0% found this document useful (0 votes)
230 views1 page

SCADA Signal List - Mansehra

This letter from the Chief Engineer (Protection & Control) of the National Transmission and Despatch Company to Chint Electrical Co. discusses the SCADA I/O signal list submitted for the 220/132kV substation in Mansehra. It notes some deficiencies in the list, including that open and close commands for different voltage CBs and transformer tap changers should be separate. It also states that power factor measurements for transmission lines and protection signals for the 132kV bus coupler are missing. Chint is asked to incorporate the corrections and resubmit the signal list to NPCC for approval, copying NTDC.

Uploaded by

KASHIF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
230 views1 page

SCADA Signal List - Mansehra

This letter from the Chief Engineer (Protection & Control) of the National Transmission and Despatch Company to Chint Electrical Co. discusses the SCADA I/O signal list submitted for the 220/132kV substation in Mansehra. It notes some deficiencies in the list, including that open and close commands for different voltage CBs and transformer tap changers should be separate. It also states that power factor measurements for transmission lines and protection signals for the 132kV bus coupler are missing. Chint is asked to incorporate the corrections and resubmit the signal list to NPCC for approval, copying NTDC.

Uploaded by

KASHIF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

NATIONAL TRANSMISSION AND DESPATCH COMPANY

Chief Engineer (Protection & Control) NTDC

No. CE/P&C/NTDC/MN/Mansehra/________ DATED:_______________

M/s Chint Electrical Co.,


GG-315, Street # 12, Phase-4, DHA, Lahore

Sub: CONTRACT NO. : ADB-67R-2014 – DESIGN, MANUFACTURING, SUPPLY,


TESTING & COMMISSIONING OF 220KV AIS SUBSTATION AT MANSEHRA.
SCADA I/O SIGNAL LIST FOR 220/132KV SUBSTATION MANSEHRA.
Ref: M/s Chint Office letter no. CHINT/ADB-67R/2019/11/18-E03 dated: 18-11-2019

With reference to subject matter, this office has reviewed the SCADA signal list submitted by
your office vide above reffered letter. This office has followings observations and comments:

1. Open and close command for 220kV CBs shall be separate/ independent.
2. Open and close command for 132kV CBs shall be separate/ independent.
3. Tap changer Raise and Lower command shall be separate/ independent for each
Transformer.
4. Followings signals are missing:
a. Power factor measurement for all Transmission lines (220kV & 132kV).
b. 132kV Bus Coupler protection (overcurrent & earth fault) operated.

After incorporating the above difficiencies/ discripencies, same shall be submitted to the office
of G.M. (S.O) NPCC, NTDC Islamabad, for approval, with copy to this office along with
attachements for reference/ record.

(Engr. Farooq Rashid)


Addl. C.E.(Protection & Control), North, NTDC
Copy to:
1. G.M. (SO) NPCC, NTDC, Islamabad
2. C.E. (Telecom) NTDC, 625- WAPDA House, Lahore.
3. C.E. (MP&M) NTDC, Shaheen Complex, Lahore
4. C.E. (Substation Design) NTDC, WAPDA House Lahore
- M/File - M/ File (N) - R/ File

_____________________________________________________________________________________________
130-WAPDA House, Lahore, Pakistan. Tel: +92-42-99202655 Fax: +92-42-99202184 Email: ce.pac@ntdc.com.pk

You might also like