Fire Survival Cables Submittal Document

The document provides technical details of 4C x 16 sqmm fire survival cables. It specifies details like conductor material, insulation material, thickness, core identification, bedding material, armour material, diameter and oversheath material and thickness. The cable meets the fire performance circuit integrity test of 950 degree Celsius for 3 hours.

Uploaded by

pradeepyellur
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
131 views11 pages

Fire Survival Cables Submittal Document

The document provides technical details of 4C x 16 sqmm fire survival cables. It specifies details like conductor material, insulation material, thickness, core identification, bedding material, armour material, diameter and oversheath material and thickness. The cable meets the fire performance circuit integrity test of 950 degree Celsius for 3 hours.

Uploaded by

pradeepyellur
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Annexure - 16.

3 DOCUMENT SUBMITTAL

PROJECT: SHS - PROJECT TIGER, Bengaluru Ref No: SHS-PTB-SIBI-FF-DS-0013 Rev:1

Contract No : SHS/PT/EEA/DS/XXXX Date: 28-5-2024

Subject : Fire survival cables

TO:
M/s. Mace Project and Cost Management Private Limited, FROM:
703 Vatika City Point, M.G.Road,
Gurgaon 122 002, Haryana, India,
Tel: +92 12 4436 8216, 436 8217

ENCLOSURES / ATTACHMENTS: ACTIONS REQUESTED:


Consultant Drawings For incorporation within the design

Consultant Specifications For Information

Shop Drawings for review For review and comment

Reports For Costing For Tender

Sketches  For Approval For Construction

Samples SENT VIA:

Contract Documents By Hand or Courier Due Date:

 Other: Separate Cover Via: Email


ENCLOSURES
Item Type Doc. No. Title Rev. No. No. of pages
1 Scan Fire Survival cables Rev 1 10

Name : Rajaram Gopu

Designation : Project Manager Signed :


COMMENTS:

A-Compliant B-Compliant With Comments C-Not Compliant

Name :
Designation : Signed:

Please acknowledge receipt by signing, dating, and returning a copy of this Transmittal
Comment reply sheet
TDS No 0013 rev-1

Sl No Client/Consultant comment SIBI reply Remarks


As per BOQ ,cables to be fire Fire survial cables re submitted for approval,highlighted
survival cables.Submitted data cable sizes.
sheet is XLPE cables, which is not
1
acceptable, to be updated updated
and re submitted for our review and
approval
CHECKLIST FOR MATERIAL SUBMITTAL (MAT)
Name of material submittal Armored cables(fire survival)
Date: 27-5 -2024 INDICATIVE
SMT Ref No: A 6.0 a, b, c, d & e

S.no Item Yes No Remark


1. MAT form is properly filled up and signed. Yes
Material Technical Datasheet/Literature is
2. Yes
attached
Material Safety Datasheet is attached N/A
3. (Depending on product)
4. In house Test Certificate/MTC for the N/A
product quality compliance is attached
Relevant Contract Specification / BOQ
5. Yes
page is attached
Approved Vendor List page copy is Yes
6.
attached
7. Drawing copy where the material is Yes
mentioned (any one sample) is attached.
Manufacturer's ISO Certificate is attached N/A
8. (If Vendor prequalification is not submitted).
9. Any Variation from Specification. N/A

Whether Specification variation details N/A


10.
attached.
Letter for regional and recycled material
11.
attached. N/A
N/A
Letter declaring VOC (Volatile Organic
12.
Compounds) limit is attached (if applicable).
N/A
13. LEED/ GRIHA Compliance (If applicable).
N/A
Approved Logistic Plan for stacking or
14.
storage of material is attached

Note: Sample Tag should go along with material submittal

NAME: Rajaramgopu

SIGN: (For Sub Contractor QC)

Form Ref: PRM/CL-MAT/R0/May2021


Classification: Public
PROJECT : PROJECT TIGER, BENGALURU
CLIENT : SIEMENS HEALTHINEERS
PRINCIPAL ARCHITECT
: ELLER + ELLER ARCHITECTS
INDIAN PARTNER ARCHITECTS
: VENKATARAMANAN ASSOCIATES
SMEP CONSULTANTS: DESIGN TREE SERVICE CONSULTANTS PVT. LTD
SUBJECT : FPS BOQ-Factory Building Phase-I

SL.NO DESCRIPTION UNIT Total Qty

A FIRE PUMP ROOM EQUIPMENT (BIS APPROVED)

6.0 1100 V GRADE POWER / CONTROL CABLES


Supply, installation, testing & commissioning of following sizes of 600V/1000V
Grade Fire Survival galvanised steel wire Armoured cable in the strandard
aluminium/Copper conductor,constructed / designed as per BS 7846. Cable
shouldbe suitable to retain the circuit integrity as per BS 8519 and certified for
CWZ for F 120 fire test as per BS 8491 Standard on existing cables tray / hume
pipe / trenches etc as required complete in all respect as per site requirement.

a 3.5C x 95 sq.mm Copper cables for main pumps Rmt 80


b 4C x 16 Sqmm. Copper cables for Jockey pumps Rmt 60
c 12C x 2.5 Sqmm. Copper cables for Diesel engines Rmt 40
d 2C x 2.5 Sqmm. Copper cables for Instrumentation Rmt 70
e 3.5C x 70 Sqmm. Copper cables for water curtain pumps Rmt 40

Designtree Service Consultants Pvt.Ltd


Date - 08.03.2023,Rev-02. VENKATRAMANAN ASSOCIATES
# Classification - Public Fire protection System
Document ID: TE/QMS/F/02
Rev. No. : 01 Issued Date : 10/06/2021

Technical Particulars of LT XLPE FS Cables

Sr.No. Particulars 4 X 16 Sq.mm


1 Name of Manufacturer Polycab India Ltd
2 Type of cable FS cable
3 Voltage Grade V 600/1000
4 No of cores X size in sqmm 4 X 16
5 Conductor
a) Material Plain annealed Copper Class 2 to BS EN 60228
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 1.15
c) Shape of the main conductor Compact circular Stranded
Material over conductor to meet the fire resistance
d) Two Layers of Glass mica Tapes
requirements
e) Fire Performance Circuit intigrity test 950°C for 3 Hours
6 Insulation
a) Material XLPE (GP 8) as per BS 7655: Section 1.3
b) Nominal Thickness of insulation (mm) 0.7
c) Core identification Blue,Brown,Black & Grey
7 Bedding
a) Material Extruded polymeric material as per clause 9 of BS 7846:2015
b) Minimum thickness of extruded bedding (mm) 0.44
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal diameter of armour (mm) 1.25
d) Tolerances on armour dimension(mm) ±0.070
9 Oversheath
Extruded polymeric material Type LTS 1 as per BS 7655:
a) Material
Section 6.1
b) Minimum Thickness of oversheath (mm) 1.08
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 1.47
b) Calculated Cable reactance (ohm/km) 0.0908
c) Impedance of cable (ohm/km) 1.47
d Approx. Cable Capacitance (mfd/km) 0.28
Maximum conductor temperature under normal
11 90°C
operating conditions
Maximum conductor temperature at the termination
12 250°C
of short circuit
Short Circuit rating of conductor for the duration of
13 2.29
1 sec (kA)
14 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 95
(b) In Air at 40°C (A) 89
15 Applicable Standard BS 7846 : 2015
16 Approx. overall diameter of the cable (mm) 25.5 ± 2.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
2
(i) for Cables pulled with stocking (kg.) 7x D where D is the overall diameter of the cable
ii) for Cables pulled with pulling eyes (kg) 326
19 Standard Drum Length with tolerance (mtr.) 1000 ± 5%
5% of order quantity & Individual Non-standard drum length
20 Non-Standard Drum Length mtrs
minimum 200 Mtrs
21 Embossing POLYCAB ELECTRIC CABLE 600/1000 V BS:7846-F2
YEAR POLYCAB ELECTRIC CABLE 600/1000 V NO OF CORE
22 Printing X SQ MM. BS : 7846-F2 H WITH SEQUENTIAL MARKING at
every one meter of interval
Note:-The values given above are subject to tolerances
as per the relevant standards.
Incase of any Typographical error /Discrepancy,
relevant standards shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 01 Issued Date : 10/06/2021

Technical Particulars of LT XLPE FS Cables

Sr.No. Particulars 4 X 70 Sq.mm


1 Name of Manufacturer Polycab India Ltd
2 Type of cable FS cable
3 Voltage Grade V 600/1000
4 No of cores X size in sqmm 4 X 70
5 Conductor
a) Material Plain annealed Copper Class 2 to BS EN 60228
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 0.268
c) Shape of the main conductor Sector shaped stranded
Material over conductor to meet the fire resistance
d) Two Layers of Glass mica Tapes
requirements
e) Fire Performance Circuit intigrity test 950°C for 3 Hours
6 Insulation
a) Material XLPE (GP 8) as per BS 7655: Section 1.3
b) Nominal Thickness of insulation (mm) 1.1
c) Core identification Blue,Brown,Black & Grey
7 Bedding
a) Material Extruded polymeric material as per clause 9 of BS 7846:2015
b) Minimum thickness of extruded bedding (mm) 0.76
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal diameter of armour (mm) 2.00
d) Tolerances on armour dimension(mm) ±0.10
9 Oversheath
Extruded polymeric material Type LTS 1 as per BS 7655:
a) Material
Section 6.1
b) Minimum Thickness of oversheath (mm) 1.48
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 0.342
b) Calculated Cable reactance (ohm/km) 0.0786
c) Impedance of cable (ohm/km) 0.351
d Approx. Cable Capacitance (mfd/km) 0.41
Maximum conductor temperature under normal
11 90°C
operating conditions
Maximum conductor temperature at the termination
12 250°C
of short circuit
Short Circuit rating of conductor for the duration of
13 10.02
1 sec (kA)
14 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 212
(b) In Air at 40°C (A) 226
15 Applicable Standard BS 7846 : 2015
16 Approx. overall diameter of the cable (mm) 41.0 ± 3.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
2
(i) for Cables pulled with stocking (kg.) 7x D where D is the overall diameter of the cable
ii) for Cables pulled with pulling eyes (kg) 1428
19 Standard Drum Length with tolerance (mtr.) 500 ± 5%
5% of order quantity & Individual Non-standard drum length
20 Non-Standard Drum Length mtrs
minimum 200 Mtrs
21 Embossing POLYCAB ELECTRIC CABLE 600/1000 V BS:7846-F2
YEAR POLYCAB ELECTRIC CABLE 600/1000 V NO OF CORE
22 Printing X SQ MM. BS : 7846-F2 H WITH SEQUENTIAL MARKING at
every one meter of interval
Note:-The values given above are subject to tolerances
as per the relevant standards.
Incase of any Typographical error /Discrepancy,
relevant standards shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 01 Issued Date : 10/06/2021

Technical Particulars of LT XLPE FS Cables

Sr.No. Particulars 4 X 95 Sq.mm


1 Name of Manufacturer Polycab India Ltd
2 Type of cable FS cable
3 Voltage Grade V 600/1000
4 No of cores X size in sqmm 4 X 95
5 Conductor
a) Material Plain annealed Copper Class 2 to BS EN 60228
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 0.193
c) Shape of the main conductor Sector shaped stranded
Material over conductor to meet the fire resistance
d) Two Layers of Glass mica Tapes
requirements
e) Fire Performance Circuit intigrity test 950°C for 3 Hours
6 Insulation
a) Material XLPE (GP 8) as per BS 7655: Section 1.3
b) Nominal Thickness of insulation (mm) 1.1
c) Core identification Blue,Brown,Black & Grey
7 Bedding
a) Material Extruded polymeric material as per clause 9 of BS 7846:2015
b) Minimum thickness of extruded bedding (mm) 0.76
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal diameter of armour (mm) 2.00
d) Tolerances on armour dimension(mm) ±0.10
9 Oversheath
Extruded polymeric material Type LTS 1 as per BS 7655:
a) Material
Section 6.1
b) Minimum Thickness of oversheath (mm) 1.56
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 0.247
b) Calculated Cable reactance (ohm/km) 0.0764
c) Impedance of cable (ohm/km) 0.259
d Approx. Cable Capacitance (mfd/km) 0.47
Maximum conductor temperature under normal
11 90°C
operating conditions
Maximum conductor temperature at the termination
12 250°C
of short circuit
Short Circuit rating of conductor for the duration of
13 13.59
1 sec (kA)
14 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 254
(b) In Air at 40°C (A) 279
15 Applicable Standard BS 7846 : 2015
16 Approx. overall diameter of the cable (mm) 45.0 ± 3.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
2
(i) for Cables pulled with stocking (kg.) 7x D where D is the overall diameter of the cable
ii) for Cables pulled with pulling eyes (kg) 1937
19 Standard Drum Length with tolerance (mtr.) 500 ± 5%
5% of order quantity & Individual Non-standard drum length
20 Non-Standard Drum Length mtrs
minimum 200 Mtrs
21 Embossing POLYCAB ELECTRIC CABLE 600/1000 V BS:7846-F2
YEAR POLYCAB ELECTRIC CABLE 600/1000 V NO OF CORE
22 Printing X SQ MM. BS : 7846-F2 H WITH SEQUENTIAL MARKING at
every one meter of interval
Note:-The values given above are subject to tolerances
as per the relevant standards.
Incase of any Typographical error /Discrepancy,
relevant standards shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 01 Issued Date : 10/06/2021

Technical Particulars of LT XLPE FS Cables

S.No Particulars 12 X 2.5 Sq.mm


1 Name of Manufacturer Polycab India Limited
2 Type of cable FS cable
3 Voltage Grade V 600/1000
4 No of cores X size in sqmm 12 X 2.5
5 Conductor
a) Material Plain annealed Copper Class 2 to BS EN 60228
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 7.41
c) Shape of the main conductor Circular Stranded
Material over conductor to meet the fire resistance
d) Two Layers of Glass mica Tapes
requirements
e) Fire Performance Circuit intigrity test 950°C for 3 Hours
6 Insulation
a) Material XLPE (GP 8) as per BS 7655: Section 1.3
b) Nominal thickness of insulation (mm) 0.7
c) Core identification All cores grey with number printing
7 Bedding
a) Material Extruded polymeric material as per clause 9 of BS 7846:1997
b) Minimum Thickness of extruded bedding (mm) 0.44
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal diameter of armour (mm) 1.25
d) Tolerances on armour dimension(mm) ±0.070
9 Oversheath
Extruded polymeric material Type LTS 1 as per BS 7655:
a) Material
Section 6.1
b) Minimum thickness of outersheath(mm) 1.08
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 9.45
b) Calculated Cable reactance (ohm/km) 0.114
c) Impedance of cable (ohm/km) 9.45
d Approx. Cable Capacitance (mfd/km) 0.16
Maximum conductor temperature under normal
11 90°C
operating conditions
Maximum conductor temperature at the termination
12 250°C
of short circuit
Short Circuit rating of conductor for the duration of
13 0.36
1 sec (kA)
14 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 20
(b) In Air at 40°C (A) 18
15 Applicable Standard BS 7846 : 2015
16 Approx. overall diameter of the cable (mm) 27.0 ± 2.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
2
(i) for Cables pulled with stocking (kg.) 7x D where D is the overall diameter of the cable
ii) for Cables pulled with pulling eyes (kg) 153
19 Standard Drum Length with tolerance (mtr.) 1000 ± 5%
5% of order quantity & Individual Non-standard drum length
20 Non-Standard Drum Length mtrs
minimum 200 Mtrs
21 Embossing POLYCAB ELECTRIC CABLE 600/1000 V BS:7846-F2
YEAR POLYCAB ELECTRIC CABLE 600/1000 V NO OF CORE
22 Printing X SQ MM. BS : 7846-F2 H WITH SEQUENTIAL MARKING at
every one meter of interval
Note:-The values given above are subject to tolerances
as per the relevant standards.
Incase of any Typographical error /Discrepancy,
relevant standards shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 01 Issued Date : 10/06/2021

Technical Particulars of LT XLPE FS Cables

S.No Particulars 2 X 2.5 Sq.mm


1 Name of Manufacturer Polycab India Ltd.
2 Type of cable FS cable
3 Voltage Grade V 600/1000
4 No of cores X size in sqmm 2 X 2.5
5 Conductor
a) Material Plain annealed Copper Class 2 to BS EN 60228
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 7.41
c) Shape of the main conductor Circular Stranded
Material over conductor to meet the fire resistance
d) Two Layers of Glass mica Tapes
requirements
e) Fire Performance Circuit intigrity test 950°C for 3 Hours
6 Insulation
a) Material XLPE (GP 8) as per BS 7655: Section 1.3
b) Nominal Thickness of insulation (mm) 0.7
c) Core identification Brown & Blue
7 Bedding
a) Material Extruded polymeric material as per clause 9 of BS 7846:2015
b) Minimum thickness of extruded bedding (mm) 0.44
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal diameter of armour (mm) 0.90
d) Tolerances on armour dimension(mm) ±0.050
9 Oversheath
Extruded polymeric material Type LTS 1 as per BS 7655:
a) Material
Section 6.1
b) Minimum Thickness of oversheath (mm) 0.92
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 9.45
b) Calculated Cable reactance (ohm/km) 0.114
c) Impedance of cable (ohm/km) 9.45
d Approx. Cable Capacitance (mfd/km) 0.16
Maximum conductor temperature under normal
11 90°C
operating conditions
Maximum conductor temperature at the termination
12 250°C
of short circuit
Short Circuit rating of conductor for the duration of
13 0.36
1 sec (kA)
14 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 41
(b) In Air at 40°C (A) 36
15 Applicable Standard BS 7846 : 2015
16 Approx. overall diameter of the cable (mm) 16.0 ± 2.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
2
(i) for Cables pulled with stocking (kg.) 7x D where D is the overall diameter of the cable
ii) for Cables pulled with pulling eyes (kg) 25
19 Standard Drum Length with tolerance (mtr.) 1000 ± 5%
5% of order quantity & Individual Non-standard drum length
20 Non-Standard Drum Length mtrs
minimum 200 Mtrs
21 Embossing POLYCAB ELECTRIC CABLE 600/1000 V BS:7846-F2
YEAR POLYCAB ELECTRIC CABLE 600/1000 V NO OF CORE
22 Printing X SQ MM. BS : 7846-F2 H WITH SEQUENTIAL MARKING at
every one meter of interval
Note:-The values given above are subject to tolerances
as per the relevant standards.
Incase of any Typographical error /Discrepancy,
relevant standards shall be prevailed.
A. RECOMMENDED MAKES FOR MECHANICAL WORKS

1 FIRE PUMPS (ELECTRICAL MOTOR DRIVEN) - BIS APPROVED : KIRLOSKAR BROS. LTD / LUBI / MATHER & PLATT (WILO)

2 DIESEL ENGINE PUMPS (FM APPROVED) : KIRLOSKAR BROS. LTD / LUBI / MATHER & PLATT (WILO)

:Siemens, KIRLOSKAR BROS, CROMPTON GREAVES, HINDUSTAN


3 ELECTRIC MOTORS
MOTORS, ABB

4 G.I. / M.S. PIPES : JINDAL (HISSAR) / TATA


5 SPRINKLER OUTLETS (UL LISTED & FM APPROVED) : SANT/ JAINSONS/ GRINNEL/ VICTAULIC
D.I THREADED FITTINGS (25MM DIA TO 50MM ) UL LISTED & FM
6 : NATIONAL / SANT / NVR / JAINSONS / NEW
APPROVED
GROOVED FITTINGS (65MM DIA & ABOVE) UL LISTED & FM
7 : NATIONAL / SANT / NEW/ VICTAULIC / JAINSONS
APPROVED
8 BUTTERFLY VALES : SANT / LEHRY / JAINSONS/ TYCO / HD
9 NON – RETURN VALVES : SANT / LEHRY / JAINSONS/ TYCO / HD
10 GATE VALVES (Screwed end) : SANT / LEHRY / JAINSONS/ TYCO / HD
11 BALL VALES (Screwed end) : SANT / LEHRY / JAINSONS/ TYCO / HD
12 STRAINERS : SANT / LEHRY / JAINSONS/ TYCO / HD
13 C.I. GATE VALVES : SANT / LEHRY / JAINSONS/ TYCO / HD
14 FLOW METRE : SANT / FORBES MARSHALL / EUREKA/ GERAND
15 PRESSURE SWITCH : INDFOS / SWITZER / DANFOSS
16 PRESSURE GAUGE : DELTA / H. GURU / FIEBIG / PRICOL
17 ANTICORROSIVE MATERIAL : I W L / RUSTECH / PEDILITE
18 HYDRANT VALVES : NEWAGE GUJARAT / AAAG / ESSEL / MINIMAX
19 BRANCH PIPE WITH NOZZLE : NEWAGE GUJARAT / AAAG / ESSEL / MINIMAX
20 FIRE HOSES : NEWAGE GUJARAT / AAAG / ESSEL / MINIMAX
21 HOSE COUPLINGS : NEWAGE GUJARAT / AAAG / ESSEL / MINIMAX
22 HOSE REEL : NEWAGE GUJARAT / AAAG / ESSEL / MINIMAX
23 HOSE BOX / FIRE DUCT SHUTTER : NEWAGE GUJARAT / AAAG / ESSEL / MINIMAX
24 FIRE EXTINGUISHERS : SAFEX / MINIMAX / KANEX / FYREX / CEASFIRE
25 SPRINKLERS : TYCO / HD / RAPIDROP / VIKING
26 SPRINKLER ALARM VALVE : TYCO / HD / RAPIDROP / VIKING
27 ZONE CONTROL VALVE : TYCO / HD / RAPIDROP / VIKING
28 POST INDICATOR VALVES : TYCO / HD / RAPIDROP / VIKING
29 FLOW SWITCH : SYSTEM SENSOR / POTTER / SWITZER / LEVCON
30 PAINT : ASIAN / BERGER / JOTUN
31 AIR RELEASE VALVES : SANT / NVR / SAFEX / NEU-G
32 WELDING ELECTRODES : ESAB / ADVANI
33 PRESSURE REDUCING VALVE : TYCO / HD / RAPIDROP / VIKING
34 DELUGE VALVE : TYCO / HD / RAPIDROP / VIKING
35 WATER CURTAIN NOZZLE : HD / TYCO / RAPIDDROP
36 FLEXIBLE HOSE : TYCO / HD / RAPIDROP / VIKING
37 PIPE SUPPORTS : FISCHER / HILTI / HIRA WAVERN
38 PASSIVE FIRE PROTECTION : FISCHER / HILTI
39 ANTIVIBRATION PADS : DUNLOP / RESISOFLEX
40 CABLE TRAYS : STORACK / PAN / MAG

B. RECOMMENDED MAKES FOR ELECTRICAL WORKS

1 BATTERY : EXIDE / STANDARD / AMAR RAJA/ MINIMAX


2 MOTOR CONTROL CENTRE : VINTEK POWER SOLUTIONS & SYSTEMS / BLUE VOLT/
: VENUS POWER CONTROLS / G V ENGINEERS
3 CONTROL / POWER CABLES : POLYCAB / APAR CABLES / RAVI CABS /
4 MCCB : Siemens, L&T / ABB
5 CONTROL MCB : SIEMENS / ABB
6 VOLT METER SELECT SWITCH : Siemens, SALZER / KAYCEE
7 VOLTMETER ( AC / DC) : Siemens, ELEMUSER / AE
8 AMMETER ( AC / DC) : Siemens, ELEMUSER / AE

Classification - Public
#
9 POWER CONTACTORS & SWITCHGEAR : : SIEMENS / ABB / L&T / SCHNEIDER
10 INDICATING LAPS ( LED type) : Siemens, BINAY / TEKNIC
11 PUSH BUTTONS : Siemens, TEKNIC / SIEMENS
12 AUTO / MANUAL SELECTOR : Siemens, SALZER / KAYCEE
13 TIMERS : Siemens, EAPL / L & T
14 TERMINAL BLOCKS : Siemens, ELMEX / WAGO
15 CURRENT TRANSFORMERS : KALPA / VOLTAMPS / KAPPA
16 OVER LOAD RELAY : SIEMENS/ ABB/ SCHNEIDER / L & T
17 SINGLE PHASE PREVENTORS : Siemens, MINILEC / L & T
18 ENGINE CONTROL SELECTOR : Siemens, SALZER / KAYCEE / L&T
19 MAIN SUPPLY SELECTOR – DPMCB : SIEMENS / ABB/ L & T
20 BATTERY CHARGING SELECTOR : SALZER / L & T/ KAYCEE
21 BATTERY CHARGER : MICRO POWER / PARKDIVS / NPH
22 SIREN / HOOTER : KHERAJ/EQUI.
23 TOGGLE SWITCH : Siemens, JAY / EQUI.
24 END TERMINATIONS : DOWEWLS / MULTI
25 CABLE TRAY : STORACK / PAN / MAG
26 AC DIGITAL METER : Siemens, AE / ELEMUSER

C. FIRE DETECTION & ALARM WITH P.A. SYSTEM

1 SMOKE DETECTORS : SIEMENS CERBERUS


2 HEAT DETECTORS : SIEMENS CERBERUS
3 MAIN CONTROL PANEL : SIEMENS CERBERUS
4 MANUAL PULL STATIONS : SIEMENS CERBERUS
5 HOOTERS / STROBES : SIEMENS CERBERUS
6 MODULES : SIEMENS CERBERUS
7 BATTERY : HITACHI / DRYSIL / JOHNSON / EXIDE
8 FIRE SURVIVAL CABLES / WIRES : POLYCAB / KEI/ RR kabil
9 COMMUNICATION WIRES : POLYCAB / KEI/ RR kabil
10 M S CONDUITS : BHARATH / GB
11 PVC CONDUITS : VIP / ATUL / AVON PLAST
12 TWO WAY TALK BACK SPEAKERS RAVEL/ ROYAL / INNOVATIVE / WATTN ENGG. / HEINRICH
13 PUBLIC ADDRESS SPEAKERS : SIEMENS
14 TWO WAY TALK BACK CONSOLE RAVEL/ ROYAL / INNOVATIVE / WATTN ENGG. / HEINRICH
15 PUBLIC ADDRESS SYSTEM CONSOLE : SIEMENS
16 TWO WAY TALK BACK AMPLIFIERS : HEINRICH / ROYAL / INNOVATIVE / WATTN ENGG.
17 AMPLIFIERS : SIEMENS
18 COMPUTER : IBM / DELL / HP
19 PRINTER : CANON / HP / WIPRO

D. PANEL GAS SUPPRESSION SYSTEM


1 COMPLETE PACKAGE : FIRETRACE / FIRETREX / CEASFIRE/ KANNEX

Classification - Public
#