Functions

 BACnet  Modbus L-IOB Room Controller


 DALI LOYTEC
 OPC
COMPETENCE PARTNER

LIOB-591
Datasheet #89072125

L‑WEB, L‑STUDIO
The LIOB‑591 fan coil controller provides the basis for a revolutionary room auto‑
mation system based on IP, which seamlessly integrates with native BACnet/IP
networks at the controller level. Together with the L‑STUDIO software, room con‑
trol solutions can be created with little effort. Integral parts of the room control
system are a web‑based room operation via an LWEB‑802/803 dashboard and the
automatic generation of graphics for the L-PAD / L‑VIS Touch Panel for local opera‑
tion. LIOB‑591 Controllers implement the BACnet Building Controller (B-BC) pro‑
file and are BTL certified.

L‑ROC
Our room controllers provide all common interfaces and a large number of physi‑
cal I/Os for room automation projects. DALI lamps and DALI sensors are connected
to the DALI interface with an integrated DALI power supply. Up to 16 SMI sunblind
OPC motors connect to an external SMI interface. Belimo valves connect to the external
BACnet DALI OPC UA XML-DA
MP‑Bus interface. BACnet MS/TP devices connect to the RS‑485 interface, which
can also be configured as a Modbus RTU interface to connect Modbus devices like

L‑INX
energy meters or ekey finger scanners for access control or to connect the L‑STAT
Modbus MP-Bus enocean® SMI
room operator panel. EnOcean devices connect to the external EnOcean interface.
Dual Ethernet ports allow daisy chaining of LIOB-591 controllers in a ring topology
WLAN LTE SNMP
and provide BACnet/IP, Modbus/IP and OPC communication.
Optionally the LIOB-591 can communicate via wireless LAN through the
IoT LWLAN‑800 wireless adapter connected to the USB port. 20 universal I/Os, one

L‑IOB
1250 W and three 300 W TRIAC outputs connect various physical input and out‑
LIOB Local I/O
put devices. Our room automation library provides pre-built function modules for
SMS
IP
all lighting, heating, cooling, ventilation, sunblinds and access control via finger
scanners. Built‑in TSL encryption ensures secure operation of the room automa‑
tion system.

Gateways
VPN All typical room functions are supported:
• Lighting control with constant light controller
y=f(x)
VNC • Sunblind control with angle adjustment and year shade progression
IEC 61499 IEC 61131
• Temperature control for heating, cooling, and ventilation

L-VIS, L-STAT
LPAD-7,
BACnet
• Occupancy detection
• Window monitoring and window contact

Features
• Room controller for 1 room segment • Visualization of customized graphic pages through

L‑DALI
• Networking via redundant IP network LWEB‑900 (Building Management), LWEB‑803 (Monitoring
and Control), or LWEB‑802 (Web Browser)
• Programmable with L-STUDIO (IEC 61131-3 or IEC 61499)
• Support of the L‑STAT Room Operator Panel
• Extension with physical inputs and outputs using
L‑IOB I/‌O Modules (LIOB‑45x or LIOB‑55x/56x) • Built-in OPC XML‑DA and OPC UA server
Routers, NIC

• 128x64 graphic display with backlight for • Access to network statistics via SNMP
device configuration and maintenance • Compliant with ANSI/‌ASHRAE 135‑2012
• Local display of device and data point information and ISO 16484‑5:2012 standard

• Manual operation using the jog dial or VNC Client • Supports BACnet/‌IP, BACnet/SC or BACnet MS/‌TP

• Integrated AST™ functions (Alarming, Scheduling, • BACnet Client Function (Write Property,
and Trending) for each room segment Read Property, COV Subscription
Interfaces

• Node.js support1 for easy IoT integration (e.g. Google • BACnet Client Configuration with configuration
calendar, MQTT, Alexa & friends, multimedia equipment,…) tool (scan and EDE import)

• Event-driven e-mail notification • B-BC (BACnet Building Controller) functionality, BTL certified

• Math objects to execute mathematical • Modbus TCP and Modbus RTU/ASCII (Master or Slave)
operations on data points • Integrated web server for device configuration
Accessories

• Stores customized graphic pages and monitoring data points

1 requires L-IOT1 software license

buildings under control 81


Functions
L-IOB Room Controller

LIOB‑591
• DALI integration of up to 64 DALI lamps
L‑WEB, L‑STUDIO

• 8 x Universal I/O (U, I, R), 12 x Universal I/O (U) 2


• Integrated DALI power supply, 16 V DC, • Integrated heating/cooling valve control
116 mA max. current
• Supports VPN
• Integrated 1250 W heater control
• Configurable Bluetooth beacons and services: indoor
• Integrated dual fan motor control navigation, asset tracking (requires LIC-ASSET license)
and access to LWEB-900 room control solution

General Specifications
L‑ROC

Dimensions (mm) 199 x 87 x 62 (L x W x H), DIM065


Installation mountable directly via two oblong holes (ø 4.5 mm, distance 187 mm)
Power supply 85 – 240 V AC, 50 – 60 Hz
Operating conditions 0 °C to 45 °C, 10 – 90 % RH, noncondensing, degree of protection: IP30, IP20 (terminals)
Specifications
L‑INX

Type LIOB-591
Power consumption max. 15 W 3
Interfaces 2 x Ethernet (100Base-T):
Web services (OPC XML‑DA, OPC UA), BACnet/‌IP*, BACnet/SC*, LIOB‑IP, Modbus TCP
(Master or Slave), HTTP, FTP, SSH, HTTPS, Firewall, VNC, SNMP, VPN
2 x USB-A:
L‑IOB

WLAN (needs LWLAN‑800), EnOcean (needs LENO‑80x), MP-Bus (needs


LMPBUS-804), SMI (needs LSMI-804), LTE (needs LTE-800)
1 x RS‑485 (ANSI TIA/‌EIA‑485):
BACnet MS/‌TP*
or Modbus RTU/ASCII (Master or Slave)
Gateways

or L-STAT (Room operator panel)


1 x DALI with integrated DALI bus power supply 16 V DC,
116 mA max. supply current 4
* Either BACnet/IP or BACnet/SC or BACnet MS/TP (no router)
Universal I/O (IO) 8 x Universal I/O (U, I, R), 12 x Universal I/O (U) 2
L-VIS, L-STAT

Digital Output (DO) 1 x TRIAC 1250 W, 230 V AC (connector for overtemperature safety device)
LPAD-7,

3 x TRIAC 300 W, 230 V AC


Input and Output specification Please refer to the ”General Input and Output Specification of LOYTEC devices“ at the end of
the L‑IOB section for more details.
L‑IOB I/‌O extension 1 L‑IOB I/‌O Modules of Type LIOB‑45x or LIOB‑55x/56x
Program cycle time Event-triggered, 10 ms
Max. number of Rooms/‌Segments 1
L‑DALI

SMI devices via LSMI-804 16


SMI devices (maximum) 16
EnOcean devices via LENO‑80x 10
EnOcean devices (maximum) 10
Routers, NIC

EnOcean devices commissioning limit 10


L-STAT Room Operator Panels 1
DALI devices 64
DALI groups 16
DALI sensors 16
Interfaces

DALI pushbuttons (LDALI‑BM2) 64 pushbutton coupler


MP-Bus devices via LMPBUS-804 8 (16 MPL)
MP-Bus devices (maximum) 16
Accessories

2 U: 0-10V input or 0-10V output, I: 4-20 mA input, R: resistance measurement


3 Add external load: Sum of max. current drawn from all outputs x 24V + power drawn from USB and L-STAT connectors
4 With high DALI traffic (e.g. during DALI-scan) increased current consumption may occur depending on the devices connected. Therefore, according to
IEC62386-101 it is recommended to take an additional current of at least 20% for dynamic processes into account in system design.

82 www.loytec.com
Functions
L-IOB Room Controller

LIOB‑591

L‑WEB, L‑STUDIO
Runtime licenses
Programming, Tools L-STUDIO software (IEC 61131-3 or IEC 61499), L‑INX Configurator
License L‑STUDIO: included
Resource limits
Total number of data points 10 000 Math objects 50
OPC data points 5 000 Alarm logs 10

L‑ROC
BACnet objects 500 (analog, binary, multi-state) Modbus data points 300
BACnet client mappings 500 Connections (Local / Global) 2 000 / 250
BACnet calendar objects 25 Number of L‑WEB clients 32 (simultaneously)
BACnet scheduler objects 100 (64 data points per object) L‑IOB I/‌O Modules (via LIOB‑IP) 1
BACnet notification classes 32 EnOcean data points 10 per EnOcean device
Trend logs (BACnet or generic) 256 (13 000 000 entries, ≈ 200 MB) SMI devices 16

L‑INX
Total trended data points 256 MP-Bus devices 8 (16 MPL)
E-mail templates 50

Order number Product description


LIOB-591 L-IOB Room Controller, 8 x Universal I/O (U, I, R), 12 x Universal I/O (U), 1 x TRIAC 1250 W, 3 x TRIAC 300 W

L‑IOB
L‑STUDIO Development and integration platform for programmable LOYTEC controllers
L-IOT1 Add-on Software License to enable IoT functionality on LIOB-585/586/587/588/589/59x, LIOB-AIR,
and LINX-102/103/202/203
LIC‑ASSET Add-on Software License to activate asset tracking (for LDALI-ME20x-U, LDALI-3E10x-U, LDALI-PLCx,
LROC-400, LROC-401, LIOB-AIR20, LIOB-591)

Gateways
LENO‑800 EnOcean Interface 868 MHz Europe
LENO‑801 EnOcean Interface 902 MHz USA/Canada
LENO‑802 EnOcean Interface 928 MHz Japan
LWLAN‑800 Wireless LAN Interface IEEE 802.11bgn
LTE‑800 LTE Interface

L-VIS, L-STAT
LPAD-7,
LRS232-802 USB to 2 x RS-232 Interface
LMPBUS-804 MP-Bus interface for 16 devices per channel, up to 4 channels
LSMI-804 Standard Motor Interface for 64 motors, 4 SMI channels via USB
LIOB‑450 LIOB‑IP852 I/O Module: 8 UI, 2 DI, 2 AO, 8 DO (4 x Relay 6 A, 4 x Triac 0.5 A)
LIOB‑451 LIOB‑IP852 I/O Module: 8 UI, 12 DI

L‑DALI
LIOB‑452 LIOB‑IP852 I/O Module: 6 UI, 6 AO, 8 DO (8 x Relay 6 A)
LIOB‑453 LIOB‑IP852 I/O Module: 6 UI, 6 AO, 5 DO (4 x Relay 16 A, 1 x Relay 6 A)
LIOB‑454 LIOB‑IP852 I/O Module: 7 UI, 4 AO, 7 DO (5 x Relay 6 A, 2 x Triac 0.5 A), 1 Pressure Sensor
LIOB‑550 LIOB‑BIP I/O Module: 8 UI, 2 DI, 2 AO, 8 DO (4 x Relay 6 A, 4 x Triac 0.5 A)
LIOB‑551 LIOB‑BIP I/O Module: 8 UI, 12 DI
Routers, NIC

LIOB‑552 LIOB‑BIP I/O Module: 6 UI, 6 AO, 8 DO (8 x Relay 6 A)


LIOB‑553 LIOB‑BIP I/O Module: 6 UI, 6 AO, 5 DO (4 x Relay 16 A, 1 x Relay 6 A)
LIOB‑554 LIOB‑BIP I/O Module: 7 UI, 4 AO, 7 DO (5 x Relay 6 A, 2 x Triac 0.5 A), 1 Pressure Sensor
LIOB‑560 LIOB-BIP I/O Module: 20 Universal I/O (IO)
LIOB‑562 LIOB-BIP I/O Module: 40 Universal I/O, (12 optionally with 4-20 mA current output)
Interfaces

LSTAT‑800‑G3-Lx Room Operator Panel, black front, white enclosure, Modbus, temperature, rel. humidity, ext. switch/NTC,
IR receiver, Buttons (Lx)
LSTAT-801‑G3-Lx Room Operator Panel, front black, white enclosure, Modbus, temperature, rel. humidity, ext. switch/NTC,
occupancy, IR receiver, Buttons (Lx)
LSTAT‑802‑G3-Lx Room Operator Panel, front black, white enclosure, Modbus, temperature, rel. humidity, ext. switch/NTC,
occupancy, IR receiver, CO2, Buttons (Lx)
Accessories

LSTAT‑800‑G3-L20x Room Operator Panel, white front, white enclosure, Modbus, temperature, rel. humidity, ext. switch/NTC,
IR receiver, Buttons (Lx)
LSTAT-801‑G3-L20x Room Operator Panel, white front, white enclosure, Modbus, temperature, rel. humidity, ext. switch/NTC,
occupancy, IR receiver, Buttons (Lx)

buildings under control 83


Functions
L-IOB Room Controller

LIOB‑591
L‑WEB, L‑STUDIO

Order number Product description


LSTAT‑802‑G3-L20x Room Operator Panel, white front, white enclosure, Modbus, temperature, rel. humidity, ext. switch/NTC,
occupancy, IR receiver, CO2, Buttons (Lx)
LSTAT-80x-CUSTOM One-time customization cost for L-STAT custom design, including 2 working samples
LDALI‑MS2-BT DALI multi-sensor (presence detection, illuminance sensor, IR receiver, temperature sensor,
humidity sensor, 3 digital inputs, Bluetooth), up to 12 m mounting height
LDALI‑MS3-BT DALI multi-sensor (presence detection, illuminance sensor, IR receiver, temperature sensor,
humidity sensor, 3 digital inputs, Bluetooth), up to 12 m mounting height
L‑ROC

LDALI-MS4-BT DALI multi-sensor (presence detection, illuminance sensor, IR receiver, temperature sensor,
humidity sensor, 3 digital inputs, Bluetooth, flat lens), up to 5 m mounting height
LDALI‑BM2 Quadruple DALI pushbutton coupler
LDALI‑RM5 DALI Relay Module 10 A, Analog Interface 1 – 10 V
LDALI‑RM6 DALI Relay Module 10 A, Analog Interface 1 – 10 V, “spud-mount”
L‑INX

LDALI‑RM8 DALI Relay Module, 8-channel


LOY-DALI-SBM1 DALI Sunblind Module, DALI, 2 x 6A/250 V AC
LDALI-PWM4 PWM module, DALI, 4 x 3 A LED outputs, 24 V DC ext.
LDALI-PWM4-TC PWM module tunable white, DALI, 4 x 3 A LED outputs, 24 V DC ext.
LDALI-PWM4-RGBW PWM module RGBW, DALI, 4 x 3 A LED outputs, 24 V DC ext.
L‑IOB

LDALI‑PD1 DALI Phase-Cut Dimmer Module


L-TEMP2 External temperature sensor (NTC10K) for use with L‑IOB Universal Inputs
Gateways
L-VIS, L-STAT
LPAD-7,
L‑DALI
Routers, NIC
Interfaces
Accessories

84 www.loytec.com
Functions
Dimensions of the devices in mm and [inch]

[.630]
16
DIM065

L‑WEB, L‑STUDIO
LIOB‑591

46 [1.811]

L‑ROC
187 [7.362]

1250 W max. 300 W max. 300 W max. 300 W max.


PWR L N S2 S1 DO1 N DO2 N DO3 N DO4 N DA+ DA-
85-240VAC

L‑INX
50/60Hz 10 A DALI

87 [3.425]
LOYTEC
www.loytec.com

LIOB-591

L-IOB

L‑IOB
status

I/O Controller
6x4.5Ø
Made in Austria
UNIVERSAL INPUT / OUTPUT PWR OUT RS-485
Ethernet 2

IO10

IO11

IO12

IO13

IO14

IO15

IO16

IO17

IO18

IO19

IO20

24V
IO1

IO2

IO3

IO4

IO5

IO6

IO7

IO8

IO9
USB 2

5V
RESET USB 1 Ethernet 1 GND GND GND GND GND GND GND 24V GND

Gateways
11 [0.433] 177 [6.972] 11 [0.433]

199 [7.835] SCALE 1 : 2


10 0 20 40 60 80 100 mm

L‑VIS, L-STAT
LPAD-7,
L‑DALI
Routers, NIC
Interfaces
Accessories

The products of LOYTEC electronics GmbH are subject to constant development. Therefore, LOYTEC reserves the right to modify technical
specifications at any time without prior notice. The most recent datasheet can be downloaded from www.loytec.com.

buildings under control 5