Project: ETAP Page: 1

Location: 20.6.0C Date: 23-09-2024

Contract: SN:

Engineer: Revision: Base


Study Case: SM
Filename: TRAN MINH TAN 20DCLC3 20N28 Config.: Normal

Short-Circuit Summary Report

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus42 110.000 1.848 4.085 1.848 1.771 3.916 1.771 1.771 1.601 3.540 1.601 1.601 1.886 4.170 1.886 1.886

All fault currents are in rms kA. Current ip is calculated using Method C.

* LLG fault current is the larger of the two faulted line currents.
Project: ETAP Page: 2

Location: 20.6.0C Date: 23-09-2024

Contract: SN:

Engineer: Revision: Base


Study Case: SM
Filename: TRAN MINH TAN 20DCLC3 20N28 Config.: Normal

Sequence Impedance Summary Report

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)

ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus42 110.000 7.35102 37.08821 37.80969 7.39894 37.02728 37.75929 2.15061 43.01218 43.06591 0.00000 0.00000 0.00000
Project: ETAP Page: 3

Location: 20.6.0C Date: 23-09-2024

Contract: SN:

Engineer: Revision: Base


Study Case: SM
Filename: TRAN MINH TAN 20DCLC3 20N28 Config.: Normal

Sequence-of-Operation Event Summary Report

Symmetrical 3-Phase Fault at Bus42.

Time (ms) ID If (kA) T1 (ms) T2 (ms) Condition


90.0 relay1 1.848 90.0 Phase - OC1 - 50

145 CB3 55.0 Tripped by relay1 Phase - OC1 - 50