CLIENT
ARCHITECT
CONSULTANT
NAME OF THE PROJECT
LOCATION OF THE PROJECT
AREA TO BE AIR CONDITIONED
TOTAL HEIGHT
BOTTOM OF BEAM
FALSE CEILING HEIGHT
AREA
OCCUPANCY
LOAD OF COMPUTERS
EQUIPMENT LOAD
LIGHT LOAD
FLOOR ABOVE
FLOOR BELOW
OUTSIDE TEMP
INSIDE TEMP
RELATIVE HUMIDITY
AIR CHANGE / HOUR
CFM / PERSON
EXPOSED WALL
NORTH
SOUTH
EAST
WEST
NORTH EAST
SOUTH EAST
SOUTH WEST
NORTH WEST
EXPOSED GLASS
NORTH
SOUTH
EAST
WEST
NORTH EAST
SOUTH EAST
SOUTH WEST
NORTH WEST
PARTITION
TONNAGE
TOTAL CFM
TONNAGE AS PER CFM
EQUIPMENT SELECTED
REMARKS / COMMENTS
PROJECT/CLIENT:
APPLICATION      :
AREA
  Description           Area          U-factor    TD       Heat Load        DESIGN CONDITIONS                        16.00 HRS            SUMMER
                         sft                      F         BTU/H                               DB F         WB F    RH %     ENTH        GR/LB
INTERNAL SPACE SENSIBLE HEAT GAINS                                          OUTSIDE                  118        86                   52           144
WALL      N                       0       0.34         9            -       INSIDE                      76               55          26            58
          S                       0       0.34        21            -       DIFFERENCE                  42                           26            86
          E                       0       0.34        23            -
          W                       0       0.34        17            -       OCCUPANCY           2                    AREA (SFT)               2000
        NE                        0       0.34        10            -       LIGHT LOAD(w/sft)   2                    HEIGHT (FT)                   15
        SE                        0       0.34        18            -       EQPT. LOAD(W)       0
       SW                         0       0.34        14            -
       NW                         0       0.34         6            -       VENTILATION                       CFM           BF                0.15
GLASS N                           0       0.56        28            -       CFM/PERSON              7.5         15          CF                0.85
          S                       0       0.56        12            -       ACH                     1          500
          E                       0       0.56        12            -       SELECTED CFM                       500
          W                       0       0.56     163              -
        NE                        0       0.56        12            -       REHEAT ( IF REQUIRED)
        SE                        0       0.56        12            -       NEW SHF                                         0.88
       SW                         0       0.56        85            -       NEW TOTAL SPACE HEAT                        41400.67          BTU/H
       NW                         0       0.56     138              -       NEW SPACE SENSIBLE HEAT                     36432.59          BTU/H
GLASS TRANS:                      0       1.13        42            -       MINIMUM REHEAT REQUIRED                     13396.39          BTU/H
PARTITION                         0        0.4        37            -                     REHEAT                              0           BTU/H
ROOF INSUL                        0        0.1        72            -
ROOF EXPOSED                      0        0.4        72            -          SOLAR COEFFICIENTS                        WALL U-FACTOR
CEILING                           0        0.3        37            -       EAST                        12           EAST                     0.34
FLOOR                             0        0.3        37            -       WEST                     163             WEST                     0.34
VENTILATION                     500       0.16        42     3,402.00       NORTH                       28           NORTH                    0.34
INFILTRATION                                                        -       SOUTH                       12           SOUTH                    0.34
PEOPLE                            2                245         490.00       NORTH EAST                  12           NORTH EAST               0.34
LIGHTING LOAD                  4000       1.25    3.41      17,050.00       NORTH WEST               138             NORTH WEST               0.34
EQUIP LOAD (W)                    0               3.41              -       SOUTH EAST                  12           SOUTH EAST               0.34
MISCELLANEOUS                                                       -       SOUTH WEST                  85           SOUTH WEST               0.34
                                                 TOTAL      20,942.00       TRANSMISSION             1.13            PARTITION                    0.4
                 DEDUCT FOR STORAGE EFFECT
                       SENSIBLE HEAT SUBTOTAL               20,942.00       ROOF                     0.12            FLOOR                  0.3
                          DUCT GAIN AND SAFETY               2,094.20       CEILING
                     TOTAL SPACE SENSIBLE HEAT              23,036.20
INTERNAL SPACE LATENT HEAT GAINS                                                                        WALL TD
VENTILATION                     500        0.1        86     4,321.50       EAST                                23 NORTH EAST                      10
INFILTRATION                                                        -       WEST                                17 NORTH WEST                       6
PEOPLE                            2                205         410.00       NORTH                                   9 SOUTH EAST                   18
MISCELLANEOUS                                                       -       SOUTH                               21 SOUTH WEST                      14
                         LATENT HEAT SUBTOTAL                4,731.50
                                 SAFETY FACTOR %               236.58       ESTIMATED BY
                      TOTAL SPACE LATENT HEAT                4,968.08       DATE
                                TOTAL SPACE HEAT            28,004.28
VENTILATION AIR HEAT
SENSIBLE HEAT                   500       0.92        42    19,278.00
LATENT HEAT                     500       3.83        26    49,725.00
                          RETURN AIR GAIN @ 5%               1,400.21
                                GRAND TOTAL HEAT            98,407.49
SHF                            0.82 REHEAT (W)                          0
ADP                              55 CFM REQUIRED                 1195
DHA                       1194.95 TONS                            8.2