0% found this document useful (0 votes)
47 views51 pages

AS Series Analog Module Guide

Uploaded by

Seyed ali Amiri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
47 views51 pages

AS Series Analog Module Guide

Uploaded by

Seyed ali Amiri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 51

AS Series

Analog Modules:
AD/DA/XA/RTD/
TC/Function
Card

VAHID MOGHADAM
09122407352
Outline
• Hardware Introduction

• Module Setups

• Setup Procedures

• Demonstrations

• Exercises

Delta Confidential 2
Purpose
In this chapter, you will learn …..
… more about specifications of the module hardware
… more about module setups
… more about data protection and data backup

3
• Hardware Introduction

• Module Setups

• Setup Procedures

• Demonstrations

• Exercises

Delta Confidential 4
AS04AD-A
Electrical specifications
Module name AS04AD-A
Number of inputs 4
Analog-to-digital Voltage input/Current input
conversion
Supply voltage 24 VDC (20.4 VDC~28.8 VDC) (-15%~+20%)
Connector type Removable terminal block
Conversion time 2ms/channel

An analog circuit is isolated from a digital circuit by a digital


integrated circuit/an optocoupler, but the analog channels are not
isolated from one another.
Isolation Isolation between a digital circuit and a ground: 500 VDC
Isolation between an analog circuit and a ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between the 24 VDC and a ground: 500 VDC

Delta Confidential 5
AS04AD-A
Functional specifications
Analog-to-digital
Voltage input
conversion
Rated input range -10~10V 0~10V ±5V 0~5V 1~5V
Hardware input range -10.1~10.1V -0.1~10.1V -5.05~5.05V -0.05~5.05V 0.95~5.05V
Fiducial error
0.2%
(Room temperature)
Fiducial error
0.5%
(Full temperature range)
Linearity error
0.02%
(Room temperature)
Linearity error
0.06%
(Full temperature range)
Hardware resolution 16 bits
Input impedance 2MΩ
Absolute input range ±15V

Delta Confidential 6
AS04AD-A
Functional specifications
Analog-to-digital
Current input
conversion
Rated input range ±20mA 0mA~20mA 4mA~20mA
Hardware input range -20.2mA~20.2mA -0.2mA~20.2mA 3.8mA~20.2mA
Fiducial error
0.2%
(Room temperature)
Fiducial error
0.5%
(Full temperature range)
Linearity error
(Room temperature) 0.04%
(Full temperature range)
Linearity error 0.10%
Hardware resolution 16 bits
Input impedance 250Ω
Absolute input range ±32mA
Delta Confidential 7
AS04DA-A
Electrical specifications
Module name AS04DA-A
Number of outputs 4
Analog-to-digital
Voltage input/Current input
conversion
Supply voltage 24 VDC (20.4 VDC~28.8 VDC) (-15%~+20%)
Connector type Removable terminal block
Conversion time 2ms/channel
An analog circuit is isolated from a digital circuit by a digital integrated
circuit/an optocoupler, but the analog channels are not isolated from one
another.
Isolation Isolation between a digital circuit and a ground: 500 VDC
Isolation between an analog circuit and a ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between the 24 VDC and a ground: 500 VDC
8
Delta Confidential 8
AS04DA-A
Functional specifications
Analog-to-digital Voltage output
conversion
Rated output range ±10V 0V~10V ±5V 0V~5V 1V~5V
Hardware output range -10.1~10.1V -0.1~10.1V -5.05~5.05V -0.05~5.05V 0.95~5.05V

Fiducial error 0.2%


(Room temperature)

Fiducial error
(Full temperature range) 0.5%
Linearity error 0.05%
(Room temperature)
Linearity error 0.05%
(Full temperature range)
Hardware resolution 12 bits

Output impedance ≧500Ω at 1V~5V

Delta Confidential 9
AS04DA-A
Functional specifications
Analog-to-digital Current output
conversion
Rated output range 0mA~20mA 4mA~20mA
Hardware output range -0.2mA~20.2mA 3.8mA~20.2mA
Fiducial error
0.2%
(Room temperature)
Fiducial error
0.5%
(Full temperature range)
Linearity error
(Room temperature) 0.03%
(Full temperature range)
Linearity error 0.03%
Hardware resolution 12 bits
Output impedance ≦550Ω

Delta Confidential 10
AS06XA-A
Electrical specifications
Module name AS06XA-A
Number of analog 4 inputs
inputs/outputs 2 outputs
Analog-to-digital
Voltage input/Current input/Voltage output/Current output
conversion
Supply voltage 24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type Removable terminal block
Conversion time 2ms/channel
An analog circuit is isolated from a digital circuit by a digital
integrated circuit/an optocoupler, but the analog channels are not
isolated from one another.
Isolation Isolation between a digital circuit and the ground: 500 V DC
Isolation between an analog circuit and the ground: 500 V DC
Isolation between an analog circuit and a digital circuit: 500 V DC
Isolation between the 24 V DC and the ground: 500 V DC
Delta Confidential 11
AS06XA-A
Functional specifications for the analog-to-digital conversion
Analog-to-digital
Voltage input
conversion
Rated input range -10V~10V 0V~10V ±5V 0V~5V 1V~5V
Hardware input range -10.1~10.1V -0.1~10.1V -5.05~5.05V -0.05~5.05V 0.95~5.05V
Fiducial error
0.2%
(Room temperature)
Fiducial error
0.5%
(Full temperature range)
Linearity error
0.02%
(Room temperature)
Linearity error
0.06%
(Full temperature range)
Hardware resolution 16 bits
Input impedance 2MΩ
Absolute input range ±15V

Delta Confidential 12
AS06XA-A
Functional specifications for the analog-to-digital conversion
Analog-to-digital
Current input
conversion
Rated input range ±20mA 0mA~20mA 4mA~20mA
Hardware input range -20.2mA~20.2mA -0.2mA~20.2mA 3.8mA~20.2mA
Fiducial error
(Room temperature) 0.2%

Fiducial error
(Full temperature range) 0.5%
Linearity error
(Room temperature) 0.04%

Linearity error
(Full temperature range) 0.10%
Hardware resolution 16 bits
Input impedance 250Ω
Absolute input range ±32mA

Delta Confidential 13
AS06XA-A
Functional specifications for the digital -to-analog conversion
Digital-to-analog
conversion Voltage output
Rated output range ±10V 0V~10V ±5V 0V~5V 1V~5V
Hardware output range -10.1~10.1V -0.1~10.1V -5.05~5.05V -0.05~5.05V 0.95~5.05V
Fiducial error
(Room temperature) 0.2%

Fiducial error
(Full temperature range) 0.5%
Linearity error
(Room temperature) 0.05%

Linearity error
(Full temperature range) 0.05%
Hardware resolution 12 bits
Permissible load 1 kΩ~2 MΩ: ±10 V and 0 V~10 V
impedance ≧500 Ω: 1 V~5 V

Delta Confidential 14
AS06XA-A
Functional specifications for the digital -to-analog conversion
Digital-to-analog conversion Voltage output
Rated output range 0mA~20mA 4mA~20mA
Hardware output range -0.2mA~20.2mA 3.8mA~20.2mA
Fiducial error
(Room temperature) 0.2%

Fiducial error
(Full temperature range) 0.5%

Linearity error
(Room temperature) 0.03%

Linearity error
(Full temperature range) 0.10%

Hardware resolution 12 bits


Permissible load impedance ≦550Ω

Delta Confidential 15
AS-04RTD
Electrical specifications
Number of
4
analog inputs
2-WIRE & 3-WIRE Pt100/Ni100/Pt1000/Ni1000/JPt100/LG-
Ni1000/Cu50/Cu100/0~300Ω/0~3000Ω
Pt100: DIN 43760-1980 JIS C1604-1989; 100Ω 3850 PPM/°C
Applicable Pt1000: DIN EN60751; 1 kΩ 3850 PPM/°C
sensor Ni100/Ni1000: DIN 43760
JPt100: JIS C1604-1989
LG-Ni1000
Cu50/Cu100
Supply voltage 24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type Removable terminal block

Delta Confidential 16
AS-04RTD
Electrical specifications
25°C/77°F: The error allowed is ±0.1% of full
Pt100/Ni100/Pt1000/Ni1000/ scale.
JPt100 -20~60°C/-4~140°F: The error allowed is
±0.5% of full scale.
25°C/77°F: The error allowed is ±0.1% of full
Overall accuracy LG-Ni1000
scale.
25°C/77°F: The error allowed is ±4% of full
Cu50
scale.
25°C/77°F: The error allowed is ±2% of full
Cu100
scale.
Conversion time Two-wire/Three-wire configuration: 200 ms/channel
An analog circuit is isolated from a digital circuit by a digital integrated
circuit/an optocoupler, and the analog channels are isolated from one
another by optocouplers.
Isolation Isolation between a digital circuit and the ground: 500 V DC
Isolation between an analog circuit and the ground: 500 V DC
Isolation between an analog circuit and the digital circuit: 500 V DC
Isolation between the 24 V DC and the ground: 500 V DC

Delta Confidential 17
AS-04RTD
Functional specifications
Analog-to-
Input
digital Centigrade (°C) Fahrenheit (°F)
impedance
conversion

Pt100:-180°C~800°C Pt100:-292°F~1,472°F
Ni100:-80°C~170°C Ni100:-112°F~338°F
Pt1000:-180°C~800°C Pt1000:-292°F~1,472°F
Rated input Ni1000:-80°C~170°C Ni1000:-112°F~338°F 0~300Ω
range JPt100:-180°C~500°C JPt100:-112°F~338°F 0~3000Ω
LG-Ni100:-50°C~180°C LG-Ni100:-58°F~356°F
Cu50:-50°C~150°C Cu50:-58°F~302°F
Cu100:-50°C~150°C Cu100:-58°F~302°F

Average
Range: 1~100
function
Self-diagnosis Disconnection detection

Delta Confidential 18
AS-04TC
Electrical specifications
Module name AS04TC-A
Number of analog inputs 4
Type J, type K, type R, type S, type T, type E, type N, and type B
Applicable sensor
thermocouples; ±100 mV voltage inputs
Supply voltage 24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type Removable terminal block
25°C/77°F: The error allowed is ±0.5% of full scale.
Overall accuracy
-20~60°C/-4~140°F: The error allowed is ±1% of full scale.
Conversion time 200 ms/channel
An analog circuit is isolated from a digital circuit by a digital
integrated circuit/an optocoupler, and the analog channels are
isolated from one another by optocouplers.
Isolation between a digital circuit and the ground: 500 VDC
Isolation Isolation between an analog circuit and the ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between the 24 V DC and the ground: 500 VDC
Isolation between analog channels: 120 VAC
Delta Confidential 19
AS-04TC
Functional specifications
Analog-to-digital
Centigrade (°C) Fahrenheit (°F) Voltage input
conversion

Type J: -100°C~1,150°C Type J: -148°F~2,102°F


Type K: -100°C~1,350°C Type K: -148°F~2,462°F
Type R: 0°C~1,750°C Type R: 32°F~3,182°F
Rated input Type S: 0°C~1,750°C Type S: 32°F~3,182°F
±100 mV
range Type T: -150°C~390°C Type T: -238°F~734°F
Type E: -150°C~980°C Type E: -238°F~1,796°F
Type N: -150°C~1,280°C Type N: -238°F~2,336°F
Type B: 200°C~1,800°C Type B: 32°F~3,182°F

Average function Range: 1~100


Self-diagnosis Disconnection detection

Delta Confidential 20
AS-F2AD
2 analog signal input channels:
Item Voltage Input Current input
Analog Signal DC 0~+10V DC 4~20mA
Resolution 12-bit 11-bit
Input 2MΩ 250Ω
impedance
Conversion 3ms / CH
time

Digital Value Output


4000

Digital Value O utput


2000
Characteristic
curve
0 10V 4 20mA
Curr ent input
Voltage input

Digital value Card1 SR168 (CH1) SR169 (CH2)


output Card2 SR170 (CH1) SR171 (CH2)

Users can use the program to read the values in SR to obtain the corresponding
A/D conversion value for the channel.

Delta Confidential 21
AS-F2DA
2 analog signal output channels:
Item Voltage output Current output
Analog Signal DC 0~+10V DC 4~20mA
Resolution 12-bit 12-bit
Output
≥1kΩ ≤500Ω
impedance
Conversion
2ms / CH
time
Voltage Output
10V 20mA

Curr ent Output


Characteristic
curve
0 4000 4 4000
Di gital Value Input Digital Value Input

Digital value Card1 SR172(CH1) SR173(CH2)


output Card2 SR174(CH1) SR175(CH2)

Users can use the instruction MOV to move the value to the SR to obtain the
corresponding voltage output value.
Delta Confidential 22
• Hardware Introduction

• Module Setups

• Setup Procedures

• Demonstrations

• Exercises

Delta Confidential 23
Module Setups

24
Delta Confidential
Function Card F2AD/F2DA Setups

25
Delta Confidential
• Hardware Introduction

• Module Setups

• Setup Procedures

• Demonstrations

• Exercises

Delta Confidential 26
Setup Procedures

Delta Confidential 27
Create a New Project

Delta Confidential 28
Set up Communication

Delta Confidential 29
Set up Parameters

Delta Confidential 30
Set up Parameters
Analog range:-32000~32000

User-defined scale range

Example:
AS04AD-A CH1 uses current mode;
the measured range is 0~20mA.
See the values at a glance!
Delta Confidential 31
Set up Parameters

Delta Confidential 32
Download Parameters

Delta Confidential 33
• Hardware Introduction

• Module Setups

• Setup Procedures

• Demonstrations

• Exercises

Delta Confidential 34
Example of AD/DA Modules
Wiring examples of the AIO module

mA 1 2 3
V
+ 1
2 3 +
VR2
- VR1 -

04DA 04AD 04DA


VO1 VO2 V1+ V2+ VO1 VO2
IO1 IO2 I1+ I2+ IO1 IO2
AG AG VI1- VI2- AG AG
SLD SLD V3+ V4+ SLD SLD
VO3 VO4 I3+ I4+ VO3 VO4
IO3 IO4 VI3- VI4- IO3 IO4
AG AG SLD SLD AG AG
SLD SLD • • SLD SLD
• 24V AG 24V • 24V
0V 0V 0V

Delta Confidential 35
Example of AD/DA Modules
【Baseline conditions】
• The switch VR1 on the control panel controls the voltage output and the value is shown on the list in
ISPSoft.
• The switch VR2 on the control panel controls the current output and the value is shown on the list in ISPSoft.
Store the values of voltage input sent by channel 1 of AS04AD, voltage output sent by channel 1 of AS04DA,
voltage output sent by channel 2 of AS04DA and voltage output sent by channel 3 of AS04DA to data
registers via HWCONFIG.
• If the analog range of the voltage input sent by channel 1 of AS04AD is 0V~10.0V, the corresponding digital
value range will be 0~32000.
• If the digital range of the voltage output sent by channel 1/2 of AS04DA is 0V~10.0V, the voltage output of
the corresponding analog value range 0~32000 will be 0V~10.0V.
• If the digital range of the current output sent by channel 3 of AS04DA is 0mA~20.0mA, the current output of
the corresponding analog value range 0~32000 will be 0mA~20.0mA.

【Descriptions on devices】
Devices of PLC Descriptions
D28002 The register of a voltage input sent by channel 1 of AS04AD
D28022 The register of a voltage output sent by channel 1 of AS04DA
D28024 The register of a voltage output sent by channel 2 of AS04DA
D28026 The register of a current output sent by channel 3 of AS04DA
Delta Confidential 36
Example of AD/DA Modules
Create a new
project

Delta Confidential 37
Example of AD/DA Modules
Create
a communication

Delta Confidential 38
Example of AD/DA Modules
Set up a module

Delta Confidential 39
Example of AD/DA Modules
Set up
parameters
for AS04AD

Delta Confidential 40
Example of AD/DA Modules
Set up
parameters
for AS04DA

Delta Confidential 41
Example of AD/DA Modules
Download
parameters

Delta Confidential 42
Example of AD/DA Modules
【Explanation】
• When the PLC runs, the output sent by channel 1 (stored in
D28022) and channel 2 of AS04DA (stored in D28024) is
10V.
• Convert the voltage output value (stored in D28002) sent by
channel 1 of AS04AD to the current output value (stored in
D28026) sent by channel 3 of AS04DA.
• The output sent by channel 1 of AS04DA is 10V. Use the AI-
1 VR switch to divided the voltage and change the voltage
ranging 0~10V on the list of AO-1.
• The output sent by channel 2 of AS04DA is 10V. Use the AI-
2 VR switch to divide the voltage value detected by channel
1 of AS04AD and convert it to current output sent by channel
3 of AS04DA to change the current ranging 0~20mA on the
list of AO-2.

Delta Confidential 43
Example of AS04RTD
【 Baseline conditions 】
Wiring example of the AS332T is connected with a right-side extension module AS04RTD-
temperature module A and uses Pt100 temperature sensor to detect the ambient
temperature. (unit: 0.1 ℃)
Store the values of the detected temperature sent by channel 1 of
AS04RTD to data registers via HWCONFIG.

【 Descriptions on devices 】
Devices of
Descriptions
PLC / HMI
The register for a temperature detected value
D28042
sent by channel 1 of AS04RTD

Delta Confidential 44
Example of AS04RTD
Create a new
project

Delta Confidential 45
Example of AS04RTD
Create
a communication

Delta Confidential 46
Example of AS04RTD
Set up a module

Delta Confidential 47
Example of AS04RTD
Set up
parameters
for AS04RTD

Delta Confidential 48
Example of AS04RTD
Download
parameters

Delta Confidential 49
• Hardware Introduction

• Module Setups

• Setup Procedures

• Demonstrations

• Exercises

Delta Confidential 50
Smarter. Greener. Together.

To learn more about Delta, please visit www.deltaww.com.