 - 22 NT10136
I DINT10H4125C 1 - 22 NT10136
I DINT10H4125D 1 - 22 NT10136
I DINT10H480C 1 - 22 NT10136
I DINT10H480D 1 - 22 NT10136
DINT10H HS 1 - 40 NT10136
DINT10HTC 1 - 50 NT30141
DINTMS1001 1 - 38 NT10136
DINTMS1002 1 - 38 NT10136
DINTMS1003 1 - 38 NT10136
DINTMS1003 2 - 30 NT10136
DINTMS631 1 - 38 NT10136
DINTMS632 1 - 38 NT10136
DINTMS633 1 - 38 NT10136
DINTMS801 1 - 38 NT10136
DINTMS802 1 - 38 NT10136
DINTMS803 1 - 38 NT10136
DINTMS803 2 - 30 NT10136
DINTSHT110415U 1 - 39 NT30141
DINTSHT2460U 1 - 39 NT30141
I DINTT100 2 - 64 NT40143
DINTT100 2 - 64 NT40143
A DM15036 2-6 NT40143
A DM15054 2-6 NT40143
A DM15072 2-6 NT40143
Alphanumeric Index
DSRCBH1030A 1 - 29 NT30141
DSRCBH1610A 1 - 29 NT30141
DSRCBH1630A 1 - 29 NT30141
DSRCBH2010A 1 - 29 NT30141
DSRCBH2030A 1 - 29 NT30141
I DSRCBH2510A 1 - 29 NT30141
DSRCBH2530A 1 - 29 NT30141
I DSRCBH3210A 1 - 29 NT30141
DSRCBH3230A 1 - 29 NT30141
I DSRCBH4010A 1 - 29 NT30141
DSRCBH4030A 1 - 29 NT30141
DSRCBHTC 1 - 50 NT30141
I DSRCBS0630B 1 - 28 NT30141
DSRCBS0630C 1 - 28 NT30141
I DSRCBS1030B 1 - 28 NT30141
DSRCBS1030C 1 - 28 NT30141
I DSRCBS1630B 1 - 28 NT30141
DSRCBS1630C 1 - 28 NT30141
I DSRCBS2030B 1 - 28 NT30141
DSRCBS2030C 1 - 28 NT30141
I DSRCBS2530B 1 - 28 NT30141
DSRCBS2530C 1 - 28 NT30141
I DSRCBS3230B 1 - 28 NT30141
DSRCBS3230C 1 - 28 NT30141
DSRCBSAX 1 - 40 NT10136
DSRCBSAXAL 1 - 40 NT10136
I DSRCBSAXALG 1 - 40 NT10136
DSRCD240100 1 - 25 NT30141
I DSRCD240100A 1 - 26 NT30141
DSRCD24030 1 - 25 NT30141
DSRCD240300 1 - 25 NT30141
DSRCD24030A 1 - 26 NT30141
DSRCD24030AI 1 - 25 NT30141
DSRCD263100S 1 - 25 NT30141
DSRCD26330 1 - 25 NT30141
DSRCD263300S 1 - 25 NT30141
I DSRCD26330A 1 - 26 NT30141
DSRCD26330AI 1 - 25 NT30141
DSRCD280100 1 - 25 NT30141
I DSRCD280100A 1 - 26 NT30141
DSRCD28030 1 - 25 NT30141
I DSRCD280300 1 - 25 NT30141
I DSRCD28030A 1 - 26 NT30141
DSRCD4100100 1 - 25 NT30141
DSRCD4100100S 1 - 25 NT30141
DSRCD410030 1 - 25 NT30141
DSRCD4100300 1 - 25 NT30141
DSRCD4100300S 1 - 25 NT30141
I DSRCD410030A 1 - 26 NT30141
Alphanumeric Index
DTC2020240L 1 - 54 NT30141
DTC202024L 1 - 54 NT30141
DTC2404240 1 - 52 NT30141
DTC244012 1 - 52 NT30141
DTC244024 1 - 52 NT30141
DTC2440240 1 - 52 NT30141
DTC2504240L 1 - 54 NT30141
DTC254012L 1 - 54 NT30141
DTC2540240L 1 - 54 NT30141
I DTC404024 1 - 52 NT30141
DTC4040240 1 - 52 NT30141
DTC4040240L 1 - 54 NT30141
I DTC634024 1 - 52 NT30141
DTC6340240 1 - 52 NT30141
DTC6340240L 1 - 54 NT30141
DTCB10 1 01C 1 - 20 NT10136
I DTCB10 1 01D 1 - 21 NT10136
DTCB10 1 02C 1 - 20 NT10136
DTCB10 1 02D 1 - 21 NT10136
DTCB10 1 04C 1 - 20 NT10136
DTCB10 1 04D 1 - 21 NT10136
DTCB10 1 05C 1 - 20 NT10136
I DTCB10 1 05D 1 - 21 NT10136
DTCB10 1 06B 1 - 19 NT10136
DTCB10 1 06C 1 - 20 NT10136
DTCB10 1 06D 1 - 21 NT10136
DTCB10 1 10B 1 - 19 NT10136
DTCB10 1 10C 1 - 20 NT10136
DTCB10 1 10D 1 - 21 NT10136
I DTCB10 1 13C 1 - 20 NT10136
I DTCB10 1 13D 1 - 21 NT10136
DTCB10 1 16B 1 - 19 NT10136
DTCB10 1 16C 1 - 20 NT10136
DTCB10 1 16D 1 - 21 NT10136
DTCB10 1 20B 1 - 19 NT10136
DTCB10 1 20C 1 - 20 NT10136
DTCB10 1 20D 1 - 21 NT10136
DTCB10 1 25B 1 - 19 NT10136
DTCB10 1 25C 1 - 20 NT10136
DTCB10 1 25D 1 - 21 NT10136
DTCB10 1 32B 1 - 19 NT10136
DTCB10 1 32C 1 - 20 NT10136
DTCB10 1 32D 1 - 21 NT10136
DTCB10 1 40B 1 - 19 NT10136
DTCB10 1 40C 1 - 20 NT10136
DTCB10 1 40D 1 - 21 NT10136
I DTCB10 1 50B 1 - 19 NT10136
DTCB10 1 50C 1 - 20 NT10136
DTCB10 1 50D 1 - 21 NT10136
Alphanumeric Index
DTCB10 3 06C 1 - 20 NT10136
DTCB10 3 06D 1 - 21 NT10136
DTCB10 3 10B 1 - 19 NT10136
DTCB10 3 10C 1 - 20 NT10136
DTCB10 3 10D 1 - 21 NT10136
I DTCB10 3 13C 1 - 20 NT10136
I DTCB10 3 13D 1 - 21 NT10136
DTCB10 3 16B 1 - 19 NT10136
DTCB10 3 16C 1 - 20 NT10136
DTCB10 3 16D 1 - 21 NT10136
DTCB10 3 20B 1 - 19 NT10136
DTCB10 3 20C 1 - 20 NT10136
DTCB10 3 20D 1 - 21 NT10136
DTCB10 3 25B 1 - 19 NT10136
DTCB10 3 25C 1 - 20 NT10136
DTCB10 3 25D 1 - 21 NT10136
DTCB10 3 32B 1 - 19 NT10136
DTCB10 3 32C 1 - 20 NT10136
DTCB10 3 32D 1 - 21 NT10136
DTCB10 3 40B 1 - 19 NT10136
DTCB10 3 40C 1 - 20 NT10136
DTCB10 3 40D 1 - 21 NT10136
I DTCB10 3 50B 1 - 19 NT10136
DTCB10 3 50C 1 - 20 NT10136
DTCB10 3 50D 1 - 21 NT10136
DTCB10 3 63B 1 - 19 NT10136
DTCB10 3 63C 1 - 20 NT10136
DTCB10 3 63D 1 - 21 NT10136
I DTCB10 4 01C 1 - 20 NT10136
DTCB10 4 02C 1 - 20 NT10136
I DTCB10 4 04C 1 - 20 NT10136
I DTCB10 4 04D 1 - 21 NT10136
DTCB10 4 06C 1 - 20 NT10136
I DTCB10 4 06D 1 - 21 NT10136
DTCB10 4 10C 1 - 20 NT10136
I DTCB10 4 10D 1 - 21 NT10136
I DTCB10 4 13C 1 - 20 NT10136
I DTCB10 4 13D 1 - 21 NT10136
DTCB10 4 16C 1 - 20 NT10136
I DTCB10 4 16D 1 - 21 NT10136
DTCB10 4 20C 1 - 20 NT10136
I DTCB10 4 20D 1 - 21 NT10136
DTCB10 4 25C 1 - 20 NT10136
DTCB10 4 25D 1 - 21 NT10136
DTCB10 4 32C 1 - 20 NT10136
DTCB10 4 32D 1 - 21 NT10136
DTCB10 4 40C 1 - 20 NT10136
I DTCB10 4 40D 1 - 21 NT10136
DTCB10 4 50C 1 - 20 NT10136
Alphanumeric Index
DTCB6110C 1 - 14 NT10136
DTCB6110D 1 - 15 NT10136
DTCB6113C 1 - 14 NT10136
DTCB6113D 1 - 15 NT10136
DTCB6116C 1 - 14 NT10136
DTCB6116D 1 - 15 NT10136
DTCB6120C 1 - 14 NT10136
DTCB6120D 1 - 15 NT10136
DTCB6125C 1 - 14 NT10136
DTCB6125D 1 - 15 NT10136
DTCB6132C 1 - 14 NT10136
DTCB6132D 1 - 15 NT10136
DTCB6140C 1 - 14 NT10136
DTCB6140D 1 - 15 NT10136
DTCB6150C 1 - 14 NT10136
DTCB6150D 1 - 15 NT10136
DTCB6163C 1 - 14 NT10136
DTCB6163D 1 - 15 NT10136
DTCB6202C 1 - 14 NT10136
DTCB6202D 1 - 15 NT10136
DTCB6204C 1 - 14 NT10136
DTCB6204D 1 - 15 NT10136
DTCB6206C 1 - 14 NT10136
DTCB6206D 1 - 15 NT10136
DTCB6210C 1 - 14 NT10136
DTCB6210D 1 - 15 NT10136
I DTCB6213C 1 - 14 NT10136
I DTCB6213D 1 - 15 NT10136
DTCB6216C 1 - 14 NT10136
DTCB6216D 1 - 15 NT10136
DTCB6220C 1 - 14 NT10136
DTCB6220D 1 - 15 NT10136
DTCB6225C 1 - 14 NT10136
DTCB6225D 1 - 15 NT10136
DTCB6232C 1 - 14 NT10136
DTCB6232D 1 - 15 NT10136
DTCB6240C 1 - 14 NT10136
DTCB6240D 1 - 15 NT10136
DTCB6250C 1 - 14 NT10136
DTCB6250D 1 - 15 NT10136
DTCB6263C 1 - 14 NT10136
DTCB6263D 1 - 15 NT10136
DTCB6302C 1 - 14 NT10136
DTCB6302D 1 - 15 NT10136
DTCB6304C 1 - 14 NT10136
DTCB6304D 1 - 15 NT10136
DTCB6306C 1 - 14 NT10136
DTCB6306D 1 - 15 NT10136
DTCB6310C 1 - 14 NT10136
Alphanumeric Index
I DTCBD6440C 1 - 16 NT10136
DTCBDC101C 1 - 17 NT10136
DTCBDC102C 1 - 17 NT10136
DTCBDC104C 1 - 17 NT10136
I DTCBDC105C 1 - 17 NT10136
DTCBDC106C 1 - 17 NT10136
DTCBDC110C 1 - 17 NT10136
DTCBDC116C 1 - 17 NT10136
DTCBDC120C 1 - 17 NT10136
DTCBDC125C 1 - 17 NT10136
DTCBDC132C 1 - 17 NT10136
DTCBDC140C 1 - 17 NT10136
DTCBDC150C 1 - 17 NT10136
DTCBDC163C 1 - 17 NT10136
DTCBDC201C 1 - 17 NT10136
DTCBDC202C 1 - 17 NT10136
DTCBDC204C 1 - 17 NT10136
DTCBDC206C 1 - 17 NT10136
DTCBDC210C 1 - 17 NT10136
DTCBDC216C 1 - 17 NT10136
DTCBDC220C 1 - 17 NT10136
DTCBDC225C 1 - 17 NT10136
DTCBDC232C 1 - 17 NT10136
DTCBDC240C 1 - 17 NT10136
DTCBDC250C 1 - 17 NT10136
DTCBDC263C 1 - 17 NT10136
DTCBDC410B 1 - 18 NT10136
DTCBDC416B 1 - 18 NT10136
I DTCBDC420B 1 - 18 NT10136
I DTCBE6106C 1 - 24 NT10136
DTCBE6110C 1 - 24 NT10136
DTCBE6116C 1 - 24 NT10136
DTCBE6120C 1 - 24 NT10136
DTCBE6125C 1 - 24 NT10136
DTCBE6132C 1 - 24 NT10136
I DTCBE6140C 1 - 24 NT10136
I DTCBE6150C 1 - 24 NT10136
DTCBE6163C 1 - 24 NT10136
I DTCBE6306C 1 - 24 NT10136
I DTCBE6310C 1 - 24 NT10136
I DTCBE6316C 1 - 24 NT10136
I DTCBE6320C 1 - 24 NT10136
I DTCBE6325C 1 - 24 NT10136
I DTCBE6332C 1 - 24 NT10136
I DTCBE6340C 1 - 24 NT10136
I DTCBE6350C 1 - 24 NT10136
I DTCBE6363C 1 - 24 NT10136
DTCF35 1 - 50 NT30141
DTCS3212 1 - 44 NT30141
Alphanumeric Index
A DTPC2LDRCBO 1 - 49 NT40143
DTPC4 2-2 NT30141
A DTPC4LD 1 - 49 NT40143
A DTPC4LD 2-2 NT40143
A DTPC4LDCB 1 - 48 NT30141
DTPC4LDCBV 1 - 48 NT30141
DTPC6 2-2 NT30141
DTPC8 2-2 NT30141
DTPF 1 - 50 NT30141
DTPF 2 - 16 NT30141
DTPF 2 - 31 NT30141
DTPF 2 - 51 NT30141
DTPF 3 - 41 NT30141
DTPF 3 - 68 NT30141
DTPLB 1 - 44 NT30141
DTPLL24 1 - 44 NT30141
DTPLL240 1 - 44 NT30141
I DTPLLCL 1 - 44 NT30141
DTPLLGR 1 - 44 NT30141
DTPLLOR 1 - 44 NT30141
DTPLLRD 1 - 44 NT30141
DTSHT110415V 1 - 39 NT30141
DTSHT2460V 1 - 39 NT30141
DTSP 1 - 50 NT30141
DTTAX16PN3 1 - 50 NT30141
DTTAX25PN 1 - 50 NT30141
DTTAX25SP 1 - 50 NT30141
DTTAX50PN 1 - 50 NT30141
DTTC35 1 - 50 NT30141
DTTC5 1 - 50 NT30141
DTTLT35LPN 1 - 50 NT30141
DTTLT35PN 1 - 50 NT30141
DTTLT35SP 1 - 50 NT30141
I DTUVT12VDC 1 - 39 NT30141
DTUVT240VAC 1 - 39 NT30141
DTUVT24VDC 1 - 39 NT30141
E
E125 NJ 3 100 3 - 24 NT20138
E125 NJ 3 125 3 - 24 NT20138
E125 NJ 3 20 3 - 24 NT20138
E125 NJ 3 32 3 - 24 NT20138
E125 NJ 3 50 3 - 24 NT20138
E125 NJ 3 63 3 - 24 NT20138
E250 NJ 3 100 3 - 47 NT20138
E250 NJ 3 125 3 - 47 NT20138
E250 NJ 3 160 3 - 47 NT20138
E250 NJ 3 20 3 - 47 NT20138
E250 NJ 3 250 3 - 47 NT20138
E250 NJ 3 32 3 - 47 NT20138
Alphanumeric Index
I GB248183TF 2 - 62 NT40143
GB248183U 2 - 62 NT40143
GB248184U 2 - 63 NT40143
I GB260183TF 2 - 62 NT40143
GB260183U 2 - 62 NT40143
I GB272181TF 2 - 64 NT40143
I GB272182TF 2 - 63 NT40143
GB272182TF 2 - 63 NT40143
I GB272183PNTF 2 - 63 NT40143
GB272183PNU 2 - 63 NT40143
I GB272183TF 2 - 62 NT40143
GB272183U 2 - 62 NT40143
GB272184U 2 - 63 NT40143
I GB284183TF 2 - 62 NT40143
GB284183U 2 - 62 NT40143
I GB296181TF 2 - 64 NT40143
I GB296182TF 2 - 63 NT40143
GB296182TF 2 - 63 NT40143
I GB296183PNTF 2 - 63 NT40143
GB296183PNU 2 - 63 NT40143
I GB296183TF 2 - 62 NT40143
GB296183U 2 - 62 NT40143
GB296184U 2 - 63 NT40143
GBBBC 2 - 64 NT40143
GBIC 2 - 64 NT40143
GBIB 2 - 64 NT40143
GBL148L 2 - 64 NT40143
GBL148R 2 - 64 NT40143
GBL4996L 2 - 64 NT40143
GBL4996R 2 - 64 NT40143
GBLM 2 - 64 NT40143
GBPL3P 2 - 64 NT40143
GBPL4P 2 - 64 NT40143
GBSPP3P 2 - 64 NT40143
GBSPP4P 2 - 64 NT40143
GBTOC 2 - 51 NT40143
GBTB1 2 - 64 NT40143
GBTB2 2 - 64 NT40143
GBTB3 2 - 64 NT40143
GBTB4 2 - 64 NT40143
GBTOC 2 - 64 NT40143
GBUSL 2 - 64 NT40143
H
H125 NJ 3 100 3 - 30 NT20138
H125 NJ 3 125 3 - 30 NT20138
H125 NJ 3 20 3 - 30 NT20138
H125 NJ 3 32 3 - 30 NT20138
H125 NJ 3 50 3 - 30 NT20138
H125 NJ 3 63 3 - 30 NT20138
Alphanumeric Index
I H800 NE 3 AG # 3 - 109 NT20138
I H800 NE 3 AP # 3 - 109 NT20138
I H800 NE 3 APG # 3 - 109 NT20138
H800 NE 4 630 3 - 109 NT20138
H800 NE 4 800 3 - 109 NT20138
H800 NE 4 800 X1L 3 - 110 NT20138
H800 NE 4 800 X1S 3 - 110 NT20138
I H800 NE 4 AGN # 3 - 109 NT20138
I H800 NE 4 AN # 3 - 109 NT20138
I H800 NE 4 AP # 3 - 109 NT20138
I H800 NE 4 APN # 3 - 109 NT20138
HC12153 4 - 16 NT40143
HC12183 4 - 16 NT40143
HC12213 4 - 16 NT40143
HC12243 4 - 16 NT40143
HC12273 4 - 16 NT40143
HC12303 4 - 16 NT40143
HC12333 4 - 16 NT40143
HC12363 4 - 16 NT40143
HC12393 4 - 16 NT40143
HC12423 4 - 16 NT40143
HC12453 4 - 16 NT40143
HC16153 4 - 16 NT40143
HC16183 4 - 16 NT40143
HC16213 4 - 16 NT40143
HC16243 4 - 16 NT40143
HC16273 4 - 16 NT40143
HC16303 4 - 16 NT40143
HC16333 4 - 16 NT40143
HC16363 4 - 16 NT40143
HC16393 4 - 16 NT40143
HC16423 4 - 16 NT40143
HC16453 4 - 16 NT40143
HC22153 4 - 16 NT40143
HC22183 4 - 16 NT40143
HC22213 4 - 16 NT40143
HC22243 4 - 16 NT40143
HC22273 4 - 16 NT40143
HC22303 4 - 16 NT40143
HC22333 4 - 16 NT40143
HC22363 4 - 16 NT40143
HC22393 4 - 16 NT40143
HC22423 4 - 16 NT40143
HC22453 4 - 16 NT40143
HCD250 4 - 17 NT40143
HCD250P 4 - 17 NT40143
HCD800 4 - 17 NT40143
HCDN630 4 - 17 NT40143
HCDW630 4 - 17 NT40143
Alphanumeric Index
A ILC4SLD10H 1 - 49 NT40143
A ILC4SLD10H 2-3 NT40143
ILC4SLDCB1001P 1 - 48 NT40143
ILC4SLDCB1001PD 1 - 48 NT40143
ILC4SLDCB1003P 1 - 48 NT40143
ILC4SLDCB1003PD 1 - 48 NT40143
ILC4SLDCB1251P 1 - 48 NT40143
ILC4SLDCB1251PD 1 - 48 NT40143
ILC4SLDCB1253P 1 - 48 NT40143
ILC4SLDCB1253PD 1 - 48 NT40143
ILC4SLDCB1P 1 - 48 NT40143
ILC4SLDCB1PD 1 - 48 NT40143
ILC4SLDCB801P 1 - 48 NT40143
ILC4SLDCB801PD 1 - 48 NT40143
ILC4SLDCB803P 1 - 48 NT40143
ILC4SLDCB803PD 1 - 48 NT40143
ILC 8EN 2-3 NT40143
ILC 8S 2-3 NT40143
ILCSB 2-3 NT40143
IRC 5 - 28 NT30141
IRC 5 - 29 NT30141
ISO 3160SFH 2 - 31 NB20064
ISO 3160SFH 2 - 69 NB20064
K
KEY92268 2 - 16 NT40143
KEY92268 2 - 30 NT40143
KEY92268 2 - 51 NT40143
KEYCL001 2 - 16 NT40143
KEYCL001 2 - 30 NT40143
KEYCL001 2 - 51 NT40143
L
I L125 NJ 3 100 3 - 31 NT20138
I L125 NJ 3 125 3 - 31 NT20138
I L125 NJ 3 20 3 - 31 NT20138
I L125 NJ 3 32 3 - 31 NT20138
I L125 NJ 3 50 3 - 31 NT20138
I L125 NJ 3 63 3 - 31 NT20138
I L125 NJ 4 100 3 - 31 NT20138
I L125 NJ 4 125 3 - 31 NT20138
I L125 NJ 4 20 3 - 31 NT20138
I L125 NJ 4 32 3 - 31 NT20138
I L125 NJ 4 50 3 - 31 NT20138
I L125 NJ 4 63 3 - 31 NT20138
L125 PJ 3 100 3 - 29 NT20138
L125 PJ 3 125 3 - 29 NT20138
L125 PJ 3 20 3 - 29 NT20138
L125 PJ 3 32 3 - 29 NT20138
L125 PJ 3 50 3 - 29 NT20138
L125 PJ 3 63 3 - 29 NT20138
Alphanumeric Index
LSIG 6 - 25 NT20138
LSIG 6 - 36 NT30141
LSIP 3 - 132 NT30141
LSIP 6 - 25 NT20138
LSIP 6 - 36 NT30141
M
A M22IVS 1 - 42 NT40143
MCEPCN5MFM 2-7 NB20054
MCEPCN9MFM 2-7 NB20054
I A MH6S633 5-9 NZ00150
I A MH6S644 5-9 NZ00150
I A MS12S1033 5-9 NZ00150
I A MS12S1044 5-9 NZ00150
I A MS12S1233 5-9 NZ00150
I A MS12S1244 5-9 NZ00150
I A MS16S1633 5-9 NZ00150
I A MS16S1644 5-9 NZ00150
I A MS20E2033 5-9 NZ00150
I A MS20E2044 5-9 NZ00150
I A MS25E2533 5-9 NZ00150
I A MS25E2544 5-9 NZ00150
I A MS6N433 5-9 NZ00150
I A MS6N444 5-9 NZ00150
I A MS6N633 5-9 NZ00150
I A MS6N644 5-9 NZ00150
I A MS6S633 5-9 NZ00150
I A MS6S644 5-9 NZ00150
I A MS8N833 5-9 NZ00150
I A MS8N844 5-9 NZ00150
I A MS8S833 5-9 NZ00150
I A MS8S844 5-9 NZ00150
MST 5 - 28 NT30141
MST 5 - 29 NT30141
N
NC212/183U 2 - 58 NT40143
NC218/183U 2 - 58 NT40143
NC224182U 2 - 60 NT40143
NC224183PNU 2 - 59 NT40143
NC224/183U 2 - 58 NT40143
NC224/184U 2 - 59 NT40143
NC230/183U 2 - 58 NT40143
NC236182U 2 - 60 NT40143
NC236/183U 2 - 58 NT40143
NC236/184U 2 - 59 NT40143
NC242/183U 2 - 58 NT40143
NC248182U 2 - 60 NT40143
NC248183PNU 2 - 59 NT40143
NC248/183U 2 - 58 NT40143
NC248/184U 2 - 59 NT40143
Alphanumeric Index
NCH46/2427/183U 2 - 60 NT40143
NCH46/273U 2 - 60 NT40143
NCH46/3627/183U 2 - 60 NT40143
NCH46/4827/183U 2 - 60 NT40143
NCL243 2 - 61 NT40143
NCL24C 2 - 61 NT40143
NCS250GT 2 - 61 NT40143
NEB185 1 - 50 NT40143
NEB185 2 - 57 NT40143
NEB33S 2 - 57 NT40143
NLC12FE 2-9 NT40143
NLC12S 2-9 NT40143
NLC15FE 2-9 NT40143
NLC15S 2-9 NT40143
NLC18FE 2-9 NT40143
NLC18S 2-9 NT40143
NLC21FE 2-9 NT40143
NLC21S 2-9 NT40143
NLC24S 2-9 NT40143
NLC8FE 2-9 NT40143
NLC8S 2-9 NT40143
P
PRE-TRIP ALARM 6 - 10 NT20138
I PXB80012U 4-4 NT40143
I PXB80018U 4-4 NT40143
I PXB80024U 4-4 NT40143
I PXB80030U 4-4 NT40143
I PXB80036U 4-4 NT40143
I PXB80042U 4-4 NT40143
I PXB80048U 4-4 NT40143
I PXB80060U 4-4 NT40143
I PXB8006U 4-4 NT40143
I PXB80072U 4-4 NT40143
R
RD1B212 8-5 NT30141
RD1B214 8-5 NT30141
RD1B215 8-5 NT30141
I RD1B21H 8-5 NT30141
I RD1DF12 8-6 NT30141
RD1DF14 8-6 NT30141
I RD1DF15 8-6 NT30141
RD1EP212 8-7 NT30141
RD1EP214 8-7 NT30141
RD1EP215 8-7 NT30141
RD1EP21H 8-7 NT30141
RD1G212 8 - 10 NT30141
I RD1G214 8 - 10 NT30141
I RD1G215 8 - 10 NT30141
RD3AF12 (110 V AC) 8-4 NT30141
Alphanumeric Index
S125 GJ 3 20 3 - 28 NT20138
S125 GJ 3 32 3 - 28 NT20138
S125 GJ 3 50 3 - 28 NT20138
I S125 GJ 3 50PM 3 - 146 NT20138
S125 GJ 3 63 3 - 28 NT20138
S125 GJ 3 63PM 3 - 146 NT20138
S125 GJ 4 100 3 - 28 NT20138
S125 GJ 4 125 3 - 28 NT20138
S125 GJ 4 20 3 - 28 NT20138
S125 GJ 4 32 3 - 28 NT20138
S125 GJ 4 50 3 - 28 NT20138
S125 GJ 4 63 3 - 28 NT20138
I S125ND3 3 - 143 NT20138
I S125ND4 3 - 143 NT20138
S125 NF 1 100 3 - 25 NT20138
S125 NF 1 125 3 - 25 NT20138
S125 NF 1 16 3 - 25 NT20138
S125 NF 1 20 3 - 25 NT20138
S125 NF 1 25 3 - 25 NT20138
S125 NF 1 32 3 - 25 NT20138
S125 NF 1 40 3 - 25 NT20138
S125 NF 1 50 3 - 25 NT20138
S125 NF 1 63 3 - 25 NT20138
S125 NF 1 80 3 - 25 NT20138
S125 NJ 3 100 3 - 27 NT20138
S125 NJ 3 125 3 - 27 NT20138
S125 NJ 3 20 3 - 27 NT20138
S125 NJ 3 20PM 3 - 146 NT20138
S125 NJ 3 32 3 - 27 NT20138
S125 NJ 3 32PM 3 - 146 NT20138
S125 NJ 3 50 3 - 27 NT20138
S125 NJ 3 63 3 - 27 NT20138
S125NN3 3 - 142 NT20138
I S125NN4 3 - 142 NT20138
S1600 NE 3 1250 3 - 122 NT20138
I S1600 NE 3 AG # 3 - 122 NT20138
I S1600 NE 3 AP # 3 - 122 NT20138
I S1600 NE 3 APG # 3 - 122 NT20138
S1600 NE 4 1250 3 - 122 NT20138
I S1600 NE 4 AGN # 3 - 122 NT20138
I S1600 NE 4 AN # 3 - 122 NT20138
I S1600 NE 4 AP # 3 - 122 NT20138
I S1600 NE 4 APN # 3 - 122 NT20138
S1600NN3 3 - 142 NT20138
S1600NN4 3 - 142 NT20138
S160 GJ 3 100 3 - 44 NT20138
S160 GJ 3 125 3 - 44 NT20138
S160 GJ 3 160 3 - 44 NT20138
S160 GJ 3 160PM 3 - 146 NT20138
Alphanumeric Index
S250NN3 3 - 142 NT20138
S250NN4 3 - 142 NT20138
S250 PE 3 125 3 - 52 NT20138
S250 PE 3 125 AC 3 - 54 NT20138
S250 PE 3 250 3 - 52 NT20138
S250 PE 3 250 AC 3 - 54 NT20138
S250 PE 3 40 AC 3 - 54 NT20138
I S250 PE 3 AP 3 3 - 52 NT20138
I S250 PE 4 125 3 - 52 NT20138
I S250 PE 4 125 AC 3 - 54 NT20138
S250 PE 4 250 3 - 52 NT20138
I S250 PE 4 250 AC 3 - 54 NT20138
I S250 PE 4 40 AC 3 - 54 NT20138
I S250 PE 4 AN 4 3 - 52 NT20138
I S250 PE 4 AP 4 3 - 52 NT20138
I S250 PE 4 APN 4 3 - 52 NT20138
S400 CJ 3 250 3 - 70 NT20138
S400 CJ 3 400 3 - 70 NT20138
S400 GE 3 250 3 - 75 NT20138
S400 GE 3 250 X1L 3 - 76 NT20138
S400 GE 3 250 X1S 3 - 76 NT20138
S400 GE 3 400 3 - 75 NT20138
S400 GE 3 400PM 3 - 146 NT20138
S400 GE 3 400 X1L 3 - 76 NT20138
S400 GE 3 400 X1S 3 - 76 NT20138
S400 GE 3 AG 400 3 - 75 NT20138
I S400 GE 3 AP 400 3 - 75 NT20138
I S400 GE 3 APG 400 3 - 75 NT20138
I S400 GE 4 250 3 - 75 NT20138
S400 GE 4 250 X1L 3 - 76 NT20138
S400 GE 4 250 X1S 3 - 76 NT20138
S400 GE 4 400 3 - 75 NT20138
I S400 GE 4 400 X1L 3 - 76 NT20138
I S400 GE 4 400 X1S 3 - 76 NT20138
S400 GE 4 AGN 400 3 - 75 NT20138
I S400 GE 4 AN 400 3 - 75 NT20138
I S400 GE 4 AP 400 3 - 75 NT20138
I S400 GE 4 APN 400 3 - 75 NT20138
S400 GJ 3 250 3 - 73 NT20138
S400 GJ 3 400 3 - 73 NT20138
I S400 GJ 4 250 3 - 73 NT20138
S400 GJ 4 400 3 - 73 NT20138
I S400ND3 3 - 143 NT20138
S400 NE 3 250 3 - 72 NT20138
S400 NE 3 400 3 - 72 NT20138
S400 NE 4 250 3 - 72 NT20138
S400 NE 4 400 3 - 72 NT20138
S400 NJ 3 250 3 - 71 NT20138
S400 NJ 3 400 3 - 71 NT20138
Alphanumeric Index
I S800 RE 3 AG # 3 - 107 NT20138
I S800 RE 3 AP # 3 - 107 NT20138
I S800 RE 3 APG # 3 - 107 NT20138
S800 RE 4 630 3 - 107 NT20138
S800 RE 4 800 3 - 107 NT20138
I S800 RE 4 800 X1L 3 - 108 NT20138
I S800 RE 4 800 X1S 3 - 108 NT20138
I S800 RE 4 AGN # 3 - 107 NT20138
I S800 RE 4 AN # 3 - 107 NT20138
I S800 RE 4 AP # 3 - 107 NT20138
I S800 RE 4 APN # 3 - 107 NT20138
S800 RJ 3 630 3 - 105 NT20138
S800 RJ 3 800 3 - 105 NT20138
S800 RJ 4 630 3 - 105 NT20138
S800 RJ 4 800 3 - 105 NT20138
SAFET6106 1-7 NT10136
I SAFET6106SHT 1-8 NT10136
SAFET6110 1-7 NT10136
SAFET61100 1-7 NT10136
SAFET61100NA 1-7 NT10136
I SAFET61100NASHT 1-8 NT10136
I SAFET61100SHT 1-8 NT10136
I SAFET6110SHT 1-8 NT10136
SAFET6116 1-7 NT10136
SAFET6116SHT 1-8 NT10136
SAFET6120 1-7 NT10136
SAFET6120SHT 1-8 NT10136
SAFET6125 1-7 NT10136
SAFET6125SHT 1-8 NT10136
SAFET6132 1-7 NT10136
SAFET6132SHT 1-8 NT10136
SAFET6140 1-7 NT10136
I SAFET6140SHT 1-8 NT10136
SAFET6150 1-7 NT10136
I SAFET6150SHT 1-8 NT10136
SAFET6163 1-7 NT10136
SAFET6163NA 1-7 NT10136
I SAFET6163NASHT 1-8 NT10136
I SAFET6163SHT 1-8 NT10136
SAFET6180 1-7 NT10136
I SAFET6180SHT 1-8 NT10136
SAFET6206 1-7 NT10136
I SAFET6206SHT 1-8 NT10136
SAFET6210 1-7 NT10136
I SAFET62100 1-7 NT10136
I SAFET62100NA 1-7 NT10136
I SAFET62100NASHT 1-8 NT10136
I SAFET62100SHT 1-8 NT10136
I SAFET6210SHT 1-8 NT10136
Alphanumeric Index
I SAFET64100NA 1-7 NT10136
I SAFET64100NASHT 1-8 NT10136
I SAFET64100SHT 1-8 NT10136
I SAFET6410SHT 1-8 NT10136
I SAFET6416 1-7 NT10136
I SAFET6416SHT 1-8 NT10136
SAFET6420 1-7 NT10136
I SAFET6420SHT 1-8 NT10136
I SAFET6425 1-7 NT10136
I SAFET6425SHT 1-8 NT10136
SAFET6432 1-7 NT10136
I SAFET6432SHT 1-8 NT10136
I SAFET6440 1-7 NT10136
I SAFET6440SHT 1-8 NT10136
SAFET6450 1-7 NT10136
SAFET6450SHT 1-8 NT10136
SAFET6463 1-7 NT10136
I SAFET6463NA 1-7 NT10136
I SAFET6463NASHT 1-8 NT10136
I SAFET6463SHT 1-8 NT10136
SAFET6480 1-7 NT10136
I SAFET6480SHT 1-8 NT10136
SAFETLCK 12 1-9 NT10136
SAFETLCK 24 1-9 NT10136
SAFE-TPC1 2-2 NT10136
SAFE-TPC23 2-2 NT10136
SAFETPF 1-9 NT10136
SAFETPF 2 - 10 NT10136
SAFETPF 2 - 31 NT10136
SAFETPF 2 - 51 NT10136
SPD1 5 - 28 NT30141
SPD1 5 - 29 NT30141
SPD3 5 - 28 NT30141
SPD3 5 - 29 NT30141
I SRCB 1010 1 - 10 NT10136
SRCB 1030 1 - 10 NT10136
SRCB 1610 1 - 10 NT10136
SRCB 1630 1 - 10 NT10136
SRCB 2010 1 - 10 NT10136
SRCB 2030 1 - 10 NT10136
SRCBHA 1 - 10 NT10136
SRCBLCK 12 1 - 10 NT10136
SRCBLCK 24 1 - 10 NT10136
SRCBWA 1 - 10 NT10136
SSW2 5 - 28 NB20052
SSW2 5 - 29 NB20052
SSW3 5 - 28 NB20052
SSW3 5 - 29 NB20052
STK250ND/TH 2 - 31 NT40143
Alphanumeric Index
T2AL00M3RTA 3 - 123 NT20138
T2AL00M3STA 3 - 32 NT20138
T2AL00M3STA 3 - 59 NT20138
T2AL00M3STA 3 - 92 NT20138
T2AL00M3SWA 3 - 32 NT20138
T2AL00M3SWA 3 - 59 NT20138
T2AL00M3SWA 3 - 92 NT20138
T2AL00M4STA 3 - 115 NT20138
T2AL00M4STA 3 - 123 NT20138
T2AL00M5SWA 3 - 115 NT20138
T2AL00M5SWA 3 - 123 NT20138
T2AX00B1STA 3 - 32 NT20138
T2AX00B1STA 3 - 59 NT20138
T2AX00B1STA 3 - 92 NT20138
T2AX00B1STA 3 - 115 NT20138
T2AX00B1STA 3 - 123 NT20138
T2AX00B2STA 3 - 32 NT20138
T2AX00B2STA 3 - 59 NT20138
T2AX00B2STA 3 - 92 NT20138
T2AX00B2STA 3 - 115 NT20138
T2AX00B2STA 3 - 123 NT20138
T2AX00M3RTA 3 - 32 NT20138
T2AX00M3RTA 3 - 59 NT20138
T2AX00M3RTA 3 - 92 NT20138
T2AX00M3RTA 3 - 115 NT20138
T2AX00M3RTA 3 - 123 NT20138
T2AX00M3STA 3 - 32 NT20138
T2AX00M3STA 3 - 59 NT20138
T2AX00M3STA 3 - 92 NT20138
T2AX00M3STA 3 - 115 NT20138
T2AX00M3STA 3 - 123 NT20138
T2AX00M3SWA 3 - 32 NT20138
T2AX00M3SWA 3 - 59 NT20138
T2AX00M3SWA 3 - 92 NT20138
T2AX00M3SWA 3 - 115 NT20138
T2AX00M3SWA 3 - 123 NT20138
T2AX00M4SWA 3 - 115 NT20138
T2AX00M4SWA 3 - 123 NT20138
I T2AX00M5SWA 3 - 115 NT20138
I T2AX00M5SWA 3 - 123 NT20138
T2BA123SHA 3 - 38 NT20138
T2BA123SHA 4 - 14 NT20138
T2BA253LHA 3 - 38 NT20138
T2BA253LHA 3 - 65 NT20138
T2BA253LHA 4 - 14 NT20138
T2BA253SHA 3 - 65 NT20138
T2BA253SHA 4 - 14 NT20138
I T2BA403LHA 3 - 98 NT20138
T2BA403SHA 3 - 98 NT20138
Alphanumeric Index
T2CLSBB25033 5 - 34 NT30141
I T2CLSBB25043 5 - 34 NT30141
T2CLSBB25044 5 - 34 NT30141
T2CLSBB40033 5 - 34 NT30141
I T2CLSBB40043 5 - 34 NT30141
T2CLSBB40044 5 - 34 NT30141
T2CLSBB63033 5 - 34 NT30141
T2CLSBB63043 5 - 34 NT30141
T2CLSBB63044 5 - 34 NT30141
T2CR123SG 3 - 38 NT20138
T2CR123SG 4 - 14 NT20138
T2CR124SG 3 - 38 NT20138
T2CR124SG 4 - 14 NT20138
T2CR253SG 3 - 38 NT20138
T2CR253SG 3 - 65 NT20138
T2CR253SG 4 - 14 NT20138
T2CR254SG 3 - 38 NT20138
T2CR254SG 3 - 65 NT20138
T2CR254SG 4 - 14 NT20138
T2CR403SG 3 - 98 NT20138
T2CR403SG 4 - 13 NT20138
T2CR403SG 4 - 14 NT20138
T2CR404SG 3 - 98 NT20138
T2CR404SG 4 - 13 NT20138
T2CR803LHGA 3 - 118 NT20138
T2CR803SHGA 3 - 118 NT20138
T2CR804LHGA 3 - 118 NT20138
T2CR804SHGA 3 - 118 NT20138
T2CS121SG 3 - 37 NT20138
T2CS121SG 4 - 13 NT20138
T2CS122SG 4 - 13 NT40143
T2CS123SG 3 - 37 NT20138
T2CS123SG 4 - 13 NT20138
T2CS124SG 3 - 37 NT20138
T2CS124SG 4 - 13 NT20138
T2CS251SG 3 - 64 NT20138
T2CS251SG 4 - 13 NT40143
T2CS253SG 3 - 37 NT20138
T2CS253SG 3 - 64 NT20138
T2CS253SG 4 - 13 NT20138
T2CS254SG 3 - 37 NT20138
T2CS254SG 3 - 64 NT20138
T2CS254SG 4 - 13 NT20138
T2DA12A 3 - 41 NT20138
I T2DF25A 3 - 41 NT20138
I T2DF25A 3 - 68 NT20138
I T2DF40A 3 - 101 NT20138
I T2DM25A 3 - 41 NT20138
I T2DM25A 3 - 68 NT20138
Alphanumeric Index
A T2HL25CAP 3 - 38 NT20138
A T2HL25CAP 3 - 65 NT20138
T2HL40A 3 - 99 NT20138
T2HL40A 3 - 119 NT20138
A T2HL40CAP 3 - 99 NT20138
T2HL80CAP 3 - 119 NT20138
A T2HLS125NFCAP 3 - 38 NT30141
A T2HLS160NFCAP 3 - 65 NT30141
T2HLX6A 3 - 127 NT20138
T2HLX6CAP 3 - 127 NT20138
T2HP12R6BN 3 - 34 NT20138
T2HP12R6RN 3 - 34 NT20138
A T2HP25PALK 3 - 34 NT30141
A T2HP25PALK 3 - 34 NT30141
A T2HP25PALK 3 - 61 NT30141
T2HP25R6BN 3 - 34 NT20138
T2HP25R6BN 3 - 61 NT20138
T2HP25R6RN 3 - 34 NT20138
T2HP25R6RN 3 - 61 NT20138
A T2HP40PALK 3 - 94 NT30141
T2HP40R6BN 3 - 94 NT20138
T2HP40R6RN 3 - 94 NT20138
T2HP80PALK 3 - 116 NT20138
T2HP80R6BN 3 - 116 NT20138
T2HP80R6ME 3 - 116 NT20138
T2HP80R6RN 3 - 116 NT20138
T2HPX6PALK 3 - 124 NT20138
T2HPX6R6BN 3 - 124 NT20138
T2HPX6R6ME 3 - 124 NT20138
T2HPX6R6RN 3 - 124 NT20138
A T2HS12R5GM 3 - 34 NT20138
T2HS12R5RM 3 - 34 NT20138
T2HS250SHAFT 3 - 22 NT20138
T2HS250SHAFT 3 - 34 NT20138
T2HS250SHAFT 3 - 34 NT20138
T2HS250SHAFT 3 - 61 NT20138
A T2HS25R5GM 3 - 34 NT20138
A T2HS25R5GM 3 - 61 NT20138
A T2HS25R5RM 3 - 34 NT20138
A T2HS25R5RM 3 - 61 NT20138
T2HS400SHAFT 3 - 94 NT20138
T2HS400SHAFT 3 - 116 NT20138
T2HS400SHAFT 3 - 124 NT20138
T2HS400SHAFT 6 - 11 NT20138
T2HS400SHAFT 6 - 26 NT20138
T2HS400SHAFT 6 - 37 NT20138
A T2HS40R5GM 3 - 94 NT20138
A T2HS40R5RM 3 - 94 NT20138
T2HS80R6GM 3 - 116 NT20138
Alphanumeric Index
T2ML40L3B 3 - 95 NT20138
T2ML40L4B 3 - 95 NT20138
T2ML40RB 3 - 95 NT20138
T2ML80L3A 3 - 117 NT20138
T2ML80L4A 3 - 117 NT20138
T2ML80RA 3 - 117 NT20138
I A T2MLH40L3B 3 - 95 NT20138
I A T2MLH40L4B 3 - 95 NT20138
I A T2MLH40RB 3 - 95 NT20138
T2MM25L05A 3 - 33 NT20138
T2MM25L05A 3 - 60 NT20138
T2MM25L15A 3 - 33 NT20138
T2MM25L15A 3 - 60 NT20138
T2MM40L06A 3 - 93 NT20138
T2MM40L06A 3 - 119 NT20138
T2MM40L21A 3 - 93 NT20138
T2MM40L21A 3 - 119 NT20138
T2MM40S06A 3 - 119 NT20138
T2MM40S21A 3 - 119 NT20138
I T2MS123SFA 3 - 36 NT20138
I T2MS124SFA 3 - 36 NT20138
T2MS253LFA 3 - 36 NT20138
T2MS253LFA 3 - 63 NT20138
I T2MS253SFA 3 - 63 NT20138
T2MS254LFA 3 - 36 NT20138
T2MS254LFA 3 - 63 NT20138
I T2MS254SFA 3 - 63 NT20138
I T2MS403SFA 3 - 96 NT20138
I T2MS404SFA 3 - 96 NT20138
T2MS803LFA 3 - 117 NT20138
T2MS803SFA 3 - 117 NT20138
T2MS804LFA 3 - 117 NT20138
T2MS804SFA 3 - 117 NT20138
T2MSX63SFA 3 - 125 NT20138
T2MSX64SFA 3 - 125 NT20138
T2MW00L 3 - 125 NT20138
T2MW00LA 3 - 36 NT20138
T2MW00LA 3 - 63 NT20138
T2MW00LA 3 - 96 NT20138
T2MW00LA 3 - 117 NT20138
T2MW00S 3 - 125 NT20138
T2MW00SA 3 - 36 NT20138
T2MW00SA 3 - 63 NT20138
T2MW00SA 3 - 96 NT20138
T2MW00SA 3 - 117 NT20138
T2MW12CA 3 - 36 NT20138
T2MW25CA 3 - 36 NT20138
T2MW25CA 3 - 63 NT20138
T2MW40CB 3 - 96 NT20138
Alphanumeric Index
T2SH00A10TA 3 - 59 NT20138
T2SH00A10TA 3 - 92 NT20138
T2SH00A10TA 3 - 115 NT20138
T2SH00A10TA 3 - 123 NT20138
T2SH00A20TA 3 - 32 NT20138
T2SH00A20TA 3 - 59 NT20138
T2SH00A20TA 3 - 92 NT20138
T2SH00A20TA 3 - 115 NT20138
T2SH00A20TA 3 - 123 NT20138
T2SH00A40TA 3 - 32 NT20138
T2SH00A40TA 3 - 59 NT20138
T2SH00A40TA 3 - 92 NT20138
T2SH00A40TA 3 - 115 NT20138
T2SH00A40TA 3 - 123 NT20138
I T2SH00D01TA 3 - 115 NT20138
I T2SH00D01TA 3 - 123 NT20138
T2SH00D02TA 3 - 32 NT20138
T2SH00D02TA 3 - 59 NT20138
T2SH00D02TA 3 - 92 NT20138
T2SH00D02TA 3 - 115 NT20138
T2SH00D02TA 3 - 123 NT20138
T2SH00D04TA 3 - 32 NT20138
T2SH00D04TA 3 - 59 NT20138
T2SH00D04TA 3 - 92 NT20138
T2SH00D04TA 3 - 115 NT20138
T2SH00D04TA 3 - 123 NT20138
T2SH00D10TA 3 - 32 NT20138
T2SH00D10TA 3 - 59 NT20138
T2SH00D10TA 3 - 92 NT20138
T2SH00D10TA 3 - 115 NT20138
T2SH00D10TA 3 - 123 NT20138
T2SH00D20TA 3 - 32 NT20138
T2SH00D20TA 3 - 59 NT20138
T2SH00D20TA 3 - 92 NT20138
T2SH00D20TA 3 - 115 NT20138
T2SH00D20TA 3 - 123 NT20138
T2SH16A10WA 3 - 59 NT20138
T2SH16A20WA 3 - 59 NT20138
T2SH16D02WA 3 - 59 NT20138
T2SH16D10WA 3 - 59 NT20138
T2SH16D20WA 3 - 59 NT20138
A T2SW3P1251255K 3 - 20 NT20138
A T2SW3P125TC 3 - 20 NT20138
A T2SW3P2501505K 3 - 20 NT20138
A T2SW3P2502505K 3 - 20 NT20138
A T2SW3P250TC 3 - 20 NT20138
A T2SW3P250TC 3 - 20 NT20138
A T2SW3P6304005K 3 - 20 NT20138
A T2SW3P6306005K 3 - 20 NT20138
Alphanumeric Index
T2UV80D02NTA 3 - 123 NT20138
T2UV00D10NTA 3 - 32 NT20138
T2UV00D10NTA 3 - 59 NT20138
T2UV00D10NTA 3 - 92 NT20138
T2UV80D10NTA 3 - 115 NT20138
T2UV80D10NTA 3 - 123 NT20138
I T2UV00D20NTA 3 - 32 NT20138
I T2UV00D20NTA 3 - 59 NT20138
I T2UV00D20NTA 3 - 92 NT20138
I T2UV80D20NTA 3 - 115 NT20138
I T2UV80D20NTA 3 - 123 NT20138
T40CAPLAB 3 - 93 NZ00150
T40CAPLAB 3 - 94 NZ00150
T40CAPLAB 3 - 94 NZ00150
T40CAPLAB 3 - 95 NZ00150
T40CAPLAB 3 - 95 NZ00150
T40CAPLAB 3 - 96 NZ00150
T40CAPLAB 5 - 36 NZ00150
T80CAPLAB 3 - 116 NT20138
TAA5LY 1-9 NT10136
TAL111 1 - 68 NB30088
TAL111MINI 1 - 68 NB30088
TAL171 1 - 68 NB30088
TAL211 1 - 68 NB30088
TAL211MINI 1 - 68 NB30088
TAL271 1 - 68 NB30088
TAL371MP240VAC 1 - 68 NB30088
TAL371PRO 1 - 68 NB30088
TAL372PRO 1 - 68 NB30088
TAL471PRO 1 - 68 NB30088
TAL472PRO 1 - 68 NB30088
TAL791PRO 1 - 68 NB30088
TAL892PLUSTOP 1 - 68 NB30088
TAL892PLUSTOP 1 - 68 NB30088
TALCEPLUSTOP 1 - 68 NB30088
I TDAA2 8 - 14 NT30141
I TDAB2 8 - 14 NT30141
TDAC2 8 - 14 NT30141
TDB50SG12 1-9 NT10136
I TDGA2 8 - 14 NT30141
TDGB2 8 - 14 NT30141
TDGC2 8 - 14 NT30141
TDGD2 8 - 14 NT30141
TDGE2 8 - 14 NT30141
TDGF2 8 - 14 NT30141
TDGH2 8 - 14 NT30141
TEMRELAY 7 - 32 NT40143
TEMVISIONMAX 7 - 32 NT40143
I A TEMVISIONPRO 7 - 32 NT40143
Alphanumeric Index
TKNHP0B 6 - 37 NB20071
TKNHP0C 2 - 22 NB20071
TKNHP0C 3 - 39 NB20071
TKNHP0C 3 - 66 NB20071
TKNHP0C 3 - 99 NB20071
TKNHP0C 6 - 27 NB20071
TKNHP0C 6 - 37 NB20071
TKNHP0D 2 - 22 NB20071
TKNHP0D 3 - 39 NB20071
TKNHP0D 3 - 66 NB20071
TKNHP0D 3 - 99 NB20071
TKNHP0D 6 - 27 NB20071
TKNHP0D 6 - 37 NB20071
TKNHP0E 2 - 22 NB20071
TKNHP0E 3 - 39 NB20071
TKNHP0E 3 - 66 NB20071
TKNHP0E 3 - 99 NB20071
TKNHP0E 6 - 27 NB20071
TKNHP0E 6 - 37 NB20071
TKNHP0F 2 - 22 NB20071
TKNHP0F 3 - 39 NB20071
TKNHP0F 3 - 66 NB20071
TKNHP0F 3 - 99 NB20071
TKNHP0F 6 - 27 NB20071
TKNHP0F 6 - 37 NB20071
TKNHP0G 2 - 22 NB20071
TKNHP0G 3 - 39 NB20071
TKNHP0G 3 - 66 NB20071
TKNHP0G 3 - 99 NB20071
TKNHP0G 6 - 27 NB20071
TKNHP0G 6 - 37 NB20071
TKNHP0H 2 - 22 NB20071
TKNHP0H 3 - 39 NB20071
TKNHP0H 3 - 66 NB20071
TKNHP0H 3 - 99 NB20071
TKNHP0H 6 - 27 NB20071
TKNHP0H 6 - 37 NB20071
TKNHP0I 2 - 22 NB20071
TKNHP0I 3 - 39 NB20071
TKNHP0I 3 - 66 NB20071
TKNHP0I 3 - 99 NB20071
TKNHP0I 6 - 27 NB20071
TKNHP0I 6 - 37 NB20071
TKNHP0J 2 - 22 NB20071
TKNHP0J 3 - 39 NB20071
TKNHP0J 3 - 66 NB20071
TKNHP0J 3 - 99 NB20071
TKNHP0J 6 - 27 NB20071
TKNHP0J 6 - 37 NB20071
Alphanumeric Index
TKNHP0T 3 - 39 NB20071
TKNHP0T 3 - 66 NB20071
TKNHP0T 3 - 99 NB20071
TKNHP0T 6 - 27 NB20071
TKNHP0T 6 - 37 NB20071
TKNHP0U 2 - 22 NB20071
TKNHP0U 3 - 39 NB20071
TKNHP0U 3 - 66 NB20071
TKNHP0U 3 - 99 NB20071
TKNHP0U 6 - 27 NB20071
TKNHP0U 6 - 37 NB20071
TKNHPKEY0A 2 - 22 NB20071
TKNHPKEY0A 3 - 39 NB20071
TKNHPKEY0A 3 - 66 NB20071
TKNHPKEY0A 3 - 99 NB20071
TKNHPKEY0A 6 - 27 NB20071
TKNHPKEY0A 6 - 37 NB20071
TKNHPKEY0B 2 - 22 NB20071
TKNHPKEY0B 3 - 39 NB20071
TKNHPKEY0B 3 - 66 NB20071
TKNHPKEY0B 3 - 99 NB20071
TKNHPKEY0B 6 - 27 NB20071
TKNHPKEY0B 6 - 37 NB20071
TKNHPKEY0C 2 - 22 NB20071
TKNHPKEY0C 3 - 39 NB20071
TKNHPKEY0C 3 - 66 NB20071
TKNHPKEY0C 3 - 99 NB20071
TKNHPKEY0C 6 - 27 NB20071
TKNHPKEY0C 6 - 37 NB20071
TKNHPKEY0D 2 - 22 NB20071
TKNHPKEY0D 3 - 39 NB20071
TKNHPKEY0D 3 - 66 NB20071
TKNHPKEY0D 3 - 99 NB20071
TKNHPKEY0D 6 - 27 NB20071
TKNHPKEY0D 6 - 37 NB20071
TKNHPKEY0E 2 - 22 NB20071
TKNHPKEY0E 3 - 39 NB20071
TKNHPKEY0E 3 - 66 NB20071
TKNHPKEY0E 3 - 99 NB20071
TKNHPKEY0E 6 - 27 NB20071
TKNHPKEY0E 6 - 37 NB20071
TKNHPKEY0F 2 - 22 NB20071
TKNHPKEY0F 3 - 39 NB20071
TKNHPKEY0F 3 - 66 NB20071
TKNHPKEY0F 3 - 99 NB20071
TKNHPKEY0F 6 - 27 NB20071
TKNHPKEY0F 6 - 37 NB20071
TKNHPKEY0G 2 - 22 NB20071
TKNHPKEY0G 3 - 39 NB20071
Alphanumeric Index
TKNHPKEY0O 3 - 99 NB20071
TKNHPKEY0O 6 - 27 NB20071
TKNHPKEY0O 6 - 37 NB20071
TKNHPKEY0P 2 - 22 NB20071
TKNHPKEY0P 3 - 39 NB20071
TKNHPKEY0P 3 - 66 NB20071
TKNHPKEY0P 3 - 99 NB20071
TKNHPKEY0P 6 - 27 NB20071
TKNHPKEY0P 6 - 37 NB20071
TKNHPKEY0Q 2 - 22 NB20071
TKNHPKEY0Q 3 - 39 NB20071
TKNHPKEY0Q 3 - 66 NB20071
TKNHPKEY0Q 3 - 99 NB20071
TKNHPKEY0Q 6 - 27 NB20071
TKNHPKEY0Q 6 - 37 NB20071
TKNHPKEY0R 2 - 22 NB20071
TKNHPKEY0R 3 - 39 NB20071
TKNHPKEY0R 3 - 66 NB20071
TKNHPKEY0R 3 - 99 NB20071
TKNHPKEY0R 6 - 27 NB20071
TKNHPKEY0R 6 - 37 NB20071
TKNHPKEY0S 2 - 22 NB20071
TKNHPKEY0S 3 - 39 NB20071
TKNHPKEY0S 3 - 66 NB20071
TKNHPKEY0S 3 - 99 NB20071
TKNHPKEY0S 6 - 27 NB20071
TKNHPKEY0S 6 - 37 NB20071
TKNHPKEY0T 2 - 22 NB20071
TKNHPKEY0T 3 - 39 NB20071
TKNHPKEY0T 3 - 66 NB20071
TKNHPKEY0T 3 - 99 NB20071
TKNHPKEY0T 6 - 27 NB20071
TKNHPKEY0T 6 - 37 NB20071
A TL100EM 100 3K 6-7 NT20138
A TL100EM 15 3K 6-7 NT20138
A TL100EM 20 3K 6-7 NT20138
A TL100EM 30 3K 6-7 NT20138
A TL100EM 40 3K 6-7 NT20138
A TL100EM 50 3K 6-7 NT20138
A TL100EM 60 3K 6-7 NT20138
A TL100EM 75 3K 6-7 NT20138
TL100EMR5GM 6-8 NT20138
A TL100EMR6BN 6-8 NT20138
TL101240V 5 - 31 NT30141
A TL101CIP 5 - 31 NT30141
I TL1250NE 1000 3 FC 6 - 34 NT20138
I TL1250NE 1000 3 LG 6 - 34 NT30141
I TL1250NE 1250 3 FC 6 - 34 NT20138
I TL1250NE 1250 3 LG 6 - 34 NT30141
Alphanumeric Index
UXKB0003A 6 - 37 NT30141
UXKB0013A 3 - 38 NT20138
I UXKC0001B 6 - 11 NT20138
UXKC0002B 6 - 11 NT20138
I UXKC0003B 6 - 11 NT20138
UXKC0004A 6 - 26 NT20138
UXKC0005A 6 - 26 NT20138
UXKC0006D 6 - 36 NT30141
UXKC0007D 6 - 36 NT30141
UXKC0012A 3 - 132 NT30141
I UXKC0013A 3 - 132 NT30141
UXKC0020A 3 - 132 NT20138
UXKC0020A 6 - 11 NT20138
UXKC0020A 6 - 26 NT20138
UXKC0020A 6 - 36 NT20138
UXKC0021B 6 - 11 NT20138
UXKC0022B 6 - 26 NT20138
UXKC0023B 6 - 36 NT30141
UXKC0024B 6 - 36 NT30141
UXKC0025B 3 - 132 NT30141
UXKC0026C 6 - 36 NT30141
I UXKC0027C 6 - 36 NT30141
UXKE0030A 6-8 NT20138
I UXLB0006C 3 - 22 NT20138
I UXLB0008C 3 - 22 NT20138
UXLB0009D 6 - 10 NT20138
UXLB0010D 6 - 25 NT20138
UXLB0011D 6 - 35 NT30141
I UXLB0012C 3 - 131 NT30141
UXLB0013D 6 - 10 NT20138
UXLB0014D 6 - 10 NT20138
UXLB0015D 6 - 25 NT20138
UXLB0016D 6 - 25 NT20138
UXLB0017D 6 - 35 NT30141
UXLB0018D 6 - 35 NT30141
I UXLB0019D 3 - 131 NT30141
UXLB0020C 3 - 131 NT30141
I UXLB0021C 3 - 131 NT30141
I UXLB0023C 3 - 131 NT20138
I UXLB0024D 6 - 35 NT20138
UXLB0025D 6 - 35 NT20138
UXLB0026D 6 - 35 NT20138
I UXMB0006B 3 - 132 NT30141
UXMB0008B 3 - 132 NT30141
UXMB0009B 3 - 132 NT30141
I UXMC0001B 6 - 11 NT20138
I UXMC0003B 6 - 11 NT20138
I UXMC0004B 6 - 11 NT20138
UXMC0005B 6 - 11 NT20138
Alphanumeric Index
I UXUB0018B 6 - 35 NT20138
I UXUB0038B 3 - 131 NT20138
I UXUB0038B 6 - 10 NT20138
I UXUB0038B 6 - 25 NT20138
I UXUB0038B 6 - 35 NT20138
UXXB0001D 3 - 22 NT20138
UXXB0003C 3 - 22 NT20138
UXXB0004D 6 - 10 NT20138
UXXB0005D 6 - 10 NT20138
UXXB0006D 6 - 10 NT20138
UXXB0007D 6 - 25 NT20138
UXXB0008D 6 - 25 NT20138
UXXB0009D 6 - 25 NT20138
UXXB0010D 6 - 35 NT30141
UXXB0011D 6 - 35 NT30141
UXXB0012D 6 - 35 NT30141
UXXB0013C 3 - 131 NT30141
UXXB0014C 3 - 131 NT30141
I UXXB0015C 3 - 131 NT30141
I UXXB0016C 3 - 131 NT30141
I UXXB0017C 3 - 131 NT30141
I UXXB0018C 3 - 131 NT30141
I UXXB0023D 6 - 35 NT20138
UXXB0024D 6 - 35 NT20138
I UXXB0025D 6 - 35 NT20138
I UXYB0004A 6 - 27 NT20138
I UXYB0004A 6 - 27 NT20138
I UXYC0005A 6 - 27 NT20138
I UXYC0005A 6 - 27 NT20138
UXYD0001A 3 - 132 NT20138
UXYD0001A 6 - 12 NT20138
UXYD0001A 6 - 27 NT20138
UXYD0001A 6 - 37 NT20138
UXYD0002A 3 - 132 NT20138
UXYD0002A 6 - 12 NT20138
UXYD0002A 6 - 27 NT20138
UXYD0002A 6 - 37 NT20138
V
VS125NJ3100 6-5 NT20138
VS125NJ3125 6-5 NT20138
VS125NJ320 6-5 NT20138
VS125NJ332 6-5 NT20138
VS125NJ350 6-5 NT20138
VS125NJ363 6-5 NT20138
VS250NJ3160 6-6 NT20138
VS250NJ3250 6-6 NT20138
X
XA63012U 4-3 NT40143
I XA63016U4POLE 4-5 NT40143
Alphanumeric Index
I XB80048U4POLE 4-6 NT40143
XB80060U 4-3 NT40143
XB8006U 4-3 NT40143
XB80072U 4-3 NT40143
I XB8008U4POLE 4-6 NT40143
XBSSL 800 12U 4-7 NT40143
XBSSL 800 15U 4-7 NT40143
XBSSL 800 18U 4-7 NT40143
XBSSL 800 21U 4-7 NT40143
XBSSL 800 24U 4-7 NT40143
XBSSL 800 30U 4-7 NT40143
XBSSL 800 36U 4-7 NT40143
I XBSSL 800 3U 4-7 NT40143
XBSSL 800 6U 4-7 NT40143
XBSSL 800 9U 4-7 NT40143
XBSSR 800 12U 4-8 NT40143
XBSSR 800 15U 4-8 NT40143
XBSSR 800 18U 4-8 NT40143
XBSSR 800 21U 4-8 NT40143
XBSSR 800 24U 4-8 NT40143
XBSSR 800 30U 4-8 NT40143
XBSSR 800 36U 4-8 NT40143
I XBSSR 800 3U 4-8 NT40143
XBSSR 800 6U 4-8 NT40143
XBSSR 800 9U 4-8 NT40143
XC100012U 4-9 NT40143
XC100018U 4-9 NT40143
XC10001X4R12U 4 - 10 NT40143
XC10001X4R24U 4 - 10 NT40143
XC10001X4R36U 4 - 10 NT40143
XC100024U 4-9 NT40143
XC10002X4R12U 4 - 10 NT40143
XC10002X4R24U 4 - 10 NT40143
XC10002X4R36U 4 - 10 NT40143
XC100030U 4-9 NT40143
XC100036U 4-9 NT40143
XC100042U 4-9 NT40143
I XC100048U 4-9 NT40143
XC10006U 4-9 NT40143
XCW0840LS13 7-6 NZ00150
XCW0840LS16 7-6 NZ00150
I XDM6-3 6 - 27 NT20138
I XDM6-4 6 - 27 NT20138
XEC1640LS20 7-6 NZ00150
XEC1640LS25 7-6 NZ00150
XEC1640LS32 7-6 NZ00150
XEC1640LS40 7-6 NZ00150
XFE10 3 - 132 NT20138
I XH630PJ 400 3 6 - 15 NT20138
Alphanumeric Index
I XS2500ND25003RC 3 - 145 NT30141
XS2500NE 2500 RC3 3 - 129 NT20138
I XS2500NE 2500 RC4 3 - 129 NT20138
I XS2500NN3RC 3 - 142 NT30141
XS2500NN4FC 3 - 142 NT20138
XS2500SE 25003L 3 - 129 NT20138
I XS2500SE 25004L 3 - 129 NT20138
XS3200NE32003 RC 3 - 130 NT30141
A XS400OCRSK 6 - 12 NT20138
XS630NJ 400 3 6 - 14 NT20138
XS630NJ 630 3 6 - 14 NT20138
A XS630OCRSK 6 - 27 NT20138
XS630SE 630 3 6 - 16 NT20138
A XS630SE 6303LSIG 6 - 16 NT20138
XS630SE 630 4 6 - 16 NT20138
I A XS630SE 6304LSIG 6 - 16 NT20138
XS800NJ 800 3 6 - 19 NT20138
XS800NJ 800 4 6 - 19 NT20138
XS800NN3 6 - 13 NT20138
XS800SE 800 3 6 - 21 NT20138
A XS800SE 800 3LSIG 6 - 21 NT20138
XS800SE 800 4 6 - 21 NT20138
I A XS800SE 800 4LSIG 6 - 21 NT20138
A XV1250NE1000 3 K 6 - 30 NT20138
A XV1250NE1250 3 K 6 - 30 NT20138
I A XV1250NE 400 3 K 6 - 30 NT20138
A XV1250NE 800 3 K 6 - 30 NT20138
A XV400NE 160 3K 6-9 NT20138
A XV400NE 250 3K 6-9 NT20138
A XV400NE 400 3K 6-9 NT20138
A XV630PE 400 3K 6 - 24 NT20138
A XV630PE 630 3K 6 - 24 NT20138
A XV800PE 800 3K 6 - 24 NT20138
Y
A YASD22D 6-8 NT20138
A YASD34 6 - 11 NT20138
Z
ZS125 GJ 3 100 3 - 135 NT20138
ZS125 GJ 3 125 3 - 135 NT20138
ZS125 GJ 3 20 3 - 135 NT20138
ZS125 GJ 3 32 3 - 135 NT20138
ZS125 GJ 3 50 3 - 135 NT20138
ZS125 GJ 3 63 3 - 135 NT20138
ZS125 GJ 4 100 3 - 135 NT20138
ZS125 GJ 4 100 SN 3 - 135 NT20138
ZS125 GJ 4 125 3 - 135 NT20138
ZS125 GJ 4 125 SN 3 - 135 NT20138
ZS125 GJ 4 20 3 - 135 NT20138
ZS125 GJ 4 20 SN 3 - 135 NT20138
SERVICES
CORP-NHP SERVICE-CPB
Field support services Charge out fees*
NHP Service provides a comprehensive range of value 0OTJUF4UBOEBSEIPVSMZSBUFIS
add services that support and enhance the reliability and Normal business hours:
performance of NHP products. Our team of proficiently BNQN .POEBZUP'SJEBZ
qualified technicians are available for a variety of lifecycle "MMTJUFXPSLJTTVCKFDUUPNJOJNVNGPVSIPVST JODMVEFT
services, including: travel and organisation time).
r 1SPEVDUSFQBJSTBOETFSWJDF r .JOJNVNDIBSHFOPSNBMCVTJOFTTIPVST
r 0OTJUFFNFSHFODZCSFBLEPXOTFSWJDF IPVST UIFSFBGUFSIS
r 1SFWFOUBUJWFNBJOUFOBODF BOE r .JOJNVNDIBSHFBGUFSIPVST
r $PNNJTTJPOJOH IPVST UIFSFBGUFSIS
Product repairs and service r .JOJNVNDIBSHFQVCMJDIPMJEBZT
Our National Service Headquarters is based in Melbourne. IPVST UIFSFBGUFSIS
'PSPWFSZFBST XFIBWFTVQQPSUFEBMM/)1QSPEVDUT 3FUVSOUPCBTF4UBOEBSEIPVSMZSBUFIS
GSPNNPUPSTUBSUFSTUPDJSDVJUCSFBLFST5SBEJUJPOBMMZ "MMSFUVSOUPCBTFXPSLJODVSTBNJOJNVNFWBMVBUJPODIBSHF
products are returned to our National service centre for starting from $200, and thereafter a quote is issued for the
NBJOUFOBODFBOESFQBJS8IFOUIJTJTOPUQPTTJCMF XF SFQBJSTFSWJDFXPSLUPCFDPNQMFUFEPOUIFJUFN5IJTRVPUF
EFQMPZPVSñFMETFSWJDFUFDIOJDJBOTUPDPNQMFUFUIFUBTLT XJMMDPWFSCPUIMBCPVSBOEQBSUT
at customer sites. Overtime on request:
Products covered by NHP Service: r)PVSMZSBUFBGUFSIPVSTIS
1. NHP variable speed drives r)PVSMZSBUFGPSQVCMJDIPMJEBZTIS
2. NHP soft starters Special service quotes:
3. NHP auto transformer starters 5IFTFSWJDFTBMFTUFBNDBOBMTPDSFBUFTQFDJBMTFSWJDFRVPUFT
4. NHP liquid resistance starters GPSTDIFEVMFEXPSLPSNBJOUFOBODFDPOUSBDUT
5FSBTBLJ"$#T .$$#T Payment:
/)1QPXFSGBDUPSDPSSFDUJPOQBOFMTBOEQPXFS $VTUPNFSTUIBUEPOPUIBWFBOBDDPVOUXJUI/)1DBOVTF
quality products /)1TTFDVSF7*4"BOE.BTUFS$BSEDSFEJUDBSEGBDJMJUJFT
1SPEVDUTBOEPSTFSWJDFPíFSFEGPSTBMFJOUIJTQPDLFUCPPL
Emergency breakdown assistance BSFTVCKFDUUPPVSTUBOEBSE$POEJUJPOTPG4BMF BQQMJDBCMF
Modern facility managers demand consistency and BUUIFEBUFUIFPSEFSJTQMBDFE/)1TUBOEBSE$POEJUJPOTPG
efficiency of performance. In industrial applications, 4BMFDBOCFWJFXFEPOPVSXFCTJUFBU
production is paramount. http://www.nhp.com.au/cos or by requesting a copy for
In the case of commercial installations, continuity of service any of our offices.
is equally important. In either case, disruption can result in Contacts
DPTUMZMPTTFTBOEDPOTFRVFOUJBMEBNBHFT:PVXBOUBDUJPO
BOEZPVXBOUJUGBTU/)1TFSWJDFPíFSTQSPUFDUJPOUP Normal business hours: contact your local NHP branch.
FOTVSFUIBUZPVSQMBOUBOEFRVJQNFOUDPOUJOVFTUPXPSLGPS "GUFSIPVSTQIPOF/)1/)1XIFSFZPVSBGUFSIPVST
you. Our service technicians are on call and are equipped to TFSWJDFSFRVFTUXJMMCFBOTXFSFECZUFDIOJDBMMZUSBJOFE/)1
NJOJNJTFEPXOUJNF DVTUPNFSTFSWJDFTUBí XIPXJMMBTTFTTUIFMFWFMPGTFSWJDF
TVQQPSUSFRVJSFEBOEBSSBOHFGPSUIFXPSLUPCFDPNQMFUFE
Darwin
Cairns
Townsville
13
12
11
Rockhampton
14
15
Toowoomba Brisbane
16
22 21
9 19
Perth 7
6
17 23 20
Newcastle
10 Canberra Sydney
Adelaide Albury
8 2 4 18 Wollongong
1 Melbourne Auckland
NHP Branch Offices 3 24
5 Hamilton
NHP Resident Sales Staff Laverton Dandenong
New Plymouth
Launceston
Napier
Wellington
Hobart Christchurch
Dunedin
28
Valid until August 2014