10900 Session 2022
B4 - DC SYSTEMS & POWER ELECTRONICS
PS2 - DC FOR DISTRIBUTION SYSTEMS
Unidirectional step-up isolated DC-DC converter for MVDC electrical networks
Piotr DWORAKOWSKI*1, Pierre LE METAYER1,3, Drazen DUJIC2, Cyril BUTTAY1,3
1 SuperGrid Institute 2 École polytechnique 3
Univ Lyon, CNRS, INSA Lyon,
France fédérale de Lausanne Université Claude Bernard Lyon 1,
Switzerland Ecole Centrale de Lyon, Ampère,
UMR5005, 69621, Villeurbanne,
France
piotr.dworakowski@supergrid-institute.com
pierre.lemetayer@supergrid-institute.com
drazen.dujic@epfl.ch
cyril.buttay@insa-lyon.fr
SUMMARY
The medium voltage direct current (MVDC) technology is emerging in power distribution and collection
after the high voltage direct current (HVDC) has been demonstrated and exploited as the economically
viable solution for long-distance transmission of bulk power. This article focuses on the DC-DC
converter for MVDC electrical networks. A classification of DC-DC converters is proposed according
to three criteria: power flow directionality, galvanic isolation and modularity. A 20 MW ±10 kV radial
MVDC network is defined. Three unidirectional step-up, isolated and monolithic DC-DC converter
topologies (phase-shifted full bridge - PSFB, single active bridge - SAB and SAB with output inductor
- SAB-L) are discussed focusing on the output filter design (LC, C or CL). They all offer full power
controllability and fault blocking capability in case of faults in low voltage direct current (LVDC) and
MVDC systems. A simulation model of the case study MVDC network and the DC-DC converters is
presented. Simulation results are presented in steady state showing the typical voltage and current
waveforms of the selected DC-DC converters. Six fault scenarios are defined including pole-to-pole and
pole-to-ground faults. Simulation results are presented focusing on the fault current in the diode rectifier
bridge. The most severe fault case is the pole-to-pole fault at the DC-DC converter terminals. The
MVDC voltage polarity reversal occurs, forward biasing the rectifier bridge diodes. The pole-to-ground
fault results in low fault current due the high value grounding resistance. The PSFB is observed to offer
the best performance in steady state and fault conditions. The PSFB output filter inductor fulfils the role
of current ripple filtering and fault current limitation.
KEYWORDS
Direct current system, medium voltage, power electronics, indirect DC converter, boost converter.
INTRODUCTION
The medium voltage direct current (MVDC) technology is emerging in power distribution and collection
after the high voltage direct current (HVDC) has been demonstrated and exploited as the economically
viable solution for long-distance transmission of bulk power [1]. The MVDC technology is an attractive
solution for applications involving DC loads and sources where high energy efficiency and high power
flow controllability are required. It has been implemented in some pilot projects in China [2], [3] and
Europe [4], [5]. The researchers evaluate the interest of MVDC in solar [6] and wind [7] applications.
The benefits of MVDC technology can be analysed in terms of energy efficiency [8], power dispatch,
power capacity, power supply range, raw material consumption, CO2 emissions, resilience of
distribution network or ancillary services to the AC grid. However, the actual benefits of MVDC
technology must be evaluated case by case according to application requirements.
CIGRE has provided some foundations for the MVDC network development in the technical brochure
(TB) 793 [9] and the efforts continue in the ongoing working group (WG) C6/B4.37 “Medium Voltage
DC distribution systems”. CIRED has analysed DC networks in the TB with an intriguing title “DC
Networks on the distribution level – New trend or Vision?” [10]. CIGRE WG A3.40 is currently working
on the MVDC switching equipment. CIGRE WG B1.82 has started, addressing the MVDC cable system
requirements. This article focuses on the DC-DC converter - solid state transformer (SST) for MVDC
electrical networks.
In the future medium voltage electrical networks, the DC-DC converters may exist as standalone,
interfacing MVDC systems with low voltage direct current (LVDC) systems, with HVDC systems or
with another MVDC system (Fig. 1). The DC-DC converters may also exist as a part of power
electronics-based transformers, as currently studied by CIGRE WG B4.91. The main role of a standalone
DC-DC converter is to adapt the voltage between two DC systems. However, the DC-DC converter can
also provide power flow controllability and fault current blocking/limiting, and can be classified
according to power flow directionality, galvanic isolation and modularity. In this article a LVDC-
MVDC, unidirectional step-up, isolated and monolithic DC-DC converter is analysed. The converter
structure and operating principles are devised for an interface between a LVDC photovoltaic energy
source and the MVDC network.
LVDC DC MVDC MVDC DC MVDC MVDC DC HVDC
system DC system system DC system system DC system
a) b) c)
Fig. 1. DC-DC converter interfacing: LVDC with MVDC (a), two MVDC systems (b) and MVDC with
HVDC (c). In majority cases where voltage difference between two DC systems is high, galvanic
isolation by means of medium frequency transformer is needed.
This article is organised as follows. Section 1 proposes a classification of DC-DC converters for MVDC
networks. Section 2 presents a case study MVDC network. Section 3 discusses three DC-DC converter
topologies. Section 4 presents a simulation model of the case study network and DC-DC converters.
Section 5 illustrates the performance of the DC-DC converter thanks to simulations in steady state and
transient regimes.
SECTION 1: CLASSIFICATION OF DC-DC CONVERTERS FOR MVDC NETWORKS
A classification of DC-DC converters suitable in MVDC networks is proposed according to three
criteria: power flow directionality, galvanic isolation and modularity. The power flow directionality is
the one of the major functional differences between a DC-DC converter in DC systems and a transformer
in AC systems. The transformer is inherently bidirectional but the DC-DC converter can be designed to
be either unidirectional or bidirectional. The DC-DC converters can provide:
• bidirectional power flow (for example between two MVDC systems),
• unidirectional power flow stepping down (for example from HVDC to MVDC),
• unidirectional power flow stepping up (for example from LVDC to MVDC).
1
The general diagrams of isolated DC-DC converter topologies are presented in Fig. 2. The isolated
DC-DC converters are composed of DC-AC bridge, transformer and AC-DC bridge. In case of
unidirectional converter, the rectifier bridge can involve diodes only. Obviously, a bidirectional DC-DC
converter can be also used in an applications which require unidirectional power flow only. However,
the performance to cost ratio of the unidirectional converter is expected to be higher than its bidirectional
counterpart.
lower higher
voltage voltage
a)
b)
c)
Fig. 2. General diagrams of isolated DC-DC converter topologies: bidirectional (a), unidirectional step
down (b) and unidirectional step up (c).
The choice between isolated and non-isolated DC-DC converters for DC systems is likely to be similar
to the choice between transformers and autotransformers in AC systems. The galvanic isolation between
two DC systems allows the independent isolation coordination design and grounding choice between
lower and higher voltage circuits. If there was no galvanic isolation, then the DC system with lower
voltage would have to respect the overvoltage constraints of the DC system with higher voltage,
resulting in more bulky and costly equipment. The same approach applies to AC networks where the
autotransformer is used in low ratio applications only.
The choice of isolated DC-DC converters may be also driven by the power electronics design
constraints. The isolated DC-DC converters based on the conversion chain {DC-AC bridge / transformer
/ AC-DC bridge} allow to decouple the constraints in the similar way as it is done in transformers. The
transformer has a low number of turns of thick wire in the low voltage winding and a high number of
turns of thin wire in the high voltage winding. Finally, a comparable quantity of copper in both low
voltage and high voltage windings is used. In isolated DC-DC converters the low voltage bridge can be
optimised for high current and the high voltage bridge can be optimised for low current. In non-isolated
DC-DC converters the power electronic switches have to withstand both the voltage of the DC system
with higher voltage and the current of the DC system with lower voltage. This results in a design which
is far from the optimum and it is clearly visible when analysing a basic non-isolated converter like
buck/boost [11] presented in Fig. 3. Finally, it can be concluded that the DC-DC converter with high
stepping ratio is likely to be isolated. According to [12], high stepping ratio is equal or higher than 5.
The DC-DC converters for MVDC networks can be designed as monolithic or modular. In the
monolithic isolated DC-DC converter there is one DC-AC bridge, one transformer and one AC-DC
2
bridge which process the entire power. In the modular isolated DC-DC converter there are multiple
bridges and transformers, each processing a fraction of power. The input and output bridges can be
connected either in parallel or in series. For example, the input parallel and output series (IPOS)
connection allows to reach high step-up ratio. The modularity of DC-DC converters can be also achieved
thanks to the modularity of the bridges. The typical modular bridge structures are neutral point clamped
(NPC) [13] and modular multilevel converter (MMC) [14]. The DC-DC converters based on MMC are
suitable for HVDC applications [15] and may be also suitable for MVDC applications where the 2-level
and NPC are not cost effective (likely above 10/20 kV).
higher lower higher lower higher lower
voltage voltage voltage voltage voltage voltage
a) b) c)
Fig. 3. Basic non-isolated DC-DC converters: bidirectional (a), unidirectional step down - buck (b) and
unidirectional step up boost (c).
The classification of DC-DC converters suitable for MVDC networks is summarised in Fig. 4. It is noted
that the combinations between the classification according to power flow directionality, the
classification according to galvanic isolation and the classification according to modularity are possible.
For example, a bidirectional monolithic DC-DC converter can be either isolated or non-isolated.
DC-DC converters DC-DC converters DC-DC converters
bidirectional unidirectional isolated non-isolated monolithic modular
step-up step-down bridge topology I/O parallel/series
a) b) c)
Fig. 4. Classification of DC-DC converters for MVDC networks according to power flow directionality
(a), galvanic isolation (b) and modularity (c).
SECTION 2: CASE STUDY MVDC NETWORK
An MVDC collection network suitable for wind [7], [16] and photovoltaic (PV) [6], [17] power plants
is analysed. A radial MVDC network is proposed for the case study as presented in Fig. 5. A symmetrical
monopole topology is selected. The grounding on the DC side with high value resistance allows to
minimise the DC fault current. The MVDC network is realized with underground cables. The interface
with the AC network is ensured by an AC-DC station with a voltage source converter (VSC) and a
transformer. DC-DC converters are considered to interface with the LVDC photovoltaic sources. The
ratings of the analysed MVDC network, representative of a large-scale PV power plant, are presented
in Table 1.
AC
AC
MVDC network
network
DC
DC DC DC
DC DC DC
LVDC sources
Fig. 5. Single line diagram of the case study MVDC network. Switchgear is not represented.
3
Table 1. Ratings of the case study MVDC network.
AC-DC MVDC MVDC DC-DC LVDC
power voltage line current power voltage
20 MW ±10 kV (20 kV) 1 kA 250 kW 1.2 kV
SECTION 3: MVDC DC-DC CONVERTER
The isolated DC-DC converter topologies suitable in high power applications include series resonant
converter (SRC) [18], LLC DC-DC resonant converter [19], phase-shifted full bridge (PSFB) [20],
single active bridge (SAB) [21] and dual active bridge (DAB) [22]. The isolated DC-DC converters
often involve a transformer operating at frequency higher than 50/60 Hz (for example 10 kHz), offering
size and weight reduction compared to a transformer operating at 50/60 Hz [23].
In this article three unidirectional isolated DC-DC converter topologies suitable for MVDC networks
are analysed: PSFB, SAB and a variant of SAB. The PSFB is composed of LV inverter bridge, medium
frequency transformer (MFT), MV rectifier bridge and output LoCo filter as presented in Fig. 6. The
SAB topology is very similar, but the output filter involves the capacitor Co filter only. A variant of the
SAB with output filter CoLext is considered as well (SAB-L). The output filter influences the DC-DC
converter response under MVDC network fault conditions. The resonant topologies (SRC and LLC) and
the DAB are not analysed in this article, but they are expected to have similar responses under MVDC
faults to the SAB. All analysed topologies are expected to offer similar cost, size and efficiency but their
response to MVDC faults is different as presented in the following sections.
LVDC LV inverter MFT MV rectifier Output filter MVDC
Lo/2
Q1 Q3
2Co
Vin Cin Lf Vo
1:m
2Co
Q2 Q4
Lo/2
Fig. 6. Circuit diagram of the unidirectional isolated monolithic DC-DC converter based on phase-
shifted full bridge topology. 1.7 kV SiC MOSFETs are used in LV inverter and 1.7 kV SiC Schottky
diodes with RC snubbers are used in MV rectifier.
The PSFB converter design was presented by the authors in [24] and the SAB design was presented in
[25]. The main design parameters are presented in Table 2. In the PSFB the LV inverter bridge generates
a square waveform voltage while controlling the phase shift φ between two legs: the leading leg
(switches Q1, Q2) and the lagging leg (switches Q3, Q4). The resulting duty cycle D is defined by
φ
𝐷 =1− (1)
180°
In this paper, the SAB LV inverter bridge is controlled with phase shift as in the PSFB.
Table 2. Design parameters of the selected DC-DC converters.
Input MFT MFT turns MFT leakage Filter Filter
capacitor frequency ratio inductance inductor capacitor
PSFB Lo = 8 mH
SAB Cin = 250 µF f = 20 kHz m = 20.125 Lf = 5 µH NA Co = 100 pF
SAB-L Lext = 8 mH
4
The control of the MVDC network is based on the master-slave principle where the DC-AC converter
controls the MVDC voltage and the DC-DC converters inject the maximum power generated by the
LVDC sources. In practice, the DC-DC converter regulates the input LVDC voltage. In case of fault in
the MVDC network, the DC-DC converter blocks the LV bridge. This effectively prevents any steady
state fault current contribution from the LVDC source to the MVDC network. A fault in the LVDC
source does not impact the MVDC network in steady state, thanks to the diode rectifier and galvanic
isolation.
SECTION 4: SIMULATION MODEL
The electromagnetic transient simulation models were developed to support the analysis of the DC-DC
converter in the case study MVDC network as presented in Fig. 7. The model is suitable for the analysis
of DC-DC converter under faults in the MVDC network.
Source Unidirectional isolated DC-DC converter 5km cable model AC-DC converter
Lo/2 Fg2 Lext/2 Lcable Rcable LDC
Fg3
Fg1 CAC-DC
2Co Ccable
VLVDC VMVDC
Rn
Fp1 Fp2 Fp3
Fig. 7. Simulation model of the MVDC network with: DC-DC converter (detailed switched model),
cable (π model) and AC-DC converter (average model). Fault cases defined in Table 4 are visualized.
The detailed switched model [26] of the DC-DC converter was used. The MV diode bridge is modelled
with an equivalent diode with a forward voltage drop of 16.8 V and an on-state resistance of 2.57 mΩ.
This values correspond to the series connection of silicon carbide (SiC) Schottky diodes [27]. The LVDC
source is modelled with a current source controlled to deliver the nominal power. The 5 km cable section
is represented by a π model (Table 3). The AC-DC converter is represented by the average model [26]
which was detailed in [28] (Table 3).
Table 3. Design parameters of the MVDC cable and AC-DC converter.
Cable AC-DC converter
Rcable 8.8 mΩ/km x 5 km Rn 1 kΩ
Lcable 134 µH/km x 5 km LDC 500 µH
Ccable 1.81 µF/km x 5 km CAC-DC 1.8 mF
The fault cases are summarized in Table 4. The short circuit is modelled by a simple switch with internal
resistance of 10 mΩ.
Table 4. Definition of fault cases.
Name Description
Fp1 Pole-to-pole fault in the diode rectifier
Fg1 Pole-to-ground fault in the diode rectifier
Fp2 Pole-to-pole fault in the output filter
Fg2 Pole-to-ground fault in the output filter
Fp3 Pole-to-pole fault at the DC-DC converter terminals
Fg3 Pole-to-ground fault at the DC-DC converter terminals
SECTION 5: SIMULATION RESULTS
The steady state waveforms of three selected DC-DC topologies are presented in Fig. 8, for the
maximum power and nominal output voltage. The input is regulated to the nominal LVDC system
voltage. It is seen that, with the analysed design, the SAB and SAB-L present higher current ripple and,
since the same output capacitor is kept for all cases, higher output voltage ripple. This higher current
ripple results in higher repeated peak current of semiconductor switches.
5
a)
b)
c)
Fig. 8 : Steady state waveforms of the DC-DC converters: PSFB (a), SAB (b) and SAB-L (c).
Simulation results for the fault cases defined in Table 4 are presented in Fig. 9. The fault occurs at 0.04
s. The LV inverter bridge is blocked 5 µs after the fault instant considering that the protection triggers
due to overcurrent or overvoltage. In order to discard the influence of the AC-DC converter control on
the analysis of DC-DC converter, its current reference is brought down to 0 A after 5 µs. The focus of
this section is to study the influence of the output filter configuration on the diode rectifier bridge current
during faults.
6
Fp1 Fg1
Fp2 Fg2
Fp3 Fg3
Fig. 9. Current in diode and output voltage VMVDC of the DC-DC converter for fault cases defined in
Table 4. The rated current of the diode is 25 A.
One can observe that the most severe fault case for the diode bridge is the pole-to-pole fault at the
DC-DC converter terminals (Fp3). In the SAB the diode current peaks above 1000 A (compared to the
rated current 25 A) because there is no inductor to limit the current. Such high current, even for a short
time, would require a significant oversizing of the diode bridge to prevent destruction. Fig. 10 shows a
zoom at the time right after the fault instant. One can observe that the high current in the SAB is the
result of voltage oscillations due to the discharge of cable capacitance. The voltage polarity is reversed,
forward biasing the diodes. In the SAB-L the current does not reach high values as the inductor Lext
limits the capacitor discharge and there is no voltage polarity reverse. In the PSFB the oscillations are
still present but they do not result in important current in the diodes thanks to the filter inductor Lo.
7
Fig. 10. Zooms at the fault instant for the fault case Fp3.
The same filter capacitor Co was used for each DC-DC topology. For SAB and SAB-L this results in
larger output voltage ripple than in the PSFB as there is no DC inductor inside the converter to reduce
the current ripple. In order to have a similar voltage ripple in all topologies, the output capacitor would
have to be increased for the SAB and SAB-L. In case of fault, this would result in even higher diode
current due to capacitor discharge. The PSFB filter inductor fulfils the role of current ripple filtering and
fault current limitation.
It can be observed that the pole-to-pole faults in the output filter, in the diode rectifier or at the DC-DC
converter terminals, do not result in high current in diodes. In Fp1 case it is seen that the output voltage
polarity is reversed. However, this does not result in high current in diodes because the fault is localised
between the filter capacitor (energy source) and the rectifier. The fault current simply does not flow
through the diodes.
The pole-to-ground faults have no impact on the diode bridge but it can be observed that output voltage
oscillations are triggered. The SAB-L presents the most severe oscillations. However, the output
capacitor voltage never generates the voltage polarity reversal, so the diodes are never forward biased.
CONCLUSION
The DC-DC converter for MVDC electrical networks was introduced. The classification of DC-DC
converters was proposed according to three criteria: power flow directionality, galvanic isolation and
modularity. The case study MVDC network was defined. Three unidirectional step-up, isolated and
monolithic DC-DC converter topologies were discussed focusing on the output filter design (LC, C or
CL). They all offer full power controllability and fault blocking capability in case of faults in LVDC
and MVDC systems. The simulation model of the case study MVDC network and the DC-DC converters
was presented. The simulation results were presented in steady state showing the typical voltage and
current waveforms of the selected DC-DC converters. Six fault scenarios were defined including pole-
to-pole and pole-to-ground faults within the DC-DC converter. The simulation results were presented
focusing on the fault current in the diode rectifier bridge. The most severe fault case was found to be the
pole-to-pole fault at the DC-DC converter terminals. The MVDC voltage polarity reversal occurs,
forward biasing the rectifier bridge diodes. The pole-to-ground faults result in low fault current due the
high value grounding resistance. The PSFB was observed to offer the best performance in steady state
and fault conditions. The PSFB output filter inductor fulfils the role of current ripple filtering and fault
current limitation. The assessment of DC-DC converters should be completed including the response
under the lightning and switching impulse minding the output filter (LC, C or CL). The main challenges
related to the development of MVDC DC-DC converter include: medium voltage and medium frequency
transformer and rectifier, dielectric design and integration for compact size, and SiC inverter design for
high efficiency.
8
BIBLIOGRAPHY
[1] B. Grainger and R. W. De Doncker, Medium Voltage DC System Architectures. IET Digital Library,
2021.
[2] M. M. Eissa, “Medium-Voltage Direct Current Concept, Modeling, Operation, Control, Protection,
and Management—An Extensive Article Review,” in Medium Voltage Direct Current Grid, M. M.
Eissa, Ed. Academic Press, 2019, pp. 1–41.
[3] G. Bathurst, G. Hwang, and L. Tejwani, “MVDC - The New Technology for Distribution
Networks,” in 11th IET International Conference on AC and DC Power Transmission, 2015, pp.
1–5.
[4] J. Yu, K. Smith, M. Urizarbarrena, N. MacLeod, R. Bryans, and A. Moon, “Initial designs for the
ANGLE DC project; converting existing AC cable and overhead line into DC operation,” in 13th
IET International Conference on AC and DC Power Transmission (ACDC 2017), 2017, pp. 1–6.
[5] P. Maibach, C. Haderli, A. Schlachter, and J. Berry, “The Flexible Power Link of Western Power
Distribution: A Case Study,” in CIGRE Session 2020, Paris, 2020.
[6] H. A. B. Siddique, S. M. Ali, and R. W. De Doncker, “DC collector grid configurations for large
photovoltaic parks,” in 2013 15th European Conference on Power Electronics and Applications
(EPE), 2013, pp. 1–10.
[7] M. De Prada Gil, J. L. Domínguez-García, F. Díaz-González, M. Aragüés-Peñalba, and O. Gomis-
Bellmunt, “Feasibility analysis of offshore wind power plants with DC collection grid,” Renewable
Energy, vol. 78, pp. 467–477, Jun. 2015.
[8] P. Le Métayer et al., “Break-even distance for MVDC electricity networks according to power loss
criteria,” in 2021 23rd European Conference on Power Electronics and Applications (EPE’21
ECCE Europe), 2021, pp. 1–9.
[9] CIGRE WG C6.31, “Medium voltage direct current (MVDC) grid feasibility study,” Feb. 2020.
[10] CIRED WG 2019-1, “DC Networks on the distribution level – New trend or Vision?,” Jul. 2021.
[11] K. Tytelmaier, O. Husev, O. Veligorskyi, and R. Yershov, “A review of non-isolated bidirectional
dc-dc converters for energy storage systems,” in 2016 II International Young Scientists Forum on
Applied Physics and Engineering (YSF), 2016, pp. 22–28.
[12] C. Barker, C. Davidson, D. Trainer, and R. Whitehouse, “Requirements of DC-DC Converters to
facilitate large DC Grids,” in CIGRE Session 2012, Paris, 2012.
[13] A. Nabae, I. Takahashi, and H. Akagi, “A New Neutral-Point-Clamped PWM Inverter,” IEEE
Transactions on Industry Applications, vol. IA-17, no. 5, pp. 518–523, Sep. 1981.
[14] A. Lesnicar and R. Marquardt, “An innovative modular multilevel converter topology suitable for
a wide power range,” in 2003 IEEE Bologna Power Tech Conference Proceedings, 2003, vol. 3, p.
6 pp. Vol.3-.
[15] D. Jovcic et al., “DC-DC converters in HVDC grids and for connections to HVDC systems: CIGRE
technical brochure 827,” Mar. 2021.
[16] P. le Métayer, P. Dworakowski, and J. Maneiro, “Unidirectional thyristor-based DC-DC converter
for HVDC connection of offshore wind farms,” in 2020 22nd European Conference on Power
Electronics and Applications (EPE’20 ECCE Europe), 2020, p. P.1-P.9.
[17] A. Cabrera-Tobar, E. Bullich-Massagué, M. Aragüés-Peñalba, and O. Gomis-Bellmunt,
“Topologies for large scale photovoltaic power plants,” Renewable and Sustainable Energy
Reviews, vol. 59, pp. 309–319, Jun. 2016.
[18] F. C. Schwarz and J. B. Klaassens, “A Controllable 45-kW Current Source for DC Machines,” IEEE
Transactions on Industry Applications, vol. IA-15, no. 4, pp. 437–444, Jul. 1979.
[19] Bo Yang, F. C. Lee, A. J. Zhang, and Guisong Huang, “LLC resonant converter for front end
DC/DC conversion,” in APEC. Seventeenth Annual IEEE Applied Power Electronics Conference
and Exposition (Cat. No.02CH37335), 2002, vol. 2, pp. 1108–1112 vol.2.
[20] L. H. Mweene, C. A. Wright, and M. F. Schlecht, “A 1 kW 500 kHz front-end converter for a
distributed power supply system,” IEEE Transactions on Power Electronics, vol. 6, no. 3, pp. 398–
407, Jul. 1991.
[21] J. Jacobs, M. Thommes, and R. De Doncker, “A transformer comparison for three-phase single
active bridges,” in 2005 European Conference on Power Electronics and Applications, 2005, p. 10
pp.-P.10.
9
[22] R. W. A. A. De Doncker, D. M. Divan, and M. H. Kheraluwala, “A three-phase soft-switched high-
power-density DC/DC converter for high-power applications,” IEEE Transactions on Industry
Applications, vol. 27, no. 1, pp. 63–73, Jan. 1991.
[23] P. Dworakowski, “Modelling and analysis of medium frequency transformers for power
converters,” PhD thesis, Gdansk University of Technology, 2020.
[24] P. Le Métayer, Q. Loeuillet, F. Wallart, C. Buttay, D. Dujic, and P. Dworakowski, “Unidirectional
Isolated DC-DC converter for Photovoltaic MVdc Power Collection Networks,” submitted for
publication.
[25] K. Park and Z. Chen, “Analysis and design of a parallel-connected single active bridge DC-DC
converter for high-power wind farm applications,” in 2013 15th European Conference on Power
Electronics and Applications (EPE), 2013, pp. 1–10.
[26] CIGRE WG B4.57, “Guide for the Development of Models for HVDC Converters in a HVDC
Grid,” 2014.
[27] P. Le Métayer, D. Dujic, C. Buttay, and P. Dworakowski, “Medium Voltage Diode Rectifier Design
for High Step-Up DC-DC Converter,” accepted for publication at EPE’22.
[28] P. Dworakowski, J. Paez, W. Grieshaber, A. Bertinato, and E. Lamard, “Protection of radial MVDC
electric network based on DC circuit breaker and DC fuses,” submitted for publication.
10