Overcurrent Relay Settings Guide

This document summarizes overcurrent relay settings for two relays: an Ashida VRNFS relay and a Square D SEPAM S40 relay. It lists the manufacturer, model, and ratings for each relay, along with pickup, time dial, and delay settings for the long-time inverse, instantaneous, and extremely inverse time overcurrent elements for phases and ground.

Uploaded by

Sathiya Seelan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
199 views1 page

Overcurrent Relay Settings Guide

This document summarizes overcurrent relay settings for two relays: an Ashida VRNFS relay and a Square D SEPAM S40 relay. It lists the manufacturer, model, and ratings for each relay, along with pickup, time dial, and delay settings for the long-time inverse, instantaneous, and extremely inverse time overcurrent elements for phases and ground.

Uploaded by

Sathiya Seelan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project: ETAP Page: 1

Location: 12.6.5C Date: 03-13-2017


Contract: Revision: Base
Engineer: Overcurrent Relay Settings
Filename: Protection

OCR: Ashida VRNFS


MFR: Ashida Tag #: CT Base kV If (kA)
Model: VRNFS Phase: 100/5

OC Level: OC1
Range Setting
Phase TOC IEC - Long Time Inverse (TMS)
Pickup (Tap) 0.1 - 2.4 xCT Sec 1.380
Time Dial 0.063
Phase INST Pickup 0.1 - 24 xCT Sec 24.000
Time Delay 0.05 - 300 Sec 0.250

Neutral TOC Extremely Inverse Time


Pickup (Tap) 0.1 - 1 xCT Sec 1.000
Time Dial 0.100
Neutral ST Definite Time
Pickup 0.1 - 15 xCT Sec 5.000
Time Dial 0.41

OCR: SEPAM S40


MFR: Square D Tag #: CT Base kV If (kA)
Model: Sepam Series 40 Phase: 100/5

GND: 100/5

OC Level: OC1
Range Setting
Phase TOC IEC - Long Time Inverse (TMS)
Pickup (Tap) 0.1 - 2.4 xCT Sec 1.450
Time Dial 0.069
Phase INST Pickup 0.1 - 24 xCT Sec 35.000
Time Delay 0.05 - 300 Sec 0.050

Neutral TOC Extremely Inverse Time


Pickup (Tap) 0.1 - 1 xCT Sec 1.000
Time Dial 0.269
Neutral INST Pickup 0.1 - 15 xCT Sec 10.000
Time Delay 0.05 - 300 Sec 0.350