CLIENT: Requisition No.
: -
Document No.:
DATA SHEET
IBO-TiA9-EXE-HHA-50-HVA-TDS-0001
ELECTRIC DUCT HEATER
Page: 5 of 15
Rev. No.: 0
ENG BY: Item Tag No.: HW-5080
PROVISION OF DETAIL ENGINEERING DESIGN (DED) PM9
SIMPLIFICATION AND PROCUREMENT OF MATERIALS FOR BEKOK B
Service: HVAC System
FIRST HYDROCARBON
TERENGGANU
GENERAL
1 ITEM NAME ELECTRIC DUCT HEATER 7 LOCATION ROOF OF COMPRESSOR CONTROL ROOM - MODULE 9
2 TAG NO. HW-5080 8 QUANTITY 1
3 EQUIPMENT DESCRIPTION ELECTRIC HEATERS 9 MODE OF OPERATION INTERMITTENT
4 CERTIFICATION UL (Zero Clearance To Combustible Surface) 10 AIR FLOW (*)
5 HEATING CAPACITY 4.0 kW 11 PRESSURE DROP 50 max. Pa
6 ELECTRICAL SUPPLY 480V/ 3PHASE/ 60Hz 12 AREA CLASSIFICATION SAFE AREA
MATERIAL AND CONSTRUCTION DATA
1 ELEMENT TYPE FULL SHEATHED, FINNED TUBULAR ELECTRIC HEATING COIL
2 ELEMENT MATERIAL 80% NICKEL, 20% CHROMIUM WIRE SPIRALLY FORMED AND HELD IN PLACE BYMAGNESIUM OXIDE
3 TERMINAL BOX TYPE NEMA 12
4 DISCONNECT SWITCH TYPE NEMA 12
5 FRAME MATERIAL TYPE 316L STAINLESS STEEL
6 FRAME MATERIAL THICKNESS (*)
7 LIFTING LUGS YES, if > 25 kg
8 EARTHING BOSS YES
9 PANEL INGRESS PROTECTION IP 42
OPERATORS, CONTROLS AND ACCESSORIES
1 THERMAL CUTOUT YES NO TYPE Automatic Reset
2 SECONDARY CUTOUT YES NO TYPE Manually Resetable
3 THERMAL CUTOUT SET POINT (*) Deg. C
4 SECONDARY CUTOUT SET POINT (*) Deg. C
5 TEMPERATURE CONTROL YES NO TYPE/MODEL TYRISTOR
6 CONTROL CIRCUIT TRANSFORMER YES NO TYPE/MODEL (*)
7 DOOR INTERLOCK DISCONNECT SWITCH YES NO MATERIAL SS
8 FUSES YES NO
9 AIR FLOW SWITCH YES NO TYPE/MODEL (*)
10 TEMPERATURE CLASS T3
11 CONTROL VOLTAGE SEE NOTE 3
12 CAPACITY CONTROL THYRISTOR CONTROL
13 SAFETY FEATURE HIGH TEMPERATURE PROTECTION THERMAL CUT OFF (Hi : 90 Deg. C / HiHi : 125 Deg. C)
AIR FLOW SWITCH
DISCONNECT SWITCH
SCHEDULE OF HVAC DUCT HEATERS
OVERALL SIZE
AIR FLOW
NO. TAG NO. LOCATION (WIDTH x HEIGHT x PRESSURE DROP (Pa) Kw RATING REMARKS
(CMH)
LENGTH)
1. HW-5080 COMPRESSOR CONTROL ROOM - MODULE 9 (*) (*) 50* *
NOTES
1 * - ASTERISK DENOTES VENDOR TO COMPLETE/VERIFY
2 EACH DUCT HEATER SHALL BE COMPLETED WITH A LOCAL DUCT HEATER CONTROL PANEL.
3 24V DC SHALL BE DERIVED FROM DUCT HEATER CONTROL PANEL BY VENDOR.
4 THE EQUIPMENT/ PACKAGE SHALL SUITABLE FOR OPERATION IN ZONE 2, GAS GROUP II A, TEMP. CLASS T3 (ELECTRICAL) AND
ZONE 1, GAS GROUP II A, TEMP. CLASS T3 (INSTRUMENT)