Tocguide
Tocguide
RG-379
                    Prepared by
   Water Permits & Resource Management Division
                    RG-379
                 December 2000
                                  Robert J. Huston, Chairman
                             R. B. “Ralph” Marquez, Commissioner
                                 John M. Baker, Commissioner
    Copies of this publication are available for public use through the Texas
State Library, other state depository libraries, and the TNRCC Library, in
compliance with state depository law. For more information on TNRCC
publications call 512/239-0028 or visit our Web site at:
http://www.tnrcc.state.tx.us/publications
    The TNRCC is an equal opportunity/affirmative action employer. The agency does not allow discrimination on the basis of
    race, color, religion, national origin, sex, disability, age, sexual orientation or veteran status. In compliance with the
    Americans with Disabilities Act, this document may be requested in alternate formats by contacting the TNRCC at (512)239-
    0028, Fax 239-4488, or 1-800-RELAY-TX (TDD), or by writing P.O. Box 13087, Austin, TX 78711-3087.
                                                                iii
                             Table of Contents
1    Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 Monitoring Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4 Monitoring Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5 Compliance Strategy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
9 Compliance Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
10 Public Notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
11   Laboratory Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
     11.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
     11.2 Analytical Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
                                                           iv
Appendices
     Appendix 1: Total Organic Carbon Monthly Operating Reports . . . . . . . . . . . . . 45
     Appendix 2: Side Effects (for Alum or Ferric Coagulation) . . . . . . . . . . . . . . . . . 51
     Appendix 3: Calculating Chemical Feed Rates . . . . . . . . . . . . . . . . . . . . . . . . . . 54
     Appendix 4: Process Control Jar Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
     Appendix 5: Unregulated Disinfection By-Products . . . . . . . . . . . . . . . . . . . . . . . 64
     Appendix 6: Acronyms and Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
     Appendix 7: Formulas and Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
     Appendix 8: Lab Approval Form and Instructions . . . . . . . . . . . . . . . . . . . . . . . 72
     Appendix 9: Densities and Equivalent Weights of Commercial Alum . . . . . . . . . . . 76
     Appendix 10: Texas Rules Regarding TOC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
List of figures
     Figure 3-1:     TOC Sampling Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
     Figure 5-1:     Compliance Determination Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . 7
     Figure 7-1:     Example of PODR Graph . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
     Figure 7-2:     Example of PODR Determination (When PODR is Met Twice) . . . . 26
     Figure 7-3:     Water “Not Amenable to Treatment” . . . . . . . . . . . . . . . . . . . . . . . . 27
     Figure A2-1:    Example of Increased Turbidity with Enhanced Coagulation . . . . . . . 52
List of tables
     Table 6-1:     Step 1 Matrix of Required TOC Removal Percentage . . . . . . . . . . . . . 8
     Table 7-1:     Example of PODR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
     Table 7-2:     Coagulant Dosage Equivalents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
     Table 7-3:      Step 2 Target pH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
     Table 7-4:      Step 2 Jar Test Procedure Summary . . . . . . . . . . . . . . . . . . . . . . . . . 12
     Table 7-5:     Step 2 Dosing Solution Recipes for Dry Chemical . . . . . . . . . . . . . . . 14
     Table 7-6:      Example of Step 2 Jar Test Data Sheet . . . . . . . . . . . . . . . . . . . . . . . 24
     Table 8-1:     Summary of Alternative Compliance Criteria (ACCs or ‘Outs’) . . . . . 28
     Table 11-1:    Analytical Methods for Demonstration of Compliance . . . . . . . . . . . . 36
     Table 11-2:    Necessary Analytical Methods for TOC Compliance Strategies . . . . . 37
     Table A2-1:    Additional Sludge Production Equations . . . . . . . . . . . . . . . . . . . . . . . 52
     Table A5-1:    Impact of Changing Disinfection Strategy on DBPs . . . . . . . . . . . . . . . 64
     Table A5-2:    Health-Based Values for Unregulated Disinfection By-Products . . . . . 65
List of examples
     Example 4-1: Determining Raw Water TOC for a Blended Source . . . . . . . . . . . . . . 6
     Example 6-1: Step 1 Removal Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
     Example 7-1: Converting from Percent to Grams-Per-Liter . . . . . . . . . . . . . . . . . . . 16
     Example 7-2: Preparing a 20 g/L Dosing Solution . . . . . . . . . . . . . . . . . . . . . . . . . . 17
                                                      v
Example 7-3: Determining Number of Jars for Water > 60 Alkalinity . . . . . . . . . . . . 19
Example 7-4: Determining Number of Jars for Water < 60 Alkalinity . . . . . . . . . . . . 21
Example 7-5: Determining the PODR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
                                              vi
1 Introduction
     TOC removal is required for certain plants under the Stage 1 Disinfectants and
     Disinfection By-Products Rule (DBP1R). The Texas regulations relating to TOC
     removal are contained in Appendix 10 of this document. The TOC requirements apply
     only to plants that treat surface water or groundwater under the direct influence of
     surface water (GUI) using sedimentation for treatment.
     Disinfection is a crucial way to protect the public from pathogens. Unfortunately, at the
     same time that disinfectants are inactivating pathogens, they are also reacting with
     naturally-occurring disinfection by-product precursors (DBP-Ps) to form disinfection
     by-products (DBPs). Some of the DBPs, such as trihalomethanes (THMs), are a health
     concern. Total organic carbon (TOC) is used as a surrogate measurement for DBP-Ps.
     The treatment technique for removal of TOC lessens the concentration of DBP-Ps
     available to form DBPs during disinfection.
     If you are a treatment plant operator, you will find clear, easy-to-read guidance
     on how to comply with the TOC rules in this manual. If you have questions, call the
     TNRCC Public Drinking Water Section (Chemical Monitoring Team) at 512/239-
     6020.
     The material presented here is adapted from the EPA’s Enhanced Coagulation and
     Precipitative Softening Guidance Manual. The EPA publication number for this
     guidance manual is EPA 815-R-99-012. The EPA guidance document is available from
     the EPA Safe Drinking Water Hotline: 1-800-426-4791. The EPA Office of
     Groundwater and Drinking Water (OGDW) Web site is:
                          www.epa.gov/OGWDW
     The wording in this TNRCC guidance manual, RG-379, has been changed from the
     EPA’s to make it more readable, but the requirements are intended to be identical with
     EPA’s. This TNRCC guidance manual is available from TNRCC Publications,
     512/239-0028. TNRCC guidance documents can also be requested on the Web. Go
     to the TNRCC web site below and click on Publications at:
                          www.tnrcc.state.tx.us
                                    Page 1 of 84
2 Applicability
      All surface water treatment plants that use conventional treatment must comply with the
      TOC requirements. Conventional systems are those that use coagulation, flocculation,
      sedimentation, and filtration to treat the water. Each treatment plant must meet the TOC
      requirements. The requirements include monthly monitoring, monthly reporting, and
      quarterly compliance determinations. You will find the exact rule language for the
      applicability requirements in Appendix 10 of this guidance document; the citation is
      §290.112(a).
      The system must do its own sampling and report the results to the TNRCC each month.
      The Total Organic Carbon Monthly Operating Report (TOC-MOR) reporting forms
      are shown in Appendix 1 of this document. After the TNRCC receives the reports, we
      will determine if the plant has met the monitoring, reporting, and treatment technique
      requirements.
      Systems serving 10,000 people or more must start monitoring January 2001.
      Compliance for these large systems will be calculated starting January 2002. Data
      collected during 2001 will not be used for compliance. Systems serving less than
      10,000 people must start monitoring January 2003. Compliance for these smaller
      systems will be calculated starting January 2004. Data collected by small systems in
      2003 will not be used for compliance.
                                     Page 2 of 84
3 Monitoring Locations
                           Figure 3-1: TOC Sample Set Locations
                                         You will find the exact rule
                                         language for the TOC
                                         monitoring requirements in
                                         Appendix 10 of this guidance
                                         document; the citation is
                                         290.112(c).
                 Page 3 of 84
NOTE ON MONITORING PLAN:
The raw and treated water sampling points must be shown on the plant schematic in the system’s
monitoring plan.
                                             Page 4 of 84
4 Monitoring Frequency
     Every plant must sample the raw water TOC, the raw water alkalinity, and the treated
     water TOC at least once a month. This group of samples is called a TOC sample set.
     The results of the TOC sample set are used to calculate the percent of the TOC in the
     raw water that is removed by sedimentation, known as the actual percent TOC
     removal. You can find the exact rule language for the TOC monitoring requirements in
     Appendix 10 of this guidance document; the citation is 290.112(b).
     A plant is required to do at least one TOC sample set every month. If samples
     must be sent to a lab, you should consider how long it takes to get samples back from
     the lab when scheduling sample collection. For instance, if it takes the lab three weeks
     to return sample results, you should probably sample early in the month, so the results
     will be back in time to fill out the TOC-MOR.
     A plant may choose to do more than one TOC sample set in a month. If you
     choose to, you may take more than one TOC sample set in a month; the results of all
     TOC sample sets that are taken in accordance with the sampling requirements, and at
     the locations designated in the monitoring plan, must be reported. The average removal
     ratio for all the TOC sample sets will be used to calculate compliance (see Compliance
     Determination). Multiple TOC sample sets may be necessary if a plant treats water that
     is highly variable. For instance, if your plant treats water from two reservoirs in one
     month, you should probably take a TOC sample set before and after changing between
     water sources. Or, if heavy rains change the treatability of the source water, you should
     consider taking a TOC sample set before and after the rain.
     Collect the raw water alkalinity and the raw water TOC samples at the same time. The
     treated water sample should be taken at about the same time as the raw water sample.
     The rules say that raw and treated measurements must be taken within one hour of each
     other. Some continuous monitoring equipment automatically samples treated water one
     detention time later than raw water. If you wish to purchase this type of equipment,
     contact the TNRCC for permission (512/239-6020).
                                    Page 5 of 84
                  two to four weeks. Therefore, you should
                  take the TOC sample set early in the month, so that the analytical results get
                  back in time to report to the TNRCC.
          TOC samples must be taken from untreated raw water (before any disinfectant,
          oxidant, or other treatment is applied). Compliance sampling is complicated by this
          requirement, because utilities frequently apply disinfectant in the source-to-plant
          transmission lines. This may make it impossible to sample the plant influent immediately
          after the raw waters are blended, because disinfectant is present. Sampling schemes
          that address this difficulty are discussed below.
          Groundwater and surface waters blended before the application of disinfectant can
          simply be sampled after blending. Groundwater introduced to the treatment train after
          rapid mix should not be included in the raw water TOC sampling.
          Systems that blend groundwater and surface water should consider blending the water
          after treatment, so that low-turbidity groundwater does not make it harder to treat the
          surface water.
          Sampling of the blended raw water is not allowed in this case, because disinfectant or
          oxidant is present. Get the raw water parameters by using one of the methods below.
                  COMPOSITE SAMPLE: Get a raw water sample from each source and
                  create a composite sample by mixing the samples in proportion to the percent
                  of the influent each compromises. For example, if a source is 30% of the plant
                  influent flow, it should be 30% of the composite sample’s volume. Once the
                  composite sample is created, a single TOC or alkalinity analysis can be
                                         Page 6 of 84
                      performed. Composite sampling is less expensive than weighted calculation.
                                            Page 7 of 84
5. Compliance Strategy
     There are three ways to be in compliance with the TOC treatment technique
     requirements:
             ! Meet the Step 1 TOC removal requirement
             ! Meet the Step 2 TOC removal requirement
             ! Meet any of the alternative compliance criteria (ACC or “outs”).
     Most systems will find that they will need to meet the Step 1 TOC removal
     requirements. The order in which you will consider the plant’s compliance strategy is
     shown in Figure 5.1, below.
NO YES
                                                     NO            I am OUT
        Do I meet Step 2?                                         of compliance
     You must first review the ACCs in Chapter 8 of this guidance document. If the plant
     can meet one of these criteria, you must still monitor and report the results of your
     sample sets each month, However, you do not need to meet a specific TOC removal
     requirement.
     If you have reviewed the list of ACCs and find that the plant CANNOT meet one of
     the criteria, you need to try to meet Step 1 TOC removal requirements in Chapter 6 of
     this guidance document.
     If you determine that the plant CANNOT meet the Step 1 removal requirements, you
     must run a Step 2 jar test. The Step 2 jar test will give you a Step 2 alternative TOC
                                    Page 8 of 84
removal requirement, as described in Chapter 7 of this guidance document.
                              Page 9 of 84
6. Step 1 TOC Removal Requirements
              If the plant does NOT meet one of the alternative compliance criteria (ACC or “outs”)
              in Chapter 8, you must determine whether the plant can meet the Step 1 removal
              requirement for its water, as shown in Table 6-1. To use the table, measure raw
              water TOC and alkalinity and find the box on the table that applies to your raw water.
              The percent shown in the box is your plant’s Step 1 required removal percent. (If the
              plant CAN’T meet the Step 1 TOC removal requirement in Table 6-1, you must use
              the Step 2 requirements in Chapter 7.) You will find the exact rule language for the
              TOC removal requirements in Appendix 10 of this guidance document; the citation is
              290.112(b).
              The percent removal requirements specified in Table 6-1 were developed based on the
              “treatability” of different water. TOC removal is generally more difficult as alkalinity
              increases and TOC decreases. In higher alkalinity waters, pH depression to a level at
              which TOC removal is optimal (pH between 5.5 and 6.5) is more difficult and cannot
              be achieved easily through the addition of coagulant alone. TOC removal is generally
              more difficult as the TOC level decreases, because there are fewer opportunities for
              particles to contact each other and form flocs.
              Month-to-month changes in raw water TOC and/or alkalinity levels will cause some
              plants to move from one box of Table 6-1 to another. Therefore, the plant’s required
              TOC removal may change, based on the TOC and alkalinity level of the monthly raw
              water compliance sample.
                                            Page 10 of 84
Page 11 of 84
7. Step 2 Alternative TOC Removal
   Requirement
7.1 Introduction
         If a plant fails to meet the Step 1 removal requirement in any month (and does not
         satisfy one of the ACC), you must determine the plant’s alternative TOC removal
         requirement (Step 2 removal requirement).
         Utilities that choose to use jar testing (not pilot testing) to determine their Step 2
         removal requirements should follow the procedures described in this guidance
         document. A system that chooses to use pilot-scale Step 2 testing should follow the
         procedures described in the EPA guidance document discussed on page 1.
         A Step 2 jar test will set the plant’s required percent removal for up to six months (see
         Chapter 9 - Compliance Determination for more details).
         In a Step 2 jar test, 10 mg/L increments of alum (or an equivalent amount of iron
         coagulant) are added to determine the incremental removal of TOC. TOC removal is
         calculated for each 10 mg/L increment of coagulant added. Coagulant must be added in
         the required increments until a target pH is achieved. The point where adding 10 mg/L
         more of alum does not remove at least 0.3 mg/L of TOC is defined as the point of
         diminishing return (PODR). Table 7-1 provides an example of how data is used to
         determine the PODR.
         The percent TOC removal achieved at the PODR in the Step 2 jar test is defined as the
         plant’s alternative percent TOC removal requirement, subject to approval by the
         TNRCC public drinking water program. (Defining the PODR is discussed in detail in
         section 7.3.3 of this guidance manual.)
                                        Page 12 of 84
Table 7-1:                                                                              Example of
 PODR                      Alum        TOC          Change     TOC                     Calculation
                           Dose        Level        in TOC    Removal
                          (mg/L)      (mg/L)        (mg/L)      (%)
                             0          4.9          NA         NA
                             10         4.2          0.7        14.3
                             20         3.8          0.4        22.2
                             30         3.5          0.3        28.6
                             40         3.3          0.2       32.7
                             50         3.2           0.1       34.7
                 PODR
                            Alternative Percent TOC
                            Removal Requirement
             The goal of the Step 2 procedure is to determine the amount of TOC that can be
             removed with reasonable amounts of coagulant, and to define an alternative TOC
             removal percentage. The procedure is neither designed nor intended to be used to
             establish a full-scale coagulant dose requirement. Once a plant’s alternative TOC
             removal percentage is approved by TNRCC, a plant may achieve this removal at full
             scale using any appropriate combination of treatment chemicals.
After you start being required to do Step 2 jar testing, you may do the jar testing once
                                              Page 13 of 84
                 and use those results for six months. However, you may wish to redo the Step 2 jar
                 testing if your raw water changes due to rain or blending. There is no upper limit on
                 frequency of jar testing for a plant required to do Step 2.
7.3 Step 2 Jar Test Method
                 The Step 2 procedure is based on the incremental addition of a metal-based coagulant
                 to define an alternative TOC removal percentage. Only aluminum- or iron-based
                 coagulants may be used for the Step 2 procedure. The addition of acid, polymers, or
                 other treatment chemicals to the jars used in the test is not permitted.
                 Alum must be used in 10 mg/L increments; the equivalent increments for other
                 coagulants are shown in Table 7-2.
The Step 2 procedure requires that coagulant be added in increments until the pH of the
                                                         Page 14 of 84
tested sample is at or below the target pH (Table 7-3). The target pH values are
dependent upon the alkalinity of the raw water to account for the fact that higher
coagulant dosages are needed to reduce pH in higher alkalinity waters.
For a water with alkalinity of less than 60 m/L (as CaCO3) – for which addition of small
amounts of coagulant drives the pH below the target pH before significant TOC
removal is achieved – add base to maintain the pH between 5.3 and 5.7 until the
PODR criterion is met. The chemical used to adjust the pH should be the same
chemical used in the full-scale plant, unless that chemical does not perform adequately
in jar tests. Substitute chemicals should be used in this case.
The following jar test procedure should be used to conduct Step 2 testing. This method
relies on the addition of coagulant only; acid and polymers must NOT be used in the jar
test, even if they are used in full-scale treatment. Base must added if the pH of the
water drops too much (see Table 7-3). Table 7-4 summarizes the sequence of the Step
2 jar test procedure.
                               Page 15 of 84
7.3.1   Step 2 Jar Testing Supplies
        The following equipment and chemical reagents are needed to perform the testing.
        !      Jar test apparatus with 1 or 2 liter (L) beakers or square mixing jars.
        !      Dosing solution of alum or other coagulant. The dosing solution must be
               freshly prepared the day of the test. See section 7.3.3 for information on
               preparing an alum or ferric dosing solution. The dosing solution must be made
               from straight coagulant that is NOT blended with polymer or other chemicals.
        !      Base (if needed to adjust pH).
        !      Hydrometer. If using a liquid coagulant, a hydrometer or other equipment to
               measure the specific gravity of the coagulant.
        !      pH meter. The pH meter should be calibrated in accordance with Standard
               Methods (APHA 1998).
        !      Sample bottles. Sample bottles for alkalinity and pH analysis of coagulated
               water. Sample bottles for TOC analysis.
        !      25 and 50 mL pipettes, with bulbs. Pipettes are used to accurately measure
               volumes during preparation of dosing solutions. Volumetric pipettes may be
               used for more precise dosages. Plastic disposable syringes (without needles)
               may be used to measure coagulant doses to be applied during the jar tests, but
               not to prepare the dosing solution.
        !      1 L graduated cylinders.
        !      Large carboys for collecting raw water (preferably with siphons or taps for
               dispensing water). A suitable laboratory tap may also be used.
        !      Magnetic stirrer with stirring bars.
        !      Miscellaneous beakers and other glassware.
        !      Data sheet (see Figure 7-6 for an example).
                                     Page 16 of 84
            When you prepare the dosing solution, you should make it strong enough so that when
            you add 1 ml of it to the jar test jar, you get a 10 mg/L alum dose (or an equivalent
            amount of iron). For example, if you are using alum and 1- liter jars, you will need to
            make a 10,000 mg/L (10 g/L, 10 mg/mL) solution. That way, when you add 1 ml of
            dosing solution to the 1 liter jar, you will get a dose of 10 mg/L. However, if you are
            using alum and 2-liter jars, you will need to make the dosing solution twice as strong so
            that when you add 1 ml of solution to the larger jar, you still get a 10 mg/L dose.
          Table 7-5: Step 2 Dosing Solution Recipes for Dry (Solid) Chemicals
                                   Desired Increment in       Dosing Solution Recipe
            Coagulant Chemical          Step 2 Jars       To dose 1-L jars To dose 2-L jars
          Regular Grade Alum (dry)          10               10 grams         20 grams
              Al2 (SO 4 )3 •14H 2 O       mg – Al2(SO4)3•14H2O
                                                per liter
          Reagent Grade Alum (dry)               11.2                11.2 grams         22.4 grams
              Al2 (SO 4 )3 •18H 2 O      mg – Al2(SO4)3•18H2O
                                               per liter
           Ferric Chloride (dry)                  5.5                 5.5 grams          11 grams
                     FeCl3                 mg – FeCl3 per liter
           Ferric Chloride (dry)                  9.1                 9.1 grams         18.2 grams
                FeCl3 •6H 2 O           mg – FeCl3•6H2O per liter
            Ferric Sulfate (dry)                  9.5                 9.5 grams          19 grams
              Fe 2 (SO 4 )3 •9H 2 O       mg – Fe2(SO4)3•9H2O
                                                per liter
            Ferrous Sulfate (dry)                 9.4                 9.4 grams         18.8 grams
                FeSO4 •7H 2 O           mg – FeSO4•7H2O per liter
            To prepare a dosing solution using one of the dry chemicals listed in Table 7-5, use the
            following procedure:
            1.      Add about 400 ml of distilled or deionized water to a 1000-ml volumetric flask.
            2.      Add the proper amount of dry coagulant to the flask and swirl it until the
                    chemical dissolves.
                                            Page 17 of 84
          3.      Finish filling the flask to the 1000 ml mark with distilled or deionized water.
          4.      Stopper the flask and completely mix the dosing solution by inverting the flask
                  several times.
          Determining how much dry coagulant is contained in each milliliter of the liquid
          coagulant:
          The strength of a liquid iron or alum coagulant is typically reported on a percent basis.
          For example, each pound of a 30 percent (%) liquid alum solution contains 0.30
          pounds of reactive (dry) alum. However, in order to prepare a dosing solution, you
          must know the amount of reactive (dry) chemical, in each milliliter of the liquid solution.
          Therefore, the first step in preparing a dosing solution is to convert the concentration of
          the liquid coagulant from percent (%) to milligrams-per-milliliter (mg/ml) using the
                                          Page 18 of 84
              following equation.
              Concentration [mg/ml]
                 = % Alum [g of dry alum/100 g of liquid coagulant solution]
                      × Specific Gravity [g solution/mL solution]
                           × 1000 [mg/g conversion factor]                             Equation 7-1
              Example 7-1 shows the procedure for converting from percent to milligrams-per-
              milliliter when using liquid alum.
              Figuring out how much liquid coagulant to use when making a dosing solution:
              After you have determined how much dry coagulant each milliliter of liquid coagulant
              contains, you can figure out how much liquid coagulant is needed to make a liter of
              dosing solution. To make a liter of dosing solution, use the following equation.
              Example 7-2 shows the calculations for figuring out how much liquid alum to use when
              making a Step 2 jar test dosing solution.
                                            Page 19 of 84
Example 7-2: Preparing a 20 g/L dosing solution
The operator from Example 7-1 wants to make a dosing solution with the liquid alum he is using
at his plant. The liquid alum contains no additional chemicals, and his jar test apparatus has 2-
liter jars. How much of the liquid alum should he use to make his dosing solution?
Solution:
The liquid alum contains no additional chemicals, so the operator knows it can be used to
prepare the dosing solution. He is using 2-liter jars and alum, so he uses the far right-hand
column of Table 7-4 to find out that he will need 20 g of alum to prepare one liter of dosing
solution. From the calculations he made in Example 7-1, the operator knows that each milliliter
of liquid coagulant contains 641 mg of dry alum. Now he can plug all this information into
Equation 7-2 to find out how much liquid alum he needs to use to make the dosing solution.
          Amount of liquid coagulant [mL] =
          20 [g of alum] ÷ 641 [mg of alum/mL of liquid alum] × 1000 [mg of alum/g of alum]
                         = 32.1 [mL of liquid alum]
               However, if you are using other coagulants, such as polymer, polyaluminum chloride, or
               alumina chlorhydrate, you must begin your Step 2 jar test with a dose of 10 mg/L alum
               dose.
                                              Page 20 of 84
          you may need to add a base to keep the pH from dropping to the target pH before you
          reach the PODR.
          The first time you do a Step 2 jar test, you should start with one full set of jars. If you
          meet the PODR after three or four jars, the TNRCC may allow you to run fewer jars in
          future tests.
7.3.4.1   Determining the Number of Jars When the Raw Water Alkalinity                               Is
          60 mg/L or Higher
          If your raw water alkalinity level is at least 60 mg/L, you can use the following
          procedure to determine the number of jars that you will have to run during this first Step
          2 jar test.
          !        Collect a sample of raw water and fill one of the jar test jars to the full mark.
          !        Measure the pH and alkalinity of the raw water.
          !        Place the jar on a magnetic stirrer.
          !        Add alum to this sample in 10 mg/L increments (or equivalent ferric dose). Use
                   Table 7-1 to determine appropriate incremental doses for each type of
                   coagulant.
          !        Measure and record the pH after each incremental coagulant dose.
          !        Determine the alum or ferric dose required to reach the target pH. Use Table
                   7.2 to determine the target pH).
          The number of increments of alum you have to put in to hit the target pH will be the
          number of jars you need to dose with alum (or iron coagulant) when you do the jar test.
          Example 7-3 shows how an operator goes through the process of determining the
          number of jars needed for a Step 2 jar test when the alkalinity is relatively high.
                                          Page 21 of 84
Example 7-3: Determining the number of jars needed for a Step 2 jar test when the raw
water alkalinity level is at least 60 mg/L.
An operator at a treatment plant that uses ferric chloride has a raw water with an alkalinity level
of 84 mg/L and a pH of 7.6. The plant is currently applying a ferric dose of 19 mg/L.
Solution:
Since the plant is using ferric chloride, the operator uses Table 7-1 to determine that a dose of
5.5 mg/L is equivalent to a 10 mg/L alum dose. Since the plant is currently applying 19 mg/L of
ferric, the operator can determine the plant’s equivalent alum dose using the following equation.
          Equivalent alum dose at the plant =
                 19 mg/L [ferric dose] ÷ 5.5 [mg/L of ferric/10 mg/L of alum] × 10 [mg/L of alum]
                        = 34.5 mg/L
Using this result, the operator determines that the Step 2 jar test can begin with an equivalent
alum dose of 30 mg/L, i.e., at jar number 3. She then refers to Table 7-1 to determine the
appropriate incremental ferric chloride dose. Since the jar test apparatus has 2-liter jars and the
plant uses a dry coagulant, the operator refers to Table 7-4 and uses 11 grams of FeCl3 to
prepare one liter of dosing solution. Using one of the 2-liter jars and the procedure described in
section 7.3.4.1, she obtains the following results.
                                                 Ferric Dose
   Jar #      Equivalent Alum Dose                                         Alkalinity          pH
                                            (ml of dosing solution)
     0                    0                           0 (raw water)            84             7.6
     3                  30                           16.5                                     7.1
     4                  40                           22                                       7.0
     5                  50                           27.5                                     6.8
     6                  60                           33                                       6.5
     7                  70                           38.5                                     6.4
     8                  80                           44                                       6.3
     9                  90                           49.5                                     6.1
Based on these results and Table 7-3, the operator correctly concludes that she must run the
Step 2 jar test out to an equivalent alum dose of at least 80 mg/L.
7.3.4.2        Determining the Number of Jars When the Raw Water Alkalinity                       Is
               less than 60 mg/l
               When the raw water alkalinity level is below 60 mg/L, small increases in coagulant
               doses can produce rapid decreases in pH. Consequently, an operator may reach the
               target pH long before reaching the PODR. This problem is particularly severe when
               the raw water alkalinity level is below 20 to 30 mg/L.
               The TNRCC is concerned that the Step 2 Jar Test may be concluded before the
               PODR is reached. Consequently, we require that you raise the coagulant dose by at
               least 5 increments before concluding the test. Basically, you must run at least five jars
               above your current coagulant dose. For example, if you are currently apply 26 mg/L of
               alum, the TNRCC might not approve the results of the jar test unless doses of 20, 30,
                                             Page 22 of 84
40, 50, 60, and 70 mg/L are included in the test.
If your raw water alkalinity level is below 60 mg/L, you may find that the pH of your jar
falls below the target pH before you reach the maximum dose you need to apply. In this
case, you will need to add a base to one or more of the jars to keep the pH within the
target pH range. When you have a raw water with relatively low alkalinity, you should
use the following procedure to determine the number of jars that you will have to run
during your first Step 2 jar test.
!        Collect a sample of raw water and fill one of the jar test jars to the full mark.
!        Place the jar test jar on a magnetic stirrer.
!        Measure the pH and alkalinity of the raw water.
!        Add alum to this sample in 10 mg/L increments (or equivalent ferric dose). Use
         Table 7-1 to determine appropriate incremental doses for each type of
         coagulant.
!        Measure and record the pH after each incremental coagulant dose.
!        If the pH of the jar falls below 5.3, add enough base to raise the pH level to
         between 5.3 and 5.7.
!        If you have not increased the coagulant dose by at least 5 increments (i.e., 50
         mg/L of alum or an equivalent amount of iron), keep going till you have.
The number of increments of alum you have to put in to hit the target pH will be the
number of jars you need to dose with alum (or iron coagulant) when you do the jar test.
Example 7-4 shows how an operator goes through the process of determining the
number of jars needed for a Step 2 jar test when the alkalinity is below 60 mg/L (as
CaCO3).
                               Page 23 of 84
Example 7-4: Determining the number of jars needed for a Step 2 Jar Test when the raw
water alkalinity level is less than 60 mg/L.
An operator at a treatment plant that uses a pure polymer coagulant has a raw water with an
alkalinity level of 21 mg/L and a pH of 7.3. The plant is currently applying a polymer dose of 6.3
mg/L and uses liquid caustic to adjust the pH of its finished water.
Solution:
Because the plant uses polymer as its primary coagulant, the operator realizes that he must
prepare his dosing solution using dry alum. Since the jar test apparatus has 2-liter jars, the
operator refers to Table 7-4 and uses 20 grams of regular grade dry alum to prepare one liter of
dosing solution.
The operator also realizes that Section 7.3.3 of the guidance manual requires him to begin the
the Step 2 jar test at an incremental alum dose of 10 mg/L, because the plant uses polymer as
its primary coagulant. In addition, he knows that the TNRCC will probably make him apply an
alum dose of at least 50 mg/L (i.e., 5 incremental doses) before they will approve his results.
Each 10 mg/L alum dose will consume about 5 mg/L of alkalinity. Consequently, the operator
knows that he will probably need to adjust the pH for the last couple of doses. To address this
problem, he prepares a 10% dilution of his liquid caustic to use in the test. Then, using one of the
2-liter jars and the procedure described above in section 7.3.4.2, he obtains the following results.
Based on these results, the operator concludes that he must run the Step 2 jar test out to an
equivalent alum dose of at least 50 mg/L. However, since the last three increments gave some
unclear results, he decides to run the jar test out to a dose of 70 mg/L, just to be safe. Finally,
he realizes that he will need to add some of the dilute caustic to the last couple of jars to keep
the pH of the settled water between 5.3 and 5.7.
                                             Page 24 of 84
                                 Table 7-6: Example of Step 2 Jar Test Data Sheet
                                                    PERFORMANCE DATA
Jar No.      COAGULANT                    BASE                   Alkalinity         pH       TOC     Incremental TOC     TOC
                Dose          Volume      Dose    Volume                                                 Removal       Removal
               (mg/L)          (mL)      (mg/L)    (mL)       (mg/Las CaCO3)                (mg/L)       (mg/L)          (%)
 RAW
 1
 2
 3
 4
 5
 6
 7
 8
 9
10
11
12
 TOC
(mg/L)
Coagulant Dose
                                                           Page 25 of 84
Page 26 of 84
7.3.6   Collect Raw Water for Testing
        You should conduct the jar test with freshly collected water, if at all possible. Collect as
        much raw water for the jar test as you will need (10 to 30 liters, depending on number
        and size of jars).
                NOTE ON STORAGE: If you absolutely must store the raw water for
                subsequent testing, the sample should be refrigerated at approximately 4NC.
                Before starting any testing with the sample, adjust the temperature of the sample
                back to the ambient raw water temperature during collection, by bringing the
                temperature up gradually. Samples that have been stored should be inverted to
                re-suspend any solids that have settled to the bottom of the container during
                storage. It is best to collect fresh raw water for a jar test.
        Fill the coagulant syringe for each jar with the appropriate amount of coagulant. If pH
        adjustment is needed for one or more jars, fill the base syringe with the appropriate
        type and amount of base. Lay the syringes next to the respective jars.
                                        Page 27 of 84
7.3.9          Mix and Settle
              Rapid mix, flocculate, and settle, using the times listed on the data sheet.
              After settling, measure the pH of the jars. Note the values in the data sheet. Take
              samples for alkalinity, if desired, and analyze within appropriate holding times.
                                              Page 28 of 84
Example 7-5: Determining PODR
A surface water treatment plant runs a step 2 jar test and gets these results:
                             Example of Step 2 Jar Test Results
                                  Coagulant Dose                          Settled Water TOC
        Jar #       (mg/Alum or equivalent dose of iron coagulant)               (mg/L)
          1                              0                                        8.0
          2                             10                                        7.0
          3                             20                                        6.6
          4                             30                                        6.2
          5                             40                                        6.0
          6                             50                                        6.0
          7                             60                                        6.0
What is the PODR for this jar test? What is the alternative removal requirement for this plant?
Solution:
(1) PODR: The PODR is the point at which 10 mg/L of additional alum removes less than 0.3
mg/L of TOC. Calculate how much TOC each increment of additional alum achieved. Results
are shown below:
              Example of Step 2 Jar Test Results with Calculation Results
                     Coagulant Dose            Settled Water TOC     Incremental TOC Removed
        Jar #     (mg/Alum or equivalent              (mg/L)                  (mg/L)
                  dose of iron coagulant)
          1                   0                        8.0                      n/a
          2                  10                        7.0                      1.0
          3                  20                        6.6                      0.4
          4                  30                        6.2                      0.4
          5                 40                         6.0                      0.2
          6                  50                        6.0                      0.0
          7                  60                        6.0                      0.0
The PODR is at Jar 5, 40 mg/L of alum added, where addition of a 10 mg/L increment of alum
results in removal of 0.2 mg/L of TOC, which is less than 0.3.
(2) Alternative removal requirement: The alternative removal requirement is the percent
removal that is achieved in the Step 2 jar test at the PODR. The TOC removal in jar 5 is the
new required removal for this plant. For the that jar:
                       % TOC removal = (1 - 6.0/8.0) x 100 = 25%
                Example of Step 2 Jar Test Results With Calculation Results
                   Coagulant Dose         Raw Water Settled Water     Incremental       TOC
        Jar #        (mg/Alum or             TOC         TOC         TOC Removed       removal
                equivalent dose of iron     (mg/L)      (mg/L)           (mg/L)          %
                      coagulant)
          5               40                 8.0              6.0         0.2          25.0%
The removal at the PODR is 25% The system must now achieve 25% TOC removal from the
raw water, unless the alternative removal requirement is above the Step 1 requirement.
                Graphing your results may help you to better understand the Step 2 jar test. Figure 7-1
                shows the results of the jar test in Example 7-5.
                                              Page 29 of 84
             Figure 7-1: Graph of Step 2 Jar Test Results (Data from Example 7-5)
               8.0
                                                 PODR
                                                                       New Step 2
               7.0                                                     Required
                                                                       Removal
                                                                       (25%)
               6.0
                          10     20      30     40         50   60
                          DOSE (increments of 10 mg/L)
 Figure 7-                                                                                 2:
                        Slope < 0.3 mg/TOC removed per
 Example                                                                                   of
                                                                PODR
                                 10 mg/L alum added
  PODR                             Reached TWICE                                        Determi
  nation        8.0                                                         New          When
                                                                            Step 2
the PODR                                                                    Required    Occurs
  Twice         6.0                                                         Removal
                                                                            (50%)
4.0
                           10 20     30  40      50   60              70      80
                           DOSE (increments of 10 mg/L)
                                           Page 30 of 84
Page 31 of 84
7.3.11.3 Water “Not Amenable to Treatment”
            Sometimes, a Step 2 jar test will show that there is no additional TOC removal, no
            matter how much coagulant is added. Plants may apply to the state for a waiver from
            the enhanced coagulation requirements if they consistently fail to achieve the PODR
            (TOC removal is never greater than 0.3 mg/L TOC removed per 10 mg/L alum or
            equivalent dose of ferric salt added at all coagulant dosages during the Step 2 jar test
            procedure).
               These plants have a water in which enhanced coagulation will not work. An example of
               the graph of the Step 2 jar test for water not amenable to treatment is shown in Figure
               7-3. The plant should send the TNRCC the Step 2 MOR with the graph showing the
               jar test results to the TNRCC to demonstrate that the PODR cannot be achieved.
                               10       20      30      40      50       60
                               DOSE (increments of 10 mg/L)
                                             Page 32 of 84
8 Alternative Compliance Criteria
  (ACCs or “Outs”)
           The TOC in some waters is not very easy to remove by coagulation or precipitative
           softening. For this reason, ACCs were developed to allow plants flexibility for
           establishing compliance with the treatment technique requirements. These criteria
           recognize the low potential of certain waters to produce disinfection by-products
           (DBPs), and also account for those waters with TOC that is very difficult to remove.
           A plant can establish compliance with the enhanced coagulation or enhanced softening
           TOC removal requirement by meeting any one of the eight ACCs. The ACCs are
           summarized in Table 8-1 and discussed in detail in sections 8.1 through 8.8.
           All systems that wish to meet one of these “outs” must send in the ACC-MOR, along
           with their TOC-MOR. The ACC-MOR is included in Appendix 1 of this guidance
           manual, along with other reporting forms.
                                          Page 33 of 84
8.1 ACC 1: Raw Water TOC < 2.0 mg/L
         If the raw water contains less than 2.0 mg/L of TOC, calculated quarterly as a running
         annual average, a utility is in compliance with the treatment technique for the whole
         year.
         This criterion also can be used on a monthly basis. For example, in every month in
         which raw water TOC is less than 2.0 mg/L, the plant can establish compliance for that
         month by meeting this criterion.
         This criterion also can be used on a monthly basis. For example, for individual months
         in which treated water TOC is less than 2.0 mg/L, the plant can establish compliance
         for that month by meeting that criterion.
         If the running annual average raw water TOC is less than 4.0 mg/L, and the raw water
         alkalinity is more than 60 mg/L, and the running annual average of TTHM is no more
         than 40 Fg/L, and the running annual average of HAA5 is no more than 30 Fg/L, the
         plant is in compliance for the whole year.
                                         Page 34 of 84
         This ACC can’t be used on a monthly basis, because the TTHM and HAA5 averages
         for a whole year are used to calculate compliance.
         If the running annual average of TTHM is less than 40 Fg/L, and the running annual
         average of HAA5 is less than 30 Fg/L, and the plant uses only chlorine in the plant and
         distribution system, the plant is in compliance for the whole year.
         This ACC can’t be used on a monthly basis, because the TTHM and HAA5 average
         for a whole year (running annual average) is used to calculate compliance.
                 MONITORING & REPORTING: Systems that meet ACC 4 are not required
                 to do extra monitoring, but they must report their TTHM and HAA5
                 compliance values, and certify that only chlorine is used as a disinfectant in the
                 plant and distribution system.
         If the running annual average SUVA is less than or equal to 2.0 L/mg-m, the utility is in
         compliance for the whole year.
                                        Page 35 of 84
         This criterion also can be used on a monthly basis. For example, in every month in
         which raw water SUVA is less than 2.0 L/mg-m, the plant can establish compliance for
         that month by meeting this criterion.
         This criterion is also available on a monthly basis; for individual months in which treated
         water SUVA is less than or equal to 2.0 L/mg-m, the plant can establish compliance for
         that month by meeting ACC 6.
         This criterion can be used on a yearly basis. If treated water alkalinity is less than 60
         mg/L, calculated quarterly as a running annual average, the plant is in compliance for the
         whole year.
This criterion also can be used on a monthly basis. For example, in every month in
                                        Page 36 of 84
        which a softening plant lowers treated water alkalinity to less than 60 mg/L, the plant
        can establish compliance for that month by meeting this criterion.
                MONITORING & REPORTING: Plants that meet this “out” must measure and
                report treated water alkalinity, as well as raw water alkalinity.
        This criterion can be used on a yearly basis. If magnesium removal is at least 10 mg/L,
        calculated quarterly as a running annual average, the plant is in compliance for the
        whole year.
        This criterion also can be used on a monthly basis. For example, in every month in
        which magnesium removal is more than 10 mg/L, the plant can establish compliance for
        that month by meeting this criterion.
                MONITORING & REPORTING: Plants that want to meet this “out” must
                measure and report raw and treated water magnesium hardness. The operator
                must calculate and report the amount of magnesium hardness that is removed.
                                       Page 37 of 84
9 Compliance Determination
                The TNRCC will calculate compliance and notify you if a treatment technique violation
                occurs. The compliance calculation method is included here to assist you in determining
                whether you are likely to have a violation. If you take more than one sample set in a
                month, the results of those sample sets should be averaged. (Process control sample
                sets do not have to be reported.)
        Step 1: If you are using Step 1, the required removal percent is in the Step 1 Matrix (Table
        6-1).
        Step 2: If you are meeting Step 2, the Step 2 alternative required removal requirement is
        determined by doing a Step 2 jar test (Chapter 7). A plant that fails to meet Step 1, and is
        required to go to Step 2, can use the Step 2 alternative removal requirements for the quarter
        that the jar test is performed, and the following quarter. The Step 2 alternative removal
        requirement can be used for that six-month period, even for months that the plant meets the
        Step 1 removal percentage.
                                                Page 38 of 84
Removal Ratio: The removal ratio for a sample set is                          Removal Ratio =
the actual removal percent divided by the required
removal percent. If the actual removal is greater than the                   Actual Removal %
required removal, the ratio is greater than one, and the                   Required Removal %
plant is in compliance for that sample set.
        MULTIPLE SAMPLE SETS IN A MONTH: If a plant takes multiple samples in a month, the
        removal ratio should be calculated for each sample set. The average of all the removal ratios,
        for all the sample sets taken that month, is reported as the monthly removal ratio for
        compliance for that month.
QUARTERLY
Quarterly Average Removal Ratio: The                                       Quarterly Average
quarterly average removal ratio is the                                     Removal Ratio =
average of the monthly average removal ratios                      Month 1      Month 2       Month 3
for a calendar quarter.                                            Removal   + Removal +Removal
                                                                    Ratio        Ratio         Ratio
                                                                                  3
Annual Average Removal Ratio: The
annual average removal ratio is the average                 Annual Average Removal Ratio =
of the quarterly average removal ratios for last           Quarter 1       Quarter 2     Quarter 3   Quarter 4
                                                           Average         Average       Average      Average
                                                                                                     +Removal
four quarters.                                             Removal     +   Removal     + Removal
                                                             Ratio           Ratio        Ratio         Ratio
                                                                                                     1.0
ratio is greater than or equal to 1.0, the system          Annual Average
is in compliance.
                                                            Removal Ratio
                                                   Page 39 of 84
10 Public Notification
      Systems that are required to meet Step 1, and have a annual removal ratio less than
      1.00 must notify their customers of the violation. The TNRCC will tell you if you have a
      violation. The following language is required by federal law [30 CFR 141.32 (79)].
      You will find the exact Texas rule language for the TOC public notification in Appendix
      10 of this guidance document; the citation is 290.112(g). In the following paragraph,
      replace [words in this font] as needed.
              The United States Environmental Protection Agency (EPA) sets drinking water
              standards and requires the disinfection of drinking water. However, when used
              in the treatment of drinking water, disinfectants react with naturally-occurring
              organic and inorganic matter present in water to form chemicals called
              disinfection by-products (DBPs). EPA has determined that a number of DBPs
              are a health concern at certain levels of exposure. Certain DBPs, including
              some trihalomethanes (THMs) and some haloacetic acids (HAAs), have been
              shown to cause cancer in laboratory animals. Other DBPs have been shown to
              affect the liver and the nervous system, and cause reproductive or
              developmental effects in laboratory animals. Exposure to certain DBPs may
              produce similar effects in people. EPA has set standards to limit exposure to
              THMs, HAAs, and other DBPs.
      After this language, the system may add more explanation, including language that
      explains that high TOC alone does not indicate the presence of a known health risk.
      The TNRCC will notify you of any noncompliance. We will also tell you if you need to
      notify your customers. We strongly recommend that you do not issue a public notice
      for a TOC violation unless you have discussed the potential violation with the Chemical
      Monitoring Team at 512/239-6020.
                                    Page 40 of 84
11 Laboratory Methods
11.1 Introduction
             This chapter provides an overview of acceptable analytical methods for compliance
             with the TOC removal requirements. Required procedures for sample collection,
             sample handling, and analysis are summarized, along with recommended quality
             assurance and quality control practices. The purpose of this chapter is to provide a
             general review of laboratory procedures necessary to implement the TOC
             requirements, not to replace the analytical methods required by the DBPR.
             The water quality parameters that are important for compliance include TOC, alkalinity,
             pH, total trihalomethane (TTHM), haloacetic acid (group of five) (HAA5), ultraviolet
             light absorbance at 254 nm (UV-254), dissolved organic carbon (DOC), specific
             ultraviolet absorbance (SUVA), and magnesium hardness. The approved methods are
             summarized in Table 11.1.
The TOC sample set (required for all compliance strategies) includes both TOC and
                                           Page 41 of 84
           alkalinity data, which all systems must measure and report on the TOC-MOR. The
           reporting requirements for Step 2 are summarized in Chapter 7. The reporting
           requirements for ACCs are summarized in detail in Chapter 8. Table 11-2 shows the
           methods a system must use, depending on the compliance strategy being used.
           TOC samples must not be filtered prior to analysis. TOC samples must either be
           analyzed or must be acidified to achieve pH less than 2.0 by minimal addition of
           phosphoric or sulfuric acid as soon as practical after sampling, not to exceed 24 hours.
           Acidified TOC samples must be analyzed within 28 days.
In all of the methods, total organic carbon (TOC) is measured after conversion of
                                          Page 42 of 84
           organic matter to carbon dioxide (inorganic carbon). The methods to accomplish this
           conversion include heat, ultraviolet irradiation, chemical oxidants, or combinations of
           oxidants that convert organic carbon to carbon dioxide.
           Results are reported in mg/L and are typically rounded to two significant figures. A
           minimum reporting level (MRL) of 0.7 mg/L was established by a panel of experts
           for the Information Collection Rule (ICR). The practical quantitation limit (PQL)
           reported by laboratories performing TOC analysis should be consistent with this MRL.
           Values reported by the laboratory at less than the PQL should be reported by the plant
           as half of the PQL.
           Three Standard Methods – 5310B, 5310C, and 5310D – are included in the DBPR
           (Table 11.1). These methods should be followed in accordance with the supplement to
           the 19th Edition of Standard Methods for the Examination of Water and
           Wastewater, American Public Health Association, 1998. Method 5310B is a
           combustion-infrared method; Method 5310C is a persulfate-ultraviolet oxidant method;
           and Method 5310D is a wet-oxidant method. A summary of these methods for the
           determination of TOC is provided below.
                                          Page 43 of 84
               purged from the sample prior to analysis. This process also removes volatile organic
               carbon from the sample, which contributes to carbon loss. However, this loss is
               generally insignificant. The CO2 from oxidation of organic and inorganic carbon is
               measured using a nondispersive infrared analyzer or titrated colorimetrically. Any
               combustion instrument used for compliance purposes under the DBP1R should be
               capable of providing quantitative data at concentrations # 0.5 mg/L.
11.2.2     Alkalinity
               Total alkalinity is measured by titration of the sample to an electrochemically
               determined endpoint (pH 4.5). Alkalinity is reported in milligrams per liter as calcium
               carbonate (CaCO3). The methods are based on the assumption that all of the alkalinity
               concentration is the sum of carbonate, bicarbonate, and hydroxide concentrations, and
               assume that other alkalinity-contributing compounds are absent. Borates, phosphates,
               silicates, or other bases won’t be measured if they are present (Standard Methods,
               1989, p 2-35).
               Three titration methods are approved for alkalinity measurements at 40 CFR 141.89.
               These methods are:
               !       Standard Method 2320B – in Standard Methods for the Examination of
                       Water and Wastewater, 19th Edition, American Public Health Association,
                       1998.
               !       Method ASTM D1067-92B – in the Annual Book of ASTM Methods, 1998,
                       Vol. 11.01.
               !       USGS I-1030-85 – in Methods for Determination of Inorganic Substances
                                             Page 44 of 84
                   in Water and Fluvial Sediments: U.S. Geological Survey Techniques of
                   Water-Resources Investigations.
           The sample pH of the raw water where the sample was collected must be recorded.
           Care must be used in sampling and storage, and in preparation of the primary standards
           for sodium carbonate, sulfuric acid, hydrochloric acid.
           Waters with low SUVA values contain primarily non-humic matter that is difficult to
           remove with enhanced coagulation. On the other hand, the TOC in waters with high
           SUVA values is generally easier to remove using enhanced coagulation. SUVA is an
           alternative compliance criterion for demonstrating compliance with TOC removal
           requirements. Systems are not required to perform enhanced coagulation or enhanced
           softening if the raw or treated water SUVA is #2.0 L/mg-m (Chapter 8).
           Two separate analytical methods are necessary to make this measurement: UV-254
           and DOC. Although these methods are briefly described in sections 11.2.4 and 11.2.5,
           respectively, they are described in greater detail in the EPA guidance document. DOC
           and UV-254 samples used to determine a SUVA value must be taken at the same time
           and same location. Both samples are filtered according to the procedures outlined in the
           discussion of DOC. The TNRCC recommends, but does not require, that both DOC
           and UV samples be filtered as one large aliquot.
           DOC measurements are performed using the same analytical techniques used to
           measure TOC (methods 5310B, 5310C, and 5310D). However, samples for DOC
           measurement must be vacuum-filtered or pressure-filtered through a 0.45 Fm pore size
           filter prior to analysis. Filtering should occur before preservation, storing, or shipping
           the sample. The lab should ensure that no contamination or dilution of the sample
                                          Page 45 of 84
           occurs during filtration.
           The 0.45 Fm pore filters that are used for DOC samples may contain organic
           plasticizers (binding material), which can leach into the sample during filtration. This
           leaching can increase the level of organic carbon in the sample after filtration and create
           experimental error. To prevent contamination from organic binding material in
           membrane filters, the membrane filter must be washed with reagent-grade water before
           a sample is passed through it. Typically, washing with several 100 mL volumes of water
           is required for a 47-mm diameter filter. Vacuum or pressure filtration can be used to
           help this process. You should experiment to find adequate washing procedures for each
           batch of filter membranes. Adequate washing is demonstrated when the DOC of the
           filtered water is within 5% of the TOC of the water prior to filtration.
           High turbidity samples may clog the filter, so more than one membrane may be
           needed.When multiple filter membranes are required for a sample, each sequential filter
           membrane must be taken through the same washing procedure as described above, and
           the presample filter blank should be analyzed.
           The last aliquot of deionized wash water passed through the filter prior to sample
           filtration must be saved and used as a filtered blank. This filtered blank must be
           analyzed using procedures identical to those used for analysis of the samples, and must
           have a DOC content of less than 0.5 mg/L. The filtration apparatus should be
           adequately washed to remove organic matter.
                                          Page 46 of 84
           particles before analysis.
                                           Page 47 of 84
          with this criterion.
          In Texas, most plants add an oxidative disinfectant to the raw water. If oxidants are
          added prior to the finished water TOC and UV-254 monitoring, the utilities are
          required to establish treated water SUVA by conducting a jar test in which no
          disinfectants are added. The jar test can be performed by adding an equivalent amount
          of alum that is used at full-scale (plus any polymer) in a jar test. Due to interference
          from iron in the UV-254 measurement, utilities using ferric salts for coagulation should
          conduct a finished water SUVA jar test with an equivalent amount of alum.
                   POLYMER AND ACID: Unlike the Step 2 jar test, if polymer or acid is added
                   at full scale, they can also be used in the finished water SUVA jar test
                   FERRIC: Ferric plants must replace the ferric with alum in the finished water
                   SUVA jar test. Ferric interferes with UV-254 measurements.
          After completion of the jar test, settled water DOC and UV-254 should be used to
          calculate SUVA. Filtration with a pre-washed 0.45 Fm membrane is required for DOC
          and UV-254 determination.
          General guidelines for performing process control jar tests are included in Appendix 3
          of this guidance manual. You may use the guidelines for process control jar testing as a
          helpful tool to design appropriate finished water SUVA jar testing for your plant.
                                         Page 48 of 84
Appendices
Appendix 1:   TOC-Monthly Operating Reports
                          Page 49 of 84
Appendix 1: Total Organic Carbon
            Monthly Operating Reports
Systems required to remove TOC must fill out the Total Organic Monthly Operating Report (TOC-
MOR) each month and submit it to the TNRCC. Your report is due to the TNRCC no later than the
10th day of the month following the reporting period. The reports must be sent to
                        TNRCC
                        Public Drinking Water Section (MC-155)
                        Water Permits & Resource Management Division
                        P.O. Box 13087
                        Austin, Texas 78711-3087
TOC-MOR
              You must record the monthly actual TOC removal on the TOC-MOR. The measured
              values for raw water TOC, raw water alkalinity, and treated water TOC must be
              recorded on this worksheet, no matter what compliance strategy you are using (Step 1,
              Step 2, or ACC).
              You only have to do one TOC sample set every month. Even though you only need to
              do a single monthly TOC sample set, the worksheet has room for you to record the
              results for more than one TOC sample set, if you want to do additional sample sets.
              Most systems leave all the rows blank except for one. The rows for that data are
              labeled as “Dates.” You may want to do more than one TOC sample set on one day. If
              you do that, you can change the labeling to reflect the actual date the data was taken.
              The results of all sample sets taken in accordance with the monitoring plan at the
              designated sampling sites must be reported to TNRCC on the TOC-MOR. If you
              want to find out how you are doing without reporting results, you may take process
              control samples at sites not designated as compliance monitoring points.
              The TOC-MOR worksheet is also the worksheet that will calculate the Step 1 monthly
              compliance. Every system required to comply with the TOC rules must send in a
              printout of the TOC-MOR worksheet every month.
ACC-MOR
              The ACCs are commonly called “outs” because they get you “out” of having to remove
              TOC. Some of the ACCs reflect the fact that it is very difficult to remove TOC from
              some raw waters. Other ACCs recognize a treatment process that is working well
                                            Page 50 of 84
        under special circumstances, like softening. Chapter 8 contains detailed information on
        the ACCs. You need to submit the ACC-MOR (pages 2 and 3 of the TOC-MOR) if
        you are achieving compliance with the TOC rule by meeting one of the ACC.
Step 2-MOR
        If you are not able to meet either the Step 1 removal requirement (Chapter 6) or one of
        the ACCs (Chapter 8), you will have to do Step 2 jar testing. Chapter 7 contains
        detailed information on Step 2. If you can meet the Step 1 removal requirement, or an
        ACC, you do not need to do Step 2 jar testing.
        You only need to submit the Step 2-MOR (page 2 of the TOC-MOR) to the TNRCC
        if you are required to do Step 2 jar testing. Step 2 jar testing is performed in order to
        determine your Step 2 alternative removal requirement. You must report the results of
        Step 2 jar testing on the Step 2-MOR. These results include the mixing conditions,
        coagulant doses, base addition (if any), and pH and TOC from each jar. The Step 2-
        MOR includes a graph of your jar test results, which shows the point of diminishing
        returns (PODR). The removal the plant gets at the PODR is the plant’s alternative
        minimum removal requirement.
        If you are required to do Step 2 jar testing, the Step 2 alternative removal requirement
        that you determine replaces the value from the Step 1 matrix as the amount of TOC
        removal that you need to achieve.
                                       Page 51 of 84
insert TOC-MOR
                 Page 52 of 84
insert Step 2 MOR
                    Page 53 of 84
insert ACC-MOR page 1
                        Page 54 of 84
insert ACC-MOR page 1
                        Page 55 of 84
Appendix 2: Side Effects of Enhanced
            Coagulation
            In pursuing the goal of additional TOC removal, systems should be aware of potential
            side effects that may impact their plant. The EPA guidance manual (available from the
            Safe Drinking Water Hotline at 1-800-426-4791) provides additional information on
            the secondary effects of enhanced coagulation and enhanced softening. This appendix
            merely summarizes some of the possible side effects for systems that are not softening.
Coagulant Dose
            Generally, it is necessary to add more coagulant to remove TOC than is needed to
            remove turbidity. Therefore, the problems that arise are those you would expect from
            increasing coagulant dose and decreasing pH.
pH of Coagulation
            Besides adding additional coagulant, it may be necessary to lower the pH in some
            waters, so that coagulation occurs at the best pH. For alum, the best pH range is from
            approximately 6.8 to 7.5, depending on the water constituents and whether the plant is
            operating in the charge neutralization or sweep floc mode. Therefore, the problems that
            arise are those you would expect from increasing coagulant dose and decreasing pH.
Floc Quality
            Adding additional coagulant (beyond that needed to optimize turbidity removal) and
            lowering the pH of coagulation may adversely impact floc formation. Floc may tend to
            be larger, fluffier, and more difficult to settle. This is true especially if the plant is
            operating in the range of charge neutralization.
Turbidity
            Adding additional coagulant, beyond that needed to optimize turbidity removal, may
            increase settled water turbidity. This is especially true if the plant is operating in the
            charge neutralization range. This phenomenon is illustrated in Figure A2-1. Increased
            settled water turbidity may make it more difficult for filters to remove the turbidity and
            may shorten filter runs.
                                            Page 56 of 84
            Figure A2-1: Example of Increased Turbidity with Enhanced Coagulation
            TOC                                                                      Turbidity
         (mg/L)                                                                        (NTU)
Sludge Quantity
                Adding additional coagulant, beyond that needed to optimize turbidity removal, may
                adversely impact the quality and quantity of sludge. Sludge production will likely
                increase. In order to estimate how much this will cost, you should do jar, pilot, or full-
                scale testing. Full-scale testing will provide the most and best information. Predictive
                equations are given in Table A2.1 for sludge production from alum or ferric coagulation,
                but the equations are only an estimate.
                                               Page 57 of 84
Sludge Quality
            Sludge will likely be more difficult to dewater. Enhanced coagulation usually results in
            an increased coagulant dose, so clarifier sludge may contain more metals.
Aluminum
            If you are using alum or lime that has aluminum in it, the concentration of dissolved
            aluminum may increase if the pH is decreased. Aluminum is very soluble from pH 6.2 to
            6.5, and over 8.0.
Manganese
            For systems that need to remove manganese, if the manganese is not entirely oxidized
            before the settling tank, manganese may break through. Chlorine or potassium
            permanganate need to be in contact with the water for a period of 15 minutes to four
            hours to get complete oxidation of manganese. Chlorine dioxide will oxidize manganese
            in 5 minutes. If greensand filters are used to remove manganese, letting the pH get
            below 6.2 will make the filters work poorly. Also, manganese may be found in some
            ferric coagulant products. If one of these products is used, it may actually add dissolved
            manganese to the water.
Corrosion
            Lowering the pH and increasing the dissolved metal salts in the water may make the
            water more corrosive. Corrosion in a distribution system is not an equilibrium state – it
            is always in a state of change. You should check the Langelier index and Baylis curve
            for the water entering the distribution system after changing your process to meet the
            TOC removal requirements.
Disinfectant
            The disinfectant demand may decrease, because TOC is part of the disinfectant
            demand. Therefore, reducing the TOC level will reduce chlorine (or other disinfectant)
            demand.
                                           Page 58 of 84
Appendix 3: Chemical Feed Rates
           Example Standard Operating Procedure (SOP) for
            Measuring and Adjusting Chemical Feed Rates
Summary:
In order to treat water effectively, chemicals must be dosed accurately. This SOP contains the
procedures for measuring and adjusting the alum and polymer feed rates. Adjusting the coagulant feed
involves:
                  1.      measuring the current alum and polymer feed rates,
                  2.      calculating the current dosages using the results of the first step,
                  3.      comparing the results of the second step with the target values set using jar tests
                          or the plant superintendent’s recommendation,
                  4.      making necessary adjustments to the alum and polymer feed rates, and
                  5.      verifying that the new feed rate produces the desired doses.
Procedure (Example):
A. Measuring Feed Rates
   I. Alum
      A. Take the stopwatch and the appropriately sized graduated cylinder to the rapid mix (if there
         are no calibration cylinders on the feed stream that you can use).
      B. Measure and record the volume of alum pumped into the rapid mix for 60 seconds.
         1. If you are not going to conduct a jar test, empty the cylinder into the rapid mix.
         2. If you are going to conduct a jar test, pour most of the alum into the rapid mix, but keep
             enough to prepare the dosing solution.
                                                Page 59 of 84
    II. Polymer
        A. Take the stopwatch and the appropriately sized graduated cylinder to the chemical room (if
           there are no calibration cylinders on the feed stream that you can use).
        B. Get the waste bucket (old milk jug).
        C. Valve off the polymer injection line.
        D. Open the valve on the polymer pump sampling tap and flush the injection line into the waste
           bucket for 60 seconds.
        E. Using the graduated cylinder, measure and record the volume of polymer pumped for 60
           seconds.
           1. If you are not going to conduct a process control jar test, empty the cylinder back into
               the polymer drum.
           2. If you are going to conduct a process control jar test, pour most of the polymer back
               into the polymer barrel, but keep a little to prepare the dosing solution.
        F. Close the sampling tap valve and open the valve to the feed (water) line.
    III. Lime
        A. Take the bowl and the stopwatch to the lime feeder.
        B. Place the bowl under the point where the lime drops into the dilution water, and measure
           and record the amount of lime that is fed in 60 seconds.
        C. Take the bowl containing the lime to the lab.
        D. Set up the balance, transfer the lime to the weighing paper, and weigh the sample.
        The following equation assumes that the equivalent dry weight of the liquid alum solution is
        5.34 lbs of dry alum per gallon of alum. If the specific gravity of your alum solution is not close
        to 1.33, this assumption may be slightly inaccurate. A more accurate approach involves
        measuring the specific gravity of each batch of alum delivered by the vendor and then using the
        vendor’s product-specific chart that shows the relationship between the specific gravity versus
        the dry weight equivalency.
                                                Page 60 of 84
 Equation A3 & 1: Calculating the Current Alum Dose
                          alum feed rate ( ml alum ) ( ( gal alum ) ( ( 5.34 lbs dry alum )
                                           minute       3,785 ml alum             gal alum
      alum dose (ppm) '
                                               gal        8.34 lbs water         lbs dry alum
                        raw water flow rate (        ) ((                ) ((                     )
                                              minute         gal water        1,000,000 lbs water
        NOTE: When comparing the current alum dose with a target dose obtained from
        the jar test (see Appendix 4), it is extremely important to use identical values for
        the dry weight equivalent in the two procedures.
II. Polymer
    Since the polymer dosing solution for the jar tests is based on a purely volumetric basis, the
    actual chemical dosages should be calculated on a similar basis, so that the results can be
    compared. When calculating the current polymer dose, Equation A3-2 applies:
III. Lime
     Since the lime dosing solution for the jar tests is based on dry weight, the actual chemical
     dosages should be calculated on a similar basis, so that the results can be compared. When
     calculating the current lime dose, the Equation A3-3 applies:
                                            Page 61 of 84
     Equation A3 & 3: Calculating the Current Lime Dose
                                                    grams of lime         lb lime
                                       lime feed rate (           ) ( (             )
                                                        minute          454 g lime
     lime dose (ppm) '
                                       gal water       8.34 lbs water             lb lime
                       raw flow rate (           ) ( (                )( (                     )
                                        minute            gal water        1,000,000 lbs water
               NOTE: When adjusting the alum dose, it is essential to use the same dry weight
               equivalent value in this calculation that was used to prepare the dosing solution for the
               jar test. This equation assumes that the equivalent dry weight of the concentrated alum
               solution is 5.34 lbs of dry alum per gallon of alum. If the specific gravity of the alum
               solution differs substantially from 1.33, this assumption may be slightly inaccurate. A
               more accurate approach involves measuring the specific gravity of each batch of alum
               delivered by the vendor and then using the vendor’s product-specific chart that shows
                                             Page 62 of 84
            the relationship between the specific gravity versus dry weight equivalency.
II. Polymer
    Adjustments to the polymer feed rate should be based on the results of jar tests or
    recommendations of the plant superintendent. Because the polymer dosing solution for the jar
    tests is based on a purely volumetric basis, Equation A3-5 applies:
   Equation A3 & 5: Calculating the Required Polymer Feed Rate
     required polymer feed
                                                      gal water                 gal polymer
     rate (ml per minute) ' raw water flow rate (               ) ( dosage (                   )
                                                        minute               million gal water
                                                  3,785 ml polymer
                                       .      ( (                  )
                                                     gal polymer
                                raw water flow rate (gpm) ( dosage (ppm) ( 3,785
                            '
                                                     1,000,000
III. Lime
    Adjustments to the lime feed rate should be based on the results of jar tests or
    recommendations of the plant superintendent. Because the lime dosing solution for the jar test is
    on a dry weight basis, Equation A3-6 applies:
                                           Page 63 of 84
2.
     Page 64 of 84
Appendix 4: Process Control Jar Testing
Summary
Jar testing can be a very useful way to determine the desired coagulant feed rate and the effect of
different coagulants or coagulant aids, like polymers. Process control jar testing is very different than the
Step 2 jar testing described in Chapter 4 of this guidance manual. For process control jar testing, you
can choose what chemicals to feed and what doses to feed. When the process control jar test is
finished, you will have useful information to run the plant better. A Step 2 jar test is much more limited,
and it only results in a regulatory compliance number. However, after running a Step 2 jar test and
determining the plant’s new required TOC removal, doing a process control jar test may help you set
full scale operating conditions to meet that new required removal.
This example SOP provides instructions on the preparation of dosing solutions and procedures for a
process control jar test. It should be used in conjunction with Appendix 3, which discusses chemical
feed-rate measurement and adjustment. This example is for a plant that uses alum, polymer, and lime
(or caustic), and that has two-liter jars.
                NOTE ABOUT PERSONALIZING THE SOP: You will need to modify this example
                to work for other chemicals or operating conditions. In other words, if your plant uses
                other chemicals, or uses different solutions than those in this example, you must write an
                SOP that works for those chemicals.
                NOTE ABOUT MIXING TIMES: Generally, jar tests result in better coagulation and
                settling than occurs full scale. One main reason for this is that mixing in jar tests is
                perfect, and mixing full-scale is not. Obviously, the hydraulics in a 2-liter jar are more
                controlled than in a large flow-through plant where short circuiting and dead zones are
                present. It may be necessary for the operator to modify the mixing times for jar testing
                to better match full-scale results. One way to start down this road is to determine the
                hydraulic detention time and baffling factor in each process unit and compare the
                resulting mixing times with the mixing times recommended in this SOP and the Step 2
                process. Then, the operator can go through a process of changing the mixing times,
                comparing the results to full scale, until the results correlate better.
                                                 Page 65 of 84
Equipment Needed (Example)
The equipment needed for your plant to go through this process may be different. For this example, the
operator would need:
       !       the log book for jar test results,
       !       two 2-gallon raw water containers,
       !       jar test apparatus with six 2-liter jars (this example uses 2-L jars),
       !       three 1000 ml volumetric flasks,
       !       10 mL TenSette (automatic pipettor),
       !       several 5-mL, 10-mL, and 25-mL syringes,
       !       equipment to conduct pH, turbidity, and alkalinity tests, and
       !       triple beam balance.
Procedure (Example):
I. Preparation of Dosing (Stock) Solutions:
   Dosing solutions must be prepared in concentrations that allow accurate dosing of the amount of
   raw water being tested in a jar test. Dosing solutions tend to lose their strength over time and should
   be used within 24 hours of preparation.
                                               Page 66 of 84
Equation A4 & 1: Preparing the Alum Dosing (Stock) solution
                                                                         g dry alum
                                         % dry weight of stock solution (            ) ( 1000 ml of stock solution
         ml (liquid) alum                                                100 g water
                                '
    per litre of stock solution                             0.48 g dry alum                                1.33 g alum
                                    concentration of alum (                 ) ( specific gravity of alum (
                                                                 g alum                                      g water
                                         % dry weight ( 1000
                                     '
                                          100 ( 0.48 ( 1.33
                                                  Page 67 of 84
C. Fill the jar test jars.
   Fill each of the five jar test jars halfway full with the raw water from one of the jugs then finish
   filling the five jars to the 2 L mark with the water from the other jug.
H. Flash mix.
   Let the samples stir at 100 rpm for 30 seconds to simulate the flash mix (use the time and speed
   that best represents your plant, if known).
I. Flocculate.
   Reduce the stirring rate of the jar test apparatus to 30 rpm, inject each sample of coagulated
   water with the required lime dose, and let the samples mix for 15 minutes to simulate the
   flocculator (use the time and speed that best represents your plant, if known).
J. Settle.
   Turn the stirrers off and let the samples sit for 30 minutes to simulate the sedimentation process
   (use the time and speed that best represents your plant, if known).
                                             Page 68 of 84
    1.   Which combination of dosages formed a floc first?
    2.   What is the appearance of the floc in each sample?
    3.   After flash mix and flocculation, which sample had the best settling flock?
    4.   What is the appearance of the settled water in each sample?
         NOTE ON DYNAMIC JAR TESTING: In this SOP, and in most jar testing, disinfectants
         are not added. Because disinfectants may act as a coagulant aid, leaving them out may
         prevent the jar test not from matching full-scale results. One way that you may be able to
         make the jar test match full-scale results is to pull samples for jar testing from the plant after
         disinfectant is added. If coagulant is added concurrently with disinfectant, this can be tricky.
         You will need to consider where in the plant samples can be taken to best represent the
         water entering the settling basins. Or, possibly, you could add disinfectant to the jars, but
         this is less likely to represent full-scale conditions.
                                             Page 69 of 84
       Appendix 5: Unregulated Disinfection
                   By-Products
                            Table A5-1: Impact of Changing Disinfection Strategy on DBPs
Changing from...               to.....                  Will make these DBPs....
(plant(1)/distribution
system (2))                                             Decrease, or                              increase                      or not change
Cl2 /Cl2                       Cl2 /                    TTHM, HAA5, HAN, HAK,
                               chloramine (3)           CP, CNX
                               chloramine/              TTHM, HAA5, HAN, HAK,                     CNX                           CP
                               chloramine (3)           aldehydes
                                         (3)
                               O3 /Cl2                  TTHM (4), HAA5 (4), HAN (4)               HAK (4), CP,
                                                                                                  aldehydes (4)
                               O3 /chloramine           TTHM (5)
                               ClO2 /chloramine         TTHM (5)
Cl2 /chloramine                Chloramine/              TTHM (5)
                               chloramine
                               O3 /chloramine (3)       TTHM, HAA5, HAN, CP                       HAK, aldehydes (6)            CNX
                               ClO2 /chloramine         TTHM (5)
O3 /Cl2                        O3 /chloramine (3)       TTHM, HAA5, HAN, HAK,                     CP, CNX
                                                        aldehydes
Chloramine/                    O3 /chloramine (3)       TTHM (4), HAA5 (4)                        HAK (4), aldehydes,           HAN
chloramine                                                                                        CP, CNX
DISINFECTANTS:
Cl2 =        Free chlorine
Chloramine = Monochloramine-dominant mixture of the chloramines (mono-, di- and tri-) formed as reaction products of free chlorine and
             nitrogen (from ammonia) at a mass ratio of between 3:1 to 5:1 Cl2 :NH4 -N. (If chloramines are used in the plant, free chlorine is
             not used in the distribution system.)
ClO 2 =      Chlorine dioxide (ClO 2 is only suitable as a primary disinfectant)
O3 =         Ozone (O3 is only suitable as a primary disinfectant)
DISINFECTION BY-PRODUCTS:
TTHM =        Total of the four trihalomethanes that contain bromine or chlorine.                 HAK =     Haloketones
HAA5 =        Total of the five haloacetic acids (that contain bromine or chlorine)               HAN =     Haloacetonitriles
        that are regulated                                                                        CNX =     Cyanogen halides
Aldehydes: includes halogenated and non-halogenated aldehyde species.                             CP =      Chloropicrin
NOTES:
(1)    Plant disinfectant is the primary disinfectant.
(2)    Distribution system disinfectant is the secondary disinfectant.
(3)    Adapted from Table 3-2. Impacts of Disinfection Practice on DBP Formation, EPA Guidance Manual: Microbial and Disinfection By-
       product Rules Simultaneous Compliance Guidance Manual (EPA 815-R-99-011) August 1999, U.S. EPA, Washington D.C. Available
                                                                  Page 70 of 84
      from the Safe Drinking Water Hotline, 1-800-426-4791).
(4)   One of the two utilities reported no change.
(5)   From experience with Texas utility data.
(6)   One of the two utilities did not analyze for this DBP.
                                                           Page 71 of 84
Appendix 6: Acronyms and Definitions
A5.1 Acronyms
AA       atomic absorption
ACC      alternative compliance criteria. The eight alternative compliance criteria are part of the
         TOC removal requirements of the DBP1R. A plant that meets one of the ACC is not
         required to remove TOC for the period of time that the ACC covers.
AOC      assimilable organic carbon. A parallel measurement to biodegradable organic carbon
         (BDOC).
AOP      advanced oxidation process
ASTM     American Society for Testing Materials
AWWA     American Water Works Association
AWWARF   American Water Works Association Research Foundation
BAT      best available technology
BCAA     bromochloroacetic acid (see HAA)
BDL      below detection limit. If a contaminant is measured in a concentration lower than the
         method can be accurately used, it is considered BDL. Often, values reported as BDL are
         reported as zero. See MDL.
BDOC     biodegradable organic carbon. This is a concern in distribution systems, because a high
         concentration of BDOC may result in regrowth of microorganisms in the distribution
         system. A parallel measurement to AOC.
BF       baffling factor. The BF is used to account for potential short circuiting when calculating
         the effective contact time for calculating CT.
BOD      biological oxygen demand. Usually used in wastewater applications. This is a measure of
         how much oxygen will be used up by the biological components present in water.
CCP      Composite Correction Program. This is the EPA evaluation and adjustment program,
         which includes the CPE and CTA processes.
CCPP     calcium carbonate precipitation potential. This describes the extent to which a water may
         tend to form calcium carbonate scale on surfaces such as pipes.
CDBAA    chlorodibromoacetic acid (see HAA)
CFR      Code of Federal Regulations
COD      chemical oxygen demand. Usually used in wastewater applications. This is a measure of
         how much oxygen will be used up by the chemical components present in water.
CPE      Comprehensive Performance Evaluation. This is the extensive evaluation process
         designed to determine what specific factors are limiting a plant’s ability to achieve
         optimized performance. The CPE is part of the EPA’s Composite Correction Program
         (CCP).
CT       concentration-time (the product of disinfectant concentration and effective contact time
         (T10). This value describes the effectiveness of a given level of disinfectant in a given
         unit process.
CTA      Comprehensive Technical Assistance. An intensive period of technical assistance to a
                                        Page 72 of 84
        plant, in which technical skills are transferred to the plant operators. CTA is part of the
        EPA’s Composite Correction Program (CCP).
CWS     community water system
DAF     dissolved air flotation
DBP     disinfection by-product
DBP1R   Stage 1 Disinfection By-Product Rule
DBP2R   Stage 2 Disinfection By-Product Rule
DBPFP   disinfection by-product formation potential
DBPP    disinfection by-product precursor. Molecules present in natural water that will tend to
        form disinfection by-products when the water is disinfected. The EPA is using total
        organic carbon (TOC) and specific ultraviolet absorbance (SUVA) as surrogates for
        DBPP.
DBPR    Disinfection By-Product Rule
DCAA    dichloroacetic acid
DI      deionized
DOC     dissolved organic carbon. This group parameter measures the total amount of carbon
        present in organic molecules dissolved in the water. Basically, it is done on the same
        machine as total organic carbon (TOC), but the sample is filtered before analysis.
DOX     dissolved organic halogen. This group parameter measures the total amount of dissolved
        organic carbon that has halogen atoms attached to it. The halogens of interest are
        bromine and chlorine. Iodine and fluorine are generally not of interest in this context.
EBCT    empty-bed contact time
EC      enhanced coagulation
EPA     Environmental Protection Agency
ES      enhanced softening
ESWTR   Enhanced Surface Water Treatment Rule
FACA    Federal Advisory Committee Act
FP      formation potential (as in DBPFP)
G       velocity gradient. It is used to calculate the energy transferred to water in a mixing
        process.
GAC     granular activated carbon. GAC is a form of carbon that has been activated using heat so
        that each grain contains many pores. The surface area of a gram of GAC is the size of a
        football field. Because of this high surface area, GAC has many more sites upon which
        contaminants can adsorb than other filter media, such as sand.
GC      gas chromatograph
HAA     haloacetic acid (a DBP). There are nine different HAAs.
HAA5    haloacetic acid (group of 5). The Stage 1 Disinfection By-Product Rule includes a
        maximum contaminant level (MCL) for the sum of five HAAs. These are
        monochloroacetic acid (MCAA), dichloroacetic acid (DCAA), trichloroacetic acid
        (TCAA), monobromoacetic acid (MBAA), and dibromoacetic acid (DBAA).
HAAFP   haloacetic acid formation potential. The theoretical maximum amount of HAA a water
        can form.
                                       Page 73 of 84
HDT        hydraulic detention time
HLR        hydraulic loading rate for filters (see SLR).
ICR        Information Collection Rule
IESWTR     Interim Enhanced Surface Water Treatment Rule
LCA        Limited Compliance Assistance
LSI        Langelier saturation index
LT1ESWTR   Stage 1 Long-Term Enhanced Surface Water Treatment Rule
LT2ESWTR   Stage 2 Long-Term Enhanced Surface Water Treatment Rule
LTA        Limited Technical Assistance
LTESWTR    Long-Term Enhanced Surface Water Treatment Rule
MCL        maximum contaminant level. The concentration level of a contaminant that is regulated. If
           a system has a contaminant concentration greater than the MCL, they may be in violation
           of the regulations (see RAA).
MCLG       maximum contaminant level goal. The health-effects based ideal level for a contaminant.
           This is not the regulated concentration.
MDL        method detection limit. The concentration below which a given method cannot accurately
           measure concentration (see BDL).
MF         microfiltration
MIB        methylisoborneol. An odor-causing compound produced by some algae.
MOR        monthly operating report
MRDL       maximum disinfectant residual limit. Regulations promulgated by EPA in November 1998
           put in place these limits on the allowable concentration of disinfectant leaving a plant.
MRDLG      maximum disinfectant residual limit goal
MTBE       methyl tert-butyl ether
MW         molecular weight
MWCO       molecular weight cutoff
NF         nanofiltration
NOAEL      no observed adverse effect level
NOM        natural organic matter
NPDWR      National Primary Drinking Water Regulation
NTNCWS     nontransient, noncommunity water system. A water system that serves the same people
           all year, but is not a community. A school or factory may be a NTNCWS.
NTU        Nephelometric turbidity unit. A measurement of the cloudiness of water.
PAC        powdered activated carbon (often used to remove taste and odor compounds)
PACl       polyaluminum chloride (sometimes abbreviated as PAC, but not to be confused with
           powdered activated carbon)
PE         professional engineer or performance evaluation
PODR       point of diminishing returns. This has specific meaning for the DBP1R TOC removal
           requirements. In a Step 2 jar test, the PODR is the point at which an additional 10 mg/L
           of alum results in the removal of no more than 0.3 mg/L of TOC.
psi        pounds per square inch (pressure)
                                          Page 74 of 84
RAA      running annual average
RO       reverse osmosis
rpm      revolutions per minute
SDS      simulated distribution system
SDWA               Safe Drinking Water Act
SHMP     sodium hexametaphosphate
SLR      surface loading rate for filters (also referred to as HLR)
SMCL     secondary maximum contaminant level
SOC      synthetic organic chemical
SOR      surface overflow rate or supplemental operating report
SUVA     specific ultraviolet absorbance
SWTR     Surface Water Treatment Rule
T        detention time (see HDT) or temperature.
T10      effective contact time. The time within which 10% of a tracer material will have passed
         through a unit process. Theoretical T10 can be calculated by multiplying the baffling
         factor (BF) by the theoretical hydraulic detention time (HDT).
TBAA     tribromoacetic acid (see HAA)
TCAA     trichloroacetic acid (see HAA)
TEEX     Texas Engineering Extension Service.
THM      trihalomethane (a DBP). These are halogenated organic molecules with one carbon,
         three halogens, and one hydrogen. The four THMs of interest are: chloroform (three
         chlorines, also called trichloromethane), dichlorobromomethane, dibromochloromethane,
         and bromoform (three bromines, also called tribromomethane).
THMFP    trihalomethane formation potential. A group parameter describing what concentration of
         THMs a water may form under set conditions (see FP and UFC).
TNRCC    Texas Natural Resource Conservation Commission
TOC      total organic carbon. A group parameter measuring the total amount of carbon in a water
         present as organic molecules. EPA is using TOC as a surrogate for DBPPs in the
         DBP1R (see DOC).
TON      threshold odor number
TOX      total organic halogen
TTHM     total trihalomethanes. The sum of the four THMs (see THM).
TWDB               Texas Water Development Board
TWUA               Texas Water Utilities Association
UF       ultrafiltration
UFC      uniform formation conditions. Specific disinfection conditions for measuring how much of
         a given disinfection by-product a water may form.
UV       ultraviolet
UV-254   absorbance of ultraviolet light at a wavelength of 254 nanometers
                                       Page 75 of 84
A5.2 Definitions
Enhanced Coagulation
Enhanced coagulation means the addition of sufficient coagulant for improved removal of disinfection by-
product precursors by conventional filtration treatment (EPA definition).
                                               Page 76 of 84
Appendix 7: Formulas and Conversions
Percent Solution Values                               Feed Rate Formulas
      1% = 0.084 lb/gal or 1.3 oz/gal
                      (or 10,000 mg/L)                ppm (mg/L) x GPM                  = lb/hr
      2% = 0.170 lb/gal or 2.7 oz/gal                   2000
      3% = 0.258 lb/gal or 4.1 oz/gal
      4% = 0.348 lb/gal or 5.6 oz/gal                 ppm (mg/L) x GPM x 0.06           = gal/hr
      5% = 0.440 lb/gal or 7.0 oz/gal                   % solution
      6% = 0.533 lb/gal or 8.5 oz/gal
      7% = 0.629 lb/gal or 10.1 oz/gal                (lb/6-minutes) x 20,000 = ppm (mg/L)
      8% = 0.726 lb/gal or 11.6 oz/gal                        gpm
      9% = 0.825 lb/gal or 14.9 oz/gal
                      (or 90,000 mg/L)                (gram/6-minutes) x 44             = ppm (mg/L)
____________________________________                          gpm
_
                                                      * gpm = gallons per minute of plant
                                                      * 6 minute collection for dry feeder
                                                      ________________________________
Conversions
Ounces (fluid) × 29.57   = mL                         Equations
Ounces (dry) × 28.35     = grams
Cubic Ft. × 7.48         = gallons                    In the following calculations:
Gal × 8.34               = lbs                            pi = 3.14, L = length, W = width,
Gal × 3785               = mL                             d = diameter, r = radius, H = height
Gal/Hr × 63              = mL/min
Grains/gal × 17.1        = PPM                                  Area = A (sq ft):
Grams × 15.43            = grains                                  Rectangle: A = L × W
MGD × 694                = gpm                                     Circle: A = pi × r × r
10,000 ppm (mg/L)        = 1%                                   Volume = V (cu ft):
Pounds × 453             = grams                                   Rectangular tanks: V = L × W × H
ppm × 8.33               = lb/million gallons
Quarts × 946             = mL                                      Circular tanks: V = pi × r × r × H
Cubic Ft. × 62.4         = Pounds
Pounds × 7000            = Grains
Gal × 3.785              = Liters                                  In pipes: V = pi × d × d × L
1 mile                   = 5280 ft                                                      4
2.31 ft of water         = 1 psi
0.433 psi                = 1 ft of water              (Divide pipe diameters by 12 to convert from
                                                      inches to feet.)
                                                Page 77 of 84
Appendix 8: Laboratory Approval Form
            and Instructions
Lab Approval Instructions
Approved-Lab Analytes
          Public water systems must run samples for:
                    !        alkalinity,
                    !        turbidity,
                    !        pH,
                    !        temperature,
                    !        disinfectant residual,
                    !        daily point-of-entry chlorite,
                    !        chlorine dioxide,
                    !        calcium, and
                    !        phosphate
          at a laboratory approved by TNRCC. Utilities collect these samples themselves. Most
          utilities will analyze these samples at their own lab.
          If the system sends any of the samples listed on the Laboratory Approval Form to an
          outside lab that is NOT run by a public water system (a commercial lab), that lab must
          be certified by the Texas Department of Health (TDH) to perform those analyses. For
          information on laboratory certification, contact the TDH at 512/458-7587.
                                         Page 78 of 84
“Not Required” Analytes
          The analytes that are listed on the form include all of those that must be analyzed at an
          approved lab. Your system may not be required to analyze for all of the analytes on the
          list. For example, if your system treats groundwater, you are not required to measure
          turbidity, and you should write “Not Required” on the form in the line for turbidity.
          As another example, only systems that use chlorine dioxide must measure chlorite and
          chlorine dioxide. If you do not use chlorine dioxide, write the words “Not Required” in
          the space for chlorite and chlorine dioxide.
          Calcium and phosphates are also examples of chemicals a system may not be required
          to measure. If you are not required to optimize corrosion control as a result of the
          Lead/Copper Rule, write “Not Required” on the lines for calcium and phosphate.
Certified-Lab Analytes
          Public water systems must have the following analyses performed by a lab certified by
          the TDH:
          !       bacteriological,
          !       trihalomethane (TTHM),
          !       haloacetic acid (HAA5),
          !       bromate,
          !       synthetic organic chemical (SOC),
          !       volatile organic chemical (VOC),
          !       inorganic chemical (IC), and
          !       monthly distribution system chlorite.
          Except for the bacteriological samples and monthly chlorite samples, all the certified-lab
          analyte samples are collected by TNRCC’s sampling contractor. The contractor
          delivers the samples to TDH for analysis.
                                         Page 79 of 84
Monitoring Plan
          A copy of the Laboratory Approval Form must be attached to the system’s monitoring
          plan. For information on monitoring plans, contact the TNRCC’s Public Drinking
          Water Chemical Monitoring Team at 512/239-6020. On the monitoring plan, the
          system must attach documentation showing that any outside labs it uses are approved
          or certified, as appropriate.
          If you send approved-lab analytes to a commercial lab, that commercial lab must be
          TDH-certified in the appropriate analysis. Evidence of the commercial lab’s
          certification must be attached to the monitoring plan.
          If you send approved-lab analytes to a different public water system’s lab, that public
          water system’s lab must be TNRCC approved in the appropriate analysis. You must
          attach a copy of that public water system lab’s Laboratory Approval Form to your
          monitoring plan.
                                         Page 80 of 84
                                               LAB APPROVAL FORM
                       I certify that I am familiar with the information contained in this report and that, to the best of my knowledge, the
                       information is true, complete, and accurate.
         Operator's
        Signature:
     Certificate No.
          & Grade:
pH
Temperature
TOC
UV254
Alkalinity
    Disinfectant 2
      Free Chlorine
      Total Chlorine
      Chlorine Dioxide
    Chlorite 3
    at point of entry
    Calcium 3
Phosphate 3
1         Write “Not Required” next to analytes you are not required to measure. If samples are sent to an outside lab, write the name of
          the lab next to the analytes you send there.
2         For systems using chlorine dioxide.
                                                                 Page 81 of 84
3   For systems reporting water quality parameters for the Lead/Copper Rule.
                                                   Page 82 of 84
Appendix 9: Densities and Equivalent
            Weights of Commercial Alum
            Solutions
Specific Gravity   Lb/Gal   % A l 2O 3         Equivalent %   Pound Dry Alum     Gram Dry Alum
                                                Dry Alum*     per Gal Solution      per Liter
                                                                                    Solution
    1.0069         8.40       0.19                  1.12            0.09            11.277
    1.0140         8.46       0.39                  2.29            0.19            23.221
    1.0211         8.52       0.59                  3.47            0.30            35.432
    1.0284         8.58       0.80                  4.71            0.40            48.438
    1.0357         8.64       1.01                  5.94            0.51            61.521
    1.0432         8.70       1.22                  7.18            0.62            74.902
    1.0507         8.76       1.43                  8.41            0.74            88.364
    1.0584         8.83       1.64                  9.65            0.85            102.136
    1.0662         8.89       1.85                  10.88           0.97            116.003
    1.0741         8.96       2.07                  12.18           1.09            130.825
    1.0821         9.02       2.28                  13.41           1.21            145.110
    1.0902         9.09       2.50                  14.71           1.34            160.368
    1.0985         9.16       2.72                  16.00           1.47            175.760
    1.1069         9.23       2.93                  17.24           1.59            190.830
    1.1154         9.30       3.15                  18.53           1.72            206.684
    1.1240         9.37       3.38                  19.88           1.86            223.451
    1.1328         9.45       3.60                  21.18           2.00            239.927
    1.1417         9.52       3.82                  22.47           2.14            256.540
    1.1508         9.60       4.04                  23.76           2.28            273.430
    1.1600         9.67       4.27                  25.12           2.43            291.392
    1.1694         9.75       4.50                  26.47           2.58            309.540
    1.1789         9.83       4.73                  27.82           2.74            327.970
    1.1885         9.91       4.96                  29.18           2.89            346.804
    1.1983         9.99       5.19                  30.53           3.05            365.841
    1.2083         10.08      5.43                  31.94           3.22            385.931
    1.2185         10.16      5.67                  33.35           3.39            406.370
    1.2288         10.25      5.91                  34.76           3.56            427.131
    1.2393         10.34      6.16                  36.24           3.74            449.122
    1.2500         10.43      6.42                  37.76           3.93            472.000
    1.2609         10.52      6.67                  39.24           4.12            494.777
    1.2719         10.61      6.91                  40.65           4.31            517.027
    1.2832         10.70      7.16                  42.12           4.51            540.484
    1.2946         10.80      7.40                  43.53           4.71            563.539
    1.3063         10.89      7.66                  45.06           4.91            588.619
    1.3182         10.99      7.92                  46.59           5.12            614.149
    1.3303         11.09      8.19                 48.18            5.34            640.938
    1.3426         11.20      8.46                  49.76           5.57            668.078
    1.3551         11.30      8.74                  51.41           5.81            696.657
    1.3679         11.41      9.01                  53.00           6.05            724.987
                                         Page 83 of 84
* 17% Al2O3 in Dry Alum + 0.03% Free Al2O3 (From Allied Chemical Company Alum Handbook and EPA CPE Handbook, page K-2)
Page 84 of 84