NATIONAL TRANSMISSION AND DESPATCH COMPANY
Chief Engineer (Protection & Control) NTDC
No. CE/P&C/NTDC/MN/Mansehra/________ DATED:_______________
M/s Chint Electrical Co.,
GG-315, Street # 12, Phase-4, DHA, Lahore
Sub: CONTRACT NO. : ADB-67R-2014 – DESIGN, MANUFACTURING, SUPPLY,
TESTING & COMMISSIONING OF 220KV AIS SUBSTATION AT MANSEHRA.
SCADA I/O SIGNAL LIST FOR 220/132KV SUBSTATION MANSEHRA.
Ref: M/s Chint Office letter no. CHINT/ADB-67R/2019/11/18-E03 dated: 18-11-2019
With reference to subject matter, this office has reviewed the SCADA signal list submitted by
your office vide above reffered letter. This office has followings observations and comments:
1. Open and close command for 220kV CBs shall be separate/ independent.
2. Open and close command for 132kV CBs shall be separate/ independent.
3. Tap changer Raise and Lower command shall be separate/ independent for each
Transformer.
4. Followings signals are missing:
a. Power factor measurement for all Transmission lines (220kV & 132kV).
b. 132kV Bus Coupler protection (overcurrent & earth fault) operated.
After incorporating the above difficiencies/ discripencies, same shall be submitted to the office
of G.M. (S.O) NPCC, NTDC Islamabad, for approval, with copy to this office along with
attachements for reference/ record.
(Engr. Farooq Rashid)
Addl. C.E.(Protection & Control), North, NTDC
Copy to:
1. G.M. (SO) NPCC, NTDC, Islamabad
2. C.E. (Telecom) NTDC, 625- WAPDA House, Lahore.
3. C.E. (MP&M) NTDC, Shaheen Complex, Lahore
4. C.E. (Substation Design) NTDC, WAPDA House Lahore
- M/File - M/ File (N) - R/ File
_____________________________________________________________________________________________
130-WAPDA House, Lahore, Pakistan. Tel: +92-42-99202655 Fax: +92-42-99202184 Email: ce.pac@ntdc.com.pk