Ieee 3004.11
Ieee 3004.11
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                                                                        IEEE Std 3004.11-2019
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
            Abstract: Covered in this recommended practice is the protection of bus and switchgear used in
            industrial and commercial power systems. Also provided are fault protection and isolation strategies
            for the substation bus and switchgear, including the bus, circuit breakers, fuses, disconnecting
            devices, transformers, and the structures on which they are mounted.
            Keywords: arc flash, arc flash protection, differential protection, double-ended substation, high
            impedance bus differential relay, IEEE 3004.11™, percentage differential relay, tie circuit breaker
            IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics Engineers,
            Incorporated.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
            Important Notices and Disclaimers Concerning IEEE Standards Documents
            IEEE documents are made available for use subject to important notices and legal disclaimers. These notices
            and disclaimers, or a reference to this page, appear in all standards and may be found under the heading
            “Important Notices and Disclaimers Concerning IEEE Standards Documents.” They can also be obtained on
            request from IEEE or viewed at http://standards.ieee.org/IPR/disclaimers.html.
            IEEE Standards do not guarantee or ensure safety, security, health, or environmental protection, or ensure
            against interference with or from other devices or networks. Implementers and users of IEEE Standards
            documents are responsible for determining and complying with all appropriate safety, security, environmental,
            health, and interference protection practices and all applicable laws and regulations.
            IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and
            expressly disclaims all warranties (express, implied and statutory) not included in this or any other document
            relating to the standard, including, but not limited to, the warranties of: merchantability; fitness for a particular
            purpose; non-infringement; and quality, accuracy, effectiveness, currency, or completeness of material. In
            addition, IEEE disclaims any and all conditions relating to: results; and workmanlike effort. IEEE standards
            documents are supplied “AS IS” and “WITH ALL FAULTS.”
            Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there
            are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to
            the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved and
            issued is subject to change brought about through developments in the state of the art and comments received
            from users of the standard.
            In publishing and making its standards available, IEEE is not suggesting or rendering professional or other
            services for, or on behalf of, any person or entity nor is IEEE undertaking to perform any duty owed by any
            other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his or
            her own independent judgment in the exercise of reasonable care in any given circumstances or, as appropriate,
            seek the advice of a competent professional in determining the appropriateness of a given IEEE standard.
            IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,
            EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO:
            PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS;
            OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY,
            WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR
            OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE
            UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND
            REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE.
                                                                          3
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
            Translations
            The IEEE consensus development process involves the review of documents in English only. In the event that
            an IEEE standard is translated, only the English version published by IEEE should be considered the approved
            IEEE standard.
Official statements
            A statement, written or oral, that is not processed in accordance with the IEEE SA Standards Board Operations
            Manual shall not be considered or inferred to be the official position of IEEE or any of its committees and shall
            not be considered to be, or be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or
            educational courses, an individual presenting information on IEEE standards shall make it clear that his or her
            views should be considered the personal views of that individual rather than the formal position of IEEE.
            Comments on standards
            Comments for revision of IEEE Standards documents are welcome from any interested party, regardless
            of membership affiliation with IEEE. However, IEEE does not provide consulting information or advice
            pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a
            proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a
            consensus of concerned interests, it is important that any responses to comments and questions also receive
            the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and Standards
            Coordinating Committees are not able to provide an instant response to comments or questions except in
            those cases where the matter has previously been addressed. For the same reason, IEEE does not respond to
            interpretation requests. Any person who would like to participate in revisions to an IEEE standard is welcome
            to join the relevant IEEE working group.
Copyrights
            IEEE draft and approved standards are copyrighted by IEEE under US and international copyright laws. They
            are made available by IEEE and are adopted for a wide variety of both public and private uses. These include
            both use, by reference, in laws and regulations, and use in private self-regulation, standardization, and the
            promotion of engineering practices and methods. By making these documents available for use and adoption
            by public authorities and private users, IEEE does not waive any rights in copyright to the documents.
                                                                          4
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
            Photocopies
            Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to photocopy
            portions of any individual standard for company or organizational internal use or individual, non-commercial
            use only. To arrange for payment of licensing fees, please contact Copyright Clearance Center, Customer
            Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions
            of any individual standard for educational classroom use can also be obtained through the Copyright Clearance
            Center.
            Users of IEEE Standards documents should be aware that these documents may be superseded at any time
            by the issuance of new editions or may be amended from time to time through the issuance of amendments,
            corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the
            document together with any amendments, corrigenda, or errata then in effect.
            Every IEEE standard is subjected to review at least every 10 years. When a document is more than 10 years old
            and has not undergone a revision process, it is reasonable to conclude that its contents, although still of some
            value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have
            the latest edition of any IEEE standard.
            In order to determine whether a given document is the current edition and whether it has been amended
            through the issuance of amendments, corrigenda, or errata, visit the IEEE Xplore at http://ieeexplore.ieee.org/
            or contact IEEE at the address listed previously. For more information about the IEEE SA or IEEE’s standards
            development process, visit the IEEE SA Website at http://standards.ieee.org.
Errata
            Errata, if any, for all IEEE standards can be accessed on the IEEE SA Website at the following URL: http://
            standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata periodically.
Patents
            Attention is called to the possibility that implementation of this standard may require use of subject matter
            covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to the
            existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant has
            filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the IEEE
            SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may indicate
            whether the Submitter is willing or unwilling to grant licenses under patent rights without compensation
            or under reasonable rates, with reasonable terms and conditions that are demonstrably free of any unfair
            discrimination to applicants desiring to obtain such licenses.
            Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
            responsible for identifying Essential Patent Claims for which a license may be required, for conducting inquiries
            into the legal validity or scope of Patents Claims, or determining whether any licensing terms or conditions
            provided in connection with submission of a Letter of Assurance, if any, or in any licensing agreements are
            reasonable or non-discriminatory. Users of this standard are expressly advised that determination of the
            validity of any patent rights, and the risk of infringement of such rights, is entirely their own responsibility.
            Further information may be obtained from the IEEE Standards Association.
                                                                          5
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
            Participants
            At the time this IEEE recommended practice was completed, the Power System Protection Working Group
            had the following membership:
            The following members of the individual balloting committee voted on this recommended practice. Balloters
            may have voted for approval, disapproval, or abstention.
                                                                          6
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                   Thomas Rozek                               Michael Simon                              James Van De Ligt
                   Ryandi Ryandi                              Jeremy Smith                               Benton Vandiver
                   Daniel Sabin                               Jerry Smith                                Gerald Vaughn
                   Hugo R. S. Reategui                        Gary Smullin                               John Vergis
                   Chester Sandberg                           Wayne Stec                                 John Wang
                   Steven Sano                                Bill Stewart                               Daniel Ward
                   Vincent Saporita                           Gary Stoedter                              Keith Waters
                   Todd Sauve                                 Peter Sutherland                           John Webb
                   Bartien Sayogo                             C. Taylor                                  Kenneth White
                   Thomas Schossig                            David Tepen                                Iain Wright
                   Robert Schuerger                           Michael Thompson                           Dean Yager
                   Robert Seitz                               Wayne Timm                                 Jian Yu
                   Nikunj Shah                                David Tucker                               Luis Zambrano
                   Vinod Simha                                Marcelo E. Valdes                          Gaetano Zizzo
            When the IEEE-SA Standards Board approved this recommended practice on 5 September 2019, it had the
            following membership:
*Member Emeritus
                                                                          7
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
            Introduction
             This introduction is not part of IEEE Std 3004.11-2019, IEEE Recommended Practice for Bus and Switchgear Protection
             in Industrial and Commercial Power Systems.
            This recommended practice was developed by the Industrial and Commercial Power Systems Standards
            Development Committee of the IEEE Industry Applications Society as part of a project to repackage IEEE’s
            popular series of “color books.” The goal of this project is to speed up the revision process, eliminate duplicate
            material, and facilitate use of modern publishing and distribution technologies.
            When this project is completed, the technical material included in the 13 “color books” will be included in
            a series of new standards. Approximately 60 “dot” standards, organized into the following categories, will
            provide in-depth treatment of many of the topics formerly covered in the color books:
            In many cases, the material in a “dot” standard comes from a particular chapter of a particular color book. In
            other cases, material from several color books has been combined into a new “dot” standard. The material in
            this recommended practice replaces Chapter 13 of IEEE Std 242-2001, (IEEE Buff Book™).
            This publication provides a recommended practice for the electrical design of commercial and industrial
            facilities. It is likely to be of greatest value to the power-oriented engineer with limited commercial or industrial
            plant experience. It can also be an aid to all engineers responsible for the electrical design of commercial and
            industrial facilities. However, it is not intended as a replacement for the many excellent engineering texts and
            handbooks commonly in use, nor is it detailed enough to be a design manual. It should be considered a guide
            and general reference on electrical design for commercial and industrial facilities.
            Tables, charts, and other information that have been extracted from codes, standards, and other technical
            literature are included in this publication. Their inclusion is for illustrative purposes; where technical accuracy
            is important, the latest version of the referenced document should be consulted to assure use of complete, up-
            to-date, and accurate information.
                                                                          8
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
            Contents
            1. Scope��������������������������������������������������������������������������������������������������������������������������������������������������������� 11
               1.1 General discussion������������������������������������������������������������������������������������������������������������������������������ 11
               1.2 Word usage����������������������������������������������������������������������������������������������������������������������������������������� 14
2. Normative references�������������������������������������������������������������������������������������������������������������������������������� 14
3. Definitions������������������������������������������������������������������������������������������������������������������������������������������������� 15
            5. Zones of protection������������������������������������������������������������������������������������������������������������������������������������ 17
               5.1 Double-ended substations with two tie CB in series��������������������������������������������������������������������������� 20
            9. Differential protection������������������������������������������������������������������������������������������������������������������������������� 37
               9.1 Bus differential basics������������������������������������������������������������������������������������������������������������������������ 37
               9.2 High-impedance bus-differential relays��������������������������������������������������������������������������������������������� 42
               9.3 Low-impedance bus-differential relays���������������������������������������������������������������������������������������������� 44
               9.4 Modern differential-protection alternatives���������������������������������������������������������������������������������������� 46
            12. Protecting the secondary terminals and connected bus on a step-down substation transformer�������������� 50
               12.1 General discussion���������������������������������������������������������������������������������������������������������������������������� 50
               12.2 Low-voltage (LV) bus protection using primary-side protective devices����������������������������������������� 50
               12.3 Selection of transformer primary fuses for arc-flash protection on the transformer secondary bus�� 51
               12.4 Zone-selective interlocking across a substation transformer������������������������������������������������������������ 51
13. Low-voltage bus conductors, switchgear, switchboard, and motor control-center protection����������������� 53
                                                                                             9
                                                                 Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
            17. Triggered current limiters (TCLs)����������������������������������������������������������������������������������������������������������� 57
19. Conclusions��������������������������������������������������������������������������������������������������������������������������������������������� 57
                                                                                          10
                                                                Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
            IEEE Recommended Practice
            for Bus and Switchgear
            Protection in Industrial and
            Commercial Power Systems
            1. Scope
            This recommended practice covers the protection of bus and switchgear used in industrial and commercial
            power systems. It provides fault protection and isolation strategies for the substation bus and switchgear,
            including the bus, circuit breakers, fuses, disconnecting devices, transformers, and the structures on which
            they are mounted.
            Several factors have contributed to increasing interest in the improving protection of buses in industrial and
            commercial power distribution systems. These include:
                                                                         11
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
               —     Availability of more powerful, microprocessor-based protective relays, and circuit breaker with direct
                     trip units, allowing the application of improved protection to complicated bus configurations;
               —     Availability of high relaying accuracy current transformers (CTs), airgap CTs, air-core sensors
                     (Rogowski coils) and optical current sensors, which have better performance with high fault currents
                     or have immunity to saturation not easily available with traditional iron core current transformers;
               —     Increased understanding of, and interest in, mitigating the arc-flash hazard.
            To isolate bus faults, all power source circuits connected to the bus must be acted on by one or more of the
            following:
            These disconnection devices shut down all loads and associated processes supplied by the bus and might affect
            other parts of the power system.
            Many existing high-voltage (HV) substations are outdoor air-insulated structures enclosed by a fence where
            the limit of approach for a bus is established mainly via clearances. In many industrial and commercial power
            systems, power distribution is implemented at LV (1 kV or less) or MV (1001 V to 38 kV). MV equipment
            standards define MV class equipment up to a 52 kV utilization category which harmonizes IEEE equipment
            standards with the corresponding IEC standards. The type of equipment selected can have a great effect on the
            reliability, maintainability, and ease of implementation of a power system as well as the ease of implementing
            the required safety practices. For various applications, designers may select enclosures for buses that include,
            but are not limited to:
            Among the various selections, the designer will find that the standards define different tests that might indicate
            that one type of equipment might be more suitable for a specific application than another as the tradeoffs between
            costs, physical size, maintenance needs, operational complexity, location, and reliability are considered.
            Equipment might vary with respect to the degree of bus insulation or isolation, compartmentalization, and
            other characteristics that impact bus reliability, safety, maintainability, or other factors.
            To further reduce the occurrence of faults, the bus and associated equipment should be installed in a location
            where these are least subjected to extreme environmental conditions. Equipment standards such as the
            IEEE C37 family of standards and UL standards will define “standard conditions” and “special conditions”
            (IEEE Std C37.100.1™) for equipment environments. Whenever possible, equipment should be applied at
            standard conditions to optimize reliability and maintainability of equipment.
                                                                         12
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            A preventive-maintenance program is essential to detect deterioration, to make repairs, and to check and test
            relays, trip units, control systems, and circuit breaker performance before a fault occurs (see IEEE Std 3007.2™
            [B16]). The dielectric properties of insulating materials can deteriorate over time, particularly if the equipment
            is subject to greater-than-standard temperatures or transient overvoltage conditions. Moving mechanical parts
            can become difficult to move because of a loss of lubricity in lubricants and bonds formed at joints, and
            electronic capacitors can lose capacitance over time. Proper maintenance is an integral part of equipment
            protection, safety, and optimization of capital investments. Proper implementation of safety practices such
            as those described in NFPA 70E, require that maintenance of electrical equipment be properly conducted
            following manufacturers’ instructions or generally accepted industry practices.
            Modern protective relays, trip units, and control systems can measure, monitor, and calculate parameters
            important to implement condition-based maintenance. Modern electronic devices with appropriate
            communications capabilities can monitor each other as well as implement system-wide protection functions
            to facilitate system-wide maintenance and protection. In addition to proper maintenance, consideration should
            be given to including instrumentation and sensing devices or functions useful to diagnose power-system and
            equipment problems that might occur over the life of the equipment. Powerful multifunction digital meters,
            relays, and trip units are economical now. The ability to implement advanced digital communications within
            modern controls and protection devices allows remote control of equipment for greater safety and flexibility.
            Remote diagnostic capability allows experts located in remote locations to troubleshoot problems at the
            equipment regardless of physical location.
            Regardless of the steps taken to avoid bus faults, such faults occasionally occur. High-speed protective
            relaying, direct acting protection (integral trip units), or appropriately rated fuses should be used to minimize
            fault duration. Rapid clearing times limit damage, minimize arc-flash energy, and mitigate the effects of short
            circuits on other parts of the power system. Providing proper bus protection requires a well-designed system.
            Each equipment assembly should be provided with a main protective device for each power source, either as
            an integral part of the assembly, or in a remote location, protecting the incoming line. In some cases, it might
            be advisable to install the main device in a dedicated and separate section to manually isolate the line-side bus
            from the source if adequate protection of the line-side bus cannot be obtained to sufficiently reduce arc-flash
            incident-energy values. If the main protective device is omitted in an assembly and provided by a remote
            line side overcurrent device, the installation may be acceptable if the device provides appropriate protection;
            however, the lack of a local disconnect may not be optimal for maintenance purposes. The main circuit breaker
            sometimes is omitted at the secondary of a power transformer when the secondary feeder breakers have ratings
            that adequately protect the transformer from overloading. This topology might reduce the effectiveness of
            secondary bus protection because the transformer reduces the sensitivity of the primary protection for
            secondary faults unless specific protection schemes are put in place to properly deal with the situation, like
            transformer differential that includes the secondary side bus within its zone of protection.
            When power systems are grounded through a resistance or reactance to limit fault damage, the short-circuit
            current available to detect a ground fault is smaller and requires more sensitive protective relaying. A delta-wye
            transformer connection reflects a secondary ground fault current through two primary phase windings. The
            reduced value of current at the primary makes secondary ground fault currents in solidly grounded secondary
            transformers more difficult to detect. When the secondary of the transformer is impedance grounded, a
            secondary side ground fault may be indistinguishable from load for relays on the primary side and, hence,
            providing secondary side sensitive ground-fault relaying is important to initiate the opening of all sources that
            can feed the fault (see IEEE Std 242™-2001 (IEEE Buff Book™), Chapter 8 [B12]).1
            1
              It should be noted that at the time of the writing of this standard, the IEEE Color Books are in the process of being replaced by the
            IEEE 3000 Series of standards. Hence a reference to a Color Book now may be better replaced by a reference to the appropriate
            IEEE 3000 Series dot standards by the reader when this standard is read. For a guide to the published IEEE 3000 Series dot standards,
            consult the IEEE published standards catalog.
                                                                               13
                                                         Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            The word should indicates that among several possibilities one is recommended as particularly suitable,
            without mentioning or excluding others; or that a certain course of action is preferred but not necessarily
            required (should equals is recommended that).
            The word may is used to indicate a course of action permissible within the limits of the standard (may equals
            is permitted to).
            The word can is used for statements of possibility and capability, whether material, physical, or causal (can
            equals is able to).
            2. Normative references
            The following referenced documents are indispensable for the application of this document (i.e., these must
            be understood and used, so each referenced document is cited in text and its relationship to this document is
            explained). For dated references, only the edition cited applies. For undated references, the latest edition of the
            referenced document (including any amendments or corrigenda) applies.
            IEEE Std 3001.5™, IEEE Recommended Practice for the Application of Power Distribution Apparatus in
            Industrial and Commercial Power Systems.5
            IEEE Std 3004.1™, IEEE Recommended Practice for the Application of Instrument Transformers in Industrial
            and Commercial Power Systems.
            IEEE Std 3004.5™, IEEE Recommended Practice for the Application of Low-Voltage Circuit Breakers in
            Industrial and Commercial Power Systems.
            IEEE Std C37.2™, IEEE Standard Electrical Power System Device Function Numbers, Acronyms, and
            Contact Designations.6
            IEEE Std C37.20.1™, IEEE Standard for Metal-Enclosed Low-Voltage (1000 Vac and below, 3200 Vdc and
            below) Power Circuit Breaker Switchgear.
            2
              The use of the word must is deprecated and shall not be used when stating mandatory requirements, must is used only to describe
            unavoidable situations.
            3
              The use of will is deprecated and shall not be used when stating mandatory requirements, will is only used in statements of fact.
            4
              CSA standards may be obtained from the Canadian Standards Association, http://www.csagroup.org/ In this document the CEC is
            equivalent to NFPA 70 for Canada and Z462 is equivalent to NFPA 70E for Canada.
            5
              IEEE publications are available from The Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854, USA
            (http://standards.ieee.org/).
            6
              ANSI device numbers are used throughout this document to represent protective relays and control elements used in electrical power
            system diagrams. Some of the ones used in this document are: 50-Instantaneous Overcurrent Relay, 51-Time-Overcurrent Relay,
            52-Circuit Breaker, 86-Lockout Relay and 87-Differential Relay. Letters that follow the numbers such as B for bus, N for neutral, T for
            transformer and G for ground further identify the purpose of the device. IEEE Std C37.2 standardizes this nomenclature.
                                                                              14
                                                        Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            IEEE Std C37.20.7™, IEEE Guide for Testing Metal-Enclosed Switchgear Rated Up to 52 kV for Internal
            Arcing Faults.
            IEEE Std C37.100.1™, IEEE Standard of Common Requirements for High Voltage Power Switchgear Rated
            Above 1000 V.
            IEEE Std C37.110™, IEEE Guide for the Application of Current Transformers Used for Protective Relaying
            Purposes.
            IEEE Std C62.22™, IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current
            Systems.
IEEE Std 1584™, IEEE Guide for Performing Arc-Flash Hazard Calculations.
            3. Definitions
            For the purposes of this document, the following terms and definitions apply. The IEEE Standards Dictionary
            Online should be consulted for terms not defined in this clause.9
            air core sensors: Also known as Rogowski coils. Specially designed air-core mutual inductor whose output
            voltage is proportional to the time-rate-of-change of current of the input (primary) current.
            arc-flash incident energy: The amount of thermal energy impressed on a surface, a certain distance from
            the source, generated during an electrical arc event. Incident energy is measured in joules or calories per
            centimeter squared (J/cm2 or cal/cm2).10
            bus: A portion of a switchgear, switchboard or distribution system that electrically interconnects several
            circuit breakers or switches and is protected as a separate entity from other network elements. It may also
            directly connect other elements such as grounding transformers, or a source transformer and the incoming
            compartment of distribution equipment.
            current transformers (CTs): A current transformer (CT) transforms line current into current values suitable
            for standard protective relays and meters, while isolating these instruments from line voltages. A CT has two
            windings, designated as primary and secondary, that are insulated from each other. (See IEEE Std 3004.1-2013.)
            high-impedance differential scheme: A differential method of bus protection using CTs paralleled on a high-
            impedance load (a voltage or current relay in series with a stabilizing resistor). Throughout this text the symbol
            87B inside a circle is used to indicate a differential relay in drawings. (See IEEE Std C37.234-2009.)
high-voltage power distribution system: A power system with nominal voltage at or above 69 kV.
            7
              NFPA publications are available from Publications Sales, National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101,
            Quincy, MA 02269-9101, USA (http://www.nfpa.org/).
            8
              UL standards are available from Global Engineering Documents, 15 Inverness Way East, Englewood, Colorado 80112, USA (http://
            www.global.ihs.com/).
            9
              IEEE Standards Dictionary Online is available at: http://dictionary.ieee.org.
            10
               How to calculate potential arc-flash incident energy is described in IEEE Std 1584™. The hazard this represents and implications for
            electrical safety are discussed in NFPA 70E.
                                                                               15
                                                         Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            isolated bus (within equipment): Bus within distribution equipment where each phase conductor is separated
            from other phase conductors by insulating barriers.
            low-impedance differential scheme: A differential method of bus protection using CTs separately connected
            to an electronic device that measures and vector sums the measured currents to determine differential restraint
            and operate currents. (See IEEE Std C37.234-2009.)
NOTE—Throughout this text, the symbol 87B inside a circle is used to indicate a differential relay in drawings.
low-voltage power distribution system: A power distribution system with nominal voltage of 1 kV or less.
            medium-voltage power distribution system: A power distribution system with nominal voltage between
            1001 V and 69 kV, inclusive. Traditionally in North America, medium voltage was limited to 38 kV but
            equipment standards have evolved to match IEC practices; hence, MV equipment standards include 52 kV
            today.
            zone of protection: Divisions of protection that are logical subsections of the protection system used to isolate
            faulted section, i.e., generators, transformers, buses, transmission lines, distribution lines or cable circuits, and
            motor circuits.
            NOTE—In LV and MV systems, zones may be classified as primary or backup, differential or overcurrent. Differential
            zones of protection are bounded by the sensing used in the differential protection scheme. Overcurrent zones of protections
            are bounded by the overcurrent protection device at the supply side of protected zone.
            zone selective interlocking (ZSI): A method used to improve the response of protective devices in the event
            of a fault by allowing line-side devices to react faster to faults within their zone while maintaining selectivity
            for faults that occur within the zone of the load-side device. ZSI utilizes a signal between a load-side
            overcurrent protective device and a line-side protective device to indicate that the load-side device has sensed
            and is reacting to an overcurrent condition. The signal is used by a line-side device to alter a corresponding
            protective characteristic to a slower response to allow the load-side device to clear the fault without sacrificing
            selectivity. (See IEEE Std 1683™-2014.)
            Within equipment bus protection conforms to the equipment definitions of metal-enclosed and metal-clad
            type equipment construction. In metal-enclosed equipment, the bus may be exposed when the external panels
            are removed. In metal-clad switchgear, the bus is protected within an interior grounded metal compartment.
            Metal-clad switchgear construction is defined by IEEE Std C37.20.2. Metal-enclosed is defined by
            IEEE Std C37.20.1 for equipment rated 1 kV or less and by IEEE Std C37.20.3 for equipment rated above 1
            kV. UL 891 defines bus systems for switchboards rated 1000 V ac and less. Bus may also have insulation of
            various types applied which may provide additional electrical protection.
            When determining what is appropriate protection for a bus system, it is important to understand the level and
            quality of the protection that bus receives. Metal barriers that isolate a bus from one compartment to another
            can be expected to provide some level of protection from unintended contact. Insulation can be expected to
            improve the dielectric reliability of the system. However, the environment, application, quality, and amount of
            maintenance are also concerning, regardless of the bus housing and degree or quality of insulation.
                                                                         16
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            The equipment bus may have many different arrangements depending on the requirements for continuity of
            service for the bus and essential feeders supplied from the bus. Within any one line up of equipment there
            could be one or more buses. The most common arrangements are single bus radial systems with or without
            main devices and double ended line ups with two sources, a tie, and with mains for each source. Other more
            complex arrangements with dual ties in series or more than two sources are also possible. In the interest of
            reliability, a system designer may decide to implement a system with multiple sources in multiple enclosures
            with tie bus separately housed to connect the equipment where the bus associated with each source is located.
            This kind of arrangement lends itself well to dual ties. When a system is divided into multiple individual line
            ups of equipment with tie bus in between them, consideration should be given to the protection of the longer tie
            bus which may be more exposed than a short length of tie bus within a single piece of equipment with multiple
            sources. IEEE Std C37.234-2009 describes various bus schemes and associated protection zones used in MV
            and HV systems. The methods of protecting substation buses and switchgear might vary depending on voltage,
            arrangement of the buses, economic considerations, and other practical considerations.
               —     Greater than 52 kV
               —     Above 1 kV to 52 kV (in the past 38 kV instead of 52 kV was the MV to HV transition value)
               —     Equal to or less than 1 kV
            Industrial and commercial power distribution systems may include buses at 52 kV and less. Modern large
            industrial complexes, however, may include distribution, sub-transmission, or transmission substation buses
            at a higher voltage level. IEEE Std C37.234 discusses power bus configurations and associated protection
            schemes for HV arrangements. Also, other IEEE standards address specific configurations where necessary.
            Examples of such configuration for interconnections between an industrial facility and its supply utility are
            also given in numerous references (e.g., Beckmann, et al. [B3]).
            5. Zones of protection
            It is critical to ensure the reliability of the protection systems including:
               —     Dependability: The system must operate when there is a fault (identify fault location and isolate the
                     faulted part of the system), and
               —     Security and selectivity: Only the faulted power system zone is isolated, and the remainder of the
                     power system continues its normal operations.
            Zones may have defined demarcation (e.g., transformer differential protection). Protection may be defined
            as primary and back up protection as established by time-current coordination (overcurrent thresholds) or
            other protection methods. Zones of protection can be identified by the sensor locations that define the zone
            within which a fault might be detected, or by the controlled switching elements that can clear the fault once it
            is detected. When multiple sensors are used for the various types of protection, proper location of the sensors
            can ensure that blind spots are minimized. When using the same sensor for multiple functions or using sensors
            located within the switching devices (such as in LV circuit breakers), it is important to understand that blind
            spots might be created and these need to be assessed. If multiple sensors are used and they can be dedicated to
            different protective functions and zones, then the systems designer should strive to achieve overlapping zones
            of protection that eliminate blind spots. However, excessive overlap can negatively impact system reliability
            as well.
                                                                         17
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Figure 1 shows a simple radial substation with a single source. In this example, differential protection is
            applied using dedicated CTs that are arranged so that the differential-protection zone and overcurrent-
            protection overlap, and the entire bus is protected. Figure 2 shows the same substation bus protection, but only
            one set of CTs is used. Here, there is no overlap. However, for a simple topology in medium and low voltage,
            protection is provided by either scheme. In a system with networked sources, CT location can create short
            spots that are outside of the faster protection zone, or that are inside multiple protection zones, and can cause
            mal-operation of the protection system. For a more thorough discussion of network applications, see 5.1 of
            IEEE Std C37.234-2009.
                                                                         18
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            For the purposes of this standard, protection zones related to a CT are drawn so that the CT is included in
            the pertinent zone. A CT circuit may have a fault within the bus that is measured by the CT; in that case, the
            measurement will contribute to detection in both differential and overcurrent zones. If the fault is such that the
            CT undermeasures, it may contribute to a differential zone but may not be detected by an overcurrent zone.
              Figure 4—Double-ended substation, single tie, with dedicated CTs for the two differential
                                                    zones
            Figure 4 illustrates a typical design for systems with multiple sources and tie circuit breaker(s). Differential
            zones should overlap so that no bus sections are left without fast differential protection.
                                                                         19
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
               —     To isolate a tie bus or connection that is considered to have a realistic probability of failure;
               —     To help ensure complete isolation of the buses from each other for maintenance activities and safety.
            There are multiple ways to implement differential protection in such a scheme. Two or three differential
            zones may be created. The tie bus may be included in different ways depending which tie the differential
            zone controls and the location of the CTs associated with the ties. Table 1 shows five ways to locate CTs
            and implement bus differential protection in two-source dual-tie schemes. Selecting the method that is most
            applicable to a situation will depend on:
            In these schemes, faults that occur on the main part of the load buses are well protected with proper selectivity.
            However, the system reaction to faults near the tie circuit breakers or in the tie interconnection can vary with
            each scheme.
            In the first scheme described in Table 1 and shown in Figure 5, two differential zones are implemented. Each
            bus differential relay will open both ties which means any fault sensed anywhere in the buses will separate the
            sources. This is acceptable when sources are operating in parallel or when the fault is on the distant bus when
            only one source is connected. However, if the fault is in the tie bus between the tie CTs (fault 3), then both
            sources will be taken off line. A fault within the tie bus not located between the CTs (fault 2 and fault 4) will
            cause one source to open and both ties to open, isolating the fault, but unnecessarily disconnecting one of the
            main buses. Hence, if it is perceived that fault locations 2, 3, and 4 are where faults could happen, this may not
            be a good scheme from a reliability perspective; however, it is a good scheme from a protection perspective.
            An interlocking scheme using logic from one or both relays may be implemented to prevent operation of
            the main CBs and operate only the tie circuit breakers when both differential zones sense differential faults
            simultaneously, which occurs when a fault is in the overlapping zone. This may be considered if a fault in
            location 3 is more probable than a fault in location 2 or location 4.
            In the second scheme described in Table 1 and shown in Figure 6, two differential zones are implemented.
            Each bus differential relay operates one tie circuit breaker. One of the sets of tie-CTs is located within the tie
            bus and the other CT set is located within one of the main buses. In this scheme, bus fault locations 3 and 4 are
            on the tie interconnection. If a fault happens at location 3, both zones will sense the fault, causing both ties and
            both sources to open, fully isolating the fault, but also removing both sources from both load buses. If the fault
            is at fault location 4, only one source and one tie will open, isolating the fault location from only one source. If
            the other tie is closed and that source is connected, the fault may not be fully isolated. Also, the connected load
            will be dropped because of the one main CB opening and isolate the main bus.
            The third scheme, described in Table 1 and shown in Figure 7, is similar to the second, but the controlled tie
            CBs are the more remote from the main CBs. This scheme is an improvement from the second in that a fault in
            location 3 or location 4 will be isolated from both sources. However, a fault in location 3 will also isolate both
            main load buses, and one in location 4 will clear one load bus.
                                                                         20
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            In the fourth scheme described in Table 1 and shown in Figure 8, CTs associated with the tie circuit breakers
            are located on the main load buses and overlap. The tie interconnection is within both zones so a fault in fault
            locations 2, 3, and 4 will cause both ties and both load buses to be isolated from sources. An interlocking
            scheme using logic from one or both relays may be implemented that operates only the tie circuit breakers
            when both differential zones sense differential faults simultaneously, which occurs when a fault is located in
            the overlapping zone. This may be considered if a fault in location 3 is more probable than a fault in location 2
            or location 4.
            In the fifth scheme described in Table 1 and shown Figure 9, four sets of CTs associated with the tie CB
            are used. Tie bus faults are always selectively isolated. However, faults at location 2 and location 4 can still
            unnecessarily clear a load bus. If faults at locations 1 and 5 are deemed improbable, it may be advisable to
            implement a logic scheme that prevents the main bus protection differential from tripping the main CBs for
            a set delay if the tie differential protection is opening the tie CB. That may improve reliability but may delay
            protection if a fault occurs at location 1 or 5. Generally when using bus differential, the intent and expectation
            is fast bus protection. Delaying the opening of a source CB is not normal practice and should be carefully
            considered if contemplated as it significantly limits the benefit associated with bus differential protection.
            These examples demonstrate that there is no single perfect implementation of differential protection in sources
            with multiple sources and multiple ties in series. What is optimal for a situation will depend on various factors
            including perception of the most probable fault locations and the need for reliability. In addition to differential
            protection, interlocking logic can further improve a scheme to ensure minimum interruption of power to
            served loads.
            The main overcurrent protection can be used as a backup to the ties in case the tie circuit breakers fail to isolate
            the fault. Modern digital protective relays have capabilities for providing this, and the best way may vary
            based on the exact relay used and degree of complexity deemed acceptable. Protective relay manufacturers
            should be consulted on the best method suitable for the given situation and specific product recommendations.
            These methods should not require delays long enough to allow another CB to open, i.e., more than three to
            six cycles. As with any protection solution, the complexity needs to be weighed against the reliability risks
            associated with the complexity.
            The feeder overcurrent protection might allow a portion of conductors inside the CBs to be protected by the
            differential protection instead of the feeder overcurrent protection (as Figure 3 and Figure 4 imply). A fault
            internal to the circuit breaker would be a very serious event in the main equipment. Therefore, it may be
            acceptable to allow the lack of selectivity created by the differential zone instead of simply allowing the feeder
            overcurrent-zone to provide the protection at delays required for selective operation of the system.
                                                                         21
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                                                                                                                                                   Table 1—Dual tie substation with bus differential implementation alternatives
                                                                                                                                                                                                           Figure     Substation           Fault            M1           T1            M2            T2          Bus 1             Bus 2    Tie Bus     Fault
                                                                                                                                                                                                                                                                                                                                                       cleared
                                                                                                                                                                                                       5            2 CTs between      1             Open         Open          Unaffected    Open          Cleared        Unaffected      N/A        Yes
                                                                                                                                                                                                                    ties               2             Open         Open          Unaffected    Open          Deenergized    Unaffected      Cleared    Yes
                                                                                                                                                                                                                                       3            Open          Open          Open          Open          Deenergized    Deenergized     Cleared    Yes
                                                                                                                                                                                                                                       4            Unaffected    Open          Open          Open          Unaffected     Deenergized     Cleared    Yes
                                                                                                                                                                                                                                       5            Unaffected    Open          Open          Open          Unaffected     Cleared         N/A        Yes
                                                                                                                                                                                                       6            2 CTs around       1            Open          Open          Unaffected    Unaffected    Cleared        Unaffected      N/A        Yes
                                                                                                                                                                                                                    1 tie, zone        2            Open          Open          Open          Open          Cleared        Deenergized     N/A        Yes
                                                                                                                                                                                                                    control near tie
                                                                                                                                                                                                                                       3            Open          Open          Open          Open          Deenergized    Deenergized     Cleared    Yes
                                                                                                                                                                                                                                       4            Unaffected    Unaffected    Open          Open          Unaffected     Deenergized     Not cleared No
                                                                                                                                                                                                                                       5            Unaffected    Unaffected    Open          Open          Unaffected     Cleared         N/A        Yes
                                                                                                                                                                                                       7            2 CTs around       1            Open          Open          Unaffected    Unaffected    Cleared        Unaffected      N/A        Yes
                                                                                                                                                                                                                    1 tie, zone        2            Open          Open          Open          Open          Cleared        Deenergized     N/A        Yes
                                                                                                                                                                                                                    control far tie
                                                                                                                                                                                                                                       3            Open          Open          Open          Open          Deenergized    Deenergized     Cleared    Yes
                                                                                                                                                                                              22
                                                                                                                                                                                                                                       4            Unaffected    Unaffected    Open          Open          Unaffected     Deenergized     Cleared    Yes
                                                                                                                                                                                                                                       5            Unaffected    Unaffected    Open          Open          Unaffected     Cleared         N/A        Yes
                                                                                                                                                                                                                                                                                                                                                                                                       IEEE Std 3004.11-2019
                                                                                                                                                                                                       8            2 CTs outside      1            Open          Open          Unaffected    Unaffected    Cleared        Unaffected      N/A        Yes
                                                                                                                                                                                                                    both ties, with    2            Unaffected    Open          Unaffected    Open          Not cleared    Deenergized     N/A        Yes
                                                                                                                                                                                                                    3rd zone logic
                                                                                                                                                                                                                                       3            Unaffected    Open          Unaffected    Open          Unaffected     Unaffected      Cleared    Yes
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
                Figure 5—Double ended substation with 2 ties and 1 CT set per tie CB with minimum tie
                                                  zone overlap
Figure 6——Double ended substation with 2 ties and 1 CT set per CB; 1 tie in each zone
                                                                         23
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
Figure 7—Double ended substation with 2 ties and 1 CT set per CB; 1 tie in each zone
Figure 8——A double ended substation with 2 ties and 1 CT set per CB; full tie bus overlap
                                                                         24
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
Figure 9—Double ended substation with 2 ties and 2 CT sets per tie CB; full tie bus overlap
               —     Large magnetic forces in some systems are severe during the first few fault cycles and can tear the bus
                     from its attachment points and bend rigid conductors. These effects create additional fault points and
                     can whip flexible conductors, damaging the conductors and nearby equipment along the path of fault
                     current from source to fault;
               —     The I2t heating effect created over time by excessive current can deteriorate insulation and even result
                     in softening and melting of conductors along the current path;
               —     Arcing at the point where the fault occurs can be very damaging, causing melting, burning, and
                     contamination that can damage nearby equipment as well.
            In addition, it is not unusual for operating personnel to be near important equipment containing high-energy
            buses. Personnel might be engaged in operating circuit breakers, racking circuit breakers in and out. They
            might be engaged in other operation or maintenance activity on buses, device control wiring, instrumentation,
            and other portions of the distribution, control, and metering system. An arcing fault exposes nearby personnel
            to arc-flash related injuries, and fast protection is very important.
                                                                         25
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Fast protection in the case of an in-equipment arcing fault can reduce the incident heat energy released by
            the arc. This in turn can also reduce the arc-flash protection boundary around the equipment and reduce the
            likelihood of the blast effects that could be created by the arc. In addition to lessening the personnel injury
            aspects of arc flash, fast clearing times will also reduce fault damage to the equipment.
            The improved safety provided to personnel by fast, sensitive protection can also have significant value in
            terms of productivity and reliability, such as reducing:
            Therefore, when considering whether to add the cost and complexity of fast bus protection it is important to
            consider the following:
            Fast-bus transfer schemes should be considered as a part of the protection solution when multiple sources
            are available and maintaining power to loads is important for reliability or safety. However, if the bus itself is
            faulted, then transfer between multiple sources must be blocked. Such schemes are further discussed in 6.11
            of IEEE Std 3004.8.
            To achieve selective coordination, overcurrent relays and trip units may have delay settings and high-current
            setting ranges to delay opening the source circuit breakers upon the occurrence of a feeder fault. This is
            not uncommon in industrial systems that require selective systems to ensure system reliability. Presently,
            systems covered by the NEC’s definition of Emergency (section 700, NEC), Legally Required Standby
            Systems (section 701, NEC) or Critical-Operations-Power systems (section 708, NEC) also require selective
            performance. For such systems, the NEC requires complete selectivity, called selective coordination in the
            NEC, from the branch overcurrent protective device to the emergency power source and for the normal
            power source. The NEC mandate requires instantaneous protection, if present, to be selective. The extent
            to which protection system selectivity applies depends on the revision of the NEC that has been adopted
                                                                         26
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            by the jurisdiction and how these requirements of that revision are interpreted by the jurisdiction. Systems
            designed for selective coordination might not provide sensitive, high-speed bus and switchgear protection
            unless designs, components, or protective schemes are specifically selected to provide high-speed protection
            and selective coordination simultaneously in the fault current range of interest. See Valdes et al. [B41] and
            [B43] for further reading.
            On MV and HV systems, fuses, overcurrent relays, and arc-flash relays that trip circuit breakers are often
            used for 3-phase fault and inter-phase fault protection where fault currents are typically high and overcurrent
            protection can be effective. These systems are supplemented with sensitive ground relays when the system is
            low-resistance-grounded (MV) and with ground-fault detection in high-impedance grounded systems (LV and
            MV). In LV, high-impedance-grounded systems, ground-fault detection systems are required to annunciate the
            occurrence of a ground fault when tripping is not immediately initiated. Systems that identify fault location
            are desirable to facilitate rapid and safer troubleshooting and to expedite the removal of an accidental ground-
            fault. Chapter 4 and Chapter 8 of IEEE Std 242-2001 (IEEE Buff Book™) provide details on relays and
            procedures for proper settings. Modern switchgear standards also allow for MV circuit breakers with built-in,
            direct-acting trip units that might incorporate GF detection and protection.
            On LV systems, most applications use circuit breakers or fuses. Electronic trip units for LV circuit breakers
            perform the sensing and timing functions that provide required protection for LV circuits and apparatus.
            Modern LV trip units implement protection, metering, communications, and logic capabilities that are
            very capable. The selectivity and protection clearing time possible with LV integral trips often exceeds the
            capabilities possible with component relays operating those same LV circuit breakers. IEEE Std 3004.5
            describes how to select and apply LV circuit breakers. IEEE P3004.3/D1b-2017 covers LV fuse application.
            Differential protection of LV buses presents additional challenges to similar protection in MV and HV buses
            (see Valdes et al. [B45]). In LV buses, fault currents may be high multiples of load current, while arcing faults
            may be significantly lower magnitude than maximum calculated bolted-faults. However, working distances
            are shorter, hence incident arc-flash energy per unit time may be high causing every millisecond that protection
            is accelerated to be important. For that reason, implementation of differential protection may be desirable, but
            traditional methods may be difficult, expensive, or too space consuming to be practical. Techniques such as
            combining partial differential with zone-selective-interlocking, using differential protection integral to the
            LV protection, or implementing zone-selective interlocking or other manufacturer-specific techniques may be
            valuable in providing improved protection in a more practical manner.
            The suitability of the protection afforded to LV equipment depends partly on the type of equipment containing
            the bus and the standards around which that equipment is designed, manufactured, and tested. When the feeder
            circuit breaker clearing time, fed from a bus, exceeds three cycles, the bus in the equipment should have
            adequate withstand rating to prevent subsequent internal damage during the time that a through fault might last
            (before being cleared by the feeder device in the equipment). LV power-circuit-breaker switchgear (UL 1558,
            IEEE Std C37.20.1) is furnished with a 30-cycle rated bus per the requirements of the standard. Protection
            should not require 30 cycles to clear a large-magnitude fault. UL 891-listed switchboards normally available
            with a 3-cycle withstand rating may be available with optional 30-cycle rated bus based on testing performed
            by the manufacturer over and above that required by the UL standard for that equipment. When using protective
            relays in LV equipment, extreme care should be taken to ensure that clearing times do not exceed equipment or
            circuit breaker withstand capabilities. Integral circuit breaker trips are designed to not allow the circuit breaker
            or equipment withstand capabilities to be exceeded; hence, even if protective relays are implemented, the
            integral trips should not be removed. Distribution equipment that has branches that always have instantaneous
            protection, such as LV MCC, are not required, by applicable standards, to have significant withstand ratings as
            any significant through fault will be interrupted by the instantaneous protection in the feeders.
            When considering arc-resistant equipment (ANSI/IEEE Std C37.20.7), it is important to ensure that the
            protection for all buses and conductors within the equipment protects the buses within the identified arc-
            resistant withstand time identified by the manufacturer for the arc-resistant equipment. This might be difficult,
            and therefore requires special attention when the line-side conductors of equipment fed by a step-down
                                                                         27
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                          IEEE Std 3004.11-2019
                    IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            transformer are protected by a device on the line side of the transformer. See Mello et al. [B24], Simpson
            [B33], and Valdes et al. [B41] for further reading.
            Implementation of fast digital communications networks, such as that defined by the IEC 61850 [B39] set of
            standards, in LV and MV protective devices, allows both distributed and central processing of current, voltage,
            and device data. Fast digital communication facilitates fast, sophisticated protection that can accommodate
            changes in system topology and can identify the fault location within the equipment, optimizing protection as
            required by the actual topology in place at the time of the fault. For further reading on use of IEC 61850 in MV
            and HV applications, see Apostolov et al. [B1] and [B2], and for an example of an LV application, see Valdes
            et al. [B44].
            LV bus protection tends to rely on the direct-acting integral trip units provided with circuit breakers tested and
            listed as a system that includes the circuit-breaker mechanism and the integral trip unit. The trip unit is not
            only designed to provide the proper protection adjustability that might be suitable for a range of connected
            loads, it is also designed to protect the circuit breaker from being applied above its withstand capabilities. LV
            power circuit breakers (LVPCB) are also UL listed (UL 1066 [B40]) for use with separate protection relaying.
            LV, circuit-breaker direct-acting trip units provide most of the protective functions even when self-powered
            from fault current. It is not recommended that a LVPCB be used without its integral trip unit even if additional
            protective functions are implemented via separate protective relaying such as differential or overcurrent
            relays. When operating LVPCB from external relays, such as an arc-flash relay, it is important to consider the
            additional operating time that a shunt-trip coil might add versus the usually faster, internal, flux-shifter coil
            that the direct-acting trip unit might use. Manufacturers should be consulted to ensure that the operating time
            and clearing time of the circuit breaker and all auxiliary devices are included.
            To reduce the possibility of destructive arcing faults, phase or ground, on 480Y/277 V and 600/347 V systems,
            and to lessen the shock hazard when enclosure rear covers are open, the LV bus can be provided with an
            insulating cover. This is generally available as an option on LV power switchgear and might be available
            on some switchboard designs, particularly those with individually mounted devices and rear access to cable
            terminations. Front-access switchboards have very limited capabilities for insulated bus coverings. It is not
            usually available in panelboards.
            Insulated and/or isolated bus may be available as an option on MV, metal-enclosed switchgear
            (IEEE Std C37.20.3), MV motor control (ANSI/UL 347 [B36]), on LV switchgear (IEEE Std C37.20.1), LV
            motor control centers (UL 845, [B37]), and on switchboards (UL 891 [B38]). Insulated bus is mandatory in
            metal-clad switchgear (IEEE Std C37.20.2).
            7.2 Low-voltage (LV) bus ground-fault protection for solidly grounded systems
            Electronic trip units in circuit breakers are available with integral residually connected phase sensors and may
            implement an external neutral sensor, if required. Some circuit breakers and switches (UL 977 [B39]) might
            also use external zero-sequence sensing and process the signal within the device to generate a trip. Separate
            ground-fault relays using zero sequence sensing are also commonly applied and trip the circuit breaker via
            a shunt trip device. The 2017 NEC® (NFPA 70) requires ground-fault protection on solidly grounded, wye-
            connected electric services of more than 150 V to ground, and not exceeding 1 kV phase to phase, for the
            following devices:
            The NEC (230.95 for services, 215.10 for feeders, and 210.13 for branch circuit devices) states that GF
            protection must be provided in certain applications and that the maximum pickup setting for the ground fault
                                                                         28
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                             IEEE Std 3004.11-2019
                       IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            function (or sensor) is 1200 A. A GF function with a deliberate time-delay characteristic must trip within 1
            s for currents equal to or greater than 3000 A. It also states that this requirement does not apply in certain
            applications (such as continuous processes where interruption would be more hazardous than the ground fault
            itself). It should be noted that in many situations there is not a given standard that determines practice but the
            interpretation of that standard by the local inspector (Authority Having Jurisdiction). UL 1053 also defines
            an additional point on the ground-fault curve at 150% of the nominal pickup setting that must not exceed 2
            s clearing time. Figure 10 shows an example of an LV ground-fault protection curve and the various NEC-
            required limits. NEMA PB2.2 [B27] also provides guidelines for interconnecting LV ground-fault protection
            in complex systems as well as recommendations for assessment of acceptable bus damage in the case of a
            low-magnitude, single-phase, arcing ground fault. Ground-fault protection in systems with multiple sources
            is complex. Different manufacturers employ different schemes to achieve proper protection in complex
            systems. Some are more suitable for open-transition systems, others for closed-transition systems. For further
            details, see IEEE Std 242-2001 (IEEE Buff Book™)11 Chapter 8 and NEMA PB2.2, as well as manufacturers’
            application guidelines.
            Where main service-entrance circuit-breakers rated 1000 A or more are required to have ground-fault
            protection in solidly grounded systems, achieving selective coordination requires coordination of the ground-
            fault device with load-side phase protection (provided by circuit breakers or fuses). Selective coordination
            can be achieved using delays, nested pickup thresholds, and careful selection of device response curve where
            alternatives exist. Protection can be enhanced using zone-selective interlocking. Bus-differential protection
            can also be set sufficiently sensitive to provide ground-fault protection in some cases. However, achieving
            selective coordination for ground faults between line-side ground-fault relays and load-side phase protection
            might be very difficult because of the limited flexibility in ground-fault device curve shape and pick up settings
            that are allowed by the applicable standards. See Figure 10.
            11
                 See footnote 5.
                                                                          29
                                                      Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Though the NEC requires only a single level of GF detection and tripping based on the detected GF is not
            required, consideration should be given to the implications of meeting only the minimum requirements in
            the NEC for GF fault indication on LV HRG systems. Not correcting a first ground creates the possibility
            that a high-current phase-to-phase fault will occur between two circuit breakers if a second ground fault on
            a different phase of the system happens before the first GF is removed. When two GFs exist simultaneously,
            the resulting phase-to-phase fault may result in the loss of multiple circuits. Various systems for detecting
            grounded circuits in HRG systems at load-side circuits exist today. These systems can be used to facilitate
            trouble shooting of ground faults for more efficient and safer removal. Use of load-side GF detection in LV
            HRG systems is recommended. GF detection on an HRG system could be based on voltage or current sensing.
            Sensing and indication may be as basic as simply indicating a fault on the system exists to increasing levels
            of information detail such as identifying which phase is grounded, which main equipment feeder, or even
            which branch circuit overcurrent device is feeding the fault circuit. Detail level detection is advised to improve
            maintainability, safety, and reliability. In some cases, LV switchgear or overcurrent devices such as electronic
                                                                         30
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            overloads may have built-in detection to facilitate such detail location identification and relays systems to
            implement such detection is available. To prevent a fault from persisting too long and eventually resulting in
            a dangerous multiple phase fault, consideration should be given to alarming that is difficult to go unnoticed.
            Consideration should be given to tripping overcurrent devices even if it is days after having first alarmed
            a persistent GF. Ground-fault protection in LV systems is discussed further in IEEE Std 142 (IEEE Green
            Book™) [B11].
            The main, or incomer’s, ground-fault relaying should be set to be selective with overcurrent relaying on load-
            side feeders, if possible. A feeder ground fault of sufficient magnitude will be sensed as a phase fault by the
            feeder overcurrent relay and as a ground fault by the main incomer’s GF relaying. Inverse-time overcurrent
            relays, without instantaneous elements, are commonly used. If the feeders have ground-sensor instantaneous
            protection, faster time-overcurrent delays are possible.
            Because most faults are ground faults, or eventually become ground faults, ground-fault protection greatly
            improves bus overcurrent protection. Additional descriptions and guidance on ground-fault protection can be
            found in IEEE Std 242 (IEEE Buff Book™) [B12].
            These schemes are described in 7.2 of IEEE Std C37.234-2009. The primary advantage of zone-selective
            interlocking is its ability to provide faster fault clearing for bus faults without sacrificing system selectivity
            with feeder protection fed by the bus. ZSI is an economical alternative to bus differential protection and may
            provide a suitable alternative in those situations where CT saturation makes differential schemes impractical.
            ZSI might provide less sensitive, or slower protection than differential relays. Also, while differential systems
            are inherently selective for through faults, ZSI systems are not. The lowest tier overcurrent device in a ZSI
                                                                         31
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                            IEEE Std 3004.11-2019
                      IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            scheme must be coordinated with load-side devices not included in the ZSI system. Zone-selective interlocking
            is particularly suited for circuit breakers with integral trip units commonly provided with LV circuit breakers.
            ZSI is beneficial even in MV circuit breakers with relays and separate CTs. It is less demanding on CT
            accuracy relative to differential-protection schemes. The ZSI restraint signal sent from one tier to another is
            commonly conveyed over a dedicated control circuit. On systems using protective relays, the signal could also
            be conveyed using serial communications, particularly those designed following IEC 61850 standards.
Figure 11—ZSI scheme with two circuit breakers and two protection devices
            Modern zone-selective interlocking allows improvements in clearing time, provides interlocking of LV-to-
            MV devices across transformers, can be applied with directional relaying, and can provide other advanced
            capabilities. Proper implementation of modern interlocking schemes can improve protection speed and
            sensitivity for buses located in upper tiers within any distribution topology. In rare cases, selectivity may
            be slightly improved using ZSI capabilities.12 For additional reading on advancements in zone-selective-
            interlocking, see Valdes et al. [B41] and [B42].
            12
                 Traditionally, ZSI is not considered capable to provide selectivity improvements, only protection improvements.
                                                                                 32
                                                           Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                          IEEE Std 3004.11-2019
                    IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            faster than the feeder-cable protection. This type of function should be confirmed with the manufacturer of the
            protective devices used. In component relays this will require separate inverse functions for blocking logic and
            protection and ability to implement the required logic. In LV trips the capability should be discussed with the
            manufacturer.
            Not all manufacturers or devices implement delay settings the same way. In LV ZSI implementations within
            LV circuit breaker trip units, unrestrained and restrained protection might be selected various ways:
               a)     User selects “restrained” backup timing and the trip unit automatically sets “unrestrained” protective
                      timing. This is the most common and simplest configuration in LV trip units.
               b)     User selects both unrestrained and restrained timing. This configuration is more complex but might
                      provide greater flexibility. It is important to properly identify which delay is the restrained and which
                      delay is the unrestrained when adjusting the settings in the trip unit.
               c)     User selects the same unrestrained protective timing for all tiers and a fixed “delta” time delay to
                      be added to upper tier devices based on load-side fault location. This configuration might allow for
                      tighter backup timing but requires some sort of centralized control to identify fault location and logic
                      that includes system topology considerations. This scheme might be able to adapt backup delays to
                      topology changes as well. See Valdes et al. [B42] and [B43] for further reading on this ZSI scheme.
               d)     User sets protection threshold and trip unit has only fixed timing for in-zone protection and a second
                      fixed timing for out-of-zone backup timing. This scheme is suitable for high fault ranges where
                      excessive backup timing might be undesirable and in-zone protection is desired to occur as quickly as
                      possible.
               e)     User sets two or more alternate setting groups composed of multiple settings and the restraint signal is
                      used to alternate between them. This method is more common in MV protection but is also available
                      in LV trip units. It requires multiple user settings but provides very flexible alternate protection that
                      can be used as backup protection. The signal required to alternate between setting groups is more
                      appropriately called a logical input than a restraint signal as it can be used to alternate between
                      protective settings used to back up a lower-tier failed circuit breaker or to reset bus protection as
                      required for varying system topologies.
            When the available short time or ground-fault delay settings permit three or more circuit breakers to be
            coordinated, the restrained timing on a trip unit could be selected in a manner where all the upper layers of
            trip units are selectively coordinated one to the other in the traditional method where ZSI is not being used.
            The case of main-tie-main systems is one where this might occur most often. However, these nested delays
            are not strictly necessary. Backup, restrained timing could be set the same for all protective tiers. If the in-
            zone protective timing and the backup timing coordinate, and all circuit breakers operate properly, the system
                                                                         33
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            should be selective under all fault conditions, regardless of whether backup timing is nested in multiple levels
            or not. However, if a lower tier device fails to clear properly and all backup timing is set the same for multiple
            tiers, then multiple tiers of line-side devices might trip together. This may, or may not, be desirable when one
            considers that this only happens if a fault has happened downstream and the circuit breaker that is intended
            to operate fails to clear the fault. Tripping multiple devices may be desirable to minimize equipment damage
            and ensure reliable fault clearing given evidence of a compromised protective scheme. See Figure 12 for an
            illustration of this concept.
            It is important to note that the ZSI schemes implemented in trip units or protective relays might allow the
            manipulation of multiple protective functions (e.g., short-time, ground-fault, instantaneous) upon receipt of a
            blocking signal. Typically, only one signal path is used, and if the receiving unit does not know why the signal
            was sent; it will shift whichever functions are ZSI-enabled to their restrained settings. This allows a lower
            tier device to have only short-time zone interlocking implemented, but the device on the line side might have
            ground-fault and short-time protection shifted if the phase overcurrent of the lower tier device can be adjusted
            to coordinate with the line-side ground-fault characteristic. The signal from the lower tier will shift both upper
            protective functions once the load-side short time ZSI function picks up, which might occur immediately after
            current exceeds the pickup threshold setting. Figure 13 illustrates an example.
                                                                         34
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
             Figure 13—Time current curves showing feeder CB with only short-time interlocked with a
                         CB equipped with both short-time and ground-fault protection
            Advanced algorithms and circuit breaker protection systems can implement enhanced zone-selective-
            interlocking not previously available. Directional zone-selective-interlocking allows interlocking to operate
            in systems with multiple sources and ties restraining the proper source side circuit breaker depending on fault
            location. Directional capability can also help ensure that a protective device does not issue a restraint signal
            because of regenerative fault current supplied by a motor onto a bus fault upstream. Other algorithms allow
            separate interlocking of instantaneous and short-time protection or may be capable of automatically shifting
            the current pickup thresholds which allows pickup settings to be set to the same current threshold without
            regard to maintaining separation between pickups due to tolerance considerations.
            Figure 14 illustrates the timing of a ZSI interlocking signal issued by an LV circuit breaker and the timing
            requirements for an instantaneous protection function of an MV instantaneous (device 50) relay. The left
            diagram shows an LV circuit breaker short-time and instantaneous curve along with the associated restraint
            signal timing issued by the same circuit breaker trip unit. The center panel shows the timing of the various
            subsystem functions associated with the instantaneous function of a protective relay able to receive a logical
            input and process it to alter its protective functions. The lines in the center panel, from bottom (fastest) to top
            (slowest) represent the following:
                                                                         35
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
               —     Commit time for the relay, i.e., the time it takes for the relay algorithm or circuitry to make the
                     irrevocable decision to assert a trip. In this case, the minimum time that decision can take. For
                     instantaneous elements, the commit time is often inversely proportional to the ratio of fault current to
                     threshold pickup setting;
               —     The second line above that represents the additional time the relay allocates to sweeping its logical
                     inputs and processing associated logic. At the end of this time, the relay will assert its trip if the logic
                     allows it. This line may be viewed as the “blocking window.” If the blocking signal arrives before this
                     time, the relay logic can block or alter its operation and not assert a trip even if the fault current had
                     previously exceeded the commit time;
               —     The third line represents the output contact from the relay. Output contacts might be solid state or
                     mechanical. Mechanical contacts usually are a few milliseconds slower than solid state contacts;
               —     The fourth, top most line represents the clearing time of a 3-cycle MV circuit breaker.
            The third panel superimposes the LV circuit-breaker, short-time and instantaneous curve, its associated issued
            restraint signal, and the various lines representing the MV instantaneous element and MV circuit breaker.
            The LV restraint signal is to the left and below the MV line representing the MV instantaneous trip blocking
            window that indicates these two devices might be made selective by using the LV restraint signal to alter
            the MV relay operating characteristics. Many modern digital relays offer the ability to block instantaneous
            protection. Operational details may vary by manufacturer and device model and should be obtained from
            manufacturers’ application literature or by consultation with the manufacturer for a specific relay and trip
            unit. This capability is particularly useful for fast protection of the transformer secondary bus between the
            transformer secondary terminals and the first LV device.
Figure 14—Interlock signal timing for circuit-breaker trip units and protective relays
                                                                         36
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            CBF schemes provide supplemental backup protection for through faults and are not primary protection to
            upper-tier buses. Figure 15 shows a schematic comparison of a CBF scheme versus a ZSI scheme. For further
            information on CBF applications, see IEEE Std C37.119 [B20].
            A word of caution is appropriate for CBF schemes. Added complexity in a protection system provides
            added opportunity for equipment failures, wiring failures, and testing failures. CBF protection should not
            be considered for simple systems in which the only outcome of the circuit breaker failing to trip is that the
            line-side circuit breaker or fuse clears the fault. Normal backup protection, potentially enhanced with ZSI,
            is usually good enough for radial distribution topologies. CBF schemes are for buses with multiple sources
            of power where the failure of a circuit breaker to properly isolate the fault may cause multiple systems to be
            impacted. This type of protection is usually only seen in utility applications for major substations, but with
            distributed resources becoming much more common, it is becoming more common for complex industrial and
            commercial power systems.
            9. Differential protection
            9.1 Bus differential basics
            Bus-differential relaying can provide sensitive, high-speed, selective protection for buses, including
            switchgear buses. A bus-differential relay measures all currents entering and exiting the protection zone and
            operates if the difference between the current sources and current loads is above the differential protection
            threshold. Because of this inherent selectivity, a differential relay does not need to have intentional delays
            to coordinate with relays in adjacent zones, and it does not need to coordinate pickup thresholds with other
            protection—a benefit especially when large fault currents flow through the differential zone. Bus-differential
            protection is used when high-speed fault clearance is required to limit the damaging effect to equipment and
            to maintain service to as much load as possible. In addition, it permits complete zone protection coverage and
            overlapping with other power-system relaying as indicated in Figure 11, Figure 12, and Figure 13, for a variety
            of bus configurations. One of the challenges associated with the applications of bus differential relays, is the
            behavior of the current transformers associated with the differential schemes. Current transformers saturate
            when subjected to excessive fault currents and to dc components in currents under transient fault conditions
            at fault inception (IEEE Std C37.110). Saturation of one or more of those current transformers providing
                                                                         37
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            inputs to the differential scheme may cause relay mis-operation and compromise the scheme reliability. CT
            requirements for differential schemes are discussed in detail in IEEE Std C37.234, IEEE Std 3004.1, and
            other literature. It is advisable to review such references as well as the relay supplier requirements prior to the
            selection of the connected CTs. CT characteristics are especially important when using high impedance bus
            differential relays. Modern low impedance bus differential relays are developed with separate input modules
            for each CT input signal, and each input is digitized before current inputs are vectorially summed in the relay.
            Some details are discussed in the subsequent clauses and more details can be found in associated literature.
            Bus-differential relaying often is applied to complex systems that have multiple sources and perhaps multiple
            buses at the same voltage level. Improved arc-flash protection is another reason to implement differential
            protection, to provide the fastest and most sensitive protection without sacrificing system reliability.
            Traditionally, these goals have been used to justify the extra cost and complexity of high-speed bus-differential
            relaying. Advances in modern digital relays, digital communications, and alternate sensing techniques
            has lowered the cost and complexity of implementing differential protection in industrial and commercial
            applications and make applications in commercial LV systems more feasible.
            The basic principle of differential protection is that, under normal conditions, the phasor sum of all measured
            currents entering and leaving the bus is zero (Kirchoff’s current law). This is ideally always true under normal
            load conditions, otherwise, a fault has occurred within the protected zone.
                                                                         38
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Differential relaying is typically provided to supplement basic overcurrent protection. It is frequently used on
            a 15 kV-bus, sometimes on a 5kV-bus, and with increasing frequency, on LV buses. The following factors are
            often used to determine whether differential relaying should be provided (see Cable et al. [B5]):
               —     Degree of exposure to faults. For example, open outdoor buses have a higher degree of exposure; and
                     metalclad switchgear, properly installed and in a clean environment, might have minimum exposure.
                     Contaminated environments increase the possibilities of faults, and equipment located in these
                     environments needs better protection;
                                                                         39
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
               —     Magnitude of the fault current causing damage of the bus components and voltage depression impact
                     to the adjacent electrical equipment as a result of slow fault clearance, such as motor control circuit
                     drop-out or synchronous motors falling out of synchronism;
               —     Power-system stability. The capability of a system to return to a stable, steady-state mode of operation
                     after a system disturbance might require high-speed bus differential relaying. The faster clearing
                     time obtained with high-speed differential relaying enhances the probability of maintaining stability
                     through and after a fault;
               —     Use of sectionalized-bus arrangements that require the use of other, more complex protection methods.
                     Sectionalized-bus arrangements make differential protection more useful and desirable, particularly
                     when secondary selective distribution systems are used. The faulted bus can be isolated quickly and
                     continuity of service maintained to a portion of the load served by any other bus;
               —     Effects of bus failure on other parts of the power system and associated processes. On a major plant
                     bus, the cost of differential relaying is usually insignificant when compared with the savings associated
                     with the reduction in damage to the equipment and the reduced outage time of important plant or
                     process facilities. This cost can include the cost to repair electrical equipment, clean up production
                     machinery and processes, as well as the opportunity cost incurred and lost revenue resulting from the
                     inability to continue plant operations.
               —     If problems exist in selectively coordinating the system overcurrent-relay settings or the selective
                     coordination requires excessive delays, differential relaying is effective in obtaining selectivity
                     and faster protection simultaneously. An example is a system that consists of major bus distribution
                     lineups at the same voltage level, with one bus feeding another. This configuration generally results in
                     unacceptably high overcurrent relay pickup and delay settings required to obtain coordination.
               —     Arc-flash incident energy protection. Delays and nested pickups, often required to provide selectivity
                     for bus main breakers, can increase arc-flash incident energy. The energy released by an arc flash can
                     create significant hazard to operating and maintenance personnel. Sensitive bus-differential protection
                     should reduce the severity of the hazard while enabling selectivity for through-faults at protected
                     buses. Where improved arc-flash mitigation is desired, bus-differential protection is an alternative to
                     losing selectivity to overlapping short-time bands and instantaneous protection or slowed protection
                     required to maintain selectivity.
            On a bus fed by a local generator, bus differential relaying is recommended to clear the bus quickly and
            minimize impact on the generator system. Simple overcurrent relays might not be sufficiently fast or sensitive
            to protect the generator if these are set to be selective with other load-side protection.
            The differential relay should trip all circuit breakers connected to the bus. Typically, a high-speed, multi-
            contact lockout relay (device 86B) is used for this purpose. This auxiliary device should also have normally
            closed contacts in the circuit breaker closing circuits to prevent inadvertent manual closing of a circuit breaker
            on the fault until after the incident has been investigated further. The lockout relay then must be reset manually
            before any circuit breakers can be closed. In some schemes, where optimum protection speed is desired,
            controls might be connected such that source circuit breakers are directly tripped by the protection relay and
            the lockout relay is used to trip feeders. Modern digital differential relays may have enough contacts to trip all
            bus breakers and provide lockout functionality.
                                                                         40
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Figure 19 shows a simple, current-based differential scheme that may be created by simply connecting current
            sensors in a differential manner from each source and feeder circuit in parallel to a simple overcurrent relay
            using the net difference from the sum of all currents as the input to the relay. If the current into the bus through
            the source is equal to the current leaving the bus through the three feeders, the net sum is zero and no current
            flows through the relay. When a fault occurs on the bus, the source contribution into that bus does not flow
            through the feeders and hence is sensed as a differential current by the relay. This simple scheme requires that
            the characteristics of the CT be considered. CT ratios should match, however other characteristics may vary.
            Reviewing CT characteristics with the relay manufacturer is recommended. Generally, this simple scheme
            will require the protection to be set high (50 device) or delayed (51 device) to prevent CT performance from
            negatively impacting security.
            The simple differential scheme such as shown in Figure 19 might be susceptible to false operation because of
            sensing inaccuracy during large through faults. A load-side fault could cause enough current to flow that the
            source and feeders CTs, even if nominally identical, could produce enough difference in secondary current that
            the relay could incorrectly assert a fault that is not there. Adding delays or increasing the operational threshold
            are ways to minimize the possibility of incorrect operation; however, slowing and desensitizing differential
            protection is not usually desirable, and to some degree, defeats the purpose of having differential protection.
            This type of implementation might be suitable for small systems with a very limited number of circuits. The
            more common types of differential relays employed in industry today are called low-impedance and high-
            impedance differential relays. Both types of relay expand the number of circuits that can be accommodated
            and implement techniques to allow sensitive thresholds and very fast operation that can perform as well as fast
            instantaneous protective elements in single-circuit protective relays. In the past, high-impedance differential
            relaying was generally considered superior; however, with improvements in digital relays, low-impedance
            differential relaying can perform as well as high-impedance differential relaying in speed and sensitivity while
            providing for a more flexible implementation.
                                                                         41
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            In classic high-impedance bus-differential relays, CT secondary currents are summed via their secondary
            circuit wiring as shown in the upper portion of Figure 20. The net differential current is forced to flow through
            a resistance as shown in the lower portion of Figure 20. The scheme is relatively simple and straight forward.
            Accordingly, it remains widely used despite the need to address certain practical considerations as discussed
            further throughout this subclause.
            The CTs used with traditional high impedance differential relays must have the same ratio, enough accuracy,
            matched characteristics if possible, and proper polarity connection to ensure that the secondary current outputs
            from the paralleled CTs have a vector sum of zero in the same way that the primary currents in the bus sum to
            zero during normal load conditions. Current differences are forced through the high-impedance input at the
            bus differential relay causing a voltage across the relay. In some cases, the relay is in series with a resistor,
            and those relays will operate from the current through the relay and resistor. The relay is set to trip based on
            the voltage across the relay and can be sensitive to small differential currents. Typical relay settings allow
            one CT to saturate without relay misoperation. During external faults, with saturation of some of the CTs,
            the voltage does not rise above a certain level defined by the saturated CT impedance and wiring impedance.
                                                                         42
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            The circuit is required to have overvoltage protection, typically in the form of a metal oxide varistor, to limit
            the voltage across the relay-input resistor created during internal faults. This type of relay has been used for
            several decades because it is robust, cost effective, secure, and fast. Limitations of high-impedance differential
            relays and precautions while applying them can be summarized as:
               —     Dedicated, well-matching CTs are required. The CTs should have distributed secondary windings that
                     have little or no secondary leakage reactance. Manufacturers of the relays provide guidance on CT
                     selection to ensure that the CTs are properly matched to each other and to the relay capability;
               —     CTs must be sized to have an accuracy class that will produce an operate signal on the relay while
                     saturated;
               —     CT secondary circuits must be connected with the correct polarity so secondary currents flow in the
                     proper direction.
            Under normal load conditions, differential current should be zero through the differential impedance. Under
            through-fault conditions, although bus currents are still balanced, one or more of the CTs might saturate. A
            fully saturated CT produces reduced secondary current and can become a (relatively) low-impedance path
            for other current sources in the circuit. Secondary CT wiring is an important consideration in determining the
            voltage across a saturated CT. It is usually preferred to run CT secondary leads to minimize wiring impedance
            and equalize resistance among the various load circuits. The operating-threshold voltage for the differential
            protection must be greater than the voltage that could occur across the parallel path provided by a completely
            saturated CT. For a bus fault within the differential zone, a large voltage should be produced across the relay
            impedance. The overvoltage protection provided by a metal-oxide varistor clamps the voltage peaks to a level
            acceptable for the relay. The relay operational threshold must be set below the clamping voltage created by the
            overvoltage protection. Manufacturer’s literature should be consulted to secure relay behavior under system
            conditions especially:
            Under severe through-fault conditions, CTs carrying the most fault current might saturate. The relay tripping-
            voltage threshold must be set above the voltage that could develop across the relay with a completely saturated
            CT. A completely saturated CT produces no current output and becomes simply a (mostly resistive) impedance
            in the circuit. The CT wiring and internal resistance are small relative to the internal resistance of the high-
            impedance relay path. Therefore, the worst-case voltage across the relay under a large through-fault condition
            is the voltage drop across the combination of saturated CT wiring and saturated CT internal resistance. The
            voltage selected as a tripping threshold must be greater than the possible voltage that could develop across a
            saturated CT and associated wiring.
            The relay setting threshold should have enough margin to account for potential variation in the available fault
            current and in the impedance used in the calculations. This threshold affects the minimum sensitivity setting
            for the relay. To simplify calculations, it is recommended that all CTs be connected to one junction point or
            terminal board. CTs should not be connected into subsets and the subsets brought to a common connection
            point separately.
                                                                         43
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            During a high-current internal-bus fault, the relay presents high impedance to the flow of CT secondary
            current. This impedance causes a large voltage to be developed across the relay. Even if the CTs on incoming
            circuits eventually saturate, a large voltage is developed during the first part of the half cycle prior to CT
            saturation. Relays should be set to operate from that voltage during the time prior to CT saturation. This setting
            should provide the relay enough information and time to make reliable tripping decisions. Manufacturers
            implement various filtering, sampling, and signal processing techniques to improve sensitivity, accuracy,
            speed, and reliability for the sensing circuit—even when fault magnitudes might be large and source CTs reach
            saturation. The net current flowing through the sensing circuit can be very non-sinusoidal; however, modern
            relays can discern a fault within a cycle of fault inception.
            The voltage peaks created during a fault can exceed the voltage withstand of the relay and even prove
            hazardous, hence the voltage must be clamped to a reasonable level that is greater than the expected pickup
            threshold of the relay.
            9.2.4 Protecting the high-impedance differential relay from excessive current and circuit-
            breaker failure
            The relay current-withstand and overvoltage protection energy limits might be exceeded in cases where the
            circuit breaker that the relay controls does not open quickly enough. Additional protective elements need to
            be included for such situations. Common implementations include a parallel metal oxide varistor (MOV), or
            shunting the differential current through a parallel, low-impedance circuit made of internal relay contacts or
            using an external 86 auxiliary relay connected in parallel with the protection relay’s sensing circuit.
            High-impedance differential relays may implement a series overcurrent function (50/51) that provides back-
            up protection and continues to operate even after the shunt bypass contact is closed to protect the main sensing
            circuit and overvoltage protection.
            A high-impedance differential relay cannot implement functions that require measuring any single circuit
            current because the current information at the relay always represents the net total current flowing in the zone.
            One last concern is that, because the high-impedance relay can be set very sensitively, it is important to
            account for normal and acceptable currents that may exist or temporarily occur within the protected zone.
            These currents may result from auxiliary control power transformers and even currents shunted to ground by
            arresters or surge protective devices.
               —     CTs may be shared with other metering and protective functions within the relay;
               —     CT ratio can be corrected or changed at the relay as required;
               —     The relay will impose a threshold-restraint function to desensitize the relay in proportion to some
                     measure of the through current in the differential zone to guard against false tripping from CT sensing
                     error, see Thompson [B34];
               —     The relay can adjust for a CT wired with any polarity; however, it is recommended that all CTs be
                     wired with a consistent secondary current direction to facilitate trouble shooting.
                                                                         44
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Modern low-impedance differential relays might implement various algorithms creating a restraint function
            and use separate measured currents (or rate of change of current) to improve protection sensitivity, speed, and
            prevent false operation. Because the relay receives each CT signal independently, the relay can implement
            various additional protective and measurement algorithms with each separate CT signal and any combination
            of CT signals. Additional protective functions such as breaker-failure detection, overcurrent protection of
            load-side circuits, and other multi-function protection, with sophisticated algorithms may be provided by the
            same relay.
            A commonly used method to account for measurement error in low-impedance differential relays is the
            percent-restraint function. The relay sums the currents (vector sum of phasors) from all CT inputs to detect
            the differential-current increase resulting from an internal fault. To account for errors introduced by variations
            in CT performance and by CT saturation, the relay also may implement one of various methods based on
            the measured current magnitudes to create a restraint current. The differential current from the phasor
            summation, referred to as the operate current, is compared with the restraint current. The relay operates when
            the operate current exceeds a minimum threshold and a percentage of restraint current. Graphically this is
            shown as a slope called the percentage-current-differential characteristic for the differential relay. Figure 22
            illustrates this principle. Low-impedance differential relays that implement this characteristic are referred to
            as percentage-differential relays. A second, steeper slope is often added to address the increasing inability for
            the CTs to accurately replicate higher primary currents and hence ensure that the relay does not misoperate if
            a CT is saturated during a high-current fault. This second slope makes the relay stable against misoperations
            but can significantly desensitize the protection during a high-current fault. The second slope is also shown in
            Figure 22.
                                                                         45
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Modern, digital, low-impedance differential relays implement additional algorithms to detect saturated CTs
            and the pending saturation of a CT. These algorithms vary by manufacturer. These algorithms improve the
            sensitivity and security of modern, digital, low-impedance differential relays.
            The relay must have separate input connections for each CT that is part of the differential scheme. Typically,
            that will be three CTs per source or feeder circuit, one for each phase conductor. One technique to connect
            more circuits to any one relay is to put CTs for multiple circuits in parallel and use the net sum of these CTs
            as an input to the relay. This technique requires that the paralleled CTs be of equal ratio and class, and that the
            combined expected secondary current from the paralleled CTs does not exceed the relay input signal ratings.
            The manufacturer’s literature should be consulted when this technique is used to determine if this might cause
            issues with protection algorithms. When implementing low-impedance differential relaying, consideration
            should be given to any additional circuits that might be added in the future to ensure that the relay has sufficient
            inputs for planned expansion of the bus system. See Kasztenny [B22] and Thompson [B34] for additional
            reading on percentage differential relays and Holback [B9] for a comparison between high-impedance and
            percentage differential relays.
                                                                         46
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            An additional benefit of using digital communications to provide current data from the circuit-breaker cubicle
            to the CCPU is that CT leads are always connected to the local node at the circuit breaker bay. For this local
            connection, the CT leads do not extend to a central differential relay location. Thus, CT burden is reduced
            and the CT is less likely to saturate, and CT wiring does not have to cross where equipment is separated for
            shipping purposes (shipping splits).
            Distributed data acquisition combined with centralized data processing provides an economic and flexible
            solution. This solution accounts for CT saturation, uses the same sensors for multiple functions such as
            metering, control and other protection, and uses integral sensors that are normally provided in LV circuit
            breakers and in some MV circuit breakers, as well. These systems make differential protection a reasonable
            option in some LV systems where traditional differential protection and its components might otherwise be
            considered too costly, too complex, or incapable of fitting into the available space. Distributed systems can
            easily account for dynamic changes in system topology and circuit-breaker status and can define a zone of
            protection as required in response to different system conditions.
            Schemes using communications technology can provide differential protection over large systems where
            traditional CT wiring would be impractical. IEC 61850 communication may also be used to implement
            directional comparisons. These might be less demanding of communication buses because less information is
            communicated from the local data-acquisition node to the central-processing node at which the comparisons
            are made. See Apostolov et al. [B2] and [B44] for additional reading on this subject.
            A communications-based architecture is shown in Figure 23. Alternative architectures are possible with
            different levels of functionality distributed between the local and centralized communicating devices.
            Information distributed within the system can include several discrete signals such as circuit-breaker status
            and blocking signals as well as analog current and voltage phasor, sampling data.
                                                                         47
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Among the drawbacks of this type of scheme is the wide variation that might be found between alternatives
            available and the unfamiliarity of users with this type of protection. In a centralized scheme, the provision of
            multiple important protection and control functions in one processor raises the concern that there might be a
            single point of failure affecting too many important functions. That concern can be alleviated by providing
            redundancy in sensitive portions of the system and by designing the system such that, in the event of a single
            device or communication failure, sufficient protection and control remains to keep the system safe and
            operable.
            When implementing protection and control schemes using centralized processors, there are many factors that
            need to be considered to ensure that protection is fast and reliable, including being able to accurately predict
            protection timing regardless of other demands for available communication bandwidth, processing power, or
            available memory. Generally, monitoring functions will be lower priority than control functions, and control
            functions will be lower priority than protection functions. Fault events may cause significant increases in
            data to flow, and this can cause the system to operate in an unintended way if the design does not properly
            account for the potential large flow of time-critical data during fault events. Designing complex control and
            monitoring systems is complex and requires skilled personnel. Adding protection functions makes it even
            more critical that system designers understand the ramification of all system design decisions and that the
            system be robustly tested prior to full implementation.
            Another advantage occurs when partial differential schemes are applied on buses being fed from multiple
            parallel sources, which can otherwise be difficult to coordinate. Consider that the feeder overcurrent device
            in such a system will see all the current flowing to line-side faults, regardless of how the sources contribute
            to this current. The degree to which the sources may share can be difficult to predict and makes traditional
            representation on time current curves difficult. The relay in the partial differential scheme sees the same fault
            current as the feeder device or the faulted bus, regardless of how sources are sharing that current, making
            classic time current curve evaluation straightforward. The relay can disconnect all sources simultaneously
            selectively. Furthermore, the partial differential relay can be interlocked with blocking signals from the load-
            side overcurrent or ground fault relays allowing for faster protection of the bus without negatively impacting
            selectivity.
            When a normally closed tie circuit breaker separates loads as shown in Figure 24, this scheme can provide
            selectivity between the two sources for bus faults and load-side faults. In a conventional scheme with relays
            on each incoming line, a fault on either bus results in a loss of both incoming lines because their settings are
            identical. With the partial differential scheme, a fault on one bus causes a summation of currents in one set of
            relays and a subtraction of currents in the other set of relays (not shown). This difference in currents allows the
            incoming line relays to be selective and only the faulted bus is de-energized.
            Partial differential relays should provide sufficient delay to be selective with relays on the load circuits.
            Consequently, the sensitivity and speed of partial differential protection is not as good as in full differential
            protection. A partial differential scheme may be enhanced by use of blocking signals (ZSI) from load-side
            load relays to force the partial differential protection to be restrained if the fault is detected by load protection
                                                                         48
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            relays, or trips fast enough. This requires that the blocking signal arrive at the device providing the partial
            differential protection before the partial differential protection commits to asserting a trip.
            Bus backup protection is inherently provided by the primary relaying or trip units at the remote ends of the
            supply lines. This setup is known as remote-backup protection. It might not be adequate because of system
            instability and effects on other portions of the power system, and local-backup relaying might be necessary.
            The performance of various remote- and local-backup relaying schemes should be analyzed. IEEE Std C37.95-
            2014 [B19] gives further information on utility-service supply-line requirements and the backup protection of
            utility relaying.
            Circuit-breaker failures can cause catastrophic results, such as complete system shutdown. In MV and HV
            applications, local circuit-breaker failure or stuck-circuit-breaker relay schemes are available to quickly
            trip supply-side circuit breakers that are able to isolate the failed protective device if the circuit breaker on
            the faulted circuit fails to operate within a specified time. These schemes were normally applied only on
            buses where the extra expense could be economically justified when discrete relays were the norm. Now,
            multifunction relays provide these functions without additional cost. In LV systems, backup protection is
            provided by upper tier devices employing nested delays or zone-selective-interlocking. It should be noted that
            the backup to a failed LV main, fed from a transformer, is provided by the first MV protective device ahead of
            the transformer. Unless protection has been implemented to specifically provide fast backup protection, the
            protection provided by an MV protector on the line side of a transformer, for a LV fault on the secondary side
            of the transformer, might be several orders of magnitude slower than the expected, failed, LV protection. This
            situation can lead to significant equipment damage and extremely hazardous levels of arc-flash energy. See the
            following clause in this recommended practice for some further discussion on this subject as well as Mello et
            al. [B24].
            Some low-impedance differential relays incorporate multiple protective functions that can back up the
            protection provided by the differential-relay algorithm, as well as provide additional protection for feeder
            circuits.
                                                                         49
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
               —     The protective device, circuit breaker, switch, and fuses are located on the transformer primary circuit
                     at a higher voltage than the secondary conductors that require sensitive protection;
               —     The distance might be significant between the MV protective device and the location where sensing for
                     protection of the lower-voltage bus is located;
               —     The lower-voltage equipment might not easily accommodate instrument transformers of sufficient
                     accuracy and burden capability to provide proper sensitivity and performance;
               —     The transformer winding configuration might further desensitize any primary-side sensing of
                     secondary fault current;
               —     Transformer inrush current requirements require accommodation by any primary sensing and
                     protection implemented.
            It is common to protect secondary substation transformers with dedicated primary fused switches. However,
            the fuses often do not provide adequate protection of the secondary bus and can allow very large levels of
            incident arc-flash energy and equipment damage in the case of an equipment arcing fault. The fuses can provide
            adequate protection for large-magnitude faults on the primary connections of the transformer. The transformer
            ratio and relatively small magnitude of an arcing secondary fault can cause the fault to be difficult to detect
            with primary-side current sensing. The following subclauses describe some alternatives for protecting this
            section of the power-distribution system.
            Ground-fault protection on the bus between the transformer secondary terminals and the first LV devices may
            be important. The NEC only requires ground-fault protection on service entrance disconnects rated at 1200
            A or greater. However, the line side of the service entrance disconnects may also be subject to ground faults
            and should be protected for low magnitude arcing ground faults if possible. See Paul et al. [B28] for further
            discussion on ground faults between the transformer terminals and the first secondary protective device.
                                                                         50
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Omitting a secondary main from a double-ended substation (in this case, double-ended substation refers to
            a substation with two sources and a tie device on the bus that can be used to separate the sources) is not
            recommended. A fault on a transformer primary, which is directly connected to the main LV bus by the
            transformer, would be fed from both sources. The current from the opposite transformer is limited by the
            impedance of the two transformers. It might be small and difficult to detect by the overcurrent protection from
            the far transformer, and it might last for a long time causing significant damage and hazard.
            A fuse is only current-limiting when the fault current is sufficiently large to drive fuse performance into the
            fuse current-limiting range, above the threshold current, or current limiting threshold. If the fuse is selected
            with a larger current rating than needed, the threshold current is larger than might be prudent. The goal is to
            select a fuse size and type with a threshold current that is less than the least-expected secondary arcing current
            when reflected to the primary voltage. However, even if the secondary arcing fault current is less than the MV
            fuse current-limiting threshold, applying a fuse with an inverse time characteristic will shorten the duration of
            the arc current, resulting in less incident energy and less equipment damage at the secondary bus between the
            transformer and the first LV primary device.
               —     Systems considerations such as maximum load current expected, steady-state and transient current,
                     available source fault current, expected secondary arcing current;
               —     Transformer characteristics such as impedance, magnetizing current, applicable damage curves,
                     output power, kVA; short-circuit voltage; service voltage; operation with or without overload;
               —     Local code requirements;
               —     Fuse characteristics for the multiple fuses considered such as:
                     — Rated currrent, the current that the fuse can withstand without abnormal heating;
                     — Minimum interrupting current, the minimum current that can melt the fuse. Generally, fuses should
                       not be applied where the sustained load could range above fuse rating and below minimum melting
                       current.
            By selecting a smaller fuse ampere rating and a more extreme inverse-time characteristic, the incident energies
            may be substantially lessened at the secondary LV equipment. If the selection process is followed properly,
            the system should not have nuisance fuse openings and still be selectively coordinated. It is important to
            follow fuse manufacturers’ guidelines and understand the expected transformer needs when tighter protection
            is implemented to not incur nuisance operation of the fuses upon energization of the transformer.
                                                                         51
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            In component relays typically used in MV systems, a similar capability might go by various names such as
            blocking or instantaneous blocking systems. In both the LV and MV implementations, the basic theory is the
            same. In a distribution system composed of multiple tiers of devices, the load-side lower tiers send a signal to
            line-side upper tiers when sensing a fault above a preset threshold. The upper tier devices receive the signal
            and using internal logic, alter their tripping characteristics, typically slowing their response to allow the load-
            side device to clear the fault. The zone interlocking can be described as forcing the line-side device to shift to a
            backup protection role in the interest of maximizing selectivity.
            The ability to extend the interlocking capability between the last primary protective device and the first
            secondary device is advantageous because it provides protection of the transformer secondary terminals
            and connected conductors without the need to compromise protection or selectivity. Also, there is no need
            to include long secondary conductors within a transformer differential scheme. Figure 26 shows multiple
            ways to design a scheme that uses LV-to-MV interlocking to protect the transformer primary and transformer
            secondary without sacrificing system reliability.
            Protection of the transformer primary and secondary might be implemented using two separate relays or two
            protective elements within one relay. Sensing for secondary faults might be done using CTs located on the
            transformer primary or secondary. Secondary sensing might be easier to set sensitively because the transformer
            inrush current does not need to be considered. When the transformer secondary is a solidly grounded wye,
            attention must be paid to ground faults that are lesser magnitude and are also reduced to 58% of the ground
            current when sensed at the primary side (because of the wye-delta winding).
            In 25(a) the zone-interlocking signal is routed from the LV equipment feeders to the LV main, and from the
            LV main to the MV relay. To improve the sensitivity of the MV relay protection, the restraint signal could be
            taken directly from the LV feeders allowing the LV main and MV transformer feeder to operate for equivalent
            faults—it makes no difference to the reliability of the substation.
            In 25(b) the secondary LV circuit breaker is not included. In this configuration, the MV primary device is
            operated as an LV main. This configuration is not recommended for substations with multiple sources that
            could result in transformers energized from the LV side.
            In 25(c) one or more relays can be used to implement transformer-differential and overcurrent protection
            of load-side conductors simultaneously. This configuration might be easier to implement than a transformer
            differential scheme that includes the secondary conductors within the zone of protection. Various
            considerations might affect the selection of a scheme that includes the secondary bus in the differential zone of
            protection or relies on protection with a 50/51 device. The considerations are the following:
               —     Length of secondary conductors and distance between sensors in the secondary equipment and the MV
                     relay;
               —     Required size of secondary CTs required for differential protection might be difficult to locate within
                     the LV equipment;
               —     Desensitizing differential sensing required to account for transformer magnetizing current;
               —     Access to a fast blocking signal from an LV trip unit or protective relay system;
               —     Ability and time to process a blocking signal for 50/51 protective elements.
            Discussed in 8.4 is the subject of modeling the settings and timing of an LV-side sensing scheme interlocked
            with MV-side protection. The figures below depict the implementation of the three different transformer
            secondary bus protection schemes discussed in this subclause.
                                                                         52
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            LV power circuit-breaker switchgear built to the IEEE C37.20.1 standard can only employ LV power circuit
            breakers (LVPCB). These circuit breakers can be supplied both with and without series fuses. Switchboards
            and motor-control centers can be designed to include LVPCBs, molded case circuit breakers (MCCB), or
            fusible load-break switches. Each of these protective devices has different characteristics that should be
            considered from the bus protection perspective. Equipment manufacturers generally implement protective
            devices that are compatible with the capabilities of the equipment. Implementing external protective relays to
            provide protection by operating LVPCB without using the circuit breaker’s integral protection as backup can
            cause circuit breakers to operate slower than the equipment can withstand. If relays are required for complex
            protection or control applications, the circuit breaker trip should be included to ensure that protection is no
            slower than the equipment or circuit breaker can withstand. For protection where fast instantaneous fault
            clearing is required, it is likely that the integral trip will be faster than an external protective relay.
            Equipment buses protected by current-limiting fuses will, under most circumstances, be well coordinated and
            well protected from large-magnitude bolted-fault currents occurring within the equipment or flowing through
            the equipment. However, as fuse continuous rating increases, they may provide slow protection for lesser-
            magnitude arcing currents, and the protection might not be enough for adequate arc-flash incident energy
            mitigation. If arc-flash incident-energy mitigation is expected to be provided by LV fuses, it is important
            to verify that expected arcing currents are large enough to cause the fuses to operate at the speed required
            to provide the desired level of arc-flash incident energy mitigation desired. Equipment buses protected by
                                                                         53
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                            IEEE Std 3004.11-2019
                      IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            LVPCB13, or large insulated case circuit breakers14 might use nested delays to achieve selectivity. Multiple
            levels of circuit breakers coordinated with nested delays might result in main breakers with short-time clearing
            times of several hundred milliseconds. Nested delays might also result in main or even feeder circuit breakers
            with decreased sensitivity and increased clearing times at the levels required to protect against arcing faults,
            resulting in slower clearing times and significant incident energy and equipment damage.
            Instantaneous trips in circuit breakers provide faster protection than short-time delays; however, these can
            negatively impact selectivity. Methods to coordinate circuit breakers with instantaneous trips have been
            developed by various manufacturers. Manufacturers should be consulted to properly optimize the selectivity
            that might be possible using any one manufacturer’s device(s). The protection afforded by short delays can
            also be improved with the use of zone-selective interlocking schemes between circuit breakers and ground-
            fault relays in fusible switches. Bus-differential protection is another protection scheme that might be used to
            protect LV buses. Using a combination of these capabilities can provide protection that is sensitive to a wide
            range of bus-fault magnitudes while maintaining selectivity for large fault magnitudes. For further reading on
            this subject, see NEMA publications on selectivity [B25] and [B26] as well as Valdes et al. [B41].
            Remote operation of circuit breakers or switches and remote racking capability might also be employed to
            reduce the exposure of operating personnel to arc-flash hazard and should be considered whenever possible.
            Most devices available in the industry have capability for remote operation. Use of digital microprocessor-
            based relays in MV systems and digital trips in LV systems, both of which can use powerful communication,
            allow implementation of remote control, metering, and diagnostic systems that can significantly reduce the
            need for operating personnel to enter the flash protection boundary. Because of the increased safety these
            methods provide, these capabilities should be considered whenever possible and practicable.
            IEC MV equipment standards (IEC 62271-200 2011) specifically address this same concern by describing
            these “supplementary” measures to provide additional personnel protection:
                 a)     Fast fault clearing via light, pressure, heat, or differential current sensing protection;
                 b)     Controllable type fuses made up of a current limiting fuse in parallel with a current path that can be
                        opened quickly to commutate the current to the parallel current limiting path;
                 c)     Extremely fast elimination of the arc by diverting the current to an arc quenching device that shunts
                        fault current and collapses voltage to eliminate the arcing fault;
                 d)     Remote operation of equipment;
            13
               Low-voltage power circuit breakers (LVPCB) are a specific type of LV circuit breaker which complies with IEEE Std C37.13. These
            circuit breakers may also be listed devices under UL1066.
            14
               Insulated case circuit breakers are UL 489 listed circuit breakers that share some characteristics of LVPCB. See IEEE Std 3004.5 for
            further information.
                                                                               54
                                                         Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                          IEEE Std 3004.11-2019
                    IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            When considering use of this kind of device, the manufacturer should be consulted and applicability to the
            system carefully considered. These devices have excellent arc-flash, incident-energy mitigation, and in
            some applications, such as a retrofit in an existing installation, these might provide one of very few practical
            alternatives to achieve small levels of incident energy. However, there are risks and limitations that must be
            considered in consultation with the respective manufacturers.
            Arc quenching devices may be controlled with arc-flash relays (see Clause 16), simple overcurrent detection,
            differential relays, and other sensing logic. This logic might be implemented in a continuous protection mode
            or as part of a temporary protection scheme used during hazardous maintenance or operation activity. The
            latter is sometimes recommended because of the possible impact or cost of nuisance operation. For further
            reading concerning shunt energy absorbing devices, see Kay et al. [B23] and Roscoe et al. [B31].
            Shorting switches have been used to create a low impedance path for fault current in some MV and HV circuits
            to ensure that overcurrent relays protecting the circuit sensed the current as fast as possible. These same
            devices, and others like them, are now also used for arc-flash protection as described in this subclause.
                                                                         55
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            When implementing a light-based arc-flash relay, it is important to understand that the relay is a volume
            protector, not a circuit protector. It can sense that there is light above threshold within the volume the sensors
            are applied. But it cannot differentiate one circuit from another if there are multiple circuits within the volume,
            nor can they detect a remote arcing fault within a circuit if the fault is within a remote volume.
            Light-based relays can also nuisance operate if they perceive light from another source as being light caused
            by an accidental arcing event. Current-sensing based confirmation is implemented to protect against this
            possibility; however, light could be caused by an electromagnetic air circuit breaker interrupting a remote
            fault within the protected volume. Current sensing may not differentiate the light from an interrupting circuit
            breaker or from a non-electrical source, from the light generated by an accidental electrical arc. Arc-flash relays
            implemented near fuses, sealed vacuum circuit breakers, or gas insulated equipment would not be subjected to
            light from the operation of those devices. If using an arc-flash relay around low voltage circuit breakers, it may
            be advisable to use the relay only during maintenance or implement another method to minimize the possibility
            of a nuisance operation due to an interrupting LV circuit breaker. See Roscoe et al. [B32] for additional reading
            on this subject. In articles 240.67 and 240.87 of the NEC (2017), there is a function referred to as an energy
                                                                         56
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            reducing switch (ERMS) that is expected to be used only during maintenance similar to how it is suggested for
            an arc-flash relay in applications where a nuisance trip presents an unacceptable risk.
            As with all protective relays, it is important to not confuse the relay operating time with fault clearing time.
            Fault clearing time must include the controlled circuit breaker operating time as well as any intermediary
            relays or other sources of delay.
            When considering use of an arc-flash relay, the manufacturer should be consulted for exact application
            guidelines as they may vary from manufacturer to manufacturer.
            In addition to opening very fast, these devices can be used as fault current limiters to protect otherwise
            underrated equipment; however, they should not be used for that purpose in new system designs if full rated
            equipment is available. In some applications, such as retrofitting existing installations, these devices may
            provide one of few practical alternatives to achieve lower levels of incident energy or protect equipment that
            is underrated for the available prospective short-circuit current. However, there are limitations that must be
            considered in consultation with the respective manufacturers.
            Coordinate the system voltage rating with the surge arrester voltage rating for surge protection selectivity
            when protection is installed on transformer primary. Consult with the manufacturers for application.
            For further discussion of voltage surge protection, see Chapter 6 in IEEE Std 141 (IEEE Red Book™), 7.8 of
            IEEE Std C37.20.3-2001, IEEE Std C62.22, and IEEE Std C62.92.1.
            19. Conclusions
            Because of its importance in the electric power system, the bus and switchgear should be designed, located,
            and maintained to prevent faults as well as to protect quickly when faults happen. System reliability and
            safety is promoted by good protection as well as by good systems design; designing for maintainability, future
            expansion when applicable, and by considering prevention through design practices that maximize safety for
            maintenance and operating personnel. IEEE standards in the 3007 series of operation, maintenance, and safety
            standards [B15], [B16], and [B17] offer guidance on these subjects.
                                                                         57
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            The preferred protection practice for switchgear buses applied at 1 kV or greater is differential protection.
            But today, in an arc-flash conscious world, differential protection should be considered for LV buses as well.
            In LV systems, arcing currents can be substantially lower than bolted fault currents, hence the sensitivity of
            protection is as important as the operating time. Differential protection can get around the need to use ever
            increasing thresholds that eventually cause important bus protection to be insufficiently sensitive to provide
            desired protection. For additional reading, see Pavavicharn et al. [B29] and Rifaat [B30]. Arc-flash relays
            provide an alternative to bus differential protection or a way to compliment bus differential protection. Light-
            based sensing technology has been available for several years but is rapidly evolving with new products
            frequently being introduced into the market.
            Improved zone-selective-interlocking capabilities available in protective relays and integral LV trip units
            provide additional ways to improve bus protection over traditional nested threshold and nested static time
            delay-based selectivity. Protection of buses, such as the one between a distribution transformer’s terminals and
            the first secondary overcurrent protector, is important for arc-flash protection as well as for system reliability.
            Today, multiple manufacturers offer systems, devices, and protection schemes specifically targeting buses in
            LV substations including the bus between the secondary substation transformer LV terminals and the first LV
            overcurrent device in the system. Such protection may not have been considered important enough to warrant
            the cost or complexity just a few years ago, but today the importance has grown and the complexity and cost
            are lower. For further reading, see Valdes et al. [B41], and Hodgson and Shipp [B8].
            Modern digital relays with embedded computers able to handle complex computational tasks and complex
            logic are commonly and more cost effectively available from multiple manufacturers. Advances in electronics
            and sensing facilitate improvements in the products available. Schemes that in the past required many dedicated
            CTs connected to dedicated single function relays can now be implemented with fewer CTs connected to
            multifunction protective relays. Additional communications, metering, and diagnostic capabilities provided
            by the same relays add to the value provided by the investment and expand the range of benefits the devices
            can provide. The industry has also introduced new switching devices that allow relay-controlled protection in
            applications that formerly were relegated to simpler and lower cost but more limited protection. How a bus
            is configured is also important to its long-term protection. How it is connected to its sources, interconnection
            circuit breakers or ties, bus transfer schemes, and other factors will affect safety, ability to maintain system
            reliability, and the capability for future growth. How reliable and well protected a bus is will depend on these
            factors as well as on the relaying used. Location of the equipment in a good environment and maintenance on
            a planned basis helps prevent faults, may prevent nuisance operations by protective devices, and ensures the
            devices operate as expected when called upon to do so. If a fault does occur, high-speed, sensitive relaying
            limits the damage so that repairs can be made quickly, and service is restored in a short time. Fast clearing of
            arcing faults also can save lives by minimizing the electrical explosion and consequent arc-flash hazard.
            Modern technology and continuous innovation provide an ever-increasing array of alternatives; it is up to the
            system design and protection engineer to fully take advantage of them.
                                                                         58
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            Annex A
            (informative)
            Bibliography
            Bibliographical references are resources that provide additional or helpful material but do not need to be
            understood or used to implement this standard. Reference to these resources is made for informational use
            only.
            [B1] Apostolov, A., “IEC 61850 Based Bus Protection—Principles and Benefits,” IEEE Power and Energy
            Society General Meeting, pp. 1-6, 2009, http://dx.doi.org/10.1109/PES.2009.5275403.
            [B2] Apostolov, A. and D. Tholomier, “Impact of IEC 61850 on Power System Protection,” IEEE PES Power
            Systems Conference and Exposition, 2006. PSCE, 2006.
            [B3] Beckmann, J. J., D. Dalasta, E. W. Hendron, and T. D. Higgins, “Service Supply Line Protection,”
            IEEE Transactions on Industry and General Applications, vol. IGA5, pp. 657-671, November/
            December 1969, http://dx.doi.org/10.1109/TIGA.1969.4181091.
            [B4] Behrendt, K., K. Costello, and S. Zocholl, “Considerations for Using High-Impedance or Low-Impedance
            Relays for Bus Differential Protection,” 63rd Annual Conference for Protective Relay Engineers (Sponsored
            by IEEE Power and Energy Society and Texas A&M University), pp. 1-15, 2010, http://dx.doi.org/10.1109/
            CPRE.2010.5469509.
            [B5] Cable, B. W., L. J. Powell, and R. L. Smith, “Application Criteria for High-Speed Bus
            Differential Protection,” IEEE Transactions on Industry Applications, vol. IA-19, no. 4, July 1983, http://
            dx.doi.org/10 .1109/TIA.1983.4504263.
            [B7] Franklin, R. et al., “High-Impedance Differential Applications, With Mismatched CTs,” Proceedings of
            the Western Protective Relay Conference, Spokane, WA, October 2017.
            [B8] Hodgson, D. L. and D. Shipp, “Arc-Flash Incident Energy Reduction Using Zone Selective
            Interlocking,” IEEE Transactions on Industry Applications, vol. 46, no. 3, pp. 1243-1251, 2010, http://
            dx.doi.org/10.1109/ TIA.2010.2046284.
            [B9] Holbach, J., “Comparison Between High Impedance and Low Impedance Bus Differential Protection,”
            IEEE Power Systems Conference 2009, Clemson, SC, USA.
            [B10] IEC 61850:2017, SER Series: Communication networks and systems for power utility automation—All
            parts.
            [B11] IEEE Std 142™ (IEEE Green Book™), IEEE Recommended Practice for Grounding of Industrial and
            Commercial Power Systems.
            [B12] IEEE Std 242™ (IEEE Buff Book™), IEEE Recommended Practice for Protection and Coordination of
            Industrial and Commercial Power Systems.
            [B13] IEEE P3004.3™/D1b-2017, IEEE Draft Recommended Practice for the Application of Low-Voltage
            Fuses in Industrial and Commercial Power Systems.
                                                                         59
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            [B14] IEEE Std 3004.8™, IEEE Recommended Practice for Motor Protection in Industrial and Commercial
            Power Systems.
            [B15] IEEE Std 3007.1™, IEEE Recommended Practice for the Operation and Management of Industrial and
            Commercial Power Systems.
            [B16] IEEE Std 3007.2™ IEEE Recommended Practice for the Maintenance of Industrial and Commercial
            Power Systems.
            [B17] IEEE Std 3007.3™, IEEE Recommended Practice for Electrical Safety in Industrial and Commercial
            Power Systems.
            [B18] IEEE Std C37.20.9™, IEEE Standard for Metal-Enclosed Switchgear Rated 1 kV to 52 kV Incorporating
            Gas Insulating Systems.
[B19] IEEE Std C37.95™-2014, IEEE Guide for Protective Relaying of Utility-Consumer Interconnections.
[B20] IEEE Std C37.119™, IEEE Guide for Breaker Failure Protection of Power Circuit Breakers.
[B21] IEEE Std C37.234™, IEEE Guide for Protective Relay Applications to Power System Buses.
            [B22] Kasztenny, B., G. Brunello, and L. Sevov, “Digital low-impedance bus differential protection with
            reduced requirements for CTs,” Transmission and Distribution Conference and Exposition, 2001 IEEE/PES,
            http://dx.doi.org/10.1109/TDC.2001.971325.
            [B23] Kay, J. A., J. Arvola, and L. Kumpulainen, “Protecting at the Speed of Light,” IEEE
            Industry Applications Magazine, vol. 17, no. 3, pp. 12-18, 2011, http://dx.doi.org/10.1109/
            MIAS.2010.939635.
            [B24] Mello, M., M. Noonan, M. Valdes, and J. Benavides, “Arc-Flash Hazard Reduction at Incoming
            Terminals of LV Equipment,” IEEE Petroleum and Chemical Industry Technical Conference, 2014.
[B25] NEMA AB5-2016, Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers.
[B27] NEMA PB2.2, Application Guide for Ground-Fault Protective (GFP) Devices for Equipment.
            [B28] Paul, D. and B. Chavdarian, IEEE Industry Applications Magazine, vol. 21, no. 1, pp. 23-32, 2015.
            Available at: , http://dx.doi.org/10.1109/MIAS.2014.2345797.
            [B30] Rifaat, R. M., “Considerations in applying power bus protection schemes to industrial and IPP
            Systems,” IEEE Transactions on Industry Applications, vol. 40, no. 6, pp. 1705-1711, November-December
            2004, http:// dx.doi.org/10.1109/TIA.2004.836223.
            [B31] Roscoe, G., T. Papallo, and M. Valdes, “Arc-flash energy mitigation by fast energy capture,” 56th
            Annual Petroleum and Chemical Industry Conference, IEEE Industry Applications Society Record of
            Conference Papers, pp. 1-9, 2009.
                                                                         60
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 3004.11-2019
                   IEEE Recommended Practice for Bus and Switchgear Protection in Industrial and Commercial Power Systems
            [B32] Roscoe, G., M. E. Valdes, and R. Luna, “Methods for arc-flash detection in electrical equipment,” 57th
            Annual Petroleum and Chemical Industry Conference (PCIC), IEEE Industry Applications Society Record of
            Conference Papers, pp. 1-8, 2010, http://dx.doi.org/10.1109/PCIC.2010.5666877.
            [B33] Simpson, R. H., “NEC Design Compliance, System Protection and Arc-Flash Hazard,”
            IEEE Transactions on Industry Applications, vol. 49, no. 4, pp. 1928-1936, 2003, http:// dx .doi .org/
            10.1109/TIA .2013.2256768.
            [B34] Thompson, M. J., “Percentage Restrained Differential, Percentage of What?” Proceedings of the 37th
            Annual Western Protective Relay Conference, Spokane, WA, October 2010.
            [B36] UL 347-CSA C22.2 No. 253—NMX-J-564–106-ANCE, Standard for Safety for Medium-Voltage AC
            Contactors, Controllers, and Control Centers.
[B40] UL 1066, UL Standard for Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures.
            [B41] Valdes, M. E. and J. Dougherty, “Advances in Protective Device Interlocking for Improved
            Protection and Selectivity,” IEEE Transactions on Industry Applications, vol. 50, no. 3, pp. 1639-1648,
            2014, http://dx .doi.org/10.1109/TIA.2013.2285941.
            [B42] Valdes, M., P. Hamer, T. Papallo, R. Narel, and B. Premerlani, “Zone Based Protection for Low-voltage
            Systems; Zone Selective Interlocking, Bus Differential and the Single Processor Concept,” IEEE Petroleum
            and Chemical Industry Technical Conference, pp. 1-10, 2007, http://dx.doi.org/10.1109/PCICON.2007
            .4365789.
            [B43] Valdes, M. E., S. Hansen, and P. Sutherland, “Optimized Instantaneous Protection Settings:
            Improving Selectivity and Arc-Flash Protection,” IEEE Industry Applications Magazine, vol. 18, no. 3, pp.
            66-73, 2012, http://dx.doi.org/10.1109/MIAS.2012.2186008.
            [B44] Valdes, M. E., I. Purkayastha, and T. Papallo, “The Single-Processor Concept for Protection and Control
            of Circuit Breakers in Low-Voltage Switchgear,” IEEE Transactions on Industry Applications, vol. 40, no.
            4, pp. 932-940, 2004, http://dx.doi.org/10.1109/TIA.2004.831270.
            [B45] Valdes, M. E. and L. Sevov, “Considerations for Differential Protection in Low Voltage Buses,”
            IEEE Industry Applications Magazine, 2017.
                                                                         61
                                                     Copyright © 2019 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.
   RAISING THE
   WORLD’S
   STANDARDS
   Connect with us on:
          Twitter: twitter.com/ieeesa
          Facebook: facebook.com/ieeesa
          LinkedIn: linkedin.com/groups/1791118
          Beyond Standards blog: beyondstandards.ieee.org
          YouTube: youtube.com/ieeesa
   standards.ieee.org
   Phone: +1 732 981 0060
Authorized licensed use limited to: UNIVERSIDADE FEDERAL FLUMINENSE. Downloaded on March 18,2020 at 03:05:52 UTC from IEEE Xplore. Restrictions apply.