PROPOSED FITOUT FOR DCG4-0202 ON 2ND FLOOR
SDS_WD_DLF_101.16
SUMMARY OF ELECTRICAL LOADS
S.NO. Description Connected Diversity Maximum
demand
Load(KW) (KW)
A Light Load 1.299 0.9 1.16
B Raw Power Load 10.6 0.4 4.24
C UPS Power Load 5.3 0.9 4.77
D HVAC Load 5 0.9 4.5
TOTAL 23 15
Total ELECTRICAL LOAD 15KW
SUMMARY OF UPS LOADS
S.NO. Description Connected Diversity Maximum
demand
Load(KW) (KW)
Emergency Light Load (20% of lights
A load) 0.26 1 0.26
B UPS POWER LOAD 5.3 0.9 4.77
TOTAL 6 5
UPS CAPACITY
Adopting Loading Factpr 0.8 and Power Factor 0.8
Invertor Capacity works out to be = 10KVA
Selection of Inverter 1NO.=15KVA
S.L. DESCRIPTION LOAD QTY. TOTAL
(WATTS) (WATTS)
A LIGHTING
1 4" 12W ROUND RECESSED LIGHTS 12 75 900
2 1X15W DECORATIVE DOWN LIGHTER 15 2 30
3 1X10W DOWN LIGHTER 10 0 0
4 1X18W SUSPENDED LINEAR LIGHT 18 8 144
5 COVE LIGHT 5WMTR. 5 45 225
6 SIGNAGE 0 0 0
1.3KW
B RAW SWITCH SOCKET
1 6A SOCKET OUTLET 100 21 2100
2 2X6A SOCKET OUTLET 150 0 0
3 16A SOCKET OUTLET 500 15 7500
4 16A SOCKET CLEANING 500 2 1000
10.6KW
C UPS SWITCH SOCKET
1 1X6A SOCKET OUTLET 100 17 1700
2 2X6A SOCKET OUTLET 150 24 3600
3 3X6A SOCKET OUTLET 150 0 0
4 16A SOCKET OUTLET 500 0 0
5 2X16A SOCKET OUTLET 1000 0 0
5.5KW
D HVAC
1 HVAC UNIT 5000 1 5000
SUB TOTAL 5KW
SDS_WD_DLF_101.17 HEAT LOAD ESTIMATE FOR OFFICE AT SECOND FLOOR
CUSTOMER : UDAY BHAN JI DESIGN CONDITION
ESTIMATED BY: TIME OF PEAK LOAD:
DATE: 30-12-2023 DB %RH WB GR/LB
AREA : 2446 SQFT. OUTSIDE 110 29 80.17 74
TOTAL HT. 9.50 FEET INSIDE 74 55 62.49 66
AVG. HT. 9.50 FEET DIFF. 36 X X X
PEOPLE 34 NOS X 10 CPM = 340 340
1.5 AIR CHANGES PER HOUR = 233
FRESH AIR 340
= 410
STRUCT. SQFT FACTOR TEMP. BTUHR EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM SENSIBLE HEAT F.A 340 8 0.15X0.67
WALL N 0 0.34 4 0 PEOPLE 34 NOS. 220
WALL NE 0 0.34 10 0 ERLH SUBTOTAL
WALL E 0 0.34 18 0 FACTOR 5%
WALL SE 0 0.34 18 0 ERLH TOTAL
WALL S 495 0.34 16 1) EFFECTIVE
2692 ROOM TOTAL HEAT
WALL SW 0 0.34 14 0 2) F.A. 340 8 0.67X0.85
WALL W 0 0.34 12 0 GRAND TOTAL1+2+3
HEAT SUBTOTAL=
WALL NW 0 0.34 6 0 FACTOR
GLASS N 0 0.56 23 0 GRAND TOTAL HEAT
GLASS NE 0 0.56 12 0 AIRCONDITIONING TONNAGE
GLASS E 0 0.56 12 0
GLASS SE 0 0.56 12 0 ERSHF
GLASS S 0 0.56 12 0 INDICATED ADP
GLASS SW 0 0.56 85 0 SELECTED ADP
GLASS W 0 0.56 163 0 DEHUMIDIFIER CFM
GLASS NW 0 0.56 138 0
ALL GLASS 0 1.13 36 0 RETURN AIR GAIN
PRT. WL. 240 0.4 31 2976 STRUCT. SQFT. FACTOR TEMP.
PRT. GLS. 0 1.13 31 0 WALL N 0 0.34 25
ROOF 0 0.12 56 0 WALL NE 0 0.34 31
CEILING 0 0.4 31 0 WALL E 0 0.34 39
FLOOR 0 0.4 31 0 WALL SE 0 0.34 39
F.A. 340 36 0.15 X 1.08 1983 WALL S 0 0.34 37
PEOPLE 34 NOS. 230 7820 WALL SW 0 0.34 35
LIGHT(w) 1299 1 3.412 4432 WALL W 0 0.34 33
EQPT.(kw) 2 1 3410 6820 WALL NW 0 0.34 27
OTHERS(kw) 0 1 3410 0 PRT. WL. 0 0.4 31
ERSH SUBTOTAL 26723 3) TOTAL R.A. GAIN
FACTOR 10% 2672
ERSH TOTAL 29395
273
7480
7753
388
8141
37536
1550
39086
1954
41040
3.49
0.742
54
54
1534
BTU/HR.