GUARANTEED TECHNICAL PARTICULARS FOR

30KV 10KA CLASS-3 LIGHTNING ARRESTERS

1. Name of the manufacture : LAMCO INDUSTRIES PRIVATE LIMITED.,


B-39, I.E. Sanathnagar, HYDERABAD-018(T.S)
INDIA.

2. Type : Medium Duty Station Class Metal-Oxide


Gapless Lightning Arrester "MORESTER"
type 'SL'.

3. Reference Standard : IEC 99-4 of 2006 / IS-3070 (part-3) 1993.

4. Model (Drg. No.) : 2400300

5. No. of Units : One


6. Rated Voltage : 30 KV

7. Nominal discharge current : 10 KA

8. Reference current : 3 mA

9. Reference voltage : Greater than the rated


Arrester voltage at
reference current

10. Leakage Current at COV : Less than 0.8 mA

11. Max. continuous operating voltage : 24 KVrms

12. Maximum residual voltage for discharge


current of (8/20 micro sec. wave)
i) 5000 Amps : 83 KVpeak
ii) 10000 Amps : 88 KVpeak
iii) 20000 Amps : 95 KVpeak

13. Max. steep front residual voltage at


10KA with one micro sec. rise time : 99 KVpeak

14. Max. switching impulse residual voltage


with 40/80 us wave at 1000 Amps : 73 KVpeak

15. Energy dissipation capability : 9 KJ/KV


(Cumulative of 3 sequential shots)

16. High current 4/10 u sec. test value : 100 KApeak

17. Long duration current tests


i) Current peak : As per discharge Class-3
of IEC 99-4 (Table-4).
ii) Virtual duration : 2400 us
Continued on page...2
(2400300) :: 2 ::

G.T.P 30KV 10KA L.A's (continued..2)

18. Pressure relief class : Class 'A'

19. Short circuit current capability : 40 KArms

20. Partial discharge at 1.05 times MCOV : Less than 10 pC

21. Temporary over voltage withstand


value for
a) 1.0 Second : 34.5 KVrms
b) 10.0 Second : 33.0 KVrms
c) 100.0 Second : 31.5 KVrms

22. Insulation withstand strength of


Arrester housing
i) One minute 50 Hz dry & wet : 110 KVrms
ii) Lightning impulse voltage withstand: 175 KVpeak

23. Nominal Creepage distance : 900 mm

24. Weight of complete unit : 22 ±10% Kgs

25. Height of the Arrester : Refer Drg No. 2400300

26. Minimum recommended centre to centre


spacing between Arresters : 555 mm

27. Clearance required from ground


equipment at various heights of
Arrester unit : 440 mm

28. Earthing arrangement provided for : Ground Terminal Bracket


earthing side of Arrester (Drg. 6220151-A) provided
for connecting earth strip

29. Mounting flange dimensional details : End castings,3 holes(11mmØ)


120 deg apart at 200 mm PCD.

for LAMCO INDUSTRIES PRIVATE LIMITED.

(P.G RAJU)
ASST.MANAGER (D&D)