EDWARDS® Catalog u Intelligent Input-Output
LIFE SAFETY        &   INCIDENT MANAGEMENT
Input/Output
Modules
SIGA-IO, SIGA-MIO
                                                                                                                           7300-1657:
                                                                                                                              0210    S3424
Overview                                                             Standard Features
SIGA-IO and MIO Input/Output Modules are intelligent analog          • 10 modules in one
addressable devices that form part of EDWARDS’s Signature              Multiple applications including normally-open or normally-
line of products. The actual operation of the SIGA-IO and MIO          closed alarm relay and latching or non-latching alarm inputs.
is determined by the “personality code” selected by the installer,     The installer selects one of up to 10 personality codes to be
which is downloaded to the module from the Signature loop              downloaded from the loop controller.
controller during system configuration.
                                                                     • Adjustable time delays
Depending on their assigned personality, Input/Output Modules          User sets the expected response time (5 - 120 seconds) for
provide the following modes of operation:                              maximum flexibility.
  • Output with monitor input (two personalities)                    • Plug in (UIO) or standard 1-gang mount
  • Input/programmable output (eight personalities)                    UIO versions allow quick installation where multiple modules
Each IO module requires one module address.                            are required. The 1-gang mount version is ideal for remote
                                                                       locations that require a single module.
                                                                     • Automatic device mapping
                                                                       Signature modules transmit information to the loop controller
                                                                       regarding their circuit locations with respect to other Signature
                                                                       devices on the wire loop.
                                                                     • Electronic addressing
                                                                       Programmable addresses are downloaded from the loop
                                                                       controller, a PC, or the SIGA-PRO Signature Program/Service
                                                                       Tool. There are no switches or dials to set.
                                                                     • Intelligent device with microprocessor
                                                                       All decisions are made at the module to allow lower
                                                                       communication speed with substantially improved control panel
                                                                       response time and less sensitivity to line noise and loop wiring
                                                                       properties; twisted or shielded wire is not required.
Page 1 of 6                                                                                       D ATA S H E E T    E85001-0533
                                                                                        Not to be used for installation purposes. Issue 1.1
Application                                                           Personality codes 33: Alarm input and N.O. relay output
                                                                      Personality code 33 configures the module as a normally-open,
The SIGA-IO mounts to a standard North American one-gang              dry-contact relay and an alarm latching input for Class B contact
electrical box, making it ideal for locations where only one module   initiating devices. When the input contact of the initiating device
is required. Separate I/O and data loop connections are made to       changes state, the I/O module sends an alarm signal to the
each module.                                                          Signature loop controller and the alarm condition is latched at the
The SIGA-MIO is part of the UIO family of plug-in Signature           module.
Series modules. It functions identically to the SIGA-IO, but          Personality code 34: Alarm input and N.C. relay output
takes advantage of the modular flexibility and easy installation      Personality code 34 operates the same as personality code 33,
that characterize all UIO modules. Two- and six-module UIO            except that the output is configured as a normally closed, dry-
motherboards are available. These can accommodate individual          contact relay.
risers for each on-board module, or risers that are shared by any
combination of its UIO modules. All wiring connections are made       Personality code 35: Delayed alarm input and N.O. relay
to terminal blocks on the motherboard. UIO assemblies may be          output
mounted in EDWARDS enclosures.                                        Personality code 35 configures the module as a normally-open,
                                                                      dry-contact relay and an alarm latching input for Class B contact
                                                                      initiating devices. This personality requires that a change in the
                                                                      state of the initiating device be maintained for approximately
Electronic Addressing                                                 16 seconds before the I/O module sends an alarm signal to
The loop controller electronically addresses each module saving       the Signature loop controller. The alarm condition is latched at
valuable time during system commissioning. Setting complicated        the module. Use only with non-retarded, N.O. waterflow alarm
switches or dials is not required. Each module has its own unique     switches.
serial number stored in its “on-board memory”. The loop controller
                                                                      Personality code 36: Delayed alarm input and N.C. relay
identifies each device on the loop and assigns a “soft” address
                                                                      output
to each serial number. If desired, the modules can be addressed
                                                                      Personality code 36 operates the same as personality code 35,
using the SIGA-PRO Signature Program/Service Tool.
                                                                      except that the output is configured as a normally closed, dry-
                                                                      contact relay. Use only with non-retarded, N.C. waterflow alarm
                                                                      switches.
Personality Codes                                                     Personality code 37: Active input (non-latching) and N.O.
A signature module requires a Signature loop controller to            relay output
download the personality code that determines how it will             Personality code 37 configures the module as a normally-open,
operate. The Input/Output Module provides personality codes 31        dry-contact relay and an active input for Class B contact initiating
through 40. For personalities 33 through 40, the outputs must be      devices. When the input contact of the initiating device changes
programmed to be activated by the panel.                              state, the I/O module sends an active signal to the Signature loop
Personality code 31 (default): N.O. relay output with monitor         controller. The active signal does not latch, and restores when
input                                                                 the input device returns to its normal state. Typically used for
Personality code 31 configures the module as a normally-open          monitoring N.O. fans, dampers, doors, etc.
output relay contact that requires a maintained dry contact           Personality codes 38: Active input (non-latching) and N.C.
input activation. The activation must take place within a time        relay output
period defined by the user (15 seconds default; 5 - 120 seconds       Personality code 38 operates the same as personality code 37,
selectable) after the output circuit activation. If the fire alarm    except that the output is configured as a normally closed, dry-
control panel does not receive a monitor input within the specified   contact relay. Typically used for monitoring N.C. fans, dampers,
time, it will generate a trouble condition.                           doors, etc.
Personality code 32: N.C. relay output with monitor input             Personality code 39: Active input (latching) and N.O. relay
Personality code 32 operates the same as personality code 31,         output
except that the output is configured as a normally closed, dry-       Personality code 39 configures the module as a normally-open,
contact relay.                                                        dry-contact relay and an active latching input for Class B contact
                                                                      initiating devices. When the input contact of the initiating device
                                                                      changes state, the I/O module sends an active signal to the
                                                                      Signature loop controller and the active condition is latched at the
                                                                      module.
                                                                      Personality code 40: Active input (latching) and N.C. relay
                                                                      output
                                                                      Personality code 40 operates the same as personality code 39,
                                                                      except that the output is configured as a normally closed, dry-
                                                                      contact relay.
Page 2 of 6                                                                                         D ATA S H E E T   E85001-0533
                                                                                         Not to be used for installation purposes. Issue 1.1
Installation                                                              Warnings & Cautions
The SIGA-IO: modules mount to North American 2½ inch (64                  This module will not operate without electrical power. As fires
mm) deep 1-gang boxes and 1½ inch (38 mm) deep 4 inch                     frequently cause power interruption, we suggest you discuss
square boxes with 1-gang covers. They also can be snapped                 further safeguards with your fire protection specialist.
directly to the SIGA-MP mounting plates. The terminals are suited
for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.                       EDWARDS recommends that these modules be installed
                                                                          according to latest recognized edition of national and local fire
                                                                          alarm codes.
                              UIO Motherboard
                                                                          Testing & Maintenance
                                          Plug-in (UIO)                   The module’s automatic self-diagnosis identifies when it is
                                             Module
                                                                          defective and causes a trouble message. The user-friendly
                                                                          maintenance program shows the current state of each module
                                                                          and other pertinent messages. Single modules may be turned off
                                                                          (de-activated) temporarily, from the control panel.
                    Cabinet or electrical enclosure
                                                                          Scheduled maintenance (Regular or Selected) for proper system
                                                                          operation should be planned to meet the requirements of the
                                                                          Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and
SIGA-MIO: mount the UIOxR motherboard inside a suitable                   ULC CAN/ULC 536 standards.
EDWARDS enclosure with screws and washers provided. Plug the
module into any available position on the motherboard and secure
the module to the motherboard with the captive screws. Wiring
connections are made to the terminals on the motherboard (see             Compatibility
wiring diagram). UIOxR motherboard terminals are suited for #12           These modules are part of EDWARDS’s Signature Series intelligent
to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.                               processing and control platform. They are compatible with EST3,
                                                                          EST3X and iO Series control panels.
                                          Compatible electrical box
                                                      Wall plate, white
                                                         (1-gang)
                                                                M
                                                           ALAR
                                                      FIRE DULE
                                                        MO
Page 3 of 6                                                                                             D ATA S H E E T    E85001-0533
                                                                                              Not to be used for installation purposes. Issue 1.1
Typical Wiring (SIGA-IO)
Modules will accept #18 AWG to #12 AWG (0.75mm2 to 2.50mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2)
are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.
Input/Output Module (personality codes 31 - 40)
                                                            8
                                                                                                                                        Wiring Notes:
            N.O. or N.C.                                                                                                                 1
    5                                                                                                                                        Maximum 25 Ohm resistance per wire.
            N.O. or N.C.                                                                                              UL/ULC
                                                                                                                      Listed             2   #12 AWG (2.5 mm²) max; #18 AWG (0.75²) mm min.
                                                                                                                      47 kW              3
                                                                                                                      EOL                    10 Vdc @ 350 mA, max.
                                                                                                                                         4   See the loop controller installation sheet for wiring
                                                                                                                                             specifications.
Input/Output Module
               7 2 (personality codes
                                   6 31
                                      3 2- 40)
                                            1
                                                                                      Input/Output Module                                5   System programming determines whether contact
                                                            8 TB2                                                                            will be normally-open (N/O) or normally-closed (N/C).
            N.O. or N.C.                           8 7 65                                                                                6   Supervised and power-limited.
    5       N.O. or N.C.                                                                                              UL/ULC             7   Power-limited unless connected to a nonpower-
             Red LED (Active/Alarm)                                         Green LED (Normal/Trouble)                Listed
                                                                                                                                             limited source. If the source is nonpower-limited,
                                                                                                                      47 kW                  eliminate the power-limited mark and:
                                                                                                                      EOL                    • Maintain a 1/4-inch (6.4 mm) space from power-
                                                   4 3 21
                                                                                                                                                limited wiring.
                              7   2                             TB1   6     3     2      1                                                   or
                                                                                                                                             • Use FPL, FPLR, FPLP, or an equivalent cable in
                                                                                      Input/Output Module                                       accordance with the National Electric Code.
                         6   4    2                             TB2
                                                                                                                                         8   The Nomex isolation barrior separates power-limited
From loop controller Data in (+)                   8 7 65                 Data out (-)
                                                                                             To next device                                  and nonpower-limited wiring. Watch out for the sharp
or previous device   Data in (-)                                          Data out (+)                                                       corners during installation and maintenance.
          Red LED (Active/Alarm)                                           Green LED (Normal/Trouble)
                                                   4 3 21
                                                                TB1
                         6   4    2
Input/Output
From loop controller Module
                     Data in (+) (personality codes 31out-(-)40)
                                                  Data
                                                                                             To next device
Typical      Wiring
or previous device Data(SIGA-MIO)
                        in (-)                                            Data out (+)
        5
Modules will accept #12 AWG (2.5mm2), #18 AWG (0.75mm2), #16 (1.0mm2), and #14 AWG (1.50mm2) wire sizes. Note: Sizes #16 AWG
(1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring
requirement specifications. 1 2 4
                                                                                       TB1 through TB6
Green LED (Normal/Trouble)                                                            Input/Output Module
    Red LED (Active/Alarm)                             1 23 4
 Input/Output Module (personality codes 31 UIO2R
                                           - 40)or UIO6R motherboard
                              4   3
               Data In
        5
                                      4
                 Data                 3                                                                                                 Wiring Notes:
                 Circuit              2
                                      1                                                                                                  1   Maximum 25 Ohm resistance per wire. Maximum
                                          1 TB72   4
                                                                                       TB1 through TB6                                       circuit capacitance of 0.1 mF.
          Data Out
Green LED (Normal/Trouble)                                                            Input/Output Module                                2
                                                                              4
                                                                                                                                             10 Vdc @ 350 mA, max.
    Red LED (Active/Alarm)                             1 23 4                          No connections required
                                                                              3   UIO2R
                                                                                    for MIO.or UIO6R
                                                                                             Other      motherboard
                                                                                                   modules
                                                                              2                                                          3   See the Signature loop controller installation sheet for
                                                                                       May require connections.
                              4   3                                           1                                                              wiring specifications.
                                                                          TB15
               Data In                                                            Remove motherboard jumpers.                            4   Supervised and power-limited
                                   4                   1 23 4                                                                            5   UL/ULC listed 47 kW EOL
                Data
               TB8  through   TB13 3
                Circuit            2                                                                                                     6   System programming determines whether contact
                                   1
                                                                                                                                             will be normally-open (N/O) or normally-closed (N/C).
                                           TB7                        7     6 Dry contact relay
              Data Out                                                                                                                   7   Power-limited unless connected to a nonpower-
                                                                              4        No connections required                               limited source. If the source is nonpower-limited,
                                                                              3
                                                                              2
                                                                                       for MIO. Other modules                                eliminate the power-limited mark and:
                                                                                       May require connections.
                                                                              1                                                              • Maintain a 1/4-inch (6.4 mm) space from power-
                                                                          TB15                                                                  limited wiring.
                                                                                  Remove motherboard jumpers.                                or
                                                                                                                                             • Use FPL, FPLR, FPLP, or an equivalent cable in
                                                       1 23 4                                                                                   accordance with the National Electric Code.
               TB8 through TB13
                                                                                                                                        8    See the UIO2R or UIO6R installation sheet for
                                                                                                                                             additional instructions about the separation of power-
                                                                      7     6 Dry contact relay                                              limited and nonpower-limited wiring.
Page 4 of 6                                                                                                                               D ATA S H E E T            E85001-0533
                                                                                                                               Not to be used for installation purposes. Issue 1.1
Signature Series Overview
The Signature Series intelligent analog-addressable system from                    Fast Stable Communication – Built-in intelligence means less information
EDWARDS is an entire family of multi-sensor detectors and mounting                 needs to be sent between the device and the Signature Data Controller
bases, multiple-function input and output modules, network and non-                (SDC). Other than regular supervisory polling response, Signature devices
network control panels, and user-friendly maintenance and service tools.           only need to communicate with the SDC when they have something new
Analog information from equipment connected to Signature devices is                to report. This provides very fast control panel response and allows a lower
gathered and converted into digital signals. An onboard microprocessor             baud rate (speed) to be used for communication on the circuit. The lower
in each Signature device measures and analyzes the signal and decides              baud rate offers several advantages including:
whether or not to input an alarm. The microprocessor in each Signature
device provides four additional benefits – Self-diagnostics and History Log,        • Less sensitivity to circuit wire characteristics.
Automatic Device Mapping, and Fast, Stable Communication.                           • Less sensitivity to noise glitches on the cable.
Self-diagnostics and History Log – Each Signature Series device                     • Less emitted noise from the data wiring.
constantly runs self-checks to provide important maintenance information.
The results of the self-check are automatically updated and permanently             • Twisted or shielded wiring is not required.
stored in its non-volatile memory. This information is accessible for review
                                                                                   Diagnostic LEDs – Twin LEDs on most Signature devices provide visual
any time at the control panel, PC, or using the SIGA-PRO Signature
                                                                                   indication of normal and alarm-active conditions. A flashing green LED
Program/Service Tool.
                                                                                   shows normal system polling. A flashing red LED means the module is in
Automatic Device Mapping –The Signature Data Controller (SDC) learns               alarm-active state.
where each device’s serial number address is installed relative to other
                                                                                   Testing & Maintenance – Automatic self-diagnosis identifies when a
devices on the circuit. The SDC keeps a “map” of all Signature Series
                                                                                   Signature device is defective and causes a trouble message. The user-
devices connected to it. The Signature Series Data Entry Program also
                                                                                   friendly maintenance program shows the current state of each device and
uses the mapping feature. With interactive menus and graphic support, the
                                                                                   other pertinent information. Single devices may be turned off temporarily, from
wired circuits between each device can be examined. Layout or “as-built”
                                                                                   the control panel. Scheduled maintenance (Regular or Selected) for proper
drawing information showing branch wiring (T-taps), device types and their
                                                                                   system operation should be planned to meet the requirements of the Authority
address are stored on disk for printing hard copy. This takes the mystery
                                                                                   Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC
out of the installation. The preparation of “as-built” drawings is fast and
                                                                                   536 standards.
efficient.
                                                                                   Quality and Reliability – EDWARDS Signature devices are manufactured
Most Signature modules use a “personality code” selected by the installer
                                                                                   in North America to strict international ISO 9001 standards. All electronics
to determine their actual function. Personality codes are downloaded
                                                                                   utilize surface mount technology (SMT) for smaller size and greater immunity
from the SDC during system configuration and are indicated during
                                                                                   to RF noise. A conformal coating is used for humidity and corrosion
device mapping.
                                                                                   resistance.
Specifications
 Model                                                  SIGA-IO                                                            SIGA-MIO
 Description                               Standard Mount Input/Output Module                                  Plug-in (UIO) Input/Output Module
                                  North American 2½ inch (64 mm) deep one-gang boxes
 Mounting                        and 1½ inch (38 mm) deep 4 inch square boxes with one-                 Plugs into UIO2R or UIO6R Motherboards only.
                                        gang covers and SIGA-MP mounting plates
 Current
                    Standby                                                                 250 µA
                   Activated                                                                430 µA
 Relay type                                                                              Form A or B.
 Contact ratings (pilot duty)                                24 Vdc: 2 A.      120 Vac: 0.5 A (Not rated for capacitive loads.)
 Initiating Device Circuit
   EOL (end-of-line) resistor                                                     UL/ULC listed 47k Ohm
       Max. circuit resistance                                                  50 Ohm (25 Ohms per wire)
    Max. circuit capacitance                                                              0.1 µF
 Wiring Terminations                                               Suitable for #12 to #18 AWG (2.5 mm² to 0.75mm²)
 Personality Codes                                                            Ten Selectable Codes Available
 Address Requirements                                                            Uses One Module Address
 Operating Voltage                                                          15.2 to 19.95 Vdc (19 Vdc nominal)
 Construction                                                                High Impact Engineering Polymer
 Environment
      Operating Temperature                                              32° F to 120° F (0° C to 49° C)
        Storage Temperature                                             -4° F to 140° F (-20° C to 60° C)
                      Humidity                                                    0 to 93% RH
 LED Operation                             On-board Green LED - Flashes when polled; On-board Red LED - Flashes when in alarm/active
 Compatibility                      Use SIGA-IO and SIGA-MIO with: Signature Loop Controller Plug SIGA-MIO into: UIO6R or UIO2R Motherboards
 Agency Listings                                                              UL, ULC, MEA, CSFM
Page 5 of 6                                                                                                         D ATA S H E E T       E85001-0533
                                                                                                          Not to be used for installation purposes. Issue 1.1
                                                     Ordering Information
                                                     Catalog                                                                             Ship Wt.
                                                                    Description
                                                     Number                                                                              lbs (kg)
                                                                                                                                           0.34
                                                     SIGA-IO        Input/Output Module (Standard Mount) - UL/ULC Listed
   L I F E S A F E TY & I NCI DE NT M AN AGEM EN T                                                                                        (0.15)
                                                                                                                                           0.22
  Contact us                                         SIGA-MIO       Input/Output Module (Plug-in) - UL/ULC Listed
                                                                                                                                          (0.10)
  Phone: 800-655-4497 (Option 4)
  Email:   edwards.fire@carrier.com
  Website: edwardsfiresafety.com                     Related Equipment
                                                     27193-11     Surface Mount Box - Red, 1-gang                                          2 (1.2)
  8985 Town Center Pkwy
  Bradenton, FL 34202                                27193-16     Surface Mount Box - White, 1-gang                                        2 (1.2)
                                                                  Universal Input-Output Module Board w/Riser Inputs                        0.32
                                                     SIGA-UIO2R
  © 2020 Carrier                                                  - Two Module Positions                                                   (0.15)
  All rights reserved.                                            Universal Input-Output Module Board w/Riser Inputs                        0.62
                                                     SIGA-UIO6R
                                                                  - Six Module Positions                                                   (0.28)
                                                                  UL listed cabinet for mounting releasing modules, red with white
                                                     MFC-A                                                                                7.0 (3.1)
                                                                  “FIRE”.
                                                                    Transponder Mounting Bracket (allows for mounting
                                                     SIGA-MB4                                                                            0.4 (0.15)
                                                                    two 1-gang modules in a 2-gang box)
                                                     SIGA-MP1       Signature Module Mounting Plate, 1 footprint                         1.5 (0.70)
                                                     SIGA-MP2       Signature Module Mounting Plate, 1/2 footprint                       0.5 (0.23)
                                                                                                                                            1.02
                                                     SIGA-MP2L      Signature Module Mounting Plate, 1/2 extended footprint
                                                                                                                                           (0.46)
                                                                                                                                                       04-04-20
Page 6 of 6                                                                                                D ATA S H E E T     E85001-0533
                                                                                                 Not to be used for installation purposes. Issue 1.1