Mde 5341F
Mde 5341F
MDE-5341F
Computer Programs and Documentation
All Gilbarco Inc. and/or Veeder-Root Company computer programs (including software on diskettes and within memory chips) and documentation are copyrighted by, and shall
remain the property of, Gilbarco Inc. and/or Veeder-Root Company. Such computer programs and documents may also contain trade secret information. The duplication, disclosure,
modification, or unauthorized use of computer programs or documentation is strictly prohibited, unless otherwise licensed by Gilbarco Inc. and/or Veeder-Root Company.
MID
The Frontier dispenser conforms to Measuring Instruments Directive (MID) 2004/22/EC.
The approval number is UK/0126/0170.
ATEX
The Frontier dispenser is ATEX certified. The approval number is ITS05ATEX53877.
Table of Contents
1 – Introduction 1-1
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Abbreviations and Acronyms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Common Terms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page i
Table of Contents
Index Index-1
Page ii MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Purpose Introduction
1 – Introduction
Purpose
This manual contains step-by-step instructions for installing Gilbarco® Frontier pumps and
dispensers. Installation of these pumps as a group is similar except for some differences in
field wiring, calibration, parameter setting, and hydraulic connections. This manual does not
include site preparation instructions. After the installation is complete, a Gilbarco Authorized
Service Contractor (ASC) must commission the unit to activate the warranty. Proper
completion of the checklist is required for commissioning of the unit.
IMPORTANT INFORMATION
Read and follow all safety precautions outlined in “Important Safety Information” on
page 2-1 and save it in a readily accessible location.
Biodiesel greater than 5% and ethanol greater than 10% is not evaluated.
Required Tools
The following tools are required for installing the Frontier pumps and dispensers:
• Flat-blade and Phillips® Screwdrivers
• 1/4-inch Nut Driver
• 5/16-inch Nut Driver
• 7-mm Nut Driver
• Putty knife
• Static Guard Wrist Strap
• Cutters
• Pliers
• Electronic Multimeter
Related Documents
Document
Number Title GOLDSM Library
MDE-2755 Gilbarco STP Control and Dispenser Isolation Relay Box PA0287 Environmental Products
MDE-5077 Frontier Owner’s Manual Frontier
MDE-5078 Frontier Technical Manual Frontier
FE-321 Gilbarco STP Isolation Relay Box PA0287 Engineering Diagrams
577013-796 In-station Diagnostic Vapor Flow Meter Installation Guide -
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 1-1
Introduction Abbreviations and Acronyms
Page 1-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Common Terms Introduction
Common Terms
Term Description
CIM Door CIM Door - Main pump and CRIND displays are mounted on this door.
Combo This unit is configured as Master on one side and Satellite on the other.
Dispenser A dispensing device that receives fuel under pressure from the Submersible Turbine Pump
(STP) at the Underground Storage Tank (UST).
Grade Fuel that is dispensed and has an assigned price.
Listed Products bearing authorized Listing Mark of Underwriters Laboratories (UL) as
manufacturer’s declaration that product complies with UL’s requirements in accordance
with terms of UL’s Listing and Follow-up Service agreement.
Master This unit dispenses fuel to one saddle tank and to a second saddle tank through a satellite
unit.
Product Refers to fuel in storage tank.
Pump A dispensing device that utilizes a self-contained pumping unit and motor to move fuel
from the storage tank using suction.
Satellite A dispensing unit that receives product from, and registers at the Master unit allowing both
saddle tanks on a vehicle to be filled at the same time.
SMART Meter™ Electronic device that measures the flow of product from the UST to the end user.
Teflon The DuPont™ trade name for PolyTetraFluoroEthylene (PTFE).
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 1-3
Introduction Common Terms
Page 1-4 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Important Safety Information
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 2-1
Important Safety Information
No Open Fire In an Emergency
Inform Emergency Personnel
Compile the following information and inform emergency
Open flames from matches, lighters, welding torches or other personnel:
sources can ignite fuels and their vapors. • Location of accident (for example, address, front/back of
No Sparks - No Smoking building, and so on)
• Nature of accident (for example, possible heart attack, run
over by car, burns, and so on)
Sparks from starting vehicles, starting or using power tools, • Age of victim (for example, baby, teenager, middle-age,
burning cigarettes, cigars or pipes can also ignite fuels and their elderly)
vapors. Static electricity, including an electrostatic charge on your • Whether or not victim has received first aid (for example,
body, can cause a spark sufficient to ignite fuel vapors. Every time you stopped bleeding by pressure, and so on)
get out of a vehicle, touch the metal of your vehicle, to discharge any • Whether or not a victim has vomited (for example, if
electrostatic charge before you approach the dispenser island. swallowed or inhaled something, and so on)
Working Alone
It is highly recommended that someone who is capable of rendering
! WARNING
first aid be present during servicing. Familiarize yourself with Gasoline/DEF ingested may cause unconsciousness
Cardiopulmonary Resuscitation (CPR) methods, if you work with or and burns to internal organs. Do not induce vomiting.
around high voltages. This information is available from the American Keep airway open.
Red Cross. Always advise the station personnel about where you will Oxygen may be needed at scene. Seek medical
be working, and caution them not to activate power while you are advice immediately.
working on the equipment. Use the OSHA Lockout/Tagout
procedures. If you are not familiar with this requirement, refer to this ! WARNING
information in the service manual and OSHA documentation. DEF generates ammonia gas at higher temperatures. When
Working With Electricity Safely opening enclosed panels, allow the unit to air out to avoid
Ensure that you use safe and established practices in working with breathing vapors. If respiratory difficulties develop, move victim
electrical devices. Poorly wired devices may cause a fire, explosion or away from source of exposure and into fresh air. If symptoms
electrical shock. Ensure that grounding connections are properly persist, seek medical attention.
made. Take care that sealing devices and compounds are in place.
Ensure that you do not pinch wires when replacing covers. Follow
OSHA Lockout/Tagout requirements. Station employees and service
! WARNING
contractors need to understand and comply with this program Gasoline inhaled may cause unconsciousness and
completely to ensure safety while the equipment is down. burns to lips, mouth and lungs.
Keep airway open.
Hazardous Materials
Seek medical advice immediately.
Some materials present inside electronic enclosures may present a
health hazard if not handled correctly. Ensure that you clean hands
after handling equipment. Do not place any equipment in the mouth ! WARNING
Gasoline/DEF spilled in eyes may cause burns to eye
! WARNING tissue.
In the event of inclement weather, including snow, ice, or flooding Irrigate eyes with water for approximately
that makes driving conditions dangerous, please avoid servicing 15 minutes.Seek medical advice immediately.
units. Always use available door stops to secure upper doors
against unwanted/unexpected movement, especially during high
winds. If necessary, reschedule service to avoid damage to the ! WARNING
equipment. Weather may change unexpectedly; be aware of local Gasoline/DEF spilled on skin may cause burns.
weather conditions. During service, if conditions develop making Wash area thoroughly with clear water.
service unsafe, close the unit(s) and proceed to a safe location. Seek medical advice immediately.
! WARNING ! WARNING
The pump/dispenser contains a chemical known to the State of DEF is mildly corrosive. Avoid contact with eyes, skin, and
California to cause cancer. clothing. Ensure that eyewash stations and safety showers are
close to the work location. Seek medical advice/recommended
treatment if DEF spills into eyes.
! WARNING
The pump/dispenser contains a chemical known to the State of IMPORTANT: Oxygen may be needed at scene if gasoline has
California to cause birth defects or other reproductive harm. been ingested or inhaled. Seek medical advice immediately.
Lockout/Tagout
Lockout/Tagout covers servicing and maintenance of machines
Gilbarco Veeder-Root encourages the recycling of our and equipment in which the unexpected energization or start-up
products. Some products contain electronics, batteries, of the machine(s) or equipment or release of stored energy
or other materials that may require special could cause injury to employees or personnel. Lockout/Tagout
management practices depending on your location. applies to all mechanical, hydraulic, chemical, or other energy,
Please refer to your local, state, or country regulations but does not cover electrical hazards. Subpart S of 29 CFR Part
for these requirements. 1910 - Electrical Hazards, 29 CFR Part 1910.333 contains
specific Lockout/Tagout provision for electrical hazards.
Page 2-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Important Safety Information
! WARNING
General Exclusion
Problems caused by faulty installation are not covered by this warranty. This warranty applies
only if equipment has been installed, used, and maintained in-accordance with Gilbarco
installation, operating, and service instruction.
Use of service personnel other than qualified Gilbarco ASCs without prior approval of
Gilbarco product support department will void payment of the warranty claim in question.
Damage suffered by Gilbarco equipment resulting from shipping, accident, power surges,
neglect, misuse, act of God, or abuse is not covered by this warranty.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 2-3
Important Safety Information
Page 2-4 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Zoning Diagram Hazardous Locations
3 – Hazardous Locations
Zoning Diagram
The dispenser must be installed to not compromise the zones illustrated in Figure 3-1 and
Figure 3-2 on page 3-2.
Figure 3-1: Zoning Diagram with Grill
Frontier pumps and dispensers are Atmosphere Explosible (ATEX) approved. Zoning diagram
is as per ATEX.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 3-1
Hazardous Locations Zoning Diagram
Frontier pumps and dispensers are ATEX approved. Zoning diagram is as per ATEX.
WARNING
National Fire Protection Association (NFPA) 70® section 514 table 3 defines the area under
the dispenser as a Class 1 Division 1 hazardous location.
Page 3-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Required Equipment and Materials Preliminary Installation Information
WARNING
Where fuels are involved, you are working in a dangerous environment of gasoline,
gasoline vapor, and electricity.
Failure to install this equipment in accordance with NFPA 30A and NFPA 70 could result in
severe injury or death.
Failure to install the equipment in accordance with NFPA 30A and NFPA 70 may adversely
affect the safe use and operation of the system.
Accurate, sound installations reduce service calls. Experienced, licensed contractors must
perform the installation and follow accurate and safe installation techniques. Careful
installation can eliminate potential problems.
The equipment manufacturer must provide instructions for other equipment such as STP, shear
valves, and underground tanks. Gilbarco does not provide complete installation instructions
for other manufacturer’s equipment.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 4-1
Preliminary Installation Information Important Considerations when Changing Fuel Types
WARNING
Certain special alternative fuels such as E25 and E85 and additives can degrade
pump/dispenser performance or integrity if the dispensers are not designed for use with
such fuels. Additionally, converting to certain standard fuels (gasoline, diesel, kerosene,
and so on) from alternative fuels such as those with ethanol (E25 and E85), methanol, or
biodiesel or from alternative fuels to standard fuels can degrade dispenser performance or
integrity. Similar effects can also occur when converting units to different standard fuel
types. As per UL 87A requirements, units dispensing E25 and E85 fuel must not be
used to dispense any other type of fuel such as gasoline.
Leaks and potential environmental hazards can result or components may fail prematurely.
The following guidelines must be followed when changing fuel types for a pump/dispenser or
using alternative fuels or fluids:
• Verify with your Gilbarco ASC or Distributor if the fuel which you will be using is
compatible with the pumps/dispensers to be dispensing the fuel.
• For flexible fuel dispensers, do not use standard hydraulic parts used in other Gilbarco
pumps/dispensers for service parts in these units. Standard dispenser parts may not be
compatible with fluids.
• Biodiesel fuels must be of American Society for Testing and Materials (ASTM) standards
for Biodiesel fuels. Mixes of diesel with cooking oils, other plant or animal derived oils,
and so on are not considered Biodiesel. Use of such mixes may void warranty on the
hydraulic components of the unit.
• Review the latest copy of the unit’s warranty statement regarding the use of fuel.
• Certain fuels (especially fuels enhanced with alcohol) when first used in tanks previously
containing a different fuel may clean out the tanks and force a large amount of
contaminant into the dispenser. Other than abnormally clogging filters, this large quantity
of contaminant may damage certain dispenser components. Do not run units without
filters at such times. It is normally required that tanks and lines be cleaned of all water,
sediment, and contaminant before such conversions to minimize potential
pump/dispenser downtime or damage. Damage to hydraulic components from
contamination when not using filters is not covered by Warranty. Consult your ASC or
Gilbarco Distributor for recommendations.
• Although conversions from one fuel to an equivalent fuel (say from another supplier)
generally do not create issues, it is recommended that after making any fuel type
conversions (including those to alternative fuels such as E25 and E85 or back), all units be
visually inspected for leaks two days, one week, and one month after fuel conversion.
Have your ASC repair any leaks found. This must also be performed for standard fuels
when significant new additives are incorporated.
• Whenever non-equivalent fuel conversions are performed, it is recommended that all units
be checked for calibration within one month of fuel conversion.
• Some non-equivalent fuel conversions will necessitate the requirement to change the
pump/dispenser filter type previously used. Consult your ASC or Gilbarco Distributor for
any changes required.
• In flexible fuel dispensers, Gilbarco recommends the use of 10 micron filters for
gasoline-based flexible fuels. Although the use of finer filtration is allowable, filters will
tend to clog prematurely, causing excessive filter maintenance cost.
• An anti-siphon valve must be installed on aboveground storage tanks where the DEF level
can be at a higher elevation than the supply piping or the dispenser. The valve will prevent
a potential leak in the piping from creating a siphon that can cause a product release.
Page 4-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Preparing for Installation Preliminary Installation Information
3 Use circuit breakers to turn off all power to pumps/dispensers and STPs. Multiple disconnects
may be required.
4 Inspect the pump/dispenser cartons and contents for shipping damage. Gilbarco does not cover
shipping damage under its warranty policy. Notify the shipper of any damage.
6 Ensure that the fuel grade for product lines matches the pump/dispenser brand panels and the
foundation layout. Product lines from the island pit box must have labels.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 4-3
Preliminary Installation Information Before Mounting Unit on Fuel Island
Frontier units have features that prevent water intrusion into the dispenser’s interior. However,
the doors and covers must be opened or replaced in a specific order - the bottom panel first,
which provides access, allowing the release of the security latch on the top door and opening
of the door.
WARNING
DEF, flexible fuels such as biodiesel, high alcohol percentage fuels, such as E25 and E85, and
so on, may be incompatible with certain plumbing materials and hydraulic components.
Use of incompatible materials or components with alternative fuels such as E25 and E85 or
DEF can result in leaks or unexpected failures of components resulting in fire or explosion or
environmental damage.
When dispensing alternative fuels such as E25 and E85 or DEF, verify with the manufacturer if
the material of all plumbing components are compatible with the fuels such as E25 and E85 or
DEF being dispensed.
Note: Before mounting the unit on the fuel island, read and understand this section
completely. This information is essential to avoid installation errors.
IMPORTANT INFORMATION
Do not make assumptions about configurations based on previous experience, hose
positions, or layout of the unit that you are replacing, whether it is a Gilbarco unit or that
of any other manufacturer.
Model grade mapping (inlet piping) for Frontier units is different from The Advantage® Series
and Multi Product Dispenser (MPD)-3 Series as well as other manufacturers units. Incorrect
matching of unit piping to supply lines can cause costly rework and time delays.
The first Grade/product is always left when facing J-box of Frontier units.
Page 4-4 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Before Mounting Unit on Fuel Island Preliminary Installation Information
WARNING
Where fuels are involved, you are working in a potentiality hazardous environment where
fuels and their vapors may be present and could be ignited with sparks from grinding and
cutting tools.
Always conduct work at the required safe distance away from a hazardous area and use
the appropriate tools.
When powering a dispenser with a GFI, the return neutral of any device to which the dispenser
supplies power must be the same neutral as that of the dispenser. For example, the STP control
relay.
The first method is commonly found with existing applications. The second is recommended
for new ground and up installations to reduce installation cost.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 4-5
Preliminary Installation Information Before Mounting Unit on Fuel Island
Page 4-6 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Mounting Unit to Island
Fill in any openings from the smaller length Frontier cabinet to the potentially longer pit box
opening for other units. Seal as required.
Where low temperatures are expected, dispensing equipment including hanging hardware,
must be insulated, heated, or located in a temperature-controlled enclosure suitable for UL
class 1 division 2 environment to prevent from freezing.
The unit must be located in class 1 where high ambient temperatures are common, consider
insulating the dispenser or placing it in a location where it is out of direct sun to maximize
shelf life.
When mounting dispensers for DEF directly to the island, install sumps to prevent leaks and
spills from migrating off site.
WARNING
Lifting heavy equipment can be hazardous.
Use lifting equipment of proper capacity and factor of safety when moving or positioning
the unit. Stand clear from pump/dispenser when lifting and lowering.
Before mounting the unit to the island, verify if the pit box and unit base are compatible. Some
pit box plates have rain lips that require modifications before placing the Frontier unit on the
plate. If the Frontier unit does not fit properly onto the pit box plate, the unit will have to be
lifted according to the instructions in this section and moved to a safe work area. If this
modification is not required, do the following, and then proceed to “Before Mounting Unit on
Fuel Island” on page 4-4.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-1
Lifting Frontier Units Installing Units on Island
Note: Frontier units have hoisting brackets mounted on top of the upper housing.
1 Verify if the hoisting brackets are tight. Use the bolts provided with the brackets or grade 8
bolts.
CAUTION
Do not run slings around columns or under the upper piping housing. This will damage the columns
or sheathing.
2 Lift and position the unit to the work area for modification or onto the island.
Page 5-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Installation Instructions for Frontier Suction System
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-3
Installation Instructions for Frontier Suction System Installing Units on Island
Page 5-4 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Installation Instructions for Frontier Suction System
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-5
Installation Instructions for Frontier Suction System Installing Units on Island
Page 5-6 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Installation Instructions for Frontier Pressure System
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-7
Installation Instructions for Frontier Pressure System Installing Units on Island
Figure 5-6: Frontier Pressure System for Ultra-High Flow Single Unit
Page 5-8 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Installation Instructions for Frontier Pressure System
Figure 5-7: Frontier Pressure System for Ultra-High Flow Dual Unit - 1
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-9
Installation Instructions for Frontier Pressure System Installing Units on Island
Figure 5-8: Frontier Pressure System for Ultra-High Flow Dual Unit - 2
Page 5-10 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Installation Diagram for Frontier
DISCHARGE SIDE
SUCTION LINE
OF PUMP
CONNECTED TO PUMP SYSTEM
ELBOWS = 2 TO 4 MAX.
RECOMMENDATION AT LEAST
10 mm RISE PER METER FOR
THIS SECTION
50 mm INTERNAL
DIAMETER
DEAD STOCK D SUCTION PIPE
"V"=3.5m
STORAGE TANK
"H"
100 mm FROM
BOTTOM OF TANK
IMPORTANT:
ALTITUDE METER 2200 400 1400 100 1500 100 1600 100 RECOMMENDED INLET PIPE DIAMETER= 50 mm ID
DETAIL VIEW A HORIZONTAL PIPE LENGTH "H" = 20 Meters Maximum
-20 55 -20 40 -20 45 -20 45 VERTICAL LENGTH OF PIPE= "V" AS PER THE RESPECTIVE GRAPHS FOR OTHER THAN SPECIFIED CONDITION
DEAD STOCK D = 200MM MINIMUM.
BEND QUANTITY 4 2 4 2 4 2 4 2
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-11
Installation Diagram for Frontier Installing Units on Island
P20025
Page 5-12 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Installation Diagram for Frontier
SP20025
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-13
Installation Diagram for Frontier Installing Units on Island
Page 5-14 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Installation Diagram for Frontier
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-15
Connecting Pump/Dispenser Inlet Pipes Installing Units on Island
WARNING
Flexible fuels such as biodiesel, high alcohol percentage fuels, and so on, may be incompatible
with certain plumbing materials and hydraulic components.
Use recommended sealant, Loctite® #567 (Part Number 56747) and Loctite Primer-N 7649
(Part Number 21347) for pipe threads. Do not use thread tape.
Use of incompatible materials or components with alternative fuels such as E25 and E85 or
DEF can result in leaks or unexpected failures of components resulting in fire or explosion or
environmental damage.
When dispensing alternative fuels such as E25 and E85 or DEF, verify with the manufacturer of
the material or component that all plumbing components are compatible with the fuels or DEF
being dispensed. Do not replace the dispenser or pump parts with those incompatible with the
fuel or DEF involved.
WARNING
The shear valves must be installed correctly.
Improperly or insufficiently anchored shear valves can lead to fire or explosion that could
result in severe injury or death.
Note: Pumps do not have to use shear valves, except in special circumstances. The following
procedure for a pump is identical to that of a dispenser, except that a shear valve may
not be used. The contractor must provide and install pipe unions whether shear valves
are used or not.
IMPORTANT INFORMATION
National Pipe Taper (NPT) pipe threads can at times be difficult to seal during installation or
later, because of various conditions such as minor thread damage, contamination, slight
thread imperfections, poor assembly practice and other reasons. Gilbarco has found that
although NPT threads can be sealed normally with a good quality pipe sealant alone (the
normal recommendation), on many occasions, fewer issues are created during installation by
using a combination of sealant and Teflon pipe tape. The additional expense incurred to apply
both will save money for the installer in the long run by spending less time correcting leaks
during installation.
When using a Teflon pipe tape, it is extremely important to apply it properly so that no tape
stringers are created to enter the hydraulic system. Tape stringers can cause serious issues
with valves, nozzles, and other hydraulic components. For information on how to properly use
the Teflon pipe tape and thread sealant to ensure fewer installation issues and fewer
subsequent pump/dispenser problems, refer to “Inlet Pipe Assembly” on page 5-18.
This information and recommendation does not apply to hanging hardware connections.
Damage to aluminum parts of the hanging hardware or dispenser can occur since it is very
difficult to control proper torque tightening because of the thread-assembly friction.
Page 5-16 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Connecting Pump/Dispenser Inlet Pipes
1 Remove the vertical low hydraulic cabinet brace (found only in some units) to gain access
during the installation of plumbing. Reinstall this brace after you complete the installation of
the plumbing.
For units with a shear valve, a contractor-provided union must be installed on the shear valve.
For proper tightening of the union to the shear valve, refer to the shear valve manufacturer’s
instructions. For units without shear valves, a contractor-provided union must be installed on
the ground stub pipe.
For additional shear valve information, see Figure 5-16 on page 5-20. Since Frontier units
require special considerations, ensure that you read and understand the information on shear
valves later in this section for those units.
CAUTION
The shear valves or other dispenser components can be damaged or broken if improper
wrench techniques are used. The installer must use two wrenches so that stress is not
applied to the shear portion of the valve during tightening.
2 To maximize installation ease, Standard Frontier units are shipped with inlet plumbing. The
installer provides and installs the plumbing in the lower Hydraulics Cabinet when required.
Where required, use a approved sealant suitable for the applicable fuel type.
CAUTION
Units used with alternative fuels such as ethanol (E25 and E85), biodiesel, or others require
contractor-supplied plumbing components to be suitable for use with such components.
Consult your part suppliers for recommendations for their hydraulic parts based on the fuel
types to be utilized.
Fuel leaks or component failure may occur if the components are not compatible with these
fuels.
3 Ensure that you remove any shipping plugs or caps that may be present in the pipes, shear
valves, and unions. Leave the mounting bolts a little loose at this time to allow more
adjustment when aligning the piping.
Notes: 1) The contractor-supplied pipe and fittings must be 1-1/2-inch NPT Schedule 40 black
iron. The Frontier pipe and fittings must be 2-inch NPT Schedule 40 black iron.
Vapor Recovery is 1-inch NPT.
2) Flexible pipes are not allowed within the dispenser.
For information regarding the valves or shear valves required for vapor recovery return lines
consult the Local Regulatory Agencies.
To ensure proper operation of the shear valve during a vehicle collision, all piping above the
shear valve must be secured to the lower cross brace using U-bolts sized according to the
plumbing involved.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-17
Connecting Pump/Dispenser Inlet Pipes Installing Units on Island
1 From the pipe nipple end (about 2 to 3 threads), wrap the inlet pipe with Teflon tape
[12 to 15 revolutions (see Figure 5-14)].
CAUTION
Do not use tape at the very end of the pipe nipple to avoid tape entering the dispenser hydraulics.
Tape in the hydraulics can cause failures of valves, nozzles, or other significant problems.
Pipe Threads: Use recommended sealant, Loctite #567 (Part Number 56747) and Loctite
Primer-N 7649 (Part Number 21347) for pipe threads. Do not use thread tape.
CAUTION
Applicable to Dispensers Rated for E25 and E85 Use:
Do not use tape at the very end of the pipe nipple to avoid tape entering the dispenser hydraulics.
Tape in the hydraulics can cause failures of valves, nozzles, or other significant problems.
Use only UL-listed TPS PTFE Pipe Sealant manufactured by SAF-T-LOC International Corp.
Page 5-18 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Connecting Pump/Dispenser Inlet Pipes
2 Apply a moderate bead of sealant completely around the nipple end at the edge of the Teflon
tape (see Figure 5-15).
Note: For pipe threads, ensure that you apply the primer before applying the sealant.
Follow the manufacturer’s instructions.
3 After the sealant has been properly applied, tighten the connection to 130 foot-pounds.
WARNING
Always use the provided adjustable cross brace to secure plumbing in the dispenser, or the
shear valve may not operate properly during a vehicle collision.
The cross brace is not an optional feature!
Also, use of non-rigid piping materials such as field-bendable tubing to connect to the inlet may
also result in the shear valve not operating properly during a collision.
Use of black iron pipe inside the dispenser is required for fuel lines at the outlet of the
shear valves.
CAUTION
Do not use pry (crow) bar to position pump/dispenser over conduit or pipes. This could
damage valves, conduit, or other parts of the unit.
5 Double-check the alignment of the frame, conduit, and pipes. Secure the piping to the safety
brace using U-bolts or pipe clamps that are supplied by the contractor.
Note: Misaligned piping can result in a leak.
WARNING
For Frontier units, do not permanently remove the strainer under any circumstances to
accommodate the shear valves from certain manufacturer’s that may not properly position the
shear section of the valve as shown in Figure 5-16 on page 5-20.
Use a Morrison or equivalent shear valve to ensure proper position of the shear section of the
shear valve.
Failure to use the strainer could result in failure of the valves or meters, void warranty, and
create a safety hazard with an improperly operating valve.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-19
Connecting Pump/Dispenser Inlet Pipes Installing Units on Island
7 Tighten the anchor bolts at this time. Verify if the shear valves are properly tightened to the pit
box or shear valve anchor bracket, as required. If removed earlier, reinstall the vertical cabinet
brace in the lower hydraulic cabinet.
Page 5-20 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Connecting Pump/Dispenser Inlet Pipes
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-21
Connecting Vapor Return Line to Vapor Shear Valve Installing Units on Island
Contractor-supplied
1” NPT Vapor Return Pipe supplied
Fittings, Pipe, and
in the Unit
Shear Valve
Contractor-supplied
Fittings, Pipe, and Shear
Valve
Page 5-22 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Units on Island Anchoring Pump/Dispenser to Island
WARNING
Improper anchoring of units could cause damage, severe injury, or death resulting from the
unit tipping over from the impact or drive-off.
1 Verify if the shear valves are firmly anchored to the island form [concrete or pit box
(see Figure 5-19)].
Note: If the shear valve is not anchored properly, it may not operate correctly during a severe
impact. Follow the shear valve manufacturer’s instructions.
Figure 5-19: Anchoring Shear Valves Using Anchor Brackets
Pump/Dispenser Base
Anchor Bracket
2 Loosely anchor the pump/dispenser to the island according to the foundation layout locations,
using all the required anchoring points as follows:
• Use 1/2-inch anchor studs with heavy duty large washers (slot designed for that size).
• Use bolts or studs that are of 5-grade steel.
• Use hardware that is corrosion-protected or resistant.
Note: Do not use plastic, low strength, or pallet bolts.
• Studs/bolts must be securely anchored to the island or pit box (see Figure 5-20).
• For additional important information, refer to the anchor or pit box manufacturer’s
instructions.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 5-23
Anchoring Pump/Dispenser to Island Installing Units on Island
Page 5-24 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Conduit and Wiring in Unit
1 For units with the J-box, run a 1-inch rigid conduit to the J-box entering the unit from Side 2.
Run any existing wiring to the main J-box through the 1-inch J-box conduit that enters the unit
from Side 2. Connect the 1-inch conduit with class 1 Division 1 explosion-proof conduit
union.
If the conduit is entering the unit from outside the dispenser pit box, refer to “Electrical
Related Items” on page 8-3 and “Reference Information” on page 9-1 before proceeding.
Use an 8 X 1-inch diameter conduit, to run to the electronics cabinet of the unit from Side 2.
Use additional conduits and coupling, if required.
2 If required, install the conduit for call buttons, Ethernet®, and speaker wires using similar
procedures as outlined for the power conduit. However, when facing Side 1, call button, and so
on, the conduit must be to the right side of the unit and power wiring to the left. Ensure that
you follow earlier steps and warnings for installing the conduit through the air gap plate or
side of the electronics cabinet.
Note: Call button, Ethernet, and speaker wires cannot be in the same conduit as the power and
two communication wiring to the unit. They must be in a separate conduit.
2 Commonly, a field connection conduit runs through the side column to the J-box with a
1-inch NPT male end. Run all the field wiring through this field conduit. All wiring
connections may take place in the factory-installed J-box. Before proceeding, refer to
“Electrical Related Items” on page 8-3 and “Reference Information” on page 9-1.
3 In all units where a J-box is used (factory or contractor-supplied), the following are mandatory
requirements:
• The connection of the conduit to the J-box must be made with a clearance of at least
9 inches from the pump/dispenser base to the bottom of the J-box connection stub. To
accomplish this, the conduit can be routed to enter the J-box from the side or top.
• The J-box must be securely fastened to the unit by means of a bracket or brace. It must not
be held in place only by a conduit. Factory-supplied boxes are fastened only by a conduit.
• Installation of the J-box and all fittings must be performed to allow the installer to turn any
and all threaded fittings by a minimum of 45° in a single movement using appropriate
tools (for example, pipe wrench).
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 6-1
Installing Conduit and Wiring in Unit
WARNING
The bottom plate of the electronics cabinet and the top plate of the hydraulics cabinet
are separated to provide an air gap between the electrical and hydraulic housings.
Loss of air gap integrity due to improper installation can allow fuel vapors into areas
where they may ignite. The resulting fire and/or explosion can lead to serious injury or
death.
Running the conduit through the air gap requires strict compliance with procedures
outlined in this manual. No holes in air gap plates can be left unsealed the following
installation.
WARNING
The electronics cabinet is an unclassified area and as such must be protected against
flammable vapor entry.
Improper installation of the conduit through the side of the electronics cabinet may
result in flammable vapors penetrating the electronics cabinet where it may ignite
resulting in fire and/or explosion that can lead to serious injury or death.
Running the conduit through the side of the electronics cabinet requires strict
compliance with the procedures outlined in this manual.
IMPORTANT INFORMATION
For conduit entry through the vapor barrier, the air gap penetration conduit must not be
longer than 8 inches. This will allow removal of the dispenser (if required) in the future
and accommodate wiring a new dispenser without pulling a new wire.
When a dispenser without a J-box is removed from the island, the conduit and wires
will be cut immediately below the potting dam. This will leave enough wire to splice into
a class 1, Div 1, Group C, and D explosion-proof J-box when a new (or previously
removed) unit is installed/reinstalled over the containment box.
For conduit entry through the vapor barrier, the Frontier unit contains eight sets of conduit
knockout holes (four on the right and four on the left) for access to the electronics cabinet.
Knock out the aligned (top and bottom air gap plate) 1-inch plugs for the required number and
positions of contractor-supplied conduits (do not use conduits smaller than 1inch with the
conduit plate provided). For field installations, only two conduits at opposite corners can be
installed per plate. Use the knockouts on the left (facing Side 1) for all power and two-wire
connections. Ethernet, International Forecourt Standards Forum (IFSF), speaker, intercom,
and/or call button wiring must use knockouts on the right. For conduit entry through the side
of the electronics cabinet, the Frontier unit contains eight sets of conduit knockout holes (four
on the right and four on the left) for access to the electronics cabinet. Knock out the 1-inch
plugs for the required number and positions of contractor-supplied conduits.
Page 6-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Conduit and Wiring in Unit
To seal the air gaps and conduits in Frontier units, proceed as follows:
1 Install the contractor-supplied 1 listed metal, rigid, threaded conduit through both the top and
bottom air gap conduit plate holes according to the following procedure (see Figure 6-1).
2 From the electronics cabinet, remove two screws (not shown) and the upper conduit plate from
the top air gap plate. Retain all parts for reassembly.
4 Fasten the conduit to the conduit plate removed using a machined flat conduit lock nut and
washer on the bottom of the plate. Fasten a listed, metallic conduit capped bushing on the top
of the plate.
5 Remove the two screws (not shown) and the bottom air gap conduit plate from the bottom air
gap plate. Retain all parts for reassembly.
Note: (Canada only) The gasket for the plate will come off with the plate. The gasket must be
reinstalled with the plate.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 6-3
Installing Conduit and Wiring in Unit
6 Remove the aligned knockout plugs from the bottom air gap conduit plate as required, and
reinstall the plate and screws.
7 From the electronics cabinet, slide the conduit down through the knockout in the bottom air
gap plate.
8 Reinstall the top air gap conduit plate onto the top air gap plate using screws, to secure the
conduit in place.
WARNING
Installation using this method requires Gilbarco Installation Kit (M07838K001). Failure to use the
kit will result in damage or injury.
Sealing Electronics
Compound Cabinet
Potting Disc
Potting Disc
Page 6-4 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Wiring Installing Conduit and Wiring in Unit
WARNING
Installation using this method requires Gilbarco Installation Kit (M07838K001). Failure to use the
kit will result in damage or injury.
Notes: 1) Conduit seal boots and liquid deflectors are not used on all dispensers.
2) Use UL-listed metallic conduit capped bushing for wire protection.
3) On dispensers without the factory-installed J-box, run conduits for:
• The power and two-wire communications.
• Speakers and call buttons (if required), and
• SMARTConnect™ (if required) through the side column into the electronics
cabinet as shown in Figure 6-2 on page 6-4.
Installing Wiring
Note: The wiring must be gas and oil-resistant, color-coded, or tagged for identification
purposes, and rated for 300 V or higher. Data wires for new installations must be a
twisted-pair (unshielded) with 10 to 12 twists per foot.
Operating Environment
Environment Range
Relative Humidity 20 to 95% (non-condensing)
Minimum outside ambient temperature -4 °F (-20 °C)
Maximum outside ambient temperature 140 °F (60 °C)*
*Electronics have been evaluated and are rated for use at a maximum
of 131 °F (55 °C) outside ambient temperature.
To ensure proper unit performance, operation under severe environmental conditions may
require special options such as card reader heaters and so on.
Notes: 1) Ensure that enough extra wire length (minimum of 5 feet or 2 meters) is provided to
make the run to the stub up location at the bottom of the electronics cabinet.
2) Remember that you may be routing the conduit over to come up at the stub up to the
electronics cabinet. Depending on which end of the unit the stub up is on, you may be
routing across the entire unit length.
2 For the side column conduit entry, install a short two-inch threaded nipple into the top of the
sealing fitting.
3 For the side column conduit entry, install a capped pulling elbow. The use of a Killark® Y-3
fitting is recommended.
4 The remaining conduit must be made up to match the installation layout for the unit at the site.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 6-5
Installing Conduit and Wiring in Unit Installing Wiring
The following is the list of the most common procedures for conduit entry to the right when
facing Side 1:
• The length of the conduit must extend straight out from the capped Y fitting or pulling
elbow.
• For the side column entry, the conduit must then be turned by 90°, vertical under the air
gap plate knock out.
• Use the required air gap plate knock out. Do not knock out any knock out plugs that will
not be used as an opening for conduit.
• All the conduits that enter into the electronics cabinet must be potted.
• At least 1 inch of conduit must extend above the bottom shelf of the electronics cabinet.
• Complete the conduit run with a conduit nut on the inside of the cabinet.
• Pull all wires properly through the conduit. Finalize the procedure by potting the conduit
end.
• Allow 18 inches of wire in the electronics cabinet for field connections. The wire must be
trimmed as required on field connection.
• All the conduits and fittings must be listed and suitable for use in class 1, Division 1
hazardous locations from the seal off fitting to the potted conduit.
WARNING
Sparks can ignite fuel/vapors.
Fire/explosion can result in severe injury or death.
Use caution when testing wires. Do not test when exposed fuel and vapors are
present.
Only use a Megger® tester on new field wiring.
For existing wiring, use a digital multimeter to test for continuity/resistance.
Test the insulation of the new wiring from the station and to the electronics cabinet before
connecting the wires. Refer to the Warning above. This checks for damage that can occur
while pulling wires through the conduit.
1 Ensure that wires are disconnected at both ends. If you do not disconnect wires at both ends,
you can damage the pump/dispenser electronics.
5 Measure the resistance. Follow the test equipment manufacturer’s instructions. Insulation
resistance of more than 50 megohms is satisfactory. Check the local authority requirements.
8 When all wiring tests are complete, the wiring may be potted.
Page 6-6 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Wiring Installing Conduit and Wiring in Unit
2 For units with the J-box installed, remove the box cover and save for reassembly.
Note: For Frontier units that are replacing older units, if the existing wire is too short to reach
the installed J-box and a splice must be made, the contractor must provide and use a
class 1 Division 1 explosion-proof J-box to make connections according to the code.
Refer to “Before Mounting Unit on Fuel Island” on page 4-4.
3 The following table contains information on cables that are used for specific applications.
Description Part Number Application
Main AC M02338 All Frontier Master Units
Valve Intercept M02372 Master of Combo Unit - for Satellite Light Only
Combo Neutral M02384 Satellite Side of Combo Unit, Satellite
Transformer M02370 Master of Combo Unit
Subassembly ~ OR ~
Frontier Satellite - for Satellite Light Only
~ OR ~
Legacy Satellite
Combo Pump M02385A001 Frontier Satellite, Combo
Handle
Combo 9 VAC M02386A001 Frontier Satellite, Combo
4 Some cable configurations require that one of the existing connectors be cut off the wires. This
allows the wire to be secured to other wires with wire nuts. For more information, see
“Appendix B: Wiring Diagrams” on page B-1 and for illustrations noted in the table refer to
step 3.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 6-7
Installing Conduit and Wiring in Unit Supplying Connections for Three-phase Pump
Page 6-8 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Supplying Connections for One-phase Pump Installing Conduit and Wiring in Unit
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 6-9
Installing Conduit and Wiring in Unit Potting Conduit Stubs
2 Make the connections as shown in Figure 6-3 on page 6-8 and Figure 6-4 on page 6-9. Do not
disturb the factory wiring in the J-box and electronics cabinet.
3 For units with J-boxes, use pipe plugs to seal the unused openings in all J-boxes. Replace the
cover on the boxes.
4 Double-check all wiring connections for wire nuts, lugs, caps, and so on. Reinstall the J-box
cover. Ensure that you do not pinch the wires and use all J-box bolts.
5 Replace the lower doors and close the doors to the electronics cabinet.
Potting up to Unit
Fill the sealing fitting with potting compound to seal the pathway of the field wiring to the
station building. Refer to “Completing Field Wiring” on page 6-10.
1 Mix the compound in a clean vessel according to the compound manufacturer’s instructions.
Mix only as much potting compound as can be used before the compound hardens.
2 Using a funnel, carefully pour the sealing compound into the conduit from the top until the
compound is within 1/4-inch from the top of the conduit (see Figure 6-5 on page 6-11).
Note: Ensure that you pour slowly to prevent air bubbles from forming in the compound and
wires around.
3 Immediately clean the spilt compound from the conduit threads and cabinet surfaces.
Page 6-10 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Potting Conduit Stubs Installing Conduit and Wiring in Unit
Frontier Unit with Field Conduit Sealing for Conduit Through the Vapor
Barrier WARNING
Note: With Potting Dam in place, carefully pour Sealing Fuel vapors allowed to
Compound through Funnel to fill the Conduit. travel between the
Hydraulics and
electronics cabinets
Funnel presents the risk of fire or
explosion.
The resulting fire or
Electronics explosion may lead to
Cabinet Wires serious injury or death.
UL-listed Metallic Conduit
Capped Bushing(s) Sealing Never compromise the
Compound vapor barrier integrity by
leaving out conduit plates
or open holes (for
example, using conduit
smaller than 1-inch
diameter). For Canadian
applications, do not leave
UL-listed Conduit out any gaskets.
Locknut
Contractor provided
Conduit 8 X 1” The listed metallic conduit
Hydraulics
nut must be installed at
Cabinet
the top of the 8 inches
conduit for mechanical
retention of potting in the
Fiber Potting Dam
event of explosion.
Coupling installed
Coupling
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 6-11
Installing Conduit and Wiring in Unit Connecting to In-station Diagnostic (ISD) Vapor Flow Meter
At Dispensing Unit
The Vapor Flow Meter is part of an ISD system that measures the amount of vapor returning to
the UST. The wiring for this device is intrinsically safe and must be run in a separate conduit
to the Veeder-Root® monitoring equipment or as per other allowable Veeder-Root
recommendations. The conduit must be potted where it enters and leaves any designated
hazardous zones. The potting requirements for hazardous zones must be followed so that fuel
vapors do not migrate to other areas. The ISD Vapor Flow Meter wiring terminates at the Tank
Level Sensor (TLS) console. The flow meter is in-line and near the vapor return shear valve in
the hydraulic area of the unit. Do not create any liquid flow traps. For more information on
liquid traps, see Figure 5-18 on page 5-22.
Hydraulic Cabinet Area of Unit (only vapor return associated parts shown for clarity)
Seal-off
(Contractor-supplied)
Page 6-12 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Connecting to In-station Diagnostic (ISD) Vapor Flow Meter Installing Conduit and Wiring in Unit
Epoxy Sealing
Sealing of wiring connections is required to ensure proper performance of intrinsically safe
devices where minor corrosion can affect communication to the device.
CAUTION
Epoxy sealant is irritating to the eyes, respiratory system, and skin. It can cause
an allergic skin reaction. It contains epoxy resin and cycloaliphatic
epoxycarboxylate.
Precautions: Wear suitable protective clothing, gloves, eye, and face protection.
Use only in well ventilated areas. Wash thoroughly before eating, drinking, or
smoking.
From Probe,
Sensor, or
Transducer
B C To Console
Wire Nuts
Note: When the temperature is below 50 °F (10 °C), keep the resin in a warm place before
mixing (for example, in an inside pocket next to the body).
1 Open the epoxy sealant package, and remove the resin pack.
2 Hold the resin pack as shown in A (see Figure 6-7), and bend the pack along the length.
3 Firmly squeeze the red side of the resin as shown in B (see Figure 6-7), forcing it through the
center seal and into the black side.
4 Mix thoroughly to a uniform color by squeezing the contents back and forth 25-30 times.
5 Squeeze the mixed, warm resin into one end of the bag, and cut off the other end.
6 Slowly insert the wiring connections into the sealing pack until they fit snugly against the
opposite end as shown in C (see Figure 6-7).
7 Twist the open end of the bag and use the tie-wrap to close it. Position the tie-wrapped end
upwards until the resin solidifies.
8 Push the epoxy sealed bag into the J-box. Replace and tighten the J-box cover.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 6-13
Installing Conduit and Wiring in Unit Connecting to In-station Diagnostic (ISD) Vapor Flow Meter
To TLS Console
Wiring from the ISD Flow Meter J-box terminates at the TLS console. For additional
information, refer to the In-station Diagnostic Vapor Flow Meter Installation Guide
(Veeder-Root document number 577013-796). For correct polarity connections,
see Figure 6-8.
Note: Correct polarity must be observed when making the connection.
Figure 6-8: Field Wiring ISD Flow Meter Polarity
Black (-)
Intrinsically Safe
From ISD Flow
Wiring from Meter
Veeder-Root TLS
Console
White (+)
Designates
1/2” Rigid Conduit Connection
Page 6-14 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installing Breakaways, Hoses, Swivels, and Nozzles
Teflon tape must not be used for hanging hardware. Sealant must not be used for sealing
connections unless the threads involved are pipe threads. O-ring seals do not require sealant.
However, a small amount of silicone sealant can be used to avoid rolling or damaging of the
O-ring during assembly.
WARNING
Hold-open devices on nozzles that are not of the pressure activated type, can
allow flow to occur through the nozzle for an activated fueling position, without the
subsequent customer manually opening the nozzle.
Spilt or uncontrolled dispensed fuel may result in potential fire, explosion, fuel
chemical burns, or environmental contamination. Serious injury or death may
result.
WARNING
The hose pulled away from the pump/dispenser could drain fuel or pull the unit over during
a drive-off. Explosion and fire or pull off of the dispenser during a drive-off could result in
severe injury or death.
WARNING
Use of hoses other than standard lengths may create a tripping hazard.
WARNING
Flexible fuels such as Biodiesel, high alcohol percentage fuels, and so on, may be
incompatible with certain plumbing materials and hydraulic components.
Use of incompatible materials or components with alternative fuels can result in leaks or
unexpected failures of components resulting in fire or explosion or environmental damage.
When dispensing alternative fuels, verify with the manufacturer of the material or component
that all plumbing components are compatible with the fuels being dispensed.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 7-1
Installing Breakaways, Hoses, Swivels, and Nozzles Units Without Hose Retractors
CAUTION
Hose Torque
Recommended torque when installing hoses is 40-50 N.m (30-35 ft-lbs). DO NOT OVER
TIGHTEN or damage to the nozzle could occur. Applicable when connecting hoses to the skid
tank, during internal repairs, and nozzle replacement.
1 Install the breakaway whip hose to the pump/dispenser outlet casting (see Figure 7-1 on
page 7-3).
2 Install the listed breakaways to the whip hoses. Follow the breakaway manufacturer’s
instructions:
• Clean all threads.
• Place the sealant on male threads only. Follow the sealant manufacturer’s instructions.
Note: Use only UL-classified pipe sealant approved for use with petroleum products.
Remove the sealant if it is found inside the hose or fittings. Clean off the excess
sealant. Do not use Teflon tape as it may damage the unit.
• Use a smooth-faced wrench to tighten all fittings securely. Do not overtighten.
Note: Do not tighten the breakaway by twisting the hose. This can damage the coupling.
Page 7-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Units Without Hose Retractors Installing Breakaways, Hoses, Swivels, and Nozzles
4 Install the swivel (if used) to the hose. Follow the swivel manufacturer’s instructions.
5 Install the nozzle to the swivel or the hose. Follow the nozzle manufacturer’s instructions.
Note: Check for the correct nozzle cradle/hook type (vapor, non-vapor, and so on). It must not
be possible to activate the nozzle boot switch with the nozzle properly held in place in
the nozzle boot.
6 Use an ohm meter to check for continuity from the end of the nozzle to the conductive metal
surface in the unit (applies to both types of hose-retrievers or non-retrievers).
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 7-3
Installing Breakaways, Hoses, Swivels, and Nozzles Units Without Hose Retractors
Page 7-4 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Do Not Turn on AC Power Completing Installation
8 – Completing Installation
WARNING
Applying power before electrical and mechanical inspections have been
completed can be hazardous. Hazardous high voltage, fuel, and fuel vapors may
be present or the equipment may be damaged.
Serious fires, explosions, and electrical shocks could result in injuries or deaths
Power must not be applied to the unit and associated STPs when installing,
servicing or making electrical wiring connections, or replacing any electrical
components, including light bulbs. Multiple disconnects may be required.
Power must only be applied to the unit after the commissioning Gilbarco ASC
checks wiring and so on. The installer must inspect the unit per “Installation
Checklists” before contacting the commissioning ASC. Incorrect installation
could result in an unsafe unit condition. Damage from improper wiring or
installation will not be covered by warranty.
When all installation procedures are complete up to this point, the unit must be inspected by a
Gilbarco ASC.
After the inspection is complete, the system must be purged by the installing contractor.
Irrespective of when the purging operation is performed, proceed to “Installation Checklists”.
Installation Checklists
To ensure proper and safe operation of all equipment and to ensure warranty coverage,
installers must inspect the installation. The “Mechanical and Hydraulic Related Items” on
page 8-2 checklist and “Electrical Related Items” on page 8-3 checklist may be used as a guide
(many of the items on the lists must already have been checked by the electrician as covered
earlier).
Follow the checklists and perform all the required inspections. The forms must be provided
with each unit, if not, contact the Gilbarco Distributor. It is only required to complete the
station electrical inspection portions of the form (List 3) in every form, (for every unit at the
station).
Note: To preserve the originals for future use, make several copies of all the checklists in this
manual.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 8-1
Completing Installation Installation Checklists
MDE-4226
Item Procedure Refer To Checked Related Item
1 Shear valves must be installed according to the valve page 5-23 of this List 1, Item 1
manufacturer’s recommendations. Shear point is ±0.75” manual
of grade and properly mounted. Vapor line shear valves
are required for many localities.
2 The lower piping brace must be installed according to the page 5-16 of this List 1, Item 13
installation manual and all product pipes must be properly manual
anchored to it.
3 Flexible pipes must not be used within the dispenser. - List 1, Item 2
However, flexible pipes that meet the local and state
codes can be used below the pump/dispenser, when
allowed by regulatory authorities.
4 Pumps (self-contained units) must have a vacuum - List 1, Item 3
actuated pressure regulating valve (Gilbarco Model 52 or
equivalent) to prevent positive pressure at the pump base
when used with above ground tanks.
5 Hose breakaways must be used and installed according Manufacturer’s List 1, Item 5
to the manufacturer’s recommendations. For units with specifications
retrievers, breakaways, and whip hoses must be attached
to the nozzle end. For units without retrievers, it is
attached to the dispenser end.
6 All hanging hardware must be checked for continuity. page 7-1 of this List 1, Item 6
manual
7 The unit must be properly anchored to the island or skid page 5-23 of this List 1, Item 7
tank. manual
8 Vapor recovery piping at the pump/dispenser must have page 5-22 of this List 1, Item 8
no traps or sags. Unit must be mounted using proper manual
quantity, size, and strength mounting hardware.
9 Verify correct nozzles, piping and brand panels for each Unit order List 1, Item 9
grade. Also, verify if correct product lines are connected specific
to each pump/dispenser inlet.
10 All code, regulatory agency, or customer-specified safety As provided with List 1, Item 10
warning signs, labels, or decals have been installed. and for unit
11 Long hose lengths beyond Gilbarco recommendations NFPA 30A List 1, Item 11
must not be used without special retrievers.
• For VaporVac hoses, no more than 6” of hose length
may rest on the ground when the nozzle is resting in the
boot.
• For Balance Vapor Recovery hoses, no portion of the
hose may be on the ground.
12 Verify shear valve, Nozzle, and Dispenser proper shutoff page 8-6 of this N/A
operation. manual
Page 8-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Installation Checklists Completing Installation
MDE-4226
Item Procedure Refer To Checked Related Item
1 Conduit entries into the electronics cabinet must be installed List 2, Item 1
according to the installation manual. No unplugged openings must
be allowed between the electronics cabinet interior and the vapor
barrier or at the side of the electronics cabinet.
List 2, Item 2
Field conduit into the electronics cabinet must be properly potted
according to the local, state, and national codes as per the
installation manual. This is in addition to potting requirements for
the conduit below the base of the pump/dispenser.
2 Field conduit installed in dispenser hydraulics cabinet must be List 2, Item 3
securely fastened to the brace supplied with the unit, using
appropriately sized U-bolts or pipe clamps.
3 Equipment must be installed in conjunction with an emergency “Grounding” on List 3, Item 2
power cutoff to remove all power from the equipment in case of an page 9-9
emergency.
4 STP isolation relays are required for all dispensers. List 3, Item 3
5 Use twisted-pair wires as specified for two-wire communication for List 2, Item 5
new installations or where a new wire is pulled. Do not use
shielded wires for video feed, for SMARTConnect and Applause
Media System.
6 Use twisted-pair wires for color display communication wiring. List 2, Item 5
7 All wiring must be of stranded copper of the gauge and insulation List 2, Item 6
casing specified.
8 All grounds must be properly connected according to the List 2, Item 7
installation manual requirements as well as the state, local, and
national codes.
9 Conduit and J-boxes must be approved for hazardous locations • NFPA 30A List 2, Item 8
and properly sized for the wiring involved. • NFPA 70
• UL 87
• NEC
10 Properly size all circuit breakers for the units/unit options involved. NEC and local List 3, Item 5
codes
11 All pump/dispenser wiring must be properly spaced and isolated List 3, Item 6
from wiring for electrically noisy devices such as variable speed
STPs, station equipment motors, and other devices.
12 All power wiring and circuit breakers to Gilbarco equipment must List 3, Item 7
be dedicated and not be shared with other equipment.
13 All circuit breakers to Gilbarco equipment must be clearly labeled List 3, Item 8
and readily accessible.
14 All distribution boxes must be clearly labeled showing the List 3, Item 9
pump/dispenser number connections.
15 All pumps/dispensers must be wired to the same phase of List 3, Item 10
electrical power.
16 New site wiring must be Megger-tested and wired to the same List 3, Item 11
phase, unless isolation relays are used to protect it against cross
phasing. Old site wiring must be continuity and short-tested with a
digital meter.
17 Wiring must be color-coded or tagged, sized for distance and N/A
application, and resistant to gas and oil.
18 J-boxes must be secured with all bolts and have no unplugged List 2, Item 9
openings.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 8-3
Completing Installation Purging Air from System and Testing
Frontier Units
The Frontier units are received precalibrated, but must be checked for calibration before use.
Purging requires the unit to be configured for gallons, liters, or imperial gallons.
IMPORTANT INFORMATION
When purging Frontier units, if you exceed more than 250 volume units for any meter on a side,
the startup technician will not be able to reset the volume totals to zero or any other value for
opening the station. Avoid purging of more than 200 units of volume per meter as a result.
Purging, calibration, and calibration verification can be performed within this limit and totals
reset, if required.
CAUTION
Do not attempt to purge these lines using the dispenser nozzle as the dispenser
meters may suffer damage due to overspeed.
To prepare for purging, use the following steps for each shear valve in all units. Be observant
during purging and check for plumbing leaks as you move toward the tank. For blender
nozzles, select a blend grade. Ensure that the prices are set (by the ASC) before you begin.
3 Use a UL-approved sealant to connect a “gasoline suitable, conductive hose” to the shear
valve test port.
5 Place the drain end of the closed valve in an approved metallic container. Clean up any spills
promptly.
6 Turn on power to STPs. Activate the STP for the line being purged.
Page 8-4 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Purging Air from System and Testing Completing Installation
7 Slowly open the mechanical valve until you obtain a slow, constant stream of fuel flow.
Maintain contact between the metallic valve and the can during fuel flow.
8 Turn off STP, bleed pressure using the mechanical valve, remove the valve and hose, and
reinstall the pipe plug to the shear valve using UL-approved sealant suitable for the fuel
involved.
9 For purging air from the system with fuel in lines, perform all steps in “For New and Existing
Pumps and Dispensers with Fuel in Lines (Purging Through Nozzle)”.
For New and Existing Pumps and Dispensers with Fuel in Lines (Purging
Through Nozzle)
CAUTION
Purging air at high flow rates through the meter can permanently damage them.
Noise is not an indication of overspeed in many cases.
CAUTION
Meters and other hydraulic devices can be permanently damaged by
contamination if units are not equipped with filters during purging and other
installation processes.
To purge air in new and existing pumps/dispensers where underground product lines are full
with fuel, proceed as follows:
3 Slowly open the nozzle until you obtain a slow, constant stream of fuel flow.
Note: For SMART Meter-equipped units, never exceed the nozzle slow latch setting until fuel
flow is steady.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 8-5
Completing Installation Purging Air from System and Testing
4 Purge the system with the amount of fuel specified in the following table:
For Pump this Amount
Start-ups (installing new systems) 35 gallons (130 liters) per hose
Existing sites where the product lines are full 50 gallons (186 liters) per hose*
*This value depends on the following procedures in the sequence listed (especially for new
sites). Also, a lot can depend on line lengths, unusual plumbing situations (air traps), and so on,
what may be good for most sites may not work for all. Generally, you can observe the effect of
air if successive calibration checks read plus. After they stop reading plus, you have purged all
the air.
7 Repeat steps 1 on page 8-5 through 6 for each affected hose and each meter.
Frontier units have enhanced security software. You must periodically spin the pulser to
maintain a higher purging flow rate.
WARNING
Do not substitute the pulser while power is being supplied to the unit. Lethal voltages exist
within the dispenser and damage to the unit could occur if certain critical steps are not
followed. It is recommended that only Gilbarco-certified ASCs, who are trained in the
service and operation of Frontier dispensers perform this procedure.
Note: Dispense a minimum of 75 gallons (341 liters) through each DEF hose. For overhead
lines where no air bleed is used at a high point, purge amount can sometimes run into
hundreds of gallons.
3 Open the nozzle. Fuel must not continue to dribble out of the nozzle for more than a few
seconds. If fuel continues to flow for a longer period, check the shear valve or nozzle for
problems.
6 Activate the fueling position for the same fuel on the opposite side of the unit.
Page 8-6 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Calibration Procedure for Frontier Units Completing Installation
7 For the side to be tested (opposite activated side), remove the nozzle from the boot but do not
activate the boot switch by raising the nozzle boot lever or allowing the auto on flapper to
activate.
8 Open the nozzle. Fuel must not continue to dribble out of the nozzle for more than a few
seconds. If fuel continues to flow for a longer period, check the nozzle or inform the ASC to
check the dispenser valve or valve O-rings.
IMPORTANT INFORMATION
Units must be properly purged before calibration or calibration verification. Incomplete
purging of air can result in inaccurate calibration or errors in calibration verification
testing (normally, subsequent calibration checks will read plus). Always verify any
calibration after setting.
The Frontier meters are precalibrated, but calibration must be verified. Depending on the type
of unit, the procedure is slightly different. After calibration, the Weights and Measures
(W&M) switch must be seal-wired to prevent calibration tampering. Ensure that you draw the
seal wire tightly.
The currently produced Frontier units are precalibrated to Litre and programmed to default
programming values.
Note: Perform the calibration verification procedure after calibration.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 8-7
Completing Installation Calibration Procedure for Frontier Units
Page 8-8 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Reference Contents Reference Information
9 – Reference Information
Information in this section is provided for the installing contractor’s reference. The contractor
may or may not be required by individual contract to perform all or any of the requirements
outlined. However, all installations must conform to the requirements of this section.
Reference Contents
Section and Information Location
Installation Differences when Replacing The Advantage Series page 9-2
Electrical Requirements page 9-3
Emergency Power Cutoff Switch
Circuit Breakers page 9-3
STP Control Relay Boxes for Dispensers
STP Isolation Relays for Electronic Dispensers
Conduit page 9-4
Wiring
Twisted-pair Wiring - Data Wire Lengths page 9-6
Twisted-pair Conduit
Twisted-pair Cable
Ethernet Cable page 9-7
Cable Ordering Information
Ethernet Cable Installation Personnel and Procedures
Grounding page 9-9
Sealing ‘Y’ Fittings page 9-10
Plumbing Requirements page 9-11
Pipe Installation
Pipe Size
Pumps (Standard Flow)
Pumps (High Flow)
Dispensers (Standard Flow) page 9-13
Dispensers (High Flow)
Dispensers (Frontier High Gallon)
Check Valves (Used on Pumps and Frontier Units only) page 9-13
Shear Valves (Generally Used on Dispensers Only)
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 9-1
Reference Information Installation Differences when Replacing The Advantage Series
Page 9-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Electrical Requirements Reference Information
Item Description
Wiring in The Encore Series units use wiring terminal blocks, as appropriate, for field wiring whereas The
Electronics Advantage Series units use wire nut connections.
Cabinet
Mandatory The installer must pot each conduit entering the electronics cabinet in two locations as specified in
conduit this manual. One is at the entry into the electronics cabinet and the other is in the pit box. The
potting Advantage Series units only require potting below the unit.
requirements
Calibration All the Frontier meters are electronically calibrated. The Advantage meters are mechanically
calibrated.
Electrical Requirements
Electrical requirements are as follows:
• Sites must be prepared according to NFPA 30A, NFPA 70, and applicable national, state,
and local codes/regulations.
• All circuit breaker panels and relay boxes must be mounted securely to the wall.
• Only UL-recognized/approved components and/or systems may be used.
• Licensed electricians experienced with pump and dispenser installations must be used to
make all electrical connections.
• Installation requires a dedicated circuit phase system. All electronic units must be wired to
the same power leg.
• An earth ground is required for all circuits.
Circuit Breakers
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 9-3
Reference Information Electrical Requirements
• Circuit breakers must be installed away from the pumps/dispensers, readily accessible and
clearly marked.
• A separate circuit breaker is required for each STP (dispenser models) or each pump
motor (self-contained models).
• One circuit breaker is required for each pump/dispenser to allow the isolation of the
pump/dispenser.
When powering a dispenser with a GFI/RCD, the return neutral of any device to which the
dispenser supplies power must be the same neutral as that of the dispenser. For example, the
STP control relay.
Note: For 3-phase STP, use isolation relay at the input of the 3-phase STP control box.
• Gilbarco requires installation of STP isolation relays in addition to STP control relays.
Combined STP Control Relay/Isolation Relay boxes are recommended.
• Isolation relays must be installed for each STP control line at each dispenser or dispenser
grouping on a single circuit breaker.
• Neutral wire must be routed to the control relays from the dispenser circuit breaker (For
more information, see “Appendix B: Wiring Diagrams” on page B-1).
Conduit
Gilbarco recommends that spare conduits be run for future high speed communications. For
details, refer to “Twisted-pair Conduit” on page 9-6.
• Use a minimum of 1-inch conduit for all Frontier pumps/dispensers except for Frontier,
where you must use 3/4-inch conduit to connect wires to the pump/dispenser. Infoscreen®
and Two-wire data wires can share this conduit (For model-specific wiring diagrams, see
“Appendix B: Wiring Diagrams” on page B-1).
Page 9-4 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Electrical Requirements Reference Information
• Use separate 1-inch conduit for e-CRIND or intercom wiring. This is required for higher
data rate Transmission Control Protocol/Internet Protocol (TCP/IP) communication.
• Run all power and light wires in threaded, rigid metal conduit or in a rigid non-metallic
conduit. The conduit must conform to national and local electrical codes. If non-metallic
conduit is used, it must be at least two feet underground. The last two feet of the
underground run to the J-box must be a rigid metal conduit or threaded steel intermediate
metal conduit.
• Never share the conduit or wire troughs with other manufacturer’s equipment (that is,
speaker wires, and so on).
Note: The same conduit may be used for routing power to the pump/dispenser and the
two-wire data loop (class 1 circuit). The two-wire data loop is a class 1 circuit.
• Metal conduit is not sufficient to provide an equipment ground. A separate ground wire
must be used.
• Knock-out boxes or flexible conduit are not permitted for installation.
Note: Extra J-boxes added to the pump/dispenser must be listed class 1, Div. 1, Group C
and D explosion-proof.
• All electrical fittings must be listed for class 1, Group C and D hazardous locations, as
required by NFPA 30A and NFPA 70.
• A Seal-off ‘Y’ fitting (for example, Killark Type EY) must be installed on all units as a
first connection where the conduit leaves the ground.
Wiring
For high speed communications information, refer to “Twisted-pair Conduit” on page 9-6.
• All pumps/dispensers must be wired according to NFPA 30A, NFPA 70, and applicable
national, state, and local codes/ regulations.
• All circuits must be class 1 N.E.C wired except the speaker (intercom) circuit which must
be class 2 N.E.C. The speaker (intercom) circuit requires a separate 1-inch conduit.
• Only stranded gas and oil-resistant copper wire rated for 300 Volts (up to 240 VAC source)
and 176°F (80 °C) may be used.
• In the main conduit, for communications, only twisted-pair, Two-wire data pairs may be
used.
• All dispensers must be wired on the same phase.
Note: If the Gilbarco isolation relay box is installed, dispensers are not required to be on
the same phase.
• Only listed wire nuts may be used for connections. Tape is not permitted.
• Seal-off Y fitting(s) must be potted after all wires are run and tested to termination points.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 9-5
Reference Information Electrical Requirements
Note: When installing new two-wire communication wiring, use unshielded twisted-pair data
wires. Do not use shielded wires. Wiring specifications: two-wire twisted-pair (UTP)
with 10 to 12 twists per foot, stranded annealed copper tinned with 18 AWG minimum
required for runs up to 1000 feet or 14 AWG minimum for runs up to 2600 feet. Do not
use daisy chain communications wiring. Insulation specifications: Polyvinyl chloride
(PVC) insulation of type TFFN or MTW, UL-approved gasoline and oil-resistant. Refer
C&M Corporation Part #27525 (18 AWG) or equivalent. Gilbarco part number for the
wire is Q13221-02.
Twisted-pair Conduit
Gilbarco recommends the use of 1-inch rigid conduit and fittings (refer to “Conduit”
on page 9-4) for twisted-pair cable(s). This will allow up to two speakers and two call/stop
buttons per side, plus Ethernet.
Note: Terminate the conduit in the dispenser containment pan consistent with all national and
local electrical codes.
Twisted-pair Cable
Gilbarco-specified cable must be used to permit issuance of a Certificate of Conformance
and/or warranty. Use of cables of other types may also create a hazardous situation.
WARNING
Petroleum vapors may migrate inside the cable insulation between conductors
and sheathing of various cables, including twisted-pair cables. Vapors may
ignite, leading to serious injury or death.
Page 9-6 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Electrical Requirements Reference Information
Ethernet Cable
Gilbarco requires use of 10 Base-T or Category 5E (CAT5E) Cable as specified in this
document.
IMPORTANT INFORMATION
A copy of the ANSI/TIA/EIA TSB 67 Certification of Conformance from the wiring
personnel must be provided to the ASC before the site can be commissioned. The
certificate is part of the documentation that must be on the file at the installation site.
A certification of the field test will be required at equipment start-up. For any questions
regarding this procedure, contact Gilbarco.
The following are the two ways to connect high-speed data to the dispenser:
a An Ethernet or Category 5 (CAT5) cable installation.
b FlexPay Connect
• POS controls CRIND on dedicated twisted-pair
• POS controls CRIND with pump data on same wire
• Applause on dedicated twisted-pair
• Applause with pump data on same wire
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 9-7
Reference Information Electrical Requirements
IMPORTANT INFORMATION
Petroleum vapors may migrate inside the cable insulation between conductors
and sheathing of various cables, including 10 Base-T or CAT5 E Cable. Vapors
may ignite, leading to serious injury or death.
It is crucial that the installer follow NECs, article 501 requirements by removing
the outer jacket and spreading the wire pairs at the seal-off points of the CAT5E
Cable, so that a good vapor seal is achieved. This is required because all
CAT5E Cables will conduct vapors inside their outer jacket.
Conduit seal-offs required as per National Electric Code, section 514.9. As the outer
jacket defeats the seal-off, the jacket must be removed and the conductor pairs
separated to allow a good seal (see Figure 9-2).
Seal-off
Low-voltage Conduit
Sealing Compound
Poured here
Separated Pairs
Page 9-8 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Electrical Requirements Reference Information
Grounding
Grounding requirements are as follows:
• NFPA 70 requires connecting the following to the system ground:
- Consoles - Relay control boxes
- Pumps and dispensers - Circuit breaker panel
- Submerged turbine pumps - Electronic leak detectors
• Gilbarco requires connecting each pump/dispenser to an equipment grounding conductor
(see Figure 9-3) located in the conduit per NFPA 70, Article 250. The following applies to
ground conductor:
- Use of wire no smaller than 12 AWG.
- Use of wire with green or green and yellow striped insulation.
- Connection to green grounding screw in the J-box.
- Grounding the providing power under NFPA 70, Article 250.
- Bonding the neutral bus to an approved grounding electrode.
Gilbarco Console
Metal Conduit Conduit
Isolated Ground
Main Circuit Pump/Dispenser Power Outlet
Breaker Panel Circuit Breaker Panel (Hubbel IG5261t)
Conductor
Neutral Bus
Ground Bus
Neutral Bus
Note: For Frontier units without the J-box, connect the ground wire using UL-listed wire nut to the lead
provided in the cabinet from the grounding terminal.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 9-9
Reference Information Electrical Requirements
Gilbarco uses Killark type EY fittings and recommends them or their equivalent for vertical
conduit runs. The following sealing directions are for Killark fittings only, and instructions
may vary for other manufacturer’s fittings. Read and understand all instructions completely
before you begin.
Conduit Wires
Close-up Plug
Sealing Compound
Floor Dam
Conduit
2 Separate conductors and fill the conduit in and around conductors using Killark type “PF”
packing fiber to make a floor dam to hold the fluid sealing compound.
Note: Floor dam must be even with the conduit stop in the lower hub of the fitting. Ensure that
the conductor insulation is not damaged. Force pack between conductors and hubs,
pushing any shreds of packing fiber away from conductors to prevent leakage path.
3 Use only Killark type “SC” sealing compound with Killark fittings, and do the following:
a Use a clean mixing vessel for every batch of sealant.
b Mix the compound at the rate of three parts compound to one part water by volume.
c Sprinkle the compound in water while stirring, until a thick paste is formed.
d Do not mix more compound than can be used in 15 minutes.
e Continue mixing for at least three minutes, until consistency is just fluid enough to pour
slowly, like thick gravy (not watery).
Page 9-10 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Plumbing Requirements Reference Information
4 Slowly pour the fluid compound till it fills the bottom of the Close-up plug threads.
Note: Be careful to pour slowly, to avoid trapping air bubbles in the seal.
5 Immediately wipe off any spilled compound and close the seal with a close-up plug.
Note: Initial setting of the sealing compound will occur within 30 minutes. Compound requires
a minimum of eight hours above 32 °F (0 °C) to develop sufficient strength to withstand
explosion pressures.
Plumbing Requirements
Pipe Installation
For Installation of underground liquid storage systems (Chapter 9), refer to Petroleum
Equipment Institute (PEI) publication RP100 Recommended Practices and for installation of
above-ground storage systems for motor vehicle fueling, refer to PEI publication RP200
Recommended Practices.
Product inlet pipes and vapor pipes for Gilbarco pumps/dispensers vary in location between
models. Product piping order differs from blenders to previous Advantage Series models. See
model-specific footprint before installing pipes.
• Check national, state, and local regulations for installation of the pipe system.
• Use containment system as required by national, state, and local regulations.
• Below the unit, use UL and code-approved flexible pipe (constructed of UL-approved
pipe material and UL-approved fittings).
Note: Some local regulatory agencies do not allow the use of a galvanized piping
component when diesel is involved. Consult local regulators. Also, galvanized
piping is not usable for certain Alternative fuels, such as E25 and E85 or Biodiesel.
IMPORTANT INFORMATION
Gilbarco supplies galvanized Tubing (not pipe). However, no zinc or galvanizing is
present on the inner circumference of any tubing or piping supplied by Gilbarco.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 9-11
Reference Information Plumbing Requirements
Pipe Size
The required pipe size depends on the number of units sharing lines, size of the STPs
(dispensers only), and length of the run. The following guidelines must be followed:
Page 9-12 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Plumbing Requirements Reference Information
Ensure that there is only one check valve in each dedicated line (preferred method). Use of
multiple check valves can restrict flow and cause cavitation, resulting in significant flow rate
reductions. If installation necessitates placing more than one unit on a single dedicated product
line, then check valves must be placed at each pumping unit. Check valves must be accessible
for service.
The inlet check valve for Frontier units is required for accuracy in metering fuel. Use a
factory-installed option or installation-installed check valve of low pressure drop.
Note: Components must be compatible with the fluid type being dispensed. For more
information, consult the concerned manufacturer.
Note: For some locations, shear valves are required for pumps.
For installation of underground liquid storage systems (Chapter 9), refer to PEI publication
RP100 Recommended Practices and for installation of above-ground storage systems for motor
vehicle fueling refer to PEI publication RP200 Recommended Practices. A shear valve
(see Figure 5-17 on page 5-21) is an NFPA 30A required safety device. It closes automatically
to stop product flow during a fire or if the dispenser gets knocked off the island. It also
provides a means of manually closing inlet pipes.
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page 9-13
Reference Information Plumbing Requirements
Page 9-14 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix A: Elevation Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page A-1
Appendix A: Elevation Diagrams
16 3/4
20 1/4
8 3/8
1 5/8
13/16
1 5/8
11 7/8
23 3/4
Notes: 1) Only two conduits per plate can be field-installed at diagonal knockouts.
2) Not used for field connection for pumping units.
3) Dimensions are in inches.
Page A-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-1
Appendix B: Wiring Diagrams
Page B-2 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-3
Appendix B: Wiring Diagrams
Page B-4 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-5
Appendix B: Wiring Diagrams
Page B-6 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-7
Appendix B: Wiring Diagrams
Page B-8 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-9
Appendix B: Wiring Diagrams
Page B-10 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-11
Appendix B: Wiring Diagrams
Page B-12 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-13
Appendix B: Wiring Diagrams
Page B-14 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-15
Appendix B: Wiring Diagrams
Figure B-16: Frontier Vapor Recovery Mono Three-phase Suction and One-Phase Pressure
Page B-16 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-17
Appendix B: Wiring Diagrams
Figure B-18: Frontier Vapor Recovery Duo Three-phase Suction and Pressure
Page B-18 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Appendix B: Wiring Diagrams
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Page B-19
Appendix B: Wiring Diagrams
Page B-20 MDE-5341F Frontier Single and Dual Installation Manual · December 2021
Index
Index
A J
Air, Purging From System 8-4–8-6 J-Box 9-2
Anchoring
Pump/Dispenser 5-11
L
ASC 8-1, 8-4, 8-7
Lifting Encore Units 5-1
C M
Calibration 9-3
Mounting the Unit 4-4, 5-1
CAUTION 5-6, 5-7, 5-8, 8-5
Pit Box 4-5
Changing Fuel Types 4-1
Plumbing Requirements 4-5
Alternative fuels 4-1
Conduit Installation 4-6
Vapor Barrier 6-3 P
Conduit, electrical 9-4 Pipe 9-11
Pipe, plumbing 5-10, 9-11, 9-12
Piping Layout 9-2
D
Plumb 9-11
DANGER 9-6
Potting Discs 6-4
Purging
E Underground Lines 8-4
Electric, Electrical, Electricity 9-3 Purging Air From The System 8-4–8-6
Electrician 9-3
Electronics Cabinet 9-3
S
Wiring 9-3
Service Procedures
Encore Cabinet 4-4
Purging Air 8-4–8-6
Epoxy Sealing 6-14
Setting PPU 8-7
Ethernet Cable 9-7
Shear Valve 9-13
Shutoff Operation 8-6
F SMART Meter 1-2
For New and Existing Pumps and STP 4-3, 5-10
Existing Dispensers With Fuel
In Lines 8-5
T
For New Dispensers 8-4
The Advantage Series
Installation differences 9-2
G TLS Console 6-15
Ground 9-5, 9-9
Ground Fault Interrupt 4-6
V
Grounding 9-9
Vapor Return Line 5-11
H W
Hazardous Locations 3-1
WARNING 5-1, 5-8, 5-12, 6-2, 6-3,
6-6, 6-12, 7-2, 8-1
I Wiring 9-5
IMPORTANT 4-5, 5-5, 6-2, 8-7 Field Wiring 6-10
Inlet Pipes 5-5 Operating Environment 6-5
Installation Checklists
Hydraulic Related 8-2
Mechanical 8-2
Installing Units
Flexible fuels 5-5
MDE-5341F Frontier Single and Dual Installation Manual · December 2021 Index-1
The Advantage® Series, CRIND®, Gilbarco®, G-SITE®, Infoscreen®, and Transac® are registered trademarks of Gilbarco Inc. CIM™,
SMARTConnect™, and SMART Meter™ are trademarks of Gilbarco Inc.
All product names, logos, and brands are the property of their respective owners and are for identification purposes only. Use of these names,
logos, and brands does not imply endorsement.