FIRE DETECTION AND ALARM SYSTEM 8200
GENERAL NOTES AND SPECIFICATIONS 790 2500 4720 300
1. ALL INSTALLATION SHALL FOLLOW THE PERTINENT NATIONAL FIRE PROTECTION ASSOCIATION NFPA-13 B
STANDARDS AND FIRE CODE OF THE PHILIPPINES AND OTHER APPLICABLE LAWS, RULES AND REGULATIONS.
2150
2. THE DISTANCE OF THE SPRINKLER HEAD (ENDENT OR UPRIGHT)TO A WALL OR HIGH PARTITION MUST NOT BE
EXCEED 2.25M OR HALF OF THE DISTANCE BETWEEN TWO SPRINKLER HEAD. S
3. THE FIRE PROTECTION DESIGN AND FIT-OUT WORKS, WHICH IS SUBJECT TO THE REVIEW AND APPROVAL BY
THE BUILDING ADMINISTRATOR, SHALL BE EXECUTED BY THE MEP CONSULTATNT AND CONSTRUCTED UNDER
1400
1250
THE OCCUPANT'S OWN CONTRACT AGREEMENT. S
4. THE OFFICE UNIT SHALL PROVIDE WITH FIRE PROTECTION SYSTEM INCLUDING ACTIVE I.E. FIRE SUPPRESSION,
FIRE SPRINKLER SYSTEM, AND FIRE DETECTION AND PASSIVE SYSTEM I.E. COMPARTMENTALIZATION,
JEWELRY
DISPLAY
FIRE-RATED WALLS AND FLOORS, AND FIRE DAMPER.
2410
S
5. THE SPRINKLER SYSTEM IN THE OFFICE UNIT IS BASED ON NON-COMBUSTIBLE CEILING MATERIALS. THE
10800
CLOTHING SECTION
CEILING MATERIALS THAT CAN BE USED FOR THE CEILING ARE THE FOLLOWING: S
· ACOUSTIC TILE OR ON METAL T-RUNNER
· GYPSUM BOARD ON METAL SUSPENSION SYSTEM
JEWELRY
DISPLAY
· OTHER SIMILAR NON-COMBUSTIBLE MATERIALS S
7250
2600
6. THE DISTANCE OF THE SPRINKLER HEAD (PRIGHT OR PENDENT)TO A WALL OR HIGH PARTITION MUST NOT
EXCEED 2.25M OR HALF OF THE DISTANCE BETWEEN TWO SPRINKLER HEAD.
7. THE SPRINKLER HEADS SHALL NOT USED FOR HANGING-DECORATIVE ITEMS SUCH AS CHRISTMAS LANTERNS,
1030
WHICH CAN DAMAGE THE FUSIBLE LINKS OR THE SPRINKLERS AND WILL IMPAIR THE PROTECTION COVERAGE.
S
2240
GENERAL NOTES FDAS LAYOUT SCALE: 1:50 MTS 1
CONCRETE SLAB
TAPPED TO BUILDING
ADMIN FDASFACP
SD SD SD SD SD SD
TO NEAREST EXISTING
SMOKE DETECTOR
BATTERY OPERATED BATTERY OPERATED
SMOKE DETECTORS SMOKE DETECTORS
FIRE ALARM RISER DIAGRAM NOT TO SCALE 2 SMOKE DETECTOR MOUNTING DETAIL NOT TO SCALE 3
FDAS GENERAL NOTE
PROPOSED OFFICE SHOWROOM FIT-OUT CHRISTIAN SILVINO CARLOS
FDAS LAYOUT
FIRE ALARM RISER DIAGRAM F
-- PROFESSIONAL MECHANICAL ENGINEER (AS-BUILT) SMOKE DETECTOR MOUNTING DETAIL