1. This document provides calculations for sizing earthing conductors for various plant auxiliaries. 2. It calculates the required cross-sectional area based on a formula that considers fault current and time using values of 50,000 amps and 1 second. 3. For most equipment, including generators, transformers, switchgear, motors over 90kW, and the system neutral, the calculation shows 65x10 mm conductor is adequate.

Uploaded by

Mohan Babu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views17 pages

BHEL Earthing Drawing

1. This document provides calculations for sizing earthing conductors for various plant auxiliaries. 2. It calculates the required cross-sectional area based on a formula that considers fault current and time using values of 50,000 amps and 1 second. 3. For most equipment, including generators, transformers, switchgear, motors over 90kW, and the system neutral, the calculation shows 65x10 mm conductor is adequate.

Uploaded by

Mohan Babu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

 

17
 

1.0 TYPICAL SIZING CALCULATION FOR EARTHING CONDUCTORS OF PLANT AUXILIARIES

1.01 NEUTRAL & ENCLOSURE EARTHING OF GENERATOR TRANSFORMER,


STATION TRANSFORMER, LT AUXILIARY TRANSFORMER, LT BUSDUCT,

 A= 0.01216   I   t c

I= 50000.00 Amperes
tc= 1.00 Sec
 A= 608.00 Square mm

Hence the Size chosen 65 x 10 mm is adequate

1.02 11 & 6.6 kV EQUIPMENT


 A= 0.01216  I   t c

I= 50000.00 Amperes
tc= 1.00 Sec
 A= 608.00 Square mm

Hence the Size chosen 65 x 10 mm is adequate

1.03 415 V SWITCHGEAR , MCCS , BATTERY CHARGER ,


DISTRIBUTION BOARDS, FUSE DISTRIBUTION BOARDS,
 A= 0.01216  I  t 
 
c

I= 50000.00 Amperes
tc= 1.00 Sec
 A= 608.00 Square mm

Hence the Size chosen 65 x 10 mm is adequate

1.04 SUB-MAT, RUNWAY CONDUCTOR/MAIN EARTH LEAD ALONG COLUMNS


 A= 0.01216  I   t c

I= 50000.00 Amperes
tc= 1.00 Sec
 A= 608.00 Square mm

Hence the Size chosen 65 x 10 mm is adequate

1.05 415 V MOTORS

ABOVE 90 KW
 A= 0.01216  I  t  
c

I= 50000.00 Amperes

tc= 1.00 Sec


 A= 608.00 Square mm

Hence the Size chosen 65 x 10 mm is adequate

ABOVE 30 KW UPTO 90 KW
 A= 0.01216  I  t 
 
c

I= 3000.00 in Amperes = Effective Short circuit current for 0.2 sec pre-arcing
time ( Refer enclosed fuse characterstics of siemens type 3 NA2)
tc= 0.20 Sec
 A= 16.31 Square mm

Hence the Size chosen 25 x 3 mm is adequate


 

ABOVE 5 KW UPTO 30 KW
 A= 0.01216  I  t 

c

I= 2000.00 in Amperes = Effective Short circuit current for 0.2 sec pre-arcing
time ( Refer enclosed fuse characterstics of siemens type 3 NA2)
tc= 0.20 Sec
 A= 10.88 Square mm

Hence the Size selected 8 SWG GI wire is adequate

Upto 5 KW
 A= 0.01216  I 
 t 

c

I= 600.00 in Amperes = Effective Short circuit current for 0.2 sec pre-arcing
time ( Refer enclosed fuse characterstics of siemens type 3 NA2)
tc= 0.20 Sec
 A= 3.26 Square mm

Hence the Size selected 8 SWG GI wire is adequate

1.06 SYSTEM NEUTRAL


The maximum system neutral fault current is 50 kA of the 415 system, so that
will be considered for calculations.
 A= 0.01216  I 
  t 
c

I= 50000.00 Amperes
tc= 1.00 Sec
 A= 608.00 Square mm
Hence the Size chosen 65 x 10 mm is adequate