Airstage Ajy040lelah
Airstage Ajy040lelah
English
OUTDOOR UNIT
For authorized service personnel only.
INSTALLATIONSANLEITUNG
Deutsch
AUSSENGERÄT
Nur für autorisiertes Fachpersonal.
MANUEL D’INSTALLATION
Français
UNITÉ EXTÉRIEURE
Uniquement réservé aux techniciens agréés.
MANUAL DE INSTALACIÓN
Español
UNIDAD EXTERIOR
Sólo para personal de servicio autorizado.
AJY040LELAH
AJY045LELAH MANUALE D’INSTALLAZIONE
Italiano
AJY054LELAH UNITÀ ESTERNA
A uso esclusivo del personale tecnico autorizzato.
AJH040LELAH
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
EλληvIkά
AJH045LELAH ΕΞΩΤΕΡΙΚΉ ΜΟΝΆΔΑ
AJH054LELAH Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό.
MANUAL DE INSTALAÇÃO
Português
UNIDADE EXTERIOR
Apenas para técnicos de assistência autorizados.
РУКОВОДСТВО ПО УСТАНОВКЕ
Русский
ВНЕШНИЙ МОДУЛЬ
Только для авторизованного обслуживающего персонала.
KURULUM KILAVUZU
Türkçe
DIŞ ÜNİTE
Yalnızca yetkili servis personeli için.
[Original instructions]
10.1. Normal operation codes ………………………………………………………… 18 Use a wall hole pipe. Otherwise, it may cause a short circuit.
10.2. Error codes ……………………………………………………………………… 18
Do not place the outdoor unit near the handrail of the balcony.
Children may climb onto the outdoor unit, lean over the handrail and fall over.
11. INFORMATION ………………………………………………………………………… 18
Use only a specified power cable. Poor connection, poor insulation, and exceeding the
allowable current will lead to electric shock and fire.
Attach the connecting cables securely to the terminal. Or secure it firmly with a “wiring
suppressor”.
Loose connection will lead to malfunction, electric shock, and fire.
Install a breaker (Included with earth leakage circuit breaker) to cut off all AC main cur-
rent at the same time.
If you do not install a breaker, it may cause electric shock and fire.
During installation, make sure that the refrigerant pipe is attached firmly before you run
the compressor.
Do not operate the compressor under the condition of refrigerant piping not attached
properly with 2-way or 3-way valve open. This may cause abnormal pressure in the
refrigeration cycle that leads to rupture and even injury.
During the pump-down operation, make sure that the compressor is turned off be-
fore you remove the refrigerant piping. Do not remove the connection pipe while the
compressor is in operation with 2-way or 3-way valve open. This may cause abnormal
pressure in the refrigeration cycle that leads to breakage and even injury.
En-1
When setting it up near the equipment that generates electromagnetic waves and the
equipment that generates the higher harmonics wave, be sure to take measures against
noise. Otherwise, it may cause malfunction or failure. Installation (This book)
manual
When energizing to the crankcase heater, please turn on the power 12 hours or earlier 1
before operation begins. When the energizing time is short, it may cause failure. Be-
sides, please do not turn off power during the busy season.
Drain cap For outdoor unit drain piping work
Children should be monitored to ensure they do not play with the device.
This product is not intended to be used by people (including children) with physical, sen- 3
sory or mental disability, or persons lacking experience or knowledge unless they have
been given by the through a person responsible for their safety, supervision or instruc-
tion concerning the use of the device. Drain pipe For outdoor unit drain piping work
En-2
CAUTION CAUTION
The following parts are optional parts specific to R410A refrigerant. Perform drain work in accordance with this Manual, and ensure that the drain water is
Do not use parts other than those listed below. properly drained. If the drain work is not carried out correctly, water may drip down from
the unit, wetting the furniture.
2.4.1 Separation tube kit
When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe
Separation tube uses the following parts.
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may
Separation tube Total cooling capacity of indoor unit (kw) freeze in extremely cold weather.
UTP-AX054A ALL • As the drain water flows out of the outdoor unit during heating operation, install the
drain pipe and connect it to a commercial 16 mm hose.
2.4.2 Header • When installing the drain pipe, plug all the holes other than the drain pipe mounting
hole in the bottom of the outdoor unit with putty so there is no water leakage.
Header uses the following parts. A header is used for connecting the indoor units.
Header Drain pipe mounting hole
Total cooling capacity of indoor unit (kw)
3-6 Branches 3-8 Branches
UTR-H0906L UTR-H0908L ALL Base
Drain cap mounting hole ×3
2.4.3 External connect kit
Drain pipe
Model Usage Air
227
For External output (Error status / CN136) (Operation status / CN137)
305
321
341
UTY-XWZXZF For External input (CN135)
Install the unit in an area that would not inconvenience your neighbors, as they could be Consider the transportation route, installation space, maintenance space, and access,
affected by the airflow coming out from the outlet, noise, or vibration. and install the unit in a location with sufficient space for the refrigerant piping.
If it must be installed in proximity to your neighbors, be sure to obtain their approval. Observe the installation space specifications
If the unit is installed in a cold region that is affected by snow accumulation, snow fall, or that are shown in the figures.
freezing, take appropriate measures to protect it from those elements. Keep the same space at rear air intake.
To ensure a stable operation, install inlet and outlet ducts. Provide the same space for the air intake at the
rear of the outdoor unit.
Install the unit in an area that would not cause problems even if the drain water is Air intake
If the installation is not performed according to
discharged from the unit. Otherwise, provide drainage that would not affect people or the specifications, it could cause a short circuit
objects. and result in a lack of operating performance.
Install the unit in an area that has no heat sources, vapors, or the risk of the leakage of As a result, the outdoor unit might easily be
flammable gas in the vicinity. stopped by high-pressure protection.
Rear view
Install the unit in an area that is away from the exhaust or vent ports that discharge
vapor, soot, dust, or debris. Installation methods not shown in the following examples are not recommended. Perfor-
mance may drop significantly.
Install the indoor unit, outdoor unit, power supply cable, transmission cable and remote
control cable at least 1 meter away from a television or radio.
The purpose of this is to prevent TV reception interference or radio noise. (Even if they
are installed more than 1 meter apart, you could still receive noise under some signal
conditions.)
Keep the length of the piping of the indoor and outdoor units within the allowable range.
For maintenance purposes, do not bury the piping.
En-3
150 500
2000 or
more 3000 or
150 200 600 more
600
300 1000 1500
200
(3) Obstacles at front only (4) Obstacles at front and rear only
3.4. Transporting the unit
WARNING
Do not touch the fins. Otherwise, personal injury could result.
150
1000 or more
1000 or more CAUTION
When carrying the unit, hold the handles on the right and left sides and be careful.
When an obstruction is present also in the upward area (Unit: mm) If the outdoor unit is carried from the bottom, hands or fingers may be pinched.
(1) Obstacles at rear and above only (2) Obstacles at rear, sides, and above only • Carry slowly in the manner as shown on “Fig. B” holding the handles “Fig. A” in right and
left sides. (Be careful not to touch with hands or objects.)
• Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on the
1000 1500 sides of the unit may be deformed.
Fig. A Fig. B
Suction grille
300
250 500
Max. 500
Handle
250 Max. 500
Handle
3.3.2 Multiple outdoor unit installation Front view Rear view
• Provide at least 25 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for the piping.
• No more than 3 units must be installed side by side. 3.5. Installing the unit
When 3 units or more are arranged in a line, provide the space as shown in the following
• Please install the outdoor unit without slant. (within 3 degrees )
example when an obstruction is present also in the upward area.
• Install 4 anchor bolts at the locations indicated with arrows in the figure.
When the upward area is open (Unit: mm) • To reduce vibration, do not install the unit directly on the ground. Install it on a secure
base (such as concrete blocks).
(1) Obstacles at rear only (2) Obstacles at front only • The foundation shall support the legs of the unit and have a width of 50 mm or more.
• Depending on the installation conditions, the outdoor unit may spread its vibration during
operation, which may cause noise and vibration. Therefore, attach damping materials
(such as damping pads) to the outdoor unit during installation.
• Install the foundation, making sure that there is enough space for installing the connec-
tion pipes.
• Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially avail-
able M10 bolts, nuts, and washers.)
1500 or more • The bolts should protrude 20 mm. (Refer to the figure.)
300
• If overturning prevention is required, purchase the necessary commercially available
(3) Obstacles at front and rear only items.
Unit: mm
166 650 154
Bolt
50 50
AIR Nut
16
500 Base
20
1500 or more
410
Do not install directly on the ground, this may result in equipment failure.
Provide ample space for ice buildup from condensate between the bottom of the unit and
the flat surface on which it is mounted.
Otherwise, there is risk that the drainage water will freeze between the device and the
surface, disabling drainage.
1500
CAUTION
If the unit is installed in a region that is exposed
to high winds, freezing conditions, freezing rain,
1500 snow fall or heavy snow accumulation, take
appropriate measures to protect it from those ele-
500 ments.
Max. 300 To ensure stable operation, the outdoor unit must
be installed on a raised stand or rack, at or above
the anticipated snow depth for the region.
The installation of snow hoods and drift preven-
tion fencing is recommended when blowing and
drifting snow is common to the region.
Base
En-4
En-5
Nitrogen gas
Apply nitrogen gas while brazing the pipes. 5.3. Opening the knockout hole
Nitrogen gas pressure: 0.02 MPa (= pressure
felt sufficiently on the back of your hand) Brazing area
CAUTION
If a pipe is brazed without applying nitrogen gas, it will create an oxidation film.
Be careful not to deform or scratch the panel while opening the knockout holes.
This can degrade performance or damage the parts in the unit (such as the compressor
or valves). To protect the piping insulation after opening a knockout hole, remove any burrs from
the edge of the hole. It is recommended to apply rust prevention paint to the edge of the
Do not use flux to braze pipes. If the flux is the chlorine type, it will cause the pipes to
hole.
corrode.
In addition, if the flux contains fluoride, it will affect the refrigerant piping system due to • Pipes can be connected from 4 directions, front, lateral side, rear side and bottom.
deterioration of refrigerant oil. (Fig. A)
• When connecting at the bottom, remove the service panel and piping cover on the front
For brazing material, use phosphor copper that does not require flux.
of the outdoor unit, and open the knockout hole provided at the bottom corner of the
piping outlet.
5.2. Indoor unit pipe connections • It can be installed as shown on “Fig. B” cutting out the 2 slits as indicated on “Fig. C”.
(When cutting slits, use a steel saw.)
CAUTION Fig. A
For details, refer to the Installation Instruction Sheet of each part.
Separation tube
Horizontal Vertical
B A B
A:
Outdoor unit or Refrigerant
branch kit Service
or
A panel
B: Horizontal line
Indoor unit or Refrigerant
branch kit ± 15°
B A
GOOD GOOD
Fig. B Fig. C
PROHIBITED
Header
Gas pipe Horizontal line Horizontal line
C β1
H1 = 0 to 10 mm
(α1: 0° to 1°)
Outdoor
GOOD α1 View C β1: -10° to 10°
Slit
unit side H1 Slit
Liquid pipe Horizontal line Vertical line Bottom
D connection
H2 = 0 to 10 mm
Outdoor α2 (α2: 0° to 1°)
unit side H2 β2 β2: -10° to 10°
GOOD
View D
PROHIBITED
CAUTION
Do not connect a separation tube after a header.
Leave the distance 0.5 m or more for straight part to branch tube and header.
To indoor unit or
Header
0.5 m or more
Main pipe
To indoor unit
To indoor unit
En-6
CAUTION
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of
curvature of 100 mm or more.
If the pipe is bent repeatedly at the same place, it will break.
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes at an angle of more than 90°.
• When pipes are repeatedly bent or stretched, the material will harden, making it difficult
to bend or stretch them any more.
• Do not bend or stretch the pipes more than 3 times.
5.4.3 Pipe connection
CAUTION
Be sure to install the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the flare nut cannot be tightened smoothly.
If the flare nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the outdoor unit pipe until immediately before connect-
ing the connection pipe.
After installing the piping, make sure that the connection pipes do not touch the com-
pressor or outer panel. If the pipes touch the compressor or outer panel, they will vibrate
and produce noise.
(1) Detach the caps and plugs from the 3-way valve (Liquid)
3-way valve
pipes. (Gas)
(2) Center the pipe against the port on the
outdoor unit, and then turn the flare nut
by hand. Flare nut Flare nut
(3) Tighten the flare nut of the connection
pipe at the outdoor unit valve connec-
tor. Connection
(4) After tightening the flare nut by hand, Connection pipe pipe (Gas)
use a torque wrench to fully tighten it. (Liquid)
En-7
Breaker
Outdoor unit Remote con-
Power supply cable troller cable
En-8
GOOD PROHIBITED
1 wire 2 pcs at one side Wires twisted
Transmission line
Refrigerant
system 3
Transmission line
Refrigerant
6.4.1 Transmission wiring specifications system 2
Follow the specifications below for the transmission cable.
Use Size Cable type Remarks
Transmission line
22AWG LEVEL 4 (NEMA)
LONWORKS ®
Transmission cable 0.33mm² non-polar 2core, twisted pair Refrigerant
compatible cable system 3
solid core diameter 0.65mm
Twisted pair with shielded type.
Use the shielded wire specified and always ground it both end. 6.5. Wiring method
6.4.2 Wiring rules 6.5.1 Connection diagrams
(1) Total length of transmission cable
Total transmission line length: MAX 3,600 m Power supply: 400V 3Φ 50Hz
Breaker:
EF + EG + GH + HJ + HK + KL < 3,600 m (Fig.2) L1 L2 L3 N (1) Earth leakage circuit breaker
In the following cases , Signal Amplifier is required. (2) Current breaker (over current)
1 When the total length of the transmission line exceeded 500 m.
AB + BC + BD > 500 m (Fig.1) Breaker
2 When the total number of units* is over 64.
3 Transmission line length between each unit* ≥ 400 m Outdoor
(2) Length of transmission cable between 1 network segment (NS) unit L1 L2 L3 N
To other refrigerant circuit outdoor unit
EF + EG + GH + HJ + HK ≤ 500 m (Fig.2) Power supply
KL ≤ 400 m (Fig.2)
Transmission
Unit* means indoor unit, outdoor unit, Touch Panel Controller and System Controller,
Signal Amplifier, single split adaptor, Network Convertor etc.
Fig. 1
Outdoor unit
Transmission line
System
B C Controller
A
Terminal Indoor unit Indoor unit Indoor unit
resistor D
Transmission Transmission Transmission
Indoor unit Power supply Remote control Power supply Remote control Power supply Remote control
Touch
Panel
When AB+BC+BD> 500 m Controller
:Signal Amplifier is required.
Fig. 2 *1 *1 *1
*2 *2
NS 1 NOTE: *2
Outdoor unit Do not use loop wiring. Breaker Breaker Breaker
Indoor unit This may lead to parts
F damage and erroneous
E operation. Power supply Remote Power supply Remote Power supply Remote
230V 1Φ 50Hz controller 230V 1Φ 50Hz controller 230V 1Φ 50Hz controller
Terminal resistor *1: The number of power supply terminals is different depending on the indoor unit model.
For the wiring, refer to the indoor unit installation manual.
*2: Earth (Ground) the remote controller if it has an earth (ground) cable.
G Transmission line • There are two types of remote controller: the 2-wire type and the 3-wire type. For details,
see the relevant remote controller installation manual. (When connecting the 2-wire type
H J Touch remote controller, Y3 is not used.)
Panel The wiring example for outdoor and indoor units is shown in figure.
K Controller
NS 2
Signal Amplifier
L System
Controller
Terminal resistor
En-9
Input 4
(CN134: Red)
Cable tie Input 5
(CN135:
About 550 mm
(accessory) Input 3
About 520 mm
Cable Output 1
Input 2
clamp (CN136:
(CN132: Green)
Black)
Ring terminal (M5)
Output 2 Input 1
(CN131: Yellow)
8 to 10 mm
(CN137:
45 to 50 mm
Blue)
40 mm
30 mm
25 to
25 to
CAUTION
Earth (ground) Do not bundle the cable for base heater with other cables.
Cable tie Cable tie
cable
(accessory)
Power supply
cable Transmission cable Power supply cable
When connecting cable to Input 2
Transmission cable
How to connect wiring to the terminal
Caution when wiring cable
(1) Use ring terminals with insulating sleeves as shown in the figure to connect to the
terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
About 550 mm
(3) Use the specified cables, connect them securely, and fasten them so that there is
no stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent Cable (for external
the screws from being properly tightened. input and output)
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table below for the terminal screw tightening torques.
connected unit connected unit connected unit connected unit connected unit
Use one side of the Connect both ends of shielded wire to earth (Ground).
twisted-pair cable
En-10
* A twisted pair cable (0.33 mm² (22AWG)) should be used. Figure: Terminal resistor setting
Maximum length of cable is 150 m. NS1 (Network segment 1)
About the setting of
* Use an external input and output cable with appropriate external dimension, depending (Set terminal resistor at outdoor units)
terminal resistor
on the number of cables to be installed.
Terminal resistor: on Outdoor unit
6.6.4 Base heater terminal
: On
This is the output signal for base heater. Output signal ON, when the outdoor temperature
goes down below 2°C, and signal OFF at the outdoor temperature 4°C. Master unit Refrigerant system 1
: Off
P.C.B.
Terminal resistor: off Signal amplifier
Install
Voltage: Refrigerant system 2
CN115 power supply input voltage Base heater *9 Master unit Do not
(Black) install
*8
cable
(0.82 mm2 (18AWG))
*8: Connect to pin 1 and pin 3. No connection pin 2 and pin 4. Refrigerant system 3
*9: The allowable current is 1 A or less. Master unit
NS2 (Network NS3 (Network segment 3) NS4 (Network
segment 2) segment 4)
Terminal resistor: on
En-11
Refrigerant
Switch Setting (Forbidden) 2 7 0 0
Setting Type of switch 27
Setting range (Factory default)
circuit
address REF AD (Forbidden) 2 8 0 0
28
×10 ×1 (Factory default)
0 0 0 Refrigerant Setting
(Forbidden) 2 9 0 0
29
circuit 0–99 example (Factory default)
1 0 1
2 0 2
address 63 Level 1 (stop) 0 0
Level 2
• • • REF AD × 10 REF AD × 1 0 1
(operated at 40% capacity)
• • • Level 3
Rotary Switch (REF AD × 1): Factory setting “0” Energy saving 0 2
98 9 8 (operated at 60% capacity) 3 0
level setting *1
Rotary Switch (REF AD × 10): Factory setting “0” Level 4
99 9 9 30 0 3
(operated at 80% capacity)
Level 5
7.4. Push button setting (operated at 100% capacity)
0 4
The capacity limit can be selected by the external input terminal (CN133) when operating
Various functions can be set. Set when necessary.
with the “Energy Saving Peak Cut function”.
Perform settings after all indoor units have stopped operation. The lower the level, the more the effect of energy saving, but the cooling/heating perfor-
Table. A: List of Settings mance will also drop.
7 segment display Factory
(Forbidden) 3 1 0 0
No Setting Item 31
First 2 digits Last 2 digits default (Factory default)
En-12
1: Function setting
(Flashing)
En-13
1: Function setting
End
The number of indoor units with normal settings
7.6. Indoor unit address setting will be displayed at the first 2 digits of the 7 seg-
ment LED display. The number of indoor units with
7.6.1 Indoor unit address setting error will be displayed at the last 2 digits.
Address must be set for the indoor unit.
Manual setting → • When setting with the switch inside the indoor unit, refer to
the indoor unit operating manual. NOTE:
After the “ENTER” button is pressed, the end
• When setting with a remote control, refer to the remote
processing will occur for about 30 seconds. During
control operating manual.
this period, the 7 segment will blink.
Automatic setting → • Check that the wiring is as shown in the figure below.
Operate using the outdoor master unit of each refrigerant End
system.
Fig. Wiring example for automatic address setting 7.7. Resistance measurement of transmission cable
(1) Signal amplifier wiring example (Measure with breaker OFF)
(2)(3)(4) Indoor unit wiring example
(Connect the indoor and outdoor units of the same refrigerant system as shown Distance from termination resis-
below.) CAUTION tor (m)
Refrigerant system1 Signal amplifier Do not turn on the power if the resistance 0 ~ 200 ~ 300 ~400 ~500
between the terminals of the transmission ~100
cable is abnormal. Otherwise, the PC A short circuit somewhere or 2
Master unit 0~
board may be damaged. or more termination resistors are
50
Refrigerant system2 connected
Measure the resistance between 2 terminals
of a transmission cable. 50
(1) Transmission cable connecting in- 60
Master unit door units, outdoor units, and signal 70
Signal amplifier amplifiers 80
Refrigerant system3 Measure the resistance of the signal
90
amplifier terminal and the terminal of
100
the indoor and outdoor units connected
Master unit 110
farthest away from the device where
terminal resistor is measured. 120
A value from the table is displayed, 130
Approximate resistance (Ω)
NOTE: 140
depending on the distance from the
• When network is connected to other refrigerant systems, the automatic address function
cannot be used. signal amplifier and the device where 150
• The addresses of indoor units that have been configured automatically cannot be as- the terminal resistor is set. 160
signed in the order when they are installed. (Refer to the indoor unit installation manual This value is an estimate. 170
for the procedures to check the addresses.) (2) Transmission cable connecting 180
outdoor units in a refrigerant system
190 Faulty contact or wiring
The resistance between the terminals ~ length over 500 m
of the transmission cable is 45-60 Ω.
1K Faulty contact, open circuit, or no
This value is an estimate.
~∞ termination resistor
En-14
En-15
19.05) 10 13 16 21
* When an ambient temperature and relative humidity exceed 32 °C, please strengthen (*1)
Confirm the number of connected indoor units and the
heat insulation of refrigerant pipe.
volume ratio of the indoor units connection.
9. TEST RUN
Normal operation will not be possible without performing the Indoor unit connection check. When it finishes normally, nothing will be displayed on
7 segment display.
9.1.1 Things to confirm before starting the Indoor unit connection
check
To ensure safety, check that the following work, inspections and operations have been
completed.
En-16
Example:
When “Indoor unit capacity error [E221]” and “Indoor unit duplicate address error [E261]”
occurred.
Before the test operation, check the following items. Press the “ENTER” button for Press the “ENTER” button for
(1) Is there a gas leakage? (At pipe connections {flange connections and brazed areas}) more than 3 seconds. more than 3 seconds.
(2) Is the system charged with the specified volume of refrigerant? This will be dis- This will be dis-
(3) Is the refrigerant circuit address correct? played when the played when the
(4) Is a breaker installed at the power supply cable of outdoor unit? cooling test opera- heating test opera-
(5) Are the cable connected to the terminals without looseness, and in accordance with tion is complete. tion is complete.
the specifications?
(6) Are the initial settings of the switches of the outdoor unit correctly configured? This will be This will be
(7) Is the 3-way valve of the outdoor unit open? (Gas pipe and liquid pipe) displayed after 5 displayed after 5
(8) Is power supplied to the crank case heater for more than 12 hours? Electricity current seconds. seconds.
in short period of time may result in compressor damage.
(9) Are all the indoor units within the same coolant system connected to the power? Op-
erating indoor units which are not connected to the power may result in malfunctions.
(10) Is Indoor unit connection check performed? Test run doesn't operate if Indoor unit Settings for stopping test run
connection check is not performed. operation
After checking that the above items are all in order, refer to “9.3.
Test run method” to test operation the unit.
If there are problems, adjust immediately and recheck.
9.3. Test run method Press the “ENTER” button for Press the “ENTER” button for
more than 3 seconds. more than 3 seconds.
Be sure to configure test run settings only when the outdoor unit has stopped oper- This will be dis- This will be dis-
ating. played when the played when the
cooling operation heating operation
• Depending on the communication status between the indoor and outdoor units, it may
mode is canceled. mode is canceled.
take several minutes for the system to start operating after settings for the test run are
complete. This will be This will be
• After the test run settings are complete, the outdoor unit and the connected indoor displayed after 5 displayed after 5
units will start operating. Room temperature control will not activate during test opera- seconds. seconds.
tion (continuous operation).
• If a knocking sound can be heard in the liquid compression of the compressor, stop
the unit immediately and then energize the crank case heater for a sufficient length of
time before restarting the operation.
Perform test operation for each refrigerant system. EXIT
You can set “cooling test operation" or “heating test operation” with the push button on the
outdoor unit PC board. After the test operation is complete, turn off the power. Attach the cover of the electrical
component box and the front panel of the outdoor unit.
NOTE:
• Check that the indoor and outdoor units connected to the same refrigerant system are
operating normally.
• When indoor or outdoor units are not operating, or when the indoor and outdoor units
of other refrigerant systems are operating, the indoor/outdoor unit address are not
configured correctly.
• The system will not operate normally with an incorrect DIP switch setting.
Stop the system immediately and recheck the DIP switch setting.
En-17
1: , 2: , 3: , 4: , 5: , 6: , 7: , 8: , 9: , 0:
You can determine the operating status by the lighting up and blinking of the LED display.
Check the status using the table below.
Communica- E 1 4. 2 Outdoor unit network communication 2 error Input during cooling/heating operation under cool-
7. Input power
tion error E 1 4. 5 The number of indoor unit shortage ing/heating condition (refer to item 15)
E 2 2. 1 Indoor unit capacity error Maximum electric current (temperature condition is
8. Max. Current
E 2 4. 2 Connection unit number error (Indoor unit) max. cooling condition [refer to item 16])
Function setting
E 2 6. 1 Indoor unit duplicate address error
error 9. Air circulation Air circulation
E 2 8. 1 Auto address setting error
E 2 8. 4 Signal amplifier auto address error 10. Noise level Noise level
Indoor unit 11. Refrigerant Refrigerant type and initial charging amount
E 5 U. 1 Indoor unit miscellaneous error
actuator error
Means pressure of High Pressure side/Low Pres-
E 6 1. 5 Outdoor unit reverse/missing phase & wiring error 12. Max. pressure (HP/LP)
sure side
E 6 2. 3 Outdoor unit EEPROM access error
E 6 2. 6 Outdoor unit inverters communication error 13. Protection Protection level against dust and water
E 6 2. 8 Outdoor unit EEPROM data corruption error 14. Working temperature Working temperature
Outdoor unit
E 6 3. 1 Outdoor unit inverter error
PCB/Electrical Dry-bulb temperature and wet-bulb temperature
Outdoor unit inverter PCB power short interruption 15. Condition of cooling/heating
component/ E 6 7. 2 under standard cooling/heating condition
error
Switch error
Outdoor unit rush current limiting resister temp. rise Dry-bulb temperature and wet-bulb temperature at
E 6 8. 2 16. Condition of max. cooling
error (protective operation) maximum electric current and input
Outdoor unit transmission PCB parallel communica- 17. Manufacture year Manufacture year
E 6 9. 1
tion error
18. Origin Origin country
E 7 1. 1 Outdoor unit discharge temp. thermistor 1 error
E 7 2. 1 Outdoor unit compressor temp. thermistor 1 error Manufacturer
E 7 3. 3 Outdoor unit heat ex. liquid temp. thermistor error FUJITSU GENERAL LIMITED
19. Manufacturer
E 7 4. 1 Outside air temp. thermistor error Address: 3-3-17, Suenaga, Takatsu-ku, Kawasaki
E 7 5. 1 Outdoor unit suction gas temp. thermistor error 213-8502, Japan
E 7 7. 1 Outdoor unit heat sink temp. thermistor error
Outdoor unit sub-cool heat ex. gas inlet temp. therm-
E 8 2. 1
Outdoor unit istor error
sensor error Outdoor unit sub-cool heat ex. gas outlet temp.
E 8 2. 2
thermistor error
E 8 3. 2 Outdoor unit liquid pipe temp. thermistor 2 error
Outdoor unit current sensor 1 error
E 8 4. 1
(permanent stop)
E 8 6. 1 Outdoor unit discharge pressure sensor error
E 8 6. 3 Outdoor unit suction pressure sensor error
E 8 6. 4 Outdoor unit high pressure switch 1 error
En-18