Per Phase Bus Strip De rating Factor
K1                                      1 No of Bus Bar per Phase 1
Bus bar Insulating Material De K2                                    1.2 PVC Sleeving
Bus bar Position De rating
Factor                         K3                                      1 Edge-mounted bars
Bus bar Installation Media De
rating Factor                  K4                                      1 Calm indoor atmosphere
Bus bar Artificial Ventilation                                               with artificial ventilation
De rating Factor               K5                                      1
Enclosure & Ventilation De
rating Factor                          K6                        0.95 Indoors ( Panel is well Ventilated)
Proxy Effect De rating Factor K7                                 0.82 min factor
 Altitude of Bus Bar
installation De rating Factor K8                                       1 Altitude > 1000m
Total De rating Factor                                         0.9348
Desire Current Rating of Bus
bar based on Current Density                                   400
1.2 Sq.MM
Current Rating of Bus bar
after De rating Factor                                         373.92
Bus bar Cross Section Area as per Short Circuit= Isc X√ ((K/( θtx100)x(1+ α20xθ) xt
Faultlevel A                                          50000
Material Constant                                      1.166
Temp Rise of Busbnar Theta1                              135 DegC
Constant                                                 100
Constant                                                   1
Alfa20 (Temp Coeff at 20DegC)                       0.00403
Operating Temp of Busbar                                  50 DegC
Duration (Sec.)                                            1 Seconds
Bus bar Cross Section Area as per       509.347621963625     Sq.mm
Short Circuit                                                                                     10.18695   50
As per the busbar 40 X 8 the                  602             Amps
Current is
 Bus bar Current Details:
 Rated Voltage                               415V
 Desire Maximum Current Rating                400
 of Bus bar (I2)
 Fault Current (Isc)                         50KA
 Fault Duration (t)                          1 Sec
 Bus bar Temperature details:
 Operating Temperature of Bus                50°C
 bar (θ)
 Final Temperature of Bus bar               185°C
 during Fault(θ1)=.
 Temperature rise of Bus Bar Bar            135°C
 during Fault (θt=θ1-θ)
 Ambient Temperature (θn)                    50°C
 Maximum Bus Bar Temperature                 85°C
 Rise
 Altitude of Panel Installation on       1000 Meter
 Site
 Bus bar Details:
 Bus bar Material                           Copper
 Current Density of Bus Bar               1.2 Sq,MM
 Material
 Temperature Co efficient of               0.00403
 Material Resistance at 20°c(α20)
 Material Constant(K)                        1.166
                       Bus bar Size Calculation
Current Rating of Bus bar after De rating Factor (I1)=   373.92
                I2 X De rating Factor
Bus bar Cross Section Area as per Short Circuit          509.35
       Final Calculated Bus Bar Cross Section Area        510
              Actual Selected Bus bar size is            50 X 10
Panel        1008000000 2560000   0.254%
        40          30       40      30    40   30   40   250