SPECIFICATION ‘STANDARD SPECIFICATION No.
ENGINEERS. FOR
cea NO NUNED Reread! 6-51-0043 Rev. 5
GROUNDING RESISTOR ago 1 of7
=I User treet
& feu
fare
SPECIFICATION
FOR
NEUTRAL GROUNDING RES
REVISED AND ISSUED AS STANDARD
ee ‘SPECIFICATION.
REVISED AND ISSUED AS STANDARD
cio eee ‘SPECIFICATION
3} onga06 REVISED AND ISSUED AS STANDARD
‘SPECIFICATION -
2 2801.90 _ISSUEDAS STANDARD SPECIFICATION KVS 86 ent
- — ‘Standards Standards
Rev Committee Bureau
Prepared Checked
Date Purpose _Gonvenor__ Chairman
No. J td
‘Approved by
Format No. &-00-0001-F1 Rev. 0 Copyright Ell — All rights reservedSPECIFICATION STANDARD SPECIFICATION No.
SSRIS (SS) ENGINEERS,
seaebis ONA UMITED Reiopal 6-51-0043 Rev. 5
GROUNDING RESISTOR, Page 20f7
Abbreviations:
GL. Galvanised Iron
Electrical Standards Committee
Convenor: Mr. A Ananthanarayan
Members: Mr. VP Sharma
Mr. KV Subramanyam
Mr. CR Mandal/Mr. Ashok Choudhury
Mr. SK Kaul
Mr. UA Patro
Format No, 6:00-0007-F1 Rev. 0 Copyright BIL Al rights reserved‘SPECIFICATION
[STANDARD SPECIFICATION No.
6-51-0043 Rev. 5
Page 3of7
eee: OMAR oh
GROUNDING RESISTOR,
CONTENTS,
1.0 SCOPE
2.0 STANDARDS
3.0 GENERAL REQUIREMENTS
eee
50 TECHNICAL REQUIREMENTS
6.0 INSPECTION, TESTING AND ACCEPTANCE
7.0 PACKING AND DESPATCH
Format No. €-00-0001-F1 Rev. 0
‘Copyright EIL ~ Arights reserved5 SPECIFICATION STANDARD SPECIFICATION No.
SSHSITET SS) ENGINEERS. "
SNe FOR!
seareiics ONO Me NEUTRAL 6-51-0043 Rev. 5
GROUNDING RESISTOR Page 4 of 7
1.0 SCOPE
1.1 The intent of this specification is to define the requirements for design, manufacture, testing,
packing and transport of Neutral Grounding Resistor (NGR),
2.0 CODES AND STANDARDS
2.1 The equipment shall comply with the requirements of latest revision of the following
standards issued by BIS (Bureau of Indian Standards) and other agencies, unless otherwise
specified:
IS:5 Colours for ready mixed paints and enamels
IS: 2705 Current transformers.
IS: 3043 Code of practice for earthing
IS: 3427 A.C. metal enclosed switchgear and controlgear for rated voltages
above IkV and up to and including 52kV.
IS: 13947 _L.V. switchgear and controlgear.
IEEE: 32 Neutral Grounding Devices- Standard requirements, terminology and
test procedure.
ASTM-A240 Specification for heat resisting Chromium and Chromium-Nickel
stainless steel plate, sheet and strip for pressure vessels
2.2 Incase of imported equipment, standards of the country of origin shall be applicable if these
standards are equivalent or more stringent than the applicable Indian standards.
2.3. The equipment shall also conform to the provisions of Indian Electricity Rules and statutory
regulations currently in force in the country.
24 Incase Indian standards are not available for any equipment, standards issued by IEC/ BS!
VDE/ IEEE/ NEMA or equivalent agency shall be applicable,
2.5 Incase of any contradiction between various referred standards/ specifications’ data sheet and
statutory regulations, the following order of decreasing priority shall govern:
- Statutory regulations
- Data sheets
- Job specification
- This specification
: Codes and standards.
3.0 GENERAL REQUIREMENTS
3.1 The offered equipment shall be brand new with state of art technology and proven field track
record, No prototype equipment shall be offered.
3.2. Vendor shall ensure availability of spare parts and maintenance support services for the
offered equipment at least for’IS years from the date of supply.
3.3 Vendor shall give a notice of at least one year to the end user of equipment and EIL before
phasing out the product/spares to enable the end user for placement of order for spares and
services,
4.0 SITE CONDITIONS,
The Neutral Grounding Resistor shall be suitable for outdoor installation (without a shed)
for satisfactory operation under conditions of restricted natural ventilation in a tropical
humid and corrosive atmosphere as prevalent in refineries, petrochemical and fertilizer
plants. The NGR shall be designed to operate under site conditions as specified in the data
sheet. If not specifically mentioned therein, a design ambient temperature of 40° C and an
altitude not exceeding 1000 m above mean sea level shall be considered,
Format Ne. &00-0007-F1 Rev. 0 ‘Copyight EL — All ights reservedSPECIFICATION —_—_stavonnDspcrteano
eit OQAiiw Woe 6-5-0043 Row 5
‘GROUNDING RESISTOR Page 5 of 7
5.0 TECHNICAL REQUIREMENTS
or Resistors
SAL ‘The resistor elements shall be made of unbreakable, corrosion proof, joint-less stainless steel
313
521
5.2.5
5.2.6
grid conforming to ASTM standard A240-304. The grids shall be in punched form.
The resistor shali be sized for carrying the rated current specified in the data sheet for 10
seconds with maximum temperature limited to 790° C for stainless steel resistor elements,
while limiting the temperature of aluminium conductor / bus bar to 350° C.
If specified in the data sheets, the resistor shall also be sized to carry 10% of the rated
current continuously with the maximum operating temperature of resistor elements limited
to 415° C. Further, the temperature rise of the resistor elements when they carry 10% of the
rated current followed by the specified rated current for 10 seconds shall not exceed the
temperature limits specified in clause 5.1.2 above. Under the steady-state conditions when
the NGR carries 10% of the rated current, the surface temperature of the enclosure,
excluding the roof but including the separate canopy, shall be limited to maximum 70° C.
Grids shall be mounted on stee! rods insulated by special heat-resistant insulating materials,
suitable for the above temperatures. Ceramic/ porcelain insulators shall be used to insulate
the resistor elements from the enclosure, The insulators and terminal bushings shall have
adequate minimum creepage values (total and protected) for the required voltage grade.
Resistor banks shall be provided in series and parallel combinations to achieve the overall
resistance value. Minimum two banks in parallel shall be provided in the system, unless
specified otherwise.
Enclosure
‘The resistor elements shall be housed in 2 naturally ventilated sheet steel enclosure with
‘minimum IP-31 degree of ingress protection and suitable for outdoor installation.
‘The enclosure thickness shall not be less than 3 mm. The NGR shall have a suitable
arrangement for fixing it on concrete foundations/ grouting in floor.
‘The terminals for neutral and earthing connections shall be housed in a separate vermin-
proof, weatherproof terminal box with minimum IP-55 degree of ingress protection. The
terminal box shall be provided with a separate bolted removable undrilled gland plate of
non-magnetic material. This shall be drilled at site to suit the cable entry
‘A separate canopy shall be provided above the enclosure roof with a suitable air gap
between them, It shall also cover the terminal compartment. Suitable lifting arrangement
shall be provided to lift the“eanopy.
It shall be possible to periodically clean the resistor elements and enclosure after removing
the bolted side covers.
Facility shall be provided to earth the enclosure at two points. For this purpose, suitably
sized studs shall be provided on the sides of the enclosure to accommodate the connection
of GI strip.
‘The bottom of the enclosure shall be provided with a drain plug to remove water that may
get collected in the enclosure.
Format No, -00-0001-F1 Rev. 0 Copyright EL ~ Alvights reservedSRG IIE ft ENCINEERS SPECIFICATION ‘STANDARD SPECIFICATION No.
sear ESA UMITED FOR
So ett eens nce NEUTRAL 6-51-0043 Rev. 5
GROUNDING RESISTOR Page 6 of7
53 Terminals
5.3.1 The two ends of the resistor shall be brought out to suitable epoxy/ porcelain bushing type
terminals of adequate rating for the neutral and earth connections. The terminals shall be
suitable for terminating the specified size of cables/ earthing strip and shall be supplied
complete with tinned-copper lugs. Bolted type link shall be provided for isolating the
resistor at the neutral end,
5.3.2 Suitable washers shall be provided between the grid element ends and the terminals to
‘maintain good electrical contact.
5.3.3 The connection between the transformer neutral and the NGR shall be carried out by means
of single core / multi core cable of size and type as specified in the data sheet.
5.3.4 The connection between the NGR and the earth pits shall be carried out using GI Earthing
strip/ cable as specified in the data sheet.
54 Space Heater
Suitable anti-condensation space heater shall be provided inside the NGR enclosure to
prevent condensation of moisture. This shall be rated to operate from a 240 V, 50 Hz, single
phase supply. The terminals of the space heater shall be brought out to a separate
weatherproof terminal box. The terminal box/M.B shall have minimum IP-55 degree of
ingress protection
The space heater shall be controlled using a double pole MCB and thermostat provided in
the terminal box. The MCB shall be operable from the front of enclosure without opening.
the terminal box cover.
35 The current transformer, if specified, shall be of cast resin type suitable for the applicable
voltage grade and temperature conditions. The secondary connections of the current
transformer shall be brought out to suitable terminals in M.B and shall be provided with a
shorting link
5.6 Cooling
The Neutral Grounding Resistor shell be natural air cooled. Forced cooling shall not be
used. If required, louvers can be provided in the enclosure provided they are completely
guarded on the inside with a fine wire mesh,
5.7 Nameplate Marking
The equipment shall be provided with a stainless steel nameplate located prominently
indicating following minimum information
a Make
b. Tag No,
c. Resistor nominal value in ohms
a. Rated voltage ¢
€ System voltage and frequency
f Rated current
a Time rating in seconds
h ‘Temperature rise in centigrade
i Enclosure protection class.
5.8 Painting
‘Afier manufacture, all surfaces to be painted shall be thoroughly cleaned, descaled, made free
from rust and given one coat of primer and two coats of epoxy paint of shade 632 as per IS: 5
or as specified in the data sheet,
Format No. 6:00-0001-F1 Rev. 0 Copyright BIL — Alvights reseedSPECIFICATION [STANDARD SPECIFICATION No.
SOiifetazeT ay ENGINEERS,
2a ROR UMITED FOR 6-51-0043 Rev. 5
60
61
62
63
64
70
ao Ral table NEUTRAL
GROUNDING RESISTOR Page 7 of7
INSPECTION, TESTING AND ACCEPTANCE
The offered NGR shall have been suitably type tested and manufacturer shall furnish test
certificates in this regard.
During fabrication, the equipment shall be subjected to inspection by EIL/ Owner or by an
agency authorised by the owner. Minimum four weeks advance notice shall be given to
‘owner for this purpose, Manufacturer shall furnish all necessary information concerning the
supply to EIL/ Owner's inspector. Tests shall be carried out at manufacturer's works under his,
care and expense.
The following tests shall be conducted:
a. Visual and dimension checking
b. Measurement of resistance value at prevailing ambient temperature by Kelvin
Double Bridge.
©. One minute power frequency high voltage withstand test
d. Insulation resistance measurement, both before and after the power frequency
high voltage test.
e. Heat run test.(on one NGR of each rating)
‘The heat run test shall be conducted by passing the rated current for rated time on a limited
resistor section in a proportionately sized test enclosure. The temperature rise shall be
measured under simulated conditions ensuring that heat produced (Rt) in the test enclosure
is more than or equal to the calculated value of energy dissipation required for the test
enclosure in proportion to the complete Neutral Grounding Resistor enclosure as per the
thermal model adopted,
PACKING AND DESPATCH
lll the equipment shall be divided into several sections for protection and ease of handling,
uring transportation. The equipment shall be properly packed for the selected mode of
transportation i.e. by ship/ rail or trailer and shall be wrapped in polythene sheets before
being placed in crates/ cases to prevent damage to finish. The crates’ cases shall have skid
bottom for handling. Special notations such as ‘Fragile’, “This side up’, “Center of gravity’,
“Weight’,’ Owner's particulars’, "PO nos.’ etc., shall be clearly marked on the packages
together with other details as per purchase order.
‘The equipment may be stored outdoors for long periods before installation. ‘The packing,
shall be completely suitable for outdoor storage in areas with heavy rains/ high ambient
temperature unless otherwise agreed,
Format No, 6.00-0001-F1 Rev. 0 Copyright EI. ~ Al rights reserved