IEEE Guide For The Design of Low-Voltage Auxiliary Systems For Electric Power Substations
IEEE Guide For The Design of Low-Voltage Auxiliary Systems For Electric Power Substations
Sponsored by the
Substations Committee
  Authorized licensed use limited to: Centro Universitário Fei. Downloaded on October 11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                                                                         IEEE Std 1818™-2017
Sponsor
    Substations Committee
    of the
    IEEE Power and Energy Society
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on October 11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    Abstract: Considered in this guide are the components of both the ac and dc systems and the
    provided guidelines and recommendations for designing the appropriate systems for the substation
    under consideration. This guide includes the low-voltage auxiliary systems from the source(s) to the
    distribution point(s). Reliability requirements and load characteristics are discussed and distribution
    methods are recommended.
    Keywords: ac system, auxiliary systems, battery, dc system, IEEE 1818, low voltage, station
    power, station service
    IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics Engineers,
    Incorporated.
                                              STD22934
                                              STDPD22934
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on October 11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    Important Notices and Disclaimers Concerning IEEE Standards Documents
    IEEE documents are made available for use subject to important notices and legal disclaimers. These notices
    and disclaimers, or a reference to this page, appear in all standards and may be found under the heading
    “Important Notice” or “Important Notices and Disclaimers Concerning IEEE Standards Documents.”
    IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and
    expressly disclaims all warranties (express, implied and statutory) not included in this or any other document
    relating to the standard, including, but not limited to, the warranties of: merchantability; fitness for a particular
    purpose; non-infringement; and quality, accuracy, effectiveness, currency, or completeness of material. In
    addition, IEEE disclaims any and all conditions relating to: results; and workmanlike effort. IEEE standards
    documents are supplied “AS IS” and “WITH ALL FAULTS.”
    Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there
    are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to
    the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved and
    issued is subject to change brought about through developments in the state of the art and comments received
    from users of the standard.
    In publishing and making its standards available, IEEE is not suggesting or rendering professional or other
    services for, or on behalf of, any person or entity nor is IEEE undertaking to perform any duty owed by any
    other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his or
    her own independent judgment in the exercise of reasonable care in any given circumstances or, as appropriate,
    seek the advice of a competent professional in determining the appropriateness of a given IEEE standard.
    IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,
    EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO:
    PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS;
    OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY,
    WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR
    OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE
    UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND
    REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE.
Translations
    The IEEE consensus development process involves the review of documents in English only. In the event that
    an IEEE standard is translated, only the English version published by IEEE should be considered the approved
    IEEE standard.
                                                                        3
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    Official statements
    A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board Operations
    Manual shall not be considered or inferred to be the official position of IEEE or any of its committees and shall
    not be considered to be, or be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or
    educational courses, an individual presenting information on IEEE standards shall make it clear that his or her
    views should be considered the personal views of that individual rather than the formal position of IEEE.
Comments on standards
    Comments for revision of IEEE Standards documents are welcome from any interested party, regardless
    of membership affiliation with IEEE. However, IEEE does not provide consulting information or advice
    pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a
    proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a
    consensus of concerned interests, it is important that any responses to comments and questions also receive
    the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and Standards
    Coordinating Committees are not able to provide an instant response to comments or questions except in
    those cases where the matter has previously been addressed. For the same reason, IEEE does not respond to
    interpretation requests. Any person who would like to participate in revisions to an IEEE standard is welcome
    to join the relevant IEEE working group.
    Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with
    the provisions of any IEEE Standards document does not imply compliance to any applicable regulatory
    requirements. Implementers of the standard are responsible for observing or referring to the applicable
    regulatory requirements. IEEE does not, by the publication of its standards, intend to urge action that is not in
    compliance with applicable laws, and these documents may not be construed as doing so.
Copyrights
    IEEE draft and approved standards are copyrighted by IEEE under U.S. and international copyright laws. They
    are made available by IEEE and are adopted for a wide variety of both public and private uses. These include
    both use, by reference, in laws and regulations, and use in private self-regulation, standardization, and the
    promotion of engineering practices and methods. By making these documents available for use and adoption
    by public authorities and private users, IEEE does not waive any rights in copyright to the documents.
Photocopies
    Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to photocopy
    portions of any individual standard for company or organizational internal use or individual, non-commercial
    use only. To arrange for payment of licensing fees, please contact Copyright Clearance Center, Customer
    Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions
    of any individual standard for educational classroom use can also be obtained through the Copyright Clearance
    Center.
                                                                        4
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    Updating of IEEE Standards documents
    Users of IEEE Standards documents should be aware that these documents may be superseded at any time
    by the issuance of new editions or may be amended from time to time through the issuance of amendments,
    corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the
    document together with any amendments, corrigenda, or errata then in effect.
    Every IEEE standard is subjected to review at least every ten years. When a document is more than ten years
    old and has not undergone a revision process, it is reasonable to conclude that its contents, although still of
    some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that
    they have the latest edition of any IEEE standard.
    In order to determine whether a given document is the current edition and whether it has been amended through
    the issuance of amendments, corrigenda, or errata, visit the IEEE-SA Website at http://ieeexplore.ieee.org/xpl/
    standards.jsp or contact IEEE at the address listed previously. For more information about the IEEE-SA or
    IEEE’s standards development process, visit the IEEE-SA Website at http://standards.ieee.org.
Errata
    Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL: http://
    standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata periodically.
Patents
    Attention is called to the possibility that implementation of this standard may require use of subject matter
    covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to the
    existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant has
    filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the IEEE-
    SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may indicate
    whether the Submitter is willing or unwilling to grant licenses under patent rights without compensation
    or under reasonable rates, with reasonable terms and conditions that are demonstrably free of any unfair
    discrimination to applicants desiring to obtain such licenses.
    Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
    responsible for identifying Essential Patent Claims for which a license may be required, for conducting inquiries
    into the legal validity or scope of Patents Claims, or determining whether any licensing terms or conditions
    provided in connection with submission of a Letter of Assurance, if any, or in any licensing agreements are
    reasonable or non-discriminatory. Users of this standard are expressly advised that determination of the
    validity of any patent rights, and the risk of infringement of such rights, is entirely their own responsibility.
    Further information may be obtained from the IEEE Standards Association.
                                                                        5
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    Participants
At the time this IEEE guide was completed, the D9 Working Group had the following membership:
    The following members of the balloting committee voted on this guide. Balloters may have voted for approval,
    disapproval, or abstention.
                                                                        6
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    When the IEEE-SA Standards Board approved this guide on 28 September 2017, it had the following
    membership:
*Member Emeritus
                                                                        7
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    Introduction
      This introduction is not part of IEEE Std 1818-2017, IEEE Guide for the Design of Low-Voltage Auxiliary Systems for
      Electric Power Substations.
    IEEE Guide 1818 was created by members of Working Group D9 and is under the sponsorship of the
    Substations Committee of the IEEE Power & Energy Society. This guide provides guidance and information
    to substation engineers on factors to consider in the design of ac and dc auxiliary systems for application in
    electric substations. This guide references several existing standards and is not intended to replace existing
    documentation, but to provide guidance for the application of ac and dc systems specifically in substation
    applications.
Acknowledgment
The D9 Working Group would like to acknowledge Chuck Haahr for his fine work as technical editor.
                                                                        8
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    Contents
    1. Overview��������������������������������������������������������������������������������������������������������������������������������������������������� 13
       1.1 Scope�������������������������������������������������������������������������������������������������������������������������������������������������� 13
       1.2 Purpose����������������������������������������������������������������������������������������������������������������������������������������������� 13
2. Normative references�������������������������������������������������������������������������������������������������������������������������������� 13
3. Definitions������������������������������������������������������������������������������������������������������������������������������������������������� 13
                                                                                    9
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    List of Figures
Figure 13—Sub-panelboard��������������������������������������������������������������������������������������������������������������������������� 46
Figure 20—Secondary selective system with backup generator and additional redundancy�������������������������� 51
                                                                              10
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    Figure C.1—Substation one-line diagram������������������������������������������������������������������������������������������������������ 85
                                                                             11
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    List of Tables
                                                                              12
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
    IEEE Guide for the Design of Low-
    Voltage Auxiliary Systems for
    Electric Power Substations
    1. Overview
    1.1 Scope
    This guide will consider the components of both the ac and dc systems and provide guidelines and
    recommendations for designing the appropriate systems for the substation under consideration. This
    guide covers the low-voltage auxiliary systems from the source(s) to the distribution point(s). Reliability
    requirements and load characteristics are discussed, and distribution methods are recommended.
    1.2 Purpose
    The low-voltage ac and dc auxiliary systems comprise very important parts of the substation equipment. The
    design of the ac and dc auxiliary systems facilitates the safe and reliable operation of the substation. This
    guide considers various factors that affect the design of the ac and dc auxiliary systems such as reliability, load
    requirements, system configurations, personnel safety, and protection of auxiliary systems equipment.
    2. Normative references
    The following referenced documents are indispensable for the application of this document (i.e., they must
    be understood and used, so each referenced document is cited in text and its relationship to this document is
    explained). For dated references, only the edition cited applies. For undated references, the latest edition of the
    referenced document (including any amendments or corrigenda) applies.
IEEE Std 485™, IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications.1,2
IEEE Std 525™, IEEE Guide for the Design and Installation of Cable Systems in Substations.
    3. Definitions
    For the purposes of this document, the following terms and definitions apply. The IEEE Standards Dictionary
    Online should be consulted for terms not defined in this clause.3
    1
      The IEEE standards or products referred to in this clause are trademarks of The Institute of Electrical and Electronics Engineers, Inc.
    2
      IEEE publications are available from The Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854, USA
    (http://standards.ieee.org).
    3
      IEEE Standards Dictionary Online subscription is available at: http://www.ieee.org/portal/innovate/products/standard/
    standards_dictionary.html.
                                                                       13
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    authority having jurisdiction (AHJ): The organization, office, or individual that has the responsibility and
    authority for approving equipment, installations, or procedures.
    available short-circuit current: (at a given point in a circuit) The maximum current that the power system
    can deliver through a given circuit to any negligible-impedance short circuit applied at the given point, or at
    any other point that will cause the highest current to flow through the given point.
    basic impulse insulation level (BIL): A reference impulse insulation strength expressed in terms of the crest
    value of the withstand voltage of a standard full impulse voltage wave.
battery duty cycle: The sequence of loads a battery is expected to supply for specified time periods.
cell size: The rated capacity of a cell, or the number of positive plates in a cell.
    equalizing charge: A charge, at a level higher than the normal float voltage, applied for a limited period of
    time, to correct inequalities of voltage, specific gravity, or state of charge that may have developed between the
    cells during service.
extra-high voltage (EHV): A maximum system voltage that is greater than 242 kV but less than 1000 kV.
    ferroresonance: (A) A phenomenon usually characterized by overvoltages and very irregular wave shapes
    and associated with the excitation of one or more saturable inductors through capacitance in series with the
    inductor. (B) An electrical resonant condition associated with the saturation of a ferromagnetic device, such
    as a transformer, through capacitance. Ferroresonance can arise when (1) due to dissimilar phase switching,
    the capacitance normally in shunt with the ferromagnetic device becomes energized in series with the device,
    (2) a weak source is isolated with a lightly loaded feeder containing power-factor-correction capacitors.
    For example, if the resulting voltage buildup produces saturation of the feeder transformers, there will be
    an interchange of energy between the system capacitance and the nonlinear magnetizing reactance of the
    transformers.
    float charge: A constant-voltage applied to a battery to maintain it in a fully charged condition, while
    minimizing degradation or water consumption.
    float service: Operation of a dc system in which the battery spends the majority of the time on float charge with
    infrequent discharge. Syn: standby service.
fully rated system: Every protective device is rated to at least the available fault current at the service point.
    high voltage: A class of nominal system voltages equal to or greater than 100 000 V and equal to or less than
    242 000 V.
low voltage: Voltage levels that are less than or equal to 1 kV.
medium voltage: A class of nominal system voltages greater than 1000 V and less than 100 000 V.
    molded-case circuit breaker (MCCB): A circuit breaker that is assembled as an integral unit in a supporting
    and enclosing housing of insulating material.
    nominal battery voltage: The value assigned to a battery of a given voltage class for the purpose of convenient
    designation. The operating voltage of the system may vary above or below this value.
    nominal system voltage: The ac system voltage by which the system is designated and to which certain
    operating characteristics of the system are related.
                                                                       14
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    panelboard: A single panel or group of panel units designed for assembly in the form of a single panel,
    including buses and automatic overcurrent devices, and equipped with or without switches for the control
    of light, heat, or power circuits; designed to be placed in a cabinet or cutout box placed in or against a wall,
    partition, or other support; and accessible only from the front. (Adapted from the NEC.) See also: switchboard.
    period: An interval of time in the battery duty cycle during which the current (or power) is assumed to be
    constant for purposes of cell-sizing calculations.
    rated capacity (lead-acid): The capacity assigned to a cell by its manufacturer for a given discharge rate, at a
    specified electrolyte temperature and specific gravity, to a given end-of-discharge voltage.
    remote terminal unit (RTU): A piece of equipment located at a distance from a master station to facilitate
    monitoring and control the state of outlying power equipment and to communicate the information back to the
    master station or host.
    separately derived system: A wiring system whose power is derived from a generator, transformer, or
    converter windings and has no direct electrical connection, including a solidly connected grounded circuit
    conductor, to supply conductors originating in another system.
    series rated system: Each protective device needs to only be rated for the available fault current at its
    terminals.
    station service voltage transformer (SSVT): A transformer that supplies power from a station high-voltage
    bus to the station auxiliaries and also to the unit auxiliaries during unit startup and shutdown, or when the unit
    auxiliaries transformer is not available, or both.
    switchboard: (A) A large, single-panel, frame, or assembly of panels on which are mounted, on the face, back,
    or both, switches, overcurrent and other protective devices, buses, and usually instruments. Switchboards are
    generally accessible from the rear as well as from the front, and are not intended to be installed in cabinets.
    (Adapted from the NEC.) (B) A metal-enclosed panel or assembly of panels that may contain molded case,
    insulated case, or power circuit breakers, bolted pressure contact or fusible switches, protective devices,
    and instruments. These devices may be mounted on the face or the back of the assembly. Switchboards are
    generally accessible from the rear as well as from the front; however, they can be front accessible only.
    switchgear: (A) A general term covering switching and interrupting devices and their combination with
    associated control, instrumentation, metering, protective, and regulating devices and covering assemblies
    of these devices with associated interconnections, accessories, and supporting structures used primarily
    in connection with the generation, transmission, distribution, and conversion of electrical power. (B) An
    assembly of equipment used to switch and control electrical power.
    tertiary winding: An additional winding in a transformer that can be connected to a synchronous condenser,
    a reactor, an auxiliary circuit, etc. For transformers with wye-connected primary and secondary windings, it
    may also help (1) to stabilize voltages to the neutral, when delta connected (2) to reduce the magnitude of third
    harmonics when delta connected (3) to control the value of the zero-sequence impedance (4) to serve load.
    valve-regulated lead-acid (VRLA) cell: A lead-acid cell that is sealed with the exception of a valve that
    opens to the atmosphere when the internal pressure in the cell exceeds atmospheric pressure by a preselected
                                                                       15
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    amount. VRLA cells provide a means for recombination of internally generated hydrogen and oxygen to limit
    water consumption.
    vented battery: A battery in which the products of electrolysis and evaporation are allowed to escape to the
    atmosphere as they are generated. These batteries are also commonly referred to as flooded.
    4
      Notes in text, tables, and figures of a standard are given for information only and do not contain requirements needed to implement this
    standard.
                                                                        16
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    NOTE—The above letters reference different subsections covering specific components of ac auxiliary power schemes as
    follows: A: see 4.2, 4.3, and 4.4; B: see 4.5; C: see 4.6; D: see 4.7; E: see 4.8; F: see 4.9.
In the first step of the design process, the design engineer should review:
    In general, the design criteria of the ac auxiliary system are determined by the existing, proposed, and future
    substation loads, typically measured in kVA. Diversity of the total connected load needs to be considered as
    not all loads are concurrent. For example, the control enclosure cooling system should not run simultaneously
    with the heating system; redundant cooling systems are not concurrent; and spring charging motors for power
    circuit breakers may not run concurrently.
                                                                       17
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Also considered with the substation loads are the equipment voltage ratings and phase requirements (single-
    or three-phase) of the substation equipment to be installed. When sizing auxiliary transformers and other
    station power components, the designer should consider substation expansion and short-term loads, such
    as construction or maintenance loads. Timing of any proposed expansion may dictate initial installation or
    deferral of station power components. Some loads may be identified as critical, which requires ac service to
    be maintained continuously. Depending upon such critical loads, the substation may require two or three ac
    station service sources with the ability to transfer loads between sources.
    Due to the importance of the station power to the operation and reliability of the substation, the following factors
    should be considered in order to determine the required station power configurations. This guide indicates
    various equipment ratings (voltage, ampacity, capacity, etc.) compliant with IEEE and NEMA standards.
    Equipment with other ratings conforming to standards published by other organizations is available. Design
    philosophies and practices presented in this guide should be adapted appropriately based on the equipment
    utilized in design and authority having jurisdiction.
    System stability considerations are important for the reliability requirements of the station power. If the loss
    of a substation results in a system disturbance to the electrical grid that could create a blackout condition in
    the area, the station service system should have an independent power source. The auxiliary power system
    requirements for redundant supply may also need to include the ability for the station to complete black start
    operations—meaning a local generation source is required to supply the station power system and battery
    chargers for the protection circuits in the event of a system collapse and subsequent repowering. See 4.3.5 and
    4.7.5.
    Some substations serve critical loads such as hospitals, manufacturing complexes, government offices,
    schools, or serve large blocks of load where the substation reliability requirements are high. Some substations
    are connected to power plants that obtain at least a portion of their station service from the substation. Loss
    of the substation station service may result in tripping the plant and lead to a loss of revenue. These type of
    stations may need multiple station power sources. Other less critical substations may only have one station
    power source.
    Substation equipment protection considerations should be given to all substations regardless of the size.
    High-voltage and extra-high-voltage substations contain expensive equipment such as transformers where
    the cooling system is important for operation and a backup source is generally required. Similarly, protective
    relays or other electronic control equipment located in high-temperature areas may require a continuous
    cooling system and a second power source. Separately implemented control and protection schemes may be
    implemented to mitigate the likelihood of equipment damage. The control and protection schemes are outside
    the scope of this guide.
    For neutral grounding, there are several different grounding philosophies. The designer should ground station
    service transformer neutrals per utility practice or local jurisdictional requirements.
The designer may consider the following list when designing an ac system for substations:
                                                                       18
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                          IEEE Std 1818-2017
                        IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
          d)     Non-essential loads
          e)     Conductor types and sizes
          f)     Voltage drop calculations
          g)     Jurisdictional requirements such as the National Electrical Code® (NEC®) [B34]5
          h)     Arc flash considerations
    Several secondary voltage levels are available for ac auxiliary systems. When determining the secondary
    voltage, the designer may use a standard voltage level determined by the designer’s power system or use a
    voltage level based on the supplied equipment. Either way, the designer should consider the factors listed
    in 4.4. Voltage ratings listed in this document are typical of North American power systems, but are not all
    inclusive. Variations to these voltages discussed in this document are common in other areas of the world.
    Three ac sources are represented in Figure 1. One source, typically the most reliable source, is designated as
    the primary, or normal, source. The second source is designated as the backup source and is used when the
    normal source is unavailable. The third source is used as a second backup and is utilized only when both the
    normal and secondary sources are unavailable.
There are four sources that are commonly used as substation ac auxiliary power sources:
    Each source has advantages and disadvantages. Substation location, substation equipment, and bus
    configurations may dictate which source is normal. The selection of redundant sources is important so an
    outage would not remove both normal and alternate sources.
    The tertiary of a power transformer in substations can provide a reliable source for station power applications.
    When the primary and secondary windings are connected wye, a third winding connected in delta is typically
    used for transformer stabilizing purposes. A tertiary winding presents a low impedance path for zero-sequence
    currents and harmonics, thereby reducing the zero-sequence impedance presented to the outside world, while
    avoiding the problem of tank heating. The tertiary winding typically has a volt-ampere rating between 20% to
    30% of the volt-ampere rating of the primary winding. The tertiary winding typically has a medium-voltage
    rating up to 34.5 kV. If there are plans to use the transformer tertiary for station auxiliary power purposes, the
    tertiary winding is brought out of the transformer through bushings.
    The volt-ampere rating of the tertiary winding typically exceeds the maximum volt-ampere requirement of a
    substation’s ac auxiliary power load and is an adequate ac auxiliary power source.
    5
        The numbers in brackets correspond to those of the bibliography in Annex A.
                                                                        19
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Consideration should be given to the available fault current at the tertiary bus. In the case that the fault current
    magnitude exceeds the interrupting rating of the protective equipment, such as fuses or circuit breakers,
    several options can be employed to mitigate the fault current. These options include installing current limiting
    fuses, resistors, or reactors; or increasing the transformer tertiary impedance.
    The substation bus is another available source for auxiliary station power. When distribution voltage is
    available, distribution transformers are typically utilized for station service. Transmission voltage buses can
    be used, but are not typically preferred due to their relatively high cost. A station service voltage transformer
    (SSVT) is used to transform the transmission bus voltage to the ac auxiliary voltage. These transformers are
    available for voltages from 34.5 kV to 345 kV. One or more SSVTs might be required, depending on required
    station power load. See Figure 2 for possible connections.
    The SSVT is located within the line or bus zone of protection. A fault on the SSVT may be cleared by the
    protective relay or by a high-side fuse. Depending on the size of the SSVT, the required fuse ampacity may not
    be available for certain voltage levels. The protection engineer should be consulted for the final location when
    determining the required SSVT protection. Low-side overcurrent protection of the secondary conductors
    used for auxiliary station service are typically applied as close to the secondary terminals as possible. Surge
    protection is typically needed on the high-side connection of the SSVT. If arresters protecting other equipment
    in the station are close enough to protect the SSVT, a dedicated arrester for the SSVT may not be required.
    Guidance on surge protection and separation effects can be found in IEEE Std C62.22™ [B27].
                                                                       20
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    A common source for substation auxiliary station power is the use of nearby distribution feeder circuits. The
    feeder primary is typically connected to a step-down transformer located near the control enclosure. If the
    feeder is owned by another utility, a revenue meter is installed. Since the feeder has more exposure to faults, it
    is typically used as a backup to the primary source.
    Generators may also be used as an ac auxiliary power source. In substations, generators are typically used
    as an emergency/backup power source. There are many disadvantages in using generators as a permanent ac
    auxiliary source. Choosing to use generators as a permanent ac auxiliary source requires additional design
    considerations. When using generators, designers should consider fire-protection systems, fuel-storage
    systems, ventilation, and the climate. Generators may also be housed in a separate building structure, which
    requires the installation of a ventilation system. If the generators are located outdoors in the switchyard, there
    is a reduced need for fire-protection installation, fuel-storage systems, or building ventilation.
    In order to design a reliable station service system, the ac loads for the system need to be identified and
    calculated. The designer should consider the ultimate plan for the substation in order to account for future
    loads anticipated at the station. After the ac loads have been identified, the demand and load factors for each
    load should be applied. The resultant ac loads are used to size the station service transformer(s) and determine
    associated conductor ratings. The use of demand and load factors allow for the economical selection of the
    transformer size without being overly conservative.
The following types of loads should be considered when identifying the overall station load:
                                                                       21
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
        d)    Ancillary structures: The substation may have additional structures for maintenance, storage, or other
              purposes. Include any heating, ventilation, and air conditioning (HVAC), equipment, or structure
              auxiliary load if it is sourced from the substation ac system.
        e)    Future build out: In order to account for the ultimate load of the substation, any future loads should be
              considered and included in calculating the maximum station load. This includes loads for additional
              power transformers, cooling and heating, breakers, etc.
    Once all planned and future loads have been identified, the ratings for each load need to be established. Ratings
    may be provided by the equipment manufacturer in amperes, watts, or kVA. In order to calculate the station
    load, a common basis needs to be used. Either current or kVA are typically used because both are easy and
    straightforward. If current is used, the total power should be calculated based on the respective voltage class
    of the equipment. Loads also should be segregated between single-phase and three-phase. For multiple-phase
    systems, loads need to be balanced between phases for optimal transformer loading.
    The demand factor is the ratio of the maximum coincident demand of a system, or part of a system, to the total
    load connected to the system, or part of the system, per IEEE Std 141™ [B3]:
    Demand factors can also be established for a subset of similar equipment (such as receptacles) rather than only
    a single system-level demand factor.
    The second consideration is the amount of time that a load runs based on a selected period of time, referred
    to as load factor. Load factor is the ratio of the average load over a designated period of time to the peak load
    occurring in that period per IEEE Std 141 [B3]:
    The period for which the load factor is considered should be chosen based on the load capability of the
    transformer(s) that is used in the design. For best practice, loads operating for three hours or more should be
    considered as continuous load. High loads that operate for short periods of time also need special consideration
    in relation to the entire system load.
    After equipment ratings have been established, the demand and load factors are selected. Selecting the demand
    and load factors often requires engineering judgment in terms of familiarity with substation operations and
    understanding how the loads such as receptacles, lighting, air conditioning, transformer cooling fans, etc.,
    are applied. Applying the demand and load factors provides a more realistic adjusted load (rather than simply
    summing up the nameplate ratings of the equipment) for sizing of the station service transformers. In the
    process of determining the ultimate loading, various conditions (generally the worst case scenario) under
    which loads may be operated should be considered, such as seasonal and/or time of day. The person responsible
    for the sizing of the transformer can perform the total adjusted load calculations.
    For information on the process of sizing transformers, see 4.6. Be aware that the thermal time constants
    (overload capability) of transformers are determined by the manufacturers and are typically different for
                                                                       22
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    dry type and liquid-immersed units. Refer to IEEE Std C57.91™ [B24] and IEEE Std C57.96™ [B25] for
    additional information.
    A general example of a substation load analysis is shown Table 1. The example only considers the case of loads
    running during the daytime in the summer. It is not an exact or comprehensive analysis for substations, but
    intended to illustrate one practical approach to the process. Load analysis varies based on substation voltage
    class, capacity, climate, and any non-traditional loads.
In the example, adjusted kVA load (for transformer sizing) is determined as follows:
adjusted kVA = quantity × kVA per unit × demand factor × load factoor (3)
    Justification or reasoning for the demand and load factors should be documented, such as shown in the
    comments column of the example.
    Subclause 4.5 presents general information useful in the selection of both line and load conductors. It describes
    various characteristics essential to conductor selection: conductor type, insulation type, insulation voltage
    rating, insulation temperature rating, conductor terminations, and conductor size. An essential document in
    understanding ac and dc cables used in substation design is IEEE Std 525™.
    A process flow chart has been developed to aid the designer/engineer in the conductor selection process.
    However, any rules and restrictions set forth by the authority having jurisdiction (AHJ) in the area that work is
    being performed supersede any documents referenced in this section.
    This section covers the selection of both line and load conductors. There are six main characteristics to consider
    when selecting a conductor—conductor type, insulation type, cable insulation voltage rating, cable insulation
    temperature rating, the terminations being connected to (temperature rating, ampacity, etc.), and conductor
    size. The engineer performing the conductor selection can use the process flow chart shown in Figure 3 and
    described in 4.5 for guidance on conductor selection based on these characteristics.
    For specific examples on selecting conductors (control, instrument, power, and communication), refer to the
    annexes in the latest version of IEEE Std 525.
                                                                       23
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                                                                                                                                                                               Table 1—Generic substation ac load study
                                                                                                                                                                                                                                                                   Three-
                                                                                                                                                                                                                                                     Single-
                                                                                                                                                      Equipment                      Volts   Amps      kW      Power     kVA     Load     Demand                    phase
                                                                                                                                                                       Qty   Phase                                                                  phase load                              Comments
                                                                                                                                                        type                         (ac)    (each)   (each)   factor   (each)   factor    factor                demand load
                                                                                                                                                                                                                                                      (kVA)
                                                                                                                                                                                                                                                                    (kVA)
                                                                                                                                                       Outdoor                                                                                                                 Considering one in use
                                                                                                                                                                        4     1ø     120     15.00    1.530     0.85    1.800    1.000     0.25        1.80
                                                                                                                                                      receptacles                                                                                                              at any given time.
                                                                                                                                                                                                                                                                               Considering two in use at any given
                                                                                                                                                                                                                                                                               time, more constant loads than
                                                                                                                                                        Indoor                                                                                                                 outdoor (commissioning, etc.).
                                                                                                                                                                        8     1ø     120     15.00    1.530     0.85    1.800    1.000     0.25        3.60
                                                                                                                                                      receptacles                                                                                                              Load factor is a median estimate for
                                                                                                                                                                                                                                                                               any connected equipment, which
                                                                                                                                                                                                                                                                               could run for two hours or more.
                                                   Copyright
                                                                                                                                                                                                                                                                               Estimated load and demand
                                                                                                                                                         Indoor
                                                                                                                                                                       20     1ø     208     1.20     0.213     0.85    0.250    1.000     1.000       5.00                    factors are based on potential
                                                                                                                                                     building lights
                                                                                                                                                                                                                                                                               occupancy at any given time.
                                                         Fei. Downloaded
                                                                                                                                                                                                                                                                               Basement lights are typically only
                                                                                                                                24
                                                               © 2017 IEEE.
                                                                                                                                                                                                                                                                               turned on as needed (maintenance,
                                                                                                                                                       Basement
                                                                                                                                                                       70     1ø     120     0.21     0.021     0.85    0.025    1.000     1.000       1.75                    etc.), but could be on for extended
                                                                                                                                                        lighting
                                                                         on October
                                                                                                                                                                                                                                                                               periods of time, depending on the
                                                                                                                                                                                                                                                                                                                                                            IEEE Std 1818-2017
                                                                             All rights
                                                                                                                                                                                                                                                                               One running at any given time,
                                                                                     11,2024
                                                                                                                                                       Roll-up
                                                                                                                                                                        2     3ø     208     3.27     1.000     0.85    1.176    0.000     1.000                    0.00       typically not running more than 15 s
                                                                                                                                                      door motor
                                                                                                                                                                                                                                                                               per operation (hence 0 load factor).
                                                                                        reserved.
                                                                                                                                                                                                                                                                               Estimated four running
                                                                                                                                                     Exhaust fans       6     3ø     208     2.61     0.800     0.85    0.941    1.000     0.667                    3.76
                                                                                                                                                                                                                                                                               at any given time.
                                                                                                                                                       Fire alarm
                                                                                                                                                                        2     1ø     120     4.17     0.500     1.00    0.500    1.000     1.000       1.00                    Both running at all times.
                                                                                                                                                         panel
                                                                                                                                                                                                                                                                               Load factor depends on
                                                                                                                                                         3 HP                                                                                                                  requirements (ambient conditions
                                                                                                                                                     battery room       1     3ø     208     7.31     2.238     0.85    2.633    1.000     1.000                    2.63       for chargers, etc.). In this case,
                                                                                                                                                                                                                                                                                                                          IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
                                                   Copyright
                                                                                                                                                         HVAC
                                                                                                                                                     Receptacles—
                                                                                                                                                                                                                                                                                Assumed four used at any given time.
                                                                                                                                                      rack service/
                                                                                                                                                                                                                                                                                Load factor is a median estimate for
                                                         Fei. Downloaded
                                                                                                                                                      maintenance       30     1ø     120     15.00    1.530     0.85    1.800    0.500     0.133       3.60
                                                                                                                                                                                                                                                                                any connected equipment, which
                                                                                                                                25
                                                                                                                                                     (10-receptacle
                                                               © 2017 IEEE.
                                                                                                                                                                                                                                                                                could run for two hours or more.
                                                                                                                                                      power strip)
                                                                         on October
                                                                                                                                                                                                                                                                                Though there are ten receptacles,
                                                                                                                                                                                                                                                                                                                                                              IEEE Std 1818-2017
                                                                             All rights
                                                                                                                                                                                                                                                                                typically, no more than two or three
                                                                                                                                                                                                                                                                                are used at a time for smaller loads
                                                                                                                                                     Communication
                                                                                     11,2024
                                                                                                                                                                                                                                                                                (laptops, test equipment, etc.).
                                                                                                                                                     rack power strip    1     1ø     120     15.00    1.530     0.85    1.800    0.300     0.500       0.27
                                                                                                                                                                                                                                                                                Those small loads require less than
                                                                                        reserved.
                                                                                                                                                      (10 receptacle)
                                                                                                                                                                                                                                                                                half the available ampacity of any
                                                                                                                                                                                                                                                                                given receptacle. Rough estimate of
                                                                                                                                                                                                                                                                                180 VA per receptacle used here.
                                                                                                                                                        420 MVA                                                                                                                 Only one transformer. Loads
                                                                                                                                                       transformer                                                                                                              mostly consist of fans, pumps,
                                                                                                                                                                         1     3ø     208     50.00    16.193    0.90    17.992   1.000     1.000                    17.99
                                                                                                                                                         auxiliary                                                                                                              etc., which are considered to be
                                                                                                                                                      power supply                                                                                                              running for at least three hours.
                                                                                                                                                                                                                                                                                                                            IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    The first step in conductor selection is to determine the type of conductor to be used. The conductor material
    and stranding type are the most important factors to consider (i.e., aluminum versus copper and stranded
    versus solid). There are advantages to using each type of conductor depending on the application. Consider
    characteristics such as their weight, conductivity, and surrounding environmental conditions for the application
    of the conductors. Copper has historically been used for conductors of insulated cables due to its desirable
    electrical and mechanical properties. The need for mechanical flexibility usually determines whether a solid or
    a stranded conductor is used, and the degree of flexibility is a function of the total number of strands. A single
    insulated or bare wire is defined as a conductor, whereas an assembly of two or more insulated conductors,
    with or without an overall covering, is defined as a cable. All of this information is typically available from the
    cable manufacturer. For additional information on conductor material and stranding, see IEEE Std 141 [B3]
    and IEEE Std 525.
                                                                       26
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Cable insulation voltage rating is selected based on the operating voltage, and the expected fault-clearing
    time. Further guidance on selecting the voltage rating of cables should be provided by the AHJ, or by specific
    product literature provided by the manufacturer.
    For jacketed conductors, the insulation type should be selected to meet the local environmental conditions—
    such as dry, wet, or both, and chemical resistance. Typically, information on the application of different
    insulation types is available from the manufacturer. There may also be requirements by the AHJ. IEEE Std 141
    [B3] and IEEE Std 525 provides general guidance on cable insulation selection.
    The temperature rating of the cable should be selected to withstand the ambient temperature of the environment
    in which it is installed, in addition to any self-heating that may occur. The designer selecting the conductor
    should note that the conductor installation may cross multiple environments, all of which should be considered.
    Typical conductor temperature ratings are 60 °C, 75 °C, 90 °C, and 105 °C.
4.5.6 Consideration for the characteristics of termination points and connected equipment
    The ampacity of a conductor with a given temperature rating may need to be reduced depending on the type
    of termination points to which the conductor is connected. The conductor should not be allowed to become
    hotter than the thermal rating of the interconnected equipment. Typical equipment terminals are limited by the
    manufacturer to 75 °C. For an example involving cable selection based on termination ratings, see Annex B.
4.5.7.1 Introduction
The following factors should be considered when selecting the conductor size:
    All conductors should be initially sized based on the ampacity of the load(s) they are supplying. The size of the
    conductor may be based on requirements provided by the AHJ, or by specific product literature provided by
    the manufacturer. For an example involving the initial conductor size selection, reference Annex B. Once the
    initial conductor type and size selection is made, verify the conductor has been sized to avoid overheating and
    excessive voltage drop. If the verifications prove the conductor size to be inadequate, then the engineer should
    make an economically and practically sound decision to redesign the load-distribution scheme. The redesign
    decision could involve any of the following options:
                                                                       27
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    The ampacity rating of a cable may vary based on ambient temperature, burial depth, and proximity to other
    current-carrying conductors. The manufacturer can provide ampacity ratings based on a range of ambient
    temperatures. If the ambient temperature in the area of a particular cable installation is not within range of
    the ambient temperature specified by the manufacturer, then the ampacity should be adjusted. Guidance for
    this type of ampacity adjustment factor should be obtained from the cable manufacturer or the AHJ. For an
    example involving ampacity adjustment based on ambient temperature, see B.2.
    Losses by means of voltage drop across a conductor are directly proportional to the length and impedance of
    the conductor. Per Ohm’s law, the higher the current a conductor is carrying, or the higher the resistance of a
    conductor, the greater the voltage drop. Voltage drop can create under-voltage issues for substation equipment,
    leading to various malfunctions, depending on the type of equipment.
                  2× I × L ×[ R × pf + X ×sin(arccos( pf ))]
        %VD =                                                ×100                                                                         (4)
                                      V
                  I × L × 3 ×[ R × pf + X ×sin(arccos( pf ))]
        %VD =                                                 ×100                                                                        (5)
                                      V
        where
             VD is the line-to-neutral voltage drop of the conductor expressed in volts, for a 1Ø conductor
             or the line-to-line voltage drop of the conductor expressed in volts for a 3Ø conductor
             V is the nominal voltage of the circuit
              R is the alternating-current resistance in ohms to neutral per unit measurement
              X is the alternating-current reactance in ohms to neutral per unit measurement
              I is the load in amperes at 100%
              L is the length of the conductor in unit measurement being considered for the voltage drop
              pf is the equivalent power factor being considered for the circuit. If this factor has been accounted for
             in the load study, then a value of 1.0 should be used in the voltage drop calculation
    After a conductor size is selected with an acceptable level of voltage drop, verify the terminal voltage delivered
    compared to the operating voltage range of the load. It is important that adequate voltage is delivered to
    critical loads (i.e., trip coils, battery chargers, etc.). It is common for the AHJ to provide standards that provide
    acceptable levels of voltage drop. For an example involving voltage drop calculations, see B.2.
    Verify the conductor size can withstand the available short-circuit current at its termination point. Sizing
    of the conductor based on available fault current is a function of initial or continuous conductor operating
    temperature, the final conductor temperature after a fault, the maximum possible fault-clearing time based
    on protective devices, and available fault current at the circuit’s termination point. The conductor final
    temperature limits should be obtained from the cable manufacturer. Suggested methods and values for sizing
    a conductor based on short-circuit current can be found in IEEE Std 525 and IEEE Std 242™ [B4]. However,
                                                                       28
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    any rules and/or standards provided by the AHJ should be considered before any other methods of calculation
    are applied. For an example involving sizing a conductor based on short-circuit calculations, see Annex B.
    The objective of 4.6 is to provide items for consideration to help the substation designer select the appropriate
    station service transformer for the substation. Subclause 4.6 discusses the required number of transformers,
    transformer power rating (kVA), transformer connections, transformer short-circuit rating, and some other
    items to consider.
        a)    Pole- or structure-mounted transformer: The primary is connected overhead to the bus and the
              secondary can be brought to the main panel via conduit or trench. This transformer type is simplest
              when the load is single phase and less than 100 kVA and the required secondary voltage is 120/240 V
              or 240/480 V. However, three-phase installations are common as well.
        b)    Pad-mounted transformer: To limit the voltage drop and reduce the length of the secondary conductors,
              the transformers are typically located near the control enclosure. The location should not interfere
              with vehicle movement within the substation yard, and should be located near the cable entrance
              for easy access to the control enclosure load center. The primary cables are connected to the bus/
              transformer tertiary and brought underground to the transformer. The secondary cables are connected
              to the ac system as required. This transformer type is typically used when medium voltage is available,
              the connected load is predominantly three-phase, and the total load is greater than 100 kVA.
        c)    Station service voltage transformer (SSVT): This transformer type combines the characteristics of a
              voltage transformer with convenient power capability. Used in the substation application if no low-
              or medium-voltage bus is available, or no nearby distribution feeder exists, or the cost of installing
              the feeder is high. One to three transformers can be installed depending the required kVA rating. The
              primary is normally connected from phase to ground. Typical secondary ratings available 120/240 V,
              277/480 V, 240/480 V, and 600 V (ac).
    The number of station power transformers required for a substation can be determined based on the design
    criterion discussed in 4.2.5. One transformer may be acceptable for a low-load substation. For substations
    with high load or high reliability requirements, two or more station power transformers may be required. An
    important factor that can affect the number of station power transformers is the available sources for station
    power.
    Many utilities and power producers have developed standards and guidelines that help determine the number
    of station power transformers that are required for a particular substation. These guidelines are based on the
    utility system conditions and reliability requirements.
    The amount of station load determines whether single-phase or three-phase transformers are required. In
    general, single-phase transformers have been used for distribution substations when the load is single-phase
    and it has a low current rating. Three-phase transformers have been used for high-voltage and extra-high-
    voltage substations when the load is high and some station load requires three-phase voltage input. Using a
    single-phase transformer to serve large station load may result in a high level of secondary current. This could
                                                                       29
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    result in equipment with higher current rating as well as larger conductors due to excessive voltage drop. Other
    loads, such as maintenance and construction equipment, may dictate if three-phase transformers are required
    for station power.
4.6.5.1 Introduction
    Station service transformer ratings are specified by the kVA rating, transformer primary and secondary
    voltages, the short-circuit rating, and the basic impulse insulation level (BIL) rating.
    The capacity of a transformer is determined by the amount of current it can carry continuously at rated voltage
    without exceeding the design temperature. Transformer ratings are given in kilovolt-amperes (kVA) since the
    capacity is limited by the load current.
    The kVA rating of the transformer should be selected to account for the expected load which the transformer
    is required to serve including anticipated future load. See 4.4 for detailed information regarding load
    classification and calculations. For a more general approach, the following methods can be used to determine
    the transformer kVA rating. The 20% design margin used in this guide is conceptual. The designer may use a
    design margin as appropriate for the application and per the owner’s operating practice.
    For small substation with light load requirements, the kVA rating of the single-phase transformer is determined
    by calculating the ultimate connected load and adding a margin of 20%:
For large substations with high load requirements, the loads may be differentiated as follows:
        a)    Continuous loads: Loads that continue to operate for three hours or more are considered as continuous
              loads. In substations the following loads can be considered continuous:
              1)     Control building HVAC and lighting
              2)     Transformer fans and/or pumps
              3)     Battery chargers
              4)     Equipment heaters
              5)     Yard lighting
              6)     Illuminated signs and miscellaneous inverters and receptacle loads
        b)    Non-continuous loads: Loads that are momentary are considered non-continuous loads. In substations
              the following loads can be considered non-continuous. For larger substations, the designer may want
              to consider not adding design margin to the non-continuous load.
              1)     Breaker’s ac motor spring chargers running current: Since this load type is momentary and the
                     possibility of more than one breaker charging motor starting at the same time is remote, it is
                                                                       30
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
                     suggested that the load of only two motors loads are added to the transformer kVA rating
                     calculations.
        c)    Maintenance and construction loads: Depending on duration of these loads, loads could fall under
              either continuous or non-continuous.
              1)     Maintenance loads including transformer and breaker processing equipment.
              2)     Construction loads including construction trailers and equipment.
    Once the recommended transformer kVA rating is calculated, Table 2 can be used to select the appropriate
    transformer size for the application. Normally, the next transformer rating greater than the calculated value is
    selected. Sizes other than listed in Table 2 may be available from manufacturers. A list of preferred continuous
    kVA ratings can be found in IEEE Std C57.12.00™ [B21].
    The primary and secondary voltage of the transformer should be specified. The following factors affect both
    the primary and secondary voltage:
        a)    Available source
        b)    Transformer type: single-phase or three-phase
        c)    Transformer connection
        d)    Load voltage requirements
        e)    Transformer impedance
    For a single-phase transformer, the primary voltage can be specified phase-to-phase or phase-to-ground. For
    a three-phase transformer with a delta-connected primary or for a three-wire system, a phase-phase voltage is
    specified. For a four-wire source, or for a transformer with wye-connected winding(s), both phase-phase and
    phase-ground voltage are specified.
The following are typical substation secondary voltages (the list is not all inclusive):
                                                                       31
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
                                                                       32
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    The short-circuit ratings for distribution transformers are set by IEEE Std C57.12.00 [B21]. The maximum
    magnitude required for units with secondary voltages rated less than 600 V is given in the table below:
    Two winding distribution transformers with secondary voltages rated above 600 V are required to withstand
    short-circuits limited only by the transformer’s impedance.
             1250
        t=                                                                                                                                (7)
              I2
t=I (8)
where
t = 2s (9)
t=I (10)
where
                 IS
        I SC =                                                                                                                          (11)
                 Zt
                                                                       33
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
where
    For example, a 50 kVA single-phase transformer with a 120/240 V (ac) secondary and a 3.5% impedance will
    have a short-circuit capability of:
        50 000
               0.035 = 5952.4 A                                                                                                         (12)
         240
    Equipment connected to this transformer shall have the ability to withstand this current for the duration
    indicated above, and be capable of interrupting that current if the equipment is a protective device such as a
    circuit breaker or fuse.
    The station service transformer impedance should be considered when evaluating the ac system equipment
    rating. The ac equipment should withstand the maximum fault current and the circuit breakers should be
    capable of interrupting the fault. The transformer impedance has a direct effect on system fault current. The
    impedance determines the maximum short-circuit current.
    The percentage impedance can be specified as low as 2% for small distribution transformers, and as high as
    20% for large power transformers. Impedance values outside this range are generally specified for special
    applications.
    The BIL rating of overhead distribution transformers 500 kVA and smaller is its ability to withstand overvoltage
    conditions resulting due to fault conditions, lightning surges, or any over-voltage due to switching surges.
    Table 4 meets IEEE Std C57.12.20™ [B23] and can be used to specify the BIL rating of the transformer.
4.6.6.1 Introduction
    Single-phase distribution transformers are manufactured with one or two primary bushings. The single-
    primary-bushing transformers can be used only on grounded wye systems. For this connection, the H1 bushing
                                                                       34
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    is connected to an available phase. If a two-bushing transformer is used, the H1 is connected the same, and the
    H2 bushing is connected to ground as shown in Figure 4.
    When a primary delta system is available, a phase-to-phase voltage is applied between the two bushings H1
    and H2 as shown in Figure 5.
                                                                       35
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Three-phase transformer connection can be achieved by using two or three single-phase transformers and
    connected as required. When a three-phase transformer is required, a pad-mounted three-phase transformer
    is normally used for the station power applications. A pad-mounted three-phase transformer is applicable to
    below-grade connection from both the primary and the secondary’s sides. The following are some examples of
    transformer connections that have been used for substation station service applications:
Delta-delta connection
    The delta-delta connection shown in Figure 6 is suitable for both ungrounded and effectively grounded
    sources. Phase-to-phase voltage is applied to H1, H2, and H3 terminals of the transformer. For substation
    applications when the required voltage is 240 or 480, a three-wire connection is used. When the required
    voltage is 240/120 V or 480/240 V, a four-wire service can be used. The delta-delta four-wire service is
    accomplished by grounding the midtap of one of the transformer windings. However, if single-phase load is to
    be connected, the three-phase capability of the transformer is derated.
                                                                       36
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    The disadvantages of the delta-delta connection include the absence of a neutral terminal on either side.
    Another drawback is that the electrical insulation is stressed to the line voltage. Therefore, a delta connection
    requires increased insulation to accommodate the higher voltage across the line-line compared to the wye-
    connection with line-neutral voltage for the same power. The delta connection is susceptible to ferroresonance.
Delta-wye connection
    The delta-wye connection shown in Figure 7 is suitable for both ungrounded and effectively grounded sources.
    The transformer primary is connected delta, and therefore phase-to-phase voltages are connected to H1, H2,
    and H3 transformer terminals. The secondary is suitable for three-wire service or, if neutral is grounded,
    four-wire grounded service. In substation applications four-wire service is normally used. Typical substation
    secondary voltages for this transformer connection are 480/277 V or 208/120 V.
                                                                       37
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    When the neutral is grounded the transformer acts as ground source for the secondary system. Fundamental
    and harmonic frequency zero-sequence currents in the secondary lines supplied by the transformer do not
    flow in the primary lines. Instead, these zero-sequence currents circulate in the closed delta primary windings.
    When supplied from an effectively grounded primary system, a ground relay for primary system does not see
    load unbalances and ground faults in the secondary system.
    When used in 25 kV and 34.5 kV three-phase four-wire primary systems, ferroresonance can occur when
    energizing or de-energizing the bank using single-pole switches located at the primary terminals. With smaller
    kVA transformers in the bank, the probability of ferroresonance is higher.
Wye-wye connection
    The wye-wye connection shown in Figure 8 is best applied at the four-wire primary and secondary where both
    the primary and secondary neutrals are grounded. The high-voltage terminals H1, H2, and H3 are connected to
    the three-phases, and the H0 neutral is connected to ground. In a grounded wye-wye 240/120 V or 480/240 V
    cannot be supplied, only 208/120 V or 480/277 V can be supplied by this connection.
                                                                       38
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
The following operating conditions should be considered when this transformer connection is selected:
        a)    Excessive tank heating can result depending on the transformer construction. For three-legged core
              construction, excessive tank heating is probable. For five-legged transformers, tank heating is possible
              if the load unbalance is high. Tank heating can be limited if the transformer bank is made from three
              single-phase transformers.
        b)    Zero-sequence currents and harmonics transfer to the primary. The secondary can act as high
              impedance ground source.
        c)    A ferroresonance condition is unlikely if the transformer bank is made from three single-phase
              transformers, but is possible for a four- or five-legged constructed transformer.
        d)    Coordination between the source ground protective device and the secondary ground protective
              device is required because the secondary current can pass to the primary.
    The open delta–open delta connection as shown in Figure 9 shows connection to a grounded wye-connected
    source such as a distribution bus. Phase-to-ground voltage is applied across the two transformer primary
    windings. This connection provides a 240/120 V secondary. The A-C and A-B voltages are 240 V where A-n
    and C-n are 120 V. The B phase in this connection is the high leg 208 V B-n.
                                                                       39
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    The open delta–open delta connection as shown in Figure 10 shows connection to a delta-connected
    source such as a three-phase transformer tertiary winding. Phase-to-phase voltage is applied across the two
    transformer primary windings. This connection provides a 240/120 V secondary. The A-C and A-B voltages
    are 240 V where A-n and C-n are 120 V. The B phase in this connection is a high leg.
                                                                       40
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    One benefit for the above two applications is when there is a large amount of single-phase loads 240/120 V
    and a small amount of three-phase 240 V load. This can economically provide that with a larger single-phase
    transformer connected to C-phase primary (with secondary grounded neutral tap) and a smaller transformer
    connected to A-phase. Typical substation ac station auxiliary loads tend to be single-phase with a small amount
    of three-phase loads (typically cooling pumps or larger three-phase battery chargers).
    Another benefit is that the open delta connection avoids the ferroresonance issues of the closed delta
    transformer connections.
    The connection is good for substations with a lot of single-phase load and a small amount of three-phase loads.
    This is inefficient for applications with substantial amounts of three-phase loads as you only get 58% of the
    capacity with only two transformers instead of three equally sized transformers.
    The need for an auxiliary power system transfer switch is related to the criticality of the substation. If only one
    station service power source is available, a transfer switch is not required. If there are no critical ac system
    requirements, the dc battery system may be sufficient to operate the critical dc systems until the ac station
    service power is restored.
    Most substations are provided with two sources of station service ac power. The two sources of station service
    power are generally designated as the normal source and the alternate (or backup or secondary) source.
                                                                       41
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    To simplify the operation of the transfer between sources, a “break before make” operation is suggested.
    “Break before make” operations keep sources from operating in parallel. In the case of manual operation of
    the transfer switch, it may be desirable to disable or lock out one source while the other source is being used.
    In either case, sufficient training should be provided so operators do not parallel sources. Most substation ac
    loads do not require continuous service to function as designed. The station service should be reviewed for
    sensitive loads that may require continuous ac service to function.
    Since the auxiliary power sources can be supplied at different voltages than the utilization voltage in the
    substation, the transfer switch or scheme can be applied at either the primary or secondary voltage. The higher
    voltage application results in lower current rated equipment. 13.8 kV, 12.47 kV, 4.16 kV, 480 V, and 240/120 V
    are common auxiliary power voltages and the transfer switch/scheme can be applied at any of these voltages.
    The auxiliary power source can be either three-phase or single-phase, depending on the station service
    requirements. Transfer switches typically can be purchased with two, three, or four poles. A four pole switch
    has the ability to switch the neutral and is necessary on a system that has separately derived neutrals. Using
    a transfer scheme at medium-voltage levels requires auxiliary voltage transformers and either programming
    protective relays or incorporating a programmable controller for transfer and return to normal functions.
    Smaller rated transfer switches can be wall mounted. Floor-mounted switches are common. Transfer switches
    can be purchased for indoor or outdoor mounting.
    The transfer switch may be as simple as two input sources with switching devices and one output to the load.
    The transfer system may be as elaborate as a unit switchgear consisting of two input switching devices, two
    transformers, two main circuit breakers, one tie circuit breaker, and multiple branch circuit breakers.
    Another consideration when designing the transfer system is the reliability of the transfer switch. It may
    be prudent to make provisions to bypass the switch in the event of the switch’s failure, maintenance, or
    replacement. This may be accomplished by having a third source routed to the substation ac load center that
    is left normally open and locked out until it is needed. It may be more cost effective to route another set of
    conductors from either or both the normal and alternate source to the substation ac load center. Similar to the
    transfer operation, training and procedures should be provided to the operator so that the operator is less likely
    to parallel sources during a bypass operation.
    Another important consideration when installing a transfer switch is to specify a switch with break before
    make operation. This allows for a transfer of normal and alternate sources that may be out of phase or
    connected to different phases on single-phase systems. For example, a normal three-phase source connected to
    a distribution bus may be 30 degrees out of phase with an alternate source connected to the tertiary windings of
    a power transformer. A break before make operation allows a transfer between these two sources that are out of
    phase. It is important to maintain proper phase rotation between different power sources.
    For less critical substations, a manual transfer switch provides the capability of transferring from the primary
    to the alternate source. The manual transfer switch is a much simpler and lower cost switch than an automatic
    transfer switch. However, the use of the manual transfer switch requires station alarms to alert operations
    personnel of the loss of the normal ac source and dispatching personnel to the substation to operate the manual
    transfer switch.
                                                                       42
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Due to the loss of the normal ac source, many station devices will lose power. The battery charger cannot
    supply the charging source for the dc battery system. In this situation, the dc battery system is the source for
    station critical systems, such as system protection functions and control and breaker tripping, until operation
    personnel responds and manually operates the ac transfer switch. Other systems, such as control enclosure
    cooling/heating, may also be unavailable until operations responds. The designer should consider the effects of
    temperature on control enclosure components and response time when considering a manual transfer switch.
    If the substation has only one source of ac power, a manual transfer switch may still be desirable as a connection
    point for a temporary ac alternate source, such as a portable generator.
    The manual transfer switch can consist of two manually operated switching devices (usually such as circuit
    breakers) capable of interrupting the load current of the transfer switch or a manually operated switch similar
    to a disconnect switch that has on–off–on capability to select between the two sources. The two switching
    devices are typically mechanically interlocked so both ac sources are not connected in parallel. Fault current
    interruption capability is not required in the transfer switch, but a withstand rating should be specified.
    Indication of source status (hot or dead) is not typically provided. Some type of alarm is necessary to detect the
    loss of the primary (and perhaps secondary) ac source.
    Critical substations, or substations with critical ac loads, may require an automatic transfer switch between the
    normal and alternate sources. The transfer should occur only after a time delay to avoid inadvertent transfer
    and only when the alternate source is available.
    Automatic return to the normal source should occur only after the normal source has been restored for a
    specified time to confirm it is not an unstable source.
    The low-voltage (< 1 kV) automatic transfer switch consists of essentially a form C power relay capable
    of interrupting the load current of the transfer switch. Higher voltage transfer switches can be composed
    of two electrically operated switching devices (usually circuit breakers). The two switching devices can be
    electrically and/or mechanically interlocked to keep the ac sources from being connected in parallel. Fault
    current interruption capability is not required in the transfer switch, but a withstand rating should be specified.
    Detection and indication of source status (hot or dead) is required. Time delays and control sequencing is
    necessary to reduce the chance of transferring to a de-energized or unstable source. Indicating lights and relays
    are usually provided. Alarm indication of transfer should be provided. Close and latch capability should also
    be considered in equipment rating.
    Transfer switches can be cascaded to allow multiple sources to provide power to the station service system.
    Depending on the criticality of the substation, two ac sources (bus derived and distribution derived) can be
    normal primary and alternate, and that resultant connection can be further supported from an onsite generator
    to support essential ac loads such as battery chargers, control enclosure HVAC, and communication systems
    as required.
    Another alternate would be for both sources to be designated as normal sources. The ac load can be divided
    between the two sources with the transfer switch system consisting of the two normally closed circuit breakers
    and a normally open transfer circuit breaker.
    In some instances, depending on the criticality of the station, the transfer switch alternate source may be a local
    backup generator. The transfer switch controller typically provides both the ac transfer function and the ability
    to exercise the generator following a pre-determined maintenance schedule. A number of alarms are available
                                                                       43
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    (engine temperature, fail to start, engine running, oil pressure, etc.) and provisions need to be made to transmit
    these to the operations center.
    The designer responsible for designing the bus layout and distribution circuit configuration of an auxiliary ac
    system should take the following parameters into consideration, at a minimum:
These loads are related to equipment operation and are necessary to the proper function of the substation.
        a)    Power transformer loads (cooling systems, fans, oil pumps, load tap changers, etc.)
        b)    DC battery chargers
        c)    Power circuit breaker loads (control, compressors, charging motors, etc.)
        d)    Power equipment heating circuits
        e)    Protective relaying, supervisory, alarm, communications, and control equipment
        f)    AC/DC converters for uninterruptable power supplies
        g)    Control enclosure HVAC systems
        h)    Fire alarm and fire suppression circuits
        i)    Security lighting
These loads are not essential for functioning and reliability of the substation.
    In this system, a single normal service and station power transformer supply all auxiliary ac load. There is no
    duplication of equipment. System cost is the lowest of all the circuit arrangements.
                                                                       44
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    The simplest version of this system is shown in Figure 11. It has panelboards supplied directly from station
    power transformer. Secondary breakers may not be required on the transformer as shown in Figure 11, Figure
    12, and Figure 13. One of the panelboards (“A”) is used to connect a feed to another panelboard (“B”).
    A variation of this system is shown in Figure 12 where a power block is used to split a power supply coming
    from transformer breaker into cables feeding both panelboards “A” and “B.”
    Another version of a simple radial system is shown in Figure 13, where a main panelboard is connected directly
    to a station power transformer. Breakers are used to supply sub-panelboards.
                                                                       45
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
Figure 13—Sub-panelboard
    The main deficiency of the systems shown in Figure 11, Figure 12, and Figure 13 is that the panelboards do
    not have independent feeds from the main system and are connected to a station power transformer breaker
    through a single common cable susceptible to failure. In the case of the cable fault or a failure of one of the
    panelboards ahead of the internal main breaker, the whole auxiliary ac power system becomes de-energized.
    To make a simple radial system more reliable and flexible, the auxiliary bus with feeder breakers (switchboard
    or switchgear), shown in Figure 14 may be used. In this system, the auxiliary bus is connected directly to the
    transformer breaker through a bus, or cable run, and panelboards are connected to the bus via feeder breakers
    and separate individual cables. A failure of any panelboard or a cable feeding it should result in a tripping of
    the corresponding feeder breaker, leaving the rest of the ac system intact.
                                                                       46
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Further improvement of redundancy of a simple radial system may be achieved through installation of a
    backup generator, which starts upon loss of the station power transformer’s feed to the auxiliary bus, tripping
    the transformer breaker and closing the generator breaker as shown in Figure 15.
                                                                       47
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    The main advantages of a simple radial system are low cost and operational simplicity. However, it has
    less reliability compared to more robust systems. A loss of the normal supply, main cable, or station power
    transformer results in the interruption of auxiliary ac service for the entire substation. Another drawback of
    a simple radial system is the necessity to de-energize it to perform routine maintenance of its main elements
    (transformer, transformer breaker, auxiliary bus, etc.).
    If a simple radial ac system is applied to a larger substation, its expanded version with two station power
    transformers may be used. See Figure 16.
    The advantages and disadvantages of expanded radial systems are the same as those described for the simple
    ones. However, by having two transformers, a better redundancy of power supply is achieved. The panelboards
    can be fed through automatic or manual transfer switches, which can also provide added flexibility in the
    continuity of power supply to the load if one of the transformers or buses is out of service.
    Protection against loss of a primary power supply can be gained through the use of a primary selective system
    shown in Figure 17. Each station power transformer is connected to two separate primary feeders through
    switching equipment to provide normal and alternate sources of power supply. Upon failure of the normal
    source, the transformer is switched to the alternate source. Switching can be either manual or automatic.
    Each panelboard can be fed through an automatic or manual transfer switch, which provides the continuity of
    power supply to the load if one of the transformers or buses is out of service.
                                                                       48
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    If a pair of station power transformers is connected through a secondary tie circuit breaker or automatic
    transfer switch, the end result is a secondary selective system shown in Figure 18. If any of the primary feeders
    or transformers fails, power supply from the remaining source is maintained through the corresponding
    transformer’s secondary breaker and a tie breaker. Tie breaker may be normally open. If this is the case, after
    failure of one of the sources and opening of affected transformer’s secondary breaker, a tie breaker should be
    closed either manually or automatically to provide a power supply for the bus section normally connected to
    the failed source. When a power supply from this source is restored, a manual opening of the tie breaker and
    closing of the returning to service transformer’s breaker are recommended.
    Each panelboard can be fed through an automatic or manual transfer switch, which provides the continuity of
    power supply to the load if one of the transformers or buses is out of service.
                                                                       49
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    If the level of redundancy provided by a secondary selective system shown in Figure 18 is not sufficient, a
    backup generator with a circuit breaker may be added to it as shown in Figure 19. Normally, the generator’s
    breaker is open, and for a loss of a single primary feeder or transformer, this scheme works exactly like the
    one shown in Figure 18. But upon the loss of both transformer feeds (both transformer secondary breakers are
    open) the backup generator starts automatically and its breaker closes, restoring power to both buses. Manual
    closing of the transformer breaker is recommended upon restoration of any primary feed after stopping the
    backup generator.
    Each panelboard can be fed through an automatic or manual transfer switch, which can allow the continuity of
    power to the load if one of the transformers or buses is out of service.
                                                                       50
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    If even more redundancy is needed, Figure 19 may be developed into a system with two tie breakers and
    possibly three transformers and a backup generator as shown in Figure 20. For applications with process-
    critical equipment, additional provisions may be required for smooth transition during restoration of power.
    The operational logic for this scheme is consistent with the one described for the schemes shown in Figure 17
    and Figure 18.
Figure 20—Secondary selective system with backup generator and additional redundancy
    The size of cable feeding any load or panelboard is required to be selected in accordance with requirements of
    the AHJ or any applicable code, and to be protected by an upstream breaker or protective device.
                                                                       51
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                           IEEE Std 1818-2017
                         IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    AC distribution panelboards are utilized for termination of service and feeder cable circuits and for origination
    of feeder and branch cable circuits for distribution of auxiliary ac electrical power to loads in electrical
    substations.
    An ac distribution panelboard is an assembly of bus bars, switching overcurrent protection devices, and
    connections housed in an enclosure with purpose to control and distribute auxiliary ac power to substations
    loads. AC distribution panelboards have a main bus bar for each phase, main lug only (MLO), or a main
    device such as a switch, fuses or molded-case circuit breaker (MCCB), and neutral and/or ground buses, if
    appropriate. Depending on voltage rating, ac distribution panelboards can be specified with a switch and/or
    overcurrent devices, such as plug or cartridge fuses or MCCBs, to serve as branch circuit devices. Most ac
    distribution panelboards utilized in modern industrial applications, such as electrical power substations, use
    MCCBs for main, feeder, and branch circuit overcurrent devices.
    Bus bars in ac distribution panelboards are current density rated and meet temperature rise limitations
    established in UL 67 [B38] (UL Standards are typical in the United States—other jurisdictions may have
    similar standards boards). Standard bus bar current densities are 750 amperes per square inch for aluminum
    bus bars and 1000 amperes per square inch for copper bus bars. Some ac distribution panelboard manufacturers
    offer reduced current densities of 600 amperes per square inch for aluminum bus bars and 800 amperes per
    square inch for copper bus bars.
    AC distribution panelboards used in electrical substation applications should be designed with consideration
    for the size of the conductors being terminated within the panelboard. The specified panelboards should
    accommodate the bending radius of conductors routed within them and should have adequate gutter spacing.
    The terminals of molded-case circuit breakers and other protective devices should be suitable for the wire
    size of the circuits on which the protective devices are applied. To be conservative, the designer designing the
    panelboard should account for the possibility of increases in wire sizing. The designer should also consider
    the space necessary for the electricians to perform terminations in the available space within the panelboard.
    For any application of ac panelboards, all panelboard manufacturers’ catalog and technical data should be
    considered carefully.
Typical voltage ratings for ac panelboards for different ac systems are given in Table 5.
                                                                       52
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                           IEEE Std 1818-2017
                         IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Although more ratings are available, typical nominal continuous rms current ratings of ac distribution
    panelboard main buses, main terminal lugs, main fuse and holder, and MCCB utilized in applications in
    electrical substations range between 100 A and 800 A. The maximum main current rating in ac panelboards is
    usually less than 1600 A. The current rating of an ac distribution panelboard should not be less than the feeder
    and branch circuit capacity required for the load.
    Typical nominal continuous rms current ratings of feeder and branch circuits range between 20 A and 400 A.
    The maximum feeder and branch circuit current rating in ac distribution panelboards is usually 1200 A.
    Unless marked to indicate otherwise, the provisions for cable terminations provided in ac distribution
    panelboards are based on the use of 60 °C temperature rise for wire sizes 14 AWG to 1 AWG and 75 °C
    temperature rise for wire sizes 1/0 AWG and larger.
    Unless rated for 100 percent continuous load at its rated current, the total load on any overcurrent device
    utilized in an ac distribution panelboard should not exceed 80 percent of its nominal current rating.
    The rms symmetrical and asymmetrical short-circuit current at an ac distribution panelboard location should
    be determined in accordance with methods provided in IEEE Std 141™ [B3], unless otherwise directed by
    the AHJ. The rated rms symmetrical and asymmetrical interrupting current of an ac distribution panelboard
    should exceed the available short-circuit current at the location in the electrical system. Consideration should
    be given to possible future increases in available short-circuit current. Most ac distribution panelboards are
    selected to have a fully integrated short-circuit interrupting rating where the ac distribution panelboard and all
    overcurrent devices enclosed in the ac distribution panelboard have a short-circuit current rating greater than
    the available short-circuit current at the location in the electrical system, but series ratings may be utilized.
    Selectivity between overcurrent devices should be considered, if possible.
    AC distribution panelboards are typically designed and manufactured in accordance with NEMA PB1 [B31]
    and UL 67 [B38] or similar standards, and are usually supplied in suitable cabinets or enclosures which are
    manufactured in accordance with standards such as NEMA 250 [B29] or UL 50 [B37] and designed to be
    mounted in or on a wall or other support structure and accessible only from the front. In general, ac distribution
    panelboards should be specified and applied in accordance with national or local standards, including all
    provisions for grounding. However, ultimate guidance for design, manufacturing, and installation/application
    of ac distribution panelboards should come from the AHJ.
    Usual service conditions for ac distribution panelboards are ambient temperature of −5° C to 40 °C for ac
    distribution panelboards utilizing molded-case circuit breakers, and −30 °C to 40 °C for ac distribution
    panelboards utilizing enclosed switches. Usual altitude is not greater than 2000 m (6600 ft). AC distribution
    panelboards for outdoor application can have a greater rated ambient temperature range and should be
    provided with enclosures with a suitable weatherproof rating. For suggested applications of enclosures based
    on location, see NEMA 250 [B29].
                                                                       53
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    AC distribution panelboards tested and certified to meet requirements of International Building Code (IBC)
    [B28] Zone 3 or Zone 4 or other similar standards should be considered in seismically active areas. Ultimately,
    any guidance for panelboard design based on seismic conditions should originate from the AHJ.
    An ac distribution panelboard utilized for service equipment to provide main control and means of cutoff of
    the supply conductors near the point of entrance of supply conductors of a building, structure, or other area or
    premises should meet all requirements for service equipment required in UL 67 [B38] and UL 869A [B41],
    unless otherwise dictated by the AHJ.
    Guidance for the specification of MCCBs is given in NEMA AB-1 [B30] and UL 489 [B40]. Guidance for
    specifying fusible switches is given in UL 98 [B39].
    Several studies may be performed for auxiliary system protection. These studies include a short-circuit current
    study for selection of equipment and cable sizing, a coordination study to evaluate and select the equipment
    rating and protective device rating of auxiliary systems, and an arc flash study.
    The upstream feeder protective device (fused safety switch, fuses, MCCBs, etc.) of the panelboard or
    switchboard should be sized to protect the panelboard or switchboard and the feeder cable(s).
    Panelboard and switchboard may have a main incoming protective device. For a panelboard or switchboard
    with a main incoming protective device (breaker or fuses, breaker), the main incoming protective device
    should be sized to protect the panel bus bars. There is no limit to the number of circuits (fuses, MCCBs) in the
    panelboard or switchboard. At one time, this was a 42 circuit limit, and that limit may still be in force in certain
    jurisdictions.
    Panelboard and switchboard circuit protection (sizing) should be determined based on the terminal and load
    ampacity. Typically this is based on 100% of the non-continuous and 125% of the continuous load current with
    some design margin of the circuit load. Typical design margin is 10% to 20%.
    In order to properly protect the equipment and coordinate the fault clearing, circuit breakers should be properly
    selected. There are three important aspects to proper selection of circuit breakers. They are the rated maximum
    voltage, rated continuous current, and the short-circuit current rating.
    The voltage rating of the circuit breaker should be not less than the maximum operating voltage of the ac
    system. Typical low-voltage ac circuit breaker voltage ratings are 120, 120/240, 208Y/120, 240, 277, 347,
    480Y/277, 480, 600Y/347, and 600 volts.
    The short-circuit current rating is the maximum short-circuit current that a circuit breaker can successfully
    interrupt. The circuit breakers for an ac system should have a current interrupting rating equal to or higher than
    the actual ac system maximum fault current. Typical low-voltage ac circuit breaker current interrupting ratings
    are 7.5 kA, 10 kA, 14 kA, 18 kA, 20 kA, 22 kA, 25 kA, 35 kA, 42 kA, 50 kA, 65 kA, 85 kA, 100 kA, 125 kA,
    150 kA, and 200 kA.
                                                                       54
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    The circuit breaker current rating should not be less than 125% of the calculated maximum load. 100% rated
    breakers are available if required, or may provide benefit to accommodate preferences with frame size. It may
    be appropriate to include a 10% design margin.
    In some cases, thermal trip units or electronic trip units should be selected based on equipment protection
    requirements or the arc flash energy limitation requirements. The trip unit setting should be clearly identified
    in the circuit breaker order and design document.
For more information on the selection and application of molded-case breakers, see IEEE Std 1458™ [B17].
    Appropriate fuse selection is important for the protection and fault-clearing coordination of the ac auxiliary
    power system. The important ratings to consider when properly selecting fuses for ac auxiliary power system
    protection are voltage rating and current rating.
    The ac voltage rating of the fuse should not be less than the operating voltage of the ac auxiliary power system.
    Typical ac fuse voltage ratings are 125 V, 250 V, and 600 V; 300 V and 480 V ratings are also available.
    The ac current rating of a fuse is the maximum ac continuous current that can flow through a fuse without
    interrupting. When the rating is exceeded, the fuse blows, opening the circuit. The maximum ac continuous
    current required to supply an ac load should be considered when selecting the ac fuse rating. Typical ac
    continuous current fuse ratings range from 1 A to 600 A.
    Documents for specifying equipment include the necessary information for manufactures or suppliers to
    prepare and submit a firm proposal to furnish the requested equipment. The equipment specification usually
    comprises both commercial and technical requirements.
    The commercial requirements are typically a set of terms and conditions that address how, when, and to whom
    the proposals are to be returned. Other information included may be legal considerations, such as taxes or
    liabilities. Commercial requirements are not discussed in further detail.
    The technical requirements include the description of the necessary performance requirements for the
    equipment. The information in the description should include, as needed, the operational criteria of the
    equipment related to its design, construction, testing, and shipment.
    Subjects that need to be addressed when specifying auxillary power equipment include voltage/current
    levels, service conditions, code requirements/restrictions, delivery dates, delivery/transportation to site, and
    temporary storage of equipment.
    Designers should be aware that the standard equipment offered by suppliers may not meet the robust
    requirements needed for some substations. For instance, the size and layout of the substation may warrant
    larger cables be used between equipment. These larger cable sizes require larger cable bending space and
    termination sizes, and hence bigger enclosure sizes.
    Numerous standards have been written to specify requirements of equipment to be used in ac auxiliary power
    systems. These standards cover transformers, surge arresters, transfer switches, panelboards, medium- and
    low-voltage fuses, medium- and low-voltage circuit breakers, etc.
                                                                       55
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
              IEEE Std C57.12.00, IEEE Standard for General Requirements for Liquid-Immersed Distribution,
              Power, and Regulating Transformers [B21]
              IEEE Std C62.22, IEEE Guide for the Application of Metal-Oxide Arresters for Alternating-Current
              Systems [B27]
              NEMA PB 2, Deadfront Distribution Switchboards
              UL 489 (NEMA AB 1), Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker
              Enclosures [B30]
              UL 891, Switchboards [B42]
              UL 991, Tests for Safety-Related Controls Employing Solid-State Devices [B43]
              UL 1008, Transfer Switch Equipment [B44]
    NEMA (National Electrical Manufacturers Association) creates ratings for equipment based on expected
    performance. NEMA does not require independent testing to verify that the manufacturer is compliant to the
    standard. Compliance to the standard is up to the manufacturer.
    NEMA 250 [B29] describes types of enclosures for electrical equipment up to 1000 V maximum. NEMA
    publishes descriptions of their enclosure types for both non-hazardous and hazardous locations. They also
    define which enclosure types may be used for indoor/outdoor use and which enclosure types may be used for
    indoor use only.
    The designer should choose the type of enclosure specific to environmental, atmospheric, and site conditions.
    For example, a NEMA Type 1 enclosure provides a minimum degree of protection for indoor use in a non-
    hazardous location, while a NEMA Type 3R enclosure provides a minimum degree of protection for outdoor
    use in a non-hazardous location. The degree of protection offered by these types of enclosures may be sufficient
    for a particular substation environment.
    There are several features that should be considered to enhance the operation and maintenance of the ac station
    service system.
        a)    Provide disconnect switches that can be visibly verified and used for electrical clearance points on the
              high side of the station service transformer, and between the transformer and the service panel.
        b)    Provide transfer switches to allow transferring load to an alternate source when the normal source
              (primary bank, bus, station service bank, or line) needs to be cleared. Transfer switches are typically
              break before make and need a mechanical interlocking means to avoid paralleling the sources.
        c)    Indoor and outdoor panels need to have adequate working space. Recommended depth, width, and
              head room clear distances are shown in Table 6 and accompanying notes.
        d)    Panels should be dead-front design, and outdoor panels should be lockable.
        e)    Clearly mark phases at the transformer bank and in the distribution panels to facilitate future trouble
              shooting.
                                                                       56
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    For optimal performance and to reduce maintenance, consider the following features for outdoor distribution
    panels:
        a)     Utilize rain-tight construction: Minimum NEMA 3R or equivalent. Include a drip shield to reduce the
               likelihood of water entering the panel.
        b)     Steel cabinets should have a minimum of 4 mils paint by wet process or powder-coat type. Epoxy or
               two coat epoxy/polyester are common for good durability. Aluminum, or in highly corrosive areas
               stainless steel, cabinets may also be used.
        c)     Do not use piano-type (continuous) hinges on doors. Use a multi-point latching system.
        d)     Cover all vents with small mesh screen to reduce insect or rodent infestation. Secure in place. Use
               material such as brass that does not corrode over time.
    The purpose of the standby ac system would be to provide continued ac power to essential systems for a set
    period of time after all sources to the auxiliary power system are unavailable. The essential systems may
    be defined as the dc power systems that provide the power required for relaying, control, telemetry, and
    communications, and any ac power needed for breaker operation.
    Factors that may determine the need for a standby backup ac system are the criticality of the substation, the
    battery life for the essential systems, and the reliability of the ac sources for the auxiliary system. If there is a
    possibility that an event can occur where the minimum time period to provide dc power is exceeded, a standby
    backup ac system may be considered.
    The standby backup ac system should be a stand-alone unit that provides power without the support of the
    overall electric power system. An automatic start for the system may be desirable, considering that telemetry
    and communications functions may be disabled. Control of the generator would be through an auto-transfer
    switch. Manual control may also be available. Isolation of the sources to the auxiliary power system is
    necessary before connecting the standby backup ac system. The designer should avoid ac system paralleling.
    The standby backup ac system used in substation normally consists of a generator. The fuel source for the
    standby generator should be selected based on regional conditions, such as temperature and availability of
    fuels. The generator is normally used in the substation for one of the following reasons:
                                                                       57
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
        a)    Used as backup to the normal source when only one source is available, and the substation requires
              two redundant ac sources.
        b)    Used as the third source when two sources are available, and the substation requires three ac sources.
        c)    Under emergency condition when all the normal ac sources are not available, the backup generator is
              used to restore the system.
    When the generator is used as a backup to one or more normal ac system(s), the station load can be transferred
    to the generator automatically by the use of an automatic-transfer switch or by manual transfer, as required.
    Prior to the start of the dc system design, the designer should consider several factors that are crucial to
    successful implementation. Typically in substation applications, the primary purpose of dc auxiliary systems
    is to provide a reliable power source for the power system protection. DC systems provide power to operate
    protective relays, monitoring equipment, and control circuits that operate power circuit breakers or other
    fault-isolating equipment. The dc systems are designed to provide power for these protection systems during
    outages and when the power systems are intact. Several key factors are listed below. Figure 21 is a simplified
    dc block diagram.
5.1.2 Reliability
    The reliability requirements of the power system are typically defined by the system protection design.
    For example, the design requirements for transmission equipment is likely different than the requirements
    for distribution equipment. These designs determine the robustness requirements for the systems. System
    reliability standards should be reviewed to determine if back-up equipment or automatic switching is required
    in the event of one piece of equipment failing.
5.1.3 Redundancy
    The redundancy requirements of dc systems are typically related to the power system protection requirements.
    For example, a transmission substation may be designed with redundant components of the protection system.
    Redundant components may include ac voltage sources, protective relays, breaker trip coils, and duplicate
                                                                       58
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    components of the dc systems. Failure of one or more components of a non-redundant dc system may prevent
    operation of the protection and control systems, which could lead to system outages or stability problems.
    Providing redundant dc system components, such as batteries, chargers, and panelboards, may improve the
    integrity of the power system in the event of power system faults, dc system maintenance, or other utility
    operation.
    A distribution system may not have similar design requirements or concerns related to system stability. A
    designer could consider that the criticality of a certain distribution substation, such as the nature or location
    of the load or customers served by that substation, may justify the addition of redundancy in the dc system.
    Consideration for system back-up methods for failed equipment such as mobile substations or field ties to an
    alternate source, could provide a more economical or acceptable solution to dc system redundancy.
5.1.4 Environment
    The environment that dc systems are exposed to impact the reliability of battery performance including the
    capacity and life of the battery. Key environmental components include: temperature, vibration, cleanliness,
    and ventilation. Some applications may be susceptible to seismic considerations.
    The dc system design should be based on capacity and performance. Applicable criteria should be reviewed to
    confirm a reliable and cost-effective system has been selected for the life of the installation.
        a)    Load on the dc system when the maximum output of the battery charger is exceeded.
        b)    Demand on the battery when the output of the charger is interrupted.
        c)    Demand during the duty cycle.
        d)    Battery re-charging time.
        e)    DC system redundancy requirements.
        f)    The battery standby duration (e.g., 2 h, 4 h, 8 h, 12 h), when auxiliary ac power is lost.
        g)    Battery life—What is the projected minimum life of the dc system? Are battery life cycle costs factored
              into cost of operation?
        h)    Battery type
        i)    Cost/reliability—What was the cost and quality of the battery initially selected? Does operational
              history align with published life/costs?
        j)    Available fault current of the dc system.
        k)    Arc flash hazards—Reference NFPA 70E [B36].
        l)    Operating temperatures—Is the battery to be subjected to temperature extremes? When air
              conditioning is lost, what is the expected minimum or maximum temperature the battery can be
              expected to reach? What are the expected times to reach these temperatures?
        m)    Maintenance intervals—The overall reliability of the battery depends on proper maintenance.
        n)    Location—Is the battery located where required maintenance can be completed? Is the battery
              properly ventilated? Is any associated equipment susceptible to damage from electrolyte?
                                                                       59
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
        o)    Vibration/shock—Is the battery located near rotating equipment? Lead-acid batteries easily shed their
              active materials from the surface of the plates, affecting battery life.
        p)    Weight/size—Physical size and weight can play a significant role in determining the type of battery to
              be selected. Is there enough room for the battery and rack in the proposed location? Can the location
              of the battery accept the floor loading? Can the battery cells be replaced with all adjacent equipment
              installed, or are lifting measures required (e.g., a multi-cell jar can easily weigh over 50 kg)? Is
              adequate space allocated to get either a permanent or portable lifting device installed? Parallel strings
              could be considered to reduce weight and size.
        q)    Design process—Does the design process account for verification of the dc system loads for all
              additions or changes?
        r)    Changed state loads—Does the design need to account for loads that may change state? Examples
              are breaker spring charging motors that run on dc on loss of ac, or a supervisory control and data
              acquisition (SCADA) computer monitor that is fed from an inverter source that fails to dc on loss of its
              normal ac service.
        s)    Is emergency lighting required? If so, can an alternate source be provided?
        t)    Does the dc system have alternatives in the substation emergency power system?
        u)    Safety components in the dc design include mitigating arc flash, electric shock, and short circuits.
    The design considerations need to accommodate both the owner’s requirements and those of any regulatory
    agency, AHJ, or quasi-regulatory agency. Other considerations may include those of any insurer or transmission
    operator (e.g., black start plans). For example, a black start, or system restoration plan, may require more than
    one attempt to close a transmission path and re-establish a secure source of the station ac service. During these
    attempts, breaker spring motors may have to charge on the station battery, which may be overlooked in an
    existing load case and may need to be accounted for in a new design.
        a)    Circuit breakers
        b)    Circuit switchers
        c)    Motor operators
        d)    Protective relay systems
        e)    SCADA
        f)    Fire protection/detection
        g)    Emergency lighting
        h)    Security systems
    While most of the equipment is required to be operational at all times, some may be defined as non-critical and
    may be segregated to reduce loads in the event where the battery of the dc system is required to carry substation
    loads without the battery charger available. Consideration should be given to limit the amount of non-critical
    loads connected to the battery to provide reliability to the system protection and to limit the size of the battery.
    The equipment may require dc voltages at different values such as 125 V (dc) for circuit breaker controls and
    12 V (dc) or 24 V (dc) for a radio communication system. The designer needs to determine the best method
                                                                       60
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    to supply the various voltages. It is not recommended to tap a larger voltage battery for lower voltages (i.e.,
    24 V tap on a 125 V [dc] battery). If alternate voltages are required to be supplied from a single battery, dc–
    dc converters are typically utilized for smaller non-critical loads at a lower voltage or a second dc system
    dedicated to the communications equipment could be installed. It is not recommended to install many dc–dc
    converters to provide different voltages. Vendors should be consulted to determine if alternate power supplies
    can be used.
    To start the design process, it is recommended that the designer create a one-line diagram showing the battery
    (or batteries), charger (or chargers), dc panels, and all connected loads. Consideration should also be given
    for future load growth. A review of the overall substation one-line may aid in determining future possible
    additions.
    The one-line diagram is very important. The following should be considered during the design of the one-line
    diagram:
    The designer should evaluate the criticality of the substation facilities and owner’s preference or regulatory
    requirements. High-voltage and extra-high voltage (EHV) protective relay systems are normally designed
    with two independent systems. The systems are inclusive from the dc feeds to independent trip coils in the
    circuit breakers. The designer should review whether separate battery systems and panels are required, a single
    battery system with independent dc panels, or one battery system and panel. Independent systems may provide
    better opportunities for maintenance or replacement in the event of equipment failure or the need to upgrade in
    the future. The ability to tie redundant dc systems may also aid in maintenance activities.
    The number of battery systems may depend on the voltage level of the equipment. For example, if a
    communication system requires 48 V (dc) and the substation equipment is 125 V (dc), the designer needs to
    consider whether the communication equipment would be supplied by its own battery and charger as noted in
    5.2, or be supplied by a dc-dc converter. The decision should consider reliability and control enclosure space
    among other issues. The number of battery systems has a direct impact on the size of the control house as
    battery systems typically occupy wall space that can dictate building size.
    The designer needs to account for any dc load transfer requirements. Load transfer could be automatic or
    manual and serves to backup one dc system in the event of a charger failure from another system or similar
    event. The need to transfer and the details of a transfer scheme can be dictated by owner’s preference or design
                                                                       61
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    criteria, criticality of the substation, or other similar reasons. All equipment that could serve additional load
    upon transfer should be sized appropriately for that additional load.
    There may be regulatory requirements that require the ability to transfer the dc load to enhance reliability of
    the protection systems for the electric transmission system. In North America, the North American Electric
    Reliability Corporation (NERC) and regional transmission organizations have established requirements for dc
    system reliability.
    5.4 DC batteries
    5.4.1 Battery types
    Battery types and their characteristics are discussed extensively in several other IEEE guides (refer to Annex
    A). Common types of batteries used in substation applications include: valve regulated lead acid (VRLA),
    vented lead acid (VLA) which are commonly referred to as flooded, and nickel-cadmium (NiCd). This may
    change with time due to continued development of new battery technologies. Vented lead acid batteries are the
    most common battery types used in substation applications. The intent of this document is not to focus on lead
    acid batteries, and any references or examples that utilize lead-acid batteries is for convenience.
    The type of battery used should be based on reliability and economic criteria. Designers, through the use of
    various IEEE guides, manufacturer’s specifications, and owner’s preference, should familiarize themselves
    with the impact of each type of battery on the design of the overall dc system. Considerations for selecting
    different battery types should include: battery load requirement, environmental conditions (temperature range,
    moisture), battery life, design, duty cycle, capacity, and planned maintenance cycle.
    In most utility substation applications, the battery is not exposed to many deep cycles, so the ability
    to accommodate many cycles may not be as important compared to other factors, such as battery life and
    maintenance.
    Typically, the battery charger supports substation loads with the battery available to supply energy for short-
    duration activities, such as breaker trips and closes where the battery charger response time or capacity cannot
    support the transient. The battery is also available to supply critical long- and short-duration loads when there
    is loss of dc output from the battery charger.
5.4.2.1 Introduction
    IEEE Std 485™, IEEE Std 1115™, and IEEE Std 1189™ are standards that should be referenced for
    determining the battery size needed (based on the type of batteries used) for the dc system of substations.
    These standards include requirements a designer should consider for obtaining the appropriate battery rating.
    However, to aid the designer, some considerations are repeated here. In addition, this guide places emphasis
    on substation specific application considerations.
    First using the one-line or equivalent document, the designer should review all the continuous loads such as
    protective relays, SCADA systems, emergency lighting, indicating lights, communication equipment (power
    line carrier, radio, telecom, microwave, fiber optic), security systems, fire protection, etc. Continuous loads
    can be obtained for new substations by reviewing vendor literature or calculations from previous designs. For
    upgrades at existing facilities, the data may need to be obtained by field testing, or by examining the existing
    charger load, as vendor data may not be readily available. The field-obtained continuous load measurements
    should be evaluated for end-of-load-cycle voltage and operating experience. When reviewing the literature,
    the continuous loads should be evaluated at the final battery voltage (end of discharge or minimum cell voltage)
                                                                       62
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    selected (for example 105 V). For example, if a device has a load of 125 W, one may be tempted to have the
    load at 1 A for a 125 V (dc) system. However, at final battery voltage of 105 V the load would be 1.19 A.
    Care should be taken to tabulate all known loads. The designer should also review the design for future loads
    and “phantom” loads that may be added by personnel other than the substation designer. For example, the
    control enclosure may be designed by another person who includes a fire-protection system to meet local
    codes and may add dc emergency lighting.
    Substation designers should consider limiting loads connected to substation batteries used primarily for
    protection purposes to provide a longer-lasting source to the protective system. Reduction of continuous loads
    to help reduce the required battery size may be considered.
    Momentary loads are those such as breaker open or close that occur at various times through the duty cycle
    (see IEEE Std 485). Many substation momentary loads such as breaker operations, lockout relays, and
    communication system operations operate in time frames of several cycles (electrical cycles or Hz, not to be
    confused with duty or load cycles) and careful analysis using IEEE guides and the battery manufacturer may
    be required. For example, an EHV system may detect a fault in ¼ cycle, initiate communications for 1 cycle,
    operate protective devices in ½ cycle, and open the circuit breaker(s) in 2 cycles. The whole operation is over
    in less than 5 cycles from detection. Typical sizing per IEEE Std 485 looks at loads of 1 minute as the shortest
    period. After all momentary loads are considered and the initial battery size selected, it may be advisable to
    contact the battery vendor to verify the selected battery can respond to the expected loads and duration of the
    load. See Figure 22.
                                                                       63
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    If a discrete load sequence can be determined, the peak one-minute load can be determined more accurately
    than if the loads are summed. For example, if a substation bus trips on differential via a lockout relay (LOR)
    that trips three breakers with logic that opens a motor-operated disconnect (MOD) after the breakers open,
    the peak current would be either the LOR current, the sum of the three breaker trip coil currents, or the motor-
    operated disconnect locked rotor current. The single max current (breaker trips or locked rotor of MOD) would
    be used as the peak one-minute load. This reduces the likelihood of an overly conservative battery size. It
    requires careful examination of the trip sequence to understand the peak momentary loads. Computer analysis
    programs may be used. As described in IEEE Std 485, all load cases should be analyzed to verify that the proper
    case is identified. A traditional load case that may have been used over an eight-hour period, for example, may
    not be applicable in a situation where the substation may be required to cycle multiple loads, or an extended
    period in order to restore the system after a blackout. When sizing momentary loads for motor-operated
    disconnects, the locked rotor value should be used for the dc load of the motor operator to accommodate for
    misoperations of the motor-operated switch. Multiple protection events should be considered, and the highest
    current draw should be the worst case momentary load. Examination of the station’s ac single lines and dc
    protection schematics is required to determine the protection events.
    Another important issue when determining the worst case momentary load is whether to consider a breaker-
    failure situation where a breaker-fail relay can operate a group of devices around a failed breaker to isolate
    the fault. When utilized, breaker-failure relaying is a form of the secondary power system protection that
    requires a second contingency to operate. If breaker-failure protection is used, a second contingency to operate
    the breaker fail may provide the worst case tripping scenario, and this contingency should be considered to
    properly size the battery. In many cases, the breaker-fail operation may put a larger load on the battery, and
    both loads may occur within a minute time frame because the breaker fail would occur in a matter of cycles. In
    a breaker-failure event, the highest fault current in the sequence of events in that one-minute duration should
    be used for the worst case. If the original trip included a motor-operated device, it would still be operating
    when breaker fail occurred, and thus should be included in both conditions before and after the breaker-fail
    operation to determine the worst case scenario.
    As mentioned above, restoration from “black-start,” or system restoration scenario, may need to be
    considered. During “black-start” or system restoration, several trip and close cycles may be required to restore
    the transmission system after a collapse. It would not be uncommon for two or three attempts to be made to
    get the system to restore and become stable. As part of the “black start,” all the station breakers may be opened
    prior to closing in a selected transmission path.
    The duty cycle of a battery is defined in IEEE Std 485 as the loads a battery is expected to supply during
    specified time periods. The duration of the duty cycle and the specific loads on the battery during that time
    period determines the size of a battery based on IEEE Std 485 battery sizing. An important consideration for
    determining the length of the duty cycle is the response time required to restore the ac and dc auxiliary systems
    to normal operation. For example, a realistic sequence of events that would follow a battery charger failure
    may include the following:
                                                                       64
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    It is not difficult to imagine this process taking longer than the 8-hour duration typically used in substation
    designs. Under certain circumstances (particularly during major storms where there are multiple station
    outages) the acknowledgement of the initial alarm is likely delayed due to other priorities, thus increasing the
    battery duty cycle duration. The lack of availability of personnel to respond to an alarm may also increase the
    duration during weekends or holidays. The battery may function properly supporting continuous load during
    an extended time to replace the charger, but may not fulfill its design basis if called upon. Remote devices may
    be needed to clear a fault having a greater impact.
    Another important impact is loss of ac to the control enclosure. Similar to the loss of the charger, the battery
    supports critical station loads during this type of event. However, many control enclosures may not have been
    designed to limit temperature minimums or maximums without the heating or cooling systems available. The
    designer should review the battery capability during this type of event.
    The operating voltages of batteries are usually greater than their nominal voltage ratings. For example, on
    a 48-nominal-volt systems, operating voltages are typically over 50 V and operating voltages are typically
    over 130 V for 125-nominal-volt systems. The operating voltages vary depending on the chemistry and
    specific gravity of the battery electrolyte. The float voltages (voltage in the nominal charged condition) for
    an individual cell vary from approximately 2.17 V per cell to 2.25 V per cell, depending on the type of battery
    and number of cells. In some cases, these batteries are equalize charged (continuation of the regular charge at
    a higher voltage). It is important to verify that the equalization charge voltage does not exceed the maximum
    system voltage of the dc system which is typically dictated by equipment ratings.
    In substation applications, the maximum dc system voltage is typically limited to 140 V. In this case, the
    maximum cell voltage depends on the number of cells in the battery. The designer should review with the
    owner if the required equalization voltage would exceed alarm limits or normal equipment ratings (typically
    140 V for 125 V (dc) systems). In that case, the number of cells may need to be reduced or the equalization
    voltage reduced, increasing the recharge time. The minimum voltage for lead acid battery cells is typically 1.75
    V per cell, which is normally considered fully discharged. Other battery types will have differing discharge
    values. The designer should verify that the final battery voltage would support the equipment terminal voltage
    sufficient for the equipment operation. Voltage drop calculations need to be included in this consideration.
    Make sure to check connected equipment ratings if there are any questions. The voltage of the battery is
    calculated by using the following formula:
( voltage of the cell) × (number of cells in series) = battery system voltage (13)
The number of cells and the end voltage of a battery system can be calculated using the following formulas:
                                                                       65
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    NOTE—Equation (14) and Equation (15) include the equation and an example in the second half that results in, or uses,
    60 cells.
    Battery chargers are discussed in detail in other IEEE guides. The battery charger is the dc power supply
    that is normally used to provide the continuous loads of the station, and as a means to maintain charge on the
    battery, recharge after an event, and to provide an equalizing charge to bring the battery back into specification
    when cell voltages are outside manufacturer’s tolerances. The charger filtering requirements may differ per
    connected load. The filtering levels are typically adequate to accommodate the continuous load currents to the
    duty cycle, however they may not be adequate to accommodate the tripping transient current requirements on
    most substation applications. Thus, even with a battery eliminator type filtering, removing the battery from the
    dc circuit may also compromise system protection requirements.
There are four types of battery chargers commonly available as described in IEEE Std 1375™ [B16]:
    Battery charger sizing is based on the amount of energy required to recharge a battery that has been discharged
    per its full design duty cycle, the desired recharge time, the continuous dc load supported by the charger during
    the recharging period, and various factors.
    For a given battery duty cycle, the amount of amp-hours removed is known from the battery sizing calculation
    (either manual or via computer program). This amount of charge is what the battery charger needs to supply
    in order to recharge the battery in a certain amount of time. If the amp-hours removed is not known from an
    available design calculation, a conservative method is to use the 8-hour amp-hour rating of the battery. This
    method will typically lead to a larger-than-necessary charger, as the amp-hours removed from a battery during
    a full duty cycle is typically less than the amp-hour rating of the battery.
    For the recharge time, the designer should consider the owner’s preference or design criteria. Typical times of
    8 hours to 24 hours are used. While a shorter recharge time may restore a fully discharged battery faster, this
    may cause other problems. A faster recharge may lead to plate damage of the battery due to overheating, or
    the charger being oversized for day-to-day operations. The designer needs to review the probability of a worst
    case event happening during recharge, and use that to help determine battery size. For large charger sizes, the
    designer may consider installing two chargers operating in parallel. Since, under normal operating conditions,
                                                                       66
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
     the full capacity of the charger is not needed, it can allow for routine maintenance, or even a single charger
     failure to occur, without an effect on battery performance.
     The recharge factor accounts for additional energy needed to fully recharge the battery. During charging,
     the recharge efficiency of the battery should be considered, including losses (e.g., heat) experienced during
     recharging that are not included in the amp-hours removed. The recharge factor depends on the battery
     technology. The battery manufacturer’s specifications and literature should be consulted, but typical values
     include 1.1 for VLA, 1.15 for VRLA, 1.3 for vented Ni-Cd, and 1.4 for valve-regulated Ni-Cd.
     A design margin factor may be included at the discretion of the designer. While chargers do not age or lose
     capacity over time like batteries, it may be desirable to add an additional design margin to account for
     future station load growth, changes in the battery duty cycle, or other factors. If the battery duty cycle amp-
     hours removed is used in the charger sizing, then there is typically no additional design margin already
     included. If the conservative method of using the 8-hour amp-hour rating of the battery for the amp-hours
     removed in charger sizing, then a design margin from the battery sizing calculation may already be
     included. Note the charging rate should be limited to 20% of the 8-hour capacity per battery manufacturer
     recommendations.
     An altitude/temperature correction factor may be needed based on the installation conditions or the charger.
     The charger manufacturer’s specifications and literature should be consulted to determine these factors.
Sizing—The following formula may be used to determine the required dc output of the battery charger.
                     éæ A ö          ù
                 I = êçç ÷÷÷ e + I C ú (d )(k )                                                                                         (16)
                     êëçè t ø        úû
where
     The designer should review the owner’s preference, or design criteria, regarding the method of connecting
     the battery charger to the dc system. All connection methods have benefits and drawbacks. The charger can
     be connected at various points in the system including:
                                                                     67
                                                  Copyright © 2017 IEEE. All rights reserved.
 Authorized licensed use limited to: Centro Universitário Fei. Downloaded on October 11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
                                                                       68
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    If the charger is connected directly to the battery or on the source side of the disconnect switch, it could be
    considered a reliable method of charging the battery, since there are minimal points of failure in between the
    charger and battery. However, since the charger also serves to supply power to continuous loads under normal
    operation, a fault on the battery, or removal of the battery for replacement (by opening the battery disconnect
    switch [Figure 23] or disconnecting the main battery leads/cables [Figure 25]), may disconnect the charger
    from the loads.
    The charger size does not typically accommodate the worst case tripping current requirements. Most chargers
    do not have capability to source more current than the rating or a tripping transient (even with the battery
    eliminator option on some chargers). Substation design and operation activities need to coordinate to prevent
    operating or sourcing continuous load with charger and without a battery. Even though this may be functional,
    it removes the capacity of the battery to accommodate the higher loads of worse case tripping scenarios, and
    thus provides a false sense of security by compromising the capability of the dc system to provide the required
    dc power for the system protection.
    If the charger is connected on the load side of the battery disconnect switch (Figure 23), or at the dc panel
    (Figure 24), it maintains a connection to the continuous loads even in the event of a battery failure or
    replacement. However, if the charger gets disconnected from the battery due to an event at the dc panel, the
    battery loses its means to re-charge.
    Although the charger may be equipped with integral ac and dc circuit breakers or fuses, the designer may
    consider external protection as well. The ac feed breaker from the main ac source should be protected in
    accordance with applicable local codes. The dc output may need to be connected with another overcurrent
    device to coordinate with the overall dc system. Typical charger overcurrent protection is conservatively sized
    at 140% of the charger current rating. The cables connecting the charger to the dc system need to be sized to
    accommodate the overcurrent protection ratings of the charger dc output and the overcurrent protection in
    the dc cabinet (if the charger is connected to a dc panel with overcurrent protection). This overcurrent device
    could be either a fuse or circuit breaker depending in owner preference, local codes, or coordination needs.
    Both the ac and dc external protection should be used to protect the external circuit and cabling. The current
    limiting characteristics of the selected charger should be reviewed in accordance with IEEE Std 1375 [B16].
                                                                       69
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    5.6 DC panels
    5.6.1 Introduction
    The dc panels are used to distribute power to various loads in a substation and can come in many varieties.
    Panels can come with overcurrent protection on the main feed or main lug only (where the main dc feed
    connects directly to the dc bus). Branch circuits can be protected by circuit breakers, fuses, fuses with knife
    blade isolation, or combinations of these, such as a circuit breaker in the positive leg and knife switch isolation
    in the negative. The designer should review applicable local codes and owner’s preference as to what type
    should be used.
    The designer should review if there is separation required by local codes, owner’s preference, or design
    criteria. This could be based on whether there is a need to separate loads as critical or non-critical. Critical
    loads are those that would be required to have dc power under unusual system conditions, such as loss of
    power to the site, black start path, loss of the charger, etc.
    The designer should size the dc panel to accommodate the required number of circuits needed for existing load
    as well as planned load growth. Branch circuits should be sized in accordance with the NEC, local codes, or
    owner’s design criteria, as applicable. Branch circuits should coordinate with downstream devices, such as
    fuses or circuit breakers. The installed cable should be sized to exceed the required load. Circuit size should
    also account for any voltage drop. Voltage drop includes the effects of current through all interconnecting cable
    to and from the remote device. The cable should be sized so the device can operate at minimum battery voltage
    (i.e., 105 V [dc] on a 125 V [dc] battery) so that the minimum device voltage (90 V [dc] typical minimum pick-
    up) is available at the remote device. It may be prudent to build some conservatism in the design calculation to
    allow for variations in field conditions due to cable lengths, device tolerances, etc.
    To provide for a more robust dc system, it may be determined that a load transfer or paralleling scheme is
    required. The designer should consider the additional load that will be applied in a paralleling scheme and is
    accounted for in calculations that size the battery, charger, cables, etc. that are part of the dc system(s) that may
    accommodate the added load. The specific details and method of transfer should also be reviewed.
    When designing a load transfer between two dc systems, the fault currents and arcing currents should be
    considered. Panels and protection devices should be rated for the maximum fault current of the entire system.
    The designer should also consider if the two systems should be run in parallel or interlocked to not allow
    parallel operation. Paralleling the battery banks will result in increasing the available fault current. It is also
    recommended that paralleled battery banks should be the same type and size to ensure equal load sharing.
    Additionally, if battery chargers are to be operated in parallel, the designer should verify that the selected
    chargers will operate when paralleled. Consideration of paralleling two batteries with different state of charge
    may cause unexpected current flows and excessive loading on the good battery.
    Manual transfer of dc load can be accomplished with disconnect switches or temporary cables. Manual load
    transfer should be accomplished in a safe manner using switching procedures, electrical isolation, physical
    locks, and other methods. The equipment (cable, switch, lugs, etc.) that actually transfers the load from one
    system to the other should be sized for the expected load to be transferred, as well as future load growth. Figure
    26 and Figure 27 show two possible manual transfer schemes.
                                                                       70
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    In the above examples, the manual disconnect switches are sized for the larger of the two connected panel
    loads. The cabling to the switches is sized for the total dc system loads. Means to provide isolation of the
    switches for maintenance should be considered.
    A simple paralleling/transfer system may be the use of a normally open breaker or fuse position in each of
    the main dc panels tying the two together when both are closed. Administrative control procedures should be
    established to implement the paralleling or transfer of the two systems. Both battery systems will be sized for
    the total station dc load and load profile. While more costly than battery systems designed for single segregated
    loads, it provides for maintenance of the battery(s) with no disruption in supply.
5.7.3 DC transfer
    DC transfer could be accomplished via transfer switches similar to those used on ac systems. Figure 28
    illustrates one version of that method. This configuration creates a single point of failure, and a complete
                                                                       71
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    dc outage would be required to upgrade or replace a failed automatic transfer switch (ATS). This may be
    acceptable in non-critical applications since there is only one circuit to the dc panels. Other methods may
    include bypass switches to allow maintenance of the transfer switch while still powering the dc loads.
    Automatic transfer switches can be purchased with internal bypass switches and removable transfer switches
    for maintenance. As with the transfer/paralleling schemes, the batteries and equipment in the transfer scheme
    are to be sized for the total station dc load.
5.8.1.1 Introduction
    The battery and dc system has many options for monitoring. The battery charger itself may be equipped with
    monitoring functions such as loss of dc, low dc, battery grounds, and loss of charger ac. Some microprocessor-
    based chargers have programmable flexibility to provide many other forms of battery monitoring, such as
    battery temperature, impedance, and an on-line partial battery capacity test. Many microprocessor-based
    relays have the option to monitor the dc source voltage to the relay and can provide additional alarm capability.
    An auxiliary relay may be used to monitor systems where automatic monitoring may not be available. Through
    the use of communication links, continuous loads may be monitored from the charger directly to a SCADA
    remote terminal unit (RTU) or other similar device. A dc shunt may be used to measure battery current directly
    and connect to a monitoring device. Please refer to IEEE Std 1491™ [B18].
    While the battery is not normally a direct fire hazard, several conditions may present hazards. If the battery
    main terminals become shorted between the main terminals, and there is no protection (fuse or circuit breaker)
    as allowed by IEEE Std 1375 [B16] for overcurrent, the short-circuited battery would become a fire hazard.
    The availability of fire-resistant jars may be specified to reduce fire hazards. Thermal runaway conditions
    also present fire hazards. Another common hazard is the generation of hydrogen gas produced by VLA, Ni-
    Cad, and VRLA batteries during charging—especially when an equalizing charge is applied. Removal of any
    potential hydrogen build-up should be considered by the designer. This build-up may be removed through
    normal building exhaust or leakage, direct exhaust of the battery area, or by inclusion of fresh air into the
                                                                       72
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    building ventilation system. IEEE Std 1635™ [B20] notes several other recommendations. The designer
    should be aware of any restrictions imposed by the AHJ in regards to battery ventilation. IEEE Std 979™
    [B10] provides guidance for fire protection in substation applications. IEEE Std 1375 [B16] provides some
    additional guidance as well on physical protection of batteries. Local codes or the owner’s preference should
    be reviewed as to whether the battery should be housed in its own room or enclosure.
    The battery charger also does not present any direct fire hazard. However they generate heat as part of the
    ac–dc conversion and care should be taken to restrict flammable material from being located above the vent
    openings.
    Working clearance meeting the requirements of the NESC [B1] Table 125-1 (or local codes) should be used to
    provide safe access to the equipment for workers and in the event of an emergency.
    As discussed in 5.8.1.2.1, working space meeting the requirements of NESC [B1] Table 125-1, or other
    jurisdictional codes, should be maintained. In retrofit designs of older stations, the designer should check
    clearances that may have been compromised over the life of the substation, or in replacing equipment that was
    installed prior to code applicability. Consideration should also be given to a method for removing battery cells
    in the future. Space for a permanent or temporary lifting device may be needed. Typical substation battery
    cells weigh 20 kg to 70 kg (44 lb to 154 lb). Lifting cells of that weight can be very difficult for maintenance
    from upper steps or tiers of a battery rack.
    An eyewash station (or equivalent device) should be available to support workers in the event of acid contact.
    Provisions should be made for storing the specific gravity tester and an acid-resistant cloak if required by the
    owner. Consideration should be given to using a spill containment system around the battery to absorb acid in
    the event of a catastrophic cell failure. Refer to 5.8.1.3 and IEEE Std 1578™ [B19] for further information.
    The designer should review owner’s preference or local codes for separation of multiple battery systems.
    Physical separation or barriers may be required for multiple systems to reduce the likelihood of a catastrophic
    event (e.g., fire or short circuit) on one dc system propagating to other dc systems. This can include physical
    separation by air gap or installation of a barrier (a wall or locating batteries in separate rooms). As the battery
    system is crucial in allowing most substation equipment to successfully operate, care should be given to
    provide as much protection to the battery system as reasonably possible.
    Reliability is also dependent on battery area temperature. Battery area temperature should be monitored and
    kept constant (refer to 5.8.1.2.5 and 5.8.1.4). Owner’s operating practice for response to building high or
    low temperatures should be reviewed to determine effect on battery performance and reliability. Low or high
    temperatures outside the design of the battery load profile can impact reliability.
    Reliability of the dc system is also affected by the placement location of dc panels. Separation of dc panels
    may reduce the likelihood of a single panel fire removing both dc systems, and should be considered. Cable
    routing should also be reviewed. Some utilities run dc cables from different systems in separate locations to
    enhance reliability.
    If the battery is placed in its own room due to owner’s preference or local codes, the battery room door should
    have a fire rating at least equal to the fire rating of the walls. The battery room door should also incorporate
    all necessary signage to inform workers of potential hazards of the area, such as acid containing, explosive
    mixtures, etc., as required by the AHJ. Interior signage should identify the exit doors. Depending on room
    design and local codes, the battery room door may also need to incorporate a blast louver to relieve pressure
    in the event of a hydrogen build-up and explosion. The battery room door should have a panic bar on the
                                                                       73
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    inside, and open outward into the control room or outside to allow safe egress of personnel in the event of an
    emergency. Requirements for securing the door such as locks should be reviewed by the designer.
    Battery temperature plays a key role in battery performance. Battery specifications are generally published at
    25 °C (77 °F) and temperatures that vary from this can affect performance. During the battery sizing calculation
    the designer should consider the minimum and maximum temperature that the battery area could reach. For
    example, in a cold weather climate in winter, the battery area could easily reach 13 °C (55 °F) during a loss of
    ac to the substation, depending on building insulation levels during the needed response time. Conversely, in a
    warm weather climate in summer, the same loss of ac could drive the battery area over 40 °C (104 °F). Normal
    operating practices should also be reviewed to determine baseline conditions as part of the battery calculation.
    If the owner keeps the battery area cooler than the battery manufacturer’s recommended temperature, battery
    performance may be below published data and the designer should account for the discrepancy in the design
    calculation. Batteries that are installed outdoors, or in non-climate control enclosures, may be subject to large
    variations in temperature.
    The designer should review applicable local codes regarding acid containment. It is typical practice to install a
    spill-containment system that contains the acid to an area immediately adjacent to the battery and neutralizes
    it for safe handling and disposal. Use of acid-resistant paint on the floors and walls of the battery area is
    recommended to reduce damage to the building in the event of a spill. If permanent spill containment is not
    installed, the designer should review local codes or owner’s preference to determine if on-site temporary
    acid-absorbent material or temporary containment is required. For example, in the United States, the NFPA 1
    [B33] requires spill containment for an individual vessel with more than 208 liters of electrolyte or multiple
    containers exceeding 3785 liters. Most substation batteries have electrolyte volumes below those limits. Refer
    to IEEE Std 1578 [B19] for further information.
    The designer should review the footprint required for a containment system. The designer should consider
    adequate worker access and remove tripping hazards that may be created by installation of a mechanical
    containment system.
    When selecting a battery rack, there are several things that should be considered, including temperature
    differences, weight of the battery, available space, and maintenance requirements. Battery racks generally
    come in three types—step, tier, or stepped tier as shown in Figure 29. A step rack is designed so the battery
    levels are “stepped” from one another (usually offset by the depth of a cell). A tiered rack has the levels of
    batteries on top of each other. A stepped tier is a combination of the two.
                                                                       74
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    For substation applications, steps and tiers are usually limited to two levels. Step racks generally have a larger
    footprint than an equivalent tiered rack, and cells can be easier to access. Tiered racks tend to save floor space
    due to their smaller footprint. Other considerations with larger batteries include height and weight. Battery
    weight can also be an issue for battery installation or removal, especially in tight space and/or with taller racks.
    Battery weight should be considered during structural design.
    The height variations between upper and lower levels of a battery rack are a concern. Height variations can
    cause cell temperature differences within the same battery system. Since cell temperature can impact battery
    characteristics, interconnecting cells at different temperatures can lead to an early failure of the battery system.
    As a general rule, temperature gradients in excess of 3 °C should be avoided.
    Battery racks should have an acid-resistant coating applied to the structural frame to preserve its integrity. It
    may also be advantageous to have a liner of polyethylene or similar material on the support rails to further
    protect the rails from damage and provide electrical isolation.
    The battery rack should be specified based on its correct seismic zone. A seismic rack has the same basic
    design as a non-seismic rack with additional bracing applied to hold the rack and cells in place.
    Substation batteries used for operation and control of interrupting devices and protection system, SCADA,
    etc. are typically ungrounded with ground fault detection. Communication systems, such as those used by
    telecom companies, are typically a positively grounded 24 V (dc) or 48 V (dc) system. The designer should be
    aware of the difference and not mix the two. Direct contact input to opposite systems should be avoided and
    use of interposing relays or devices should be used. Addition of unintentional grounds should be reviewed
    during the design and installation process.
    As discussed further in 5.8.2.3.2, the battery is the source of fault current for the dc system. The cables between
    the main battery terminals and the first overcurrent protection device (breaker or fuse) are usually unprotected
    (unless using a mid-point fuse). Thus, designs should place the main battery overcurrent protection as close
    to the main terminals as possible to reduce this exposure. A short circuit to any portion of the battery main
                                                                       75
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    terminals can produce extreme heat and fire hazard. Any damage to the cables from the battery can subject a
    worker to the full short-circuit capability of the battery. The designer should review the owner’s preference to
    separate the positive and negative cables of the battery to reduce the possibility of a direct short circuit being
    applied to the battery. When separating cables, cables should be placed in non-magnetic conduits to reduce
    induced fields from causing other potential hazards. With multiple battery systems, the designer should not
    route main dc cables near one another to preserve independence and reliability.
    IEEE Std 1375 [B16] gives additional guidance on the methods of protecting the main dc feed to the load
    device from the battery. They include:
        a)    Battery fuse (in both positive and negative leads for ungrounded systems)
        b)    Battery circuit breaker (including both positive and negative leads for ungrounded systems)
        c)    Battery disconnect switch (fused or non-fused) that allows the battery to be disconnected from the
              load circuits
        d)    Mid-point battery fuse which protects for internal and external faults and limits fault energy by up to
              half of the battery capacity for certain types of faults; cable only, no overcurrent provided
IEEE Std 1375 [B16] gives a description of the advantages and disadvantages of each method.
    The designer needs to review the coordination between all devices in the dc circuit in accordance with the
    NEC [B34], local codes, or owner’s design criteria. Overcurrent protection devices should be sized such that
    an upstream device does not trip for a downstream operation. For example, if a dc panel circuit feeds both a
    relay panel fuse and a circuit breaker trip coil, the relay panel fuse should operate due to a protective relay
    power supply or circuit failure and leave the circuit breaker trip coil operational.
    Since the battery is the primary current source in case of short circuit, the battery data sheet or manufacturer
    should be consulted to determine available fault current. The interrupting devices in downstream circuits
    should be reviewed for their dc ratings. Many devices may appear to have sufficient interrupting capability, but
    do not have the appropriate asymmetrical interruption current (AIC). Without proper AIC, a breaker may not
    interrupt the current. It may weld closed or open without the ability to dissipate the energy. These conditions
    could result in damage to equipment, injury to personnel, and/or other unintended operations. Similar
    conditions apply to fuses used for interrupting faults.
    The designer should consider protection of the main dc feed by use of circuit breakers or fuses. Subclause
    5.8.2.2 and IEEE Std 1375 [B16] give more guidance on protection of the battery main feed.
    The designer should consider local codes as well as owner’s preference or design criteria when selecting circuit
    breakers or fuses. Fuses may have a lower initial installed cost, but may require additional spare material to be
    stored on site to allow for replacement in the event of an operation. Fuses may also require a fuse monitor to
    be installed to detect and provide indication that they have operated. Circuit breakers may have a higher initial
    installed cost, but they provide indication they have operated, and usually do not require replacement after
    they have operated.
                                                                       76
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    The dc equipment should be selected to be of the proper rating for their intended location. Outdoor rated
    equipment may be installed within indoor substation locations, but indoor rated equipment should not be
    installed outdoors. It may be advantageous to have some dc panels placed closer to the loads they support,
    such as circuit breakers in a large transmission substation. In this application, outdoor rated equipment may be
    required, such as NEMA 3R or NEMA 4.
    As discussed previously, the dc equipment should be rated for interruption of fault current. System
    configuration should be considered for determining ultimate fault current availability. If a main breaker is
    used, it should be able to interrupt the maximum short-circuit current available from the battery for the life
    of the battery. The designer should review interrupting capability during a battery replacement. Continuous
    current rating should match or exceed the current drawn by existing loads and allow for future growth. Voltage
    rating should match or exceed the maximum battery voltage (i.e., 250 V [dc] for a 125 V [dc] battery). Fault-
    interrupting current ratings at a dc level should be known. A large battery may be capable of currents over 10
    kA. DC interrupting capability of the main fuse or circuit breaker should be reviewed. The interrupting rating
    of the distribution panel is based on the breaker(s) with the lowest fault current rating.
    The designer should review local codes and owner’s preference or design criteria regarding the need to
    provide isolation switches for the battery and charger. Main isolation switches can allow a temporary battery
    to be installed during maintenance, upgrades, or replacement. Since it is usually not feasible to shut down an
    entire substation during a battery change out, providing an isolation switch where a temporary battery can be
    connected can be advantageous during upgrades or emergencies, such as battery failure. Similar logic can be
    applied to chargers, though in case of a charger failure or replacement, it is usually easier to connect a charger
    temporarily than a battery.
    As discussed previously, access per NESC [B1] Table 125-1 or other local codes should be maintained. Table
    125-1 provides minimum clearances, but owner’s preference and design criteria should also be reviewed.
    Battery cells/jars can be heavy enough that workers may not be able to lift without mechanical assistance.
    Access room may need to be maintained for mechanical lifting devices to install or remove battery cells/jars.
    Safe working clearances between the battery and other equipment should be maintained. Overhead lifting
    devices may need to be anchored to building supports to remove battery cells.
    Battery chargers may also require lifting devices. The designer should also consider the heat generated by
    chargers when evaluating equipment accessibility.
    The designer should review owner’s preference for any back-ups and/or spare parts. Based on the importance
    of the substation, there may be a need for back-up equipment (either charger or battery bank). As discussed
    previously, if provisions are made during design, then back-up supplies can easily be connected. If back-up
    supplies are required, the design should account for the time frame required to facilitate timely or permanent
    connection of any back-up supplies, including the location of back-up or temporary connections. Also, the
    designer needs to review if automatic actions are required to place any back-up supplies in service.
                                                                       77
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Annex A
    (informative)
    Bibliography
    Bibliographical references are resources that provide additional or helpful material but do not need to be
    understood or used to implement this standard. Reference to these resources is made for informational use
    only.
[B1] Accredited Standards Committee C-2, National Electrical Safety Code® (NESC®).6,7
    [B2] Distribution Transformer Handbook, First Edition, Transformer connections, General Electric, October
    1951.
    [B3] IEEE Std 141™, IEEE Recommended Practice for Electric Power Distribution for Industrial Plants
    (IEEE Red Book™).
    [B4] IEEE Std 242™, IEEE Recommended Practice for Protection and Coordination of Industrial and
    Commercial Power Systems (IEEE Buff Book™).
    [B5] IEEE Std 446™, IEEE Recommended Practice for Emergency and Standby Power Systems for Industrial
    and Commercial Applications (IEEE Orange Book™).
    [B6] IEEE Std 450™, IEEE Recommended Practice for Maintenance, Testing, and Replacement of Vented
    Lead-Acid Batteries for Stationary Applications.
    [B7] IEEE Std 484™, IEEE Recommended Practice for Installation Design and Installation of Vented Lead-
    Acid Batteries for Stationary Applications.
    [B8] IEEE Std 485™, IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stationary
    Applications.
    [B9] IEEE Std 946™, IEEE Recommended Practice for the Design of DC Auxiliary Power Systems for
    Generating Systems.
[B10] IEEE Std 979™, IEEE Guide for Substation Fire Protection.
    [B11] IEEE Std 1106™, IEEE Recommended Practice for Installation, Maintenance, Testing, and Replacement
    of Vented Nickel-Cadmium Batteries for Stationary Applications.
    [B12] IEEE Std 1115™, IEEE Recommended Practice for Sizing Nickel-Cadmium Batteries for Stationary
    Applications.
    [B13] IEEE Std 1187™, IEEE Recommended Practice for Installation Design and Installation of Valve-
    Regulated Lead-Acid Batteries for Stationary Applications.
    [B14] IEEE Std 1188™, IEEE Recommended Practice for Maintenance, Testing, and Replacement of Valve
    Regulated Lead-Acid (VRLA) Batteries and Stationary Applications.
    6
      The IEEE standards or products referred to in Annex A are trademarks owned by the Institute of Electrical and Electronics Engineers,
    Incorporated.
    7
      IEEE publications are available from the Institute of Electrical and Electronics Engineers (http://standards.ieee.org/).
                                                                       78
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    [B15] IEEE Std 1189™, IEEE Guide for Selection of Valve-Regulated Lead-Acid (VRLA) Batteries for
    Stationary Applications.
[B16] IEEE Std 1375™, IEEE Guide for the Protection of Stationary Battery Systems.
    [B17] IEEE Std 1458™, IEEE Recommended Practice for the Selection, Field Testing, and Life Expectancy
    of Molded Case Circuit Breakers for Industrial Applications.
    [B18] IEEE Std 1491™, IEEE Guide for Selection and use of Battery Monitoring Equipment in Stationary
    Applications.
    [B19] IEEE Std 1578™, IEEE Recommended Practice for Stationary Battery Electrolyte Spill Containment
    and Management.
    [B20] IEEE Std 1635™, IEEE/ASHRAE Guide for the Ventilation and Thermal Management of Batteries for
    Stationary Applications.
    [B21] IEEE Std C57.12.00™, IEEE Standard for General Requirements for Liquid-Immersed Distribution,
    Power, and Regulating Transformers.
[B22] IEEE Std C57.12.10™, IEEE Standard Requirements for Liquid-Immersed Power Transformers.
    [B23] IEEE Std C57.12.20™, IEEE Standard for Overhead-Type Distribution Transformers 500 kVA and
    Smaller: High Voltage, 34 500 V and Below; Low Voltage, 7970/13 800Y V and Below.
    [B24] IEEE Std C57.91™, IEEE Standard for Loading Mineral-Oil-Immersed Transformers and Step-Voltage
    Regulators.
[B25] IEEE Std C57.96™, IEEE Guide for Loading Dry-Type Distribution and Power Transformers.
    [B26] IEEE Std C57.105™, IEEE Guide for Application of Transformer Connections in Three-Phase
    Distribution Systems.
    [B27] IEEE Std C62.22™, IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating-
    Current Systems.
[B29] NEMA 250, Enclosures for Electrical Equipment (1000 Volts Maximum).
[B30] NEMA AB-1, Molded-Case Circuit Breakers, Molded Case Switches, and Circuit-Breaker Enclosures.
    8
     The Uniform Building Code is available from the International Code Council (http://iccsafe.org).
    9
     NEMA publications are available from the National Electrical Manufacturers Association (http://www.nema.org/).
    10
       NFPA publications are published by the National Fire Protection Association (http://www.nfpa.org/).
    11
      National Electrical Code, NEC, and NFPA 70 are registered trademarks of the National Fire Protection Association.
                                                                       79
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                           IEEE Std 1818-2017
                         IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
[B40] UL 489, Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures.
[B43] UL 991, Standard for Tests for Safety-Related Controls Employing Solid-State Devices.
    12
         UL publications are available from Underwriters Laboratories (http://www.ul.com/).
                                                                           80
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Annex B
    (informative)
    One of the cables the designer is selecting will supply a 120 V, 200 A single-phase load, will be located outdoors,
    and will be assumed to be connected to 75 °C termination. Based on the given information, the designer
    selects a 600 V, 75 °C, 4/0, cross-linked polyethylene high heat-resistant water-resistant (XHHW) conductor,
    per NEC 2014 Tables 310.104(A), 310.15(B)(16), and cable manufacturer recommendations. Upon receiving
    specification back from the panel supplier, the designer discovers that the branch circuit breaker terminations
    on the panel are only rated for 60 °C. The designer should now find a different solution for the 200 A load, as
    their cable should be derated to the 60 °C temperature rating: 195 A [see Table 310.15(B)(16)].
    In addition to temperature rating of terminations, the availability of terminations at the connected equipment
    may be a limiting factor as well. For example, when sizing conductors it is determined that a single 250
    kcmil conductor would meet the ampacity requirements. The equipment terminations are the tap-screw
    type, however, and only allow two connections with sizes ranging from 4 AWG to 4/0 AWG. The designer
    determines that two 1 AWG conductors would still meet the ampacity requirements of the circuit. So in this
    case, the availability of terminations ultimately governed the conductor size.
    The designer verifies the conductor is adequately sized based on the available fault current at the circuit
    breaker termination. The AHJ has dictated that the short-circuit capability ratings be determined based on
    IEEE Std 242-2001 [B4]. The available fault current in this case is 20 kA. Based on the manufacturer specs
    and associated time-current trip curves, the circuit breaker feeding the load should trip within a maximum
    time of 1.5 cycles. The designer has selected 1 AWG XHHW copper conductors, with a continuous operating
    temperature of 60 °C, and a short-circuit temperature rating of 250 °C.
The designer first calculates the virtual available fault current based on IEEE Std 242-2001 [B4], Figure 9‑4:
KT = 1.2
    Based on the virtual available fault current, and a fault-clearing time of 0.025 s, the designer determines that a
    single 2 AWG copper conductor would be sufficient, based on IEEE Std 242-2001 [B4], Figure 9-2. Since two
    1 AWG conductors are being used per phase, there is no need to change the size of the conductor.
                                                                       81
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    that the ambient temperature for the area is 29 °C, and as a result selects all of their cables based on 30 °C
    ambient temperature ratings.
    One of the branch circuits is designed to feed an SF6 gas cart for outdoor HV breaker servicing. The gas cart
    product manual states that it has a power demand of 60 A, a power factor of 0.9, and requires a 208 V, 3-Ø, four-
    wire supply. The circuit run is 61 m (200 ft) long and routed through a 4 in polyvinyl chloride (PVC) conduit
    with two other 3-Ø, four-wire circuits. The supply conductor will be connected to copper termination points,
    rated at 75 °C. Gas carts are rarely operated for more than two hours. Any load that is not expected to run for
    three hours or more is considered a non-continuous load, per NEC Article 100. Based on this information and
    NEC 210.19(A)(1), 310.15(B)(16), the designer initially selects the branch circuit conductor that supplies the
    SF6 gas cart to be 6 AWG, copper thermoplastic heat and water-resistant nylon-coated (THWN) rated at 75 °C.
    Once the initial selection has been made, the designer should account for conductor bundling effects and
    voltage drop. The calculation for bundling effects is performed first, per NEC 310.15(B)(3)(a). There are two
    ways that this process can be executed; the first one shown below is not recommended, but has been given for
    demonstration purposes.
    Note that the value used in the calculation is 70%, since, out of the total of 12 conductors in the PVC conduit,
    only 9 are current-carrying:
where
    It is clear from this conductor bundling calculation that the 6 AWG conductor does not have sufficient ampacity
    to supply the load. At this point there are two ways to find the appropriate conductor to supply the load per
    NEC 310.15(B)(3)(a): 1) select a conductor of the same type, yet with higher ampacity rating, and calculate
    the adjusted ampacity of the conductor per NEC Table 310.15(B)(3)(a) until a sufficient conductor is selected,
    or 2) apply the adjustment factor to the full load amperes, and then select a conductor of sufficient ampacity
    from NEC Table 310.15(B)(16). The second option is the easiest route, as it only requires one calculation,
    instead of iterative calculations:
where
    Based on this calculation, the designer would select 3 AWG copper THWN. The designer also has the option
    of routing one or two of the sets of 3-Ø, four-wire circuits through another raceway, in order to decrease, or
    possibly eliminate, the correction factor for conductor bundling.
    Next, the designer should consider the voltage drop of the conductor. The designer has designed the system
    to where the voltage drop of the feeders does not exceed 2% to the point of termination at the panel, and 5%
    overall. The voltage drop is calculated based on the initial information given, formula given in NEC 2011,
    Table 9, Note 2, as well as the values given in Table 9, as shown below.
                                                                       82
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 1818-2017
                       IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    First, effective Z is calculated for a 3 AWG copper wire running through PVC conduit. Note that if available,
    the impedance given by the manufacturer should be used in the calculation. NEC Table 9 provides values
    based on uncoated wires, and could be used for estimation:
                                                               0.2253Ω
        Z e = 0.25× 0.9 + .047 ×sin (arccos (0.9)) =                                                                                   (B.4)
                                                                 kFT
VD = I L × Z E × L × 3 (B.5)
                      VD 4.68 V
        %Drop =          =       ×100 = 2.25%                                                                                          (B.7)
                      VL   208 V
        where
    Note that the calculation above is essentially the same as the 3-Ø voltage drop calculation except it is simplified
    into two separate equations.
    In this case, the voltage drop is acceptable, as it is below the required 3% per NEC 210.19(A) (Note 4). Had
    it been excessive, the designer would have to select a conductor with a lower impedance cable (usually larger
    size), or find an alternate route to decrease the distance of the circuit feeding this load.
    Further into the design of the auxiliary system, the designer finds out that the ambient temperature at the
    substation is not 29 ° C—it is actually 33 °C. The load amperes should be recalculated to account for the
    change in ambient temperature, per NEC Table 310.15(B)(2)(a):
                    IL    85.71
        I L ′′ =        =       = 91.18 A                                                                                              (B.8)
                   0.94   0.94
        where
    In this case, the conductor size does not need to be adjusted, as it can satisfy the load amperes requirement per
    NEC Table 310.15(B)(16).
    The last check the designer performs is for the short-circuit rating of the selected conductor. The AHJ has
    dictated that the short-circuit capability ratings be determined based on IEEE Std 525. The available fault
    current in this case is 10 kA. Based on the manufacturer specs and associated time-current trip curves, the
                                                                       83
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    circuit breaker feeding the load should trip within a maximum time of 0.5 cycles. The designer has selected
    3 AWG copper THWN conductor, with a continuous operating temperature of 75 °C, and a short-circuit
    temperature rating of 250 °C.
    Based on the information provided, the designer performs a short-circuit capability calculation, based on
    IEEE Std 525:
                             I
        A=                                   in circular mils                                                                          (B.9)
                 0.0297      T + 234
                        log10 2
                    t        T 1 +234
        where
                          10 000
        A=                            = 11 996.5 in circular mils ≈ 9AWG                                (B.10)
             0.0297         250 + 234
                      log10
             0.00833         75 + 234
    The chosen conductor size, based on the calculated amount of area, is 9 AWG. This is smaller than selected
    conductor size 3 AWG, so no change in conductor size is necessary.
                                                                       84
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Annex C
    (informative)
                                                                       85
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    From a battery sizing standpoint, options A and C would require batteries with the same total A-hour
    requirements as they both would require a single battery to accommodate the substation dc load. Option
    B would likely require two smaller batteries, possibly different sizes depending on how the primary and
    secondary loads are split.
        1.    Determine the voltage and number of cells—Select the number of battery cells to be used to support
              voltage level
        2.    Battery sizing considerations—Determine adjustment factors like growth, aging, design margin, and
              temperature correction
        3.    Select the battery type and determine the characteristics of the cell—Battery type is the specific
              manufacture and style; characteristics of the cell include amperes per positive plate and construction
              (lead calcium, lead selenium, etc.)
        4.    Determine the time span of the duty cycle—How long the system has to run without the battery under
              charge
        5.    Construct the minute-by-minute load profile (the duty cycle), which is very site specific—Determine
              the continuous loads on the dc system, and determine the momentary, worst case switching event (the
              maximum stress on the dc system)
        6.    Calculate the required positive plates of the battery for each period in the duty cycle utilizing the cell-
              sizing worksheet—Figure 3 in IEEE Std 485
Step 1
    This example considers a 125 V nominal system with maximum dc voltage = 140 V and utilize a 60 cell
    battery. The example utilizes a 1.75 V per cell end-of-life cycle = 105 V for 60 cell battery.
Step 2
    The design margin provides additional capacity to accommodate future substation additions or expansions
    without requiring an upgrade to the substation battery due to capacity.
    Because a battery’s performance is affected by temperature, the temperature correction factor is needed to
    adjust the required battery capacity for any environment above or below the standard battery temperature
    rating.
    IEEE Std 450™ [B6] and IEEE Std 1188™ [B14] recommend that a battery be replaced when the actual
    capacity drops to 80% of its rated capacity. Based on end-of-life capacity, a 125% aging factor is typically
    used.
Step 3
                                                                       86
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    This example looks at several types of flooded batteries, including lead selenium and lead calcium, and selects
    the correct size for each type.
Step 4
    This example assumes a 12-hour duty cycle with the event starting the duty cycle being a failure of the battery
    charger. Thus, when the battery supplies the complete dc power for 12 hours, then the worst case tripping
    would occur. The definition of worst case tripping in this case is a fault and sequence of events that would lead
    to the highest tripping current during the last minute of the 12-hour duty cycle.
Step 5
    One of the most variable components of battery sizing is defining the duty cycle or the load(s) over a defined
    time period that the battery may be required to supply dc power. It is not the intent of this example to define
    the duty cycle for every battery application, but to provide guidance and discussion on some of the issues that
    should be taken into consideration.
    Some utilities may have a standard duty cycle defined for simplicity, or to provide consistency in the battery
    sizing applications. Considerations should include: duration of duty cycle, worst case tripping current (applied
    at beginning and/or end of duty cycle), continuous loading, and random loads.
The duty cycle with 16.5 A continuous load and 63 A worst case tripping, is shown in Figure C.2.
New substation—Add all loads connected to battery that are on for the 12-hour duration of the duty cycle.
    Existing substation expansion—Record the charger output current and float voltage under float charging.
    Multiply the current by a correction factor (ratio of end-of-life voltage to float voltage) in order to accommodate
    the current at the lower end-of-life voltage. Then, add all new loads connected to the battery being installed on
    the expansion project.
                                                                       87
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 1818-2017
                       IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    In manufacturer documentation for relays or similar devices, power supply burden/load is typically listed at
    a range or a higher value than what is observed or calculated from battery charger readings. The maximum
    current draw listed is generally assuming a maximum, or more significant, amount of data processing or contact
    operation than what occurs during normal operation. During a fault or switching event, the load drawn by a
    relay or other device is generally higher than what is measured during normal operation. In lieu of determining
    load for every device in an existing station, the designer may consider adding a multiplier or safety factor to
    the current measured on the battery charger in order to account for increased “continuous” loads during fault
    or switching events.
From the dc panel schematic, add up the continuous loads to calculate the continuous current.
    The total watts is divided by the end-of-life voltage (105 V in this example) to get the total calculated
    continuous current. Note that Table C.1 is an example only and the designer should verify the manufacturer’s
    published data.
                                                                       88
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
For continuous current calculations, use the total watts divided by the end-of-life voltage.
Step 6
                                                                       89
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 1818-2017
                       IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Calculate the required positive plates of the battery for each period in the duty cycle utilizing the cell-sizing
    worksheet—Figure 3 in IEEE Std 485.
    Since different types of batteries, and similar batteries by different manufacturers, have different plate designs
    they also have different discharge curves. Thus it is important to calculate this step separately for each different
    type of battery or manufacturer.
    You can calculate the amperes per positive plate for a particular battery from the vendor battery discharge curve
    or table of discharge rates for specific time and divide it by the number of positive plates. If the manufacturer
    data provides the total number of plates, the number of positive plates can be calculated by the following:
                   discharge rate
        RTT =                                                                                                                          (C.2)
                   positive plates
        where
The discharge rate above shows the calculations of RT for Vendor B at 1 minute and 720 minute rates.
Continue this for other manufacturers to fill out table of amperes per positive plate (RT).
    Complete the battery cell–sizing worksheet from the vendor’s discharge curves that can be found in their
    literature (see Figure C.3).
                                                                       90
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    Multiply the uncorrected values by the temperature correction factor, design margin, and aging factors to
    calculate the number of positive plates and the total number of plates. Then, round the calculated number of
    positive plates up to the next whole number.
    Match the number of plates to the battery manufacturer’s size to obtain the 8-hour AH rating of the battery of
    each type.
Manufacturer A = 456 AH
Manufacturer B = 440 AH
    Compare the cost of Manufacturer A and Manufacturer B battery sizes to select the most economical battery
    that is properly sized for this application.
    Per IEEE Std 485 battery sizing guidelines, the time increment of the duty cycle in battery sizing should be
    in one minute increments. Thus when determining the worst case scenario, the designer should look at the
    sequence of events that would occur in the last minute and select the one that sums up to the highest value. For
    example if there is a fault on transformer T1, the sequence of operations would be: trip breakers 5B2, 5B3,
    and BT1. After BT1 is tripped, it would be likely that there would be an auto-restoration function to restore
    the 34.5 kV bus via the bus tie breaker. This would likely occur in the same minute that the fault occurred and
    tripped the breakers on the bus. However, all of the original tripping would have occurred prior to the reclosing
    function. Therefore, the designer should look at the tripping load and the resulting restoration load and select
    the higher value for the worse case tripping during the last minute. A more likely scenario would be for a
    breaker-failure condition with motor operators rather than breakers. The motor operators would likely still be
    operating when the breaker-fail function tripped more devices. In order to fully understand the sequence of
    events, it is important to review a relay and metering diagram that shows what devices would trip for various
    faults on the system. It is also important to include auxiliary relays, such as lock out relays if they are used.
    For example, a bus differential relay may operate a lock out relay to trip all the equipment on the bus. The load
                                                                       91
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                         IEEE Std 1818-2017
                       IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
    of the lockout should be included in the calculation. The metering and relay diagram would also show all the
    devices that would be tripped, reclosing schemes, and breaker-fail schemes.
    Device load should be taken from the manufacturer’s nameplate data, for example breaker trip coil ratings.
    For motor operators, the locked rotor value should be used in order to accommodate the worst case scenario of
    operating a switch that may be iced up, or that the blade may be corroded and stuck in the jaws due to lack of
    frequent operation.
From 5.5.2, the following formula is used to determine the required dc output of the battery charger.
              A          
        I =   e + I C  (d )(k )                                                                                                 (C.3)
              
             t          
where
                                 1       
        A = 16.5 A×12h + 79.5 A× hours = 199.325 Ah removed
                                  60    
I C = 16.5 A
The estimate assumes the altitude is below 3300 ft and k = 1.0 (verify manufacturer data)
             199.325              
        I =         ×1.1 + 16.5×1.1×1 = 48.29
              8                  
From manufacturer available sizes, select the closed size that is equal or greater than this value.
    From the battery charger manufacturer data, verify the dc output breaker size to coordinate the cable size
    between the charger and the dc system. For a 50 A battery charger, the dc breaker size is 70 A.
    The cable should be sized to 125% of overload device. The cable to connect the charger to the dc system
    should be sized to accommodate 87.5 A.
                                                                       92
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
                                                        IEEE Std 1818-2017
                      IEEE Guide for the Design of Low-Voltage Auxiliary Systems for Electric Power Substations
From cable capacity tables select a 4 AWG copper conductor for this application.
                                                                       93
                                                   Copyright
Authorized licensed use limited to: Centro Universitário       © 2017 IEEE.
                                                         Fei. Downloaded     All rights
                                                                         on October     reserved.
                                                                                     11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.
IEEE
standards.ieee.org
Phone: +1 732 981 0060                 Fax: +1 732 562 1571
© IEEE
      Authorized licensed use limited to: Centro Universitário Fei. Downloaded on October 11,2024 at 18:25:53 UTC from IEEE Xplore. Restrictions apply.