MECOL INDUSTRIES
S. No. 691/A, H. No. 1B, Bibvewadi, Pune Satara Road, PUNE : 411009
                                                                        TEL : 020 – 24482025
                             Guaranteed Technical Particular / Technical Data Sheet for 10 kA Class 1 Indoor Surge Arrester.
Sr.   Description                                             Unit                                        Specifications
No.
1     Rated Voltage of the Arrester                           kV
                                                                      3.0    6.0    7.2     9     12     15     18     21     24      27     30      33      36
                                                              rms
2     System Voltage                                          kV
                                                                      3.3    6.6    6.6    11     11     11     22     22     22      33     33      33      33
                                                              rms
3     Maximum System Voltage                                  kV
                                                                      3.6    7.2    7.2    12     12     12     24     24     24      36     36      36      36
                                                              rms
4     Maximum Continuous Operating Voltage (MCOV)             kV
                                                                      2.55   5.1    6.1    7.65   10.2   12.8   15.3   17.9   20.4   23.0   25.5    28.0    30.6
                                                              rms
5     Housing Material                                        ---                                          Silicone Rubber
6     Rated Frequency                                         Hz                                                50 / 60
7     Nominal Discharge Current (NDC)                         kAp     10     10     10     10     10     10      10     10    10     10      10      10      10
8     Long Duration Class                                     ---     1      1      1      1      1      1        1     1     1      1       1       1       1
9     Insulation withstand of an housing
            i) 1 minute Power Frequency Voltage               kVrms
                                                                      15     21     21     27     27     50     50     50     50      70     70     70       70
            ii) Standard lightning Impulse Voltage (1.2/50µ   kVp
                                                                      45     60     75     75     75     125    125    125    125    170    170     170     170
            sec.)
10    Steep Current Impulse Residual Voltage at NDC           kVp     11.2   22.6   28.2   34     45.3   54.0   65.5   75.6   90     97.4   105.0   115.8   126
11    Lightning Current Impulse Residual Voltage at           kVp
            i) 0.5 NDC                                                 9.3   18.6   23.2   28.0   37.3   44.6   54.0   62.4   74.0   77.4   88.0    96.9    106.0
            ii) 1.0 NDC                                               10.0   20.0   25.0   30.0   40.0   48.0   58.0   67.2   79.0   86.4   96.0    105.6   115.0
            iii) 2.0 NDC                                              11.3   22.6   28.2   34.0   45.3   54.3   65.5   76.0   90.0   97.7   105.0   115.9   126.0
12    Switching Current Impulse Residual Voltage at           kVp
      i) 125 Ap                                                       7.3    14.7   18.3   22     29.3   25.2   43      43    58.0   62.6   66.0    73.0    79.6
      ii) 500 Ap                                                      8.0    16.0   20.0   24     32.0   38.4   46     57.4   64.0   69.1   73.0    80.7    88.0
13    High Current Impulse withstand capability               kAp     100    100    100    100    100    100    100    100    100    100    100     100     100
14    Energy Handling Capability                              kJ/kV    2      2      2      2      2      2      2      2      2      2      2       2       2
15    Voltage Vs Time characteristic (TOV capability) for     kVrms
      i) 0.1 second                                                   3.7    7.3    8.8    11.0   14.7   18.4   22.0   25.8   29.4   33.1   36.8    36.8    44.2
      ii) 1.0 second                                                  3.6    7.1    8.5    10.6   14.1   17.7   21.2   24.7   28.2   31.8   35.3    35.3    42.4
      iii) 10 seconds                                                 3.4    6.7    8.1    10.1   13.5   16.9   20.2   23.7   27.0   30.4   33.7    33.7    40.4
      iv) 100 seconds.                                                3.2    6.5    7.8    9.7    12.9   16.2   19.4   22.6   25.8   29.0   32.3    32.3    38.7
16    Reference current                                       mAp     1.5    1.5    1.5    1.5    1.5    1.5    1.5    1.5    1.5     1.5    1.5    1.5      1.5
17    Reference Voltage at reference current (≥)              kVrms    3      6     7.2     9      12     15     18     21     24     27     30      33      36
18    Internal Partial Discharge (≤)                          pC      10     10     10      10     10     10     10     10     10     10     10      10      10