SIPROTEC 5 - Configuration 05.06.
2024 , 10:47:15 AM
________________________________________________________________________________________________
Device: 7UM85 Generator Protection
Product code
Short: P1L177269
Long: 7UM85BAAAAA00AAAA0AM021112111BAAA000000AC0CH2BA2CB2
Technical Data:
Firmware: Current version
Binary inputs: 15
Binary outputs: 20 Relays (6 Standard, 14 Fast, 0 High-Speed, 0 Power)
Current transformers: 6 for protection
2 for measurement and sensitive ground-current detection
Voltage transformers: 8 standard
Measuring-transducer inputs: 0 (20 mA or 10 V, fast)
0 (20 mA, standard)
0 (DC 300 V)
0 (20 mA, fast)
0 (temperature)
Housing width: 1/2 x 19''
Housing type: Flush mounting
Modules in 19" row 1: IO208, PS201, IO202
LEDs/Push-buttons: 16 LEDs
Operation Panel: Integrated
Key switch: Without
Display type: Small display
Front Design: Standard
Power Supply: DC 24 V - 48 V
________________________________________________________________________________________________
1/9
SIPROTEC 5 - Configuration 05.06.2024 , 10:47:15 AM
________________________________________________________________________________________________
Redundant Power Supply: No
Communication/Plug-in modules:
Communications encryption: Normal
Integrated Ethernet port J: for DIGSI 5
Plug-in module position E: ETH-BA-2EL: 2x electric Ethernet 100 Mbit/s, RJ45
Communication Protocols: applicable for DIGSI 5, IEC 61850-8-1
MMS and
GOOSE, IEC 60870-5-104, DNP3 TCP, Modbus TCP,
Synchrophasor (IEEE
C37.118 - IP), Profinet IO, SUP, DHCP, SNTP, SNMP, etc.
Redundancy protocols: Line Mode, RSTP, HSR, PRP
Plug-in module position F: Port is available but not assembled
Functions:
Function points class: Base + 200 function points
Note on function-points class
The function-points class results from the sum of the function points of the selected functions. You can
apply these functions according to the selected function-points class. The device also allows each other
selection of functions if the sum of the required function points is within the selected function-points
class.
From Version V9.3 on the function-points class "1400+" is withdrawn. With this class function-points
exceeding the limit of 1400 were free of charge. The maximum function-points class is now 1400. If a
function-points budget of more than 1400 points is required for a device the application
Function-Point-Manager need to be applied. All function points are liable to cost.
In the engineering phase DIGSI 5 checks that the selected configuration is suitable (capable of running
in the device) before loading it to the device.
Miscellaneous:
Warranty: 2 years
Special Approvals: Without
Firmware: Current version
________________________________________________________________________________________________
2/9
SIPROTEC 5 - Configuration 05.06.2024 , 10:47:15 AM
________________________________________________________________________________________________
7UM85 Generator Protection - Overview Function points calculation
(P1L177269)
Functions Free of Charge
ANSI Function Abbr. Included
Protection functions for 3-pole tripping 3-pole
Hardware quantity structure expandable I/O
14 Locked rotor I> + n<
37 Undercurrent I< 9X
38 Temperature supervision θ>
49R Thermal overload rotor protection (motor) θR 9X
50HS Instantaneous high-current tripping I>>> 9X
50/51 TD Overcurrent protection with positive-sequence current I1 I1> 20 X
(from V7.9)
50N/ 51N Overcurrent protection, ground IN> 9X
TD
50N/ 51N Overcurrent protection, 1-phase IN> 9X
TD
50L Load-jam protection I>L
59N, 67Ns Stator ground-fault protection (non-directional, V0>, ∠(V0,I0) 9X
directional)
74TC Trip-circuit supervision TCS
85/21 Universal teleprotection scheme for distance protection
(from V9.20)
86 Lockout
AFD Arc-protection (only with plug-in module ARC-CD-3FO)
Measured values - standard
Switching statistic counters
PQ-Basic measured values: THD (Total Harmonic
Distortion) and harmonics (from V8.01) THD voltage
aggregation values (from V8.40)
________________________________________________________________________________________________
3/9
SIPROTEC 5 - Configuration 05.06.2024 , 10:47:15 AM
________________________________________________________________________________________________
CFC (Standard, control)
Inrush current detection
External trip initiation
Control
Protection interface, serial
Monitoring and supervision
Fault recording of analog and binary signals
Frequency-tracking groups (from V7.8) 6X
Temperature acquisition via communication protocol
Functions with Costs
ANSI Function Abbr. Included Quantity Value Points
IEC 61850-9-2 Merging Unit MU 0 200 0
function (Note: Max. 2 streams
per MU function, each MU
function requires a
ETH-BD-2FO plug-in module)
Process Bus Client function PB client 0 100 0
(Note: This function requires a
ETH-BD-2FO plug-in module)
IEC 61850-9-2 Merging Unit MU (7SS85 0 295 0
function for 7SS85 CU (Note: CU)
Only for communication with a
7SS85 with Significant
properties: "CU: ...". This
function requires a
ETH-BD-2FO plug-in module)
IEEE 1588v2/PTP Grandmaster GMC 0 200 0
Clock (Note: This function
requires a ETH-BD-2FO, with
V9.20)
21GT Impedance protection for Z< 1 25 25
transformers
24 Overexcitation protection V/f 2X 2 25 0
25 Synchrocheck, synchronization Sync 0 50 0
function
________________________________________________________________________________________________
4/9
SIPROTEC 5 - Configuration 05.06.2024 , 10:47:15 AM
________________________________________________________________________________________________
25 Synchronization function with Sync 1 80 80
balancing commands, 1
channel for each sync. location
27 Undervoltage protection: V< 2 5 0
"3-phase" or 2X
"positive-sequence system V1"
or "universal Vx"
27 Undervoltage protection: V< 2X 2 5 0
"3-phase" or "universal Vx"
27R, 59R Rate-of-voltage-change dV/dt 0 5 0
protection (from V8.30)
Undervoltage-controlled Q>/V< 0 15 0
reactive power protection
32, 37 Power protection P<>, Q<> 0 15 0
active/reactive power
32R Reverse-power protection - P< 2X 2 5 0
37 Power-plant disconnection -dP 0 50 0
protection
40 Underexcitation protection 1/xd 1 45 45
46 Negative-sequence I2> 2X 2 5 0
overcurrent protection
46 Unbalanced-load protection I2² t> 1X 1 10 0
(thermal)
46 Negative-sequence I2>, ∠(V2,I2) 0 5 0
overcurrent protection with
direction
47 Overvoltage protection, V2> 2X 2 5 0
negative-sequence system
47 Overvoltage protection, V2/V1> 2X 2 5 0
negative-sequence/positive-se
quence system
48 Starting-time supervision for I²start 0 10 0
motors
49 Thermal overload protection θ, I²t 2X 2 10 0
49 Thermal overload protection, θ, I²t 1X 1 5 0
user-defined characteristic
49H Hot spot calculation θh, I²t 0 20 0
49F Field-winding overload IF² t 0 10 0
protection
________________________________________________________________________________________________
5/9
SIPROTEC 5 - Configuration 05.06.2024 , 10:47:15 AM
________________________________________________________________________________________________
49S CG Stator overload protection θ, I²t 0 15 0
with cold-gas consideration
49R CG Rotor overload protection with θ, IR²t 0 15 0
cold-gas consideration
50/51 Overcurrent protection, phases I> 2X 2 30 0
TD
Instantaneous tripping at SOTF 0 10 0
switch onto fault
50Ns/ Sensitive ground-current INs> 0 5 0
51Ns detection for systems with
resonant or isolated neutral
systems incl. a) 3I0>, b)
admittance Y0>, c) 3I0-harm>
(from V7.8)
50Ns/ Sensitive ground-current INs> 0 5 0
51Ns protection for systems with
resonant or isolated neutral
systems
Intermittent ground-fault Iie> 0 20 0
protection
50GN Shaft-current protection INs> 0 10 0
50 Startup overcurrent protection I-Start > 0 20 0
50/27 Inadvertent energization I>, V<reset 0 15 0
protection
50N DC, Direct-current/ direct-voltage IDC<>, VDC 0 10 0
27,59F protection <>
DC
50BF Circuit-breaker failure CBFP 1 10 10
protection, 3-pole
50RS Circuit-breaker restrike CBRS 0 20 0
protection
50EF End-fault protection (Note: 0 5 0
Only useable for distributed
busbar protection with 7SS85
CU with V8.40)
51V Overcurrent protection, t=f(I,V) 2X 2 10 0
voltage dependent
59, 59N Overvoltage protection: V> 2X 2 5 0
"3-phase" or "zero-sequence
system V0" or "universal Vx"
27TH, Stator ground-fault protection V03.H<, 0 20 0
59TH, with 3rd harmonic V03.H>;
59THD ΔV03.H
59N IT Turn-to-turn fault protection V0> 0 15 0
60 Voltage-comparison ΔU> 0 5 0
supervision
________________________________________________________________________________________________
6/9
SIPROTEC 5 - Configuration 05.06.2024 , 10:47:15 AM
________________________________________________________________________________________________
64G Stator ground-fault protection RSG< 0 55 0
100 % (20Hz)
64F Rotor ground-fault protection RRG< 0 25 0
(1-3Hz) (1 - 3 Hz)
64F, Rotor ground-fault protection IRG> 2X 2 5 0
frated (IRgnd>, fn)
64F, Rotor ground-fault protection RRG< 0 10 0
frated (Rgnd<, fn)
66 Restart inhibit for motors I²t 0 15 0
67 Directional overcurrent I>, ∠(V,I) 0 5 0
protection, phases
67N Directional overcurrent IN>, ∠(V,I) 0 15 0
protection, ground
67Ns Dir. sensitive ground-fault 0 30 0
detection for systems with
resonant or isolated neutral
incl. a) 3I0>, b) V0>, c)
Cos-/SinPhi, d) Transient
ground-fault fct., e) Phi(V,I), f)
admittance
Directional stage with a ∠(V0h,I0h) 0 10 0
harmonic; Note: this stage
additionally requires the
function "67Ns Dir. sensitive
ground-fault detection for
systems with resonant or
isolated neutral"
Directional intermittent Iie dir> 0 20 0
ground-fault protection
68 Power-swing blocking ΔZ/Δt 0 25 0
78 Out-of-step protection ΔZ/Δt 0 55 0
74CC Closed-circuit supervision CCS 2X 2 5 0
(from V7.9)
81 Frequency protection: "f>" or f<>; df/dt<> 1X 1 5 0
"f<" or "df/dt"
81 AF Abnormal frequency fBand 0 15 0
protection
81U Underfrequency load-shedding f<(UFLS) 0 15 0
Vector-jump protection Δφ> 0 20 0
87B Busbar differential protection ΔI 0 150 0
for 7UM85 (from V8.01)
Bay 2X 2 50 0
________________________________________________________________________________________________
7/9
SIPROTEC 5 - Configuration 05.06.2024 , 10:47:15 AM
________________________________________________________________________________________________
87T Transformer differential ΔI 0 40 0
protection
87N Restricted ground-fault ΔIN 0 15 0
protection
87M Motor differential protection ΔI 0 40 0
87G Generator differential ΔI 1 40 40
protection
PMU Synchrophasor measurement PMU 0 40 0
Measured values - extended: 0 3 0
Min, Max, Avg
PQ-Basic measured values: 0 20 0
Voltage unbalance (from
V8.40)
PQ-Basic measured values: 0 30 0
Voltage variations - voltage
dips, swells and interruptions
(from V8.40)
PQ-Basic measured values: 0 10 0
TDD - Total Demand Distortion
(from V8.40)
CFC arithmetic 0 40 0
Circuit-breaker monitoring ΣIx, I²t, 2P, tO, 0 10 0
(from V9.20) tC, pole
scatter,
discepancy
Disconnector monitoring (from tO, tC 0 5 0
V9.50)
Switching sequences function 0 5 0
PoW Point-on-wave switching (from PoW 0 425 0
V7.90)
Circuit-breaker 4X 4 3 0
Disconnector/Grounding 4X 4 3 0
switch
Multiplexing of protection 0 50 0
interface
SSR Slow-scan recorder (Mod.: SSR 1X 1 40 0
from V8.80, Non-Mod.: from
V9.40)
CR Continuous recorder (Mod.: CR 1X 1 25 0
from V9.20, Non-Mod.: from
V9.40)
PQ-10/12 cycle values for CR 0 25 0
continuous recorder (from
V9.20)
________________________________________________________________________________________________
8/9
SIPROTEC 5 - Configuration 05.06.2024 , 10:47:15 AM
________________________________________________________________________________________________
TR Trend recorder (Mod.: from TR 1X 1 25 0
V9.30, Non-Mod.: from V9.40)
PQ-Trend value for Trend TR 0 25 0
Recorder (from V9.30)
PQ-Flicker values for Trend TR 0 25 0
Recorder (from V9.30)
Transformer side 7UM85 2X 2 30 0
Cyber Security: Role-Based 0 25 0
Access Control (from V7.8)
Cyber Security: IEEE 802.1x 0 10 0
based network authentication
(from V8.3)
Total: 200