AS Series Analog Module Guide
AS Series Analog Module Guide
Analog Modules:
AD/DA/XA/RTD/
TC/Function
Card
VAHID MOGHADAM
09122407352
Outline
• Hardware Introduction
• Module Setups
• Setup Procedures
• Demonstrations
• Exercises
Delta Confidential 2
Purpose
In this chapter, you will learn …..
… more about specifications of the module hardware
… more about module setups
… more about data protection and data backup
3
• Hardware Introduction
• Module Setups
• Setup Procedures
• Demonstrations
• Exercises
Delta Confidential 4
AS04AD-A
Electrical specifications
Module name AS04AD-A
Number of inputs 4
Analog-to-digital Voltage input/Current input
conversion
Supply voltage 24 VDC (20.4 VDC~28.8 VDC) (-15%~+20%)
Connector type Removable terminal block
Conversion time 2ms/channel
Delta Confidential 5
AS04AD-A
Functional specifications
Analog-to-digital
Voltage input
conversion
Rated input range -10~10V 0~10V ±5V 0~5V 1~5V
Hardware input range -10.1~10.1V -0.1~10.1V -5.05~5.05V -0.05~5.05V 0.95~5.05V
Fiducial error
0.2%
(Room temperature)
Fiducial error
0.5%
(Full temperature range)
Linearity error
0.02%
(Room temperature)
Linearity error
0.06%
(Full temperature range)
Hardware resolution 16 bits
Input impedance 2MΩ
Absolute input range ±15V
Delta Confidential 6
AS04AD-A
Functional specifications
Analog-to-digital
Current input
conversion
Rated input range ±20mA 0mA~20mA 4mA~20mA
Hardware input range -20.2mA~20.2mA -0.2mA~20.2mA 3.8mA~20.2mA
Fiducial error
0.2%
(Room temperature)
Fiducial error
0.5%
(Full temperature range)
Linearity error
(Room temperature) 0.04%
(Full temperature range)
Linearity error 0.10%
Hardware resolution 16 bits
Input impedance 250Ω
Absolute input range ±32mA
Delta Confidential 7
AS04DA-A
Electrical specifications
Module name AS04DA-A
Number of outputs 4
Analog-to-digital
Voltage input/Current input
conversion
Supply voltage 24 VDC (20.4 VDC~28.8 VDC) (-15%~+20%)
Connector type Removable terminal block
Conversion time 2ms/channel
An analog circuit is isolated from a digital circuit by a digital integrated
circuit/an optocoupler, but the analog channels are not isolated from one
another.
Isolation Isolation between a digital circuit and a ground: 500 VDC
Isolation between an analog circuit and a ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between the 24 VDC and a ground: 500 VDC
8
Delta Confidential 8
AS04DA-A
Functional specifications
Analog-to-digital Voltage output
conversion
Rated output range ±10V 0V~10V ±5V 0V~5V 1V~5V
Hardware output range -10.1~10.1V -0.1~10.1V -5.05~5.05V -0.05~5.05V 0.95~5.05V
Fiducial error
(Full temperature range) 0.5%
Linearity error 0.05%
(Room temperature)
Linearity error 0.05%
(Full temperature range)
Hardware resolution 12 bits
Delta Confidential 9
AS04DA-A
Functional specifications
Analog-to-digital Current output
conversion
Rated output range 0mA~20mA 4mA~20mA
Hardware output range -0.2mA~20.2mA 3.8mA~20.2mA
Fiducial error
0.2%
(Room temperature)
Fiducial error
0.5%
(Full temperature range)
Linearity error
(Room temperature) 0.03%
(Full temperature range)
Linearity error 0.03%
Hardware resolution 12 bits
Output impedance ≦550Ω
Delta Confidential 10
AS06XA-A
Electrical specifications
Module name AS06XA-A
Number of analog 4 inputs
inputs/outputs 2 outputs
Analog-to-digital
Voltage input/Current input/Voltage output/Current output
conversion
Supply voltage 24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type Removable terminal block
Conversion time 2ms/channel
An analog circuit is isolated from a digital circuit by a digital
integrated circuit/an optocoupler, but the analog channels are not
isolated from one another.
Isolation Isolation between a digital circuit and the ground: 500 V DC
Isolation between an analog circuit and the ground: 500 V DC
Isolation between an analog circuit and a digital circuit: 500 V DC
Isolation between the 24 V DC and the ground: 500 V DC
Delta Confidential 11
AS06XA-A
Functional specifications for the analog-to-digital conversion
Analog-to-digital
Voltage input
conversion
Rated input range -10V~10V 0V~10V ±5V 0V~5V 1V~5V
Hardware input range -10.1~10.1V -0.1~10.1V -5.05~5.05V -0.05~5.05V 0.95~5.05V
Fiducial error
0.2%
(Room temperature)
Fiducial error
0.5%
(Full temperature range)
Linearity error
0.02%
(Room temperature)
Linearity error
0.06%
(Full temperature range)
Hardware resolution 16 bits
Input impedance 2MΩ
Absolute input range ±15V
Delta Confidential 12
AS06XA-A
Functional specifications for the analog-to-digital conversion
Analog-to-digital
Current input
conversion
Rated input range ±20mA 0mA~20mA 4mA~20mA
Hardware input range -20.2mA~20.2mA -0.2mA~20.2mA 3.8mA~20.2mA
Fiducial error
(Room temperature) 0.2%
Fiducial error
(Full temperature range) 0.5%
Linearity error
(Room temperature) 0.04%
Linearity error
(Full temperature range) 0.10%
Hardware resolution 16 bits
Input impedance 250Ω
Absolute input range ±32mA
Delta Confidential 13
AS06XA-A
Functional specifications for the digital -to-analog conversion
Digital-to-analog
conversion Voltage output
Rated output range ±10V 0V~10V ±5V 0V~5V 1V~5V
Hardware output range -10.1~10.1V -0.1~10.1V -5.05~5.05V -0.05~5.05V 0.95~5.05V
Fiducial error
(Room temperature) 0.2%
Fiducial error
(Full temperature range) 0.5%
Linearity error
(Room temperature) 0.05%
Linearity error
(Full temperature range) 0.05%
Hardware resolution 12 bits
Permissible load 1 kΩ~2 MΩ: ±10 V and 0 V~10 V
impedance ≧500 Ω: 1 V~5 V
Delta Confidential 14
AS06XA-A
Functional specifications for the digital -to-analog conversion
Digital-to-analog conversion Voltage output
Rated output range 0mA~20mA 4mA~20mA
Hardware output range -0.2mA~20.2mA 3.8mA~20.2mA
Fiducial error
(Room temperature) 0.2%
Fiducial error
(Full temperature range) 0.5%
Linearity error
(Room temperature) 0.03%
Linearity error
(Full temperature range) 0.10%
Delta Confidential 15
AS-04RTD
Electrical specifications
Number of
4
analog inputs
2-WIRE & 3-WIRE Pt100/Ni100/Pt1000/Ni1000/JPt100/LG-
Ni1000/Cu50/Cu100/0~300Ω/0~3000Ω
Pt100: DIN 43760-1980 JIS C1604-1989; 100Ω 3850 PPM/°C
Applicable Pt1000: DIN EN60751; 1 kΩ 3850 PPM/°C
sensor Ni100/Ni1000: DIN 43760
JPt100: JIS C1604-1989
LG-Ni1000
Cu50/Cu100
Supply voltage 24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type Removable terminal block
Delta Confidential 16
AS-04RTD
Electrical specifications
25°C/77°F: The error allowed is ±0.1% of full
Pt100/Ni100/Pt1000/Ni1000/ scale.
JPt100 -20~60°C/-4~140°F: The error allowed is
±0.5% of full scale.
25°C/77°F: The error allowed is ±0.1% of full
Overall accuracy LG-Ni1000
scale.
25°C/77°F: The error allowed is ±4% of full
Cu50
scale.
25°C/77°F: The error allowed is ±2% of full
Cu100
scale.
Conversion time Two-wire/Three-wire configuration: 200 ms/channel
An analog circuit is isolated from a digital circuit by a digital integrated
circuit/an optocoupler, and the analog channels are isolated from one
another by optocouplers.
Isolation Isolation between a digital circuit and the ground: 500 V DC
Isolation between an analog circuit and the ground: 500 V DC
Isolation between an analog circuit and the digital circuit: 500 V DC
Isolation between the 24 V DC and the ground: 500 V DC
Delta Confidential 17
AS-04RTD
Functional specifications
Analog-to-
Input
digital Centigrade (°C) Fahrenheit (°F)
impedance
conversion
Pt100:-180°C~800°C Pt100:-292°F~1,472°F
Ni100:-80°C~170°C Ni100:-112°F~338°F
Pt1000:-180°C~800°C Pt1000:-292°F~1,472°F
Rated input Ni1000:-80°C~170°C Ni1000:-112°F~338°F 0~300Ω
range JPt100:-180°C~500°C JPt100:-112°F~338°F 0~3000Ω
LG-Ni100:-50°C~180°C LG-Ni100:-58°F~356°F
Cu50:-50°C~150°C Cu50:-58°F~302°F
Cu100:-50°C~150°C Cu100:-58°F~302°F
Average
Range: 1~100
function
Self-diagnosis Disconnection detection
Delta Confidential 18
AS-04TC
Electrical specifications
Module name AS04TC-A
Number of analog inputs 4
Type J, type K, type R, type S, type T, type E, type N, and type B
Applicable sensor
thermocouples; ±100 mV voltage inputs
Supply voltage 24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type Removable terminal block
25°C/77°F: The error allowed is ±0.5% of full scale.
Overall accuracy
-20~60°C/-4~140°F: The error allowed is ±1% of full scale.
Conversion time 200 ms/channel
An analog circuit is isolated from a digital circuit by a digital
integrated circuit/an optocoupler, and the analog channels are
isolated from one another by optocouplers.
Isolation between a digital circuit and the ground: 500 VDC
Isolation Isolation between an analog circuit and the ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between the 24 V DC and the ground: 500 VDC
Isolation between analog channels: 120 VAC
Delta Confidential 19
AS-04TC
Functional specifications
Analog-to-digital
Centigrade (°C) Fahrenheit (°F) Voltage input
conversion
Delta Confidential 20
AS-F2AD
2 analog signal input channels:
Item Voltage Input Current input
Analog Signal DC 0~+10V DC 4~20mA
Resolution 12-bit 11-bit
Input 2MΩ 250Ω
impedance
Conversion 3ms / CH
time
Users can use the program to read the values in SR to obtain the corresponding
A/D conversion value for the channel.
Delta Confidential 21
AS-F2DA
2 analog signal output channels:
Item Voltage output Current output
Analog Signal DC 0~+10V DC 4~20mA
Resolution 12-bit 12-bit
Output
≥1kΩ ≤500Ω
impedance
Conversion
2ms / CH
time
Voltage Output
10V 20mA
Users can use the instruction MOV to move the value to the SR to obtain the
corresponding voltage output value.
Delta Confidential 22
• Hardware Introduction
• Module Setups
• Setup Procedures
• Demonstrations
• Exercises
Delta Confidential 23
Module Setups
24
Delta Confidential
Function Card F2AD/F2DA Setups
25
Delta Confidential
• Hardware Introduction
• Module Setups
• Setup Procedures
• Demonstrations
• Exercises
Delta Confidential 26
Setup Procedures
Delta Confidential 27
Create a New Project
Delta Confidential 28
Set up Communication
Delta Confidential 29
Set up Parameters
Delta Confidential 30
Set up Parameters
Analog range:-32000~32000
Example:
AS04AD-A CH1 uses current mode;
the measured range is 0~20mA.
See the values at a glance!
Delta Confidential 31
Set up Parameters
Delta Confidential 32
Download Parameters
Delta Confidential 33
• Hardware Introduction
• Module Setups
• Setup Procedures
• Demonstrations
• Exercises
Delta Confidential 34
Example of AD/DA Modules
Wiring examples of the AIO module
mA 1 2 3
V
+ 1
2 3 +
VR2
- VR1 -
Delta Confidential 35
Example of AD/DA Modules
【Baseline conditions】
• The switch VR1 on the control panel controls the voltage output and the value is shown on the list in
ISPSoft.
• The switch VR2 on the control panel controls the current output and the value is shown on the list in ISPSoft.
Store the values of voltage input sent by channel 1 of AS04AD, voltage output sent by channel 1 of AS04DA,
voltage output sent by channel 2 of AS04DA and voltage output sent by channel 3 of AS04DA to data
registers via HWCONFIG.
• If the analog range of the voltage input sent by channel 1 of AS04AD is 0V~10.0V, the corresponding digital
value range will be 0~32000.
• If the digital range of the voltage output sent by channel 1/2 of AS04DA is 0V~10.0V, the voltage output of
the corresponding analog value range 0~32000 will be 0V~10.0V.
• If the digital range of the current output sent by channel 3 of AS04DA is 0mA~20.0mA, the current output of
the corresponding analog value range 0~32000 will be 0mA~20.0mA.
【Descriptions on devices】
Devices of PLC Descriptions
D28002 The register of a voltage input sent by channel 1 of AS04AD
D28022 The register of a voltage output sent by channel 1 of AS04DA
D28024 The register of a voltage output sent by channel 2 of AS04DA
D28026 The register of a current output sent by channel 3 of AS04DA
Delta Confidential 36
Example of AD/DA Modules
Create a new
project
Delta Confidential 37
Example of AD/DA Modules
Create
a communication
Delta Confidential 38
Example of AD/DA Modules
Set up a module
Delta Confidential 39
Example of AD/DA Modules
Set up
parameters
for AS04AD
Delta Confidential 40
Example of AD/DA Modules
Set up
parameters
for AS04DA
Delta Confidential 41
Example of AD/DA Modules
Download
parameters
Delta Confidential 42
Example of AD/DA Modules
【Explanation】
• When the PLC runs, the output sent by channel 1 (stored in
D28022) and channel 2 of AS04DA (stored in D28024) is
10V.
• Convert the voltage output value (stored in D28002) sent by
channel 1 of AS04AD to the current output value (stored in
D28026) sent by channel 3 of AS04DA.
• The output sent by channel 1 of AS04DA is 10V. Use the AI-
1 VR switch to divided the voltage and change the voltage
ranging 0~10V on the list of AO-1.
• The output sent by channel 2 of AS04DA is 10V. Use the AI-
2 VR switch to divide the voltage value detected by channel
1 of AS04AD and convert it to current output sent by channel
3 of AS04DA to change the current ranging 0~20mA on the
list of AO-2.
Delta Confidential 43
Example of AS04RTD
【 Baseline conditions 】
Wiring example of the AS332T is connected with a right-side extension module AS04RTD-
temperature module A and uses Pt100 temperature sensor to detect the ambient
temperature. (unit: 0.1 ℃)
Store the values of the detected temperature sent by channel 1 of
AS04RTD to data registers via HWCONFIG.
【 Descriptions on devices 】
Devices of
Descriptions
PLC / HMI
The register for a temperature detected value
D28042
sent by channel 1 of AS04RTD
Delta Confidential 44
Example of AS04RTD
Create a new
project
Delta Confidential 45
Example of AS04RTD
Create
a communication
Delta Confidential 46
Example of AS04RTD
Set up a module
Delta Confidential 47
Example of AS04RTD
Set up
parameters
for AS04RTD
Delta Confidential 48
Example of AS04RTD
Download
parameters
Delta Confidential 49
• Hardware Introduction
• Module Setups
• Setup Procedures
• Demonstrations
• Exercises
Delta Confidential 50
Smarter. Greener. Together.