1.0 TYPICAL SIZING CALCULATION FOR EARTHING CONDUCTORS OF PLANT AUXILIARIES
1.01 NEUTRAL & ENCLOSURE EARTHING OF GENERATOR TRANSFORMER,
STATION TRANSFORMER, LT AUXILIARY TRANSFORMER, LT BUSDUCT,
A= 0.01216 I t c
I= 50000.00 Amperes
tc= 1.00 Sec
A= 608.00 Square mm
Hence the Size chosen 65 x 10 mm is adequate
1.02 11 & 6.6 kV EQUIPMENT
A= 0.01216 I t c
I= 50000.00 Amperes
tc= 1.00 Sec
A= 608.00 Square mm
Hence the Size chosen 65 x 10 mm is adequate
1.03 415 V SWITCHGEAR , MCCS , BATTERY CHARGER ,
DISTRIBUTION BOARDS, FUSE DISTRIBUTION BOARDS,
A= 0.01216 I t
c
I= 50000.00 Amperes
tc= 1.00 Sec
A= 608.00 Square mm
Hence the Size chosen 65 x 10 mm is adequate
1.04 SUB-MAT, RUNWAY CONDUCTOR/MAIN EARTH LEAD ALONG COLUMNS
A= 0.01216 I t c
I= 50000.00 Amperes
tc= 1.00 Sec
A= 608.00 Square mm
Hence the Size chosen 65 x 10 mm is adequate
1.05 415 V MOTORS
ABOVE 90 KW
A= 0.01216 I t
c
I= 50000.00 Amperes
tc= 1.00 Sec
A= 608.00 Square mm
Hence the Size chosen 65 x 10 mm is adequate
ABOVE 30 KW UPTO 90 KW
A= 0.01216 I t
c
I= 3000.00 in Amperes = Effective Short circuit current for 0.2 sec pre-arcing
time ( Refer enclosed fuse characterstics of siemens type 3 NA2)
tc= 0.20 Sec
A= 16.31 Square mm
Hence the Size chosen 25 x 3 mm is adequate
ABOVE 5 KW UPTO 30 KW
A= 0.01216 I t
c
I= 2000.00 in Amperes = Effective Short circuit current for 0.2 sec pre-arcing
time ( Refer enclosed fuse characterstics of siemens type 3 NA2)
tc= 0.20 Sec
A= 10.88 Square mm
Hence the Size selected 8 SWG GI wire is adequate
Upto 5 KW
A= 0.01216 I
t
c
I= 600.00 in Amperes = Effective Short circuit current for 0.2 sec pre-arcing
time ( Refer enclosed fuse characterstics of siemens type 3 NA2)
tc= 0.20 Sec
A= 3.26 Square mm
Hence the Size selected 8 SWG GI wire is adequate
1.06 SYSTEM NEUTRAL
The maximum system neutral fault current is 50 kA of the 415 system, so that
will be considered for calculations.
A= 0.01216 I
t
c
I= 50000.00 Amperes
tc= 1.00 Sec
A= 608.00 Square mm
Hence the Size chosen 65 x 10 mm is adequate