Electrical Machines
EE-260
                      Instructor: Dr Alina Mirza
Department of Electrical Engineering, Military College of Signals
     National University of Sciences & Technology (NUST)
Determining Transformer Model’s Parameters
The parameter of the transformer model i.e., the
values of resistances and inductances can be
experimentally determined using two simple
tests: The open circuit test and the short circuit
test.
1.The Open Circuit Test: One of the winding is open circuited, and a full load rated
voltage is applied to the other side.
 This measurement is normally done on the low voltage side of transformer, since lower voltages
are easier to work with)
               (a). The Open Circuit Test
  Rp & Xp are too small as compared to Rc and Xm. Approximately all the voltage
  drops across the excitation impedance
 Convenient to consider admittance
 of the excitation branch and then
 compute Rc and Xm.
 Conductance of the core- loss resistor
                                            The total excitation admittance is:
Susceptance of the magnetizing inductor
                                                        1      1
                                                   YE     j
                                                        Rc    XM
   (a). The Open Circuit Test (cont…
Magnitude of YE referred to primary        The admittance is
side
                                                      I OC
                                                 YE        
                                                      VOC
The P.F. for real transformer is always                 I OC
lagging. Therefore: I lags V by θ
                                                 YE           cos 1 PF
                                                        VOC
                                                 Y E  A- jB
                                          Finally RC and XM can be obtained
                    (b) Short Circuit Test
•   In this test the low voltage terminals of the transformer are short circuited.
•   Apply a variable voltage source to high voltage side. Fairly low voltages are applied
    on this side and are adjusted such that current in short circuited winding is equal to
    rated current.
•   Caution: Make sure to keep the applied voltage at a safe level, otherwise you could
    burn the transformer’s winding.
•   (this measurement is normally done on the high voltage side of transformer, since
    currents will be lower on that side, and lower currents are easier to work with)
             (b) Short Circuit Test (cont…
    •     The input voltage, current, and power are measured.
    •     Negligible current flows through the excitation branch as the input voltage is
          very low.
    •     Ignoring the excitation current, voltage drop can be attributed to series
          elements in the circuit.
Magnitude and angle of the series impedances           The series impedance ZSE is :
referred to the primary side of the transformer is
                                                               VSC 0     VSC
                                                     Z SE                    
                 VSC                                          I SC    I SC
        Z SE 
                 I SC
PF  cos  
                    PSC
                               cos 1 sc
                                           P           Z SE  Req  jX eq
                   VSC I SC             I SCVSC
                                                       Z SE  ( RP  a 2 Rs )  j ( X P  a 2 X S )
                  Tests : Find Values of Components
              Determining the Values of Components in the Transformer Model
         Open Circuit Test                                          Short Circuit Test
                                                                                                            Secondary
                  Ampere                                                      Ampere
                   Meter
                                                                                                              Short
                           Wattmeter                                           Meter   Wattmeter
                                       IP(t)                                                       IP(t)     Circuit
                    A                          • •                              A                          • •
                   Volt
                                       VP(t)         Open                 V
                                                                                Volt
                                                                                                   VP(t)          A
       V(t)   V   Meter
                                                                   V(t)        Meter
                                                     Circuit
  Figure 2-19 Connection for            Transformer            Figure 2-20 Connection for           Transformer
  transformer open-circuit test                                transformer short-circuit test
Apply rated primary (input) Voltage                               Apply Low voltages at input
IO No-Load current flows primary
                                                                 Full load IP & IS current flows
Wattmeter reads …..?              Core losses
                                                                 Wattmeter reads I2R (Copper)
Example 2-2:
The equivalent circuit impedance of a 20 kVA, 8000/240 V. 60 HZ transformer
are to be determined. The open circuit test was performed on the secondary side
of the transformer, and short circuit test was performed on the primary side of
the transformer, and the following data were taken. Find the impedance of the
approximate equivalent circuit referred to primary side, and sketch the circuit.
        Open-circuit test (on              Short-circuit test (on primary)
            secondary)
              Voc= 240 V                               Vsc= 489 V
              Ioc=7.133 A                               Isc= 2.5 A
              Poc= 400 W                               Psc= 240 W
1. Transformer Voltage Regulation and
Efficiency
  Due to series impedance in the transformer,
  the output voltage of the transformer varies
  with the load even if input voltage remains
  constant.
  Full-load voltage regulation is a quantity that compares the output voltage of the
  transformer at no load with the output voltage at full load
          VS ,nl  VS , fl
   VR                        100%
              VS , fl
Since at no load:        VS  VP / a     • Low voltage regulation means smaller
                                           winding impedance.
                                         • For an ideal transformer, VR = 0 %
           How to determine Voltage Regulation?
                                                                                       11
             Voltage Regulation
• Voltage Regulation depends on both
  – Magnitude of series impedances
  – Phase angle of the current
• How to measure ?
  – Phasor diagram
                                     12
              Power Factor
• Cosine angle between fundamental current and voltage
                                       13
                2. The Transformer Phasor Diagram
                                                               IS -
                                      VReq       VjXeq
                                                                        L Lagging
                        VP            =ReqIS     =XeqIS         VS      o Power Factor
                         a                                              a Load
                                                                        d
Phase        relation
                             VP
between IS & VReq ?
                             a
                                      VRe q  VjXeq  VS
Phase        relation
between IS & VXeq ?                                                VS is assumed to be at
                                               VP/a                angle 0o      ( VS-). All
                                                                   other voltages & currents
                                                                   are compared to this
                                                                   reference
         VReq
                             VjXeq
                                                VS
                 IS                                                            VP/a > VS
                                                         Vp/a  Vsfl
                                               % VR                    100  Positive
                                                                               ?
                                                            Vsfl                            14
Fig 2-27(a) Vector Dig                              2. The Transformer Phasor Diagram
  Unity Power Factor
                                                              IS       (cont...
                                                               -
                               VReq                  VjXeq
                                                                     L
             VP               =ReqIS                 =XeqIS          o   Unity
                                                              VS         Power Factor
              a                                                      a
                                                                     d   Load
                   VP
                   a
                           VRe q  VjXeq  VS
                         VP/a
                                                                          VP/a > VS
                                                                         Vp/a  Vsfl
                                                               % VR                    100  ?
                                               VS
                   Fida Muhammad (Air University)                           Vsfl
                                                                                       Positive    15
Fig 2-27(a) Vector Dig
                         2. The Transformer Phasor Diagram
      Leading PF
                                             I 
                                                    (cont…
                                                      S
                                VReq         VjXeq         L
                    VP                                     o    Leading
                               =ReqIS        =XeqIS   VS
                                                           a    Power Factor
                     a                                          Load
                                                           d
                         VP
                         a
                               VRe q  VjXeq  VS
                              VP/a                             Vp/a  Vsfl
                                                      % VR                   100  ?
                                                                  Vsfl
                                                               VP/a <VS
           VReq
                                                                Negative
                                        VS                                         16
                       3. Transformer Efficiency
  The efficiency is given by:
                 Pout
                     100%
                 Pin
                   Pout
                             100%
              Pout  Plosses
   From the transformer equivalent circuit efficiency can be easily calculated
   The power losses comprise                At any given load efficiency can be
       – Copper losses                      calculated as:
       – Hystersis losses                        Pout  Vs I s Cos s
       – Eddy current losses
                                                           Vs I s Cos s
                                                                             100
The efficiency for a power transformer is            Pcu  Pcore  Vs I s Cos
between 0.9 to 0.99.                                                                  17
Example 2-5:
 A 15 kVA, 2300/230-V transformer is to be tested to determine its excitation
 branch components, its series impedance and its voltage regulation.
 The data have been taken by using the
 connections shown in the following
 Figures.
                                           Open-ckt test Short-ckt test
                                            Voc=2300 V         Vsc=47 V
                                             Ioc=0.21 A        Isc=6.0 A
                                             Poc= 50 W       Psc= 160 W
                                                                           1
Example 2-5:
 a. Find the equivalent circuit of this transformer referred to the
    high-voltage side.
 b. Find the equivalent circuit of this transformer referred to the low-
    voltage side.
 c. Calculate the full-load voltage regulation at 0.8 lagging power
    factor, 1.0 power factor, and at 0.8 leading power factor.
 d. Plot the voltage regulation as load is increased from no load to
    full load at power factors of 0.8 lagging, 1.0, and 0.8 leading.
 e. What is the efficiency of the transformer at full load with a power
    factor of 0.8 lagging?
Example 2-5: (Solution)
 a)
     From the OCT data
                          2
Example 2-5: (Solution)
 For equivalent circuit referred to primary side the Excitation branch elements
 are found as
                                                            a = 2300/230
                                                                     = 10
  The short-circuit impedance angle
                                                     The series elements referred
                                                     to the primary
 The equivalent series impedance
Example 2-5: (Solution)
              The transformer equivalent circuit referred
                           its primary side
Example 2-5: (Solution)
b)   To find the equivalent circuit referred to the low-voltage side, the impedance is
divided by a2.
               The transformer equivalent circuit referred its secondary side
Example 2-5: (Solution)
c)   VR ?                                 15 kVA, 2300/230-V transformer
Full-load current on the secondary side
                                             From the circuit
Example 2-5: (Solution)
c.
                             Tetha=cos^-1(PF)
 The Voltage regulation is
                                                7
Example 2-5: (Solution)
Phasor Diagram
                          8
Example 2-5: (Solution)
c.
At PF = 1.0, current Is = 65.2 L 0° A
                                        9
Example 2-5: (Solution)
c.
At PF = 1.0, current Is = 65.2 L 0° A
                                        9
Example 2-5: (Solution)
                          10
Example 2-5: (Solution)
                          10
Example 2-5: (Solution)
                          Plot of voltage regulation versus load
d.                                       (Matlab)
                                                                   11
Example 2-5: (Solution)
e.
To find the efficiency of the transformer. first calculate its losses.
The copper losses are:
 The core losses are
The output power at 0.8 leading PF