Ravgp 1101 at 8 e
Ravgp 1101 at 8 e
A10-1902
Revision 1: Sep., 2019
Revision 2: Oct., 2019
SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
OUTDOOR UNIT
<SUPER DIGITAL INVERTER>
RAV-GP1101AT8-E RAV-GP1101AT8-TR
RAV-GP1101AT8J-E RAV-GP1101AT8J-TR
RAV-GP1401AT8-E RAV-GP1401AT8-TR
RAV-GP1401AT8J-E RAV-GP1401AT8J-TR
RAV-GP1601AT8-E RAV-GP1601AT8-TR
RAV-GP1601AT8J-E RAV-GP1601AT8J-TR
–2–
8. TROUBLESHOOTING ................................................................. 45
8-1. Summary of Troubleshooting ............................................................................................ 45
8-2. Diagnostic Procedure for Each Check Code (Outdoor Unit) ......................................... 57
8-3. Sensor characteristics ....................................................................................................... 68
9. SETUP AT LOCAL SITE AND OTHERS ..................................... 70
9-1. Calling of check Code History .......................................................................................... 70
9-2. Group Control Operation ................................................................................................... 70
9-3. Outdoor Unit ....................................................................................................................... 72
10.ADDRESS SETUP ....................................................................... 79
10-1. Address Setup Procedure ............................................................................................... 79
10-2. Address Setup & Group Control ..................................................................................... 80
10-2-1. System Configuration ...................................................................................................... 81
10-2-2. Automatic Address Example from Unset Address (No miss-wiring) .......................... 82
10-3. Remote Controller Wiring ................................................................................................ 83
10-4. Address Setup (Manual setting from remote controller) .............................................. 84
10-5. Confirmation of Indoor Unit No. Position ...................................................................... 85
11. REPLACEMENT OF THE SERVICE P.C. BOARD MCC-1599 ... 87
12. HOW TO EXCHANGE COMPRESSOR ..................................... 88
12-1. Exchanging Procedure of Compressor (Outline) .......................................................... 88
12-2. Exchange of Compressor ................................................................................................ 88
13. DETACHMENTS ........................................................................ 89
13-1. Outdoor Unit ..................................................................................................................... 89
14. EXPLODED VIEWS AND PARTS LIST ................................... 101
14-1. Outdoor Unit ................................................................................................................... 101
14-2. Inverter Assembly .......................................................................................................... 107
–3–
Original instruction
Please read carefully through these instructions including important information which complies with the
“Machinery Directive” (Directive 2006/42/EC), and ensure that you understand them.
Some of the details provided in these instructions differ from the service manual, and the instructions provided
here take precedence.
–4–
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective
gloves and ‘safety’ work clothing.
In addition to such normal protective gear, wear the protective gear described below when undertaking the
special work detailed in the table below.
Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns,
electric shocks and other injuries.
Protective gloves
All types of work
“Safety” working clothing
The important contents concerned to the safety are described on the product itself and on this Service Manual.
Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication Explanation
Indicates contents assumed that an imminent danger causing a death or serious injury of
DANGER the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the
WARNING repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage (∗) may be caused on the
CAUTION repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
∗ Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
Mark Explanation
–5–
Warning Indications on the Air Conditioner Unit
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions.
If removing the label during parts replace, stick it as the original.
WARNING WARNING
ELECTRICAL SHOCK HAZARD
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies
Disconnect all remote electric before servicing.
power supplies before servicing.
WARNING WARNING
Moving parts.
Moving parts.
Do not operate unit with grille removed.
Do not operate unit with grille removed.
Stop the unit before the servicing.
Stop the unit before the servicing.
CAUTION CAUTION
High temperature parts. High temperature parts.
You might get burned when removing You might get burned when removing this
this panel. panel.
CAUTION CAUTION
Do not touch the aluminum fins of the unit.
Do not touch the aluminum fins of the unit.
Doing so may result in injury.
Doing so may result in injury.
CAUTION
CAUTION
BURST HAZARD BURST HAZARD
Open the service valves before the
Open the service valves before the operation,
operation, otherwise there might be the
otherwise there might be the burst.
burst.
–6–
Precaution for Safety
The appliance shall be installed in accordance with national wiring regulations. Capacity shortages of the
power circuit or an incomplete installation may cause an electric shock or fire.
DANGER
Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit
breaker to the OFF position. Otherwise, electric shocks may result.
Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the
circuit breaker to the OFF position.
Failure to set the circuit breaker to the OFF position may result in electric shocks through contact
with the interior parts.
Only a qualified installer (∗1) or qualified service person (∗1) is allowed to remove the intake grille
Turn off of the indoor unit or service panel of the outdoor unit and do the work required.
breaker.
Before starting to repair the outdoor unit fan or fan guard, be absolutely sure to set the circuit
breaker to the OFF position, and place a “Work in progress” sign on the circuit breaker.
When cleaning the filter or other parts of the indoor unit, set the circuit breaker to OFF without
fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
Do not turn ON the circuit breaker under the condition of removing a cabinet, a panel, etc.
Otherwise, it leads to an electric shock with a high voltage, resulting in loss of life.
Prohibition
–7–
WARNING
Before starting to repair the air conditioner, read carefully through the Service Manual, and repair
the air conditioner by following its instructions.
Only qualified service person (∗1) is allowed to repair the air conditioner.
Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury,
water leaks and/or other problems.
Only a qualified installer (∗1) or qualified service person (∗1) is allowed to carry out the electrical
work of the air conditioner.
Under no circumstances must this work be done by an unqualified individual since failure to carry
out the work properly may result in electric shocks and/or electrical leaks.
Wear protective gloves and safety work clothing during installation, servicing and removal.
When connecting the electrical wires, repairing the electrical parts or undertaking other electrical
jobs, wear gloves to provide protection for electricians, insulating shoes and clothing to provide
protection from electric shocks.
Failure to wear this protective gear may result in electric shocks.
Use wiring that meets the specifications in the Installation Manual and the stipulations in the local
regulations and laws.
Use of wiring which does not meet the specifications may give rise to electric shocks, electrical
leakage, smoking and/or a fire.
Only a qualified installer (∗1) or qualified service person (∗1) is allowed to undertake work at
General heights using a stand of 50 cm or more.
When working at heights, use a ladder which complies with the ISO 14122 standard, and follow
the procedure in the ladder’s instructions.
Also wear a helmet for use in industry as protective gear to undertake the work.
When working at heights, put a sign in place so that no-one will approach the work location,
before proceeding with the work.
Parts and other objects may fall from above, possibly injuring a person below.
Do not touch the aluminum fin of the outdoor unit.
You may injure yourself if you do so. If the fin must be touched for some reason, first put on
protective gloves and safety work clothing, and then proceed.
Do not climb onto or place objects on top of the outdoor unit.
You may fall or the objects may fall off the outdoor unit and result in injury.
When transporting the air conditioner, wear shoes with additional protective toecap.
When transporting the air conditioner, do not hold the bands around the packing carton.
You may injure yourself if the bands should break.
This air conditioner has passed the pressure test as specified in IEC 60335-2-40 Annex EE.
When you access inside of the electric cover to repair electric parts, wait for about five minutes
after turning off the breaker. Do not start repairing immediately. Otherwise you may get electric
shock by touching terminals of high-voltage capacitors. Natural discharge of the capacitor takes
Electric
shock hazard about five minutes.
Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair,
or removal work is being carried out.
There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
When checking the electric parts, removing the cover of the electric parts box of Indoor Unit and/
or front panel of Outdoor Unit inevitably to determine the failure, put a sign “Do not enter” around
the site before the work. Failure to do this may result in third person getting electric shock.
Prohibition Before operating the air conditioner after having completed the work, check that the electrical
parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the
circuit breaker to the ON position. You may receive an electric shock if the power is turned on
without first conducting these checks.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the
electrical parts with the electrical parts box cover of one or more of the indoor units and the
service panel of the outdoor unit removed in order to find out exactly where the trouble lies, wear
insulated heat-resistant gloves, insulated boots and insulated work overalls, and take care to
Stay on avoid touching any live parts.
protection You may receive an electric shock if you fail to heed this warning. Only qualified service person
(∗1) is allowed to do this kind of work.
(∗1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
–8–
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of
the main unit, otherwise an electric shock is caused when a leak occurs. If the earth wire is not
correctly connected, contact an electric engineer for rework.
After completing the repair or relocation work, check that the earth wires are connected properly.
Check earth
wires. Be sure to connect earth wire. (Grounding work) Incomplete earth causes an electric shock.
Do not connect earth wires to gas pipes, water pipes, and lightning rods or earth wires for
telephone wires.
Do not modify the products. Do not also disassemble or modify the parts.
It may cause a fire, electric shock or injury.
Prohibition of
modification.
When any of the electrical parts are to be replaced, ensure that the replacement parts satisfy the
specifications given in the Service Manual (or use the parts contained on the parts list in the
Service Manual).
Use of any parts that do not satisfy the required specifications may give rise to electric shocks,
Use specified smoking and/or a fire.
parts. Replace components only with parts specified by the manufacturer. Other parts may result
in the ignition of refrigerant in the atmosphere due to the refrigerant leak.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the
electrical parts with the electrical parts box cover of one or more of the indoor units and the
service panel of the outdoor unit removed in order to find out exactly where the trouble lies, place
Do not bring "Keep out" signs around the work site before proceeding.
a child close to Third-party individuals may enter the work site and receive electric shocks if this warning is not
the equipment. heeded.
Connect the cut-off lead wires with crimp contact, etc. put the closed end side upward and then
apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
Insulating
measures
When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because
the oil that coats the pipes may otherwise burn.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle.
When using a gas stove, etc. be sure to put out fire before work; otherwise the oil mixed with
refrigerant gas may catch fire.
No fire
2) Do not use a brazing in the closed room.
When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammable material around to the refrigerant cycle; otherwise fire of the brazing
may catch the inflammable material.
–9–
The refrigerant used by this air conditioner is the R32.
Check the used refrigerant name and use tools and materials of the parts, which match with it.
For the products, which use R32 refrigerant, the refrigerant name is indicated at a position on
the outdoor unit where is easy to see.
To prevent miss charging, the route of the service port is changed from one of the former R22.
Be careful for miss charging since a charging port of R32 is the same diameter as that of R410A.
Do not use any refrigerant different from the one specified for complement or replacement.
Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may
result in a failure or explosion of the product or an injury to your body.
For an air conditioner, which uses R32, never use other refrigerant than R32.
For an air conditioner, which uses other refrigerant (R22, R410A etc.), never use R32.
If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating
cycle and an injur y due to breakage may be caused.
If the different type of refrigerants are mixed in, be sure to recharge the refrigerant
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the
refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over
Refrigerant
the specified standard amount is charged and an abnormal high pressure is applied to the inside
of the refrigerating cycle resulted in cause of breakage or injury.
Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute
vacuuming, and then newly recharge the specified amount of liquid refrigerant.
In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other
than R32 into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating
cycle resulted in cause of injury due to breakage.
After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into
the room and flows near a fire source, such as a cooking range, noxious gas may be generated.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device.
The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as
breakage or injury is caused.
After repair work, surely assemble the disassembled parts, and connect and lead the removed
wires as before.
Perform the work so that the cabinet or panel does not catch the inner wires.
Assembly/ If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is
Cabling caused at user’s side.
After the work has finished, be sure to use an insulation tester set (500V MΩ) to check the
resistance is 1MΩ or more between the charge section and the non-charge metal section
(Earth position).
Insulator If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
check
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, it may generate noxious gases, causing a fire.
A case of leakage of the refrigerant and the closed room full with gas is dangerous because a
shortage of oxygen occurs. Be sure to execute ventilation.
Ventilation If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, it may generate noxious gases,
causing a fire.
– 10 –
When the refrigerant gas leaks, find out the leaked position and repair it surely.
If the leaked position cannot be found out and the repair work is interrupted, pump-down and
tighten the service valve, otherwise the refrigerant gas may leak into the room.
When gas touches to fire such as fan heater, stove or cooking stove, it may generate noxious
gases, causing a fire though the refrigerant gas itself is innocuous.
When installing equipment, which includes a large amount of charged refrigerant in a sub-room,
it is necessary that the concentration does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit concentration, an accident of shortage of oxygen is
caused.
Tighten the flare nut with a torque wrench in the specified manner.
Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which
Compulsion may result in refrigerant leakage.
Nitrogen gas must be used for the airtight test.
The charge hose must be connected in such a way that it is not slack.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or
fire is caused.
Install the outdoor unit properly in a location that is durable enough to support the weight of the
outdoor unit. Insufficient durability may cause the outdoor unit to fall, which may result in injury.
Once the repair work has been completed, check for refrigerant leaks, and check the insulation
resistance and water drainage.
Then perform a trial run to check that the air conditioner is running properly.
After repair work has finished, check there is no trouble. If check is not executed, a fire, electric
shock or injury may be caused. For a check, turn off the power breaker.
Check after
repair After repair work (installation of front panel and cabinet) has finished, execute a test run to check
there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front
panel and cabinet.
Check the following matters before a test run after repairing piping.
• Connect the pipes surely and there is no leak of refrigerant.
• The valve is opened.
Do not Running the compressor under condition that the valve closes causes an abnormal high
operate the pressure resulted in damage of the parts of the compressor and etc. and moreover if there is
unit with the leak of refrigerant at connecting section of pipes, the air is suctioned and causes further
valve closed. abnormal high pressure resulted in burst or injury.
Only a qualified installer (∗1) or qualified service person (∗1) is allowed to relocate the air
conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual
since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
Check the following items after reinstallation.
Check after 1) The earth wire is correctly connected.
reinstallation 2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable.
If check is not executed, a fire, an electric shock or an injury is caused.
When the service panel of the outdoor unit is to be opened in order for the compressor or the
area around this part to be repaired immediately after the air conditioner has been shut down, set
the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the
service panel.
If you fail to heed this warning, you will run the risk of burning yourself because the compressor
pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair
work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor,
Cooling check inverter or the areas around these parts to be repaired immediately after the air conditioner has
been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes
before opening the service panel.
If you fail to heed this warning, you will run the risk of burning yourself because the fan motor,
reactor, inverter heat sink and other parts will be very hot to the touch.
In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant
gloves designed to protect electricians.
(∗1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
– 11 –
Only a qualified installer (∗1) or qualified service person (∗1) is allowed to install the air
conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks,
injury, water leakage, noise and/or vibration may result.
Before starting to install the air conditioner, read carefully through the Installation Manual, and
follow its instructions to install the air conditioner.
Do not install the air conditioner in a location that may be subject to a risk of exposing to a
combustible gas.
If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
When transporting the air conditioner, use a forklift truck and when moving the air conditioner by
Installation hand, move the unit with 4 people.
Install a circuit breaker that meets the specifications in the Installation Manual and the stipulations
in the local regulations and laws.
Install the circuit breaker where it can be easily accessed by the agent.
Do not place any combustion appliance in a place where it is directly exposed to the wind of air
conditioner, otherwise it may cause imperfect combustion.
When carrying out the pump-down work shut down the compressor before disconnecting the
refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the
compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the
refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury, etc.
Compulsion When removing the brazing parts of suction and discharge pipe for the compressor, remove them
at the place ventilated well after recovering the refrigerant. Improper recovering may cause the
spurt of the refrigerant and the refrigeration oil, causing an injury.
Do not vent gases to the atmosphere.
Venting gases to the atmosphere is prohibited by the law.
Prohibition
CAUTION
Ensure wearing of gloves when performing any work in order to avoid injury from parts, etc.
Failure to wear the proper protective gloves cause an injury due to the parts, etc.
Wearing of
gloves
When performing the brazing work, check whether refrigerant leaks or remains.
If the leakage refrigerant gas touches a fire source, it may generate noxious gases, causing a fire.
Confirm
Relocation
• Only a qualified installer (∗1) or qualified service person (∗1) is allowed to relocate the air conditioner.
It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks,
injury, water leakage, noise and/or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant
pipe.
Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will
cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level,
and possibly resulting in rupture, injury, etc.
(∗1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
– 12 –
Declaration of Conformity
Manufacturer: TOSHIBA CARRIER CORPORATION
336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN
Complies with the provisions of the “Machinery Directive” (Directive 2006/42/EC) and the regulations
transposing into national law
Note: This declaration becomes invalid if technical or operational modifications are introduced without the
manufacturer’s consent.
Specifications
Sound pressure level (dB(A))
Model Weight (kg)
Cooling Heating
RAV-GP1101AT8-E ∗ ∗ 95
RAV-GP1401AT8-E ∗ ∗ 95
RAV-GP1601AT8-E ∗ ∗ 95
RAV-GP1101AT8J-E ∗ ∗ 95
RAV-GP1401AT8J-E ∗ ∗ 95
RAV-GP1601AT8J-E ∗ ∗ 95
RAV-GP1101AT8-TR ∗ ∗ 95
RAV-GP1401AT8-TR ∗ ∗ 95
RAV-GP1601AT8-TR ∗ ∗ 95
RAV-GP1101AT8J-TR ∗ ∗ 95
RAV-GP1401AT8J-TR ∗ ∗ 95
RAV-GP1601AT8J-TR ∗ ∗ 95
∗ Under 70 dB(A)
– 13 –
Refrigerant R32
This air conditioner adopts a new HFC type refrigerant (R32) which does not deplete the ozone layer.
– 14 –
<Caution items>
1) The opposite side dimension of the air-conditioner’s flared nut using R32 and the shape of the charge
port are the same as those of R410A.
2) Be careful not to charge refrigerant by mistake. Should the different type of refrigerant mix in, be sure to
recharge the refrigerant.
3) Do not mix the other refrigerant or refrigerating oil with the refrigerant.
4) Since the pressure of R32 is 1.6 times higher than that of the former refrigerant (R22), use tools and
parts with high pressure resistance specification similar to R410A.
5) In the installation time, use clean pipe materials and work with great attention so that water and others
do not mix in because pipes are affected by impurities such as water, oxide film, oil, etc. Use the clean
pipes. Be sure to braze while flowing nitrogen gas in the pipe. (Never use gas other than nitrogen gas.)
6) For the earth protection, use a vacuum pump for air purge.
7) R32 refrigerant is Single-component refrigerant that does not change its composition.
Although it is possible to charge the refrigerant with either liquid or gas, charge it with liquid.
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used.
It is necessary to select the most appropriate pipes to conform to the standard.
Use clean pipes or joints to which little impurities adhere.
1) Copper pipe
<Piping>
The pipe thickness, flare-finishing size, flare nut and others differ according to a refrigerant type.
When using a long copper pipe for R32, it is recommended to select “Copper or copper-base pipe without
seam” and one with bonded oil amount 40mg/10m or less.
Also do not use crushed, deformed, discolored (especially inside) pipes.
(Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
Be sure to select the pipes with copper thickness in the table below since the pressure of an air conditioner
using R32 is higher than that of R22.
Nominal Outer Thickness (mm) Make sure not to use a thin copper
diameter diameter (mm) R410A or R32 pipe such as 0.7 mm copper
thickness in the market.
1/2 6.4 0.80
3/8 9.5 0.80
1/2 12.7 0.80
5/8 15.9 1.00
2) Joint
The flare joint and socket joint are used for joints of the copper pipe.
The joints are rarely used for installation of the air conditioner.
However clear impurities when using them.
– 15 –
4. Tools
Note 1 When flaring is carried out for R410A or R32 using the conventional flare tools, adjustment of
projection margin is necessary. For this adjustment, a copper pipe gauge, etc. is necessary.
Note 2 When saturation temperature is described, the gauge manifold differs for R410A and R32.
If saturation temperature reading is required, special tools exclusive for R32 are required.
Note 3 Since R32 has a slight possibility of burning, be sure to use the tools corresponding to R32.
Note 4 Like R410, a Vacuum pump adapter needs installing to prevent a Vacuum pump oil (mineral oil) from
flowing backward into the Charge hose. Mixing of the Vacuum pump oil into R32 refrigerant may cause
a trouble such as generation of sludge, clogging of capillary, etc.
Note 5 Be sure to use those tools after confirming they correspond to each refrigerant.
Note 6 For a refrigerant cylinder exclusive for R32, the paint color (or label color) of the cylinder is set to the
specified color (light blue) together with the indication of the refrigerant name.
Note 7 Although the container specification is the same as R410A, use a recovering container exclusive for
R32 to avoid mixing with other refrigerants.
Note 8 Be careful for miss charging of the refrigerant during work. Miss charging of the refrigerant type may
cause not only damage of the equipment but also a fire etc.
General tools
In addition to the above exclusive tools, the following equipment is necessary as the general tools.
1) Pipe cutter 6) Spanner or Adjustable wrench
2) Reamer 7) Hole core drill
3) Pipe bender 8) Tape measure
4) Level vial 9) Metal saw
5) Screwdriver (+, –)
Also prepare the following equipment for other installation method and run check.
1) Clamp meter 3) Insulation resistance tester (500VMΩ)
2) Thermometer 4) Electroscope
– 16 –
1. SPECIFICATIONS
1-1. Outdoor Unit
1101AT8(J)-E 1401AT8(J)-E 1601AT8(J)-E
Model Outdoor unit RAV-GP
1101AT8(J)-TR 1401AT8(J)-TR 1601AT8(J)-TR
3 phase 380-415, 50Hz
Power supply
(Power exclusive to outdoor is required)
Type Hermetic compressor
Compressor Motor (kW) 3.75 3.75 3.75
Pole 4 4 4
Refrigerant charged (kg) 2.6 2.6 2.6
Refrigerant control Pulse motor valve
Max (m) 75 75 75
Min (m) 3 3 3
Pipe
Height Outdoor lower (m) 30 30 30
Difference Outdoor Height 30 30 30
Height (m) 1,340 1,340 1,340
Outer dimension Width (m) 900 900 900
Depth (m) 320 320 320
Silky shade
Appearance
(Munsell 1Y8.5/0.5)
Total weight (kg) 95 95 95
Heat exchanger Finned tube
Fan Propeller fan
Fan unit Standard air flow (m3/min) 101 103 103
Motor (W) 100+100 100+100 100+100
Connecting pipe Gas side (mm) 15.9 15.9 15.9
(Outdoor unit side) Liquid side (mm) 9.5 9.5 9.5
Sound pressure level Cooling/Heating (dB-A) 49/50 51/52 51/53
Sound power level Cooling/Heating (dB-A) 66/67 68/69 68/70
Outside air temperature cooling (°C) 46 to -15°C
Outside air temperature heating (°C) 15 to -20°C
– 17 –
1-2. Operation Characteristic Curve
• Operation characteristic curve, 50Hz <Super Digital Inverter>
<Cooling> <Heating>
10
15
9 GP160
SP160 14
13
8
12
7 11
10
6
Current (A)
Current (A)
GP140
SP140 8
5
7
4 SP110 6
GP110
5
3
4
• Conditions • Conditions
2 Indoor : DB27˚C/WB19˚C 3 Indoor : DB20˚C
Outdoor : DB35˚C Outdoor : DB7˚C/WB6˚C
Air flow : High 2 Air flow : High
1 Pipe length : 7.5m Pipe length : 7.5m
400V, 50Hz (3 phase) 1 400V, 50Hz (3 phase)
0 0
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 90 100 110
Compressor speed (rps) Compressor speed (rps)
<Cooling> <Heating>
105 120
100 110
95 100
90
90
80
Capacity ratio (%)
Capacity ratio (%)
85
70
80
60
75
50
70
40
65
30
60 20
• Conditions • Conditions
Indoor : DB27˚C/WB19˚C Indoor : DB20˚C
55 Indoor air flow : High 10 Indoor air flow : High
Pipe length : 7.5m Pipe length : 7.5m
50 0
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 -20 -18 -16 -14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10
– 18 –
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. Outdoor Unit
RAV-GP1101AT8(J)-E, -TR RAV-GP1401AT8(J)-E, -TR RAV-GP1601AT8(J)-E, -TR
– 19 –
RBC-TWP30E2, RBC-TWP50E2 (Simultaneous Twin)
B
Inner Inner
diameter DIA D diameter DIA D
(Units: mm)
Model (RBC-) A B C D
– 20 –
RBC-TRP100E (Simultaneous Triple)
<Gas side>
Header assembly
(Units: mm)
300
100
1 pc.
<Liquid side>
Branch pipe assembly
100
1 pc.
Insulator
DIA 15.9
DIA 12.7 DIA 9.5
DIA 6.4
12
10
46
9
28
24
26
– 21 –
3. OUTDOOR UNIT REFRIGERATING CYCLE DIAGRAM
TO sensor
TS sensor
PMV
TL sensor
Pressure
switch
Strainer
P
Heat exchanger
TD sensor DIA 8, 2 rows, 52 stages Distributor Refrigerant pipe
FP1.45, flat fin at liquid side DIA 9.5
Packed valve
In cooling operation
In heating operation Refrigerant pipe
at gas side DIA 15.9
Strainer Ball valve
DIA 25 × L210
Accumulator Rotary compressor
(2500cc) (RX420A3F-27M)
RAV-GP1101 series
Pressure Pipe surface temperature
Compressor Indoor/outdoor
(Mpa) (kg/cm2G) Discharge Suction Indoor heat Outdoor heat drive revolution Indoor fan temp. condition
exchanger exchanger
frequency (rps)
Pd Ps Pd Ps (TD) (TS) (TC) (TL) (TE) Indoor Outdoor
Standard 2.3 1.1 23.5 11.7 80.2 12.9 11.0 44.6 36.9 36.6 HIGH 27/19 35/-
Cooling Overload 3.1 1.5 32.0 14.8 67.0 17.0 16.0 48.0 47.0 35.4 HIGH 32/24 46/-
Low load 2.2 0.7 22.6 7.4 70.0 2.0 1.0 36.0 16.0 33.0 LOW 18/15.5 -15/-
Standard 2.5 0.8 25.9 8.2 87.2 3.2 41.0 7.6 3.0 40.2 HIGH 20/- 7/6
Heating Overload 3.4 1.4 35.1 13.8 77.0 20.0 53.0 22.0 19.0 26.4 LOW 30/- 24/18
Low load 2.0 0.2 20.0 1.7 78.0 -25.0 31.0 -10.0 -23.0 90.6 HIGH 15/- -20/-
RAV-GP1401 series
Pressure Pipe surface temperature
Compressor Indoor/outdoor
(Mpa) (kg/cm2G) Discharge Suction Indoor heat Outdoor heat drive revolution Indoor fan temp. condition
exchanger exchanger
frequency (rps)
Pd Ps Pd Ps (TD) (TS) (TC) (TL) (TE) Indoor Outdoor
Standard 2.4 1.0 24.0 10.6 89.7 9.3 8.0 46.8 37.6 50.4 HIGH 27/19 35/-
Cooling Overload 3.3 1.3 34.0 13.4 73.0 18.0 17.0 51.0 50.0 42.0 HIGH 32/24 46/-
Low load 2.2 0.7 22.7 7.5 71.0 3.0 2.0 37.0 16.0 33.0 LOW 18/15.5 -15/-
Standard 2.7 0.8 27.8 8.2 90.8 1.5 44.0 7.6 2.7 51.6 HIGH 20/- 7/6
Heating Overload 3.3 1.2 34.1 12.3 76.0 17.0 52.0 20.0 17.0 26.4 LOW 30/- 24/18
Low load 1.9 0.2 19.5 1.7 77.0 -25.0 30.0 -10.0 -23.0 90.6 HIGH 15/- -20/-
RAV-GP1601 series
Pressure Pipe surface temperature
Compressor Indoor/outdoor
(Mpa) (kg/cm2G) Discharge Suction Indoor heat Outdoor heat drive revolution Indoor fan temp. condition
exchanger exchanger
frequency (rps)
Pd Ps Pd Ps (TD) (TS) (TC) (TL) (TE) Indoor Outdoor
Standard 2.4 1.0 24.1 10.3 98.6 8.7 7.0 48.4 38.3 61.2 HIGH 27/19 35/-
Cooling Overload 3.4 1.2 35.0 12.2 77.0 19.0 18.0 54.0 53.0 48.6 HIGH 32/24 46/-
Low load 2.2 0.8 22.7 7.6 72.0 4.0 3.0 37.0 17.0 33.0 LOW 18/15.5 -15/-
Standard 3.0 0.8 30.5 8.2 100.9 0.7 48.0 7.6 2.4 60.0 HIGH 20/- 7/6
Heating Overload 3.2 1.2 33.0 12.3 75.0 17.0 51.0 20.0 17.0 26.4 LOW 30/- 24/18
Low load 1.9 0.2 19.5 1.7 77.0 -25.0 30.0 -10.0 -23.0 90.6 HIGH 15/- -20/-
∗ This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
meter becomes 2 times of No. of compressor revolutions (rps).
– 22 –
4. WIRING DIAGRAM
4-1. Outdoor Unit
RAV-GP1101AT8(J)-E, -TR RAV-GP1401AT8(J)-E, -TR RAV-GP1601AT8(J)-E, -TR
– 23 –
5. SPECIFICATIONS OF ELECTRICAL PARTS
5-1. Outdoor Unit
No. Parts name Type Specifications
1 Compressor RX420A3F-27M —
23 Fuse (Mounted on P.C. board, MCC-1599) FJL 250V 3.15A T3.15 A, AC 250 V
– 24 –
6. REFRIGERANT R32
This air conditioner adopts the R32 refrigerant which 7. Be sure to carry out installation or removal
does not damage the ozone layer. according to the installation manual.
The working pressure of the new refrigerant R32 is Improper installation may cause refrigeration
1.6 times higher than conventional refrigerant (R22). trouble, water leakage, electric shock, fire, etc.
The refrigerating oil is also changed in accordance 8. Unauthorized modifications to the air conditioner
with change of refrigerant, so be careful that water, may be dangerous. If a breakdown occurs please
dust, and existing refrigerant or refrigerating oil are call a qualified air conditioner technician or
not entered in the refrigerant cycle of the air electrician.
conditioner using the new refrigerant during Improper repair may result in water leakage,
installation work or servicing time. electric shock and fire, etc.
The next section describes the precautions for air
conditioner using the new refrigerant.
Conforming to contents of the next section together
6-2. Refrigerant Piping Installation
with the general cautions included in this manual, 6-2-1. Piping Materials and Joints Used
perform the correct and safe work.
For the refrigerant piping installation, copper pipes
and joints are mainly used.
6-1. Safety During Installation/Servicing Copper pipes and joints suitable for the refrigerant
As R32’s pressure is about 1.6 times higher than that must be chosen and installed.
of R22, improper installation/servicing may cause a Furthermore, it is necessary to use clean copper
serious trouble. By using tools and materials pipes and joints whose interior surfaces are less
exclusive for R32, it is necessary to carry out affected by contaminants.
installation/servicing safely while taking the following
precautions into consideration. 1. Copper Pipes
1. Never use refrigerant other than R32 in an air It is necessary to use seamless copper pipes
conditioner which is designed to operate with R32. which are made of either copper or copper alloy
If other refrigerant than R32 is mixed, pressure in and it is desirable that the amount of residual oil is
the refrigeration cycle becomes abnormally high, less than 40 mg/10 m.
and it may cause personal injury, etc. by a rupture. Do not use copper pipes having a collapsed,
2. Confirm the used refrigerant name, and use tools deformed or discolored portion (especially on the
and materials exclusive for the refrigerant R32. interior surface).
The refrigerant name R32 is indicated on the Otherwise, the expansion valve or capillary tube
visible place of the outdoor unit of the air may become blocked with contaminants.
conditioner using R32 as refrigerant. As an air conditioner using R32 incurs pressure
A diameter of the charge port for R32 is the same higher than when using R22, it is necessary to
as that for the R410A’s. Be careful not to charge choose adequate materials.
the refrigerant by mistake. Thicknesses of copper pipes used with R32 are as
3. If a refrigeration gas leakage occurs during shown in Table 6-2-1. Never use copper pipes
installation/servicing, be sure to ventilate fully. thinner than 0.8mm even when it is available on
If the refrigerant gas comes into contact with fire, a the market.
poisonous gas may occur.
4. When installing or removing an air conditioner, do NOTE
not allow air or moisture to remain in the
refrigeration cycle. Refer to the “6-6. Instructions for Re-use Piping of
Otherwise, pressure in the refrigeration cycle may R22 or R407C”.
become abnormally high so that a rupture or
personal injury may be caused.
5. After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater, space
heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that, even
when refrigerant leaks, its concentration does not
exceed the marginal level.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal level, an
oxygen starvation accident may result.
– 25 –
Table 6-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
1. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for piping whose outer diameter exceeds 20
mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 6-2-3 to 6-2-5 below.
b) Socket Joints
Socket joints are such that they are braced for connections, and used mainly for thick piping whose
diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 6-2-2.
– 26 –
c) Insertion of Flare Nut
d) Flare Processing
DIA D
Make certain that a clamp bar and copper pipe have been A
cleaned.
By means of the clamp bar, perform the flare processing
correctly.
Use either a flare tool for R410A / R32 or conventional flare
tool.
Flare processing dimensions differ according to the type of
flare tool. Fig. 6-2-1 Flare processing dimensions
When using a conventional flare tool, be sure to secure
“dimension A” by using a gauge for size adjustment.
Table 6-2-3 Dimensions related to flare processing for R410A or R32 / R22
A (mm)
Outer
Nominal Thickness Conventional flare tool Conventional flare tool
diameter Flare tool for
diameter (mm) (R410A or R32) (R22)
(mm) R410A, R22
clutch type
Clutch type Wing nut type Clutch type Wing nut type
1/4 6.4 0.8 0 to 0.5 1.0 to 1.5 1.5 to 2.0 0.5 to 1.0 1.0 to 1.5
3/8 9.5 0.8 0 to 0.5 1.0 to 1.5 1.5 to 2.0 0.5 to 1.0 1.0 to 1.5
1/2 12.7 0.8 0 to 0.5 1.0 to 1.5 2.0 to 2.5 0.5 to 1.0 1.5 to 2.0
5/8 15.9 1.0 0 to 0.5 1.0 to 1.5 2.0 to 2.5 0.5 to 1.0 1.5 to 2.0
Table 6-2-4 Flare and flare nut dimensions for R410A or R32
Dimension (mm)
Nominal Outer diameter Thickness Flare nut width
diameter (mm) (mm) (mm)
A B C D
Dimension (mm)
Nominal Outer diameter Thickness Flare nut width
diameter (mm) (mm) (mm)
A B C D
– 27 –
6˚
to 4
45˚
A B C D
43˚
to 4
5˚
Fig. 6-2-2 Relations between flare nut and flare seal surface
NOTE
When applying oil to the flare surface, be sure to use oil designated by the manufacturer.
If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 6-2-6 Tightening torque of flare for R410A or R32 [Reference values]
– 28 –
6-3. Tools
6-3-1. Required Tools
Refer to the “4. Tools” (Page 16)
Place the handle of the gauge manifold Low in the (For refrigerant charging, see the figure below.)
fully opened position, and turn on the vacuum pump’s
power switch. Then, evacuating the refrigerant in the
cycle.
Opened
(Gas side)
Refrigerant cylinder
(With siphon pipe)
Service valve
Check valve
Closed
Open/Close valve
for charging
Service port
– 29 –
1) Be sure to make setting so that liquid can be charged.
2) When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
R32 refrigerant is a Single-component refrigerant that does not change its composition.
Although it is possible to charge the refrigerant with either liquid or gas, charge it with liquid.
(If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner
change.)
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold Gauge manifold
OUTDOOR unit OUTDOOR unit
cylinder
Refrigerant
Refrigerant
cylinder
Electronic Electronic
balance balance
Siphon
Fig. 6-4-2
6-5. Brazing of Pipes 1) Phosphor bronze brazing filler tends to react with
6-5-1. Materials for Brazing sulfur and produce a fragile compound water
solution, which may cause a gas leakage.
1. Silver brazing filler Therefore, use any other type of brazing filler at a
Silver brazing filler is an alloy mainly composed hot spring resort, etc., and coat the surface with a
of silver and copper. paint.
It is used to join iron, copper or copper alloy, and 2) When performing brazing again at time of
is relatively expensive though it excels in solder servicing, use the same type of brazing filler.
ability.
– 30 –
2. Characteristics required for flux 6-5-3. Brazing
• Activated temperature of flux coincides with the As brazing work requires sophisticated techniques,
brazing temperature. experiences based upon a theoretical knowledge, it
• Due to a wide effective temperature range, flux is must be performed by a person qualified.
hard to carbonize. In order to prevent the oxide film from occurring in the
• It is easy to remove slag after brazing. pipe interior during brazing, it is effective to proceed
with brazing while letting dry Nitrogen gas flow.
• The corrosive action to the treated metal and
brazing filler is minimum.
• It excels in coating performance and is harmless Never use gas other than Nitrogen gas.
to the human body.
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and 1. Brazing method to prevent oxidation
shape of treated metal, type of brazing filler and 1) Attach a reducing valve and a flow-meter to the
brazing method, etc. Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping material,
3. Types of flux and attach a flow-meter to the cylinder.
• Noncorrosive flux 3) Apply a seal onto the clearance between the
Generally, it is a compound of borax and boric piping material and inserted copper pipe for
acid. Nitrogen in order to prevent backflow of the
It is effective in case where the brazing Nitrogen gas.
temperature is higher than 800°C. 4) When the Nitrogen gas is flowing, be sure to
keep the piping end open.
• Activated flux
5) Adjust the flow rate of Nitrogen gas so that it is
Most of fluxes generally used for silver brazing
lower than 0.05 m³/Hr or 0.02 MPa (0.2kgf/cm²)
are this type.
by means of the reducing valve.
It features an increased oxide film removing
capability due to the addition of compounds such 6) After performing the steps above, keep the
as potassium fluoride, potassium chloride and Nitrogen gas flowing until the pipe cools down to
sodium fluoride to the borax-boric acid a certain extent (temperature at which pipes are
compound. touchable with hands).
7) Remove the flux completely after brazing.
4. Piping materials for brazing and used
brazing filler/flux
– 31 –
6-6. Instructions for Re-use Piping of R22 or R407C
Instruction of Works: 5. A dryer on the market is attached to the existing
The existing R22 and R407C piping can be pipes.
reused for our digital inverter R32 products • There is possibility that copper green rust generated.
installations. 6. Check the oil when the existing air conditioner was
removed after refrigerant had been recovered.
WARNING In this case, if the oil is judged as clearly different
compared with normal oil
Confirming the existence of scratches or dents on the
• The refrigerator oil is copper rust green :
existing pipes and confirming the reliability of the pipe
There is possibility that moisture is mixed with
strength are conventionally referred to the local site.
the oil and rust forms inside of the pipe.
If the specified conditions can be cleared, it is
possible to update existing R22 and R407C pipes to • There is discolored oil, a large quantity of the
those for R32 models. remains, or bad smell.
• A large quantity of sparkle remained wear-out
powder is observed in the refrigerator oil.
6-6-1. Basic Conditions Needed to Reuse the 7. The air conditioner which compressor was
exchanged due to a trouble compressor.
Existing Pipe
When the discolored oil, a large quantity of the
Check and observe three conditions of the refrigerant remains, mixture of foreign matter, or a large
piping works. quantity of sparkle remained wear-out powder is
1. Dry (There is no moisture inside of the pipes.) observed, the cause of trouble will occur.
2. Clean (There is no dust inside of the pipes.) 8. Installation and removal of the air conditioner are
3. Tight (There is no refrigerant leak.) repeated with temporary installation by lease and etc.
9. In case that type of the refrigerator oil of the
existing air conditioner is other than the following
6-6-2. Restricted Items to Use the Existing
oil (Mineral oil), Suniso, Freol-S, MS (Synthetic oil),
Pipes alkyl benzene (HAB, Barrel-freeze), ester series,
In the following cases, the existing pipes cannot be PVE only of ether series.
reused as they are. Clean the existing pipes or • Winding-insulation of the compressor may
exchange them with new pipes. become inferior.
1. When a scratch or dent is heavy, be sure to use NOTE
the new pipes for the works.
2. When the thickness of the existing pipe is thinner The above descriptions are results of confirmation by
than the specified “Pipe diameter and thickness” our company and they are views on our air
be sure to use the new pipes for the works. conditioners, but they do not guarantee the use of the
• The operating pressure of R32 is high. If there is existing pipes of the air conditioner that adopted
a scratch or dent on the pipe or a thinner pipe is R410A in other companies.
used, the pressure strength may be inadequate,
which may cause the pipe to break in the worst 6-6-3. Branching Pipe for Simultaneous
case. Operation System
• In the concurrent twin system, when TOSHIBA-
∗ Pipe diameter and thickness (mm) specified branching pipe is used, it can be reused.
Branching pipe model name:
Reference outside Wall thickness
diameter (mm) (mm)
Material RBC-TWP30E, RBC-TWP50E, RBC-TRP100E
6.4 0.8 —
On the existing air conditioner for simultaneous
operation system (twin system), there is a case of
9.5 0.8 —
using branch pipe that has insufficient compressive
12.7 0.8 — strength. In this case please change it to the branch
15.9 1.0 — pipe for R32 or R410A.
• In case that the pipe diameter is DIA 12.7 mm or 6-6-4. Curing of Pipes
less and the thickness is less than 0.7 mm, be When removing and opening the indoor unit or
sure to use the new pipes for works. outdoor unit for a long time, cure the pipes as follows:
3. The pipes are left as coming out or gas leaks. • Otherwise rust may forms when moisture or foreign
(Poor refrigerant) matter due to dewing enters in the pipes.
• There is possibility that rain water or air including • The rust cannot be removed by cleaning, and a
moisture enters in the pipe. new piping work is necessary.
4. Refrigerant recovery is impossible.
(Refrigerant recovery by the pump-down operation Place position Term Curing manner
on the existing air conditioner) 1 month or more Pinching
Outdoors
• There is possibility that a large quantity of poor Less than 1 month
Pinching or taping
oil or moisture remains inside of the pipe. Indoors Every time
– 32 –
6-6-5. Final Installation Checks
NO
Is it possible to operate the existing air conditioner?
YES
NO
Test run
– 33 –
6-6-6. Handling of Existing Pipe 6-6-7. Recovering Refrigerant
When using the existing pipe, carefully check it for Use the refrigerant recovery equipment to recover the
the following: refrigerant.
• Wall thickness (within the specified range)
• Scratches and dents 6-7. Charging additional refrigerant
• Water, oil, dirt, or dust in the pipe Amount of additional refrigerant shall be restricted by
• Flare looseness and leakage from welds the following explanation to ensure the reliability.
• Deterioration of copper pipe and heat insulator Miss-charging leads to the abnormal high pressure in
• Before recovering the refrigerant in the existing the refrigerant cycle, causing a rupture, an injury and
system, perform a cooling operation for at least 30 a compressor malfunction.
minutes.
6-7-1. [Assumed gas leak]
Cautions for using existing pipe The refrigerant can be charged only when the
• Do not reuse a flare nut to prevent gas leaks. amount of a leak such as a slow-leak found at the
Replace it with the supplied flare nut and then installation work can be ensured that it is within the
process it to a flare. additional limits shown in the following.
• Blow nitrogen gas or use an appropriate means to Recharge the refrigerant if the amount of leakage is
keep the inside of the pipe clean. unknown when you feel “Cooling is not working well”
If discolored oil or much residue is discharged, or “Heating is not working well”.
wash the pipe.
• Check welds, if any, on the pipe for gas leaks. 6-7-2. [Limiting the additional charge]
• There may be a problem with the pressure • The maximum amount of additional refrigerant shall
resistance of the branch pipes of the existing be up to 10 % of the normal amount of the
piping. refrigerant.
Replace them with branch pipes (sold separately). If no improvement in symptoms can be found at the
above limitation, recover all gases and recharge the
When the pipe corresponds to any of the following, normal amount of refrigerant.
do not use it. Install a new pipe instead. • If the slow leak is found at the installation work and
• The pipe has been opened (disconnected from the connection pipe length is 15 m or less, tighten
indoor unit or outdoor unit) for a long period. the flare nut at the leak point and do not add the
• The pipe has been connected to an outdoor unit refrigerant.
that does not use refrigerant R22, R410A, R32
R407C. 6-7-3. [Cautions on charging additional
• The existing pipe must have a wall thickness equal refrigerant]
to or larger than the following thicknesses.
• When charging additional refrigerant, use a
Reference outside Wall thickness
balance with an accuracy of more than 10g scale.
diameter (mm) (mm)
Material Do not use a health-meter etc.
• If the refrigerant gas leaks, find the leakage point
6.4 0.8 —
and repair it securely. Though the refrigerant gas
9.5 0.8 — itself is innocuous, if it touch a fire source such as
fan heater, stove or kitchen stove, noxious gas may
12.7 0.8 — occur.
15.9 1.0 — • When charging the refrigerant, charge with liquid
refrigerant.
19.1 1.2 —
Work carefully and charge it little by little since it
22.2 1.0 Half hard may be rapidly charged due to the liquid state.
28.6 1.0 Half hard
– 34 –
6-8. General safety precautions for using R32 refrigerant
6-8-1. Recovery 6-8-2. Decommissioning
• When removing refrigerant from a system, either for • Before carrying out this procedure, it is essential
servicing or decommissioning, it is recommended that the technician is completely familiar with the
good practice that all refrigerants are removed equipment and all its details. Only a qualified
safely. installer (∗1) or qualified service person (∗1) is
• When transferring refrigerant into cylinders, ensure allowed to do this work.
that only appropriate refrigerant recovery cylinders • It is recommended good practice that all
are employed. refrigerants are recovered safely.
• Ensure that the correct number of cylinders for • Prior to the task being carried out, an oil and
holding the total system charge are available. refrigerant sample shall be taken in case analysis is
• All cylinders to be used are designated for the required prior to re-use of reclaimed refrigerant.
recovered refrigerant and labelled for that • It is essential that electrical power is available
refrigerant before the task is commenced.
(i.e. special cylinders for the recovery of
refrigerant).
• Cylinders shall be complete with pressure relief a) Become familiar with the equipment and its
valve and associated shut-off valves in good operation.
working order. b) Isolate system electrically.
• Empty recovery cylinders are evacuated and, if c) Before attempting the procedure ensure that :
possible, cooled before recovery occurs. • Mechanical handling equipment is available, if
required, for handling refrigerant cylinders;
• The recovery equipment shall be in good working
• All personal protective equipment is available
order with a set of instructions concerning the
and being used correctly;
equipment that is at hand and shall be suitable for
• The recovery process is supervised at all times
the recovery of mildly flammable refrigerants.
by a competent person;
• In addition, a set of calibrated weighing scales shall • Recovery equipment and cylinders conform to
be available and in good working order. the appropriate standards.
• Hoses shall be complete with leak-free disconnect d) Pump down refrigerant system, if possible.
couplings and in good condition. e) If a vacuum is not possible, make a manifold so
• Before using recovery machine check that it is that refrigerant can be removed from the various
satisfactory working order, has been properly parts of the system.
maintained and that any associated electrical f) Make sure that cylinder is situated on the scales
components are sealed to prevent ignition in the before recovery takes place.
event of a refrigerant release. g) Start the recovery machine and operate in
• Consult manufacturer if in doubt. accordance with manufacturer’s instructions.
• The recovered refrigerant shall be returned to the h) Do not overfill cylinders (No more than 80%
refrigerant supplier in the correct recovery cylinder, volume liquid change).
and the relevant Waste Transfer Note arranged. i) Do not exceed the maximum working pressure of
the cylinder, even temporarily.
• Do not mix refrigerants in recovery units and j) When the cylinders have been filled correctly and
especially not in cylinders. the process complete, make sure that the
• If compressors or compressor oils are to be cylinders and the equipment are removed from
removed, ensure that they have been evacuated to site promptly and all isolation valves on the
an acceptable level to make certain that mildly equipment are closed off.
flammable refrigerant does not remain within the k) Recovered refrigerant shall not be changed into
lubricant. another refrigerant system unless it has been
• The evacuation process shall be carried out prior to cleaned and checked.
returning the compressor to the suppliers.
• Only electric heating to the compressor body shall (*1) Refer to the “Definition of Qualified Installer or
be employed to accelerate this process. Qualified Service Person.”
• When oil is drained from a system, it shall be
carried out safely. 6-8-3. Labelling
• Equipment shall be labelled stating that it has been
de-commissioned and emptied of refrigerant.
• The label shall be dated and signed.
• Ensure that are labels on the equipment stating the
equipment contains mildly flammable refrigerant.
– 35 –
7. CIRCUIT CONFIGURATION AND CONTROL
SPECIFICATIONS
7-1. Outdoor Unit Control
7-1-1. Print Circuit Board, MCC-1596 (Compressor IPDU)
CN13 (Black)
Terminal for power relay
F02
Electric circuit protective fuse
(500V, 31.5A)
CN12 (White)
Terminal for MCC-1600 (CN17)
F01
Electric circuit protective fuse
(500V, 31.5A)
CN11 (Red)
Terminal for power relay
CN04 (Red)
Terminal for PTC thermistor
CN211 (Red), CN212 (White), CN213 (Black) CN19 (Yellow), CN20 (Yellow)
Compressor output terminal Terminal for reactor CH78
– 36 –
7-1-2. Print Circuit Board, MCC-1597 (Fan Motor IPDU)
– 37 –
7-1-3. Print Circuit Board, MCC-1599 (Interface (CDB))
CN02 (Red)
Connector for CN802 (White)
MCC-1600 (CN10 and CN19) Connector for MCC-1597 (CN504)
F01
CN700 (Yellow) Power supply protective fuse
4-way valve connector (250V, 3.15A)
Temp.sensor connector
CN604 (White) TL sensor
CN603 (White) TD sensor
CN602 (Yellow) TO sensor
CN601 (White) TE sensor
CN600 (White) TS sensor
Indoor/Outdoor communication
signal LED
CN690 (Green) CN609 (Blue) CN710 (White) D503 (Green), (Outdoor → Indoor)
High-pressure Case thermostat connector PMV1 Connector D502 (Orange), (Indoor → Outdoor)
switch connector
– 38 –
7-1-4. Print Circuit Board, MCC-1600 (Noise Filter)
F01
Varistor protective fuse
(250V, 6.3A)
CN06 (White)
Power supply terminal (L2)
CN17 (White)
F02 Terminal for
MCC-1596 (CN02)
Varistor protective fuse
(250V, 6.3A) CN18 (Black)
Terminal for
power relay
CN07 (Black)
Power supply terminal (L3) CN19 (Gray)
Terminal for
F03 MCC-1599 (CN02)
Varistor protective fuse
(250V, 6.3A) CN09 (Brown)
Terminal for
grounding
CN20 (White)
Power supply terminal (L2) CN23 (Red)
Connector for
MCC-1597 (CN500)
CN08 (Gray)
Neutral terminal
– 39 –
7-2. Outline of Main Controls
1. PMV (Pulse Motor Valve) control
1) PMV is controlled between 30 and 500 pulses during operation.
2) In cooling operation, PMV is usually controlled with the temperature difference between TS sensor and
TC sensor aiming 1 to 4K as the target value.
3) In heating operation, PMV is usually controlled with the temperature difference between TS sensor and
TE sensor aiming –1 to 4K as the target value.
4) When the cycle excessively heated in both cooling and heating operation, PMV is controlled by TD
sensor. The target value is usually 91°C in cooling operation and 96°C in heating operation.
REQUIREMENT
A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the
compressor life. In a case of trouble on the compressor, be sure to check there is no trouble in the resistance
value or the refrigerating cycle of each sensor after repair and then start the operation.
TD [˚C]
Abnormal stop
111
Frequency normal down
109
Frequency slow down
106
Frequency hold
103
Frequency slow up
(Up to command)
96
As command is
– 40 –
3. Outdoor fan control
Revolution frequency allocation of fan taps [rpm]
W1 W2 W3 W4 W5 W6 W7 W8 W9 WA WB WC WD WE
GP110 to Up 200 240 240 260 320 380 480 500 530 610 640 660 720 780
GP160 Down — — 200 280 360 400 500 520 550 630 660 700 740 820
∗ : WB for GP110
3-2) Heating fan control
c The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency.
(Control from minimum W1 to maximum (according to the following table))
d For 3 minutes after the operation has started, the maximum fan tap corresponding to the zone in
the following table is fixed and then the fan is controlled by temperature of TE sensor.
TE [˚C] e When TE ≥ 24°C continues for 5 minutes, the
compressor stops.
–2 taps / 20 sec. (Up to W1) It is the same status as the normal thermostat-
Stop timer count OFF without trouble display.
24 The compressor restarts after approx. 2 minutes
–2 taps / 20 sec. (Up to W1) 30 seconds and this intermittent operation is not
21 abnormal.
–1 tap / 20 sec. (Up to W1) f In case that the status in item e generates
18 frequently, stain on filter of the suction part of the
Revolution frequency hold indoor unit is considered.
Clean the filter and then restart the operation.
15
+1 tap / 20 sec
(Up to the maximum tap of each zone)
– 41 –
4. Coil heating control
1) This control function heats the compressor by turning on the stopped compressor instead of a case
heater.
It purposes to prevent stagnation of the refrigerant inside of the compressor.
2) As usual, turn on power of the compressor for the specified time before a test run after installation;
otherwise a trouble of the compressor may be caused.
As same as a test run, it is recommended to turn on power of the compressor beforehand when starting
operation after power of the compressor has been interrupted and left as it is for a long time.
3) A judgment for electricity is performed by TD and TO sensors.
If TO sensor is trouble, a backup control is automatically performed by TE sensor.
For a case of TO sensor trouble, judge it with outdoor LED display.
4) For every model, the power is turned off when TD is 30°C or more.
REQUIREMENT
While heating the winding wire by applying a current to it, an abnormal sound may be generated. It is no
abnormality.
Current [A]
Frequency down
I1
Hold Hold
I1–1.0
Normal operation
– 42 –
7. Current release value shift control Current release control value (I1)
1) This control purposes to prevent troubles of the [A]
electronic parts such as the compressor driving Temperature range GP110 GP140 GP160
elements and the compressor during cooling
operation. 47˚C≤ TO 7.5 7.5 7.5
2) The current release control value (I1) is selected 39˚C≤ To < 47˚C 7.5 8.7 9.6
from the following table according to TO sensor TO < 39˚C 9.6 9.6 9.6
value.
TO < –5˚C 7.5 8.7 9.6
TO trouble 7.5 7.5 7.5
HEAT COOL
HEAT TC / COOL TL
[˚C] Abnormal stop TC TL
a
Frequency normal down a 62°C 63°C
b
Frequency slow down b 57°C 62°C
c
Frequency hold c 55°C 60°C
d
Frequency slow up (Up to command) d 53°C 58°C
e
As command is
e 49°C 54°C
– 43 –
10. Defrost control
1) In heating operation, defrost operation is performed when TE sensor satisfies any condition in A zone to
D zone.
2) During defrosting operation, it finishes if TE sensor continued 12°C or higher for 3 seconds or continued
7°C ≤ TE < 12°C for 1 minute.
The defrost operation also finishes when it continued for 10 minutes even if TE sensor temperature was
7°C or lower.
3) After defrost operation was reset, the compressor stopped for approx. 40 seconds and then the heating
operation starts.
TE [˚C] 0 10 15 39 45 55 d [min.]
–2
–5
A zone
–10
B zone D zone
–23
∗ C zone
* The minimum TE value and To value between 10 and 15 minutes after heating operation has started
are stored in memory as TEO and ToO, respectively.
In normal To In abnormal To
A zone When status (TEO – TE) – (ToO – To) ≥ 3˚C When status (TEO – TE) ≥ 3˚C
continued for 20 seconds continued for 20 seconds
B zone When status (TEO – TE) – (ToO – To) ≥ 2˚C When status (TEO – TE) ≥ 2˚C
continued for 20 seconds continued for 20 seconds
C zone When status (TE ≤ –23˚C) continued for 20 seconds
D zone When compressor operation status of TE < –2˚C is calculated by d portion
– 44 –
8. TROUBLESHOOTING
8-1. Summary of Troubleshooting
<Wired remote controller type>
1. Before troubleshooting
1) Required tools/instruments
• + and – screwdrivers, spanners, long-nose pliers, nippers, push pins for reset switch
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
a) The following operations are normal.
1. Compressor does not operate.
• Is the air conditioner being controlled by the 3-minute protective function?
• Is it in standby status though the room temperature has reached the setup temperature?
• Is it being operated in timer mode or fan mode?
• Is an overflow trouble detected on the indoor unit?
• Is the remote controller set in “heating” under the high outside air temperature?
2. Indoor fan does not operate.
• Is the air conditioner being controlled by the cool air discharge preventive function in “heating”?
3. Outdoor fan does not operate or fan speed changes.
• Does high-temperature release operation control work in heating operation?
• Does outside low-temperature operation control work in cooling operation?
• Is defrost operation performed?
4. ON/OFF operation cannot be performed from remote controller.
• Is it being operated by the central control system?
• Is an automatic address being set up?
(When the power is turned on at the first time or when indoor unit address setting is changed, the
operation cannot be performed for maximum approx. 5 minutes after power-ON.)
• Is being carried out a test run by operation of the outdoor unit?
5. LED for the indoor and outdoor communication does not flash.
∗ service switches (SW01 or SW02) on the outdoor unit allow
• Does standby power saving operation control work?
(LED does flash, when the inside and outside communication is being stopped during the standby
power saving control. Operating service switches (SW01 or SW02) on the outdoor unit allow to
restart the communication.)
b) Did you return the wiring to the initial positions?
c) Are connecting wiring of indoor unit and remote controller correct?
2. Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Trouble → Confirmation of check code display → Check trouble position and parts.
on wired remote controller
NOTE
For cause of a trouble except the items to be checked, miss diagnosis of microcomputer due to outer noise or
power conditions is considered. If there is any noise source, change the wires of the remote controller to shield
wires.
– 45 –
<Wireless remote controller type>
1. Before troubleshooting
1) Required tools/instruments
• + and – screwdrivers, spanners, long-nose pliers, nippers, etc.
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
a) The following operations are normal.
1. Compressor does not operate.
• Is the air conditioner being controlled by the 3-minute protective function?
• Is it in standby status though the room temperature has reached the setup temperature?
• Is it being operated in timer mode or fan mode?
• Is the remote controller set in “heating” under the high outside air temperature?
2. Indoor fan does not operate.
• Is the air conditioner being controlled by the cool air discharge preventive function in “heating”?
3. Outdoor fan does not operate or fan speed changes.
• Does high-temperature release operation control work in heating operation?
• Does outside low-temperature operation control work in cooling operation?
• Is defrost operation performed?
4. ON/OFF operation cannot be performed from remote controller.
• Is the air conditioner in forced operation?
• Is it being operated by the central control system?
• Is an automatic address being set up?
(When the power is turned on at the first time or when indoor unit address setting is changed, the
operation cannot be performed for maximum approx. 5 minutes after power-ON.)
• Is a test run of the air conditioner being carried out?
5. LED for the indoor and outdoor communication does not flash.
∗ LED is placed on the outdoor unit control board. (CDB P.C. board)
• Does standby power saving operation control work?
(LED does flash, when the inside and outside communication is being stopped during the standby
power saving control. Operating service switches (SW01 or SW02) on the outdoor unit allow to
restart the communication.)
b) Did you return the wiring to the initial positions?
c) Are connecting wires between indoor unit and receiving unit correct?
2. Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Check trouble
Trouble → Confirmation of lamp display →
position and parts.
NOTE
For cause of a trouble except the items to be checked, miss diagnosis of microcomputer due to outer noise or
power conditions is considered. If there is any noise source, change the wires of the remote controller to shield
wires.
– 46 –
Outline of troubleshooting
The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with
the following method.
Method to judge the troubleshooting by flashing indication on indoor unit lamp display
(the signal receiving unit of wireless remote controller)
When the protective function operates the self-diagnosis contents appear in flashing indication on indoor unit
lamp display.
— Power supply OFF or miss-wiring between receiving unit and indoor unit
No indication at all
P05
Negative phase detection trouble
P07 Heat sink overheat trouble Outdoor unit trouble
Gas leak detection trouble
Operation Timer Ready P15
P22
Outdoor unit: Outdoor unit trouble
Protective device of
P26 Outdoor unit: Inverter Idc operation ∗1
outdoor unit worked.
Outdoor unit: Position detection trouble
P29
– 47 –
Lamp indication Check code Cause of trouble occurrence
F04
Simultaneous flash
Simultaneous flash
H01
Compressor break down
Operation Timer Ready H02 Outdoor compressor system trouble ∗1
Compressor lock
H03 Current detection circuit trouble } Power supply, outdoor P.C. board trouble
Case thermostat worked. } Compressor overheat, outdoor wiring trouble
Flash H04
PS pressure sensor trouble Outdoor unit
low pressure protective operation low pressure system trouble
H06
∗1: These are representative examples and the check code differs according to the outdoor unit to be combined.
– 48 –
Others (Other than Check Code)
Simultaneous flash
– 49 –
8-1-1. Monitor Function of Remote Controller
Calling of sensor temperature display
<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service
monitor mode from the remote controller.
<Procedure>
the CODE No. of data to be monitored. RESET TEST SET CL SWING/FIX UNIT
T LOUVER
2 4 1 3
<Operation procedure>
1 2 3 4
Returned to usual display
CODE No. Data name Unit CODE No. Data name Unit
01 Room temperature ˚C 60 Outdoor heat exchanger (Coil) temperature (TE) ˚C
(Remote controller) 61 Outside temperature (TO) ˚C
02 Indoor room air temperature (TA) ˚C
Outdoor unit data
Ø
3 Push button to select the indoor unit to be monitored.
UNIT LOUVER
Each data of the indoor unit and its outdoor units can be monitored.
Ø
4 Pushing button returns the status to the usual display.
∗1 The indoor discharge temperature of CODE No. [F8] is the estimated value from TC or TCJ sensor.
Use this value to check discharge temperature at test run.
(A discharge temperature sensor is not provided to this model.)
• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.
– 50 –
Check Code List (Outdoor)
:Go on, : Flash, : Go off
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
Remote Sensor lamp part
controller Automatic Operation
Block indication Representative trouble position Detection Explanation of trouble contents reset continuation
indication
Operation Timer Ready Flash
F04 ALT Outdoor unit Discharge temp. sensor (TD) trouble Outdoor Open/Short-circuit of discharge temp. sensor was detected. — —
Open/Short-circuit of heat exchanger temp. sensor was detected.
F06 ALT Outdoor unit Temp. sensor (TE, TS, TL) trouble Outdoor Miss-wiring between TE sensor and TS sensor — —
F08 ALT Outdoor unit Outside temp. sensor (TO) trouble Outdoor Open/Short-circuit of outside temp. sensor was detected.
F07 ALT Outdoor unit Temp. sensor (TL) trouble Outdoor Open/Short-circuit of heat exchanger temp. sensor was detected. — —
F12 ALT Outdoor unit Temp. sensor (TS) trouble Outdoor Open/Short-circuit of suction temp. sensor was detected. — —
F13 ALT Outdoor unit Temp. sensor (TH) trouble Outdoor Open/Short-circuit of heat sink temp. sensor (Board installed) was detected. — —
F15 ALT Outdoor unit Misconnection of temp. sensor (TE, TS) Outdoor Misconnection of outdoor heat exchanger temp. sensor and suction temp. sensor was detected. — —
F31 SIM Outdoor unit EEPROM trouble Outdoor Outdoor P.C. board part (EEPROM) trouble was detected. — —
When reached min-Hz by current release control, short-circuited current (Idc) after
H01 Outdoor unit Compressor break down Outdoor DC excitation was detected. — —
H02 Outdoor unit Compressor lock Outdoor Compressor lock was detected. — —
H03 Outdoor unit Current detection circuit trouble Outdoor Current detection circuit trouble — —
H04 Outdoor unit Case thermostat operation Outdoor Case thermostat operation was detected. — —
L10 SIM Outdoor unit Setting trouble of service P.C. board type Outdoor When outdoor service P.C. board was used, model type select jumper setting was inappropriate. — —
1) Trouble parts on outdoor P.C. board (MCU communication, EEPROM, TH sensor trouble)
L29 SIM Outdoor unit Other outdoor unit trouble Outdoor 2) When outdoor service P.C. board was used, model type selection was inappropriate. — —
Operation Timer Ready Flash 3) Other trouble (Heat sink abnormal overheat, gas leak, 4-way valve inverse trouble) was detected.
P03 ALT Outdoor unit Discharge temp. trouble Outdoor Trouble was detected by discharge temp. release control. — —
Outdoor unit When case thermostat worked, trouble was detected by high release control from indoor/
P04 ALT High pressure system trouble, Power supply voltage trouble Outdoor outdoor heat exchanger temp. sensor. Power supply voltage trouble — —
P05 ALT Power supply trouble Outdoor Power supply voltage trouble — —
P07 ALT Outdoor unit Heat sink overheat Outdoor Abnormal overheat was detected by outdoor heat sink temp. sensor. — —
– 51 –
P15 ALT Gas leak detection Outdoor Abnormal overheat of discharge temp. or suction temp. was detected. — —
P20 ALT Outdoor unit High pressure system trouble Outdoor Trouble was detected by high release control from indoor/outdoor heat exchanger temp. sensor. — —
P22 ALT Outdoor unit Outdoor fan trouble Outdoor Trouble (Over-current, lock, etc.) was detected on outdoor fan drive circuit. — —
P26 ALT Outdoor unit Inverter Idc operation Outdoor Short-circuited protective operation of compressor drive circuit element (IPM) worked. — —
P29 ALT Outdoor unit Position detection trouble Outdoor Position detection trouble of compressor motor was detected. — —
No remote controller header unit Remote Signal was not received from indoor unit.
E01 Remote controller communication trouble controller Master remote controller was not set. (including 2 remote controllers) — —
Remote
E02 Remote controller send trouble controller Signal cannot be sent to indoor unit. — —
Regular communication trouble between indoor and
E03 remote controller Indoor No communication from remote controller and network adapter —
E04 Indoor/Outdoor serial trouble Indoor Serial communication trouble between indoor and outdoor —
E08 Duplicated indoor addresses Indoor Same address as yours was detected.
Remote In 2-remote controller control, both were set as header.
E09 Duplicated master remote controllers controller (Indoor header unit stops warning and follower unit continues operation.) — —
E10 Communication trouble between CPU Indoor MCU communication trouble between main motor and micro computer
Regular communication trouble between header and Regular communication was impossible between header and follower indoor units.
E18 follower indoor units Indoor Communication between twin header (Master unit) and follower (sub unit) was impossible. —
L03 SIM Duplicated indoor header units Indoor There are multiple header units in a group. — —
L07 SIM There are group cable in individual indoor unit. Indoor When even one group connection indoor unit exists in individual indoor unit. — —
L08 SIM Unset indoor group address Indoor Indoor address group was unset. — —
L09 SIM Unset indoor capacity Indoor Capacity of indoor unit was unset. — —
L30 SIM Outside trouble input to indoor unit (Interlock) Indoor Abnormal stop by CN80 outside trouble input — —
Indoor In heating operation, trouble was detected by temp. down of indoor heat exchanger or temp. up
P19 ALT 4-way valve inverse trouble Outdoor of TE, TS. —
When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.
: It is based on a situation.
:Go on, : Flash, : Go off
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
Remote Sensor lamp part
controller Automatic Operation
Block indication Representative trouble position Detection Explanation of trouble contents reset continuation
indication
Operation Timer Ready Flash
F01 ALT Indoor unit Heat exchanger sensor (TCJ) trouble Indoor Open/Short-circuit of heat exchanger (TCJ) was detected. —
F02 ALT Indoor unit Heat exchanger sensor (TC) trouble Indoor Open/Short-circuit of heat exchanger (TC) was detected. —
F10 ALT Indoor unit Room air temp. sensor (TA) trouble Indoor Open/Short-circuit of room air temp. (TA) was detected. —
F29 SIM Indoor unit Other indoor P.C. board trouble Indoor EEPROM trouble (Other trouble may be detected. If no trouble, automatic address is repeated. — —
P01 ALT Indoor unit Indoor fan trouble Indoor Indoor AC fan trouble was detected. (Fan thermal relay worked.) — —
P10 ALT Indoor unit Overflow detection Indoor Float switch worked. — —
P12 ALT Indoor unit Indoor fan trouble Indoor Indoor fan trouble (Over-current / Lock, etc.) was detected. — —
P31 ALT Other indoor unit trouble Indoor Other indoor under condition of warning in group. E03/L07/L03/L08 warning —
Sub remote controller trouble in a group
— By unit with warning No. ALT Trouble in indoor group Network adapter (Details of remote controller are displayed with unit No. Only central control side is displayed.) — —
Network adapter/ Communication trouble of central control system signal
— — LAN system communication trouble Center ∗ Is not displayed on the remote controller
Network adapter/
L20 SIM LAN system communication trouble Center Duplicated indoor address of central control system communication —
— — There are multiple communication adapters. Network adapter There are multiple communication adapters on remote controller communication line.
– 52 –
Check code table
The contents of trouble detected by indoor unit
No communication from remote 1. Check cables of remote controller and communication adapters.
Stop Displayed when
E03 controller (including wireless) and trouble is • Remote controller LCD display OFF (Disconnection)
(Automatic reset)
communication adapter detected • Central remote controller [97] check code
The serial signal is not output from 1. Outdoor unit does not completely operate.
outdoor unit to indoor unit. • Inter-unit wire check, correction of miss-wiring.
• Miss-wiring of inter-unit wire Displayed when • Check outdoor P.C. board. Correct wiring of P.C. board.
Stop
E04 • Serial communication circuit trouble (Automatic reset) trouble is
detected 2. When outdoor unit normally operates
of outdoor P.C. board
• Check P.C. board (Indoor receiving / Outdoor sending).
• Serial communication circuit trouble
of indoor P.C. board
E08 Duplicated indoor unit address 1. Check whether remote controller connection (Group/Individual)
was changed or not after power supply turned on
L03 Duplicated indoor header unit Displayed when (Finish of group construction/Address check).
Stop trouble is * If group construction and address are not normal when the
L07 There is group wire in individual indoor detected power has been turned on, the mode automatically shifts to
unit. address setup mode. (Resetting of address)
Stop Displayed when 1. Judge follower unit while header unit is [E03], [L03], [L07] or [L08].
P31 Unit automatically stops while warning (Follower unit) trouble is
is output to other indoor units. 2. Check indoor P.C. board.
(Automatic reset) detected
Coming-off, disconnection or short- Displayed when 1. Check indoor heat exchanger temp. sensor (TCJ).
F01 Stop trouble is
circuit ofindoor heat exchanger temp. 2. Check indoor P.C. board.
(Automatic reset) detected
sensor (TCJ)
Coming-off, disconnection or short- Displayed when 1. Check indoor heat exchanger temp. sensor (TC).
F02 Stop trouble is
circuit ofindoor heat exchanger temp. 2. Check indoor P.C. board.
(Automatic reset) detected
sensor (TC)
Coming-off, disconnection or short- Displayed when 1. Check indoor room air temp. sensor (TA).
F10 Stop trouble is
circuit of indoor room air temp. sensor 2. Check indoor P.C. board.
(Automatic reset) detected
(TA)
Indoor EEPROM trouble Stop Displayed when 1. Check indoor EEPROM. (including socket insertion)
F29 (Automatic reset) trouble is
• EEPROM access trouble detected 2. Check indoor P.C. board.
Communication trouble between indoor Displayed when 1. Check indoor P.C. board.
MCU Stop trouble is
E10 (Automatic reset)
• Communication trouble between fan detected
driving MCU and main MCU
Regular communication trouble between Displayed when 1. Check remote controller wiring.
Stop trouble is 2. Check indoor power supply wiring.
E18 indoor header and follower units and
(Automatic reset) detected
between master and sub units 3. Check indoor P.C. board.
– 53 –
Operation of diagnostic function
Check code Status of Judgment and measures
Cause of operation air conditioner Condition
Indoor unit
Disconnection, short-circuit of Displayed when 1. Check discharge temp. sensor (TD).
F04 Stop
discharge temp. sensor (TD) trouble is detected 2. Check outdoor P.C. board (MCC-1599).
Disconnection, short-circuit of outdoor Displayed when 1. Check temp. sensor (TE).
F06 Stop
temp. sensor (TE) trouble is detected 2. Check outdoor P.C. board (MCC-1599).
Disconnection, short-circuit of outdoor Displayed when 1. Check temp. sensor (TL).
F07 Stop
temp. sensor (TL) trouble is detected 2. Check outdoor P.C. board (MCC-1599).
Disconnection, short-circuit of suction Displayed when 1. Check suction temp. sensor (TS).
F12 Stop
temp. sensor (TS) trouble is detected 2. Check outdoor P.C. board (MCC-1599).
Miss-mounting of outdoor temp. Displayed when 1. Check temp. sensor (TE, TS).
F15 Stop
sensor (TE, TS) trouble is detected 2. Check outdoor P.C. board (MCC-1599).
Disconnection, short-circuit of outside Displayed when 1. Check outside temp. sensor (TO).
F08 Continue
temp. sensor (TO) trouble is detected 2. Check outdoor P.C. board (MCC-1599).
Disconnection, short-circuit of heat Displayed when 1. Check outdoor P.C. board (MCC-1599).
F13 Stop
sink temp. sensor (TH) trouble is detected (Q201 is incorporated in TH sensor.)
Displayed when 1. Check outdoor P.C. board (MCC-1599).
F31 Outdoor P.C. EEPROM trouble Stop
trouble is detected
Displayed when 1. Outdoor service P.C. board
L10 Unset jumper of service P.C. board Stop
trouble is detected Check model type setting jumper wire.
1. Check outdoor P.C. board
Communication trouble between Displayed when (MCC-1596, MCC-1597, MCC-1599).
L29 Stop
outdoor P.C. board MCU trouble is detected 2. Connection check between CN802 of MCC-1599 and
CN504 of MCC-1597, and also connection check
between CN505 of MCC-1597 and CN851 of MCC-1596.
Heat sink overheat trouble 1. Check screw tightening between PC. Board and heat
Displayed when
P07 ∗ Heat sink temp. sensor detected Stop sink and check radiator grease (MCC-1599).
trouble is detected
over specified temperature. 2. Check heat sink blast path.
1. Check gas leak, recharge
Detection of gas leak 2. Check full open of service valve.
∗ Discharge temp. sensor (TD), Displayed when 3. Check PMV (Pulse Motor Valve).
P15 Suction temp. sensor (TS) detected Stop
trouble is detected 4. Check broken pipe.
temperature over specified temp. 5. Check discharge temp. sensor (TD), suction temp.
sensor (TS).
4-way valve inverse trouble 1. Check operation of 4-way valve.
∗ After heating operation has started, 2. Check outdoor heat exchanger (TE), suction temp.
indoor heat exchanger temp. lowers sensor (TS).
under the specified temp. Displayed when 3. Check indoor heat exchanger sensor (TC).
P19 Stop
∗ After heating operation has started, trouble is detected 4. Check 4-way valve coil.
outdoor heat exchanger / suction 5. Check PMV (Pulse Motor Valve).
temp. rises over the specified temp.
Compressor break down 1. Check power supply voltage. (AC342 to 457V)
∗ Although operation has started, Displayed when 2. Overload operation of refrigerating cycle
H01 operation frequency decreases and Stop trouble is detected
operation stops.
Compressor lock 1. Trouble of compressor (Lock, etc.): Replace compressor.
Displayed when
H02 ∗ Over-current detection after Stop 2. Wiring trouble of compressor (Open phase)
trouble is detected
compressor start-up
Displayed when 1. Check outdoor P.C. board (MCC-1599).
H03 Current detection circuit trouble Stop
trouble is detected (AC current detection circuit)
1. Check connection of Ps sensor connector.
2. Check failure of Ps sensor.
Displayed when
F23 Ps sensor trouble Stop 3. Check compressing power trouble of compressor.
trouble is detected
4. Check 4-way valve trouble.
5. Check outdoor P.C. board trouble.
– 54 –
Operation of diagnostic function
Check code Status of Judgment and measures
Cause of operation air conditioner Condition
Indoor unit
Discharge temp. trouble 1. Check refrigerating cycle (Gas leak)
P03 ∗ Discharge temp. (TD) over Stop Displayed when 2. Trouble of electronic expansion valve
specified value was detected. trouble is detected 3. Check discharge temp. sensor (TD).
– 55 –
The contents of trouble detected by remote controller or central controller (TCC-LINK)
Operation of diagnostic function
Status of Judgment and measures
Check code Cause of operation air conditioner Condition
– 56 –
8-2. Diagnostic Procedure for Each Check Code (Outdoor Unit)
1) This section describes the diagnostic method for each check code displayed on the remote controller.
2) In some cases, a check code indicates multiple symptoms.
In this case, confirm LED display on the outdoor P.C. board to narrow the contents to be confirmed.
3) The display on the remote controller may differ from that of LED.
The check code on the remote controller is displayed only when the same trouble occurred continuously by
multiple times while LED of the outdoor P.C. board is displayed when a trouble occurred once.
1 2 3 4
YES
YES
YES
YES
– 57 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
[F04] <Display 1> <Display 2> [Discharge temp. sensor (TD) trouble]
YES
<Display 1> <Display 2> Heat exchanger temp. sensor (TE) trouble]
YES
<Display 1> <Display 2> [Heat exchanger temp. sensor (TL) trouble] → Refer to [F07] column.
<Display 1> <Display 2> [Suction temp. sensor (TS) trouble] → Refer to [F12] column.
<Display 1> <Display 2> [Miss-wiring of heat exchanger sensor (TE, TS)] → Refer to [F15] column.
[F07] <Display 1> <Display 2> [Heat exchanger temp. sensor (TL) trouble]
YES
– 58 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
[F08] <Display 1> <Display 2> [Outside air temp. sensor (TO) trouble]
YES
[F12] <Display 1> <Display 2> [Suction temp. sensor (TS) trouble]
YES
[F13] <Display 1> <Display 2> [Heat sink temp. sensor (TH) trouble]
[F15] <Display 1> <Display 2> [Miss-wiring of heat exchanger sensor (TE, TS)]
Is mounting status of NO
Correct sensor mounting.
TE and TS sensors normal?
YES
YES
YES
– 59 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
YES
YES
YES
Is it not abnormal overload? Correct and clear the cause.
NO
YES
YES
YES
Is compressor normal? Replace outdoor P.C. board.
NO
NO
Is there no refrigerant stagnation? Compressor lock → Replace
YES
NO Check TE, TS sensors and PMV.
Does PMV normally operate?
Trouble → Replace
YES
– 60 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
<Display 1> <Display 2> [Power supply trouble (Vdc)] → Refer to [P05] column.
NO
Are CN609 connection Correct connector.
and case thermostat normal? Case thermostat trouble → Replace
YES
NO
Is cooling/heating operation available Replace outdoor P.C. board
when short-circuiting case thermostat? (MCC-1599).
YES
NO
Is there no gas leak? Repair trouble position.
Is it not refrigerant shortage? Recharge refrigerant.
YES
NO
Is valve fully opened? Open valve fully.
YES
NO
Is PMV normal? Replace PMV.
YES
[L10] <Display 1> <Display 2> [Unset model type] : Only when service P.C. board is used
– 61 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
<Display 1> <Display 2> [Heat sink temp. sensor (TH) trouble] → Refer to [F13] column.
<Display 1> <Display 2> [Unset model type] → Refer to [L10] column.
<Display 1> <Display 2> [Heat sink overheat trouble] → Refer to [P07] column.
<Display 1> <Display 2> [Gas leak detection] → Refer to [P15] column.
<Display 1> <Display 2> [4-way valve inverse trouble] → Refer to [P19] column.
– 62 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
NO
NO
Is PMV normal? Replace PMV.
YES
YES
Is it not abnormal overload? Correct and clear the cause.
NO
YES
NO NO
Does cooling outdoor fan Is there no fan breakage
normally operate? or coming-off?
YES YES
Connection of connectors,
Fan IPDU, Fan motor, Wiring.
Overcharge of refrigerant/
Clogging/Pipe breakage/
Abnormal overload
– 63 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
[P04]
C
Heating operation
NO Are connections of NO
Does the heating indoor fan
normally operate? connectors, capacitors
and fan motor normal?
YES
YES
NO
YES
Replace
Replace indoor P.C. board. TC or TCJ sensor.
<Display 1> <Display 2> [Case thermostat operation] → Refer to [H04] column.
<Display 1> <Display 2> [Power supply trouble (Vdc)] → Refer to [P05] column.
<Display 1> <Display 2> [High pressure protective operation] → Refer to [P20] column.
– 64 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
[P05] <Display 1> <Display 2> [Power supply trouble (Voltage trouble)]
Is there open phase YES
of the power supply? Correct wiring.
NO
Is power supply NO
voltage normal? Confirm electric construction, etc.
(AC342 to 457V)
YES
Replace outdoor P.C. board (MCC-1600).
YES
Does something block the
NO
ventilation around the heat sink? Remove blocking matter.
Does something block air flow from the fan? Correct short-circuit.
(Short-circuit, etc.)
YES
Replace outdoor P.C. board (MCC-1596).
Is power supplied NO
Replace coil of 4-way valve.
to 4-way valve coil?
YES
OK
– 65 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
NO
Is valve fully opened? Open valve fully.
YES
Heating season
Heating operation Is resistance value NO
of TL sensor correct?
(Measurement of resistance value)
YES
Replace sensor.
YES
Check outdoor fan.
Trouble → Replace, retightening
YES
Check the same items as
[P22] trouble.
YES
Eliminate interfering element.
YES YES
Repair trouble position.
YES
Replace indoor P.C. board.
YES
Check overcharge of refrigerant, clogging of cycle,
broken pipe, abnormal overload, etc.
Trouble → Correct trouble position.
– 66 –
Check Outdoor Check and troubleshooting
code LED display (Item without special mention Indicates part of outdoor unit.)
YES
Replace fan motor.
Replace outdoor P.C. board
(MCC-1597).
SW804 SW801
ON
Push
1 2 3 4
— <Display 1> <Display 2> [Other trouble] Compressor disorder due to sudden change of load, etc.
No code ∗ Although the display of outdoor LED outputs, the unit automatically restarts
and trouble is not determined.
∗ LED display also may output due to negative phase of compressor or wire
coming-off.
– 67 –
8-3. Sensor characteristics
30
Resistance (kΩ)
20
10
0
0 10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
1 — —
2 OUTPUT White
3 GND Black
150 15 4 DC5V Red
100 10
50 5
0 0
0 10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
∗ As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the
resistance value cannot be measured.
– 68 –
Table Inspection of outdoor unit main parts
1 Compressor Measure the resistance value of each winding by using the tester.
(Model : RX420A3F-27M)
Red
Position Resistance value
Red – White
Under 20°C
2 Outdoor fan motor Measure the resistance value of each winding by using the tester.
(Model : ICF-280-A100-1)
Red
Position Resistance value
Red – White
Under 20°C
3 4-way valve coil Measure the resistance value of each winding by using the tester.
(Cooling/heating switching)
(Model : STF-H01AJ1736A1) Resistance value
1725 ± 172.5 Ω
Connector : White
Under 20°C
4 PMV coil Measure the resistance value of each winding by using the tester.
(Model : UKV-A038)
Position Resistance value
Gray – Orange 46 ± 3 Ω
Gray – Yellow 46 ± 3 Ω
Gray – Red 46 ± 3 Ω
Gray – Black 46 ± 3 Ω Under 20°C
– 69 –
9. SETUP AT LOCAL SITE AND OTHERS
9-1. Calling of check Code History
<Contents>
The trouble contents in the past can be called.
<Procedure>
TEMP. ON / OFF
Service Check goes on, the CODE No. 01 is displayed, and then TIME SAVE
A VENT
the content of the latest alarm is displayed. The number and FILTER
L
RESET TEST SET CL SWING/FIX UNIT
T LOUVER
<System example>
IN IN Master IN IN IN
1-1 2-1 3-1 4-1 7-1
Max. 8 units
Remote controller
– 70 –
Indoor unit power-ON sequence
<Automatic
address judgment>
Not normal NO
Gr construction check 3 minutes elapse
Normal YES
∗ Gr normal
1) There is no duplicated indoor unit address.
2) There is no invalid indoor unit address.
3) Individual unit and master/follower units
are not intermingled.
4) Only a unit for individual.
5) A master indoor unit and 1 or more
follower indoor units for Gr.
<Initial communication>
Outdoor model distinction (10 seconds) (Indoor unit) <Cautions at test run>
Twin Master/follower distinction (Indoor unit) • Power supply/Indoor/Outdoor serial and Gr wiring: OK
Gr construction, louver information (Remote controller)
• Powers of all indoor units are turned on within 3 minutes.
• Reception time for remote controller operation
(After power supply was turned on)
1) When address is OK : Approx. 50 seconds
2) In AUTO address : Approx. 4 to 5 minutes
<Usual regular
communication>
• In a group operation, if the indoor unit which was fed power after judgment of automatic address cannot
receive regular communication from the master unit and regular communication on identical pipe within 120
seconds after power was turned on, it reboots (system reset).
→ The operation starts from judgment of automatic address (Gr construction check) again.
(If the address of the master unit was determined in the previous time, the power fed to the master unit
and reboot works, the master unit may change though the indoor unit line address is not changed.)
– 71 –
9-3. Outdoor Unit
9-3-1. Various Setting on Outdoor Unit (Existing piping, Power save, Cooling-only, etc.)
The following settings are available by DIP switch setup and jumper line setup.
Turn the switch to ON when DIA 19.1 is used for the existing pipe.
Existing
High static pressure setup
piping setup In this case, the heating capacity may lower according to outside
Existing piping setup
temp. and indoor temp. in heating operation.
Power save setup
Snow-proof fan control
Turn the switch to ON when using the power save function.
Power save ∗ all are OFF at shipment.
setup The control to lower the compressor frequency (Approx. –10%) is
performed by indoor heat exchanger temp. in heating operation.
– 72 –
9-3-2. Service Support Function (LED Display, Switch Operation)
1. Outline
A various setup and operation check can be performed by DIP switches at 3 positions
(SW802, SW803, SW804) and the pushdown button switches (SW800, SW801) at 2 positions.
Operation part
SW800 Pushdown button switch Exchanges the displayed contents of LED (D800 to D804) on the outdoor
SW803 DIP switch control P.C. board.
Display part
Trouble display
When all SW803 are OFF, or when any of D800 to D804 goes on, LED
D800 to D804 Yellow LED
displays that the outdoor controller detects a trouble.
When status of SW803 is other than OFF, various indications are displayed.
Power-ON display
D805 Green LED When the power of the outdoor unit is turned on, LED goes on.
When SW801 and SW804 operate the specific operation, LED flashes.
ON ON
1 2 3 4 1 2 3 4
1 2 3 4 1 2 3 4 D805
SW802 SW803 SW800 SW801 SW806 D804
D803
LED D802
D805
D804
D803
D801
D802
D801
D800
D800
D502 D503
– 73 –
9-3-3. Others
1. Selection of LED display (SW800, SW803 operation)
1) Display selection list
The displayed contents of LED D800 to D804 on the outdoor control P.C. board can be exchanged by
operation of SW803.
Trouble display (The latest trouble: Latest trouble including present) Refer to
After trouble status was cleared, the trouble which generated 2)
SW803 before can be confirmed by this setting. (Reconfirmation is
ON available even if power supply was turned off once.)
• If a trouble generates at present, the same contents as those
1 2 3 4 of trouble which is generating at present are displayed.
• Only trouble of TO sensor is not displayed by this setting.
(Confirm it by setting of trouble which is generating at present.)
1 2 3 4 1 2 3 4 1 2 3 4
TO TL TH
SW803 SW803 SW803
ON ON ON
1 2 3 4 1 2 3 4 1 2 3 4
TA TC TCJ
SW803 SW803 SW803
ON ON ON
1 2 3 4 1 2 3 4 1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
– 74 –
2) Trouble display
The trouble which is generating at present and the latest trouble (Latest trouble information including
present) can be confirmed by lighting LED D800 to D804 on the outdoor control P.C. board.
a) When all DIP switch SW803 are OFF, the status of trouble which is generating at present is displayed.
b) <1> only of DIP switch SW803 is turned on, the trouble which generated before
(Latest trouble information including present) is displayed.)
c) If there is a trouble, any of LED D800 to D804 goes on. (Display 1)
d) When pushing the pushdown button switch SW800 for approx. 1 second, the display is exchanged.
(Display 2)
e) When pushing SW800 again or after 2 minutes, the status returns to that of Display c.
(Legend)
Present trouble Latest trouble
SW803 SW803
ON ON D800 D801 D802 D803 D804 D805
(Yellow) (Yellow) (Yellow) (Yellow) (Yellow) (Green)
1 2 3 4 1 2 3 4
∗ As the Check code displayed on the wired remote controller may differ according to type of indoor model,
multiple codes are described.
– 75 –
3) Sensor, current, compressor operation frequency, PMV opening display
The values detected by the controller, such as temperature sensor or current value are simply confirmed.
(Legend)
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
TA TC TCJ
SW803 SW803 SW803
LED ON ON ON
display
1 2 3 4 1 2 3 4 1 2 3 4
– 76 –
4) Specific operation for maintenance check (SW801, SW804)
The following specific operations for the maintenance check are performed by operation of SW801 or
SW804.
a) Select DIP switch SW804. (See table below)
b) Push the pushdown button switch SW801 for approx. 1 second.
c) The following functions start. While each function starts, LED D805 (Green) flashes.
d) When pushing the pushdown button switch SW801 again for approx. 1 second, when selecting DIP switch
SW804 or when the specified time of each function elapsed, each function stops and LED D805 (Green)
returns to the continuous lighting.
<Specific operation>
1 2 3 4
1 2 3 4
Note 1) Indoor cooling test run demand / Indoor heating test run demand
Only when combining with the following indoor unit, cooling/heating operation can be performed from
the outdoor unit.
Test run is unavailable: Indoor units other than the above-mentioned indoor units, are included in the
twin, triple connection.
Note 2) The forced test run by this setting cannot be cleared on the indoor remote controller.
Be sure to clear the test run by operation of the outdoor unit. (Push SW801 again for 1 second.)
– 77 –
SW804 Operation when pushdown button switch SW801 is pushed
1 2 3 4
– 78 –
10. ADDRESS SETUP
10-1. Address Setup Procedure
When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor
unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address
setup completes with power-ON of the outdoor unit. The operation of the remote controller is not accepted
while automatic address works. (Approx. 4 to 5 minutes)
YES
NO
Is group control performed?
Turn on power of outdoor unit. Turn on power of outdoor unit. Turn on power of outdoor unit.
• When the following addresses are not stored in the neutral memory (IC503) on the indoor P.C. board, a test
run operation cannot be performed. (Unfixed data at shipment from factory)
– 79 –
10-2. Address Setup & Group Control
<Definitions of terms>
Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64)
Group address : 0 = Single (Not group control)
1 = Master unit in group control
2 = Sub unit in group control
Master unit (= 1) : The representative of multiple indoor units in group operation sends/receives signals to/
from the remote controllers and sub indoor units.
(* It has no relation with an indoor unit which communicates serially with the outdoor units.)
The operation mode and setup temperature range are displayed on the remote controller
LCD.
(Except air direction adjustment of louver)
Sub unit (= 2) : Indoor units other than master unit in group operation
Basically, sub units do not send/receive signals to/from the remote controllers.
(Except alarm and response to demand of service data)
Header unit (Representative unit) (Master Twin)
: This unit communicates with the indoor unit (follower) which serial-communicates with the
outdoor units and sends/receives signal (Command from compressor) to/from the outdoor
units as the representative of the cycle control in the indoor units of the identical line
address within the minimum unit which configures one of the refrigerating cycles of Twin.
Follower unit (Subordinate unit) (Sub Twin)
: Indoor units excluding the header unit in Twin
This unit communicates with (Header) indoor unit in the identical line address and performs
control synchronized with (Header) indoor unit.
This unit does not perform the signal send/receive operation with the outdoor units. :
No judgment for serial signal trouble.
– 80 –
10-2-1. System Configuration
1. Single
Outdoor
1-1
Indoor (Master/Header)
Individual
Remote
controller
2. Twin 3. Triple
(Max. : 8 units)
5. Multiple groups operation (Single, Twin, Triple operation) (Manually addresses change)
• Header unit: The header unit receives the indoor unit data (thermostat status) of the follower (Without
identical line address & indoor/outdoor serial) and then finally controls the outdoor compressor
matching with its own thermostat status.
The header unit sends this command information to the follower unit.
• Follower unit: The follower unit receives the indoor unit data from the header (With identical line address &
indoor/outdoor serial) and then performs the thermostat operation synchronized with the
header unit.
The follower unit sends own thermostat ON/OFF demand to the header unit.
(Example)
No. 3-1 header unit sends/receives signal to/from No. 3-2 and No. 3-3 follower units.
(It is not influenced by the refrigerating line 1 or 2 address indoor unit.)
– 81 –
10-2-2. Automatic Address Example from Unset Address (No miss-wiring)
2. Single group operation (Multiple outdoor units = Multiple indoor units only with serial communication)
Change is necessary
Manually change addresses of the multiple follower units
simultaneously from the remote controller.
– 82 –
10-3. Remote Controller Wiring
• Strip off approx. 9 mm the wire to be connected.
• For single system, use non polarity, 2 core wire
is used for wiring of the remote controller. Wiring diagram
(0.5 mm² to 2.0 mm² wires)
• For the synchronous twin, triple system, use 2-
core shield wire (Vinyl cord for microphone 0.5 Terminal block for remote controller Terminal block
wiring of indoor unit
to 2.0 mm²) to conform to the EMC standard.
A A Remote controller
B B unit
Remote controller
Remote controller Remote controller inter-unit wiring
Indoor/Outdoor Indoor/Outdoor
connecting wires connecting wires
1 2 3
Indoor power
1 2 3
inter-unit wiring
Outdoor side Outdoor side
L1 L2 L3 N L1 L2 L3 N
Remote controller
wiring A B A B A B
Indoor side Indoor side Indoor side
1 2 3 1 2 3 1 2 3
Indoor/Outdoor
connecting wires
1 2 3 Indoor power Indoor power
Outdoor side inter-unit wiring inter-unit wiring
L1 L2 L3 N
Triple
– 83 –
10-4. Address Setup (Manual setting from remote controller)
(Example of 2-lines cabling)
In case that addresses of the indoor units will be (Solid line: Cabling, Broken line: Refrigerant pipe)
determined prior to piping work after wiring work
Outdoor Outdoor
• Set an indoor unit per a remote controller. 1 2 3 1 2 3
• Turn on power supply.
1 2 3 1 2 3 1 2 3 1 2 3
Indoor Indoor Indoor Indoor
A B A B A B A B
Line address → 1 1 2 2
Indoor unit address → 1 2 1 2
1 Group address → 1 2 2 2
Push + + buttons simultaneously for
4 seconds or more. A B
2 (←
← Line address)
Remote controller
Using the temperature setup / For the above example, perform setting by
connecting singly the wired remote controller
buttons, set the CODE No. to 12. without remote controller inter-unit cable.
3
Group address
Using timer time / buttons, set the line Individual : 0000
Master unit : 0001
address. Sub unit : 0002
In case of group control
5 (←
← Indoor unit address)
Using the temperature setup / buttons, set the CODE No. to 13.
8 (←
← Group address)
Using the temperature setup / buttons, set the CODE No. to 14.
9 Using timer time / buttons, set Individual to 0000, Header unit to 0001, and Follower
unit to 0002.
11 Push button.
Setup completes. (The status returns to the usual stop status.)
TEMP. ON / OFF
FILTER
L
RESET TEST SET CL SWING/FIX UNIT
T LOUVER 4, 7, 10
1
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11 END
– 84 –
10-5. Confirmation of Indoor Unit No. Position
1. To know the indoor unit addresses though position of the indoor unit body is recognized
• In case of individual operation (Wired remote controller : indoor unit = 1 : 1)
(Follow to the procedure during operation)
<Procedure>
2 Push
UNIT LOUVER
button (button of left side).
Unit No. 1-1 is displayed on LCD. TEMP. ON / OFF
1 2 END
4 seconds or more.
TIMER SET FAN MODE
– 85 –
<Maintenance/Check list>
Aiming in environmental preservation, it is strictly recommended to clean and maintain the indoor/outdoor units
of the operating air conditioning system regularly to secure effective operation of the air conditioner.
It is also recommended to maintain the units once a year regularly when operating the air conditioner for a
long time.
Check periodically signs of rust or scratches, etc. on coating of the outdoor units.
Repair the trouble position or apply the rust resisting paint if necessary.
If an indoor unit operates for approx. 8 hours or more per day, usually it is necessary to clean the indoor/
outdoor units once three months at least.
These cleaning and maintenance should be carried out by a qualified dealer.
Although the customer has to pay the charge for the maintenance, the life of the unit can be prolonged.
Failure to clean the indoor/outdoor units regularly will cause shortage of capacity, freezing, water leakage or
trouble on the compressor.
Object
Part name Contents of check Contents of maintenance
Indoor Outdoor
Heat exchanger • Blocking with dust, damage check • Clean it when blocking is found.
• Visual check for swing and balance • Replace fan when swinging or
• Check adhesion of dust and external balance is remarkably poor.
Fan
appearance. • If a large dust adheres, clean it with
brush or water.
Front panel, Louver — • Check dirt and scratch. • Cleaning/Coating with repair painting
– 86 –
11. REPLACEMENT OF THE SERVICE P.C. BOARD MCC-1599
1. Setting the jumper wires and DIP switches
J800 to J803 Model switching Cut these jumper wires according to the following table.
Jumper wire Set these jumper wires to the settings of the P.C. board
J804 to J811 Settings
before replacement
RAV-GP1101AT8* × O × ×
RAV-GP1401AT8* O × × ×
RAV-GP1601AT8* × × × ×
[ : Characters that indicate the following
O : Connected,
No. character : Standard models
J : For heavily salt-affected areas
× : Cut
MCC-1599
SW804 SW805
SW802 SW803
J807 to J811 J804 to J806
J800 to J803
– 87 –
12. HOW TO EXCHANGE COMPRESSOR
12-1. Exchanging Procedure of Compressor (Outline)
START
Leakage check
Vacuuming
END
– 88 –
13. DETACHMENTS
13-1. Outdoor Unit
RAV-GP1101AT8*, RAV-GP1401AT8*, RAV-GP1601AT8* series
1 Common
procedure WARNING
Stop operation of the air conditioner and turn off
breaker switch.
CAUTION
Ensure wearing of gloves when performing any work
in order to avoid injury from parts, etc.
1. Detachment
1) Remove the service panel.
(Hexagonal screws M4 × 10, 2 pcs.) Service panel
• Remove the screws and then pull service panel
downward to remove.
2) Remove the power supply cable and the indoor/
outdoor connecting wire from the cord clamp and
the terminal.
3) Remove the top plate.
(Hexagonal screws M4 × 10, 5 pcs.)
CAUTION
The power supply cable and the indoor/outdoor
connecting wire must be affixed along the crossover
pipe using a commercially available bundling band so
that they do not make contact with the compressor,
gas valve, gas pipe and discharge pipe.
– 89 –
No. Part name Procedure Remarks
2 Discharge 1. Detachment
port cabinet Heat exchanger Motor base
1) Carry out the operation in 1. of above.
2) Remove the screws fixing the inverter assembly,
the discharge port cabinet and the partition board.
(ST1T M4 × 8, 4 pcs.)
3) Remove the screws for the discharge port cabinet
and the bottom plate.
(Hexagonal screw M4 × 10, 2 pcs.)
4) Remove screw for the discharge port cabinet and
heat exchanger. (ST1T M4 × 8, 1 pc.)
5) Remove screw for the discharge port cabinet and
the motor base. (ST1T M4 × 8, 2 pcs.)
6) Remove screws for the discharge port cabinet
and the fin guard.
(Hexagonal screw M4 × 10, 2 pcs.)
2. Attachment
1) Attach the discharge port cabinet and end board
of heat exchanger and fix with a screw.
(ST1T M4 × 8, 1 pc.) Discharge
port cabinet
2) Mount other removed screws into original
positions.
– 90 –
No. Part name Procedure Remarks
2. Attachment
1) Temporarily suspend the side cabinet on the
inverter assembly using the hook.
2) Mount the removed screws in the opposite
procedure to that during detachment.
Hook
Inverter assembly
– 91 –
No. Part name Procedure Remarks
4 Inverter 1. Detachment
assembly 1) Carry out the operation in 1. of , 1. of above.
2) Remove the connectors connected to the Fan IPDU
board, the connector connected to other components
from the control board Cut the
(Interface board). banding band
CN600 : TS sensor (3P: White, tube: Gray)
CN601 : TE sensor (2P: White, tube: Blue) Fan-IPDU board
CN602 : TO sensor (2P: Yellow, tube: Black) Remove the fan motor lead wire
CN603 : TD sensor (3P: White, tube: Red) from the cord clamp.
CN604 : TL sensor (2P: White, tube: White)
CN609 : Case thermostat. (2P: Blue)
CN690 : High pressure switch (3P: Green)
Discharge port
CN700 : 4-way coil (3P: Yellow) cabinet Interface board
CN710 : PMV coil (6P: White)
Cut the
• Fan IPDU board banding band
CN700 : Outdoors lower fan motor (3P: Blue)
CN750 : Outdoors upper fan motor (3P: White)
Cut the banding band and remove connector connected Remove the fan motor lead wire
from fan motor to fan motor relay board. from the cord clamp.
∗ Remove connectors after unlocking housing section
3) Remove the screw (1 position) fixing the discharge port
cabinet.
4) Cut bundling band fixing various lead lines to inverter
assembly.
5) Remove sound-insulation plate (upper).
6) Remove terminal cover of compressor and remove
compressor lead. Sound-insulation plate
7) Pull up the inverter assembly at upper side to remove (upper)
hook of partition plate (rear left part).
2. Attachment
1) Mount the inverter assembly on the partition plate.
CAUTION
When mounting the inverter assembly on the partitioning
plate, ensure proper mounting of the hook (rear left part)
Sound-insulation plate
with partitioning plate. (rolling out)
Inverter
assembly
Partition plate
Compressor lead
Case thermostat Hook
Inverter
assembly
– 92 –
No. Part name Procedure Remarks
2. Attachment
1) Mount the interface board (Control board).
2) Mount the individual components in the Support (4 positions)
opposite procedure to that during detachment.
– 93 –
No. Part name Procedure Remarks
Screw
Support
(2 positions) Heat sink
– 94 –
No. Part name Procedure Remarks
2. Attachment
1) Mount noise filter board.
2) Mount components in the opposite method to that when
removing.
Inverter assembly (front)
Screws
(2 positions)
Using
State of noise
Using the hook, filter board
it is possible to temporarily suspend when removed
the inverter assembly (front).
– 95 –
No. Part name Procedure Remarks
8 Compressor 1. Detachment
IPDU board 1) Carry out the operation in 1. of , 1. of ,
MCC-1596 1. of , 1. of and 1. of .
2) Remove the screw (4 positions) fixing the inverter
assembly (IPDU).
3) Remove the lead wire and connector to other
components from the compressor IPDU board.
CN04 : Posistor (Red)
CN09 : Power supply terminal block (Yellow)
CN10 : Power supply terminal block (Yellow)
CN11 : Relay (Red)
CN12 : Noise filter board (White)
CN13 : Relay (Black)
CN101 : FAN-IPDU board (3P, White)
CN211 : Compressor (Red)
CN212 : Compressor (White)
CN213 : Compressor (Black)
CN851 : FAN-IPDU board (5P, Red)
2. Attachment
Inverter assembly (front)
1) Mount compressor IPDU board.
2) Mount components in the opposite method to that Screws (4 positions)
when removing.
Compressor
IPDU board
Screws (3 positions)
– 96 –
No Part name Procedure Part name
Be sure to fix the fan motor lead to the motor base using the
metal band of the motor base so that the fan motor lead
does not come to contact with the propeller fan.
Ferrite core
Connector of
lower fan motor
Fan motor
Projection/Refrigerating
cycle side
– 97 –
No. Part name Procedure Remarks
WARNING
In case of removing the piping by broiling the welded
part with a burner, if there is oil in the pipe, it may burst
into flames at the moment that wax melted, so take
sufficient care.
Ferrite core
CAUTION
Note so that the flame does not catch the
4-way valve and PMV. (A malfunction may be caused.)
Remove
(Discharge pipe)
11) Pull off the discharge pipe and the suction pipe of
the refrigerating cycle upward.
12) Remove the compressor nuts which fix the
compressor to the bottom plate. (3 pcs.) Remove
13) Pull out the compressor toward you. (Suction pipe)
CAUTION
As weight of the compressor is 20kg or more, handle it
by 2 workers. Compressor nuts
(3 pcs.)
450
– 98 –
No. Part name Procedure Remarks
NOTE
• After replacement of the compressor, be sure
to replace the compressor lead. (Repair part
code of compressor lead: 43160612)
In this time, wrap the ferrite core with the
compressor lead wire by 1 time. Ferrite core
0t
• As shown in the right figure, mount the
o5
sound-insulation plate (rolling in, rolling out)
0
by passing through it between the
0 to 50
compressor and the piping, and between the (Compressor lead positioning standard)
piping and the partition board.
Put the end of Pass through sound-
• Fix TD sensor by the bundling band for heat- sound-insulation insulation plate
proof on the market via the pipe cover so that plate (rolling out) (rolling out) between
on the other end suction pipe and
TD sensor does not directly come to contact at this position. header pipe.
with the discharge pipe.
3. Vacuuming
1) Connect the vacuum pump to the charge Suction pipe Header pipe
port and the check joint of the gas pipe valve
and then drive the vacuum pump.
2) Carry out vacuuming until the vacuum low
pressure gauge indicates 1 (mmHg). Discharge pipe
4. Refrigerant charge
1) Add the refrigerant amount determined by Sound-insulation plate
(rolling out)
the pipe length from the charge port of the Insert one side
valve. under cultural rivet.
SW804 SW801
– 99 –
No. Part name Procedure Remarks
2. Attachment
1) Surely match the positioning projection of
the coil with the concave part of PMV main
unit and then fix it.
REQUIREMENT
To prevent scratch on the product, carry out
the work on cardboard, cloth, etc.
2. Attachment
1) Push the hooking claws (8 positions) with
hands from the front side to fix the claws.
2) Attach the bell mouth fixed with screws and
washers.
(PT2P M3 × 14 and washer, 4 pcs.)
REQUIREMENT
Check that all the hooking claws are fixed at
the specified positions.
– 100 –
14. EXPLODED VIEWS AND PARTS LIST
14-1. Outdoor Unit
RAV-GP1101AT8-E, RAV-GP1101AT8J-E
RAV-GP1101AT8-TR, RAV-GP1101AT8J-TR
– 101 –
Model name RAV-GP
Location
Part No. Description 1101AT8-E 1101AT8J-E
No.
1101AT8-TR 1101AT8J-TR
1 43F19904 HOLDER, SENSOR (TS) 3 3
2 43F32441 NIPPLE, DRAIN 1 1
3 43F47401 BONNET, 3/8 IN 1 1
4 43F47669 NUT, FLANGE 2
5 43049739 CUSHION, RUBBER 3 3
6 43141530 COMPRESSOR, RX420A3F-27M 1 1
7 43F50407 THERMOSTAT,BIMETAL 1 1
8 43F60029 FILTER, NOISE 1 1
9 43F63317 HOLDER,THERMOSTAT 1 1
10 43197164 NUT, FLANGE 2
11 43197174 NUT, COMP 3
12 43F97212 NUT 3
13 43100437 PANEL, FRONT, PIPING 1 1
14 43100438 PANEL, BACK, PIPING 1 1
15 43100439 PANEL, FRONT 1 1
16 43100440 PLATE, ROOF 1 1
17 43100470 PANEL, SIDE 1 1
18 43100442 PANEL, AIR OUTLET 1 1
19 43100443 BASE ASSY 1 1
20 43107274 GUARD, FIN, SIDE 1 1
21 43107275 GUARD, FIN, BACK 1 1
22 43107276 HANGER 3 3
23 43119540 GUARD, FAN ASSY 2 2
24 43120244 FAN, PROPELLER, PB521 2 2
25 43122113 BELL MOUTH 2 2
26 4312C100 MOTOR, FAN, ICF-280-A100-1 (A) 2 2
27 43146676 JOINT,CHECK 1 1
28 4314N092 VALVE, PACKED, 9.52 1 1
29 37546878 VALVE, 4-WAY, STF-H0404 1 1
30 4314N080 COIL, SOLENOID, STF-H01AJ1736A1 1 1
31 43146724 VALVE, BALL, SBV-JA5GTC-1, ROHS 1 1
32 43148294 ACCUMULATOR 1 1
34 43151301 SWITCH, PRESSURE 1 1
35 43160612 LEAD ASSY, COMPRESSOR 1 1
36 43147194 BONNET, 5/8 IN 1 1
37 4311M659 MARK, TOSHIBA 1 1
38 4314G266 CONDENSER ASSY, DOWN 1
39 4314G268 CONDENSER ASSY, DOWN 1
40 4314G269 CONDENSER ASSY, UP 1
41 4314G271 CONDENSER ASSY, UP 1
42 4314N023 VALVE, PLUS, MODULAING, UKV-25D100 1 1
43 4314N025 COIL, PMV, UKV-A038 1 1
44 4314Q031 STRAINER 1 1
45 4314Q032 STRAINER 1 1
46 43158227 REACTOR 1 1
– 102 –
Outdoor Unit
RAV-GP1401AT8-E, RAV-GP1401AT8J-E
RAV-GP1401AT8-TR, RAV-GP1401AT8J-TR
– 103 –
Model name RAV-GP
Location
Part No. Description 1401AT8-E 1401AT8J-E
No.
1401AT8-TR 1401AT8J-TR
1 43F19904 HOLDER, SENSOR (TS) 3 3
2 43F32441 NIPPLE, DRAIN 1 1
3 43F47401 BONNET, 3/8 IN 1 1
4 43F47669 NUT, FLANGE 2
5 43049739 CUSHION, RUBBER 3 3
6 43141530 COMPRESSOR, RX420A3F-27M 1 1
7 43F50407 THERMOSTAT,BIMETAL 1 1
8 43F60029 FILTER, NOISE 1 1
9 43F63317 HOLDER,THERMOSTAT 1 1
10 43197164 NUT, FLANGE 2
11 43197174 NUT, COMP 3
12 43F97212 NUT 3
13 43100437 PANEL, FRONT, PIPING 1 1
14 43100438 PANEL, BACK, PIPING 1 1
15 43100439 PANEL, FRONT 1 1
16 43100440 PLATE, ROOF 1 1
17 43100470 PANEL, SIDE 1 1
18 43100442 PANEL, AIR OUTLET 1 1
19 43100443 BASE ASSY 1 1
20 43107274 GUARD, FIN, SIDE 1 1
21 43107275 GUARD, FIN, BACK 1 1
22 43107276 HANGER 3 3
23 43119540 GUARD, FAN ASSY 2 2
24 43120244 FAN, PROPELLER, PB521 2 2
25 43122113 BELL MOUTH 2 2
26 4312C100 MOTOR, FAN, ICF-280-A100-1 (A) 2 2
27 43146676 JOINT,CHECK 1 1
28 4314N092 VALVE, PACKED, 9.52 1 1
29 37546878 VALVE, 4-WAY, STF-H0404 1 1
30 4314N080 COIL, SOLENOID, STF-H01AJ1736A1 1 1
31 43146724 VALVE, BALL, SBV-JA5GTC-1, ROHS 1 1
32 43148294 ACCUMULATOR 1 1
34 43151301 SWITCH, PRESSURE 1 1
35 43160612 LEAD ASSY, COMPRESSOR 1 1
36 43147194 BONNET, 5/8 IN 1 1
37 4311M659 MARK, TOSHIBA 1 1
38 4314G266 CONDENSER ASSY, DOWN 1
39 4314G268 CONDENSER ASSY, DOWN 1
40 4314G269 CONDENSER ASSY, UP 1
41 4314G271 CONDENSER ASSY, UP 1
42 4314N023 VALVE, PLUS, MODULAING, UKV-25D100 1 1
43 4314N025 COIL, PMV, UKV-A038 1 1
44 4314Q031 STRAINER 1 1
45 4314Q032 STRAINER 1 1
46 43158227 REACTOR 1 1
– 104 –
Outdoor Unit
RAV-GP1601AT8-E, RAV-GP1601AT8J-E
RAV-GP1601AT8-TR, RAV-GP1601AT8J-TR
– 105 –
Model name RAV-GP
Location
Part No. Description 1601AT8-E 1601AT8J-E
No.
1601AT8-TR 1601AT8J-TR
1 43F19904 HOLDER, SENSOR (TS) 3 3
2 43F32441 NIPPLE, DRAIN 1 1
3 43F47401 BONNET, 3/8 IN 1 1
4 43F47669 NUT, FLANGE 2
5 43049739 CUSHION, RUBBER 3 3
6 43141530 COMPRESSOR, RX420A3F-27M 1 1
7 43F50407 THERMOSTAT,BIMETAL 1 1
8 43F60029 FILTER, NOISE 1 1
9 43F63317 HOLDER,THERMOSTAT 1 1
10 43197164 NUT, FLANGE 2
11 43197174 NUT, COMP 3
12 43F97212 NUT 3
13 43100437 PANEL, FRONT, PIPING 1 1
14 43100438 PANEL, BACK, PIPING 1 1
15 43100439 PANEL, FRONT 1 1
16 43100440 PLATE, ROOF 1 1
17 43100470 PANEL, SIDE 1 1
18 43100442 PANEL, AIR OUTLET 1 1
19 43100443 BASE ASSY 1 1
20 43107274 GUARD, FIN, SIDE 1 1
21 43107275 GUARD, FIN, BACK 1 1
22 43107276 HANGER 3 3
23 43119540 GUARD, FAN ASSY 2 2
24 43120244 FAN, PROPELLER, PB521 2 2
25 43122113 BELL MOUTH 2 2
26 4312C100 MOTOR, FAN, ICF-280-A100-1 (A) 2 2
27 43146676 JOINT,CHECK 1 1
28 4314N092 VALVE, PACKED, 9.52 1 1
29 37546878 VALVE, 4-WAY, STF-H0404 1 1
30 4314N080 COIL, SOLENOID, STF-H01AJ1736A1 1 1
31 43146724 VALVE, BALL, SBV-JA5GTC-1, ROHS 1 1
32 43148294 ACCUMULATOR 1 1
34 43151301 SWITCH, PRESSURE 1 1
35 43160612 LEAD ASSY, COMPRESSOR 1 1
36 43147194 BONNET, 5/8 IN 1 1
37 4311M659 MARK, TOSHIBA 1 1
38 4314G266 CONDENSER ASSY, DOWN 1
39 4314G268 CONDENSER ASSY, DOWN 1
40 4314G269 CONDENSER ASSY, UP 1
41 4314G271 CONDENSER ASSY, UP 1
42 4314N023 VALVE, PLUS, MODULAING, UKV-25D100 1 1
43 4314N025 COIL, PMV, UKV-A038 1 1
44 4314Q031 STRAINER 1 1
45 4314Q032 STRAINER 1 1
46 43158227 REACTOR 1 1
– 106 –
14-2. Inverter Assembly
RAV-GP1101AT8(J)-E, RAV-GP1401AT8(J)-E, RAV-GP1601AT8(J)-E
RAV-GP1101AT8(J)-TR, RAV-GP1401AT8(J)-TR, RAV-GP1601AT8(J)-TR
701
– 107 –
Model name RAV-GP
Location
Part No. Description 1101AT8(J)-E, 1401AT8(J)-E, 1601AT8(J)-E
No.
1101AT8(J)-TR, 1401AT8(J)-TR, 1601AT8(J)-TR
701 43F58288 REACTOR, CH-56-4Z 1
702 43154177 RELAY 1
704 43158207 REACTOR, CH-68 1
705 43153006 PTC-THERMISTOR 1
706 43050425 SENSOR ASSY, SERVICE 3
707 43150319 SENSOR ASSY, SERVICE 2
708 43160565 TERMINAL BLOCK, 3P, 20A 1
709 43160579 TERMINAL, 30A, 4P 1
710 43F60859 FUSE BLOCK, 30A, 250V 1
711 4316V416 PC BOARD ASSY, MCC-1596, COMP-IPDU 1
712 4316V391 PC BOARD ASSY, MCC-1597, FAN-IPDU 1
713 4316V534 PC BOARD ASSY, MCC-1599, CDB 1
714 4316V398 PC BOARD ASSY, MCC-1600, N/F 1
715 43F63325 HOLDER, SENSOR (TE) 1
717 43160590 FUSE 3
718 43282001 BUSHING 5
719 43183020 COLLAR 5
720 43F63248 SUPPORTER, ASSY 2
721 43060700 FUSE, 10A, 250V 1
– 108 –
72-34 Horikawa-cho, Saiwai-ku, Kawasaki-shi, Kanagawa 212-8585, JAPAN
Copyright © 2019 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.
Revision record
First issue — — Mar., 2019
Revision 1 Words were corrected. All the pages Sep., 2019
Revision 2 The service part number was changed. Page 108 Oct., 2019
(PC BOARD ASSY, MCC-1599, CDB)