Datasheet Timer
Datasheet Timer
Wiring diagram
(with control signal)
Wiring
Wiring diagram
diagram (with control signal
For outline drawing see page 5 (with control signal) and pause signal)
Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT) 2 CO (DPDT) H
Rated current/Maximum peak current A 16/30 12/30 12/30
Rated voltage/
Maximum switching voltage V AC 250/400 250/400 250/400
Rated load AC1 VA 4000 3000 3000
Rated load AC15 (230 V AC) VA 750 750 750
Single phase motor rating (230 V AC) kW 0.5 0.5 0.5
Breaking capacity DC1: 30/110/220 V A 16/0.3/0.12 12/0.3/0.12 12/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Supply specification
Nominal voltage (UN) V AC (50/60 Hz) 24…240 24…240 24…240
V DC 24…240 24…240 24…240
Rated power AC/DC VA (50 Hz)/W < 1.5/< 2 < 2/< 2 < 2/< 2
Operating range V AC 16.8…265 16.8…265 16.8…265
V DC 16.8…265 16.8…265 16.8…265
Technical data
Specified time range (0.05…1)s, (0.5…10)s, (0.05…1)min, (0.5…10)min, (0.05…1)h, (0.5…10)h, (0.05…1)d, (0.5…10)d
Repeatability% ±1 ±1 ±1
Recovery time ms 200 200 200
Minimum control impulse ms 50 50 50
VI-2016, www.findernet.com
1
83 83 SERIES
SERIES Modular timers 16 A
2
83 SERIES 83
Modular timers 8 - 16 A SERIES
Wiring diagram
(without control signal)
Wiring diagram
(with control signal)
3
83 83 SERIES
SERIES Modular timers 16 A
Ordering information
Example: 83 series, modular timers, 1 CO (SPDT) - 16 A, supply rated at (24…240)V AC/DC.
8 3 . 0 1 . 0 . 2 4 0 . 0 0 0 0
Series Versions
0000 = Standard
Type
0 = Multi-function Supply voltage
(AI, DI, GI, SW, BE, CE, DE, WD) 240 = (24 … 240)V AC/DC
1 = On-delay (AI)
2 = Interval (DI) Supply version
4 = Off-delay with control signal (BE) 0 = AC (50/60 Hz)/DC
5 = Multi-function
(AE, GE, IT, FE, EEa, DEp, BEp, SHp) No. of poles
6 = Power off-delay (True off-delay) (BI) 1 = 1 CO (SPDT)
8 = Star-delta (SD) 2 = 2 CO (DPDT) for 83.02, 83.52 and 83.62
9 = Asymmetrical flasher (LI, LE, PI, PE) 2 = 2 NO (DPST-NO) for 83.82
Technical data
Insulation
Dielectric strength between input and output circuit V AC 4000
between open contacts V AC 1000
Insulation (1.2/50 µs) between input and output kV 6
EMC specifications
Type of test Reference standard 83.01/02/52/11/21/41/82/91 83.62
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV
air discharge EN 61000-4-2 8 kV 8 kV
Radio-frequency electromagnetic field (80 ÷ 1000 MHz) EN 61000-4-3 10 V/m 10 V/m
(1000 ÷ 2700 MHz) EN 61000-4-3 3 V/m 3 V/m
Fast transients (burst) (5-50 ns, 5 and 100 kHz) on Supply terminals EN 61000-4-4 7 kV 6 kV
H on control signal terminal (B1) EN 61000-4-4 7 kV 6 kV
Surges (1.2/50 µs) on Supply terminals common mode EN 61000-4-5 6 kV 6 kV
differential mode EN 61000-4-5 6 kV 4 kV
on control signal terminal (B1) common mode EN 61000-4-5 6 kV 6 kV
differential mode EN 61000-4-5 4 kV 4 kV
Radio-frequency common mode (0.15 ÷ 80 MHz) EN 61000-4-6 10 V 10 V
on Supply terminals (80 ÷ 230 MHz) EN 61000-4-6 10 V 10 V
Radiated and conducted emission EN 55022 class A class A
Other data
Current absorption on control signal (B1) < 1 mA
- max cable length (capacity of ≤ 10 nF/100 m) 150 m
- when applying a control signal to B1, which B1 is isolated from A1 and A2 by an opto-coupler, and can therefore be
is different from the supply voltage at A1/A2 operated at a voltage other than the supply voltage.
If using a control signal of between (24… 48)V DC and a supply voltage
of (24…240)V AC, ensure that the signal - is connected to A2 and the +
is applied to B1, and that L is applied to B1 and N to A2.
External potentiometer for 83.02/52 Use a 10 kΩ / ≥ 0.25 W linear potentiometer. Maximum cable length 10
m. When using an external potentiometer, the timer automatically use
its setting in place of the internal setting.
Consider the voltage potential at the potentiometer to be the same as
the timer supply voltage.
Power lost to the environment without contact current W 1.4
with rated current W 3.2
VI-2016, www.findernet.com
4
83 SERIES 83
Modular timers 16 A SERIES
Outline drawings
83.01 83.02/52
Screw terminal Screw terminal
83.11 83.21
Screw terminal Screw terminal
83.41 83.62
Screw terminal Screw terminal
H
83.82 83.91
Screw terminal Screw terminal
VI-2016, www.findernet.com
5
83 83 SERIES
SERIES Modular timers 16 A
Accessories
Sheet of marker tags, for types 83.01/11/21/41/62/82, plastic, 72 tags, 6 x 12 mm 060.72
060.72
087.02.2
Z1 Z2
Functions LED*
Supply NO output Contacts
voltage contact Open Closed
15 - 18 15 - 16
OFF Open
25 - 28 25 - 26
H ON Open
15 - 18 15 - 16
25 - 28 25 - 26
Open 15 - 18 15 - 16
ON
(Timing in Progress) 25 - 28 25 - 26
15 - 16 15 - 18
ON Closed
25 - 26 25 - 28
* The LED on type 83.62 is illuminated when supply voltage is supplied to timer.
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
*
* With DC supply, positive polarity has to be connected to B1 terminal (according to EN 60204-1).
VI-2016, www.findernet.com
** ** A voltage other than the supply voltage can be applied to the control signal (B1), example:
A1 - A2 = 230 V AC
B1 - A2 = 12 V DC
6
83 SERIES 83
Modular timers 16 A SERIES
Functions
Wiring diagram U = Supply voltage S = Signal switch = Output contact
Multi-function Type (AI) On-delay.
without control signal 83.01 Apply power to timer. Output contacts transfer after preset time has
83.02 elapsed. Reset occurs when power is removed.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
83.01
83.02 type
Contact mode selector Functions without control signal (example: AI) Functions with control signal (example: BE)
2 timed contacts
Both output contacts (15-18 and 25-28) Both output contacts (15-18 and 25-28)
follow the timing function follow the timing function
Both output contacts [15-18 and 25(21)-28(24)] Both output contacts [15-18 and 25(21)-28(24)]
stay permanently open stay permanently open
1 timed +
1 instantaneous contact
VI-2016, www.findernet.com
The output contact 15-18 follows the timing function The output contact 15-18 follows the timing function
The output contact 21-24 follows the power supply (U) The output contact 21-24 follows the control signal (S)
7
83 83 SERIES
SERIES Modular timers 16 A
Functions
Wiring diagram U = Supply voltage S = Signal switch P = Pause switch = Output contact
Multi-function Type (AE) On-delay with control signal.
with control signal 83.52 Power is permanently applied to the timer.
Closing the Signal Switch (S) initiates the preset delay, after which times the
AE output contacts transfer and remain so until the power is removed.
T
with control signal and pause (BEp) Off-delay with control signal and pause signal.
signal Power is permanently applied to the timer. The output contacts transfer
immediately on closure of the Signal Switch (S). Opening the signal switch
initiates the preset delay, after which the output contacts reset. Closure of the
pause switch (X1-X2) will immediately halt the timing process, but the elapsed
time will be retained. The current state of the output contacts will be maintained. On
opening of the pause switch, timing resumes from the retained value.
(DEp) Interval with control signal on and pause signal.
Power is permanently applied to the timer. On momentary or maintained closure
of Signal Switch (S), the output contacts transfer, and remain so for the duration
of the preset delay, after which they reset. Closure of the pause switch (X1-X2)
will immediately halt the timing process, but the elapsed time will be retained. The
current state of the output contacts will be maintained. On opening of the pause
switch, timing resumes from the retained value.
(SHp) “Shower” function (Off-delay with control signal and pause signal).
H Power is permanently applied to the timer. The output contacts transfer
immediately on closure of the Signal Switch (S). Opening the signal switch
initiates the preset delay, after which the output contacts reset. Closure of the
pause switch (X1-X2) will immediately halt the timing process, but the elapsed
time will be retained. During the pause, the output contacts 15-18 and 25-28 will
be open. On opening of the pause switch, timing resumes from the retained value
and the output contacts will take the previous condition.
83.52 type
Functions with control signal and pause signal
Contact mode selector Function SHp
(example: BEp)
2 timed contacts
Both output contacts (15-18 and 25-28) follow the timing function Both output contacts (15-18 and 25-28) follow the timing function
Both output contacts [15-18 and 25(21)-28(24)] stay permanently open Both output contacts [15-18 and 25(21)-28(24)] stay permanently open
1 timed +
1 instantaneous contact
VI-2016, www.findernet.com
The output contact 15-18 follows the timing function The output contact 15-18 follows the timing function. The output
The output contact 21-24 follows the control signal (S) contact 21-24 is always open, unless during the pause, when is closed
8
83 SERIES 83
Modular timers 16 A SERIES
Functions
Wiring diagram U = Supply voltage S = Signal switch = Output contact
Mono-function Type (AI) On-delay.
without control signal 83.11 Apply power to timer. Output contacts transfer after preset time has
elapsed. Reset occurs when power is removed.
83.82
with control signal (S) 83.41 (BE) Off-delay with control signal.
Power is permenently applied to the timer.
The output contacts transfer immediately on closure of the control
signal (S). Opening the control signal initiates the preset delay, after
which time the output contacts reset.
83.41
Asymmetrical recycler 83.91 (LI) Asymmetrical flasher (starting pulse on)- (Z1-Z2 open).
without control signal Apply power to timer. Output contacts transfer immediately and cycle
between ON and OFF for as long as power is applied. The ON and OFF
times are independently adjustable.
83.91 (PE) Asymmetrical flasher (starting pulse off) with control signal -
(Z1-Z2 linked).
Power is permenently applied to the timer.
Closing the control signal (S) initiates delay T1 after which the output
Z1-Z2 open: (LE) function contacts transfer and continue to cycle between OFF and ON, until the
Z1-Z2 linked: (PE) function control signal is opened.
VI-2016, www.findernet.com