0% found this document useful (0 votes)
28 views172 pages

Rec 15

This document provides information on installation, operation and maintenance of recloser equipment. It contains details on safety, technical parameters, product description, functionality, handling, installation, commissioning, operation, maintenance and troubleshooting procedures.

Uploaded by

Marko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views172 pages

Rec 15

This document provides information on installation, operation and maintenance of recloser equipment. It contains details on safety, technical parameters, product description, functionality, handling, installation, commissioning, operation, maintenance and troubleshooting procedures.

Uploaded by

Marko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 172

The present Technical Manual contains information necessary for the installation, commissioning and

operation. It is absolutely necessary for the proper use of the recloser to read the Technical Manual carefully
before starting and to adhere to the instructions and the relevant regulations.

Safety first
• Installation, operation and maintenance shall only be carried out by trained and experienced personnel who
are familiar with the equipment and the electrical safety requirements.

• During installation, commissioning, operation and maintenance of the equipment the relevant legal
regulations (such as IEC/DIN/VDE), accident prevention regulations and the connecting conditions of the
electric utilities shall be followed.

• Take note that during operation of the recloser certain parts are subject to dangerous voltage. Mechanical
parts, also remote-controlled, can move quickly. Failure to comply may result in death, severe personal
injury or damage to equipment.

• Pay attention to the hazard statements located throughout this manual.

• The operating conditions of the recloser shall comply with the technical data specified in this manual.

• Personnel installing, operating and maintaining the equipment shall be familiar with this manual and its
contents.

For special configurations please contact Tavrida Electric representative.


Contents
1 Introduction ....................................................................................................................................................5
1.1 Applicability ..............................................................................................................................................6
1.2 Safety Instructions: ...................................................................................................................................6
1.3 Abbreviations............................................................................................................................................7
2 Technical Parameters ....................................................................................................................................9
3 Product Description.....................................................................................................................................14
3.1 Outdoor Switching Module .....................................................................................................................15

3.2 Control Cable .........................................................................................................................................17


3.3 Recloser Control.....................................................................................................................................17

4 Functionality .................................................................................................................................................27
4.1 Protection ...............................................................................................................................................28

4.2 Measurement .........................................................................................................................................50

4.3 Communication ......................................................................................................................................52

4.4 Remote Engineering...............................................................................................................................53


4.5 Indication ................................................................................................................................................54

5 Product Handling .........................................................................................................................................56


5.1 Transportation ........................................................................................................................................57
5.2 Storage Conditions .................................................................................................................................58
5.3 Inspection ...............................................................................................................................................58
5.4 Unpacking ..............................................................................................................................................58

5.5 Handling Requirements ..........................................................................................................................62

6 Installation ....................................................................................................................................................69
6.1 Required Equipment...............................................................................................................................70
6.2 Installation Procedure.............................................................................................................................70

6.3 Dismounting Procedure ..........................................................................................................................80


3
7 Commissioning ............................................................................................................................................81
7.1 No-load Tests .........................................................................................................................................82

7.2 On-load Tests .........................................................................................................................................83


8 Operation ......................................................................................................................................................84
8.1 Switching ................................................................................................................................................85

8.2 Logging ...................................................................................................................................................86

8.3 Measurements........................................................................................................................................88
8.4 Date and Time Settings ..........................................................................................................................88
8.5 Other RC5_4 Control Options ................................................................................................................88

8.6 Settings Configuration ............................................................................................................................95

9 Maintenance and Troubleshooting ..........................................................................................................100


9.1 Maintenance .........................................................................................................................................101
9.2 Troubleshooting....................................................................................................................................101

9.3 Components Replacement Procedure .................................................................................................109

10 Product Coding ..........................................................................................................................................115


10.1 Recloser Coding ...................................................................................................................................116
10.2 Recloser Components Coding .............................................................................................................119
11 Appendices .................................................................................................................................................122
Appendix 1. Type Tests ...............................................................................................................................123
Appendix 2. Spare Parts and Accessories ..................................................................................................125
Appendix 3. Outdoor Switching Module Drawings.......................................................................................126
Appendix 4. Recloser Control Drawings ......................................................................................................128
Appendix 5. Control Cable Drawings ...........................................................................................................129
Appendix 6. Package Drawings ...................................................................................................................130
Appendix 7. Mounting Kits Drawings ...........................................................................................................132
Appendix 8. Connectors Drawings ..............................................................................................................163
Appendix 9. Recloser Control Wiring Diagram ............................................................................................170
List of changes .............................................................................................................................................171

4
1 Introduction
1.1 Applicability
This Technical Manual applies to the following range of products manufactured by Tavrida Electric:
• Automatic Circuit Recloser – Rec15/25_Al1_5p
▪ Outdoor Switching Module – OSM15/25_Al_1
▪ Recloser Control – RC5_4
The model numbers are shown on the equipment nameplates. If your equipment does not correspond to these
numbers then this Technical Manual is not applicable.
Every care has been taken in the preparation of this manual. However, please note that not all the details or
variations in the equipment or process being described can be covered. Neither is it expected to address all
contingencies associated with the installation and operation of this equipment. For any further information
please contact your nearest Tavrida Electric representative.
Important! Due to continuous product improvement, specifications and design are subject to change
without notice.

1.2 Safety Instructions:


General hazard statements applicable to this equipment are described in this section. Statements related to
specific tasks or procedures are located throughout this manual.
DANGER! Contact with hazardous voltage can cause death or severe personal injury. Contact with switching
module or recloser control terminals should only be undertaken when equipment is isolated from applicable
sources of voltage.
WARNING! Follow all locally approved safety procedures when installing or operating this equipment.
Improper handling, installation, operation or maintenance can result in death, severe personal injury or damage
to equipment.
WARNING! Power distribution equipment must be properly selected and used only for the intended purpose.

6
1.3 Abbreviations
ABR Automatic Backfeed Restoration
AT Auxiliary Transformer
BAT Battery
BF Bolted Fault
BTM Bluetooth Module
CC Control Cable (Umbilical)
CCV Close condition verifier
CLP Cold Load Pickup
CPM Control Panel Module
CT Current Transformer
CU Current unbalance
D Delayed
EF Earth Fault protection element
EF1 Low set Earth Fault protection element for Delayed trips
EF2 Low set Earth Fault protection element for Instantaneous trips
EF3 High set Earth Fault protection element for Instantaneous trips
EFID Earth Fault Interruption Detection
EL Event Log
ETH Ethernet Module
HL Hot Line protection element
I Instantaneous
I/O Input/Output
IOI Input/Output Interface
IOM Input/Output Module
LCD Liquid Crystal Display
LP Load Profile
LS Loss of Supply protection element
ME Measurement element
ML Malfunction Log
MMI Man Machine Interface
MPM Main Processor Module
NAP Neutral Admittance Protection
NVS Neutral Voltage Shift
OC Overcurrent protection element
OC1 Low set Overcurrent protection element for Delayed trips
OC2 Low set Overcurrent protection element for Instantaneous trips
OC3 High set Overcurrent protection element for Instantaneous trips
OCID Overcurrent Interruption Detection
OCR Overcurrent protection element with reclosing
PCI Personal Computer Interface

7
PSFM Power Supply Filter Module
RC Recloser Control
RCM Recloser Control Module
RTC Real Time Clock
RTU Remote Telecommunication Unit
SA Surge Arrester
SCADA Supervisory Control And Data Acquisition
SD Source Detector
SECR Sectionalizer Reclosing
SEF Sensitive Earth Fault
SEFID Sensitive Earth Fault Interruption Detection
SEFR Sensitive Earth Fault with reclosing
SI Synchronization indicator
TCI Telecommunication Interface
TDI TELARM Dispatcher Interface
TEL Tavrida Electric
UF Under Frequency
UV Under Voltage
VRC Voltage Reclosing Control
VT Voltage Transformer
VU Voltage Unbalance
ZSC Zone Sequence Coordination

8
2 Technical Parameters
Main technical data and recloser technical parameters are presented in tables below.

Table 1 – Recloser technical parameters


Parameter OSM15_Al_1 OSM25_Al_1
Rated data
Rated maximum voltage (Ur) 15.5 kV 27 kV
Rated short-duration powerfrequency withstand voltage (Ud), 1 min dry 50 kV 60 kV
Rated short-duration powerfrequency withstand voltage, 10s wet 45 kV 50 kV
Rated lightning impulse withstand voltage (peak) (Up) 110 kV 1251 / 1502 kV
Rated continuous current (Ir) 630 A 630 A
Rated cable-charging current switching 10 A 25 A
Rated line-charging current switching 2A 5A
Rated short-circuit breaking current (Isc) 16 kA 12.5 kA
Rated peak withstand current (Ip) 41.6 kA 32.5 kA
Rated short-time withstand current (Ik) 16 kA 12.5 kA
Rated duration of short circuit (tk) 4s 4s
Rated frequency (fr) 50/60 Hz 50/60 Hz
Switching performance
Mechanical life (CO-cycles) 30 000 30 000
Operating cycles, rated current (CO-cycles) 30 000 30 000
Electrical endurance, breaking current (O-CO cycles) See Figure 1 See Figure 1
Closing time, not more than 77 ms 77 ms
Opening time for overcurrent protection according to IEC 62271-111/C37.60, not 43 ms 43 ms
more than (at I>2xIp)
Clearing time for overcurrent protection according to IEC 62271-111/C37.60, not 51 ms 51 ms
more than (at I>2xIp)
Rated operating sequence O-0.1s-CO-2s-CO-2s-CO O-0.1s-CO-2s-CO-2s-CO
General information
Main circuit resistance < 85 μOhm < 95 μOhm
Weight 68 kg 72 kg
2000 m (derating according 2000 m (derating
Altitude to ANSI C37.60 applied according to ANSI C37.60
above 1000 m) applied above 1000 m)
Humidity 100%, condensing 100%, condensing
Solar Radiation ≤ 1.1 kW/m² ≤ 1.1 kW/m²
Temperature Range -40 °C ... +55 °C -40 °C ... +55 °C
Monostable magnetic Monostable magnetic
Type of driving mechanism
actuator actuator
Very heavy (as per IEC Very heavy (as per IEC
Pollution level
60815) 60815)

1 Across vacuum gap


2 Closed contacts

10
Figure 1
Vacuum interrupter switching life cycle

Table 2 – Sensors parameters


Parameter Phase current sensors Zero-sequence current sensor Voltage sensors
Range where accuracy is provided 1 … 8000 A 3
1 … 8000 A 3
0.3 … 27 kV
Range of sensor coefficients at 20°C 1.8 … 2.2 V/kA 1.8 … 2.2 V/kA 0.1 … 0.2 V/kV

Table 3 – Measurement accuracy4


Parameter Basic error Range where accuracy is guaranteed
Phase currents The greater of ±1% or ±2A 0 ... 630 A
Residual current5 The greater of ±5% or ±0.5A 0 ... 400 A
Phase to earth voltages The greater of ±1% or ±0.1 kV 0.3 ... 16.0 kV
Line to line voltages The greater of ±1% or ±0.1 kV 0.5 ... 27.0 kV
Frequency
- at dF/dt<0.2 Hz/s ±0.025 Hz 45 ... 55 Hz, 55 ...65 Hz
- at dF/dt<0.5 Hz/s ±0.05 Hz
Power factor ±0.02 0 ... 1
Active and reactive energy ±2% 40 … 630A, 4.5 ... 27 kV
Active, reactive and total power ±2% 40 … 630A, 4.5 ... 27 kV

Table 4 – Electromagnetic compatibility


Parameter Rated value Applicable standard
Rated power frequency voltage (1 min) 2 kV IEC 60255-5
Rated impulse voltage, at 0.5J 5 kV IEC 60255-5
Electrical fast transient/burst immunity 4 kV IEC 60255-22-4 (Level IV)
Surge immunity (applied to external AC voltage terminals)
- common 4 kV IEC 61000-4-5 (Level IV)
- transverse 2 kV
Control elements surge withstand capability (SWC) 125 kV (6 kA) IEEE C37.60-2012

3
The Rogowski coil can measure current in a wide range but for the purpose of over-voltage, protection suppressors are fitted in the secondary circuits. These
suppressors chop the signal from the Rogowski coil if primary current exceeds 8 kA.
4
If RC5_4 sensor coefficient settings are configured in accordance with guidelines in Table 6 of this guide. Error is measured at normal climatic conditions.
5
Note that overcurrent protection pickup setting value shall not exceed SEF pickup setting value times 300.

11
Table 5 – Power supply characteristics
Parameter Value
85 … 265 V AC
Supply voltage range
110 … 220 V DC6
Rated power consumption, not more 40 VA
Maximum power consumption, not more 75 VA
Duration of operation without auxiliary supply 48 hours

Table 6 – Degree of protection


Component Degree of protection
Outdoor switching module IP65
Recloser control IP65
Control cable IP65

Table 7 – Rechargeable Battery (BAT) parameters


Parameter Value
G26EPX EnerSys 0765-2003 sealed
Type7 HAZE HZB12-26 sealed lead acid
lead acid
Rated voltage 12 V 12 V
Rated capacity 26 Ah 26 Ah
Temperature range -40 °C ... +55 °C -25 °C ... +50 °C
25 % at -40 °C 50 % at -25 °C
65 % at -20 °C 65 % at -15 °C
Relative capacity at different temperatures 84 % at 0 °C 85 % at 0 °C
100 % at +25 °C 100 % at +20 °C
110 % at +40 °C 102 % at +40 °C
120 % at +55 °C
16 years at +20 °C 12 years at +20 °C
10 years at +25 °C 9 years at +30 °C
Expected battery life at average operating temperature
6.5 years at +30 °C 4 years at +40 °C
2.7 years at +40 °C 0.8 years at +50 °C

Table 8 – Input/Output module (IOM) parameters

Parameter Value
Digital inputs
Rated voltages of signal applied to digital inputs
- for IOM-04 12/24/30/48/60 V DC
- for IOM-03 110/125/220 V DC
Pickup voltage of signal applied to digital inputs
- for IOM-04 Above 7 V
- for IOM-03 Above 100 V
Reset voltage
- for IOM-04 Below 3 V
- for IOM-03 Below 30 V
Maximum continuous voltage of signal applied to digital inputs
- for IOM-04 75 V
- for IOM-03 275 V
Input resistance
- for IOM-04 3 kOhm
- for IOM-03 125 kOhm
Recognition time, not more 20 ms
Reset time, not more 20 ms
Digital outputs
Rated voltage 250 V AC
Rated current 16 A
Breaking capacity DC1 (at L/R=1ms): 30/110/220 V 16/0.3/0.12 A
Minimum switching load 500 mW (10V/5mA)

6
Note that additional DC circuit breakers are required.
7
Other types of batteries with identical parameters can be used in RC5_4 upon agreement with client.

12
Table 9 – Wired Ethernet module (ETH) parameters

Parameter Value
USB 1.2 (according to RC5 specification)
IEEE 802.3 10Base-T
Applicable standard
IEEE 802.3u 100Base-T
IEEE 802.3x Flow Control
Interface RJ-45 10/100 Ethernet port
Maximum receive / transmit speed Up to 70 Mbps (full duplex mode)
Dimensions 60.2 x 50 x 37.6 mm
Net weight, not more 25 g
Power consumption 1.0 W (max)
Operation temperature -40…+85 °C

Table 10 – Optical Ethernet module (ETH) parameters


Parameter Value
USB 1.2 (according to RC5 specification)
IEE802.3u 100Base-FX
Applicable standard
IEC 9314-3: 1990
ANSI X3.166-1990
Interface ST
Maximum receive / transmit speed 100–125 Mbps (full duplex mode)
Dimensions 132 x 71 x 39 mm
Net weight, not more 115 g
Power consumption 1.0 W (max)
Operation temperature -40…+85 °C

Table 11 – Bluetooth module (BTM) parameters

Parameter Value
Bluetooth version 2.0
Frequency 2402 … 2485 MHz
Channel intervals 1 MHz
Operation range 10 m
Operation mode Slave
Profile Serial port
Tx Power +6 dBm
Rx Sensitivity -84 dBm
Power consumption 0.3 W
Operation temperature -40…+85 °C

Table 12 – Wi-Fi module (WFM) parameters


Parameter Value
Applicable standard FCC/CE/TELEC/SRRC
802.11b, 802.11g, 802.11n, 802.11e, 802.11i
Protocol TCP/IP
DHCP
802.11b: +20 dBm
Tx Power 802.11g: +17 dBm
802.11n: +14 dBm
802.11b: -91 dBm (11 Mbit/s)
Rx Sensitivity 802.11g: -75 dBm (54 Mbit/s)
802.11n: -72 dBm (MCS7)
Security WPA/WPA2
Cipher Type WEP/TKIP/AES
Power consumption (Pout = +17 dBm) 1.0 W
Operation range 50 m
Operation temperature -40…+85 °C

13
3 Product Description
3.1 Outdoor Switching Module
The OSM15/25_Al_1 is a three-phase vacuum circuit breaker designed for outdoor application with the rated
maximum voltage of 15.5 kV and 27 kV correspondingly.
The circuit breaker is installed inside of a lightweight aluminum enclosure with a superior corrosion protection
and very heavy pollution areas application rating. The enclosure of the Outdoor Switching Module
encapsulates a magnetic actuator, mechanical trip and lockout mechanism and auxiliary electric circuits that
contain passive electronic components only.
The switching module is equipped with six high voltage bushings with embedded current and voltage sensors.
The bushings are covered by silicone rubber insulation and mount on the top of the tank and provide 500 mm
(OSM15) or 860 mm (OSM25) creepage distance.
The bushings are marked with the terminal designation X1, X2 or X3 for the default source side and X4, X5 or
X6 for the default load side. The source and load side can be reversed in the RC settings if required.

Figure 2
General arrangement of the OSM15/25_Al_1

1 Upper terminal
2 Vacuum interrupter
3 Lower terminal
4 Movable contact with bellows
5 Flexible junction shunt
6 Drive insulator
7 Opening and contact pressure spring
8 Magnetic actuator (complete module)
9 Armature
10 Synchronizing shaft
11 Actuator coil
12 Interlocking pins
13 Auxiliary contacts
14 Frame
15 Support insulator

Figure 3
Internal arrangement of the OSM15/25_Al_1 vacuum circuit breaker

Mechanism Enclosure
The switching module mechanism enclosure is made of a corrosion resistant anodized aluminum alloy. The
enclosure is coated with light gray powder coating.

15
Fixing holes (M12) on each side of the enclosure allow the application of various mounting kits and installation
on poles and other structures.
The earthing provision (M12) is labelled for identification.

Magnetic Actuator
Tavrida Electric has the most reliable mechanical structure of the vacuum circuit breaker. It uses single-coil
magnetic actuators. All switching elements of a pole are assembled along a single axis. All mechanical
movements are therefore direct and linear. Design of the magnetic actuator guarantee minimum contacts
discrepancy at closing and electrical or mechanical tripping.
Due to the design, any typical failures of critical components, such as mechanical latching, gears, chains,
bearings and levers, tripping and closing coils, motors to charge springs are completely avoided.

Vacuum Interrupter
Tavrida Electric vacuum interrupters are the most compact in its class and show excellent mechanical, voltage
withstand and current breaking capabilities. The use of a specially designed axial magnetic field distribution
provides even current density over the contact surface and consequently substantial improvement of vacuum
interrupting performance. Advanced technology and materials provide vacuum integrity in vacuum interrupter
during the entire switching module lifetime (30 years).

Current and Voltage Sensing


Current sensing is performed by low power current sensors (Rogowski coils) that are inbuilt into each pole. It
ensures a precise acquisition of both phase and neutral currents at a very wide range without saturation.
Six precise low power capacitive voltage sensors on source and load side terminals are inbuilt into poles. It
allows the recloser to provide power quality monitoring and network self-healing algorithms implementation.
For details on sensor parameters refer to “Technical Parameters” section of this guide.

Mechanical Trip and Lockout Mechanism


A mechanical trip hook is located at the bottom of the mechanism enclosure (Figure 3). When the hook is
pulled down, the Outdoor Switching Module is mechanically opened, locked in the OPEN position and
electrically isolated from the driver. The “Coil Isolated” warning event is generated by the RC5_4 to provide
indication of the locked state. The Outdoor Switching Module remains locked and cannot be operated until the
trip hook is pushed back into the operating position.

Figure 4
Mechanical trip hook

Main Contact Position Indicator


The position indicators are located under a protective cover at the bottom of the mechanism enclosure and is
clearly visible from the ground. The indicator color is red “I” when the main contacts are closed and green “O”
when they are open.

16
Figure 5
Main contact position indicator

3.2 Control Cable


Umbilical_5 control cable connects the Outdoor Switching Module actuator, metering and auxiliary circuits to
the RC5_4. Control cable wires are well protected from UV radiation and sharp objects. The cable is equipped
with a heavy duty 42 pin male connector on the Outdoor Switching Module side and a heavy duty 32 pin female
connector on the Recloser Control side.
Control cable length can be 5, 7, 12 or 20 meters.

Figure 6 Figure 7
Control cable Heavy duty connector

3.3 Recloser Control


The RC5_4 is a new generation control box that is the result of more than 20 years of recloser production and
service experience.
The RC5_4 recloser control cubicle is made from powder coated anodized aluminum alloy.
The RC5_4 has 4 drainage filters installed in the bottom, one per corner. It allows effective Recloser Control
dehumidification without using any heaters. Advanced drainage filters design ensure IP65 for Recloser Control.
Removable customization plate 180x70 mm is placed at the bottom of Recloser Control. It is possible to modify
customization plate and install additional modules or cable glands in case required.

17
1 Three-point locking system
2 Rubber seal
3 Fixing rod
4 2 x IP65 glands for Power supply cable
( 9…17 mm)
5 Anti-vandal cover for Control Cable
6 External door
7 Control panel module
8 Internal door
9 Thermal overcurrent circuit breakers
10 Dust proof drainage filter
11 Earthing stud
12 Mounting brackets
13 Bottom interface plate
14 Battery circuit breaker
15 Door position switch

Figure 8
RC5_4 with internal door closed

16 Door position switch


17 Remote telecommunication unit
(RTU) mounting plate
18 Place for Input/Output module (IOM)
19 Recloser Control Module (RCM)
20 Battery
21 Power Supply Filter Module (PSFM)

Figure 9
RC5_4 with internal door open

The external door has a padlock provision that is suitable for a shackle with up to a 12 mm diameter. The
external and internal doors can be securely fixed in the open position.
The anti-vandal cover is fixed from inside the housing with one captive screw placed at the bottom of Recloser
Control. It protects the Umbilical cable from unauthorized disconnection.

18
1 Control cable terminal
2 Anti-vandal cover
3 Locking holes
4 Captive screw

Figure 10
Anti-vandal cover installation

The RC5_4 is equipped with stainless steel earthing provision with M12x30 mm bolt. All internal components
and parts are earthed to the main Recloser Control with 2.5 mm2 cooper earthing jumpers.

1 Dust proof drainage filters


2 Cable glands for auxiliary
power supply connection
3 Control cable entrance
4 Earthing provision
5 Bottom interface plate
6 M12x30 stainless steel
bolt
7 Stainless steel spring
washer
8 2 pcs. Stainless steel
washers

Figure 11
Recloser Control bottom view

The RC5_4 is equipped with a Door Position Switch which is used for disabling the CPM when the Recloser
Control door is closed, as well as providing a SCADA indication of Recloser Control door position.
The door position switch is mounted on the inside of the door and is actuated by the lever mounted opposite
to the switch on the inside of the door.

Figure 12
Door position switch

19
RC5_4 control cubicle has the following standard and optional internal components:

Table 13– Standard and optional components of RC5_4


Module or Component Standard Optional
CPM •
RCM •
PSFM •
BAT •
IOM •
ETH •
WFM •
BTM •
LED •

Control Panel Module (CPM)


The CPM provides local control and indication functions to the RC5_4.
The CPM has an integrated USB interface for PC connection.

Figure 13
CPM front (left) and back (right) views

Recloser Control Module (RCM)


The RCM is the recloser control module. The RCM provides protection, communication, measurement, power
quality monitoring, automation and control functions.

20
Figure 14 Figure 15
RCM connections with other Recloser Control modules RCM without connections

Power Supply Filter Module (PSFM)


This module provides impulse noise protection for all internal modules of the RC5_4.

Figure 16
Power Supply Filter Module

The PSFM is connected to the RCM via a WAGO plug (Figure 16).

Rechargeable Battery (BAT)


The rechargeable battery provides the RC5_4 with auxiliary power when the main auxiliary power is not
present.
The power supply system is designed to provide optimum battery charging and to optimize battery lifetime.
Technical parameters of Rechargeable Battery are in Table 7.

21
Input/Output Module (IOM)
The RC5_4 can be supplied with an IOM (Figure 17) on request (refer to section „3. Product coding“ of this
guide). The IOM provides control and indication functions via digital inputs/outputs (for details on functionality
refer to section „6.3.4 Digital Input/Output Interface (IOI)“ of this guide).

Figure 17
Overall view of IO module

The IOM has twelve digital inputs and twelve digital outputs. The location of connectors (marked „15“…“18“)
with these inputs and outputs are shown in Figure 18.

Figure 18
Location of IOM connectors

Digital inputs are electrically isolated by means of opto-couplers (Figure 19).

Figure 19
Digital inputs

Bistable relays with changeover contacts are used for the digital outputs as illustrated in Figure 20.

22
Figure 20
Digital outputs

Technical parameters of Input/Output Module are in Table 8.

Ethernet (ETH)
Ethernet interface module can be supplied as an accessory.

Wired Ethernet module


Wired Ethernet module provides full remote (SCADA) and local communication and engineering functionality
via RJ45 port.

Figure 21
Wired Ethernet module installed on RCM

Technical parameters for Wired Ethernet interface are in Table 9.

Optical Ethernet module


Optical Ethernet module provides full remote (SCADA) and local communication and engineering functionality
via optical fiber ST interface.

23
Figure 22
Optical Ethernet module

Technical parameters for Optical Ethernet interface in Table 10.

Wi-Fi Module (WFM)


The RC5_4 can be supplied with a Wi-Fi module in request.
The Wi-Fi module provides full remote (SCADA) and local communication and engineering functionality over
wireless TCP/IP connection.
It is connected to the RCM via a USB cable (Figure 23).

Figure 23
Wireless module with its USB cable

Technical parameters of Bluetooth module are in Table 12.

Bluetooth Module (BTM)


The RC5_4 can be supplied with a Bluetooth module on request.
The Bluetooth module provides point-to-point wireless connection between the Recloser Control and a
personal computer.
It is connected to the RCM via a USB cable (Figure 23).
Technical parameters of Bluetooth module are in Table 11.

24
LED Lightning Strip
The RC5_4 can be supplied with a cabinet light (LED strip) that is activated when external door is opened.

Figure 24
LED strip

Anti-vandal Housing
The RC5_4 can also be supplied with an additional reinforced Anti-vandal housing to prevent stealing and
cabinet destruction. The locked Anti-vandal housing cannot be opened with an ordinary tool (screwdriver,
wrench, etc.); and cannot be broken with a crowbar. The Anti-vandal housing has all necessary provisions for
ventilation, cabling and earthing.

25
Figure 25
Anti-vandal housing

26
4 Functionality
4.1 Protection
Overview
The protection functionality is designed for the following key applications:
• Radial line recloser;
• Ring line recloser:
▪ Normally closed,
▪ Normally open,
▪ The point of independent power producers’ connection to the grid;
• Rezip recloser – provides protection and reconfiguration in radial, ring and meshed networks where
conventional protection grading is impossible;
• Standard sectionalizer – provides automatic segregation of the faulty section basing on number of upstream
recloser operations;
• Rezip sectionalizer – allows overcoming the limit of the number of sectionalizers in series and minimize
upstream recloser operations to segregate the faulty section.
Protection device mode (Recloser or Sectionalizer) can be independently selected for each of four protection
group.
A complete list of protection elements is presented in the Table 14.

Table 14 – List of protection elements


Protection element Short name ANSI code
Bolted Fault BF
Phase Overcurrent OC 51/50/67
Earth Fault EF 51N/50N/67N
Phase and Earth Overcurrent Reclosing AR OC 79
Sensitive Earth Fault SEF 51Ns/67Ns
Sensitive Earth Fault Reclosing AR SEF 79
Neutral Admittance Protection NAP 21YN
Neutral Admittance Protection Reclosing AR NAP 79
Neutral Voltage Shift NVS 59N
Voltage Unbalance VU 47
Current Unbalance CU 46
Undervoltage UV 27
Undervoltage Reclosing AR UV 79
Overvoltage OV 59
Overvoltage Reclosing AR OV 79
Underfrequency UF 81U
Underfrequency Reclosing AR UF 79
Overfrequency OF 81O
Overfrequency Reclosing AR OF 79
Voltage Reclosing Control VRC
Autoreclosing Timeout ART
Cold Load Pickup CLP
Source Detector SD 32
Automatic Backfeed Restoration ABR
Close Condition Verifier CCV
Synchronization Indicator SI 25
Hot Line HL
Fault Locator FL 21FL
Loss of Supply LS
Loss of Supply Autoreclosing AR LS
Sectionalizing SEC
Overcurrent Interruption Detection OCID
Earth Fault Interruption Detection EFID
Sensitive Earth Fault Interruption Detection SEFID

28
Radial line recloser
The Radial line recloser provides protection against the following faults:
• Short circuit. Phase-to-phase and three-phase short circuits;
• Earth fault. Single-phase and double-phase earth faults;
• Bolted fault. Very low impedance fault, typically caused by human factor or accident;
• Low current earth fault caused by a high impedance phase to ground short circuit;
• Upstream broken conductor. Conductor touching ground at the source side;
• Downstream broken conductor. Conductor touching ground at the load side;
• Low system voltage caused by an incorrect network operation mode, tap changer malfunction, under-
generation, or islanding. This protection prevents sensitive loads, such as motors, from overload and
failure;
• Low system frequency caused by local under-generation, islanding or generation system malfunctions;
• High system voltage caused by tap changer malfunction, over-generation or islanding. This protection
prevents sensitive loads from damage;
• High system frequency caused by islanding.
Protection elements against short circuit, high impedance earth fault, low system voltage, and low system
frequency faults are provided with independent reclosing elements.
Reclosing elements are controlled by the Voltage Reclosing Control (VRC). The VRC blocks autoreclosing if
power quality fails to meet customer requirements.

Ring line recloser


The Ring line recloser is provided with a unique source detector with the source threshold voltage setting. This
source detector continuously detects the direction of power flow through the recloser main contacts. The
source threshold voltage setting provides possibility to define the live line voltage level according to
particularities of the network configuration.
The Ring line recloser provides protection and automation as the radial line recloser. In addition the Ring line
recloser has directional elements to determine power flow direction (direct/reverse). The Ring line recloser has
independently configurable sets of settings for direct and reverse power flow.
In addition Ring line recloser provides the following functionalities involved in loop automation, self-healing
schemes and independent power producers’ connection to the grid:
• Loss of Supply – provides recloser tripping if it detects source lost.
• Automatic Backfeed Restoration – provides automatically closing a normally open recloser if it detects a
source on the either side of the recloser and absence of a source on the other side
• Live Load Blocking – monitors power supply from the load and source side and only allows closing if a
source is present at the correct side;
• Synchronization Check – provides closing command execution only if voltage parameters from both sides
are within predefined ranges.

Rezip recloser
The Rezip recloser is used to automate various networks where traditional time and current grading is
impossible. Unlike a conventional recloser, the Rezip recloser can be used in ring and meshed networks and
self-healing schemes. Any number of Rezip reclosers can be connected in series.

Standard sectionalizer
Standard sectionalizer provides automatic segregation of the faulty segment of the radial or ring feeder basing
on number of upstream recloser operations.
Standard sectionalizer provides detection and subsequent trip during the dead time of upstream recloser
• Short circuit. Phase-to-phase and three-phase short circuits;
• Earth fault. Single-phase and double-phase earth faults;
• Low current Earth fault caused by a high impedance phase to ground short circuit.

29
Rezip sectionalizer
The Rezip sectionalizer provides detection and subsequent trip during dead time of upstream recloser as the
Standard sectionalizer.
In addition Rezip sectionalizer automatically finds and segregates the faulty segment of radial, ring or meshed
feeder by opening all devices which have sensed fault current and then close them one by one till the faulty
segment is found. When faulty segment is found, only the nearest device to the fault will open to lockout.
Rezip sectionalizer can be used with other automation features to provide sophisticated network healing
algorithms.
The Rezip sectionalizer allows to:
• Overcome the limit of the number of sectionalizers in series;
• Minimize protection settings design resources (same protection settings for all Rezip sectionalizers for the
most applications can be programmed);
• Minimize the number of upstream recloser operations and power interruptions for healthy network sections.

Protection Elements
OCR mode
OCR mode defines whether device operates as Recloser with OCR element or as a Sectionalizer with SECR
element.
OCR mode can be independently selected for each protection group.
OCR mode settings are described in Table 15.
Table 15 – OCR mode settings
Settings Range Default
OCR mode Recloser/Sectionalizer Recloser

Source Detector (SD)


The source detector element has two main functions:
• Provides power flow direction to directional protection elements (ring operation mode);
• Provides source side information for loss of supply protection element.
Protection elements: AR OC, HL, AR SEF, VU, CU, AR UV, AR UF, AR OV, AR OF, CCV and ABR operation
depends on the source side being identified. If power flows from „Source +“ side, then „Set +“ protection
settings are active, if power flows from „Source -“ side, then „Set -“ protection settings are active.
Source detector has a changeable voltage detection level. In case power source voltage is less than specified,
it will not consider as a source.
Table 16 – Source Detector element settings
Settings Designation Range Resolution Default
Operating mode Mode Enable/Disable n.a. Disable
Source threshold voltage, kV Ust8 0.5–27.0 0.1 0.5

Bolted Fault (BF)


This element provides instantaneous tripping when bolted fault conditions are detected. As it deals both with
positive sequence voltage and current it provides better sensitivity for bolted faults than conventional highset
overcurrent elements.

Phase Overcurrent (OC)


This element is available for OCR mode “Recloser” only.
This element provides protection against overloads, phase-to-phase and three-phase short circuits.

8
The value of Ust setting cannot exceed the value of Rated voltage configuration setting.

30
OC protection consists of six (6) individual overcurrent elements providing three stages of protection for both
the Forward (Source+) and Reverse (Source-) power flow directions: OC1+, OC1-, OC2+, OC2-, OC3+, OC3-
.

OC1
Phase overcurrent low set element OC1 is designated to provide time delayed trips. It is enabled in any
selected sequence in the Overcurrent Reclosing element. „I“ (Instantaneous) stands for accelerated and „D“
(Delayed) for delayed step of overcurrent protection in an autoreclosing sequence.

OC2
Phase overcurrent low set element OC2 is designated to provide accelerated trips. If a sequence step in the
Overcurrent Reclosing Element is set „D“ OC2 element is disabled. If a sequence step in the Overcurrent
Reclosing element is set „I“ OC2 element is enabled.

OC3
Phase fault high set instantaneous element provides protection against phase high current faults with a
reduced number of trips to lockout. If there is no intention to reduce the number of trips to lockout at high
current faults, enabling this element is not recommended. OC1 and OC2 allow reduction of tripping time to any
desired value at high currents.
For details on available TCC refer to Table 20 of this guide.
OC3 element settings are described in Table 21.

Earth Fault (EF)


This element is available for OCR mode “Recloser” only.
This element provides protection against single phase and double phase earth faults.
EF protection consist of six (6) individual overcurrent protection elements providing three stages of protection
for both the Direct (Source+) and Reverse power flow (Source-) directions: EF1+, EF1-, EF2+, EF2-, EF3+,
EF3-.

EF1
Earth fault low set element EF1 is designated to provide time delayed trips. It is enabled in any selected
sequence in the Overcurrent Reclosing element. „I“ (Instantaneous) stands for accelerated and „D“ (Delayed)
for delayed step of overcurrent protection in an autoreclosing sequence.

EF2
Earth fault low set element EF2 is designated to provide accelerated trips. If a sequence step in the Overcurrent
Reclosing Element is set „D“ EF2 element is disabled. If the sequence step in the Overcurrent Reclosing
element is set „I“ EF2 element is enabled.

EF3
Earth fault high set instantaneous element provides protection against high earth current faults with a reduced
number of trips to lockout. If there is no intention to reduce the number of trips to lockout at high current faults,
enabling this element is not recommended. EF1 and EF2 allow reduction of tripping time to any desired value
at high currents.
For details on available TCC refer to Table 17 of this guide.
EF3 element settings are described in Table 18.
Table 17 – TCC types
Settings Designation Range Default
ANSI: Extremely Inverse (EI), Moderately Inverse (MI), Very Inverse (VI)
IEC: Extremely Inverse (EI), Very Inverse (VI), Inverse (I)
Type of time current
TCC Definite Time (TD) TD
characteristic
Custom: custom curves are available on request. Contact Tavrida
Electric representative.

31
Table 18 – High Set elements settings
Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Disable
Pickup current, A Ip 40–12500 1 40
Tripping time, s Tt 0.00–2.00 0.01 0.00
Hot Line blocking mode HLBM Enable/Disable n.a. Enable

TCC can be uploaded to the RC5_4 via TELARM configuration software.


Phase overcurrent and earth fault TD, IEC and ANSI time current curves settings are described in Tables 24–29.

Table 19 – OC/EF TD TCC settings


Settings Designation Range Step size Default
Tripping time, s Tt 0.00–100.00 0.01 10.00
Pickup current, A Ip 39–6000 1 100
Hot Line blocking mode HLBM Enable/Disable n.a. Enable

Table 20– Available IEC TCC with parameters


TCC type Designation A n
Extremely Inverse IEC EI 80 2.0
Very Inverse IEC VI 13.5 1.0
Inverse IEC I 0.14 0.02

Table 21 – OC/EF IEC TCC settings


Settings Designation Range Step size Default
Asymptote current, A Ias 3–1280 1 100
Time multiplier Tm 0.01–15.00 0.01 1.00
Minimum time, s Tmin 0.05–100.00 0.01 0.05
Maximum time, s Tmax 0.05–100.00 0.01 10.00
Pickup current, A Ip 39–6000 1 100
Time adder, s Ta 0.00–2.00 0.01 0.00
Reset time, s Tres 0.00–20.00 0.01 0.00
Hot Line blocking mode HLBM Enable/Disable n.a. Enable

Table 22 – Available ANSI TCC with parameters


TCC type Designation A B D n
Extremely Inverse ANSI EI 28.2 1.217 29.1 2.0
Very Inverse ANSI VI 19.61 0.114 21.6 2.0
Moderately Inverse ANIS MI 0.0515 0.114 4.85 0.02

Table 23 – OC/EF ANSI TCC settings


Settings Designation Range Step size Default
Asymptote current, A Ias 3–1280 1 100
Time multiplier Tm 0.01–15.00 0.01 1.00
Minimum time, s Tmin 0.05–100.00 0.01 0.05
Maximum time, s Tmax 0.05–100.00 0.01 10.00
Pickup current, A Ip 510–6000 1 100
Time adder, s Ta 0.00–2.00 0.01 0.00
Hot Line blocking mode HLBM Enable/Disable n.a. Enable

9
10 A for OC protection.
10
10 A for OC protection.

32
Table 24– OC/EF custom TCC settings11
Settings Designation Range Step size Default
Number of sections n.a. 1/2/3 n.a. 3
Maximum time, s Tmax 0.05–100.00 0.01 10.00
First intermediate time, s T1 0.05–100.00 0.01 3.00
Second intermediate time, s T2 0.05–100.00 0.01 0.25
Minimum time, s Tmin 0.05–100.00 0.01 0.05
Pickup current, A Ip 3 –6000
10
1 100
First intermediate current, A I1 310–6000 1 500
Second intermediate current, A I2 310–6000 1 1000
Maximum current, A Imax 310–6000 1 3000
First section asymptote, A Ias1 1–6000 1 10
Second section asymptote, A Ias2 1–6000 1 10
Third section asymptote, A Ias3 1–6000 1 10
Hot Line blocking mode HLBM Enable/Disable n.a. Enable

Phase and Earth Overcurrent Reclosing (AR OC)


This element is available for OCR mode “Recloser” only.
The AR OC element provides reclosing initiated by tripping of one of OC1, OC2, OC3, EF1, EF2 or EF3
elements. The user set delay between trip and reclose is called „reclose time“ (Tr) and can be set
independently for each trip in the sequence. If the fault is not cleared during „reclose time“, the recloser will
trip again. This will repeat a number of times until the fault is cleared or the AR OC element reaches the end
of the user defined reclose sequence. At this point the recloser remains open and will no longer reclose
automatically. This is known as „lockout“ and the recloser can only be closed by local or remote operator
command, which clears the lockout condition.
AR OC settings are described in Table 25 and Table 26.

Table 25 – Radial line recloser AR OC element settings


Settings Designation Range Default
Operating mode Mode Normal/Rezip/ZSC ZSC
Mode = Normal/ZSC 1/2/3/4 4
Number of trips to lockout Nt
Mode = Rezip 2/3/4 2
Highset trips to lockout Nhs 1/2/3/4 1
For 4 trips to lockout:
IIII/IIID/IIDD/IDDD/DDDD/DDDI/DDII/
DIII/ IIDI/IDII/IDDI
For 3 trips to lockout:
Mode = Normal/ZSC III/IID/IDD/DDD/DDI/DII/IDI IIDD
For 2 trips to lockout:
Reclosing sequence Seq
II/ID/DD/DI
For 1 trip to lockout:
I/D
For 4 trips to lockout: DIII
Mode = Rezip n.a. For 3 trips to lockout: DII
For 2 trips to lockout: DI
Accelerate, Decelerate, Normal,
Mode = Normal/ZSC Normal
First closure mode SST mode Unconditional AR
Mode = Rezip n.a. Accelerate
Mode = Normal/ZSC 1-180 1
First closure time SST time
Mode = Rezip n.a. 0.1
Mode = Normal/ZSC 0.10–1800.00 1.00
First reclose time, s Tr1
Mode = Rezip 0.20–1800.00 0.20
Second reclose time, s Tr2 1.00–1800.00 10.00
Third reclose time, s Tr3 1.00–1800.00 30.00
Mode = Normal/ZSC 1-180 1
Reset time, s Tres
Mode = Rezip n.a. 0.10

Table 26 – Ring line recloser AR OC element settings


Settings Designation Range Default
Operating mode Mode Normal/Rezip/ZSC ZSC

11
Custom TCC could be configured via user software TELARM only.

33
Mode = Normal/ZSC 1/2/3/4 4
Number of trips to lockout+ Nt+
Mode = Rezip 2/3/4 2
Highset trips to lockout+ Nhs+ 1/2/3/4 1
For 4 trips to lockout:
IIII/IIID/IIDD/IDDD/DDDD/DDDI/DDII/
DIII/ IIDI/IDII/IDDI
For 3 trips to lockout:
Mode = Normal/ZSC III/IID/IDD/DDD/DDI/DII/IDI IIDD
For 2 trips to lockout:
Reclosing sequence+ Seq+ II/ID/DD/DI
For 1 trip to lockout:
I/D
For 4 trips to lockout: DIII
Mode = Rezip n.a. For 3 trips to lockout: DII
For 2 trips to lockout: DI
Accelerate, Decelerate, Normal,
Mode = Normal/ZSC Normal
First closure mode+ SST mode+ Unconditional AR
Mode = Rezip n.a. Accelerate
Mode = Normal/ZSC 1-180 1
First closure time+ SST time+
Mode = Rezip n.a. 0.1
Mode = Normal/ZSC 0.10–1800.00 1.00
First reclose time+, s Tr1+
Mode = Rezip 0.20–1800.00 0.20
Second reclose time+, s Tr2+ 1.00–1800.00 10.00
Third reclose time+, s Tr3+ 1.00–1800.00 30.00
Mode = Normal/ZSC 1-180 1
Reset time+, s Tres+
Mode = Rezip n.a. 0.10
Mode = Normal/ZSC 1/2/3/4 4
Number of trips to lockout- Nt-
Mode = Rezip 2/3/4 2
Highset trips to lockout- Nhs- 1/2/3/4 1
For 4 trips to lockout:
IIII/IIID/IIDD/IDDD/DDDD/DDDI/DDII/
DIII/ IIDI/IDII/IDDI
For 3 trips to lockout:
Mode = Normal/ZSC III/IID/IDD/DDD/DDI/DII/IDI IIDD
For 2 trips to lockout:
Reclosing sequence- Seq- II/ID/DD/DI
For 1 trip to lockout:
I/D
For 4 trips to lockout: DIII
Mode = Rezip n.a. For 3 trips to lockout: DII
For 2 trips to lockout: DI
Accelerate, Decelerate, Normal,
Mode = Normal/ZSC Normal
First closure mode- SST mode- Unconditional AR
Mode = Rezip n.a. Accelerate
Mode = Normal/ZSC 1-180 1
First closure time- SST time-
Mode = Rezip n.a. 0.1
Mode = Normal/ZSC 0.10–1800.00 1.00
First reclose time-, s Tr1-
Mode = Rezip 0.20–1800.00 0.20
Second reclose time-, s Tr2- 1.00–1800.00 10.00
Third reclose time-, s Tr3- 1.00–1800.00 30.00
Mode = Normal/ZSC 1-180 1
Reset time-, s Tres-
Mode = Rezip n.a. 0.10

Reset time
The Reset time setting in the autoreclosing element controls the time elapsed between the closing command
execution generated by the relay to the breaker and the time the auto-reclose function resets to the initial cycle.
This timer is used to withstand fault restrikes in case an intermittent fault has been detected.
The First closure time setting controls how quickly autoreclosing will be enabled after an operator (local or
remote) closing command is executed.

Reset time for autoreclosing sequence


The Reset timer for the autoreclosing sequence starts counting when the close command is initiated by the
AR OC protection element that has been executed and no fault current is detected after closing. If the

34
measured current does not exceed the pickup setting and the Reset timer stops counting, a current reclosing
cycle will be continued. In the case that, after closing, the measured current does not exceed the pickup setting
within the Reset time period, a new autoreclosing sequence will be enabled and will be executed for
consequent faults. The Reset time counter starts counting from zero for each automatic closing event in an
autoreclosing sequence.

First closure time (SST timer)


The Single shot to lockout algorithm is supported by the AR OC element. This function allows tripping and
lockout (preventing autoreclosing) if a fault has been detected by the operator during the First closure time.
The Single shot to lockout function will be disabled in case “Unconditional AR” is selected for First closure
mode. Recloser can make up to 4 closing operations including the first close initiated by operator.

Overcurrent Interruption Detection (OCID)


This element is available for OCR mode “Sectionalizer” only.
This element provides detection of the overload, phase-to-phase and three phase short circuit fault passage
and interruption due to operation of upstream device. OCID operates according to definite time TCC.
OCID settings are described in Table 27 and Table 28.

Table 27 – Radial line recloser OCID element settings


Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Enable
Detection time, s Td 0.00–100.00 0.01 0.1
Pickup current, A Ip 10–6000 1 100
Reset time, s Tres 0.00–100.00 0.01 0.1
Fault interruption reset time, s Tfir 0.10–100.00 0.01 1.00

Table 28 – Ring line recloser OCID element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Enable
Detection time+, s Td+ 0.00–100.00 0.01 0.1
Pickup current+, A Ip+ 10–6000 1 100
Reset time+, s Tres+ 0.00–100.00 0.01 0.1
Fault interruption reset time+, s Tfir+ 0.10–100.00 0.01 1.00
Operating mode- Mode- Enable/Disable n.a. Enable
Detection time-, s Td- 0.00–100.00 0.01 0.1
Pickup current-, A Ip- 10–6000 1 100
Reset time-, s Tres- 0.00–100.00 0.01 0.1
Fault interruption reset time-, s Tfir- 0.10–100.00 0.01 1.00

Earth Fault Interruption Detection (EFID)


This element is available for OCR mode “Sectionalizer” only.
This element provides detection of the earth fault current passage and interruption due to operation of
upstream device. EFID operates according to definite time TCC.
EFID settings are described in Table 29 and Table 30.

Table 29– Radial line recloser EFID element settings


Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Enable
Detection time, s Td 0.00–100.00 0.01 0.1
Pickup current, A Ip 5–6000 1 100
Reset time, s Tres 0.00–100.00 0.01 0.1
Fault interruption reset time, s Tfir 0.10–100.00 0.01 1.00

35
Table 30– Ring line recloser EFID element settings
Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Enable
Detection time+, s Td+ 0.00–100.00 0.01 0.1
Pickup current+, A Ip+ 5–6000 1 100
Reset time+, s Tres+ 0.00–100.00 0.01 0.1
Fault interruption reset time+, s Tfir+ 0.10–100.00 0.01 1.00
Operating mode- Mode- Enable/Disable n.a. Enable
Detection time-, s Td- 0.00–100.00 0.01 0.1
Pickup current-, A Ip- 5–6000 1 100
Reset time-, s Tres- 0.00–100.00 0.01 0.1
Fault interruption reset time-, s Tfir- 0.10–100.00 0.01 1.00

Sensitive Earth Fault Interruption Detection (SEFID)


This element is available for OCR mode “Sectionalizer” only.

This element provides earth fault interruption detection in the networks with insulated/compensated neutral. It
is also applicable in earthed neutral systems for high-impedance earth fault protection. Current based as well
as current and angle based detection option is provided with corresponding settings. SEFID operates
according to definite time TCC.

SEFID settings are described in Table 31 and Table 32.

Table 31– Radial line recloser SEFID element settings


Settings Designation Range Default
Operating mode Mode Enable/Disable Enable
Detection type Type Current/Current and angle Current
Pickup current, A Ip 0.5–80 4
Type = Current n.a. n.a.
Torque angle, deg At
Type = Current and angle 0–359 0
Detection time, s Td 0.15–100.00 1.00
Reset time, s Tres 0.15–100.00 0.15
Fault interruption reset time, s Tfir 0.10–100.00 1.00

Table 32 – Ring line recloser SEFID element settings


Settings Designation Range Default
Operating mode+ Mode+ Enable/Disable Enable
Detection type+ Type+ Current/Current and angle Current
Pickup current+, A Ip+ 0.5–80 4
Type = Current n.a. n.a.
Torque angle+, deg At+
Type = Current and angle 0–359 0
Detection time+, s Td+ 0.15–100.00 1.00
Reset time+, s Tres+ 0.15–100.00 0.15
Fault interruption reset time+, s Tfir+ 0.10–100.00 1.00
Operating mode- Mode- Enable/Disable Enable
Detection type- Type- Current/Current and angle Current
Pickup current-, A Ip- 0.5–80 4
Type = Current n.a. n.a.
Torque angle-, deg At-
Type = Current and angle 0–359 0
Detection time-, s Td- 0.15–100.00 1.00
Reset time-, s Tres- 0.15–100.00 0.15
Fault interruption reset time-, s Tfir- 0.10–100.00 1.00

Sectionalizing (SEC)
This element is available for OCR mode “Sectionalizer” only.

36
This element provides count of upstream recloser operations during the fault and after predefined number of
counts device will trip and lockout if mode is Standard/Rezip or reclose if mode is Rezip.
Standard (with up to 3 series sections in use) and Rezip (with unlimited devices number) modes are supported.
SEC settings are described in Table 33 and Table 34.

Table 33 – Radial line recloser SEC element settings


Settings Designation Range Default
Operating mode Mode Standard/Rezip/FPI12 Standard
Mode = Standard/Rezip 1/2/3/4 1
Number of fault detections to trip Nd
Mode = FPI n.a. n.a.
Mode = Standard/Rezip 1.00–180.00 10.00
Sequence reset time, s Tsr
Mode = FPI n.a. n.a.
Mode = Standard/Rezip 0.10–180.00 0.10
Reset time, s Tres
Mode = FPI n.a. n.a.
Mode = Standard/Rezip 0.00–100.00 0.00
Tripping time, s Tt
Mode = FPI n.a. n.a.
Mode = Rezip 0.20–1800.00 1.00
Reclose time, s Tr
Mode = Standard/FPI n.a. n.a.
Mode = Rezip 1–1800 10
Blocking time, s Tbl
Mode = Standard/FPI n.a. n.a.

Table 34 – Ring line recloser SEC element settings


Settings Designation Range Default
Operating mode Mode Standard/Rezip/FPI Standard
Mode = Rezip 1/2/3/4 1
Number of fault detections to trip Nd
Mode = Standard/FPI n.a. n.a.
Mode = Rezip 1.00–180.00 10.00
Sequence reset time, s Tsr
Mode = Standard/FPI n.a. n.a.
Mode = Rezip 0.10–180.00 0.10
Reset time, s Tres
Mode = Standard/FPI n.a. n.a.
Mode = Rezip 0.00–100.00 0.00
Tripping time, s Tt
Mode = Standard/FPI n.a. n.a.
Mode = Rezip 0.20–1800.00 1.00
Reclose time, s Tr
Mode = Standard/FPI n.a. n.a.
Mode = Rezip 1–1800 10
Blocking time, s Tbl
Mode = Standard/FPI n.a. n.a.
Mode = Standard 1/2/3/4 1
Number of fault detections to trip+ Nd+
Mode = Rezip/FPI n.a. n.a.
Mode = Standard 1.00–180.00 10.00
Sequence reset time+, s Tsr+
Mode = Rezip/FPI n.a. n.a.
Mode = Standard 0.10–180.00 0.10
Reset time+, s Tres+
Mode = Rezip/FPI n.a. n.a.
Mode = Standard 0.00–100.00 0.00
Tripping time+, s Tt+
Mode = Rezip/FPI n.a. n.a.
Mode = Standard 1/2/3/4 1
Number of fault detections to trip Nd
Mode = Rezip/FPI n.a. n.a.
Mode = Standard 1.00–180.00 10.00
Sequence reset time, s Tsr
Mode = Rezip/FPI n.a. n.a.
Mode = Standard 0.10–180.00 0.10
Reset time, s Tres
Mode = Rezip/FPI n.a. n.a.
Mode = Standard 0.00–100.00 0.00
Tripping time, s Tt
Mode = Rezip/FPI n.a. n.a.

12
Fault Passage Indicator

37
Flag Reset
This element is available for OCR mode “Sectionalizer” only.
This element is used by OCID, EFID and SEFID elements and common for all of them. Interruption detection
element is to remain in corresponding “Flag” state until user-defined time elapsed or manual reset via control
panel or communications.
Flag Reset settings are described in Table 35.

Table 35 – Flag Reset settings


Settings Designation Range Step size Default
Reset Flags by Trip - Enable/Disable n.a. Disable
Reset Flags by timer - Enable/Disable n.a. Disable
Flag reset time, s Tf 0.10–3600.00 0.01 0.10

Loss of Supply (LS)


This element trips recloser if the source is lost (no HV voltage is present).
LS settings are described in Table 36.
Table 36 – LS element settings
Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Disable
Tripping time, s Tt 0.10–100.00 0.01 10.00
Voltage Reclosing Control blocking
VRC blocking mode Enable/Disable n.a. Disable
mode

Loss of Supply Autoreclosing (AR LS)


The AR LS element provides reclosing initiated by the LS element tripping.
The delay between power supply restoration and reclose is called „reclose time“ (Tr). Tr time setting is
configured by the user. If loss of supply occurs again prior to reset time expiration, the recloser will trip again
and will not reclose automatically. This is known as „lockout“ and the recloser can only be closed by local or
remote operator command, which clears the lockout condition.
AR LS settings are described in Table 37.
Table 37– AR LS element settings
Settings Designation Range Default
Operating mode Mode Normal/Rezip Normal
Mode = Normal 1/2 1
Number of trips to lockout13 Nt
Mode = Rezip n.a. 2
Mode = Normal 0.10–180.00 10.00
Reclose time, s Tr
Mode = Rezip 0.20–180.00 0.20

REZIP
Rezip is the automation algorithm that enables complex distribution network automation. Rezip can be used
in networks where the recloser application is not possible due to protection coordination restrictions. The
algorithm is initiated by an upstream recloser trip. Once the loss of supply is detected, all Rezip reclosers will
trip during recloser dead-time. When the recloser closes, it restores supply to the closest Rezip recloser(s). It
activates the AR LS timer and after a preset time Rezip reclosers will close restoring the power supply to
downstream Rezip recloser(s). Immediately after closure Rezip the recloser(s) are operating in Instantaneous
protection mode and if any of them detects the fault, it will trip before the upstream protection device will. By
the time next Rezip recloser is closer by the AR LS, the upstream Rezip OC/EF protection is disabled, so no
grading between Rezip reclosers is needed.

13
In Rezip mode this setting has a fixed value and is unavailable (hidden).

38
The algorithm provides the set-up simplicity of a traditional sectionalizer and at the same time reducing the
fault clearing time and network reconfiguration time application in far more complex networks and provide an
unlimited number of sections to limit the number of customers affected.

Rezip is applicable in meshed grid automation schemes together with ABR functionality. Rezip enables the
building of self-healing networks where it is not possible with conventional reclosers and sectionalizers.

Zone Sequence Coordination


The AR OC provides Zone Sequence Coordination (ZSC). ZSC forces the AR OC element to step to the next
count in the reclose sequence on reset of all protection elements if it detects a downstream protection device
has operated. This functionality is required for applications where a fuse-saving philosophy is used.

Hot Line (HL)


This element consists of two sub-elements which provide protection against short circuit faults during Hot Line
maintenance. It generally has more sensitive settings than corresponding OCR settings and it has no reclosing
functions. HL consists of two Overcurrent elements, one for Phase Overcurrent (HLOC) and one for Earth
Fault (HLEF). Operation of either element results in the trip to lockout.
HL settings are described in Tables 43-46.
Table 38 – Radial line recloser HLOC element settings
Settings Designation Range Step size Default
Pickup current, A Ip 10-1280 1 10
Tripping time, s Tt 0.00–2.00 0.01 0.00

Table 39 – Ring line recloser HLOC element settings


Settings Designation Range Step size Default
Pickup current+, A Ip+ 10-1280 1 10
Tripping time+, s Tt+ 0.00–2.00 0.01 0.00
Pickup current-, A Ip- 10-1280 1 10
Tripping time-, s Tt- 0.00–2.00 0.01 0.00

Table 40 – Radial line recloser HLEF element settings


Settings Designation Range Step size Default
Pickup current, A Ip 4-1280 1 4
Tripping time, s Tt 0.00–2.00 0.01 0.00

Table 41 – Ring line recloser HLEF element settings


Settings Designation Range Step size Default
Pickup current+, A Ip+ 4-1280 1 4
Tripping time+, s Tt+ 0.00–2.00 0.01 0.00
Pickup current-, A Ip- 4-1280 1 4
Tripping time-, s Tt- 0.00–2.00 0.01 0.00

Sensitive Earth Fault (SEF)


This element provides protection against high impedance earth faults.
SEF settings are described in Table 42 and Table 43.
SEF TD and custom time current curves settings are described in Table 44 and Table 45.

Table 42 – Radial line recloser SEF element settings


Settings Designation Range Step size Default
Operating mode Mode Disable/Alarm/Trip Trip

39
Fault identification type Type Current/Current and angle Current
14
Type = Current TD/TEL I TD
Time current characteristic TCC
Type = Current and angle TD TD
Type = Current n.a. n.a.
Torque angle, deg At
Type = Current and angle 0–359 0

Table 43– Ring line recloser SEF element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Disable/Alarm/Trip Trip
Fault identification type+ Type+ Current/Current and angle Current
Type = Current TD/TEL I15 TD
Time current characteristic+ TCC+
Type = Current and angle TD TD
Type = Current n.a. n.a.
Torque angle+, deg At+
Type = Current and angle 0–359 0
Operating mode- Mode- Disable/Alarm/Trip Trip
Fault identification type- Type- Current/Current and angle Current
Type = Current TD/TEL I15 TD
Time current characteristic- TCC-
Type = Current and angle TD TD
Type = Current n.a. n.a.
Torque angle-, deg At-
Type = Current and angle 0–359 0

Table 44 – SEF TD TCC settings


Settings Designation Range Step size Default
Tripping time, s Tt 0.01–100.00 0.01 10.00
Pickup current, A Ip 0.5–80 1 4

Table 45– SEF TEL I TCC settings15


Settings Designation Range Step size Default
Number of sections n.a. 1/2/3 n.a. 3
Maximum time, s Tmax 0.10–100.00 0.01 10.00
First intermediate time, s T1 0.10–100.00 0.01 3.00
Second intermediate time, s T2 0.10–100.00 0.01 0.25
Minimum time, s Tmin 0.10–100.00 0.01 0.10
Pickup current, A Ip 0.5–80 1 4
First intermediate current, A I1 1–6000 1 500
Second intermediate current, A I2 1–6000 1 1000
Maximum current, A Imax 1–6000 1 3000
First section asymptote, A Ias1 1–80 1 4
Second section asymptote, A Ias2 1–6000 1 10
Third section asymptote, A Ias3 1–6000 1 10

Sensitive Earth Fault Reclosing (AR SEF)


This element provides reclosing initiated by the SEF element operation. It also supports single shot to lockout
functionality.
AR SEF settings are described in Table 46 and Table 47.

Table 46 – Radial line recloser AR SEF element settings


Settings Designation Range Step size Default
Number of trips to lockout Nt 1/2/3/4 n.a. 1
First reclose time, s Tr1 0.10–180.00 0.01 1.00
Second reclose time, s Tr2 1.00–180.00 0.01 10.00

14
Custom inverse type curve that is available on request. Contact Tavrida Electric representative.
15
Custom TCC could be configured via user software TELARM only.

40
Third reclose time, s Tr3 1.00–180.00 0.01 30.00
Reset time, s Tres 1–180 1 1

Table 47 – Ring line recloser AR SEF element settings


Settings Designation Range Step size Default
Number of trips to lockout+ Nt+ 1/2/3/4 n.a. 1
First reclose time+, s Tr1+ 0.10–180.00 0.01 1.00
Second reclose time+, s Tr2+ 1.00–180.00 0.01 10.00
Third reclose time+, s Tr3+ 1.00–180.00 0.01 30.00
Reset time+, s Tres+ 1–180 1 1
Number of trips to lockout- Nt- 1/2/3/4 n.a. 1
First reclose time-, s Tr1- 0.10–180.00 0.01 1.00
Second reclose time-, s Tr2- 1.00–180.00 0.01 10.00
Third reclose time-, s Tr3- 1.00–180.00 0.01 30.00
Reset time-, s Tres- 1–180 1 1

Neutral Admittance Protection (NAP)


This element operates from either the SEF or EF to provide single stage of admittance (Y0), conductance (G0)
and susceptance (B0) elements which provides delayed trips when the magnitude of (Y0/G0/B0) exceeds the
set value.
NAP settings are described in Table 48 and Table 49.
Table 48 – Radial line recloser NAP element settings
Settings Designation Range Default
Protection type Type Y0/G0/B0 Y0
Type = Y0 n.a. n.a.
Direction mode Dmode Bidirectional/Forward/
Type = G0/B0 Bidirectional
Reverse
Operating mode Mode Enable/Disable Disable
Type = Y0 0.1-100.0 0.1
Pickup admittance, mS Y0
Type = G0/B0 n.a. n.a.
Type = G0 0.1-100.0 0.1
Pickup conductance, mS G0
Type = Y0/B0 n.a n.a.
Type = B0 0.1-100.0 0.1
Pickup susceptance, mS B0
Type = Y0/G0 n.a. n.a.
Type = G0/B0
-179–179 0
Correction angle, deg Ac Dmode = Forward/Reverse
Type = Y0 n.a. n.a.
Minimum U0, kV U0min 0.5–10.0 0.5
Tripping time, s Tt 0.05–100.00 0.05
Reset time, s Tres 0.00–100.00 0.00

Table 49 – Ring line recloser NAP element settings


Settings Designation Range Default
Protection type+ Type+ Y0/G0/B0 Y0
Type = Y0 n.a. n.a.
Direction mode+ Dmode+ Bidirectional/Forward/
Type = G0/B0 Bidirectional
Reverse
Operating mode+ Mode+ Enable/Disable Disable
Type = Y0 0.1-100.0 0.1
Pickup admittance+, mS Y0+
Type = G0/B0 n.a. n.a.
Type = G0 0.1-100.0 0.1
Pickup conductance+, mS G0+
Type = Y0/B0 n.a n.a.
Type = B0 0.1-100.0 0.1
Pickup susceptance+, mS B0+
Type = Y0/G0 n.a. n.a.
Correction angle+, deg Ac Type = G0/B0 -179–179 0

41
Dmode = Forward/Reverse
Type = Y0 n.a. n.a.
Minimum U0+, kV U0min+ 0.5–10.0 0.5
Tripping time+, s Tt+ 0.05–100.00 0.05
Reset time+, s Tres+ 0.00–100.00 0.00
Protection type- Type- Y0/G0/B0 Y0
Type = Y0 n.a. n.a.
Direction mode- Dmode- Bidirectional/Forward/
Type = G0/B0 Bidirectional
Reverse
Operating mode- Mode- Enable/Disable Disable
Type = Y0 0.1-100.0 0.1
Pickup admittance-, mS Y0-
Type = G0/B0 n.a. n.a.
Type = G0 0.1-100.0 0.1
Pickup conductance-, mS G0-
Type = Y0/B0 n.a n.a.
Type = B0 0.1-100.0 0.1
Pickup susceptance-, mS B0-
Type = Y0/G0 n.a. n.a.
Type = G0/B0
-179–179 0
Correction angle-, deg Ac- Dmode = Forward/Reverse
Type = Y0 n.a. n.a.
Minimum U0-, kV U0min- 0.5–10.0 0.5
Tripping time-, s Tt- 0.05–100.00 0.05
Reset time-, s Tres- 0.00–100.00 0.00

Neutral Admittance Protection Reclosing (AR NAP)


This element provides reclosing initiated by the NAP element operation. It also supports single shot to lockout
functionality.
AR NAP settings are described in Table 50 and Table 51.

Table 50 – Radial line recloser AR NAP element settings


Settings Designation Range Step size Default
Number of trips to lockout Nt 1/2/3/4 n.a. 2
First reclose time, s Tr1 0.10–180.00 0.01 1.00
Second reclose time, s Tr2 1.00–180.00 0.01 10.00
Third reclose time, s Tr3 1.00–180.00 0.01 30.00
Reset time, s Tres 1–180 1 1

Table 51 – Ring line recloser AR NAP element settings


Settings Designation Range Step size Default
Number of trips to lockout+ Nt+ 1/2/3/4 n.a. 2
First reclose time+, s Tr1+ 0.10–180.00 0.01 1.00
Second reclose time+, s Tr2+ 1.00–180.00 0.01 10.00
Third reclose time+, s Tr3+ 1.00–180.00 0.01 30.00
Reset time+, s Tres+ 1–180 1 1
Number of trips to lockout- Nt- 1/2/3/4 n.a. 2
First reclose time-, s Tr1- 0.10–180.00 0.01 1.00
Second reclose time-, s Tr2- 1.00–180.00 0.01 10.00
Third reclose time-, s Tr3- 1.00–180.00 0.01 30.00
Reset time-, s Tres- 1–180 1 1

Neutral Voltage Shift (NVS)


This element provides phase to earth overvoltage protection of electrical equipment in networks with insulated/
compensated neutral caused by earth fault. It also provides islanding detection for network sections with
distributed generation.
NVS settings are described in Table 52 and Table 53.

42
Table 52 – Radial line recloser NVS element settings
Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Disable
Pickup voltage Up 0.05–1.00 0.01 0.30
Tripping time, s Tt 0.10–100.00 0.01 10.00

Table 53 – Ring line recloser NVS element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Disable
Pickup voltage+ Up+ 0.05–1.00 0.01 0.30
Tripping time+, s Tt+ 0.10–100.00 0.01 10.00
Operating mode- Mode- Enable/Disable n.a. Disable
Pickup voltage- Up- 0.05–1.00 0.01 0.30
Tripping time-, s Tt- 0.10–100.00 0.01 10.00

Voltage Unbalance (VU)


This element provides sensitive load protection and detects an upstream broken conductor condition.
VU settings are described in Table 54 and Table 55.

Table 54 – Radial line recloser VU element settings


Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Enable
Voltage unbalance Uu 0.05–1.00 0.01 1
Tripping time, s Tt 0.10–100.00 0.01 10.00

Table 55 – Ring line recloser VU element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Disable
Voltage unbalance+ Uu+ 0.05–1.00 0.01 1
Tripping time+, s Tt+ 0.10–100.00 0.01 10.00
Operating mode- Mode- Enable/Disable n.a. Disable
Voltage unbalance- Uu- 0.05–1.00 0.01 1
Tripping time-, s Tt- 0.10–100.00 0.01 10.00

Current Unbalance (CU)


This element provides three phase load protection and detects a downstream broken conductor condition.
CU settings are described in Table 56 and Table 57.

Table 56 – Radial line recloser CU element settings


Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Disable
Current unbalance Iu 0.05–1.00 0.01 0.20
Minimum I2, A I2min 1–80 1 10
Tripping time, s Tt 0.10–300.00 0.01 10.00

Table 57 – Ring line recloser CU element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Disable
Current unbalance+ Iu+ 0.05–1.00 0.01 0.20
Minimum I2+, A I2min+ 1–80 1 10

43
Tripping time+, s Tt+ 0.10–300.00 0.01 10.00
Operating mode- Mode- Enable/Disable n.a. Disable
Current unbalance- Iu- 0.05–1.00 0.01 0.20
Tripping time-, s Tt- 0.10–300.00 0.01 10.00
Minimum I2-, A I2min- 1–80 1 10

Voltage Reclosing Control (VRC)


This element monitors the quality of the high voltage power supply. It blocks reclosing initiated by any AR
element when voltage and/or frequency do not meet user set values. VRC state is also used by Close Condition
Verifier element to determine allowable closing conditions. Close blocking mode (in case enabled) will block
device closing initiated by any interfaces (local or remote) in case VRC conditions are not fulfilled.
VRC settings are described in Table 58 and Table 59.

Table 58 – Radial line recloser VRC element settings


Settings Designation Range Default
Voltage unbalance mode VU control mode Enable/Disable Disable
Neutral voltage shift mode NVS control mode Enable/Disable Disable
Over voltage mode OV control mode Enable/Disable Disable
Under voltage mode UV control mode Enable/Disable Disable
Under frequency mode UF control mode Enable/Disable Disable
Over frequency mode OF control mode Enable/Disable Disable
Close blocking mode Close blocking mode Enable/Disable Disable
Voltage unbalance VUp 0.05–1.00 0.20
Neutral voltage shift
NVSp 0.05–1.00 0.40
(zero sequence voltage)
Pickup overvoltage multiplier OVp 1.00–1.30 1.20
Pickup undervoltage multiplier UVp 0.60–1.00 0.80
45.00 - 49.99 for Frated=50Hz 49.50 for Frated=50Hz
Pickup underfrequency, Hz UFp
55.00 - 59.99 for Frated=60Hz 59.50 for Frated=60Hz
50.01 - 55.00 for Frated=50Hz 50.50 for Frated=50Hz
Pickup overfrequency, Hz OFp
60.01 - 65.00 for Frated=60Hz 60.50 for Frated=60Hz

Table 59 – Ring line recloser VRC element settings


Settings Designation Range Default
Voltage unbalance mode VU control mode Enable/Disable Disable
Neutral voltage shift mode NVS control mode Enable/Disable Disable
Over voltage mode OV control mode Enable/Disable Disable
Under voltage mode UV control mode Enable/Disable Disable
Under frequency mode UF control mode Enable/Disable Disable
Over frequency mode OF control mode Enable/Disable Disable
Close blocking mode Close blocking mode Enable/Disable Disable
Voltage unbalance+ VUp+ 0.05–1.00 0.20
Neutral voltage shift+
NVSp+ 0.05–1.00 0.40
(zero sequence voltage)
Pickup overvoltage multiplier+ OVp+ 1.00–1.30 1.20
Pickup undervoltage multiplier+ UVp+ 0.60–1.00 0.80
45.00 - 49.99 for Frated=50Hz 49.50 for Frated=50Hz
Pickup underfrequency+, Hz UFp+
55.00 - 59.99 for Frated=60Hz 59.50 for Frated=60Hz
50.01 - 55.00 for Frated=50Hz 50.50 for Frated=50Hz
Pickup overfrequency+, Hz OFp+
60.01 - 65.00 for Frated=60Hz 60.50 for Frated=60Hz
Voltage unbalance- VUp- 0.05–1.00 0.20
Neutral voltage shift-
NVSp- 0.05–1.00 0.40
(zero sequence voltage)
Pickup overvoltage multiplier- OVp- 1.00–1.30 1.20
Pickup undervoltage multiplier- UVp- 0.60–1.00 0.80
45.00 - 49.99 for Frated=50Hz 49.50 for Frated=50Hz
Pickup underfrequency-, Hz UFp-
55.00 - 59.99 for Frated=60Hz 59.50 for Frated=60Hz

44
50.01 - 55.00 for Frated=50Hz 50.50 for Frated=50Hz
Pickup overfrequency-, Hz OFp-
60.01 - 65.00 for Frated=60Hz 60.50 for Frated=60Hz

Autoreclosing Timeout (ART)


Reclosing will be made only if the voltage from source side of protection device (protection device is Open)
meets the requirements of VRC element. Otherwise, device will not reclose. If the voltage did not recover until
Autoreclosing timeout is expired, protection device will go to lockout.
ART settings are described in Table 60.

Table 60 – ART element settings


Settings Designation Range Step size Default
Autoreclosing timeout, min ART 00.00.01–06.00.00 00.00.01 00.01.00

Undervoltage (UV)
This element provides a trip command when the voltage falls below a set value.
UV settings are described in Table 61 and Table 62.

Table 61 – Radial line recloser UV element settings


Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Disable
Pickup voltage multiplier Up 0.60–1.00 0.01 0.80
Tripping time, s Tt 0.10–100.00 0.01 10.00

Table 62 – Ring line recloser UV element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Disable
Pickup voltage multiplier+ Up+ 0.60–1.00 0.01 0.80
Tripping time+, s Tt+ 0.10–100.00 0.01 10.00
Operating mode- Mode- Enable/Disable n.a. Disable
Pickup voltage multiplier- Up- 0.60–1.00 0.01 0.80
Tripping time-, s Tt- 0.10–100.00 0.01 10.00

Undervoltage Reclosing (AR UV)


This element provides reclosing initiated by the UV element operation.
AR UV settings are described in Table 63 and Table 64.
Table 63 – Radial line recloser AR UV element settings
Settings Designation Range Step size Default
Number of trips to lockout Nt 1/2 n.a. 1
Reclose time, s Tr 0.10–180.00 0.01 10.00

Table 64 – Ring line recloser AR UV element settings


Settings Designation Range Step size Default
Number of trips to lockout+ Nt+ 1/2 n.a. 1
Reclose time+, s Tr+ 0.10–180.00 0.01 10.00
Number of trips to lockout- Nt- 1/2 n.a. 1
Reclose time-, s Tr- 0.10–180.00 0.01 10.00

45
Overvoltage (OV)
This element provides load protection and detects high source voltage.
OV settings are described in Table 65 and Table 66.

Table 65 – Radial line recloser OV element settings


Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Disable
Pickup voltage multiplier Up 1.00–1.40 0.01 1.05
Tripping time, s Tt 0.10–100.00 0.01 10.00

Table 66 – Ring line recloser OV element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Disable
Pickup voltage multiplier+ Up+ 1.00–1.40 0.01 1.05
Tripping time+, s Tt+ 0.10–100.00 0.01 10.00
Operating mode- Mode- Enable/Disable n.a. Disable
Pickup voltage multiplier- Up- 1.00–1.40 0.01 1.05
Tripping time-, s Tt- 0.10–100.00 0.01 10.00

Overvoltage Reclosing (AR OV)


This element provides reclosing initiated by the OV element operation.
AR OV settings are described in Table 67 and Table 68.
Table 67 – Radial line recloser AR OV element settings
Settings Designation Range Step size Default
Number of trips to lockout Nt 1/2 n.a. 1
Reclose time, s Tr 0.10–300.00 0.01 10.00

Table 68 – Ring line recloser AR OV element settings


Settings Designation Range Step size Default
Number of trips to lockout+ Nt+ 1/2 n.a. 1
Reclose time+, s Tr+ 0.10–300.00 0.01 10.00
Number of trips to lockout- Nt- 1/2 n.a. 1
Reclose time-, s Tr- 0.10–300.00 0.01 10.00

Underfrequency (UF)
This element provides load protection and detects low system frequency.
UF settings are described in Table 69 and Table 70.

Table 69 – Radial line recloser UF element settings


Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Disable
45.00-50.00 Hz for rated frequency=50 Hz 45.00
Pickup frequency, Hz Fp 0.01
55.00-60.00 Hz for rated frequency=60 Hz 55.00
Tripping time, s Tt 0.10–180.00 0.01 0.10

Table 70 – Ring line recloser UF element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Disable
Pickup frequency+, Hz Fp+ 45.00–50.00 Hz for rated frequency=50 Hz 0.01 45.00

46
55.00–60.00 Hz for rated frequency=60 Hz 55.00
Tripping time+, s Tt+ 0.10–180.00 0.01 0.10
Operating mode- Mode- Enable/Disable n.a. Disable
45.00–50.00 Hz for rated frequency=50 Hz 45.00
Pickup frequency-, Hz Fp- 0.01
55.00–60.00 Hz for rated frequency=60 Hz 55.00
Tripping time-, s Tt- 0.10–180.00 0.01 0.10

Underfrequency Reclosing (AR UF)


This element provides reclosing initiated by the UF element operation.
AR UF settings are described in Table 71 and Table 72.

Table 71 – Radial line recloser AR UF element settings


Settings Designation Range Step size Default
Number of trips to lockout Nt 1/2 n.a. 1
Reclose time, s Tr 0.10–180.00 0.01 10.00

Table 72 – Ring line recloser AR UF element settings


Settings Designation Range Step size Default
Number of trips to lockout+ Nt+ 1/2 n.a. 1
Reclose time+, s Tr+ 0.10–180.00 0.01 10.00
Number of trips to lockout- Nt- 1/2 n.a. 1
Reclose time-, s Tr- 0.10–180.00 0.01 10.00

Overfrequency (OF)
This element provides protection against a high system frequency.
OF settings are described in Table 73 and Table 74.

Table 73 – Radial line recloser OF element settings


Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Disable
50.00–55.00 for rated frequency=50 Hz 55.00
Pickup frequency, Hz Fp 0.01
60.00–65.00 for rated frequency=60 Hz 65.00
Tripping time, s Tt 0.10–180.00 0.01 0.10

Table 74 – Ring line recloser OF element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Disable
50.00–55.00 for rated frequency=50 Hz 55.00
Pickup frequency+, Hz Fp+ 0.01
60.00–65.00 for rated frequency=60 Hz 65.00
Tripping time+, s Tt+ 0.10–180.00 0.01 0.10
Operating mode- Mode- Enable/Disable n.a. Disable
50.00–55.00 for rated frequency=50 Hz 55.00
Pickup frequency-, Hz Fp- 0.01
60.00–65.00 for rated frequency=60 Hz 65.00
Tripping time-, s Tt- 0.10–180.00 0.01 0.10

Overfrequency Reclosing (AR OF)


This element provides reclosing initiated by the OF element operation.
AR OF settings are described in Table 75 and Table 76.

47
Table 75 – Radial line recloser AR OF element settings
Settings Designation Range Step size Default
Number of trips to lockout Nt 1/2 n.a. 1
Reclose time, s Tr 0.10–180.00 0.01 10.00

Table 76 – Ring line recloser AR OF element settings


Settings Designation Range Step size Default
Number of trips to lockout+ Nt+ 1/2 n.a. 1
Reclose time+, s Tr+ 0.10–180.00 0.01 10.00
Number of trips to lockout- Nt- 1/2 n.a. 1
Reclose time-, s Tr- 0.10–180.00 0.01 10.00

Automatic Backfeed Restoration (ABR)


Automatic Backfeed Restoration is used to automatically close a normally open recloser if it detects a source
(via the SD element) on the either side of the recloser and absence of a source on the other side.
ABR function is designed to provide maximum safety for operators and equipment. Restoration disarm function
will prevent circuit-breaker closing for the ABR function in case power supply is absent from both sides longer
than specified Restoration disarm timeout (Trd) setting.
This element is only applicable for ring line type reclosers.
ABR element settings are described in Table 77.

Table 77 – ABR element settings


Settings Designation Range Step size Default
Operating mode Mode Disable/Both/Only+/Only- n.a. Disable
Restoration disarm mode RD mode Enable/Disable n.a. Disable
Restoration disarm timeout Trd 00.00.01–06.00.00 00.00.01 00.00.10
Restoration time+, s Tr- 0.10–180.00 0.01 60.00
Restoration time-, s Tr- 0.10–180.00 0.01 60.00

Close Condition Verifier (CCV)


The Close Condition Verifier element controls breaker closing requests generated from local or remote
interfaces, an input/output module, or protection elements. If the network situation complies with the CCV
closing settings, closing is unblocked and vice versa.
A Hot tag for side + or – is generated if the Source Detector identifies that a source is found and the Voltage
Reclosing Control element identifies that the power quality is within the acceptable limits.
A Dead tag for side + or – is generated if the Source Detector identifies that a source is lost.
The CCV functionality can be Enabled or Disabled via the configuration menu. The CCV element settings are
described in Table 78.

Table 78 – CCV element settings


Settings Designation Range Step size Default
CCV enabled/disabled
Hot+ / Dead- allowed Hot+ / Dead- allowed Enable/Disable n.a. Disable
Hot- / Dead+ allowed Hot- / Dead+ allowed Enable/Disable n.a. Disable
Dead- / Dead+ allowed Dead- / Dead+ allowed Enable/Disable n.a. Disable
Hot+ / Hot- allowed Hot+ / Hot- allowed Enable/Disable n.a. Disable

Synchronization Indicator (SI)


The Synchronization Indicator is active only if the CCV setting Hot+ / Hot- allowed = Enabled. The SI element
monitors voltage magnitude and phase angle differences from both sides of the recloser. The CCV element

48
will allow breaker closing if the voltage magnitude and phase angle difference is static and both parameters
do not exceed the predefined thresholds described in Table 79.

Table 79 – SI element settings


Settings Designation Range Step size Default
Maximum voltage difference, p.u. dU 0.01–0.30 0.01 0.05
Maximum phase angle difference, deg dP 5–90 1 5

Fault Locator (FL)


This element calculates three data points:
• Xf – estimated distance from the recloser to the fault location in kilometers;
• X1_fault – estimated positive sequence reactance of the fault in primary ohms;
• X0_fault – estimated zero sequence reactance of the fault in primary ohms.
These points are calculated based on the selected phasor (phasor selection method is developed by Tavrida
Electric). Fault details are available in case of short circuit fault dropout or the recloser open to lockout after
unsuccessful reclosing. The indicated value of the estimated distance to fault (Xf) is limited with maximum fault
distance setting. Values indicated are updated after one of the OC1, EF1, OC2, EF2, OC3, EF3, SEF pickups
firstly in autoreclosing sequence.
Data points calculated based on the optimal phasor are available locally and remotely (in Event log, System
status, or via SCADA).Data points calculated at the moment of the protection device pickup or the protection
device tripping are available via SCADA only. Full list of the indicated data is presented in Table 80.

Table 80 – Fault Locator data points


Indication availability
Data point Designation
Event log System status SCADA
Values calculated based on the optimal phasor (according to Tavrida Electric algorithm)
Estimated distance from the recloser to the
Xf   
fault location in kilometers
Estimated positive sequence reactance of
X1_fault   
the fault in ohms
Estimated zero sequence reactance of the
X0_fault   
fault in ohms
Values calculated based at the moment of the protection device pickup
Estimated distance from the recloser to the
Xf  
fault location in kilometers
Values calculated based at the moment of the protection device tripping
Estimated distance from the recloser to the
Xf  
fault location in kilometers
Overcurrent fault AB resistance in ohms Rab  
Overcurrent fault AB reactance in ohms Xab  
Overcurrent fault BC resistance in ohms Rbc  
Overcurrent fault BC reactance in ohms Xbc  
Overcurrent fault CA resistance in ohms Rca  
Overcurrent fault CA reactance in ohms Xca  
Earth fault A resistance in ohms Rag  
Earth fault A reactance in ohms Xag  
Earth fault B resistance in ohms Rbg  
Earth fault B reactance in ohms Xbg  
Earth fault C resistance in ohms Rcg  
Earth fault C reactance in ohms Xcg  

FL settings are described in Table 81 and Table 82.

Table 81 – Radial line recloser FL element settings


Settings Designation Range Step size Default
Operating mode Mode Enable/Disable n.a. Disable

49
Downstream line X1, Ohm/km X1 0.0000–2.0000 0.0001 0.3500
Downstream line X0, Ohm/km X0 0.0000–4.0000 0.0001 1.5000
Maximum fault distance, km Lm 0.0–1000.0 0.1 1.0

Table 82– Ring line recloser FL element settings


Settings Designation Range Step size Default
Operating mode+ Mode+ Enable/Disable n.a. Disable
Downstream line X1+, Ohm/km X1+ 0.0000–2.0000 0.0001 0.3500
Downstream line X0+, Ohm/km X0+ 0.0000–4.0000 0.0001 1.5000
Maximum fault distance+, km Lm+ 0.0–1000.0 0.1 1.0
Operating mode- Mode- Enable/Disable n.a. Disable
Downstream line X1-, Ohm/km X1- 0.0000–2.0000 0.0001 0.3500
Downstream line X0-, Ohm/km X0- 0.0000–4.0000 0.0001 1.5000
Maximum fault distance-, km Lm- 0.0–1000.0 0.1 1.0

Cold Load Pickup (CLP)


In some cases, when power supply is restored after prolonged outage, this results in greater than normal
power demand. The main cause of this problem is the large number of electric heaters, furnaces, refrigerators,
air conditioners and other thermostat-controlled loads. Higher current is often seen by protection as short circuit
or overload, that result in circuit breakers automatically tripping to protect the system from overload, and the
power goes off again. The CLP element enables temporary increasing current pickup setting to sustain cold
load current and avoid tripping without compromising protection sensitivity. This functionality is applicable for
radial recloser as only in this case can the duration of power interruption for a group of customers be observed.
CLP settings are described in Table 83.
Table 83 – CLP element settings
Parameter Designation Range Resolution
Recognition time, min Trec 0–60 1
Reset time, min Tres 1–400 1
Cold load multiplier CLM 1.0–2.0 0.1

4.2 Measurement
Overview
The Main Processor gets the analog signals from the Outdoor Switching Module current and voltage sensors,
converts them into digital format, and filters it for Harmonic content. The RMS values of the filtered signals are
used for protection and indication as shown in the table below.

Table 84 – Applicability of RMS values of the signals


Applicability
Settings Designation Range Resolution
Protection Indication
Phase currents, A Ia, Ib, Ic 0 … 12500 1A  
Residual current , A 16
In 0 … 12500 0.1 A  
Positive sequence current, A I1 0 … 12500 1A  
Negative sequence current, A I2 0 … 12500 1A  
Neutral voltage shift measured from Source + side, kV Un+ 0 … 30 0.1 kV  
Neutral voltage shift measured from Source - side, kV Ub- 0 … 30 0.1 kV  
Positive sequence voltage measured from Source + side, kV U1+ 0 … 30 0.1 kV  
Positive sequence voltage measured from Source - side, kV U1- 0 … 30 0.1 kV  
Negative sequence voltage measured from Source + side, kV U2+ 0 … 30 0.1 kV  
Negative sequence voltage measured from Source - side, kV U2- 0 … 30 0.1 kV  
Frequency measured from Source + side17, Hz F+ 40-60 at 50Hz 0.01 Hz  
40-70 at 60Hz

16
Residual current In is equal to three times the zero sequence current Io.
17
Voltage and frequency memory is used if all three phase to earth voltages on any side drop below approximately 0.5 kV.

50
Frequency measured from Source – side13, Hz F- 40-60 at 50Hz 0.01 Hz  
40-70 at 60Hz
Single-phase power factor PFa, PFb, PFc -1 … 1 0.01 
Three-phase power factor PF3ph -1 … 1 0.01 
Phase-to-earth voltages measured from Source + side, kV Ua+, Ub+, Uc+ 0 … 30 0.1 kV 
Phase-to-earth voltages measured from Source - side, kV Ua-, Ub-, Uc- 0 … 30 0.1 kV 
Phase-to-phase voltages measured from Source + side, kV Uab+, Ubc+, Uac+ 0 … 30 0.1 kV 
Phase-to-phase voltages measured from Source - side, kV Uab-, Ubc-, Uac- 0 … 30 0.1 kV 
Positive sequence active power, kW P1 -65535 … 1 kW 
65535
Single-phase active power, kW Pa, Pb, Pc -65535 … 1 kW 
65535
Three-phase active power, kW P3ph -65535 … 1 kW 
65535
Single-phase reactive power, kVAr Qa, Qb, Qc -65535 … 1 kVAr 
65535
Three-phase reactive power, kVAr Q3ph -65535 … 1 kVAr 
65535
Single-phase active energy, kWh Wa, Wb, Wc 0 … 9999999 1 kWh 
Three-phase active energy, kWh W3ph 0 … 9999999 1 kWh 
Single-phase reactive energy, kVArh Ea, Eb, Ec 0 … 9999999 1 kVArh 
Three-phase reactive energy, kVArh E3ph 0 … 9999999 1 kVArh 
Phase angle difference between U1+ and U1-, degrees PhAngDifU1 0 … 180 or 1 degree 
“Undefined”
Angle between Un and In, degrees An -179 … 180 or 1 degree  
“Undefined”

Signal filtering effectively rejects higher harmonics. Phase current measuring channels are additionally
equipped with inrush filters.

Inrush Filter
Reclosers described in the current product guide incorporate a unique inrush filter. This allows filtering of
magnetizing currents occurring at energizing transformers or distribution feeders with step-down-transformers.
In contrast to the widely used inrush restraint, which blocks the operation of protection for the period of inrush,
the filter leaves all protection active and sensitive to faults for the whole period of line energizing.
The advantages are:
• This feature makes it possible to select the settings of current-based protection elements based on actual
load and fault levels, not considering any side effects due to transformer load energizing;
• If, after maintenance closing or performing backfeed restoration for a faulty feeder part, the fault clearing
time is significantly reduced as all protection elements operate correctly without any delays.
Figure 26 and Figure 27 demonstrate the comparison of current measurement results at load energizing
captured by the recloser without and with inrush filter enabled.

Figure 26
Basic frequency phase currents RMS. No inrush filter applied

51
Figure 27
Basic frequency phase currents RMS. Tavrida Electric inrush filter applied

4.3 Communication
Overview
Indication and control are provided through the following interfaces:

• Personal Computer Interface (PCI)


• Telecommunication Interface (TCI)
• Digital Input/Output Interface (IOI)
• TELARM dispatcher Interface (TDI)

In the „Local“ mode, the recloser is controlled via the MMI or PCI. In the „Remote“ mode the recloser is
controlled via TCI, TDI or IOI. Indication is provided via all interfaces in both modes.

Personal Computer Interface (PCI)


The PCI provides Indication and control via a PC (with installed TELARM software). The connection is
established via the USB port located on the front the Control Panel Module (CPM), RS-232 serial port, RJ45
interface of Wired Ethernet module, ST interface of Optical Ethernet module, WiFi module, or Bluetooth
module.

The PCI provides the following functionality (refer to TELARM software):


• Data upload/download;
• Firmware upload.

Uploading/Downloading data
Data can be uploaded/downloaded via the PC (refer also to the description of the on-line mode of TELARM
software) when the communication link is established. The communication link is password protected. The
password is configured via the PCI at the time of the first communication session and stored in the MPM flash
memory. If the control signal „Erase passwords“ has been activated the password is erased. A new password
can be uploaded from the PC during the next communication session.

Uploading firmware
A PC with installed TELARM is required for firmware uploading.

Telecommunication Interface (TCI)


TCI is an embedded RTU interface that can be used for remote indication and control.
The RTU is connected to the SCADA via a radio modem, phone modem, GSM modem, RS485-RS232
converter or directly.
Available communication protocols are DNP3, Modbus and IEC 60870-5-104.

52
Digital Input/Output Interface (IOI)
The IOI provides control and indication via the digital Input-Output Module (IOM). The IOM provides 12 digital
inputs and 12 digital outputs for SCADA control and indication. Each input/output function is individually
customizable.

4.4 Remote Engineering


The TELARM Dispatcher Interface (TDI) enables multiple recloser connections to Tavrida Electric TELARM
Dispatcher® for remote control and supervision. TELARM Dispatcher can be installed on one or multiple PCs
with full or limited access to all or some of the reclosers. Connection via Internet or Local Area Network (LAN)
is available. Physical connection of an RC5_4 to the Internet can be done via wireless connection - GPRS
modem (Figure 28) or wired connection - USB-Ethernet module (Figure 29).
Both the RC5_4 recloser control(s) and PC(s) with TELARM software can connect to RC Internet Server
software (RCIS). This software provides communication between a PC and multiple RC5_4. RCIS itself is a
Windows® service. Connection between TELARM software and RCIS is protected with SSL encryption.
Individual certificates are issued for each PC with TELARM which will connect to RCIS.
Benefits of using a TDI are the following:
• Remote control is available even without a SCADA system in place (or as backup for existing SCADA
system).
• SCADA is usually available in dispacther centers only. With TDI regional operators can check protection
devices remotely without any support request form the Dispatcher Center.
• Potential problems can be identified and eliminated faster because all logs from protection device, including
Event log, detailed Fault profile and fault oscillography are available remotely and can be analyzed by an
operator immediately after protection device has operated.

Figure 28
Structure of the system with wireless connection

Figure 29
Structure of the system with wired connection

53
4.5 Indication
Man-Machine Interface (MMI)
The MMI provides control and indication via the Control Panel Module (CPM) if the CPM is enabled. If the
CPM is disabled, no control and indication functions are supported by the MMI.

1 LCD
2 USB Port
General Control Pushbuttons
3 ON / OFF / Test
4 Control Mode
5 Closed
6 Open
LCD Control Pushbuttons
7 LCD Contrast
8 Navigation
9 Enter
10 Escape
Fast Key Pushbuttons
11 Malfunction Log
12 Event Log
13 Protection ON/OFF
14 Earth Fault ON/OFF
15 Sensitive Earth Fault ON/OFF
16 Reclosing ON/OFF
17 Hot Line ON/OFF
18 Backfeed Restoration ON/OFF or
Customized protection ON/OFF18
19 Active [Protection] Group

Figure 30
Control Panel Module (CPM)

6 Title Bar
LCD Display 7 Menu Bar
1 TEL Logo 8 Status Bar
2 Title string 9 Date and Time
3 Label of Indication data, Control data or Settings 10 Parameter values of Indication data, Control data or
4 Path Settings
5 Context icon 11 Scroll Bar

Figure 31
Liquid Crystal Display (LCD)

18
Following protections can be appointed on “ABR” pushbutton in TELARM: ABR, CCV, UV, OV, UF, OF, VU, CU, BF, LS, NVS, NAP.

54
The Title bar is shown in all menus and includes the following elements:
• TEL logo icon
• Title string defining menu type
• Path to the current menu
• Context icon

55
5 Product Handling
5.1 Transportation
The serviceability of the equipment is critically dependent on safe and careful handling during transportation
sudden impacts or shocks during loading and unloading can lead to damage of critical components.
It is important to adequately secure the equipment to minimize the risk of damage during transportation.
Fixation may be secured by using web slings.
The Rec15/25_Al1_5p package consists of a wooden pallet fumigated according to ISPM 15 rules, galvanized
steel collars and cover (see Figure 32). For details on package dimensions and weight refer to Appendix 4 of
this guide.

Figure 32
Rec15/25_Al1_5p package

WARNING! It is not permitted to stack more than two packages during transportation.
To move the recloser package, use a hydraulic lift or fork lift truck (Figure 33).

Figure 33
Package lifting methods

57
5.2 Storage Conditions
The packaged recloser should be stored in dry storage areas with natural ventilation.
WARNING! It is not permitted to stack more than two packages during storage.
Unpacked and assembled equipment can be stored before installation. Keep it in a clean, dry location with
sufficient air circulation and temperature to prevent condensation. Insulation must be protected against dirt
and moisture.

5.3 Inspection
Each recloser is completely assembled, tested, and inspected at the factory. It is in good condition when
accepted by the carrier for shipment. Upon receipt, inspect the package for signs of damage. After unpacking
the recloser, inspect its components thoroughly for damage incurred during shipment. If damage is discovered,
file a claim with the carrier immediately. The inspection process is described in the table below:

Table 85 – Inspection list

# Object Inspection description

1 Plastic details Absence of mechanical damages, scratches, spots


2 Silicon insulation Absence of mechanical damages
3 Metal parts Absence of mechanical damages, rust and spots

5.4 Unpacking
Follow the recommendation below to unpack:

Pole Mounted Recloser

2. Unscrew eight screws from upper collar and take it


1. Cut strapping tapes off

3. Remove screws from other collars 4. Take off collars one by one

58
6. Cut four buckles that hold the pole interface part
(if pole interface is applicable). Refer to Mounting Kit
5. Remove box with Control cable (if box is applicable) Preparation section for details

8. Remove RC by pushing from right to left, then


7. Unscrew fasteners that hold RC on holder forward

9. Open RC internal door and unscrew captive screw to re- 10. Pull right side down and slide left to remove
lease anti-vandal cover anti-vandal protection

59
11. Unscrew eight screws holding the mounting bracket

Substation Recloser

1. Unscrew twelve screws from upper collar and take 2. Unscrew ten screws from bottom collar
it off

3. Take off collars 4. Unscrew fasteners that hold RC on holder

60
5. Remove RC5 by pushing from right to left, then 6. Open RC internal door and unscrew captive screw to release
forward anti-vandal cover

7. Pull right side down and slide left to remove anti- 8. Unscrew holder for voltage transformer (if VT holder is
vandal protection applicable). Refer to Handling and Installation Guide for details

9. Cut four buckles holding RC holder 10. Cut two buckles holding box with fasteners

61
11. Unscrew eighteen fasteners holding the mounting 12. Cut five buckles holding the mounting kit accessories
kit accessories

13. Unscrew eight fasteners holding the mounting kit 14. Unscrew eight screws holding the mounting bracket
accessories

5.5 Handling Requirements


To avoid equipment damage, follow the handling recommendations listed below:
1. In case a crane is used, the recloser components should be lifted using special lifting provisions located at
the Recloser Control cubicle and the Outdoor Switching Module mounting kit. See Handling and Installation
guide for details.
2. The HV assembly and the Recloser Control should be appropriately fixed/lifted to avoid equipment damage.
3. In case the recloser components are delivered on a pallet, it can be moved using a properly rated forklift
vehicle.

Outdoor Switching Module Handling


To lift the Outdoor Switching Module separately from the frame use four lifting provisions located on lower
holders.
WARNING! Do not use the Outdoor Switching Module bushings for lifting and handling. Failure to comply may
result in damage to the equipment.

62
Figure 34
Outdoor Switching Module handling

Recloser Control Handling


The RC5_4 has two holders with lifting provision. Two holders placed at the bottom of the Recloser Control
together with a mounting bracket allowing it to stand in the vertical position without any additional equipment.

Figure 35
Recloser Control handling

63
Pole Mounting Kit Preparation
After unpacking the mounting kit, it should look as shown below:

Figure 36
Mounting kit configuration out of box

Initially the L-shape surge arrester holders and pole interface bracket are in the “transportation” position (if
applicable). It is necessary to change them to the operational position according to the sequence described
below:

1. Unscrew surge arresters holder 2. Flip 3. Fasten with torque of 40N*m


from OSM tank

4. Unscrew surge arresters holder 5. Remove pole interface bracket 6. Install surge arresters holder and
(if applicable) and flip surge fasten with torque of 40N*m (for frontal
arresters holder (for frontal installation only)
installation only)

64
Frontal Installation
To connect the pole interface bracket to the mounting frame, use the M16 fasteners included in the delivery
package.

1. Unscrew four M16 bolts installed on pole interface bracket 2. Fasten pole interface bracket using M16 fasteners

Lateral Installation

1. Unscrew four M16 bolts installed on pole interface bracket 2. Unscrew two bolts holding surge arresters bracket

3. Unscrew four bolts holding OSM mounting brackets 4. Rotate OSM 90 degrees and install mounting brackets

65
5. Fasten OSM mounting brackets using M12 fasteners 5. Install surge arresters bracket on OSM tank and attach
pole interface bracket (if applicable)

6. Fasten pole interface bracket using M16 fasteners kit

Substation Mounting Kit Preparation


It is recommended to assemble the mounting kit in horizontal position. Use M12 fasteners included. Tightening
torque for M12 should be not less than 40 Nm.

1. Fasten four holders for structure height adjustment to 2. Fasten four base holders
each other

66
3. Connect bottom of the base holders using four 4. Fasten four support parts according to substation bay
horizontal holders installation pinouts

5. Fasten four channels at required height 6. Connect bottom of the channels using square holder

7. Connect middle of the channels using square holder 8. Fasten Outdoor Switching Module holder

67
10. Fasten support for voltage transformer holder
9. Fasten the Recloser Control holder
(if VT holder is applicable)

11. Fasten voltage transformer holder (if VT holder is applicable).


Refer to Handling and Installation Guide for details

68
6 Installation
Installation operations are carried out by utility technical personnel and can be supervised by Tavrida Electric
technical representatives. This chapter describes installation procedures and required equipment. For more
detailed information about the installation process contact a Tavrida electric technical representative.

6.1 Required Equipment


1. Set of wrenches (8-24mm);
2. Set of screw drivers (+ and - );
3. Screw driver “-” 2.5x0.4 for WAGO terminals;
4. Diagonal pliers;
5. Power line connection provision:
▪ Wires (preferable insulated) (6 pcs.);
▪ Support insulators 3 pcs. (if required);
▪ Cable lugs applicable for chosen connection wires and M12 bolt (6 pcs.);
▪ Connection clamps (waterproof if insulated connection wires are used) (6 pcs.).
6. Hydraulic cable terminal lug manual clamp up to 240mm2;
7. Alcohol for insulation cleaning;
8. Crane or other lift for the Outdoor Switching Module and RC5_4 lifting.

6.2 Installation Procedure


WARNING! The installation procedure in this manual is offered as a guide only. It should be used in conjunction
with the utility’s own safety procedures. Before installation begins, all necessary precautions should be carried
out.

Outdoor Switching Module Installation


Before starting the Outdoor Switching Module installation, make sure that:
• The Outdoor Switching Module main contacts are open,
• The control cable is disconnected,
• The Outdoor Switching Module control cable socket cover is closed.
The mounting kit and surge arresters (depending on particular installation) should be installed according to
procedure described in the Handling and Installation guide.
The Outdoor Switching Module installed on the mounting frame should be lifted as shown in Figure 37.
ATTENTION! The HV assembly lifting facilities should not come into contact with bushings, surge arresters or
auxiliary VT bushing extensions.
ATTENTION! When installing the HV assembly, make sure that the connection to the line is performed
according to the procedure described in the Handling and Installation guide.

70
Figure 37
Outdoor Switching Module lifting method (frontal and lateral installation)

Installation example using two M20 hot-dip galvanized threated rods is shown in figure below.

Figure 38
Outdoor Switching Module through the pole installation example

Installation example using four hot-dip galvanized U-profiles (bolted to interface bracket) and four hot-dip
galvanized threated rods is shown in Figure 39.

71
Figure 39
Outdoor Switching Module around the pole installation example

The substation mounting kit is applicable for two types of substation bay installation pinouts:
• 558…609 x 1056...1219 mm (Figure 40);
• 729…909 x 862…900 mm (Figure 41).

Figure 40 Figure 41
Substation mounting kit installation example Substation mounting kit installation example

Outdoor Switching Module installation example at substation mounting kit is shown in figure below.

72
Figure 42
Outdoor Switching Module substation installation example

RC5_4 installation
Before starting the Recloser Control installation, make sure that:
• The Recloser Control doors are closed,
• The control cable is disconnected,
• The Recloser Control cable socket cover is closed.

Figure 43
Recloser Control lifting method

73
The Recloser Control installation example using four hot-dip galvanized U-profiles and four hot-dip galvanized
threated rods is shown in figure below.

Figure 44
Recloser Control around the pole installation example

Recloser Control installation example using two hot-dip galvanized threated rods is shown in figure below.

Figure 45
Recloser Control through the pole installation example

The Recloser Control installation example at substation mounting kit is shown in figure below.

74
Figure 46
Recloser Control substation installation example

In case of Anti-vandal housing installation, it needs to be mounted on a pole first (Figure 47). After that the
Recloser Control should be installed inside of the Anti-vandal housing using M20 studs (Figure 48).

Figure 47
Anti-vandal housing installation examples

75
Figure 48
Recloser Control installation inside of the Anti-vandal housing

Auxiliary VT Installation
Auxiliary voltage transformer should be installed on a dedicated VT holder of a mounting kit.
Line connections to auxiliary voltage transformer should be performed in accordance to a VT technical manual
by trained personnel who are familiar with the equipment.

Earthing
ATTENTION! The Outdoor Switching Module, its mounting frame and the Recloser Control should be
connected to the same earthing bus using 12mm nuts and bolts tightened to 50 Nm.
Earthing points on the OSM15/25_Al_1 and the RC5_4 are shown below.

Figure 49
Earthing terminals position

ATTENTION! Make sure that the system impedance to ground is less than 5 ohms. System impedance to
ground can be measured on site using special equipment or previously measured value for particular
grounding bar can be provided by the utility. In case this requirement is not met it may lead to death or injury
to people during operation.

76
It is recommended to arrange high voltage assembly earthing as it shown in Figure 50. The Outdoor Switching
Module, mounting frame, auxiliary supply VTs should be earthed using separate earthing jumpers connected
to the common earthing bus. Surge arresters grounding wires should be connected to special earthing
provisions placed on surge arresters holders.

Figure 50
Complete earthing assembly

Primary Line Connection

Aerial Connectors
Aerial connectors (Figure 51) provide a reliable connection of cable conductors from 35 to 240 mm2 cross
section. Aerial connectors and fasteners are made of stainless steel. The clamp is made of Sn-Bi coated brass.

Figure 51 Figure 52
Aerial connector Conductor connection via aerial connectors

Tightening torque of connector nuts is 20±1 Nm.

77
Protective covers can be used to protect connections against the environment (Figure 53 and Figure 54).If
cable diameter is more than 10 mm, the cone end of each cover should be cut to the corresponding diameter
to fit the cable tightly (Figure 55).

Figure 53 Figure 54
Aerial connector with bird protection Aerial connector with bird protection

Figure 55
Aerial connector with bird protection

NEMA Connectors
Two-hole and Four-hole NEMA palm connectors (Figure 56) provide a reliable connection to power line of any
type of conductors treated correspondingly.
NEMA connectors are preinstalled and tightened the Outdoor Switching Module terminals during assembly.
The power line connection can be done using the M12 bolts and nuts (not supplied). It is recommended to use
HDG or stainless steel M12 fasteners and tin-coated cable lugs for power line connection to prevent corrosion.

Figure 56
NEMA palm connectors

Tightening torque for power line connection depends on M12 fasteners material used, but not less than 40
Nm.
Surge arresters and auxiliary VT HV terminals connection can be done directly to NEMA terminals.
Special NEMA protective covers can be used to protect line connections against the birds or aggressive
environmental factors (Figure 57).

78
Figure 57
NEMA connectors with bird protection

All technical parameters are met without the protective covers installed.
Protective covers and NEMA terminals allows multidirectional primary line wires-to-terminals connection.

Burndy® NEMA Connectors


Two-hole Burndy® connectors (Figure 58) provide a reliable connection to power line of any type of conductors
treated correspondingly. The connectors are made of Sn-Bi coated brass.

Figure 58
Two-hole Burndy® NEMA connector

RC5_4 Connection to Auxiliary Supply


ATTENTION! Auxiliary supply VT connection wire should not be earthed inside the VT secondary
compartment.
Before the auxiliary supply from a pole mounted VT is connected to the RC5_4, resistance measurement
should be performed. Switch digital Multi-meter to the Ohm metering mode and enable beeping signal.
Connect one electrode to the earthing bar (with the connected VT base earthing bar) and second electrode to
both connection wires (one by one or to both of them simultaneously). Resistance should be infinite, sound
signal should not appear.
Resistance measurement is not performed in case an external AC/DC supply is used.

79
ATTENTION! Corresponding AC1 and AC2 earthing jumpers should be removed before external AC/DC
source with predefined neutral is connected to the RC5_4.
After the main line is powered, the commissioning engineer should make sure that the auxiliary supply is
connected correctly. The auxiliary supply voltage should be checked by digital voltmeter.
For that purpose the RC5_4 battery switch should be set OFF, corresponding AC switch (both switches if two
supply options is used) set ON.
Measured AC voltage at terminals 1-2 and 8-9 (in case two VTs are installed) should not exceed the limits of
85-265 V.
Connection terminals for the Recloser Control auxiliary power supply are shown below (Figure 59).

Figure 59
Auxiliary supply connections inside PSFM

Bayonet connection terminals for the Recloser Control auxiliary power supply (available on request) are shown
below (Figure 60 and Figure 61).

Figure 60 Figure 61
Auxiliary power supply connection with bayonet connectors Three pin bayonet connector

6.3 Dismounting Procedure


Protection device dismounting should be performed in reverse order to the installation procedure. All safety
procedures and precautions should be applied accordingly. The integrity of the line should be restored in case
the protection device is removed completely.

80
7 Commissioning
7.1 No-load Tests
ATTENTION. Before powering the main line, the recloser should be in the OPEN position. The recloser shall
be closed via the MMI only after the no-load tests are performed.

Powering the Protection Device


Switch on the battery switch. Make sure that local time and date are correct. If date, time or both are incorrect
connect to the Recloser Control via USB, Bluetooth or TDI (see “6.5. Other RC5_4 Control Options” for details)
and synchronize date and time on your computer with the RTC of the Recloser Control using TELARM. Date
and time is visible at the MMI screen.
Date and time synchronization procedure:
TELARM->On-line->Synchronize date and time
Date and time setup via MMI:
CPM Main Menu -> Control Data -> Set Date and Time
After that the commissioning engineer should make sure that the MMI menu navigation is OK, indication on
the MMI is OK.

RC5 Power Supply Check


For each of the conditions described below check that MMI displays no errors and MMI LED function (Lockout
LED, Mode – Local LED, State – Open LED, On or Off LED of each protection button, Active group – 1 LED)
• Battery switch is OFF, AC supply switch is ON;
• Battery switch is ON, AC supply switch is OFF19;
• Battery switch is ON, AC supply switch is ON.
NOTE: Up to 60 s might be required for the RC5_4 circuits energizing.

Checking CVCS Coefficients


Check that the CVCS coefficients in the RC5_4 settings correspond to the RTC.
CVCS coefficient indications:
MMI -> Main menu -> Settings -> System -> Measurement
To correct coefficients, connect to the Recloser Control via TELARM:
TELARM -> On-line -> Rec -> System settings -> System -> ME settings
Change “Wires to terminal connection” setting. Check that all other System settings in TELARM are correct for
the particular device. How to upload settings is described in “6.6. Settings Modifications”.

Checking Phase Sequences


After powering the main line at the Outdoor Switching Module OPEN state, the commissioning engineer should
perform the PHASE SEQUENCE check-up. The negative sequence voltage (U2) should be less than 1kV.
Negative voltage sequence indication:
MMI -> Main menu -> Indication data -> Measurement -> U2
If the negative sequence voltage is observed, it is recommended to change the software setting (changing
phase sequence System-Phase sequence).
Changing phase sequence:
TELARM -> On-line -> Rec -> System settings -> System -> Configuration -> Wires to terminal
connection
Change “Wires to terminal connection” setting. Check that all other System settings in TELARM are correct for
this particular device. How to upload the System settings is described in the “Operation” chapter.

19
If rechargeable battery is available.

82
7.2 On-load Tests
After all No-load tests are executed, the main contacts can be closed (via the MMI, USB, Bluetooth or TDI).
Check that measurements of phase currents, power factors, active and reactive power etc. are correct:
MMI -> Main menu -> Indication data -> Measurement

83
8 Operation
8.1 Switching
Mechanical Tripping
NOTE! Operation of the mechanical trip hook should be done by means of high voltage operating rod for live-
line operations.
To trip the recloser mechanically, pull down the manual trip hook to the lockout position (Figure 62). In this
position, the recloser is mechanically locked in the OPEN position and the actuator is electrically isolated. This
prevents CLOSING (locally or remotely).

Figure 62
Mechanical trip of switching module

Operation via MMI


To operate the device via the MMI, change the mode of the protection device to “Local” by pressing the ”MODE”
button (Figure 63).
Local device mode indication is:
“Local” LED above the “MODE” button is active.

Tripping
To trip the switching module via the MMI, push the green button «O» (Figure 63). Tripping via MMI is available
both in Local and Remote modes.

85
Figure 63
Switching module operation control via MMI

Closing
To close the recloser via the MMI, push the red button «I» (Figure 63).
NOTE! Make sure that the Recloser Control is in Local mode.
NOTE! Make sure that the manual trip hook is pushed back into the operating position. If it is not, change the
mechanical trip hook position using the high voltage operating rod for live-line operations.

Delayed Closing
The RC5_4 functionality provides an option of delayed closing, meaning that after the close button is pushed
the recloser will not be closed instantaneously, but after some delay. The corresponding setting is configurable
in setup menu:
Main menu -> Settings -> System -> MMI -> Close delay
You may stop delayed closing by pressing the ESC button.

Indication
The open state of the Outdoor Switching Module main contacts is indicated via
• LED above “O” button
• Mechanical position window on the Outdoor Switching Module
The closed state of the Outdoor Switching Module main contacts is indicated via
• LED above “I” button
• position window on Outdoor Switching Module

8.2 Logging
Logs
From the control panel the following logs can be read:
• Event log (EL)
• Malfunction log (ML)
Other logs like Fault profile, Load profile, Communication log are available only using a PC via the PCI, TCI or
TDI interfaces.

86
Figure 64
Event log via MMI

This screen (Figure 64) is a default one in case “Lockout” is present. Pressing the “Event Log” button provides
transition to this screen from any menu.
To enter the EL via the MMI menu:
Main menu -> Indication data -> IDC -> Event log
The latest event is placed at the bottom of the list. Info about the number of the event in the list, time and date
of the event is displayed on the screen.
To navigate in the EL, use arrow buttons. The “open door pictogram” marker in the top right corner of the
screen means that additional info is applicable. To see this additional info, press the ENTER button, to go back
to the EL menu press ESC button.

Figure 65
Malfunction log via MMI

This screen (Figure 65) is a default one in case LOCKOUT is absent and there are some unread events in the
Malfunction log. Pressing the “Malfunctioning log” pushbutton provides transition to this screen from any menu.
To enter the ML via the MMI menu:
Main menu -> Indication data -> IDC -> Malfunction log
Some events have characters that classify events: “M” – malfunction or “W” - warning. A character is shown
in the beginning of the event description string.
It is not possible to see the load profile via the MMI. Load profile step can be changed via the MMI.
To change Load profile step via the MMI:
Main menu -> Settings -> System -> IDC -> Load profile step
NOTE! It is only possible to erase all logs at once, single event removal is not possible.
To erase all readings in all logs, select corresponding function in the menu as shown below and confirm the
action:
Main menu -> Control data -> Erase logs

Counters
From the control panel the following counters can be read:
• Protection counters
Main menu -> Indication data -> IDC -> Protection counters
• Lifetime counters
Main menu -> Indication data -> IDC -> Lifetime counters

87
• Log filling counters
Main menu -> Indication data -> IDC -> Log filling counters

8.3 Measurements
All measurement data is available via the MMI menu
Main menu -> Indication data -> ME

8.4 Date and Time Settings


Time and date readings are available in every MMI menu.
Changing time and date settings:
Main menu -> Control data -> Set date and time
Daylight saving time settings:
Main menu -> Settings -> System -> RTC

8.5 Other RC5_4 Control Options


PCI – Personal Computer Interface
The PCI provides Indication and control via a PC with installed TELARM Lite software and RC5 driver. The
connection is established via the USB port located on the front the Control Panel Module, via RS-232 port #5,
RJ45 interface of Ethernet module on the RCM or via a Bluetooth module.
The PCI provides the following control and indication functionality:
• Indication signals generated by PCI
• Data upload/download via PC
• Firmware upgrade/downgrade via PC
To operate the recloser via the USB interface it is required to have a USB 2.0 Type A Male to Type B Male
cable. To operate the recloser via the Bluetooth interface it is required to have a PC with Bluetooth module.
To operate the recloser via the Ethernet interface it is required to have an Ethernet or fiberglass cable.

Connection Establishment via USB


1. Connect the PC and the RC5_4 with Type A Male to Type B Male USB cable20;
2. Select a recloser that you want to connect in TELARM Lite;
3. Set “PC interface” to USB;
4. Click “Connect” button.

20
NOTE! The USB cable is not in the standard scope of supply, however it can be ordered separately. Please contact the Tavrida Electric representative for
details.

88
Figure 66
USB interface connection

Connection Establishment via Bluetooth


1. Enable the BTM mode on the RC5_4 using the MMI:
Main menu -> Settings -> System -> Configuration -> BTM mode
2. Pair the device with the PC (default pairing code is 5555);
3. Select a recloser that you want to connect in TELARM Lite;
4. Set “PC interface” to Bluetooth;
5. Set Auto COM port or choose appropriate COM port;
6. Click “Connect” button.

89
Figure 67
Bluetooth interface connection

Connection establishment via Ethernet


1. Connect the PC and the RC5_4 with twisted pair cable or optical fiber cable21;
2. Select a recloser that you want to connect in TELARM Lite;
3. Set “PC interface” to TCP/IP;
4. Enter Recloser Control IP address and port. It can be checked in MMI:
Main menu -> Settings -> Comms -> PCI -> Ethernet
5. Click “Connect” button.

21
NOTE! The twisted pair cable and optical fiber cable are not in the standard scope of supply, however it can be ordered separately. Please contact the
Tavrida Electric representative for details.

90
Figure 68
Ethernet interface connection

Connection establishment via Wi-Fi module


1. Enable “Access point” operating mode in Wi-Fi settings of RC5_4 using MMI:
Main menu -> Settings -> Comms -> PCI -> Wi-Fi
2. Connect your PC to the RC5_4 SSID network;
2. Select a recloser that you want to connect in TELARM Lite;
3. Set “PC interface” to TCP/IP;
4. Enter Recloser Control IP address and port. It can be checked in MMI:
Main menu -> Settings -> Comms -> PCI -> Ethernet
5. Click “Connect” button.

91
Figure 69
Wi-Fi interface connection

Operation
NOTE! Operation via PCI is possible in “Local” mode only. Current operation mode can be verified on the MMI.
NOTE! System status and logs are automatically downloaded to TELARM Lite after the RC5_4 is connected
via PCI.
After PCI connection is established, the following control commands are available from TELARM Lite:
• Trip/Close commands;
• Date and time synchronization;
• Control mode selection;
• Protection groups selection;
• Switching protection state or particular element ON/OFF

92
Figure 70
TELARM Lite control commands

TDI – TELARM Dispatcher Interface

Connection Establishment
It is possible to connect an external modem to be used for remote communication and control using TELARM
Dispatcher Interface (TDI) system.
To establish a TDI connection it is required to have:
A PC with
• Installed TELARM (can be provided by your local Tavrida Electric representative);
• Access to the internet.
Installed Internet Server on a PC with static IP
• Corresponding certificate in TELARM root folder.
Appropriate configuration for all objects mentioned above.

93
NOTE! Access to an internet server can be established via different ways which could be provided by Tavrida
Electric technical representatives. So far, all connections via TDI were provided completely or partially by
Tavrida Electric technical representatives.
Remote connection and operation are possible only in case the corresponding TELARM model is imported to
the computer and connection between the PC and the Recloser Control via Internet Server is established.
The communication system architecture for protection devices is shown in Figure 71.

Figure 71
TDI communication architecture

TELARM connection procedure over TDI is described below:


NOTE! The following actions will be successful in case the Internet server, the Recloser Control and the PC
settings are correct.
• Check that your PC has connection to Internet;
• In TELARM settings chose menu:
Main Menu -> Tools -> Options…
A popup window will appear
• Choose Communication settings;
• Set “Interface type” to Internet;
• Enter server address corresponding to Internet Server IP address.
• Select protection device in TELARM scheme and choose:
Main Menu -> On-Line -> Connect

Operation
NOTE! Operation via the TDI is possible in “Remote” mode only. Current operation mode can be verified on
the MMI.
After the TDI connection is established, the following commands can be executed from TELARM:
• Upload settings to the device (see chapter Settings):
Main Menu -> On-Line -> Upload settings to the device…
• Download settings from the device (see chapter Settings):
Main Menu -> On-Line -> Download settings from the device…
• Download logs:
Main Menu -> On-Line -> Download logs…
• Download system status:
Main Menu -> On-Line -> Download System Status…
• Trip:

94
Main Menu -> On-Line -> Trip…
• Close command:
Main Menu -> On-Line -> Close…
NOTE! After a Trip/Close command request, a popup window will appear (Error! Reference source not
found.)
Upon confirmation, the command will be sent to the controller.
• Switch protection state or particular element ON/OFF:
Main Menu -> On-Line -> Switch element On/Off -> Prot on…
• Synchronize date and time command:
Main Menu -> On-Line -> Synchronize date and time…
NOTE! After a Synchronize date and time command request, a popup window will appear (Error! Reference
source not found.).

8.6 Settings Configuration


Settings Downloading
To download settings:
1) Select the device on the TELARM Lite and establish the connection;
2) In the “Settings” tab, click the “Read all settings” button (Figure 72);
3) The successful downloading reading will appear in Connection log;

Figure 72
Settings downloading

95
System Settings Editing
System settings can be edited locally via the MMI or the PCI or remotely via the TDI interface.
System settings modifications using the MMI:
Main menu -> Settings -> System
To edit system settings locally using the PCI:
1) Select the device on the TELARM Lite and establish the connection;
2) In the “Settings” tab, click the “System” button;
3) “System settings” window will popup where it is possible to edit system settings (Figure 73).

Figure 73
System settings editing

Protection Settings Editing


Protection settings can be edited locally via the MMI or the PCI or remotely via the TDI interface.
Protection settings modifications using the MMI:
Main menu -> Settings -> Protection -> Group #
Protection settings can be changed in each protection group independently.
NOTE! To apply updated settings it is required to upload them to the controller. Uploading settings is described
in “Uploading protection settings”.
To edit protection settings locally (PCI):
1) Select the device on the TELARM Lite and establish the connection;
2) In the “Settings” tab, click the “Protection” button;
3) “Protection settings” window will popup where it is possible to edit settings, pick-up values and TCC curves
(Figure 74).

96
Figure 74
Protection settings editing

Communication Settings Editing


Communication settings can be edited locally via the MMI or the PCI or remotely via the TDI interface.
Communication settings modifications using the MMI:
Main menu -> Settings -> Comms
To edit Communication settings locally (PCI):
1) Select the device on the TELARM Lite and establish the connection;
2) In the “Settings” tab, click the “Communication” button;
3) “Communication settings” window will popup where it is possible to edit protocols and interfaces settings
(Figure 75).

97
Figure 75
Communication settings editing

Settings Uploading
To upload settings to the device:
1) Select the device on the TELARM Lite and establish the connection;
2) In the “Settings” tab, click the “Upload” button;
3) Select the settings do you want to upload in a pop-up wizard window (Figure 76).

98
Figure 76
Settings uploading wizard

99
9 Maintenance and
Troubleshooting
9.1 Maintenance
Tavrida Electric recloser is a maintenance free device. No regular maintenance operations are required during
the entire period of operation.

9.2 Troubleshooting
NOTE! In case the actions listed below do not help, contact your nearest Tavrida Electric representative.
WARNING! All replacement operations of the HV assembly equipment require power line de-energizing. All
necessary precautions (visible line gaps, temporary groundings etc.) should be applied.

PCI Connection Problems


NOTE! In case there are problems connecting to the device via the PCI interface check the following.
Possible reason Malfunction identification procedure Corrective action
Check that secondary power supply switches are in
In case the voltage at the secondary power supply
ON position
inputs of the RCM is absent, find the reasons of the
RCM is shutdown Check the voltage on power supply inputs of the
malfunction similar to “Loss of auxiliary supply”
RCM
described in paragraph labeled Loss of AC supply
The voltage shall be in the range 85-265 V.
Improper connection to Check the connection according to chapter 6.5.1 of
It is no malfunction
RC5 via PCI this guide
The most likely reason for malfunction in a control
RCM malfunction Replace the RCM
cubicle if no other reason was identified.

CPM Malfunction
NOTE! If it is possible to connect to the device via the PCI interface but the CPM doesn’t work properly, check
the following.
Possible reason Malfunction identification procedure Corrective action
Check if LEDs on the CPM are lit
Check if the screen lights but no readings are visible
Low or no contrast of the screen It is no malfunction
Push the button “Contrast” several times till the
readings become clearly visible
Download System settings from the RCM.
Check in section “Configuration” the CPM mode
The CPM mode is disabled via PCI Activate CPM mode via PCI
The CPM mode is disabled if the check box is not
ticked
Improper connection of plugs Provide reliable connection of the
Check the connection of the plug “1” and plug “19”
connecting the CPM and the RCM plugs “1” and “19”
Connect new CPM via new wiring to the RCM
RCM malfunction If the new CPM with new wiring doesn’t work properly Replace the RCM
it is most likely a malfunction of the RCM
If the new CPM with new wiring works properly, replace
Malfunction of wiring connecting the new wiring with the old one
Replace wiring
the RCM and the CPM If the new CPM doesn’t work properly with the old
wiring it is a wiring malfunction
If the new CPM works properly with the old wiring it is
CPM malfunction Replace the CPM
CPM malfunction

Active Malfunction
Replacing procedure for components is described in paragraph “9.3 Components Replacement Procedure”

RCM Fault
Possible reason Malfunction identification procedure Corrective action
Internal fault of the RCM. None Replace the RCM

Driver Fault
Possible reason Malfunction identification procedure Corrective action

101
Internal fault of the driver module. None Replace the RCM

IOM Fault
Possible reason Malfunction identification procedure Corrective action
Replace the IOM. If the new IOM does
Internal fault of the Input/Output module. None not work as well, replace the RCM
together with the IOM

RTU Short Circuit


Possible reason Malfunction identification procedure Corrective action
Disconnect the RTU from the power supply
Internal RTU short circuit Turn the RTU supply on via the MMI If signal Replace RTU
disappears short circuit is inside the RTU
If the signal does not disappear disconnect Plug “10”
Short circuit in the wires connecting RTU
If the signal disappears the short circuit is in the Replace the wiring
and RCM
wiring between the RTU and the RCM
RCM malfunction If the signal does not disappear the problem is in the
Replace the RCM
RCM

Figure 77
RTU power supply plug at RCM

NOTE! Wire numbers shall comply with the numbers of the socket.

Loss of AC Supply
Possible reason Malfunction identification procedure Corrective action
Check the voltage at the power supply input
Check the auxiliary voltage transformer
terminals (Figure 78) If the voltage is less than 85 V
Auxiliary voltage transformer malfunction and its wiring, fix the malfunctioning
it is a malfunction of the auxiliary voltage
component
transformer
If the voltage is between 85-265 V, check the
PSFM malfunction voltage at the RCM input (Figure 79) If the voltage Replace PSFM
is less than 85 V, the malfunction is in the PSFM
RCM malfunction In case the voltage at the RCM inputs is between
Replace the RCM
85-265 V it is an RCM malfunction

102
Figure 78
Auxiliary supply connections inside PSFM

Figure 79
Auxiliary supply connections at RCM

Battery Fault
Possible reason Malfunction identification procedure Corrective action
Check if the battery switch is in the ON position
Check that the battery is properly connected to the
RCM.
Plug “13” wires 1(+) and 2(-)
The battery is disconnected Check the wiring connection to the battery Turn the battery switch to ON position.
by the battery switch terminals. Provide reliable connection of wiring
“+” terminal = wire with “+” mark
“-” terminal = battery sensor
In case signal disappears you have located the
problem
Disconnect the wiring from the RCM.
Wiring malfunction Plug “13” wires 1(+) and 2(-) Replace the wiring assembly
Disconnect the wiring from the battery

103
Wires marked “+” and “-”
Check that switch and wiring is not short circuited or
broken.
NOTE! Reconnect the wiring properly after the tests
are done
If none of the above described reasons were
Internal fault of the battery Replace the battery
confirmed it is likely to be an internal battery fault

Figure 80
Battery and battery sensor inputs Plug “13” at RCM

NOTE! Wire numbers comply with the numbers of inputs in the plug.

Excessive Trip Time


Possible reason Malfunction identification procedure Corrective action
Outdoor Switching Module actuator coil Check if the reading in the malfunction log “Outdoor
Refer to 7.2.3.10
short circuit Switching Module coil short circuit” is present
Outdoor Switching Module actuator coil Check if the reading in malfunction log “Outdoor
Refer to 7.2.3.9
open circuit Switching Module coil open circuit” is present
Check if the malfunction “Driver is not ready” is
The “Excessive trip time malfunction”
Driver is not ready present
will disappear
Wait for 1 min and open the recloser
Switch off the RC5_4 and battery
Disconnect plug “8“ from the RCM
Disconnect wire 7 and 8 from plug “8”
Short circuit inputs 7 and 8 of plug “8” by a short
piece of insulated wire. See Figure 81
RCM malfunction Connect plug “8” to the RCM Replace the RCM
Switch on RC5_4 and battery
The indication of the main contact position should
change to “Open”
If the indication doesn’t change to “Open” the
malfunction is in the RCM
If RCM replacement doesn’t help:
Switch off the RC5_4 and the battery
Disconnect “8” plug from the RCM
Open circuit in Control Cable Replace the control cable
Disconnect the control cable from the RC5_4.
Disconnect the control cable from the Outdoor
Switching Module

104
Possible reason Malfunction identification procedure Corrective action
Short circuit pins 22 and 29 of the heavy duty
connector of the control cable (Outdoor Switching
Module side) as it is shown in Figure 82
Connect the control cable to the RC5_4
Connect plug “8” to the RCM
Switch on the RC5_4 and battery
The indication of the main contacts position should
change to “Open”
If the indication doesn’t change to “Open” the
malfunction is in the control cable
If none of the above described actions helped it is
Outdoor Switching Module malfunction Replace the Outdoor Switching Module
an Outdoor Switching Module malfunction

Figure 81
Main contact position indicator inputs at RCM

RC5_4 side interface OSM15_Al_1 side interface

5 7 29 22

Figure 82
Main contact position indicator inputs of heavy duty connector of the RC5_4 (left picture) and umbilical heavy duty connector
from the Outdoor Switching Module side (right picture)

NOTE! To short circuit the two pins of the connectors use two miniature crocodile clips and a wire.

105
Excessive Close Time
Possible reason Malfunction identification procedure Corrective action
Fix the “Outdoor Switching Module coil
Outdoor Switching Module coil Check if the reading in the malfunction log “Outdoor short circuit” (refer to 7.2.3.10) or
short/open circuit Switching Module coil short circuit” is present “Outdoor Switching Module coil open
circuit” (refer to 7.2.3.9) malfunction first
Check that the malfunction “Driver is not ready” is
present The “Excessive close time malfunction”
Driver is not ready
Wait for 1 min and open the Outdoor Switching will disappear
Module
Switch off the RC5_4 and battery
Disconnect plug „8“ from the RCM
The indication of main contact position should
RCM malfunction Replace the RCM
change to “Close”
If the indication doesn’t change to “Close” the
malfunction is in the RCM
Switch off the RC5_4 and the battery
Disconnect the control cable from the RC5_4.
Switch on the RC5_4 and battery
Short circuit in the wiring connecting the The indication of main contact position should
Replace the RC5_4
RCM with control cable change to “Close”
If the indication doesn’t change to “Close” the
malfunction is in the wiring connecting the RCM with
control cable
Switch off the RC5_4 and the battery
Connect the control cable to the RC5_4.
Disconnect the control cable from the Outdoor
Switching Module
Open circuit in Control Cable Switch on the RC5_4 and the battery Replace the control cable
The indication of the main contact position should
change to “Close”
If the indication doesn’t change to “Close” the
malfunction is in the control cable
If none of the above described actions helped it is
Outdoor Switching Module malfunction Replace the Outdoor Switching Module
an Outdoor Switching Module malfunction

Outdoor Switching Module Coil Isolated


Possible reason Malfunction identification procedure Corrective action
The Outdoor Switching Module is Check if the Outdoor Switching Module is switched Return the Outdoor Switching Module
switched off manually off manually. to “operated” position.
Wiring connecting drivers of the RCM
Check that wiring connecting the drivers of the RCM
and control cable are not properly Connect wiring properly
and control cable are properly connected
connected
Switch off the RC5_4 and the battery and wait for 2
minutes
Short circuit inputs 1 and 2 of plug “8” of the RCM
(Figure 83)
Switch on the RC5_4 and the battery
The RCM malfunction The malfunction readings should change to Replace the RCM
“Outdoor Switching Module coil short circuit”
In case the reading doesn’t change the malfunction
is in the RCM
NOTE! Remove the short circuiting wiring after the
test. Connect the wiring to the drivers properly.
Switch off the RC5_4 and the battery and wait for 2
minutes
Short circuit pins 1 and 3 of the RC5_4 heavy duty
connector as it is shown in Figure 84
Switch on the RC5_4 and the battery
Wiring assembly in the RC5_4 is open The malfunction readings should change to
Replace the RC5_4
circuited “Outdoor Switching Module coil short circuited”
If the reading doesn’t change the malfunction is in
wiring assembly between the RCM and control
cable
NOTE! Remove the short circuiting wiring after the
test.

106
Check that the heavy duty plugs of the control
cable, Outdoor Switching Module and RC5_4 are
Control Cable is not connected properly Connect control cable properly
visually not damaged
Check that the control cable is connected properly
Switch off the RC5_4 and the battery and wait for 2
minutes
Short circuit pins 37 and 39 of the heavy duty
connector of the control cable (Outdoor Switching
Module side) as it is shown in Figure 84
Switch on the RC5_4 and the battery The
Control Cable malfunction Replace the control cable
malfunction readings should change to “Outdoor
Switching Module coil short circuited”
If the reading doesn’t change the malfunction is in
the control cable
NOTE! Remove the short circuiting wiring after the
test.
If none of the above described actions helped it is
Outdoor Switching Module malfunction Replace the Outdoor Switching Module
an Outdoor Switching Module malfunction

Figure 83
Outdoor Switching Module actuator coil inputs at RCM

107
RC5_4 side interface OSM15/25_Al_1 side interface

1 3 39 37

Figure 84
Outdoor Switching Module actuator coil inputs of heavy duty connector of RC5_4 (left picture) and umbilical heavy duty
connector from Outdoor Switching Module side (right picture)

NOTE! To short circuit the two pins of the connectors use two miniature “crocodile” clips and a wire.

Outdoor Switching Module Actuator Coil Short Circuit


Possible reason Malfunction identification procedure Corrective action
Wiring connecting drivers of the RCM
Check that wiring connecting the drivers of the RCM
and control cable are not properly Connect wiring properly
and control cable are properly connected
connected
Switch off the RC5_4 and the battery and wait for 2
minutes
Short circuit inputs 1 and 2 of plug “8” of the RCM
(Figure 83)
Switch on the RC5_4 and the battery
The RCM malfunction The malfunction readings should change to Replace the RCM
“Outdoor Switching Module coil short circuit”
In case the reading doesn’t change the malfunction
is in the RCM
NOTE! Remove the short circuiting wiring after the
test. Connect the wiring to the drivers properly.
Switch off the RC5_4 and the battery and wait for 2
minutes
Short circuit pins 1 and 3 of the RC5_4 heavy duty
connector as it is shown in Figure 84
Switch on the RC5_4 and the battery
Wiring assembly in the RC5_4 is open The malfunction readings should change to
Replace the RC5_4
circuited “Outdoor Switching Module coil short circuited”
If the reading doesn’t change the malfunction is in
wiring assembly between the RCM and control
cable
NOTE! Remove the short circuiting wiring after the
test.
Check that the heavy duty plugs of the control
cable, Outdoor Switching Module and RC5_4 are
Control Cable is not connected properly Connect control cable properly
visually not damaged
Check that the control cable is connected properly
Switch off the RC5_4 and the battery and wait for 2
minutes
Short circuit pins 37 and 39 of the heavy duty
connector of the control cable (Outdoor Switching
Module side) as it is shown in Figure 84
Switch on the RC5_4 and the battery The
Control Cable malfunction Replace the control cable
malfunction readings should change to “Outdoor
Switching Module coil short circuited”
If the reading doesn’t change the malfunction is in
the control cable
NOTE! Remove the short circuiting wiring after the
test.
If none of the above described actions helped it is
Outdoor Switching Module malfunction Replace the Outdoor Switching Module
an Outdoor Switching Module malfunction

108
Driver Not Ready
Possible reason Malfunction identification procedure Corrective action
Wait for 60 s. If the signal disappears this warning is
Switching capacitors are still charging Not required
not associated with any malfunction.
In case this message has not disappeared and
Fix the “Outdoor Switching Module coil
Outdoor Switching Module actuator coil messages “Outdoor Switching Module coil short
short circuit” (refer to 7.2.3.10) or
short circuit or Outdoor Switching circuit” or “Outdoor Switching Module coil isolated”
“Outdoor Switching Module coil open
Module actuator coil isolated appear it is necessary to remove the reason of
circuit” (refer to 7.2.3.9)
these malfunctions.
If none of the above described actions helped it is
RCM malfunction Replace the RCM
an RCM malfunction

9.3 Components Replacement Procedure


RCM Replacement

Dismounting
1) Disconnect all wiring assemblies and the earthing wire connected to the RCM;
2) Unscrew four nuts fixing the RCM and remove the washers (Figure 85);
3) Pull the RCM from the fixing studs and take it out of the housing.

Figure 85
RCM with fixing nuts and washers (marked by arrows)

Installation
1) Take a spare RCM with appropriate protective, system and communication settings and put it on the fixing
studs and install washers;
2) Tighten four nuts fixing RCM;
3) Connect the wiring to the RCM according to the wiring assembly diagram (Figure 86).

109
Figure 86
RCM Wiring diagram

Plug numbering correspond to socket numbering.

CPM Replacement

Dismounting
1) Disconnect plug “19” from the CPM;
2) Unscrew six nuts fixing the CPM and remove the washers (Figure 87);
3) Pull the CPM from the fixing studs and take it out of the housing.

110
Figure 87
Nuts holding CPM on RC5_4 internal door

Installation
1) Install the CPM on the fixing studs;
2) Tighten six nuts fixing the CPM;
3) Connect plug “19” to the CPM.

PSFM Replacement

Dismounting
1) Make sure that there is no voltage on any inputs of the PSFM;
2) Disconnect all auxiliary supply wiring from the PSFM;
3) Disconnect plug “14” from the RCM;
4) Disconnect earthing wires;
5) Remove cable ties fixing cable “14”;
6) Unscrew four nuts fixing the PSFM and remove the washers;
7) Take the PSFM out of the housing.

111
Figure 88
PSFM fixing provisions

Installation
1) Install the new PSFM on the fixing studs inside the RC5_4;
2) Tighten four nuts with washers fixing the PSFM;
3) Connect plug “14” to RCM;
4) Connect one earthing wire from the control cubicle to the stud on the PSFM marked with the grounding sign.
Earthing wire from the PSFM connection to the stud on the control cubicle located above the PSFM;
5) In case you have a PSFM without a plug, use the old one. Numbers on the wires correspond to numbers
on plug “14”;
6) Connect the auxiliary supply wiring to the inputs of the PSFM.

Battery Replacement

Dismounting
1) Switch off the battery circuit breaker;
2) Disconnect the plug “13” from the RCM;
3) Disconnect the wires from the battery terminals - the minus terminal should be disconnected first;
4) Unscrew four bolts from the battery fixing plate (Figure 89);
5) Remove the Battery.

112
Figure 89
Battery fixing provisions

Installation
1) Switch off the battery circuit breaker;
2) Switch off auxiliary AC power supply circuit breaker;
3) Disconnect plug “13” from the RCM;
4) Mount the battery to the appropriate place;
5) Install battery fixing plate and fix it with four bolts (Figure 89);
6) Install plus terminal to the battery;
7) Connect plug “13” to the appropriate RCM socket;
8) Switch on auxiliary AC power supply circuit breaker;
9) Switch on the battery circuit breaker.

RC5_4 Replacement
RC5_4 dismounting and installation should be performed according to the Installation section of this document.
NOTE! To upload protection and communication settings to a newly installed Recloser Control, refer to chapter
6.6.1.3 and 6.6.2.3 correspondingly.

Outdoor Switching Module Replacement


The Outdoor Switching Module dismounting and installation should be performed according to the Installation
section of this document.
NOTE! Each Outdoor Switching Module is supplied with current and voltage sensor (CVCS) coefficients. If the
Outdoor Switching Module has been replaced, it is recommended to upload the correct CVCS coefficients into
the Recloser Control. To upload sensor coefficients refer to chapter 5.1.3 of this guide.

Mechanical Trip Hook Replacement


If the mechanical trip hook should be mounted or unmounted, the trip hook shaft should always be secured
against rotating with a 9 mm wrench as shown in Figure 90. The shaft has corresponding flats milled for the
wrench. The stop nut of the hook should be fixed or released with a 13 mm wrench.
NOTE! Rotation of the mechanical trip hook shaft inside of switching module’s tank during dismounting or
installation might lead to malfunction and inability to perform close/open operations! Such cases are not
covered by warranty!

113
Figure 90
Securing the trip hook shaft against rotation

114
10 Product Coding
10.1Recloser Coding
Rec25_Al1_5p(P1…P20)

Product group

Outdoor Switching Module type

Recloser Control type


Table 86 – Recloser coding description
Parameter
Parameter Applicable options Code extended Code
description
Default C.0 1
P1 Customization
Other – Contact Tavrida Electric representative … …
OSM with Rogowski coils and 220V actuator coil, version 5 25TP-ROG220V5 1
P2 OSM type OSM with Rogowski coils as current sensors and 220V actuator coil,
25TP-ROG220V6 2
version 6 (with increased 3I0 measurement accuracy)
According to customization – contact Tavrida Electric representative L.Custom 1
English MMI, stickers, nameplates for RC and OSM EN15/EN25 2
Portuguese MMI, stickers, nameplates for RC and OSM PT15/PT25 3
P3 Language English MMI, stickers EN 4
Portuguese MMI, stickers PT 5
Spanish MMI, stickers ESP 6
Spanish MMI, stickers, nameplates for RC and OSM ESP15/ESP25 7
P4 Controller type Recloser control cubicle RC5_4 RC5.4A 1
2.72.027 2.72.027-6.45-4.02 1
2.74.004 2.74.004-6.45-4.02 2
2.75.021 2.75.021-6.45-4.02 3
2.75.030 2.75.030-6.45-4.02 4
P5 Firmware version
2.75.042 2.75.042-6.45-4.02 5
2.76.030 2.76.030-6.46-4.02 7
2.75.045 2.75.045-6.46-4.02 8
2.75.047 2.75.047-6.46-4.02 9
Without mounting kit SURF 1
Standard mounting kit without pole interface part 10 2
Mounting kit with pole interface part for M16 studs 10M18 3
Mounting kit with pole interface part for M20 studs 10M22 4
Mounting kit with pole interface part for M20 studs for through the pole
10M22TH 5
installation
Mounting kit with M16 interface bracket for around the pole installation
10M18AR500 6
with 500 mm U-profiles fixed with 450 mm M16 studs
P6 OSM mounting kit Mounting kit with M20 interface bracket for around the pole installation
10M22AR700 7
with 700 mm U-profiles fixed with 450 mm M20 studs
Mounting kit with M16 interface bracket for around the pole installation
10M18AR500M16 8
with 500 mm U-profiles bolted to interface bracket and 450 mm M16 studs
Mounting kit with M20 interface bracket for around the pole installation
10M22AR700M20 9
with 700 mm U-profiles bolted to interface bracket and 450 mm M20 studs
Substation mounting kit with adjustable height SUB A
Mounting kit with pole interface part for M16 studs for through the pole
10M18TH B
installation
Without ATMK.0 1
Holder for cast resin VT CR 2
Holder for cast resin VT for around the pole installation with two 500 mm
CRAR500M16 3
U-profiles and M16 studs
P7 AT mounting kit Holder for cast resin VT for around the pole installation with two 700 mm
CRAR700M20 4
U-profiles and M20 studs
Two holders for cast resin VT for around the pole installation with two
CR-CRAR500M16 5
500 mm U-profiles and M16 studs
Two holders for cast resin VT for around the pole installation with two
CR-CRAR700M20 6
700 mm U-profiles and M20 studs

116
Two holders for cast resin VT for around the pole installation with four
2CRAR500M16 7
500 mm U-profiles and M16 studs
Two holders for cast resin VT for around the pole installation with four
2CRAR700M20 8
700 mm U-profiles and M20 studs
Cast resin VT installation kit for substation mounting kit CR-SUB 9
Oil power transformer installation kit for substation mounting kit OPT-SUB A
Cast resin CT installation kit for substation mounting kit CT-SUB B
Holder for cast resin VT for through the pole installation with base holder
CRTH22 C
for M20 studs and 700 mm U-profile
Holder for cast resin VT for through the pole installation with base holder
CRTHM20 D
for M20 studs, 700 mm U-profile and two M20 studs
Two holders for cast resin VT for through the pole installation with base
2CRTH22 E
holder for M20 studs and two 700 mm U-profile
Two holders for cast resin VT for through the pole installation with base
2CRTHM20 F
holder for M20 studs, two 700 mm U-profile and M20 studs
CRVT mounting kit for single lift installation CRSL G
2x CRVT mounting kit for single lift installation 2CRSL H
5 meters with protective conduit 5mAL1DD.5 1
7 meters with protective conduit 7mAL1DD.5 2
12 meters with protective conduit 12mAL1DD.5 3
20 meters with protective conduit 20mAL1DD.5 4
P8 Control cable No control cable provided CC.0 5
5 meters 5mAL1DD.5N 6
7 meters 7mAL1DD.5N 7
12 meters 12mAL1DD.5N 8
20 meters 20mAL1DD.5N 9
Without CON.0 1
Two hole NEMA connector N2Al 2
Two hole Burndy® connector N2B 3
Primary connector Four hole NEMA connector N4Al 4
P9
type Clamp type aerial connector with bird protection Aerial-BG 5
Two hole NEMA connector with bird protection N2Al-BG 6
Four hole NEMA connector with bird protection N4Al-BG 7
U-bolts of clamp type kit with fasteners UBOLT 8
Without EA.0 1
Earthing
P10 According to customization – contact Tavrida Electric representative EA.Custom 2
accessories
Two cross pressure terminals for 25–70 mm2 wire 2CPT25-70x13 3
Without PC.0 1
According to customization – contact Tavrida Electric representative PC.Custom 2
5 meters double core 1.5 mm2 cable with 6 mm ring lug at VT side and
5mx2x1.5xR6S 3
crimp sleeve lug at RC side
2
7 meters double core 1.5 mm cable with 6 mm ring lug at VT side and
7mx2x1.5xR6S 4
crimp sleeve lug at RC side
12 meters double core 1.5 mm2 cable with 6 mm ring lug at VT side and
12mx2x1.5xR6S 5
crimp sleeve lug at RC side
20 meters double core 1.5 mm2 cable with 6 mm ring lug at VT side and
20mx2x1.5xR6S 6
crimp sleeve lug at RC side
2
Two 5 meters double core 1.5 mm cable with 6 mm ring lug at VT side
2x5mx2x1.5xR6S 7
and crimp sleeve lug at RC side
P11 Power cable Two 7 meters double core 1.5 mm2 cable with 6 mm ring lug at VT side
2x7mx2x1.5xR6S 8
and crimp sleeve lug at RC side
2
Two 12 meters double core 1.5 mm cable with 6 mm ring lug at VT side
2x12mx2x1.5xR6S 9
and crimp sleeve lug at RC side
Two 20 meters double core 1.5 mm2 cable with 6 mm ring lug at VT side
2x20mx2x1.5xR6S A
and crimp sleeve lug at RC side
2
4.5 meters triple core 1.5 mm cable with 6 mm ring lug at VT side and
4.5mx3x1.5xR6S B
crimp sleeve lug at RC side
2
11 meters triple core 1.5 mm cable with 6 mm ring lug at VT side and
11mx3x1.5xR6S C
crimp sleeve lug at RC side
5 meters triple core 2.5 mm2 cable with 6 mm ring lug at VT side and
5mx3x2.5xR6S D
crimp sleeve lug at RC side
2
7 meters triple core 2.5 mm cable with 6 mm ring lug at VT side and
7mx3x2.5xR6S E
crimp sleeve lug at RC side

117
12 meters triple core 2.5 mm2 cable with 6 mm ring lug at VT side and
12mx3x2.5xR6S F
crimp sleeve lug at RC side
2
20 meters triple core 2.5 mm cable with 6 mm ring lug at VT side and
20mx3x2.5xR6S G
crimp sleeve lug at RC side
5 meters triple core 2.5 mm2 cable with 6 mm ring lug at VT side and
5mx3x2.5xR6CNL H
Cnlinko® YM20 connector at RC side
7 meters triple core 2.5 mm2 cable with 6 mm ring lug at VT side and
7mx3x2.5xR6CNL J
Cnlinko® YM20 connector at RC side
2
12 meters triple core 2.5 mm cable with 6 mm ring lug at VT side and
12mx3x2.5xR6CNL K
Cnlinko® YM20 connector at RC side
20 meters triple core 2.5 mm2 cable with 6 mm ring lug at VT side and
20mx3x2.5xR6CNL L
Cnlinko® YM20 connector at RC side
Without RCMK.0 1
According to customization – contact Tavrida Electric representative RCMK.Custom 2
800 mm U-profiles fastened to RC with M20 fasteners for around the pole
AR800 3
installation with 1000 mm M16 studs
P12 RC mounting kit RC installation kit for substation mounting kit SUB1 4
500 mm U-profiles fastened to RC with M20 fasteners for around the pole
AR500 5
installation with 450mm M16 studs
Two 450 mm M20 studs TH20 6
Two 450 mm M16 studs TH18 7
Without B.0 1
Battery ready B-R 2
P13 Battery type –15 degrees rated battery B-15 5
–25 degrees rated battery B-25 3
–40 degrees rated battery B-40 4
Without IO.0 1
Input-output
P14 12–60 VDC IO.60 2
module
110–250 VDC IO.220 3
Without E.0 1
P15 Ethernet Wired Ethernet (RJ45 interface) E.W 2
Optical Ethernet E.Op 3
Without LWA.0 1
Local wireless
P16 Bluetooth BT 2
access
Wi-Fi WF 3
Socket wiring without socket holder cover PO.0 1
Socket wiring with blank socket holder cover PO.Blank 2
EU socket connected to AC1 power input EU 3
P17 Power outlet
Two NBR sockets 2NBR 4
Socket wiring with associated plate for two NBR sockets For2NBR 5
According to customization – contact Tavrida Electric representative PO.Custom 6
Without CL.0 1
P18 Cabinet light
LED strip LED5V 2
Without IDAE.0 1
Internal door According to customization – contact Tavrida Electric representative IDAE.Custom 2
P19 additional
equipment Blank plate IDAE.Blank 3
Kit of C-class LVSA wit In=10 kA for AC1 power input 2xLVSA-C10 4
Without BP.0 1
According to customization – contact Tavrida Electric representative BP.Custom 2
Blank plate BP.Blank 3
Bottom interface
P20 Plate with two glands for d = 4.5–10 mm 2xG4.5-10 4
plate
Plate with two glands for d = 4.5–10 mm and wireless module plug LWA-2xG4.5-10 5
Plate with two Cnlinko® YM20 connectors 2xYM20.M3 6
Plate with two Cnlinko® YM20 connectors and wireless module plug LWA-2xYM20.M3 7

118
10.2Recloser Components Coding
Outdoor Switching Module Coding
OSM15_Al_1(P1_P2)

Outdoor switching module

Rated voltage, kV

Tank material

Switching module type

Table 87 – Outdoor Switching Module coding description


Parameter Parameter description Applicable options Code extended
OSM without intermediate unit, connectors and mounting
5-SP
hardware in individual packing, version 5
P1 OSM modification
OSM without intermediate unit, connectors and mounting
6
hardware in individual packing, version 6
None 0
P2 Primary connector type Aerial lugs A
Two-hole NEMA pads NEMA2

Each Outdoor Switching Module has the following nameplates:


• Serial number plate
• Parameters nameplate

Figure 91
Outdoor Switching Module nameplate and serial number plate

The serial number plate contains information about the Outdoor Switching Module type and serial number.
The nameplate describes Outdoor Switching Module technical parameters.

119
Recloser Control Coding
RC5_4M(P1…P12)

Table 88 – Recloser Control coding description


Parameter
Parameter Applicable options Code extended Code
description
Default C.0 1
P1 Customization
Other – Contact Tavrida Electric representative … …
English MMI, stickers, nameplates RC.EN 1
Portuguese MMI, stickers, nameplates RC.PT 2
Spanish MMI, stickers, nameplates RC.ESP 7
P2 Language English MMI, stickers EN 3
Portuguese MMI, stickers PT 4
Spanish MMI, stickers ESP 6
According to customization – contact Tavrida Electric representative L.Custom 5
P3 Controller type Recloser control cubicle RC5_4 RC5.4A 1
2.72.027 2.72.027-6.45-4.02 1
2.74.004 2.74.004-6.45-4.02 2
P4 Firmware version Factory default firmware FV.D 3
2.76.030 2.76.030-6.46-4.02 4
2.75.045 2.75.045-6.46-4.02 5
Without B.0 1
Battery ready B-R 2
P5 Battery type –15 degrees rated battery B-15 5
–25 degrees rated battery B-25 3
–40 degrees rated battery B-40 4
Without IO.0 1
Input-output
P6 12–60 VDC IO.60 2
module
110–250 VDC IO.220 3
Without E.0 1
P7 Ethernet Wired Ethernet (RJ45 interface) E.W 2
Optical Ethernet E.Op 4
Without LWA.0 1
Local wireless
P8 Bluetooth BT 2
access
Wi-Fi WF 4
Socket wiring without socket holder cover PO.0 1
Socket wiring with blank socket holder cover PO.Blank 2
P9 Power outlet EU socket connected to AC1 power input EU 3
Two NBR sockets 2NBR 4
Socket wiring with associated plate for two NBR sockets For2NBR 5
Without CL.0 1
P10 Cabinet light
LED strip LED5V 2
Without IDAE.0 1
Internal door According to customization – contact Tavrida Electric representative IDAE.Custom 2
P11 additional
equipment Blank plate IDAE.Blank 3
Kit of C-class LVSA wit In=10 kA for AC1 power input 2xLVSA-C10 4
Without BP.0 1
According to customization – contact Tavrida Electric representative BP.Custom 2
Blank plate BP.Blank 3
Bottom interface
P12 Plate with two glands for d = 4.5–10 mm 2xG4.5-10 4
plate
Plate with two glands for d = 4.5–10 mm and wireless module plug LWA-2xG4.5-10 5
Plate with two Cnlinko® YM20 connectors 2xYM20.M3 6
Plate with two Cnlinko® YM20 connectors and wireless module plug LWA-2xYM20.M3 7

Each Recloser Control has adhesive serial number plate and riveted stainless steel nameplate on the internal
door. The nameplates contain information about the Recloser Control type, serial number, ratings and
manufacturing date.

120
Figure 92
Nameplate and serial number plate of Recloser Con-
Figure 93
trol Recloser Control nameplate placement

Control Cable Coding


TES_RecParamKit_ControlCableKit_Sm5DD.5 (P1_P2_P3)

Table 89 – Control cable coding description


Parameter Parameter description Applicable options Code extended
5 meters 5
7 meters 7
P1 Control cable length
12 meters 12
20 meters 20
Cable enclosed with conduit A
P2 Design
Outdoor UV-resistant cable N
For installation to final product OEM
P3 Delivery type
For delivery in individual package SP

Each Control cable has a colored tube with serial number.

Figure 94
Control cable tie with serial number

121
11 Appendices
Appendix 1. Type Tests
Rec15_Al1_5p Type Tests
Standard Chapter Test name Test center name Test report
IEEE C37.60-2012 6.2.2 Power-frequency withstand voltage test (wet) KEMA 1487-15
IEEE C37.60-2012 6.2.6.1 Power-frequency withstand voltage test (dry) KEMA 1487-15
IEEE C37.60-2012 6.2.6.2 Lightning impulse withstand voltage test KEMA 1487-15
IEEE C37.60-2005 6.3.2.1 Load switching tests PowerTech PowerTech_18930-26
Measurement of the resistance of the main
IEEE C37.60-2012 6.4 KEMA 1488-15
circuit
IEEE C37.60-2012 6.5 Temperature-rise tests KEMA 1488-15
Temperature-rise tests of the auxiliary and
IEEE C37.60-2012 6.5.5 KEMA 1488-15
control equipment
Short time withstand current and peak
IEEE C37.60-2012 6.6 KEMA 2268-15
withstand current tests
IEEE C37.60-2003 6.7 DC withstand voltage test PowerTech PowerTech_18490-27
Transformer magnetizing current switching
IEEE C37.74-2003 6.3.2.3 PowerTech PowerTech_18930-26
tests
IEEE C37.60-2012 6.106 Partial discharge tests KEMA 1487-15
IEEE C37.60-2012 6.101 Line charging and cable charging current tests KEMA 2422-15
IEEE C37.60-2012 6.102 Making current tests KEMA 2268-15
IEEE C37.60-2012 6.103 Rated symmetrical interrupting KEMA 2268-15
IEEE C37.60-2012 6.104 Critical current tests KEMA 2268-15
IEEE C37.60-2012 6.105 Minimum tripping current tests KEMA 1474-15
IEEE C37.60-2012 6.108 Time-current tests KEMA 1474-15
IEEE C37.60-2012 6.109 Mechanical duty tests KEMA 2424-15
Control electronic elements surge withstand
IEEE C37.60-2003 6.111 PowerTech PowerTech_18490-27
capability tests
IEEE C37.60-2012 6.111.2 Oscillatory and fast transient surge tests KEMA 1475-15
IEC 60068-2-1 - Cold test - operational KEMA 1469-15
IEC 60068-2-2 - Dry heat test - operational KEMA 1469-15
IEC 60068-2-30 - Damp heat cyclic test KEMA 1469-15
Simulated solar radiation at ground level and
IEC 60068-2-5 - KEMA 1470-15
guidance for solar radiation testing
IEC 60664 Lightning impulse withstand voltage test on
- KEMA 1475-15
IEC 60255-5 auxiliary and control circuits
Power-frequency withstand voltage test on
IEC 62271-1 6.10.6 KEMA 1475-15
auxiliary and control circuits

Rec25_Al1_5p Type Tests


Standard Chapter Test name Test center name Test report
IEEE C37.60-2012 6.2.2 Power-frequency withstand voltage test (wet) KEMA 1490-15
IEEE C37.60-2012 6.2.6.1 Power-frequency withstand voltage test (dry) KEMA 1490-15
IEEE C37.60-2012 6.2.6.2 Lightning impulse withstand voltage test KEMA 1490-15
CESI_A8028049
IEEE C37.60-2005 6.3.2.1 Load switching tests CESI
CESI_A9007127
IEEE C37.60-2012 6.106 Partial discharge tests KEMA 1490-15
Measurement of the resistance of the main
IEEE C37.60-2012 6.4 KEMA 1491-15
circuit
IEEE C37.60-2012 6.5 Temperature-rise tests KEMA 1491-15
Short time withstand current and peak
IEEE C37.60-2012 6.6 KEMA 2269-15
withstand current tests
Power-frequency withstand voltage test on
IEEE C37.60-2003 6.10.6 CESI CESI_A8034569
auxiliary and control circuits
IEEE C37.60-2012 6.101 Line charging and cable charging current tests KEMA 2423-15
IEEE C37.60-2012 6.102 Making current tests KEMA 2269-15
IEEE C37.60-2012 6.103 Rated symmetrical interrupting KEMA 2269-15
IEEE C37.60-2012 6.104 Critical current tests KEMA 2269-15

123
Standard Chapter Test name Test center name Test report
IEEE C37.60-2012 6.105 Minimum tripping current tests KEMA 1471-15
KEMA Final TDT 1510-
IEEE C37.60-2003 6.108 Time-current tests KEMA
10 V1
IEEE C37.60-2012 6.109 Mechanical duty tests KEMA 2425-15
IEEE C37.60-2012 6.111.3 Simulated surge arrester operation test KEMA 1492-15
IEC 60664 Lightning impulse withstand voltage test on
- CESI CESI_A8034569
IEC 60255-5 auxiliary and control circuits
IEC 60068-2-1 - Cold test - operational KEMA 1472-15
IEC 60068-2-2 - Dry heat test - operational KEMA 1472-15
IEC 60068-2-30 - Damp heat cyclic test KEMA 1472-15
Simulated solar radiation at ground level and
IEC 60068-2-5 - KEMA 1473-15
guidance for solar radiation testing
KEMA Final TIC 1471-
KEMA
IEC 60529 - Enclosure protection test 12 V1
TEL TestLab EDRTL_216-2013E
KEMA Final TIC 1471-
IEC 60870-5-104 Ed.2 - Communication protocol test KEMA 12 V1
KEMA 12-01304
KEMA Final TIC 1471-
EDP_07-0969 rev 1F - Battery test KEMA
12 V1
ESKOM specification - Pollution test (KIPTS) KIPTS KIPTS 31-07-2010
KEMA Final TDT 2138-
IEC 60255-22-2 - Electrostatic discharge KEMA
10
Disturbance of the radiated electromagnetic KEMA Final TDT 2138-
IEC 60255-22-3 - KEMA
field 10
IEC 60255-21-1 - Vibration, shock, bump and seismic test INPE laboratório MSQL-7420/2018
R&D CENTER at
IEC 62271-214 6.2.7 Internal Arc Classification (IAC) 48–2018
FGC UES

Components Type Tests


Standard Chapter Component Test name Test center name Test report
IEEE C37.60-2012 6.7 OSM15_Al Verification of the protection KEMA 1489-15
IEC 60529 - RecUnit_RC5 Verification of the protection INPE MSQL-6965/2018
X-radiation test procedure for
IEEE C37.60-2012 6.11 VI_25 KEMA 1493-15
vacuum interrupters

124
Appendix 2. Spare Parts and Accessories
Spare parts and accessories can be ordered separately in case of theft or damage. Contact your local sales
representative to choose the option suitable for you.
Part name Description Package type Dimensions, mm Mass, kg
OSM15_Al_1 Outdoor switching module Cardboard box 810x810x890 82
OSM25_Al_1 Outdoor switching module Cardboard box 810x810x890 86
RecUnit_Umbilical_4 Control cable Cardboard box 550x400x200 up to 19

RecUnit_RC5_4M Recloser control cubicle Cardboard box 935x580x445 45

Connectors for external conductors and


RecKit_Connector_6(SP) Cardboard box 194x127x75 2.2
OSM terminals

Rubber insulators for external wires


RecKit_Ins_1(SP) Cardboard box 255x185x100 0.5
connectors of OSM

Two-hole connectors for connection of


RecKit_Connector_5(NEMA2-SP) Cardboard box 255x185x100 2.7
NEMA cable lug to OSM terminal

Rubber insulators for two-hole NEMA and


RecKit_Ins_3(NEMA2_SP) Cardboard box 255x185x100 0.6
OSM terminals connections

Four-hole connectors for connection of


RecKit_Connector_5(NEMA4-SP) Cardboard box 255x185x100 3.1
NEMA cable lug to OSM terminal

Rubber insulators for four-hole NEMA and


RecKit_Ins_3(NEMA4_SP) Cardboard box 407x259x136 2.2
OSM terminals connections

Control module suitable for RC5 recloser


CM_RCM_1M Cardboard box 400x330x210 10
control cubicle
Input/Output module 24/60 VDC suitable for
EA_IntBoard_IOM-04 Cardboard box 316x196x56 0.5
RC5 recloser control cubicle
Input/Output module 100/220 VDC suitable
EA_IntBoard_IOM-03 Cardboard box 316x196x56 0.5
for RC5 recloser control cubicle
Power supply filter module suitable for
EA_Filter_PSFM-2 Cardboard box 202x180x87 1.5
RC5_4 recloser control cubicle
Control panel in English suitable for RC5
EA_MMI_CPM-1(EN) Cardboard box 300x250x35 2
recloser control cubicle
Control panel in Portuguese suitable for
EA_MMI_CPM-1(PT) Cardboard box 300x250x35 2
RC5 recloser control cubicle
Battery for recloser uninterruptable power
Rechargeable Battery Cardboard box – –
supply
Kit for organizing Ethernet in RC5 (USB-
RecParamKit_EthernetKit_E.W Plastic bag – 0.1
Ethernet module)
Kit for organizing wireless access with RC5
RecParamKit_LWAKit_LWA.BT Plastic bag – 0.1
(Bluetooth)
RecKit_AntiVandalHousing_2 Anti-vandal housing for RC5 Galvanized steel box 1395x1145x800 –

125
Appendix 3. Outdoor Switching Module Drawings

Figure 95
Dimensions of OSM15_Al_1(5) with aerial connectors

Figure 96
Dimensions of OSM15_Al_1(5) with NEMA connectors

126
Figure 97
Dimensions of OSM25_Al_1(5) with aerial connectors

Figure 98
Dimensions of OSM25_Al_1(5) with NEMA connectors

127
Appendix 4. Recloser Control Drawings

Figure 99
Dimensions of RC5_4

128
Appendix 5. Control Cable Drawings

Figure 100
Dimensions of control cable

Table 90 – Control cable characteristics


Part number L, m Mass, kg
Umbilical_5(5) 5 5
Umbilical_5(7) 7 6.5
Umbilical_5(12) 12 11.2
Umbilical_5(20) 20 18.6

129
Appendix 6. Package Drawings

Figure 101
Dimensions of pole mounted recloser package

Figure 102
Placement of pole mounted recloser components in a box

130
Figure 103
Dimensions of substation recloser package

Figure 104
Placement of substation recloser components in a box

131
Appendix 7. Mounting Kits Drawings

Figure 105
Dimensions of standard OSM mounting kit arrangement for front installation

132
Figure 106
Dimensions of standard OSM mounting kit arrangement for lateral installation

133
Figure 107
Dimensions of interface bracket

134
Figure 108
Dimensions of OSM mounting kit with M16 pole interface (front installation)

135
Figure 109
Dimensions of OSM mounting kit with M16 pole interface (lateral installation)

136
Figure 110
Dimensions of OSM mounting kit with M20 pole interface (front installation)

137
Figure 111
Dimensions of OSM mounting kit with M20 pole interface (lateral installation)

138
Figure 112
Dimensions of OSM mounting kit for installation through the pole (front installation)

139
Figure 113
Dimensions of OSM mounting kit for installation through the pole (lateral installation)

140
Figure 114
Dimensions of OSM mounting kit for installation around the pole (front installation):
M16 interface bracket, 500 mm U-profiles, M16 threaded rods

141
Figure 115
Dimensions of OSM mounting kit for installation around the pole (lateral installation):
M16 interface bracket, 500 mm U-profiles, M16 threaded rods

142
Figure 116
Dimensions of OSM mounting kit for installation around the pole (front installation):
M20 interface bracket, 700 mm U-profiles, M20 threaded rods

143
Figure 117
Dimsensions of OSM mounting kit for installation around the pole (lateral installation):
M20 interface bracket, 700 mm U-profiles, M20 threaded rods

144
Figure 118
Dimesnsions of OSM mounting kit for installation around the pole (front installation):
M16 interface bracket, 500 mm U-profiles, M16 threaded rods, M16 bolts

145
Figure 119
Dimensions of OSM mounting kit for installation around the pole (lateral installation):
M16 interface bracket, 500 mm U-profiles, M16 threaded rods, M16 bolts

146
Figure 120
Dimensions of OSM mounting kit for installation around the pole (front installation):
M20 interface bracket, 700 mm U-profiles, M20 threaded rods, M20 bolts

147
Figure 121
Dimensions of OSM mounting kit for installation around the pole (lateral installation):
M20 interface bracket, 700 mm U-profiles, M20 threaded rods, M20 bolts

148
Figure 122
Dimensions of OSM substation mounting kit

149
Figure 123
Dimensions of RC mounting kit for around the pole installation:
500 mm U-profiles, 450 mm M16 threaded rods

150
Figure 124
Dimensions of RC mounting kit for around the pole installation:
800 mm U-profiles, 1000 mm M16 threaded rods

151
Figure 125
Dimensions of RC mounting kit for through the pole installation

152
Figure 126
Dimensions of RC substation mounting kit

153
Figure 127
Dimensions of VT mounting kit:
One VT holder

154
Figure 128
Dimensions of VT mounting kit:
One VT holder, two 500 mm U-profiles and M16 threaded rods

Figure 129
Dimensions of VT mounting kit:
One VT holder, two 700 mm U-profiles and M20 threaded rods

155
Figure 130
Dimensions of VT pole mounting kit:
One VT holder, one 700 mm U-profile, base holder

Figure 131
Dimensions of VT pole mounting kit:
One VT holder, one 700 mm U-profile, base holder, M20 threaded rods

156
Figure 132
Dimensions of VT mounting kit:
Two VT holders, two 500 mm U-profiles and M16 threaded rods

157
Figure 133
Dimensions of VT mounting kit:
Two VT holders, two 700 mm U-profiles and M20 threaded rods

158
Figure 134
Dimensions of VT mounting kit:
Two VT holders, four 500 mm U-profiles and M16 threaded rods

159
Figure 135
Dimensions of VT mounting kit:
Two VT holders, four 700 mm U-profiles and M20 threaded rods

Figure 136
Dimenssions of VT pole mounting kit:
Two VT holders, two 700 mm U-profiles, base holder

160
Figure 137
Dimensions of VT pole mounting kit:
Two VT holders, two 700 mm U-profiles, base holder, M20 threaded rods

Figure 138
Dimensions of VT substation mounting kit:
Holder for cast resin VT

161
Figure 139
Dimensions of VT substation mounting kit:
Holder for oil power transformer

Figure 140
Dimensions of CT substation mounting kit

162
Appendix 8. Connectors Drawings

Figure 141
Dimensions of aerial connector

163
Figure 142
Dimensions of bird guards for aerial connector

164
Figure 143
Dimensions of two-hole NEMA connector

165
Figure 144
Dimensions of bird guards for two-hole NEMA connector

166
Figure 145
Dimensions of four-hole NEMA connector

167
Figure 146
Dimensions of bird guards for four-hole NEMA connector

168
Figure 147
Dimensions of Burndy® NEMA connector

169
Appendix 9. Recloser Control Wiring Diagram

Figure 148
RC5_4 wiring diagram

170
List of changes
Document version Change date Scope of change Reason of change
1.0 14.01.2019 Initial version of document Parametric recloser introduction
− Spanish localization added
− LED strip description added Functionality introduction and
2.0 25.03.2019
− Auxiliary supply bayonet connector description added document improvement
− RC mounting kit for through the pole installation added
− HL blocking mode added to OC and EF protections
− VRC blocking mode added to LS protection
− Various measurements and protections value range
Functionality introduction and
3.0 26.11.2019 and default settings changes
document improvement
− Wi-Fi module added
− Optical Ethernet module added
− ABR pushbutton customization added
− TELARM Basic replaced with TELARM Lite
− Vibration type test added
Functionality introduction and
4.0 08.02.2021 − ANSI codes reference added
document improvement
− Trip hook dismounting/installation procedure added
− Anti-vandal housing added

171

You might also like