Evolution Series E9000 Motor Control Centers: Installation & Maintenance Guide DEH-40472 Rev. 04
Evolution Series E9000 Motor Control Centers: Installation & Maintenance Guide DEH-40472 Rev. 04
       imagination at work
Evolution Series E9000 Installation & Maintenance Guide
Contents
WARNINGS
                    Warning notices are used in this publication to emphasize that hazardous voltages, currents, or other condi-
                    tions that could cause personal injury are present in this equipment or may be associated with its use.
                    Warning notices are also used for situations in which inattention or lack of equipment knowledge could
                    cause either personal injury or damage to equipment.
CAUTIONS
NOTES
This document is based on information available at the time of its publication. While efforts have been made to ensure accuracy, the information contained herein
does not cover all details or variations in hardware and software, nor does it provide for every possible contingency in connection with installation, operation, and
maintenance. Features may be described herein that are not present in all hardware and software systems. GE Industrial Systems assumes no obligation of notice
to holders of this document with respect to changes subsequently made.
GE Industrial Systems makes no representation or warranty, expressed, implied, or statutory, with respect to, and assumes no responsibility for the accuracy, completeness,
sufficiency, or usefulness of the information contained herein. No warrantees of merchantability or fitness for purpose shall apply.
                                                                                                                                                                              2
Evolution Series E9000 Installation & Maintenance Guide
Chapter 1 – Introduction
Secure Open
3
Evolution Series E9000 Installation & Maintenance Guide
                          Loosen screw,
                          lift and pull
                          barrier forward
Figure 3. Horizontal bus barrier mounting slot and screw
                                                                                                                       4
Evolution Series E9000 Installation & Maintenance Guide
Chapter 2 – Receiving, Handling & Storage
Receiving
Before leaving the factory, the motor control center is
given a final mechanical and electrical inspection and
is packed in accordance with the best practices for
electrical equipment.
5
Evolution Series E9000 Installation & Maintenance Guide
Chapter 3 – Installation
                                                                         Figure 7A. Low bus position of ground and neutral bus (minimum
                                                                         available space for conduit entry) in 13-inch deep section, 6-inch cover.
                                                                         Figure 7B. Standard position of ground and neutral bus with 12-inch
                                                                         cover compartment at the bottom of MCC.
                                                                                                                                                     6
Evolution Series E9000 Installation & Maintenance Guide
Preparation of Flooring
For most installations, the MCC floor sills can rest on the
finished floor. The foundation for the equipment should
be level and even. Although not normally required, the
purchaser may elect to install, level and grout the steel
members or MCC floor sills in the floor, as illustrated in
Figure 8 and Figure 9. If the floor sills are removed, lifting
and moving the shipping sections must be done carefully.
                                                                                                       Loosen screw,
                                                                                                       lift and pull
                                                                                                       barrier forward
                                                                       Figure 12. Horizontal bus barrier mounting slot and screw
                                                                       Table 1. Torque values for various bolt sizes and joint types.
                                                                                              Copper Joints                Aluminum Joints
                                                                         Bolt Size
Figure 10. Side view of a 20-inch-deep section showing the cover                          lb-ft       N-m                lb-ft     N-m
plates, plug bottoms and joining points                                  5/16-18          5–9         7–12               6.5–9     9–12
                                                                         3/8-16           12–16       16–22              10–15     14–20
                                                                         1/2-13           30–39       41–53              25–35     34–47
                                                                         5/8-11           65–80       88–108             35–45     47–61
                                                                         3/4-10           125–150     169–203            50–75     68–102
                                                                       Note: When assembling or connecting to aluminum bus, apply a suitable joint
Bus Splicing                                                           compound between the contacting surfaces.
Main, neutral and ground bus splice bars (with all asso-
ciated hardware) are furnished, as necessary, to join
sections together. They are located in the first section to
the right of the joint. See Figures 13, 14 and 15 for approxi-
mate dimensions for main, neutral, and ground bus.
                                                                                                                                                     8
Evolution Series E9000 Installation & Maintenance Guide
Bus Splice Kits                                                                        as illustrated. Note that for Condition 3, where there is
Table 2. Bus Splice Kits                                                               an enclosure on opposite sides of the working space,
Splicing From / To E9000/E9000                                                         the clearance for only one working space is required.
                                         Size            SC Rating
                                  Bars/                            Splice
     Main Bus Splice                     (in.)           600V Max.
Amps                              Phase                            Instruction
     Assembly Kit                        (thick x        (sym.
                                  Copper                           Drawing*
                                         width)          amps)
Standard Splicing
600      110C1735G1SM             1          1/4 x 2 65K                 110C1258TG1
800      110C1735G4SM             1          3/8 x 2 65K                 110C1256TG1
1200 110C1735G7SM 1                          1/2 x 2 100K                110C1253TG1
1600/
      110C1735G12SM 2                        1/2 x 2 100K                110C1263TG1
2000
2500 110C1735G13SM 2                         1/2 x 2 100K                110C1785TG1
N3R and Spacer Shells
600      110C1735G14SM 1                     1/4 x 2 65K                 110C1258TG1
800      110C1735G15SM 1                     3/8 x 2 65K                 110C1256TG1
1200 110C1735G16SM 1                         1/2 x 2 100K                110C1253TG1   Figure 14. General Working Clearance Requirements
1600/
      110C1735G17SM 2                        1/2 x 2 100K                110C1263TG1
2000
2500 110C1735G13SM 2                         1/2 x 2 100K                110C1263TG1
*Included in kits.
Note: Standard plating is tin. Refer to factory for alternate plating.                 Installation of Top Entry Conduits
                                                                                       After the motor control center is in place and leveled, and
                                                                                       the sections are joined together, conduits can be brought
                                                                                       into the tops of sections as required. Figure 15 and
NEC Work Space                                                                         Figure 16 show the conduit entry space available at the
                                                                                       tops of standard sections. Refer to drawings furnished by
NEC Work Space is defined in Table 110.26(a) Working                                   GE for deviations on specific installations. Note: Top rear
Spaces. Included in these clearance requirements is the                                entrance should only be used with full rear accessibility.
step-back distance from the face of the equipment.
Table 110.26(a) provides requirements for clearances
away from the equipment, based on the circuit voltage                                                Always remove top cover plates when drilling
to ground, and whether there are grounded or unground-                                               holes. This prevents small metal chips from falling
ed objects in the step-back space, or if there are exposed                                           into the panel and cause serious damage.
live parts across from each other. The voltages to ground
consist of two groups: 0 to 150 and 151 to 600, inclusive.
Remember, where an ungrounded system is utilized, the
voltage to ground will be the greatest voltage between
the given conductor and any other conductor of the
circuit. For example, the voltage to ground for a 480-
volt ungrounded delta system is 480 volts.
9
Evolution Series E9000 Installation & Maintenance Guide
                                                                      Figure 17. Typical top entry of main cables to the incoming-line lug
                                                                      compartment (600A shown)
Figure 16. Top conduit entry space for 20-inch and 22-inch sections
Equipment Wiring
              When pulling, bending, and terminating field wiring,
              avoid scraping, cutting or otherwise damaging           Figure 18. Typical bottom entry or main cables to the incoming-
              cable insulation or strands.                            line lug compartment (600A shown)
11
Evolution Series E9000 Installation & Maintenance Guide
Figure 21. Side cutout dimensions on 13", 20", 22" and 25".
                                                                   Terminal Blocks
Figure 19. Typical Type C terminal board at the top of a section   The new style terminal blocks are mounted on a metal
                                                                   rail located at the bottom of the unit, as shown in
                                                                   Figure 22. The terminal block easily slides into position
                                                                   from either side of the mounting rail.
height, order a blank filler door with hinge hardware and        9. Slide the unit into the vertical section, then push at
a snap shelf. See the renewal parts bulletin for ordering            the top and bottom until the stabs are fully engaged
blank doors and gasket materials. The gasket material                with the vertical bus.
lines the inner perimeter of the section. Figure 23 shows        10. Rotate the latches at the top and bottom of the unit
the gasket material mounted to the outside of the door.              clockwise to engage the latches with the horizontal
                                                                     shelves above and below the unit. See Figures 25
                       Gasket                                        and 26.
                                                                 11. Verify the operation of the disconnect handle and
                                                                     safety interlocks, as described later in this manual.
Figure 26. Quarter-turn latch located at the bottom of the unit.    Operating Handles, Door Interlocks and
                                                                    Padlocking Provisions
                                                                    All Evolution motor control center units are furnished
Removal of Draw-Out Motor Control Center Units                      with disconnect operating handles that are integral to
                                                                    the unit structure. The position of the disconnect
              Some units may still have control power applied       (ON–OFF for switches or ON–OFF–TRIP for circuit breakers)
              from an external source after the unit disconnect     is indicated by the position of the operating handle.
              has been switched to the OFF position. Be extremely   The operating handle is interlocked with a catch on the
              careful when removing units from any motor
              control center. Failure to observe this precaution    inside of the unit door to prevent inadvertent opening
              can result in serious injury or death.                of the door when the disconnect is in the ON position,
                                                                    as shown in Figure 27. Switching the handle to OFF
                                                                    allows access to the interior of the unit.
The procedure for removing a motor control center
unit is generally the reverse of the procedure for                  Each disconnect operating handle is equipped with an
installing a unit:                                                  interlock that prevents opening the door when the dis-
1. Ensure that the unit disconnect is in the OFF position,          connect is ON.
    as shown in Figure 25.
2. Turn the door latches a quarter turn, open the unit              A concealed screw can be turned counterclockwise
    door and the vertical wiring trough door.                       with a 5/32” Allen wrench to defeat the door interlock
3. Disconnect all field-connected wiring by separating              and access the breaker disconnect when ON, as shown
    the pull-apart terminal blocks in the unit. Pass the            in Figure 28. Only qualified personnel should be
    terminal blocks and wires into the vertical wiring              allowed to defeat the interlock.
    trough. Note that the plastic knock-outs in the verti-
    cal wireway barrier can be removed and left within
    the vertical wireway, with the field wiring, rather
    than threading the wiring and terminals back
    through the knock-out.
4. Disconnect any other field-installed wires that are
    terminated in the unit. Remove these wires from the
    unit, tag them (if desired), and leave them in the
    vertical wireway adjacent to the unit.
                                                                                                                                    14
Evolution Series E9000 Installation & Maintenance Guide
                                                                      Operating Handle
                                                                      The operating handle must be moved out of the way
                                                                      to access to the breakerdisconnect. Make sure that the
                                                                      disconnect operating handle is in the OFF position, as
                                                                      shown in Figure 30. Open the door, then remove the
                                                                      mounting screw securing the base of the handle to the
                                                                      side of the unit, as shown in Figure 31. The handle can
Figure 29. The door cannot be opened when the disconnect is ON.       then be rotated up and out of the way, as shown in
                                                                      Figure 32, allowing access to the breaker.
Figure 30. Operating handle, also showing the safety lockout hasp.
15
Evolution Series E9000 Installation & Maintenance Guide
                                                                  1. Remove left rear cover on right shipping module (Figure 1.) Save
                                                                     the screws for later reassembly of the cover. Note that the left
                                                                     module right rear cover has a flange that will be underneath
                                                                     the removed covered with it is replaced. This provides an over-
                                                                     lapping connection in the rear of the two spliced modules
                                                                     (Detail C).
                                                                  2. Slide adjoining shipping modules as close together as possible
                                                                     while carefully aligning the modules front-to-back.
                                                                  3. Join shipping modules together using (4 sets) 1/2 hardware
                                                                     (front only). Hardware kits shipping with modules.
                                                                  4. Assemble bus splices per splice instructions (included in splice
Figure 33. Grasp the center of the door.                             kit).
                                                                  5. Install wireway transition channel barrier by sliding it though
                                                                     the 5 x 5 wireway cutout and attaching it using (1) 1/4-28 x 3/8
                                                                     thread rolling (Figure 3).
                                                                  6. Re-attach right, rear cover by re-attaching 1/4-20 x 5/8 sealing
                                                                     screw (Detail C).
                                                                  7. Attached center cap using (8) 1/4-20 x 5/8 thread rolling screws
                                                                     (Figure 1).
                                                                  Notes:
                                                                  1. 3-inch floor members can be installed similarly to standard
                                                                     MCC flor members.
                                                                  2. Module doors can be removed by removing 1/4-20 x 3/8 thread
                                                                     rolling screws from door hinge bracket (Detail D).
17
Evolution Series E9000 Installation & Maintenance Guide
Chapter 4 – Operation
Preparing for Initial Operation                                     The operating handle should move upward to the
                                                                    OFF position after the breaker has been reset. After
In addition to the normal circuit checking after wiring is
                                                                    the reset, turn the circuit breaker ON and then OFF
completed, the following specific actions should be
                                                                    to confirm proper operation.
taken before energizing the equipment:
                                                                10. Visually check all units and enclosures to ensure
1. Check and tighten any electrical connections, such
                                                                    that electrical spacings have not been reduced
    as lugs and bus splices that may have loosened
                                                                    because of shipping and handling actions.
    during shipment, handling and installation. Torque
                                                                11. Verify that the motor control center enclosure and
    values are provided on or adjacent to components or
                                                                    units are grounded.
    lugs. See torque labels in MCC vertical wireway door.
                                                                12. Replace all protection barriers and panels that have
2. Operate each magnetic device by hand to verify
                                                                    been removed during installation.
    that all moving parts operate freely. Check all elec-
                                                                13. Carefully clean the equipment interior with a clean
    trical contacts for proper operation.
                                                                    cloth, soft brush or vacuum cleaner to remove all
3. Current transformers are shipped with a shunt
                                                                    metal chips, dust, wire and other debris.
    across the secondary if the circuit is not complete.
                                                                14. After taking precautions to prevent accidental contact
    Remove the shunt after completing the connections
                                                                    with the motor control center buswork, conduct the
    to the transformer secondary.
                                                                    following insulation-resistance test with a 1000 Vdc
4. Verify that the horsepower and voltage rating of
                                                                    (Megger) tester. With all disconnects in the OFF position,
    the motor agree with the rating stamped on the
                                                                    • Apply voltage between all phase pairs.
    starter unit to which it is connected.
                                                                    • Apply voltage between each phase and ground.
5. Check each overload heater or electronic overload
                                                                    All readings should be 1 megohm minimum; typical
    relay setting against the motor full-load current.
                                                                    values will be 50–100 megohm but may vary
                                                                    based on humidity.
            Check current transformer-operated overload             Similarly, test individual feeder and motor circuit
            relays to be certain that overload heaters are
            in place. Do not operate starters without               wiring (field wiring) as each set of conductors is
            overload protection.                                    pulled into the motor control center, before termi-
                                                                    nating the conductors at either end.
                                                                15. With all disconnects OFF, close and latch all doors
6. Check all circuit breaker trip settings and fuse ratings
                                                                    and secure all external covers.
   against the drawings supplied with the equipment.
   a. If trip settings must be changed, use the GE rating
      plug extractor tool (catalog number TRTOOL) to
                                                                Initial Operation of the Motor Control Center
      remove rating plugs from Spectra circuit breakers.
   b. See the startup procedure following information
                                                                             Because of problems that may occur during
      regarding instantaneous trip settings on magnetic-                     the initial energizing of the motor control
      only circuit breakers.                                                 equipment, only qualified personnel should
                                                                             carry out this startup procedure.
              Power-factor correction capacitors on             Figure 36. Partially close the pilot device bracket
              individual motor circuits should be temporarily   and extension bubble as shown
              disconnected during startup.
                                                                                                            Extension Bubble
Door Closing Procedure of Pilot Device Bracket,
Extension Bubble Door for Some GP/FP Drives
E9000 MCC units                                                  Door Gasket Door Cut Out
                                                                Figure 38. Adjust the pilot device bracket and extension bubble lip
                                                                so it enters in between the keeper bracket and inside of the door
                                     Variable
                                     Frequency
                                     Drive
                                                                                                                              20
Evolution Series E9000 Installation & Maintenance Guide
21
Evolution Series E9000 Installation & Maintenance Guide
                                                                                                                22
Evolution Series E9000 Installation & Maintenance Guide
23
Evolution Series E9000 Installation & Maintenance Guide
Chapter 6 – Overload Heaters
Heaters for Ther-Mag Circuit Breaker Controllers                    Size 2 (Standard and Ambient Comp.)
                                                                        Motor Full-    Heater       Motor Full-    Heater
For continuous-rated motors with a service factor of                   Load Amps       Number      Load Amps       Number
1.15 to 1.25, select the appropriate heaters for the                  3-Ph, 3 Heater   CR 123     3-Ph, 3 Heater   CR 123
motor full-load current. For continuous-rated motors                    5.48-5.85       C630A       16.8-17.9       C180B
                                                                        5.85-6.47       C695A       18.0-18.7       C198B
with a service factor of 1.0, multiply the motor full-load              6.48-7.35       C778A       18.8-20.4       C214B
current by 0.9 and use this value to select heaters.                    7.36-8.06       C867A       20.5-22.7       C228B
                                                                        8.07-9.03       C955A       22.8-24.7       C250B
                                                                        9.04-9.61       C104B       24.8-26.3       C273B
Overload relay tripping current in 40°C ambient is the                  9.62-10.5       C113B       26.4-29.5       C303B
minimum value of full-load current multiplied by 1.25.                  10.6-11.6       C125B       29.6-32.5       C330B
                                                                        11.7-12.5       C137B       32.6-36.7       C366B
                                                                        12.6-13.6       C151B       36.8-41.9       C400B
Provide short-circuit protection in accordance with the                 13.7-16.7       C163B       42.0-43.2       C440B
National Electrical Code.                                                                           43.3-45.0       C460B
                                                                                                                            24
Evolution Series E9000 Installation & Maintenance Guide
25
Evolution Series E9000 Installation & Maintenance Guide
                                                                                                                    26
Evolution Series E9000 Installation & Maintenance Guide
                                                                                                                   28
Evolution Series E9000 Installation & Maintenance Guide
29
Evolution Series E9000 Installation & Maintenance Guide
Size 5 – 300:15 CT (Standard and Ambient Comp.)            Overload Heaters for Fused Controllers
   Motor Full-     Heater    SG         Instantaneous
   Load Amps       Number   Rating        Trip Setting     For continuous-rated motors with a service factor of
  3-Ph, 3 Heater   CR123     Plug      Rec.         Max.   1.15 to 1.25, select the appropriate heaters for the
     106-115       C592A     250        LO            3
     116-125       C630A     250        LO            4
                                                           motor full-load current. For continuous-rated motors
     126-135       C695A     250         2            4    with a service factor of 1.0, multiply the motor full-load
     136-151       C778A     250         2            5    current by 0.9 and use this value to select heaters.
     152-164       C867A     300         2            4
     165-179       C955A     300         2            5
     180-195       C104B     350         2            4    Overload relay tripping current in 40° C ambient is the
     196-215       C113B     350         2            5    minimum value of full-load current multiplied by 1.25.
     216-231       C125B     400         2            4
     232-255       C137B     400         2            5
     256-270       C151B     400         3            5
                                                                        Overload relays with automatic reset may auto-
                                                                        matically start a motor connected to a two-wire
                                                                        control circuit. When automatic restarting is not
Size 6 – 600:5 CT (Standard and Ambient Comp.)                          desired, use a three-wire control circuit.
   Motor Full-     Heater    SG         Instantaneous
   Load Amps       Number   Rating        Trip Setting
  3-Ph, 3 Heater   CR123     Plug      Rec.         Max.
     181-197       C220A     400       MIN.           4    Provide short-circuit protection in accordance with the
     198-214       C239A     400         2            5    National Electrical Code, except that fuses are not to
     215-238       C268A     500       MIN            4
     239-258       C301A     500       MIN            4
                                                           exceed the value shown in the table.
     259-290       C326A     500         2            5
     291-346       C356A     600       MIN            5    Suitable for use in a circuit capable of delivering not
     347-387       C379A     600         2            5
                                                           more than the maximum RMS symmetrical amperes
     388-424       C419A     600         3          MAX
                                                           indicated in the Maximum Fuse and Short-Circuit
                                                           Rating table below, 600 V maximum, when protected
Size 6 – 600:5 CT (Standard and Ambient Comp.)             by an appropriate fuse having an interrupting rating
   Motor Full-     Heater     SK        Instantaneous      not less than the available short-circuit current.
   Load Amps       Number   Rating        Trip Setting
  3-Ph, 3 Heater   CR123     Plug      Rec.         Max.
     181-197       C220A      400       LO            4
     198-214       C239A      400        2            4                 Opening of the fuse(s) may be an indication that
     215-238       C268A      400        3            5                 a fault current has been interrupted. To provide
     239-258       C301A     500        LO            4                 continued protection against fire or shock hazard,
     259-290       C326A     500         2            5                 examine all current-carrying parts and other
     291-346       C356A      800       LO            4                 components of the motor controller and replace any
     347-387       C379A     800        LO            5                 damaged components. If heater burnout occurs,
     388-423       C419A      800        2            5                 the complete overload relay must be replaced.
     424-467       C466A     1000       LO            4
     468-516       C526A     1000        2            4
     517-540       C592A     1000        2            5
                                                                                                                             30
Evolution Series E9000 Installation & Maintenance Guide
Size 0 and 1 (Standard and Ambient Comp.)                       Size 2 (Standard and Ambient Comp.)
       Motor Full-         Heater          Maximum                  Motor Full-     Heater      Maximum
       Load Amps           Number            Fuse                   Load Amps       Number        Fuse
     3-Ph., 3-Heater        CR123           Rating                3-Ph., 3-Heater    CR123       Rating
         .41-.45            C054A             3                      5.48-5.85       C630A         20
         .46-.49            C060A             3                      5.86-6.47       C695A         20
         .50-.53            C066A             3                      6.48-7.35       C778A         25
         .54-.59            C071A             3                      7.36-8.06       C867A         30
         .60-.65            C078A             3                      8.07-9.03       C955A         30
         .66-.76            C087A             3                      9.04-9.61       C104B         35
         .77-.84            C097A             3                      9.62-10.5       C113B         35
         .85-.93            C109A             3                      10.6-11.6       C125B         40
        .94-1.04            C118A             3                      11.7-12.5       C137B         45
        1.05-1.15           C131A              3                     12.6-13.6       C151B         50
        1.16-1.27           C148A              3                     13.7-16.7       C163B         60
        1.28-1.39           C163A              3                     16.8-17.9       C180B         60
        1.40-1.55           C184A              6                     18.0-18.7       C198B        70➀
        1.56-1.73           C196A              6                     18.8-20.4       C214B        80➀
        1.74-1.89           C220A              6                     20.5-22.7       C228B        80➀
        1.90-2.05           C239A              6                     22.8-24.7       C250B        90➀
        2.06-2.28           C268A              6                     24.8-26.3       C273B        90➀
        2.29-2.47           C301A              6                     26.4-29.5       C303B       100➀
        2.48-2.79           C326A             10                     29.6-32.5       C330B       100➀
        2.80-3.31           C356A             10                     32.6-36.7       C366B       100➀
        3.32-3.70           C379A             12                     36.8-41.9       C400B       100➀
        3.71-4.06           C419A             15                     42.0-43.2       C440B       100➀
        4.07-4.47           C466A             15                     43.3-45.0       C460B       100➀
        4.48-4.95           C526A             15
        4.96-5.49           C592A             20
        5.50-5.91           C630A             20                Size 3 (Standard)
        5.92-6.47           C695A             25
        6.48-7.20           C778A             25                    Motor Full-     Heater      Maximum
        7.21-8.22           C867A             30                    Load Amps       Number        Fuse
        8.23-8.72           C955A             30                  3-Ph., 3-Heater    CR123       Rating
        8.73-9.67           C104B            35➀                     19.0-19.3       F233B         70
        9.68-10.4           C113B            35➀                     19.4-22.1       F243B         80
        10.5-11.0           C125B            40➀                     22.2-23.4       F270B         80
        11.1-12.4           C137B            45➀                     23.5-27.0       F300B         90
        12.5-13.2           C151B            50➀                     27.1-29.1       F327B        100
        13.3-15.4           C163B            60➀                     29.2-31.8       F357B       110➀
        15.5-17.1           C180B            60➀                     31.9-33.9       F395B       125➀
        17.2-18.0           C198B            60➀                     34.0-37.6       F430B       125➀
                                                                     37.7-41.9       F487B       150➀
                                                                     42.0-47.7       F567B       175➀
Size 1 (Standard and Ambient Comp.)                                  47.8-52.1       F614B       175➀
       Motor Full-         Heater          Maximum                   52.2-55.8       F658B       200➀
       Load Amps           Number            Fuse                    55.9-59.7       F719B       200➀
     3-Ph., 3-Heater        CR123           Rating                   59.8-68.1       F772B       200➀
        17.2-18.1           C198B            60➀                     68.2-71.5       F848B       200➀
        18.2-20.0           C214B            60➀                     71.6-78.2       F914B       200➀
        20.1-21.5           C228B            60➀                     78.3-87.5       F104C       200➀
        21.6-22.5           C250B            60➀                     87.6-90.0       F114C       200➀
        22.6-23.9           C273B            60➀
        24.0-26.3           C303B            60➀
        26.4-27.0           C330B            60➀
31
Evolution Series E9000 Installation & Maintenance Guide
                                                                                                                                        32
Evolution Series E9000 Installation & Maintenance Guide
Heaters for NEMA Size 6 and 7 Fused Controllers                   Electronic Overload for Circuit Breaker
For continuous-rated motors with a service factor of              and Fused Controllers
1.15 to 1.25, select the appropriate heaters for the              The tripping current is 120% of the dial setting. For
motor full-load current. For continuous-rated motors              continuous-rated motors with a service factor of 1.15
with a service factor of 1.0, multiply the motor full-load        to 1.25, set the dial to the motor full-load current. For
current by 0.9 and use this value to select heaters.              continuous-rated motors with a service factor of 1.0,
                                                                  set the dial to 0.9 of the motor full-load current. Refer
Overload relay tripping current in 40° C ambient is the           to GEH-6430 or 6431 before energizing.
minimum value of full-load current multiplied by 1.25.
Provide short-circuit protection in accordance with the                           Opening of the branch-circuit protective device
National Electrical Code.                                                         may be an indication that a fault current has
                                                                                  been interrupted. To provide continued protection
                                                                                  against fire or shock hazard, examine all current-
             Opening of the circuit breaker or power fuse may                     carrying parts and other components of the motor
             be an indication that a fault current has been                       controller and replace any damaged components.
             interrupted. To provide continued protection                         If heater burnout occurs, the complete overload
             against fire or shock hazard, examine all current-                   relay must be replaced.
             carrying parts and other components of the motor
             controller and replace any damaged components.
             If heater burnout occurs, the complete overload
             relay must be replaced.                              Provide short-circuit protection in accordance with NEC
                                                                  Article 430 or CE Code Part 1.
33
Catalog numbers of electronic overloads for various sizes of            AF-600 FP / AF-650 GP Drives E9000
NEMA starters and current ranges.                                       Panel mount use with RTXP base adapter
NEMA     FLA Range     Catalog                                                        Cat. No.                FLA                          Torque
                                         Max. Fuse in Amps              Contactor                                         Lug/ wire size
Size     in Amps       Number                                                         Class 10     Class 20   range                        (in-lbs)
1        0.8 to 1.59   CR324CXD                                         LAR02AJ       RTN1B        NA         0.16-0.26   #14-8 AWG        14-20
1        1.6 to 3.19   CR324CXE                                         LAR25AJ       RTN1C        NA         0.27-0.41   #14-8 AWG        14-20
                                   Time-Delay Time-Delay
1        3.2 to 6.49   CR324CXF                                                       RTN1D        RT12D      0.42-0.65   #14-8 AWG        14-20
                                   Class R&J 30 Class J 60
1        6.5 to 12.8   CR324CXG                                                       RTN1F        RT12F      0.66-1.10   #14-8 AWG        14-20
1        13 to 27      CR324CXH                                                       RTN1G        RT12G      1.11-1.50   #14-8 AWG        14-20
2        13 to 25.6    CR324DXG                                                       RTN1H        RT12H      1.51-1.90   #14-8 AWG        14-20
2        26 to 49.9    CR324DXH    60              100                                RTN1J        RT12J      1.91-2.5    #14-8 AWG        14-20
2        50 to 100     CR324DXJ                                                       RTN1K        RT12K      2.51-4.10   #14-8 AWG        14-20
3        17 to 34.9    CR324FXK                                                       RTN1L        RT12L      4.11-6.3    #14-8 AWG        14-20
3        35 to 64.9    CR324FXL    100             200                  LAR45AJ       RTN1M        RT12M      6.31-8.5    #14-8 AWG        14-20
3        65 to 90      CR324FXM                                                       RTN1N        RT12N      8.51-12.0   #14-8 AWG        14-20
4        17 to 34.9    CR324FXK                                                       RTN1P        RT12P      12.1-16     #14-8 AWG        14-20
4        35 to 64.9    CR324FXL    200             400                                RTN1S        RT12S      16.1-18     #14-8 AWG        14-20
4        65 to 135     CR324FXM                                                       RTN1T        RT12T      18.1-22     #14-8 AWG        14-20
5➀       32 to 64.0    CR324GXN                                                       RTN1U        RT12U      22.1-26     #14-8 AWG        14-20
5➀       65 to 129.9   CR324GXP    400             600                                RTN1V        RT12V      26.1-32     #14-8 AWG        14-20
5➀       130 to 270    CR324GXQ                                                       RTN1W        RT12W      32.1-40     #14-8 AWG        14-20
6➁                                                                      LAR08AJ       RTN2A        NA         11.5-15     #10-3 AWG        50
         130 to 259.9 CR324HXS     600             Class L 1200
➀ 300:15 CT’s
➁ 800:5 CT’s                                                            Mount direct to contactor
                                                                                        Cat. No.                                           Torque
                                                                        Contactor                             FLA range Lug/ wire size
                                                                                        Class 10   Class 20                                (in-lbs)
IEC Style Overload Relays                                               LAR08AJ         RTN2B      NA         15.1-19     #10-3 AWG        50
C2000 Contactor CLNCJ Type RT Overload Relay for 1/2X Starter                           RTN2C      NA         19.1-25     #10-3 AWG        50
Current    Max                                   Lug/        Torque                     RTN2D      RT22D      25.1-32     #10-3 AWG        50
                 Cat. No. Class Cat. No. Class                                          RTN2E      RT22E      32.1-43     #10-3 AWG        50
Range      CB                                    wire size   (in-lbs)
0.4-.65    15    RTN1D     10   RT12D    20      #14-8       14-20                      RTN2G      RT22G      43.1-55     #10-3 AWG        50
                                                                        LAR10AJ
0.65-1.1   15    RTN1F     10   RT12F    20      #14-8       14-20                      RTN2H      RT22H      55.1-65     #10-3 AWG        50
1-1.5      15    RTN1G     10   RT12G    20      #14-8       14-20                      RTN2J      RT22H      65.1-82     #10-3 AWG        50
1.3-1.9    15    RTN1H     10   RT12H    20      #14-8       14-20                      RTN2L      RT22L      82.1-97     #10-1 AWG        50
1.8-2.7    15    RTN1J     10   RT12J    20      #14-8       14-20                      RTN2M      RT22M      97.1-110    #10-1 AWG        50
2.5-4.1    15    RTNIK     10   RT12K    20      #14-8       14-20                      RTN3B      NA         55-80       #6-250 MCM       275
                                                                                        RTN3C      RT32C      80.1-90     #6-250 MCM       275
4.0-6.3    15    RTNIL     10   RT12L    20      #14-8       14-20
                                                                        KAR08CJ         RTN3D      RT32D      90.1-120    #6-250 MCM       275
5.5-8.5    15    RTNIM     10   RT12M    20      #14-8       14-20
                                                                                        RTN3E      RT32E      120.1-140   #6-250 MCM       275
8.0-12     30    RTNIN     10   RT12N    20      #14-8       14-20
                                                                                        RTN3F      RT32F      140.1-190   #6-250 MCM       275
10.0-16    35    RTNIP     10   RT12P    20      #14-8       14-20
                                                                                        RTN4N      NA *       120-190     #6-350MCM        200
14.5-18    40    RTNIS     10   RT12S    20      #14-8       14-20
                                                                        KAR95BYWZ       RTN4P      NA *       190.1-280   #6-350MCM        200
17.5-22    50    RTNIT     10   RT12T    20      #14-8       14-20                      RTN4R      NA *       280.1-310   #6-350MCM        200
                                                                                        RTN4N      NA *       120-190     #6-350 MCM       200
                                                                        KAR95BJWZ       RTN4P      NA *       190.1-280   #6-350 MCM       200
                                                                                        RTN4R      NA *       280.1-310   #6-350 MCM       200
                                                                        KAR10BYWZ       RTN5A      NA *       120-190     #6-350MCM        375
                                                                        KAR11BYWZ       RTN5B      NA *       190.1-280   #6-350MCM        375
                                                                        KAR11BJWZ       RTN5B      NA *       190.1-280   #6-350 MCM       375
                                                                        KAR12BJWZ       RTN5C      NA *       280.1-400   #6-350 MCM       375
                                                                                        RTN5C      NA *       280.1-400   #8-500 MCM       375
                                                                        KAR12BYWZ       RTN5D      NA *       400.1-500   #8-500 MCM       375
                                                                                        RTN5E      NA *       500.1-650   #8-500 MCM       375
                                                                        *Class 30 is available
                                                                        WZ – Special for Mebane
                                                                                                                                                      34
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency
that may be met in connection with installation, operation, or maintenance. Should further information be desired or
should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be
referred to the GE Company.
                        imagination at work
                                                                                                                            DEH-40472 R04 01/09