Lighting Calculation
Lighting Calculation
         LIGHTING CALCULATION
            September 2021
   HAMAD MEDICAL CORPORATION
LIGHTING CALCULATION
SEPTEMBER 2021
CONSULTANT
                DSG W.L.L.
  Architectural and Engineering Consultancy
                 P.O. Box 5785
           Doha, The State of Qatar
PROJECT SPECIFICATION
                    INDEX
Date                9/6/2021
Object
Alwaab Doha Qatar
Basement Floor - Lighting Design
Luminaire list
                                                                                                               4
Basement Floor - Lighting Design
P 28.0 W
ΦLamp 3900 lm
ΦLuminaire 3900 lm
η 100.00 %
CRI 80
Index B2
                                                                 5
Basement Floor - Lighting Design
P 57.0 W
ΦLamp 7700 lm
ΦLuminaire 7700 lm
η 100.00 %
CRI 80
Index B11
                                                                 6
Basement Floor - Lighting Design
                                   7
Basement Floor - Lighting Design
Work planes
Calculation surfaces
                                                                                              8
Basement Floor - Lighting Design
Ground area: 144.26 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) |
Clearance height: 3.900 m | Mounting height: 3.900 m                                                                              9
Basement Floor - Lighting Design
Results
g1 0.57 - - S3
1.14 W/m²/100 lx - -
Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms
Luminaire list
                                                                                                                                                        10
Basement Floor - Lighting Design
                                               11
Basement Floor - Lighting Design
Fitting 1x 1 x LED ET
Index B2
                                                                                                   12
Basement Floor - Lighting Design
                                    X          Y         Mounting   Luminaire
                                                         height
                                                                                13
Basement Floor - Lighting Design
Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms
                                                                                                                                    14
Basement Floor - Lighting Design
Ground area: 6060.17 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) |
Clearance height: 4.100 m | Mounting height: 3.200 m                                                                               25
Basement Floor - Lighting Design
Results
Utilisation profile: Places of public assembly - Public car parks (indoor), Parking areas
Luminaire list
                                                                                                                                              26
Basement Floor - Lighting Design
                                        27
Basement Floor - Lighting Design
Fitting 1x 1 x LED ET
Index B2
Arrangement A1
                                                                                                     28
Basement Floor - Lighting Design
Arrangement A2
Arrangement A3
Arrangement A4
                                                                                               29
Basement Floor - Lighting Design
Arrangement A5
Arrangement A6
Arrangement A7
                                                                                               30
Basement Floor - Lighting Design
Arrangement A8
Arrangement A9
                                                                                               31
Basement Floor - Lighting Design
Arrangement A12
                                                                                               32
Basement Floor - Lighting Design
Arrangement A13
Arrangement A14
                                                                                              33
Basement Floor - Lighting Design
Arrangement A15
Arrangement A17
                                                                                               34
Basement Floor - Lighting Design
Arrangement A18
                                                                                               35
Basement Floor - Lighting Design
Arrangement A21
                                                                                               36
Basement Floor - Lighting Design
Arrangement A22
Arrangement A23
Arrangement A24
                                                                                               37
Basement Floor - Lighting Design
Utilisation profile: Places of public assembly - Public car parks (indoor), Parking areas
                                                                                                                               38
Basement Floor - Lighting Design
Utilisation profile: Places of public assembly - Public car parks (indoor), Parking areas
                                                                                                                               39
Basement Floor - Lighting Design
Utilisation profile: Places of public assembly - Public car parks (indoor), Parking areas
                                                                                                                               40
Basement Floor - Lighting Design
Utilisation profile: Places of public assembly - Public car parks (indoor), Parking areas
                                                                                                                               41
Basement Floor - Lighting Design
Utilisation profile: Places of public assembly - Public car parks (indoor), Parking areas
                                                                                                                               42
Basement Floor - Lighting Design
Utilisation profile: Places of public assembly - Public car parks (indoor), Parking areas
                                                                                                                               43
Date                9/6/2021
Object
Alwaab Doha Qatar
Ground Floor - Lighting Design
Content
Site 1 - Building 1
         Ground Floor
         Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
         Consult 1
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12       .............................
         Workplane (Consult 1) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17                                       .............................
         ESRD 1
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20       .............................
         Workplane (ESRD 1) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24                                      .............................
         Nephrology 1
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27       .............................
         Workplane (Nephrology 1) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31                                            .............................
         Patient Education
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
                                                                                                                                                                                           .............................
         Luminaire layout plan         . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
                                                                                                                                                                                           34
Ground Floor - Lighting Design
Content
         Pharmacy Consult
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42       .............................
         Workplane (Pharmacy Consult) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45                                                .............................
         Physiotherapy
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48       .............................
         Workplane (Physiotherapy) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53                                             .............................
Ground Floor - Lighting Design
Luminaire list
20 Trilux FINEA 50 R 1140 HO 8TW OP DALI WHITE 35.0 W 4138 lm 118.2 lm/W LF4A
40 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
16 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                         4
Ground Floor - Lighting Design
P 10.0 W
ΦLamp 1287 lm
ΦLuminaire 1287 lm
η 100.00 %
CRI 80
Index LF4B
                                                         5
Ground Floor - Lighting Design
P 35.0 W
ΦLamp 4138 lm
ΦLuminaire 4138 lm
η 100.00 %
CRI 80
Index LF4A
                                                          6
Ground Floor - Lighting Design
P 18.0 W
ΦLamp 2091 lm
ΦLuminaire 2091 lm
η 100.00 %
CRI 80
Index LF4
                                                          7
Ground Floor - Lighting Design
                                 8
Ground Floor - Lighting Design
Work planes
                                                                                               9
Ground Floor - Lighting Design
Ground area: 17.67 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 10
Ground Floor - Lighting Design
Results
g1 0.54 - - S12
1.53 W/m²/100 lx - -
Utilisation profile: Healthcare premises - Examination rooms (general), Examination and treatment
Luminaire list
8 Trilux FINEA 50 R 1140 HO 8TW OP DALI WHITE 35.0 W 4138 lm 118.2 lm/W LF4A
4 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                                        11
Ground Floor - Lighting Design
                                        12
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4A
Arrangement A3
                                                                                                   13
Ground Floor - Lighting Design
Arrangement A7
                                                                                           14
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A2
Arrangement A5
                                                                                                   15
Ground Floor - Lighting Design
Arrangement A6
Arrangement A8
                                                                                           16
Ground Floor - Lighting Design
Utilisation profile: Healthcare premises - Examination rooms (general), Examination and treatment
                                                                                                                                    17
Ground Floor - Lighting Design
Ground area: 21.41 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 18
Ground Floor - Lighting Design
Results
g1 0.54 - - S8
1.49 W/m²/100 lx - -
Luminaire list
10 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
2 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                                 19
Ground Floor - Lighting Design
                                     20
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4
Arrangement A3
                                                                                                   21
Ground Floor - Lighting Design
Arrangement A4
                                                                                           22
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A2
Arrangement A6
                                                                                                   23
Ground Floor - Lighting Design
                                                                                                                         24
Ground Floor - Lighting Design
Ground area: 21.41 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 25
Ground Floor - Lighting Design
Results
g1 0.53 - - S10
1.49 W/m²/100 lx - -
Luminaire list
10 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
2 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                                 26
Ground Floor - Lighting Design
                                           27
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4
Arrangement A3
                                                                                                   28
Ground Floor - Lighting Design
Arrangement A4
                                                                                           29
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A2
Arrangement A6
                                                                                                   30
Ground Floor - Lighting Design
                                                                                                                         31
Ground Floor - Lighting Design
Ground area: 27.00 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 32
Ground Floor - Lighting Design
Results
g1 0.45 - - S6
1.48 W/m²/100 lx - -
Utilisation profile: Healthcare premises - Examination rooms (general), Examination and treatment
Luminaire list
12 Trilux FINEA 50 R 1140 HO 8TW OP DALI WHITE 35.0 W 4138 lm 118.2 lm/W LF4A
4 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                                        33
Ground Floor - Lighting Design
                                                34
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4A
Arrangement A1
                                                                                                   35
Ground Floor - Lighting Design
Arrangement A7
                                                                                           36
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A3
Arrangement A4
                                                                                                   37
Ground Floor - Lighting Design
Arrangement A6
Arrangement A8
                                                                                           38
Ground Floor - Lighting Design
Utilisation profile: Healthcare premises - Examination rooms (general), Examination and treatment
                                                                                                                                    39
Ground Floor - Lighting Design
Ground area: 12.17 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 40
Ground Floor - Lighting Design
Results
g1 0.63 - - S4
1.75 W/m²/100 lx - -
Luminaire list
8 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
                                                                                                                                                41
Ground Floor - Lighting Design
                                               42
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4
Arrangement A1
Arrangement A2
                                                                                                   43
Ground Floor - Lighting Design
Arrangement A3
Arrangement A4
                                                                                           44
Ground Floor - Lighting Design
                                                                                                                           45
Ground Floor - Lighting Design
Ground area: 37.08 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 46
Ground Floor - Lighting Design
Results
g1 0.47 - - S2
1.30 W/m²/100 lx - -
Luminaire list
12 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
4 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                                47
Ground Floor - Lighting Design
                                            48
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4
                                                                                                   49
Ground Floor - Lighting Design
                                                                                           50
Ground Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A2
Arrangement A4
                                                                                                   51
Ground Floor - Lighting Design
Arrangement A6
Arrangement A8
                                                                                           52
Ground Floor - Lighting Design
                                                                                                                           53
Date                9/6/2021
Object
Alwaab Doha Qatar
First Floor - Lighting Design
Content
Site 1 - Building 1
          First Floor
          Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
          Diabetic Consult 1
          Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
                                                                                                                                                                                            .............................
          Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12       .............................
          Workplane (Diabetic Consult 1) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16                                               .............................
          Dietician Consult
          Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
                                                                                                                                                                                            .............................
          Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19       .............................
          Workplane (Dietician Consult) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23                                             .............................
          Head Nurse
          Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
                                                                                                                                                                                            .............................
          Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26       .............................
          Workplane (Head Nurse) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30                                            .............................
          Isolation Room 1
          Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
                                                                                                                                                                                            .............................
          Luminaire layout plan         . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
                                                                                                                                                                                            33
First Floor - Lighting Design
Content
          POCT + Phlebotomy
          Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
                                                                                                                                                                                            .............................
          Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39       .............................
          Workplane (POCT + Phlebotomy) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44                                                   .............................
First Floor - Lighting Design
Luminaire list
42 Trilux FINEA 50 R 1140 HO 8TW OP DALI WHITE 35.0 W 4138 lm 118.2 lm/W LF4A
10 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
10 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                          4
First Floor - Lighting Design
P 10.0 W
ΦLamp 1287 lm
ΦLuminaire 1287 lm
η 100.00 %
CRI 80
Index LF4B
                                                         5
First Floor - Lighting Design
P 35.0 W
ΦLamp 4138 lm
ΦLuminaire 4138 lm
η 100.00 %
CRI 80
Index LF4A
                                                          6
First Floor - Lighting Design
P 18.0 W
ΦLamp 2091 lm
ΦLuminaire 2091 lm
η 100.00 %
CRI 80
Index LF4
                                                          7
First Floor - Lighting Design
                                8
First Floor - Lighting Design
Work planes
                                                                                               9
First Floor - Lighting Design
Ground area: 21.41 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 10
First Floor - Lighting Design
Results
g1 0.49 - - S6
1.47 W/m²/100 lx - -
Utilisation profile: Healthcare premises - Examination rooms (general), Examination and treatment
Luminaire list
10 Trilux FINEA 50 R 1140 HO 8TW OP DALI WHITE 35.0 W 4138 lm 118.2 lm/W LF4A
2 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                                        11
First Floor - Lighting Design
                                                12
First Floor - Lighting Design
Fitting 1x LED
Index LF4A
Arrangement A3
                                                                                                     13
First Floor - Lighting Design
Arrangement A4
                                                                                             14
First Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A2
Arrangement A6
                                                                                                     15
First Floor - Lighting Design
Utilisation profile: Healthcare premises - Examination rooms (general), Examination and treatment
                                                                                                                                    16
First Floor - Lighting Design
Ground area: 19.00 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 17
First Floor - Lighting Design
Results
g1 0.57 - - S8
1.55 W/m²/100 lx - -
Utilisation profile: Healthcare premises - Examination rooms (general), Examination and treatment
Luminaire list
10 Trilux FINEA 50 R 1140 HO 8TW OP DALI WHITE 35.0 W 4138 lm 118.2 lm/W LF4A
2 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                                        18
First Floor - Lighting Design
                                               19
First Floor - Lighting Design
Fitting 1x LED
Index LF4A
Arrangement A3
                                                                                                     20
First Floor - Lighting Design
Arrangement A4
                                                                                             21
First Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A2
Arrangement A6
                                                                                                     22
First Floor - Lighting Design
Utilisation profile: Healthcare premises - Examination rooms (general), Examination and treatment
                                                                                                                                    23
First Floor - Lighting Design
Ground area: 18.89 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 24
First Floor - Lighting Design
Results
g1 0.60 - - S10
1.58 W/m²/100 lx - -
Luminaire list
10 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
2 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                            25
First Floor - Lighting Design
                                        26
First Floor - Lighting Design
Fitting 1x LED
Index LF4
Arrangement A3
                                                                                                     27
First Floor - Lighting Design
Arrangement A4
                                                                                             28
First Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A2
Arrangement A6
                                                                                                     29
First Floor - Lighting Design
                                                                                                                          30
First Floor - Lighting Design
Ground area: 20.52 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 31
First Floor - Lighting Design
Results
g1 0.50 - - S2
1.45 W/m²/100 lx - -
Utilisation profile: Healthcare premises - Wards, maternity wards, Examination and treatment
Luminaire list
10 Trilux FINEA 50 R 1140 HO 8TW OP DALI WHITE 35.0 W 4138 lm 118.2 lm/W LF4A
                                                                                                                                                   32
First Floor - Lighting Design
                                              33
First Floor - Lighting Design
Fitting 1x LED
Index LF4A
Arrangement A1
                                                                                                     34
First Floor - Lighting Design
Arrangement A4
                                                                                             35
First Floor - Lighting Design
Utilisation profile: Healthcare premises - Wards, maternity wards, Examination and treatment
                                                                                                                               36
First Floor - Lighting Design
Ground area: 30.28 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 37
First Floor - Lighting Design
Results
g1 0.54 - - S4
1.39 W/m²/100 lx - -
Luminaire list
12 Trilux FINEA 50 R 1140 HO 8TW OP DALI WHITE 35.0 W 4138 lm 118.2 lm/W LF4A
4 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                                38
First Floor - Lighting Design
                                               39
First Floor - Lighting Design
Fitting 1x LED
Index LF4A
Arrangement A1
                                                                                                     40
First Floor - Lighting Design
Arrangement A7
                                                                                             41
First Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A3
Arrangement A4
                                                                                                     42
First Floor - Lighting Design
Arrangement A6
Arrangement A8
                                                                                             43
First Floor - Lighting Design
                                                                                                                            44
Date                9/7/2021
Object
Alwaab Doha Qatar
Second Floor - Lighting Design
Content
Site 1 - Building 1
         Second Floor
         Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
                                                                                                                                                                                       .............................
         Dialysis Teaching
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15       .............................
         Workplane (Dialysis Teaching) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17                                              .............................
         Equipment Store 1
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20       .............................
         Workplane (Equipment Store 1) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22                                                 ..............................
         FMD Secretary
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25       .............................
         Workplane (FMD Secretary) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30                                             .............................
Second Floor - Lighting Design
Content
         Hall way 1
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31                                                                         .............................
         Luminaire layout plan         . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   . 33.............................
         Workplane (Hall way 1) / Perpendicular illuminance (adaptive)                                           .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .
                                                                                                                                                                                                                                                                     37.............................
         office 1
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
                                                                                                                                                                                           .............................
         Luminaire layout plan         . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
                                                                                                                                                                                           40
         Workplane (office 1) / Perpendicular illuminance (adaptive)                                       . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44. . . . . . . . . . . . . . . . . . . . . . . . . . . .
                                                                                                                                                                                           .
         Work Room
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
                                                                                                                                                                                            .............................
         Luminaire layout plan         . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
                                                                                                                                                                                            47
         Workplane (Work Room) / Perpendicular illuminance (adaptive)                                               . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
                                                                                                                                                                                            49
Second Floor - Lighting Design
Luminaire list
14 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
6 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
 1            Trilux          TI500R0O   FINEA 50 R 650 LP 840 OP FO WHITE      10.0 W   1287 lm   128.7 lm/W          LF4D
                              2100L401
                              0_00000
 25           Trilux          TI500R0O   FINEA 50 R 1140 LP 840 OP FO WHITE     18.0 W   2091 lm   116.2 lm/W          LF4C
                              4000L401
                              0_00000
                                                                                                                              4
Second Floor - Lighting Design
P 31.0 W
ΦLamp 4200 lm
ΦLuminaire 4200 lm
η 100.00 %
CRI 80
Index A1
                                                                  5
Second Floor - Lighting Design
P 10.0 W
ΦLamp 1287 lm
ΦLuminaire 1287 lm
η 100.00 %
CRI 80
Index LF4B
                                                         6
Second Floor - Lighting Design
P 10.0 W
ΦLamp 1287 lm
ΦLuminaire 1287 lm
 η                         100.00 %
                                               Polar LDC
 Luminous efficacy         128.7 lm/W
CCT 4000 K
CRI 80
Index LF4D
                                                           7
Second Floor - Lighting Design
P 18.0 W
ΦLamp 2091 lm
ΦLuminaire 2091 lm
η 100.00 %
CRI 80
Index LF4
                                                          8
Second Floor - Lighting Design
P 18.0 W
ΦLamp 2091 lm
ΦLuminaire 2091 lm
 η                         100.00 %
                                               Polar LDC
 Luminous efficacy         116.2 lm/W
CCT 4000 K
CRI 80
Index LF4C
                                                           9
Second Floor - Lighting Design
P 19.0 W
ΦLamp 2200 lm
ΦLuminaire 2200 lm
η 100.00 %
CRI 80
Index C2
                                                                  10
Second Floor - Lighting Design
                                 11
Second Floor - Lighting Design
Work planes
                                                                                              12
Second Floor - Lighting Design
Ground area: 30.11 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 13
Second Floor - Lighting Design
Results
g1 0.51 - - S2
1.16 W/m²/100 lx - -
Luminaire list
                                                                                                                                                14
Second Floor - Lighting Design
                                                15
Second Floor - Lighting Design
Index A1
                                                                                                      16
Second Floor - Lighting Design
                                                                                                                         17
Second Floor - Lighting Design
Ground area: 36.12 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 18
Second Floor - Lighting Design
Results
g1 0.41 - - S10
1.18 W/m²/100 lx - -
1.27 W/m²/100 lx - -
Utilisation profile: Healthcare premises - Rooms for general use, Waiting rooms
Luminaire list
                                                                                                                                              19
Second Floor - Lighting Design
                                                20
Second Floor - Lighting Design
Index C2
Arrangement A1
                                                                                                      21
Second Floor - Lighting Design
Utilisation profile: Healthcare premises - Rooms for general use, Waiting rooms
                                                                                                                           22
Second Floor - Lighting Design
Ground area: 15.89 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 23
Second Floor - Lighting Design
Results
g1 0.50 - - S12
1.51 W/m²/100 lx - -
Luminaire list
6 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
4 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                            24
Second Floor - Lighting Design
                                            25
Second Floor - Lighting Design
Fitting 1x LED
Index LF4
Arrangement A1
Arrangement A3
                                                                                                      26
Second Floor - Lighting Design
Arrangement A6
Arrangement A8
                                                                                            27
Second Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A2
Arrangement A4
                                                                                                    28
Second Floor - Lighting Design
Arrangement A5
Arrangement A7
                                                                                            29
Second Floor - Lighting Design
                                                                                                                          30
Second Floor - Lighting Design
Ground area: 73.55 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 31
Second Floor - Lighting Design
Results
g1 0.42 - - S8
1.80 W/m²/100 lx - -
1.98 W/m²/100 lx - -
Utilisation profile: Healthcare premises - Rooms for general use, Corridors: Cleaning
Luminaire list
 1         Trilux               TI500R0O        FINEA 50 R 650 LP 840 OP FO WHITE           10.0 W         1287 lm   128.7 lm/W          LF4D
                                2100L401
                                0_00000
 25        Trilux               TI500R0O        FINEA 50 R 1140 LP 840 OP FO WHITE          18.0 W         2091 lm   116.2 lm/W          LF4C
                                4000L401
                                0_00000
                                                                                                                                               32
Second Floor - Lighting Design
                                         33
Second Floor - Lighting Design
Fitting 1x LED
Index LF4D
Arrangement A2
                                                                                                     34
Second Floor - Lighting Design
Fitting 1x LED
Index LF4C
                                                                                                     35
Second Floor - Lighting Design
                                         X          Y         Mounting   Luminaire
                                                              height
                                                                                     36
Second Floor - Lighting Design
Utilisation profile: Healthcare premises - Rooms for general use, Corridors: Cleaning
                                                                                                                           37
Second Floor - Lighting Design
Ground area: 14.93 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 38
Second Floor - Lighting Design
Results
g1 0.58 - - S6
1.63 W/m²/100 lx - -
Luminaire list
8 Trilux FINEA 50 R 1140 LP 8TW OP DALI WHITE 18.0 W 2091 lm 116.2 lm/W LF4
2 Trilux FINEA 50 R 650 LP 8TW OP DALI WHITE 10.0 W 1287 lm 128.7 lm/W LF4B
                                                                                                                                            39
Second Floor - Lighting Design
                                       40
Second Floor - Lighting Design
Fitting 1x LED
Index LF4
Arrangement A1
                                                                                                    41
Second Floor - Lighting Design
Arrangement A5
                                                                                            42
Second Floor - Lighting Design
Fitting 1x LED
Index LF4B
Arrangement A4
Arrangement A6
                                                                                                    43
Second Floor - Lighting Design
                                                                                                                          44
Second Floor - Lighting Design
Ground area: 15.76 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                                 45
Second Floor - Lighting Design
Results
g1 0.48 - - S4
1.19 W/m²/100 lx - -
1.49 W/m²/100 lx - -
Utilisation profile: Healthcare premises - Rooms for general use, Waiting rooms
Luminaire list
                                                                                                                                              46
Second Floor - Lighting Design
                                        47
Second Floor - Lighting Design
Index C2
Arrangement A1
                                                                                                      48
Second Floor - Lighting Design
Utilisation profile: Healthcare premises - Rooms for general use, Waiting rooms
                                                                                                                           49
Date                9/7/2021
Object
Alwaab Doha Qatar
Lower Roof Floor - Lighting Design
Content
Site 1 - Building 1
         Technical Room 1
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14       .............................
         Workplane (Technical Room 1) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17                                                ..............................
         Technical Room 2
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20       .............................
         Workplane (Technical Room 2) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24                                                ..............................
Lower Roof Floor - Lighting Design
Luminaire list
                                                                                                                3
Lower Roof Floor - Lighting Design
P 28.0 W
ΦLamp 3900 lm
ΦLuminaire 3900 lm
η 100.00 %
CRI 80
Index B2
                                                                  4
Lower Roof Floor - Lighting Design
                                     5
Lower Roof Floor - Lighting Design
Work planes
                                                                                              6
Lower Roof Floor - Lighting Design
Ground area: 121.37 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) |
Clearance height: 2.600 m | Mounting height: 2.600 m                                                                              7
Lower Roof Floor - Lighting Design
Results
g1 0.45 - - S2
0.97 W/m²/100 lx - -
1.04 W/m²/100 lx - -
Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms
Luminaire list
                                                                                                                                                          8
Lower Roof Floor - Lighting Design
                                                     9
Lower Roof Floor - Lighting Design
Fitting 1x 1 x LED ET
Index B2
                                                                                                      10
Lower Roof Floor - Lighting Design
Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms
                                                                                                                                    11
Lower Roof Floor - Lighting Design
Ground area: 199.66 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) |
Clearance height: 2.600 m | Mounting height: 2.600 m                                                                              12
Lower Roof Floor - Lighting Design
Results
g1 0.35 - - S4
0.97 W/m²/100 lx - -
1.04 W/m²/100 lx - -
Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms
Luminaire list
                                                                                                                                                        13
Lower Roof Floor - Lighting Design
                                                   14
Lower Roof Floor - Lighting Design
Fitting 1x 1 x LED ET
Index B2
                                                                                                      15
Lower Roof Floor - Lighting Design
                                                                                               16
Lower Roof Floor - Lighting Design
Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms
                                                                                                                                    17
Lower Roof Floor - Lighting Design
Ground area: 272.11 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Maintenance factor: 0.80 (fixed) |
Clearance height: 2.600 m | Mounting height: 2.600 m                                                                              18
Lower Roof Floor - Lighting Design
Results
g1 0.37 - - S6
0.93 W/m²/100 lx - -
0.99 W/m²/100 lx - -
Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms
Luminaire list
                                                                                                                                                        19
Lower Roof Floor - Lighting Design
                                                   20
Lower Roof Floor - Lighting Design
Fitting 1x 1 x LED ET
Index B2
                                                                                                      21
Lower Roof Floor - Lighting Design
Arrangement A3
                                                                                               22
Lower Roof Floor - Lighting Design
Arrangement A4
                                                   23
Lower Roof Floor - Lighting Design
Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms
                                                                                                                                    24
Date                9/6/2021
Object
Alwaab Doha Qatar
Basement Floor - Emergency Lighting Design
Content
Site 1 - Building 1
         Basement Floor
         Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
         Generator Room
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17       .............................
         Workplane (Generator Room) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24                                                .............................
         Parking
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27       .............................
         Calculation surface / Driveway 2 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31                                       .............................
         Calculation surface / Driveway 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32                                       .............................
         Calculation surface / Driveway 3 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33                                       .............................
Content
Luminaire list
                                                                                                                    4
Basement Floor - Emergency Lighting Design
P 28.0 W
ΦLamp 3900 lm
ΦLuminaire 3900 lm
η 100.00 %
CRI 80
Index B2
                                                                       5
Basement Floor - Emergency Lighting Design
P 57.0 W
ΦLamp 7700 lm
ΦLuminaire 7700 lm
η 100.00 %
CRI 80
Index B11
                                                                       6
Basement Floor - Emergency Lighting Design
                                             7
Basement Floor - Emergency Lighting Design
Work planes
Calculation surfaces
                                                                                                 8
Basement Floor - Emergency Lighting Design
Ground area: 144.26 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 3.900 m | Mounting height: 3.900 m                                                                                               9
Basement Floor - Emergency Lighting Design
Results
g1 0.45 S3
1.51 W/m²/100 lx
Luminaire list
                                                                                                                               10
Basement Floor - Emergency Lighting Design
                                               11
Basement Floor - Emergency Lighting Design
Fitting 1x 1 x LED ET
Index B2
                                                                                                  12
Basement Floor - Emergency Lighting Design
                                             X          Y         Mounting   Luminaire
                                                                  height
                                                                                         13
Basement Floor - Emergency Lighting Design
                                                                                               14
Basement Floor - Emergency Lighting Design
Ground area: 515.77 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 3.900 m | Mounting height: 2.800 m - 3.900 m                                                                                     15
Basement Floor - Emergency Lighting Design
Results
g1 0.21 S5
2.17 W/m²/100 lx
Luminaire list
                                                                                                                               16
Basement Floor - Emergency Lighting Design
                                               17
Basement Floor - Emergency Lighting Design
Fitting 1x 1 x LED ET
Index B2
                                                                                                    18
Basement Floor - Emergency Lighting Design
Arrangement A4
                                                                                              19
Basement Floor - Emergency Lighting Design
Arrangement A5
                                                                                            20
Basement Floor - Emergency Lighting Design
Index B11
                                                                                                   21
Basement Floor - Emergency Lighting Design
                                                X          Y          Mounting   Luminaire
                                                                      height
Arrangement A9
                                                                                             22
Basement Floor - Emergency Lighting Design
Arrangement A10
                                                                                            23
Basement Floor - Emergency Lighting Design
                                                                                               24
Basement Floor - Emergency Lighting Design
Ground area: 6060.17 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 4.100 m | Mounting height: 3.200 m                                                                                                25
Basement Floor - Emergency Lighting Design
Results
Luminaire list
                                                                                                                       26
Basement Floor - Emergency Lighting Design
                                             27
Basement Floor - Emergency Lighting Design
Fitting 1x 1 x LED ET
Index B2
Arrangement A1
                                                                                                    28
Basement Floor - Emergency Lighting Design
Arrangement A2
Arrangement A3
Arrangement A4
                                                                                              29
Basement Floor - Emergency Lighting Design
Arrangement A5
                                                                                              30
Basement Floor - Emergency Lighting Design
                                                                                                 31
Basement Floor - Emergency Lighting Design
                                                                                                 32
Basement Floor - Emergency Lighting Design
                                                                                                 33
Basement Floor - Emergency Lighting Design
Ground area: 104.66 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 3.650 m | Mounting height: 3.650 m                                                                                               34
Basement Floor - Emergency Lighting Design
Results
g1 0.45 S7
1.56 W/m²/100 lx
Luminaire list
                                                                                                                               35
Basement Floor - Emergency Lighting Design
                                                 36
Basement Floor - Emergency Lighting Design
Fitting 1x 1 x LED ET
Index B2
                                                                                                    37
Basement Floor - Emergency Lighting Design
                                                                                               38
Date                9/6/2021
Object
Alwaab Doha Qatar
Ground Floor - Emergency Lighting Design
Content
Site 1 - Building 1
         Ground Floor
         Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
         Elec. Room
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
                                                                                                                                                                                             ............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11       .............................
         Workplane (Elec. Room) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13                                          .............................
         Euip Store
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16       .............................
         Workplane (Euip Store) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18                                        .............................
         House Keeping
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21       .............................
         Workplane (House Keeping) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23                                               .............................
         Lobby
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
                                                                                                                                                                                           .............................
         Luminaire layout plan         . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
                                                                                                                                                                                           26
Ground Floor - Emergency Lighting Design
Content
Luminaire list
                                                                                                                      4
Ground Floor - Emergency Lighting Design
P 28.0 W
ΦLamp 3900 lm
ΦLuminaire 3900 lm
η 100.00 %
CRI 80
Index B2
                                                                     5
Ground Floor - Emergency Lighting Design
P 19.0 W
ΦLamp 2200 lm
ΦLuminaire 2200 lm
η 100.00 %
CRI 80
Index C2
                                                                     6
Ground Floor - Emergency Lighting Design
                                           7
Ground Floor - Emergency Lighting Design
Work planes
                                                                                               8
Ground Floor - Emergency Lighting Design
Ground area: 13.64 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                              9
Ground Floor - Emergency Lighting Design
Results
g1 0.45 S6
3.26 W/m²/100 lx
Luminaire list
                                                                                                                                10
Ground Floor - Emergency Lighting Design
                                           11
Ground Floor - Emergency Lighting Design
Fitting 1x 1 x LED ET
Index B2
Arrangement A1
                                                                                                     12
Ground Floor - Emergency Lighting Design
                                                                                             13
Ground Floor - Emergency Lighting Design
Ground area: 6.42 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                             14
Ground Floor - Emergency Lighting Design
Results
g1 0.088 S4
2.54 W/m²/100 lx
Luminaire list
                                                                                                                                15
Ground Floor - Emergency Lighting Design
                                           16
Ground Floor - Emergency Lighting Design
Index C2
Arrangement A1
                                                                                                     17
Ground Floor - Emergency Lighting Design
                                                                                               18
Ground Floor - Emergency Lighting Design
Ground area: 6.35 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                             19
Ground Floor - Emergency Lighting Design
Results
g1 0.086 S2
2.55 W/m²/100 lx
Luminaire list
                                                                                                                                20
Ground Floor - Emergency Lighting Design
                                            21
Ground Floor - Emergency Lighting Design
Index C2
Arrangement A1
                                                                                                     22
Ground Floor - Emergency Lighting Design
                                                                                               23
Ground Floor - Emergency Lighting Design
Ground area: 8.40 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                             24
Ground Floor - Emergency Lighting Design
Results
g1 0.56 S8
2.33 W/m²/100 lx
Luminaire list
                                                                                                                                25
Ground Floor - Emergency Lighting Design
                                           26
Ground Floor - Emergency Lighting Design
Index C2
Arrangement A1
                                                                                                   27
Ground Floor - Emergency Lighting Design
                                                                                            28
Date                9/6/2021
Object
Alwaab Doha Qatar
First Floor - Emergency Lighting Design
Content
Site 1 - Building 1
         First Floor
         Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6. . . . . . . . . . . . . . . . . . . . . . . . . . . .
         IDF Room
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15       .............................
         Workplane (IDF Room) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17                                          .............................
         Patient Pantry
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20       .............................
         Workplane (Patient Pantry) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22                                            .............................
First Floor - Emergency Lighting Design
Luminaire list
                                                                                                                     3
First Floor - Emergency Lighting Design
P 28.0 W
ΦLamp 3900 lm
ΦLuminaire 3900 lm
η 100.00 %
CRI 80
Index B2
                                                                    4
First Floor - Emergency Lighting Design
P 19.0 W
ΦLamp 2200 lm
ΦLuminaire 2200 lm
η 100.00 %
CRI 80
Index C2
                                                                    5
First Floor - Emergency Lighting Design
                                          6
First Floor - Emergency Lighting Design
Work planes
                                                                                              7
First Floor - Emergency Lighting Design
Ground area: 9.38 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                             8
First Floor - Emergency Lighting Design
Results
g1 0.066 S2
1.94 W/m²/100 lx
Luminaire list
                                                                                                                                 9
First Floor - Emergency Lighting Design
                                              10
First Floor - Emergency Lighting Design
Index C2
Arrangement A1
                                                                                                      11
First Floor - Emergency Lighting Design
                                                                                              12
First Floor - Emergency Lighting Design
Ground area: 22.12 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                              13
First Floor - Emergency Lighting Design
Results
g1 0.26 S6
2.00 W/m²/100 lx
Luminaire list
                                                                                                                                 14
First Floor - Emergency Lighting Design
                                          15
First Floor - Emergency Lighting Design
Fitting 1x 1 x LED ET
Index B2
Arrangement A1
                                                                                                      16
First Floor - Emergency Lighting Design
                                                                                            17
First Floor - Emergency Lighting Design
Ground area: 9.06 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                             18
First Floor - Emergency Lighting Design
Results
g1 0.066 S4
2.02 W/m²/100 lx
Luminaire list
                                                                                                                                 19
First Floor - Emergency Lighting Design
                                            20
First Floor - Emergency Lighting Design
Index C2
Arrangement A1
                                                                                                      21
First Floor - Emergency Lighting Design
                                                                                                22
Date                9/7/2021
Object
Alwaab Doha Qatar
Second Floor - Emergency Lighting Design
Content
Site 1 - Building 1
         Second Floor
         Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
         Dialysis Teaching
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
                                                                                                                                                                                           .............................
         Luminaire layout plan         . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
                                                                                                                                                                                           17
         Workplane (Dialysis Teaching) / Perpendicular illuminance (adaptive)                                                . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19. . . . . . . . . . . . . . . . . . . . . . . . . . . .
                                                                                                                                                                                           .
         Equipment Store 1
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20                            .............................
         Luminaire layout plan         . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .............................
                                                                                                                                                                                                                        22
         Workplane (Equipment Store 1) / Perpendicular illuminance (adaptive)                                                    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .
                                                                                                                                                                                                                        25.............................
         RO Plant
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
                                                                                                                                                                                           .............................
         Luminaire layout plan         . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
                                                                                                                                                                                           28
Second Floor - Emergency Lighting Design
Content
         Work Room
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34       .............................
         Workplane (Work Room) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36                                            .............................
Second Floor - Emergency Lighting Design
Luminaire list
                                                                                                                      4
Second Floor - Emergency Lighting Design
P 31.0 W
ΦLamp 4200 lm
ΦLuminaire 4200 lm
η 100.00 %
CRI 80
Index A1
                                                                     5
Second Floor - Emergency Lighting Design
P 19.0 W
ΦLamp 2200 lm
ΦLuminaire 2200 lm
η 100.00 %
CRI 80
Index C2
                                                                     6
Second Floor - Emergency Lighting Design
                                           7
Second Floor - Emergency Lighting Design
Work planes
 Workplane (Dialysis Main Consumable Store)   77.4 lx   8.65 lx   254 lx   0.11    0.034   S10
 Perpendicular illuminance (adaptive)
 Height: 0.000 m, Wall zone: 0.000 m
                                                                                                   8
Second Floor - Emergency Lighting Design
Ground area: 96.71 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                              9
Second Floor - Emergency Lighting Design
Results
g1 0.11 S10
1.24 W/m²/100 lx
Luminaire list
                                                                                                                                10
Second Floor - Emergency Lighting Design
                                                             11
Second Floor - Emergency Lighting Design
Index A1
Arrangement A1
Arrangement A2
                                                                                                   12
Second Floor - Emergency Lighting Design
Arrangement A3
                                                                                           13
Second Floor - Emergency Lighting Design
Workplane (Dialysis Main Consumable Store)   77.4 lx   8.65 lx   254 lx   0.11   0.034   S10
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
                                                                                                 14
Second Floor - Emergency Lighting Design
Ground area: 30.11 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                              15
Second Floor - Emergency Lighting Design
Results
g1 0.046 S2
1.45 W/m²/100 lx
Luminaire list
                                                                                                                                16
Second Floor - Emergency Lighting Design
                                                17
Second Floor - Emergency Lighting Design
Index A1
Arrangement A1
Arrangement A2
                                                                                                   18
Second Floor - Emergency Lighting Design
                                                                                               19
Second Floor - Emergency Lighting Design
Ground area: 36.12 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                              20
Second Floor - Emergency Lighting Design
Results
g1 0.014 S6
1.41 W/m²/100 lx
1.52 W/m²/100 lx
Luminaire list
                                                                                                                                21
Second Floor - Emergency Lighting Design
                                                22
Second Floor - Emergency Lighting Design
Index C2
Arrangement A1
                                                                                                     23
Second Floor - Emergency Lighting Design
Arrangement A2
                                                  24
Second Floor - Emergency Lighting Design
                                                                                                25
Second Floor - Emergency Lighting Design
Ground area: 70.70 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                              26
Second Floor - Emergency Lighting Design
Results
g1 0.079 S8
1.29 W/m²/100 lx
Luminaire list
                                                                                                                                27
Second Floor - Emergency Lighting Design
                                           28
Second Floor - Emergency Lighting Design
Index A1
Arrangement A1
Arrangement A2
                                                                                                   29
Second Floor - Emergency Lighting Design
Arrangement A3
                                                                                           30
Second Floor - Emergency Lighting Design
                                                                                               31
Second Floor - Emergency Lighting Design
Ground area: 15.76 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m                                                                                              32
Second Floor - Emergency Lighting Design
Results
g1 0.031 S4
1.36 W/m²/100 lx
1.69 W/m²/100 lx
Luminaire list
                                                                                                                                33
Second Floor - Emergency Lighting Design
                                           34
Second Floor - Emergency Lighting Design
Index C2
Arrangement A1
                                                                                                     35
Second Floor - Emergency Lighting Design
                                                                                                36
Date                9/7/2021
Object
Alwaab Doha Qatar
Lower Roof Floor - Emergency Lighting Design
Content
Site 1 - Building 1
         Technical Room 1
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14       .............................
         Workplane (Technical Room 1) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17                                                ..............................
         Technical Room 2
         Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
                                                                                                                                                                                           .............................
         Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20       .............................
         Workplane (Technical Room 2) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23                                                ..............................
Lower Roof Floor - Emergency Lighting Design
Luminaire list
                                                                                                                     3
Lower Roof Floor - Emergency Lighting Design
P 28.0 W
ΦLamp 3900 lm
ΦLuminaire 3900 lm
η 100.00 %
CRI 80
Index B2
                                                                         4
Lower Roof Floor - Emergency Lighting Design
                                               5
Lower Roof Floor - Emergency Lighting Design
Work planes
                                                                                                    6
Lower Roof Floor - Emergency Lighting Design
Ground area: 121.37 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.600 m | Mounting height: 2.600 m                                                                                               7
Lower Roof Floor - Emergency Lighting Design
Results
g1 0.013 S2
1.18 W/m²/100 lx
1.27 W/m²/100 lx
Luminaire list
                                                                                                                                8
Lower Roof Floor - Emergency Lighting Design
                                                     9
Lower Roof Floor - Emergency Lighting Design
Fitting 1x 1 x LED ET
Index B2
Arrangement A1
                                                                                                     10
Lower Roof Floor - Emergency Lighting Design
                                                                                                    11
Lower Roof Floor - Emergency Lighting Design
Ground area: 199.66 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.600 m | Mounting height: 2.600 m                                                                                               12
Lower Roof Floor - Emergency Lighting Design
Results
g1 0.067 S4
1.21 W/m²/100 lx
1.30 W/m²/100 lx
Luminaire list
                                                                                                                                13
Lower Roof Floor - Emergency Lighting Design
                                                   14
Lower Roof Floor - Emergency Lighting Design
Fitting 1x 1 x LED ET
Index B2
Arrangement A1
                                                                                                     15
Lower Roof Floor - Emergency Lighting Design
Arrangement A2
Arrangement A3
                                                                                              16
Lower Roof Floor - Emergency Lighting Design
                                                                                                   17
Lower Roof Floor - Emergency Lighting Design
Ground area: 272.11 m² | Reflection factors: Ceiling: 0.0 %, Walls: 0.0 %, Floor: 0.0 % | Maintenance factor: 0.80 (fixed) | Clearance
height: 2.600 m | Mounting height: 2.600 m                                                                                               18
Lower Roof Floor - Emergency Lighting Design
Results
g1 0.094 S6
1.16 W/m²/100 lx
1.23 W/m²/100 lx
Luminaire list
                                                                                                                                19
Lower Roof Floor - Emergency Lighting Design
                                                   20
Lower Roof Floor - Emergency Lighting Design
Fitting 1x 1 x LED ET
Index B2
Arrangement A1
                                                                                                     21
Lower Roof Floor - Emergency Lighting Design
Arrangement A2
Arrangement A3
Arrangement A4
                                                                                              22
Lower Roof Floor - Emergency Lighting Design
23