SECTION 15891
HVAC DUCTWORK
PART 1 - GENERAL
1.1   SECTION INCLUDES
      A.   The Work shall consist of furnishing and installation of all HVAC ductwork as
           shown on the drawings and specified herein.
1.2   QUALITY ASSURANCE
      A.   Ductwork shall comply with the requirements of NFPA 90A; Standard for the
           Installation of Air Conditioning and Ventilation System.
      B.   Comply with NFPA 96; Standard for the Installation of Equipments for the
           Removal of Smoke and Grease-laden Vapors of Commercial Cooking
           Equipment - Chapter 3; Duct System for kitchen hood duct systems.
      C.   SMACNA Standards: Comply with SMACNA "High and Low Pressure
           Duct Construction Standards" for fabrication and installation of ductwork,
           as well as "HVAC Duct Construction Standards, Metal and Flexible."
      D.   Fabricator and Installer: Firm(s) with a minimum of five (5) years of
           successful fabrication/installation experience on projects similar to that
           required for the project.
.
PART 2 - PRODUCTS
2.1   DUCTWORK MATERIALS
      A.   General: HVAC duct design shall be in accordance with applicable
           requirements of ASHRAE, SMACNA, SASO, NFPA or UL codes and
           Standards. Shop fabricate ductwork of gages and reinforcement complying
           with SMACNA - HVAC Duct Construction Standards and/or ASHRAE
           Handbook, Equipment Volume, Chapter 16 - Duct Construction, and as
           shown on drawings. Ducts shall be low pressure ducts with 500 Pa pressure
           rating and seal Class B as per SMACNA Standards, unless indicated
           otherwise on drawings. Ductwork shall be constructed in sizes and
           configuration as shown on drawings.
      B.   Exposed Ductwork Materials: Where ductwork is indicated to be exposed to
           view in occupied spaces, provide materials which are free from visual
           imperfections including pitting, seam marks, roller marks, oil canning, stains
           and discolorations, and other imperfections, including those which would
           impair painting.
      C.   Sheet Metal: Unless indicated otherwise indicated, fabricate ductwork from
           galvanized sheet steel complying with ASTM A 653 and A 924, lock-forming
           quality, with G90 zinc coating; and ducts shall have mill-phosphatized finish
                                      15891 - 1
           for surfaces exposed to view.
      D.   Kitchen Hood Exhaust Ducts: Kitchen hood exhaust ducts and supports
           used for smoke and vapor removal from cooking equipment, exposed to
           view, shall be fabricated from minimum 18 gage thick stainless steel sheet
           conforming to ASTM A 240, type 304, and the rest of the duct shall be
           fabricated of black sheet steel, welded construction. Shop fabricate ductwork
           complying with SMACNA "HVAC Duct Construction Standards", and NFPA
           96 "Removal of Smoke and Grease-Laden Vapors from Commercial
           Cooking Equipments".
2.2   MISCELLANEOUS DUCTWORK ACCESSORIES
      A.   General: Provide manufacturer's standard materials and products of types
           and sizes indicated and, where not otherwise indicated, provide type and
           size required to comply with ductwork system requirements and SMACNA
           Standards including all the necessary fittings, fasteners, sealant, duct
           hardware i.e. test holes, quadrant locks and duct access doors for proper
           connection to ductwork and equipment. Ducts shall be low pressure type as
           per SMACNA Standards with static pressure rating of minimum 2 inches,
           and with seal Class B.
      B.   Fittings: Provide radius type fittings fabricated of multiple sections with
           maximum 15o change of direction per section. Unless specifically detailed
           otherwise, use 45o laterals and 45o elbows for branch takeoff connections.
           Where 90o branches are indicated, provide conical type tees.
      C.   Duct Sealant: Non-hardening, non-migrating mastic or liquid elastic sealant,
           type applicable for fabrication/installation detail, as compounded and
           recommended by manufacturer specifically for sealing joints and seams in
           ductwork.
      D.   Duct Cement: Non-hardening migrating mastic or liquid neoprene based
           cement, type applicable for fabrication/installation detail, as compounded
           and recommended by manufacturer specifically for cementing fitting
           components, or longitudinal seams in ductwork.
      E.   Ductwork Support Materials: Except as otherwise indicated, provide hot-
           dipped galvanized steel fasteners, anchors, rods, straps, trim and angles for
           support of ductwork.
      F.   Flexible Ducts: Either spiral-wound spring steel with flameproof vinyl
           sheathing, or corrugated aluminum; complying with UL 181, Class 1,
           complete with minimum 38 mm thick continuous flexible fiberglass sheath
           insulation, 16 kg/m³ density, and vapor barrier jacket.
2.3   DAMPERS:
      A.   Low Pressure Manual Dampers: Provide dampers of single blade type or
           multiblade type, constructed in accordance with SMACNA - Low Pressure
           Duct Standards -with static pressure rating of minimum 2 inches.
      B.   Motorized Dampers: Provide dampers with parallel blades for 2-position
                                      15891 - 2
     control, or opposed blades for modulating control. Construct blades of 16
     gage steel, 13 mm diameter steel axles spaced on 229 mm centers.
     Construct frame of 50 x 13 x 3 mm steel channel for face areas 2.32 m² and
     under; 100 x 32 x 16 gage channel for face areas over 2.32 m². Provide
     galvanized steel finish with aluminum touch-up.
C.   Fire Dampers: Fire Dampers: Provide fire dampers, of types and sizes as
     indicated on Drawings where required. Construct casings of 20 gage
     galvanized steel with bonded red acrylic enamel finish. Provide fusible link
     rated at 71-74oC unless otherwise indicated. Provide damper with positive
     lock in closed position, and with the following additional features:
     1.      Damper Blade Assembly: Single-blade type or multi-blade type as
             required.
     2.      Blade Material: Steel, match casing.
D.   Motor-Driven Fire Dampers: Provide motor-driven fire dampers, of types
     and sizes indicated or required. Construct casings of 20 gage galvanized
     steel with bonded red acrylic enamel finish. Provide fusible link rated at 71-
     74oC unless otherwise indicated, and curtain type stainless steel interlocking
     blades, with motor equipped with instant closure cluch, stainless cable
     damper blade linkage, motor mounting bracket and 800 mm long wire leads
     for connecting to smoke/heat detector, and with motor mounted
     outside/inside air stream.
E.   Smoke Dampers: Smoke damper shall be designed for the smoke isolation
     of sections of ducting in ventilation systems, basically consisting of a flanged
     casing, shut off blades with overlapping interlocking joints. Blades are
     connected by internal linkage for parallel action. External linkage parallel
     action also available. Smoke dampers to be leakage tested as appropriate to
     the requirements of UL555S.
     Casing and blades shall be of a galvanized sheet steel to BS EN 10142 or
     equivalent. Casing bearing made from sintered bronze. Blades shall have
     standard face linkage for parallel blade operation. Size and type of damper
     shall be as shown on drawings. Dampers shall be electrically operated and
     controlled through BMS. All accessories required for electric operation shall
     be provided.
F.   Combination Fire and Smoke Dampers: Combination fire/smoke dampers
     shall be designed for the fire/smoke isolation of sections of ducting in
     ventilation systems, basically consisting of a flanged casing, shut off blades
     with overlapping interlocking joints, with side seals to close off gap between
     case and blades. Blades are connected by internal linkage for parallel
     action. Damper is fitted with internal jack shaft incorporating fusible link
     assembly.
     Fire dampers to be independently tested as appropriate to the requirements
     of UL555 (Fire rating 3 hours). Additional leakage tested as appropriate to
     the requirements of UL555S.
                                 15891 - 3
            Casing and blade shall be of galvanized sheet steel to BS EN 10142 or
            equivalent. Casing bearings made from sintered bronze. Blades shall have
            standard face linkage parallel blade operation. Size of dampers shall be as
            shown on drawings. Dampers shall be electrically operated and controlled
            through BMS. All accessories required for electric operation shall be
            provided
2.4   TURNING VANES:
      A.    Provide turning vanes constructed of 38 mm wide curved blades set at 20
            mm o.c., supported with bars perpendicular to blades set at 50 mm o.c., and
            set into side strips suitable for mounting in ductwork.
2.5   DUCT HARDWARE:
      A.    Test Holes: Provide in ductwork at fan inlet and outlet, and elsewhere as
            indicated, duct test holes, consisting of slot and cover, for instrument tests.
      B.    Quadrant Locks: Provide for each damper, quadrant lock device on one end
            of shaft; and end bearing plate on other end for damper lengths over 300
            mm. Provide extended quadrant locks and end extended bearing plates for
            externally insulated ductwork.
2.6   DUCT ACCESS DOORS:
      A.    General: Provide where indicated, duct access doors of sizes indicated.
      B.    Construction: Construct of same or greater gage as ductwork served,
            provide insulated doors for insulated ductwork. Provide flush frames for un-
            insulated ductwork, extended frames for externally insulated duct. Provide
            one side hinged, otherwise with one handle-type latch for doors up to 300
            mm high and smaller, 2 handle-type latches for larger doors.
2.7   FLEXIBLE CONNECTIONS:
      A.    Provide flexible duct connections wherever ductwork connects to vibration
            isolated equipment. Construct flexible connections of neoprene-coated
            flameproof fabric crimped into duct flanges for attachment to duct and
            equipment. Make airtight joint. Provide adequate joint flexibility to allow for
            thermal, axial, transverse, and torsional movement, and also capable of
            absorbing vibrations of connected equipment.
2.8   VARIABLE AIR VOLUME (VAV) BOXES (Relief or By-Pass Type):
      A.    VAV boxes shall be completely factory-assembled. Units designed shall be
            of sizes as shown on drawings and shall have factory catalog rating for L/S.,
            static pressure and noise criteria as required. Units shall have damper shaft
            with optional location of linkage arrangement (left or right of unit) for single
            damper control actuator to be mounted on exterior of unit. Static pressure
            loss through the unit shall be consistent at all times regardless of air volume
            damper position.
                                        15891 - 4
      B.   Cabinet shall be constructed of not less than 22 gauge, zinc-coated steel.
           Internal surfaces shall be acoustically and thermally insulated as required
           with glass fiber, surface-treated to prevent erosion. Insulation material shall
           meet NFPA and NBFU 90A.
      C.   Performance of unit shall be based on tests conducted in accordance with
           ASHRAE Standard 36-72 and with ADC Standard 1062R4 with no ductwork
           between unit discharge and sound room.
      D.   Control Actuator: Factory-mounted electric/electronic actuator with
           appropriate linkages in accordance with box requirements. Control actuator
           shall be furnished by the air volume control box manufacturer.
      E.   Room Temperature Controls: To be furnished by the air volume control box
           manufacturer, as indicated on the drawings, in accordance with the air
           volume control box requirements. Thermostat shall be a wall-mounted
           electric/electronic type with appropriate mounting hardware supplied by the
           controls supplier.
      F.   Box identification: Each airflow control box shall be clearly marked with an
           identification label and airflow indicator. Identification label shall include
           such information as unit nominal L/S, maximum factory-set L/S, minimum
           factory-set L/S, and coil type and coil hand when supplied.
2.9   CONSTANT AIR VOLUME BOXES (Mechanical)
      A.   Shall be single duct terminal box for constant volume systems for supply or
           extract application, casing with acoustic and thermal lining, erosion resistant
           to approx. 20 m/s, with circular inlet spigot suitable for DIN circular duct
           sizes, outlet suitable for fixing of angle flange or slide on flanges, inspection
           cover sealed by a quick release clamping bar, casing air leakage to Class II
           VDI 3803 and DIN 24194, box complies with clean room Class 3 VDI 2083
           and Class 100 of US Standard 209b.
      B.   Volume flow rate controller mechanical system powered without external
           power supply, with integral bellows doubling as an oscillation damper, high
           accuracy on set volume flow rates, differential pressure range 50 to 1500
           Pa, volume flow range 5:1.
      C.   Constructed of galvanized sheet steel casing, lining of attenuator and
           regulator section with mineral wool density 30 to 40 kg/m³, erosion protected
           with laminated glass fiber scrim up to air velocity of 20 m/s non-flammable to
           DIN 4102, material Class A2. Aluminum regulator, polyurethane bellows and
           stainless steel control spring. Additional Acoustic Cladding, consisting of 40
           mm mineral wool and outer casing of 1 mm galvanized sheet steel to reduce
           casing radiated noise.
      D.   Reheat coil (Where shown on drawings) shall be fixed to box discharge, to
           heat the volume flows, flanged both sides. Attenuator provided to fit box or
           reheat coil, to reduce air regenerated noise, with angle flange or slide on
           flanges on both ends. Boxes shall be of type and size as shown on
           drawings.
                                       15891 - 5
2.10   SOUND ATTENUATORS:
       A.   Refer to Section 15240 - VIBRATION ISOLATION AND NOISE CONTROL.
2.11   DUCT INSULATION:
       A.   Refer to Section 15250 - MECHANICAL INSULATION.
2.12   DUCTWORK FABRICATION
       A.   Ductwork shall be fabricated in factory qualified for the fabrication of ducts
            and shall be subject to approval of the Engineer. Rectangular ducts shall be
            fabricated in 1200, 2400, 3000, or 3600 mm lengths, unless otherwise
            indicated or required to complete runs. Round ducts (if used) shall be
            provided in manufacturer’s standard lengths. Pre-assemble work in shop to
            greatest extent possible, so as to minimize field assembly of systems.
            Disassemble systems only to extent necessary for shipping and handling.
            Match-mark sections for reassembly and coordinated installation.
       B.   Shop fabricate ductwork of gages and reinforcement complying with
            SMACNA - HVAC Duct Construction Standards -and/or ASHRAE
            Handbook, Equipment Volume, Chapter 16; Duct Construction; for
            appropriate static pressure rating classification.
       C.   Fabricate duct fittings to match adjoining ducts, and to comply with duct
            requirements as applicable to fittings. Except as otherwise indicated,
            fabricate elbows with centerline radius equal to associated duct width; and
            fabricate to include turning vanes in elbows where shorter radius is
            necessary. Limit angular tapers to 30o for contracting tapers and 20o for
            expanding tapers.
       D.   Fabricate ductwork with accessories installed during fabrication to the
            greatest extent possible.
       E.   Fabricate ductwork with duct liner in each section of duct where indicated.
            Laminate liner to internal surfaces of duct in accordance with instructions by
            manufacturers of lining and adhesive, and fasten with mechanical fasteners.
2.13   DIFFUSERS, REGISTERS AND GRILLES
       A.   General: Diffusers, registers and grilles shall be factory fabricated of
            aluminum, type and finish as shown on the drawings or as approved by the
            Engineer.
       B.   Submittal:
            1.      A schedule of all air inlets and outlets indicating location, types,
                    specified air quantity, neck or face velocity, sound power level
                    values, and maximum and minimum air quantity ranges.
            2.      Copies of manufacturer's technical specifications including detailed
                    installation instructions for ducts and hardware.
                                       15891 - 6
     3.      Certificates of compliance stating that the material used and
             construction conform to all requirements of this specification.
     4.      The Contractor shall be responsible for diffusion, spread, drop and
             throw. If, according to the certified data of manufacturer of the
             proposed units, the sizes indicated on Drawings will not perform
             satisfactorily, units shall be re-selected to perform quietly and
             effectively in accordance with manufacturer's recommendation.
C.   Diffusers shall distribute the specified quantity of air evenly over space
     intended, without causing noticeable drafts, air movement in excess of 0.25
     m/sec in occupied zones, or dead spots anywhere in the conditioned area.
D.   Ceiling diffusers shall be of the square, round, perforated and/or linear slot,
     bar type as shown on the drawings. The type of ceiling construction where
     the diffusers are to be installed shall determine the type of compatible
     diffuser rings or frames to be provided. Diffusers shall be sized in
     accordance with the recommendations of the manufacturer. Diffusers shall
     be equipped with baffles or other devices required to provide air distribution
     pattern. Factory fabricated turning vanes, furnished by the diffuser
     manufacturer, shall be provided at each diffuser, branch duct, or take-off,
     except where flexible ductwork is used. Opposed blade volume damper and
     separate pattern adjustment shall be provided by the diffuser manufacturer
     and shall be installed so that it can be removed through the diffuser neck for
     exhaust and shall be similar to diffusers used for supply, except that
     elements used solely for air pattern control shall be omitted.
     Diffuser shells, frames, perforated face plates, and all air volume controls
     and air turning devices shall have baked-on flat enamel or equivalent finish.
     Color of finish for shells and other component parts shall be gray or off-
     white. Color of exposed frames and face plates shall be as approved by the
     Engineer.
E.   Registers shall be provided with factory fabricated volume dampers
     furnished by the register manufacturer. Volume dampers shall be of the
     group-operated, opposed blade type and shall be key and adjustable.
     Supply registers shall have two sets (horizontal and vertical) of directional
     blades or vanes. Exhaust and return registers shall be similar to supply
     registers, except that they shall have a single set of non-directional face bars
     or vanes having the same appearance as the supply registers. Registers
     shall be factory primed, ready for finish painting. Volume dampers and
     splitter assemblies shall be factory finished in baked black enamel or
     equivalent.
F.   Grilles shall be manufactured and finished in same manner as registers,
     except that volume dampers shall be omitted. Grilles, volume adjusters and
     air control devices made of steel (if required) shall be zinc-phosphate treated
     prior to priming and finishing.
                                 15891 - 7
       G.    Security diffusers, grilles and registers:
             1.      Security diffusers, grilles and registers shall be manufactured to
                     meet all applications of highest security and safety while maintaining
                     the necessary air distribution requirements and Shall be constructed
                     using approved design that allows the grill to become an integral part
                     of the wall for additional strength and shall meet ASTM standard.
                     Security grade diffusers, grilles and registers shall be installed as
                     per the manufacturer instructions and recommendations to ensure
                     proper installation.
2.14   FRESH AIR INTAKE AND RELIEF OUTLET (VENT) HOOD:
       A.   Hood shall be constructed of heavy gauge extruded aluminum louvers.
            Blades shall be of stormproof extruded aluminum with corners mitered and
            welded. Roof and curb caps shall be formed by heavy gauge aluminum and
            the assembly shall be braced by angular steel.
       B.   Provide birdscreen, built-up curb and cleanable filters, where required. Size
            shall be as shown on the drawings.
2.15   AIR FILTERS
       A.   All outside air and recirculated air shall be filtered, except as noted. Filters
            shall be underwriters' Laboratories, Inc. listed filters. Air flow shall not
            exceed rated capacity at specified efficiency. Performance shall be tested
            and certified per ASHRAE Standard 52-76.
       B.   Definitions:
            1.       Efficiency: as measured by the Dust Spot Method on Atmospheric
                     Air, per ASHRAE Test Standard 52-76, unless otherwise noted.
            2.       Arrestance: per ASHRAE Test Standard 52-76.
            3.       Dust holding capacity: per ASHRAE Test Standard 52-76.
       C.   Filter types, provide as follows:
            1.       Flat Panel Filter, Replaceable Type (F1).
            2.       Bag Filter, Extended Surface Type (F2).
            3.       Cartridge Filter (F3).
            4.       Inertial Filter (IF).
       D.   Flat Panel Filters, Replaceable Type (F1): Pleated media shall be blend of
            cotton and synthetic fibers. Casing shall be double wall, rigid chipboard
            frame with expanded metal media support, cross braced on both sides of
            filter. Thickness shall be as noted.
            1.       Filter frames shall be metal with holding latches. The filter shall have
                     an average atmospheric dust spot efficiency of not less than 25 to
                                             15891 - 8
             30% when tested in accordance with ASHRAE Test Standard 52-76.
             Initial resistance at 2.7 m/s face velocity shall be maximum 50 kPa
             for 50 mm thick unit.
     2.      Provide filters similar to American Air Filter, AM-AIR 301.
E.   Bag Filters, Extended Surface, Non-Supported Type (F2): Provide
     replaceable bag type. Glass fiber media shall be supported on leaving side
     with flexible mesh. . The filter shall have an average atmospheric dust spot
     efficiency of not less than 60 to 65% when tested in accordance with
     ASHRAE Test Standard 52-76.
     1.      Side access housings (for low and medium efficiency filters): Filter
             mounting section shall be fully factory assembled and dimensionally
             compatible with factory fabricated air handling units, or as shown on
             plans.
             a.      Provide hinged and recessed access doors on both sides of
                     each housing with hinged cast aluminum spring loaded
                     latches on opposite sides of each door and closed cell
                     neoprene rubber perimeter gasketing. Hinges shall be zinc
                     plated.
             b.      Provide molded polyvinyl chloride flexible filter sealing
                     gaskets with extruded aluminum retainers. Sealing pressure
                     shall be applied against entering air face of filter header. Seal
                     adjacent filters by vertical gasket strips attached to filter
                     header.
             c.      Housing shall be minimum 16 gauge galvanized steel
                     construction with 100 mm turned-in flanges for attachment to
                     adjacent equipment. Pre-drilled attachment holes shall be on
                     not more than 300 mm centers. Provide integral track, for 50
                     mm thick pre-filters.
             d.      Insulate internally the same as air handling unit casing.
F.   Cartridge Filters (F3): Filter shall consist of water resistant media made from
     ultra fine glass filters. Media shall be pleated and have crimped aluminum
     separators to maintain uniform spacing. The pleated media pack shall be
     inserted into galvanized steel cell sides with a 19mm galvanized sheet steel
     header on the air entering side. The filters shall have crossed wire bracing
     on air leaving side. . The filter shall have an average atmospheric dust spot
     efficiency of not less than 80-85% when tested in accordance with ASHRAE
     Test Standard 52-76.
G.   Filter gauges shall be differential pressure type and dial type with range and
     minor divisions as noted under Installation.
H.   Filter gauges shall be differential pressure type and dial type with built-in
     facility for transmitting a warning signal to the BMS when filter resistance has
     reached twice original value or that recommended by air filter manufacturer.
                                 15891 - 9
           Range and minor divisions shall be as noted under installation. Provide
           indication lamps at following locations.
           1.      Before Filter.
           2.      After Filter.
           3.      Provide complete with static pressure taps and two way cocks to
                   permit calibration.
PART 3 - EXECUTION
3.1   INSTALLATION OF METAL DUCTWORK
      A.   General: Assemble and install ductwork in accordance with recognized
           industry practices which will achieve air tight (5 percent leakage for systems
           rated 75 mm and under; one percent for systems rated over 75 mm) and
           noiseless (no objectionable noise) systems, capable of performing each
           indicated service. Install each run with minimum number of joints. Align
           ductwork accurately at connections, within 3 mm misalignment tolerance
           and with internal surfaces smooth. Support ducts rigidly with suitable ties,
           braces, hangers and anchors of type which will hold ducts true-to-shape and
           to prevent buckling. Support vertical ducts at every floor.
      B.   Field Fabrication: Complete fabrication of work at project as necessary to
           match shop-fabricated work and accommodate installation requirements.
      C.   Routing: Locate ductwork runs, except as otherwise indicated, vertically and
           horizontally and avoid diagonal runs wherever possible. Locate runs as
           indicated by diagrams, details and notations or, if not otherwise indicated,
           run ductwork in shortest route which does not obstruct usable space or block
           access for servicing building and its equipment.
           Hold ducts close to walls, overhead construction, columns, and other
           structural and permanent-enclosure elements of building. Limit clearance to
           13 mm where furring is shown for enclosure or concealment of ducts, but
           allow for insulation thickness, if any. Where possible, locate insulated
           ductwork for 25 mm where furring is shown for enclosure or concealment of
           ducts, but allow for insulation thickness, if any. Where possible, locate
           insulated ductwork for 25 mm clearance outside of insulation. Wherever
           possible in finished and occupied spaces, conceal ductwork from view, by
           locating in mechanical shafts, hollow wall construction or above suspended
           ceilings. Do not encase horizontal runs in solid partitions, except as
           specifically shown. Coordinate layout with suspended ceiling and lighting
           layouts and similar finished work.
      D.   Electrical Equipment Spaces: Do not route ductwork through transformer
           vaults and their electrical equipment spaces and enclosures.
      E.   Penetrations: Where ducts pass through interior partitions and exterior walls,
           conceal space between construction opening and duct or duct insulation with
                                      15891 - 10
           sheet metal flanges of same gage as duct. Overlap opening on 4 sides by at
           least 38 mm. Fasten duct and substrate.
      F.   Coordination: Coordinate duct installations with installation of accessories,
           dampers, equipment, controls and other associated work of ductwork
           system.
      G.   Installation: Install metal ductwork in accordance with SMACNA HVAC Duct
           Construction Standards.
3.2   INSTALLATION OF FLEXIBLE DUCTS:
      A.   Maximum Length: For any duct run using flexible ductwork, do not exceed
           1200 mm extended length.
      B.   Installation: Install in accordance with Section III of SMACNA - HVAC Duct
           Construction Standards, Metal and Flexible.
3.3   INSTALLATION OF DUCTWORK ACCESSORIES
      A.   Install duct accessories in accordance with manufacturer's installation
           instructions, with applicable portions of details of construction as shown in
           SMACNA Standards, and in accordance with recognized industry practices
           to ensure that products serve intended function.
      B.   Install turning vanes in square or rectangular 90o elbows in supply and
           exhaust air systems, and elsewhere as indicated.
      C.   Install access doors to open against system air pressure, with latches
           operable from either side, except outside only where duct is too small for
           person to enter.
      D.   Coordinate with other work, including ductwork, as necessary to interface
           installation of duct accessories properly with other work.
3.4   INSTALLATION OF DIFFUSERS, REGISTERS AND GRILLES
      A.   General: Install diffusers, registers and grilles in accordance with
           manufacturer's written instructions and in accordance with recognized
           industry practices to insure that products serve intended functions.
      B.   Coordinate with other work, including ductwork and duct accessories, as
           necessary to interface installation of air outlets and inlets with other work.
      C.   Locate ceiling air diffusers, registers, and grilles, as indicated on Drawings.
3.5   FIELD QUALITY CONTROL
      A.   Leakage Tests:
           1.      After each duct system which is constructed for duct classes 75 mm
                   of w.g. and below is completed, test for duct leakage in accordance
                                       15891 - 11
                   with SMACNA Air Duct Leakage Test Manual. Repair leaks and
                   repeat tests until total leakage is less than 5% of system design air
                   flow.
           2.      Operate installed duct accessories to demonstrate compliance with
                   requirements. Test for air leakage while system is operating. Repair
                   or replace faulty accessories, as required to obtain proper operation
                   and leak-proof performance.
3.6   EQUIPMENT CONNECTIONS
      A.   General: Connect metal ductwork to equipment as indicated, provide flexible
           connection for each ductwork connection to equipment mounted on vibration
           isolators, and/or equipment containing rotating machinery. Provide access
           doors as indicated.
3.7   ADJUSTING AND CLEANING
      A.   Clean ductwork internally, unit-by-unit as it is installed, of dust and debris.
           Clean external surfaces of foreign substances which might cause corrosive
           deterioration of metal or, where ductwork is to be painted, might interfere
           with painting or cause paint deterioration.
      B.   Temporary Closure: At ends of ducts which are not connected to equipment
           or air distribution devices at time of ductwork installation, provide temporary
           closure of polyethylene film or other covering which will prevent entrance of
           dust and debris until time connections are to be completed.
      C.   Adjusting: Adjust ductwork accessories for proper settings, install fusible
           links in fire dampers and adjust for proper action.
3.8   SYSTEM TESTING AND BALANCING
      A.   Conform to the requirements of Section 15990 - TESTING, ADJUSTING
           AND BALANCING.
                                END OF SECTION
                                      15891 - 12